GAS PROCESS SWITCHPOINTS

S.NO. STEP DESCRIPTION

1 FINAL DEPRESSURE_1 DIFFERENTIAL PRESSURE SWITCHPOINT

TARGET FILLING VOLUME (TOTALIZED REGENERANT VOLUME FROM


2 FILL_2 PREVIOUS FILL STAGE)
GAS REGENERANT SUPERHEATER DIFFERENTIAL TEMPERATURE
3 HEAT_1 (IN - OUT)

4 HEAT_2 GAS REGENERATION DRIER OUTLET SOAK TEMPERATURE

5 COOL_2 GAS TARGET TEMPERATURE DURING DOWNFLOW COOLING

TOTALIZED DISPLACEMENT FLOW (TOTALIZED FLOW FROM PREVIOUS


6 REGENERANT DISPLACEMENT STAGE)
REGENERANT
7 MINIMUM REGENERANT DISPLACEMENT TIMER
DISPLACEMENT_3

8 MAXIMUM REGENERANT DISPLACEMENT TIMER

XV-125 TARGET VALUES

S.NO. STEP DESCRIPTION

INTERMEDIATE
1 TARGET OPENING
PRESSURE UP_2
INTERMEDIATE
2 RAMP TIME
PRESSURE UP_2
REGENERANT
3 TARGET OPENING
DISPLACEMENT_3
REGENERANT
4 RAMP TIME
DISPLACEMENT_3 & 4
FINAL PRESSURE
5 TARGET OPENING
UP2_01
FINAL PRESSURE
6 RAMP TIME
UP2_01
OINTS

