Products Introduction
01 Terminology

EHS : Eco(-friendly) Heating System

GEN1 : The 1st Generation of EHS Products (’09 Sep. ~)


Outdoor Unit + Comm. Kit (Samsung) + Hydro Unit (Airpac)

GEN2 : The 2nd Generation of EHS Products (’10 Aug. ~)


Outdoor Unit + Hydro Unit + A2A Indoor

A2A : Heat Delivery from Outdoor Air to Indoor Air

A2W : Heat Delivery from Outdoor Air to Indoor Water

DHW : Domestic Hot Water Tank

LT/MT/HT : Low (~59) / Middle (~69) / High (70~) Temperature

TDM : Time Division Multi System between A2A & A2W

4
02 Market Trend
1. Enforced EU Regulatory and Legislation for Energy
- RE (Renewable Energy) use and energy efficiency should be increased
- EU included air-to-water heat pumps in the renewable energy category

World Kyoto Protocol : Till 2012, green house gas should be reduced averagely 5.2% less than
wide that in 1990GHG (8% for EU)
Directives
RE Use Increase Energy Efficiency Increase Low Carbon
RES EPB EUP EE
Renewable Energy Source E. Performance of Building E. Using Products E. Efficiency

World
wide

Eco label-house, building Energy grade, Eco Index for Eco-Design

According to EU Timeline, each nation should implement the Directives above till Feb. 2009
EU
It is expected to be mandatory till about 2012 : Some nations such as France, Germany,
Nations
Sweden and UK have implemented EUP and EPB

5
02 Market Trend
2. Heat Pump : Lower Energy Cost and CO2 Emission Up to 33%
This economical and ecological system not only save energy costs, but also reduce CO2 Emission
using highly efficient heat pump technology.

Economic Ecological

Energy Cost CO2 Emission


(Euro/kWh) [EU, 2007] (kg/kWh) [EU, 2007]
0.3
0.06
0.048 32% 0.204 33%
0.2
0.04
0.033
0.143
0.02 0.1

0.00 0.00
Gas Boiler Eco Heating Gas Boiler Eco Heating

6
03 Heat Pump in the Market
Samsung
Year 2009 Daikin Melco LG CIAT (’10 Gen1)

Image

Type Split / Mono Split / Mono Split Mono Split


Capacity 7~16kW 8~14kW 9~16kW 7~31kW 8~14kW
COP 4.05~4.56 3.4~3.7 4.09~4.49 3.4~4.38 4.15~4.6
[S] 231% [S124% [S] 133% [S] 120%
Dimension Base Point
[L] 76% [L] 77% [L] 82% [L] 71%
Ambient Temp. -20~35℃ (-25~35℃) -25~21℃ -20~30℃ -15~30℃ -20~35℃
Weight 56/103kg 120/134kg 56/105kg 82/135kg 57/105kg
3 times more CO2 50% ↓ 4 times efficiency installed in High COP(4.6)
Top efficient than boiler Cost 30% ↓ relief of a boiler

USP Minimal install cost Easy Install CO2 90%↓ Comfort heating CO2 70%↓
Flexible configuration Low Op. cost Digital solution Op. Cost 30%↓ Op. Cost 30%↓
Main
Absolutely safe Minimal maintenance Minimal maintenance Easy Install
Reliable Reliable

7
04 Samsung’s EHS
1. Newly Introduced with A2W and A2A
Solar Panel
Water pipes

Refrigerant pipes

EEV Kit

Indoor Unit

Hydro Unit Room


refrigerant-water Domestic Hot Water(DHW) Thermostat
heat exchanging Tank OEM
Outdoor Unit
Remote Controller
Initially attached on
the hydro unit Warm and Safe Water

Under Floor
Heating & Radiator

8
04 Samsung’s EHS
2. Integrated Indoor Climate Control in One System

A2W A2A

Under Floor Heating Air Cooling

50%
Saving on
Cost
Radiator Domestic Hot Water Air Heating

9
04 Samsung’s EHS
3. Perfect Solution for Residential House
Water

Air
Air
Air

Water

Water
Water

Air
Water
Water

Water

10
05 Features
1. Smart Time Division Multi Technology
A smart control of Time Division Multi (TDM) operation between air-to-water and air-to-air,
enables one outdoor unit to operate for both functionalities resulting in lower product cost
and space saving.

