Design Rules for Electrical Equipment Numbering

AS BUILT

X1 08-Dec-15 AB AS BUILT Ge Jinghua Zhang Xiyi Shao Changjuan

APPROVED FOR
00 21-Nov-13 AFC Ge Jinghua Zhang Xiyi Shao Changjuan
CONSTRUCTION
ISSUED FOR
E 14-Nov-13 IFA Ge Jinghua Zhang Xiyi Shao Changjuan
APPROVAL
ISSUED FOR
D 04-Nov-13 IFR Ge Jinghua Zhang Xiyi Shao Changjuan
REVIEW
ISSUED FOR
C 21-Oct-13 IFR Ge Jinghua Zhang Xiyi Shao Changjuan
REVIEW
ISSUED FOR
B 16-Sep-13 IFR Ge Jinghua Zhang Xiyi Shao Changjuan
REVIEW
ISSUED FOR
A 28-Aug-13 IDC Ge Jinghua Zhang Xiyi Shao Changjuan
DISCIPLINE CHECK
REV DATE STATUS ISSUE PURPOSE ISSUED BY CHECKED BY APPROVED BY

COMPANYDOCUMENTATTRIBUTES:
Company Contract Territory Originator Facility System Sequence
Discipline DocType Lang*
Code Code Code Code Code Number

8015 0151 CPPB 00 000 EL SP 00001 E

This document is property of the COMPANY and it shall not be disclosed to third parties, or reproduced, without permission of the
COMPANY.
LUKOILMID- EPC Well Pads and Oil Gathering System at CHINA PETROLEUM
EASTLIMITED the West Qurna (Phase 2) Contract Area PIPELINE BUREAU
Design Rules For Electrical Equipment Numbering Rev.: X1 Status: AB
COMPANY No.:
8015-0151-CPPB-00-000-EL-SP-00001-E Page: 2 of 15
Contractor No.:

DOCUMENT REVISION HISTORY SHEET

REV STATUS DATE ISSUED UPDATE / AMENDMENT DETAILS

A IDC 22-Oct-2013 Issued for Discipline Check

IFR 16-Sep-2013 Issued for Review


Issued for Review
1. Page 5, par. 1, 2.1.1, 2.1.2 change :8015-0151-CPPB-00-000-PM-
PP-00002, Tag Numbering Procedure.
2. Page 5, par. 2.1.2 delete :
841 High Voltage Switchgear 220 kV
843 Medium Voltage Switchgear 35/33kV
844 Medium Voltage Switchgear 10/11kV
Change:
841 High Voltage Switchgear 110/132kV
842 Medium Voltage Switchgear 6.6kV
843 Low Voltage (LV) Switchgear 0.4kV
3. Page 5, par. 2.1.4 chagne :
Substation No. Substation Name
12-830-ESS-02 Well Pad #2 Substation
12-830-ESS-05 Well Pad #5 Substation
12-830-ESS-10 Well Pad #10 Substation
12-830-ESS-12 Well Pad #12 Substation
11-830-ESS-11 WQ-11 Substation
11-830-ESS-13 WQ-13 Substation

C IFR 21-Oct-2013 4. Page 8, par. 3.1, 3.2 change:


8015-0151-CPPB-00-000-PM-PP-00002, Tag Numbering
Procedure.
5. Page 9, par. 3.6 add: CORE IDENTIFICATION
6. Page 10, par. 4.1, 4.2 change 8015-0151-CPPB-00-000-PM-PP-
00002, Tag Numbering Procedure.
7. Page 11, par. 4.2 delete: 813 Overhead LINES 35/33 kV
add: 815 Overhead LINES 6.6 kV
8. page 11, par. 4.4 change:
132kV overhead lines 01 is the overhead lines from GTPP to Well
pads #2,#5, #6 and 02 is overhead lines from GTPP to Well pads #7,
#8, #10,#12.
Overhead lines No. Overhead lines Name
132kV Overhead lines for
12-812-EOHL-01
WP #2,5,6
132kV Overhead lines for
12-812-EOHL-02
WP #7,8,10,12
6.6kV Overhead lines for
11-815-EOHL-11
WQ-11
6.6kV Overhead lines for
11-815-EOHL-13
WQ-13

9. Page 11 , par. 5 delete :5.2 Cathodic Protection Equipment for Tank


Issued for Review
D IFR 04-Nov-2013
All woring numbering have be corrected.

