Polyvinyl Chloride (PVC) Compounds
PVC compounds used for cords and cables with several grades of compounds are detailed in this standard
for both insulation and sheathing requirements. PVC compounds are thermoplastic by nature and
consequently are designed to operate within a prescribed temperature range. The majority of wiring
installations, however, use a general-purpose grade of PVC, which has a maximum operating temperature
of 70ºC (available in heat resisting PVC withstand to 90 o C) Sheath colours are normally grey, black or
white. Other colours can be provided on special order but experience has shown that for outdoor use
black has the highest resistance to direct sunlight, with other colours tending to fade in time under these
conditions.

PVC Power Cables (Armoured/Unarmoured)


Conductor : Copper or Aluminium
Applicable Standard : BS6004, BS6346, MS69, MS136, MS274
Voltage Rate : 300/500 & 450/750V
Range : Refer to Technical Data in following tables.

Notes : BS7671 Wiring Regulation – is currently adapted by Southern Cable in our product for new (harmonised)
requirement of color coding for insulation i.e : BROWN, BLACK, GREY, BLUE.
IEC60364 Electrical Installations for Buildings – is also standard to harmonize national wiring standards .

CROSSLINKED POLYETYLENE (XLPE) Compounds


XLPE have strong resistance to deformation even at high temperature. There are options for application
of heat, pressure or nature in the cross linking process. XLPE cables are suitable for transmission and
distribution lines because of its excellent electrical and physical properties. XLPE also has excellent
resistance to thermal deformation and aging property to permit the large carrying currents under
temperature of 90oC condition. XLPE cable is lighter in weight and smaller bending radius compare to
other kinds of cable, thus allowing for easy and reliable installation.

XLPE Power cables (Armoured/Unarmoured)


Conductor : Copper or Aluminium
Applicable Standards : BS 5467, IEC 60502 Part-1, MS2106, MS2107
Voltage Rate : 600/1000V
Range : Refer to Technical Data in following tables.

Notes : BS7671 Wiring Regulation – is currently adapted by Southern Cable in our product for new (harmonised)
requirement of color coding for insulation i.e : BROWN, BLACK, GREY, BLUE. IEC60364 Electrical Installations for
Buildings – is also standard to harmonize national wiring standards .
LOW VOLTAGE CABLES
PVC INSULATED NON-SHEATHED CABLES

PVC INSULATED PVC SHEATHED CABLES

PVC INSULATED PVC SHEATHED ARMOURED CABLES

XLPE INSULATED PVC SHEATHED CABLES

XLPE INSULATED PVC SHEATHED ARMOURED CABLES

PVC INSULATED PVC SHEATHED CABLES - AUXILIARY

PVC INSULATED PVC SHEATHED ARMOURED CABLES - AUXILIARY

XLPE INSULATED PVC SHEATHED CABLES - AUXILIARY

XLPE INSULATED COPPER TAPE SCREENED PVC SHEATHED CABLES - AUXILIARY

DC POWER CABLE (CLASS 5 FLEXIBLE COPPER CONDUCTORS)


LOW VOLTAGE CABLES

PVC INSULATED NON-SHEATHED CABLES

SPECIFICATION : MS 136 & BS 6004


VOLTAGE RATING : 450/750V
CONDUCTOR : PLAIN ANNEALED COPPER WIRE
INSULATION : GENERAL PURPOSE PVC COMPOUND

DIMENSIONAL

Nominal Nominal Max. conductor Min. insulation


No./Diameter of Mean Overall Cable weight
sectional Insulation resistance. DC at resistance at
Wires Diameter (mm) (approx.)
area Thickness 20°C 70°C

Core Identification: Required colour or Green with Yellow stripe (2stripe opposite each other and covering 30% of surface area of core)
Lower Upper
mm² No./mm mm kg/km Ω/km MΩ/km
Limit Limit

1.5 7/0.53 0.7 2.7 3.3 23 12.10 0.010

2.5 7/0.67 0.8 3.3 4.0 35 7.41 0.009

4 7/0.85 0.8 3.8 4.6 52 4.61 0.0077

6 7/1.04 0.8 4.3 5.2 73 3.08 0.0065

10 7/1.35 1 5.6 6.7 120 1.83 0.0065

16 7/1.70 1 6.4 7.8 181 1.15 0.0050

25 1.2 8.1 9.7 283 0.727 0.0050

35 min; 6 strands 1.2 9.0 10.9 377 0.524 0.0040

50 1.4 10.6 12.8 513 0.387 0.0045

70 min; 12 strands 1.4 12.1 14.6 721 0.268 0.0035

95 min; 15 strands 1.6 14.1 17.1 994 0.193 0.0035

120 1.6 15.6 18.8 1234 0.153 0.0032


min; 18 strands
150 1.8 17.3 20.9 1517 0.124 0.0032

185 min; 30 strands 2.0 19.3 23.3 1904 0.0991 0.0032

240 2.2 22.0 26.5 2485 0.0754 0.0032


min; 34 strands
300 2.4 24.5 29.6 3112 0.0601 0.0030

400 2.6 27.5 33.2 3960 0.0470 0.0028

500 min; 53 strands 2.8 30.5 36.9 4968 0.0366 0.0028

630 2.8 34.0 41.1 6325 0.0283 0.0025

http://www.southerncable.cc
All of the above information, including drawings, illustrations and graphic designs, reflects our present understanding and is to the best of our knowledge and belief correct and reliable. Users,
however, should independently evaluate the suitability of each product for the desired application. Under no circumstances does this constitute an assurance of any particular quality or
performance. Such an assurance is only provided in the context of our product specifications or explicit contractual arrangements. Our liability for these products is set forth in our standard terms
and conditions of sale.
LOW VOLTAGE CABLES

PVC INSULATED PVC SHEATHED CABLES

SPECIFICATION : MS 136 & BS 6004


VOLTAGE RATING : 300/500V
CONDUCTOR : PLAIN ANNEALED COPPER WIRE
INSULATION : GENERAL PURPOSE PVC COMPOUND
SHEATHING : GENERAL PURPOSE PVC COMPOUND

DIMENSIONAL
Nominal Max. conductor
Nominal No./Diameter of Nominal Sheath Cable weight Min. insulation
Insulation Mean Overall Diameter (mm) resistance. DC at
sectional area Wires Thickness (approx.) resistance at 70°C
Thickness 20°C

mm² No./mm mm mm Lower Limit Upper Limit kg/km Ω/km MΩ/km

1.0 1/1.13 0.6 3.8 4.5 27 18.10 0.011

1.25 3/0.73 4.2 4.9 35 14.60 0.011

1.5 1/1.38 0.7 0.8 4.3 5.0 36 12.10 0.011

1.5 7/0.53 4.3 5.1 38 12.10 0.010

2.5 7/0.67 5.0 6.0 54 7.41 0.009

4 7/0.85 0.8 5.4 6.8 75 4.61 0.0077

6 7/1.04 0.9 6.0 7.4 99 3.08 0.0065

10 7/1.35 7.2 8.8 152 1.83 0.0065


1.0
16 7/1.70 1.0 8.4 10.5 221 1.15 0.0052

25 10.0 12.5 337 0.727 0.0050


min; 7 strands 1.2 1.1
35 11.0 13.5 438 0.524 0.0044

Core Identification: Black

http://www.southerncable.cc
All of the above information, including drawings, illustrations and graphic designs, reflects our present understanding and is to the best of our knowledge and belief correct and reliable.
Users, however, should independently evaluate the suitability of each product for the desired application. Under no circumstances does this constitute an assurance of any particular
quality or performance. Such an assurance is only provided in the context of our product specifications or explicit contractual arrangements. Our liability for these products is set forth in
our standard terms and conditions of sale.
LOW VOLTAGE CABLES

PVC INSULATED PVC SHEATHED CABLES

SPECIFICATION : IEC 60502-1


VOLT. RATING : 600/1000V
CONDUCTOR : PLAIN ANNEALED COPPER WIRE
INSULATION : GENERAL PURPOSE PVC COMPOUND
SHEATHING : BLACK GENERAL PURPOSE PVC COMPOUND

DIMENSIONAL
Max. Current
Approx. Max.
Nominal Conductor Nominal Nominal Cable conductor Current rating In
Shape of Overall conductor Reactance
sectional dia. Insulation Sheath weight resistance In air at the
Conductor Diameter resistance at 50Hz
area (approx) Thickness Thickness (approx.) 50Hz at 40°C ground at
(mm) DC at 20°C
70°C 40°C
mm² mm mm mm mm kg/km Ω/km Ω/km Ω/km A A

10 3.7 9.0 170 1.83 2.19 0.115 52 75


1.0
16 4.7 10.0 230 1.15 1.38 0.107 69 98

25 5.9 12.0 340 0.727 0.870 0.102 90 125


1.2 1.4
35 7.0 13.0 440 0.524 0.627 0.0967 115 150

50 C 8.1 14.5 580 0.387 0.463 0.0950 140 175


I 1.4
70 R 9.7 16.0 800 0.268 0.321 0.0903 175 215
C
95 U 11.4 18.5 1080 0.193 0.232 0.0887 220 260
L 1.6 1.5
120 A 12.8 20.0 1330 0.153 0.184 0.0860 255 295
R
150 14.3 1.8 1.6 22.0 1630 0.124 0.150 0.0855 295 330
S
185 T 16.0 2.0 1.7 24.5 2040 0.0991 0.120 0.0850 340 375
R
240 A 18.4 2.2 1.8 27.5 2640 0.0754 0.0926 0.0836 405 435
N
300 D 20.6 2.4 1.9 30.5 3300 0.0601 0.0748 0.0831 470 490
E
400 D 23.3 2.6 2.0 33.5 4170 0.0470 0.0600 0.0819 550 555

500 26.30 2.1 37.0 5200 0.0366 0.0486 0.0807 635 630

630 29.8 2.8 2.2 40 6770 0.0283 0.0395 0.0773 760 720

800 37.05 2.3 48.5 8520 0.0221 0.0333 0.0757 865 795

1000 41.6 3.0 2.5 54.0 10700 0.0176 0.0290 0.0753 970 870

http://www.southerncable.cc
All of the above information, including drawings, illustrations and graphic designs, reflects our present understanding and is to the best of our knowledge and belief correct and reliable.
Users, however, should independently evaluate the suitability of each product for the desired application. Under no circumstances does this constitute an assurance of any particular
quality or performance. Such an assurance is only provided in the context of our product specifications or explicit contractual arrangements. Our liability for these products is set forth
in our standard terms and conditions of sale.
LOW VOLTAGE CABLES

PVC INSULATED PVC SHEATHED ARMOURED CABLES - 1 CORE

SPECIFICATION : BS6346 & MS274


VOLT. RATING : 600/1000V
CONDUCTOR : PLAIN ANNEALED COPPER WIRE
INSULATION : GENERAL PURPOSE PVC COMPOUND
INNER SHEATH : BLACK GENERAL PURPOSE PVC COMPOUND
ARMOURING : ALUMINUM WIRE
SHEATHING : BLACK GENERAL PURPOSE PVC COMPOUND

DIMENSIONAL
Nom. Sectional Area mm2 50 70 95 120 150 185 240 300 400 500 630 800 1000

CIRCULAR NON-
Shape of Conductor CIRCULAR COMPACTED
COMPACTED

Conductor dia (approx) mm 8.1 9.7 11.4 12.8 14.3 16.0 18.4 20.6 23.3 26.3 29.8 37.05 41.60

Nominal insulation
mm 1.4 1.6 1.8 2.0 2.2 2.4 2.6 2.8 3.0
thickness

Nominal Bedding Thickness mm 0.8 1.0 1.2 1.4

Bedding Dia. (Approx.) mm 12.6 14.2 16.3 18.1 20.0 22.2 25.0 27.7 31.2 34.6 40 45.8 50.8

Nom. Hard Drawn


mm 1.25 1.60 2.00 2.50
Aluminum Wire
Nominal Outer Sheath
mm 1.5 1.6 1.7 1.8 1.9 2.1 2.2 2.4 2.5
Thickness

Approx. Overall dia. mm 19.1 21.1 23.4 26.3 28.3 30.8 34.1 37.0 42.0 45.6 48 55.8 61.0

Cable weight (approx.) kg/km 740 980 1280 1620 1940 2380 3020 3690 4750 5820 7400 9560 11830

ELECTRICAL DATA
Nom. Sectional Area 2
mm 50 70 95 120 150 185 240 300 400 500 630 800 1000

Max. conductor Resistance


W/km 0.387 0.268 0.193 0.153 0.124 0.0991 0.0754 0.0601 0.0470 0.0366 0.0283 0.0221 0.0176
DC at 20OC

Trefoil 193 243 298 347 395 452 532 607 690 776 869 937 1010
Current Rating in Air at
A
30OC
Spaced* 223 279 339 386 433 486 555 618 666 718 778 819 873

Trefoil 203 248 297 337 376 423 485 542 600 660 721 756 797
Current Rating on
A
Ground at 15OC
Spaced* 211 257 305 341 377 417 469 515 549 586 627 648 679

Trefoil 0.82 0.58 0.44 0.36 0.31 0.27 0.23 0.20 0.19 0.18 0.16 0.16 0.15
Voltage Drop mV
Spaced* 0.87 0.65 0.52 0.45 0.41 0.38 0.35 0.33 0.32 0.31 0.31 - -

http://www.southerncable.cc
All of the above information, including drawings, illustrations and graphic designs, reflects our present understanding and is to the best of our knowledge and belief correct and reliable.
Users, however, should independently evaluate the suitability of each product for the desired application. Under no circumstances does this constitute an assurance of any particular quality
or performance. Such an assurance is only provided in the context of our product specifications or explicit contractual arrangements. Our liability for these products is set forth in our
standard terms and conditions of sale.
LOW VOLTAGE CABLES

PVC INSULATED PVC SHEATHED ARMOURED CABLES - 2 CORES

SPECIFICATION : BS6346 & MS274


VOLT. RATING : 600/1000V
CONDUCTOR : PLAIN ANNEALED COPPER WIRE Rd

INSULATION : GENERAL PURPOSE PVC COMPOUND


Blk
INNER SHEATH : BLACK GENERAL PURPOSE PVC COMPOUND
ARMOURING : GALVANIZED STEEL WIRE
SHEATHING : BLACK GENERAL PURPOSE PVC COMPOUND

DIMENSIONAL
Nom. Sectional
Area mm2 1.5 2.5 4 6 10 16 25 35 50 70 95 120 150 185 240 300 400

CIRCULAR NON- CIRCULAR


Shape of Conductor SHAPED STRANDED
COMPACTED COMPACTED
Nominal
mm 0.6 0.7 0.8 1.0 1.2 1.4 1.6 1.8 2.0 2.2 2.4 2.6
insulation
thickness
Nominal Bedding
mm 0.8 1.0 1.2 1.2 1.4 1.6
Thickness
Bedding Dia.
mm 7.3 8.6 10.3 11.4 13.4 15.4 16.3 17.7 20.5 23.1 26.9 28.9 31.7 35.7 40.1 44.7 49.1
(Approx.)
Nom. Galvanized
mm 0.9 0.9 0.9 0.9 1.25 1.25 1.6 1.6 1.6 1.6 2.0 2.0 2.0 2.5 2.5 2.5 2.5
Steel Wire
Nominal Outer
mm 1.4 1.5 1.6 1.7 1.8 1.9 2.1 2.2 2.3 2.4 2.5 2.7 2.9
Sheath Thickness
Approx. Overall
mm 12.3 13.6 15.1 16.5 20.1 21.9 23 24.9 27.8 30.4 35.5 38 41.3 46.4 51.2 56.4 61.9
dia.
Cable weight
kg/km 260 320 410 490 740 930 1300 1570 1970 2490 3480 4080 4810 6200 7730 9260 11330
(approx.)