UNIT SWITHPOINT MINIMUM MAXIMUM

bar 0.6 0.5 0.69

m3 1.15 0.95 4.5

C 10 1 15

C 280 250 300

C 150 120 200

m3 3 1.6 7.5

min 120 60 180

min 240 120 480

ES

UNIT SWITHPOINT MINIMUM MAXIMUM

% 10 0 25

min 20 15 30

% 20 0 100

min 20 15 30

% 30 0 100

min 17 15 30
FEED PROCESS SWITCHPOINTS

S.NO. STEP DESCRIPTION

FEED REGENERANT SUPERHEATER DIFFERENTIAL TEMPERATURE


1 HEAT_1 (IN - OUT)

2 HEAT_2 FEED REGENERATION DRIER OUTLET SOAK TEMPERATURE

3 COOL_2 FEED TARGET TEMPERATURE DURING DOWNFLOW COOLING

4 COOL_4 FEED TARGET TEMPERATURE DURING UPFLOW COOLING

TOTALIZED DISPLACEMENT FLOW (TOTALIZED FLOW FROM PREVIOUS


5 REGENERANT DISPLACEMENT STAGE)
REGENERANT
6 MINIMUM REGENERANT DISPLACEMENT TIMER
DISPLACEMENT_3

7 MAXIMUM REGENERANT DISPLACEMENT TIMER

8 *** REGENERANT FROM REGENERANT CONDENSER TEMPERATURE SP


OINTS

UNIT SWITHPOINT MINIMUM MAXIMUM

C 8 1 10

C 280 250 300

C 150 120 200

C 65 40 65

m3 20 8 60

min 60 60 180

min 240 120 480

C 76 50 90
ADJUSTABLE MAKEUP GAS DRIER TIMERS

S.NO. DESCRIPTION UNIT

1 DRIER REGENERATION (TOTAL) HOURS

2 DRIER REGENERATION SOAK min

3 INITIAL DEPRESSURE STAGE LONG STEP 3 ALARM min

4 FINAL DEPRESSURE STAGE LONG STEP 2 ALARM min

5 FILL STAGE LONG STEP 1 ALARM min

6 LIQUID REGENERANT REMOVAL STAGE LONG STEP 1 ALARM min

7 HEAT STAGE LONG STEP 2 ALARM min

8 COOL STAGE LONG STEP 1 ALARM min

9 COOL STAGE LONG STEP 2 ALARM min

10 REGENERANT END STAGE LONG STEP 1 ALARM min

11 REGENERANT DEPRESSURE TO FLARE STAGE LONG STEP 1 ALARM min

12 INTERMEDIATE PRESSURE UP STAGE LONG STEP 3 ALARM min

13 REGENERANT DEPRESSRE 2 STAGE LONG STEP 1 ALARM min

14 REGENERANT DISPLACEMENT STAGE LONG STEP 4 ALARM min

15 FINAL PRESSURE UP 2 STAGE LONG STEP 1 ALARM min

16 RECOVERY STEP 3R LONG STEP ALARM min

17 RECOVERY STEP 6R LONG STEP ALARM min

18 RECOVERY STEP 7R LONG STEP ALARM min

19 RECOVERY STEP 11R LONG STEP ALARM min


TIMERS

SET POINT MINIMUM MAXIMUM

4300 24 4300

240 1 240

35 15 60

35 15 60

35 15 60

120 15 250

420 60 600

160 15 200

300 60 600

35 15 60

35 15 60

35 15 60

35 15 60

60 30 90

60 30 120

35 15 60

35 15 60

120 15 250

300 60 600
ADJUSTABLE FEED DRIER TIMERS

S.NO. DESCRIPTION UNIT

1 DRIER REGENERATION (TOTAL) HOURS

2 DRIER REGENERATION SOAK min

3 REGENERATION LINE UP STAGE LONG STEP 2 ALARM min

4 LIQUID REGENERANT REMOVAL STAGE LONG STEP 1 ALARM min

5 HEAT STAGE LONG STEP 2 ALARM min

6 COOL STAGE LONG STEP 1 ALARM min

7 COOL STAGE LONG STEP 2 ALARM min

8 COOL STAGE LONG STEP 4 ALARM min

9 REGENERANT DISPLACEMENT STAGE LONG STEP 3 ALARM min

11 RECOVERY STEP 3 LONG STEP ALARM min

12 RECOVERY STEP 4 LONG STEP ALARM min

13 RECOVERY STEP 8 LONG STEP ALARM min


MERS

SET POINT MINIMUM MAXIMUM

170 24 170

240 1 480

35 15 60

120 15 250

360 60 600

120 15 200

300 60 600

300 60 600

60 30 90

35 15 60

120 15 250

300 60 600
MISCELLENEOUS FEED AND GAS TIMERS

S.NO. DESCRIPTION UNIT

1 VALVE VERIFICATION sec

2 REGENERANT SUPERHEATER START HOLD TIMER min

3 BKO LEVEL CYCLE COUNTER SWITCH POINT min

4 REGENERANT SUPERHEATER OUTLET TEMPERATURE RAMP TIMER min


TIMERS

SET POINT MINIMUM MAXIMUM

45 15 60

60 15 120

2 1 10

60 60 150
GAS DRIER A REGENERATION ST

STAGE STEP DESCRIPTION

OPEN PROCESS OUTLET BLEED, WAIT TO START NEXT


WAIT GA_WAIT_01 REGENERATION

GA_BYPASS_01 CLOSE PROCESS INLET BLEED


BYPASS
GA_BYPASS_02 OPEN PROCESS INLET VALVES TO BYPASS LEAD DRIER

GA_ISOLATION_01 ISOLATE DRIER TO BE REGENERATED

ISOLATION

OPEN PROCESS INLET AND CROSS OVER BLEEDS TO


GA_ISOLATION_02 COMPLETE ISOLATION

CLOSE REGENERANT DISPLACEMENT/ LOWER


GA_INITIAL DEPRESSURE_01 DEPRESSURING BLEED

OPEN REGENERANT DISPLACEMENT/ LOWER


GA_INITIAL DEPRESSURE_02 DEPRESSURING VALVES
OPEN REGENERANT DISPLACEMENT/ LOWER
GA_INITIAL DEPRESSURE_02 DEPRESSURING VALVES

INITIAL DEPRESSURE GA_INITIAL DEPRESSURE_03 INITIAL DEPRESSURING

GA_INITIAL DEPRESSURE_04 CLOSE EQUALIZATION VALVE

CLOSE REGENERANT DISPLACEMENT/ LOWER


GA_INITIAL DEPRESSURE_05 DEPRESSURING VALVES

OPEN REGENERANT DISPLACEMENT/ LOWER


GA_INITIAL DEPRESSURE_06 DEPRESSURING BLEED

GA_FINAL DEPRESSURE_01 OPEN UPPER DEPRESSURING VALVES

FINAL DEPRESSURE
GA_FINAL DEPRESSURE_02 FINAL DEPRESSURING

GA_FILL_01 ESTABLISH REGENERANT FLOW AND BACK PRESSURE

FILL
FILL

GA_FILL_02 FILL DRIER TO BE REGENERATED

GA_REGENERATION CLOSE UPPER DEPRESSURING VALVES


LINEUP_01

GA_REGENERATION OPEN VALVES TO ESTABLISH DOWNFLOW PATH FOR


LINEUP_02 REGENERANT

REGENERATION LINEUP

GA_REGENERATION ESTABLISH REGENERANT DOWNFLOW THROUGH DRIER


LINEUP_03 TO BE REGENERATED

LIQUID REGENERANT GA_LIQUID REGEN PLACE VAPORIZER IN SERVICE


REMOVAL REMOVAL_01

GA_HEAT_01 START REGENERANT SUPERHEATER


GA_HEAT_01 START REGENERANT SUPERHEATER

HEAT

GA_HEAT_02 REGENERATE

GA_COOL_01 COOL REGENERANT SUPERHEATER

COOL

GA_COOL_02 COOL DRIER DOWNFLOW WITH REGENERANT VAPOR

GA_REGENERATION END_01 STOP VAPORIZER AND REGENERANT FLOW

GA_REGENERATION END_02 ISOLATE DRIER FROM REGENERANT RETURN PATH

REGENERATION END
REGENERATION END

OPEN REGENERANT OUTLET BLEED TO COMPLETE


GA_REGENERATION END_03 ISOLATION

OPEN UPPER DEPRESSURING VALVES TO VENT


GA_DEPRESSURE FLARE_01 VAPORIZED REGENERANT TO FLARE
REGENERANT DEPRESSURE
TO FLARE (OPTIONAL)

GA_DEPRESSURE FLARE_02 CLOSE UPPER DEPRESSURING VALVES

GA_FINAL PRESSURE CLOSE PROCESS OUTLET BLEED


UP 1_01

FINAL PRESSURE UP 1
(OPTIONAL)

GA_FINAL PRESSURE OPEN PRESSURIZATION/ REGENERANT DISPLACEMENT


UP 1_02 VALVES AND PROCESS OUTLET UPSTREAM VALVE

GA_REGENERANT CLOSE REGENERANT DISPLACEMENT / LOWER


DEPRESSURE1_01 DEPRESSURING BLEED

REGENERANT DEPRESSURE
1 (OPTIONAL)

GA_REGENERANT OPEN REGENERANT DISPLACEMENT / LOWER


DEPRESSURE1_02 DEPRESSURING VALVES
REGENERANT DEPRESSURE
1 (OPTIONAL)

GA_REGENERANT OPEN REGENERANT DISPLACEMENT / LOWER


DEPRESSURE1_02 DEPRESSURING VALVES

GA_INTERMEDIATE CLOSE PROCESS OUTLET BLEED


PRESSURE UP_01

GA_INTERMEDIATE OPEN PRESSURIZATION/ REGENERANT DISPLACEMENT


PRESSURE UP_02 VALVES AND PROCESS OUTLET UPSTREAM VALVE

GA_INTERMEDIATE INTERMEDIATE PRESSURE UP


PRESSURE UP_03

INTERMEDIATE PRESSURE
UP (OPTIONAL)
GA_INTERMEDIATE CLOSE PRESSURIZATION/ REGENERANT DISPLACEMENT
PRESSURE UP_04 VALVES AND PROCESS OUTLET UPSTREAM VALVE

GA_INTERMEDIATE OPEN PROCESS OUTLET BLEED


PRESSURE UP_05

REGENERANT DEPRESSURE GA_REGENERANT EQUALIZE PRESSURE WITH DESTINATION FOR


2 (OPTIONAL) DEPRESSURE2_01 REGENERANT DISPLACEMENT

GA_REGENERANT CLOSE PROCESS OUTLET BLEED, OPEN COMMON


DISPLACEMENT_01 REGENERANT DISPLACEMENT VALVE

GA_REGENERANT CLOSE EQUAL VALVE, OPEN PRESSURE / DISPLACEMENT


DISPLACEMENT_02 AND PROCESS OUTLET UPSTREAM VALVES
GA_REGENERANT CLOSE EQUAL VALVE, OPEN PRESSURE / DISPLACEMENT
DISPLACEMENT_02 AND PROCESS OUTLET UPSTREAM VALVES

GA_REGENERANT START REGENERANT DISPLACEMENT


DISPLACEMENT_03
REGENERANT
DISPLACEMENT (OPTIONAL)