Company A Samsung EHS


14KW 14KW

14KW 14KW 14KW


14KW 14KW

Air- Air-to-water Air-to-water/


conditioner heat pump Air-to-air A smart control of
(or boiler) TDM heat pump
time division multi operation!

11
05 Features
2. Enjoy EHS in Various Ways with TDM Technology
Customers can use EHS as multi air-conditioners providing air cooling in summer and air cooling or heating in
spring /autumn, or as a highly efficient boiler in winter, and can enjoy both of these function simultaneously in
such case of quick heating in winter. Sanitary hot water supply is available in any cases.

Summer (Cooling) Winter (Heating) Winter (Quick Heating)

As multi air-conditioners As a highly efficient boiler Both at once!


14KW OFF X kW

14KW OFF 14KW 14KW 14 - X KW


14KW

Air-to-water/ Air-to-water/ Air-to-water/


Air-to-air Air-to-air Air-to-air
TDM heat pump TDM heat pump TDM heat pump

12
05 Features
3. Quick Heating by TDM Technology
Floor heating is well known as the optimal heating option for indoor thermal comfort. However, it
takes 4~8 hours to heat up the room after it is turned on. Samsung EHS TDM technology quickens that
process by blowing hot air along with floor heating to warm up the room.

Quick Heating Normal Heating

80
ON ON
20

80
ON 20 ON ON

Target Temp.
Samsung EHS

Room Temp.
Normal Heat Pumps(Floor Heating)
Initial Temp.
Time
Normally 5~20 minutes

13
06 Benefits
1. High Performance at Low Temperature
Samsung EHS is made up of an inverter compressor optimally operated according to the outdoor
temperature, offering heating performance of 90% at -10°C and reliable antifreezing protection at -20°C.

High Performance of

at -10°C

14
06 Benefits
2. Remote Controller Gives You Easy and Abundant Options
Smart user interface technology has been woven into Samsung EHS to allow easy and
convenient control of the cooling and heating system at home. This control allows onetouch
access to energy consumption statistics and other components (Solar Panel,
Back-Up Boiler, etc) monitoring.

Providing chances to reduce more energy by letting the customer make some choices in
system using patterns!

Simple Stand-by Function at Outing


The system in "stand-by mode" stops all of its functions, except for one function that prevents the
pipes from breaking/bursting due to weather changes. Additionally, this system can keep the
house at a desired temperature even when you are out.

Real-time Energy Consumption Display


5 Eco-level bar indicator shows the level of energy consumption (Solar Panel, Back-Up Boiler and
Back-Up Heater of the hydro unit).

Solar Panel and Back-Up Boiler "Work in Progress" Display


The system indicates when Solar Panel and Back-Up Boiler are in the process of hybrid heating.

Automatic Anti-Freezing Function


When the house is left unattended for an extended period during the winter and the temperature
outside goes down, the system automatically runs its heat pump to keep the water-flow above
the sub-freezing point.

15
07 Installation
A2A
1. Installation Diagram unit

EEV
Kit
Cooling

A2W RAC
Heating
unit

3
Supply Header
Return Header

Outdoor unit Hydro-unit Cooling


Radiators or FCU

Room Controller Heating


Warm
Water

DHW Tank

16
07 Installation
3. Installation Guide

For Existing Houses with Boilers For New or Renovated Houses

More Choices in Installation !

For the Lower Installation Cost !

17
08 Line-up
2009 2010 2011 2012

11/14/16 KW
RTS : 8/17
Split – Outdoor
[8/11/14 kW]
GEN 1
6/7/8 KW
RTS : 9/23
Split – Outdoor Unit
[6/7/8 & 11/14/16 KW]
GEN 2
Product
Split - Hydro Unit
[8 & 16 KW]

Mono
(1P/3P, 11/14/16 kW)

High Temp Split/Mono


[1P/3P, 11/14/16 kW]

* CO2 system technology is under development

18
09 Specification – Outdoor Unit
Spec. Comparisons : SAMSUNG vs. DAIKIN
(6/7/8kW) (11/14/16kW) SAMSUNG DAIKIN
Power supply 1Φ/230V 50Hz 1Φ/230V 50Hz