E IFA 14-Nov-2013 Issued for Approval

00 AFC 21-Nov-2013 Approved for Construction

X1 AB 08-Dec-2015 As Built
LUKOILMID- EPC Well Pads and Oil Gathering System at CHINA PETROLEUM
EASTLIMITED the West Qurna (Phase 2) Contract Area PIPELINE BUREAU
Design Rules For Electrical Equipment Numbering Rev.: X1 Status: AB
COMPANY No.:
8015-0151-CPPB-00-000-EL-SP-00001-E Page: 3 of 15
Contractor No.:

CONTENTS

1. SCOPE AND PURPOSE ............................................................................................... 5

2. IDENTIFICATION OF SUBSTATION AND EQUIPMENT IN SUBSTATION .. 5

2.1. Identification of Substation Buildings ......................................................................... 5

2.1.1. Facility code ............................................................................................................. 5

2.1.2. Unit / System code ................................................................................................... 5

2.1.3. Equipment number ................................................................................................. 5

2.1.4. Substation number .................................................................................................. 6

2.2. Identification of Equipment in Substation .................................................................. 6

1.1.1. Bus bar number ....................................................................................................... 6

2.3. Switchboard bus-bar and compartments .................................................................... 7

2.3.1. HV and MV switchgear .......................................................................................... 7

2.3.2. LV switchgear .......................................................................................................... 7

3. IDENTIFICATION OF EQUIPMENT IN UNITS..................................................... 8

3.1. Motors ............................................................................................................................. 8


3.2. Parts of Package System ............................................................................................... 8
3.3. Local Control Stations .................................................................................................. 8
3.4. Junction Boxes ............................................................................................................... 8
3.5. Welding Sockets / Local Distribution Panels .............................................................. 8
3.6. Lighting Circuits and Fixtures, Convenience Outlets ................................................ 9
3.7. Lighting Junction Boxes.............................................................................................. 10

4. OVERHEAD LINES.................................................................................................... 10

4.1. Facility Code ................................................................................................................ 10


4.2. Unit / System Code ...................................................................................................... 10
4.3. Equipment number ..................................................................................................... 11
4.4. Sequential number ....................................................................................................... 11
LUKOILMID- EPC Well Pads and Oil Gathering System at CHINA PETROLEUM
EASTLIMITED the West Qurna (Phase 2) Contract Area PIPELINE BUREAU
Design Rules For Electrical Equipment Numbering Rev.: X1 Status: AB
COMPANY No.:
8015-0151-CPPB-00-000-EL-SP-00001-E Page: 4 of 15
Contractor No.:

4.5. Location Code .............................................................................................................. 11

5. CATHODIC PROTECTION SYSTEM .................................................................... 11

5.1. Equipment for Cathodic System ................................................................................ 11

6. CABLES........................................................................................................................ 12

6.1. Sequential Number ...................................................................................................... 12


6.2. Core Identification ....................................................................................................... 12

APPENDIX 1 EQUIPMENT NUMBER ............................................................................ 13

APPENDIX 2 EQUIPMENT NUMBER PREFIXES AND SUFFIXES ......................... 15


LUKOILMID- EPC Well Pads and Oil Gathering System at CHINA PETROLEUM
EASTLIMITED the West Qurna (Phase 2) Contract Area PIPELINE BUREAU
Design Rules For Electrical Equipment Numbering Rev.: X1 Status: AB
COMPANY No.:
8015-0151-CPPB-00-000-EL-SP-00001-E Page: 5 of 15
Contractor No.:

1. SCOPE AND PURPOSE


This specification defines technical requirements for identification and numbering of electrical
equipment for the EPC Well Pads and Oil Gathering System at the West Qurna (Phase 2)
Contract Area.
This specification includes the tagging method of electrical equipment, cable circuits, cable cores
and wires.
It does not apply to electrical motors that will be defined on the 8015-0151-CPPB-00-000-PM-PP-
00002, Tag Numbering Procedure.