ELECTRICAL DATA
Nom. Sectional
Area mm2 1.5 2.5 4 6 10 16 25 35 50 70 95 120 150 185 240 300 400

Max. conductor
Resistance DC at W/km 12.1 7.41 4.61 3.08 1.83 1.15 0.727 0.524 0.387 0.268 0.193 0.153 0.124 0.0991 0.0754 0.0601 0.0470
20OC
Current Rating in
A 23 32 42 54 74 102 136 166 201 252 312 360 409 473 558 636 729
Air at 30OC
Current Rating on
A 30 40 53 66 88 119 158 190 225 277 332 377 422 478 551 616 693
Ground at 15OC

Voltage Drop mV 29.0 18.0 12.0 7.40 4.30 2.80 1.70 1.30 0.94 0.66 0.49 0.40 0.34 0.29 0.24 0.21 0.19

http://www.southerncable.cc
All of the above information, including drawings, illustrations and graphic designs, reflects our present understanding and is to the best of our knowledge and belief correct and reliable. Users, however,
should independently evaluate the suitability of each product for the desired application. Under no circumstances does this constitute an assurance of any particular quality or performance. Such an
assurance is only provided in the context of our product specifications or explicit contractual arrangements. Our liability for these products is set forth in our standard terms and conditions of sale.
LOW VOLTAGE CABLES

PVC INSULATED PVC SHEATHED ARMOURED CABLES - 3 CORES

SPECIFICATION : BS6346 & MS274


VOLT. RATING : 600/1000V
CONDUCTOR : PLAIN ANNEALED COPPER WIRE Rd Ylw

INSULATION : GENERAL PURPOSE PVC COMPOUND


Blu
INNER SHEATH : BLACK GENERAL PURPOSE PVC COMPOUND
ARMOURING : GALVANIZED STEEL WIRE
SHEATHING : BLACK GENERAL PURPOSE PVC COMPOUND

DIMENSIONAL
Nom. 2
Sectional mm 1.5 2.5 4 6 10 16 25 35 50 70 95 120 150 185 240 300 400
Area CIRCULAR NON- CIRCULAR
Shape of Conductor SHAPED STRANDED
COMPACTED COMPACTED
Nominal
insulation mm 0.6 0.7 0.8 1.0 1.2 1.4 1.6 1.8 2.0 2.2 2.4 2.6
thickness
Nominal
Bedding mm 0.8 1.0 1.2 1.4 1.6
Thickness

Bedding Dia.
mm 7.8 9.1 10.9 12.2 14.3 16.4 18.6 20.6 23.8 27.2 31.6 33.7 37.0 41.6 47.2 52.0 57.6
(Approx.)

Nom.
Galvanized mm 0.9 1.25 1.6 2.0 2.5
Steel Wire
Nominal
Outer Sheath mm 1.4 1.5 1.6 1.7 1.8 1.9 2.0 2.1 2.2 2.4 2.5 2.6 2.8 3.0
Thickness

Approx.
mm 12.8 14.1 15.8 18 21.2 23.1 25 27.3 30.5 35 39.3 42.2 47.5 51.9 57.8 63.2 69.6
Overall dia.

Cable weight
kg/km 290 360 470 670 880 1140 1650 2040 2590 2630 4690 5530 6990 8440 10670 12770 15810
(approx.)

ELECTRICAL DATA
Nom.
Sectional mm2 1.5 2.5 4 6 10 16 25 35 50 70 95 120 150 185 240 300 400
Area
Max.
conductor
Resistance W/km 12.1 7.41 4.61 3.08 1.83 1.15 0.727 0.524 0.387 0.268 0.193 0.153 0.124 0.0991 0.0754 0.0601 0.0470
DC at 20OC
Current
Rating in Air A 20 27 36 46 63 87 116 142 172 218 268 310 355 407 480 547 627
at 30OC
Current
Rating on
Ground at A 26 34 45 57 75 101 132 159 188 233 279 317 355 401 462 517 580
15OC

Voltage Drop mV 25 16 9.6 6.3 3.8 2.4 1.5 1.1 0.82 0.57 0.42 0.35 0.29 0.25 0.21 0.18 0.17

http://www.southerncable.cc
All of the above information, including drawings, illustrations and graphic designs, reflects our present understanding and is to the best of our knowledge and belief correct and reliable. Users, however,
should independently evaluate the suitability of each product for the desired application. Under no circumstances does this constitute an assurance of any particular quality or performance. Such an
assurance is only provided in the context of our product specifications or explicit contractual arrangements. Our liability for these products is set forth in our standard terms and conditions of sale.
LOW VOLTAGE CABLES

PVC INSULATED PVC SHEATHED ARMOURED CABLES - 4 CORES

SPECIFICATION : BS6346 & MS274


VOLTAGE RATING : 600/1000V
CONDUCTOR : PLAIN ANNEALED COPPER WIRE
INSULATION : GENERAL PURPOSE PVC COMPOUND
INNER SHEATH : BLACK GENERAL PURPOSE PVC COMPOUND
ARMOURING : GALVANIZED STEEL WIRE
SHEATHING : BLACK GENERAL PURPOSE PVC COMPOUND

DIMENSIONAL
Nom.
Sectional mm2 1.5 2.5 4 6 10 16 25 35 50 70 95 120 150 185 240 300 400
Area CIRCULAR NON- CIRCULAR
Shape of Conductor SHAPED STRANDED
COMPACTED COMPACTED
Nominal
insulation mm 0.6 0.7 0.8 1.0 1.2 1.4 1.6 1.8 2.0 2.2 2.4 2.6
thickness
Nominal
Bedding mm 0.8 1.0 1.2 1.4 1.6
Thickness

Bedding Dia.
mm 8.5 10.0 12.1 13.4 15.8 18.6 20.4 22.7 26.6 30.1 34.6 37.8 42.0 47.3 52.9 59.0 66.0
(Approx.)

Nom.
Galvanized mm 0.9 1.25 1.6 2.0 2.5 3.15
Steel Wire
Nominal
Outer Sheath mm 1.4 1.5 1.6 1.7 1.8 1.9 2.0 2.1 2.2 2.4 2.5 2.6 2.8 3.0 3.3
Thickness

Approx.
mm 13.5 15 17.8 19.2 22.8 26.3 27.8 30.5 35.4 39.2 44.3 49.3 53.6 59 65.7 72 81.3
Overall dia.

Cable weight
kg/km 330 420 650 790 1050 1550 2020 2510 3460 4500 5810 7420 8820 10750 13550 16470 21260
(approx.)

ELECTRICAL DATA
Nom.
Sectional mm2 1.5 2.5 4 6 10 16 25 35 50 70 95 120 150 185 240 300 400
Area
Max.
conductor
Resistance W/km 12.1 7.41 4.61 3.08 1.83 1.15 0.727 0.524 0.387 0.268 0.193 0.153 0.124 0.0991 0.0754 0.0601 0.0470
DC at 20OC

Current
Rating in Air A 20 27 36 46 63 87 116 142 172 218 268 310 355 407 480 547 627
at 30OC

Current
Rating on
Ground at A 26 34 45 57 75 101 132 159 188 233 279 317 355 401 462 517 580
15OC

Voltage Drop mV 25 16 9.6 6.3 3.8 2.4 1.5 1.1 0.82 0.57 0.42 0.35 0.29 0.25 0.21 0.18 0.17

http://www.southerncable.cc
All of the above information, including drawings, illustrations and graphic designs, reflects our present understanding and is to the best of our knowledge and belief correct and reliable. Users,
however, should independently evaluate the suitability of each product for the desired application. Under no circumstances does this constitute an assurance of any particular quality or
performance. Such an assurance is only provided in the context of our product specifications or explicit contractual arrangements. Our liability for these products is set forth in our standard
terms and conditions of sale.
LOW VOLTAGE CABLES

PVC INSULATED PVC SHEATHED ARMOURED CABLES - 1 CORE

SPECIFICATION : IEC60502-1
VOLTAGE RATING : 600/1000V
CONDUCTOR : PLAIN ANNEALED COPPER WIRE
INSULATION : GENERAL PURPOSE PVC COMPOUND
INNER SHEATH : BLACK GENERAL PURPOSE PVC COMPOUND
ARMOURING : ALUMINUM WIRE
SHEATHING : BLACK GENERAL PURPOSE PVC COMPOUND

DIMENSIONAL
Nom. Sectional
Area mm2 10 16 25 35 50 70 95 120 150 185 240 300 400 500 630 800 1000

CIRCULAR
Shape of Conductor CIRCULAR COMPACTED
STRANDED
Conductor dia
mm 3.7 4.7 5.9 7.0 8.1 9.7 11.4 12.8 14.3 16.0 18.4 20.6 23.3 26.3 29.8 37.1 41.6
(approx)

Nominal insulation
mm 1.0 1.2 1.4 1.6 1.8 2.0 2.2 2.4 2.6 2.8 3.0
thickness

Nominal Bedding
mm 1.0 1.2 1.4
Thickness

Bedding Dia.
mm 7.9 8.9 10.5 11.6 13.0 14.6 16.7 18.1 20.0 22.2 25.0 27.7 31.2 34.6 41.1 45.8 50.8
(Approx.)

Nom. Hard Drawn


mm 1.0 1.25 1.6 2.0 2.5
Aluminum Wire

Nominal Outer
mm 1.8 1.9 2.0 2.1 2.2 2.4 2.5 2.7
Sheath Thickness

Approx. Overall
mm 13.5 14.5 16.0 17.5 19.5 21.0 23.0 25.0 27.0 29.5 32.5 36.0 39.5 43.5 50.5 56.0 61.5
dia.

Cable weight
kg/km 280 360 480 600 790 1020 1330 1640 1960 2380 3020 3800 4750 5850 7580 9580 11900
(approx.)

ELECTRICAL DATA
Nom. Sectional 2
mm 10 16 25 35 50 70 95 120 150 185 240 300 400 500 630 800 1000
Area
Max. conductor
Resistance DC at W/km 1.83 1.150 0.727 0.193 0.153 0.124 0.153 0.124 0.0991 0.0754 ##### 0.0283 0.0470 0.0366 0.0283 0.0221 0.0176
20OC
Max. conductor
Resistance DC at W/km 2.19 1.38 0.870 0.627 0.463 0.321 0.232 0.184 0.149 0.120 ##### 0.0743 0.0593 0.0478 0.0387 0.0323 0.0279
70OC

Reactance at 50
A 0.141 0.130 0.123 0.116 0.113 0.107 0.103 0.101 0.0988 0.0967 ##### 0.0939 0.0923 0.0902 0.0859 0.0849 0.0837
Hz

Current Rating in
A 57 73 73 100 125 190 235 275 310 360 430 500 580 670 795 910 1020
Air at 40OC

Current Rating on
A 80 105 135 155 180 220 265 300 335 380 440 500 570 645 735 820 900
Ground at 25OC

http://www.southerncable.cc
All of the above information, including drawings, illustrations and graphic designs, reflects our present understanding and is to the best of our knowledge and belief correct and reliable. Users,
however, should independently evaluate the suitability of each product for the desired application. Under no circumstances does this constitute an assurance of any particular quality or
performance. Such an assurance is only provided in the context of our product specifications or explicit contractual arrangements. Our liability for these products is set forth in our standard
terms and conditions of sale.
LOW VOLTAGE CABLES

PVC INSULATED PVC SHEATHED ARMOURED CABLES - 2 CORES

SPECIFICATION : IEC60502-1
VOLTAGE RATING : 600/1000V
CONDUCTOR : PLAIN ANNEALED COPPER WIRE Rd
INSULATION : GENERAL PURPOSE PVC COMPOUND
INNER SHEATH : BLACK GENERAL PURPOSE PVC COMPOUND Blk
ARMOURING : GALVANIZED STEEL WIRE
SHEATHING : BLACK GENERAL PURPOSE PVC COMPOUND

DIMENSIONAL
Nom.
Sectional mm2 1.5 2.5 4 6 10 16 25 35 50 70 95 120 150 185 240 300 400
Area CIRCULAR NON- CIRCULAR
Shape of Conductor SHAPED STRANDED
COMPACTED COMPACTED
Nominal
insulation mm 0.8 1.0 1.2 1.4 1.6 1.8 2.0 2.2 2.4 2.6
thickness
Nominal
Bedding mm 1.0 1.2 1.4 1.6
Thickness

Bedding Dia.
mm 8.7 9.6 11.5 12.6 13.8 15.8 16.3 17.7 20.5 23.1 26.9 28.9 31.7 35.7 40.1 44.7 49.1
(Approx.)

Nom.
Galvanized mm 0.9 1.6 2.0 2.5
Steel Wire
Nominal
Outer Sheath mm 1.8 1.9 2.0 2.2 2.3 2.4 2.6 2.8 2.9 3.2
Thickness
Approx.
mm 14.0 15.0 17.0 18.0 19.0 21.0 23.0 24.5 27.5 31.0 35.5 37.5 40.5 46.0 50.5 55.5 60.5
Overall dia.

Cable weight
kg/km 340 380 490 570 680 870 1310 1570 1970 2700 3500 4110 4830 6240 7810 9320 11420
(approx.)

