Using Broken Delta Protection for Earth Faults
Search
The  Broken  Delta  configuration  is  used  to  protect  against  earth  faults.  It  is  a  configuration  that  works  by
monitoring the vector sum of the phase voltages.
Like Us

It consists of a delta connection on the secondary of a potential transformer that is open at one point as in
the figure. In  such  a  construction,  when  a  balanced  three  phase  voltage  is  present  in  the  star  connected
primary, the voltage across the broken point of the delta connection would be zero, as it would be a vector
sum of all three voltages.
www.boilertechnik.com
In the event of a ground fault in one phase, the phase­to­ground voltage in the
remaining  two  phases  is  now  equal  to  the  phase­to­phase  voltage  with  a Blog Archive
displacement of 60 degrees. The voltage at the broken delta becomes 3Vo or
three times the phase­to­ground voltage. ►  2017 (4)
►  2016 (13)
This  voltage  can  be  measured  by  a  relay  and  can  be  used  to  trip  the  power
system. A resistor is usually connected across the broken delta connection to ►  2015 (257)
prevent  Ferro  resonance,  a  condition  that  occurs  when  the  line  capacitance ►  2014 (117)
and the inductance in the potential transformers reach a state of resonance.
►  2013 (36)
Broken  delta  transformers  are  usually  marked  as  11kV/√3:110  volts.  It  means ►  2012 (85)
that the transformer is designed that in the event of a ground fault in the primary
side, the secondary output will be 110 V. ►  2011 (84)
►  2010 (86)
▼  2009 (108)
Labels: broken, delta, earth, earth fault, ferroresonance, ingress protection, open, power, relay, systems ►  December (12)
►  November (9)
►  October (11)
Newer Post Home Older Post
►  September (15)
►  August (8)
Resource Pages
►  July (13)
Batteries Cables ►  June (15)
Motors Capacitors ►  May (5)
Transformers Alternators
►  April (9)
Earthing Fuses
▼  March (3)

Forum Dissolved Gas Analysis
List of Articles Ripples in dc systems
Using Broken Delta Protection
Popular Posts for Earth Faults

Voltage Classification ­ LV, MV and EHV ►  February (3)
AC voltages have been classified in various manners.  In earlier times, there were just two categories ►  January (5)
LV and HV.  As the level of voltages...
►  2008 (3)
►  2006 (5)
Tan Delta testing ­ Principle and Method
Tan Delta is a a diagnostic test conducted on the insulation of cables and windings. It is used to measure the
deterioration in the cable. ... About Us

Calculating the percentage impedance of a Transformer
The impedance of a transformer is defined as the percentage of the drop in voltage to the at full load
to the rated voltage of the transform...

B, C and D types in Miniature Circuit Breakers
MCBs (Miniature Circuit Breakers) are categorized into B, C and D types.  These three ratings are
determined by the level of overload whic...

Reverse Power Relay ­ Function and Operation
A reverse power relay is a directional power relay that is used to monitor the power from a generator
running in parallel with another gener...

http://www.electrotechnik.net/2009/03/using­broken­delta­protection­for­earth.html 1/1

You might also like