USER MANUAL

209 SPTE
1. WATER

2. 2. CORROSION PROTECTION
2.1. VITROFLEX HI-TECH
2.2. Magnesium anode

3. PRODUCT CHARACTERISTICS
3.1. Storage
3.2. Heat exchanger
3.3. Insulation

4. INSTALLATION, USE AND MAINTENANCE


4.1. Installation
4.2. Use
4.3. Maintenance

5. DRAWING

6. INSTALLATION DIAGRAM

7. PERFORMANCE

8. ELECTRIC DIAGRAMS
8.1. Standard control panel
8.2 Control panel equipped with electric kit

9. ANODE TESTER
SCHEME

10. TROUBLESHOOTING

THE EQUIPMENT IS IN ACCORDANCE WITH CE DIRECTIVE 97/23 (ARTICLE 3 PARAGRAPH 3)


L’ACQUA. Type heat leakage (at + 40 °C between
1. WATER tanker and environment) KW/h
Check that the physical-chemical characteristics of water are 80 0.064
within the values shown into EC directive 80/778. 100 0.074
As far as Italy is concerned, also refer to both DPR 24-05-1988 150 0.077
n.236 as amended and integrated (at present, the Ministerial 200 0.090
Decree issued by the Ministry of Health on 14/07/1988 and the 300 0.110
Ministerial Decree issued by the Ministry of Health on 14/02/1989
as well are in force) and DM26/03/1991. 3.4. Electric kit.
Make use of treatment systems that are suitable to keep the potable Cylinders 209 SPTE may be equipped with an optional electric kit,
water characteristics as above specified and being in compliance with which consists of:
what provided for by the Authorities in charge. - Winter-summer switch (pump / element)
- Timer
2. CORROSION PROTECTION - Manually rechargeable safety thermostat
- 220 Volt 2000 watt monophase electric element.
2.1. VITROFLEX HI-TECH
Cylinders’ surface of series 209 SPTE has been treated with the 4. INSTALLATION, USE AND MAINTENANCE
anticorrosive VITROFLEX HI-TECH, which is waterproof,
dielectric, highly thermal shock-resistant and collision proof ; 4.1. Installation
furthermore, it can ensure the best alimentary-sanitary Always arrange for safety valves and expansion tanks for the primary
characteristics. VITROFLEX HI-TECH, in fact, makes SICC and secondary circuits. During the installation phase, always comply
cylinders suitable for the potable water supply, in accordance with with the laws in force and the drawings attached. The appliance shall
EEC directive 89/109. always be equipped with a cathode protection (magnesium anode).
Always arrange for an automatic air discharge valve to be placed on
2.2. Magnesium anode the cylinder upper side, by the hot water outlet line. Make use of
Cylinders 209 SPTE have an internal corrosion protection dielectric couplings when cylinder is connected to tubes which are
consisting of a fully active system given by magnesium anodes. Its made of another material. Charge and raise steam the primary circuit
wear status must be periodically checked each 6 months, at least, before the sanitary water tank. See the thermostat wiring diagram as
by pressing the proper tester key and being sure that the indicator for the electric connections (series 209 SPTE).
position stays within the green zone of the reading field, otherwise
the anode replacement should be arranged as soon as possible. To fit the electric element proceed as follows:
- remove the relevant coupling plug (1 ¼”);
3. PRODUCT CHARACTERISTICS - assembly the element;
- then connect it and arrange for a safety series manual charge
Series 209 SPTE products deal with cylinders created to produce thermostat, as to the thermostat, to avoid boiling.
hot sanitary water. They have been manufactured both in the
vertical and horizontal versions and they are particularly suitable 4.2. Use
for plants of small and medium sizes. They are equipped with The cylinder has been manufactured to produce hot water only;
brackets for the wall fastening as well as threaded couplings for therefore, any other different use shall be considered as dangerous
the feeding hydraulic connections. They mainly consist of a tanker, and unsuitable.
an exchanger and an insulation. The cylinder should be used in accordance with the temperature and
pressure limits shown on the nameplate and within such booklet as
3.1. Storage well.
Tankers have been manufactured with high quality carbon steel Check the magnesium anode at least 2 times a year and during the
plates. Their relevant arc welding deals with a totally automatic boiler normal use; such checks should be more frequent in case
procedure, which has been approved by the main testing entities. water is particularly aggressive.
Max. operation pressure allowed is of 8 bar and max. temperature
allowed is of 99 °C. Series 209 SPTE’s tanker has been internally 4.3. Maintenance
treated with VITROFLEX HI-TECH anti corrosive, so that it can Magnesium anode replacement
hold water for alimentary-sanitary purposes, in accordance with Discharge the cylinder, remove the anode tester cable, then unscrew
EEC directive 89/109. the anode plug, by means of a 40mm socket spanner, and put a
vessel for the water of the tanker lower part under the same plug.
3.2. Heat Exchanger. Make use of original anodes and gaskets to replace the old ones.
The heat exchanger consists of a pigtail coil. 12 bar is its max. Then, fill the boiler again and make sure that there is no leakage.
operation pressure, whilst 99 °C is its max. temperature.