GA_REGENERANT STOP REGENERANT DISPLACEMENT


DISPLACEMENT_04

GA_REGENERANT CLOSE DISPLACEMENT / LOWER DEPRESSURING AND


DISPLACEMENT_05 COMMON REGENERANT DISPLACEMENT VALVES

GA_REGENERANT OPEN REGENERANT DISPACEMENT / LOWER


DISPLACEMENT_06 DEPRESSURING BLEED

GA_FINAL PRESSURE UP
FINAL PRESSURE UP 2 FINAL PRESSURE UP
2_01

OPEN CROSSOVER VALVES AND PROCESS OUTLET


GA_LAG LINE UP_01 DOWNSTREAM VALVE
LAG LINE UP

CLOSE PROCESS OUTLET VALVES TO ESTABLISH LEAD-LAG


GA_LAG LINE UP_02 FLOW PATH

GAS DRIER A REGENERATION REC

GA_RECOVERY_1R WAIT TO START "FILLING" RECOVERY MODE

GA_RECOVERY_2R CLOSE LOWER REGENERANT VALVES


GA_RECOVERY_2R CLOSE LOWER REGENERANT VALVES

RECOVERY STEPS IF
CURRENTLY IN FILL_02 STEP

ESTABLISH REGENERANT FLOW AND BACK PRESSURE,


GA_RECOVERY_3R RESUME FILLING

GA_FILL_02 RETURN TO FILL_02

WAIT TO START "HEATING OR COOLING" RECOVERY


GA_RECOVERY_4R MODE

CLOSE REGENERANT VALVES, OPEN REGENERANT


GA_RECOVERY_5R CIRCULATION VALVE

OPEN REGENERANT BLEED VALVES, ESTABLISH


GA_RECOVERY_6R REGENERANT FLOW AND BACK PRESSURE
OPEN REGENERANT BLEED VALVES, ESTABLISH
GA_RECOVERY_6R REGENERANT FLOW AND BACK PRESSURE

GA_RECOVERY_7R START REGENERANT SUPERHEATER

RECOVERY STEPS IF
CURRENTLY IN LIQUID
REMOVAL_01 STEP OR HEAT
OR COOL STAGES
GA_RECOVERY_8R CLOSE REGENERANT BLEED VALVES

GA_RECOVERY_9R OPEN REGENERANT VALVES

CLOSE REGENERANT CIRCULATION VALVE, RESUME


GA_RECOVERY_10R HEATING STAGE

GA_HEAT_01 RETURN TO HEAT_01

CLOSE REGENERANT CIRCULATION VALVE, RESUME


GA_RECOVERY_11R COOLING STAGE
CLOSE REGENERANT CIRCULATION VALVE, RESUME
GA_RECOVERY_11R COOLING STAGE

GA_REGENERATION END_01 RETURN TO REGEN END_01


GAS DRIER A REGENERATION STEPS CONDITIONS

DESCRIPTION CONDITIONS

FEED DRIER A OR B IS NOT IN STEPS BYPASS_01 THROUGH REGENERATION END_01 OR IN RECOV


1 - 8 WHILE ALL THE GAS DRIER VALVE POSITIONS ARE VERIFIED

LI-009:PV < 40 AND ITS BAD PV ALARM IS NOT ACTIVE

XV-121 IS CONFIRMED OPEN WHILE XV-149, XV-150, XV-151 AND XV-152 ARE CONFIRMED CLOSE
S OUTLET BLEED, WAIT TO START NEXT
REGENERATION
TI-015:PV < 65 C AND THE CONDITION IS SATISFIED FOR 15 MINUTES.

GAS DRIER SECTION AND REGENERATION SECTION BAD PV / MV ALARM ARE NOT ACTIVE

GAS REGENERATION TIMER HAS EXPIRED (4300 MINUTES) OR OPERATOR HAS PRESSED THE GAS
BUTTON

OSE PROCESS INLET BLEED XV-128 IS CONFIRMED CLOSED WHILE ALL THE GAS DRIER VALVE POSITIONS ARE VERIFIED

S INLET VALVES TO BYPASS LEAD DRIER XV-124, XV-126 AND XV-127 ARE CONFIRMED OPEN WHILE ALL THE GAS DRIER VALVE POSITIONS

XV-122 IS CONFIRMED TO THE DRIER B SIDE


E DRIER TO BE REGENERATED
XV-123, XV-065, XV-066, XV-102 AND XV-103 ARE CONFIRMED CLOSED WHILE ALL THE GAS DRIER
ARE VERIFIED

FOR INITIAL DEPRESSURE_01:


1) DEPRESSURE TO ALTERNATE DESTINATION OPTION IS ENABLED
2) XV-087 AND XV-104 ARE CONFIRMED OPEN WHILE ALL THE GAS DRIER VALVE POSITIONS ARE V

S INLET AND CROSS OVER BLEEDS TO


COMPLETE ISOLATION
FOR FINAL DEPRESSURE_01:
1) DEPRESSURE TO ALTERNATE DESTINATION OPTION IS NOT ENABLED
2) XV-087 AND XV-104 ARE CONFIRMED OPEN WHILE ALL THE GAS DRIER VALVE POSITIONS ARE V
3) FIC-005.MV <0.5%
4) REGENERATION SECTION BAD PV / MV ALARM IS NOT ACTIVE

ENERANT DISPLACEMENT/ LOWER XV-090 IS CONFIRMED CLOSED WHILE ALL THE GAS DRIER VALVE POSITIONS ARE VERIFIED
DEPRESSURING BLEED

XV-088 AND XV-089 ARE CONFIRMED OPEN AND THE CONDITION IS SATISFIED FOR 1 MINUTE

ENERANT DISPLACEMENT/ LOWER


DEPRESSURING VALVES
ENERANT DISPLACEMENT/ LOWER ALL GAS DRIER VALVE POSITIONS ARE VERIFIED WHILE GAS DRIER SECTION BAD PV / MV ALARM
DEPRESSURING VALVES

1) IN ORDER TO ADVANCE TO INITIAL DEPRESSURE_03: PDI-010.PV > 0.40 bar


2) IN ORDER TO ADVANCE TO INITIAL DEPRESSURE_05: PDI-010.PV < / = 0.40 bar

XV-133 IS CONFIRMED OPEN AND PDI-010.PV < 0.15 bar


INITIAL DEPRESSURING
ALL GAS DRIER VALVE POSITIONS ARE VERIFIED WHILE GAS DRIER SECTION BAD PV / MV ALARM

OSE EQUALIZATION VALVE XV-133 IS CONFIRMED CLOSED WHILE ALL THE GAS DRIER VALVE POSITIONS ARE VERIFIED

ENERANT DISPLACEMENT/ LOWER XV-088 AND XV-089 ARE CONFIRMED CLOSED WHILE ALL THE GAS DRIER VALVE POSITIONS ARE V
DEPRESSURING VALVES

XV-090 IS CONFIRMED OPEN AND FIC-005.MV < 0.5 %


ENERANT DISPLACEMENT/ LOWER
DEPRESSURING BLEED
ALL GAS DRIER VALVE POSITIONS ARE VERIFIED WHILE REGENERATION SECTION BAD PV / MV ALA
ACTIVE

UPPER DEPRESSURING VALVES PDI-006.PV > 0.60 bar (GAS FINAL DEPRESSURE_01 SWITCH POINT)

PDI-006.PV < 0.40 bar AND LI-004.PV < 20 %

PV-012 IS CONFIRMED CLOSED AND PIC-012.MV < 0.5 %

FINAL DEPRESSURING XV-097, XV-098, XV-108 AND XV-136 ARE CONFIRMED OPEN

ALL GAS DRIER VALVE POSITIONS ARE VERIFIED WHILE GAS DRIER SECTION AND REGENERATION
MV ALARM IS NOT ACTIVE

PI-005.PV < 2.50 bar AND THE CONDITION IS SATISFIED FOR 5 MINUTES.

