MEP

(MECHANICAL, ELECTRICAL & PLUMBING HOTEL PROJECT


GUIDANCE FOR 100 ROOMS (16sqm to 24sqm rooms) 28-08-2013

Reference should also be made to the following separate documents;
Swimming pool design doc;
Room design template;
Room design checklist;
The kitchen, bar and laundry designs when ready;
The BOH space requirements for the project;

1) ELECTRICAL POWER
PLN supply 300 KVA , Transformer 300 KVA primary,
Secondary 220v/380v 50 Hz 3 phase,Traffo oil type step-down

2) GEN SET 1 unit
Engine - Package system, silenced type 300 KVA 1500 rpm
Continuous rated KVA 10% above rated utility power supply for total units
Alternator - Class H rotor & stator insulation, Semi automatic with motor
driven circuit breaker can be manual changeover maximum 1 minute
Fuel - Diesel or LNG if available
Controllers - Semi automatic with motor driven circuit breaker
Engine Room must be Sound proff or use Genset Silent
Noise levels - Maximum emitted noise level 65 dB 1m from gen set
Fuel storage - In ground tank 5m3 and day tank capacity 1.000 litres
minimum

3) AIR CONDITIONING
Split A/c type - Inverter type split A/C 1 PK per room wall mounted not facing
the bed
All public toilets to have A/C
LG Hercules brand recommended

4) ELEVATORS Minimum 2 guest
Gearless drive machine room less traction drive located in elevator shaft
Shaft head 4.20 m last floor to ceiling
Rope suspension 1:1 ACVVF regulated control type with
Frequency inverter passenger lift 8 persons 450 kg speed 1m per second
Stops in line 1 per floor, fully automatic 2-panel centre opening sliding doors
and material door anodized aluminum still

1

Door width 800 mm, height 2100 mm.

1 Fire lift man for Evacuation.

Maksimum Enginee lift room 20 C

Every lift must have Intercome conect to Enginee room lift

If possible lift have ARD (Auto Rescue Device)

Fireman lift should use the fire resistance cable


5) CENTRAL HOT WATER
Heat pumps - dual air to water sized to provide heat recovery at 75 liters per
hour per room at ambient temperature 25 C
Storage tanks - Hot water storage capacity @ 50 liters/room, pressurized
insulated tanks SS to SUS 304 minimum 2 tank @ 2500 liters, with
temperatur 55C
Piping & Pumps - PP-R high temperature maximum 70 C , circulation dual
pumps 1 operational 1 standby plus pressure tank if required

6) WATER SUPPLY
Cold water storage minimum raw water storage 250 M3
Pumps - Dual transfer pumps VSD constant pressure
Filtration - Depending on water supply quality, sand and carbon filter
recommended and position filter after Ground Water Tank.
After filter - A water treatment for corrosion, scale, algae and bio-fouling
should be installed after the filter process on the main distribution piping.
Volume Ground water tank enough for 45 minute handle fire pump +
Minimum all romm capacity
Minimum 2 boosters pump installed, but its advisable to install 3.
Hydropath Hydro flow recommended
Kitchen water - kitchen water supply must be separately filtered minimum 15
micron single cartridge for ice makers plus UV sterilizer
Roof tank with booster pump

7) SWIMMING POOLS refer to Swimming Pool Design Doc.
Swimming pools to be maximum 1.5 meters deep
60 cm deep for kids pools with a 4 meter separated from the adult pool
Avoid damage by flooding of the pool pump room.
Heyward recommended sterilization by way of manual or automatic dozing
system.
Heating of swimming pool in certain locations using heat pump with titanium
heat exchanger sized to suit the volume of pool water and ambient
temperature variations

8) FIRE HYDRANT
Main Electrical Centrifugal Pump with Capacity 500 Gpm,100 KW
Diesel Enginee Fire centrifugal pump capacity 500 Gpm, split case
Pumps - Jockey pump vertical multi stage 30 gpm 4.5 kw connected to
Pressure tank plate capacity 250 liter,pressure 20 bar.

