Corrosion Inhibitor Injection System Data Sheet


Surface Facility EPC Services
Phase-4 Development Project

Approval Sheet
Name Title Date Signature

Budi Prasetyo / Project Manager /


Muliawan Kukuh Deputy Project Manager

Moch. Wahyudi / Engineering &


Tegoeh SM Construction Lead

Revision Status
Rev Issue date By Chk App Issue Purpose Owner
Signature
A 18-Oct-2017 NMH BHR MMH Issued for Review
0 14-Dec-2017 NMH BHR MMH Issued for Approval
1 29-Dec-2017 NMH BHR MMH Issued for Approval
Corrosion inhibitor injection system Data Sheet

Revision Log Register

Revisions had been performed on following pages:

Page Date Revision

1-3-4-5-6-7-9 12/14/2017 According to Company Comments


3-6-7 12/29/2017 According to Company Comments

P4D-3-MLN-M-DSH-0001 , Rev 1
Page 2 of 10
Corrosion inhibitor injection system Data Sheet
CLIENT : PERTAMINA ALGERIA EP NO. OF UNIT : SEVEN (7) PRODUCTION WELLS
PLANT/AREA LOCATION : ALGERIA BLOCK 405a / MLN FIELD ONE (1) MAKE UP WELL(S)
EQUIPMENT NAME : CORROSION INHIBITOR INJECTION SYSTEM MODEL NO. : TBA
PACKAGE TAG NO. : PT-8XX (REFER TO TABLE PAGE 5) PACKAGER : TBA
PURCH. ORDER NO. : TBA
1 EXTENT OF PACKAGE
2 THE CORROSION INHIBITOR INJECTION PACKAGE FOR NEW PRODUCTION WELL PRODUCE GAS /OIL MIXTURE WITH FREE WATER CONTENTS
3 OF THE PHASE 4 DEVELOPMENT. THE FOLLOWING EQUIPMENTS AS A MINIMUM VENDOR SCOPE OF SUPPLY, BUT NOT LIMITED TO :
4

5 1. SKID MOUNTED CORROSION INHIBITOR INJECTION SYSTEM INCLUDING:


