You are on page 1of 28

3CJ2 Switch-Disconnectors

Medium-Voltage Equipment
Selection and Ordering Data

Catalog HG 12.21 · 2008

Answers for energy.


3CJ2 Switch-Disconnectors

R-HG12-029.tif

2 Siemens HG 12.21 · 2008


3CJ2 Switch-Disconnectors Contents

Contents Page

3CJ2 Description 5
Switch-Disconnectors General
Construction and mode of operation
6
7
1
Construction and mode of operation, standards 9
Medium-Voltage Equipment
Ambient conditions, dielectric strength
Catalog HG 12.21 · 2008 and product range overview 10

Invalid: Catalog HG 12 · 1993, Part 2

Equipment Selection 11
Ordering data and configuration example
Selection of basic type, switch-disconnector
12
13
2
Selection of operating mechanism and built-on
components 14
Additional equipment 16
Accessories and spare parts 17

Technical Data 19
Electrical data, dimensions and weights
Circuit diagrams
20
23
3
Data of built-on components 24

Annex 25
Inquiry form
Configuration instructions
26
27 4
Configuration aid Foldout page

Siemens HG 12.21 · 2008 3


3CJ2 Switch-Disconnectors

R-HG11-173.tif

4 Siemens HG 12.21 · 2008


3CJ2 Switch-Disconnectors Description
Contents

Contents Page

Description 5
General 6 1
Construction and mode of operation:
Construction 7
Arc-extinguishing medium 7
Arc-extinguishing process 7
Switching process 8
Operating mechanism 8
Fuse assembly 8
Make-proof earthing switch 8
Shunt release 9
Auxiliary switch 9
Spherical joint mechanism 9
R-HG11-174.tif

Standards 9
Industrial application: Refinery
Ambient conditions 10
Dielectric strength 10
Product range overview 10

Siemens HG 12.21 · 2008 5


Description 3CJ2 Switch-Disconnectors
General

3CJ2 switch-disconnector – The Loadable

Switch-disconnectors combine the functions of a and are therefore used for breaking load currents up to
switch with the establishment of an isolating distance their rated normal current.

1 (disconnector),

3CJ2 – The Sudden

R-HG12-031.tif
R-HG12-030.tif

The medium-voltage switch-disconnector 3CJ2 is designed In combination with fuses, switch-disconnectors can also be
according to the clear disconnector principle. Proven used to break short-circuit currents. The short-circuit current
hard-gas flat arcing chambers provide a higher switching is interrupted by the fuses. Subsequently, the fuses trip the
capacity than that of its competitors. Simple blade contacts three poles of the switch-disconnector, disconnecting the
and a torsion-bar spring-operated mechanism increase its faulty feeder from the power system.
making capacity and the mechanical endurance.
While connecting consumers, making on an existing short-
circuit cannot be excluded. That is why, today, switch-
disconnectors generally feature a short-circuit making
capacity.

6 Siemens HG 12.21 · 2008


3CJ2 Switch-Disconnectors Description
Construction and mode of operation

Construction
A welded base frame (1) carries the disconnector 1
arrangement (2) and the flat arcing chambers (3).

R-HG12-032.eps
Furthermore it contains the spring-operated mechanism 3
(high-speed closing and high-speed opening), or the
stored-energy mechanism (storage of high-speed
closing/opening, manual tripping and free tripping). 2 1
Optionally, the switch-disconnector can also be equipped
with a make-proof earthing switch (4) or a fuse assembly.
4
Switch-disconnectors are supplied according to category A
(20 breaking operations at rated current). A special version
with category B (100 breaking operations at rated current) is
possible. Switch-disconnector with make-proof earthing switch

The 3CJ2 can be wall-mounted with the isolating contact 1 Base frame 3 Flat arcing chamber
2 Disconnector arrangement 4 Make-proof earthing switch
side upwards or downwards, as well as on the floor or on
the ceiling – in inverted position. For wall mounting, the 3
preferred mounting position is with the isolating contact side
upwards. A 5

Arc-extinguishing medium 6
6 3
In switch-disconnectors, the arc is not extinguished in a
HG12-2117a eps

vacuum interrupter, but they operate according to the prin-


ciple of a hard-gas switch. This means that the arc splits off 5
some gas from an insulating material which surrounds the arc 7
closely, and this gas quenches the arc fast and effectively. 3
As the material providing the gas cannot regenerate itself, the
number of operating cycles is lower than that of the vacuum B 5
interrupters. Nevertheless, switch-disconnectors according to
6
the hard-gas principle are the most frequently used ones, as 6 3
they have a good cost/performance relationship.
HG12-2118a eps

Arc-extinguishing process 7
5
3CJ2 switch-disconnectors operate with a flat hard-gas arcing
chamber (3). 3
5
A: Switch in closed position.
C 8
B: During the opening movement, the contact blade (5) is
separated first. As the auxiliary contact blade (6) guided in 6
the arcing chamber is still touching, the current now flows 6 3
HG12-2119a eps

through the auxiliary contact blade.


5
C: When the contact blades reach the isolating distance, the
auxiliary contact blade opens the connection suddenly. The
breaking arc (8) burns in a small gap, and the thermal effect 3
releases enough gas to extinguish the arc rapidly and effec- 5
tively. D 6

D: Switch in open position, arc extinguished. 6


3
HG12-2120a eps

Representation of the disconnecting and arc-extinguishing process


3 Flat arcing chamber 7 Current flow (yellow)
5 Contact blade 8 Breaking arc
6 Auxiliary contact blade

Siemens HG 12.21 · 2008 7


Description 3CJ2 Switch-Disconnectors
Construction and mode of operation

Switching process
The switch-disconnector can be equipped with a spring-
operated or stored-energy mechanism. Both mechanism
types decouple the actuation of the operating shaft from the
1 2 actual switching process. When the operating shaft (1) is

1 3
actuated manually or by motor, the torsion bar springs (2)
located in the operating shaft are pre-charged, forming an
energy store. At the end of the rotary movement, a cam
plate releases the latch, and thus the energy store. In this
way, the closing and opening speed is independent of the
operator.
R-HG12-033.eps

In stored-energy mechanisms (STO), additional springs (3)


are charged during the closing process, and used as energy
Energy store of the switch-disconnector stores for the opening operation. Opening can now be done
1 Operating shaft by actuation of the operating shaft or free tripping (tripping
2 Torsion bar spring (in operating shaft) by operation of a fuse or a shunt release).
3 Additional springs
Operating mechanism
3CJ2 switch-disconnectors can be operated locally by hand
or from remote by means of a motor operating mechanism.
A motor operating mechanism is also available on request
for the make-proof earthing switch.

