You are on page 1of 4

Complementary Type 1 coordination

technical information
(IEC 60947-4-1)
DB103921

NS80H-MA and NSX100 circuit breakers, contactors


and thermal relays
Star-delta starting
"Iq" breaking performance: equal to the breaking capacity of the circuit breaker.
Starting: normal.

Motors Circuit breakers Contactors Thermal relays


220/230 V 380 V 415 V 440 V (1)
P I P I P I P I Type Rating Type Type Irth
(kW) (A) (kW) (A) (kW) (A) (kW) (A) (A) (A)
0.55 2.8 1.5 3.7 1.5 3.5 1.5 3.1 NS80H-MA 6.3 LC3-D09 LRD-07 1.6/2.5
1.1 4.4 2.2 5 2.2 4.8 2.2 4.5 NS80H-MA 6.3 LC3-D09 LRD-08 2.5/4
1.5 6.1 3 6.6 3 6.5 3 5.8 NS80H-MA 12.5 LC3-D09 LRD-08 2.5/4
2.2 8.7 4 8.5 4 8.2 4 7.9 NS80H-MA 12.5 LC3-D09 LRD-10 4/6
3 11.5 5.5 11.5 5.5 11 5.5 10.4 NS80H-MA 12.5 LC3-D09 LRD-12 5.5/8
4 14.5 7.5 15.5 7.5 14 7.5 13.7 NS80H-MA 25 LC3-D09 LRD-14 7/10
5.5 20 9 17 9 16.9 NS80H-MA 25 LC3-D12 LRD-16 9/13
11 22 11 21 11 20.1 NS80H-MA 25 LC3-D12 LRD-16 9/13
7.5 28 15 30 15 28 15 26.5 NS80H-MA 50 LC3-D18 LRD-21 12/18
11 39 18.5 37 22 40 22 39 NS80H-MA 50 LC3-D18 LRD-22 17/25
22 44 25 47 NS80H-MA 50 LC3-D32 LRD-32 23/32
15 52 30 51.5 NS80H-MA 80 LC3-D32 LRD-32 23/32
30 55 NS80H-MA 80 LC3-D32 LRD-32 23/32
18.5 64 30 59 37 66 37 64 NS80H-MA 80 LC3-D40 LR2-D33 55 30/40
37 72 NS80H-MA 80 LC3-D40 LR2-D33 57 37/50
22 75 45 80 45 76 NS80H-MA 80 LC3-D50 LR2-D33 57 37/50
0.55 2.8 1.5 3.7 1.5 3.5 1.5 3.1 NSX100B/F/N/H/S/L-MA 6.3 LC3-D09 LRD-07 1.6/2.5
1.1 4.4 2.2 5 2.2 4.8 2.2 4.5 NSX100B/F/N/H/S/L-MA 6.3 LC3-D09 LRD-08 2.5/4
1.5 6.1 3 6.6 3 6.5 3 5.8 NSX100B/F/N/H/S/L-MA 12.5 LC3-D09 LRD-08 2.5/4
2.2 8.7 4 8.5 4 8.2 4 7.9 NSX100B/F/N/H/S/L-MA 12.5 LC3-D09 LRD-10 4/6
3 11.5 5.5 11.5 5.5 11 5.5 10.4 NSX100B/F/N/H/S/L-MA 12.5 LC3-D09 LRD-12 5.5/8
4 14.5 7.5 15.5 7.5 14 7.5 13.7 NSX100B/F/N/H/S/L-MA 25 LC3-D09 LRD-14 7/10
5.5 20 9 17 9 16.9 NSX100B/F/N/H/S/L-MA 25 LC3-D12 LRD-16 9/13
11 22 11 21 11 20.1 NSX100B/F/N/H/S/L-MA 25 LC3-D12 LRD-16 9/13
7.5 28 15 30 15 28 15 26.5 NSX100B/F/N/H/S/L-MA 50 LC3-D18 LRD-21 12/18
11 39 18.5 37 22 40 22 39 NSX100B/F/N/H/S/L-MA 50 LC3-D18 LRD-22 17/25
22 44 25 47 NSX100B/F/N/H/S/L-MA 100 LC3-D32 LRD-32 23/32
15 52 30 51.5 NSX100B/F/N/H/S/L-MA 100 LC3-D32 LRD-32 23/32
30 55 NSX100B/F/N/H/S/L-MA 100 LC3-D32 LRD-32 23/32
18.5 64 30 59 37 66 37 64 NSX100B/F/N/H/S/L-MA 100 LC3-D40 LR2-D33 55 30/40
37 72 NSX100B/F/N/H/S/L-MA 100 LC3-D40 LR2-D33 57 37/50
22 75 45 80 45 76 NSX100B/F/N/H/S/L-MA 100 LC3-D50 LR2-D33 57 37/50
25 85 45 85 NSX100B/F/N/H/S/L-MA 100 LC3-D50 LR2-D33 57 37/50
30 100 55 100 55 96 NSX100B/F/N/H/S/L-MA 100 LC3-D50 LR2-D33 59 48/65
(1) Valid for 480 V NEMA.