6 - 316L SS CORROSION INHIBITOR INJECTION TANKS (STORAGE TANK) WITH FILLING CONNECTION.
7 - 316L SS CORROSION INHIBITOR INJECTION PUMP (POSITIVE DISPLACEMENT/ CONTROLLED VOLUME PUMP TYPE).
8 2. INSTRUMENTATION, PIPING, TUBINGS INCLUDING FITTINGS, VALVES, CONNECTORS, STRAINER, DISCHARGE PULSATION DAMPENER, VENTING,
9 LEVEL GAUGE, PRESSURE INDICATOR, LIQUID LEVEL, PRESSURE RELIEF VALVE AND CALIBRATION GAUGE AS SHOWN ON
10 Typical Chemical Injection Package P&ID P4D-3-MLN-P-PID-8003
11 3. ELECTRICAL EQUIPMENT/ CABLING UP TO AND INCLUDING JUNCTION BOX.
12 4. UNIT TO BE COMPLETELY WIRED AND PIPED UP.
13 5. INJECTION PUMP. A COMMON WAREHOUSE SPARE FOR THE INJECTION PUMPS TO BE PROVIDED.
14 TOTAL INJECTION PUMPS REQUIRED ARE 10 UNITS (I.E. 3 UNITS + 1 SPARE FOR 9.6 L/H PUMP CAPACITY and 5 UNITS
15 + 1 SPARE FOR 4.61 L/H PUMP CAPACITY).
16 6. LIFTING LUGS, EARTHING BOSS AND NAMEPLATE.
17 7. STRUCTURAL SKID BASE WITH DRIP PAN.
18 8. DETAIL ENGINEERING, CALCULATIONS, DRAWINGS, P&ID, ETC.
19 9. FAT (FACTORY ACCEPTANCE TEST) & SAT (SITE ACCEPTANCE TEST).
20 10. PROCUREMENT, INSTALLATION, & FABRICATION.
21 11. INSPECTION AND TESTING.
22 12. MECHANICAL WARRANTY.
23 13. ON SKID FABRICATION SUCH AS ;
24 - CARBON STEEL STRUCTURE AND PIPING SUPPLY AND FABRICATION,
25 - ERECTION AND ASSEMBLY OF EQUIPMENT,
26 - ELECTRICAL AND INSTRUMENTATION INSTALLATION,
27 - SURFACE PREPARATION AND PAINTING, (IF REQUIRED)
28 - TESTING AND PRECOMMISSIONNING,
29 - DELIVERY PORT SKIKDA ALGERIE.
30 APPLICABLE SPECIFICATIONS / DRAWINGS
31 P4D-3-MLN-M-SPE-0001 CORROSION INHIBITOR INJECTION SYSTEM SPECIFICATION
32 P4D-3-MLN-W-SPE-0002 PIPING AND VALVE CLASS
33 P4D-GEN-I-SPE-0004 SPECIFICATION FOR JUNCTION BOXES AND CABLE GLANDS
34 P4D-3-MLN-E-SPE-0002 GENERAL SPECIFICATION OF SOLAR POWER UNIT
35 P4D-3-MLN-P-PFD-8004 PFD Typical Production Well Head
36 P4D-3-MLN-P-PID-8002 TYPICAL PRODUCER WELLHEAD P&ID
37 P4D-3-MLN-P-PID-8003 Typical Chemical Injection Package P&ID
38 P4D-3-MLN-P-SYM-8001 LEGEND AND SYMBOLS P&ID
39 P4D-CPF-O-SDY-0001 MATERIAL SELECTION STUDY REPORT
40 P4D-3-GEN-G-DBS-0001 DESIGN BASIS REPORT
41 SITE AND UTILITY DATA
42 SITE CONDITION:
43 - ATMOSPHERIC PRESSURE : 996 mbar
44 - MECHANICAL DESIGN TEMPERATURE (MIN / MAX): -5 / 60 (SHADED), 80 (EXPOSED) °C
45 - RELATIVE HUMIDITY (MIN/MAX) : 20 - 80 %
46 - WIND :139 km/h @ 10 m
47 - LOCATION: TROPICALIZED, ONSHORE, OUTDOOR, DUST CONDITION (DESERT AREA).
48 ELECTRICAL INFORMATION
49 ELECTRICAL AREA CLASSIFICATION : ZONE 2, GROUP IIA, TEMPERATURE CLASS T3
50 ELECTRIC POWER SUPPLY : FROM SOLAR PANEL 24 VDC
51

52

53

54

55

56

57

58

59

60

61

62

63

64

65

66

67

68

69

70

P4D-3-MLN-M-DSH-0001 , Rev 1 Page 3 of 10


Corrosion inhibitor injection system Data Sheet
1 DESIGN REQUIREMENTS
2 DUTY SPECIFICATION :
3 1. VENDOR TO ADVISE CHEMICAL INJECTION RATES.
4 2. THE PUMPS ARE LOCATED IMMEDIATELY NEXT TO THE LINE WHERE INJECTION TAKES PLACE.
5

6 PROCESS CONTROL/SAFETY :
7 1. THE INJECTION RATE HAS TO BE LOCALLY CONTROLLED PER PUMP. THE INJECTION RATE MUST BE INDICATED LOCALLY.
8 2. THE STORAGE TANK MUST BE PROVIDED WITH A LOCAL LEVEL INDICATOR, AND A LOW LEVEL ALARM.
9 3. EACH INJECTION PUMP SHALL BE PROTECTED AGAINST OVERPRESSURE BY AN INTEGRATED RELIEF VALVE SET AT THE DESIGN PRESSURE
10 SPECIFIED FOR EACH WELL.
11 4. THE PUMP MUST BE ABLE TO SUPPLY THE CHEMICAL PRODUCT UP TO DESIGN PRESSURE OF CHOKE VALVE.
12 5. THE PUMP FLOWRATE IS CALIBRATED LOCALLY. CALIBRATION FACILITIES FOR THE INJECTION PUMP HAVE TO BE PROVIDED.
13

