Professional Documents
Culture Documents
June 2001
INSULATION CO-ORDINATION FOR HV AC
UNDERGROUND CABLE SYSTEMS
One approach is to address the inherent costs associated with the cable system, such as the cost and
design of the cable and accessories and to review the possibility of reducing the required withstand
capability of the cable system in line with “actual service requirements” in order to achieve the cable system
design which is predicated by the transient overvoltage performance.
It was decided therefore that a joint working group be established between study committees 21 (High
Voltage Cables) and 33 (Insulation Coordination) to evaluate the influence of transient overvoltages on ac
cable insulation design.
Two main types of cable system were included in this study, laminar fluid impregnated cables and extruded
insulation cables. The fluid impregnated laminar cables are designed to meet predominantly the lightning
impulse overvoltage requirements which more than covers the ac service design requirements, whilst for
extruded cables the ac service voltage stress level must also be taken into account.
As a consequence, cables in the IEC test specifications reflect this approach, with current lightning impulse
voltages being specified together with an ac high voltage test at power frequency. It should be noted that
the cable internal insulation is assumed to satisfy the required switching impulse insulation level, the cable
insulation is far less dependent on the front time and shape of the impinging overvoltage as compared to
gaseous insulation.
Underground cables are used within ac distribution and transmission systems in many ways. There are
several ways of limiting the magnitude of the overvoltages, the overall network configuration and
characteristics influencing the choice of methodology.
In reality cable systems are likely to be subjected to lower externally generated impulse overvoltages than
overhead lines due to their lower surge impedance. On the other hand, the possibility of insulation failure is
of much more concern as the insulation is not self-restoring. The risk associated with the consequence of a
failure must be balanced against the potential benefits in terms of cost saving.
For a cable system the internally generated overvoltages are also generally lower than for overhead lines. In
particular, for solidly bonded cable systems where reclosure is not applied , internal overvoltages are
generally limited to below 2 times the crest value of the phase to ground voltage.
In some cases the internal and externally generated transient overvoltage can be limited by overvoltage
protection such as Zinc Oxide surge arresters connected at either one or both ends of the cable.
It is possible to carry out insulation coordination studies by taking into account appropriate safety factors and
assuming a specified acceptable failure rate. However, further studies to confirm these safety factors are
required, particularly for the newer extruded insulated cable system technology where there is less
experience and less knowledge of some of the parameters such as ageing that need to be taken into
account. By evaluating the results of these studies the overvoltage withstand requirement can be
established and taken into account in determining the design of the primary insulation of the cable system.
Regarding the withstand capability of cable systems, suitable safety factors for design purposes and
“acceptable” performance failure rates, it is at present not possible to recommend specific changes. It would
appear however that a reduction in performance should be possible in many cases. Each circuit must be
studied on a case-by-case basis.
Some typical network configurations have been studied using numerical simulation techniques in order to
verify these conclusions. Further work is required and guidelines need to be established to facilitate
calculations and ensure consistency.
FIGURES
Figure 1 : Meshed underground network ........................................................................................................ 10
Figure 2 : Siphon, an underground cable between 2 overhead lines.............................................................. 11
Figure 3 : Underground substation entrance................................................................................................... 11
Figure 4 : Power generator output................................................................................................................... 11
Figure 5 : Auxiliary transformer supply............................................................................................................ 12
Figure 6 : Partial Weibull distributions of breakdown time (constant stress) and breakdown stress (constant
time) for an extruded cable insulation ............................................................................................. 15
Figure 7 : Lifetime curve for extruded cable insulation.................................................................................... 16
Figure 8 : Qualitative lifetime curves for cables under electric stress ............................................................. 17
Figure 9 : Distribution of representative overvoltages..................................................................................... 32
Figure 10 : Effect of surge impedance discontinuity on travelling wave ......................................................... 33
Figure 11 : Voltage buildup on cable end due to multiple reflections inside cable ......................................... 35
Figure 12 : Switching discharged cable to a live bus ...................................................................................... 36
Figure 13 : AC voltage U=145/ 3 kV............................................................................................................. 46
Figure 14 : AC voltage U=145/ 3 kV............................................................................................................. 47
Figure 15 : AC voltage U=145/ 3 kV............................................................................................................. 48
Figure 16 : AC voltage U=145/ 3 kV, E(ri)=7 kV/mm, E(re)=4 kV/mm.......................................................... 49
Figure 17 : Lightning Impulse voltage U=650 kV, E(ri)=70 kV/mm. ................................................................ 50
Figure 18 : Lightning Impulse voltage U=650 kV, Em=20 kV/mm.................................................................... 50
Figure 19 : Lightning Impulse voltage U=650 kV, b=8, ri0=20 mm, t0=20 mm. ............................................... 52
Figure 20 : Lightning Impulse voltage U=650 kV, b=40, ri0=20 mm, t0=20 mm. ............................................. 52
Background:
In recent years many underground cable circuits have been installed within the distribution and transmission
system in various parts of the world, in different arrangements than were considered in the past. Cable
circuits have been installed between metal clad switchgear with no direct connection to overhead line or
transformer. The cable system comprising cable and accessories have traditionally been designed to meet
a performance as defined by the customer following a national or international specification which in turn
generally refers to transient overvoltage levels as defined in IEC publications.
The question has been asked whether these requirements are realistic or unduly onerous in the network
configurations currently being utilised. It has also been suggested that the performance requirements might
change from circuit to circuit. Improved protection devices and network design philosophy might also
provide some scope for changing the requirements of the underground cable system which could lead to a
more economic underground system.
A similar exercise has been carried out by CIGRE Study Committee 21 in conjunction with Study
Committees 33 and 14 in the context of submarine cables and reported in CIGRE Publication No 86,
published in August 1994.
Terms of Reference:
The terms of reference agreed by Study Committees 21 and 33 were as follows:
• Identification of transmission system configurations containing high voltage cables taking into account
cables operating in cable systems connected to overhead lines via transformers as well as connected
to overhead lines directly or between overhead lines, including the various relay protection
philosophies.
• Description of all types of overvoltages which can occur in the various systems and determination of
the parameters describing the prospective amplitudes and shapes of the overvoltages emphasising
differences to overhead line systems.
• Examination of means for overvoltage amplitude limitation including recommendations for the most
suitable location of arresters and evaluation of the advantages that might be realised.
• For each cable type, classification of factors which may reduce the dielectric strength of cables, joints
and terminations in service with respect to their withstand proven in type test, e.g. ageing, variation in
production, etc., and recommendation of suitable safety factor to be applied in insulation co-ordination.
• Analysis of the existing design and testing procedures in the context of their adequacy and the
insulation co-ordination requirements, including on-site testing requirements.
• Collection of service experience with special reference to failure rates and power availability as
compared to overhead line systems and recommendation of an acceptable failure rate.
In addition it was agreed that cable systems rated at U110kV (Um 123kV) and above, would be considered.
Only the primary cable insulation would be included and not the cable metallic sheath insulation system.
Compressed gas insulated transmission lines were not included.
The overvoltages that can occur in a given cable are strongly dependent on the configuration in which the
cable is located, as well as the characteristics of the network components.
2.1 Configurations
Various configurations such as single circuit, double circuit and triple circuit lines with different arrangements
of transformer and generator connections are in use.
Many types of connections comprising overhead lines, underground cables or both are possible and can be
found. The length of such transmission lines and cables can vary significantly.
For load reasons, one circuit can consist of several cable systems.
In order to have the possibility of performing calculations, some typical configurations have been selected.
These configurations, given below, are representative of the various practical situations. Further details
regarding national practices are included in Table 12 for information purposes.
Note that in the subsequent figures each cable can consist of several cable systems.
2.1.1 Meshed underground network
Some parts of a HV network may be entirely underground as can be often seen in large towns where
urbanisation prevents the construction of overhead lines. Cables connect the busbars in the system, as
indicated in Figure 1.
Substation 2 Substation 1
Underground
cables
Substation 3
2.1.2 Siphon
A siphon is an underground cable connected between two overhead lines. It is assumed that no switching
device is located between line and cable. This configuration allows a HV link to pass through areas too wide
for an overhead line span such as rivers or small lakes. The configuration may also permit the transmission
line to pass through or near a protected site or an urbanised area.