167

Livre 1.indb 167 04/11/2009 16:00:34


Complementary Type 1 coordination
technical information
(IEC 60947-4-1)
DB103923

NSX160 to NS1000 circuit breakers, contactors and thermal relays


Star-delta starting
"Iq" breaking performance: equal to the breaking capacity of the circuit breaker alone.
Starting: normal.

Motors Circuit breakers Contactors Thermal relays


220/230 V 380 V 415 V 440 V (1)
P I P I P I P I Type Rating Type Type Irth
(kW) (A) (kW) (A) (kW) (A) (kW) (A) (A) (A)
55 105 NSX160B/F/N/H/S/L-MA 150 LC3-D80 LR2-D33 59 48/65
37 125 75 140 75 135 75 124 NSX160B/F/N/H/S/L-MA 150 LC3-D80 LR2-D33 63 63/80
45 150 75 140 NSX160B/F/N/H/S/L-MA 150 LC3-D115 LR9-D53 67 60/100
LC3-F115 LR9-F53 67
90 170 90 160 90 156 NSX250B/F/N/H/S/L-MA 220 LC3-D115 LR9-D53 67 60/100
LC3-F115 LR9-F53 67
55 180 110 180 NSX250B/F/N/H/S/L-MA 220 LC3-D115 LR9-D53 69 90/150
LC3-F115 LR9-F53 67
110 210 110 200 NSX250B/F/N/H/S/L-MA 220 LC3-D115 LR9-D53 69 90/150
LC3-F115 LR9-F53 69
132 215 NSX250B/F/N/H/S/L-MA 220 LC3-D150 LR9-D53 69 90/150
LC3-F150 LR9-F53 69
75 250 132 250 132 230 NSX400F/N/H/S/L Micrologic 1.3M 320 LC3-D150 LR9-D53 69 90/150
LC3-F150 LR9-F53 69
90 312 160 300 160 270 160 256 NSX400F/N/H/S/L Micrologic 1.3M 320 LC3-F185 LR9-F53 71 132/220
110 360 200 380 220 380 220 360 NSX630F/N/H/S/L Micrologic 1.3M 500 LC3-F265 LR9-F73 75 200/330
220 420 250 401 NSX630F/N/H/S/L Micrologic 1.3M 500 LC3-F265 LR9-F73 75 200/330
150 480 250 480 250 430 NSX630F/N/H/S/L Micrologic 1.3M 500 LC3-F330 LR9-F73 75 200/330
300 480 NSX630F/N/H/S/L Micrologic 1.3M 500 LC3-F330 LR9-F73 75 200/330
160 520 300 570 300 510 335 540 NS800N/H-NS1000L 800 LC3-F400 LR9-F73 75 200/330
Micrologic 5.0 - LR off 1000
335 580 375 590 NS800N/H-NS1000L 800 LC3-F400 LR9-F73 79 300/500
Micrologic 5.0 - LR off 1000
(1) Valid for 480 V NEMA.
Note: where more than one association is possible for a rated power, if the motor starting current is high or unknown, the highest association shoud be applied.