ELECTRICAL DATA
Nom.
Sectional mm2 1.5 2.5 4 6 10 16 25 35 50 70 95 120 150 185 240 300 400
Area
Max.
conductor
Resistance W/km 12.1 7.41 4.61 3.08 1.83 1.15 0.727 0.524 0.387 0.268 0.193 0.153 0.124 0.0991 0.0754 0.0601 0.0470
DC at 20OC
Max.
conductor
Resistance W/km 14.48 8.87 5.52 3.69 2.19 1.38 0.870 0.627 0.464 0.321 0.232 0.185 0.150 0.121 0.0931 0.0755 0.0610
DC at 70OC
Reactance at
A 0.107 0.0994 0.0983 0.0928 0.0886 0.0834 0.0879 0.0847 0.0851 0.0812 0.0805 0.0786 0.0788 0.0789 0.0780 0.0788 0.0772
50 Hz
Current
Rating in Air A 21 28 37 47 63 84 105 130 155 200 245 280 320 370 435 495 560
at 40OC
Current
Rating on
Ground at A 30 39 51 64 85 110 140 165 195 240 290 330 365 415 475 535 595
25OC
http://www.southerncable.cc
All of the above information, including drawings, illustrations and graphic designs, reflects our present understanding and is to the best of our knowledge and belief correct and reliable. Users,
however, should independently evaluate the suitability of each product for the desired application. Under no circumstances does this constitute an assurance of any particular quality or performance.
Such an assurance is only provided in the context of our product specifications or explicit contractual arrangements. Our liability for these products is set forth in our standard terms and conditions of
sale.
LOW VOLTAGE CABLES

PVC INSULATED PVC SHEATHED ARMOURED CABLES - 3 CORES

SPECIFICATION : IEC60502-1
VOLTAGE RATING : 600/1000V
CONDUCTOR : PLAIN ANNEALED COPPER WIRE Yl
Rd
INSULATION : GENERAL PURPOSE PVC COMPOUND
Bl
INNER SHEATH : BLACK GENERAL PURPOSE PVC COMPOUND
ARMOURING : GALVANIZED STEEL WIRE
SHEATHING : BLACK GENERAL PURPOSE PVC COMPOUND

DIMENSIONAL
Nom. Sectional
Area mm2 1.5 2.5 4 6 10 16 25 35 50 70 95 120 150 185 240 300 400

CIRCULAR NON- CIRCULAR


Shape of Conductor SHAPED STRANDED
COMPACTED COMPACTED
Nominal
insulation mm 0.8 1.0 1.2 1.4 1.6 1.8 2.0 2.2 2.4 2.6
thickness
Nominal
Bedding mm 1.0 1.2 1.4 1.6
Thickness
Bedding Dia.
mm 9.3 10.2 12.2 13.4 14.7 16.8 18.6 20.6 23.8 27.2 31.6 33.7 37.0 41.6 47.2 52.0 57.6
(Approx.)
Nom.
Galvanized mm 0.9 1.6 2.0 2.5 3.15
Steel Wire
Nominal Outer
Sheath mm 1.8 2.0 2.1 2.2 2.3 2.5 2.7 2.9 3.1 3.4
Thickness
Approx. Overall
mm 14.5 15.5 17.5 19.0 20.0 22.0 25.5 27.5 31.0 35.5 40.0 42.0 47.0 52.0 58.0 63.0 70.5
dia.
Cable weight
kg/km 370 430 560 660 820 1070 1670 2050 2610 3650 4720 5560 7010 8490 10750 12870 16680
(approx.)

ELECTRICAL DATA
Nom. Sectional
Area mm2 1.5 2.5 4 6 10 16 25 35 50 70 95 120 150 185 240 300 400

Max. conductor
Resistance DC W/km 12.1 7.41 4.61 3.08 1.83 1.15 0.727 0.524 0.387 0.268 0.193 0.153 0.124 0.0991 0.0754 0.0601 0.0470
at 20OC

Max. conductor
Resistance DC W/km 14.48 8.87 5.52 3.69 2.19 1.38 0.870 0.627 0.463 0.321 0.232 0.185 0.150 0.121 0.0928 0.0751 0.0603
at 70OC

Reactance at
A 0.107 0.0994 0.0983 0.0928 0.0886 0.0834 0.0879 0.0847 0.0851 0.0812 0.0805 0.0786 0.0788 0.0789 0.0780 0.0788 0.0772
50 Hz
Current Rating
A 18 23 31 40 53 71 94 115 140 175 215 245 280 325 380 435 490
in Air at 40OC
Current Rating
on Ground at A 25 33 43 54 72 93 120 140 170 205 245 280 310 350 400 450 490
25OC
http://www.southerncable.cc
All of the above information, including drawings, illustrations and graphic designs, reflects our present understanding and is to the best of our knowledge and belief correct and reliable. Users,
however, should independently evaluate the suitability of each product for the desired application. Under no circumstances does this constitute an assurance of any particular quality or
performance. Such an assurance is only provided in the context of our product specifications or explicit contractual arrangements. Our liability for these products is set forth in our standard terms
and conditions of sale.
LOW VOLTAGE CABLES

PVC INSULATED PVC SHEATHED ARMOURED CABLES - 4 CORES

SPECIFICATION : IEC60502-1
VOLTAGE RATING : 600/1000V
CONDUCTOR : PLAIN ANNEALED COPPER WIRE
INSULATION : GENERAL PURPOSE PVC COMPOUND
INNER SHEATH : BLACK GENERAL PURPOSE PVC COMPOUND
ARMOURING : GALVANIZED STEEL WIRE
SHEATHING : BLACK GENERAL PURPOSE PVC COMPOUND

DIMENSIONAL
Nom. 2
1.5 2.5 4 6 10 16 25 35 50 70 95 120 150 185 240 300 400
Sectional Area mm
CIRCULAR NON- CIRCULAR
Shape of Conductor SHAPED STRANDED
COMPACTED COMPACTED
Nominal
insulation mm 0.8 1.0 1.2 1.4 1.6 1.8 2.0 2.2 2.4 2.6
thickness
Nominal
Bedding mm 1.0 1.2 1.4 1.6 1.8
Thickness
Bedding Dia.
mm 10.1 11.2 13.4 14.8 16.2 18.6 20.4 22.7 26.6 30.1 34.6 37.8 42.0 47.3 52.9 59.0 66.0
(Approx.)
Nom.
Galvanized mm 0.9 1.6 2.0 2.5 3.15
Steel Wire
Nominal Outer
Sheath mm 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.9 2.1 2.2 2.4 2.5 2.7 2.9 3.1 3.3 3.6
Thickness
Approx.
mm 15.5 16.5 19.0 20.0 21.5 25.5 27.0 29.5 34.5 38.5 44.5 47.5 52.5 58.0 64.0 72.0 79.5
Overall dia.

Cable weight
kg/km 430 500 650 790 980 1560 2030 2520 3480 4520 6220 7440 8880 10830 13650 17240 21390
(approx.)

ELECTRICAL DATA
Nom. 2
1.5 2.5 4 6 10 16 25 35 50 70 95 120 150 185 240 300 400
Sectional Area mm
Max.
conductor W/km 12.1 7.41 4.61 3.08 1.83 1.15 0.727 0.524 0.387 0.268 0.193 0.153 0.124 0.0991 0.0754 0.0601 0.0470
Resistance
DC at 20OC
Max.
conductor W/km 14.48 8.87 5.52 3.69 2.19 1.38 0.870 0.627 0.463 0.321 0.232 0.185 0.150 0.121 0.0928 0.0751 0.0603
Resistance
DC at 70OCat
Reactance
A 0.107 0.0994 0.0983 0.0928 0.0886 0.0834 0.0879 0.0847 0.0851 0.0812 0.0805 0.0786 0.0788 0.0789 0.0780 0.0788 0.0772
50 Hz

Current Rating
A 18 23 31 40 53 71 94 115 140 175 215 245 280 325 380 435 490
in Air at 40OC

Current Rating
on Ground at A 25 33 43 54 72 93 120 140 170 205 245 280 310 350 400 450 490
25OC

http://www.southerncable.cc
All of the above information, including drawings, illustrations and graphic designs, reflects our present understanding and is to the best of our knowledge and belief correct and reliable. Users,
however, should independently evaluate the suitability of each product for the desired application. Under no circumstances does this constitute an assurance of any particular quality or performance.
Such an assurance is only provided in the context of our product specifications or explicit contractual arrangements. Our liability for these products is set forth in our standard terms and conditions of
sale.
LOW VOLTAGE CABLES

XLPE INSULATED PVC SHEATHED NON-ARMOURED CABLES

SPECIFICATION : IEC 60502-1


VOLT. RATING : 600/1000V
CONDUCTOR : PLAIN ANNEALED COPPER WIRE
INSULATION : BLACK PVC COMPOUND TYPE ST2

DIMENSIONAL

Nominal Max. Max. Current


Nominal Nominal Approx. Cable Current Short circuit
Shape of Conductor outer- conductor conductor Reactance at rating in
sectional Insulation Overall weight rating in air current for 1
Conductor dia.(approx) sheath resistance. DC resistance. 50Hz ground at
area Thickness dia. (approx.) at 40°C sec
Thickness at 20°C 50Hz at 90°C 25°C

mm² mm mm mm mm kg/km Ω/km Ω/km Ω/km A A kA

10 3.7 8.5 150 1.83 2.33 0.110 68 89 1.5


0.7
16 4.7 9.5 210 1.15 1.47 0.102 91 115 2.4

25 5.9 11.0 310 0.727 0.927 0.0979 120 145 3.7


0.9 1.4
35 7.0 12.5 410 0.524 0.669 0.0934 150 170 5.2
C
I
50 R 8.1 1.0 13.5 540 0.387 0.494 0.0905 185 205 7.4
C
70 U 9.7 15.5 750 0.268 0.342 0.0870 235 250 10.2
L 1.1
95 A 11.4 17.5 1020 0.193 0.247 0.0851 290 295 13.8
R 1.5
120 12.8 1.2 19.0 1270 0.153 0.196 0.0837 340 340 17.4
C
O
150 M 14.3 1.4 21.0 1560 0.124 0.160 0.0837 390 380 21.8
P 1.6
185 A 16.0 1.6 23.0 1930 0.0991 0.128 0.0826 455 430 26.8
C
240 T 18.4 1.7 1.7 26.0 2510 0.0754 0.0988 0.0812 545 495 34.7
E
D
300 20.6 1.8 1.8 28.5 3120 0.0601 0.0801 0.0801 630 560 43.4

400 23.3 2.0 1.9 32.0 3970 0.0470 0.0643 0.0792 735 635 57.7

500 26.3 2.2 2.0 35.5 4980 0.0366 0.0521 0.0785 850 715 72.1

630 29.80 2.4 2.2 40.0 6510 0.0283 0.0428 0.0776 985 800 90.8

800 37.05 2.6 2.3 48.0 8260 0.0221 0.0363 0.0759 1150 895 115.2
CIRCULAR
STRANDED
1000 41.6 2.8 2.4 53.0 10350 0.0176 0.0317 0.0749 1280 970 143.9

Core Identification: Natural

All of the above information, including drawings, illustrations and graphic designs, reflects our present understanding and is to the best of our knowledge and belief correct and
reliable. Users, however, should independently evaluate the suitability of each product for the desired application. Under no circumstances does this constitute an assurance of any
particular quality or performance. Such an assurance is only provided in the context of our product specifications or explicit contractual arrangements. Our liability for these products is
set forth in our standard terms and conditions of sale.
LOW VOLTAGE CABLES

XLPE INSULATED PVC SHEATHED NON-ARMOURED CABLES - 2 CORES

SPECIFICATION : IEC 60502-1


VOLTAGE RATING : 600/1000V
CONDUCTOR : PLAIN ANNEALED COPPER WIRE
INSULATION : XLPE (CROSS-LINKED POLYETHYLENE)
SHEATHING : BLACK PVC COMPOUND TYPE ST2

DIMENSIONAL
Nominal
mm² 1.5 2.5 4 6 10 16 25 35 50 70 95 120 150 185 240 300 400
sectional area
Shape of
CIRCULAR STRANDED CIRCULAR COMPACTED
Conductor

Conductor dia
mm 1.59 2.01 2.55 3.12 3.70 4.70 5.90 7.00 8.00 9.70 11.40 12.80 14.30 15.80 18.30 20.50 23.30
(approx)

Nominal
insulation mm 0.7 0.9 1.0 1.1 1.2 1.4 1.6 1.7 1.8 2.0
thickness

Nominal sheath
mm 1.8 2.0 2.1 2.2 2.3 2.5 2.7 2.9
thickness

Approx. Overall
mm 10 11 12 13 14.5 16.5 17 18.5 20.5 24 27 29.5 32.5 36 40.5 44.5 49.5
dia.

Cable weight
kg/km 110 140 180 230 330 460 640 830 1090 1520 2060 2570 3150 3920 5130 6290 8050
(approx.)