Underground cable
An underground cable is often used as the interface between an overhead line and a substation, especially
when it is a gas insulated station. This configuration allows the design of more compact stations, in
particularly when there is a large number of incoming overhead lines.
Substation
Overhead line
Underground
cable
An underground cable may be used to carry power from an inaccessible generator to a busbar. In this case,
there is not room enough to put a breaker between the generator and the cable. In many hydro power
stations the generator is located inside a mountain. In order to save space the generator is connected
directly to the step-up transformer, without usage of a circuit breaker. The secondary side of the transformer
is connected to an outdoor substation via cable which may have a length up to several kilometres. The
substation (air insulated or gas insulated) is connected to one or more overhead lines.
Overhead
line
Underground cable
Generator
Busbar
In this configuration, a cable is connected between a high power busbar and the auxiliary transformer of a
power unit. The cable is usually short.
Underground
Auxiliary cable
transformer
A discussion about the possible impact of OHL configurations on cable is given in chapter ?5.
2.2.3 Cable type
Generally it can be stated that within the voltage range 123-245 kV, many kilometres of low pressure
oil-filled, high pressure oil-filled (pipe type) and gas-pressure pipe type cables have been in use for several
decades (40 years). Extruded cables have been used since the early 1970s.
At Um = 420 and 525 kV, the cable type generally installed is low pressure oil-filled cable. Extruded cables
for this voltage range are currently being installed and put into service.
The different cables have different properties regarding the impulse withstand voltage characteristics. Also,
the ageing characteristics are different.
2.2.4 Type of switchgear
Generally SF6-insulated Gas Insulated Substations and Air Insulated Substations with SF6-circuit breakers
are used. AIS with minimum-oil and air-blast circuit breaker also remain in use.
2.2.5 Overvoltage protection
The subject will be treated more in detail in Chapter ?5. In summary, the main types of arresters are air-gap
type, SiC type with series gap and the newest type, ZnO arrester without gap. The latter has been used
since the early 1980's.
In some countries, for networks with Um ≤ 170 kV, the Petersen coil earthing method is still used. There is a
tendency to change more and more to direct or impedance earthing.
Usage of Petersen coil earthing will normally produce higher temporary overvoltages than direct earthing.
For a given system voltage this may result in usage of surge arresters with a higher rated voltage, thus
leading to a poorer protection against overvoltages.
2.2.7 Sheath bonding system
For cable systems Um = 123 kV and above, various sheath bonding systems are used.
In many cases sheath are solidly grounded at both ends. In the case of specially bonded systems (single
point bonded or cross-bonded), SVL (Sheath Voltage Limiters) are used to protect the cable sheath at
positions which are not directly grounded (Ref. [2.1]).
2.3 References
[2.1] WG21-07, "Guide to the protection of specially bonded cable systems against sheath overvoltages"
Electra N°128 January 1990
Insulated cables for 110 kV (Um = 123 kV) and higher system voltages have been used since the 1920’s with
oil-impregnated paper as insulation. By the introduction of oil at a positive pressure as impregnant for the
paper-insulation of the cable, void formation in the insulation (between paper layers, in butt spaces etc.) was
eliminated. The impregnant was maintained inside the cable with a metal sheath.
The improvements of design, materials, manufacturing techniques etc. made an increase of the rated
voltage for the oil-filled paper-insulated cables possible. In the 1950’s the first oil-filled paper insulated cables
were installed in a 380 kV network.
During the 1950’s the technology of extruded insulation was introduced for medium voltage cables. The first
high voltage cables with extruded insulation on 110kV systems were installed in the 1960's. The
improvements of design, materials, manufacturing techniques etc. resulted in cables with extruded insulation
for even higher voltages. Today cables with extruded insulation are used at installations at system voltages
up to 500 kV.
During the 1950’s extruded insulation was introduced for medium voltage cables. The cables with extruded
insulation were found to have good impulse voltage strength. With the introduction of medium and high
voltage cables with extruded insulation, the expected lifetime of these new technology cables was
questioned. Very early focus was concentrated on methods for determining the expected lifetime of cables
with extruded insulation.
A number of accelerating ageing tests were started at the manufacturers plants and at test institutions
around the world for establishing the ageing parameters. Different statistical methods were used for finding a
model to evaluate the estimated lifetime from the test results. The Weibull distribution became the world-
wide used method to estimate the expected lifetime for a full-scale cable based on the results of ageing tests
on model cables. Theoretical methods for correction of length, insulation volume (diameter, thickness),
temperatures, threshold stresses etc. were introduced. [3.1]
The results from the ageing tests combined with the experience from medium voltage cables in service were
used for designing cables at higher rated voltages. In the beginning of 1970’s 132 kV cables with extruded
Reference is also made to the papers "Working gradients of HV and EHV cables with extruded insulation
and its effect" [3.2] and "Criteria for electrical stress design of HV cables" [3.3].
3.2 Ageing of cable insulation
The electrical performance of cable insulation generally decreases with time due to degradation processes
of the insulating materials. The mechanisms of the ageing process are different depending on the physical
properties of the materials used for the insulation.
The ageing of cables with lapped impregnated insulation is mainly influenced by the operating temperature.
Gas production in the insulation due to thermal degradation is the dominating ageing process for this cable
type. As long as the gas can be dissolved in the impregnating liquid, the electric withstand stress remains
nearly constant. The applied AC stress does not have a significant influence on the ageing, provided that it is
held below the PD inception stress [3.4], [3.5] and [3.6]. Therefore the effect of electric ageing is negligible.
The ageing process of cables with extruded insulation is significantly influenced by the applied electrical
stress. Assuming, that the physical process responsible for the ageing does not change, the time to
breakdown for a given stress as well as the breakdown stress for a certain time are stochastic values which
are represented by homogeneous distribution functions. The results of many tests have shown that both
values may be approximated by Weibull distributions with two parameters (scale parameters at 63 %
probability t0 and E0, Weibull slopes a and b, see Figure 6).
( E = const ) ( t = const )
p
p
( double log scale )
63% 63%
a
b
1 1
t0 t E0 E
( log scale ) ( log scale )
Figure 6 : Partial Weibull distributions of breakdown time (constant stress) and breakdown stress
(constant time) for an extruded cable insulation
(
p( t ) = 1 − exp − (t t 0 )
a
)
For the same cable the breakdown probability as a function of the electrical stress applied for a constant
time can be written as
(
p(E) = 1 − exp − (E E 0 )
b
)
The two distribution functions may be combined, so that the complete equation for the breakdown probability
of a given cable sample is
(
p( t,E) = 1 − exp − (t t 0 ) (E E 0 )
a b
)
For a constant breakdown probability the following relation may be derived from the above:
a b
t E
⋅ = const
t 0 E0
Introducing the lifetime exponent n as the quotient of the Weibull slopes b and a
b
n=
a
the lifetime law for an extruded cable insulation becomes finally (Figure 7)
En ⋅ t = const
log E
design
stress
1
n
safety margin
operating
stress
Published values of the lifetime exponent n for XLPE cover the range from 12 to 20.
According to the lifetime law for extruded cable insulation, high electrical stress applied for short time causes
the same ageing as lower stress applied for a longer duration, provided that all other operating conditions
remain unchanged. The design philosophy for extruded cables must consider this effect. Basic values of the
design stresses are usually derived from short-term tests (design stress / design time in Figure 7).
Considering the ageing effect it has to be ensured that, at the required lifetime, there is a sufficient safety
margin (this term should be defined as I do not like margin in specifications, we do not need margin (our
accountants always think that the margins have to be reduced; in IEC 71-1 a concept of safety factor has
been introduced and can be used also for the long term withstand of the cables, the only remaining thing will
The different ageing behaviour of cables with lapped impregnated insulation and extruded insulation is also
the reason for the different design and testing philosophies according to the relevant standards and
recommendations. Typical differences in lifetime curves for lapped and extruded cable insulation are shown
qualitatively in Figure 8.
lapped insulation
operating stress
log t
The operating experience gained with the high voltage AC land cable system during the five-year period
from 1982 to 1986, have been collected by a questionnaire and prepared by CIGRÉ WG 21.10 [3.7]. The
reported failure rates and average outage times for cables are
When considering the assessment it should be noted that the cable systems differ from each other for
various reasons.