168

Livre 1.indb 168 04/11/2009 16:00:35


Complementary Type 1 coordination
technical information
(IEC 60947-4-1)
DB114968

NSX100 to NS1000 circuit breakers contactors


Star-delta starting
"Iq" breaking performance: equal to the breaking capacity of the circuit breaker alone.
Starting: normal.

Motors Circuit breakers Contactors


220/230 V 380 V 415 V 440 V (1)
P I P I P I P I Type Trip unit Irth Type
(kW) (A) (kW) (A) (kW) (A) (kW) (A) (A)
7.5 28 15 30 15 28 15 26.5 NSX100B/F/N/H/S/L Micrologic 2.2M or 6.2E-M 25/50 LC3-D18
11 39 18.5 37 22 40 22 39 NSX100B/F/N/H/S/L Micrologic 2.2M or 6.2E-M 25/50 LC3-D18
22 44 25 47 NSX100B/F/N/H/S/L Micrologic 2.2M or 6.2E-M 25/50 LC3-D32
15 52 30 51.5 NSX100B/F/N/H/S/L Micrologic 2.2M or 6.2E-M 50/100 LC3-D32
30 55 NSX100B/F/N/H/S/L Micrologic 2.2M or 6.2E-M 50/100 LC3-D32
18.5 64 30 59 37 66 37 64 NSX100B/F/N/H/S/L Micrologic 2.2M or 6.2E-M 50/100 LC3-D40
37 72 NSX100B/F/N/H/S/L Micrologic 2.2M or 6.2E-M 50/100 LC3-D40
22 75 45 80 45 76 NSX100B/F/N/H/S/L Micrologic 2.2M or 6.2E-M 50/100 LC3-D50
25 85 45 85 NSX100B/F/N/H/S/L Micrologic 2.2M or 6.2E-M 50/100 LC3-D50
30 100 55 100 55 96 NSX100B/F/N/H/S/L Micrologic 2.2M or 6.2E-M 50/100 LC3-D50
55 105 NSX160B/F/N/H/S/L Micrologic 2.2M or 6.2E-M 70/150 LC3-D80
37 125 75 140 75 135 75 124 NSX160B/F/N/H/S/L Micrologic 2.2M or 6.2E-M 70/150 LC3-D80
45 150 75 140 NSX160B/F/N/H/S/L Micrologic 2.2M or 6.2E-M 70/150 LC3-D115 or LC3-F115
90 170 90 160 90 156 NSX250B/F/N/H/S/L Micrologic 2.2M or 6.2E-M 100/220 LC3-D115 or LC3-F115
55 180 110 210 110 200 110 180 NSX250B/F/N/H/S/L Micrologic 2.2M or 6.2E-M 100/220 LC3-D115 or LC3-F115
132 215 NSX250B/F/N/H/S/L Micrologic 2.2M or 6.2E-M 100/220 LC3-D150 or LC3-F150
75 250 132 250 132 230 NSX400F/N/H/S/L Micrologic 2.3M or 6.3E-M 160/320 LC3-D150 or LC3-F150
90 312 160 300 160 270 160 256 NSX400F/N/H/S/L Micrologic 2.3M or 6.3E-M 160/320 LC3F-185
110 360 200 380 220 380 220 360 NSX630F/N/H/S/L Micrologic 2.3M or 6.3E-M 250/500 LC3-F265
220 420 250 401 NSX630F/N/H/S/L Micrologic 2.3M or 6.3E-M 250/500 LC3-F265
150 480 250 480 250 430 NSX630F/N/H/S/L Micrologic 2.3M or 6.3E-M 250/500 LC3-F330
300 480 NSX630F/N/H/S/L Micrologic 2.3M or 6.3E-M 250/500 LC3-F330
160 520 300 570 300 510 335 540 NS800N/H Micrologic 5.0 320/800 LC3-F400
NS1000L 400/1000
335 580 375 590 NS800N/H Micrologic 5.0 320/800 LC3-F400
NS1000L 400/1000
(1) Valid for 480 V NEMA.
Note: where more than one association is possible for a rated power, if the motor starting current is high or unknown, the highest association shoud be applied.

169

Livre 1.indb 169 04/11/2009 16:00:37


Low Voltage

Complementary
technical
information
Guide
2010

558E0000.indd 1 04/11/2009 17:02:04