MTI Tubular Style

High Efficiency Furnace

EXCELLENCE THROUGH PROVEN PERFORMANCE

INDUSTRIAL COMMERCIAL
EQUIPMENT MANUFACTURING LTD.


INDUSTRIAL COMMERCIAL
EQUIPMENT MANUFACTURING LTD.

EXCELLENCE THROUGH PROVEN PERFORMANCE

Originally founded as Bullocks Manufacturing during the post-war residential


housing boom, I.C.E. Manufacturing was recognized for innovation and
excellence early in our history. After the company established a reputation for
designing, manufacturing and installing natural gas conversion burners for oil
and coal-fired furnaces, founder Don Bullocks returned from an ASHRAE trade
show with a natural gas line burner. Inspired, he set out to manufacture the first
direct-fired makeup air unit in his home country of Canada.

Today, the natural gas revolution continues with I.C.E. Manufacturing at the
forefront of the commercial direct-fired industry. Don had the vision long before
many others by designing a product that has outlived his legend. Our BMA
Series is named for him (Bullocks Makeup Air). This forward thinking has carried
on through such advanced products as the HTDM, the gas valve technology
available on the BMA, and the industrial-quality GIDM product line.

All of our products have withstood the test of time. Many new products are on
the horizon to meet the ever-increasing concern over energy costs, consumption
and impact on our environment. We are building on our heritage to bring
exceptional gas-fired products to market.

I.C.E. is committed to success the success of our customers and our


employees. To us, success is driven by loyalty that comes from service, quality
and innovation. With our vast experience in the HVAC industry, we continue to
listen to and understand the needs of our customers. And we trust we will be
able to serve you well into the future.
Table of Contents
MTI STANDARD FEATURES / OPTIONAL FEATURES / ADDITIONAL OPTIONS ..................................................................................................................... 2

MTI SERIES STANDARD TEMPERATURE CONTROL OPTIONS / MISCELLANEOUS CONTROL OPTIONS.......................................................................... 3

APPLICATION GUIDE FOR INDIRECT FIRED MTI SERIES ....................................................................................................................................................... 4

MTI PERFORMANCE SPECIFICATIONS.................................................................................................................................................................................... 6

MTI BASIC UNIT WEIGHTS & MAXIMUM AIRFLOWS .............................................................................................................................................................. 8

MTI 11-200, 11-300, 11-400 100% FRESH AIR........................................................................................................................................................................ 9

MTI 11-SERIES WITH RETURN .............................................................................................................................................................................................. 10

MTI 11-SERIES WITH DISCHARGE COOLING ...................................................................................................................................................................... 11

MTI 11 SERIES WITH INLET COOLING .................................................................................................................................................................................. 12

MTI 11 SERIES WITH RIGA-FLO FILTERS .............................................................................................................................................................................. 13

MTI 11 SERIES WITH MIXBOX WITH RELIEF ........................................................................................................................................................................ 14

MTI 11 SERIES WITH RETURN AIR BLOWER ........................................................................................................................................................................ 15

MTI 12 SERIES STD & WITH RETURN.................................................................................................................................................................................... 16

MTI 12 SERIES WITH DISCHARGE COOLING ...................................................................................................................................................................... 17

MTI 12 SERIES WITH INLET COOLING .................................................................................................................................................................................. 18

MTI 12 SERIES WITH RIGA-FLO FILTERS .............................................................................................................................................................................. 19

MTI 12 SERIES WITH MIXBOX WITH RELIEF ........................................................................................................................................................................ 20

MTI 12 SERIES WITH RETURN AIR BLOWER ........................................................................................................................................................................ 21

MTI 13 SERIES WITH RETURN .............................................................................................................................................................................................. 22

MTI 13 SERIES WITH DISCHARGE COOLING ...................................................................................................................................................................... 23

MTI 13 SERIES WITH INLET COOLING .................................................................................................................................................................................. 24

MTI 13 SERIES WITH RIGA-FLO FILTERS .............................................................................................................................................................................. 25

MTI 13 SERIES WITH MIXBOX WITH RELIEF ........................................................................................................................................................................ 26

MTI 13-SERIES WITH RETURN AIR BLOWER........................................................................................................................................................................ 27

MTI INDOOR 11 SERIES WITH RETURN ................................................................................................................................................................................ 28

MTI INDOOR 11 SERIES WITH DISCHARGE COOLING ........................................................................................................................................................ 29

MTI INDOOR 11 SERIES WITH INLET COOLING .................................................................................................................................................................. 30

MTI INDOOR 11 SERIES WITH RIGA-FLO FILTERS ............................................................................................................................................................... 31

MTI 12 SERIES WITH RETURN ............................................................................................................................................................................................... 32

MTI INDOOR 12 SERIES WITH DISCHARGE COOLING......................................................................................................................................................... 33

MTI INDOOR 12 SERIES WITH INLET COOLING ................................................................................................................................................................... 34

MTI INDOOR 12 SERIES WITH RIGA-FLO FILTERS ............................................................................................................................................................... 35

MTI INDOOR 13 SERIES WITH RETURN ................................................................................................................................................................................ 36

MTI INDOOR 13 SERIES WITH DISCHARGE COOLING......................................................................................................................................................... 37

MTI INDOOR 13 SERIES WITH INLET COOLING ................................................................................................................................................................... 38

MTI INDOOR 13 SERIES WITH RIGA-FLO FILTERS ............................................................................................................................................................... 39

MTI 11 SERIES VERTICAL ....................................................................................................................................................................................................... 40


MTI Standard Features
Heat Exchanger/Manifold Motor starter with overloads
16 gauge 409 SS Tubular heat exchanger Control circuit transformer
Heavy gauge inshot burners Control panel service switch
Minimum 80% efficiency Circuit breaker
Up to 18:1 turndown ratio Terminal connections for exhaust interlock
11-Series 6:1 Nationally recognized components and service parts.
12-Series 12:1
13-Series 18:1 Assurance
Up to 110 oF temperature rise ETL & C-ETL listed, conforms to ANSI Z83.8 & CSA/CGA 2.6
Intermittent pilot assembly with spark igniter and ignition transformer Factory wired, piped, and test fired
Solid state flame monitoring system
Cabinet
Flame roll out switch
Welded structural or formed channel base frame
Blocked Flue sensor
Lifting lugs
Choice of temperature control systems
Heavy gauge galvannealed steel casing with rust-resistant grey enamel
Manifold pressure for natural gas 7-14" W.C. paint finish
Manifold pressure for propane 11" W.C. One inch thick 1.5# density neoprene coated fiberglass
Manifold includes: pilot regulator, gas valve and shutoff valve, safety The insulation is glued and pinned
shutoff valve, pressure regulator or combination modulating and pressure
regulating valve, modulating gas valve, main test fire valve, manifold Blower/Motor
pressure taps.
AMCA rated forward curve DWDI centrifugal blower
Indoor units are suitable for sidewall venting
Polished steel shaft with rust inhibitor
Available sealed combustion on indoor units
Maximum operating speed less than 75% of first critical speed
For high altitude, the performance will be derated by 4% per 1000 feet
Sealed cartridge bearings provided with optional greaseable bearings
elevation above 2000 feet
available
Controls Enclosure ODP motor, 1800 RPM, T frame, 1.15 service factor mounted on
Electronic flame safeguard relay manual reset adjustable base

High limit safety Drives designed for 150% motor brake horsepower

Factory wired control panel with numbered terminal strip Adjustable V-belt drives used up to and including 5 HP; fixed drives on
7.5 HP and larger

Optional Features
Blowers Horizontal Discharge Head Internal Vibration Isolation
Backward inclined, air foil, and plug fans 180 deg. vertical and horizontal adjustment with Blower and motor isolated on separate frame with
360 deg. of free rotation R.I.S. or spring c/w canvas connector
DX Plenum
Coil located complete with drain pan when Mix Box External Vibration Isolation
applicable. Allows the recirculation of air to occur. This will Floor mounted or suspended isolation
provide a cost effective way of space heating.
Coil Plenums Service Platform
Includes V-bank filter rack
Heating coils- steam, hot water, and glycol Cooling Provides access to controls and gas train
coils- chilled water, DX coil Inlet Hoods
Motors
Expanded metal screen inlet with optional 2" filters.
Evaporative Coolers TEFC and high-efficiency, meeting EEE and CSA
Industrial and commercial Inlet Hood & Filter Rack standards and 2-speed
Combination Inlet hood with filter rack for 2" thick
Hinged Access Doors Disconnect Switch
filters available on models 11-200 to 11-400
Door switches Weatherproof enclosure; non-fused or fused
Special access door gasketing Filter Section
High Gas Pressure Regulator
#310 ventlock fasteners Filter section with side access suitable for 2" filters.
Required on natural gas with pressure in excess of
Mushroom Hood Winter Filter Section 14" W.C and LP applications in excess of 11" W.C.
Air velocity through the inlet ranges between Located on the discharge side of burner.
High/Low Gas Pressure Switches
approximately 450 and 550 feet per minute at
Filters Manual reset, gas pressure safety switches, which
maximum air capacities listed.
2" thick permanent, pleated and throwaway filters; lock out the burner in the event of gas pressure
Complete with internal screen for debris
various efficiency bag filters and HEPA filters malfunction.
Louvered Inlet complete with filter gauge and/or indicating light.
Control Panels
Manufactured by ICE and sized for a maximum
Motorized Inlet & Discharge Damper NEMA 4 or 12 custom remote enclosures
velocity of 500 FPM to minimize potential for
Parallel blade damper with a two-position spring
precipitation entering the unit
return actuator end switch
4-Way Discharge Head
Roof Curb
The adjustable 4 way discharge head provides
Prefabricated galvanized roof curb 16" or 24" high;
4 equal quantities of air in the conditioned space
full perimeter available on most units.

Additional Options
Auto low limit freeze protection control with Firestat High density insulation
bypass timer
7-day programmable timeclock 2" thick insulation
10 point electronic circuit analyzer with
Purge timer Motor and bearings out of airstream
signal lights
Delay exhaust start Extended grease lines
Exhaust Interlock Relay
115 volt GFI service receptacle Belt guards
Proof of Closure Valve
2 Inlet Air Controller (burner economizer)
Marine service light with 100 watt bulb, guard,
and lighted switch
Corrosion resistant two-step acrylic finish
Special coatings
Audible alarm
MTI Series Standard Temperature Control Options
Building makeup air systems maintain a constant supply air temperature to the space using a discharge temperature controller. The burner output is
modulated over a wide range to compensate for fluctuations in the incoming ambient air temperature. A gas valve regulates output according to the
demand sensed by a discharge air sensor. The fan and heat system functions are typically controlled by a remote panel with a system and
summer/winter switch or a building management system.

Discharge Air Temperature Control


Used predominantly for makeup air applications to maintain supply air at a constant temperature. The burner firing rate modulates in response to a
discharge air controller.
A) Electronic Control
The electronic modulating system consists of a discharge sensor, electronic amplifier and valve, which respond instantaneously to small fluctuations in
temperature. The system is capable of close temperature control over a wide range. Optional to the system is a remote temperature selector; range 55
to 90 deg. F. The system is also available with LED temperature indication, as an available option.