Factors that may have had an influence on the conclusion are:
- The difference in length of circuits in operation.
- The age of the cable systems.
- The average ages of the cable systems surveyed in 1982-1986 are:
- PE-cables ~ 10 year
- Oil-filled cables ~ 20 year
- XLPE-cables ~ 7 year
- The failure mode of the pressure assisted paper-insulated cables is different from that of the extruded
insulation cables. In the case of oil-filled cables failures, in general, are of minor nature, rarely resulting in
an automatic disconnection, while in the case with extruded insulation cable the majority of failures result in
a breakdown of the insulation and subsequently in an automatic disconnection.
3.4.1 Basic insulation design of high voltage AC cables with lapped insulation
The insulation of such cables is formed by a number of thin paper tapes wounded around the conductor. The
shape of the conductor is circular, except for external gas pressure cables, where an oval shaped conductor
is used. Depending on the type of cable the insulation is impregnated with low viscosity oil or with a non-
draining high viscosity insulating mass.
The surface of the conductor is more or less irregular due to the interstices between the single wires. To
avoid electrical stress concentrations at such irregularities several layers of semi-conductive carbon black
paper tapes are applied on the conductor surface. For high voltage cables it is essential to form a pure radial
electric field inside the insulation. Therefore semi-conductive carbon black paper tapes, normally in
combination with metal coated paper tapes are used also over the insulation.
In order to achieve a satisfactory long duration AC withstand characteristic it is necessary to avoid ionisation
inside the insulation. Ionisation can take place in gas filled voids, which could be formed in the insulation by
different rates of expansion and contraction of the cable components during load cycles. Several cable types
have been developed using different mechanisms to overcome the ionisation problem and to form so-called
thermally stable cables.
The paper insulation of low pressure oil filled cables is impregnated with low viscosity insulating oil. During
the heating phase of a load cycle the expanding oil can flow through longitudinal channels inside the
conductor (respectively in the interstices of three-core cables) to oil expansion vessels in which the oil is
stored under pressure. When the load is reduced and the cable is cooling down, the vessel forces the oil
back into the cable. Therefore voids in oil-impregnated cables can never occur.
A metallic sheath covers the impregnated core, which can be an extruded lead sheath with reinforcement or
a corrugated aluminium sheath. Over the metallic sheath an anti-corrosion protection layer (compound) is
applied, followed by an extruded oversheath (PE or PVC).
Low pressure oil filled cables are used up to a rated voltage of 500 kV. Cables for higher rated voltages have
already been developed and successfully tested. The power frequency withstand stress of this type of cables
is about 40 kV/mm and the maximum stress under operating conditions varies between 10 and 15 kV/mm.
The insulation thickness are normally designed on the basis of the maximum permissible lightning impulse
stress in the range of 90 - 95 kV/mm depending on conductor design.
3.4.1.2 Low pressure oil filled cable with polypropylene paper laminate insulation
The use of low pressure oil filled cables with conventional paper insulation at extra high voltages (> 500 kV)
is limited due to the dielectric losses, which are proportional to the square of U0. Therefore an alternative
tape material - polypropylene paper laminate (PPL) - has been developed. The dielectric loss factor of low
pressure oil filled cables with PPL insulation is about 2.5 - 3 times lower compared to conventional paper
insulation.
The design of the complete cable is similar to that of conventional low pressure oil filled cables. Insulation
thicknesses are also determined using the maximum permissible lightning impulse stress, which is in the
range of 100 to 110 kV/mm due to the better material properties of PPL. The maximum power frequency
withstand stress is about 45 kV/mm, the maximum stress under operating conditions is 17 to 20 kV/mm.
High pressure oil filled cables have been constructed for rated voltages up to 500 kV. This type of cables has
not been used in recent installations.
The AC withstand stress is approximately 50 kV/mm and the lightning impulse withstand stress 100 kV/mm.
The paper insulated cores of external gas pressure cables are impregnated with high viscosity synthetic oil.
Directly over the core a gas tight diaphragm lead sheath is applied which is exposed to an external gas
pressure of about 15 bar. During heating periods the lead sheath expands due to the internal pressure of the
expanding impregnating oil. When the cable cools down, the external gas pressure forces the lead sheath
back to its original position. In this way the insulation remains free of voids. To enable this action of the
diaphragm lead sheath the conductors are oval-shaped. External gas pressure cables can either be
designed as self contained cables (earlier installations) or as pipe type cables (more recent installations).
Pipe type cables consist of three cores pulled into a common steel pipe. The steel pipe is filled with
compressed nitrogen.
External gas pressure cables are used up to rated voltages of 275 kV. The typical lightning impulse design
stress is in the range of 85 to 95kV/mm; typical operating stresses vary from 8 to 13 kV/mm.
The insulation of internal gas pressure cables is impregnated with a high viscosity non draining insulating
compound. This cable, in contrast to external gas pressure cable does not have a sheath. Either individual
non-laid-up cores, each protected by a gliding wire, or laid-up multi-core cables with flat steel wire armour
are fed into a steel pipe. The pipe is filled with nitrogen at a pressure of about 15 bar. The gas can penetrate
the insulation and fill any voids, which are formed in the insulation by expansion and contraction during
thermal cycles. Due to the high pressure of the gas inside the voids ionisation is suppressed.
The maximum rated voltage, for which internal gas pressure cables are used, is 110 kV. Typical values for
the lightning impulse design stress vary form 80 to 90 kV/mm. Under operating conditions the maximum AC
stress is usually 8 - 10 kV/mm.
The surface of the conductor is more or less irregular due to the interstices between the single wires. To
avoid electrical stress concentrations at such irregularities an extruded layer of semi-conductive material is
applied on the conductor surface. For high voltage cables it is essential to form a pure radial electric field
inside the insulation. Therefore an extruded semi-conductive material is applied also over the insulation.
In order to achieve a satisfactory long duration AC withstand characteristic it is necessary to avoid ionisation
(partial discharges, PD) which can take place in gas filled voids inside the insulation and at the interfaces
between the insulation and the semi-conductive layers. This is achieved by using properly defined process
parameters and by bonding the three extruded layers.
An extruded lead sheath, an aluminium sheath or a wire screen encloses the insulated core. For some
applications the cable is provided with reinforcement. Over sheath/screen there is an extruded oversheath
(PE or PVC).
Cables with extruded insulation are used up to a rated voltage of 500 kV. The power frequency withstand
stress of this type of cables is about 40 kV/mm, the maximum stress under operating conditions usually
The following tables provide details of the type (design), routine and after installation tests requirements.
As regards the tests conducted on the cable system after installation, current specifications continue to refer
to a dc voltage test being carried out on the primary installation. The internationally held view however, is
that an ac voltage test is to be preferred for extruded cables. Test equipment is now available to enable
such tests to be conducted on cable systems rated up to Um150kV and can be expected to be introduced
also at the higher voltage levels in future years. [Ref. 3.17]
It is also recognised that type approval tests should be carried out on cable samples that included any
accessories that form part of the overall cable system (joints and terminations). At voltage levels above
150kV, a long term ‘pre-qualification test’ [Ref 3.18] is also a pre-requisit, a test carried out on a length of
cable (single phase) of the order of 100m with accessories included in the test loop.
It should also be noted that the switching impulse (250/2500 µ s) test requirement is also being
recommended for inclusion in IEC specifications in the future.
The increase in operating voltage means also an increase of the voltage gradient in the insulation of cables.
Criteria for electrical stress design and suitable values have been discussed for many years.
Appendix A gives some examples commonly used world-wide. The reader will keep in mind that these
examples illustrate general practices but are not recommendations.
Note 1: Test voltage at operating condition temperature as declared for the cable
Note 2: A DC test may be applied as an alternative to the AC test.
Note 1: Test voltage at operating condition temperature as declared for the cable
Note 1: The impulse test voltage shall be minimum 6 U0 + 40 kV or according to IEC 71, when cable is connected directly to an overhead line and is so short, that the
maximum impulse voltage liable to take place is higher than 6 U0 + 40 kV. Test voltage at operating condition temperature as declared for the cable
Note 2: A DC test may be applied as an alternative to the AC test. Routine tests are made at atmospheric pressure.