2. IDENTIFICATION OF SUBSTATION AND EQUIPMENT IN SUBSTATION


2.1. Identification of Substation Buildings
Numbering of substations will be as follow:
12 - 830 - ESS - 01

2.1.1 FLACILTY CODE


12 for Well Pad

2.1.2 UNIT/SYSTEM CODE


830 for substation

2.1.3 EQUIPMENT NUMBER


ESS for substation

2.1.4 SUBSTATION NUMBER


01 for substation #1

2.1.1. Facility code


The facility code is defined in Appendix 2 of 8015-0151-SCPPB-00-000-PM-PP-00001 Document
Control Procedure

2.1.2. Unit / System code


The facility code is defined in Appendix 3 of 8015-0151-SCPPB-00-000-PM-PP-00001 Document
Control Procedure.
Especially following system codes will be allocated to various voltage system of switchgears.
-841 High Voltage Switchgear 220 kV
- 842 High Voltage Switchgear 110/132Kv
- 843 Medium Voltage Switchgear 35/33kV
- 844 Medium Voltage Switchgear 10/11kV
- 845 Medium Voltage Switchgear 6.6kV
- 846 Low Voltage (LV) Switchgear 0.4kV

2.1.3. Equipment number


The Equipment number is defined in appendix 1.
LUKOILMID- EPC Well Pads and Oil Gathering System at CHINA PETROLEUM
EASTLIMITED the West Qurna (Phase 2) Contract Area PIPELINE BUREAU
Design Rules For Electrical Equipment Numbering Rev.: X1 Status: AB
COMPANY No.:
8015-0151-CPPB-00-000-EL-SP-00001-E Page: 6 of 15
Contractor No.:

2.1.4. Substation number


The number of substation shall be identified with two numerical digits of tagging. 02 is the
second substation on a certain area. For well pads substation number is same as well pad number,
that is, 02 for substation in well pad #2 and 12 for substation in well pad #12.
Following list and numbers define entire substations in Wells and Well Pads.
Substation No. Substation Name
12-830-ESS-02 Well Pad #2 Substation
12-830-ESS-05 Well Pad #5 Substation
12-830-ESS-10 Well Pad #10 Substation
12-830-ESS-12 Well Pad #12 Substation
11-830-ESS-11 WQ-11 Substation
11-830-ESS-13 WQ-13 Substation

2.2. Identification of Equipment in Substation


Numbering of electrical equipment in substation will be as follow:
12 - 842 - 02 - ESW - 001 A

FLACILTY CODE
12 for Well Pad

UNIT/SYSTEM CODE
842 for 132kV HV switchgear

SUBSTATION NUMBER
02 for substation #2

EQUIPMENT NUMBER
ESW for switchgear

SEQUENTIAL NUMBER
starting at 001

BUSBAR NUMBER
If necessary

Examples: 12-845-02-ETR-001B is a 6.6/0.42 kV Transformer outgoing from the Bus Bar B


of 6.6kV Switchgear at substation of Well Pad #2 area.

1.1.1. Bus bar number


A = Bus bar section A, which left hand side or front bus bar
B = Bus bar section B, which right hand side or rear bus bar
E = Emergency bus bar
Examples: 12-842-05-ESW-001A1 is an incoming compartment from the Bus Bar A of
132kV Switchgear at Substation of well pad #5, Compartment number 1.
LUKOILMID- EPC Well Pads and Oil Gathering System at CHINA PETROLEUM
EASTLIMITED the West Qurna (Phase 2) Contract Area PIPELINE BUREAU
Design Rules For Electrical Equipment Numbering Rev.: X1 Status: AB
COMPANY No.:
8015-0151-CPPB-00-000-EL-SP-00001-E Page: 7 of 15
Contractor No.:

12-845-10-ESW-001B3-3 is an outgoing contactor feeder compartment from Bus


Bar B of 6.6kV Switchgear at Substation in Well Pad #10 area. Compartment
number 3, lower cubicle.

2.3. Switchboard bus-bar and compartments

2.3.1. HV and MV switchgear


HV and MV switchgear compartments will be numbered as below (front elevation):
B5-1
... A3 A2 A1 AV AB AB1 B1 B2 B3 B4 ...
B5-2

Where A1: Busbar A incoming section


B1: Busbar B incoming section
AB: Coupling section
AB1: Bus riser
AV, BV : Bus VTs of bus section A and B (when applicable)
A2, B2, A3, B3, : outgoing section of bus section A and B
Note: If 6.6kV switchgear or motor starters are arranged with double tier for contactor cubicles,
compartment number above will be followed by an additional suffix of -1 and -2.
Examples: 12-842-02-ESW-001A1 is a incoming compartment from the Bus Bar A of
132kV Switchgear at Substation of well pad #2, Compartment number 1.
12-845-12-ESW-001B3-2 is a outgoing contactor feeder compartment from Bus
Bar B of 6.6kV Switchgear at Substation in Well Pad #12 area, Compartment
number 3, below cubicle.