FYI-005A.PV > 1.80 m3/hr AND FOR 1 MINUTE IT SHOULD BE GREATER THAN 3.15 m 3/hr

PYI-013A.PV > PYI-013A.SL: 1.4 bar

ENERANT FLOW AND BACK PRESSURE PI-005.PV </= PYI-013A.PV AND PI-005.PV </= PI-060.PV

XV-093 AND PV-012 ARE CONFIRMED CLOSED ALSO PIC-012.MV < 0.5%

ALL GAS DRIER VALVE POSITIONS ARE VERIFIED WHILE REGENERATION SECTION BAD PV / MV ALA
ACTIVE
TOTALIZED ACTUAL VOLUMETRIC FLOW > 0.92 m 3
DRIER TO BE REGENERATED
LI-004.PV > 50%

UPPER DEPRESSURING VALVES XV-097, XV-098, XV-101 ARE CONFIRMED CLOSED WHILE ALL THE GAS DRIER VALVE POSITIONS A

PV-012 IS CONFIRMED CLOSED ALSO PIC-012.MV < 0.5%

TO ESTABLISH DOWNFLOW PATH FOR XV-099 AND XV-100 ARE CONFIRMED OPEN
REGENERANT

ALL GAS DRIER VALVE POSITIONS ARE VERIFIED WHILE REGENERATION SECTION BAD PV / MV ALA
ACTIVE

FYI-005A.PV > 1.80 m3/hr AND FOR 1 MINUTE IT SHOULD BE GREATER THAN 3.60 m 3/hr

LI-007.PV > 60 % AND TI-017.PV < 55 C

PYI-013A.PV > PYI-013A.SL: 1.4 bar


NERANT DOWNFLOW THROUGH DRIER
TO BE REGENERATED
XV-108 AND PV-012 ARE CONFIRMED CLOSED ALSO PIC-012.MV < 0.5%

HL-026A1 (REGENERANT CONDENSOR 1 IS RUNNING) OR HL-026A2 (REGENERANT CONDENSOR

ALL GAS DRIER VALVE POSITIONS ARE VERIFIED WHILE REGENERATION SECTION BAD PV / MV ALA
ACTIVE

SEQUENCE IS NOT IN RECOVERY MODE AND ALL GAS DRIER VALVE POSITIONS ARE VERIFIED WHI
SECTION BAD PV / MV ALARM IS NOT ACTIVE

FYI-005A.PV > 1.80 m3/hr

LI-007.PV < 30.0 % AFTER WHICH 60 min REGENERANT SUPERHEATER HOLD TIMER ACTIVATES.
ACE VAPORIZER IN SERVICE
TI-017.PV - TYI-022A.PV < 10 C, TYI-022A.PV > 65 C AND TI-017.PV - TYI-022A.PV > 0 C.
THESE CONDITION SHOULD REMAIN SATISFIED FOR 5 MINUTES AFTER ACHIEVING THE VALUES.

PIC-012.SP = PIC-012.SPT: 3.50 bar AND PYI-012A.PV = PIC-012.SPT: 3.5 bar (+ / - 0.26 bar ERROR

TIC-022 IS IN MANUAL MODE AND TIC-022.MV < 0.5 %

SEQUENCE IS NOT IN RECOVERY MODE AND ALL GAS DRIER VALVE POSITIONS ARE VERIFIED WHI
SECTION BAD PV / MV ALARM IS NOT ACTIVE

REGENERANT SUPERHEATER
REGENERANT SUPERHEATER FYI-005A.PV > 1.80 m3/hr AND PYI-012A.PV = PIC-012.SPT: 3.5 bar (+ / - 0.26 bar ERROR IS ALLOW

SUPER HEATER IS OPERATING

SEQUENCE IS NOT IN RECOVERY MODE AND ALL GAS DRIER VALVE POSITIONS ARE VERIFIED WHI
SECTION AND REGENERATION SECTION BAD PV / MV ALARM IS NOT ACTIVE

TIC-022.SP = TIC-022.SPG: 310 C AND TYI-022A.PV = TIC-022.SPG: 310 C (+ / - 10 C IS ALLOWED


REGENERATE
FYI-005A.PV > 1.80 m3/hr AND PYI-012A.PV = PIC-012.SPT: 3.5 bar (+ / - 0.26 bar ERROR IS ALLOW
014.PV > TI-016.S14: 280 C

TI-016.PV > TI-016.S14: 280 C. AFTER ACHIEVING THIS VALUE GAS DRIER REGENERATION SOAK T
(60 min)

SEQUENCE IS NOT IN RECOVERY MODE AND ALL GAS DRIER VALVE POSITIONS ARE VERIFIED WHI
SECTION AND REGENERATION SECTION BAD PV / MV ALARM IS NOT ACTIVE

REGENERANT SUPERHEATER FYI-005A.PV > 1.80 m3/hr AND PYI-012A.PV = PIC-012.SPT: 3.5 bar (+ / - 0.26 bar ERROR IS ALLOW

TIC-022.SP < / = 150 C AND TYI-022A.PV < 160.0 C

SEQUENCE IS NOT IN RECOVERY MODE AND ALL GAS DRIER VALVE POSITIONS ARE VERIFIED WHI
SECTION AND REGENERATION SECTION BAD PV / MV ALARM IS NOT ACTIVE

SUPER HEATER IS NOT OPERATING AND XL-006A GIVES GAS DRIER A "NORMAL" STATUS

TI-016.PV < 150.0 C (GAS TARGET COOLING TEMPERATURE) AND PYI-012A.PV = PIC-012.SPT: 3.5
OWNFLOW WITH REGENERANT VAPOR ERROR IS ALLOWED)

