You are on page 1of 1

1 2 3 4 5 6 7 8 9 10

SW Review :- D
1. As per submitted RFQ, kindly show Pre filter, fine filter and activated
carbon filter after air dryer.
2. Kindly consider and supply pressure reducing valve along with
compressor and also show in PID.
3. Kindly show PRV set pressure value in PID.
4. Kindly show receiver with isolation valve and confirmed the outlet
size is 3/4" E
5. Kindly show nozzle types and thread standard for site installation.
6. Kindly confirm the type of drain valve. ie auto drain / manual type.
7. Confirm the power supply agreed as per submitted RFQ.
8. Kindly specify efficiency of the supply filter.

All materials supplied are in compliance with the