2.3.2. LV switchgear
LV switchgear compartments will be numbered as below (front elevation) :
A2-R1 A2-F1 B1-F1 B3-F1 B4-F1 B2-R1 B3-R1
A2-F1
A2-R2 A2-F2 B4-F2 B3-R2
A2-R3 A2-F3 B4-F3 B3-R3
A2-F2
A2-R4 A2-F4 B2-F2 B4-F4 B2-R2
A1 AB B1
A2-R5 A2-F5 B4-F5 B2-R3
A2-F3 A2-F6 B3-F2 B4-F6 B2-R4 B3-R4
A2-R6 A2-F7 B4-F7 B2-R5 B3-R5
A2-F4 A2-F8 B3-F3 B4-F8 B3-R6
Where A1: Busbar A incoming section
B1: Busbar B incoming section
AB: Coupling section
A2, B2: Columns
F, R: Front or rear location
Note: The number of cubicles in one compartment of feeder panel may be different as per
switchgear design by vendor.
LUKOILMID- EPC Well Pads and Oil Gathering System at CHINA PETROLEUM
EASTLIMITED the West Qurna (Phase 2) Contract Area PIPELINE BUREAU
Design Rules For Electrical Equipment Numbering Rev.: X1 Status: AB
COMPANY No.:
8015-0151-CPPB-00-000-EL-SP-00001-E Page: 8 of 15
Contractor No.:

Examples: 12-846-02-ESW-001B3-F5 is a outgoing feeder compartment from Bus Bar B of


400V Switchgear at Substation in Well Pad #2 area, Compartment number 3 of
front side.
12-846-12-ESW-001A4-R3 is a outgoing feeder compartment from Bus Bar A of
400V Switchgear at Substation in Well Pad #12 area, Compartment number 4 of
rear side.
3. IDENTIFICATION OF EQUIPMENT IN UNITS
3.1. Motors
Electrical motors shall be identified as per 8015-0151-CPPB-00-000-PM-PP-00002, Tag
Numbering Procedure

3.2. Parts of Package System


Electrical parts of package system shall be identified as per8015-0151-CPPB-00-000-PM-PP-
00002, Tag Numbering Procedure
All electrical parts not only installed on package skid but also supplied as loose parts from package
system shall be identified by their equipment number.
Unless otherwise specified in the procedure or equipment datasheet, those shall be identified by the
corresponding package identification followed by suffix as per Appendix 2.
If duplicate equipment of same function is supplied as loose part, additional sequence number can
be used on the suffix.
If not applicable to the suffix in Appendix 2, vendor shall notice it to Contractor and provide the
function and purpose of the electrical parts of system.

3.3. Local Control Stations


Local control station shall be identified by the corresponding motor or equipment identification
followed by -LCS.
Example: 22-830-00-HC-001A-LCS

3.4. Junction Boxes


Junction box shall be identified by the corresponding motor, lighting fixture or equipment
identification followed by -JB.
Example: 22-414-00-KE-001A-JB
In case that multiple branch circuits are combined in one junction box, the junction box shall be
identified by the representative equipment identification following by -JB.
In some cases a numeric suffix can be applied (e.g. JB1 and JB2).

3.5. Welding Sockets / Local Distribution Panels


Welding sockets and local power / lighting distribution panels will be identified as following:
LUKOILMID- EPC Well Pads and Oil Gathering System at CHINA PETROLEUM
EASTLIMITED the West Qurna (Phase 2) Contract Area PIPELINE BUREAU
Design Rules For Electrical Equipment Numbering Rev.: X1 Status: AB
COMPANY No.:
8015-0151-CPPB-00-000-EL-SP-00001-E Page: 9 of 15
Contractor No.:

12 - 851 - 02 - ELDP - 001

FLACILTY CODE
12 for Well Pad

UNIT/SYSTEM CODE
851 for nomal lighting system

SUBSTATION NUMBER
02 for substation #2

EQUIPMENT NUMBER
ELDP for lighting distribution panel

SEQUENTIAL NUMBER
Starting at 001

Examples: 12-851-02-ELDP-001 is a normal lighting distribution panel fed from Substation


in Well Pad #2 area.
12-851-12-EWS-001 is a welding socket outlet fed from Substation in Well Pad
#12 area.