Note 1: The impulse test voltage shall be minimum 6 U0 + 40 kV or according to IEC 71, when cable is connected directly to an overhead line and is so short, that the
maximum impulse voltage liable to take place is higher than 6 U0 + 40 kV. Test voltage at operating condition temperature as declared for the cable
Note 2: A DC test may be applied as an alternative to the AC test. Routine tests are made at atmospheric pressure.
Note 1: The impulse test voltage shall be minimum 6 U0 + 40 kV or according to IEC 71, when cable is connected directly to an overhead line and is so short, that the
maximum impulse voltage liable to take place is higher than 6 U0 + 40 kV. Test voltage at operating condition temperature as declared for the cable
Note 2: A DC test may be applied as an alternative to the AC test. Routine tests are made at atmospheric pressure.
Note 1: Test voltage at maximum rated temperature (+5 K / +10 K) and according to IEC 71-1 unless otherwise specified
Note 2: Under consideration
[3.1] Users guide for Weibull statistics applied to cables reliability studies
September 1983
[3.2] Working gradients of HV and EHV Cables with extruded insulation and its effect
ELECTRA No 139, December 1991
[3.6] L. G. Brazier
The breakdown of cables by thermal instability
JIEE Vol. 77 1935, 104-115
[3.14] Recommendations for electrical tests type, sample and routine on extruded cables and
accessories at voltages > 150 (170) kV and ≤ 400 (420) kV
ELECTRA No 151, December 1993
[3.17] After Laying Tests on High Voltage Extruded Insulation Cable Systems, ELECTRA No.173
August 1997
[3.18] Recommendations for electrical tests, development and prequalification tests on extruded
cables and accessories at voltages >150(150)kV and ≤ 400 (420) kV
ELECTRA No.151, December 1993
In the following, a short classification and description of the different types of overvoltages is given.
When describing the different types of overvoltage and their origin, particular reference is made to
causes that are external or internal to the EHV system.
Overvoltages are classified in the new edition of Standard IEC 71 by different front wave duration:
Temporary Overvoltage (TOV), Slow-front Overvoltages, Fast-front Overvoltages and Very-fast-
front Overvoltages.
A schematic description of the different types of overvoltages is given in Table 10.
In EHV systems, overvoltages can be generated from different sources, either external or internal to
the system.
These overvoltages are generated by injection of charges into line conductors or by rapid variations
of the electromagnetic field in the proximity of the EHV system.
For EHV systems, causes a) and b) only are generally producing remarkable effects, while
overvoltages produced by cause c) are generally limited within the lightning impulse withstand level
of the system.
Switching Surges. The switching surges are overvoltages generally characterized by a high-
frequency damped oscillatory phenomenon, superimposed to the fundamental power frequency
voltage. These overvoltages are consequent to switching operation on the EHV system (i.e. line
opening or line energization) or fault clearance.
In particular, following to manoeuvres of opening or closing of circuit breakers, steep voltage waves
are generated, that propagate on line conductors and reflect at the points of variation of surge
impedance, like transformers, cables, etc. thus generating a high-frequency component
superimposed to the impressed fundamental power frequency voltage. Typical frequencies are in
the range from 250 to 2500 Hz but very high frequencies (above 1 MHz) can be generated in case
of switching operations or faults in Gas Insulated Systems.
The high-frequency component is rapidly damped due to losses in conductors, earth and corona
losses; typical damping time constant is from few to tens of milliseconds. The maximum value is
normally obtained at the first cycles.
The magnitude of switching surges is in cable systems generally confined within values of 2 times
the system operating voltage (p.u.). Higher values can be obtained in the case of rapidly repeated
operations of closing/opening of the circuit, e.g. reclosing operations for fault clearing, due to the
injection of a new step voltage on a pre-disturbed system. In un-earthed systems not protected by
Petersen coils, a similar phenomenon can be caused by intermittent faults of insulation to ground.
Temporary overvoltages (TOV). These overvoltages have durations from a few cycles to several
seconds. They are in general confined within values of 1.5 p.u. (may exceed 1.73 p.u in Petersen
grounded systems); waveform is a sine wave at fundamental frequency, with an harmonic content
that depends on the presence of saturated ferro-magnetic components like transformers, reactors,
etc.; the significant frequencies in TOV waveshape can be up to hundreds of Hz.
a) load rejection: in case of sudden loss of load, especially with long lines and weak feeding
systems, the loss of load can cause an increase of voltage due to generator over-excitation
caused by the change from inductive to capacitive load (open line), generator overspeed
and Ferranti effect
b) fault application and fault clearing
c) line dropping and line energizing
d) transformer energizing
e) reclosing
TOV that are caused by unconventional system configurations or breaker malfunction are defined
as special cases; in some situations, these overvoltage can reach values up to 2 times the
maximum system voltage for very long time durations or even steady state.
The special cases are mainly referred to the following situations:
a) parallel line resonance, that can be caused by capacitive coupling of an unenergized circuit
including shunt reactors with a parallel energized circuit
b) uneven breaker poles, due to single or double breaker poles stuck during closing or
opening sequences
It has to be noted that TOV can be controlled at the design and implementation stage of the EHV
system through appropriate studies and the insertion of suitable equipment and control instruments;
various mitigation techniques can also be applied for control of TOV after the system is operating.
4.2 Insulation Coordination
4.2.1 General
Traditionally, insulation coordination has been based on the electrical characteristics of air
insulation. The actual withstand voltage of air insulation depends on the shape of the applied
voltage pulse, which has led to usage of standardized voltage waveforms for the testing of high
voltage equipment. Most widely used is the 1.2/50 µs lightning impulse wave, and for rated voltages
300 kV and above also the 250/2500 µs switching impulse wave. For each rated voltage IEC
publication 71 - 1 defines a set of insulation levels for the respective impulse shapes which the
insulation must be able to withstand. These are the lightning impulse withstand level (LIWL) and for
the highest rated voltages also the switching impulse withstand level (SWIWL). In addition, the
component is tested with power frequency AC voltage.
Because the occurring overvoltages and the insulation strength are statistical in nature, a statistical
approach is in general recommended in insulation coordination studies : For the component under
study, a statistical distribution of the overvoltages (peak value) is calculated by means of simulation
software and is compared with the statistical withstand voltage of the component assuming a
particular shape of the impinging overvoltage (lightning impulse or switching impulse). This permits
the calculation of the risk of failure, as outlined in section 3.2.2.2 of IEC 71-2.
4.2.2. Cables
The withstand voltage of cable insulation has a significantly smaller dependency of the voltage
shape than external (air) insulation. As a consequence, cables are in IEC 141-1 not required to be
tested with switching impulse. Some countries, however, also require testing with switching impulse
at the highest rated voltages.
In the case of cables the statistical distribution of the impulse withstand voltage (peak value) is very
expensive to obtain because the insulation is not self restoring. As a practical solution, IEC 71-2
recommends for the withstand voltage statistical distribution usage of a step distribution changing
from 100% to 0% at the LIWL stated by the manufacturer. This means that the insulation is
assumed to fail if the insulation level is exceeded.
Performance
criterion
U w ≥ K c K sU rp [Eq.4.1]
Kc takes into account uncertainties in the calculated overvoltage distribution. The uncertainties arise
both due to inaccuracies in the overvoltage calculations, and due to the number of simulations
being finite.
Ks takes into account factors which may lead to a reduced withstand voltage:
a) Voltage shape : When the overvoltage impinging the cable has a slower wavefront than the
standard lightning impulse wave, the actual withstand voltage may be lower than the
lightning insulation level.
b) Uncertainties in testing procedures
c) Ageing : Ageing may reduce the withstand voltage with time. Extruded and paper insulated
cables have different ageing characteristics (see section ?3.2).
d) Dispersity in production : The withstand voltage may vary due to variations in materials and
production. This may particularly be the case for extruded insulation.
The cable apparatus committee (SC21) has not recommended safety factors for cable systems. For
situations with unknown safety factors, IEC 71-2 (section 4.3.4) generally recommends for internal
insulation systems usage of a safety factor of Ks=1.15. It appears that the factor 1.15 originates
from paper-oil insulation and oil-immersed insulation (transformers). Its application to cable
systems with extruded insulation should be subject to further investigations.