TYI-022A.PV - TI-017.PV < 20 C FOR ATLEAST 5 MINUTES

FYI-005A.PV > 1.80 m3/hr FOR 15 MINUTES

FIC-005.MV < 0.5 % AND PIC-012.MV < 0.5 %

ORIZER AND REGENERANT FLOW XV-099 AND XV-100 ARE CONFIRMED CLOSED AND REMAINS CLOSED FOR 5 MINUTES

ALL GAS DRIER VALVE POSITIONS ARE VERIFIED WHILE REGENERATION SECTION BAD PV / MV ALA
ACTIVE

PIC-013.MV < 0.5 % AND ALL GAS DRIER VALVE POSITIONS ARE VERIFIED WHILE REGENERATION
MV ALARM IS NOT ACTIVE
R FROM REGENERANT RETURN PATH
XV-101 IS CONFIRMED OPEN WHILE XV-091, XV-092 AND XV-136 ARE CONFIRMED CLOSED
FOR DEPRESSURE FLARE_01:
1) REGENERANT DISPLACEMENT OPTION IS NOT ENABLED
2) REGENERANT DUMP TO FLARE OPTION IS ENABLED
3) XV-093 IS CONFIRMED OPEN AND ALL GAS DRIER VALVE POSITION ARE VERIFIED

FOR FINAL PRESSURE UP1_01:


ERANT OUTLET BLEED TO COMPLETE 1) REGENERANT DISPLACEMENT OPTION IS NOT ENABLED
ISOLATION 2) REGENERANT DUMP TO FLARE OPTION IS NOT ENABLED
3) XV-093 IS CONFIRMED OPEN AND ALL GAS DRIER VALVE POSITION ARE VERIFIED

FOR REGENERANT DEPRESSURE1_01:


1) REGENERANT DISPLACEMENT OPTION IS ENABLED
2) XV-093 IS CONFIRMED OPEN AND ALL GAS DRIER VALVE POSITION ARE VERIFIED

XV-097 AND XV-098 ARE CONFIRMED OPEN AND PDI-006.PV < 0.40 bar FOR 1 MINUTE
R DEPRESSURING VALVES TO VENT
RIZED REGENERANT TO FLARE
ALL GAS DRIER VALVE POSITIONS ARE VERIFIED WHILE GAS DRIER SECTION BAD PV / MV ALARM

UPPER DEPRESSURING VALVES XV-097 AND XV-098 ARE CONFIRMED CLOSED AND ALL GAS DRIER VALVE POSITIONS ARE VERIFIE

ALL GAS DRIER VALVE POSITIONS ARE VERIFIED WHILE GAS DRIER SECTION AND REGENERATION
MV ALARM IS NOT ACTIVE

SE PROCESS OUTLET BLEED XV-121 IS CONFIRMED CLOSED AND XL-006A GIVES GAS DRIER A "NORMAL" STATUS

XV-125.MV < 0.5 %

ZATION/ REGENERANT DISPLACEMENT THE SEQUENCE WILL ADVANCE DIRECTLY TO FINAL PRESSURE UP 2_01 STEP:
1) XV-118 AND XV-119 ARE CONFIRMED OPEN AND XV-125.MV < 0.5 %
PROCESS OUTLET UPSTREAM VALVE 2) ALL GAS DRIER VALVE POSITIONS ARE VERIFIED WHILE GAS DRIER SECTION BAD PV / MV ALAR

XV-090 IS CONFIRMED CLOSED AND XL-006A INDICATES GAS DRIER A "NORMAL"STATUS


ENERANT DISPLACEMENT / LOWER
DEPRESSURING BLEED
ALL GAS DRIER VALVE POSITIONS ARE VERIFIED WHILE GAS DRIER SECTION AND REGENERATION
MV ALARM IS NOT ACTIVE

FOR INTERMEDIATE PRESSUREUP_01:


1) PDI-010.PV < / = 0.40 bar AND XV-088 AND XV-089 ARE CONFIRMED OPEN FOR 1 MINUTE
2) ALL GAS DRIER VALVE POSITIONS ARE VERIFIED WHILE GAS DRIER SECTION BAD PV / MV ALAR
ENERANT DISPLACEMENT / LOWER
DEPRESSURING VALVES
ENERANT DISPLACEMENT / LOWER
DEPRESSURING VALVES
FOR REGENERANT DEPRESSURE2_01:
1) PDI-010.PV > 0.40 bar AND XV-088 AND XV-089 ARE CONFIRMED OPEN FOR 1 MINUTE
2) ALL GAS DRIER VALVE POSITIONS ARE VERIFIED WHILE GAS DRIER SECTION BAD PV / MV ALAR

XV-121 IS CONFIRMED OPEN AND XV-125.MV < 0.5 %


SE PROCESS OUTLET BLEED
ALL GAS DRIER VALVE POSITIONS ARE VERIFIED WHILE GAS DRIER SECTION BAD PV / MV ALARM

XV-118 AND XV-119 ARE CONFIRMED OPEN AND XV-125.MV < 0.5 %
ZATION/ REGENERANT DISPLACEMENT
PROCESS OUTLET UPSTREAM VALVE
ALL GAS DRIER VALVE POSITIONS ARE VERIFIED WHILE GAS DRIER SECTION BAD PV / MV ALARM

TERMEDIATE PRESSURE UP PDI-010.PV > 0.55 bar

XV-118 AND XV-119 ARE CONFIRMED CLOSED AND XV-125.MV < 0.5 %
IZATION/ REGENERANT DISPLACEMENT
PROCESS OUTLET UPSTREAM VALVE
ALL GAS DRIER VALVE POSITIONS ARE VERIFIED WHILE GAS DRIER SECTION BAD PV / MV ALARM

FOR INTERMEDIATE PRESSUREUP_01:


1) PDI-010.PV < / = 0.40 bar AND XV-121 IS CONFIRMED OPEN
2) ALL GAS DRIER VALVE POSITIONS ARE VERIFIED WHILE GAS DRIER SECTION BAD PV / MV ALAR

EN PROCESS OUTLET BLEED

FOR REGENERANT DEPRESSURE2_01:


1) PDI-010.PV > 0.40 bar AND XV-121 IS CONFIRMED OPEN
2) ALL GAS DRIER VALVE POSITIONS ARE VERIFIED WHILE GAS DRIER SECTION BAD PV / MV ALAR

PDI-010.PV < 0.15 bar AND XV-133 IS CONFIRMED OPEN


PRESSURE WITH DESTINATION FOR
GENERANT DISPLACEMENT
ALL GAS DRIER VALVE POSITIONS ARE VERIFIED WHILE GAS DRIER SECTION BAD PV / MV ALARM

XV-132 IS CONFIRMED OPEN WHILE XV-121 IS CONFIRMED CLOSED AND XV-125.MV < 0.5 %
ESS OUTLET BLEED, OPEN COMMON
ERANT DISPLACEMENT VALVE
ALL GAS DRIER VALVE POSITIONS ARE VERIFIED WHILE GAS DRIER SECTION BAD PV / MV ALARM

FI-004.PV < 75.0 Nm3/hr AND XV-125.MV < 0.5 %

ALVE, OPEN PRESSURE / DISPLACEMENT XV-118 AND XV-119 ARE CONFIRMED OPEN WHILE XV-133 IS CONFIRMED CLOSED
CESS OUTLET UPSTREAM VALVES
ALVE, OPEN PRESSURE / DISPLACEMENT
CESS OUTLET UPSTREAM VALVES