3.6. Lighting Circuits and Fixtures, Convenience Outlets


* - 01 L 01 (R)

EQUIPMENT TAG NUMBER


Lighting or power distribution panel number

CIRCUIT NUMBER
Sequential number of circuit in panels

LETTER FOR CIRCUIT PORTION

CIRCUIT PORTION
Fixture or convenience outlet sequential nuber
Starting at 1

CORE IDENTIFICATION
Phase including single core cables
Refer to appendix 2

Examples: 12-851-02-ELDP-001-22L5 where 12-851-02-ELDP-001 is a number of


Lighting distribution panel, 22 is a circuit breaker number in Lighting distribution
panel, L5 is a circuit portion referred to below scheme.
LUKOILMID- EPC Well Pads and Oil Gathering System at CHINA PETROLEUM
EASTLIMITED the West Qurna (Phase 2) Contract Area PIPELINE BUREAU
Design Rules For Electrical Equipment Numbering Rev.: X1 Status: AB
COMPANY No.:
8015-0151-CPPB-00-000-EL-SP-00001-E Page: 10 of 15
Contractor No.:

3.7. Lighting Junction Boxes


Lighting and convenience outlet junction box shall be identified by its corresponding fixture or
convenience outlet identification.

4. OVERHEAD LINES
Numbering of overhead lines will be as follow:
12 - 812 - EOHL - 01 A

4.1 FLACILTY CODE


12 for Well Pad

4.2 UNIT/SYSTEM CODE


812 for Overhead lines 110/132kV

4.3 EQUIPMENT NUMBER


EOHL for overhead lines

4.4 OVERHEAD LINES


SEQUENTIAL NUMBER

4.5 LOCATION CODE

4.1. Facility Code


The facility code is defined in Appendix 2 of 8015-0151-SCPPB-00-000-PM-PP-00001 Document
Control Procedure.

4.2. Unit / System Code


The facility code is defined in Appendix 3 of 8015-0151-SCPPB-00-000-PM-PP-00001 Document
Control Procedure.
LUKOILMID- EPC Well Pads and Oil Gathering System at CHINA PETROLEUM
EASTLIMITED the West Qurna (Phase 2) Contract Area PIPELINE BUREAU
Design Rules For Electrical Equipment Numbering Rev.: X1 Status: AB
COMPANY No.:
8015-0151-CPPB-00-000-EL-SP-00001-E Page: 11 of 15
Contractor No.:

Especially following system codes will be allocated to various voltage system of switchgears.
- 812 Overhead LINES 110/132 kV
- 815 Overhead LINES 6.6 kV

4.3. Equipment number


The Equipment number is defined in appendix 1.

4.4. Sequential number


The number of overhead lines shall be identified with two numerical digits of tagging. For
132kV overhead lines 01 is the overhead lines from GTPP to Well pads #2,#5, #6 and 02 is
overhead lines from GTPP to Well pads #7, #8, #10,#12.
Following list and numbers define entire overhead lines in Well Pads, WQ-11 and WQ-13.

Overhead lines No. Overhead lines Name

12-812-EOHL-01 132kV Overhead lines for WP #2,5,6

12-812-EOHL-02 132kV Overhead lines for WP #7,8,10,12

11-815-EOHL-11 6.6kV Overhead lines for WQ-11

11-815-EOHL-13 6.6kV Overhead lines for WQ-13

4.5. Location Code


For 132kV OVERHEAD LINES,
A is conductor at left hand side tower in GTPP gantry and B is conductor at right hand
side tower in GTPP gantry

5. CATHODIC PROTECTION SYSTEM


5.1. Equipment for Cathodic System
Equipment for cathodic protection system will be identified as follow.
12 - 640 - 02 - ECRP - 001