Discharge Air Temperature Control With Room Override


Commonly used in applications requiring maintenance of space temperatures as well as a constant discharge temperature. Typical applications include
plants and kitchens, which may require a morning warm-up. The override feature provides auxiliary heat to a space as required and sensed by a room
thermostat.
A) Electronic Control
The electronic modulating system as described above, in addition to the RTS (Remote Temperature Sensor) is furnished with a space thermostat. If the
thermostat setting is not satisfied, the burner will go to high fire until the thermostat is satisfied. Once satisfied the burner will return to being controlled
by RTS set point.
B) Electronic Control With High-Low RTS
The electronic modulating system as described above and in addition to the High RTS (Remote Temperature Sensor), a Low RTS is provided. Each RTS
can be set at varying desired discharge air set points. A space thermostat will switch between High and Low RTS. If the thermostat setting is not
satisfied, the discharge temperature will be increased (High RTS) until the thermostat is satisfied. Once the thermostat is satisfied, the unit will return to
being controller by the Low RTS set point. (Available with A1010 only)

Space Temperature Control


Used primarily for space heating applications, i.e. maintaining the space temperature at a certain level. This is accomplished primarily by using a space
thermostat.
A) Electronic Control
The burner firing rate is modulated in response to an amplified signal from a room-mounted thermostat. The discharge temperature is maintained within
preset maximum and minimum settings on the amplifier. The control package includes a thermostat with a temperature selector mounted either on the
remote panel or in the space. (Available with A1010 only)

Building Management Systems


A) Electronic Control
The unit will be configured to accept either a 0-10 VDC, or 4-20 mA input signal to allow BMS full control over the discharge air temperature set point.

Miscellaneous Control Options


Freeze Protection
Specified to protect against untempered air entering the space. The freeze thermostat, also known as an auto low limit, is located in the discharge air
and is wired in parallel with a time delay relay. In the event that the discharge air temperature is not above the freeze thermostat setting, within a preset
time during start-up and under normal operation the unit will shut down.

Inlet Air Controller


Features an adjustable thermostat, which monitors outdoor air temperatures. When the temperature exceeds the setting of the thermostat, the burner
will not operate even when the unit is in the winter mode.

Night Setback
This feature is available as an option on all temperature control systems. By lowering the discharge air temperature requirements during unoccupied
periods the owner can realize operating economies and still provide heat to the space as required. During the occupied cycle, the unit will be brought on
though an interlock, timeclock or switch. During the unoccupied period the timeclock provided, switches the system control to a single stage thermostat
set at the desired unoccupied temperature. The unit will then be started intermittently to provide heat to maintain the space at the unoccupied
temperature setpoint.

3
Application Guide For Indirect Fired MTI Series
MTI unit models are designated by their MBH input. Thus a MTI 12-700 has 700 MBH input, or 700,000 BTUH.
All MTI units are 80% efficient at high fire, thus output is BTUH input / 0.80.
Once you have chosen your required BTUH output, you can use BTUH output / 0.80 to find your required input, then select your model. (i.e. 560,000
BTUH / 0.80 = 700,000 BTUH Model = MTI 12-700).
Choose your airflow (this may be your first step if the unit is applied in a make-up air situation).
Calculate your TSP (add your ESP with your accessories accessory pressure drops can be found on page 7). With your airflow and TSP selected
you can find your BHP from the charts on page 6 & 7.
Unit weights can be found on page 8.
Given the entering and leaving air dry bulb temperatures or temperature rise, the equation below can be used to calculate the required MBH capacity.

MBH Capacity = (CFM x C x (LAT-EAT))/0.80/1000


MBH capacity: BTUH/1000 (British Thermal units per hour
CFM: Cubic Feet per minute of air
C: Gas constant of 1.08 based on air density at 75 deg. F
EAT: Entering air dry bulb temperature (deg. F)
LAT: Leaving air dry bulb temperature (deg. F)
0.8: MTI Series Efficiency

Example For Make-Up Air


An apartment building needs to have corridor pressurization. 10% pressurization is required and it is determined that 2950 CFM exhaust is required. -20
deg. F is the design ambient, and desired discharge temp is 70 deg F. Units will be roof mounted, down discharge, and will have an ESP of 0.70" W.C.
Select the appropriate MTI model, and find the BHP for the unit.
Selection:
Since we are exhausting 2950 CFM, and desire 10% pressurization, we can calculate that we need 3245 CFM of supply air (2950 + 10% = 3245)
We know our EAT = -20 deg. F, and LAT = 70 deg. F, thus we can calculate:
MBH Capacity = (CFM x C x (LAT-EAT))/0.80/1000
MBH Capacity = (3245 x 1.08 x (70 (-20)))/0.80/1000
MBH Capacity = 394.27
The closest model available is the MTI 11-400 which has 400 MBH input

We can now calculate our TSP:


We are selecting the basic options inlet filters and damper
Inlet damper = 0.1" W.C (Page 7)
Inlet Filters = Included (Page 7)
TSP = ESP + Accessories
TSP = 0.70 + 0.1
TSP = 0.8" W.C. (Round up to 1.0" W.C)
Consulting the chart for the MTI 11-400 (page 6) at 3245 CFM and 1.0" W.C we find our BHP = 1.81 BHP Thus we need a 2.0 HP motor minimum.

Example for Heat-Vent Unit


A small banquet room needs a minimum of 20% fresh air in unoccupied mode and 100% fresh air in occupied mode. It has been calculated that at -30
deg. F the room loses 450,000 BTUH. It has been determined that 4500 CFM is required for the application. The outdoor air is -30 deg. F, and desired
leaving air is 75 deg F. Return air will be 70 deg F. ESP is calculated to be 0.5" W.C. Select the appropriate model and find the BHP for the unit.
Selection:
Part 1 (Unoccupied mode)
We are only bringing in 20% outside air in this mode, thus 900 CFM is outside air and 3600 CFM is return air.
We know our EAT for outside air = -30 deg. F, and LAT = 75 deg. F, thus we can calculate:
MBH Capacity = (CFM x C x (LAT-EAT))/0.80/1000
MBH Capacity = (900 x 1.08 x (75 (-30)))/0.80/1000
MBH Capacity = 127.58
We also know that the room is losing 450 MBH, thus we need to add that to the calculation. 450 MBH = 562.5 MBH input
Thus the total Heat input capacity required = 690.06 MBH
Before we select our model we must check the occupied mode to ensure we have sufficient heat capacity.

4
Part 2 (Occupied mode)
We will be delivering 4500 CFM of outside in this mode
We know our EAT for outside air = -30 deg. F, and LAT = 75 deg. F, thus we can calculate:
MBH Capacity = (CFM x C x (LAT-EAT))/0.80/1000
MBH Capacity = (4500 x 1.08 x (75 (-30)))/0.80/1000
MBH Capacity = 637.88
Thus to satisfy both options we need to use an MTI 12-700.

We can now calculate our TSP:


We are selecting the basic options inlet filters and damper
Inlet damper = 0.1" W.C (Page 7)
Inlet Filters = Included (Page 7)
TSP = ESP + Accessories
TSP = 0.50 + 0.1
TSP = 0.6" W.C. (Round up to 0.75" W.C)
Consulting the chart for the MTI 12-700 (page 7) at 3245 CFM (Use 4714 CFM) and 0.75" W.C we find our BHP = 2.87 BHP - We can use
a 3 hp motor.

Example for a Heating Only Unit


An entrance vestibule to a store can potentially see 100% fresh air during times when the entrance doors open frequently. Thus a durable MTI unit
should be selected for this application. 4000 CFM at 0.5" W.C is determined to be the appropriate amount of air for the vestibule, and 320 MBH is
calculated to be the appropriate amount of heat capacity required. Select the appropriate model and find the BHP for the unit.
Selection:
Since the heating load calculation has already been completed we simply need to use the heating capacity divided by the efficiency of the MTI unit
to find our model:
MBH input = MBH output/Efficiency
MBH input = 320 MBH/0.8
MBH input 400 MBH

Thus we know our model will be an MTI 11-400

We can now calculate our TSP:


We are selecting the basic options inlet filters and damper
Inlet damper = 0.1" W.C (Page 7)
Inlet Filters Included (Page 7)
TSP = ESP + Accessories
TSP = 0.50 + 0.1
TSP = 0.6" W.C. (Round up to 0.75" W.C)
Consulting the chart for the MTI 11-400 (page 6) at 4000 CFM and 0.75" W.C we find our BHP ~= 2.5 BHP. A 3 hp motor is required.

5
MTI Performance Specifications
MTI 11-200 - 200 MBH INPUT/160 MBH OUTPUT MTI 11-300 - 300 MBH INPUT/240 MBH OUTPUT
Air 0.25" 0.5" 0.75" 1.0" 1.5" 2.0" Gas Air 0.25" 0.5" 0.75" 1.0" 1.5" 2.0" Gas
Temp. W.C. W.C. W.C. W.C. W.C. W.C. Temp. W.C. W.C. W.C. W.C. W.C. W.C.
Capacity Conn. Capacity Conn.
Rise Rise
(CFM) BHP BHP BHP BHP BHP BHP Inches (CFM) BHP BHP BHP BHP BHP BHP Inches

3704 40 1.97 2.16 1.85 2.56 2.96 3.34 5556 40 2.48 2.75 3.02 3.30 3.87 4.47
2963 50 1.28 1.45 1.60 1.75 2.05 2.35 4444 50 2.83 3.04 3.27 3.49 3.96 4.45
2469 60 1.28 1.41 1.53 1.67 1.97 2.28 3704 60 1.89 2.08 2.28 2.48 2.89 3.27
2116 70 0.95 1.07 1.20 1.33 1.58 1.83 3175 70 1.38 1.56 1.73 1.90 2.22 2.54
3/4 3/4
1852 80 0.74 0.86 0.97 1.08 1.29 1.51 2778 80 1.08 1.23 1.37 1.51 1.79 2.08
1646 90 0.60 0.70 0.80 0.89 1.08 1.27 2469 90 0.87 1.00 1.12 1.25 1.51 1.77
1481 100 0.46 0.54 0.63 0.70 0.87 1.03 2222 100 0.66 0.77 0.87 0.99 1.23 1.46
1347 110 0.38 0.46 0.54 0.68 0.85 0.98 2020 110 0.54 0.62 0.73 0.95 1.15 1.30

MTI 11-400 - 400 MBH INPUT/320 MBH OUTPUT


NOTES:
Air 0.25" 0.5" 0.75" 1.0" 1.5" 2.0" Gas
Temp. W.C. W.C. W.C. W.C. W.C. W.C. All Static Values Include Blower, Burner, Casing and Filters
Capacity Conn.
Rise Accessory Static Values Must be Added to Obtain the Total Static
(CFM) BHP BHP BHP BHP BHP BHP Inches
Brake Horsepower Does Not Include Drive Losses
7407 40 3.46 3.86 4.26 4.67 5.51 6.36
Units can be derated to achieve specific heat requirements, please note on
5926 50 2.74 3.02 3.31 3.60 4.20 4.81 your order your specific heat requirement
4938 60 2.97 3.18 3.40 3.65 4.17 4.71 See page 8 for maximum allowable model airflows

4233 70 2.09 2.29 2.51 2.74 3.20 3.67


3/4 Consult factory for:
3704 80 1.58 1.78 1.98 2.18 2.60 3.02 Higher Air Capacities or Special Applications
3292 90 1.26 1.44 1.62 1.81 2.19 2.59 Performance Data on Higher Statics than Listed
2963 100 0.94 1.10 1.26 1.44 1.78 2.16 Performance Data at Elevations Other Than Sea Level

2694 110 0.76 0.90 1.07 1.37 1.73 1.95

MTI 12-400 - 400 MBH INPUT/320 MBH OUTPUT MTI 12-500 - 500 MBH INPUT/400 MBH OUTPUT
Air 0.25" 0.5" 0.75" 1.0" 1.5" 2.0" Gas Air 0.25" 0.5" 0.75" 1.0" 1.5" 2.0" Gas
Temp. W.C. W.C. W.C. W.C. W.C. W.C. Temp. W.C. W.C. W.C. W.C. W.C. W.C.
Capacity Conn. Capacity Conn.
Rise Rise
(CFM) BHP BHP BHP BHP BHP BHP Inches (CFM) BHP BHP BHP BHP BHP BHP Inches

