You are on page 1of 6

FTIM Installation guide

Fast Trip Input Module (FTIM)


for ADVC Controller Range

Scope of this document


This document describes the installation procedures for the FTIM
with ADVC Controller.
Limitations
This document is copyright and is provided solely for the use of the
purchaser. It is not to be copied in any way, nor its contents
divulged to any third party, nor to be used as the basis of a tender
or specification without the express written permission of the
manufacturer.
Disclaimer
The advisory procedures and information contained within this
document have been compiled as a guide to the safe and effective
operation of products supplied by Schneider Electric Recloser
Solutions.
It has been prepared in conjunction with references from sub-
assembly suppliers and the collective experience of the
manufacturer.
In-service conditions for use of the products may vary between
customers and end-users. Consequently, this document is offered
as a guide only. It should be used in conjunction with the customers
own safety procedures, maintenance program, engineering
judgment and training qualifications.
No responsibility, either direct or consequential, for injury or
equipment failure can be accepted by the manufacturer resulting
from the use of this document.
Copyright
© 2009 by Schneider Electric.
All rights reserved. No part of the contents of this document may be
reproduced or transmitted in any form or by any means without the
written permission of the manufacturer.

Document part number


ADVC2-1185

Schneider Electric (Australia) Pty Limited


80 Schneider Road,
Eagle Farm,
Qld 4009
AUSTRALIA
Tel: +61 7 3635 7500
Fax: +61 7 3635 7560
1 Introduction
The FTIM (Fast Trip Input Module) is an ADVC Controller Range accessory that accepts external control signals
from third party devices. It provides optically isolated inputs. These allow connection of an external protection relay
or Remote Terminal Unit (RTU). The electronic circuit is installed in a die cast, sealed enclosure which is attached
to the upper accessory mounting tray of an ADVC ULTRA controller.
It is possible to interface external trip, close or block signals to the recloser controller via the FTIM.

FTIM enclosure

Terminals
Output Isolated 12 Vdc power supply terminals
- Negative Isolated power source to
+ Positive external switches.

Inputs Optically isolated inputs

1 Fast Trip Input to trip the recloser

2 Fast Close Input to close the recloser

Input to block all trip and


3 Trip Block close commands.
Input to block all close
4 Close Block commands.

Controller connection

1.1 Compatibility
The FTIM is compatible with the ADVC Controller range. If a controller will be used with an FTIM, a connection
cable for the module has to be included during manufacturing. It is therefore necessary to specify the intended use
of an FTIM when ordering the controller. Note this connection cable cannot be retrofitted in the field.
An FTIM can be used with controllers displaying one of the following part numbers on the rating plate:
st nd rd th th th th th th th
Part number 1 2 3 4 5 6 7 8 9 10
88xxxx2xxx 8 8 x x x x 2 x x x
88xxxx3xxx 8 8 x x x x 3 x x x
88xxxx5xxx 8 8 x x x x 5 x x x

The part number has to start with “88” and the 7th digit must be a “2”, “3” or “5”.

1.2 Parts supplied with the FTIM


The following parts are supplied with each FTIM.
 1 x FTIM module Note:
 4 x M5 stainless steel screws The EMC gland and shielded
 4 x flat washers and 4 x spring washers cable are essential for
 1 x EMC cable gland reliable operation.

2 Specifications
Isolated power supply output: 12 – 15 Vdc , 100 mA max.
Optically isolated inputs: ON = 12 – 150 Vdc, 12 – 150 Vac.
OFF = 0 – 3 Vdc, 0 – 3 Vac.
Dimensions [mm]: 188 high, 119.5 wide, 37 deep.
Controller connection: Shielded cable with shielded 15 pin D-type connector.

FTIM Installation Guide (ADVC2-1185) Page 2 Schneider Electric


3 FTIM installation
The FTIM must be fitted to the upper accessory mounting tray.

3.1 Removing and installing the mounting tray


It is very easy to remove the upper accessory mounting tray:
1. Undo and remove the self locking nuts and washers;
3 2. Rotate the accessory tray to the slide-out position by lifting
Brackets
the bottom of the tray away from the cubicle; and
3. Slide the tray to your left.
Hinges
To install the upper tray, locate the accessory tray hinges to the left
of the brackets in the top corner of the cubicle. Use the corner as a
1 2 1 guide and slide the tray to your right. The self-locating hinges will
guide the tray into the brackets. Continue to slide the tray until the
Upper accessory tray removal
hinges are completely inside the brackets. Rotate the tray into the
lock-down position and fasten the nuts.

