MAC/YVC Series Specifications: MAC 75-150/YVC75-150 (50Hz)

Air-cooled ducted split Air Conditioners Models


Indoor
Unit
Outdoor
75 100
MAC

YVC
125 150

Unit 75 100 125 150


Btu/h 75,000 100,000 125,000 150,000
Nominal Capacities Cooling kW 21.98 29.30 36.63 43.95
kcal/h 18,901 25,202 31,502 37,802
V/Ph/Hz 380-415/3/50
Power Supply
Ph 3 3 3 3
Power Consumption kW 8.89 11.80 12.64 16.78
Running Current A 24.23 29.50 27.70 30.87
Type R22
Refrigerant
Precharge kg 0.5
V/Ph/Hz 220-240/1/50 380-415/3/50
Power Supply
Ph 1 1 3 3
Fan Type Forward Curve Centrifugal Direct Drive Forward Curve Centrifugal Belt Drive
Air flow m3/h 4,200 5,600 7,000 8,420
Blower Diameter-qty Inch-Ea 9x7-2 10x8-2 15x15-1 15x15-1
Motor quantity Ea 1 2 1 1
Speed (H/M/L) rpm 1350/1150/980 1250/1150/1050 1390 1380

Fan
Input Power W 1300 982x2 1442 1908
Output Power W 850.0 550x2 1,100 1,500
Running Current A 6.33 4.4x2 2.8 3.7
MAC 75-100 Motor Pulley Type - - 85*SPZ1 85*SPZ1
Blower Pulley Type - - 160*SPZ1 160*SPZ1
MAC 75-100

Tube
Material Copper Tube

Indoor Unit
Diameter mm 9.5
Material Aluminum

Coil
O Standard horizontal air discharge

Fin
Row 4 4 3 4
Fin per inch 14 14 14 14
O Adjustable 3 fan speed (direct drive) Face Area ft2 4.74 6.14 10.23 10.23
Material Electro Galvanized Steel
O Designed ESP 100 Pa Casing Finishing Epoxy Polyester Powder Paint
Insulation PE
O Build in filter rack MAC 125-150 Height mm 482 550 871 871
Dimension Width mm 1,550 1,550 1,550 1,550
MAC 125-150 Depth mm 762 762 982 982
Gross Weight kg 126 134 198 206
O Standard horizontal air discharge Air Filter Not Available
Liquid inch 5/8” 5/8” 5/8” 5/8”
O Belt driven

Piping
Pipe Size Suction inch 1-1/8” 1-3/8” 1-3/8” 1-5/8”
Drain inch 1 1 1 1
O Designed ESP 150 Pa Connection Type Brazed
V/Ph/Hz 380-415/3/50
Power Supply
O Build in filter rack Ph 3 3 3 3
Qty 1 1 1 1
O Convertible to vertical discharge at site Compressor Type Scroll
YVC

Compressor
Capacitor µF - - - -
Max. Starting Current A 95 125 125 175
Nominal Current A 16.4 19.2 22.1 24.17
Input Power W 6880 9130 10200 13620
O High efficiency scroll compressor Vibration Isolator Rubber
Protection Device Internal Over Load Protector + Phase Protector
O High and low pressure protection Qty 1 1 1 1
Fan Type / Drive Propeller / Direct Drive
YVC 75-150
O Phase reversal protection Fan Speed rpm 930 930 920 920
Blade Material Aluminium

Fan
O Vertical air discharge Diameter inch 24” 24” 26” 28”

Outdoor Unit
Rated Running Current A 1.50 1.50 2.80 3.00
Rated Output W 450 450 750 950
Rated Input W 710 710 1000 1250

Tube
Material Copper Tube
Diameter mm 9.5
Material Aluminium

Coil

Fin
REMOTE CONTROL Row
Fin per inch
2
13
2
14
2
14
2
14
Surface Area ft2 18.95 18.95 18.95 27
Material Electro Galvanized Steel
Casing
O Small wired controller Finishing Epoxy Polyester Powder Paint
Height mm 944 944 944 1,098
O Cooling operation mode Dimension Width mm 900 900 900 1,065
Depth mm 972 972 972 1,107
(auto/cool/dry/fan) Weight (included packing) kg 145 158 166 220
No. of circuit 1 1 1 1
O Sleep mode and independent On-Off timer Liquid inch 5/8 5/8 5/8 5/8

Piping
Pipe Size
Suction inch 1-1/8 1-3/8 1-3/8 1-5/8
O LCD display clock Connection Type Brazed

O Self diagnostic function Rating Conditions


o
Cooling
o o
Heating
o
Remarks: The above design and specifications are subject to change without prior notice for product improvement.
Indoor Temperature 27 C DB/19 C WB 20 C DB/15 C WB
O Room temperature setting Outdoor Temperature 35 C DB/24 C WB
o o o o
7 C DB/6 C WB

www.york-minisplit.com

ACCREDITED

BE-YV0101-00

You might also like