7407 40 3.89 4.32 4.71 5.13 6.00 6.85 9630 40 6.22 6.75 7.27 7.78 8.84 9.91
5926 50 3.06 3.35 3.64 3.95 4.55 5.17 7704 50 4.10 4.51 4.94 5.38 5.81 7.14
4938 60 3.22 3.45 3.70 3.96 4.49 4.97 6420 60 3.51 3.81 4.12 4.44 5.08 5.75
4233 70 2.33 2.56 2.79 3.01 3.25 3.48 5503 70 2.60 2.87 3.15 3.43 4.00 4.61
3/4 3/4
3704 80 1.81 2.01 2.21 2.42 2.84 3.28 4815 80 2.04 2.29 2.53 2.80 3.33 4.00
3292 90 1.38 1.56 1.74 1.93 2.31 2.73 4280 90 2.31 2.54 2.77 3.00 3.46 4.19
2963 100 1.22 1.39 1.56 1.73 2.11 2.52 3852 100 1.87 2.08 2.29 2.50 2.93 3.60
2694 110 1.04 1.19 1.36 1.53 1.90 2.30 3502 110 1.56 1.75 1.94 2.14 2.54 3.18

MTI 12-600 - 600 MBH INPUT/480 MBH OUTPUT MTI 12-700 - 700 MBH INPUT/560 MBH OUTPUT
Air 0.25" 0.5" 0.75" 1.0" 1.5" 2.0" Gas Air 0.25" 0.5" 0.75" 1.0" 1.5" 2.0" Gas
Temp. W.C. W.C. W.C. W.C. W.C. W.C. Temp. W.C. W.C. W.C. W.C. W.C. W.C.
Capacity Conn. Capacity Conn.
Rise Rise
(CFM) BHP BHP BHP BHP BHP BHP Inches (CFM) BHP BHP BHP BHP BHP BHP Inches

11111 40 8.25 9.00 9.90 10.20 11.00 12.46 12963 40 10.39 11.05 11.76 12.42 13.79 15.19
8889 50 5.28 5.75 6.25 6.73 7.70 8.71 10370 50 6.49 7.60 7.61 8.20 9.43 10.68
7407 60 4.72 5.04 5.37 5.73 6.44 7.17 8642 60 6.25 6.91 7.44 7.96 9.04 10.13
6349 70 3.39 3.69 3.99 4.31 4.94 5.60 7407 70 4.69 5.15 5.61 6.07 7.00 7.97
3/4 3/4
5556 80 2.60 2.88 3.16 3.43 4.01 4.61 6481 80 3.64 4.05 4.45 4.88 5.72 6.58
4938 90 3.12 3.34 3.58 3.84 4.37 4.90 5761 90 2.95 3.32 3.68 4.06 4.83 5.63
4444 100 2.46 2.68 2.91 3.15 3.63 4.13 5185 100 2.84 3.12 3.41 3.70 4.30 4.93
4040 110 2.01 2.22 2.44 2.66 3.10 3.56 4714 110 2.34 2.60 2.87 3.14 3.71 4.29

6
MTI Performance Specifications
MTI 12-800 - 800 MBH INPUT/640 MBH OUTPUT
NOTES:
Air 0.25" 0.5" 0.75" 1.0" 1.5" 2.0" Gas
Temp. W.C. W.C. W.C. W.C. W.C. W.C. All Static Values Include Blower, Burner, Casing and Filters
Capacity Conn.
Rise Accessory Static Values Must be Added to Obtain the Total Static
(CFM) BHP BHP BHP BHP BHP BHP Inches
Brake Horsepower Does Not Include Drive Losses
14815 40 10.39 11.05 11.76 12.42 13.79 15.19
Units can be derated to achieve specific heat requirements, please note on
11852 50 6.49 7.60 7.61 8.20 9.43 10.68 your order your specific heat requirement
9877 60 6.25 6.91 7.44 7.96 9.04 10.13 See page 8 for maximum allowable model airflows

8466 70 4.69 5.15 5.61 6.07 7.00 7.97


3/4 Consult factory for:
7407 80 3.64 4.05 4.45 4.88 5.72 6.58 Higher Air Capacities or Special Applications
6584 90 2.95 3.32 3.68 4.06 4.83 5.63 Performance Data on Higher Statics than Listed
5926 100 2.84 3.12 3.41 3.70 4.30 4.93 Performance Data at Elevations Other Than Sea Level

5387 110 2.34 2.60 2.87 3.14 3.71 4.29

MTI 13-900 - 900 MBH INPUT/720 MBH OUTPUT MTI 13-1000 - 1000 MBH INPUT/800 MBH OUTPUT
Air 0.25" 0.5" 0.75" 1.0" 1.5" 2.0" Gas Air 0.25" 0.5" 0.75" 1.0" 1.5" 2.0" Gas
Temp. W.C. W.C. W.C. W.C. W.C. W.C. Temp. W.C. W.C. W.C. W.C. W.C. W.C.
Capacity Conn. Capacity Conn.
Rise Rise
(CFM) BHP BHP BHP BHP BHP BHP Inches (CFM) BHP BHP BHP BHP BHP BHP Inches

16667 40 12.26 13.11 13.46 14.79 16.58 18.42 18519 40 10.33 11.28 12.24 13.19 15.32 17.61
13333 50 8.05 8.77 9.50 10.27 11.88 13.50 14815 50 9.67 10.44 11.21 12.02 13.69 15.43
11111 60 8.83 9.41 10.00 10.60 11.79 13.01 12346 60 10.95 11.61 12.27 12.92 14.24 15.57
9524 70 6.43 6.95 7.46 7.96 9.01 10.08 10582 70 7.86 8.44 9.00 9.56 10.71 11.86
3/4 3/4
8333 80 4.96 5.40 5.87 6.33 7.25 8.21 9259 80 5.99 6.48 6.98 7.47 8.51 9.53
7407 90 3.96 4.37 4.79 5.20 6.06 6.92 8230 90 4.74 5.19 5.64 6.09 7.02 7.95
6667 100 3.28 3.64 4.03 4.41 5.19 5.94 7407 100 3.88 4.28 4.69 5.11 5.96 6.82
6061 110 3.14 3.44 3.73 4.04 4.65 5.29 6734 110 3.23 3.60 3.99 4.38 5.16 5.97

MTI 13-1100 - 1100 MBH INPUT/880 MBH OUTPUT MTI 13-1200 - 1200 MBH INPUT/960 MBH OUTPUT
Air 0.25" 0.5" 0.75" 1.0" 1.5" 2.0" Gas Air 0.25" 0.5" 0.75" 1.0" 1.5" 2.0" Gas
Temp. W.C. W.C. W.C. W.C. W.C. W.C. Temp. W.C. W.C. W.C. W.C. W.C. W.C.
Capacity Conn. Capacity Conn.
Rise Rise
(CFM) BHP BHP BHP BHP BHP BHP Inches (CFM) BHP BHP BHP BHP BHP BHP Inches

20370 40 14.75 15.77 16.85 17.91 20.13 22.47 22222 40 14.75 15.77 16.85 17.91 20.13 22.47
16296 50 13.75 14.64 15.46 16.38 18.17 20.12 17778 50 13.75 14.64 15.46 16.38 18.17 20.12
13580 60 9.47 10.23 11.03 11.83 13.48 15.20 14815 60 9.47 10.23 11.03 11.83 13.48 15.20
11640 70 7.12 7.79 8.52 9.25 10.80 12.38 12698 70 7.12 7.79 8.52 9.25 10.80 12.38
3/4 3/4
10185 80 8.52 9.12 9.72 10.30 11.49 12.72 11111 80 8.52 9.12 9.72 10.30 11.49 12.72
9053 90 6.62 7.12 7.68 8.22 9.30 10.40 9877 90 6.62 7.12 7.68 8.22 9.30 10.40
8148 100 5.33 5.80 6.27 6.77 7.74 8.75 8889 100 5.33 5.80 6.27 6.77 7.74 8.75
7407 110 4.38 4.82 5.27 5.71 6.61 6.61 8081 110 4.38 4.82 5.27 5.71 6.61 6.61

STATIC PRESSURE DROP DUE TO ACCESSORIES


NOTE:
STATIC PRESSURE DROP ACCESSORY STATIC PRESSURE DROPS ARE CALCULATED AT MAXIMUM
ACCESSORIES
(IN INCHES W.C) CFM LOADS.

INLET LOUVER 0.2


EVAPORATIVE COOLER 0.4
INLET DAMPER 0.1
DX PLENUM AND COIL 0.6
WINTER FILTER (V-BANK) 0.6
HIGH EFFICIENCY FILTER 1.0
HORIZONTAL DISCHARGE HEAD 0.5
MUSHROOM HOOD 0.5
4 WAY DISCHARGE HEAD 0.5

7
MTI Basic Unit Weights & Maximum Airflows
Unit
Basic
Configuration
Unit Weight
VERTICAL

11 200 800
11 300 850
11 400 1,050

Unit
100% Fresh Air Basic/Mixbox DX Coil Plenum DX Coil Plenum High Efficiency Mix Box Return air Inlet Hood
Configuration
Unit Weight Unit Weight On Discharge Inlet of Unit Filter Inlet w/Relief Blower Weights
HORIZONTAL

11 200 1,050 1,150 1,650 1,425 1,250 1,300 1,600 160


11 300 1,100 1,200 1,700 1,475 1,310 1,350 1,650 160
11 400 1,175 1,325 1,900 1,650 1,475 1,550 1,800 160
12 400 N/A 1,675 2,150 1,975 1,750 1,825 2,150 160
12 500 N/A 1,675 2,150 1,975 1,750 1,825 2,150 160
12 600 N/A 1,675 2,150 1,975 1,750 1,825 2,150 160
12 700 N/A 1,900 2,400 2,175 1,950 2,100 2,360 160
12 800 N/A 1,900 2,400 2,175 1,950 2,100 2,360 160
13 900 N/A 2,200 2,750 2,525 2,350 2,250 2,650 160
13 1000 N/A 2,400 3,150 2,950 2,750 2,700 3,200 160
13 1100 N/A 2,400 3,150 2,950 2,750 2,700 3,200 160
13 1200 N/A 2,400 3,150 2,950 2,750 2,700 3,200 160

NOTE:
For all units weights are calculated using largest blower and motor sizes for each model.
All weights in LBS

Unit Velocity Maximum Maximum


High Efficiency
Model Std 2" Filters Area (FT2) Maximum at Maximum Area (FT2) Air Flow Air Flow
Filters
Airflow (1) Airflow (FPM) at 500 FPM (2) at 750 FPM (3)

11 200 3-25x20 10.41 2,500 240 2-24x24 4.0 2,000 3,000


11 300 3-25x20 10.41 4,000 384 2-24x24 4.0 2,000 3,000
11 400 3-25x20 10.41 6,000 576 2-24x24, 2-12x24 6.0 3,000 4,500
12 400 3-25x20 10.41 6,000 576 2-24x24 4.0 2,000 3,000
12 500 3-25x20 10.41 6,000 576 2-24x24 4.0 2,000 3,000
12 600 3-25x20 10.41 6,000 576 2-24x24 4.0 2,000 3,000
12 700 6-16x20 16.6 8,300 500 2-24x24, 2-12x24 6.0 3,000 4,500
12 800 6-16x20 16.6 8,300 500 2-24x24, 2-12x24 6.0 3,000 4,500
13 900 6-25x20 20.82 10,000 480 2-24x24 4.0 2,000 3,000
13 1000 6-25x20 20.82 10,000 480 2-24x24 4.0 2,000 3,000
13 1100 6-25x20 20.82 12,000 576 2-24x24, 2-12x24 6.0 3,000 4,500
13 1200 6-25x20 20.82 12,000 576 2-24x24, 2-12x24 6.0 3,000 4,500

(1) ABOVE THIS AIRFLOW SPECIAL CONFIGURATIONS MUST BE SELECTED, CONTACT YOUR LOCAL REPRESENTATIVE FOR MORE DETAILS
(2) Using Standard Cartridge Style High Efficiency Filters
(3) Using High Flow Farr Durafil Filters

8
INLET HOOD W/ FILTERS
(2-24X24X2, 2-12X24X2) 16 5

3
27
4 28

48

1
61 2

CONTROLS

VENT STACK GAS CONN.