ELECTRICAL CHARACTERISTIC
Nominal
mm² 1.5 2.5 4 6 10 16 25 35 50 70 95 120 150 185 240 300 400
sectional area
Max. conductor
resistance. DC Ω/km 12.10 7.41 4.61 3.08 1.83 1.15 0.727 0.524 0.387 0.268 0.193 0.153 0.124 0.0991 0.0754 0.0601 0.0470
at 20°C
Max. conductor
resistance. 50Hz Ω/km 15.43 9.45 5.88 3.93 2.33 1.47 0.927 0.669 0.494 0.342 0.247 0.196 0.16 0.128 0.0987 0.0780 0.0640
at 90°C

Reactance at
Ω/km 0.103 0.0961 0.0899 0.0853 0.0785 0.0771 0.0776 0.0752 0.0744 0.0731 0.0713 0.0713 0.0719 0.0720 0.0713 0.0707 0.0704
50Hz

Current In air at
A 25 32 44 57 79 100 135 165 205 255 315 370 420 485 580 665 770
40°C
Current rating In
the ground at A 35 45 60 76 98 125 160 195 230 285 340 385 435 490 565 640 725
25°C

Short circuit
kA 0.255 0.409 0.636 0.935 1.52 2.41 3.72 5.18 7.36 10.2 13.8 17.4 21.8 26.8 34.7 43.4 57.7
current for 1sec

http://www.southerncable.cc
All of the above information, including drawings, illustrations and graphic designs, reflects our present understanding and is to the best of our knowledge and belief correct and reliable. Users, however,
should independently evaluate the suitability of each product for the desired application. Under no circumstances does this constitute an assurance of any particular quality or performance. Such an
assurance is only provided in the context of our product specifications or explicit contractual arrangements. Our liability for these products is set forth in our standard terms and conditions of sale.
LOW VOLTAGE CABLES

XLPE INSULATED PVC SHEATHED NON-ARMOURED CABLES - 3 CORES

SPECIFICATION : IEC 60502-1


VOLT. RATING : 600/1000V
CONDUCTOR : PLAIN ANNEALED COPPER WIRE
INSULATION : XLPE (CROSS-LINKED POLYETHYLENE)
SHEATHING : BLACK PVC COMPOUND TYPE ST2

DIMENSIONAL
Nominal
mm² 1.5 2.5 4 6 10 16 25 35 50 70 95 120 150 185 240 300 400
sectional
Shape of
CIRCULAR STRANDED CIRCULAR COMPACTED
Conductor

Conductor
mm 1.59 2.01 2.55 3.12 3.70 4.70 5.90 7.00 8.00 9.70 11.40 12.80 14.30 15.80 18.30 20.50 23.30
dia (approx)

Nominal
insulation mm 0.7 0.9 1.0 1.1 1.2 1.4 1.6 1.7 1.8 2.0
thickness
Nominal
sheath mm 1.8 1.9 2.0 2.1 2.3 2.4 2.6 2.8 3.1
thickness

Approx.
mm 10.5 11.5 12.5 14 15.5 17.5 19 21.5 24 27.5 31.5 34 37.5 42 47 51.5 58
Overall dia.

Cable
weight kg/km 130 170 230 300 430 620 900 1190 1570 2230 3010 3760 4610 5760 7540 9240 11880
(approx.)

ELECTRICAL CHARACTERISTIC
Nominal
mm² 1.5 2.5 4 6 10 16 25 35 50 70 95 120 150 185 240 300 400
sectional
Max.
conductor
Ω/km 12.10 7.41 4.61 3.08 1.83 1.15 0.727 0.524 0.387 0.268 0.193 0.153 0.124 0.0991 0.0754 0.0601 0.0470
resistance.
DC at 20°C
Max.
conductor
Ω/km 15.43 9.45 5.88 3.93 2.33 1.47 0.927 0.669 0.494 0.343 0.248 0.197 0.16 0.129 0.0996 0.0809 0.0653
resistance.
50Hz at
90°C
Reactance
Ω/km 0.103 0.0961 0.0899 0.0853 0.0785 0.0771 0.0776 0.0752 0.0744 0.0731 0.0713 0.0713 0.0719 0.0720 0.0713 0.0707 0.0704
at 50Hz

Current In
A 21 26 37 48 65 87 115 140 175 220 270 315 360 420 495 570 655
air at 40°C

Current
rating In the
A 28 37 48 60 81 105 135 160 190 235 285 325 365 410 475 535 605
ground at
25°C

Short circuit
current for kA 0.255 0.409 0.636 0.935 1.52 2.41 3.72 5.18 7.36 10.2 13.8 17.4 21.8 26.8 34.7 43.4 57.7
1sec

http://www.southerncable.cc
All of the above information, including drawings, illustrations and graphic designs, reflects our present understanding and is to the best of our knowledge and belief correct and reliable. Users, however,
should independently evaluate the suitability of each product for the desired application. Under no circumstances does this constitute an assurance of any particular quality or performance. Such an
assurance is only provided in the context of our product specifications or explicit contractual arrangements. Our liability for these products is set forth in our standard terms and conditions of sale.
LOW VOLTAGE CABLES

XLPE INSULATED PVC SHEATHED NON-ARMOURED CABLES - 4 CORES

SPECIFICATION : IEC 60502-1


VOLTAGE RATING : 600/1000V
CONDUCTOR : PLAIN ANNEALED COPPER WIRE
INSULATION : XLPE (CROSS-LINKED POLYETHYLENE)
SHEATHING : BLACK PVC COMPOUND TYPE ST2

DIMENSIONAL
Nominal
sectional mm² 1.5 2.5 4 6 10 16 25 35 50 70 95 120 150 185 240 300 400
area
Shape of
CIRCULAR STRANDED CIRCULAR COMPACTED
Conductor

Conductor
mm 1.59 2.01 2.55 3.12 3.70 4.70 5.90 7.00 8.00 9.70 11.40 12.80 14.30 15.80 18.30 20.50 23.30
dia (approx)

Nominal
insulation mm 0.7 0.9 1.0 1.1 1.2 1.4 1.6 1.7 1.8 2.0
thickness

Nominal
sheath mm 1.8 1.9 2.0 2.1 2.3 2.4 2.6 2.8 3.0 3.3
thickness

Approx.
mm 11.5 12.5 13.5 15 17 19.5 21 23.5 26.5 30.5 34.5 38 42.5 47.5 53 59 66.5
Overall dia.

Cable weight
kg/km 160 210 280 380 550 800 1160 1550 2060 2910 3940 4970 6090 7620 9980 12250 15740
(approx.)

ELECTRICAL CHARACTERISTIC
Nominal
sectional mm² 1.5 2.5 4 6 10 16 25 35 50 70 95 120 150 185 240 300 400
area
Max.
conductor
Ω/km 12.10 7.41 4.61 3.08 1.83 1.15 0.727 0.524 0.387 0.268 0.193 0.153 0.124 0.0991 0.0754 0.0601 0.0470
resistance.
DC at 20°C
Max.
conductor
Ω/km 15.43 9.45 5.88 3.93 2.33 1.47 0.927 0.669 0.494 0.343 0.248 0.197 0.16 0.129 0.0996 0.0809 0.0653
resistance.
50Hz at 90°C
Reactance at
Ω/km 0.103 0.0961 0.0899 0.0853 0.0785 0.0771 0.0776 0.0752 0.0744 0.0731 0.0713 0.0713 0.0719 0.0720 0.0713 0.0707 0.0704
50Hz
Current In air
A 21 26 37 48 65 87 115 140 175 220 270 315 360 420 495 570 655
at 40°C
Current
rating In the A 28 37 48 60 81 105 135 160 190 235 285 325 365 410 475 535 605
ground at
25°C
Short circuit
current for kA 0.255 0.409 0.636 0.935 1.52 2.41 3.72 5.18 7.36 10.2 13.8 17.4 21.8 26.8 34.7 43.4 57.7
1sec

http://www.southerncable.cc
All of the above information, including drawings, illustrations and graphic designs, reflects our present understanding and is to the best of our knowledge and belief correct and reliable. Users, however, should
independently evaluate the suitability of each product for the desired application. Under no circumstances does this constitute an assurance of any particular quality or performance. Such an assurance is only
provided in the context of our product specifications or explicit contractual arrangements. Our liability for these products is set forth in our standard terms and conditions of sale.
LOW VOLTAGE CABLES

XLPE INSULATED PVC SHEATHED ARMOURED CABLES

SPECIFICATION : IEC 60502-1


VOLTAGE RATING : 600/1000V
CONDUCTOR : PLAIN ANNEALED COPPER WIRE
ARMOURING : ALUMINUM WIRE
INSULATION : BLACK PVC COMPOUND TYPE ST2

DIMENSIONAL
Max.
Nominal Nominal Max. Current Short
Conductor Nominal Nominal Approx. Approx. Cable conductor Current
Nominal Shape of of hard- outer- conductor Reactance rating in circuit
dia. Insulation Bedding Bedding Overall weight resistance. rating in
sect. area Cond. drawn sheath resistance. at 50Hz ground at current
(approx) Thick. Thick. dia. dia. (approx.) 50Hz at air at 40°C
AL Wire Thickness DC at 20°C 25°C for 1 sec
90°C

mm² mm mm mm mm mm mm mm kg/km Ω/km Ω/km Ω/km A A kA

10 3.7 7.3 13.0 260 1.83 2.33 0.137 27 90 1.52


0.7
16 4.7 8.0 14.0 330 1.15 1.47 0.126 100 115 2.41

25 5.9 9.7 15.5 450 0.727 0.93 0.119 135 150 3.72
0.9
35 7.0 10.8 16.5 560 0.524 0.668 0.113 165 170 5.18
C
I
50 8.1 1.0 12.1 18.0 710 0.387 0.494 0.113 200 205 7.36
R
C 1.8
70 U 9.7 13.9 1.6 20.0 940 0.268 0.342 0.107 255 250 10.2
L 1.1 1.0
95 A 11.4 15.6 21.5 1210 0.193 0.247 0.102 310 300 13.8
R
120 12.8 1.2 17.2 24.5 1560 0.153 0.196 0.101 365 340 17.4
C
O
150 M 14.3 1.4 19.2 26.5 1870 0.124 0.159 0.0999 415 385 21.8
P
185 A 16.0 1.6 21.3 28.5 2270 0.0991 0.128 0.0975 480 435 26.8
C
T
240 18.4 1.7 23.9 31.0 2890 0.0754 0.0982 0.0946 570 500 34.7
E
D 1.9
300 20.6 1.8 26.3 33.5 3520 0.0601 0.0793 0.0923 650 565 43.4

400 23.3 2.0 29.9 2.0 2.1 38.5 4550 0.0470 0.0632 0.0920 760 635 57.7

500 26.3 2.2 1.2 33.3 2.2 42.0 5620 0.0366 0.0509 0.0903 870 715 72.1

630 29.8 2.4 40.3 2.3 49.5 7290 0.0283 0.0415 0.0878 995 800 90.8

800 37.05 2.6 45.4 2.5 2.5 55.5 9320 0.0221 0.0347 0.0863 1150 890 115.2
CIRCULAR
STRANDED
1.4
1000 41.6 2.8 50.3 2.7 61.0 11580 0.0176 0.0300 0.0847 1250 940 143.9

http://www.southerncable.cc
All of the above information, including drawings, illustrations and graphic designs, reflects our present understanding and is to the best of our knowledge and belief correct and reliable. Users, however,
should independently evaluate the suitability of each product for the desired application. Under no circumstances does this constitute an assurance of any particular quality or performance. Such an
assurance is only provided in the context of our product specifications or explicit contractual arrangements. Our liability for these products is set forth in our standard terms and conditions of sale.
LOW VOLTAGE CABLES

XLPE INSULATED PVC SHEATHED ARMOURED CABLES - 2 CORES

SPECIFICATION : IEC 60502-1


Rd
VOLTAGE RATING : 600/1000V
CONDUCTOR : PLAIN ANNEALED COPPER WIRE
ARMOURING : GALVANIZED STEEL WIRE
Blk
INSULATION : BLACK PVC COMPOUND TYPE ST2

DIMENSIONAL ELECTRICAL
Max. Max. Current Current
Nominal
Cond. Nom. Nom. Approx. Nominal Approx. Cable conductor Short circuit
Nom. Shape of outer- conductor Reactance rating in rating in
dia. Insulation Bedding Bedding of gal. Overall weight resistance. current for 1
area Cond. sheath resistance. at 50Hz air at ground at
(approx) Thick. Thick. dia. steel wire dia. (approx.) 50Hz at sec
Thick. DC at 20°C 40°C 25°C
90°C

mm² mm mm mm mm mm mm mm kg/km Ω/km Ω/km Ω/km A A kA

1.5 1.59 8.9 14.0 320 12.1 15.43 0.103 29 33 0.255


0.9
2.5 2.01 9.7 14.5 370 7.41 9.45 0.0961 38 45 0.409
CIRCULAR NON
- COMPACTED
4 2.55 10.8 16.5 500 4.61 5.88 0.0899 45 59 0.636
0.7
6 3.12 11.9 17.5 590 3.08 3.93 0.0853 58 75 0.935
1.25
10 3.7 13.5 1.8 19.0 730 1.83 2.33 0.0808 79 98 1.52
CIRCULAR
COMPACTED
1.0
16 4.5 15.5 21.0 920 1.15 1.47 0.0780 105 125 2.41

25 15.9 22.5 1210 0.727 0.927 0.0770 140 160 3.72


0.9
35 17.3 23.5 1460 0.524 0.669 0.0767 170 195 5.18
1.6
50 1.0 19.5 26.0 1790 0.387 0.494 0.0746 210 230 7.36

70 22.6 2.0 29.5 2360 0.268 0.342 0.0738 260 280 10.2
1.1
95 24.6 2.1 33.5 3220 0.193 0.247 0.0726 320 335 13.8

SHAPED
120 STRANDED 1.2 1.2 25.6 2.0 2.2 36.0 3850 0.153 0.196 0.0720 370 380 17.4

150 1.4 28.0 2.3 39.0 4550 0.124 0.160 0.0719 425 425 21.8

185 1.6 30.8 2.5 44.5 5870 0.0991 0.1280 0.0713 485 480 26.8
1.4
240 1.7 38.6 2.7 48.5 7320 0.0754 0.0987 0.0709 575 555 34.7
2.5
300 1.8 42.6 2.8 53.0 8720 0.0601 0.0798 0.0707 650 620 43.4
1.6
400 2.0 47.0 3.1 58.0 10750 0.0470 0.0640 0.0704 745 695 57.7

http://www.southerncable.cc
All of the above information, including drawings, illustrations and graphic designs, reflects our present understanding and is to the best of our knowledge and belief correct and reliable. Users, however, should
independently evaluate the suitability of each product for the desired application. Under no circumstances does this constitute an assurance of any particular quality or performance. Such an assurance is only provided in
the context of our product specifications or explicit contractual arrangements. Our liability for these products is set forth in our standard terms and conditions of sale.
LOW VOLTAGE CABLES

XLPE INSULATED PVC SHEATHED ARMOURED CABLES - 3 CORES

SPECIFICATION : IEC 60502-1


VOLT. RATING : 600/1000V
CONDUCTOR : PLAIN ANNEALED COPPER WIRE Ylw
Rd
INSULATION : XLPE (CROSS-LINKED POLYETHYLENE)
Blu
ARMOURING : GALVANIZED STEEL WIRE
SHEATH : BLACK PVC COMPOUND TYPE ST2