It should be noted that the actual withstand voltage of a new cable may be significantly higher than
the stated insulation level. This is done deliberatly in order to take into account dispersity in
production, ageing effects etc. The actual withstand voltage is, however, often not known and the
safety factor (Ks=1.15) should thererefore not be omitted.
Some cable terminals (potheads) utilize air as external insulation. Because of the stronger time-
voltage characteristic of air, the terminals could in principle flashover at a significantly lower voltage
than the inner insulation when subjected to a impulse with slower front than that of the standard
lightning impulse wave. This possibility is not always considered in existing test practices. In UK,
Figure 10a illustrates a voltage wave propagating along a line with surge impedance Z1. When the
wave meets a line with surge impedance Z2 , the reflected and transmitted waves are given by
Z 2 − Z1
Ur = U 0 = ρU 0 [Eq.4.2]
Z1 + Z 2
2 Z2
Ut = U 0 = αU 0 [Eq.4.3]
Z1 + Z 2
The resulting voltage along line 1 becomes equal to the sum of the incident and reflected wave, and
the resulting voltage along line 2 becomes equal to the transmitted wave. This is illustrated in
Figure 10b, assuming that Z2 < Z1
U0
a)
Z1 Z2
? U0
U0
a U0
b)
Z1 Z2
Overhead lines and underground cables have a surge impedance of about 400 ohm and 25 ohm,
respectively. Thus, a voltage reduction results when a wave on an overhead line enters a cable,
Similarly, a voltage increase results when a wave on a cable enters an overhead line. A voltage
doubling results when a wave meets an open line end since Z2 is then infinite.
In reality, a wave is attenuated and distorted as it propagates along a line due to frequency
dependent effects in conductors and earth, and corona formation. These effects must be
considered in insulation coordination studies.
Ground wires applied to overhead lines reduce the frequency and severity of lightning overvoltages
in connected cable systems. The protective effect is achieved as lightning strokes to the overhead
line are intercepted by the ground wires and diverted to ground, thus preventing the lightning
current from being injected into the phase conductors. However, the phase conductors may still be
affected by the stroke, as the line insulation may backflashover. In that case, the ground wires will
still have a very favourable effect as they provide several parallel ground paths through the tower
It remains a possibility that the lightning will bypass the ground wires and strike a phase conductor
directly (shielding failure). For overhead lines with a sufficiently small shielding angle, the probability
of a shielding failure is typically of the order of 1 %. Also, calculations by the Electro Geometric
Model shows that the peak value of the lightning current will normally be limited to below 5-10 kA
("critical current"), although the peak value of subsequent strokes may be higher. A discussion of
shielding angles is given in [4.2].
Surge arresters of the zinc-oxide type provides an efficient means for overvoltage protection of
cable systems. These are resistive components with a highly non-linear voltage-current
relationship. As the voltage across the arrester increases it smoothly undergoes a transition from
an isolating to a highly conductive state. The arrester is placed at one or both ends of the cable
which is to be protected.
The lightning protective level Up of zinc-oxide arresters is according to IEC 99-4 given as the peak
residual voltage across terminals when subjected to a 8/20 µs current impulse with nominal peak
current. The lowest possible protective level depends mainly on the size and duration of the
temporary overvoltages in the system. The protective factor Kp is the ratio between the LIWL of the
cable and the protective level at 10 kA :
Uw
Kp = [Eq.4.4]
Up
The protective factor should in general be as high as possible because wave reflections may cause
the overvoltages along the cable to be higher than the arrester protective level. Also, the protective
level Up increases if the cable is subjected to a larger current than the nominal current. In general,
the increase in Up with increasing current is dependent on the arrester energy class.
4.5 External overvoltages
This section provides a qualitative description of the lightning overvoltages that can be expected to
occur in cable systems.
Shielding failure
If the lightning current is injected directly at a phase conductor close to the overhead line cable
junction, the lightning current is in effect fed directly into the cable. The resulting voltage is given by
the product of the cable surge impedance and the lightning current. If assuming a surge impedance
of 25 ohm and a maximum possible peak current of 10 kA for the first stroke, a voltage wave with
peak value 250 kV would be impinging the cable. A higher voltage could occur due to wave
reflections, depending on the cable length and the termination of the cable.
The highest overvoltages are expected to occur if the cable is open-ended at the far end. This may
be the situation if the line has been tripped due to a previous lightning flash. If the travel time of the
cable is longer than the time to half value of the lightning current, voltage doubling at the opposite
end will give a total of 500 kV (neglecting attenuation). For illustration, the median value for
negative first strokes is 75 µs [4.2], which corresponds to a cable length of about 12,000 m. For
shorter cables the voltage will become even higher due to multiple reflections.
Several discharges can take place in the same lightning channel. The subsequent strokes may
exceed the maximum current of 10 kA assumed for the first stroke. According to the lightning
statistics, 5% of all negative subsequent strokes have a peak current exceeding 30 kA [4.2].
Voltage doubling at the far end of the cable would for a 30 kA stroke current lead to a voltage of
1,500 kV and wave reflections could lead to even higher voltages. On the other hand, the duration
of subsequent strokes is relatively short, with a median value of the time to half value of 32 µs.
It should be noted, however, that unless the lightning current strikes the phase conductor of the
overhead line within a short distance from the overhead line/cable junction, the line insulation is
likely to flashover and the above suggested high voltages will not occur. The combination of few
shielding failures (about 1 % for a well designed line) and a short line segment (where strokes will
not cause the line insulation to flashover) makes the above suggested high overvoltages a very rare
event.
Backflashover
The majority of lightning strokes to an overhead line will terminate at the ground wires or at the
tower top. As a rough estimate the lightning current will in the latter case "see" the tower footing
Figure 11 : Voltage buildup on cable end due to multiple reflections inside cable
In reality, the situation is a lot more complicated than in Figure 11. This is partly due to the following
phenomena and factors :
• Wave reflections between the cable entrance and the site of backflashover
• Current waves on the ground wires
• Cable termination at far end
• Usage of surge arresters
• Ground potential rise at cable entrance
A typical result from Monte Carlo-simulations is that long cables tend to be subjected to lower
overvoltages than shorter cables. This is mainly because the buildup of the cable overvoltage takes
longer time for long cables, and so it may become halted by the finite duration of the stroke current.
This is also evident in Figure 11. Also, very short cables tend to be subjected to lower overvoltages
due finite steepness of the incident wave. The trend of lower overvoltages for short and very long
cables is reflected in some of the national practices for protection (see Table 12).
It is common practice to protect the cable by surge arresters at the overhead line side of the cable.
This limits the overvoltage at this end to the arrester protective level plus the voltage drop of
connecting leads. This provides good protection of most cable systems. Sometimes it may be
necessary to provide surge arresters at both ends of the cable, particularly if the opposite cable end
could be disconnected (e.g. due to line tripping). Even when a cable is protected by arresters at
both ends, a higher overvoltage could occur inside the cable due to reflections. In one case [4.4] a
voltage increase of 15 % was found at the cable point compared to the arrester protective level.
In general, a technical-economical optimal selection of rated withstand voltage and protective
devices would depend on the following factors :
1
U= U0 [Eq.4.5]
1 + 1/ n
is transmitted into the cable. It is seen from [Eq.4.5] that the transmitted voltage may approach V0 if
there are several cables connected to the busbar. If in addition the cable is open-circuited at the far
end and crossbonding is not applied, then a voltage doubling results, giving a total voltage of 2 U0.
The situation is illustrated in Figure 12.
It should be noted that overvoltages slightly in excess of 2 U0 may occur in the presence of a series
inductor at the source side. Theoretically, an overvoltage of 2.43 U0 may result at the far end of a
cable when energizing the cable from an ideal source in series with an inductor. However, this high
voltage assumes a lossless system. Reference [4.5] (p. 4.9) shows maximum cable overvoltages
for a lossy system ranging between 2.10 U0 and 2.20 U0 (depending on which cable model was
used), when energizing a crossbonded cable system.