3.2 Attaching the FTIM


Method:
1. Remove the Upper Accessory Mounting Tray
from the ADVC ULTRA cubicle (see 3.1);
2. Two mounting options are provided on the tray
(Left and Right). Select a convenient option;
3. Align the FTIM to the 4 holes as indicated.
Using the screws and washers provided, Mounting
attach the FTIM to the tray. Tighten the screws option Right
to 4Nm of torque; and Mounting
4. Fit the tray and FTIM in the Upper Accessory option Left
Mounting Space using the existing mounting
points (see 3.1).

Mounting holes

3.3 Connect the FTIM to the controller


Turn all power to the controller OFF.
(See adjacent PSU photo).

Warning:
Failure to power OFF the
controller when connecting the
FTIM to CAPE may cause
unwanted trip/close operation.

Connect the shielded 15 pin D connector to the FTIM.


Fasten the connector properly to ensure a reliable
connection.

Turn all power to the controller ON when the


installation is complete.

FTIM Installation Guide (ADVC2-1185) Page 3 Schneider Electric


4 Electrical connections
4.1 Using the built-in isolated supply 4.2 Using an external source
The FTIM has a built-in isolated power supply that can It is also possible to use a custom AC or DC source for
be used as field excitation voltage. The following field excitation of the external switches. This supply
connection diagram describes using this DC voltage as must be isolated from earth.
a source to supply the external switches. Field excitation voltage: 12 Vac/dc up to 150 Vac/dc.

Warning: Warning:
Field excitation MUST NOT be The field excitation power
provided from the battery nor supply must be isolated from
the radio power supply. earth.

- -
+ +
Field excitation voltage
12 – 150 Vac/dc
FTIM FTIM
Fast Fast
1 Trip 1 Trip
Fast Fast
2 Close 2 Close
Trip Trip
3 Block 3 Block
Close Close
4 Block 4 Block

External External

SW SW SW SW SW SW SW SW
4 3 2 1 4 3 2 1

4.3 Shielded cable 4.4 Cable Gland Specification


For the external connections, shielded cable with the An M20 EMC cable gland with the following main
following main characteristics is recommended: characteristics is required:
Operating Temperature: -55°C to +105°C  Diameter, cable max: 12 mm
Voltage Rating: 600 V  Diameter, cable min: 6 mm
Product Description:  Diameter, cable screen min: 5 mm
 Conductor: Stranded Tinned Copper  Material: Brass
 Number of Cores: 10  Plating: Nickel
 Area Conductor: 0.22 mm²  Thread size: M20
 External Diameter: 7.2 mm  Length, thread: 8 mm
 Insulation: Colour-Coded PVC  IP Rating: IP68
 Shield: Braided Tinned Copper
(90% Coverage)
 Jacket: PVC

Picture of the EMC cable gland (supplied)


Picture of the shielded cable (not supplied)

FTIM Installation Guide (ADVC2-1185) Page 4 Schneider Electric


4.5 Customer Cable Installation
4.5.1 EMC gland installation
Note:
Correct installation of the
EMC gland is essential
for reliable operation.

Clamping ring Gland body


Sleeve
‘O’ ring

Seal Braid connection

Earth braid

Cable sheath

Method Illustrations

120 cm

At 120 cm from the cable-end that will be connected to the


1. FTIM, remove 2 cm of the plastic sheath to expose the
earth braid.

2 cm

Push the end of the cable that will be connected to the


FTIM through the cable gland in the direction as shown.

2.
Note:
Pushing the cable in the
opposite direction will
damage the gland.

FTIM Installation Guide (ADVC2-1185) Page 5 Schneider Electric


Method Illustrations
Continue pushing the cable through the gland, until the
2 cm
earth braid aligns with the gland.

3.

Ensure the earth braid is in contact with the braid


4.
connection ring in the gland.

Ensure the seal and clamping mechanism is overlapping


5. with the plastic sheath. Tighten the gland sleeve to firmly
grip the cable in place.

Select a 20mm hole in the base of the controller. The two


holes on the right hand side are provided for this purpose.

6. FTIM and IOEX


cable holes

Remove the plug and fit the cable with gland.


4.5.2 Cable termination
1. Use cable ties to secure the cable to the cubicle
Note:
wall.
Shielded cable is
2. Cut the cable to the appropriate length, and
essential for reliable
terminate the cable at the FTIM connectors. operation. See 4.3.

FTIM Installation Guide (ADVC2-1185) Page 6 Schneider Electric