DIMENSIONAL ELECTRICAL

Nom. Max. Max. Current Current Short


Cond. Nom. Nom. Approx. Nominal of Approx. Cable
Nom. outer- conductor conductor Reactance rating in rating in circuit
Shape of Cond. dia. Insulation Bedding Bedding galvanized Overall weight
area sheath resistance. resistance. at 50Hz air at ground at current for
(approx) Thick. Thick. dia. steel wire dia. (approx.)
Thick. DC at 20°C 50Hz at 90°C 40°C 25°C 1 sec

mm² mm mm mm mm mm mm mm kg/km Ω/km Ω/km Ω/km A A kA

1.5 1.59 9.4 0.9 14.5 360 12.1 15.43 0.103 21 28 0.255

2.5 2.01 10.3 16.0 480 7.41 9.45 0.0961 27 37 0.409


CIRCULAR NON-
COMPACTED
4 2.55 11.4 17.0 570 4.61 5.88 0.0899 38 48 0.636
0.7
6 3.12 12.7 1.25 1.8 18.5 680 3.08 3.93 0.0853 49 60 0.935

10 3.7 1.0 14.3 20.0 860 1.83 2.33 0.0808 65 81 1.52


CIRCULAR
COMPACTED
16 4.5 16.5 22.0 1110 1.15 1.47 0.0780 89 105 2.41

25 18.0 24.5 1550 0.727 0.927 0.0770 120 135 3.72


0.9
35 20.1 1.6 26.5 1920 0.524 0.669 0.0767 145 160 5.18
1.9
50 S 1.0 22.6 29.0 2400 0.387 0.494 0.0746 175 190 7.36
H
A
70 26.6 2.0 34.0 3420 0.268 0.343 0.0738 225 235 10.2
P
1.1
E
95 D 1.2 30.1 2.0 2.2 38.0 4390 0.193 0.248 0.0726 275 280 13.8

120 S 1.2 32.6 2.3 41.0 5230 0.153 0.197 0.0720 315 320 17.4
T
R 0.124 0.160 0.0719 365 355 21.8
150 1.4 35.9 2.5 45.5 6640
A
1.4
N
185 D 1.6 40.3 2.6 50.0 8020 0.0991 0.1290 0.0713 420 405 26.8
E
240 D 1.7 45.4 2.5 2.8 55.5 10140 0.0754 0.0996 0.0709 490 465 34.7

300 1.8 1.6 49.5 3.0 60.5 12080 0.0601 0.0809 0.0707 555 515 43.4

400 2.0 55.2 3.2 66.5 15020 0.0470 0.0653 0.0704 635 580 57.7

http://www.southerncable.cc
All of the above information, including drawings, illustrations and graphic designs, reflects our present understanding and is to the best of our knowledge and belief correct and reliable. Users, however, should
independently evaluate the suitability of each product for the desired application. Under no circumstances does this constitute an assurance of any particular quality or performance. Such an assurance is only
provided in the context of our product specifications or explicit contractual arrangements. Our liability for these products is set forth in our standard terms and conditions of sale.
LOW VOLTAGE CABLES

XLPE INSULATED PVC SHEATHED ARMOURED CABLES - 4 CORES

SPECIFICATION : IEC 60502-1


VOLTAGE RATING : 600/1000V
CONDUCTOR : PLAIN ANNEALED COPPER WIRE
INSULATION : XLPE (CROSS-LINKED POLYETHYLENE)
ARMOURING : GALVANIZED STEEL WIRE
SHEATH : BLACK PVC COMPOUND TYPE ST2

DIMENSIONAL ELECTRICAL
Max.
Nom. Max. Current Current Short
Cond. Nom. Nom. Approx. Nominal of Approx. Cable conductor
Nom. Shape of outer- conductor Reactance rating in rating in circuit
dia. Insulation Bedding Bedding galvanized Overall weight resistance.
area Conductor sheath resistance. at 50Hz air at ground current
(approx) Thick. Thick. dia. steel wire dia. (approx.) 50Hz at
Thick. DC at 20°C 40°C at 25°C for 1 sec
90°C

mm² mm mm mm mm mm mm mm kg/km Ω/km Ω/km Ω/km A A kA

1.5 1.59 10.2 0.9 15.0 400 12.1 15.43 0.103 21 28 0.255

2.5 2.01 11.2 17.0 540 7.41 9.45 0.0961 27 37 0.409


CIRCULAR NON -
COMPACTED
4 2.55 12.5 18.0 660 4.61 5.88 0.0899 38 48 0.636
0.7 1.25
6 3.12 13.9 1.8 19.5 790 3.08 3.93 0.0853 49 60 0.935

10 3.7 1.0 15.8 21.5 1010 1.83 2.33 0.0808 65 81 1.52


CIRCULAR
COMPACTED
16 4.7 18.2 24.5 1460 1.15 1.47 0.0780 89 105 2.41

25 19.9 26.5 1890 0.727 0.927 0.0770 120 135 3.72


0.9 1.6
35 22.2 1.9 29.0 2360 0.524 0.669 0.0767 145 160 5.18

50 S 1.0 24.9 2.0 32.0 2970 0.387 0.494 0.0746 175 190 7.36
H
70 A 29.5 2.2 37.5 4270 0.268 0.343 0.0738 225 235 10.2
P
1.1 1.2 2.0
E
95 D 33.1 2.3 41.5 5450 0.193 0.248 0.0726 275 280 13.8

120 S 1.2 36.6 2.5 46.5 7010 0.153 0.197 0.0720 315 320 17.4
T
R
150 1.4 1.4 40.9 2.6 51.0 8400 0.124 0.160 0.0719 365 355 21.8
A
N
185 D 1.6 45.6 2.5 2.8 56.0 10180 0.0991 0.1290 0.0713 420 405 26.8
E
240 D 1.7 51.1 3.0 62.0 12900 0.0754 0.0996 0.0709 490 465 34.7
1.6
300 1.8 56.6 3.2 67.5 15470 0.0601 0.0809 0.0707 555 515 43.4

400 2.0 1.8 63.5 3.15 3.5 76.5 20230 0.0470 0.0653 0.0704 635 580 57.7

http://www.southerncable.cc
All of the above information, including drawings, illustrations and graphic designs, reflects our present understanding and is to the best of our knowledge and belief correct and reliable. Users, however,
should independently evaluate the suitability of each product for the desired application. Under no circumstances does this constitute an assurance of any particular quality or performance. Such an
assurance is only provided in the context of our product specifications or explicit contractual arrangements. Our liability for these products is set forth in our standard terms and conditions of sale.
LOW VOLTAGE CABLES

PVC INSULATED PVC SHEATHED CABLES 1.5 mm2 (AUXILIARY)

SPECIFICATION : IEC 60502-1


VOLTAGE RATING : 600/1000V
CONDUCTOR : PLAIN ANNEALED COPPER WIRE
INSULATION : GENERAL PURPOSE PVC COMPOUND
SHEATHING : BLACK GENERAL PURPOSE PVC COMPOUND

1.5 mm²
DIMENSIONAL

No. of cores 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18

Shape of
CIRCULAR STRANDED
Conductor

Conductor
mm 1.59
dia (approx)

Nominal
insulation mm 0.8
thickness
Nominal
sheath mm 1.8
thickness
Approx.
mm 11.0 11.5 12.5 13.5 14.5 15.5 16.5 18.0 18.5 19.5 20.0 21.0
Overall dia.

Cable
weight kg/km 140 170 200 240 270 280 330 370 400 420 450 480 510 550 570 610 630
(approx.)

DIMENSIONAL

No. of cores 19 20 21 22 23 24 25 26 27 28 29 30 37 40 48 50

Shape of
CIRCULAR STRANDED
Conductor

Conductor
mm 1.59
dia (approx)

Nominal
insulation mm 0.8
thickness
Nominal
sheath mm 1.8 1.9
thickness
Approx.
mm 21.0 22.0 22.5 23.0 23.5 24.5 25.0 25.5 26.0 28.0 29.0 32.0
Overall dia.

Cable
weight kg/km 650 690 710 750 790 810 840 860 890 910 950 970 1160 1250 1500 1550
(approx.)

Max Conductor Resistance DC at 20°C =12.10Ω/km

Core Identification: Black numbers white cores(for 2cores up to 48cores)

For 50 cores, White insulation with number 1 - 28 and Red insulation with number 1 - 22

http://www.southerncable.cc
All of the above information, including drawings, illustrations and graphic designs, reflects our present understanding and is to the best of our knowledge and belief correct and reliable. Users, however, should
independently evaluate the suitability of each product for the desired application. Under no circumstances does this constitute an assurance of any particular quality or performance. Such an assurance is only
provided in the context of our product specifications or explicit contractual arrangements. Our liability for these products is set forth in our standard terms and conditions of sale.
LOW VOLTAGE CABLES

PVC INSULATED PVC SHEATHED CABLES 2.5 mm2 (AUXILIARY)

SPECIFICATION : IEC 60502-1


VOLT. RATING : 600/1000V
CONDUCTOR : PLAIN ANNEALED COPPER WIRE
INSULATION : GENERAL PURPOSE PVC COMPOUND
SHEATHING : BLACK GENERAL PURPOSE PVC COMPOUND

2.5mm²
DIMENSIONAL

No. of cores 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18

Shape of
CIRCULAR STRANDED
Conductor

Conductor
mm 2.01
dia (approx)

Nominal
insulation mm 0.8
thickness
Nominal
sheath mm 1.8
thickness

Approx.
mm 12.0 12.5 13.5 14.5 15.5 17.0 18.0 19.5 20.0 20.5 21.0 21.5 22.0 23.0 23.5
Overall dia.

Cable
weight kg/km 170 210 250 300 350 370 430 490 520 560 600 640 680 730 760 810 850
(approx.)

DIMENSIONAL

No. of cores 19 20 21 22 23 24 25 26 27 28 29 30 37 40 48 50

Shape of
CIRCULAR STRANDED
Conductor

Conductor
mm 2.01
dia (approx)

Nominal
insulation mm 0.8
thickness
Nominal
sheath mm 1.8 1.9 2.0
thickness

Approx.
mm 23.5 24.0 24.5 25.0 25.5 27.0 27.5 28.0 28.5 31.5 32.5 36.0
Overall dia.

Cable
weight kg/km 870 920 960 1010 1060 1090 1120 1160 1200 1240 1280 1320 1600 1730 2060 2130
(approx.)
Max Conductor Resistance DC at 20°C =7.41Ω/km

Core Identification: Black numbers white cores(for 2cores up to 48cores)

For 50 cores, White insulation with number 1 - 28 and Red insulation with number 1 - 22

http://www.southerncable.cc
All of the above information, including drawings, illustrations and graphic designs, reflects our present understanding and is to the best of our knowledge and belief correct and reliable. Users, however, should
independently evaluate the suitability of each product for the desired application. Under no circumstances does this constitute an assurance of any particular quality or performance. Such an assurance is only provided
in the context of our product specifications or explicit contractual arrangements. Our liability for these products is set forth in our standard terms and conditions of sale.
LOW VOLTAGE CABLES

PVC INSULATED PVC SHEATHED CABLES 4 mm2 (AUXILIARY)

SPECIFICATION : IEC 60502-1


VOLTAGE RATING : 600/1000V
CONDUCTOR : PLAIN ANNEALED COPPER WIRE
INSULATION : GENERAL PURPOSE PVC COMPOUND
SHEATHING : BLACK GENERAL PURPOSE PVC COMPOUND

4 mm²
DIMENSIONAL

No. of cores 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18

Shape of CIRCULAR STRANDED


Conductor

Conductor mm 2.55
dia (approx)
Nominal
insulation mm 1.0
thickness
Nominal
sheath mm 1.8
thickness

Approx.
mm 14.0 14.5 16.0 17.0 18.5 20.0 21.5 23.5 24.0 24.5 25.5 26.0 26.5 27.5 28.0
Overall dia.

Cable
weight kg/km 230 290 360 440 510 540 630 720 770 830 890 950 1010 1090 1140 1220 1270
(approx.)

DIMENSIONAL

No. of cores 19 20 21 22 23 24 25 26 27 28 29 30 37 40 48 50

Shape of
CIRCULAR STRANDED
Conductor

Conductor
mm 2.55
dia (approx)

Nominal
insulation mm 1.0
thickness
Nominal
sheath mm 1.8 1.9 2.0 2.1 2.3
thickness

Approx.
mm 28.0 29.0 29.5 30.5 31.5 33.0 34.0 34.5 35.5 28.0 39.5 44.0
Overall dia.

Cable
weight kg/km 1300 1390 1450 1540 1620 1670 1720 1780 1860 1910 1980 2040 2460 2670 3200 3310
(approx.)

Max Conductor Resistance DC at 20°C =4.61Ω/km

Core Identification: Black numbers white cores(for 2cores up to 48cores)

For 50 cores, White insulation with number 1 - 28 and Red insulation with number 1 - 22

http://www.southerncable.cc
All of the above information, including drawings, illustrations and graphic designs, reflects our present understanding and is to the best of our knowledge and belief correct and reliable. Users, however,
should independently evaluate the suitability of each product for the desired application. Under no circumstances does this constitute an assurance of any particular quality or performance. Such an
assurance is only provided in the context of our product specifications or explicit contractual arrangements. Our liability for these products is set forth in our standard terms and conditions of sale.
LOW VOLTAGE CABLES

2
PVC INSULATED PVC SHEATHED ARMOURED CABLES - 1.5 mm (AUXILIARY)

SPECIFICATION : BS6346 & MS274


VOLTAGE RATING : 600/1000V
CONDUCTOR : PLAIN ANNEALED COPPER WIRE
INSULATION : GENERAL PURPOSE PVC COMPOUND
INNER SHEATH : BLACK GENERAL PURPOSE PVC COMPOUND
ARMOURING : GALVANIZED STEEL WIRE
SHEATHING : BLACK GENERAL PURPOSE PVC COMPOUND

1.5 mm²
DIMENSIONAL
No. of cores 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19

Shape of Conductor CIRCULAR STRANDED

Conductor dia (approx) mm 1.59

Nominal insulation thickness mm 0.6

Nominal Bedding Thickness mm 0.8

Bedding Dia. (Approx.) mm 10.2 11.1 12.0 12.9 14.0 14.5 14.8 15.3 15.7 16.1 16.6 17.0

Nom. Galvanized Steel Wire mm 0.9 1.25

Nominal Outer Sheath


mm 1.4 1.5 1.6
Thickness

Approx. Overall dia. mm 14.4 15.3 16.4 18.0 19.1 19.6 20.1 20.6 21.0 21.4 21.9 22.3

Cable weight (approx.) kg/km 390 440 450 510 650 700 720 760 800 840 880 910 960 990 1000