TOP VIEW
SA AIRFLOW
29 72

SA AIRFLOW

3
25
4
FA AIRFLOW 16 5
40
8

1
10
2

SA AIRFLOW
SIDE VIEW

16 5

NOTES:
1. PROVIDE TIGHT FITTING INSPECTION PANELS IN DUCT DOWN STREAM FROM THE DUCT FURNACE
THESE PANELS SHOULD BE 12X12 IN. SO THAT THE HEAT EXCHANGER CAN BE INSPECTED.
2. GAS CONNECTION IS 3/4 IN. N.P.T. UNLESS OTHERWISE SPECIFIED.
3. VENT CAP TO BE INSTALLED WITHOUT ALTERATIONS.

TITLE
MTI 11-200, 11-300, 11-400
100% FRESH AIR

NOTE
INDUSTRIAL COMMERCIAL SUBJECT TO CHANGE WITHOUT NOTICE
EQUIPMENT MANUFACTURING LTD. FOR ROOF CURB DRAWINGS VISIT WWW.ICE-WW.COM 9
5 F E 5

5 5

G
C

CONTROLS

TOP VIEW VENT STACK GAS CONN.

FILTERS SA AIRFLOW
H

SA AIRFLOW

F
FA AIRFLOW E B

J I

SIDE VIEW SA AIRFLOW

RA AIRFLOW

MODEL A B C D E F G H I J
11-200 87-1/4 37-5/8 61-1/2 28 16 16 47 29-1/16 10-1/2 13-3/8
11-300 87-1/4 37-5/8 61-1/2 28 16 16 47 29-1/16 12-1/2 13-3/8
11-400 87-1/4 44-1/8 61-1/2 28 16 16 47 29-1/16 12-1/2 16-5/8

NOTES:
1. PROVIDE TIGHT FITTING INSPECTION PANELS IN DUCT DOWN STREAM FROM THE DUCT FURNACE
THESE PANELS SHOULD BE 12X12 IN. SO THAT THE HEAT EXCHANGER CAN BE INSPECTED.
2. GAS CONNECTION IS 3/4 IN. N.P.T. UNLESS OTHERWISE SPECIFIED.
3. VENT CAP TO BE INSTALLED WITHOUT ALTERATIONS.

TITLE MTI 11-SERIES WITH RETURN

NOTE SUBJECT TO CHANGE WITHOUT NOTICE


10 FOR ROOF CURB DRAWINGS VISIT WWW.ICE-WW.COM
5 F E 5

5 5

G
Y C

CONTROLS

TOP VIEW VENT STACK GAS CONN.

FILTERS
H DX COIL
SA AIRFLOW

SA AIRFLOW

F X
FA AIRFLOW E B

J I

SIDE VIEW SA AIRFLOW

RA AIRFLOW

MODEL A B C D E F G H I J X Y
11-200 135 1/2 37-5/8 61-1/2 28 16 16 47 29-1/16 12-1/2 13-3/8 30 55
11-300 135 1/2 37-5/8 61-1/2 28 16 16 47 29-1/16 12-1/2 13-3/8 30 55
11-400 135 1/2 44-1/8 61-1/2 28 16 16 47 29-1/16 12-1/2 16-5/8 33 55

NOTES:
1. PROVIDE TIGHT FITTING INSPECTION PANELS IN DUCT DOWN STREAM FROM THE DUCT FURNACE
THESE PANELS SHOULD BE 12X12 IN. SO THAT THE HEAT EXCHANGER CAN BE INSPECTED.
2. GAS CONNECTION IS 3/4 IN. N.P.T. UNLESS OTHERWISE SPECIFIED.
3. VENT CAP TO BE INSTALLED WITHOUT ALTERATIONS.

TITLE
MTI 11-SERIES WITH DISCHARGE COOLING

NOTE
INDUSTRIAL COMMERCIAL SUBJECT TO CHANGE WITHOUT NOTICE
EQUIPMENT MANUFACTURING LTD. FOR ROOF CURB DRAWINGS VISIT WWW.ICE-WW.COM 11
5 F E 5

5 5

G
Y C

CONTROLS

TOP VIEW VENT STACK GAS CONN.

FILTERS SA AIRFLOW
H DX COIL

SA AIRFLOW

F X
FA AIRFLOW E B

J I

SIDE VIEW SA AIRFLOW

RA AIRFLOW

MODEL A B C D E F G H I J X Y
11-200 103-1/4 37-5/8 61-1/2 28 16 16 47 29-1/16 12-1/2 13-3/8 24 55
11-300 103-1/4 37-5/8 61-1/2 28 16 16 47 29-1/16 12-1/2 13-3/8 24 55
11-400 103-1/4 44-1/8 61-1/2 28 16 16 47 29-1/16 12-1/2 16-5/8 30 55

NOTES:
1. PROVIDE TIGHT FITTING INSPECTION PANELS IN DUCT DOWN STREAM FROM THE DUCT FURNACE
THESE PANELS SHOULD BE 12X12 IN. SO THAT THE HEAT EXCHANGER CAN BE INSPECTED.
2. GAS CONNECTION IS 3/4 IN. N.P.T. UNLESS OTHERWISE SPECIFIED.
3. VENT CAP TO BE INSTALLED WITHOUT ALTERATIONS.

TITLE MTI 11 SERIES WITH INLET COOLING

NOTE SUBJECT TO CHANGE WITHOUT NOTICE


12 FOR ROOF CURB DRAWINGS VISIT WWW.ICE-WW.COM
5 F E 5

5 5

G
C

CONTROLS

TOP VIEW VENT STACK GAS CONN.

PRE-FILTERS:
SA AIRFLOW
H RIGA-FLO:

SA AIRFLOW

F
FA AIRFLOW E B

J I

SIDE VIEW SA AIRFLOW

RA AIRFLOW

MODEL A B C D E F G H I J
11-200 87-1/4 103-1/4 61-1/2 47 16 16 47 29-1/16 10-1/2 13-3/8
11-300 87-1/4 103-1/4 61-1/2 47 16 16 47 29-1/16 12-1/2 13-3/8
11-400 87-1/4 103-1/4 61-1/2 47 16 16 47 29-1/16 12-1/2 16-5/8

NOTES:
1. PROVIDE TIGHT FITTING INSPECTION PANELS IN DUCT DOWN STREAM FROM THE DUCT FURNACE
THESE PANELS SHOULD BE 12X12 IN. SO THAT THE HEAT EXCHANGER CAN BE INSPECTED.
2. GAS CONNECTION IS 3/4 IN. N.P.T. UNLESS OTHERWISE SPECIFIED.
3. VENT CAP TO BE INSTALLED WITHOUT ALTERATIONS.

TITLE MTI 11 SERIES WITH RIGA-FLO FILTERS

NOTE SUBJECT TO CHANGE WITHOUT NOTICE


INDUSTRIAL COMMERCIAL
EQUIPMENT MANUFACTURING LTD.
FOR ROOF CURB DRAWINGS VISIT WWW.ICE-WW.COM 13
L RELIEF AIR
5 F E 5

5 5

G
C

CONTROLS

TOP VIEW VENT STACK GAS CONN.


L RELIEF AIR

H A

FILTERS SA AIRFLOW

SA AIRFLOW
K
FA AIRFLOW

E B

K K

SIDE VIEW SA AIRFLOW

RA AIRFLOW

MODEL A B C D E F G H I K L

11-200 103-1/4 37-5/8 61-1/2 28 16 16 47 20-1/16 10-1/2 11 18


11-300 103-1/4 37-5/8 61-1/2 28 16 16 47 20-1/16 12-1/2 11 18
11-400 103-1/4 44-1/8 61-1/2 28 16 16 47 20-1/16 12-1/2 14 18
NOTES:
1. PROVIDE TIGHT FITTING INSPECTION PANELS IN DUCT DOWN STREAM FROM THE DUCT FURNACE
THESE PANELS SHOULD BE 12X12 IN. SO THAT THE HEAT EXCHANGER CAN BE INSPECTED.
2. GAS CONNECTION IS 3/4 IN. N.P.T. UNLESS OTHERWISE SPECIFIED.
3. VENT CAP TO BE INSTALLED WITHOUT ALTERATIONS.

TITLE MTI 11 SERIES WITH MIXBOX WITH RELIEF

NOTE SUBJECT TO CHANGE WITHOUT NOTICE


14 FOR ROOF CURB DRAWINGS VISIT WWW.ICE-WW.COM
LOUVERED HOOD

L
5 F E 5
RELIEF AIRFLOW

5 5

D
M
G

W
C

LO
RF
AI
RA
FA AIRFLOW

CONTROLS

TOP VIEW VENT STACK GAS CONN.


L
M

LOUVERED HOOD
SA AIRFLOW
A
FILTERS

SA AIRFLOW

K
E B

SIDE VIEW SA AIRFLOW

RA AIRFLOW

MODEL A B C D E F G I J K L M
11-200 135-1/4 37-5/8 61-1/2 28 16 16 47 10-1/2 13-3/8 24 16 30
11-300 135-1/4 37-5/8 61-1/2 28 16 16 47 12-1/2 13-3/8 24 16 30
11-400 135-1/4 44-1/8 61-1/2 28 16 16 47 12-1/2 16-5/8 30 16 30

NOTES:
1. PROVIDE TIGHT FITTING INSPECTION PANELS IN DUCT DOWN STREAM FROM THE DUCT FURNACE
THESE PANELS SHOULD BE 12X12 IN. SO THAT THE HEAT EXCHANGER CAN BE INSPECTED.
2. GAS CONNECTION IS 3/4 IN. N.P.T. UNLESS OTHERWISE SPECIFIED.
3. VENT CAP TO BE INSTALLED WITHOUT ALTERATIONS.

TITLE MTI 11 SERIES WITH RETURN AIR BLOWER

NOTE SUBJECT TO CHANGE WITHOUT NOTICE


INDUSTRIAL COMMERCIAL
EQUIPMENT MANUFACTURING LTD.
FOR ROOF CURB DRAWINGS VISIT WWW.ICE-WW.COM 15
5 E E 5

5 5

G
C

CONTROLS

TOP VIEW VENT STACK GAS CONN. VENT STACK GAS CONN.