ALL GAS DRIER VALVE POSITIONS ARE VERIFIED WHILE GAS DRIER SECTION BAD PV / MV ALARM

TOTALIZED DISPLACEMENT FLOW > 3.0 m3 AND 120 MINUTES MINIMUM REGENERANT DISPLACE
EXPIRES.
REGENERANT DISPLACEMENT
ALL GAS DRIER VALVE POSITIONS ARE VERIFIED WHILE GAS DRIER SECTION BAD PV / MV ALARM

FI-004.PV < 75.0 Nm3/hr AND XV-125.MV < 0.5 %


REGENERANT DISPLACEMENT
ALL GAS DRIER VALVE POSITIONS ARE VERIFIED WHILE GAS DRIER SECTION BAD PV / MV ALARM

XV-088, XV-089 AND XV-132 ARE CONFIRMED CLOSED


EMENT / LOWER DEPRESSURING AND
EGENERANT DISPLACEMENT VALVES
ALL GAS DRIER VALVE POSITIONS ARE VERIFIED

XV-090 IS CONFIRMED OPEN AND XV-125.MV < 0.5 %


ENERANT DISPACEMENT / LOWER
DEPRESSURING BLEED
ALL GAS DRIER VALVE POSITIONS ARE VERIFIED WHILE GAS DRIER SECTION BAD PV / MV ALARM

XV-096 IS CONFIRMED CLOSED AND PI-007.PV - PI-005.PV < 1.00 bar


FINAL PRESSURE UP
ALL GAS DRIER VALVE POSITIONS ARE VERIFIED WHILE GAS DRIER SECTION BAD PV / MV ALARM

XV-094, XV-095 AND XV-120 ARE CONFIRMED OPEN AND XV-125.MV < 0.5 %
OVER VALVES AND PROCESS OUTLET
DOWNSTREAM VALVE
ALL GAS DRIER VALVE POSITIONS ARE VERIFIED WHILE GAS DRIER SECTION BAD PV / MV ALARM

OUTLET VALVES TO ESTABLISH LEAD-LAG XV-114, XV-115 AND XV-118 ARE CONFIRMED CLOSED AND ALL GAS DRIER VALVE POSITIONS ARE
FLOW PATH

GAS DRIER A REGENERATION RECOVERY CONDITIONS

CLICK ON HS-017A BUTTON TO START RECOVERY MODE


TART "FILLING" RECOVERY MODE
ALL GAS DRIER VALVE POSITIONS ARE VERIFIED WHILE GAS DRIER SECTION AND REGENERATION
MV ALARM IS NOT ACTIVE

PDI-006.PV < 0.40 bar AND LI-004.PV < 20 %

PV-012 IS CONFIRMED CLOSED AND PIC-012.MV < 0.5 %


LOWER REGENERANT VALVES
LOWER REGENERANT VALVES
XV-091 AND XV-092 ARE CONFIRMED CLOSED

ALL GAS DRIER VALVE POSITIONS ARE VERIFIED WHILE GAS DRIER SECTION AND REGENERATION
MV ALARM IS NOT ACTIVE

FYI-005A.PV > 1.80 m3/hr AND FOR 1 MINUTE IT SHOULD BE GREATER THAN 3.15 m 3/hr

PYI-013A.PV > PYI-013A.SL: 1.4 bar

ENERANT FLOW AND BACK PRESSURE, PI-005.PV </= PYI-013A.PV AND PI-005.PV </= PI-060.PV
RESUME FILLING

XV-093 AND PV-012 ARE CONFIRMED CLOSED ALSO PIC-012.MV < 0.5%

ALL GAS DRIER VALVE POSITIONS ARE VERIFIED WHILE REGENERATION SECTION BAD PV / MV ALA
ACTIVE

TOTALIZED ACTUAL VOLUMETRIC FLOW > 0.92 m 3


RETURN TO FILL_02
LI-004.PV > 50%

CLICK ON HS-017A BUTTON TO START RECOVERY MODE


T "HEATING OR COOLING" RECOVERY
MODE
ALL GAS DRIER VALVE POSITIONS ARE VERIFIED WHILE GAS DRIER SECTION AND REGENERATION
MV ALARM IS NOT ACTIVE

FIC-005.MV < 0.5 % AND PIC-013.MV < 0.5 %

PV-012 IS CONFIRMED CLOSED AND PIC-012.MV < 0.5 %


NERANT VALVES, OPEN REGENERANT
CIRCULATION VALVE
XV-108 IS CONFIRMED OPEN AND XV-091, XV-092, XV-099 AND XV-100 ARE CONFIRMED CLOSED

ALL GAS DRIER VALVE POSITIONS ARE VERIFIED WHILE REGENERATION SECTION BAD PV / MV ALA
ACTIVE

FYI-005A.PV > 1.80 m3/hr AND FOR 1 MINUTE IT SHOULD BE GREATER THAN 3.60 m 3/hr

LI-007.PV > 60 % AND TI-017.PV < 55 C

PYI-013A.PV > PYI-013A.SL: 1.4 bar


NERANT BLEED VALVES, ESTABLISH
ANT FLOW AND BACK PRESSURE
XV-101 AND XV-093 ARE CONFIRMED OPEN AND PV-012 IS CONFIRMED CLOSED ALSO PIC-012.M
NERANT BLEED VALVES, ESTABLISH
ANT FLOW AND BACK PRESSURE

HL-026A1 (REGENERANT CONDENSOR 1 IS RUNNING) OR HL-026A2 (REGENERANT CONDENSOR

ALL GAS DRIER VALVE POSITIONS ARE VERIFIED WHILE REGENERATION SECTION BAD PV / MV ALA
ACTIVE

SEQUENCE IS NOT IN RECOVERY MODE AND ALL GAS DRIER VALVE POSITIONS ARE VERIFIED WHI
SECTION BAD PV / MV ALARM IS NOT ACTIVE

FYI-005A.PV > 1.80 m3/hr

LI-007.PV < 30.0 % AFTER WHICH 60 min REGENERANT SUPERHEATER HOLD TIMER ACTIVATES.
REGENERANT SUPERHEATER
TI-017.PV - TYI-022A.PV < 10 C, TYI-022A.PV > 65 C AND TI-017.PV - TYI-022A.PV > 0 C
THESE CONDITION SHOULD REMAIN SATISFIED FOR 5 MINUTES AFTER ACHIEVING THE VALUES.