DIMENSIONAL
No. of cores 20 21 22 23 24 25 26 27 28 29 30 37 40 48 50

Shape of Conductor CIRCULAR STRANDED

Conductor dia (approx) mm 1.59

Nominal insulation thickness mm 0.6

Nominal Bedding Thickness mm 0.8

Bedding Dia. (Approx.) mm 17.6 17.9 18.9 19.3 20.4 20.9 21.1 21.7 23.4 24.3 26.9

Nom. Galvanized Steel Wire mm 1.25 1.60

Nominal Outer Sheath


mm 1.6 1.7 1.8 1.9
Thickness

Approx. Overall dia. mm 22.9 23.2 25.1 25.5 26.6 27.1 27.4 27.9 29.8 30.7 33.5

Cable weight (approx.) kg/km 1060 1090 1300 1350 1400 1430 1450 1490 1510 1540 1580 1810 1930 2230 2270

http://www.southerncable.cc
All of the above information, including drawings, illustrations and graphic designs, reflects our present understanding and is to the best of our knowledge and belief correct and reliable. Users, however, should independently
evaluate the suitability of each product for the desired application. Under no circumstances does this constitute an assurance of any particular quality or performance. Such an assurance is only provided in the context of our
product specifications or explicit contractual arrangements. Our liability for these products is set forth in our standard terms and conditions of sale.
LOW VOLTAGE CABLES

PVC INSULATED PVC SHEATHED ARMOURED CABLES - 2.5 mm2 (AUXILIARY)

SPECIFICATION : BS6346 & MS274


VOLTAGE RATING : 600/1000V
CONDUCTOR : PLAIN ANNEALED COPPER WIRE
INSULATION : GENERAL PURPOSE PVC COMPOUND
INNER SHEATH : BLACK GENERAL PURPOSE PVC COMPOUND
ARMOURING : GALVANIZED STEEL WIRE
SHEATHING : BLACK GENERAL PURPOSE PVC COMPOUND

2.5mm²
DIMENSIONAL
No. of cores 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19

Shape of Conductor CIRCULAR STRANDED

Conductor dia (approx) mm 2.01

Nominal insulation thickness mm 0.7

Nominal Bedding Thickness mm 0.8 1.0

Bedding Dia. (Approx.) mm 11.8 12.9 14.0 15.1 16.5 17.1 17.4 18.4 18.9 19.5 20.0 20.5

Nom. Galvanized Steel Wire mm 0.9 1.25 1.60

Nominal Outer Sheath


mm 1.5 1.6 1.7
Thickness

Approx. Overall dia. mm 16.2 18.0 19.1 20.4 21.8 22.4 22.7 24.6 25.1 25.7 26.3 26.8

Cable weight (approx.) kg/km 510 650 670 760 850 920 950 1000 1050 1260 1330 1380 1440 1490 1510

DIMENSIONAL
No. of cores 20 21 22 23 24 25 26 27 28 29 30 37 40 48 50

Shape of Conductor CIRCULAR STRANDED

Conductor dia (approx) mm 2.01

Nominal insulation thickness mm 0.7

Nominal Bedding Thickness mm 1.0 1.2

Bedding Dia. (Approx.) mm 21.2 21.6 22.3 22.7 24.1 24.4 24.7 25.0 25.6 27.8 29.3 32.3

Nom. Galvanized Steel Wire mm 1.6 2.0

Nominal Outer Sheath


mm 1.8 1.9 2.0 2.1
Thickness

Approx. Overall dia. mm 27.6 28.1 28.7 29.2 30.6 31.1 31.6 32.3 34.4 36.9 40.2

Cable weight (approx.) kg/km 1590 1650 1710 1770 1860 1890 1920 1980 2010 2070 2140 2460 2880 3330 3400

http://www.southerncable.cc
All of the above information, including drawings, illustrations and graphic designs, reflects our present understanding and is to the best of our knowledge and belief correct and reliable. Users, however, should independently
evaluate the suitability of each product for the desired application. Under no circumstances does this constitute an assurance of any particular quality or performance. Such an assurance is only provided in the context of our
product specifications or explicit contractual arrangements. Our liability for these products is set forth in our standard terms and conditions of sale.
LOW VOLTAGE CABLES

PVC INSULATED PVC SHEATHED ARMOURED CABLES - 4 mm2 (AUXILIARY)

SPECIFICATION : BS6346 & MS274


VOLTAGE RATING : 600/1000V
CONDUCTOR : PLAIN ANNEALED COPPER WIRE
INSULATION : GENERAL PURPOSE PVC COMPOUND
INNER SHEATH : BLACK GENERAL PURPOSE PVC COMPOUND
ARMOURING : GALVANIZED STEEL WIRE
SHEATHING : BLACK GENERAL PURPOSE PVC COMPOUND

4 mm²
DIMENSIONAL
No. of cores 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19

Shape of Conductor CIRCULAR STRANDED

Conductor dia (approx) mm 2.55

Nominal insulation thickness mm 0.8

Nominal Bedding Thickness mm 0.8 1.0

Bedding Dia. (Approx.) mm 13.8 15.1 16.5 18.2 19.9 20.6 20.9 21.7 22.3 22.9 23.6 24.2

Nom. Galvanized Steel Wire mm 1.25 1.60

Nominal Outer Sheath


mm 1.5 1.6 1.7 1.8
Thickness

Approx. Overall dia. mm 18.9 20.4 21.8 24.4 26.1 26.8 27.1 28.1 28.7 29.4 30.1 30.7

Cable weight (approx.) kg/km 750 860 890 1000 1280 1380 1430 1510 1580 1670 1760 1820 1930 2000 2020

DIMENSIONAL
No. of cores 20 21 22 23 24 25 26 27 28 29 30 37 40 48 50

Shape of Conductor CIRCULAR STRANDED

Conductor dia (approx) mm 2.55

Nominal insulation thickness mm 0.8

Nominal Bedding Thickness mm 1.0 1.2

Bedding Dia. (Approx.) mm 25.0 25.6 26.4 26.9 28.6 29.0 29.7 30.0 30.8 33.3 34.7 38.4

Nom. Galvanized Steel Wire mm 1.60 2.00

Nominal Outer Sheath


mm 1.9 2.0 2.1 2.2
Thickness

Approx. Overall dia. mm 31.7 32.4 33.2 33.7 35.4 36.6 37.3 37.7 38.4 41.2 42.5 46.4

Cable weight (approx.) kg/km 2130 2220 2320 2410 2510 2560 2880 2960 3010 3100 3180 3660 3900 4540 4640

Max. conductor resistance DC at 20OC = 4.61 W/km

Core identification : Black numbers on white cores (for 2 cores upto 48 cores)

For 50 cores - White insulation with number 1-28 and Red insulation with number 1-22
http://www.southerncable.cc
All of the above information, including drawings, illustrations and graphic designs, reflects our present understanding and is to the best of our knowledge and belief correct and reliable. Users, however, should independently
evaluate the suitability of each product for the desired application. Under no circumstances does this constitute an assurance of any particular quality or performance. Such an assurance is only provided in the context of our
product specifications or explicit contractual arrangements. Our liability for these products is set forth in our standard terms and conditions of sale.
LOW VOLTAGE CABLES

PVC INSULATED PVC SHEATHED ARMOURED CABLES - 1.5 mm2 (AUXILIARY)

SPECIFICATION : IEC60502-1
VOLTAGE RATING : 600/1000V
CONDUCTOR : PLAIN ANNEALED COPPER WIRE
INSULATION : GENERAL PURPOSE PVC COMPOUND
INNER SHEATH : BLACK GENERAL PURPOSE PVC COMPOUND
ARMOURING : GALVANIZED STEEL WIRE
SHEATHING : BLACK GENERAL PURPOSE PVC COMPOUND

1.5 mm²
DIMENSIONAL
No. of cores 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18

Shape of Conductor CIRCULAR STRANDED

Conductor dia (approx) mm 1.59

Nominal insulation thickness mm 0.8

Nominal Bedding Thickness mm 1.0

Bedding Dia. (Approx.) mm 8.7 9.3 10.1 11.1 12.1 13.2 14.2 15.5 16.0 16.3 16.9 17.4 17.9 18.4 18.9

Nom. Galvanized Steel Wire mm 0.9 1.6 1.6

Nominal Outer Sheath Thickness mm 1.8

Approx. Overall dia. mm 14.0 14.5 15.5 16.5 17.5 18.5 19.5 21.0 21.5 22.5 23.0 25.0 25.5

Cable weight (approx.) kg/km 340 370 430 480 540 550 610 680 730 760 800 830 870 920 950 1270 1310

DIMENSIONAL
No. of cores 19 20 21 22 23 24 25 26 27 28 29 30 37 40 48 50

Shape of Conductor CIRCULAR STRANDED

Conductor dia (approx) mm 1.59

Nominal insulation thickness mm 0.8

Nominal Bedding Thickness mm 1.0

Bedding Dia. (Approx.) mm 18.9 19.5 19.9 20.6 21.0 22.3 22.8 23.1 23.7 25.7 26.7 29.6

Nom. Galvanized Steel Wire mm 1.6 2.0

Nominal Outer Sheath Thickness mm 1.8 1.9 2.0

Approx. Overall dia. mm 25.5 26.5 27.5 29.0 29.5 30.0 30.5 32.5 33.5 37.5

Cable weight (approx.) kg/km 1320 1380 1430 1480 1530 1590 1620 1640 1690 1720 1760 1810 2080 2210 2790 2840

Max. conductor resistance DC at 20OC = 12.1 W/km


Core identification : Black numbers on white cores (for 2 cores upto 48 cores)
For 50 cores - White insulation with number 1-28 and Red insulation with number 1-22

http://www.southerncable.cc
All of the above information, including drawings, illustrations and graphic designs, reflects our present understanding and is to the best of our knowledge and belief correct and reliable. Users, however, should independently
evaluate the suitability of each product for the desired application. Under no circumstances does this constitute an assurance of any particular quality or performance. Such an assurance is only provided in the context of our
product specifications or explicit contractual arrangements. Our liability for these products is set forth in our standard terms and conditions of sale.
LOW VOLTAGE CABLES

PVC INSULATED PVC SHEATHED ARMOURED CABLES - 2.5 mm2 (AUXILIARY)

SPECIFICATION : IEC60502-1
VOLTAGE RATING : 600/1000V
CONDUCTOR : PLAIN ANNEALED COPPER WIRE
INSULATION : GENERAL PURPOSE PVC COMPOUND
INNER SHEATH : BLACK GENERAL PURPOSE PVC COMPOUND
ARMOURING : GALVANIZED STEEL WIRE
SHEATHING : BLACK GENERAL PURPOSE PVC COMPOUND

2.5mm²
DIMENSIONAL
No. of cores 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18

Shape of Conductor CIRCULAR STRANDED

Conductor dia (approx) mm 2.01

Nominal insulation thickness mm 0.8

Nominal Bedding Thickness mm 1.0

Bedding Dia. (Approx.) mm 9.6 10.2 11.2 12.2 13.4 13.4 14.5 15.7 17.2 17.8 18.1 18.8 19.3 19.9 20.5 21.0

Nom. Galvanized Steel Wire mm 0.9 1.6

Nominal Outer Sheath


mm 1.8
Thickness

Approx. Overall dia. mm 15.0 15.5 16.5 17.5 18.5 18.5 20.0 21.0 22.5 22.5 23.0 25.0 25.5 26.0 26.5 27.0 27.5

Cable weight (approx.) kg/km 380 430 500 570 640 660 740 830 890 920 980 1280 1360 1420 1470 1550 1590

DIMENSIONAL
No. of cores 19 20 21 22 23 24 25 26 27 28 29 30 37 40 48 50

Shape of Conductor CIRCULAR STRANDED

Conductor dia (approx) mm 2.01

Nominal insulation thickness mm 0.8

Nominal Bedding Thickness mm 1.0

Bedding Dia. (Approx.) mm 21.0 21.7 22.2 22.9 23.3 24.8 25.4 25.7 26.4 28.6 29.8 33.4

Nom. Galvanized Steel Wire mm 1.6 2.0

Nominal Outer Sheath Thickness mm 1.8 1.9 2.0 2.1 2.2

Approx. Overall dia. mm 27.5 28.5 29.0 29.5 30.0 32.0 32.5 33.5 36.0 37.5 41.5 42.0

Cable weight (approx.) kg/km 1610 1690 1740 1810 1870 1970 2010 2050 2100 2140 2200 2250 2600 3000 3540 3630

Max. conductor resistance DC at 20OC = 7.41 W/km


Core identification : Black numbers on white cores (for 2 cores upto 48 cores)
For 50 cores - White insulation with number 1-28 and Red insulation with number 1-22

http://www.southerncable.cc
All of the above information, including drawings, illustrations and graphic designs, reflects our present understanding and is to the best of our knowledge and belief correct and reliable. Users, however, should independently
evaluate the suitability of each product for the desired application. Under no circumstances does this constitute an assurance of any particular quality or performance. Such an assurance is only provided in the context of our
product specifications or explicit contractual arrangements. Our liability for these products is set forth in our standard terms and conditions of sale.
LOW VOLTAGE CABLES

PVC INSULATED PVC SHEATHED ARMOURED CABLES - 4 mm2 (AUXILIARY)

SPECIFICATION : IEC60502-1
VOLTAGE RATING : 600/1000V
CONDUCTOR : PLAIN ANNEALED COPPER WIRE
INSULATION : GENERAL PURPOSE PVC COMPOUND
INNER SHEATH : BLACK GENERAL PURPOSE PVC COMPOUND
ARMOURING : GALVANIZED STEEL WIRE
SHEATHING : BLACK GENERAL PURPOSE PVC COMPOUND

4 mm²
DIMENSIONAL
No. of cores 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18

Shape of Conductor CIRCULAR STRANDED

Conductor dia (approx) mm 2.55

Nominal insulation thickness mm 1.0

Nominal Bedding Thickness mm 1.0

Bedding Dia. (Approx.) mm 11.5 12.2 13.4 14.8 16.2 17.6 19.1 21.0 21.7 22.1 22.9 23.6 24.3 25.1 25.7

Nom. Galvanized Steel Wire mm 0.9 1.6

Nominal Outer Sheath


mm 1.8 1.9
Thickness

Approx. Overall dia. mm 17.0 17.5 19.0 20.0 21.5 21.5 24.5 26.0 27.5 27.5 28.5 29.0 29.5 30.5 31.0 32.0 32.5

Cable weight (approx.) kg/km 490 560 650 760 860 890 1270 1400 1520 1570 1650 1740 1810 1920 1990 2110 2190