14 UNLOADING CHEMICALS:
15 1. VENDOR TO ADVISE THE MOST OPTIMUM METHOD FOR CHEMICALS UNLOADING (AND STORAGE).
16

17 NOISE AND REQUIREMENT:


18 1. THE NOISE LEVEL SHALL NOT EXCEED 85 DB(A) AT 1 M FROM THE PACKAGE.
19

20 TYPICAL CORROSION INHIBITOR INJECTION PACKAGE SCHEMATIC (AS REFERENCE)


21

22

23

24

25

26

27

28

29

30

31

32

33

34

35

36

37

38

39

40

41

42

43

44

45

46

47

48

49

50

51

52

53

54

55

56

57

58

59

60

61

62

63

64

65

66

67 TIE-IN LIST
68 NO. TIE-IN NO. SERVICE SIZE (IN) RATING- TYPE REMARKS
69 1 TP-1 LIQUID OUTLET 1/2" 600# / SWRF A 182 F 316L MATERIAL
70 PACKAGE WEIGHT
71 TOTAL PACKAGE WEIGHT : VTA kg
72 SHIPPING WEIGHT : VTA kg
73

P4D-3-MLN-M-DSH-0001 , Rev 1 Page 4 of 10


Corrosion inhibitor injection system Data Sheet
1 PROCESS DATA FOR CORROSION INHIBITOR INJECTION PACKAGE
2 WELLHEAD AREA MLN-19P KMD-5P MLN-18P MLW-10P MLNW-11P MLSE-9P KMD-7P MLNW-12P
3 TAG NO. PACKAGES 61-PT-900 62-PT-900 63-PT-900 64-PT-900 67-PT-900 68-PT-900 69-PT-900 71-PT-900
4 (Remark 3)
5 TANK DATA:
6 TAG NO. OF TANKS 61-TK-900 62-TK-900 63-TK-900 64-TK-900 67-TK-900 68-TK-900 69-TK-900 71-TK-900
7 QUANTITY 1 (ONE) 1 (ONE) 1 (ONE) 1 (ONE) 1 (ONE) 1 (ONE) 1 (ONE) 1 (ONE)
8 NOMINAL WORKING CAPACITY (Remark 1) m3 1
9 DIMENSIONS; WIDTH mm VTA
10 LENGTH mm VTA
11 HEIGHT mm VTA
12 OPERATING TEMPERATURE °C AMB
13 OPERATING PRESSURE barg ATM
14

15 DESIGN PRESSURE Full vaccum / Atm+Full of water


16 DESIGN TEMPERATURE (MAX./MIN.) 60 (SHADED), 80 (UNSHADED) / - 5
17 PRODUCT HEIGHT (LLLL/ HL) mm 110 / 1221 (VTC)
18 MAXIMUM TEST FILL HEIGHT mm 1270 (VTC)
19 NOMINAL PRODUCT STORAGE day 7 (Remark 1)
20

21 PUMP DATA: (Remark 1)


22 TAG NO. OF PUMPS 61-P-900 62-P-900 63-P-900 64-P-900 67-P-900 68-P-900 69-P-900 71-P-900
23 CAPACITY @ PT (RATED) l/h 9.6 9.6 4.61 4.61 4.61 4.61 9.6 4.61
24 DISCHARGE PRESSURE barg 75
25 SUCTION PRESSURE barg ATM
26 DIFFERENTIAL PRESSURE bar 75
27 NPSH REQUIRED m VTA
28 TREATED STREAM:
29 FLUID
30 FLOWRATE (MIN/MAX) Remark 5 Min Flow Max Flow Min Flow Max Flow Min Flow Max Flow Min Flow Max Flow Min Flow Max Flow Min Flow Max Flow Min Flow Max Flow Min Flow Max Flow
31 GAS MMSCFD 6.86 21.9 1.12 17.38 1.27 10.75 4.19 7.06 1.33 12.2 - 39 1.86 19.7 1.4 8.02
32 OIL STBPD 799.66 2201.43 72.24 1862.16 96.03 943.47 504.32 1572.44 23.17 1642.01 - 2700 121.08 1000 66.98 751.91
33 WATER STBPD 16.32 44.93 1.47 38.00 1.96 19.25 10.29 32.09 0.47 33.51 - 55.10 2.47 20.41 1.37 15.35
34 INJECTION PRESSURE (OP./DES.) barg Remark 6 48/75 48,5/75 48/75 60/75 49,5/75 66/75 45/75 57/75
35

