You are on page 1of 62

Taj Gateway Hotel at Chennai As per BOQ

SL.No Item Description Unit


Qty PRICE Amount

1 SUB STATION EQUIPMENTS

1.1 11 kV Ring Main Unit(TNEB)

Instalation,testing,commissioning of 11 kV 500 mVA,630 Amps


Ring Main Unit of TNEB-
approved type and make, comprising 2 Nos Ring Feeder Load
Break Switches and 1 No
Transformer VCB Feeder, complete with all necessary protective
devices as per TNEB Norms. The
RMU shall be installed outdoors or indoors,complying TNEB
Regulations with Metering Cubicle as
descibed above, conforming to TNEB Norms with Power pack for
DC Source

INSTALLATION Set 1 0.00 0.00

1.2 11 kV Three Panel HT V CB (CLIENT)


Instalation,testing,commissioning of 11 kV HT breaker panel
consisting 1 No incomer and 2 Nos
outgoing, 630 amps 11 kV,500 MVA(26.2 kA) for.1 sec, VCB
Panel as detailed below for indoor type
11 kV THREE PANEL VCB panel With 630 Amp,500 MVA,
EDO type VCB with closing coil
spring charged closing mechanism, operation counter auxiliary
contacts for interlocks, and complete
with following:- Antipumping relay, panel illumination lamp,Space
heater and Breaker control switch,
(TRIP-NEUTRAL -CLOSE), Emergency trip button.
Busbar: 11kV , 800A, 26.2 kA, 3 Phase,Electrolytic copper with
color coded PVC heat shrunk
sleeves.with Power Pack for DC Source
INDICATING LAMPS:
Breaker ON/OFF, AUTO TRIP, SPRING CHARGED.
TRIP CIRCUIT HEALTHY, UNHEALTHY.
CTs PT :
Incomer CT : 150/75/1-1A Class 5P10- Protection & CL 1.0
Metering-Cast resin CTs, 11 kV as per SLD
Outgoing CT : 50/50/1-1A Class 5P10- Protection & CL 1.0
Metering-Cast resin CTs, 11 kV as per SLD
PT : 11kV / Sq Rt 3 : 110 V / Sq Rt 3 ,100VA,CL 1.0

( Note: Both CT & PT Shall be mounted in such a way that they


can be easily detached for
testing and calibration by TNEB in their test lab.)
RELAYS:
Incomer: 3 Ploe IDMT relay, 2 OC (50-200%) with high set
element +1 EF( 20- 80%)
or equivalent Microprocessor based Relay
Trip circuit supervision relay,24 V DC
Antipumping Relay
Master Trip relay, 24 V DC
( Inter trip from Restricted EFR and Stand By EFR shall be
provided apart from other Fault trips like
O/C, S/C,E/F, WT high , Door interlock with respective
Transformer Door.)
Auxiliary relays for WT High -Trip & Alarm
Potential free contacts for Breaker ON/OFF status.

Taj Gateway Hotel at Chennai Page- 1 of 62


Taj Gateway Hotel at Chennai
SL.No Item Description Unit
Qty PRICE Amount

METERING:
Incomer:
Digital Ammeter , Voltmeter, PF meter, Frequency meter
Digital Trivector meter with MDI ( of TNEB -approved make )

Annunciation windows with ACCEPT / RESET / TEST


pushbuttons
1 No Bell for 1 Non trip alarm ( 230 V AC).
1 No hooter for Trip faults( 24 V DC ).
The panel shall be suitable for outdoor Construction and shall be
finished in Battleship Grey colour.
The Panel Incomer and Outgoing Cable Connections shall be site
conditions
Accordingly Entry Provisions (Adaptor Box) to be considered

INSTALLATION Set 1 0.00 0.00

11 kV SINGLE Panel HT VCB (MASTER BREAKER


1.3
CLIENT)
Instalation,testing,commissioning of 11 kV HT breaker panel
consisting 1 No 630 amps 11 kV,500 MVA 18.4 kA
for 1 sec, VCB type circuit breaker .outdoor type Panel as detailed
below:
11 kV Single VCB panel With 630 Amp,500 MVA, EDO type VCB
with closing coil , shunt trip,
spring charged closing mechanism, operation counter auxiliary
contacts for interlocks, and complete
with following:- Antipumping relay, panel illumination lamp,Space
heater and Breaker control switch
,(TRIP-NEUTRAL -CLOSE), Emergency trip button.
Busbar: 11kV , 800A, 26.2 kA, 3 Phase,Electrolytic copper with
color coded PVC heat shrunk

INSTALLATION Set 1 0.00 0.00

1.4 BATTERY CHARGER( SUPPLY & ERECTION )

Supply, Installation,commissioning of automatic FLOAT-CUM-


BOOST battery charger unit with fast
response SCR controled full wave bridge rectifier( 2D+2 SCR)
complete with double wound copper conductor main
transformer,surge suppressor at the input sidea, uto float/manual
float/manualboost with double pole ON/OFF
MCB at AC input, pilot lamp for charger "ON" indication, other
protections, etc with all other features

Battery Charger 24 V DC output , 30 Amps as above including 1 no


Integral DC distribution board with
1 No 63 A DP DC MCB incomer and 10 Nos 16 A DP MCBs
outgoings. Charger Finished in Powder coated finish,
in Battleship GrayColour.
Charger Make: DUBAS or AMARRAJA or UNIVERSAL

Complete with BATTERY of 200 AH capacity 24 volts DC


hermetically sealed maintenance free lead acid batteries
charged, complete with Heavy Dutyanti-static moulded ABS plastic
/ PVC racks

Battery MAKE: EXIDE / STANDARD / HITACHI / AMAR RAJA

INSTALLATION Set 1 0.00 0.00

Taj Gateway Hotel at Chennai Page- 2 of 62


Taj Gateway Hotel at Chennai
SL.No Item Description Unit
Qty PRICE Amount

SUB TOTAL OF SUB STATION EQUIPMENTS 0.00


INSTALLATION

2 TRANSFOMER -1250 kVA

Instalation,testing,commissioning of Dry Type Packaged


TransformerUnit with integral OLTC Supply and installation of
Indoor Dry type,Transformer, IP 23 , Vacuum Resin
Impregnated/CAST RESIN totally enclosed, Delta /Star DYN11
continious duty ,1250 kVA as per IS: 11171, Class F insulated,
ANAN cooled, having impedence 5 to 6%, comprising Integral
On-Load Tap Changer (-7.5% To +7.5 %) Taps in steps of 1.5
2.1 % ,complete with Winding temperature Indicator. Suitable terminal
arrangement for HT and LT side to be provided ( 3C- 185 Sq mm
XLPE Cables on HT Side and 2000 Amps Bus Duct on the LT
Side.) Cable Adaptor Chamber and HT Cable Box shall be suitable
for bottom entry of cables , Busduct on the top entry/ side
Entry.Transformer Enclosure shall be finished in Battle Ship Grey
color, Powdercoated Finish or as per IS/IEC Standard with all
necssery fitting &accessoriess.

Rate to include the following also:

a) 1 Nos CTs (1400/5 Amp PS Class, 15 VA ) for REF protection, 1


No CT on the Transformer Neutral for each set)

b) 1 Nos CTs (1400/5 Amp PS Class, 15 VA ) for REF protection, 1


No CT on the Transformer CT in the Main LT Panel.(for each set)

c) 1 No 1400/5 Amp, Cl 5P 10, 15 VA CT on the Transformer


Neutral for Standby Earth Fault Relay (for each set)
The above CT Terminals as well as WTI contacts have to be
brought out to the Marshalling box with proper Ferrules/
identification labels

TERMINAL ARRANGEMENT

H.V TERMINALS : Suitable for Cable Box.


L.V TERMINALS : Suitable for BUSDUCT

INSTALLATION Set 2 0.00 0.00

SUB TOTAL OF TRANSFORMER INSTALATIONS 0.00


INSTALLATION

3 LT BUS DUCTS & LT RAISING MAINS

LT BUS DUCTS for TRANSFORMERS

Bus ducts suitable for outdoor installations as per specification for


up-stream installations: Sandwiched Busducts will be complete
with Aluminium bus bars with expansion joints, Fire barriers
including necessary supports and louvers for ventilation, enclosure
fabricated out of 14 gauge thick MS Housing 55 steel painted with
approved paint shade as per specification including 2 Nos. of 25 x 6
mm Aluminium earthling conductor throughout the length of the
bus duct enclosure.The cost shall also necessary supports for the
same.(As per SLD)

Taj Gateway Hotel at Chennai Page- 3 of 62


Taj Gateway Hotel at Chennai
SL.No Item Description Unit
Qty PRICE Amount

2000A,50KA TPN Aluminium Bus duct between Transformer 1,


3.1
2 & Main LT Panel

INSTALLATION M 50 0.00 0.00

3.2 LT Breaker / Transformer End flanges for above in Aluminium

INSTALLATION Each 4 0.00 0.00

3.3 Elbows, Bends & joints,wherever bends are installed in Aluminium

INSTALLATION Set 2 0.00 0.00

3.4 Flexible type (Bimetallic) Joints for the above Busduct-Supply

INSTALLATION Set 2 0.00 0.00

3.5 Horizontal Bend


INSTALLATION Nos. 2 0.00 0.00
0
3.6 Vertical up Bend
INSTALLATION Nos. 2 0.00 0.00

3.7 Vertical down Bend


INSTALLATION Nos. 2 0.00 0.00
0
3.8 Adopter box at Main LT Panel
INSTALLATION Nos. 2 0.00 0.00

3.9 Set TPN 1600A Flexibles for termination Conn. (Aluminium)


INSTALLATION Set 2 0.00 0.00

3.10 Galvanized Hangers / Rigid hanger with all necessery works


INSTALLATION Nos. 10 0.00 0.00

LT BUS DUCTS for DG

Bus ducts suitable for outdoor installations per specification for up-
stream installations: Sandwiched Busducts will be complete with
Aluminium bus bars with expansion joints, Fire barriers including
necessary supports and louvers for ventilation, enclosure fabricated
out of 14 gauge thick MS Housing 55 steel painted with approved
paint shade as per specification including 2 Nos. of 25 x 6 mm
Aluminium earthling conductor throughout the length of the bus
duct enclosure.The cost shall also necessary supports for the same.

1600A, 50KA TPN Aluminium Bus duct between DG to AMF


3.11
Panel and
AMF Panel & Main LT Panel
INSTALLATION M 40 0.00 0.00

3.12 LT Breaker / DG End flanges for above in Aluminium

INSTALLATION Nos. 4 0.00 0.00

3.13 Elbows, Bends & joints,wherever bends are installed in Aluminium

Taj Gateway Hotel at Chennai Page- 4 of 62


Taj Gateway Hotel at Chennai
SL.No Item Description Unit
Qty PRICE Amount

INSTALLATION Set 0.00 0.00

3.14 Flexible type (Bimetallic) Joints for the above Busduct-Supply

INSTALLATION Set 4 0.00 0.00

3.15 Horizontal Bend (1600 Amps)


INSTALLATION Nos. 7 0.00 0.00

3.16 Vertical up Bend (1600 Amps)


INSTALLATION Nos. 4 0.00 0.00

3.17 Vertical down Bend (1600 Amps)


INSTALLATION Nos. 4 0.00 0.00

3.18 Adopter box at Main LT Panel (1600 Amps)


INSTALLATION Nos. 4 0.00 0.00

3.19 Set TPN 1600A Flexibles for termination Conn. (Aluminium)


INSTALLATION Set 4 0.00 0.00

3.20 Galvanized Hangers / Rigid hanger with all necessery works 0


INSTALLATION Nos. 30 0.00 0.00

SUB TOTAL OF LT BUS DUCTS & LT RAISING MAINS 0.00

INSTALLATION

4 RISING MAINS

Installation, testing and commissioning of 415 V, 50 Hz ,35 kA


for 1 Sec, TPN Rising Mains in Air Insulated construction of
Aluminium bus bar (of size as per SLD) with tap-off connection
points at every floor level, expansion joints, fire barriers including
necessary busbar supports.The Rising mains shall be enclosed in
fabricated enclosure made out of 14 SWG CRCA sheet steel ,
painted with approved paint shade including 2 Nos. of 25 X 6 mm
Aluminium earthing conductor throughout the length of the rising
mains (Phase sequence should be matched with the incoming
breaker provided at LT Panel). Thrust pad shall be provided for
each rising main for necessary support to rising main and to prevent
the bus bar expansion in downward direction. Also to provide end
cover to close the end of rising main and extra supports to bus bars
at ends.Dimension to be furnished with the offer. (Shaft will have 2
nos.rising mains)

1000A ,415 V, 50 kA ,TPN Rising mains made of Aluminium


4.1
busbars. (consider future expantion also )

INSTALLATION M 50 0.00 0.00

4.2 TAP-OFF BOXES

Taj Gateway Hotel at Chennai Page- 5 of 62


Taj Gateway Hotel at Chennai
SL.No Item Description Unit
Qty PRICE Amount

Supply, installation, testing and commissioning of following


MCCB Tap-off boxes fabricated out of 14 gauge CRCA sheet steel
in cubical formation, dust and vermin proof, coupled with rising
mains. Boxes shall be treated with all anticorrosine
process before powder coating as per specifications. 2 Nos.
earthing terminals shall be provided. Boxes shall be suitable for
connecting of rising mains at top and cables at bottom

MCCB s provided in the Tap-off boxes will have adjsutable


O/C,S/C releases
for protection. MCCB rated above 200 Amp will have Micro-
processor based releases. Others shall be with adjustable thermo-
magnetic releases.

4.3 1000A 4P End Feed Box MCCB (50kA)

0 0.00 0.00
INSTALLATION Nos. 2 0.00 0.00

Tap-off box TPN complete with 315A TPN MCCB (25kA) &
4.4
provision for
multiple cable entry with suitable adopter box.

INSTALLATION Nos. 8 0.00 0.00

Tap-off box TPN complete with 200A TPN MCCB (25kA) &
4.5
provision for
multiple cable entry with suitable adopter box.

INSTALLATION Nos. 8 0.00 0.00

Tap-off box TPN complete with 125A TPN MCCB (25kA) &
4.6
provision for
multiple cable entry with suitable adopter box.

INSTALLATION Nos 0 0.00 0.00

End Cap unit For Raising Mains as per specification with all
4.6
necessery items ( consider future expantion also )

Nos. 0 0.00 0.00


INSTALLATION Nos. 2 0.00 0.00

NOTE
LT BUSDUCT and RISING MAIN QTY ARE TENTATIVE FOR
ORDERING QTY TO BE
OBTAINED BY PHYSICAL MEASUREMENTS.

SUB TOTAL OF RISING MAINS 0.00


SUPPLY
INSTALLATION

5 LT PANELS & DISTRIBUTION BOARDS

Design, Manufacture,Assemble,Supply, Installation Testing &


Commissioning of Sheet steel

Taj Gateway Hotel at Chennai Page- 6 of 62


Taj Gateway Hotel at Chennai
SL.No Item Description Unit
Qty PRICE Amount

fabricated panel,made out of 2mm thick sheet steel, duly treated by


7 tank process, and
powder coated,using only approved components , 65kA Aluminium
Bus bars,continuous
earth bars, with 2nos.earth terminals necessary lifting hooks, all
necessary gland plates &
glands complete as per specifications & single line diagram . All
panels with top / bottom entry
provision only galvanised, Zinc passivated hardware shall be used
for assembling. The cost
shall also necessary supports in etc. .

All ACB's shall have Microprocessor based


Monitoring module to read A,V,Hz,kW,kVAr,kVArh & kVAh etc.

Note:
Approval shall be taken for each & every panel
including all interlocking schemes proposed in the
form of Shop Drawings before fabrication.
Approval make of panels : who have CPRI Certification.
Approved Make of Components:-
Make:( Ammeter Cum Voltmeter Cum Frequency Meter in all
outgoing
feeders ENERCON ELF 3259 or Equivalent

5.1 MV PANEL (MV PANEL ROOM)

INCOMER

2 Nos. 2000A 4 pole ACB, Electricaly operated, Draw out type


with
65 kA(1 sec) short circuit withstand capacity. The ACB shall be
with
micro-porocessor based releases for over current,short circuit and
ground fault
(L,S,I,G) protections. ( Transformer Feeder I/C-1&2)

2 Nos 1600A 4 pole ACB, Electricaly operated, Draw out type with

65 kA(1 sec) short circuit withstand capacity. The ACB shall be


with
micro-porocessor based releases for over current,short circuit and
ground fault
(L,S,I,G) protections. ( Generator Feeder I/C-1&2 )

NOTE: IDMTL time settings of ACB releases shall be adjustable


so that
discrimination is possibble betwen HT breaker and transformer
O/G breaker

2 Sets of CTs for sensing to APFCR panel.

All incomers should have suitable interlocks.

BUS BAR RATING :

2500A TPN+E Aluminium. Bus bars of 65kA rating, Current


density 1 Amp/sq.mm with
earth busbar,25 x6 mm GI, throught the length of the panel .Each
cable alley shall

Taj Gateway Hotel at Chennai Page- 7 of 62


Taj Gateway Hotel at Chennai
SL.No Item Description Unit
Qty PRICE Amount

have one vertical drop from earth bus with sufficient no. of holes
( size to match
ECC size as per SLD) punched on to that so that out going Earth
continuity
cables(ECC) can be terminated to that.