2

Hydrant box pressure with capacity 250 liter/minute with pressure 20 bar
Steel flush mount 2 units per floor complete with alarm bell, indicator lamp,
manual push button & intercom jack
Hose reel - Hose reel machine coupling valve with brass hose nozzle
Siamese connection - Siamese connection ground level front of building and
Minimum separated minimum 5 meter.
Sprinklers - Side wall or ceiling mount for rooms pendant for back of house
and public areas and distance each Sprinkler diameter 3 meter
Each end of Sprinklers pipe at each floor need one valve

9) FIRE EXTINGUISHERS
2 units in each corridor wall mounted Dry chemical 2.5kg
other rooms 5 kg.
Gen set room, Electrical Cubical, Traffo and Panel LVMDP need CO2 type 25
KG type Trolley.

10) FIRE ALARM SYSTEM
Ceiling mounted or wall mounted at the room use smoke detectors conform
to Indonesian National Fire Alarm Code 72/1993 or new revised editions
Smoke Detectors in corridors and rooms
Fixed heat detectors kitchen and parking area
Rate of rise heat detectors restaurants and other facilities
Indictor light emergency out side ceiling enterance every rooms

11) WASTE WATER
Sewerage treatment plant, Aerobic Bio Filtration 250 liter per room per day
or as may be required by local regulations.
Suggestion if we have big land better we use system Extended Aeration

12) PUBLIC ADDRESS
Public address system should use speakers in all rooms, public areas and back
of house with extended paging addition unless using TRANSTEL PABX then no
need for in room speaker.
Automatic Monitor, display & Control from security room and front office
Speaker at corridor and emergency staircase should use the fire resistance
cable.


13) TELEPHONE SYSTEM
TRANSTEL BRAND Capacity 160 ports
Trunk lines incoming minimum 8
Digital extensions minimum 2
Single line analogue extensions 1 per room and minimum 20 for back of
house
Advanced messaging system for VOIP communication
Battery backup minimum 30 minutes
Digital telephone handset with headset hands free
3

Plug and 22 digit display
Built in message on hold
VHP interface call accounting
Integreted with Telphon speaker at rooms


14) CCTV
Recording system stand alone DVR H 264
Package system - Video compression 16 channel analogue 2 units
Hard disc 1 TERA
LCD monitor 19 inch
Camera 10 to 20 meter distance wide angle May be IP cameras

15) MATV
Receivers, decoders, modulators, splitters, cabling
UPS and 19 inch rack
61 channel local and international
TV in Rooms LCD or LED 32 inch

16) LIGHTNING PROTECTION
Radius of lightning protection 100 m EF terminal 4 m

17) HOTEL LOGO ROOF SIGNAGE
LED in Acrylic white 10 pieces

18) KITCHEN LPG (GAS)
Fire suppression system in kitchens in the exhaust hood system. ANSUL
recommended
Compleated with Fire Blanked,Head detector and signed Evacuation rod
Gas bottle storage to maintain high temperature to ensure maximum use of
gas in storage.
Solenoid safety valve gas Integrated with Fresh air fan and Exhaust fan
at the Kitchen.
Tanks by installing A/C outdoor units in bottle area or other form of heating.
Gas room must have Fresh air and Exhaust fan.
Put the Gas Ditector conectoc to Security and Engineering work area.

19) ROOMS EXHAUST SYSTEM and FRESH AIR FAN
Ducting from each bathroom to roof exhaust fan 3.000 cfm
Every room must have fresh air fan

20) GUEST ROOM DOOR LOCKS
Encoder/portable encoder for emergency door opening
Magnetic stripe card or RFID type, low battery indicator central card
ONITY or SAFLOK recommended
Guest room entrance doors to have automatic door closer and door stopper
and Alarm control if door not to clossed properly.
4


21) KEY SWITCHES
Energy saving key tag switches

22) UNIVERSAL SOCKET
Universal socket Minimum 2 unit per room,1 at Writing table
And one at bedside room.

23) Garbage
Dry Garbage
Wet Garbage complited with Air Condition.