36 LIQUID DATA:
37 TYPE LIQUID Chemical (Remark 2)
38 PUMPING TEMPERATURE °C AMB (10 - 55)
39 SPECIFIC GRAVITY 1.1
40 VISCOSITY AT OPERATING TEMPERATURE mPas < 20
41 INJECTION CONCENTRATION ppm vol 10-20 (VTC)
42 INJECTION RATE (MIN/MAX) Remark 7 1.377 8.745 0.226 7.124 0.251 4.268 0.824 2.875 0.254 4.564 15.4 0.356 7.511 0.271 3.152
43 PRODUCT DENSITY @ T, P (Sp.Gr.) kg/m3 1100 (VTC)
44 VAPOR PRESSURE bara 120 @ Flowing Temperature (VTC)
45

46

47 Remarks:
48 1. REQUIRED STORAGE CAPACITY IS 1 m 3 AS MINIMUM DETERMINED BASED ON MAXIMUM INJECTION RATE AND FOR ONE WEEK OPERATION.
49 2. THE SELECTED CORROSION INHIBITOR CORRTREAT 702 (TYPICAL WITH EXSITING) IS WATER BASED AND INJECTED PURE.
50 3. MINIMUM AND MAXIMUM FLOWRATE ARE BASED ON PRODUCTION PROFILES PROVIDED IN THE DESIGN BASIS
51 4. INJECTION PRESSURE WILL BE UPDATED BASED ON THE HYDAULIC STUDY REPORT FOR THE PRODUCTION NETWORK
52 5. INJECTION RATE ARE BASED ON FLOWLINE DESIGN PRESSURE (75 BARG) AND WELL HEAD TEMPERATURE , VENDOR SHALL CONFIRM INJECTION RATE
53