METERS:
Digital MDM (Multi data meter) A,V,F,PF,kW,kWH & kVA
INDICATING LAMPS: RYB on each bus section with MCB
Protection
with all required CT's for protection and metering

BUSCOUPLER
1 No. 2500 A 4P 65kA with out releases ACB's. with necessary
interlocks with shunt trip,
closing coil , ON/OFF lamps, Breaker control switch etc as
required.

OUTGOINGS

Each feeder will have R,Y,B indicating lamps, ON/OFF/TRIP


indication
Each outgoing MCCB will have m.p based adjustable O/L,S/C, and
E/F protection
releases and Residual device for earth fault detection. ( Applicable
for MCCB rated
200 Amps and above) Others shall be with adjustable thermo-
magnetic releases.

1250A, 50kA, FP MCCB with all necessery items - 4 Nos.


1000A,50kA, TPN MCCB with all necessary items - 3 Nos
630A, 35kA, TPN MCCB with all necessery items - 1 No.
400A, 35kA, TPN MCCB with all necessery items - 5 Nos.
315A, 35kA, TPN MCCB with all necessery items - 4 Nos.
200A, 25kA, TPN MCCB with all necessery items - 4 Nos.
160A, 25kA, TPN MCCB with all necessery items - 1 No.
NOTE:

1) All Incoming feeder should have Inter locks (Mechanical lock)

SPARE FEEDERS

1250A, 50kA, FP MCCB with all necessery items - 1 No.


400A, 50kA, TPN MCCB with all necessery items - 2 Nos.
315A, 50kA, TPN MCCB with all necessery items - 1 No.
200A, 50kA, TPN MCCB with all necessery items - 2 Nos.
INSTALLATION Set 0 0.00 0.00

5.2 CAPACITOR PANEL 1,2 (MV PANEL ROOM)

400 kVAr Automatic Power Factor correction panel

Incoming:
1250A,50kATPN MCCB with all necessery items - 1No.
with shunt trip + ELR & All releases.
Bus bar rating:
1500A TPN + E Aluminium, bus bars.

Taj Gateway Hotel at Chennai Page- 8 of 62


Taj Gateway Hotel at Chennai
SL.No Item Description Unit
Qty PRICE Amount

METERS:
Digital MDM (Multi data meter) (A, V, PF)
phase indicating lamps with C.T's,
PF compensating relay APFCR-09 step , selector switches, all
Auxiliary contacts, contactors, control fuses / MCB's
etc., complete with PF meter, etc.,

OUTGOINGS

200 A TP MCCB of 25 KA with 3 Pole contactor for switching 50


KVAR capacitor including.

supply and providing mixed di-electric extra low loss type - 6 nos

100 A TP MCCB of 25 KA with 3 Pole contactor for switching 25


KVAR capacitor including.

supply and providing mixed di-electric extra low loss type - 4 nos

ON/OFF Push button, Indicating lamps for ON/OFF - 09 sets


100A TP Terminal blocks - 10 nos

Space Provision:
25 kVAr mixed dielectric extra low loss type
Capacitor banks - 02Sets.
ON / OFF push buttons, Indicating lamps for ON/OFF - 2 sets

100A TP Terminal blocks - 02 Nos.

SUPPLY Sets. 0 0.00 0.00


INSTALLATION Sets. 0 0.00 0.00

5.3 SUB LIGHTING PANEL (GROUND FLOOR)

Incoming:
400A TPN MCCB with All necessery items (35kA) - 1No.

Bus Bar Rating:


400A TPN+E Aluminium.bus bars

Incoming with Multi data meter (V, A) ,Phase indicating lamps with
MCB Protection,
CT's,Selector switches etc., ON/OFF/TRIP indication

Outgoings:
63A TPN MCCB (25kA) - 19Nos.

Spare Feeders:
63A TPN MCCB (25kA) - 4Nos.

SUPPLY Sets. 0 0.00 0.00


INSTALLATION Sets. 0 0.00 0.00

5.4 SUB LIGHTING PANEL 1,2,3 (IST,2ND,3RD FLOOR)

Incoming:
200 A ,25kA 4P On-Load Change Over Switch -1No.

Bus Bar Rating:


200A TPN+E Aluminium.bus bars

Taj Gateway Hotel at Chennai Page- 9 of 62


Taj Gateway Hotel at Chennai
SL.No Item Description Unit
Qty PRICE Amount

Incoming with Multi data meter (V, A) ,Phase indicating lamps with
MCB Protection,
CT's,Selector switches etc., ON/OFF/TRIP indication

Outgoings:
63A TPN MCCB (25kA) - 05Nos.

Spare Feeders:
63A TPN MCB (25kA) - 02Nos.
32A TPN MCCB (25kA) - 01No.

SUPPLY Sets. 0 0.00 0.00


INSTALLATION Sets. 0 0.00 0.00

5.5 SUB LIGHTING PANEL 4 (4TH FLOOR)

Incoming:
200 A ,25kA 4P On-Load Change Over Switch -1No.

Bus Bar Rating:


200A TPN+E Aluminium.bus bars

Incoming with Multi data meter (V, A) ,Phase indicating lamps with
MCB Protection,
CT's,Selector switches etc., ON/OFF/TRIP indication

Outgoings:
63A TPN MCCB (25kA) - 05Nos.

Spare Feeders:
63A TPN MCB (25kA) - 02Nos.
32A TPN MCCB (25kA) - 01No.

SUPPLY Sets. 0 0.00 0.00


INSTALLATION Sets. 0 0.00 0.00

5.6 SUB POWER PANEL (GROUND FLOOR)

Incoming:

400A TPN MCCB with All necessery items (35kA) - 1No.

Bus Bar Rating:


400A TPN+E Aluminium.bus bars

Meters:
Incoming with Multi data meter (V, A) ,Phase indicating lamps with
MCB Protection,
CT's,Selector switches etc., ON/OFF/TRIP indication

Outgoings:
160A TPN MCCB (25kA) - 3 Nos.
63A TPN MCCB (25kA) - 6 Nos.

Spare Feeders:
160A TPN MCCB (25kA) - 01No.
63A TPN MCCB (25kA) - 02Nos.

SUPPLY Set 0 0.00 0.00


INSTALLATION Set 0 0.00 0.00

Taj Gateway Hotel at Chennai Page- 10 of 62


Taj Gateway Hotel at Chennai
SL.No Item Description Unit
Qty PRICE Amount

5.7 SUB POWER PANEL 1,2,3 (IST,2ND,3RD FLOOR)

Incoming:
315 A ,25kA 4P On-Load Change Over Switch -1No.

Bus Bar Rating:


315A TPN+E Aluminium.bus bars

Incoming with Multi data meter (V, A) ,Phase indicating lamps with
MCB Protection,
CT's,Selector switches etc., ON/OFF/TRIP indication

Outgoings:
63A TPN MCCB (25kA) - 06Nos.

Spare Feeders:
63A TPN MCCB (25kA) - 02Nos.
32A TPN MCCB (25kA) - 01Nos.

SUPPLY Sets. 0 0.00 0.00


INSTALLATION Sets. 0 0.00 0.00

5.8 SUB POWER PANEL 4 (4TH FLOOR)

Incoming:
315 A ,25kA 4P On-Load Change Over Switch -1No.

Bus Bar Rating:


315A TPN+E Aluminium.bus bars

Incoming with Multi data meter (V, A) ,Phase indicating lamps with
MCB Protection,
CT's,Selector switches etc., ON/OFF/TRIP indication

Outgoings:
63A TPN MCCB (25kA) - 06Nos.

Spare Feeders:
63A TPN MCCB (25kA) - 02Nos.
32A TPN MCCB (25kA) - 01Nos.

SUPPLY Sets. 0 0.00 0.00


INSTALLATION Sets. 1 0.00 0.00

5.9 UPS PANEL

INCOMING
200 A 3 Pole MCCB, 20 kA with double neutral link and adjustable
thermal and
fixed magnetic releases for O/C, S/C protection. MCCB neutral
shall be 200 % rated
for protection, RYB power indication, UPS ON/OFF indication
LED lamps with

protection MCB ,1 No Digital meter to read Voltage , Current, PF

Bus Bar Rating:


300A TPN+ E 200% Neutral Aluminium .bus bars

Meters:

Taj Gateway Hotel at Chennai Page- 11 of 62


Taj Gateway Hotel at Chennai
SL.No Item Description Unit
Qty PRICE Amount

Incoming with Multi data meter (V, A) ,Phase indicating lamps with
MCB Protection,
CT's,Selector switches etc., ON/OFF/TRIP indication

Outgoings:

63A TPN MCCB (10kA) D - Curve - 13Nos.

Spare Feeders:
63A TPN MCCB (10kA) D - Curve - 3Nos.

SUPPLY Set 0 0.00 0.00


INSTALLATION Set 0 0.00 0.00

5.10 MAIN LIFT PANEL (ELECTRICAL ROOM)

Incoming:

200A TPN MCCB with All necessery items (35kA) - 1No.

BUS BAR RATING:


200A TPN+E Aluminium bus bars

METERS:
Incoming with Multi data meter (V, A) ,Phase indicating lamps with
MCB Protection,
CT's,Selector switches etc., ON/OFF/TRIP indication
1No. 0 to 3000mA ELR & CBCT.

Outgoings:
63A TPN MCCB (25kA) - 07Nos.

Spare Feeders:
63A TPN MCCB (25kA) - 02Nos.

SUPPLY Set 0 0.00 0.00


INSTALLATION Set 0 0.00 0.00

5.11 PLUMBING PANEL (PLUMBING ROOM )

Incoming:

400A TPN MCCB with All necessery itmes (35kA) -1No.

BUS BAR RATING:


400A TPN+E Aluminium.bus bars

METERS:
Incoming with Multi data meter (V, A) ,Phase indicating lamps with
MCB Protection,
CT's,Selector switches etc., ON/OFF/TRIP indication

Outgoings:

200A,25kA TPN MCCB with neceessery contactor,relays (25kA)


-1 No.
100A,25kA TPN MCCB with neceessery contactor,relays (25kA)
-1 No.
63A,25kA TPN MCCB with neceessery contactor,relays (25kA) -
5 Nos.

Taj Gateway Hotel at Chennai Page- 12 of 62


Taj Gateway Hotel at Chennai
SL.No Item Description Unit
Qty PRICE Amount

Spare Feeders:
63A TPN MCCB (25kA) - 02 Nos.

SUPPLY Set 0 0.00 0.00


INSTALLATION Set 0 0.00 0.00

5.12 COLLECTION PIT SUMP PUMP PANEL

Incoming:

63A TPN MCCB with All necessery itmes (35kA) -1No.

BUS BAR RATING:


100A TPN+E Aluminium bus bars

METERS:
Incoming with Multi data meter (V, A) ,Phase indicating lamps with
MCB Protection,
CT's,Selector switches etc., ON/OFF/TRIP indication

Outgoings:

40A, 25kA, TPN MCB with all necessery items - 06 Nos. (With
Auto Level switch including all level sensor necessery wiring)

Spare Feeders:
40A, 25kA, TPN MCB with all necessery items - 1 No.

SUPPLY Set 0 0.00 0.00


INSTALLATION Set 0 0.00 0.00

5.13 HVAC MAIN PANEL (PLANT ROOM)

INCOMER-1
1250 A ,50kA 4P On-Load Change Over Switch -1No.

Note: Shunt trip Req. for trip Breaker Thro Fire Alarm Panel
Potential Free Contactor.

BUS BAR RATING :


1250A TPN+E Aluminium. Bus bars of 50kA rating, Current
density 0.8 Amp/sq.mm with earth busbar,25 x6 mm GI, throught
the length of the panel .Each cable alley shall have one vertical
drop from earth bus with sufficient no. of holes ( size to match
ECC size as per

NOTE: Feeder will have R,Y,B indicating lamps, ON/OFF/TRIP


indication
Each outgoing MCCB will have m.p based adjustable O/L,S/C, and
E/F protection
releases and Residual device for earth fault detection. ( Applicable
for MCCB rated
200 Amps and above) Others shall be with adjustable thermo-
magnetic releases.

METERS:
Digital MDM (Multi data meter) A,V,F,PF,kW,kWH & kVA
INDICATING LAMPS: RYB on each bus section with MCB
Protection
with all required CT's for protection and metering

Taj Gateway Hotel at Chennai Page- 13 of 62


Taj Gateway Hotel at Chennai
SL.No Item Description Unit
Qty PRICE Amount

Outgoings:
Each feeder will have R,Y,B indicating lamps, ON/OFF/TRIP
indication

Each outgoing MCCB will have m.p based adjustable O/L,S/C, and
E/F protection
releases and Residual device for earth fault detection. (Applicable
for MCCB rated
200 Amps and above) Others shall be with adjustable thermo-
magnetic releases.

630A, 35kA, TPN MCCB with All necessery items for chiller - 3
Nos.

SUPPLY Set 0 0.00 0.00


INSTALLATION Set 1 0.00 0.00

5.14 HVAC MAIN PUMP PANEL (PLANT ROOM)

INCOMER-1
630A, 50kA, TPN MCCB - 3 Nos.

Note: Shunt trip Req. for trip Breaker Thro Fire Alarm Panel
Potential Free Contactor.

BUS BAR RATING :


800A TPN+E Aluminium. Bus bars of 50kA rating, Current density
0.8 Amp/sq.mm with earth busbar,25 x6 mm Aluminium, throught
the length of the panel .Each cable alley shall have one vertical
drop from earth bus with sufficient no. of holes ( size to match
ECC size as per

NOTE: Feeder will have R,Y,B indicating lamps, ON/OFF/TRIP


indication
Each outgoing MCCB will have m.p based adjustable O/L,S/C, and
E/F protection
releases and Residual device for earth fault detection. ( Applicable
for MCCB rated
200 Amps and above) Others shall be with adjustable thermo-
magnetic releases.

METERS:
Digital MDM (Multi data meter) A,V,F,PF,kW,kWH & kVA
INDICATING LAMPS: RYB on each bus section with MCB
Protection
with all required CT's for protection and metering

Outgoings:
Each feeder will have R,Y,B indicating lamps, ON/OFF/TRIP
indication

Each outgoing MCCB will have m.p based adjustable O/L,S/C, and
E/F protection
releases and Residual device for earth fault detection. ( Applicable
for MCCB rated
200 Amps and above) Others shall be with adjustable thermo-
magnetic releases.

63A, 25kA, TPN MCCB with 20.0 HP Suitable star delta starter
(PRIMARY CHILLED WATER) and necessery cotactor,relays
-3 Nos.

Taj Gateway Hotel at Chennai Page- 14 of 62


Taj Gateway Hotel at Chennai
SL.No Item Description Unit
Qty PRICE Amount

125A, 25kA, TPN MCCB 40.0HP (VFD Supply by HVAC


Contractor) (SECONDARY CHILLED WATER) - 2 Nos.
125A, 25kA, TPN MCCB 25.0HP (VFD Supply by HVAC
Contractor) (SECONDARY CHILLED WATER) - 3 Nos.
125A, 25kA, TPN MCCB with 40.0 HP Suitable star delta
starter (CONDENSER PUMPS) and necessery cotactor,relays -3
Nos.

63A, 25kA, TPN MCCB with 15.0HP Suitable star delta starter
(COOLING TOWER) and necessery cotactor,relays -3 Nos.

SPARE FEEDERS:
125A, 50kA, TPN MCCB with All necessery items - 2
Nos.
63A, 50kA, TPN MCCB with All necessery items - 1
No.

SUPPLY Set 0 0.00 0.00


INSTALLATION Set 1 0.00 0.00

5.15 BASEMENT VENTILATION PANEL-1

Incoming:

315 A TPN MCCB with all necessery items 25kA - 1No.

BUS BAR RATING:


400A TPN+E Aluminium.bus bars

METERS:
Incoming with Multi data meter (V, A) ,Phase indicating lamps with
MCB Protection,
CT's,Selector switches etc., ON/OFF/TRIP indication

Outgoings:
250A, 25kA, TPN MCCB with all necessery items -02 Nos.
63A, 25kA, TPN MCCB with all necessery items -12Nos.

SPARE FEEDERS
125A, 25kA, TPN MCCB with all necessery items - 1No.
63A, 25kA, TPN MCCB with all necessery items - 2Nos.

SUPPLY Set 0 0.00 0.00


INSTALLATION Set 0 0.00 0.00

5.16 BASEMENT VENTILATION PANEL-2

Incoming:

200 A TPN MCCB with all necessery items 25kA - 1No.

BUS BAR RATING:


315A TPN+E Aluminium.bus bars

METERS:
Incoming with Multi data meter (V, A) ,Phase indicating lamps with
MCB Protection,
CT's,Selector switches etc., ON/OFF/TRIP indication

Outgoings:
63A, 25kA, TPN MCCB with all necessery items -05No.
32A, 25kA, TPN MCCB with all necessery items -04Nos.

Taj Gateway Hotel at Chennai Page- 15 of 62


Taj Gateway Hotel at Chennai
SL.No Item Description Unit
Qty PRICE Amount

SPARE FEEDERS
125A, 25kA, TPN MCCB with all necessery items - 1No.
63A, 25kA, TPN MCCB with all necessery items - 2Nos.

SUPPLY Set 0 0.00 0.00


INSTALLATION Set 0 0.00 0.00

5.17 MEZZANINE FLOOR VENTILATION PANEL

Incoming:

160 A TPN MCCB with all necessery items 25kA - 1No.

BUS BAR RATING:


200A TPN+E Aluminium.bus bars

METERS:
Incoming with Multi data meter (V, A) ,Phase indicating lamps with
MCB Protection,
CT's,Selector switches etc., ON/OFF/TRIP indication

Outgoings:
20A, 10kA, 4P MCB with all necessery items - 10 Nos.
40A, 10kA, 4P MCB with all necessery items - 02 Nos.