FILTERS SA AIRFLOW
H

SA AIRFLOW
F

FA AIRFLOW E B

I
J

SA AIRFLOW
SIDE VIEW

RA AIRFLOW

MODEL A B C D E F G H I J
12-400 119-1/2 37-5/8 61-1/2 28 16 16 47 29-1/16 12-1/2 13-3/8
12-500 119-1/2 37-5/8 61-1/2 28 16 16 47 29-1/16 12-1/2 13-3/8
12-600 119-1/2 37-5/8 61-1/2 28 16 16 47 29-1/16 12-1/2 13-3/8
12-700 119-1/2 44-1/8 61-1/2 28 16 25 47 29-1/16 12-1/2 13-7/8
12-800 119-1/2 44-1/8 61-1/2 28 16 25 47 29-1/16 12-1/2 13-7/8

NOTES:
1. PROVIDE TIGHT FITTING INSPECTION PANELS IN DUCT DOWN STREAM FROM THE DUCT FURNACE
THESE PANELS SHOULD BE 12X12 IN. SO THAT THE HEAT EXCHANGER CAN BE INSPECTED.
2. GAS CONNECTION IS 3/4 IN. N.P.T. UNLESS OTHERWISE SPECIFIED.
3. VENT CAP TO BE INSTALLED WITHOUT ALTERATIONS.

TITLE MTI 12 SERIES STD & WITH RETURN

NOTE SUBJECT TO CHANGE WITHOUT NOTICE


16 FOR ROOF CURB DRAWINGS VISIT WWW.ICE-WW.COM
5 E E 5

5 5

G
Y C

CONTROLS

TOP VIEW VENT STACK GAS CONN. VENT STACK GAS CONN.
H A

FILTERS:
DX COIL
SA AIRFLOW

SA AIRFLOW
F

X
FA AIRFLOW E B

J I

SIDE VIEW SA AIRFLOW

RA AIRFLOW

MODEL A B C D E F G H I J X Y
12-400 167 3/4 37-5/8 61-1/2 47 16 16 47 29-1/16 12-1/2 13-3/8 30 55
12-500 167 3/4 37-5/8 61-1/2 47 16 16 47 29-1/16 12-1/2 13-3/8 30 55
12-600 167 3/4 37-5/8 61-1/2 47 16 16 47 29-1/16 12-1/2 13-3/8 30 55
12-700 167 3/4 44-1/8 61-1/2 47 16 25 47 29-1/16 12-1/2 13-7/8 33 55
12-800 167 3/4 44-1/8 61-1/2 47 16 25 47 29-1/16 12-1/2 13-7/8 33 55

NOTES:
1. PROVIDE TIGHT FITTING INSPECTION PANELS IN DUCT DOWN STREAM FROM THE DUCT FURNACE
THESE PANELS SHOULD BE 12X12 IN. SO THAT THE HEAT EXCHANGER CAN BE INSPECTED.
2. GAS CONNECTION IS 3/4 IN. N.P.T. UNLESS OTHERWISE SPECIFIED.
3. VENT CAP TO BE INSTALLED WITHOUT ALTERATIONS.

TITLE MTI 12 SERIES WITH DISCHARGE COOLING

NOTE SUBJECT TO CHANGE WITHOUT NOTICE


INDUSTRIAL COMMERCIAL
EQUIPMENT MANUFACTURING LTD.
FOR ROOF CURB DRAWINGS VISIT WWW.ICE-WW.COM 17
5 E E 5

5 5

G
Y C

CONTROLS

TOP VIEW VENT STACK GAS CONN. VENT STACK GAS CONN.

H A

FILTERS
SA AIRFLOW
DX COIL

SA AIRFLOW
F

X
FA AIRFLOW E B

J I

SA AIRFLOW
SIDE VIEW

RA AIRFLOW

MODEL A B C D E F G H I J X Y
12-400 135-1/2 37-5/8 61-1/2 28 16 16 47 29-1/16 12-1/2 13-3/8 24 55
12-500 135-1/2 37-5/8 61-1/2 28 16 16 47 29-1/16 12-1/2 13-3/8 24 55
12-600 135-1/2 37-5/8 61-1/2 28 16 16 47 29-1/16 12-1/2 13-3/8 24 55
12-700 135-1/2 44-1/8 61-1/2 28 16 25 47 29-1/16 12-1/2 13-7/8 30 55
12-800 135-1/2 44-1/8 61-1/2 28 16 25 47 29-1/16 12-1/2 13-7/8 30 55

NOTES:
1. PROVIDE TIGHT FITTING INSPECTION PANELS IN DUCT DOWN STREAM FROM THE DUCT FURNACE
THESE PANELS SHOULD BE 12X12 IN. SO THAT THE HEAT EXCHANGER CAN BE INSPECTED.
2. GAS CONNECTION IS 3/4 IN. N.P.T. UNLESS OTHERWISE SPECIFIED.
3. VENT CAP TO BE INSTALLED WITHOUT ALTERATIONS.

TITLE MTI 12 SERIES WITH INLET COOLING

NOTE SUBJECT TO CHANGE WITHOUT NOTICE


18 FOR ROOF CURB DRAWINGS VISIT WWW.ICE-WW.COM
5 F E 5

5 5

G
C

CONTROLS

TOP VIEW VENT STACK GAS CONN. VENT STACK GAS CONN.

H A

PRE-FILTERS:
SA AIRFLOW
RIGA-FLO:

SA AIRFLOW
F

FA AIRFLOW E B

J I

SA AIRFLOW
SIDE VIEW

RA AIRFLOW

MODEL A B C D E F G H I J

12-400 135-1/2 37-5/8 61-1/2 28 16 16 47 29-1/16 12-1/2 13-3/8


12-500 135-1/2 37-5/8 61-1/2 28 16 16 47 29-1/16 12-1/2 13-3/8
12-600 135-1/2 37-5/8 61-1/2 28 16 16 47 29-1/16 12-1/2 13-3/8
12-700 135-1/2 44-1/8 61-1/2 28 16 25 47 29-1/16 12-1/2 13-7/8
12-800 135-1/2 44-1/8 61-1/2 28 16 25 47 29-1/16 12-1/2 13-7/8

NOTES:
1. PROVIDE TIGHT FITTING INSPECTION PANELS IN DUCT DOWN STREAM FROM THE DUCT FURNACE
THESE PANELS SHOULD BE 12X12 IN. SO THAT THE HEAT EXCHANGER CAN BE INSPECTED.
2. GAS CONNECTION IS 3/4 IN. N.P.T. UNLESS OTHERWISE SPECIFIED.
3. VENT CAP TO BE INSTALLED WITHOUT ALTERATIONS.

TITLE MTI 12 SERIES WITH RIGA-FLO FILTERS

NOTE SUBJECT TO CHANGE WITHOUT NOTICE


INDUSTRIAL COMMERCIAL
EQUIPMENT MANUFACTURING LTD.
FOR ROOF CURB DRAWINGS VISIT WWW.ICE-WW.COM 19
L RELIEF AIR
5 F E 5

5 5

G
C

CONTROLS

TOP VIEW VENT STACK GAS CONN. VENT STACK GAS CONN.
L RELIEF AIR

H A

FILTERS SA AIRFLOW

K SA AIRFLOW
FA AIRFLOW

E B
K K

SIDE VIEW SA AIRFLOW

RA AIRFLOW

MODEL A B C D E F G H I K L
12-400 135-1/2 37-5/8 61-1/2 28 16 16 47 29-1/16 12-1/2 11 18
12-500 135-1/2 37-5/8 61-1/2 28 16 16 47 29-1/16 12-1/2 11 18
12-600 135-1/2 37-5/8 61-1/2 28 16 16 47 29-1/16 12-1/2 11 18
12-700 135-1/2 44-1/8 61-1/2 28 16 25 47 29-1/16 12-1/2 14 18
12-800 135-1/2 44-1/8 61-1/2 28 16 25 47 29-1/16 12-1/2 14 18

NOTES:
1. PROVIDE TIGHT FITTING INSPECTION PANELS IN DUCT DOWN STREAM FROM THE DUCT FURNACE
THESE PANELS SHOULD BE 12X12 IN. SO THAT THE HEAT EXCHANGER CAN BE INSPECTED.
2. GAS CONNECTION IS 3/4 IN. N.P.T. UNLESS OTHERWISE SPECIFIED.
3. VENT CAP TO BE INSTALLED WITHOUT ALTERATIONS.

TITLE MTI 12 SERIES WITH MIXBOX WITH RELIEF

NOTE SUBJECT TO CHANGE WITHOUT NOTICE


20 FOR ROOF CURB DRAWINGS VISIT WWW.ICE-WW.COM
LOUVERED HOOD
M

L
5 F E 5
RELIEF AIRFLOW
5 5

D
M
G

W
LO
C

RF
AI
RA

FA AIRFLOW
CONTROLS

TOP VIEW VENT STACK GAS CONN. VENT STACK GAS CONN.
L
M

LOUVERED HOOD
A

FILTERS SA AIRFLOW

SA AIRFLOW

K
E B

SIDE VIEW SA AIRFLOW

RA AIRFLOW

MODEL A B C D E F G I K L M

12-400 167-1/2 37-5/8 61-1/2 28 16 16 47 12-1/2 24 16 30


12-500 167-1/2 37-5/8 61-1/2 28 16 16 47 12-1/2 24 16 30
12-600 167-1/2 37-5/8 61-1/2 28 16 16 47 12-1/2 24 16 30
12-700 167-1/2 44-1/8 61-1/2 28 16 25 47 12-1/2 30 16 30
12-800 167-1/2 44-1/8 61-1/2 28 16 25 47 12-1/2 30 16 30

NOTES:
1. PROVIDE TIGHT FITTING INSPECTION PANELS IN DUCT DOWN STREAM FROM THE DUCT FURNACE
THESE PANELS SHOULD BE 12X12 IN. SO THAT THE HEAT EXCHANGER CAN BE INSPECTED.
2. GAS CONNECTION IS 3/4 IN. N.P.T. UNLESS OTHERWISE SPECIFIED.
3. VENT CAP TO BE INSTALLED WITHOUT ALTERATIONS.

TITLE MTI 12 SERIES WITH RETURN AIR BLOWER

NOTE SUBJECT TO CHANGE WITHOUT NOTICE


INDUSTRIAL COMMERCIAL
EQUIPMENT MANUFACTURING LTD.
FOR ROOF CURB DRAWINGS VISIT WWW.ICE-WW.COM 21
5 F E 5

5 5

G
C

CONTROLS

TOP VIEW VENT STACK GAS CONN. VENT STACK GAS CONN. VENT STACK GAS CONN.
A

FILTERS SA AIRFLOW
H

SA AIRFLOW
F

FA AIRFLOW E B

J I

SIDE VIEW SA AIRFLOW

RA AIRFLOW

MODEL A B C D E F G H I J
13-900 160-3/4 44-1/8 61-1/2 28 16 25 47 29-1/16 12-1/2 13-1/8
13-1000 160-3/4 44-1/8 61-1/2 28 16 25 47 29-1/16 12-1/2 13-1/8
13-1100 160-3/4 44-1/8 61-1/2 28 16 25 47 29-1/16 12-1/2 13-1/8
13-1200 160-3/4 44-1/8 61-1/2 28 16 25 47 29-1/16 12-1/2 13-1/8

NOTES:
1. PROVIDE TIGHT FITTING INSPECTION PANELS IN DUCT DOWN STREAM FROM THE DUCT FURNACE
THESE PANELS SHOULD BE 12X12 IN. SO THAT THE HEAT EXCHANGER CAN BE INSPECTED.
2. GAS CONNECTION IS 3/4 IN. N.P.T. UNLESS OTHERWISE SPECIFIED.
3. VENT CAP TO BE INSTALLED WITHOUT ALTERATIONS.

TITLE MTI 13 SERIES WITH RETURN

NOTE SUBJECT TO CHANGE WITHOUT NOTICE


22 FOR ROOF CURB DRAWINGS VISIT WWW.ICE-WW.COM
5 F E 5

5 5

G
Y C

CONTROLS

TOP VIEW VENT STACK GAS CONN. VENT STACK GAS CONN. VENT STACK GAS CONN.

