1 2 3 4 5 6

25 50 R7 (8x)
1 Primary terminal
30 40 2 Terminal box for secondary terminals,
adjustment windings

30
and low voltage terminal from
capacitor voltage divider

25
3 Terminal flange FL21
1

40

50
4 Earth terminal

135
335
5 Center of gravity
A 6 Oil level glass A
7 Oil filling plug
100
8 Oil draining plug

Primary terminal
T=20 mm
Material: Aluminium
1235

B B
2133

6
5
7

Earth terminal
700
640

For cable D=8 to 15 mm


C Material: Nickelplated brass C
225

2 3
325 Total mass: 200 kg max
20

335
20 (4x)
Mass of oil: 41 kg max
8
335 Creepage dist. nom. 3625 mm.
4 Grey silicon rubber insulator
Static withstand test load 1000 N and dynamic withstand load
D 1400 N applied in any direction on primary terminal D