SPARE FEEDERS
20A, 10kA, 4P MCB with all necessery items - 04 Nos.

SUPPLY Set 0 0.00 0.00


INSTALLATION Set 0 0.00 0.00

5.18 TERRACE FLOOR VENTILATION PANEL

Incoming:
200 A TPN MCCB with all necessery items 25kA - 1No.

BUS BAR RATING:


315A TPN+E Aluminium.bus bars

METERS:
Incoming with Multi data meter (V, A) ,Phase indicating lamps with
MCB Protection,
CT's,Selector switches etc., ON/OFF/TRIP indication

Outgoings:
63 A TPN MCCB with all necessery items 25kA - 4Nos.
20A, 10kA, 4P MCB with all necessery items - 24 Nos.
40A, 10kA, 4P MCB with all necessery items - 01 No.

SPARE FEEDERS

125 A TPN MCCB with all necessery items 25kA - 1No.

20A, 10kA, 4P MCB with all necessery items - 02 Nos.

SUPPLY Set 0 0.00 0.00


INSTALLATION Set 0 0.00 0.00

5.19 UPPER BASEMENT AHU PANEL

Incoming:

160 A TPN MCCB with all necessery items 25kA - 1No.

Taj Gateway Hotel at Chennai Page- 16 of 62


Taj Gateway Hotel at Chennai
SL.No Item Description Unit
Qty PRICE Amount

BUS BAR RATING:


200A TPN+E Aluminium.bus bars

METERS:
Incoming with Multi data meter (V, A) ,Phase indicating lamps with
MCB Protection,
CT's,Selector switches etc., ON/OFF/TRIP indication

Outgoings:
20A, 10kA, 4P MCB with all necessery items - 22 Nos.

SPARE FEEDERS
20A, 10kA, 4P MCB with all necessery items - 05 Nos.

SUPPLY Set 0 0.00 0.00


INSTALLATION Set 0 0.00 0.00

5.20 GROUND FLOOR AHU PANEL

Incoming:

160 A TPN MCCB with all necessery items 25kA - 1No.

BUS BAR RATING:


200A TPN+E Aluminium.bus bars

METERS:
Incoming with Multi data meter (V, A) ,Phase indicating lamps with
MCB Protection,
CT's,Selector switches etc., ON/OFF/TRIP indication

Outgoings:
20A, 10kA, 4P MCB with all necessery items - 8 Nos.

SPARE FEEDERS
20A, 10kA, 4P MCB with all necessery items - 05 Nos.

SUPPLY Set 0 0.00 0.00


INSTALLATION Set 0 0.00 0.00

5.21 MEZANINE FLOOR AHU PANEL

Incoming:

160 A TPN MCCB with all necessery items 25kA - 1No.

BUS BAR RATING:


200A TPN+E Aluminium.bus bars

METERS:
Incoming with Multi data meter (V, A) ,Phase indicating lamps with
MCB Protection,
CT's,Selector switches etc., ON/OFF/TRIP indication

Outgoings:
40A, 10kA, 4P MCB with all necessery items - 01 No.
20A, 10kA, 4P MCB with all necessery items - 20 Nos.

SPARE FEEDERS
40A, 10kA, 4P MCB with all necessery items - 01 No.
20A, 10kA, 4P MCB with all necessery items - 04 Nos.

Taj Gateway Hotel at Chennai Page- 17 of 62


Taj Gateway Hotel at Chennai
SL.No Item Description Unit
Qty PRICE Amount

SUPPLY Set 0 0.00 0.00


INSTALLATION Set 0 0.00 0.00

5.22 AHU FLOOR PANEL 1st, 2nd &3rd FLOOR

Incoming:

160 A TPN MCCB with all necessery items 25kA - 1No.

BUS BAR RATING:


200A TPN+E Aluminium.bus bars

METERS:
Incoming with Multi data meter (V, A) ,Phase indicating lamps with
MCB Protection,
CT's,Selector switches etc., ON/OFF/TRIP indication

Outgoings:
20A, 10kA, 4P MCB with all necessery items - 02 Nos.

SPARE FEEDERS
20A, 10kA, 4P MCB with all necessery items - 02 Nos.

SUPPLY Set 0 0.00 0.00


INSTALLATION Set 0 0.00 0.00

5.23 LAUNDRY PANEL

Incoming:

315 A TPN MCCB with all necessery items 25kA - 1No.

BUS BAR RATING:


400A TPN+E Aluminium.bus bars

METERS:
Incoming with Multi data meter (V, A) ,Phase indicating lamps with
MCB Protection,
CT's,Selector switches etc., ON/OFF/TRIP indication

Outgoings:

63 A TPN MCCB with all necessery items 25kA - 7Nos.

SPARE FEEDERS

63 A TPN MCCB with all necessery items 25kA - 3No.

SUPPLY Set 0 0.00 0.00


INSTALLATION Set 1 0.00 0.00

5.24 KITCHEN PANEL

Incoming:

315 A TPN MCCB with all necessery items 25kA - 1No.

BUS BAR RATING:


400A TPN+E Aluminium.bus bars

METERS:
Incoming with Multi data meter (V, A) ,Phase indicating lamps with
MCB Protection,
CT's,Selector switches etc., ON/OFF/TRIP indication

Taj Gateway Hotel at Chennai Page- 18 of 62


Taj Gateway Hotel at Chennai
SL.No Item Description Unit
Qty PRICE Amount

Outgoings:
63 A TPN MCCB with all necessery items 25kA - 7Nos.

SPARE FEEDERS

63 A TPN MCCB with all necessery items 25kA - 3No.

SUPPLY Set 0 0.00 0.00


INSTALLATION Set 1 0.00 0.00

MS support for miscellanous works ,Panels ,supports & frames


5.25
.etc

SUPPLY Kgs 0 0.00 0.00


INSTALLATION Kgs 1000 0.00 0.00

5.26 AHU STARTER PANEL


Design, manufacture, supply, installation, testing and
commissioning of the following cubicle type, dead front, sheet
steel, wall mounted control panels including anchoring into the
wall, wiring and earthing .All internal wiring and copper earthing
of air

All outgoing shall be provided with LOCAL/REMOTE selector


and AUTO/MANUAL switch to facilitate starting from the AHU
room as well as from the AHU Sub Panel.

The panel shall include the following components and accessories.

TPN MCB as per the ratings given below, suitable for motor duty
and able to withstand fault level of 16 KA.

DOL starter with contactors, built in single phasing protection, push


buttons, indicating lamps as per HP ratings given below:

Terminal block for power distribution.

Phase indicating lights and indicating light for ON and OFF status.

Digital voltmeter and digital ammeter with selector switches, CTs


as required.

Time delay relay for delayed automatic restart of air handling unit
motor.

Wiring for microswitch to stop the fan when fire damper closes- 1
set

5 A MCB and 230/24 V AC Transformer for power supply to 2 way


valve.- 1 Set

The number of AHU control panels shall be as follows.

Taj Gateway Hotel at Chennai Page- 19 of 62


Taj Gateway Hotel at Chennai
SL.No Item Description Unit
Qty PRICE Amount

a 2.5 Amps MCB upto 1 HP DOL Starter


SUPPLY Set 0 0.00 0.00
INSTALLATION Set 10 0.00 0.00

b 5 Amps MCB for 1 to 3 HP DOL Starter


SUPPLY Set 0 0.00 0.00
INSTALLATION Set 25 0.00 0.00

c 10 Amps MCB for 3 to 5 HP DOL Starter


SUPPLY Set 0 0.00 0.00
INSTALLATION Set 8 0.00 0.00

d 16 Amps MCB for 5 to 10 HP Star/Dalt Starter


SUPPLY Set 0 0.00 0.00
INSTALLATION Set 5 0.00 0.00

e 25 Amps MCB for 10 to 20 HP Star/Dalt Starter


SUPPLY Set 0.00 0.00
INSTALLATION Set 0.00 0.00

F 32 Amps MCCB for 21 to 25 HP Star/Dalt Starter


SUPPLY Set 0.00 0.00
INSTALLATION Set 0.00 0.00

5.27 CONTROL PANELS FOR FANS


roro

All internal wiring and copper earthing of Ventilation Panel from


the panel shall be included.

The panel shall include the following components and accessories.

MCCB as per rating given below, suitable for motor duty and able
to with stand fault level of 16 kA.

Terminal block for power distribution.

Contactor, Over load relay with buit in single phasing protection.

Phase indicating lights and indicating light for ON and OFF status.

Digital voltmeter and digital ammeter with selector switches, CTs


as required.

Time delay relay for delayed automatic restart of air handling unit
motor.

Wiring for microswitch to stop the fan when fire damper closes (in
case of Fan only) - 1 set

For on / off / remote and local operation, 3 pole single throw switch
shall be provided in \ each AHU panel to facilitate override of the
automatic operation.

Taj Gateway Hotel at Chennai Page- 20 of 62


Taj Gateway Hotel at Chennai
SL.No Item Description Unit
Qty PRICE Amount

For all Incoming / Outing & starter shall be provided


ON/OFF/TRIP with suitable potential free contact for connections
to the REMOTE Indicating Panel (Building Automation Systems) -
3Nos.

The number of Ventilation Fan Starter control panels shall be as


follows.

a 10 Amps MCB C-Curve 10kA upto 1 HP DOL Starter


SUPPLY Set 0 0.00 0.00
INSTALLATION Set 55 0.00 0.00

b 30 Amps MCB C-Curve 10kA for 1 to 4.5 HP DOL Starter


SUPPLY Set 0 0.00 0.00
INSTALLATION Set 10 0.00 0.00

30 Amps MCB C-Curve 10kA for 5 to 7.5 HP STAR DELTA


c
Starter
SUPPLY Set 0 0.00 0.00
INSTALLATION Set 12 0.00 0.00

d 40 Amps MCCB 16kA for 8 to 15 STAR DELTA Starter


SUPPLY Set 0 0.00 0.00
INSTALLATION Set 6 0.00 0.00

e 63 Amps MCCB 16kA for 20 to 25 HP STAR DELTA Starter

SUPPLY Set 0 0.00 0.00


INSTALLATION Set 10 0.00 0.00

f 125 Amps MCCB 16kA for 26 to 40 HP STAR DELTA Starter

SUPPLY Set 0 0.00 0.00


INSTALLATION Set 2 0.00 0.00

Note: -
Panels for Ventilation Fan with two speed motor shall be provided
with dual DOL Starter.

63 amps 4P MCB isolator housed in totally weather-proof HENSEL


5.28
/ 'els Spelberg ' make moulded Enclosure (FOR ESCALATORS)

SUPPLY Set 0 0.00 0.00


INSTALLATION Set 0 0.00 0.00

40 amps 4P MCB isolator housed in totally weather-proof HENSEL


5.29
/ 'els Spelberg ' make moulded Enclosure

SUPPLY Set 0 0.00 0.00


INSTALLATION Set 8 0.00 0.00

32 amps 4P MCB isolator housed in totally weather-proof HENSEL


5.30
/ 'els Spelberg ' make moulded Enclosure.

SUPPLY Set 0 0.00 0.00


INSTALLATION Set 2 0.00 0.00

63 amps DP MCB isolator housed in totally weather-proof


5.31
HENSEL / 'els Spelberg ' make moulded Enclosure.

Taj Gateway Hotel at Chennai Page- 21 of 62


Taj Gateway Hotel at Chennai
SL.No Item Description Unit
Qty PRICE Amount

SUPPLY Set 0 0.00 0.00


INSTALLATION Set 2 0.00 0.00

40 amps DP MCB isolator housed in totally weather-proof


5.32
HENSEL / 'els Spelberg ' make moulded Enclosure.

SUPPLY Set 0 0.00 0.00


INSTALLATION Set 4 0.00 0.00

32 amps DP MCB isolator housed in totally weather-proof


5.33
HENSEL / 'els Spelberg ' make moulded Enclosure.

SUPPLY Set 0 0.00 0.00


INSTALLATION Set 2 0.00 0.00

5.34 Adding 63A 4P ELMCB 63A (300mA) on Existing DBs


SUPPLY Set 0.00 0.00
INSTALLATION Set 0.00 0.00

5.35 Adding 40A 4P ELMCB 63A (300mA) on Existing DBs


SUPPLY Set 0.00 0.00
INSTALLATION Set 0.00 0.00

5.36 Adding 32A 4P ELMCB 63A (300mA) on Existing DBs


SUPPLY Set 0.00 0.00
INSTALLATION Set 0.00 0.00

5.37 Adding 63A TPN MCB 10kA C-Curve on Existing DBs


SUPPLY Set 0.00 0.00
INSTALLATION Set 0.00 0.00

5.38 Adding 40A TPN MCB10kA C-Curve on Existing DBs


SUPPLY Set 0.00 0.00
INSTALLATION Set 0.00 0.00

5.39 Adding 32A TPN MCB 10kA C-Curve on Existing DBs


SUPPLY Set 0.00 0.00
INSTALLATION Set 0.00 0.00

5.40 Adding 63A DP MCB 10kA C-Curve on Existing DBs


SUPPLY Set 0.00 0.00
INSTALLATION Set 0.00 0.00

5.41 Adding 40A DP MCB 10kA C-Curve on Existing DBs


SUPPLY Set 0.00 0.00
INSTALLATION Set 0.00 0.00

5.42 Adding 32A DP MCB10kA C-Curve on Existing DBs


SUPPLY Set 0.00 0.00
INSTALLATION Set 0.00 0.00

5.43 Adding 6 - 32A SP MCB 10kA C-Curve on Existing DBs


SUPPLY Set 0.00 0.00
INSTALLATION Set 0.00 0.00

Junction Box with 20Amps12 way TB on Din Channel for loop-in


& loopout, & 1No 6/10A DP MCB all to be housed in junction Box
5.44
in Hensel enclosure .(Overall Dimensions with JB-200 x 200 x 75
mm or near about)

Taj Gateway Hotel at Chennai Page- 22 of 62


Taj Gateway Hotel at Chennai
SL.No Item Description Unit
Qty PRICE Amount

(for Mullion type shop sign pillars around walk ways- in font of
Mall)
SUPPLY Set 0 0.00 0.00
INSTALLATION Set 30 0.00 0.00

SUB TOTAL OF LT PANELS 0.00


SUPPLY
INSTALLATION

6 LT DISTRIBUTION BOARDS

FINAL DISTRIBUTION BOARDS


Supply, installation, testing and commissioning of CRCA Sheet
steel

fabricated Double-door DBs, made out of 1.6 mm thick sheet steel,

duly powder-coated with approved shade after a seven-tank process

for de--rusting, de-phosphating and elimination of similar defects-

,cubicle- compartmentalised partitions to segregate


phases,approved lockable covers with padlocking facility for each
phase.

DOUBLE-DOOR construction complete as per specifications.

Wherever the configuration complies standard Double door DB s


by approved
vendors , these shall have 6kA, & D-Curve / C-Curve / B-Curve
MCB's. Such standard DBs
shall be provided with shorting tinned copper busbars with PVC
sleeves rated 200 Amps .
No wires to be used for shorting Same phase MCBs; The DBs shall
be
complete with 2 Nos Earthing provisions, 2 Nos Flexible Earthing
Of Door ,
Neutral Terminals, DIN bars and Earth & Neutral Connectors
adequate enough
for the number of circuits.DBs installed on suface or
recessed as per site conditions.

All Kitchen Final DBs shall be with stainless steel enclosures

Note:
Approval shall be taken for each & every panel including all
interlocking
schemes proposed, in the form of Shop Drawings before
fabrication.