! ! Warning !
3.3. Insulation Always disconnect the power supply before any
Insulation concerning series 209 SPTE consists of a hard – high
kind of operation (assembly, maintenance, technical
density polyurethane insulation lined with a pre-coated lamination,
repair, etc.) !
allowing to limit leakage according to the values shown as follows:
elettrica
5. DRAWING.

Dc L La Lb Lc Ld Le
MOD. A/B C/D E
mm mm mm mm mm mm mm
80 440 825 180 90 290 175 390 3/4" 1" 1 1/4"

100 440 900 190 100 330 180 485 3/4" 1" 1 1/4"

150 500 1125 205 90 540 200 630 3/4" 1" 1 1/4"

200 500 1500 205 115 790 275 690 3/4" 1" 1 1/4"

300 600 1365 225 90 740 220 830 3/4" 1" 1 1/4"

Re

LEGENDA :
Dc Diameter
A Primary Circuit inlet
B Primary Circuit outlet
C Sanitary water inlet
D Sanitary water outlet
E Auxiliary connection
Re Electric element connection
6. INSTALLATION DIAGRAM

VA VM T

PP
V V

NR

PR

VS
VE
T NR
V

RP
V

V NR V
TR

LEGENDA

TR Thermostat
V Manual valve
VS Safety valve
NR Check valve
VE Expansion tank
PR Recirculation pump
PP Primary circuit pump
T Thermometer
VA Air valve
VM Motor-mixing valve
RP Pressure reduction gear
7. PRESTAZIONI - PRESTACIONES – PERFORMANCES - LEISTUNG

PRIMARY CIRCUIT CAPACITY (l/h)

FLOW RATE IN THE FIRST 10’


EXCHANGE SURFACE (sqm)
CONTINUOUS FLOW (l/h)
THERMAL POWER (kW)

REHEAT TIME (minutes)


MOD.

80 15,5 405 0,56 1374 21 104


100 15,5 405 0,56 1374 27 113
150 24,0 624 0,90 2117 26 173
200 31,6 821 1,13 2782 26 229
300 40,0 1042 1,34 3532 31 311

* The above data suppose what follows


Sanitary inlet temperature 12 °C
Sanitary working temperature 45 °C
Storage temperature 60 °C
Primary inlet / outlet temperature 80/70 °C

Refer to the SICC program calculation or contact the sales


technical service in order to know the appliance
performances during its operation.
8. ELECTRIC DIAGRAMS

8.1. Standard control panel

L N1 T1 S4

220 VOLT
P1 P2

8.2. Control panel equipped with electric kit

F A

D
L N1 T1 S4

220 VOLT
P1 P2
Re

LEGENDA
A THERMOSTAT
B THERMOMETER
C ANODE TESTER
D TIME PROGRAMMER
E PUMPSWITCH / ELEMENT
F SAFETY THERMOSTAT
T CYLINDER CASE
Re ELECTRIC ELEMENT
P1 SANITARY CIRCUIT PUMP
P2 HEATING PUMP
9. ANODE TESTER DIAGRAM

LEGENDA
1 MAGNESIUM ANODE
2 ELECTRIC INSULATION
3 ZINC PLATED PLUG
4 FLAT WASHER
5 EXTERNAL NOTCHED WASHER
6 NUT
7 EYLET TERMINAL
8 ANODE COLLECTION CABLE
9 SHORT CIRCUIT CABLE
10 EYLET TERMINAL
11 FEMALE FASTOM INSULATED
12 FEMALE FASTOM INSULATED
13 WASHER
14 BOLT
15 MEDIUM COUPLING
16 ANODE CHECK PUSH-BUTTON
10. TROUBLESHOOTING

Problem Cause Solution


Water leakage from the
1 No internal seal. Fit the seal by disassembling the anode.
anode.
No circulation due to a lock of the pump or Unlock or check the pump/valve after being sure
valve serving the primary circuit. that they are power supplied.
No or poor sanitary hot
2 Vent and install an automatic air valve if there is
water production. Too much air into the primary circuit.
not any.
Limestone encrusted exchanger Clean the heat exchanger.
Check the leakage by disassembling the primary
circuit and pressurising the secondary circuit, by
Too much pressure increase
3 Likely hole into the heat exchanger. closing both secondary circuit inlet and outlet,
within the primary circuit.
inserting a pressure gauge to check the pressure
change. Change the heat exchanger.
Too much pressure of the supply network Install a pressure reduction filter.

In case the pressure increase coincides with the


No expansion tank or insufficient expansion temperature increase, it is important to check if
Too much pressure increase tank temporary pressure. there is an expansion tank and its temporary
4 pressure as well.
within the secondary circuit.
The cylinder pressure must never be higher than
what provided for by its nameplate. A properly
No safety valve.
calibrated safety valve is always needed and
required.
Check that the sensor (bulb) has been correctly
installed and that it properly operates.
The primary circuit valve or Thermostat bulb has not been installed or it Check by means of tester the thermostat contact
5
pump do not start up. does not work. closing when the water temperature is lower than
the setup value. In case the contact does not
close, replace the thermostat.
Ground the appliance. Make use of dielectric
Excessive stray currents. joints. Ground the surrounding electric
6 Anode fast wear. appliances.
Excessive free surface to be protected, due to
Replace the cylinder.
stress of the internal anti-corrosion coating.