PIC-012.SP = PIC-012.SPT: 3.50 bar AND PYI-012A.PV = PIC-012.SPT: 3.5 bar (+ / - 0.26 bar ERROR

TIC-022 IS IN MANUAL MODE AND TIC-022.MV < 0.5 %

REGENERANT BLEED VALVES XV-101 AND XV-093 ARE CONFIRMED CLOSED AND ALL GAS DRIER VALVE POSITIONS ARE VERIFIE

FOR RECOVERY_10R:
1) REGENERATION SOAK TIMER IS NOT EXPIRED AND TI-016.PV > TI-016.S14: 280 C
2) XV-099, XV-100, XV-091 AND XV-092 ARE CONFIRMED OPEN
3) ALL GAS DRIER VALVE POSITION VERIFIED
PEN REGENERANT VALVES
FOR RECOVERY_11R:
1) 200 MIN REGENERATION SOAK TIMER EXPIRED AND TI-016.PV > TI-016.S14: 280 C
2) XV-099, XV-100, XV-091 AND XV-092 ARE CONFIRMED OPEN
3) ALL GAS DRIER VALVE POSITION VERIFIED

ERANT CIRCULATION VALVE, RESUME


HEATING STAGE XV-108 IS CONFIRMED CLOSED AND ALL GAS DRIER VALVE POSITIONS ARE VERIFIED

SEQUENCE IS NOT IN RECOVERY MODE AND ALL GAS DRIER VALVE POSITIONS ARE VERIFIED WHI
SECTION BAD PV / MV ALARM IS NOT ACTIVE

RETURN TO HEAT_01 FYI-005A.PV > 1.80 m3/hr AND PYI-012A.PV = PIC-012.SPT: 3.5 bar (+ / - 0.26 bar ERROR IS ALLOW

SUPER HEATER IS OPERATING

SEQUENCE IS NOT IN RECOVERY MODE AND ALL GAS DRIER VALVE POSITIONS ARE VERIFIED WHI
SECTION AND REGENERATION SECTION BAD PV / MV ALARM IS NOT ACTIVE

SUPER HEATER IS NOT OPERATING AND XL-006A GIVES GAS DRIER A "NORMAL" STATUS

ERANT CIRCULATION VALVE, RESUME


COOLING STAGE
ERANT CIRCULATION VALVE, RESUME TI-016.PV < 150.0 C (GAS TARGET COOLING TEMPERATURE) AND PYI-012A.PV = PIC-012.SPT: 3.5
COOLING STAGE ERROR IS ALLOWED)

XV-108 IS CONFIRMED CLOSED AND TYI-022A.PV - TI-017.PV < 20 C FOR ATLEAST 5 MINUTES

FYI-005A.PV > 1.80 m3/hr FOR 15 MINUTES

FIC-005.MV < 0.5 % AND PIC-012.MV < 0.5 %

ETURN TO REGEN END_01 XV-099 AND XV-100 ARE CONFIRMED CLOSED AND REMAINS CLOSED FOR 5 MINUTES

ALL GAS DRIER VALVE POSITIONS ARE VERIFIED WHILE REGENERATION SECTION BAD PV / MV ALA
ACTIVE
CONDITIONS

1 THROUGH REGENERATION END_01 OR IN RECOVERY MODE STEPS


ONS ARE VERIFIED

ACTIVE

V-150, XV-151 AND XV-152 ARE CONFIRMED CLOSED

SFIED FOR 15 MINUTES.

TION BAD PV / MV ALARM ARE NOT ACTIVE

0 MINUTES) OR OPERATOR HAS PRESSED THE GAS DRIER START

GAS DRIER VALVE POSITIONS ARE VERIFIED

OPEN WHILE ALL THE GAS DRIER VALVE POSITIONS ARE VERIFIED

RE CONFIRMED CLOSED WHILE ALL THE GAS DRIER VALVE POSITIONS

OPTION IS ENABLED
WHILE ALL THE GAS DRIER VALVE POSITIONS ARE VERIFIED

OPTION IS NOT ENABLED


WHILE ALL THE GAS DRIER VALVE POSITIONS ARE VERIFIED

RM IS NOT ACTIVE

GAS DRIER VALVE POSITIONS ARE VERIFIED

ND THE CONDITION IS SATISFIED FOR 1 MINUTE


D WHILE GAS DRIER SECTION BAD PV / MV ALARM IS NOT ACTIVE

URE_03: PDI-010.PV > 0.40 bar


URE_05: PDI-010.PV < / = 0.40 bar

< 0.15 bar

D WHILE GAS DRIER SECTION BAD PV / MV ALARM IS NOT ACTIVE

GAS DRIER VALVE POSITIONS ARE VERIFIED

WHILE ALL THE GAS DRIER VALVE POSITIONS ARE VERIFIED

< 0.5 %

D WHILE REGENERATION SECTION BAD PV / MV ALARM IS NOT

E_01 SWITCH POINT)

MV < 0.5 %

FIRMED OPEN

D WHILE GAS DRIER SECTION AND REGENERATION SECTION BAD PV /

ATISFIED FOR 5 MINUTES.

IT SHOULD BE GREATER THAN 3.15 m 3/hr

PI-060.PV

ALSO PIC-012.MV < 0.5%

D WHILE REGENERATION SECTION BAD PV / MV ALARM IS NOT


m3

ED WHILE ALL THE GAS DRIER VALVE POSITIONS ARE VERIFIED

MV < 0.5%

D WHILE REGENERATION SECTION BAD PV / MV ALARM IS NOT

IT SHOULD BE GREATER THAN 3.60 m 3/hr

ALSO PIC-012.MV < 0.5%

NNING) OR HL-026A2 (REGENERANT CONDENSOR 2 IS RUNNING)

D WHILE REGENERATION SECTION BAD PV / MV ALARM IS NOT

LL GAS DRIER VALVE POSITIONS ARE VERIFIED WHILE REGENERATION

NERANT SUPERHEATER HOLD TIMER ACTIVATES.

65 C AND TI-017.PV - TYI-022A.PV > 0 C.


D FOR 5 MINUTES AFTER ACHIEVING THE VALUES.