6.1 FLDB-s ( Lighting Distribution Board )

A 4 Way TPN Three Tire MCB DB


TPN DB with 3 phase incoming , 3 phase outgoings , phase
segregated
INCOMING:- 1 No 63 Amps 4P MCB
3 Nos 32Amps Double Pole RCCB (30 mA)
3 Nos 32 Amps DP MCBs B- Curve ( 6 kA )

OUTGOINGS:-
6 Amps/10 Amps/16 Amps B Curve SP MCBs -12 Nos

SUPPLY Set 1 0.00 0.00

Taj Gateway Hotel at Chennai Page- 23 of 62


Taj Gateway Hotel at Chennai
SL.No Item Description Unit
Qty PRICE Amount

INSTALLATION Set 1 0.00 0.00

B 6 Way TPN Three Tire MCB DB


TPN DB with 3 phase incoming , 3 phase outgoings , phase
segregated
INCOMING:- 1 No 63 Amps 4P MCB

3 Nos 32 Amps Double Pole RCCB (30 mA)

3 Nos 32 Amps DP MCBs B- Curve ( 6 kA )

OUTGOINGS:-
6 Amps/10 Amps/16 Amps B Curve SP MCBs -18 Nos

SUPPLY Set 2 0.00 0.00


INSTALLATION Set 2 0.00 0.00
C 8 Way TPN Three Tire MCB DB
TPN DB with 3 phase incoming , 3 phase outgoings , phase
segregated
INCOMING:- 1 No 63 Amps 4P MCB

3 Nos 63 Amps Double Pole RCCB (30 mA)

3 Nos 63 Amps DP MCBs B- Curve ( 6 kA )

OUTGOINGS:-
6 Amps/10 Amps/16 Amps B Curve SP MCBs -24 Nos

SUPPLY Set 6 0.00 0.00


INSTALLATION Set 6 0.00 0.00
6.2 FLDB-s ( Power Distribution Board )

A 4 Way TPN Three Tire MCB DB


TPN DB with 3 phase incoming , 3 phase outgoings , phase
segregated
INCOMING:- 1 No 63 Amps 4P MCB
3 Nos 32Amps Double Pole RCCB (30 mA)
3 Nos 32 Amps DP MCBs B- Curve ( 6 kA )

OUTGOINGS:-
6 Amps/10 Amps/16 Amps B Curve SP MCBs -12 Nos

SUPPLY Set 0.00 0.00


INSTALLATION Set 0.00 0.00

B 6 Way TPN Three Tire MCB DB


TPN DB with 3 phase incoming , 3 phase outgoings , phase
segregated
INCOMING:- 1 No 63 Amps 4P MCB

3 Nos 32 Amps Double Pole RCCB (30 mA)

3 Nos 32 Amps DP MCBs B- Curve ( 6 kA )

OUTGOINGS:-
6 Amps/10 Amps/16 Amps B Curve SP MCBs -18 Nos

SUPPLY Set 4 0.00 0.00


INSTALLATION Set 4 0.00 0.00

C 8 Way TPN Three Tire MCB DB


TPN DB with 3 phase incoming , 3 phase outgoings , phase
segregated
INCOMING:- 1 No 63 Amps 4P MCB

Taj Gateway Hotel at Chennai Page- 24 of 62


Taj Gateway Hotel at Chennai
SL.No Item Description Unit
Qty PRICE Amount

3 Nos 63 Amps Double Pole RCCB (30 mA)

3 Nos 63 Amps DP MCBs B- Curve ( 6 kA )

OUTGOINGS:-
6 Amps/10 Amps/16 Amps B Curve SP MCBs -24 Nos

SUPPLY Set 20 0.00 0.00


INSTALLATION Set 20 0.00 0.00

12 Way TPN Three Tire MCB DB ( Lighting &


6.3
PowerDistribution Board )

TPN DB with 3 phase incoming , 3 phase outgoings , phase


segregated
INCOMING:- 1 No 63 A 4P MCB

3 Nos 63 Amps Double Pole ELCB (300 mA)

3 Nos 63 Amps DP MCBs B- Curve ( 6 kA )

OUTGOINGS:-
6 Amps/10 Amps/16 Amps B Curve SP MCBs -36 Nos

SUPPLY Set 0.00 0.00


INSTALLATION Set 0.00 0.00

6.4 FLDB-s ( Lighting & PowerDistribution Board )


12 way SPN MCB DB
SPN DB with 1 phase incoming , 1 phase outgoings ,
INCOMING:- 1 No 32A DP MCB
OUTGOINGS:-
6 Amps/10 Amps/16 Amps B Curve SP MCBs -10 Nos

SUPPLY
INSTALLATION Set 0.00 0.00
Set 0.00 0.00
6.5 8 Way TPN VERTICAL DB ( for AHU UNITS)

Incoming:
63A TPN MCB (25kA) -1no
Outgoings:
40A MCB (25kA) -8no

SUPPLY Set 1 0.00 0.00


INSTALLATION Set 1 0.00 0.00

6.6 4 Way TPN VERTICAL PDB ( for AHU UNITS)

Incoming:
63A 4P MCB (10kA) -1no
Outgoings:
20A 4P MCB (10kA) -4nos.

SUPPLY Set 3 0.00 0.00


INSTALLATION Set 3 0.00 0.00

6.7 External DB ( External Lighting Distribution Board )

External lighting FDB-s ( Outdoor duty , Duly gasketed, with


sloping Canopy )

Taj Gateway Hotel at Chennai Page- 25 of 62


Taj Gateway Hotel at Chennai
SL.No Item Description Unit
Qty PRICE Amount

TPN DB with 3 phase incoming , 3 phase outgoings , Pad-lockable


Door

INCOMING:- 63Amps TPN MCB 6 kA, B Curve - 1 No


RYB power indication LED lamps with MCB protection
1 No 24 hours programmable Timer
1 no 4 pole Contactor 63 amps rating
1 no Over-ride switch for timer & contactor
63 A 4 pole ELCB 100 mA
OUTGOINGS
4 Nos 16 amps 4 pole MCB-s 6 kA, C Curve

SUPPLY Set 2 0.00 0.00


INSTALLATION Set 2 0.00 0.00

6.8 Lift- FDBs


INCOMING
63 A TP MCCB with Neutral Link 25kA - 1No.
20 A DP MCB C Curve 10kA - 1No.

METERS:
Incoming with Multi data meter (V, A) ,Phase indicating lamps with
MCB Protection,
CT's,Selector switches etc., ON/OFF/TRIP indication

Outgoings:
63A 4P RCCB (30mA) -
1No.
16A SP MCB 10kA C Curve with 6/16A switched socket Outlet -
1No.
10A SP MCB 10kA C Curve -
1No.
6A SP MCB 10kA C Curve -
1No.

SUPPLY Set 7 0.00 0.00


INSTALLATION Set 7 0.00 0.00

6.11 UPS F DB-Ground Floor & Relevant Work station areas ,

TPN DB with 3 phase incoming , 3 phase outgoings , phase


A
segregated
INCOMING:- 1 No 40A 4P MCB Isolator

3 Nos 40 Amps DP MCBs D- Curve ( 10 kA )

OUTGOINGS:-
6 Amps/10 Amps/16 Amps D Curve SP MCBs -24 Nos

SUPPLY Set 6 0.00 0.00


INSTALLATION Set 6 0.00 0.00

UPS FDB- ( EPABX , CCTV , Security , F.A Detectors Panel &


B
UPS Lighting )

TPN DB with 3 phase incoming , 3 phase outgoings , phase


segregated
INCOMING:- 1 No 40 A 4P MCB Isolator

3 Nos 40 Amps DP MCBs D- Curve ( 10 kA )

OUTGOINGS:-
6 Amps/10 Amps/16 Amps D Curve SP MCBs -12 Nos

Taj Gateway Hotel at Chennai Page- 26 of 62


Taj Gateway Hotel at Chennai
SL.No Item Description Unit
Qty PRICE Amount

SUPPLY Set 0.00 0.00


INSTALLATION Set 0.00 0.00
SUPPLY AND INSTALLATION OF THE FOLLOWING
6.12
SWITCHING DEVICES IN APPROVED ENCLOSURE.

6.13 200Amps 3P+200% N MCCB in metallic enclosure


( UPS incoming Isolator )
SUPPLY Set 1 0.00 0.00
INSTALLATION Set 1 0.00 0.00

6.14 100 Amps 4pole MCCB in metallic enclosure


( Industrial Purpose )
SUPPLY Set 0.00 0.00
INSTALLATION Set 0.00 0.00

SUB TOTAL OF LT DISTRIBUTION BOARDS 0.00


SUPPLY
INSTALLATION

7 HT & LT POWER CABLES

Supply & laying of Power cables 1100 V Grade, Copper or


Aluminium Conductors-multi-strand
construction, of only approved make:Laying rates to include for all
required Cable Clamps,
Identification Tags at required intervals,& other items like cable
ferrules / cable-tags at each
end of the cables laid. For the same Cross Sectional area of Cables,
laying rates shall be the
same whether it is Copper or Aluminium conductor cables, or
whether it is XLPE or PVC
insulation Similarly, laying rates shall be the same for Armoured &
Un-armoured Cables of .

the same Cross section. Cable trays will be measured separately

IS No 7098, Part 1- XLPE Cables


IS No 1554, Part 1, 1988- PVC Cables
IS No 694,1990- PVC Cables.Yellow & Green Striped Single Core
Copper Earthing Continuity
Cables and other Single Core copper Conductor cables

7.1 3 Core 240 Sq mm 11kV XLPE Cables


( From RMG Panel to MASTER BREAKER, MASTER
BREAKER to indoor HT Panel )
SUPPLY RM 0 0.00 0.00
INSTALLATION RM 75 0.00 0.00

7.2 3 Core 185 Sq mm 11kV XLPE Cables


( From HT Panel to Transformer-1 &Transformer-2 )
SUPPLY RM 0 0.00 0.00
INSTALLATION RM 50 0.00 0.00

7.3 3.5 C x 400 sq mm Xlpe Cables, Aluminium, armouured


( From MV Panel toHVAC,APFCR,Raising Main,Fire Fighting
Panel & HVAC Panel to Chiller)
SUPPLY RM 0 0.00 0.00
INSTALLATION RM 500 0.00 0.00

7.4 3.5 C x 300 sq mm Xlpe Cables, Aluminium, armouured


SUPPLY RM 0.00 0.00

Taj Gateway Hotel at Chennai Page- 27 of 62


Taj Gateway Hotel at Chennai
SL.No Item Description Unit
Qty PRICE Amount

INSTALLATION RM 0.00 0.00

7.5 3.5 C x 240 sq mm Xlpe Cables, Aluminium, armouured


( From MV Panel to Sub Power Panel & Power Tap off Box To
Power Panel &etc )
SUPPLY RM 0 0.00 0.00
INSTALLATION RM 200 0.00 0.00

7.6 3.5 C x 185 sq mm Xlpe Cables, Aluminium, armouured


( From HVAC Panel to Ventilation Panel)
SUPPLY RM 0 0.00 0.00
INSTALLATION RM 50 0.00 0.00

7.7 3.5 C x 150 sq mm Xlpe Cables, Aluminium, armouured


( From Main LT Panel to Plumbing Panel ,Fire Fighting Panel to
Fire Hydrant Pump & Sprinkler Pump)
SUPPLY RM 0 0.00 0.00
INSTALLATION RM 500 0.00 0.00

7.8 3.5 C x 120 sq mm Xlpe Cables, Aluminium, armouured


( For General Purpose)
SUPPLY RM 0.00 0.00
INSTALLATION RM 0.00 0.00

7.9 3.5 C x 95 sq mm Xlpe Cables, Aluminium, armouured


( From Lighting Tap off Box 1,2,3,1a,1b,1cTo Sub Lighting Panel )

SUPPLY RM 0 0.00 0.00


INSTALLATION RM 100 0.00 0.00

7.10 3.5 C x 70 sq mm Xlpe Cables, Aluminium, armouured


( From MV Panel to Lift,Laundry Equipment,UPS Panel&
Ventilation Panel to Ventilation Panel-1,FR.EX Panel)
SUPPLY RM 0 0.00 0.00
INSTALLATION RM 400 0.00 0.00

7.11 3.5 C x 50 sq mm Xlpe Cables, Aluminium, armouured


( From Lighting Tap off Box 4,5,4a,4bTo Sub Lighting Panel )
SUPPLY RM 0.00 0.00
INSTALLATION RM 0.00 0.00

7.12 3.5 C x 35 sq mm Xlpe Cables, Aluminium, armouured


SUPPLY RM 0.00 0.00
INSTALLATION RM 0.00 0.00

7.13 4 C x 25 sq mm Xlpe Cables, Aluminium, armouured


( To All Power DB,Lift FDB& Swimming pool
Equipments,Exhaust fans)
SUPPLY RM 0 0.00 0.00
INSTALLATION
..............RM............
1500 0.00 0.00

7.14 4 C x 16 sq mm Xlpe Cables, Aluminium, armouured


( To All Lighting DB )
SUPPLY RM 0 0.00 0.00
INSTALLATION RM 1000 0.00 0.00

7.15 1 C x 1000 sq mm Xlpe Cables, Aluminium, armouured


( FOR DG Neutral Contactor)
SUPPLY RM 0 0.00 0.00
INSTALLATION RM 150 0.00 0.00

Taj Gateway Hotel at Chennai Page- 28 of 62


Taj Gateway Hotel at Chennai
SL.No Item Description Unit
Qty PRICE Amount

7.16 1 C x 50 sq mm Cu Cables, ,Multi stand copper


(for UPS Panel)
SUPPLY RM 0 0.00 0.00
INSTALLATION RM 150 0.00 0.00

7.17 1 C x 16 sq mm Cu Cables, ,Multi stand copper


(From UPS to UPS DB's)
SUPPLY RM 0 0.00 0.00
INSTALLATION RM 3000 0.00 0.00

7.18 1 C x 10 sq mm Cu Cables, ,Multi stand copper


(From UPS to Common Area UPS DB's)
SUPPLY RM 0 0.00 0.00
INSTALLATION RM 5000 0.00 0.00

7.19 4 C x 25 sq mm XLPE/PVC/SWA copper conductor cables


SUPPLY RM 0 0.00 0.00
INSTALLATION RM 1000 0.00 0.00

7.20 4 C x 16 sq mm XLPE/PVC/SWA copper conductor cables


SUPPLY RM 0 0.00 0.00
INSTALLATION RM 200 0.00 0.00

7.21 4 C x 10 sq mm XLPE/PVC/SWA copper conductor cables


SUPPLY RM 0 0.00 0.00
INSTALLATION RM 1000 0.00 0.00

7.22 4 C x 6 sq mm XLPE/PVC/SWA copper conductor cables


(For AHU Units)
SUPPLY RM 0 0.00 0.00
INSTALLATION RM 4500 0.00 0.00

7.23 4 C x 4 sq mm XLPE/PVC/SWA copper conductor cables


(For AHU Units)
SUPPLY RM 0 0.00 0.00
INSTALLATION RM 9500 0.00 0.00

7.24 3 C x 35 sq mm XLPE/PVC/SWA copper conductor cables


SUPPLY RM 0.00 0.00
INSTALLATION RM 0.00 0.00

7.25 3 C x 25 sq mm XLPE/PVC/SWA copper conductor cables


SUPPLY RM 0.00 0.00
INSTALLATION RM 0.00 0.00

7.26 3 C x 16 sq mm XLPE/PVC/SWA copper conductor cables


SUPPLY RM 0.00 0.00
INSTALLATION RM 0.00 0.00

7.27 3 C x 10 sq mm XLPE/PVC/SWA copper conductor cables


SUPPLY RM 0 0.00 0.00
INSTALLATION RM 250 0.00 0.00

7.28 3 C x 6 sq mm XLPE/PVC/SWA copper conductor cables


(For Pumps )
SUPPLY RM 0 0.00 0.00
INSTALLATION RM 500 0.00 0.00

7.29 3 C x 4 sq mm XLPE/PVC/SWA copper conductor cables


(For Pumps )
SUPPLY RM 0 0.00 0.00

Taj Gateway Hotel at Chennai Page- 29 of 62


Taj Gateway Hotel at Chennai
SL.No Item Description Unit
Qty PRICE Amount

INSTALLATION RM 2000 0.00 0.00

7.30 3 C x 2.5 sq mm XLPE/PVC/SWA copper conductor cables


(For Pumps )
SUPPLY RM 0 0.00 0.00
INSTALLATION RM 4500 0.00 0.00

7.31 3 C x 1.5 sq mm XLPE/PVC/SWA copper conductor cables


(For JET FAN & CO sencer )
SUPPLY RM 0.00 0.00
INSTALLATION RM 0.00 0.00

Supply, laying inclusive of cost of conduits etcand termination of


7.32
PVC insluated control cables from
Transformer marshalling box to HT panel, input supply to
marshalling box etc.

(Make:- PRIMECAB or UNIVERSAL or RPG or POLYCAB )

a) 2C x 2.5 sq.m PVC insulated copper control cables including


termination
SUPPLY M 0.00 0.00
Laying in approved manner using GI/MS conduits M 0.00 0.00

b) 3C x 2.5 sq.mm PVC insulated copper control cables


including termination
SUPPLY M 0.00 0.00
Laying in approved manner using GI/MS conduits M 0.00 0.00

c) 4C x 2.5 sq.mm PVC insulated copper control cables


including termination
SUPPLY M 0.00 0.00
Laying in approved manner using GI/MS conduits M 0.00 0.00

d) 2C x 4.0 sq.mm PVC insulated copper control cables


including termination
SUPPLY M 0.00 0.00
Laying in approved manner using GI/MS conduits M 0.00 0.00

e) 4C x 4.0 sq.mm PVC insulated copper control cables


including termination
SUPPLY M 100 0.00 0.00
Laying in approved manner using GI/MS conduits M 100 0.00 0.00

e) 6C x 4.0 sq.mm PVC insulated copper control cables


including termination
SUPPLY M 0 0.00 0.00
Laying in approved manner using GI/MS conduits M 200 0.00 0.00

f) 6C x 2.5 sq.mm PVC insulated copper control cables


including termination
SUPPLY M 0 0.00 0.00
Laying in approved manner using GI/MS conduits M 200 0.00 0.00

g) 7C x 2.5 sq.mm PVC insulated copper control cables


including termination
SUPPLY M 0.00 0.00
Laying in approved manner using GI/MS conduits M 0.00 0.00

h) 12C x 2.5 sq.mm PVC insulated copper control cables


including termination

Taj Gateway Hotel at Chennai Page- 30 of 62


Taj Gateway Hotel at Chennai
SL.No Item Description Unit
Qty PRICE Amount

SUPPLY M 0.00 0.00


Laying in approved manner using GI/MS conduits M 0.00 0.00

i) 16C x 2.5 sq.mm PVC insulated copper control cables


including termination
SUPPLY M 0 0.00 0.00
Laying in approved manner using GI/MS conduits M 200 0.00 0.00

j) 19C x 2.5 sq.mm PVC insulated copper control cables


including termination
SUPPLY M 0.00 0.00
Laying in approved manner using GI/MS conduits M 0.00 0.00
0
k) 24C x 2.5 sq.mm PVC insulated copper control cables
including termination
SUPPLY M 0.00 0.00
Laying in approved manner using GI/MS conduits M 0.00 0.00

k) 30C x 2.5 sq.mm PVC insulated copper control cables


including termination
SUPPLY M 0.00 0.00
Laying in approved manner using GI/MS conduits M 0.00 0.00

CABLE TERMINATIONS

Termination of all the above Cables, using approved type of Copper


cable
Cable sockets of Crimping and /or soldering type,brass double
compression Glands complete with Earth tags or eyed earth
connection
lugs etc. Wherever required, banana type lugs shall be used.