H A
FILTERS
DX COIL
SA AIRFLOW

F
X
FA AIRFLOW SA AIRFLOW E B

J I

SIDE VIEW SA AIRFLOW

RA AIRFLOW

MODEL A B C D E F G H I J X Y
13-900 209 44-1/8 61-1/2 47 16 25 47 29-1/16 12-1/2 13-1/8 48 55
13-1000 209 44-1/8 61-1/2 47 16 25 47 29-1/16 12-1/2 13-1/8 48 55
13-1100 209 44-1/8 61-1/2 47 16 25 47 29-1/16 12-1/2 13-1/8 57 55
13-1200 209 44-1/8 61-1/2 47 16 25 47 29-1/16 12-1/2 13-1/8 57 55

NOTES:
1. PROVIDE TIGHT FITTING INSPECTION PANELS IN DUCT DOWN STREAM FROM THE DUCT FURNACE
THESE PANELS SHOULD BE 12X12 IN. SO THAT THE HEAT EXCHANGER CAN BE INSPECTED.
2. GAS CONNECTION IS 3/4 IN. N.P.T. UNLESS OTHERWISE SPECIFIED.
3. VENT CAP TO BE INSTALLED WITHOUT ALTERATIONS.

TITLE MTI 13 SERIES WITH DISCHARGE COOLING

NOTE SUBJECT TO CHANGE WITHOUT NOTICE


INDUSTRIAL COMMERCIAL
EQUIPMENT MANUFACTURING LTD.
FOR ROOF CURB DRAWINGS VISIT WWW.ICE-WW.COM 23
5 F E 5

5 5

G
Y C

CONTROLS

TOP VIEW VENT STACK GAS CONN. VENT STACK GAS CONN. VENT STACK GAS CONN.
A

FILTERS
SA AIRFLOW
DX COIL

SA AIRFLOW
F

X
FA AIRFLOW E B

J I

SIDE VIEW SA AIRFLOW

RA AIRFLOW

MODEL A B C D E F G H I J X Y

13-900 176-3/4 44-1/8 61-1/2 28 16 25 47 29-1/16 12-1/2 13-1/8 30 55


13-1000 176-3/4 44-1/8 61-1/2 28 16 25 47 29-1/16 12-1/2 13-1/8 30 55
13-1100 176-3/4 44-1/8 61-1/2 28 16 25 47 29-1/16 12-1/2 13-1/8 30 55
13-1200 176-3/4 44-1/8 61-1/2 28 16 25 47 29-1/16 12-1/2 13-1/8 30 55

NOTES:
1. PROVIDE TIGHT FITTING INSPECTION PANELS IN DUCT DOWN STREAM FROM THE DUCT FURNACE
THESE PANELS SHOULD BE 12X12 IN. SO THAT THE HEAT EXCHANGER CAN BE INSPECTED.
2. GAS CONNECTION IS 3/4 IN. N.P.T. UNLESS OTHERWISE SPECIFIED.
3. VENT CAP TO BE INSTALLED WITHOUT ALTERATIONS.

TITLE MTI 13 SERIES WITH INLET COOLING

NOTE SUBJECT TO CHANGE WITHOUT NOTICE


24 FOR ROOF CURB DRAWINGS VISIT WWW.ICE-WW.COM
5 F E 5

5 5

G
C

CONTROLS

TOP VIEW VENT STACK GAS CONN. VENT STACK GAS CONN. VENT STACK GAS CONN.
H A

PRE-FILTERS: SA AIRFLOW
RIGA-FLO:

SA AIRFLOW
F

FA AIRFLOW E B

J I

SIDE VIEW SA AIRFLOW

RA AIRFLOW

MODEL A B C D E F G H I J
13-900 176-3/4 44-1/8 61-1/2 28 16 25 47 29-1/16 12-1/2 13-1/8
13-1000 176-3/4 44-1/8 61-1/2 28 16 25 47 29-1/16 12-1/2 13-1/8
13-1100 176-3/4 44-1/8 61-1/2 28 16 25 47 29-1/16 12-1/2 13-1/8
13-1200 176-3/4 44-1/8 61-1/2 28 16 25 47 29-1/16 12-1/2 13-1/8

NOTES:
1. PROVIDE TIGHT FITTING INSPECTION PANELS IN DUCT DOWN STREAM FROM THE DUCT FURNACE
THESE PANELS SHOULD BE 12X12 IN. SO THAT THE HEAT EXCHANGER CAN BE INSPECTED.
2. GAS CONNECTION IS 3/4 IN. N.P.T. UNLESS OTHERWISE SPECIFIED.
3. VENT CAP TO BE INSTALLED WITHOUT ALTERATIONS.

TITLE MTI 13 SERIES WITH RIGA-FLO FILTERS

NOTE SUBJECT TO CHANGE WITHOUT NOTICE


INDUSTRIAL COMMERCIAL
EQUIPMENT MANUFACTURING LTD.
FOR ROOF CURB DRAWINGS VISIT WWW.ICE-WW.COM 25
L RELIEF AIR
5 F E 5

5 5

G
C

CONTROLS

TOP VIEW VENT STACK GAS CONN. VENT STACK GAS CONN. VENT STACK GAS CONN.
L RELIEF AIR

H A

FILTERS SA AIRFLOW

K SA AIRFLOW
FA AIRFLOW

E B
K K

SIDE VIEW SA AIRFLOW

RA AIRFLOW

MODEL A B C D E F G H I K L
13-900 167-3/4 44-1/8 61-1/2 28 16 16 47 29-1/16 12-1/2 14 18
13-1000 167-3/4 44-1/8 61-1/2 28 16 16 47 29-1/16 12-1/2 14 18
13-1100 167-3/4 44-1/8 61-1/2 28 16 16 47 29-1/16 12-1/2 14 18
13-1200 167-3/4 44-1/8 61-1/2 28 16 16 47 29-1/16 12-1/2 14 18

NOTES:
1. PROVIDE TIGHT FITTING INSPECTION PANELS IN DUCT DOWN STREAM FROM THE DUCT FURNACE
THESE PANELS SHOULD BE 12X12 IN. SO THAT THE HEAT EXCHANGER CAN BE INSPECTED.
2. GAS CONNECTION IS 3/4 IN. N.P.T. UNLESS OTHERWISE SPECIFIED.
3. VENT CAP TO BE INSTALLED WITHOUT ALTERATIONS.

TITLE MTI 13 SERIES WITH MIXBOX WITH RELIEF

NOTE SUBJECT TO CHANGE WITHOUT NOTICE


26 FOR ROOF CURB DRAWINGS VISIT WWW.ICE-WW.COM
LOUVERED HOOD
M
L
5 F E 5
RELIEF AIRFLOW
5 5

D
M
G

W
LO
C
RF
AI
RA

FA AIRFLOW
CONTROLS

TOP VIEW VENT STACK GAS CONN. VENT STACK GAS CONN. VENT STACK GAS CONN.
L
M

LOUVERED HOOD

FILTERS: SA AIRFLOW

SA AIRFLOW

K
E B

SIDE VIEW SA AIRFLOW

RA AIRFLOW

MODEL A B C D E F G I K L M

13-900 221-3/4 44-1/8 61-1/2 28 16 16 47 12-1/2 30 16 30


13-1000 221-3/4 44-1/8 61-1/2 28 16 16 47 12-1/2 30 16 30
13-1100 221-3/4 44-1/8 61-1/2 28 16 16 47 12-1/2 30 16 30
13-1200 221-3/4 44-1/8 61-1/2 28 16 16 47 12-1/2 30 16 30

NOTES:
1. PROVIDE TIGHT FITTING INSPECTION PANELS IN DUCT DOWN STREAM FROM THE DUCT FURNACE
THESE PANELS SHOULD BE 12X12 IN. SO THAT THE HEAT EXCHANGER CAN BE INSPECTED.
2. GAS CONNECTION IS 3/4 IN. N.P.T. UNLESS OTHERWISE SPECIFIED.
3. VENT CAP TO BE INSTALLED WITHOUT ALTERATIONS.

TITLE MTI 13-SERIES WITH RETURN AIR BLOWER

NOTE SUBJECT TO CHANGE WITHOUT NOTICE


INDUSTRIAL COMMERCIAL
EQUIPMENT MANUFACTURING LTD.
FOR ROOF CURB DRAWINGS VISIT WWW.ICE-WW.COM 27
5 F E 5

5 5

G
C

CONTROLS

6 GAS CONN.
TOP VIEW
FLU CONN.

A
RA AIRFLOW
FILTERS:

SA AIRFLOW

SA AIRFLOW

F
E B
FA AIRFLOW

J I

SA AIRFLOW
SIDE VIEW

MODEL A B C D E F G I J

11-200 87-1/4 37-5/8 61-1/2 28 16 16 47 10-1/2 13-3/8


11-300 87-1/4 37-5/8 61-1/2 28 16 16 47 12-1/2 13-3/8
11-400 87-1/4 44-1/8 61-1/2 28 16 16 47 12-1/2 16-5/8

NOTES:
1. PROVIDE TIGHT FITTING INSPECTION PANELS IN DUCT DOWN STREAM FROM THE DUCT FURNACE
THESE PANELS SHOULD BE 12X12 IN. SO THAT THE HEAT EXCHANGER CAN BE INSPECTED.
2. GAS CONNECTION IS 3/4 IN. N.P.T. UNLESS OTHERWISE SPECIFIED.
3. VENT CAP TO BE INSTALLED WITHOUT ALTERATIONS.

TITLE MTI INDOOR 11 SERIES WITH RETURN

NOTE SUBJECT TO CHANGE WITHOUT NOTICE


28
5 F E 5

5 5

G
Y C

CONTROLS

TOP VIEW 6 GAS CONN.


FLU CONN.
A
RA AIRFLOW
FILTERS
DX COIL
SA AIRFLOW

SA AIRFLOW

F X
FA AIRFLOW E B

J I

SIDE VIEW SA AIRFLOW

MODEL A B C D E F G I J X Y
11-200 135 1/2 37-5/8 61-1/2 28 16 16 47 12-1/2 13-3/8 30 55
11-300 135 1/2 37-5/8 61-1/2 28 16 16 47 12-1/2 13-3/8 30 55
11-400 135 1/2 44-1/8 61-1/2 28 16 16 47 12-1/2 16-5/8 33 55

NOTES:
1. PROVIDE TIGHT FITTING INSPECTION PANELS IN DUCT DOWN STREAM FROM THE DUCT FURNACE
THESE PANELS SHOULD BE 12X12 IN. SO THAT THE HEAT EXCHANGER CAN BE INSPECTED.
2. GAS CONNECTION IS 3/4 IN. N.P.T. UNLESS OTHERWISE SPECIFIED.
3. VENT CAP TO BE INSTALLED WITHOUT ALTERATIONS.

TITLE MTI INDOOR 11 SERIES WITH DISCHARGE COOLING

NOTE SUBJECT TO CHANGE WITHOUT NOTICE


INDUSTRIAL COMMERCIAL
EQUIPMENT MANUFACTURING LTD. 29
5 F E 5

5 5

G
Y C

CONTROLS

6 GAS CONN.
TOP VIEW
FLU CONN.
A

RA AIRFLOW FILTERS
DX COIL
SA AIRFLOW

SA AIRFLOW

F X
FA AIRFLOW E B

J I

SIDE VIEW SA AIRFLOW

MODEL A B C D E F G I J X Y
11-200 103-1/4 37-5/8 61-1/2 28 16 16 47 12-1/2 13-3/8 24 55
11-300 103-1/4 37-5/8 61-1/2 28 16 16 47 12-1/2 13-3/8 24 55
11-400 103-1/4 44-1/8 61-1/2 28 16 16 47 12-1/2 16-5/8 30 55

NOTES:
1. PROVIDE TIGHT FITTING INSPECTION PANELS IN DUCT DOWN STREAM FROM THE DUCT FURNACE
THESE PANELS SHOULD BE 12X12 IN. SO THAT THE HEAT EXCHANGER CAN BE INSPECTED.
2. GAS CONNECTION IS 3/4 IN. N.P.T. UNLESS OTHERWISE SPECIFIED.
3. VENT CAP TO BE INSTALLED WITHOUT ALTERATIONS.