1 +U 0
Z
Z
2 Z
Z
3
Z
n Z
U0 +
-
Voltage (n>>1):
t1
U0
t2 > t 1
2U 0
U0
Position
Reclosures are normally not used in pure cable systems as faults are assumed to be permanent.
Thus, switching is not likely to cause overvoltages exceeding 2 times the peak value of the phase
voltage. This voltage is likely to be lower than the protective margin of arresters. Reclosures may,
however, be used in networks with a mix of cable and overhead lines.
For comparison, the maximum switching overvoltages that can occur in cables are normally lower
than those occurring in overhead lines subjected to switching. This is partly due to the strong
electromagnetic coupling between phases of an overhead line and the possible usage of
reclosures. Field investigations indicate that overhead line energization (without reclosure) can give
maximum values of 1.7-2.8 U0 [4.4].
4.7 References
[4.1] CIGRE brochure 63: "Guide to procedures for estimating the lightning performance of
transmission lines", Working Group 01 report for Study Committee 33, October 1991.
[4.2] K. Berger, R.B. Anderson and H. Kröninger, "Parameters of lightning flashes", Electra No.
41, July 1975.
[4.3] J. Huse, K. Olsen and T. Ulriksen, "Lightning overvoltages in cable connections", Electra
no. 58, pp. 81-93, 1978.
[4.4] IEEE Committee Report, "Switching surges, Part III: Field and Analyzer Results for
Transmission Lines. Past, Present and Future Trends", IEEE Trans. PAS, vol. 89, no. 2, pp. 173-
189, 1970.
[4.5] IEEE PES Special Publication: "Modeling and analysis of system transients using digital
programs",
IEEE Catalog Number: 99TP133-0, 1998.
This section reports considerations on current practices being employed by the countries
represented in the working group. Some examples are given in Table 12. In addition, the impact of
network configuration on lightning overvoltages is discussed.
An air-gap is simple and robust but presents a delay before flashover. This delay, which is typical to
gaseous insulation, may be a problem for the protection of solid insulation devices. The flashover
also stresses the network by dropping the voltage very rapidly down to zero, creating a large
transient in the network.
ZnO arresters are more efficient than SiC types because they do not present the time delay and
voltage drop the SiC arresters have because of their series gap. The lack of series gap also makes
the wave forms smoother in networks protected by ZnO arresters than by SiC arresters. Finally, the
intrinsic voltage-current characteristic of ZnO is better than the SiC's. These arguments are
developed in [5.4].
Surge arresters are generally located at underground cable / overhead line interfaces. A cable may
be protected by devices located at either one or both ends, depending on its length, the risk of
overvoltages, the keraunic level and national practices.
It has to be noted that an arrester is efficient only if it is placed close to the cable it protects. The
stray inductance due to distance between protection device and cable may be of importance
because of the high steepness of the wave forms involved in lightning overvoltages.
5.2.1 Operation
Cables may also be protected against switching transients by operation restrictions. For example, a
hybrid link (overhead line and underground cable) may not be energised from the cable side, but
from the line side. Auto reclosure or circuit breaker operation proven to give raise to high
overvoltages may be forbidden.
In special cases, insertion resistor, synchronous closing or point-on-wave control may be used to
damp energising overvoltages. These devices are described in [IEC 71-2], [5.1], [5.2] and [5.3].
The presence of one or more ground wire(s) on the entire line protects the phase wire against
direct lightning strokes and reduces lightning overvoltages and backflashovers by creating a low
impedance return path to ground. This phenomenon is discussed in more detail in chapter ?4.
Without ground wire, about half of the lightning strikes hitting a line hit a phase conductor, leading
to a severe overvoltage (see [5.5]). The line insulators limit this overvoltage and transform it into a
chopped transient. An underground cable connected to such a line is thus submitted to 3 types of
overvoltages :
- Approximately half of lightning strokes hit a tower. Only few of them have a current high enough to
cause a backflashover, leading an overvoltage to the cable.
- Among the lightning stoikes hitting a phase conductor, most have a current high enough to make
an insulator flash. Thus, the overvoltages caused by these strokes and transmitted to the cable are
chopped. The behaviour of insulation stressed by such wave forms is not very well known, because
they are tested under standard wave forms.
- Few of the strokes hitting a conductor do not make the line insulators flash. The consequent
overvoltages have the same shape as the lightning current, which looks like a standard wave form.
The overvoltage amplitude can be up to the BIL of the line.
If a line has at least one ground wire, the number of these wires has two effects:
- An electro-geometric effect: the more ground wires a line has, the better the conductors are
protected against direct strokes.
- An electrical effect: the ground wires are paths to ground for the lightning current and the more
numerous they are, the better path to ground they represent, so the greater the critical current is.
The type of tower may have an impact on back flashovers. When a lightning stroke hits a tower, a
current flows into it and a voltage drop appears between its crossarms due to L.dI/dt. If the phase
conductors are in a vertical formation, the farthest crossarm will have the smallest voltage, so the
farthest phase insulation will have the smallest voltage, thus the smallest flashover probability. This
effect acts against the coupling effect. These two phenomena have the same magnitude (15 to 20
per-cent). This voltage dropping effect does not appear in a flat formation tower.
In HV overhead networks, instead of raising the diameter of a single conductor, n small conductors
(radius r) are often put together in a bundle (radius R). From the high frequency surge point of view,
the bundle is seen as a conductor having an equivalent radius of Req = n.r.R n-1 . Since R >> r,
n
the equivalent radius may be 10 to 20 times r, which has an influence on the surge impedance. For
example, the surge impedance of a line can drop from 480 to 330 ohms when replacing a single
conductor by a quadruple bundle, keeping the same total cross section. This smaller surge
impedance reduces the overvoltage (U=Zs.I) transmitted to the line at a given current. It causes
also the overvoltage transmitted to a cable (Zs=25 ohms) connected to this line to rise from 10 to
15 per-cent of the incoming overvoltage, because of a better impedance matching. Because
bundled conductors are less subject to corona effect, a surge travelling along such a line is less
damped than along a single conductor line. As a consequence, the length to be considered for
atmospheric overvoltages calculation is a little longer for bundled conductors. This effect is not very
pronounced.
The way sheaths are cross-bonded and grounded is very important for lightning overvoltages. Main
insulation of cables with sheaths grounded at both ends are normally subject to higher overvoltages
than cross-bonded ones, due to the absence of coupling effect between phases. This matter needs
further investigation.
5.4 References
[5.3] "IEEE application guide for surge protection of electric generating plants"
IEEE Std C62-23-1995
[5.4] CIGRE brochure 60 : "Metal oxide surge arresters in ac systems", WG33-06, April 1991
Table 12 : Survey of national protection practices for underground cables (for information purpose)
Some examples of different system configurations have been identified, based on the experience of the
working group member countries.
The different categories of overvoltages that can occur on the cable system have been documented.
Methods to limit the magnitude of the overvoltage vary from Utility to Utility. There is no standardised
approach and Utilities adopt their own tried and tested techniques. Internally and externally generated
overvoltages can be limited by the use of overvoltage protection devices such as zinc oxide surge
arresters connected to one end or both ends of the cable. Certain operating procedures can also minimise
the impact of internally generated switching surges.
Cable systems are likely to be subjected to lower externally generated impulse overvoltages than
overhead lines due to their lower surge impedance. On the other hand the possibility of insulation failure is
of much greater concern as the insulation is not self-restoring. The risk associated with the consequence
of a failure must be balanced against the potential benefits. As regards internally generated overvoltages,
cable switching overvoltages are likely to be less than two times the crest value of the phase to ground
voltage in magnitude. In the case of overhead lines values could exceed 2.5 p.U.
Two different types of cable system technology have been considered in the study; laminar fluid or gas
pressure cables, and extruded insulation cables. Fluid or gas pressurised cables are designed to meet
predominantly the lightning impulse overvoltage requirement. In satisfying this condition the ac service
stress level is well below the ac breakdown performance of the dielectric. In the case of extruded cables
however the ac service voltage stress is a parameter that must be considered in addition to the lightning
impulse requirement.