Make Of Glands: Baliga Lighting Or Comet


Make of Lugs/Sockets: Dowells (Biller India Pvt Ltd)
Hex Brass (Copper Alloy India Ltd)

7.33 3 Core 240 Sq mm 11kV XLPE Cables


( From RMG Panel to MASTER BREAKER, MASTER
BREAKER to indoor HT Panel )
SUPPLY SET 4 0.00 0.00
INSTALLATION SET 4 0.00 0.00

7.34 3 Core 185 Sq mm 11kV XLPE Cables


( From HT Panel to Transformer-1 &Transformer-2 )
SUPPLY SET 4 0.00 0.00
INSTALLATION SET 4 0.00 0.00

7.35 3.5 C x 400 sq mm Xlpe Cables, Aluminium, armouured


( From MV Panel toHVAC,APFCR,Raising Main,Fire Fighting
Panel & HVAC Panel to Chiller)
SUPPLY SET 76 0.00 0.00
INSTALLATION SET 76 0.00 0.00

7.36 3.5 C x 300 sq mm Xlpe Cables, Aluminium, armouured


( From MV Panel to Sub Lighting Panel)
SUPPLY SET 0.00 0.00
INSTALLATION SET 0.00 0.00
0
7.37 3.5 C x 240 sq mm Xlpe Cables, Aluminium, armouured
( From MV Panel to Sub Power Panel & Power Tap off Box To
Power Panel &etc )

Taj Gateway Hotel at Chennai Page- 31 of 62


Taj Gateway Hotel at Chennai
SL.No Item Description Unit
Qty PRICE Amount

SUPPLY SET 22 0.00 0.00


INSTALLATION SET 22 0.00 0.00

7.38 3.5 C x 185 sq mm Xlpe Cables, Aluminium, armouured


( From HVAC Panel to Ventilation Panel)
SUPPLY SET 4 0.00 0.00
INSTALLATION SET 4 0.00 0.00

7.39 3.5 C x 150 sq mm Xlpe Cables, Aluminium, armouured


( From Main LT Panel to Plumbing Panel ,Fire Fighting Panel to
Fire Hydrant Pump & Sprinkler Pump)
SUPPLY SET 40 0.00 0.00
INSTALLATION SET 40 0.00 0.00

7.40 3.5 C x 120 sq mm Xlpe Cables, Aluminium, armouured


( For General Purpose)
SUPPLY SET 2 0.00 0.00
INSTALLATION SET 2 0.00 0.00

7.41 3.5 C x 95 sq mm Xlpe Cables, Aluminium, armouured

( From Lighting Tap off Box 1,2,3,1a,1b,1cTo Sub Lighting Panel )

SUPPLY SET 12 0.00 0.00


INSTALLATION SET 12 0.00 0.00

7.42 3.5 C x 70 sq mm Xlpe Cables, Aluminium, armouured


( From MV Panel to Lift,Laundry Equipment,UPS Panel&
Ventilation Panel to Ventilation Panel-1,FR.EX Panel)
SUPPLY SET 12 0.00 0.00
INSTALLATION SET 12 0.00 0.00

7.43 3.5 C x 50 sq mm Xlpe Cables, Aluminium, armouured


( From Lighting Tap off Box 4,5,4a,4bTo Sub Lighting Panel )
SUPPLY SET 50 0.00 0.00
INSTALLATION SET 50 0.00 0.00

7.44 3.5 C x 35 sq mm Xlpe Cables, Aluminium, armouured

SUPPLY SET 50 0.00 0.00


INSTALLATION SET 50 0.00 0.00

7.45 4 C x 25 sq mm Xlpe Cables, Aluminium, armouured


SUPPLY SET 180 0.00 0.00
INSTALLATION SET 180 0.00 0.00

7.46 4 C x 16 sq mm Xlpe Cables, Aluminium, armouured


SUPPLY SET 90 0.00 0.00
INSTALLATION SET 90 0.00 0.00

7.47 1 C x 1000 sq mm Xlpe Cables, Aluminium, armouured


SUPPLY SET 4 0.00 0.00
INSTALLATION SET 4 0.00 0.00

.......7.48.......
1 C x 50 sq mm Cu Cables, ,Multi stand copper
SUPPLY SET 30 0.00 0.00
INSTALLATION SET 30 0.00 0.00

7.49 1 C x 16 sq mm Cu Cables, ,Multi stand copper


SUPPLY SET 10 0.00 0.00
INSTALLATION SET 10 0.00 0.00

Taj Gateway Hotel at Chennai Page- 32 of 62


Taj Gateway Hotel at Chennai
SL.No Item Description Unit
Qty PRICE Amount

7.50 1 C x 10 sq mm Cu Cables, ,Multi stand copper


SUPPLY SET 10 0.00 0.00
INSTALLATION SET 10 0.00 0.00

7.51 4 C x 25 sq mm XLPE/PVC/SWA copper conductor cables


SUPPLY SET 60 0.00 0.00
INSTALLATION SET 60 0.00 0.00

7.52 4 C x 16 sq mm XLPE/PVC/SWA copper conductor cables


SUPPLY SET 10 0.00 0.00
INSTALLATION SET 10 0.00 0.00

.......7.53.......
4 C x 10 sq mm XLPE/PVC/SWA copper conductor cables
SUPPLY SET 30 0.00 0.00
INSTALLATION SET 30 0.00 0.00

7.54 4 C x 6 sq mm XLPE/PVC/SWA copper conductor cables


SUPPLY SET 80 0.00 0.00
INSTALLATION SET 80 0.00 0.00

7.55 4 C x 4 sq mm XLPE/PVC/SWA copper conductor cables


(For AHU Units)
SUPPLY SET 240 0.00 0.00
INSTALLATION SET 240 0.00 0.00
0
7.56 3 C x 35 sq mm XLPE/PVC/SWA copper conductor cables
SUPPLY SET 4 0.00 0.00
INSTALLATION SET 4 0.00 0.00
0
7.57 3 C x 25 sq mm XLPE/PVC/SWA copper conductor cables
SUPPLY SET 2 0.00 0.00
INSTALLATION SET 2 0.00 0.00

7.58 3 C x 16 sq mm XLPE/PVC/SWA copper conductor cables


SUPPLY SET 2 0.00 0.00
INSTALLATION SET 2 0.00 0.00

.......7.59.......
3 C x 10 sq mm XLPE/PVC/SWA copper conductor cables
SUPPLY SET 2 0.00 0.00
INSTALLATION SET 2 0.00 0.00

7.60 3 C x 6 sq mm XLPE/PVC/SWA copper conductor cables


SUPPLY SET 2 0.00 0.00
INSTALLATION SET 2 0.00 0.00

7.61 3 C x 4 sq mm XLPE/PVC/SWA copper conductor cables


SUPPLY SET 40 0.00 0.00
INSTALLATION SET 40 0.00 0.00

7.62 3 C x 2.5 sq mm XLPE/PVC/SWA copper conductor cables

SUPPLY SET 80 0.00 0.00


INSTALLATION SET 80 0.00 0.00

7.63 3 C x 1.5 sq mm XLPE/PVC/SWA copper conductor cables


SUPPLY SET 180 0.00 0.00
INSTALLATION SET 180 0.00 0.00

SUB TOTAL OF HT & LT POWER CABLES 0.00


SUPPLY
INSTALLATION

Taj Gateway Hotel at Chennai Page- 33 of 62


Taj Gateway Hotel at Chennai
SL.No Item Description Unit
Qty PRICE Amount

8 CIRCUIT CUM POINT WIRING

GUEST ROOMS

Wiring from DB to Double Pole MCB in Each Room for


8.1
LIGHTING

Providing and fixing of following PVC insulated copper conductor


1100 volt grade stranded flexible FRLS wire in PVC conduit for
circuit wiring including providing and fixing of conduits concealed
or surface mounted including green colour with yellow band c

Separte conduit shall be taken for each circuit.Separate neutral wire


to be used for each
circuit.

2R 6 Sq mm. and 1R 4 sq mm. PVC FRLS copper wires.


(LIGHTING)

SUPPLY RM 6500 0.00 0.00


INSTALLATION RM 6500 0.00 0.00

Wiring from Double Pole MCB to Energy Saving Unit in Each


8.2
Room for LIGHTING

Providing and fixing of following PVC insulated copper conductor


1100 volt grade stranded flexible FRLS wire in PVC conduit for
circuit wiring including providing and fixing of conduits concealed
or surface mounted including green colour with yellow band c

Separte conduit shall be taken for each circuit.Separate neutral wire


to be used for each .
circuit

2R 6 Sq mm. and 1R 4 sq mm. PVC FRLS copper wires.


(LIGHTING)
SUPPLY RM 600 0.00 0.00
INSTALLATION RM 600 0.00 0.00

Wiring from Energy Saving Unit to Connector Box in Each


8.3
Room for LIGHTING

Providing and fixing of following PVC insulated copper conductor


1100 volt grade stranded flexible FRLSwire in PVC conduit for
circuit wiring including providing and fixing of conduits concealed
or surface mounted including green colour with yellow band co

Separte conduit shall be taken for each circuit.Separate neutral wire


to be used for each .
circuit

2R 6 Sq mm. and 1R 4 sq mm. PVC FRLS copper wires.


(LIGHTING)

SUPPLY RM 600 0.00 0.00


INSTALLATION RM 600 0.00 0.00

Taj Gateway Hotel at Chennai Page- 34 of 62


Taj Gateway Hotel at Chennai
SL.No Item Description Unit
Qty PRICE Amount

Design , Fabrication ,Supply, Installation , Testing and


commissioning of connector box with 4 Nos 20 x 3 mm Thic
8.4 copper bus bar including providing 1 no. of 16/20A DP MCB
Isolator in suitable size of 16 gauge power coated shee steel
enclosure ( All as pe

SUPPLY SET 192 0.00 0.00


INSTALLATION SET 192 0.00 0.00

8.5 Wiring from DB to Connector Box in Each Room for POWER

Providing and fixing of following PVC insulated copper conductor


1100 volt grade stranded flexible FRLS wire in PVC conduit for
circuit wiring including providing and fixing of conduits concealed
or surface mounted including green colour with yellow band c

Separte conduit shall be taken for each circuit.Separate neutral wire


to be used for each .
circuit

2R 10 Sq mm. and 1R 6 sq mm. PVC FRLS copper wires.


(POWER)

SUPPLY RM 4000 0.00 0.00


INSTALLATION RM 4000 0.00 0.00

Wiring from Connector Box to Each Room for Power and


8.6
Lighting

Providing and fixing of following PVC insulated copper conductor


1100 volt grade stranded flexible FRLS wire in PVC conduit for
circuit wiring including providing and fixing of conduits concealed
or surface mounted including green colour with yellow band c

Separte conduit shall be taken for each circuit.Separate neutral wire


to be used for each .
circuit

3R 4 Sq mm. PVC FRLS copper wires.

SUPPLY RM 10000 0.00 0.00


INSTALLATION RM 10000 0.00 0.00

3R 2.5 Sq mm. PVC FRLS copper wires.

SUPPLY RM 1000 0.00 0.00


INSTALLATION RM 1000 0.00 0.00

POWER SOCKET (GUESTROOM)

Supply, installation, Testing and commissioning6Amps Switched


Socket combined in Manufacturer's MS mounting box fixed flush
8.7
with the wall/ partitions with necessary accessories in etc. ( wiring
with 3 No 2.5 sqmm FRLS Cu Wires in Conduits already included

SUPPLY Set 0.00 0.00


INSTALLATION Set 0.00 0.00

Taj Gateway Hotel at Chennai Page- 35 of 62


Taj Gateway Hotel at Chennai
SL.No Item Description Unit
Qty PRICE Amount

Supply, installation, Testing and commissioning6Amps Twin


Switched Socket combined in Manufacturer's MS mounting box
8.8
fixed flush with the wall/ partitions with necessary accessories in
etc.
( wiring with 3 No 2.5 sqmm FRLS Cu Wires in Conduits already
included in Power and Lighting circuit wiring )
SUPPLY Set 0.00 0.00
INSTALLATION Set 0.00 0.00

Supply, installation, Testing and commissioning6Amps Switched


Socket combined in Manufacturer's MS mounting box fixed on
8.9 above false celling / partitions with necessary accessories in etc.
(for FCU 's) ( wiring with 3 No 2.5 sqmm FRLS Cu Wires in
Conduits
SUPPLY Set 0.00 0.00
INSTALLATION Set 0.00 0.00

Supply, installation, Testing and commissioning13Amps Twin


Universal Switched Socket combined in Manufacturer's MS
8.10
mounting box fixed flush with the wall/ partitions with necessary
accessories in etc.
SUPPLY Set 0.00 0.00
INSTALLATION Set 0.00 0.00

Supply, installation, Testing and commissioning6/16 Amps


Switched Socket combined in Manufacturer's MS mounting box
8.11 fixed flush with the wall/ partitions with necessary accessories in
etc. ( wiring with 3 No 4 sqmm FRLS Cu Wires in Conduits
already includ
SUPPLY Set 0 0.00 0.00
INSTALLATION Set 0 0.00 0.00

Supply, installation, Testing and commissioning6/16 Amps Twin


Switched Socket combined in Manufacturer's MS mounting box
8.12 fixed flush with the wall/ partitions with necessary accessories in
etc.( wiring with 3 No 4 sqmm FRLS Cu Wires in Conduits already
in

SUPPLY Set 0.00 0.00


INSTALLATION Set 0.00 0.00

Supply and installation of ApprovedShaver Socket outlet suitable


for 115 / 120 Volts output from 220 / 240 Volts 50cycles A.C.
8.13
Supply looped from Primary socket points above, The shaver
socket shall accept round or flat plug top. The unit shall be switche

SUPPLY Set 0 0.00 0.00


INSTALLATION Set 0 0.00 0.00

Supply, Erecting, connecting and commissioning ofData Socket &


basebaox with all necessary interconnectionsand other standard
8.14
accessories also in etc.approval to be obtained from Data
Vender.
SUPPLY Set 768 0.00 0.00
INSTALLATION Set 768 0.00 0.00

Supply, Erecting, connecting and commissioning ofTelephone


socket & basebaox with necessary interconnectionsand other
8.15
standard accessories also in etc.approval to be obtained from
Voice Vender.

Taj Gateway Hotel at Chennai Page- 36 of 62


Taj Gateway Hotel at Chennai
SL.No Item Description Unit
Qty PRICE Amount

SUPPLY Set 576 0.00 0.00


INSTALLATION Set 576 0.00 0.00

Supply, Erecting, connecting and commissioning of TV socket &


basebox with necessary interconnectionsand other standard
8.16
accessories also in etc.approval to be obtained from Voice
Vender.
SUPPLY Set 192 0.00 0.00
INSTALLATION Set 192 0.00 0.00

8.17 LIGHT POINTS

Wiring for the following light points with 2.5 sq.mm PVC
insulated copper conductor 1100 volts grade stranded flexible
FRLS wires of approved make in concealed or surface mounted 25
mm dia PVC conduit including providing and fixing of 6 amps sing

8.18 One light controlled by one 10 Amps SP switch


SUPPLY Set 1750 0.00 0.00

Against Conduit Supply


Against Wire Supply
Against Backbox Supply
Against Switch Supply

INSTALLATION Set 1750 0.00 0.00

Against Conduiting
Against Wiring
Against Backbox Installation
Against Switch Installation

8.19 Two lights controlled byone 10 Amps SP switch


SUPPLY Set 194 0.00 0.00

Against Conduit Supply


Against Wire Supply
Against Backbox Supply
Against Switch Supply

INSTALLATION Set 194 0.00 0.00

Against Conduiting
Against Wiring
Against Backbox Installation
Against Switch Installation

Same as Above item no 8.18 but it is for Additional Light points


8.20
The maximum length willbe 6.0Mts. for each additional point

SUPPLY Set 750 0.00 0.00

Against Conduit Supply


Against Wire Supply

INSTALLATION Set 750 0.00 0.00

Against Conduiting

Taj Gateway Hotel at Chennai Page- 37 of 62


Taj Gateway Hotel at Chennai
SL.No Item Description Unit
Qty PRICE Amount

Against Wiring

One lights controlled by Micro Switch with necessary


8.21
interconnections and other standard accessories
etc approval to be obtained from Architect(.including Micro
Switch )
SUPPLY Set 388 0.00 0.00
INSTALLATION Set 388 0.00 0.00

Wiring for the twin control light points with 2.5 sq. mm PVC
insulated copper conductor 1100 volts grad stranded flexible
8.22 FRLS wires in concealed or surface mounted 25 mm dia PVC
conduit including providing and fixing 2 Nos.6 amps 2 way rocker
opera

8.23 One light points controlled by 2 Nos 10 Amps Two way switches

SUPPLY Set 0.00 0.00


INSTALLATION Set 0.00 0.00

8.24 Two light points controlled by 2 Nos 10 AmpsTwo way switches

SUPPLY Set 384 0.00 0.00


INSTALLATION Set 384 0.00 0.00

SUB TOTAL OF CIRCUIT CUM POINT WIRING 0.00


SUPPLY
INSTALLATION

9 LIGHT FIXTURES (GUESTROOM SIDE)

Erecting, connecting and commissioning ofTable Lamp Light


9.1
Fitting with necessary
interconnections andother standard accessories including Fixing of
lamp also in etc.

INSTALLATION Set 450 0.00 0.00

Erecting, connecting and commissioning ofHalogen Light Fitting


9.2
with necessary
interconnectionsand other standard accessories including Fixing of
lamp also in etc.