Fuse assembly
The fuse assembly is mounted on a base frame attached at
the pivot point of the switch-disconnector. On this base
HG12-2121 eps

frame, the post insulators and contact pieces are mounted as


well. The tripping mechanism is directly connected to the
switch-disconnector tripping system. The tripping mechan-
Fuse assembly
ism can only operate the switch if the switch is equipped
with a stored-energy mechanism.
If a 3CJ2 with fuse assembly has to be installed with the iso-
lating contact side downwards (180° turn), this has to be
specified as a special design due to the different force condi-
tions (effect against the force of gravity). Faster breaking
according to IEC 62271-105 with 100 A fuses (12 kV) and
80 A fuses (24 kV) is also possible as a special design.
EO EP
Make-proof earthing switch
Make-proof earthing switches can be mounted on the
opening side (EO), the pivot point (EP), and the fuse cross-
member (EF). If the make-proof earthing switch has to be
HG12-2122_en eps mounted on the fuse cross-member, it will be located inside
the base frame for the type 3CJ25, and outside the base
frame for all other switch-disconnector types.

High-speed closing of the earthing switch operating mecha-


EO EF inside EF outside
nism takes place via tilt springs. When the shaft is operated,
the dead point is passed after approx. 15°, and the high-
speed closing is activated.

HG12-2123_en eps
Mechanical interlocking between the make-proof earthing
switch and the switch-disconnector is always possible
Mounting options of the make-proof earthing switch
(with restrictions in case of motor operating mechanisms).

8 Siemens HG 12.21 · 2008


3CJ2 Switch-Disconnectors Description
Construction and mode of operation, standards

Shunt release
For remote tipping, 3CJ2 switch-disconnectors with
stored-energy mechanism can be equipped with a shunt
release (1). For control via maintained contact, the tripping
current must be interrupted by an auxiliary switch operated
by the switch-disconnector; otherwise, the tripping coil will
be overloaded. 1
A shunt release only works on a switch-disconnector with a

R-HG12-034.eps
stored-energy mechanism.
1

Switch-disconnector with stored-energy mechanism


and built-on release (1)

Auxiliary switch
3CJ2 switch-disconnectors can be delivered with auxiliary
switches with 2 NO + 2 NC or 5 NO + 5 NC; the type 3CJ24
with a maximum of 3 NO + 3 NC. Make-proof earthing
switches are supplied with 2 NO + 2 NC.

The auxiliary switch is mounted on the switch-disconnector


between phases L1 and L2. If auxiliary switches are also

R-HG12-035.eps
required for built-on make-proof earthing switches, they are
located between phases L2 and L3 – in case of pivot-point
arrangement – and between phases L1 and L2 for arrange- Built-on auxiliary switch
ment on the opening side.

Spherical joint mechanism


Spring-operated switch-disconnectors can also be operated
through a spherical joint mechanism. The rotary movement
is transmitted from the front side of a switchgear panel to
the switch via levers and rods. 1

Spherical joint mechanisms are also available for the make-


proof earthing switches.
2
HG12-2124 eps

Standards
The switch-disconnectors conform to the following 3 4 5 6 7 8
standards and recommendations: Spherical joint mechanism 3DX2
1 Operating shaft lever
• VDE 0671-102 (former VDE 0670 Part 2)
2 Switching rod (threaded rod with spherical
• VDE 0670-301 (former VDE 0670 Part 3) joints M12 on both sides)
3 Lever on the drive shaft
• IEC 129
4 Drive shaft: steel shaft with 25 mm Ø,
• IEC 60265-1 or insulating shaft with 30 mm Ø
5 Notch (only for disconnector and earthing switch)
• IEC 60694 (VDE 0670 Part 1000)
6 90° stop CLOSE-OPEN
• IEC 62271-105 (VDE 0670 Part 303/9.94) 7 Indication label
– black for switch-disconnector and disconnector
– red for earthing switch and make-proof earthing switch
8 Operating lever for spherical joint mechanism 3DX2

Siemens HG 12.21 · 2008 9


Description 3CJ2 Switch-Disconnectors
Ambient conditions, dielectric strength and product range overview

Ambient conditions
40°C The switch-disconnectors are designed for the normal
operating conditions defined in the standards.

Condensation can occasionally occur under the ambient


max. 95% per day conditions shown opposite.
1 -20°C
max. 70% per month

HG12-2125_en eps

1.50 Dielectric strength


The dielectric strength of air insulation decreases with
Altitude correction factor

1.40 increasing altitude due to low air density. According to


IEC 62271-1, the values of the rated lightning impulse with-
1.30
stand voltage and the rated short-duration power-frequency
withstand voltage specified in the chapter “Technical Data”
apply to a site altitude of 1000 m above sea level. For an
1.20
altitude above 1000 m, the insulation level must be cor-
rected according to the opposite diagram.
HG11-2517c_en eps

1.10
The characteristic shown applies to both rated withstand
voltages.
1.00
1000 1500 2000 2500 3000 3500 m 4000 To select the devices, the following applies:
Site altitude U W U0 x Ka
U Rated withstand voltage under reference atmosphere
U0 Rated withstand voltage requested for the place of installation
Ka Altitude correction factor according to the opposite diagram

Example
For a requested rated lightning impulse withstand voltage
of 75 kV at an altitude of 2500 m, an insulation level of 90 kV
under reference atmosphere is required as a minimum:
90 kV W 75 kV x 1.2