FLACILTY CODE
12 for Well Pad

UNIT/SYSTEM CODE
640 for cathodic protection system

SUBSTATION NUMBER
02 for substation #2

EQUIPMENT NUMBER
Refer to appendix 1

SEQUENTIAL NUMBER
Starting at 001
LUKOILMID- EPC Well Pads and Oil Gathering System at CHINA PETROLEUM
EASTLIMITED the West Qurna (Phase 2) Contract Area PIPELINE BUREAU
Design Rules For Electrical Equipment Numbering Rev.: X1 Status: AB
COMPANY No.:
8015-0151-CPPB-00-000-EL-SP-00001-E Page: 12 of 15
Contractor No.:

Examples: 12-640-05-ECPR-001 is a rectifier fed from substation #1 in Well Pad #5

6. CABLES
Cables will be tagged as follow excluding lighting circuits, which is specified above.
* / H 1 (R)

ENDING EQUIPMENT TAG NUMBER

CALBE TYPE
Refer to appendix 2

SEQUENTIAL NUMBER

CORE IDENTIFICATION
Phase including single core cables
Refer to appendix 2

6.1. Sequential Number


Sequential number can be a letter or number. Letter type of sequential number is used for parallel
cables of one circuit and number type of sequential number is used for series cables of cascade
circuits.
Examples: 12-210-02-P-001A-M where 12-210-02-P-001A is a number of field equipment,
M is a cable type of 6.6kV medium voltage power. If the circuit has three of
parallel cables, then an additional suffix of letter A, B or C is followed by the
number of cable like 12-210-02-P-001A-MA, 12-210-02-P-001A-MB and 12-210-
02-P-001A-MC.
12-335-00-P-004A-C - where 12-335-00-P-004A is a number of field equipment, C
is a cable type of control. If the circuit is connected to three of series cables
through a junction box, then cables of secondary side of junction box has an
additional suffix of number 1, 2 or 3 followed by the number of cable like 12-335-
00-P-004A-C1, 12-335-00-P-004A-C2 and 12-335-00-P-004A-C3.

6.2. Core Identification


Core of cables is identified by an additional suffix followed by the cable number as specified in the
Appendix 2.
Examples: 12-414-00-KE-001A-C1-1 where 12-414-00-KE-001A is a number of field
equipment, first C1 is a cable type of control, which one of series cable and last
number is core number of multi core control cable.
12-210-01-P-001A-S-L - where 12-210-01-P-001A is a number of field equipment,
S is a cable type of space heater and L is a phase core of single phase power cable.
LUKOILMID- EPC Well Pads and Oil Gathering System at CHINA PETROLEUM
EASTLIMITED the West Qurna (Phase 2) Contract Area PIPELINE BUREAU
Design Rules For Electrical Equipment Numbering Rev.: X1 Status: AB
COMPANY No.:
8015-0151-CPPB-00-000-EL-SP-00001-E Page: 13 of 15
Contractor No.:

APPENDIX 1 EQUIPMENT NUMBER

CODE DESCRIPTION CODE DESCRIPTION

EAP ALARM ANNUNCIATOR PANEL ELDP LIGHTING DISTRIBUTION PANEL

EBA BATTERY (BANK) EM ELECTRIC MOTOR

EBC BATTERY CHARGER EMCC MOTOR CONTROL CENTER

EBD BUS DUCT EMEP METERING PANEL

ECA CAPACITOR (BANK) EMP MARSHALLING PANEL


NORMAL DAY & NIGHT LIGHT
ECB CIRCUIT BREAKER ENDLP
LOCAL PANEL
EMERGENCY MOTOR CONTROL NORMAL DAY & NIGHT LIGHT
ECC ENDJB
CENTER LOCAL MAIN JUNCTION BOX
ECP ELECTRICAL CONTROL PANEL ENI NEUTRAL IMPEDANCE
CATHODIC PROTECTION SYSTEM(CPS) NORMAL NIGHT LIGHT LOCAL
ECAJ ENNJB
ANODE JUNCTION BOX MAIN JUNCTION BOX
NORMAL NIGHT LIGHT LOCAL
ECCJ CPS CATHODIC JUNCTION BOX ENNLP
PANEL
ECPR CPS RECTIFIER EOHL OVERHEAD TRANSMISSION LINES