TITLE MTI INDOOR 11 SERIES WITH INLET COOLING

NOTE SUBJECT TO CHANGE WITHOUT NOTICE


30
5 F E 5

5 5

G
C

CONTROLS

TOP VIEW 6 GAS CONN.


FLU CONN.
A

RA AIRFLOW PRE-FILTERS
RIGA-FLO
SA AIRFLOW

SA AIRFLOW

F
FA AIRFLOW E B

J I

SIDE VIEW SA AIRFLOW

MODEL A B C D E F G I J
11-200 87-1/4 103-1/4 61-1/2 47 16 16 47 10-1/2 13-3/8
11-300 87-1/4 103-1/4 61-1/2 47 16 16 47 12-1/2 13-3/8
11-400 87-1/4 103-1/4 61-1/2 47 16 16 47 12-1/2 16-5/8

NOTES:
1. PROVIDE TIGHT FITTING INSPECTION PANELS IN DUCT DOWN STREAM FROM THE DUCT FURNACE
THESE PANELS SHOULD BE 12X12 IN. SO THAT THE HEAT EXCHANGER CAN BE INSPECTED.
2. GAS CONNECTION IS 3/4 IN. N.P.T. UNLESS OTHERWISE SPECIFIED.
3. VENT CAP TO BE INSTALLED WITHOUT ALTERATIONS.

TITLE MTI INDOOR 11 SERIES WITH RIGA-FLO FILTERS

NOTE SUBJECT TO CHANGE WITHOUT NOTICE


INDUSTRIAL COMMERCIAL
EQUIPMENT MANUFACTURING LTD. 31
5 E E 5

5 5

G
C

CONTROLS

6 GAS CONN. 6 GAS CONN.


TOP VIEW
FLU CONN. FLU CONN.

A
RA AIRFLOW
FILTERS
SA AIRFLOW

SA AIRFLOW
F

FA AIRFLOW E B

J I

SIDE VIEW SA AIRFLOW

MODEL A B C D E F G I J
12-400 119-1/2 37-5/8 61-1/2 28 16 16 47 12-1/2 13-3/8
12-500 119-1/2 37-5/8 61-1/2 28 16 16 47 12-1/2 13-3/8
12-600 119-1/2 37-5/8 61-1/2 28 16 16 47 12-1/2 13-3/8
12-700 119-1/2 44-1/8 61-1/2 28 16 25 47 12-1/2 13-7/8
12-800 119-1/2 44-1/8 61-1/2 28 16 25 47 12-1/2 13-7/8

NOTES:
1. PROVIDE TIGHT FITTING INSPECTION PANELS IN DUCT DOWN STREAM FROM THE DUCT FURNACE
THESE PANELS SHOULD BE 12X12 IN. SO THAT THE HEAT EXCHANGER CAN BE INSPECTED.
2. GAS CONNECTION IS 3/4 IN. N.P.T. UNLESS OTHERWISE SPECIFIED.
3. VENT CAP TO BE INSTALLED WITHOUT ALTERATIONS.

TITLE MTI 12 SERIES WITH RETURN

NOTE SUBJECT TO CHANGE WITHOUT NOTICE


32
5 E E 5

5 5

G
Y C

CONTROLS

TOP VIEW 6 GAS CONN. 6 GAS CONN.


FLU CONN. FLU CONN.
A
RA AIRFLOW
FILTERS
DX COIL
SA AIRFLOW

SA AIRFLOW
F

X
FA AIRFLOW E B

J I

SIDE VIEW SA AIRFLOW

MODEL A B C D E F G I J X Y
12-400 167 3/4 37-5/8 61-1/2 47 16 16 47 12-1/2 13-3/8 30 55
12-500 167 3/4 37-5/8 61-1/2 47 16 16 47 12-1/2 13-3/8 30 55
12-600 167 3/4 37-5/8 61-1/2 47 16 16 47 12-1/2 13-3/8 30 55
12-700 167 3/4 44-1/8 61-1/2 47 16 25 47 12-1/2 13-7/8 33 55
12-800 167 3/4 44-1/8 61-1/2 47 16 25 47 12-1/2 13-7/8 33 55

NOTES:
1. PROVIDE TIGHT FITTING INSPECTION PANELS IN DUCT DOWN STREAM FROM THE DUCT FURNACE
THESE PANELS SHOULD BE 12X12 IN. SO THAT THE HEAT EXCHANGER CAN BE INSPECTED.
2. GAS CONNECTION IS 3/4 IN. N.P.T. UNLESS OTHERWISE SPECIFIED.
3. VENT CAP TO BE INSTALLED WITHOUT ALTERATIONS.

TITLE MTI INDOOR 12 SERIES WITH DISCHARGE COOLING

NOTE SUBJECT TO CHANGE WITHOUT NOTICE


INDUSTRIAL COMMERCIAL
EQUIPMENT MANUFACTURING LTD. 33
5 E E 5

5 5

G
Y C

CONTROLS

TOP VIEW 6 GAS CONN. 6 GAS CONN.


FLU CONN. FLU CONN.
A
RA AIRFLOW FILTERS
DX COIL
SA AIRFLOW

SA AIRFLOW
F

X
FA AIRFLOW E B

J I

SA AIRFLOW
SIDE VIEW

MODEL A B C D E F G I J X Y
12-400 135-1/2 37-5/8 61-1/2 28 16 16 47 12-1/2 13-3/8 24 55
12-500 135-1/2 37-5/8 61-1/2 28 16 16 47 12-1/2 13-3/8 24 55
12-600 135-1/2 37-5/8 61-1/2 28 16 16 47 12-1/2 13-3/8 24 55
12-700 135-1/2 44-1/8 61-1/2 28 16 25 47 12-1/2 13-7/8 30 55
12-800 135-1/2 44-1/8 61-1/2 28 16 25 47 12-1/2 13-7/8 30 55

NOTES:
1. PROVIDE TIGHT FITTING INSPECTION PANELS IN DUCT DOWN STREAM FROM THE DUCT FURNACE
THESE PANELS SHOULD BE 12X12 IN. SO THAT THE HEAT EXCHANGER CAN BE INSPECTED.
2. GAS CONNECTION IS 3/4 IN. N.P.T. UNLESS OTHERWISE SPECIFIED.
3. VENT CAP TO BE INSTALLED WITHOUT ALTERATIONS.

TITLE MTI INDOOR 12 SERIES WITH INLET COOLING

NOTE SUBJECT TO CHANGE WITHOUT NOTICE


34
5 F E 5

5 5

G
C

CONTROLS

TOP VIEW 6 GAS CONN. 6 GAS CONN.


FLU CONN. FLU CONN.

A
RA AIRFLOW PRE-FILTERS
RIGA-FLO
SA AIRFLOW

SA AIRFLOW
F

FA AIRFLOW E B

J I

SIDE VIEW SA AIRFLOW

MODEL A B C D E F G I J
12-400 135-1/2 37-5/8 61-1/2 28 16 16 47 12-1/2 13-3/8
12-500 135-1/2 37-5/8 61-1/2 28 16 16 47 12-1/2 13-3/8
12-600 135-1/2 37-5/8 61-1/2 28 16 16 47 12-1/2 13-3/8
12-700 135-1/2 44-1/8 61-1/2 28 16 25 47 12-1/2 13-7/8
12-800 135-1/2 44-1/8 61-1/2 28 16 25 47 12-1/2 13-7/8

NOTES:
1. PROVIDE TIGHT FITTING INSPECTION PANELS IN DUCT DOWN STREAM FROM THE DUCT FURNACE
THESE PANELS SHOULD BE 12X12 IN. SO THAT THE HEAT EXCHANGER CAN BE INSPECTED.
2. GAS CONNECTION IS 3/4 IN. N.P.T. UNLESS OTHERWISE SPECIFIED.
3. VENT CAP TO BE INSTALLED WITHOUT ALTERATIONS.

TITLE MTI INDOOR 12 SERIES WITH RIGA-FLO FILTERS

NOTE SUBJECT TO CHANGE WITHOUT NOTICE


INDUSTRIAL COMMERCIAL
EQUIPMENT MANUFACTURING LTD. 35
5 F E 5

5 5

G
C

CONTROLS

TOP VIEW 6 GAS CONN. 6 GAS CONN. 6 GAS CONN.


FLU CONN. FLU CONN. FLU CONN.
A
RA AIRFLOW
FILTERS

SA AIRFLOW

SA AIRFLOW
F

FA AIRFLOW E B

J I

SIDE VIEW SA AIRFLOW

MODEL A B C D E F G I J
13-900 160-3/4 44-1/8 61-1/2 28 16 25 47 12-1/2 13-1/8
13-1000 160-3/4 44-1/8 61-1/2 28 16 25 47 12-1/2 13-1/8
13-1100 160-3/4 44-1/8 61-1/2 28 16 25 47 12-1/2 13-1/8
13-1200 160-3/4 44-1/8 61-1/2 28 16 25 47 12-1/2 13-1/8

NOTES:
1. PROVIDE TIGHT FITTING INSPECTION PANELS IN DUCT DOWN STREAM FROM THE DUCT FURNACE
THESE PANELS SHOULD BE 12X12 IN. SO THAT THE HEAT EXCHANGER CAN BE INSPECTED.
2. GAS CONNECTION IS 3/4 IN. N.P.T. UNLESS OTHERWISE SPECIFIED.
3. VENT CAP TO BE INSTALLED WITHOUT ALTERATIONS.

TITLE MTI INDOOR 13 SERIES WITH RETURN

NOTE SUBJECT TO CHANGE WITHOUT NOTICE


36
5 F E 5

5 5

G
Y C

CONTROLS

TOP VIEW 6 GAS CONN. 6 GAS CONN. 6 GAS CONN.


FLU CONN. FLU CONN. FLU CONN.
A
RA AIRFLOW
FILTERS
DX COIL
SA AIRFLOW

F
X
FA AIRFLOW SA AIRFLOW E B

J I

SIDE VIEW SA AIRFLOW

MODEL A B C D E F G I J X Y

13-900 209 44-1/8 61-1/2 47 16 25 47 12-1/2 13-1/8 48 55


13-1000 209 44-1/8 61-1/2 47 16 25 47 12-1/2 13-1/8 48 55
13-1100 209 44-1/8 61-1/2 47 16 25 47 12-1/2 13-1/8 57 55
13-1200 209 44-1/8 61-1/2 47 16 25 47 12-1/2 13-1/8 57 55

NOTES:
1. PROVIDE TIGHT FITTING INSPECTION PANELS IN DUCT DOWN STREAM FROM THE DUCT FURNACE
THESE PANELS SHOULD BE 12X12 IN. SO THAT THE HEAT EXCHANGER CAN BE INSPECTED.
2. GAS CONNECTION IS 3/4 IN. N.P.T. UNLESS OTHERWISE SPECIFIED.
3. VENT CAP TO BE INSTALLED WITHOUT ALTERATIONS.