Product range overview

Rated voltage Type of operating Rated normal current (A)


mechanism

kV 400 630 1000


12 Spring-operated (SPR) n n
Stored-energy (STO) l n
17.5 Spring-operated (SPR) n
Stored-energy (STO) l
24 Spring-operated (SPR) n n
Stored-energy (STO) l n
36 Spring-operated (SPR) n n
Stored-energy (STO) l

l 3CJ2 with fuse assembly n 3CJ2 without fuse assembly

10 Siemens HG 12.21 · 2008


3CJ2 Switch-Disconnectors Equipment Selection
Contents

Contents Page

Equipment Selection 11
Ordering data and configuration example 12

Selection of basic type, switch-disconnector:


Voltage level 12 kV 13
Voltage level 17.5 kV 13
Voltage level 24 kV 13
Voltage level 36 kV 14

Selection of operating mechanism and


built-on components:
Design of operating mechanism 14
2
Design of motor operating mechanism 14
Design of shunt release 15
R-HG12-036.tif

Design of make-proof earthing switch 15


Design of auxiliary switch 15
Switch-disconnector with earthing switch

Special version / Additional equipment 16


Accessories and spare parts 17
R-HG12-037.tif

Switch-disconnector with fuse assembly

Siemens HG 12.21 · 2008 11


Equipment Selection 3CJ2 Switch-Disconnectors
Ordering data and configuration example

Order number structure Built-on components and special versions («)


The switch-disconnectors are described by a 12-digit order For some built-on components and special versions, “-Z” is
number. The positions 13 to 16, which are provided for the added to the order number and a descriptive order code
usual 16-digit order number, are not required. These 12 follows. If several built-on components and special versions
characters describe the data of the switch. are required, the suffix “-Z” is listed only once. If a requested
special version is not in the catalog and can therefore not be
ordered via order code, it has to be identified with Y 9 9
after consultation. The agreement hereto is made directly
between your responsible sales partner and the order
processing department in the Switchgear Factory Berlin.

2 Position:
Order No.:
a: alphabetical
1
3
2
C
3
J
4
2
5
n
n: numerical
6
n
7
n


8
n
9
a
10 11 12
a n n – «
Order codes
n n n
Primary data
1st position Superior group
Switching devices

2nd position Main group


Switch and switch-disconnector

3rd position Subgroup


Indoor switch-disconnector, 3-pole

4th to 7th position Basic equipment


Design and ratings of the
switch-disconnector

Secondary data
8th to 12th position Operating mechanism and components

Built-on components, special versions («)


Initiated with “-Z”
Group of 3 after the Order No.
Format: a n n

Configuration example
In order to simplify the selection of the correct order number
for the requested switch type, you will find a configuration
example on each page of the chapter “Equipment Selection”.
For the selection of the operating mechanism and built-on
component types, always the last example of the primary
part was taken over and continued, so that at the end of the On the foldout page we offer a configuring aid.
equipment selection (page 16) a completely configured Here you can fill in the order number you have
switch results as an example. determined for your switch.

Example for Order No.: 3 C J 2 5 4 2 – n n n n n


Order codes:

12 Siemens HG 12.21 · 2008


3CJ2 Switch-Disconnectors Equipment Selection
Selection of basic type, switch-disconnector

12 kV Position: 1 2 3 4 5 6 7 – 8 9 10 11 12 Order codes


50/60 Hz Order No.: 3 C J 2 n n n – n n n n n – « n n n

Stored-ener. mech. (STO)


Type of oper. mechanism
Spring-oper. mech. (SPR)
Rated short-dur. power-
Rated lightning impulse

freq. withstand voltage


earth/isolating distance
earth/isolating distance

without fuse (w/oFu)


Built-on component:
Pole-center distance
withstand voltage

with fuse (Fu) 2)


Shaft length 1)
Rated voltage

Rated normal

See page 14
See page 14
See page 14
See page 15
See page 15

See page 16
current

Ur Up Ud Ir PCD SL

kV kV kV A mm mm
12 75/85 28/32 400 165 566 STO Fu 292 3 C J 2 4 4 2
210 866 STO Fu 292 3 C J 2 3 4 2
630 165 566 SPR w/oFu 3 C J 2 4 6 1
STO w/oFu 3 C J 2 4 6 8
210 866 SPR w/oFu 3 C J 2 3 6 1
STO w/oFu 3 C J 2 3 6 8
1000 210 866 SPR w/oFu 3 C J 2 3 7 1
2
1) With motor operating mechanism, the shaft length sometimes deviates
from the specified values (for actual values, refer to chapter “Technical Data”)
2) Specification of fuse dimension in mm

17.5 kV
50/60 Hz
Ur Up Ud Ir PCD SL Type of Built-on
operating compo-
kV kV kV A mm mm mechanism nent

17.5 95/110 38/45 400 210 766 STO Fu 292 3 C J 2 7 4 2


866 STO Fu 292 3 C J 2 8 4 2
630 210 766 SPR w/oFu 3 C J 2 7 6 1
866 SPR w/oFu 3 C J 2 8 6 1

24 kV
50/60 Hz
Ur Up Ud Ir PCD SL Type of Built-on
operating compo-
kV kV kV A mm mm mechanism nent

24 125/145 50/60 400 250 866 STO Fu 442 3 C J 2 5 4 2


275 966 STO Fu 442 3 C J 2 6 4 2
630 250 866 SPR w/oFu 3 C J 2 5 6 1
STO w/oFu 3 C J 2 5 6 8
275 966 SPR w/oFu 3 C J 2 6 6 1
STO w/oFu 3 C J 2 6 6 8
1000 250 866 SPR w/oFu 3 C J 2 5 7 1

Configuration example
3CJ2 switch-disconnector 3 C J 2
Rated voltage Ur = 24 kV
Rated lightning impulse withstand voltage Up = 125 kV
Rated short-duration power-frequency withstand voltage Ud = 50 kV
Rated normal current Ir = 400 A
Pole-center distance PCD = 250 mm, shaft length SL = 866 mm
Type of operating mechanism: stored-energy mechanism, components: with fuse assembly 5 4 2

Example for Order No.: 3 C J 2 5 4 2 – n n n n n


Order codes:

