No Doc : F-INS-CM-1Y-024

Revisi :1 PRESSURE TRANSMITER


Tanggal : 17 April 2016 CALIBRATION
Halaman :1

TAG
PT-203 SERVICE N/A NOTIFIKASI
NO

Locatin Manufacture YOKOGAWA Range 0~25 BarG LS 0


Type EJA530 ±
A Amb Temp 21.1 C Accurac 0.075
y % US 25

Calibration Result
As
Found:
Rising Input Signal Falling Input Signal
Input Output Input Output
% BarG mA BarG mA % % BarG mA BarG mA %
Desig Actua Error Desig Desig Desig Actual Error
Design Design n Actual l n n n Actual
0 0 4 0.012 4.08 0.048 100 25 20 25.011 20.001 0.044
25 6.25 8 6.253 7.999 0.012 75 18.75 16 18.767 16.011 0.068
12.00 12 12.011
50 12.5 12 12.509 2 0.036 50 12.5 12.518 0.072
15.99 8 8.010
75 18.75 16 18.762 3 0.048 25 6.25 6.266 0.064
20.00 4
100 25 20 25.011 1 0.044 0 0 0.014 4.000 0.056
After Adjustment (As Left)
Rising Input Signal Falling Input Signal
Input Output Input Output
% BarG mA BarG mA % % BarG mA BarG mA %
Desig Actua Error Desig Desig Desig Actual Error
Design Design n Actual l n n n Actual
0 0 4 0 4.000 0 100 25 20 25 20.00 0
25 6.25 8 6.25 8.000 0 75 18.75 16 18.75 16.00 0
12.00 12 12.00
50 12.5 12 12.50 0 0 50 12.5 12.5 0
16.00 8 8.00
75 18.75 16 18.75 0 0 25 6.25 6.25 0
20.00 4
100 25 20 25 0 0 0 0 0 4.00 0

Test Equipment Serial Number Cal Date


Source Pressure (ADDITEL 672) 27314100095 -
HART Communicator 11034984 -
Power Supply 24V EE190617 -
Crystal Digital Test Gauge 5KPSIXP2I-IA

Remarks
1. adjust lower trim and upper trim
Dilakukan Oleh Diperiksa Oleh

Tanda Tangan

Zen
Koordinator EIC
Tanggal 7 Februari 2017 21 Oktober 2011