INSTALLATION Set 225 0.00 0.00

Erecting, connecting and commissioning ofCFL Light Fitting with


9.3
necessary interconnectionsand
other standard accessories including Fixing of lamp also in etc.

INSTALLATION Set 800 0.00 0.00

Erecting, connecting and commissioning ofMirror Light Fitting


9.4
with necessary
interconnectionsand other standard accessories including Fixing of
lamp salso in etc.

INSTALLATION Set 450 0.00 0.00

Erecting, connecting and commissioning ofTV Lamp Light


9.5
Fitting with necessary

Taj Gateway Hotel at Chennai Page- 38 of 62


Taj Gateway Hotel at Chennai
SL.No Item Description Unit
Qty PRICE Amount

interconnectionsand other standard accessories including Fixing of


lamp salso in etc.

INSTALLATION Set 225 0.00 0.00

Erecting, connecting and commissioning ofHidden Wadrode


9.6
Light Fitting with necessary
interconnectionsand other standard accessories including Fixing of
lamp salso in etc.

INSTALLATION Set 450 0.00 0.00

Erecting, connecting and commissioning ofPendent Light Fitting


9.7
with necessary
interconnectionsandother standard accessories including Fixing of
lamp also in etc.

INSTALLATION Set 225 0.00 0.00

Erecting, connecting and commissioning ofNight Lamp Light


9.8
Fitting with necessary
interconnectionsand other standard accessories including Fixing of
lamp also in etc.

INSTALLATION Set 194 0.00 0.00

Supply, Erecting, connecting and commissioning of CALL Bell


9.9
Switch with necessary
interconnectionsand other standard accessories including lamp also
in etca.pproval to be
obtained from Architect.
SUPPLY Set 0 0.00 0.00
INSTALLATION Set 0 0.00 0.00

Erecting, connecting and commissioning ofMicro Lamp Light


9.10
Fitting with necessary
interconnectionsand other standard accessories including Fixing of
lamp also in etc.

INSTALLATION Set 388 0.00 0.00

Wiring ,Supply and installation of I Minute OFF Time Delay Key


Tag Operated Energy saving Switch Unit of approved make and
9.11
type with metal box housing& other wiring outlet accessories,
wiring from energy saving unit

SUPPLY&INSTALLATION Set 0 0.00 0.00

Wiring ,Supply and installation of I Minute OFF Time Delay Key


9.12 Tag approved make and type with metal box housing& other wiring
outlet accessories,

INSTALLATION Set 0 0.00 0.00

Wiring ,Supply and installation of Cat 5E Cable Energy saving


9.13 Switch Unit to Key Tag approved make with in suitable PVC
Conduit to be included.
SUPPLY mtr 0 0.00 0.00
INSTALLATION mtr 0 0.00 0.00

Taj Gateway Hotel at Chennai Page- 39 of 62


Taj Gateway Hotel at Chennai
SL.No Item Description Unit
Qty PRICE Amount

SUB TOTAL OF LIGHT FIXTURES (GUESTROOM SIDE) 0.00

SUPPLY
INSTALLATION

10 COMMON AREAS & PUBLIC AREAS

UPS WIRING

3Runs of 2.5 sqmm Cu FRLS in the floor, wall and false flooring
for UPS DB to UPS Socket in suitable PVC conduit in etc.

SUPPLY RM 200 0.00 0.00


INSTALLATION RM 200 0.00 0.00

3Runs of 4 sqmm Cu FRLS in the floor, wall and false flooring for
UPS DB to UPS Socket in suitable PVC conduit in etc.

SUPPLY RM 0.00 0.00


INSTALLATION RM 0.00 0.00

CIRCUIT WIRING- Lighting / Miscellaneous,From Final DB


to the First Point in Any Circuit

Wiring for circuit wiring from the Final DB to the first point of the
circuit in
recessed / surface PVC conduit using only approved make fire
retardant 2 mm
wall thickness heavy duty conduits incorporating approved make
requried
accessories like bends collars, junction boxes,-all as required,using
only approved make
and type of FRLS multi-strand Copper conductor wires.
Installation on roof slab shall be carried -out using purpose made
GI saddles fixed at not
less than 450mm C/C.
Conduiting above false ceiling shall be fastend between GI
cable
rungs suspended on hitech rods at <= 750 mm c/c spacing.

Elbows, Unions,Fanhooks& Fanboxes,complete with


Fasters, Galvanised MS Boxes,Junction Boxes, pull boxes,
at regular intervals,Fish wire (Pull wire), Fill-plugs & Wooden
blocks and anchor
bolts as required,all required Civil Works like Cutting & chasing as
well as making
good of all cuttings & Chases .

3 runs of 2.5 Sq mm copper wires FRLS, in Suitable PVC


10.1
conduit
Circuit wiring for Lights from FDB to Switch box in each circuit
and
Wiring from Car Parking and Corridors.
SUPPLY RM 0.00 0.00
INSTALLATION RM 0.00 0.00

Circuit wiring from FDB to First light point will be measured


as per Item No 10.1
Measurement of the following points will be from Switch to
lights in the circuit

Taj Gateway Hotel at Chennai Page- 40 of 62


Taj Gateway Hotel at Chennai
SL.No Item Description Unit
Qty PRICE Amount

to the next looped light point , and threrafter,


sequentially(ASSUMPTION)

10.2 Main Point by one 10 Amp SP switch


SUPPLY Point 50 0.00 0.00
INSTALLATION Point 50 0.00 0.00

10.2 Additional points by one 6 Amp SP switch


SUPPLY Point 50 0.00 0.00

Against Conduit Supply


Against Wire Supply
Against Backbox Supply
Against Switch Supply

INSTALLATION Point 50 0.00 0.00

Against Conduiting
Against Wiring
Against Backbox Installation
Against Switch Installation

10.3 Main Point by one 6 Amp Decorative SP switch


SUPPLY Point 50 0.00 0.00
INSTALLATION Point 50 0.00 0.00

10.4 Additional points by one 6 Amp Decorative SP switch


SUPPLY Point 50 0.00 0.00
INSTALLATION Point 50 0.00 0.00

10.5 One light points controlled by 2 Nos 10 Amps Two way switches

SUPPLY Point 0.00 0.00


INSTALLATION Point 0.00 0.00

10.6 Two light points controlled by 2 Nos 10 AmpsTwo way switches

SUPPLY Point 0.00 0.00


INSTALLATION Point 0.00 0.00

10.7 Six points controlled by one MCB.


SUPPLY Pts. 30 0.00 0.00
INSTALLATION Pts. 30 0.00 0.00

10.8 Seven points controlled by one MCB.


SUPPLY Pts. 5 0.00 0.00
INSTALLATION Pts. 5 0.00 0.00
0
10.9 Eight points controlled by one MCB.
SUPPLY Pts. 5 0.00 0.00
INSTALLATION Pts. 5 0.00 0.00

10.10 Nine points controlled by one MCB.


SUPPLY Pts. 0 0.00 0.00
INSTALLATION Pts. 0 0.00 0.00

10.11 Ten points controlled by one MCB.


SUPPLY Pts. 0 0.00 0.00
INSTALLATION Pts. 0 0.00 0.00

10.12 Eleven points controlled by one MCB.

Taj Gateway Hotel at Chennai Page- 41 of 62


Taj Gateway Hotel at Chennai
SL.No Item Description Unit
Qty PRICE Amount

SUPPLY Pts. 0 0.00 0.00


INSTALLATION Pts. 0 0.00 0.00

10.13 Twelve points controlled by one MCB.


SUPPLY Pts. 0 0.00 0.00
INSTALLATION Pts. 0 0.00 0.00

10.14 Theteen points controlled by one MCB.


SUPPLY Pts. 0 0.00 0.00
INSTALLATION Pts. 0 0.00 0.00

10.15 Fourteen points controlled by one MCB.


SUPPLY Pts. 0.00 0.00
INSTALLATION Pts. 0.00 0.00

10.16 Fifteen points controlled by one MCB.


SUPPLY Pts. 0.00 0.00
INSTALLATION Pts. 0.00 0.00

10.17 Sixteen points controlled by one MCB.


SUPPLY Pts. 0.00 0.00
INSTALLATION Pts. 0.00 0.00

10.18 Seventeen points controlled by one MCB.


SUPPLY Pts. 0.00 0.00
INSTALLATION Pts. 0.00 0.00

SUB TOTAL OF COMMON AREAS & PUBLIC AREAS 0.00


LIGHT FITTINGS & FIXTURES (OFFICE & COMMON
11
AREAS )

Supply and instalation of the following light fixtures complete with


reflectors,
lamps,ballasts, louvers, transformers,fixing accessories etc as
required.

All FTL & CFL Fittings with Electrical Non Dimmable Chokes

11.1 3x36W CFL CEILING RECESSED CAT-2 Glare Free Type


( FOR OFFICE AREA LIGHTING )
INSTALLATION No 0.00 0.00

2x36W CFL ( 2f X 2 f ) CEILING RECESSED CAT-2 Glare Free


11.2
Type
( FOR OFFICE AREA LIGHTING )
INSTALLATION No 0.00 0.00

11.3 1x18W CFL CEILING RECESSED Down Lighter


(Public areas, False Ceiling Areas)
INSTALLATION No 0.00 0.00

11.4 2x26W CFL CEILING RECESSED Down Lighter


(Public areas, False Ceiling Areas)
INSTALLATION No 0.00 0.00

11.5 1x9W CFL BULK HEAD- SURFACE MOUNTED


( Switch & light Located above ceiling in guest rooms )
INSTALLATION No 240 0.00 0.00

11.60 1x11W CFL BULK HEAD- SURFACE MOUNTED

Taj Gateway Hotel at Chennai Page- 42 of 62


Taj Gateway Hotel at Chennai
SL.No Item Description Unit
Qty PRICE Amount

( Switch & light Located above ceiling in guest rooms )


INSTALLATION No 40 0.00 0.00

11.70 1x70W METAL HALIDE SURFACE MOUNTED Down Lighter

(Public areas, False Ceiling Areas)


INSTALLATION No 0.00 0.00

11.80 1x18W CFL CEILING RECESSED Down Lighter


(Public areas, False Ceiling Areas)
INSTALLATION No 100 0.00 0.00

11.90 1x13W CFL surface mounted Down Lighter


(Public areas, False Ceiling Areas)
INSTALLATION No 0.00 0.00

11.10 12V : 50W Recessed Halogen Spots


(Public areas, False Ceiling Areas)
INSTALLATION No 250 0.00 0.00

2x28W FTL-INDUSTRIAL TYPE, (TMS) SURFACE


11.11
MOUNTED
(Basement , Plant Rooms)
INSTALLATION No 443 0.00 0.00

11.12 1x36W FTL - BOX TYPE (TMC) ,SURFACE MOUNTED


INSTALLATION No 250 0.00 0.00

1x36W FTL - REGULAR FLURECENT TUBE LIGHT,(Strip


11.13
Lights)SURFACE MOUNTED
(Non-False Ceiling passages, corridors, Cove lighting)
INSTALLATION No 155 0.00 0.00

1x36W FTL - STOVE ENAMELED TYPE , BOX TYPE


11.14
,SURFACE MOUNTED
( WITH POLYLAC COVERGUARD TYPE 4 FEET FLURECENT
LAMP )
(Kitchen)
INSTALLATION No 95 0.00 0.00

11.15 2x36W FTL - BOX TYPE (TMC) ,SURFACE MOUNTED


(Non-False Ceiling passages, corridors)
INSTALLATION No 150 0.00 0.00

11.16 1x13W CFL - DECORATIVE ,WALL MOUNTED


(In Guest roms , Public areas )
INSTALLATION No 0.00 0.00

11.17 1x36W FTL - MIRROR TOP ,SURFACE MOUNTED


(Toilet-Mirror-top pelmets)
INSTALLATION No 0.00 0.00

11.18 1 X 8W NI-CAD BACK-UP EMERGENCY EXIT LIGHTS


( Exit points Signages)
INSTALLATION No 25 0.00 0.00

Cafeteria drop Lights, for suspension at 9ft from Finished Floor


11.19
Level,
Coplete with Durable Cable for Suspension,14- 16 inches dia
Metallic dome,
Suitable for 2 nos 18 W CFL Lamps

Taj Gateway Hotel at Chennai Page- 43 of 62


Taj Gateway Hotel at Chennai
SL.No Item Description Unit
Qty PRICE Amount

(Staff cafeteria, Roof Top Restaurant-if any)


INSTALLATION No 0.00 0.00

11.20 1x 9 W CFL Step lights, recessed in Steps


INSTALLATION No 0.00 0.00

11.21 Pole Top or wall - Monted 70 W to 250 W MH / HPSV Lights

INSTALLATION No 0.00 0.00

Decorative 3 m high MS powder-coated pole Kasselec / K-Lite or


11.22
equivalent Pole
complete with integral W/P Moulded Hensel / els Spelberg Jn box
housing 10 Way
16 amps Elmex DIN channel mounted Terminal.Block
INSTALLATION Set 0.00 0.00

1x80W HPMV GATE LIGHTS, complete with cable-intake GI


11.23
Pipe of Adequqte diameter
INSTALLATION No 20 0.00 0.00

1x18W CFL Bollard LAND SCAPE LIGHTS with necessary


11.24
weather proof junction boxes, GI brackets, interconnections, etc.,

INSTALLATION No 200 0.00 0.00

11.25 24 Volts1x50 W underwater LAND SCAPE LIGHTS,


complete with Step-down transformer Unit
INSTALLATION No 20 0.00 0.00

11.26 IP 65 category 2x400w FLOOD LIGHTS METAL HALIDE,


complete with tiltable hinged mounting arrangement
INSTALLATION No 0.00 0.00

Aviation warning Light,Bajaj BJAOL-1 (double arm- with 100 W


11.27
GLS Lamps)
( Power supply from Inverter FDB )
INSTALLATION No 2 0.00 0.00

11.28 Cold cathode lights, imported type, of various Colours


recessed in Coves, in public areas, Lobbies, Coffe Shop,
Restaurants etc ;
Complete with all necessary Accessories like Dimmable Electronic
transformers
and such other items
INSTALLATION Set 0.00 0.00

Strip type LED Chain lights ( Of chosen colours ) complete with


11.29
step down transformers ,
SCR rectifier unit etc complete ,operating on DC low voltage
embedded in
prominent areas under floor, along lift cage architraves, coves
reception area counters Etc,
embedded / installed as directed at site
Set of 2 M long LED Lights
INSTALLATION Set 0.00 0.00

Taj Gateway Hotel at Chennai Page- 44 of 62


Taj Gateway Hotel at Chennai
SL.No Item Description Unit
Qty PRICE Amount

XENON Flexi Strip Chain lights of chosen colours operating on


11.30
AC low voltage
embedded in prominent areas under floor, along lift cage
architraves,
reception area counters Etc, embedded as directed at site

Set of 2 M long XENON Lights


INSTALLATION Set 0.00 0.00

11.31 Aircraft warning lights with Photosenser cell for and dawn control.

INSTALLATION Point 0.00 0.00

Supply,Erecting, connecting and commissioning of land scaping


11.32
Light Fitting with
necessary weather proof junction boxes, GI brackets,
interconnections, etc.,

INSTALLATION Nos. 150 0.00 0.00

11.33 Ceiling Fan Points


Wired by looping from lighting points, complete with Stepped,
hum-free Electronic regulator
Of Modular plate type and modular plate Switch
SUPPLY Point 0.00 0.00
INSTALLATION Point 0.00 0.00

11.34 Exhaust Fan Points

Wired as dependent point, looped from light point wiring,with 3R


x2.5 Sqmm FRLS Wires
in 19 mm MS Conduits,Using Modular plate type 3 Pin 6 amps
switched Socket Outlet near
the fan
SUPPLY Point 4 0.00 0.00
INSTALLATION Point 4 0.00 0.00

11.35 Auto flush sensor points

Wired as dependent point, looped from ligt point wiring,with 3R


x2.5 Sqmm FRLS Wires in 19 mm MS Conduits, with provision of
necessary Terminal Connector in recessed Branded Box above the
Gents' Urinal Cisterns
SUPPLY Point 15 0.00 0.00
INSTALLATION Point 15 0.00 0.00

SUB TOTAL OF LIGHT FITTINGS & FIXTURES (OFFICE


0.00
& COMMON AREAS )
SUPPLY
INSTALLATION

12 POWER CIRCUIT WIRING

Circuit wiring for RAW POWER/GEYSER/HAND DRYER using


multi-strand PVC FR copper conductor wires in ms conduit for
circuit wiring including providing fixing of conduits and above
false ceiling or along columns walls and interior partitions.

Taj Gateway Hotel at Chennai Page- 45 of 62


Taj Gateway Hotel at Chennai
SL.No Item Description Unit
Qty PRICE Amount

Separte conduit shall be taken for each circuit.Separate neutral wire


to be used for each circuit.