DIMENSIONAL
No. of cores 19 20 21 22 23 24 25 26 27 28 29 30 37 40 48 50

Shape of Conductor CIRCULAR STRANDED

Conductor dia (approx) mm 2.55

Nominal insulation thickness mm 1.0

Nominal Bedding Thickness mm 1.0 1.2 1.4

Bedding Dia. (Approx.) mm 25.7 26.5 27.1 28.1 28.6 30.9 31.6 32.0 32.8 35.6 37.0 41.5

Nom. Galvanized Steel Wire mm 1.6 2.0 2.5

Nominal Outer Sheath Thickness mm 1.9 2.0 2.1 2.2 2.3 2.4

Approx. Overall dia. mm 32.5 33.5 34.0 36.0 36.5 39.0 39.5 40.0 41.0 44.0 45.5 51.0

Cable weight (approx.) kg/km 2220 2330 2400 2780 2850 3050 3110 3170 3260 3310 3380 3490 4030 4310 5460 5580

Max. conductor resistance DC at 20OC = 4.61 W/km


Core identification : Black numbers on white cores (for 2 cores upto 48 cores)
For 50 cores - White insulation with number 1-28 and Red insulation with number 1-22
http://www.southerncable.cc
All of the above information, including drawings, illustrations and graphic designs, reflects our present understanding and is to the best of our knowledge and belief correct and reliable. Users, however, should independently
evaluate the suitability of each product for the desired application. Under no circumstances does this constitute an assurance of any particular quality or performance. Such an assurance is only provided in the context of our
product specifications or explicit contractual arrangements. Our liability for these products is set forth in our standard terms and conditions of sale.
LOW VOLTAGE CABLES

XLPE INSULATED PVC SHEATHED CABLES - 1.5mm² (AUXILIARY)

SPECIFICATION : IEC 60502-1


VOLTAGE RATING : 600/1000V
CONDUCTOR : PLAIN ANNEALED COPPER WIRE
INSULATION : XLPE (CROSS-LINKED POLYETHYLENE)
SHEATHING : BLACK PVC COMPOUND TYPE ST2

1.5 mm²
DIMENSIONAL
No. of cores 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18

Shape of
CIRCULAR STRANDED
Conductor

Conductor dia
mm 1.59
(approx)

Nominal insulation
mm 0.7
thickness

Nominal sheath
mm 1.8
thickness

Approx. Overall
mm 10.5 11.0 12.0 13.0 14.0 15.0 16.0 17.0 17.5 18.0 18.5 19.0 19.5 20.0 20.5
dia.

Cable weight
kg/km 130 150 180 210 240 250 280 320 340 360 390 410 430 460 490 520 540
(approx.)

ELECTRICAL CHARACTERISTIC
No. of cores 19 20 21 22 23 24 25 26 27 28 29 30 37 40 48 50

Shape of
CIRCULAR STRANDED
Conductor

Conductor dia
mm 1.59
(approx)

Nominal insulation
mm 0.7
thickness

Nominal sheath
mm 1.8
thickness

Approx. Overall
mm 20.5 21.0 21.5 22.0 22.5 23.5 24.0 24.5 25.0 26.5 27.5 30.5
dia.

Cable weight
kg/km 540 580 600 630 660 680 700 720 750 770 790 820 960 1040 1230 1270
(approx.)

Max. conductor resistance DC at 20OC = 12.1 W/km


Core identification : Black numbers on white cores (for 2 cores upto 48 cores)
For 50 cores - White insulation with number 1-28 and Red insulation with number 1-22

http://www.southerncable.cc
All of the above information, including drawings, illustrations and graphic designs, reflects our present understanding and is to the best of our knowledge and belief correct and reliable. Users, however, should
independently evaluate the suitability of each product for the desired application. Under no circumstances does this constitute an assurance of any particular quality or performance. Such an assurance is only provided in
the context of our product specifications or explicit contractual arrangements. Our liability for these products is set forth in our standard terms and conditions of sale.
LOW VOLTAGE CABLES

XLPE INSULATED PVC SHEATHED CABLES - 2.5mm² (AUXILIARY)

SPECIFICATION : IEC 60502-1


VOLTAGE RATING : 600/1000V
CONDUCTOR : PLAIN ANNEALED COPPER WIRE
INSULATION : XLPE (CROSS-LINKED POLYETHYLENE)
SHEATHING : BLACK PVC COMPOUND TYPE ST2

2.5mm²
DIMENSIONAL
No. of cores 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18

Shape of
CIRCULAR STRANDED
Conductor

Conductor dia
mm 2.01
(approx)

Nominal
insulation mm 0.7
thickness

Nominal sheath
mm 1.8
thickness

Approx. Overall
mm 11.0 12.0 13.0 14.0 15.0 16.5 17.5 19.0 19.5 20.0 20.5 21.0 21.5 22.0 22.5
dia.

Cable weight
kg/km 160 190 230 270 310 330 370 420 460 490 520 560 590 630 660 700 730
(approx.)

ELECTRICAL CHARACTERISTIC
No. of cores 19 20 21 22 23 24 25 26 27 28 29 30 37 40 48 50

Shape of
CIRCULAR STRANDED
Conductor

Conductor dia
mm 2.01
(approx)

Nominal
insulation mm 0.7
thickness

Nominal sheath
mm 1.8 1.9
thickness

Approx. Overall
mm 22.5 23.0 23.5 24.0 24.5 26.0 26.5 27.0 27.5 30.0 31.0 34.0
dia.

Cable weight
kg/km 750 790 820 860 900 940 970 1000 1030 1060 1090 1130 1350 1450 1740 1800
(approx.)

Max. conductor resistance DC at 20OC = 7.41 W/km

Core identification : Black numbers on white cores (for 2 cores upto 48 cores)

For 50 cores - White insulation with number 1-28 and Red insulation with number 1-22

http://www.southerncable.cc
All of the above information, including drawings, illustrations and graphic designs, reflects our present understanding and is to the best of our knowledge and belief correct and reliable. Users, however, should
independently evaluate the suitability of each product for the desired application. Under no circumstances does this constitute an assurance of any particular quality or performance. Such an assurance is only provided
in the context of our product specifications or explicit contractual arrangements. Our liability for these products is set forth in our standard terms and conditions of sale.
LOW VOLTAGE CABLES

XLPE INSULATED PVC SHEATHED CABLES - 4 mm² (AUXILIARY)

SPECIFICATION : IEC 60502-1


VOLTAGE RATING : 600/1000V
CONDUCTOR : PLAIN ANNEALED COPPER WIRE
INSULATION : XLPE (CROSS-LINKED POLYETHYLENE)
SHEATHING : BLACK PVC COMPOUND TYPE ST2

4 mm²
DIMENSIONAL
No. of cores 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18

Shape of
CIRCULAR STRANDED
Conductor

Conductor dia
mm 2.55
(approx)

Nominal
insulation mm 0.7
thickness

Nominal sheath
mm 1.8
thickness

Approx. Overall
mm 12.5 13.0 14.0 15.5 16.5 18.0 19.0 21.0 21.5 22.0 22.5 23.0 23.5 24.5 25.0
dia.

Cable weight
kg/km 200 250 300 360 420 450 510 580 630 680 720 780 830 880 930 990 1040
(approx.)

ELECTRICAL CHARACTERISTIC
No. of cores 19 20 21 22 23 24 25 26 27 28 29 30 37 40 48 50

Shape of
CIRCULAR STRANDED
Conductor

Conductor dia
mm 2.55
(approx)

Nominal
insulation mm 0.7
thickness

Nominal sheath
mm 1.8 1.9 2.1
thickness

Approx. Overall
mm 25.0 25.5 26.0 27.0 27.5 29.0 30.0 31.0 33.5 35.0 38.5
dia.

Cable weight
kg/km 1060 1120 1170 1230 1280 1340 1380 1430 1470 1520 1570 1620 1960 2120 2550 2640
(approx.)

Max. conductor resistance DC at 20OC = 4.61 W/km

Core identification : Black numbers on white cores (for 2 cores upto 48 cores)
For 50 cores - White insulation with number 1-28 and Red insulation with number 1-22

http://www.southerncable.cc
All of the above information, including drawings, illustrations and graphic designs, reflects our present understanding and is to the best of our knowledge and belief correct and reliable. Users, however, should
independently evaluate the suitability of each product for the desired application. Under no circumstances does this constitute an assurance of any particular quality or performance. Such an assurance is only
provided in the context of our product specifications or explicit contractual arrangements. Our liability for these products is set forth in our standard terms and conditions of sale.
LOW VOLTAGE CABLES

XLPE INSULATED COPPER TAPE SCREENED PVC SHEATHED CABLES (AUXILIARY)

SPECIFICATION : IEC 60502-1


VOLTAGE RATING : 600/1000V
CONDUCTOR : PLAIN ANNEALED COPPER WIRE
INSULATION : XLPE (CROSS-LINKED POLYETHYLENE)
SHEATHING : BLACK PVC COMPOUND TYPE ST2

1.5 mm²
DIMENSIONAL
No. of cores 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18

Shape of
CIRCULAR STRANDED
Conductor

Conductor dia
mm 1.59
(approx)

Nominal
insulation mm 0.7
thickness

Nominal sheath
mm 1.8
thickness

Approx. Overall
mm 10.5 11.0 12.0 13.0 14.0 15.0 16.0 17.0 17.5 18.5 19.0 19.5 20.0 20.5
dia.

Cable weight
kg/km 150 170 200 240 270 280 320 360 390 410 430 460 480 510 540 570 590
(approx.)

ELECTRICAL CHARACTERISTIC
No. of cores 19 20 21 22 23 24 25 26 27 28 29 30 37 40 48 50

Shape of
CIRCULAR STRANDED
Conductor

Conductor dia
mm 1.59
(approx)

Nominal
insulation mm 0.7
thickness

Nominal sheath
mm 1.8
thickness

Approx. Overall
mm 20.5 21.0 22.0 23.5 24.0 25.0 26.5 27.5 30.5
dia.

Cable weight
kg/km 600 630 660 690 720 750 770 790 810 830 860 880 1040 1120 1310 1350
(approx.)

Max. conductor resistance DC at 20OC = 4.61 W/km


Core identification : Black numbers on white cores (for 2 cores upto 48 cores)
For 50 cores - White insulation with number 1-28 and Red insulation with number 1-22

http://www.southerncable.cc
All of the above information, including drawings, illustrations and graphic designs, reflects our present understanding and is to the best of our knowledge and belief correct and reliable. Users, however,
should independently evaluate the suitability of each product for the desired application. Under no circumstances does this constitute an assurance of any particular quality or performance. Such an
assurance is only provided in the context of our product specifications or explicit contractual arrangements. Our liability for these products is set forth in our standard terms and conditions of sale.
LOW VOLTAGE CABLES

XLPE INSULATED COPPER TAPE SCREENED PVC SHEATHED CABLES (AUXILIARY)

SPECIFICATION : IEC 60502-1


VOLTAGE RATING : 600/1000V
CONDUCTOR : PLAIN ANNEALED COPPER WIRE
INSULATION : XLPE (CROSS-LINKED POLYETHYLENE)
SHEATHING : BLACK PVC COMPOUND TYPE ST2

2.5mm²
DIMENSIONAL
No. of cores 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18

Shape of
CIRCULAR STRANDED
Conductor

Conductor dia
mm 2.01
(approx)

Nominal
insulation mm 0.7
thickness

Nominal sheath
mm 1.8
thickness

Approx. Overall
mm 11.0 12.0 13.0 14.0 15.0 16.5 17.5 19.0 19.5 20.0 20.5 21.0 21.5 22.0 22.5
dia.

Cable weight
kg/km 180 210 260 300 350 360 410 470 510 540 570 610 640 680 720 760 790
(approx.)

ELECTRICAL CHARACTERISTIC
No. of cores 19 20 21 22 23 24 25 26 27 28 29 30 37 40 48 50

Shape of
CIRCULAR STRANDED
Conductor

Conductor dia
mm 2.01
(approx)
Nominal
insulation mm 0.7
thickness
Nominal sheath
mm 1.8 1.9
thickness

Approx. Overall
mm 22.5 23.0 23.5 24.0 24.5 26.0 26.5 27.0 27.5 30.0 31.0 34.0
dia.

Cable weight
kg/km 810 850 890 930 970 1010 1040 1070 1100 1130 1170 1200 1430 1540 1840 1890
(approx.)

Max. conductor resistance DC at 20OC = 4.61 W/km


Core identification : Black numbers on white cores (for 2 cores upto 48 cores)
For 50 cores - White insulation with number 1-28 and Red insulation with number 1-22

http://www.southerncable.cc
All of the above information, including drawings, illustrations and graphic designs, reflects our present understanding and is to the best of our knowledge and belief correct and reliable. Users, however,
should independently evaluate the suitability of each product for the desired application. Under no circumstances does this constitute an assurance of any particular quality or performance. Such an
assurance is only provided in the context of our product specifications or explicit contractual arrangements. Our liability for these products is set forth in our standard terms and conditions of sale.
LOW VOLTAGE CABLES

XLPE INSULATED COPPER TAPE SCREENED PVC SHEATHED CABLES (AUXILIARY)

SPECIFICATION : IEC 60502-1


VOLTAGE RATING : 600/1000V
CONDUCTOR : PLAIN ANNEALED COPPER WIRE
INSULATION : XLPE (CROSS-LINKED POLYETHYLENE)
SHEATHING : BLACK PVC COMPOUND TYPE ST2

4 mm²
DIMENSIONAL
No. of cores 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18

Shape of
CIRCULAR STRANDED
Conductor

Conductor dia
mm 2.55
(approx)

Nominal
insulation mm 0.7
thickness

Nominal sheath
mm 1.8
thickness

Approx. Overall
mm 12.5 13.0 14.5 15.5 16.5 18.0 19.5 21.0 21.5 22.0 22.5 23.0 24.0 24.5 25.0
dia.

Cable weight
kg/km 230 280 340 400 470 490 560 630 690 740 790 840 890 950 1000 1060 1110
(approx.)

ELECTRICAL CHARACTERISTIC
No. of cores 19 20 21 22 23 24 25 26 27 28 29 30 37 40 48 50

Shape of
CIRCULAR STRANDED
Conductor

Conductor dia
mm 2.55
(approx)

Nominal
insulation mm 0.7
thickness

Nominal sheath
mm 1.8 1.9 2.0 2.1
thickness

Approx. Overall
mm 25.0 26.0 26.5 27.0 27.5 29.0 30.0 30.5 31.0 33.5 35.0 39.0
dia.