The IEC test specifications (IEC 141 and IEC 840) reflect this approach. It is also planned to include a
switching impulse voltage requirement in future editions for system voltages above Um 170 kV (this having
been a requirement in a few countries for some years). It is believed however that this performance
requirement is not a major design parameter for paper/oil or extruded dielectric, these insulations being
less dependent on the front time and shape of the overvoltage compared to gaseous and air insulation
associated with terminations. Switching transients are clearly becoming more of an issue. There is less
information concerning “very fast transients” and the performance capability of cable insulations and
perhaps more importantly accessories under these conditions. It is possible that the standard lightning
impulse is sufficiently representative of very fast transients but the situation is unclear. In the absence of
any significant service problems that could be associated with this phenomena, it has been assumed that
performance is adequate. In the light of the fact that the occurrence of this type of overvoltage will be
greater at the higher system voltage levels, where there is less experience, particularly with extruded cable
system, further work to verify this view would seem appropriate. The deficiency associated with dc testing
of extruded cables after installation is recognised and well documented. With these exceptions it is
concluded that current and planned testing procedures are adequate.
The working group relied on existing published information pertaining to service experience, failure rates
and power availability, in the belief that this information was still valid. More up-to-date information would
however be valuable.
Insulation coordination studies using numerical simulation techniques are perfectly feasible nowadays.
However, account must be taken of suitable safety factors and of an acceptable failure rate. IEC 71-2
currently assumes a safety factor of 1.15 for cables in the absence of any other guidance. Unlike some
other electrical equipment, no specific value is specified for cables. The safety factor should take into
account voltage shape, uncertainties in testing procedures, insulation ageing, variation in production and
uncertainty in calculated overvoltages. The value of 1.15 appears to be based on paper/oil insulation and
requires further investigation, in particular for the case of extruded cables.
Similarly there are no referenced values for “acceptable failure rate” for underground cables although
some Utilities appear to have assumed a certain value, the basis of which is unclear.
The working group has undertaken system studies using the numerical simulation techniques, the
objective being to publish a “worked example” of a typical network. Unfortunately this has not been
completed within the allotted time scale and further work will be required. One interesting issue that arose
In order to facilitate such calculations, guidelines are required in order to both outline how the calculations
should be performed, how the results can be interpreted and how to adapt the testing protocol to represent
the requirements.
7.2 There should be scope for reducing the withstand capability of the cable system by verifying the
actual overvoltages generated in the system with or without the adoption of suitable protection
devices employing appropriate operating procedures. Current network modelling techniques
facilitate this possibility.
7.3 Guidelines should be developed to ensure a consistent application of the modelling techniques, in
making the calculations and interpreting the results.
7.4 Current cable testing protocols are generally satisfactory. However, more attention needs to be
paid to switching overvoltages, slow and very fast transients. The latter considerations could
introduce some additional testing requirements.
7.5 The safety factor ‘k’ (currently 1.15) needs to be investigated for both types of cable with particular
reference to cable system ageing.
7.7 Further simulation exercises are required on specific network configurations in order to verify these
preliminary conclusions.
7.8 The influence of specially bonded cable systems on the transient overvoltages appearing across
the primary insulation needs to be investigated.
This section gives some examples in common use. A few diagrams are given for the reference cable of
76/132(145) kV, 630 mm² Copper XLPE.
When an impulse or an alternative voltage U (kV) is applied, the electrical stress distribution E (kV/mm) in
the insulation layer is a function of radius r (mm):
U U
E(r ) = =
r t
r.Ln e r.Ln1 +
ri ri
6
electrical stress (kV/mm)
16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34
dista nce from conductor a xis (mm)
In the case of a radial field, equipotential lines are cylindrical and concentric to the conductor. Stress is
maximal on the conductor (or inner semi-conducting layer), where r = ri, and minimal at the surface of the
insulation layer, where r = re.
From the previous expression, the insulation thickness t (mm) is given by:
U
t = ri exp − 1
riE(ri )
It is possible to draw curves to determine the insulation thickness as a function of the conductor diameter
and the maximum electrical stress considered:
16 mm
18 mm
8,5 240 300 400 500 630 800 1000 1200 1600 2000 20 mm
22 mm
24 mm
8
electrical stress (kV/mm)
7,5
6,5
5,5
20 25 30 35 40 45 50 55 60
conductor di ameter (mm)
If the design criterion is the external stress, the following equation is easily solved with a few iterations:
V
t= − ri
t
E(re )Ln1 +
ri
It is possible to draw curves to determine the insulation thickness as a function of the conductor diameter
and the external electrical stress considered:
16 mm
18 mm
240 300 400 500 630 800 1000 1200 1600 2000 20 mm
4
22 mm
24 mm
electrical stress (kV/mm)
3,5
2,5
2
20 25 30 35 40 45 50 55 60
conductor di ameter (mm)
Three design criteria for high voltage cables are briefly described as follows: maximum stress, mean stress
and a third statistical approach [A.1 and A.2]. The minimum breakdown stress is also presented as a
variation of the mean stress.
Historically, oil-filled cables have been designed for the maximum stress at impulse, according to a
European practice, considering breakdown as a localised phenomenon at the inner surface of the
insulation, where the electrical stress is the highest.
When maximum and external stresses are both considered for the previous example, it is possible to draw
the insulation layer dimensional characteristics as a function of the conductor diameter:
95
23,5 insulation thickness
90 insulation diameter
23 240 300 400 500 630 800 1000 1200 1600 2000 85
22,5 80
75
22
70
21,5
insulation thickness (mm)
The maximum stress is predominant for small conductors, the external stress prevails for large conductors
(the limit in this example is located at a cross-sectional area of 1000 mm²).
For a voltage U and a maximum stress E(re) given, the insulation diameter can be expressed as a function
of the inner radius of insulation. Deriving this function, it is possible to determine an optimal cross-sectional
area for which:
U
ri = and re = e1.ri ≈ 2,718 ri.
E(re )
The optimal cross-sectional area in this example would be located between 300 and 400 mm².
The conductor of a HV cable is almost always chosen on a thermal criterion, a short-circuit current
intensity, or economical considerations due to total losses cost (IEC 60287 and 60949). However, it may
be noted that for small currents, the conductor designed on a usual criterion, despite its smaller diameter,
will have an increased insulation thickness which leads to a cable of a larger external diameter.
12,5 30
25
12 20
15
11,5
10
5
11
0
20 25 30 35 40 45 50 55 60
conductor di ameter (mm)
U
t=
Em
65
insulation diameter (mm)
16,5 60
55
50
45
40
16 35
30
25
20
15
15,5
10
5
0
20 25 30 35 40 45 50 55 60
conductor diameter (mm)
r t
E m = E i . i .Ln1 +
t ri
The experience on oil-filled cables was discussed once again when high voltage extruded cables appeared
in the 1960’s. A peculiar and alternative approach, based on Weibull statistics, was developed.
According to Weibull distribution without threshold (dealt in section ?3.2 dedicated to ageing), the
statistical parameter b can be evaluated for a reference cable.
it is possible to establish a new expression of the insulation thickness for this sample:
U
t j = rij exp 1
− 1
2
ri0 L 0 h 0 b
rijE i0
r 2L h
ij j j
2−b
tj
where hj is an intermediate coefficient given by: h j = 1 − 1 + (b≠2).
rij
Starting with tj=t0, the equation can be easily solved with a few iterations.
It is possible to draw curves to determine the insulation thickness as a function of the conductor diameter
and the reference cable considered:
ri0 = 20 mm
t0 = 20 mm
Lj = L0.
Two diagrams illustrate the influence of the statistical parameter b: a typical conservative value (b=8), and
an extremely high value (b=40).
Figure 19 : Lightning Impulse voltage U=650 kV, b=8, ri0=20 mm, t0=20 mm.
29
95 insulation thickness
28,5 insulation diameter
90
28 240 300 400 500 630 800 1000 1200 1600 2000
27,5 85
27 80
26,5 75
26 70
insulation thickness (mm)
Figure 20 : Lightning Impulse voltage U=650 kV, b=40, ri0=20 mm, t0=20 mm.
The criterion of minimum breakdown stress, based on mean stress, is used in Japan.
Values of EL(AC) = 20 kV/mm and EL(imp) = 50 kV/mm are currently used for high-voltage XLPE cables.