2 Nos 4 Sq mm + 1 No 2.5 sq mm FRLS copper wires in 25 mm


dia conduit(6/16amps socket)

SUPPLY RM 500 0.00 0.00


INSTALLATION RM 500 0.00 0.00

3 Nos 2.5 Sq mm FRLS copper wires in 25 mm dia conduit(6Amps


socket)

SUPPLY RM 500 0.00 0.00


INSTALLATION RM 500 0.00 0.00

Supply and installation of 1 No 6 Amp / 16 Amp 5-pin Switched


Socket outlet, located separately,free from looping from other
12.1
socket including supply and fixing of outlet boxes with necessary
accessories etc.
SUPPLY Sets 150 0.00 0.00
INSTALLATION Sets 150 0.00 0.00

Supply and installation of 1 No 6 Amp / 16 Amp Water Proof 5-


pin Switched Socket outlet, located separately,free from looping
12.2
from other socket including supply and fixing of outlet boxes with
necessary accessories etc.
SUPPLY Sets 10 0.00 0.00
INSTALLATION Sets 10 0.00 0.00

Supply and installation of 1 No 6 Amp 5-pin Switched Socket


outlet, located separately,free from looping from other socket
12.3
including supply and fixing of outlet boxes with necessary
accessories etc.
SUPPLY Sets 125 0.00 0.00
INSTALLATION Sets 125 0.00 0.00

Supply and installation of 1 No 6 Amp 5-pin Socket outlet,


12.4 located separately,free from looping from other socke including
supply and fixing of outlet boxes with necessary accessories etc.

SUPPLY Sets 100 0.00 0.00


INSTALLATION Sets 100 0.00 0.00

Supply and installation of 1 No 6 Amp 5-pin for WIFI Socket


outlet, located separately,free from looping from other socket
12.5
including supply and fixing of outlet boxes with necessary
accessories etc.
SUPPLY Sets 10 0.00 0.00
INSTALLATION Sets 10 0.00 0.00

Supply and installation of Telephone socket & basebaox with


12.6 necessary interconnectionsand other standard accessories also in
etc. approval to be obtained from Voice Vender.
SUPPLY Sets 30 0.00 0.00
INSTALLATION Sets 30 0.00 0.00

Supply and installation of TV socket & basebox with necessary


12.7 interconnectionsand other standard accessories also in etc.
approval to be obtained from Voice Vender.
SUPPLY Sets 30 0.00 0.00
INSTALLATION Sets 30 0.00 0.00

Taj Gateway Hotel at Chennai Page- 46 of 62


Taj Gateway Hotel at Chennai
SL.No Item Description Unit
Qty PRICE Amount

SUB TOTAL OF POWER CIRCUIT WIRING 0.00


SUPPLY
INSTALLATION

13 METTALLIC & PVC HOSE

Supplying and fiixng 20mm dia PVC Flexible hose gland with
check nuts.

INSTALLATION Mtrs 4000 0.00 0.00

Supplying and laying 25mm dia PVC Flexible hose gland with
check nuts.

INSTALLATION Mtrs 500 0.00 0.00

Supplying and laying 32 dia PVC Flexible hose gland with check
nuts.

INSTALLATION Mtrs 400 0.00 0.00

Supplying and fiixng 20mm dia metallic Flexible hose gland with
check nuts.

INSTALLATION Mtrs 0 0.00 0.00

Supplying and laying 25mm dia metallic Flexible hose gland with
check nuts.

INSTALLATION Mtrs 0 0.00 0.00

SUB TOTAL OF METTALLIC & PVC HOSE 0.00

FLOOR RACEWAYS, GI JUNCTION BOXES & CABLE


14
TRAYS

Supply and erection of 14SWG Thick GI Raceways, AS PER


APPROVED SAMPLE,(under floor multi-compartmetalised cable
managemnet system ) of following sizes.The rates for fixing in
floor shall be inclusive of all necessary Civil Works like Cutting &
Making Goo

14.1 300 mm x 38 mm Race ways Single Compartment


SUPPLY RM 0.00 0.00
INSTALLATION RM 0.00 0.00

14.2 225 mm x 38 mm Race ways Single Compartment


SUPPLY RM 3000 0.00 0.00
INSTALLATION RM 3000 0.00 0.00

14.3 150 mm x 38 mm Race ways Single Compartment


SUPPLY RM 0.00 0.00
INSTALLATION RM 0.00 0.00

Supply and installation of ELECTRO GALVANISED Conduits


complete with all fittings and
accessories as required. The installation rates shall include for all
breaking ,cutting &

Taj Gateway Hotel at Chennai Page- 47 of 62


Taj Gateway Hotel at Chennai
SL.No Item Description Unit
Qty PRICE Amount

chasing,and making good, provision of sutable junction boxes as


needed etc-complete in all
respects

14.4 19 mm dia
SUPPLY RM 100 0.00 0.00
ERECTION including cutting chasing,and making good, etc . RM 100 0.00 0.00

14.5 25 mm dia
SUPPLY RM 80 0.00 0.00
ERECTION including cutting chasing,and making good, etc . RM 80 0.00 0.00

14.6 32 mm dia
SUPPLY RM 25 0.00 0.00
ERECTION including cutting chasing,and making good, etc . RM 25 0.00 0.00

100 mmDia Heavy duty UPVC Ducts with collars, Unions, spigots
14.7
& all accessories

SUPPLY RM 100 0.00 0.00


Installation in ground, including excavation, concrete benching of
duct, backfilling and restoring the
excavated surface back to good condition RM 50 0.00 0.00

Installation in ground, including cutting & chasing and restoring


RM 50 0.00 0.00
the surface back to good condition

75 mm Dia Heavy duty UPVC Ducts with collars, Unions, spigots


14.8
& all accessories
SUPPLY RM 80 0.00 0.00
Installation in ground, including excavation, concrete benching of
duct, backfilling
and restoring the excavated surface back to good condition RM 50 0.00 0.00

Installation in ground, including cutting & chasing and restoring


RM 30 0.00 0.00
the surface
back to good condition

50 mm Dia Heavy duty UPVC Ducts with collars, Unions, spigots


14.9
& all accessories
SUPPLY RM 60 0.00 0.00
Installation in ground, including excavation, concrete benching of
duct, backfilling and restoring the
excavated surface back to good condition RM 30 0.00 0.00

Installation in ground, including cutting & chasing and restoring


RM 30 0.00 0.00
the surface
back to good condition

14.10 DIMMERS, DIMMABLE CHOKES ETC.

0 - 10 V, 1 x 28W FTL Electronic Dimmable Ballasts Of Helvar or


a
Tridonic or Thorn orequivalent make

SUPPLY No 50 0.00 0.00


INSTALLATION No 50 0.00 0.00

0 - 10 V, 1 x 36W FTL Electronic Dimmable Ballasts Of Helvar or


b
Tridonic or Thorn orequivalent make

SUPPLY No 5 0.00 0.00

Taj Gateway Hotel at Chennai Page- 48 of 62


Taj Gateway Hotel at Chennai
SL.No Item Description Unit
Qty PRICE Amount

INSTALLATION No 5 0.00 0.00

0 - 10 V, 1 x 18W CFL Electronic Dimmable Ballasts Of Helvar or


c
Tridonic or Thorn orequivalent make

SUPPLY No 100 0.00 0.00


INSTALLATION No 100 0.00 0.00

0 - 10 V, 2 x 36W CFL Electronic Dimmable Ballasts Of Helvar or


d
Tridonic or Thorn orequivalent make

SUPPLY No 5 0.00 0.00


INSTALLATION No 5 0.00 0.00

0 - 10 V, 2 x 26W CFL Electronic Dimmable Ballasts Of Helvar or


e
Tridonic or Thorn orequivalent make

SUPPLY No 70 0.00 0.00


INSTALLATION No 70 0.00 0.00

0 - 10 V, 2 x 28W CFL Electronic Dimmable Ballasts Of Helvar or


f
Tridonic or Thorn orequivalent make

SUPPLY No 100 0.00 0.00


INSTALLATION No 100 0.00 0.00

0 - 10 V, 2 x 18W CFL Electronic Dimmable Ballasts Of Helvar or


g
Tridonic or Thorn orequivalent make

SUPPLY No 50 0.00 0.00


INSTALLATION No 50 0.00 0.00

Dimmer unit -12 Channel of Helvar / Tridonic/ Thorn or


Equivalent, complete withBallast controllers,Digidiminput
h
modules, 7 button module & modifiers, and Infra-red Remote
control unit

SUPPLY Set 3 0.00 0.00


INSTALLATION Set 3 0.00 0.00

SUB TOTAL OF CONDUITS AND PIPES FOR


0.00
MISCELLANEOUS WORKS

FLOOR RACEWAYS, GI JUNCTION BOXES & CABLE


15
TRAYS

Supply and erection of 14SWG Thick GI Raceways, AS PER


APPROVED SAMPLE,(under floor multi-compartmetalised cable
managemnet system ) of following sizes.The rates for fixing in
floor shall be inclusive of all necessary Civil Works like Cutting &
Making Goo

15.1 300 mm x 38 mm Race ways Single Compartment


SUPPLY RM 0.00 0.00
INSTALLATION RM 0.00 0.00

Taj Gateway Hotel at Chennai Page- 49 of 62


Taj Gateway Hotel at Chennai
SL.No Item Description Unit
Qty PRICE Amount

152 225 mm x 38 mm Race ways Single Compartment


SUPPLY RM 200 0.00 0.00
INSTALLATION RM 200 0.00 0.00

152 150 mm x 38 mm Race ways Single Compartment


SUPPLY RM 300 0.00 0.00
INSTALLATION RM 300 0.00 0.00

Fabricated Floor junction boxes of GI to suit the above raceway


15.3
without any
Outlets--Mounting Frames-As per prior sample approval
(For floor-mounting at Cross-over Junctions and near the
partitions)
SUPPLY No 10 0.00 0.00
INSTALLATION No 10 0.00 0.00

GI Ladder Type Cable Trays with rungs at 300 mm C/C ,made out
of Galvanized Iron, of required mechanical strength, to be installed
in approved manner, with grip bolts and anchor bolts- as fasteners,
rigid GI angle-iron supports fixed at 600 mm C / C.The t

SUBTOTAL OF 0.00
FLOOR RACEWAYS, GI JUNCTION BOXES & CABLE
TRAYS
SUPPLY
INSTALLATION

Supply,installation and LAN configuration LAYER-3, 24 port


16.1
10/100 Mbps,manageable core switchMAKE:Molex
SUPPLY Each 0.00 0.00
INSTALLATION Each 0.00 0.00

Supply,installation,and LAN configuration of LAYER-2 24 port


16.2 10/100 Mbps, edge swithches complete with 2 nos 10/100/1000
base T ports. MAKE: Molex
SUPPLY Each 0.00 0.00
INSTALLATION Each 0.00 0.00

Supply, installation, testing and commissioning of following


Category 5E & 6 , RJ 45 jack panel prepackaged with wiring block
with legs insert labels, label holders, jumper troughs, metal back
panel, duct assembly, screws, washer and an instruction sheet

16.3 24 port jack panel- CAT 5e for voice Make: Molex


SUPPLY Each 0.00 0.00
INSTALLATION Each 0.00 0.00

16 4 24 port jack panel- CAT 6 for Data Make: Molex


SUPPLY Each 0 0.00 0.00
INSTALLATION Each 0 0.00 0.00

Supply and installation of following19 inches racks for ethernet


switches / hubs / jack panels with AC distribution system box,
wire-manager, fan tray with fans, lockable front, tinted glass door
and two pair angle to support the switches / jack panels installd in
racks Make:Molex

16.5 9 U racks
SUPPLY Each 0.00 0.00

Taj Gateway Hotel at Chennai Page- 50 of 62


Taj Gateway Hotel at Chennai
SL.No Item Description Unit
Qty PRICE Amount

INSTALLATION Each 0.00 0.00

16.6 12 U racks
SUPPLY Each 0.00 0.00
INSTALLATION Each 0.00 0.00

16.7 17 U racks
SUPPLY Each 0.00 0.00
INSTALLATION Each 0.00 0.00

16.8 36 U racks
SUPPLY Each 0.00 0.00
INSTALLATION Each 0.00 0.00

Supply, installation, termination, testing and commissioning of 4


paiCr ategory-5E LAN cable consisting of 24 AWG solid copper
16.9
conductors .The cable should have flexible jacket and ripcord for
easy stripability (. Voice) MAKE: Molex
SUPPLY Metre 0.00 0.00
INSTALLATION Metre 0.00 0.00

Supply, installation, termination,testing and commissioning of 4


paiCr ategory-6 LAN cable consisting of 24 AWG solid copper
16.10
conductors . The cable should have flexible jacket and ripcord for
easy stripability( Data) MAKE: Molex
SUPPLY Metre 0.00 0.00
INSTALLATION Metre 0.00 0.00

Supply and installation including termination in MDF/IDF of voice


grade riser cable, multi pair , CAT 3

16.11 50 PAIR
SUPPLY Metre 0.00 0.00
INSTALLATION Metre 0.00 0.00
16.12 30 PAIR
SUPPLY Metre 0.00 0.00
INSTALLATION Metre 0.00 0.00
16.13 25 PAIR
SUPPLY Metre 0.00 0.00
INSTALLATION Metre 0.00 0.00

16.14 Supply and installation of CAT -6 Backbone cables for Data.


SUPPLY Metre 0.00 0.00
INSTALLATION Metre 0.00 0.00

Supply and installation of Krone type MDF for voice, suitable for
16.15
50 Pair incoming and
1000 pair outgoing complete with Krone type connectors.

SUPPLY Each 0.00 0.00


INSTALLATION Each 0.00 0.00

Supply and installation of Krone type IDF for voice distribution.


(Telephone Tag Blocks)

16.16 50 PAIR
SUPPLY Each 0.00 0.00
INSTALLATION Each 0.00 0.00

16.17 30 PAIR
SUPPLY Each 0.00 0.00

Taj Gateway Hotel at Chennai Page- 51 of 62


Taj Gateway Hotel at Chennai
SL.No Item Description Unit
Qty PRICE Amount

INSTALLATION Each 0.00 0.00

16.18 25 PAIR
SUPPLY Each 0.00 0.00
INSTALLATION Each 0.00 0.00

16.19 10 PAIR (For Guest Rooms -Above Vestibule)


SUPPLY Each 0.00 0.00
INSTALLATION Each 0.00 0.00
0

Supply and installation of flush mounted information outlets.


(Category 5E for voice and 6 for data ) The plastic shall be high
impact, flame-retardant, UL rate thermoplastic. Dust cover / blank
shall be provided to protect unused faceplate openings.
Termination caps and plastic cover should be provided to protect
jack wiring. Quoted prices shall be inclusive of 2 mm thick GI
boxes, complete including cutting and chases, fixing of GI box with
face plate and making good as required (Face plate shall match the
colour, size as per make of wiring accessories to be used in the
project). MAKE: Molex

16.20 Single outlet with faceplate and RJ-45 jack, Cat 5e for voice outlets

SUPPLY Each 0.00 0.00


INSTALLATION Each 0.00 0.00

16.21 Single outlet with faceplate and RJ-45 jacks, Cat 6 for Data outlets.

SUPPLY Each 0.00 0.00


INSTALLATION Each 0.00 0.00

Supply and installation of 1 mtr long Category 3 UTP telephone


16.22
cable for connection to Telephone instruments.
SUPPLY Each 0.00 0.00
INSTALLATION Each 0.00 0.00

Supply and installation of Category 6 patch cord for connecting


the data outlets to the data station (computer/printer etc). It shall
have male RJ 45 connector on one end and male RJ45 connector or
open ended wire or a connector suitable for data outlet at the other
end. It shall be a 8 conductor, 4 pair cord with each conductor of
24 AWG stranded wire. MAKE: Molex

16.23 7 feet
SUPPLY Each 0.00 0.00
INSTALLATION Each 0.00 0.00

16.24 3 feet
SUPPLY Each 0.00 0.00
INSTALLATION Each 0.00 0.00

Supply and installation of GI Trunking, minimum thickness 1.6mm,


100 mm wide x 50 mm deep for laying of vertical data back bone
16.25
cabling complete with supporting and fixing arrangements. Each
floor, cutout for taking the cables shal be provided. Trunking s

SUPPLY Metre 50 0.00 0.00


INSTALLATION Metre 50 0.00 0.00

Taj Gateway Hotel at Chennai Page- 52 of 62


Taj Gateway Hotel at Chennai
SL.No Item Description Unit
Qty PRICE Amount

Supply and installation of heavy duty rigid PVC Conduit, Fire


Retardent 2 mm thick, complete with all fittings, saddles, bends,
elbows etc for internal data voice cabling.