54

55

56

57

58

59

60

61

62

63

P4D-3-MLN-M-DSH-0001 , Rev 1 Page 5 of 10


Corrosion inhibitor injection system Data Sheet
1 CORROSION INHIBITOR STRUCTRE SKID GENERAL CHARACTERISTICS (Note 13)
2 Overal package dimension : VTA
3 Overall package weight :
4 Empty Weight VTA Kg
5 Transport/Transit/Lift VTA Kg
6 Operating Weight (normal & max) VTA Kg
7 Test Weight VTA Kg
8 Center of Gravity for each weight VTA Kg
9 Maintenance weight data VTA Kg
10 TANK GENERAL CHARACTERISTICS
11 DESIGN CODE AND SPECIFICATION : MANUFACTURER STANDARD (NOTE 1)
12
13 DESIGN TEMPERATURE : REFER TO PAGE 5
14 DESIGN PRESSURE : REFER TO PAGE 5
15 OPERATING TEMPERATURE : AMB
16 OPERATING PRESSURE : ATM
17 HYDROTEST PRESSURE : : FULL OF WATER
18
19 PLATE THICKNESS ( TOP & SHELL) : 6 (VTC) + Note14 ULTRASONIC TESTING : NO
20 PLATE THICKNESS (BOTTOM) : 6 (VTC) + Note14 DYE PENETRANT TESTING : YES (100%)
21 CORROSION ALLOWANCE : N/A INSPECTION : AUTHORIZED INSPECTOR (NOTE 3)
22 INTERNALS : NO STAMP : N/A
23 FIREPROOFING : NO MATERIAL CERTIFICATION : YES (NOTE 4)
24 INSULATION : NO EMPTY WEIGHT : VTA kg (NOTE 6)
25 EXTERNAL PAINTING : N/A OPERATING WEIGHT : VTA kg
26 INTERNAL COATING : NO TEST WEIGHT : VTA kg
27 SACRIFICIAL ANODE : NO Center of Gravity for each weight : VTA Kg
28 PICKLING AND PASSIVATION : YES, ALL SS PARTS Datum to be provided in the drawing : VTA
29 STRESS RELIEVE : NO INTERNAL VOLUME : VTA m3
30 RADIOGRAPHY : 10% ON ALL BUTT WELDS
31
32 CONSTRUCTION AND MATERIAL SPECIFICATION
33 TYPE OF TANK : CYLINDRICAL (Note 15) SHELL PLATE : SS 316 L
34 LADDER & CLIPS : NO TOP ROOF PLATE : SS 316 L
35 INSULATION RINGS OR CLIPS : NO BOTTOM PLATE : SS 316 L
36 PIPING CLIPS : NO FLANGES : A 182 F 316L
37 PERSONNEL PROTECTION : NO NOZZLES : A 312 TP 316L
38 STIFFENERS : YES GASKETS : VTA
39 HINGE : YES FOR HANDHOLES EXTERNAL ATTACHMENTS : SS 316 L
40 SUPPORT : YES, LEGS (NOTE 11) EXTERNAL STUDS : A193 B8M CLASS 2
41 INTERNAL COATING : N/A EXTERNAL NUTS : A194 GR 8MA
42 INTERNALS : N/A INTERNAL STUDS : N/A
43 INTERNAL ATTACHMENTS : N/A INTERNAL NUTS : N/A
44 STIFFENERS : SS 316 L, IF ANY
45 SUPPORT - SKID : SS 316 L
46 EARTHING LUG : SS 316 L
47 LIFTING LUGS : SS 316 L
48 NAME PLATE : SS 316 L
49 NAME PLATE BRACKET : SS 316 L
50 VTA = VENDOR TO ADVISE, VTC = VENDOR TO CONFIRM, TBA = TO BE ADVISE, N/A = NOT APPLICABLE
51
52 NOTES
53 1. VENDOR SHALL BE DESIGN OF TANK WITH CONSIDERING PROCESS NEEDED.
54 2. PAINTING AND COATING SHALL BE AS PER "Specification for Surface Preparation P4D-GEN-X-SPE-0004 " & "Coating specification P4D-3-MLN-W-SPE-0003 "
55 3. REGULATING & INSPECTION AUTHORITY SHALL REFER TO DOCUMENT NO. MLN-AOI-0010, "ARH-DGM DOSSIER PREPARATION" AND
56 MLN-AOI-0011, "ALGERIAN AUTHORITIES COMMUNICATION PROCEDURE".
57 4. MATERIAL CERTIFICATION IS IN ACCORDANCE WITH EN 10204 TYPE 3.2 FOR PRESSURE RETAINING PARTS & EN 10204 TYPE 2.2 FOR NON PRESSURE PARTS.
58 5. FOR EACH CHEMICAL INJECTION TANK/COMPARTMENT UNLESS OTHERWISE NOTED.
59 6. TO BE CALCULATED FOR OVERALL WEIGHT OF THE TANK.
60 7. DESIGN LIFE SHALL BE 20 YEARS.
61 8. BOTTOM SLOPE TO DRAIN NOZZLE
62 9. NOZZLE SIZE, RATING, FACING, ORIENTATION, PROJECTION AND ELEVATION ARE INDICATIVE ONLY AND SHALL BE CONFIRMED BY VENDOR
63 10. FLANGE BOLT HOLE SHALL BE STRADLE TO CENTER LINE
64 11. 4 ( FOUR ) LEGS SHALL BE PROVIDED AT THE TANK WITH OPPOSITE MOUNTED.
65 12. ALL NOZZLE FLANGES SHALL CONFORM TO ASME B 16.5.
66 13. If different material are used between structure skid and equipment, Insulation gaskets are required to prevent galvanic corrosion
67 14. Minimum selected tank plate thickness shall be 3 mm
68
69
70
71
72
73
74
75
76
77
78
79
80
81
82
83
84
85
86
87
88
89
90
91
P4D-3-MLN-M-DSH-0001 , Rev 1 Page 6 of 10
Corrosion inhibitor injection system Data Sheet