ECTB CPS TEST BOX EPCP PACKAGE CONTROL PANEL

ECT CURRENT TRANSFORMER EPDP POWER DISTRIBUTION PANEL


PROGRAMMABLE LOGIC
EDCP DC POWER DISTRIBUTION PANEL EPLC
CONTROLLER
EDG EMERGENCY DIESEL GENERATOR EPMS POWER MANAGEMENT SYSTEM
EMERGENCY POWER DISTRIBUTION
EDP EPRP PROTECTIVE RELAY PANEL
PANEL
PACKAGE STARTER PANEL
EDS DISCONNECTOR SWITCH EPST
(LOCAL)
EMERGENCY DAY & NIGHT LIGHT
EEDJB EREA REACTOR
LOCAL MAIN JUNCTION BOX
EMERGENCY DAY & NIGHT LIGHT
EEDLP ESA SURGE ARRESTER (HV)
LOCAL PANEL
EMERGENCY NIGHT LIGHT LOCAL
EENJB ESR SWITCHRACK
MAIN JUNCTION BOX
EMERGENCY NIGHT LIGHT LOCAL
EENLP ESS SUBSTATION
PANEL
EF VENTILATION FAN ESW SWITCHGEAR

EG GENERATOR ETH THERMOSTAT


LUKOILMID- EPC Well Pads and Oil Gathering System at CHINA PETROLEUM
EASTLIMITED the West Qurna (Phase 2) Contract Area PIPELINE BUREAU
Design Rules For Electrical Equipment Numbering Rev.: X1 Status: AB
COMPANY No.:
8015-0151-CPPB-00-000-EL-SP-00001-E Page: 14 of 15
Contractor No.:

HEAT TRACING DISTRIBUTION


EHDP ETP THYRISTOR POWER PANEL
PANEL
EIRP INTERPOSING RELAY PANEL ETR TRANSFORMER
AC OR DC UNINTERRUPTIBLE
EISO ISOLATOR EUP
POWER SUPPLY
EJB JUNCTION BOX EVSD VARIABLE SPEED DRIVE

ELB LOAD BANK EVT VOLTAGE TRANSFORMER


EMERGENCY LIGHTING DISTRIBUTION
ELP EWS WELDING SOCKET OUTLET
PANEL
ELT LINE TRAP (COUPLER) ESP ELECTRICAL SUBMERSIBLE PUMP
LUKOILMID- EPC Well Pads and Oil Gathering System at CHINA PETROLEUM
EASTLIMITED the West Qurna (Phase 2) Contract Area PIPELINE BUREAU
Design Rules For Electrical Equipment Numbering Rev.: X1 Status: AB
COMPANY No.:
8015-0151-CPPB-00-000-EL-SP-00001-E Page: 15 of 15
Contractor No.:

APPENDIX 2 EQUIPMENT NUMBER PREFIXES AND SUFFIXES

CODE DESCRIPTION

CABLES
...-C CONTROL
...-D DC POWER (125 V DC)
...-E GROUNDING
...-F FIBER OPTIC
...-H. HIGH VOLTAGE POWER (132 kV AC)
...-L LOW VOLTAGE POWER (0.4 / 0.23 kV AC)
...-M MEDIUM VOLTAGE POWER (33 / 6.6 kV AC)
...-S SPACE HEATER
...-Z SPECIAL

CABLE CORES
...-R PHASE CORE OF THREE PHASE
...-Y PHASE CORE OF THREE PHASE
...-B PHASE CORE OF THREE PHASE
...-L PHASE CORE OF SINGLE PHASE
...-N NEUTRAL
...-P PROTECTIVE EARTH
...-1 NUMERIC CODE FOR MULTI-CORE CONTROL CABLES

ELECTRICAL PARTS OF PACKAGE EQUIPMENT


...-TB CABLE CONNECTION BOX OR TERMINAL BOX
...-DS DISCONNECTOR SWITCH
...-ES EMERGENCY STOP PUSH BUTTON
...-JB JUNCTION BOX
...-LCP LOCAL CONTROL PANEL (GENERIC)
...-LSP LOCAL STARTER PANEL
...-LCS LOCAL CONTROL STATION
...-PB PUSH BUTTON BOX
...-RCP REMOTE CONTROL PANEL (GENERIC)
...-RSP REMOTE STARTER PANEL
...-RCS REMOTE CONTROL STATION