TITLE MTI INDOOR 13 SERIES WITH DISCHARGE COOLING

NOTE SUBJECT TO CHANGE WITHOUT NOTICE


INDUSTRIAL COMMERCIAL
EQUIPMENT MANUFACTURING LTD. 37
5 F E 5

5 5

G
Y C

CONTROLS

TOP VIEW 6 GAS CONN. 6 GAS CONN. 6 GAS CONN.


FLU CONN. FLU CONN. FLU CONN.
A
RA AIRFLOW FILTERS: 6-16X20X2
DX COIL
SA AIRFLOW

SA AIRFLOW
F

X
FA AIRFLOW E B

J I

SIDE VIEW SA AIRFLOW

MODEL A B C D E F G I J X Y
13-900 176-3/4 44-1/8 61-1/2 28 16 25 47 12-1/2 13-1/8 30 55
13-1000 176-3/4 44-1/8 61-1/2 28 16 25 47 12-1/2 13-1/8 30 55
13-1100 176-3/4 44-1/8 61-1/2 28 16 25 47 12-1/2 13-1/8 30 55
13-1200 176-3/4 44-1/8 61-1/2 28 16 25 47 12-1/2 13-1/8 30 55

NOTES:
1. PROVIDE TIGHT FITTING INSPECTION PANELS IN DUCT DOWN STREAM FROM THE DUCT FURNACE
THESE PANELS SHOULD BE 12X12 IN. SO THAT THE HEAT EXCHANGER CAN BE INSPECTED.
2. GAS CONNECTION IS 3/4 IN. N.P.T. UNLESS OTHERWISE SPECIFIED.
3. VENT CAP TO BE INSTALLED WITHOUT ALTERATIONS.

TITLE MTI INDOOR 13 SERIES WITH INLET COOLING

NOTE SUBJECT TO CHANGE WITHOUT NOTICE


38
5 F E 5

5 5

G
C

CONTROLS

TOP VIEW 6 GAS CONN. 6 GAS CONN. 6 GAS CONN.


FLU CONN. FLU CONN. FLU CONN.
A
RA AIRFLOW PRE-FILTERS
RIGA-FLO
SA AIRFLOW

SA AIRFLOW
F

FA AIRFLOW E B

J I

SIDE VIEW SA AIRFLOW

MODEL A B C D E F G I J
13-900 176-3/4 44-1/8 61-1/2 28 16 25 47 12-1/2 13-1/8
13-1000 176-3/4 44-1/8 61-1/2 28 16 25 47 12-1/2 13-1/8
13-1100 176-3/4 44-1/8 61-1/2 28 16 25 47 12-1/2 13-1/8
13-1200 176-3/4 44-1/8 61-1/2 28 16 25 47 12-1/2 13-1/8

NOTES:
1. PROVIDE TIGHT FITTING INSPECTION PANELS IN DUCT DOWN STREAM FROM THE DUCT FURNACE
THESE PANELS SHOULD BE 12X12 IN. SO THAT THE HEAT EXCHANGER CAN BE INSPECTED.
2. GAS CONNECTION IS 3/4 IN. N.P.T. UNLESS OTHERWISE SPECIFIED.
3. VENT CAP TO BE INSTALLED WITHOUT ALTERATIONS.

TITLE MTI INDOOR 13 SERIES WITH RIGA-FLO FILTERS

NOTE SUBJECT TO CHANGE WITHOUT NOTICE


INDUSTRIAL COMMERCIAL
EQUIPMENT MANUFACTURING LTD. 39
GAS CONN.

A C

1
E 5 4 D
6" FLU CONN. 2
SA AIRFLOW

FILTER
1-20X25X1
B

G
CONTROLS H I

FA AIRFLOW

MODEL A B C D E F G H I

11-200 65 58-5/8 27 18 12 14-5/8 52-13/16 20 25


11-300 65 58-5/8 27 18 12 14-5/8 52-13/16 20 25
11-400 65 58-5/8 33-1/2 24-1/2 12 14-5/8 52-13/16 20 31-1/2

NOTES:
1. PROVIDE TIGHT FITTING INSPECTION PANELS IN DUCT DOWN STREAM FROM THE DUCT FURNACE
THESE PANELS SHOULD BE 12X12 IN. SO THAT THE HEAT EXCHANGER CAN BE INSPECTED.
2. GAS CONNECTION IS 3/4 IN. N.P.T. UNLESS OTHERWISE SPECIFIED.
3. VENT CAP TO BE INSTALLED WITHOUT ALTERATIONS.

TITLE MTI 11 SERIES VERTICAL

NOTE SUBJECT TO CHANGE WITHOUT NOTICE


40
MTI - SERIES
Industrial Indirect Fired Series INDUSTRIAL COMMERCIAL
EQUIPMENT MANUFACTURING LTD.
TYPICAL SPECIFICATIONS
Supply an ICE Manufacturing Ltd. indirect fired heat vent unit designed for (indoor) (outdoor) installation. The capacity and configuration shall be as
detailed on the drawings. The unit shall be ETL certified and listed to be in compliance with the current ANSI Z83.8 second edition; CSA/CGA 2.6-2002;
Addenda A-2003; Addenda B-2004.
The burners, gas train and controls are to be in accordance with (ANSI) requirements. Both burner and blower shall be compensated for altitude
of operation.
The unit is to be completely factory test fired to verify proper operation. The unit capacity is to be validated with an instantaneous flow meter.
A complete electrical circuit analysis is to be conducted and all systems operated and measured. A combustion analyzer is to be employed while unit
is operating at full capacity to verify combustion emissions. Burner combustion must be clean and odorless and no aliphatic aldahydes are to be
detectable. Combustion efficiency is to be at least 80% while maintaining clean emissions.

Unit Casing
Unit construction is to be of industrial quality heavy gauge bonderized steel. The unit design shall incorporate a full base pan supported by an integral
heavy base.
To ensure the casings are airtight and weatherproof, all panels are to be caulked during assembly. All casings are to be hand fitted and secured with
gasketed self-tapping screws. Roof casing are to feature three-break standing seam panel design.
Entire unit casing and accessories are to be insulated with fiberglass insulation with hard neoprene facing. (1 or 2 in. thick 1-1/2# or 2# density)
insulation is to be secured with industrial glue and welded pin spots. Insulation is to be certified to fire and flamespread ratings as outlined by the ANSI
code. The entire floor of the unit is to feature a steel liner sandwiching the insulation.
Units are to be equipped with access doors to all serviceable components. Access doors are to have full-length stainless steel piano hinges. All access
doors are to be equipped with an insulation liner, positive seal latches and gasketing. Access doors are to open outward on negative pressure sections
and inward on positive pressure sections. Access doors to feature 6 in. handles with locking roller mechanism for ease of latching. All outdoor unit
access doors are to be equipped with drain troughs.
Units are to be finished with an industrial grade chain stop alkyd enamel paint. The medium grey finish coat is to be a mimum of 3 mils thick and provide
100% coverage.

Blower/Motor Section
Unit(s) shall be supplied with a single AMCA rated centrifugal forward curved industrial statically and dynamically balanced blower. The fan shall be
mounted on a heavy duty machined and polished shaft. The shafts maximum operating speed is not to exceed 75% of its first critical speed. The
bearings and motor shall be mounted in the airstream. The T-frame motor shall be mounted in a motor compartment on a fully adjustable base. The
bearings are to be industrial pillow block type supplied with extended grease lines. The blower is to be driven with an (adjustable) (fixed) 1.25 s.f. V-belt
drive package concealed in a belt guard. Outdoor units shall have hinged door(s) to provide easy access to maintain and inspect motor, belts &
bearings.

Furnace Section
The furnace section shall be positioned downstream of the blower section to ensure it is operating in a positive pressure chamber. The furnace is to be
constructed of minimum 16 gauge heavy duty 409 (optional 304) stainless steel tubes. The furnace shall include heavy duty inshot burners.
The furnace section will operate under a negative pressure as induced by the power venter. The power venter will be two speed to provide optimum
combustion and efficiency levels on reduced capacities. The power ventor shall come standard with a blocked flue switch, and the burner equipped with
a flame roll out switch. A modulating electro-mechanical valve will reduce gas flow in response to the signal from the unit mounted PLC. The modulation
will allow reduction of capacity down to 1/6 of high fire per furnace.
Indoor units shall be suitable for sidewall venting, and shall come with optional sealed combustion kit.

Control/Manifold Compartment
Unit control enclosure to have hinged access. Terminal strip and all wiring The gas manifold shall include:
shall be numbered. The controls for the heater shall include:
main gas pressure regulator
blower motor starter w/ambient compensated overloads and auxiliary high gas pressure regulator (optional)
contact(s).
manual shutoff & test firing valve
primary to 120v control transformer
main gas automatic shutoff valve
6,ooo volt ignition transformer
auxiliary main gas automatic shutoff valve
control circuit breaker and service switch
modulating control system
manual reset temperature high limit
pilot pressure regulator
flamesafeguard circuit
pilot automatic shutoff valve
discharge temperature control sensor
pilot manual shutoff valve
differential air proving safety switch
pilot needle valve
automatic low temperature limit (optional)
multiple test ports
all wiring external to control enclosure shall be run in conduit.
h 100% makeup air
and 80/20 units

BMA h

h
Stainless steel burner

DX or evaporative cooling
Direct Gas-Fired section option
makeup Air Units
h 30:1 turndown ratio
INDUSTRIAL COMMERCIAL
EQUIPMENT MANUFACTURING LTD.

h Recirculating & Dual Air


Dual Temperature Sequence
EXCELLENCE THROUGH
OSD h Exceptional spray booth
control packages using PLCs PROVEN PERFORMANCE
Direct Fired Makeup h Booth balancing option with variable
frequency drive on exhaust
Air/Curing Units
h Premium makeup air/curing units ICE MANUFACTURING LTD.
for the refinishing industry
51 Aikins Street
Winnipeg, Manitoba
Canada R2W 4E3
h 100% makeup air & 80/20 units Tel: (204) 586-8565
IMA h Suitable for any automotive
or high-end industrial applications
Fax: (204) 589-7682
Industrial
h Backward inclined blowers www.ice-ww.com
Gas-Fired Units standard on sizes 140 and up

ICE (U.S.) INC.


Industrial Park
h Four-pass drum and tube industrial
Bolivar, Tennessee

GIDM h
grade stainless steel heat exchanger

Industrial quality forced draft power burner


United States 38008
Tel: (731) 658-7000
Indirect h High efficiency (80%) and excellent durability
Gas-Fired Units Fax: (731) 658-3090
h JIC wiring available for the automotive industry
www.ice-us.com

h Stainless steel two-pass drum


and tube heat exchanger with

HTDM h
forced draft power burner

Best turndown ratio for power


High Turndown burners in the industry (Up to 60:1)
Indirect-Fired Units h Inputs of 200, 400, 600, 1000 & 1500 MBH

h Up to 85% (minimum efficiency)

h Indoor or Outdoor packaged indirect-fired heating systems

h Stainless steel heat exchanger

MTI h
suitable for 100% outside air

Excellent temperature control through


brand name components
Indirect
Gas-Fired Units h Wide variety of configuration options

h Superior serviceability through design and simplistic operation

h Vertical air turnover heating systems

An effective and economical


AC
h
solution to heating, ventilating
or conditioning large spaces
Air Turnover Units
h Four-pass indirect-fired heat exchanger

h Optional A-coil cooling section

CUSTOM h ICE has the capability to build a wide variety of


custom-built units for any type of commercial or

BUILT h
industrial application

Specializing in heat recovery and custom


UNITS air handler with heating or cooling coils

Printed in Canada