Siemens HG 12.21 · 2008 13


Equipment Selection 3CJ2 Switch-Disconnectors
Selection of basic type, switch-disconnector / Selection of operating mechanism and built-on components

36 kV Position: 1 2 3 4 5 6 7 – 8 9 10 11 12 Order codes


50/60 Hz Order No.: 3 C J 2 n n n – n n n n n – « n n n

Stored-ener. mech. (STO)


Type of oper. mechanism
Spring-oper. mech. (SPR)
Rated short-dur. power-
Rated lightning impulse

freq. withstand voltage


earth/isolating distance
earth/isolating distance

without fuse (w/oFu)


Built-on component:
Pole-center distance
withstand voltage

See page 15
See page 15
See page 15

See page 16
with fuse (Fu) 2)
Shaft length 1)
Rated voltage

Rated normal
current

Ur Up Ud Ir PCD SL

kV kV kV A mm mm
36 170/195 70/80 630 370 1500 SPR w/oFu 3 C J 2 1 6 1
STO Fu 537 3 C J 2 1 6 2
400 1500 SPR w/oFu 3 C J 2 2 6 1
STO Fu 537 3 C J 2 2 6 2
1000 370 1500 SPR w/oFu 3 C J 2 1 7 1
400 1500 SPR w/oFu 3 C J 2 2 7 1

2 1) With motor operating mechanism, the shaft length sometimes deviates


from the specified values (for actual values, refer to chapter “Technical Data”)
2) Specification of fuse dimension in mm

8th position
Design of operating mechanism

Equipment with operating shaft lever: Operating mechanism:


with/without left/right

Without (for motor operating mechanism) Right 1


Without (for motor operating mechanism) Left 2
With (for manual operating mechanism) 3) Right 3
With (for manual operating mechanism) 3) Left 4
3) At the 9th position: A

9th position
Design of motor operating mechanism

DC voltage AC voltage

Without motor operating mechanism 4) A


24 V DC B
60 V DC C
110 V DC D
125 V DC H
220 V DC E
110 V AC 50/60 Hz F
220 V AC 50/60 Hz G
4) At the 8th position: 3 or 4

Configuration example
3CJ2 switch-disconnector 3 C J 2
Rated voltage Ur = 36 kV
Rated lightning impulse withstand voltage Up = 170 kV
Rated short-duration power-frequency withstand voltage Ud = 70 kV
Rated normal current Ir = 630 A
Pole-center distance PCD = 400 mm, shaft length SL = 1500 mm
Type of operating mechanism: stored-energy mechanism; built-on component: with fuse assembly 2 6 2 –
Equipment for manual operating mechanism: with operating shaft lever, operating mechanism on the right 3
Without motor operating mechanism A

Example for Order No.: 3 C J 2 2 6 2 – 3 A n n n


Order codes:

14 Siemens HG 12.21 · 2008


3CJ2 Switch-Disconnectors Equipment Selection
Selection of operating mechanism and built-on components

10th position Position: 1 2 3 4 5 6 7 – 8 9 10 11 12 Order codes


Design of shunt release Order No.: 3 C J 2 n n n – n n n n n – « n n n

See page 16
DC voltage AC voltage

Without shunt release 1) 2) A


24 V DC B
60 V DC C
110 V DC D
125 V DC H
220 V DC E
110 V AC 50/60 Hz F
220 V AC 50/60 Hz G
1) Basically for switch-disconnectors with spring-operated mechanism
2) Not for switch-disconnectors with stored-energy mechanism and without fuse assembly

11th position
Design of make-proof earthing switch 2
Built-on make-proof earthing switch Mechanical
interlocking

Without make-proof earthing switch 0


With make-proof earthing switch on pivot-point side 3) Without 3
With make-proof earthing switch on pivot-point side 3) With 4
With make-proof earthing switch on opening side Without 5
With make-proof earthing switch on opening side With 6
With make-proof earthing switch on fuse cross-member 4) Without 7
With make-proof earthing switch on fuse cross-member 4) With 8

3) Not for switch-disconnectors with fuse assembly


4) Only for switch-disconnectors with fuse assembly

12th position
Design of auxiliary switch
Built on the switch-disconnector Built on the make-proof
earthing switch

2 NO + 2 NC 3 NO + 3 NC 5 NO + 5 NC 5) 2 NO + 2 NC
Without auxiliary switch 0
n 1
n 2
n n 3
n n 4
n 5
n n 6

5) Not available for switch-disconnector with PCD 165 mm

Configuration example
3CJ2 switch-disconnector 3 C J 2
(Ur = 36 kV, Ir = 630 A, PCD = 400 mm, SL = 1500 mm
with stored-energy mechanism, with fuse assembly) 2 6 2 – 3 A
With shunt release 24 V DC B
With make-proof earthing switch on the opening side and with mechanical interlocking 6
With auxiliary switch 3 NO + 3 NC at the switch-disconnector and 2 NO + 2 NC at the
make-proof earthing switch 6

Example for Order No.: 3 C J 2 2 6 2 – 3 A B 6 6


Order codes:

Siemens HG 12.21 · 2008 15


Equipment Selection 3CJ2 Switch-Disconnectors
Special version / Additional equipment

Special version / Additional equipment Position: 1 2 3 4 5 6 7 – 8 9 10 11 12 Order codes


Order No.: 3 C J 2 n n n – n n n n n – « n n n

Options

Signaling switch 1 NO + 1 NC for fuse tripping – Z B 0 1


Capacitive tap – Z B 0 2
Design with upgrading according to IEC 62271-105 – Z C 0 1
Design with category B upgrading (not for 36 kV switches) – Z C 0 2
Switch-disconnector fuse combination turned by 180° – Z C 0 3
Design with insulating shaft – Z C 0 4
Special length of the fuse dimension (only after consultation with the order
processing dept. in Berlin). Length to be specified in clear text – Z Y 0 1
Shortening the operating shaft (only after consultation with the order
processing dept. in Berlin). Length to be specified in clear text – Z Y 0 2
Shaft extension by means of joint or shaft piece. Length to be specified in clear text – Z Y 0 3