1 NOZZLE SCHEDULE (NOTE 9,12 PAGE 6)

2
SIZE (IN) PROJECTION ELEVATION
TAG QTY RATING TYPE/FACING DESCRIPTION REMARK
(VTC) (mm) (mm)
3

5 N1 1 2 3000# NPT VTA VTA FILLING CONNECTION

6 N2 1 1/2 3000# NPT VTA VTA LIQUID OUTLET

7 N3 1 1 VTA VTA VTA VTA VENT C/W SAND SCREEN

8 N4 1 1 3000# NPT VTA VTA DRAIN

9 N5 A / B 2 1 3000# NPT VTA VTA LEVEL GAUGE

10 N6 1 VTA VTA VTA VTA VTA LEVEL SWITCH LOW

11 N7 1 1/2 3000# NPT VTA VTA CALIBRATION POT

12 N8 1 3/4 3000# NPT VTA VTA PURGE TANK WITH PLUG

13 N9 1 2 VTA VTA PSV DISCHARGE TO TANK

14 HH 1 VTA - - VTA VTA HAND HOLE - PLATE FLANGE


15
16
17 TYPICAL CORROSION INHIBITOR TANK SKETCH (NOTE 8 PAGE 6)
18
19 N4
20
HH
21
22
23 N9
24
Lu
gs
Lif
tin
g

25
26
27
28 N3 N1
29
30
31
N6
32
33
34 N5A
35 N8
36 N5B N2
N7
37
38
TOP VIEW
39
40
N7 N8
41
42
HH
Lug
Lifti
ng

43 N1
s

N3 N9
44
45
46
47
48
49 N5A
50
51
52
VT
A

53
54
C)
55 (C-
56 VTA
A
plate
Nam

VT
e

57
58
59
60
61
62 N5B
N6 N2
63
64
65 VTA
N4
66
Lug
thin
Ear

67
g

68
69
Sup
port
Leg

PLAN VIEW
(Fo
ur)

70
4

71
TK-8XX
72
73
74 NOTES
75
76 15. Cylindrical shape is just for reference, Vendor shall propose the adequate tank design and shall be submitted to Campany approval
77
78
79
80
P4D-3-MLN-M-DSH-0001 , Rev 1 Page 7 of 10
Corrosion inhibitor injection system Data Sheet

1 APPLICABLE TO: PROPOSALS PURCHASE AS BUILT


2 FOR PERTAMINA ALGERIA EP UNIT P-8XX (REFER TO PAGE 5)
3 SITE ALGERIA BLOCK 405a / MLN FIELD NO. OF PUMPS REQUIRED 8 UNITS (+ 2 SPARE)
4 SERVICE CORROSION INHIBITOR INJECTION PUMP SIZE AND TYPE TBA
5 MANUFACTURER TBA SERIAL NO. TBA
6
7 NOTES: INDICATES INFORMATION TO BE COMPLETED BY MANUFACTURER PURCHASER / MANUFACTURER

8 GENERAL

9 NO. MOTOR DRIVEN 10 (TEN) EA OTHER DRIVER TYPE N/A


10 PUMP ITEM NO'S P-8XX (REFER TO PAGE 5) PUMP ITEM NO'S N/A
11 MOTOR ITEM NO'S M-8XX DRIVER ITEM NO'S N/A GEAR ITEM NO'S N/A
12 MOTOR PROVIDED BY VTA DRIVER PROVIDED BY N/A GEAR PROVIDED BY N/A
13 MOTOR MOUNTED BY VTA DRIVER MOUNTED BY N/A GEAR MOUNTED BY N/A
14 MOTOR DATA SHEET NO VTA DRIVER DATA SHEET NO. N/A GEAR DATA SHEET NO. N/A
15
16 OPERATING CONDITIONS LIQUID
17 CAPACITY @ PT (l/h) TYPE OR NAME OF LIQUID
18 MAXIMUM MINIMUM PUMPING TEMPERATURE °C
19 RATED NORMAL NORMAL - MAX MIN -
20 DISCHARGE PRESSURE barg SPECIFIC GRAVITY REFER TO PAGEMINIMUM
MAXIMUM 5
21 MAXIMUM MINIMUM RATED SPECIFIC HEAT Cp J/(kg.°C)
22 SUCTION PRESSURE barg VISCOSITY Cp MINIMUM MAXIMUM
23 MAXIMUM REFER TO PAGE 5
MINIMUM VAPOR PRESSURE bara
24 DIFFERENTIAL PRESSURE
bar CORROSIVE/EROSIVE AGENTS
25 MAXIMUM MINIMUM CHLORIDE CONCENTRATION (PPM)
26 NPSH AVAILABLE m H2S CONCENTRATION (PPM)