16.16 19 mm dia
SUPPLY Metre 2000 0.00 0.00
INSTALLATION Metre 2000 0.00 0.00
16.17 25 mm dia 0
SUPPLY Metre 300 0.00 0.00
INSTALLATION Metre 300 0.00 0.00
16.18 32 mm dia
SUPPLY Metre 0.00 0.00
INSTALLATION Metre 0.00 0.00

Interconnecting 4 Way GI pull box/junction boxes made out of


minimum 1.6 mm thick GI sheets of following sizes(For conduit
terminations at Junctions, and in Shafts)
16.19 600 x 450 x 50 mm
SUPPLY Each 0.00 0.00
INSTALLATION Each 0.00 0.00
16.20 450 x 300 x 50 mm
SUPPLY Each 0.00 0.00
INSTALLATION Each 0.00 0.00
16.21 300 x 300 x 50 mm
SUPPLY Each 0.00 0.00
INSTALLATION Each 0.00 0.00

Supply and installation of wireless access points compatible with


16.22
IEEE 802.11.B
and upgradable to IEEE 802.11.G.Cost shall include radio servey
for
acertaining the reach of each points. MAKE: Molex

SUPPLY Each 0.00 0.00


INSTALLATION Each 0.00 0.00
16 SWG thick Aluminium Box Type Race Ways, single
16.23
compartment 100mmX75mm with
removable lid installed above ceiling using hitech suspension rods
at every 1000mm C/C
.--Sample to be got approved prior to prousement -cost of bends &
test to be inclused

SUPPLY Metre 0.00 0.00


INSTALLATION Metre 0.00 0.00
0
SUB TOTAL OF 0.00
DATA & VOICE CONTAINMENTS (ACTIVE
COMPONENTS & CABLING
BY SPECIALIST VENDOR)
SUPPLY
INSTALLATION

17 MATV SYSTEM ( CABLE TV ) & MUSIC SYSTEM

Providing and fixing in position the following 2MM THICK Fire-


retaradent ISI Marked rigid PVC conduits concealed or exposed as
called for including all accessories ie bends, junction boxes , outlet
boxes with cover plates of ' approved make ans design

( For RG-11 Co-axial cable)

Taj Gateway Hotel at Chennai Page- 53 of 62


Taj Gateway Hotel at Chennai
SL.No Item Description Unit
Qty PRICE Amount

17.1 19mm dia conduit


SUPPLY RM 3200 0.00 0.00
INSTALLATION RM 3200 0.00 0.00

17.2 25mm dia conduit


SUPPLY RM 2800 0.00 0.00
INSTALLATION RM 2800 0.00 0.00

17.3 32mm dia conduit


SUPPLY RM 0.00 0.00
INSTALLATION RM 0.00 0.00

Supply and fixing following signal outlet with grid plate in 2 mm


thick G.I.box complete including cutting , chases ,fixing of G.I.
boxes and making good ( Cover plate shall match the colour , size
and make of wiring accessories to be used in the project

17.4 T.V. Signal outlet


Make- CRABTREE , ANCHOR , SALZER
SUPPLY Set 20 0.00 0.00
INSTALLATION Set 20 0.00 0.00

17.5 Music Signal outlet


SUPPLY Point 0.00 0.00
INSTALLATION Point 0.00 0.00

Supply, erection testing and commissioning of following tap off


boxes for CATV system .

Make - NORSAT / GROUNDIG / KHATERIAN / ZINWELL

17.6 One way ( T-1 )

SUPPLY Set 0.00 0.00


INSTALLATION Set 0.00 0.00

17.7 Two way ( T-2 )

SUPPLY Set 0.00 0.00


INSTALLATION Set 0.00 0.00

17.8 Four way ( T-4 )

SUPPLY Set 20 0.00 0.00


INSTALLATION Set 20 0.00 0.00

Supply, erection testing and commissioning of spliter with boxes.

17.9 Two way (S-2)

SUPPLY Set 200 0.00 0.00


INSTALLATION Set 200 0.00 0.00
0
17.1 Three way (S-3)

SUPPLY Set 25 0.00 0.00


INSTALLATION Set 25 0.00 0.00

17.11 Four way (S-4)

Taj Gateway Hotel at Chennai Page- 54 of 62


Taj Gateway Hotel at Chennai
SL.No Item Description Unit
Qty PRICE Amount

SUPPLY Set 25 0.00 0.00


INSTALLATION Set 25 0.00 0.00

Supply, laying , connecting and commissioning of RG-11 co-axial


17.12
cable of MATV as per specification in existing M conduit

Make- COMSCOPE / BHONSALI / BELDON

SUPPLY RM 2500 0.00 0.00


INSTALLATION RM 2500 0.00 0.00

Supply, laying , connecting and commissioning of RG-8 co-axial


17.13
cable of MATV as per specification in existing MS conduit

Make- COMSCOPE / BHONSALI / BELDON

SUPPLY RM 2000 0.00 0.00


INSTALLATION RM 2000 0.00 0.00

Supply, laying , connecting and commissioning of RG-6 co-axial


17.14
cable of MATV as per specification in existing MS conduit

Make- COMSCOPE / BHONSALI / BELDON

SUPPLY RM 7500 0.00 0.00


INSTALLATION RM 7500 0.00 0.00

SUBTOTAL OF MATV SYSTEM ( CABLE TV ) & MUSIC


0.00
SYSTEM
SUPPLY
INSTALLATION

18 Ccable tray

Supply and erection of 14SWG Thick GI Cable Trays, AS PER


APPROVED SAMPLE,(under floor multi-compartmetalised cable
managemnet system ) of following sizes.The rates for fixing in
floor shall be inclusive of all necessary Civil Works like Cutting &
Making Goo

18.1 150 mm Wide GI

SUPPLY RM 0.00 0.00


INSTALLATION RM 0.00 0.00

18.2 300 mm Wide GI

SUPPLY RM 0.00 0.00


INSTALLATION RM 0.00 0.00
0
18.3 450 mm Wide GI

SUPPLY RM 0.00 0.00


INSTALLATION RM 0.00 0.00

18.4 600 mm Wide GI

SUPPLY RM 0.00 0.00


INSTALLATION RM 0.00 0.00

Taj Gateway Hotel at Chennai Page- 55 of 62


Taj Gateway Hotel at Chennai
SL.No Item Description Unit
Qty PRICE Amount

18.5 750 mm Wide GI

SUPPLY RM 0.00 0.00


INSTALLATION RM 0.00 0.00

18.6 1000 mm Wide GI

SUPPLY RM 0.00 0.00


INSTALLATION RM 0.00 0.00

SUBTOTAL OF CABLE TRAYS 0.00


SUPPLY
INSTALLATION

UN INTERRUPTED POWER SUPPLY (SUPPLY &


19
ERECTION)

Design, Supply, Installation, Testing and commissioning of UPS


system etc as per the specifications, data sheets, drawings, etc
comprising of the following:

Supply and Installation of the following UPS systems:

19.1 UPS System and Battery


60 KVA STAND ALONE UPS with 3 Phase Input,3 Phase Output
50Hz with inbuilt Isolation
Transformers as per the specifications With all Necessery Items &
Set 0 0.00 0.00
Base Frames ,fasteners..etc

Sealed Maintenance free batteries for 15 minutes battery backup


at full load for the above UPS
with battery cubicle with all other accessories as required. Set 0 0.00 0.00

19.2 Instalaltion and Commissioning

system shall be provided by Electrical contractor Only. Rates are


covering the delivering ,Llifting,shifting, Placing t UPS System and
batteries at site
Set 0 0.00 0.00
Note : Rates includes Base frame,Battery Racks and All necessery
items

SUBTOTAL OF UN INTERRUPTED POWER SUPPLY


0.00
(SUPPLY & ERECTION)
SUPPLY
INSTALLATION

20 EARTHING, EARTH CONDUCTORS / STRIPS

20.1 Plate Earth Stations


Providing and laying of 600 x 600 x 6.3 mm thick GI electrode,
with 2 nos

50 X 6 mm GI strips from earth electrode to inspection chamber,

50 mm dia medium class GI pipe, CI funnel with 20 gauge GI wire


mesh

masonry chamber 1000 X 500 mm with concrete base CI manhole

Taj Gateway Hotel at Chennai Page- 56 of 62


Taj Gateway Hotel at Chennai
SL.No Item Description Unit
Qty PRICE Amount

cover with fram painted with bitumastic paint and packing with
mixtures of
charcoal and common salt around plate electrode including digging
of pit
upto permanent moisture level but not less than 3 meters and
including all
civil works like excavation and back filling in all types of soil
Murrum or Rock
filling Charcoal & salt, & providing watering funnel,durable
Masonry Chamber in
rich plastered brick work, and approved quality heavy dutyCI / GI
frame
heavy duty chamber cover,etcThe earthpit identity shall be marked
on the
cover with paint in an approved manner. For Body Earthing
Except

SUPPLY Set 0 0.00 0.00


INSTALLATION Set 26 0.00 0.00

Providing and installingCopper Plate Earth Station Size


20.2
600x600x3.15mm
complying to IS: 3043,complete in all respect with excavation in all
type
of Soil, Mrrum or Rock, filling of Charcoal & salt, & providing
watering funnel,
durable masonry Chamber in rich plastered brick work, and
approved quality
heavy duty CI/GI frame, heavy duty chamber cover, etc.The
earthpit
identification shall be marked with paint on the cover in an
approved mannerf.or Neutral
Earthing
SUPPLY Set 0 0.00 0.00
INSTALLATION Set 11 0.00 0.00

Supply, & Installation of GI tape welded Earthmat of overall


20.3
dimensions

4000 mm x1200 mm with cross conductors Of GI -Size 50 x 6 mm

welded securely at 200 mm x 200 mm grid sizing comprising 2 Nos

600mm x450 mm heavy duty Cast iron chamber complete with


termination

arrangement, watering funnel etc complete. For body Earthing

SUPPLY Set 0 0.00 0.00


INSTALLATION Set 1 0.00 0.00

20.4 EARTH CONDUCTORS/STRIPS/WIRES

Supplying and installing Earthing Conductors of the following


materials of
the sizes mentioned ; rates to include all required Civil works like
breaking
and making good, fixing items like fasteners, clamps, and inclusive
of
welding, brazing and soldering to effect the connections.

Taj Gateway Hotel at Chennai Page- 57 of 62


Taj Gateway Hotel at Chennai
SL.No Item Description Unit
Qty PRICE Amount

All termination costs including cost of Lugs, wherever required


shall be
included in the rates.

20.5 8 SWG Cu. wires-


RM 1000 0.00 0.00
SUPPLY RM 1000 0.00 0.00
INSTALLATION

20.6 25 x 3 mm Cu tape
RM 0.00 0.00
SUPPLY RM 0.00 0.00
INSTALLATION

20.7 25 x 6 mm Cu tape
SUPPLY RM 0.00 0.00
INSTALLATION RM 0.00 0.00

.......20.8.......
500 x 6 mm Cu tape
SUPPLY RM 250 0.00 0.00
INSTALLATION RM 250 0.00 0.00

20.9 8 SWG GI wires-


SUPPLY RM 0.00 0.00
INSTALLATION RM 0.00 0.00

20.10 25 x 6 mm GI tape
0.00 0.00
SUPPLY RM 0.00 0.00
INSTALLATION RM

20.11 25 x 3 mm GI tape
SUPPLY RM 0 0.00 0.00
INSTALLATION RM 1000 0.00 0.00

20.12 50x 6 mm GI tape


SUPPLY RM 0.00 0.00
INSTALLATION RM 0.00 0.00

Supplying, laying and connecting 450 mm. long 50 x 6 mm.


20.13
Copper flat in openfashionwith
necessary clamps, screws, etc., as earth link etc.,
SUPPLY Set 0 0.00 0.00
INSTALLATION Set 15 0.00 0.00

Supplying, laying and connecting 300 mm. long 25 x 6 mm.


20.14
Copper flat in openfashion with
necessary SMC Type Insulators, clamps, screws, etc., as earth
linketc., for UPSearthing.
SUPPLY Set 0 0.00 0.00
INSTALLATION Set 8 0.00 0.00

SUBTOTAL OF EARTHING, EARTH CONDUCTORS /


0.00
STRIPS
SUPPLY
INSTALLATION

21 LIGHTNING PROTECTION

Taj Gateway Hotel at Chennai Page- 58 of 62


Taj Gateway Hotel at Chennai
SL.No Item Description Unit
Qty PRICE Amount

Early Stermer Lightning Protection Including Mounting Structure


21.1
as required at site with all
necessery items

Make: CIRPROTEC, NIMBUS, CEC


SUPPLY Nos 2 0.00 0.00
INSTALLATION Nos 2 0.00 0.00

21.2 Aircraft warning lights with photosenser cell for and dawn control.

SUPPLY Nos 2 0.00 0.00


INSTALLATION Nos 2 0.00 0.00

Earth disconnector box (for lightning protection) made out of sheet


21.3
steel enclosure. Providing and fixing testing
joints, made out of 25mm x 3 mm tick, CU strip, 125mm long, with
4 nos.of GI bolts, nuts,check
nuts and spring washers etc. complete as required.

SUPPLY Nos 2 0.00 0.00


INSTALLATION Nos 2 0.00 0.00

21.4 1*70 sqmm copper Conductor cable.


SUPPLY Rmt 250 0.00 0.00
INSTALLATION Rmt 250 0.00 0.00

6 Digit 7 segment LCD based transient event counter / weather


21.5
proof box.
SUPPLY Nos 2 0.00 0.00
INSTALLATION Nos 2 0.00 0.00

SUBTOTAL OF LIGHTNING PROTECTION 0.00


SUPPLY
INSTALLATION

22 SAFETY ITEMS

Supply& fixing of Set of 4nos Round bottomed fire buckets with


22.1 necessary markings filled with river sand and mounted on a
M.S.stand as per standard practice
SUPPLY Nos 0 0.00 0.00
INSTALLATION Nos 4 0.00 0.00

Supply& fixing of Shock Treatment chart in Tamil& English


22.2
languages duly laminated/ glass framed
SUPPLY Nos 0 0.00 0.00
INSTALLATION Nos 10 0.00 0.00

Supply& fixing of Rubber mats 1mtr wide, 12.5mm thick with ISI
22.3
mark& approved colour
SUPPLY Mtrs 0 0.00 0.00
INSTALLATION Mtrs 25 0.00 0.00

Supply& fixing of 230V, AC portable & re chargeable emergency


22.4
light with 2x9/11W PL lamp of BPL/Panasonic Make

SUPPLY Nos 0 0.00 0.00


INSTALLATION Nos 5 0.00 0.00

Taj Gateway Hotel at Chennai Page- 59 of 62


Taj Gateway Hotel at Chennai
SL.No Item Description Unit
Qty PRICE Amount

Supply of Hand gloves tested for 15KV with ISI mark along with
22.5
test certificate.
SUPPLY Nos 0 0.00 0.00
INSTALLATION Nos 4 0.00 0.00

Supply of 11KV Earth discharge rod made of FRP complete with


22.6 earth terminal & 10sqmm copper pvc insulated conductor of 10mtr
length.
SUPPLY Nos 0 0.00 0.00
INSTALLATION Nos 2 0.00 0.00

Supply& fixing of Vitreous enamelled 11KV Danger boards as


22.7
required by the CEIG
SUPPLY Nos 0 0.00 0.00
INSTALLATION Nos 5 0.00 0.00

Supply& fixing of Vitreous enamelled 440V Danger boards as


22.8
required by the CEIG
SUPPLY Nos 0 0.00 0.00
INSTALLATION Nos 20 0.00 0.00

Supply& fixing of First aid box of containing full compliment of


22.9
medicines, ointments & bandages etc.,
SUPPLY Nos 0 0.00 0.00
INSTALLATION Nos 5 0.00 0.00

Supply& fixing of 60X40cm teak wood box with glass door&


22.10 hooks for hanging keys& space for keeping hand gloves complete
with lock & three keys
SUPPLY Nos 0 0.00 0.00
INSTALLATION Nos 2 0.00 0.00

Supply& fixing of 5kg dry powder type fire extinguisher approved


22.11
make with ISI mark including necessary fixing brackets

SUPPLY Nos 0 0.00 0.00


INSTALLATION Nos 6 0.00 0.00

Supply& Fixing of As fitted Single line drawing duly laminated/


22.12
framed in basement electrical room
SUPPLY Nos 0 0.00 0.00
INSTALLATION Nos 2 0.00 0.00

Supply & Installation of cast iron HT cable route markers with


22.13 necessary angle iron supports& civil works (From RMG Room to
Substation)
SUPPLY Nos 0.00 0.00
INSTALLATION Nos 0.00 0.00
0

Supply & Installation of cast iron LT cable route markers with


22.13
necessary angle iron supports& civil works (street Lighting cables)

SUPPLY Nos 0.00 0.00


INSTALLATION Nos 0.00 0.00

First Aid Kit as per RedCross Standards, complete with Medicines


for Burns, Cuts vomitting , swelling , Cotton Wool , Cotton
22.14
bandages ,Surgical sprit etc . placed in a wall-mounting box with 6
mm thick front hingedGlass cover, with the sign + and the ins

SUPPLY Nos 0.00 0.00

Taj Gateway Hotel at Chennai Page- 60 of 62


Taj Gateway Hotel at Chennai
SL.No Item Description Unit
Qty PRICE Amount

INSTALLATION Nos 0.00 0.00

SUBTOTAL OF SAFETY ITEMS 0.00


SUPPLY
INSTALLATION

Taj Gateway Hotel at Chennai Page- 61 of 62


Taj Gateway Hotel at Chennai
SL.No Item Description Unit
Qty PRICE Amount

23 LIAISONING & FOLLOW-UP

Liasion with the tamilnadu ELECTRICITY BOARD FOR


23.1 obtaining LOAD SANCTION for required demand offcial fees by LS 0 0.00 0.00
client
0
Liasion with the chief electrical inspector to govt of tamilnadu for
23.2 preparation of working drawings etc. obtaining approval for LS 0 0.00 0.00
drawing ,safety certificate approval for energisiation

Supply,fixing and commisioning of temperary lights for all floors in


23.3 LS 0 0.00 0.00
basic level of lightings with fixtures, wires,switches etc

SUBTOTAL OF LIAISONING & FOLLOW-UP


INSTALLATION

TOTAL 0.00
SUPPLY
INSTALLATION

Grand Total 0.00

Taj Gateway Hotel at Chennai Page- 62 of 62

You might also like