Configuration example
3CJ2 switch-disconnector 3 C J 2
Rated voltage Ur = 36 kV
Rated lightning impulse withstand voltage Up = 170 kV
Rated short-duration power-frequency withstand voltage Ud = 70 kV
Rated normal current Ir = 630 A
Pole-center distance PCD = 400 mm
Shaft length SL = 1500 mm
Type of operating mechanism: stored-energy mechanism
Built-on component: with fuse assembly 2 6 2 –
Equipment for manual operating mechanism: with operating shaft lever, operating mechanism on the right 3
Without motor operating mechanism A
With shunt release 24 V DC B
With make-proof earthing switch on the opening side and with mechanical interlocking 6
With auxiliary switch 3 NO + 3 NC at the switch-disconnector and 2 NO + 2 NC at the
make-proof earthing switch 6
With signaling switch 1 NO + 1 NC for fuse tripping – Z B 0 1

Example for Order No.: 3 C J 2 2 6 2 – 3 A B 6 6 – Z


Order codes: B 0 1

16 Siemens HG 12.21 · 2008


3CJ2 Switch-Disconnectors Equipment Selection
Accessories and spare parts

Remark for orders


The order numbers are applicable to switch-disconnectors of Note: Arc-suppression systems and other spare parts
current manufacture. When built-on components or spare must only be replaced by instructed personnel.
parts are being ordered for an existing switch-disconnector,
always quote the type designation, serial number and the
year of manufacture of the switch-disconnector to be sure to
get the correct delivery.

Designation Remarks Order No.

Operating shaft lever For switch-disconnector 3CX1025


For make-proof earthing switch 3CX1026
Switching rod To actuate the operating shaft lever Length 1025 mm PFS: 364035-005
up to 36 kV Length 2000 mm PFS: 364035-035
Auxiliary mechanism
Arc-suppression system
For motor operating mechanism Length 280 mm
12 kV
17.5 kV
3CX6015
3CY2056
3CY2057
2
24 kV 3CY2058
36 kV 3CY2068
Conducting path For 12 kV 400 A 3CY2062
630 A 3CY2061
1000 A 3CY2070
For 17.5 kV 400 A 3CY2064
630 A 3CY2063
For 24 kV 400 A 3CY2066
630 A 3CY2065
1000 A 3CY2072
For 36 kV 630 A 3CY2067
1000 A 3CY2073

Siemens HG 12.21 · 2008 17


Equipment Selection 3CJ2 Switch-Disconnectors
Accessories and spare parts

Designation Remarks Order No.

Spherical joint mechanism for 3CJ2 …-1/2 switch-disconnectors with spring-operated mechanism (data of widths X and L in clear text)
For switch-disconnector For recommended panel width
3CJ24... 600 – 750 mm 3DX2011 X =... L =...
3CJ23... 800 – 1000 mm 3DX2012 X =... L =...
3CJ25... 800 – 900 mm 3DX2011 X =... L =...
3CJ26... 900 – 1100 mm 3DX2012 X =... L =...
3CJ27... 800 – 900 mm 3DX2011 X =... L =...
3CJ28... 900 – 1000 mm 3DX2012 X =... L =...
3CJ22 3DX2012 X =... L =...
Spherical joint mechanism for make-proof earthing switch (data of widths X and L in clear text)
For switch-disconnector For recommended panel width
3CJ24... 600 – 750 mm 3DX2013 X =... L =...
3CJ23... 800 – 1000 mm 3DX2014 X =... L =...
3CJ25... 800 – 900 mm 3DX2013 X =... L =...
3CJ26... 900 – 1100 mm 3DX2014 X =... L =...

2 3CJ27...
3CJ28...
3CJ22
800 – 900 mm
900 – 1000 mm
3DX2013 X =...
3DX2014 X =...
3DX2014 X =...
L =...
L =...
L =...
Accessories for spherical joint Operating lever for switch-disconnector 3DX2081
mechanism Operating lever for make-proof earthing switch 3DX2082
Interlocking between switch-disconnector and make-proof earthing switch 3DX2072
Additive blocking solenoid with data of operating voltage 3DX2071-Z
Bearing for shaft extension 3DX2901
Setting lever for switchgear 3DX2902
Dowel pin for shaft extension 3DX2903

Data of spherical joint mechanism


3DX2 spherical joint mechanism
1 Operating shaft lever
2 Switching rod (threaded rod with spherical
joints M12 on both sides)
3 Lever on the drive shaft
1 4 Drive shaft: steel shaft with 25 mm Ø,
or insulating shaft with 30 mm Ø
5 Notch (only for disconnector and earthing switch)
6 90° stop CLOSE-OPEN
X

2 7 Indication label
HG12-2135 eps

L – black for switch-disconnector and disconnector


– red for earthing switch and make-proof earthing switch
8 Operating lever for spherical joint mechanism 3DX2
70

50
3 4 5 6 7 8

18 Siemens HG 12.21 · 2008


3CJ2 Switch-Disconnectors Technical Data
Contents

Contents Page

Technical Data 19
Electrical data, dimensions and weights:
Voltage level 12 kV 20
Voltage level 17.5 kV 20
Voltage level 24 kV 20
Voltage level 36 kV 21

Dimension drawings 21
Circuit diagrams 23
Data of auxiliary switch 24
Data of motor operating mechanism 24
R-HG12-038.tif

Arcing chambers, contact blades and auxiliary contact blades

3
R-HG12-039.tif

Fuse holders with separating shells

Siemens HG 12.21 · 2008 19


Technical Data 3CJ2 Switch-Disconnectors
Electrical data, dimensions and weights

withstand voltage across the isolating distance

withstand voltage across the isolating distance

Weight of switch-discon./built-on earth. switch

Catalog dim. drawing no. (see pages 21 to 23)


Rated short-time withstand current (1 s)
12 kV

Number of mechanical operating cycles

Torque of spring-operated mechanism


Rated short-duration power-frequency

Rated short-duration power-frequency

Rated cable-charging breaking current

Rated cable-charging breaking current

Torque of make-proof earthing switch


Torque of stored-energy mechanism
50/60 Hz

Rated closed-loop breaking current


Rated short-circuit making current

Shaft length (with built-on motor)


Rated earth-fault breaking current
Rated peak withstand current

under earth-fault conditions

Dimension of fuse assembly


withstand voltage to earth

withstand voltage to earth


Rated lightning impulse

Rated lightning impulse

Shaft length (standard)


Rated normal current

Pole-center distance
Order No.