2A.PV = PIC-012.SPT: 3.5 bar (+ / - 0.26 bar ERROR IS ALLOWED)

V < 0.5 %

LL GAS DRIER VALVE POSITIONS ARE VERIFIED WHILE REGENERATION


PIC-012.SPT: 3.5 bar (+ / - 0.26 bar ERROR IS ALLOWED)

LL GAS DRIER VALVE POSITIONS ARE VERIFIED WHILE GAS DRIER


V / MV ALARM IS NOT ACTIVE

A.PV = TIC-022.SPG: 310 C (+ / - 10 C IS ALLOWED)

PIC-012.SPT: 3.5 bar (+ / - 0.26 bar ERROR IS ALLOWED) WHILE TI-

NG THIS VALUE GAS DRIER REGENERATION SOAK TIMER ACTIVATES

LL GAS DRIER VALVE POSITIONS ARE VERIFIED WHILE GAS DRIER


V / MV ALARM IS NOT ACTIVE

PIC-012.SPT: 3.5 bar (+ / - 0.26 bar ERROR IS ALLOWED)

0.0 C

LL GAS DRIER VALVE POSITIONS ARE VERIFIED WHILE GAS DRIER


V / MV ALARM IS NOT ACTIVE

6A GIVES GAS DRIER A "NORMAL" STATUS

EMPERATURE) AND PYI-012A.PV = PIC-012.SPT: 3.5 bar (+ / - 0.26 bar

5 MINUTES

AND REMAINS CLOSED FOR 5 MINUTES

D WHILE REGENERATION SECTION BAD PV / MV ALARM IS NOT

E POSITIONS ARE VERIFIED WHILE REGENERATION SECTION BAD PV /

V-092 AND XV-136 ARE CONFIRMED CLOSED


OT ENABLED
NABLED
DRIER VALVE POSITION ARE VERIFIED

OT ENABLED
OT ENABLED
DRIER VALVE POSITION ARE VERIFIED

ABLED
DRIER VALVE POSITION ARE VERIFIED

ND PDI-006.PV < 0.40 bar FOR 1 MINUTE

D WHILE GAS DRIER SECTION BAD PV / MV ALARM IS NOT ACTIVE

AND ALL GAS DRIER VALVE POSITIONS ARE VERIFIED

D WHILE GAS DRIER SECTION AND REGENERATION SECTION BAD PV /

GIVES GAS DRIER A "NORMAL" STATUS

NAL PRESSURE UP 2_01 STEP:


AND XV-125.MV < 0.5 %
IED WHILE GAS DRIER SECTION BAD PV / MV ALARM IS NOT ACTIVE

NDICATES GAS DRIER A "NORMAL"STATUS

D WHILE GAS DRIER SECTION AND REGENERATION SECTION BAD PV /

XV-089 ARE CONFIRMED OPEN FOR 1 MINUTE


IED WHILE GAS DRIER SECTION BAD PV / MV ALARM IS NOT ACTIVE
089 ARE CONFIRMED OPEN FOR 1 MINUTE
IED WHILE GAS DRIER SECTION BAD PV / MV ALARM IS NOT ACTIVE

< 0.5 %

D WHILE GAS DRIER SECTION BAD PV / MV ALARM IS NOT ACTIVE

ND XV-125.MV < 0.5 %

D WHILE GAS DRIER SECTION BAD PV / MV ALARM IS NOT ACTIVE

AND XV-125.MV < 0.5 %

D WHILE GAS DRIER SECTION BAD PV / MV ALARM IS NOT ACTIVE

NFIRMED OPEN
IED WHILE GAS DRIER SECTION BAD PV / MV ALARM IS NOT ACTIVE

RMED OPEN
IED WHILE GAS DRIER SECTION BAD PV / MV ALARM IS NOT ACTIVE

MED OPEN

D WHILE GAS DRIER SECTION BAD PV / MV ALARM IS NOT ACTIVE

CONFIRMED CLOSED AND XV-125.MV < 0.5 %

D WHILE GAS DRIER SECTION BAD PV / MV ALARM IS NOT ACTIVE

5%

HILE XV-133 IS CONFIRMED CLOSED


D WHILE GAS DRIER SECTION BAD PV / MV ALARM IS NOT ACTIVE

D 120 MINUTES MINIMUM REGENERANT DISPLACEMENT TIMER

D WHILE GAS DRIER SECTION BAD PV / MV ALARM IS NOT ACTIVE

5%

D WHILE GAS DRIER SECTION BAD PV / MV ALARM IS NOT ACTIVE

CLOSED

< 0.5 %

D WHILE GAS DRIER SECTION BAD PV / MV ALARM IS NOT ACTIVE

- PI-005.PV < 1.00 bar

D WHILE GAS DRIER SECTION BAD PV / MV ALARM IS NOT ACTIVE

OPEN AND XV-125.MV < 0.5 %

D WHILE GAS DRIER SECTION BAD PV / MV ALARM IS NOT ACTIVE

CLOSED AND ALL GAS DRIER VALVE POSITIONS ARE VERIFIED

RY MODE

D WHILE GAS DRIER SECTION AND REGENERATION SECTION BAD PV /

MV < 0.5 %
D WHILE GAS DRIER SECTION AND REGENERATION SECTION BAD PV /

IT SHOULD BE GREATER THAN 3.15 m 3/hr

PI-060.PV

ALSO PIC-012.MV < 0.5%

D WHILE REGENERATION SECTION BAD PV / MV ALARM IS NOT

m3

RY MODE

D WHILE GAS DRIER SECTION AND REGENERATION SECTION BAD PV /

MV < 0.5 %

092, XV-099 AND XV-100 ARE CONFIRMED CLOSED

D WHILE REGENERATION SECTION BAD PV / MV ALARM IS NOT

IT SHOULD BE GREATER THAN 3.60 m 3/hr

ND PV-012 IS CONFIRMED CLOSED ALSO PIC-012.MV < 0.5%


NNING) OR HL-026A2 (REGENERANT CONDENSOR 2 IS RUNNING)

D WHILE REGENERATION SECTION BAD PV / MV ALARM IS NOT

LL GAS DRIER VALVE POSITIONS ARE VERIFIED WHILE REGENERATION

NERANT SUPERHEATER HOLD TIMER ACTIVATES.

65 C AND TI-017.PV - TYI-022A.PV > 0 C


D FOR 5 MINUTES AFTER ACHIEVING THE VALUES.

2A.PV = PIC-012.SPT: 3.5 bar (+ / - 0.26 bar ERROR IS ALLOWED)

V < 0.5 %

AND ALL GAS DRIER VALVE POSITIONS ARE VERIFIED

D AND TI-016.PV > TI-016.S14: 280 C


ONFIRMED OPEN

RED AND TI-016.PV > TI-016.S14: 280 C


ONFIRMED OPEN

DRIER VALVE POSITIONS ARE VERIFIED

LL GAS DRIER VALVE POSITIONS ARE VERIFIED WHILE REGENERATION

PIC-012.SPT: 3.5 bar (+ / - 0.26 bar ERROR IS ALLOWED)

LL GAS DRIER VALVE POSITIONS ARE VERIFIED WHILE GAS DRIER


V / MV ALARM IS NOT ACTIVE

6A GIVES GAS DRIER A "NORMAL" STATUS


EMPERATURE) AND PYI-012A.PV = PIC-012.SPT: 3.5 bar (+ / - 0.26 bar

PV - TI-017.PV < 20 C FOR ATLEAST 5 MINUTES

AND REMAINS CLOSED FOR 5 MINUTES

D WHILE REGENERATION SECTION BAD PV / MV ALARM IS NOT