They have been improved respectively to 30 and 60 kV/mm for dry-cured cables.
Coefficient K1 corresponds to the ratio between the time duration tw of withstand voltage test (h) and the
expected life t0 of the cable (h). It is determined by the inclination n of the voltage-life curve (voltage-time
curve) :
t0
K1 = n
tw
For a reasonable value of n=12 for XLPE cables, an expected cable life of 30 years and a one-hour
withstand voltage test :
30 × 365 × 24
K1 = 12 = 2,83
1
Coefficient K2 corresponds to the ratio of breakdown strength at room temperature to that at 90°C,
coefficient K3 gives allowance for uncertain factors.
Values of K2 =1.1 and K3 =1.1 are commonly adopted.
L.Csuros and K.F. Foreman, "Some practical aspects of overvoltages on the CEGB transmission system",
IEE PROC, vol. 127, pt. C, no. 4, pp. 248-261, July 1980.
J. Lepers, M. Pays and B. Riot, "Outcome of French experience in the field of extra high voltage cables
with extruded synthetic insulation" : 21-101, CIGRE Session 1990, August 26 - September 1.
CIGRE WG 21.10, "Survey of the service experience on HV AC cable systems", Electra no. 137, pp. 47-
59, August 1991.
M.T. Bishop et. al., "Overcurrent protection alternatives for underground distribution systems", IEEE Trans.
PWRD, vol. 10, no. 1, pp. 252- , January 199?.
H. E. Orton and R. Samm, "Worldwide underground transmission cable practices", IEEE 96 SM 371-5
PWRD.
CIGRE brochure 63 : "Guide to procedures for estimating the lightning performance of transmission lines",
WG33-01, October 1991.
CIGRE Brochure 60 : "Metal oxide surge arresters in AC systems", WG33-06, April 1991.
CIGRE Brochure 39 : "Guidelines for representation of network elements when calculating transients",
WG33-02, 1990.
WG21-07, "Guide to the protection of specially bonded cable systems against sheath overvoltages",
Electra no. 128, January 1990.
A.S.H.A. Hamza, "A study of switching overvoltages on composite feeders - line-cable feeders", Energy
Convers. Mgmt, vol. 36, no. 12, pp. 1153-1165, 1995.
F.A.M. Rizk, "Some recent advances in system overvoltages and insulation coordination", Internation
Journal of Energy Systems", vol. 11, no. 1, pp. 15-19, 1991.
P.P. Barker, "Voltage quadrupling on a UD cable", IEEE Trans. PWRD, vol. 5, no. 1, pp. 498-501, January
1990.
E.W. Greenfield, "Transient behaviour of short and long cables", IEEE Trans. PAS, vol. 103, no. 11, pp.
3193-3204, November 1984.
J. Huse, K. Olsen and T. Ulriksen, "Lightning overvoltages in cable connections", Electra no. 58, pp. 81-93,
1978.
G. Maschio and A. Morello, "I cavi per altissime tensioni e le riflessioni a impulso", December 1955.
T. Karasaki, T. Goto and A. Ametani, "An abnormal overvoltage due to load rejection on EHV underground
transmission lines", IPST'95, Lisbon, 3-7, pp. 93-97, September 1995.
Von Hans-Uhlrich Paul and M. Losing, "Schutzschaltung zur Begrenzung von Schaltspannungen",
Elektrizitaetswirtschaft, Jg. 93 (1994), H. 4, pp. 129-134.
G. Maschio and A. Taschini, "Il problema delle sovratensioni manovra nei cavi ad alta tensione", April
1966.
IEEE Committee Report, "Switching surges, Part III: Field and Analyzer Results for Transmission Lines.
Past, Present and Future Trends", IEEE Trans. PAS, vol. 89, no. 2, pp. 173-189, 1970.
L. Csuros and K.F. Foreman, "Some practical aspects of overvoltages on the CEGB transmission system",
IEE Proc., vol. 127, pt. C, no. 4, pp. 248-261, July 1980.
C.F. Wagner, "Insulation co-ordination", AIEE Technical Paper 52-278, August 1952.
R.A Walling and R.D. Melchior, "Measurement of cable switching transients in underground distribution
systems", IEEE Trans. PWRD, vol. 10, no. 1, pp. 534-539, January 1995.
M. Ermel, J. Pannicke and M. Henschel, "Field measurements and modelling of the transients propagation
properties of a 380 kV cable system of 7.5 km length at BEWAG, Berlin", ?????.
Von Hans-Uhlrich Paul and M. Losing, "Die Beanspruchung der Leiter und Mantelisolation von Kunststoff-
Hochspannungskabeln durch Schaltspannungen", Elektrizitaetswirtschaft, Jg. 92 (1993), H. 4, pp. 1746-
1752.
R.A. Hartlein, V.S. Harper and H.W. Ng, "Effects of voltage surges on extruded dielectric cable life. Project
update", IEEE Trans. PWRD, vol. 9, no. 2, pp. 611-619, April 1994.
R.A. Hartlein, V.S. Harper and H.W. Ng, "Effects of voltage surges on extruded dielectric cable life", IEEE
Trans. PWRD, vol. 4, no. 2, pp. 829-842, April 1989.
R.H. Hopkinson, "Better surge protection extends URD cable life", IEEE Trans. PAS, vol. 103, pp. 2827-
2836, October 1984.
9.3 Testing
H. Ota et. al., "Application of advanced after-laying test to long-distance 275 kV XLPE cable lines", IEEE
Trans. PWRD, vol. 10, no. 2, pp. 567- , April 1995.
R. Bartnikas, R.J. Densley and R.M. Eichhorn, "Accelerated aging test for polymer insulated cables under
wet conditions", IEEE Trans. PWRD, vol. 6, no. 3, pp. 929- , July 1991.
K. Helling et. al., "Prequalification test of 400 kV XLPE cable systems", pp. 11-15, Jicable 95
F.H. Kreuger and M.C. Lelie, "The mean or maximum stress theory - Possible solution of an old dilemma",
IEEE paper 68 TP 601 - PWR, 1968.
J. Midoz (on behalf of WG21-09), "Working gradients of HV and EHV cables with extruded insulation and
its effect", Electra no. 139, December 1991.
A.J. Vandermaar, M. Wang, J.B. Neilson and K.D. Srivastava, "The electrical breakdown characteristics of
oil-paper insulation under steep front impulse voltages", IEEE Trans. PWRD, vol. 9, no. 4, pp. 1926-
October 1994.
CIGRE Working Group 21.04, "Criteria for electrical stress design of HV cables", Electra no. 169,
December 1996.
J.G. Head, P.S. Gale, D.J. Skipper and A.W. Stannett, "Ageing of oil-filled cable insulation", CIGRE 1982.
IEC PUBLICATION 71-1, "Insulation co-ordination. Part 1 : Definitions, principles and rules", Seventh
edition, 1993-12.
IEC PUBLICATION 71-2, "Insulation co-ordination. Part 2 : Application Guide", Third edition, 1996-12.
Cependant, le CIGRÉ ne pourra en aucun cas être tenu responsable des préjudices ou dommages de quelque
nature que ce soit pouvant résulter d’une mauvaise utilisation des informations contenues dans cette brochure.
Copyright © 2000
Toute reproduction, même partielle, par quelque procédé que ce soit, est interdite sans autorisation préalable.
Cette interdiction ne peut s’appliquer à l’utilisateur personne physique ayant acheté ce document pour
l’impression dudit document à des fins strictement personnelles.
Pour toute utilisation collective, prière de nous contacter à sales-meetings@cigre.org
The greatest care has been taken by CIGRE to produce this digital technical brochure so as to provide you with
full and reliable information.
However, CIGRE could in any case be held responsible for any damage resulting from any misuse of the
information contained therein.
Published by CIGRE
21, rue d’Artois
FR-75 008 PARIS
Tel : +33 1 53 89 12 90
Fax : +33 1 53 89 12 99
Copyright © 2000
All rights of circulation, translation and reproduction reserved for all countries.
No part of this publication may be produced or transmitted, in any form or by any means, without prior
permission of the publisher. This measure will not apply in the case of printing off of this document by any
individual having purchased it for personal purposes.
For any collective use, please contact us at sales-meetings@cigre.org