Up Up Ud Ud Ir Ik Ip Ima I2a I4a I6a I6b n e

kV kV kV kV A kA kA kA A A A A mm mm mm mm Nm Nm Nm kg

75 85 28 32 400 25 1) 63 63 1) 400 50 150 86 1500 210 566 730 292 – 60 60 38/ 1


3CJ2 342...
10.5
75 85 28 32 630 25 63 63 630 50 150 86 1500 210 566 730 – 44 – 60 23/ 2
3CJ2 361...
9.5
75 85 28 32 630 25 63 63 630 50 150 86 1500 210 566 730 – – 60 60 23/ 2
3CJ2 368...
9.5
75 85 28 32 1000 32 80 63 1000 50 150 86 1500 210 866 866 – 44 – 60 23/ 2
3CJ2 371...
9.5
3CJ2 442... 75 85 28 32 400 25 1) 63 63 1) 400 50 150 86 1500 165 866 866 292 – 60 60 35/ 1
8
75 85 28 32 630 25 63 63 630 50 150 86 1500 165 866 866 – 44 – 60 20/ 2
3CJ2 461...
8
75 85 28 32 630 25 63 63 630 50 150 86 1500 165 866 866 – – 60 60 20/ 2
3CJ2 468...
8

3
17.5 kV Up Up Ud Ud Ir Ik Ip Ima I2a I4a I6a I6b n e
50/60 Hz kV kV kV kV A kA kA kA A A A A mm mm mm mm Nm Nm Nm kg

95 110 38 42 400 25 1) 63 63 1) 400 50 150 86 1500 210 766 866 367 – 62 65 48/ 3
3CJ2 742... 10
95 110 38 42 630 25 63 63 630 50 150 86 1500 210 766 866 – 54 – 65 28/ 4
3CJ2 761...
10
95 110 38 42 400 25 1) 63 63 1) 400 50 150 86 1500 210 866 866 367 – 62 65 48/ 3
3CJ2 842...
10
95 110 38 42 630 25 63 63 630 50 150 86 1500 210 866 866 – 54 – 65 28/ 4
3CJ2 861...
10

24 kV Up Up Ud Ud Ir Ik Ip Ima I2a I4a I6a I6b n e


50/60 Hz kV kV kV kV A kA kA kA A A A A mm mm mm mm Nm Nm Nm kg

3CJ2 542... 125 145 50 60 400 25 1) 63 63 1) 400 50 285 86 1500 250 866 966 442 – 64 70 53/ 5
10.5
3CJ2 561... 125 145 50 60 630 25 63 63 630 50 285 86 1500 250 866 966 – 64 – 70 29/ 6
10.5
3CJ2 568... 125 145 50 60 630 25 63 63 630 50 285 86 1500 250 866 966 – – 64 70 29/ 6
10.5
3CJ2 571... 125 145 50 60 1000 32 80 63 1000 50 285 86 1500 250 866 966 – 64 – 70 29/ 6
10.5
125 145 50 60 400 25 1) 63 63 1) 400 50 285 86 1500 275 966 1066 442 – 64 70 57/ 5
3CJ2 642...
11.5
3CJ2 661... 125 145 50 60 630 25 63 63 630 50 285 86 1500 275 966 1066 – 64 – 70 32/ 6
11.5
1) Ima and Ik are defined by the fuse used

20 Siemens HG 12.21 · 2008


292 77 124,5
15

3CJ2 271...
3CJ2 262...
3CJ2 261...
3CJ2 171...
3CJ2 162...
3CJ2 161...
Order No.

50/60 Hz
36 kV

467
90
80°

°
419
90
°

261
Rated lightning impulse

100
Up

kV

170
170
170
170
170
170
withstand voltage to earth

61
513 252
Rated lightning impulse
3CJ2 Switch-Disconnectors

Up

kV

195
195
195
195
195
195
withstand voltage across the isolating distance

Dimension drawing 1
638

1) Ima and Ik are defined by the fuse used


315 280 Rated short-duration power-frequency

Ud

kV

70
70
70
70
70
70
25 withstand voltage to earth
114

Dimension drawings for 12 kV


Rated short-duration power-frequency

Ud

kV

80
80
80
80
80
80
withstand voltage across the isolating distance

C
Ir

A
Rated normal current

B
A
D
C
38
34
Ik
Rated short-time withstand current (1 s)

kA

1000 20
630 20
1000 20
630 20
Ip
Rated peak withstand current

kA

50
630 20 1) 50
50
50
630 20 1) 50
50

15
HG12-2126 eps 20
Æ 30

Æ 14
31 Rated short-circuit making current

kA

25
25
25
25
Ima
698

A
I2a Rated closed-loop breaking current

630
25 1) 630
630
630
25 1) 630
630
77 124,5 A Rated cable-charging breaking current
I4a

25
25
25
25
25
25
15
A

1/2
1/2
Rated earth-fault breaking current
I6a

70
70
70
70
70
70

Dimension
drawing no.
Rated cable-charging breaking current
A
I6b

40
40
40
40
40
40

under earth-fault conditions

90

467
90°
419

°
261

Type
n

Number of mechanical operating cycles

100

3CJ2 4...
3CJ2 3...
61
200 252
Pole-center distance

566
866
Dimension drawing 2
330 Shaft length (standard)
280

da Hr. Schleicher z.Zt. Urlaub hat!