27 WITHOUT ACCELERATION HEAD ACTUAL LIQUID TOXIC FLAMMABLE OTHER


28 TURNDOWN RATIO
29
30 PERFORMANCE (NOTE 1 PAGE 10) SITE AND UTILITY DATA
31 NUMBER OF FEEDS VTA MAX. RATED CAP. (m3/h) VTA LOCATION INDOOR OUTDOOR
32 NPSH REQUIRED m VTA HEATED UNHEATED UNDER ROOF
33 Kw RATED VTA AT RELIEF SETTING VTA ELECTRICAL AREA CLASS ZONE 2 GR IIA TEMP.CL T3
34 PLUNGER SPEED (strokes/min) VTA DESIGN MAX VTA WINTERZARION REQ'D TROPICALIZATION REQ'D
35 DIAMETER mm VTA LENGTH OF STROKE mm VTA SITE DATA
36 PUMP HEAD: VTA RANGE OF AMBIENT TEMPS: MIN/MAX 0 / 47 (62°C Peak Rate)
37 MAXIMUM PRESSURE barg VTA UNUSUAL CONDITION
38 HYDRO TEST PRESSURE barg VTA DUST FUMES SALT ATMOSPHERE
39 MAX. DISCH PRESSURE W/ JOB DRIVER barg VTA OTHER
40 MAX. KW BASIS GEAR STRENGTH N/A UTILITY CONDITIONS
41 ELECTRICITY DRIVERS HEATING CONTROL SHUTDOWN
42 CONSTRUCTION VOLTAGE 24 VDC N/A 24 VDC 24 VDC
43 SIZE ANSI FACING POSITION HERTZ N/A N/A - -
44 CONNECTIONS in CLASS PHASE N/A N/A - -
45 SUCTION VTA - VTA BOTTOM COOLING WATER INLET RETURN DESIGN MAX
46 DISCHARGE VTA - VTA SIDE TEMP °C N/A MAX N/A N/A N/A
47 FLUSH PRESS. (barg) N/A MIN N/A N/A N/A
48 SOURCE -
49 LIQUID END JACKET REQ'D INSTRUMENT AIR MAX MIN
50 TYPE DIAPHRAGHM PLUNGER PRESSURE (barg) - -
51 DIAPHRAGM DIA mm NO. REQ.
52 VALVES/FEED SUCTION DISCHARGE APPLICABLE SPECIFICATIONS:
53 TYPE Ball (VTC) Ball (VTC) API 675 POSITIVE DISPLACEMENT PUMPS - CONTROLLED VOLUME
54 NUMBER VTA VTA GOVERNING SPECIFICATION (IF DIFFERENT) :
55
56 REMARKS : -
57
58
59
60
61
62
63
64
65
66
67
68
69
70
71
72
P4D-3-MLN-M-DSH-0001 , Rev 1 Page 8 of 10
Corrosion inhibitor injection system Data Sheet

CONTROLS
1 MATERIALS (NOTE 2 PAGE 10 & VTC)
2 LIQUID END SS 316 TYPE :
3 CONTOUR PLATE - MANUAL REMOTE PNEUMATIC
4 HYDRAULIC DIAPHRAGM - AUTOMATIC LOCAL ELECTRONIC
5 PROCESS DIAPHRAGHM - STROKE CONTROL : VTA
6 PLUNGER - FLOWRATE RATED / NORMAL (Nm3/hr) VTA
7 LANTERN RING SS 316 PNEUMATIC (barg) : N/A
8 PACKING GLAND SS 316 MINIMUM N/A MAXIMUM N/A
9 PACKING Teflon Composite ELECTRONIC (mA) (NORMAL 24 VDC)
10 VALVE SS 316 MINIMUM VTA MAXIMUM VTA