Cable weight
kg/km 1130 1200 1250 1310 1370 1420 1470 1510 1560 1620 1680 1730 2060 2240 2670 2760
(approx.)

Max. conductor resistance DC at 20OC = 4.61 W/km


Core identification : Black numbers on white cores (for 2 cores upto 48 cores)
For 50 cores - White insulation with number 1-28 and Red insulation with number 1-22

http://www.southerncable.cc
All of the above information, including drawings, illustrations and graphic designs, reflects our present understanding and is to the best of our knowledge and belief correct and reliable. Users, however, should
independently evaluate the suitability of each product for the desired application. Under no circumstances does this constitute an assurance of any particular quality or performance. Such an assurance is only
provided in the context of our product specifications or explicit contractual arrangements. Our liability for these products is set forth in our standard terms and conditions of sale.
LOW VOLTAGE CABLES

DC POWER CABLE - SINGLE CORE (CLASS 5 FLEXIBLE COPPER CONDUCTORS)

SPECIFICATION : BS6004 & MS69


CONDUCTOR : PLAIN ANNEALED COPPER WIRE

CONSTRUCTION DATA
Diameter of Max. Resistance of
Approx. diameter of
wires in O Radial
Conductor Conductors at 20 C Minimum
Nominal Cross conductor Thickness
Insulation
Sectional Area of
Metal- Resistance
Insulation
Bunched Multi strand Plain Wires coated
Wires
mm² No./mm mm mm mm W/km mm W.km
0.22 7/0.20 0.21 0.60 - 92 92.4 0.60 0.015
0.5 16/0.20 0.21 0.93 - 39 40.1 0.60 0.013
0.75 24/0.20 0.21 1.14 - 26 26.7 0.60 0.011
1.00 32/0.20 0.21 1.32 - 19.5 20.0 0.60 0.010
1.25 40/0.20 0.21 1.48 - 15.6 16.1 0.70 0.010
1.35 19/0.30 0.31 1.50 - 14.6 15.0 0.70 0.010
1.5 30/0.25 0.26 1.60 - 13.3 13.7 0.70 0.010
2.5 50/0.25 0.26 2.00 - 7.98 8.21 0.80 0.009
4 56/0.30 0.31 2.60 - 4.95 5.09 0.80 0.007
6 84/0.30 0.31 3.30 3.60 3.30 3.39 0.80 0.006
10 80/0.40 0.41 4.20 4.60 1.91 1.95 1.00 0.0056
16 126/0.40 0.41 5.30 5.70 1.21 1.24 1.00 0.0046
25 196/0.40 0.41 6.60 7.10 0.780 0.795 1.20 0.0044
35 276/0.40 0.41 7.80 8.50 0.554 0.565 1.20 0.0038
50 396/0.40 0.41 9.40 10.30 0.386 0.393 1.40 0.0037
70 360/0.50 0.51 11.20 12.40 0.272 0.277 1.40 0.0032
95 475/0.50 0.51 13.00 14.50 0.206 0.210 1.60 0.0032
120 608/0.50 0.51 14.50 16.00 0.161 0.164 1.60 0.0029
150 756/0.50 0.51 - 18.00 0.129 0.132 1.80 0.0029
185 925/0.50 0.51 - 20.00 0.106 0.108 2.00 0.0029
240 1221/0.50 0.51 - 23.00 0.0817 0.0817 2.00 0.0028

608/0.50mm 756/0.50mm 925/0.50mm 1221/0.50mm


120 mm² 150 mm² 185 mm² 240 mm²

http://www.southerncable.cc
All of the above information, including drawings, illustrations and graphic designs, reflects our present understanding and is to the best of our knowledge and belief correct and reliable. Users, however, should
independently evaluate the suitability of each product for the desired application. Under no circumstances does this constitute an assurance of any particular quality or performance. Such an assurance is only
provided in the context of our product specifications or explicit contractual arrangements. Our liability for these products is set forth in our standard terms and conditions of sale.
LOW VOLTAGE CABLES

DC POWER CABLE - SCREENED

SPECIFICATION : BS6004 & MS69 & MS136


CONDUCTOR : PLAIN ANNEALED COPPER WIRE

CONSTRUCTION DATA
Nominal Max.
Minimum Jacket
No. of Across No. / Approx Dia of Conductor Insulation Dia. Of Screen
Insulation
Core Sectional Dia. conductor Resistance at Thickness Sheath Material
20ºC Resistance Thickness Dia.
Area
No. mm 2
No/mm mm W/km MW/km mm mm mm mm mm

2 1.50 30 / 0.25 1.60 13.3 0.010 0.94 8.4 Al Foil 0.80 10.00

2 3.00 24 / 0.40 2.16 6.67 0.009 0.75 9.9 Al Foil 1.20 12.32

Al Foil + Drain
2 4.00 56 / 0.30 2.60 4.95 0.0070 0.80 11.0 1.40 15.00
Wire

Al Foil + Drain
2 10.00 80 / 0.40 4.20 1.91 0.0056 1.00 15.2 1.50 18.20
Wire

Al Foil + Drain
2 16.00 126 / 0.40 5.30 1.21 0.0046 1.00 17.4 1.60 20.60
Wire

http://www.southerncable.cc
All of the above information, including drawings, illustrations and graphic designs, reflects our present understanding and is to the best of our knowledge and belief correct and reliable. Users, however, should independently evaluate
the suitability of each product for the desired application. Under no circumstances does this constitute an assurance of any particular quality or performance. Such an assurance is only provided in the context of our product
specifications or explicit contractual arrangements. Our liability for these products is set forth in our standard terms and conditions of sale.
LOW VOLTAGE CABLES

DC POWER CABLE - 2 CORES (CLASS 5 FLEXIBLE COPPER CONDUCTORS)

SPECIFICATION : BS6004, MS69 & MS136


CONDUCTOR : PLAIN ANNEALED COPPER WIRE

CONSTRUCTION DATA

Approx. diameter
Max.
of Conductor Radial Minimum Radial
Nominal Cross Resistance Of Dia. Of
Thickness of Insulation Thickness of Dia. Of Sheath
Sectional Area Conductor at Insulation
Insulation Resistance Sheath
Multi 20ºC
Bunched
strand

mm² No./mm mm W.km mm mm W.km mm mm

0.5 16/0.20 0.93 - 39.0 0.60 2.13 0.015 1.10 6.46

0.75 24/0.20 1.14 - 26.0 0.60 2.34 0.011 1.15 6.98

1.00 32/0.20 1.32 - 19.5 0.60 2.52 0.010 1.20 7.44

1.25 40/0.20 1.48 - 15.6 0.70 2.88 0.010 1.20 8.16

1.35 19/0.30 1.50 - 14.6 0.70 2.90 0.010 1.20 8.20

1.5 30/0.25 1.60 - 13.3 0.70 3.00 0.010 1.20 8.40

2.5 50/0.25 2.00 - 7.98 0.80 3.60 0.009 1.25 9.70

4 56/0.30 2.60 - 4.95 0.80 4.20 0.007 1.30 11.00

6 84/0.30 3.30 3.60 3.30 0.80 4.90 0.006 1.30 12.40

10 80/0.40 4.20 4.60 1.91 1.00 6.20 0.0056 1.40 15.20

16 126/0.40 5.30 5.70 1.21 1.00 7.30 0.0046 1.50 17.60

25 196/0.40 6.60 7.10 0.78 1.20 9.00 0.0044 1.60 21.20

http://www.southerncable.cc
All of the above information, including drawings, illustrations and graphic designs, reflects our present understanding and is to the best of our knowledge and belief correct and reliable. Users, however, should
independently evaluate the suitability of each product for the desired application. Under no circumstances does this constitute an assurance of any particular quality or performance. Such an assurance is only
provided in the context of our product specifications or explicit contractual arrangements. Our liability for these products is set forth in our standard terms and conditions of sale.
LOW VOLTAGE CABLES

DC POWER CABLE - 3 CORES (CLASS 5 FLEXIBLE COPPER CONDUCTORS)

SPECIFICATION : BS6004, MS69 & MS136


CONDUCTOR : PLAIN ANNEALED COPPER WIRE

CONSTRUCTION DATA

Approx. diameter of
Conductor Radial Minimum Radial
Nominal Cross Max. Dia. Of
Thickness of Insulation Thickness of Dia. Of Sheath
Sectional Area Resistance Insulation
Insulation Resistance Sheath
Multi
Bunched
strand

mm² No./mm mm W.km mm mm W.km mm mm

0.5 16/0.20 0.93 - 39.0 0.60 2.13 0.015 1.15 6.89

0.75 24/0.20 1.14 - 26.0 0.60 2.34 0.011 1.15 7.34

1.00 32/0.20 1.32 - 19.5 0.60 2.52 0.010 1.20 7.83

1.25 40/0.20 1.48 - 15.6 0.70 2.88 0.010 1.20 8.61

1.35 19/0.30 1.50 - 14.6 0.70 2.90 0.010 1.20 8.65

1.5 30/0.25 1.60 - 13.3 0.70 3.00 0.010 1.20 8.87

2.5 50/0.25 2.00 - 7.98 0.80 3.60 0.009 1.30 10.36

4 56/0.30 2.60 - 4.95 0.80 4.20 0.007 1.30 11.65

6 84/0.30 3.30 3.60 3.30 0.80 4.90 0.006 1.40 13.36

10 80/0.40 4.20 4.60 1.91 1.00 6.20 0.0056 1.45 16.26

16 126/0.40 5.30 5.70 1.21 1.00 7.30 0.0046 1.55 18.83

25 196/0.40 6.60 7.10 0.78 1.20 9.00 0.0044 1.70 22.80

http://www.southerncable.cc
All of the above information, including drawings, illustrations and graphic designs, reflects our present understanding and is to the best of our knowledge and belief correct and reliable. Users, however, should independently
evaluate the suitability of each product for the desired application. Under no circumstances does this constitute an assurance of any particular quality or performance. Such an assurance is only provided in the context of our
product specifications or explicit contractual arrangements. Our liability for these products is set forth in our standard terms and conditions of sale.
LOW VOLTAGE CABLES

DC POWER CABLE - 4 CORES (CLASS 5 FLEXIBLE COPPER CONDUCTORS)

SPECIFICATION : BS6430, MS69 & MS136


CONDUCTOR : PLAIN ANNEALED COPPER WIRE

CONSTRUCTION DATA

Approx. diameter of
Conductor Radial Minimum Radial
Nominal Cross Sectional Max. Dia. Of
Thickness of Insulation Thickness of Dia. Of Sheath
Area Resistance Insulation
Insulation Resistance Sheath
Multi
Bunched
strand

mm² No./mm mm W.km mm mm W.km mm mm

0.5 16/0.20 0.93 - 39.0 0.60 2.13 0.015 1.15 7.44

0.75 24/0.20 1.14 - 26.0 0.60 2.34 0.011 1.20 8.05

1.00 32/0.20 1.32 - 19.5 0.60 2.52 0.010 1.20 8.48

1.25 40/0.20 1.48 - 15.6 0.70 2.88 0.010 1.25 9.45

1.35 19/0.30 1.50 - 14.6 0.70 2.90 0.010 1.25 9.50

1.5 30/0.25 1.60 - 13.3 0.70 3.00 0.010 1.25 9.74

2.5 50/0.25 2.00 - 7.98 0.80 3.60 0.009 1.30 11.29

4 56/0.30 2.60 - 4.95 0.80 4.20 0.007 1.35 12.84

6 84/0.30 3.30 3.60 3.30 0.80 4.90 0.006 1.40 14.63

10 80/0.40 4.20 4.60 1.91 1.00 6.20 0.0056 1.50 17.97

16 126/0.40 5.30 5.70 1.21 1.00 7.30 0.0046 1.60 20.82

25 196/0.40 6.60 7.10 0.78 1.20 9.00 0.0044 1.75 25.23

http://www.southerncable.cc
All of the above information, including drawings, illustrations and graphic designs, reflects our present understanding and is to the best of our knowledge and belief correct and reliable. Users, however, should independently evaluate the
suitability of each product for the desired application. Under no circumstances does this constitute an assurance of any particular quality or performance. Such an assurance is only provided in the context of our product specifications or
explicit contractual arrangements. Our liability for these products is set forth in our standard terms and conditions of sale.
LOW VOLTAGE CABLES

DC POWER CABLE - 5 CORES (CLASS 5 FLEXIBLE COPPER CONDUCTORS)

SPECIFICATION : BS6004, MS69 & MS136


CONDUCTOR : PLAIN ANNEALED COPPER WIRE

CONSTRUCTION DATA

Approx. diameter of
Conductor
Minimum
Nominal Cross Sectional Radial Thickness Radial Thickness
Max. Resistance Dia. Of Insulation Insulation Dia. Of Sheath
Area of Insulation of Sheath
Resistance
Multi
Bunched
strand

mm² No./mm mm W.km mm mm W.km mm mm

0.5 16/0.20 0.93 - 39.0 0.60 2.13 0.015 1.20 8.15

0.75 24/0.20 1.14 - 26.0 0.60 2.34 0.011 1.20 8.72

1.00 32/0.20 1.32 - 19.5 0.60 2.52 0.010 1.20 9.20

1.25 40/0.20 1.48 - 15.6 0.70 2.88 0.010 1.30 10.38

1.35 19/0.30 1.50 - 14.6 0.70 2.90 0.010 1.30 10.43

1.5 30/0.25 1.60 - 13.3 0.70 3.00 0.010 1.30 10.70

2.5 50/0.25 2.00 - 7.98 0.80 3.60 0.009 1.35 12.42

4 56/0.30 2.60 - 4.95 0.80 4.20 0.007 1.40 14.14

6 84/0.30 3.30 3.60 3.30 0.80 4.90 0.006 1.45 16.13

10 80/0.40 4.20 4.60 1.91 1.00 6.20 0.0056 1.55 19.84

126/0.4
16 5.30 5.70 1.21 1.00 7.30 0.0046 1.70 23.11
0

196/0.4
25 6.60 7.10 0.78 1.20 9.00 0.0044 1.85 28.00
0

http://www.southerncable.cc
All of the above information, including drawings, illustrations and graphic designs, reflects our present understanding and is to the best of our knowledge and belief correct and reliable. Users, however, should independently evaluate the
suitability of each product for the desired application. Under no circumstances does this constitute an assurance of any particular quality or performance. Such an assurance is only provided in the context of our product specifications or