114 25
Shaft length (with built-on motor)

B
1000 400 1500 1500
1000 400 1500 1500
1000 370 1500 1500
1000 370 1500 1500

485
625
e




Dimension of fuse assembly


1000 400 1500 1500 537
1000 370 1500 1500 537
mm mm mm mm

C

B
90
90
90
90

C
A
D
Torque of spring-operated mechanism
Nm

165
210
C
38
34



Torque of stored-energy mechanism


Nm

15

D
HG12-2127 eps 20 Torque of make-proof earthing switch

460
600
Nm

120
150 120
120
120
150 120
120

Æ 14
Æ 30
31
13
13
13
13
13
13

59/
98/
59/
59/
98/
59/
kg

342 Weight of switch-discon./built-on earth. switch

Siemens HG 12.21 · 2008


Korr. Maßzeichnungen konnten noch nicht eingebaut werden,
7
8
7
7
8
7

Catalog dim. drawing no. (see pages 21 to 23)

21
Technical Data
Electrical data, dimensions and weights / Dimension drawings

3
Technical Data 3CJ2 Switch-Disconnectors
Dimension drawings

Korr. Maßzeichnungen konnten noch nicht eingebaut werden,


da Hr. Schleicher z.Zt. Urlaub hat!

Dimension drawings for 17.5 kV to 36 kV


490 210 210 490 210 210
306 306 38
61 38 61 34 15
34 15
° °
90 90
Æ 14 Æ 14

47

47
40
40

77 155

284
77 155

15
15

284

100

20
20

280
360

374
280

98
98

Æ 30

Æ 30
200
673

730
513

315

100
292

90
°
600

HG12-2129 eps
540 625
Dimension drawing 4 A
90
°

HG12-2128 eps

600
540 625
A Dimension Type A B C D
Dimension drawing 3
drawing no.
3/4 3CJ2 7... 766 – – –
561 C C
3/4 3CJ2 8... 866 – – –
356 38
76 34
5/6 3CJ2 5... 866 635 250 630
15
° 5/6 3CJ2 6... 966 775 275 730
90

Æ 14
561 C C
46
35

356 38
76
109 169,5

34 15
40

336

20

100 °
90
350

3
115

Æ 14
Æ 30
900

46
948

35
474
80°

109 169,5

327
706

40
490

20
442

100
350
420

443
115

Æ 30
207
90

90
°

°
HG12-2130 eps

D
HG12-2131 eps

D
672 B 672 B
A A
Dimension drawing 5 Dimension drawing 6

732
77 370/4001) 370/4001)

50
°
90

30 15
Æ 14
67,5
52,5
215

20
412
42

105
Æ 30
585
555
450
195

155,5
273
90
°

Dimension drawing 7
HG12-2132 eps

1000
474 1027 1) 370 mm for switch 3CJ2 1...
905 1500 400 mm for switch 3CJ2 2...

22 Siemens HG 12.21 · 2008


3CJ2 Switch-Disconnectors Technical Data
Dimension drawings / Circuit diagrams

Korr. Maßzeichnungen konnten noch nicht eingebaut werden,


da Hr. Schleicher z.Zt. Urlaub hat!

Dimension drawing for 36 kV


732
80 370/4001) 370/4001)

50
°
90

30 15
Æ 14

67,5
52,5
215

412

20
42

105

Æ 30
450
195

155,5

1185
1155
616
°
90

635
537

1000

HG12-2133 eps
Dimension drawing 8
474 1027
1) 370 mm for switch 3CJ2 1...
905 1500
400 mm for switch 3CJ2 2...

Circuit diagrams
F2 Control voltage Auxiliary switch (for data refer to next page)
S1
5 F3 Motor voltage 1 3 5 7 9
S1 K1A S1A K1E S1E
6 ”OPEN” ”CLOSED”
K1A K1E
HG12-2137 eps

33

S22 S4
2 4 6

X1
8 10
3
2 NO + 2 NC
M1 M
33 37
S2 S3 34 S1
36 38 1 3 5 7 9 11 13

K1A K1E
HG12-2138 eps
HG12-2136_en eps

31 2 4 6 8 10 12 14
K1E K1A
X1
32
F3
K1A K1E 3 NO + 3 NC
F2
S1
X2 1 3 5 7 9 11 13 15 17 19 21
S1 F1 31 32 33 34 35 36 37 38
1
P
HG12-2140a eps

S4 S2 S3
HG12-2139 eps
HG12-2141 eps

M
2 4 6 8 10 12 14 16 18 20 22
2 4 M1 X1

Shunt release Motor operating mechanism 5 NO + 5 NC

Legend
F1 Shunt release “Open” S1 Auxiliary switch at the switch S1E “CLOSE” pushbutton S22 Interrupter contact
F2, Electro-thermal over- S2, Position switches S1A “OPEN” pushbutton (only for make-proof
F3 current release S3 S12 Auxiliary switch for earthing switch)
K1A Auxiliary contactor “Feedback” S4 Interrupter contact for tripping signal X1 Terminal strip on
K1E Auxiliary contactor “Closed” manual emergency operation the switch
M1 Motor operating mechanism X2 Terminal strip on
the motor
The circuit diagrams shown here are examples from the manifold possibilities of switch wiring

Siemens HG 12.21 · 2008 23


Technical Data 3CJ2 Switch-Disconnectors
Data of auxiliary switch / Data of motor operating mechanism

Korr. Maßzeichnungen konnten noch nicht eingebaut werden,


da Hr. Schleicher z.Zt. Urlaub hat!

Data of auxiliary switch

Rated operating Switching Short-circuit Time coefficient


voltage capacity capability T = L/R

V A kA ms
24 DC 8 1 ≤ 30
60 DC 3 1 ≤ 30
110 DC 2 1 ≤ 30
125 DC 1.7 1 ≤ 30
220 DC 1 1 ≤ 30
110 AC 10 1 –
220 AC 10 1 –

Data of motor operating mechanism


24 kV = 20
17,5 kV + 12 kV = 52
805
580
525
HG12-2134 eps

24 kV = 176
20

17,5 kV + 12 kV = 141

Rated operating Maximum current Maximum power


voltage consumption consumption

V A W/VA
24 DC 32 780
60 DC 13 780
110 DC 7 780
125 DC 5 780
220 DC 3.5 780
110 AC 7 780
220 AC 3.5 780

24 Siemens HG 12.21 · 2008


3CJ2 Switch-Disconnectors Annex
Contents

Contents Page

Annex 25

Inquiry form 26

Configuration instructions 27
Configuration aid Foldout page

R-HG11-181.tif

Brandenburg Gate, Berlin, Germany

4
R-HG11-180.eps

Switchgear Factory in Berlin, Germany

Siemens HG 12.21 · 2008 25


Annex 3CJ2 Switch-Disconnectors
Inquiry form

Please copy, fill in and return to


your Siemens partner.