11 VALVE SEAT SS 316 OTHER PURCHASE REQUIREMENT


12 VALVE GUIDE SS 316 NAMEPLATE UNITS U.S CUSTOMARY SI
13 VALVE BODY SS 316 VENDOR FURNISHED PROCESS PIPING ON SKID PACKAGE
14 VALVE GASKET - VENDOR REVIEW PIPNG DRAWINGS
15 FRAME - VENDOR FURNISHED PULSATION SUPPRESSION DEVICES
16 SPECIAL MATERIAL TESTS (2.13.1.3) VENDOR FURNISHED RELIEF VALVE
17 INTERNAL EXTERNAL
18 MINIMUM DESIGN METAL TEMPERATURE O
C VTA
19 LOW AMBIENT TEMPERATURE MATERIAL TESTS (2.13.5) RELIEF VALVE SETTING (barg) 85
20 VENDOR FURNISHED BACK-PRESSURE VALVE
21 DOUBLE CHECK VALVE REQUIRED
22 QA INSPECTION AND TEST OIL-FILLED PRESSURE GAUGES REQUIRED
23 COMPLIANCE WITH INSPECTORS CHECK LIST VENDOR FURNISHED CONTROL PANEL
24 CERTIFICATION OF MATERIALS BASEPLATE PREPARED FOR EPOXY GROUT
25 FINAL ASSEMBLY CLEARANCES PROVIDE TECHNICAL DATA MANUAL
26 SURFACE AND SUBSURFACE EXAMINATIONS CALIBRATION GAUGE
27 RADIOGRAPHY FOR COMPLETE SCOPE OF SUPPLY, REFER TO PAGE 3 AND
28 ULTRASONIC P&ID NO. P4D-3-MLN-P-PID-8003
29 MAGNETIC PARTICLE PREPARATION FOR SHIPMENT

30 LIQUID PENETRANT DOMESTIC EXPORT BOXING


31 CLEANLINESS PRIOR TO FINAL ASSEMBLY OUTDOOR STORAGE MORE THAN 6 MONTHS
32 HARDNESS OF PARTS, WELDS & HEAT AFFECTED ZONES DOMESTIC EXPORT BOXING
33 FURNISH PROCEDURES FOR OPTIONAL TEST WEIGHTS (KG)
34 TESTS REQ'D WIT OBS PUMP VTA BASE - GEAR N/A DRIVER VTA
35 HYDROSTATIC
36 STEADY STATE ACCURACY DRIVERS
37 MECHANICAL RUN MOTOR : VTA
38 PERFORMANCE MANUFACTURER VTA
39 TYPE DC Motor (VTC)
40 FRAME NO. VTA
41 LUBRICATION FLUID (NOTE 3 PAGE 10) CONSTANT SPEED VTA
42 CRANKCASE INTERMEDIATE VARIABLE SPEED VTA
43 HYDRAULIC FLUID KW VTA RPM VTA
44 ACCESSORIES VOLTS 24 VDC PHASE N/A
45 SPEED REDUCER MANUFACTURER HERTZ N/A SERVICE FACTOR 1.0
46 INTEGRAL SEPARATE ENCLOSURE TEFC
47 MODEL OTHER (SEE SEPARATE DATA SHEETS) -
48 RATIO GAS DRIVEN -
49 BASEPLATE UNDER Part of Package STEAM TURBINE -
50 COUPLING MANUFACTURER OTHER AIR -DRIVEN
51 TYPE
52

53 DIMENSIONS (KG)

54 Pump Dimensions VTA

55

56

57

58

59 REMARKS : -

60 1. Pump Type shall be confirmed by Vendor

61

62

63

64

65

66

67
P4D-3-MLN-M-DSH-0001 , Rev 1 Page 9 of 10
Corrosion inhibitor injection system Data Sheet

1 NOTES
2
3 1. INJECTION RATE IS ADJUSTABLE FROM MAX AND TURNDOWN.
4 2. VENDOR SHALL PROVIDE PUMP AND PACKAGE MATERIAL SUITABLE FOR THE CHEMICAL LIQUID.
5 3. PUMP LUBRICATION AS PER MANUFACTURER STANDARD.
6 4. ACCURACY OF VOLUMETRIC OUTPUT SHALL BE WITHIN 1 % OF FULL INJECTION RANGE.
7 5. PUMP DISCHARGE PRESSURE SHALL NOT EXCEED THE MAXIMUM PRESSURE STATED IN PUMP DATA SHEET.
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
64
65
66
67
P4D-3-MLN-M-DSH-0001 , Rev 1 Page 10 of 10

You might also like