Inquiry concerning
Technical data Other values

o 3CJ2 switch-disconnector Rated voltage o 12 kV o 17.5 kV


o 24 kV o 36 kV o _ _ _ kV

Rated lightning impulse o 75 kV o 95 kV


withstand voltage o 125 kV o 170 kV o _ _ _ kV

Rated short-duration power- o 28 kV o 38 kV


Please frequency withstand voltage o 50 kV o 70 kV o _ _ _ kV

Rated normal current o 400 A o 630 A o 1000 A o ___A


o Submit an offer
o Call us Type of operating mechanism o Spring-operated mechanism o Stored-energy mechanism

o Visit us Fuse assembly o Without o With

Pole-center distance o 165 mm o 210 mm o 250 mm


o 275 mm o 370 mm o 400 mm o _ _ _ mm

Your address Shaft length o 566 mm o 766 mm


o 866 mm o 966 mm o 1500 mm o _ _ _ mm

Company

Secondary equipment
Dept.
For possible combinations see pages 14 and 15
Name Actuation of operating shaft o Manual operation
o Motor operation
Street
Motor operating mechanism o _ _ _ V DC o _ _ _ V AC, _ _ _ Hz

Postal code/city Shunt release o _ _ _ V DC o _ _ _ V AC, _ _ _ Hz

Auxiliary switch o 2 NO + 2 NC o 3 NO + 3 NC o 5 NO + 5 NC
Phone
Built-on make-proof earthing switch o On opening side
o On pivot point
Fax o On fuse cross-member

E-mail
Application and other requirements

4 Siemens AG

Dept.

Name

Street

Postal code/city

Fax

o Please check off _ _ _ Please fill in

26 Siemens HG 12.21 · 2008


You prefer to configure your switch-disconnector on your own? For configuration of your
Please follow the steps for configuration and enter the order number in the configuration aid. 3CJ2 switch-disconnector

1 2 3 4 5 6 7 – 8 9 10 11 12
3 C J 2 n n n – n n n n n – Z
Instruction for configuration of the 3CJ2 switch-disconnector

See page 13 and 14


1st step: Definition of the primary part (see pages 13 and 14)

See page 14
See page 14
See page 15
See page 15
See page 15

See page 16
Please specify the following ratings: Possible options:

Rated voltage (Ur) Ur: 12 kV to 36 kV


Rated lightning impulse withstand voltage (Up) Up: 75 kV to 170 kV
Rated short-duration power-frequency withstand voltage (Ud) Ud: 28 kV to 70 kV
Rated normal current (Ir) Ir: 400 A to 1000 A 3 C J 2 –
Pole-center distance (PCD) PCD: 165 to 400 mm
Shaft length (SL) of the switch shaft SL: 766 to 1500 mm + + +
Type of operating mechanism Spring-operated or stored-energy mechanism
Version with fuse With or without fuse assembly + + +

These ratings define the positions 5 to 7 of the order number. 3 C J 2 –

+ + +

+ + +

2nd step: Definition of the secondary equipment (see pages 14 and 15) 3 C J 2 –

+ + +
Please specify the following equipment features: Possible options:
+ + +

Type of operating mechanism Manual operating mechanism with operating shaft lever
(position 8) Motor operating mechanism 3 C J 2 –
Operating voltage of the motor operating mechanism Operating voltages from 24 V DC to 220 V AC
(position 9) + + +
Use of releases Operating voltages from 24 V DC to 220 V AC
(position 10) + + +
Use of make-proof earthing switches Built on the opening side, the pivot point or the fuse cross-member
(position 11) 3 C J 2 –
Use of auxiliary switches 2 NO + 2 NC, 3 NO + 3 NC, 5 NO + 5 NC
(position 12)
+ + +

These equipment features define the positions 8 to 12 of the order number.


+ + +

3 C J 2 –

+ + +
3rd step: Do you have any further requirements concerning the equipment? (Please refer to page 16)
Should you still need more options than the possible special equipment like upgrading to category B, + + +
signaling switch for fuse tripping, special lengths of fuse dimensions, etc., please contact
3 C J 2 –
your responsible sales partner.
+ + +

+ + +

3 C J 2 –

+ + +

+ + +

3 C J 2 –

+ + +

+ + +
Siemens HG 12.21 · 2008 27
Published by and copyright © 2008:
Siemens AG
Energy Sector
Freyeslebenstrasse 1
91058 Erlangen, Germany

Siemens AG
Energy Sector
Power Distribution Division
Medium Voltage
Nonnendammallee 104
13623 Berlin, Germany

For more information, please contact our


Customer Support Center.
Phone: +49 180 524 70 00
Fax: +49 180 524 24 71
(Charges depending on provider)
E-mail: support.energy@siemens.com

Order No. E50001-K1512-A211-A1-7600


Printed in Germany
Dispo 31601
KG 08.08 1.5 30 En
6101/14472 103370

Printed on elementary chlorine-free bleached paper.

All rights reserved.


If not stated otherwise on the individual pages of this
catalog, we reserve the right to include modifications,
especially regarding the stated values, dimensions and weights.
Drawings are not binding.
All product designations used are trademarks or product
names of Siemens AG or other suppliers.
If not stated otherwise, all dimensions in this
catalog are given in mm.

Subject to change without prior notice.


The information in this document contains general
descriptions of the technical options available, which
may not apply in all cases. The required technical
options should therefore be specified in the contract.

Responsible for
Technical contents: General editing:
Siemens AG, E D MV C Siemens AG, E CC MCC R
Berlin Erlangen www.siemens.com/energy

You might also like