Heating kW 6/7/8 11/14/16 5.75/6.84/8.43 11.2/14/16


Capacity
Cooling kW 7/7.5/8 11.3/14.2/15.5 7.2/8.16/8.37 13.9/17.3/17.8

Heating kW 1.31/1.59/1.93 2.42/3.21/3.90 1.26/1.58/2.08 2.46/3.17/3.83


Input
Cooling kW 1.95/2.21/2.54 2.90/3.94/4.70 2.27/2.78/2.97 3.79/5.78/6.77

COP 4.6/4.4/4.15 4.55/4.36/4.10 4.56/4.34/4.05 4.55/4.42/4.18


EER 3.6/3.4/3.15 3.9/3.6/3.3 3.17/2.94/2.82 3.67/2.99/2.63
Energy Level (Class A≥4.05) : Heating A/A/A A/A/A A/A/A A/A/A
Energy Level (Class A≥3.8) : Cooling C/D/F A/C/E F/G/G B/G/G

Dimension HxWxD mm 798 × 880 × 310 1,128 x 932 x 375 735 × 825 × 300 1,170x900x320

Heating ℃ -20~35 -20~35


Operation
Cooling ℃ 10~46 10~46
range
DHW ℃ -20~43 -20~43

Refrigerant R410A R410A

* Cooling and heating conditions are based on the floor cooling and heating
* Specifications are subject to change without prior notice for product improvement

19
09 Specification – Hydro Unit
Spec. Comparisons : SAMSUNG vs. DAIKIN

(6/7/8kW) (11/14/16kW) SAMSUNG DAIKIN

Power supply 1Φ/230V 50Hz 1Φ/230V 50Hz

Capacity kW 6/7/8 11/14/16 6/7/8 11/14/16

Dimension HxWxD mm 850 x 510 x 315 922 x 502 x 361

Heating ℃ 15 ~ 55 15 ~ 50 15 ~ 55
leaving water
temperature
Cooling ℃ 5 ~ 25 5 ~ 22

Material Epoxy painted galvanized steel Epoxy painted galvanized steel

Weight kg 45 48 46 48

Factory mounted heater kW 4 6 3 6

* Specifications are subject to change without prior notice for product improvement

20
09 Specification – Outdoor Unit (1/2)
ITEM UNIT RD060PHXEA RD070PHXEA RD080PHXEA RD110PHXEA RD140PHXEA RD160PHXEA
Function A2A/A2W Multi A2A/A2W Multi A2A/A2W Multi A2A/A2W Multi A2A/A2W Multi A2A/A2W Multi
POWER SOURCE Ph/V/Hz 1P,230~,50 1P,230~,50 1P,230~,50 1P,230~,50 1P,230~,50 1P,230~,50
CAPACITY Cooling 7,000 7,500 8,000 11,300 14,200 15,500
W
(A2W Condition#1) Heating 6,000 7,000 8,000 11,000 14,000 16,000
CONSUMPTION Cooling 1,945 2,205 2,540 2,900 3,940 4,700
W
(A2W Condition#1) Heating 1,305 1,590 1,925 2,420 3,210 3,900
R/CURRENT Cooling 8.9 10.1 11.6 12.9 17.5 20.8
A
(A2W Condition#1) Heating 6.0 7.3 8.8 10.7 14.2 17.3
EER or COP Cooling W/W 3.60 3.40 3.15 3.90 3.60 3.30
(A2W Condition#1) Heating W/W 4.60 4.40 4.15 4.55 4.36 4.10
ESEER Condition#1 W/W 5.20 5.50 4.90 5.96 5.66 5.50
CAPACITY Cooling 5,000 5,300 5,800 8.50 10.20 10.70

(A2W Condition#2) Heating 5,300 6,200 7,200 10.00 12.90 14.50
CONSUMPTION Cooling 1,850 2,040 2,320 2,700 3,520 4,040
W
(A2W Condition#2) Heating 1,555 1,875 2,250 2,860 3,850 4,530
R/CURRENT Cooling 8.5 9.3 10.6 12.0 15.6 17.9
A
(A2W Condition#2) Heating 7.1 8.6 10.3 12.7 17.1 20.1
EER or COP Cooling W/W 2.70 2.60 2.50 3.15 2.90 2.65
(A2W Condition#2) Heating W/W 3.40 3.30 3.20 3.50 3.35 3.20
ESEER Condition#2 W/W 3.60 3.70 3.70 4.91 4.82 4.29
EER Cooling W/W 3.21 3.21 3.21 3.46 3.46 3.46
(A2A Condition#3) Heating W/W 4.04 4.04 4.04 3.94 3.94 3.94

- A2W Condition#1: (Heating) Water In/Out 30℃/35 ℃, Outdoor Air DB/WB 7℃/6℃; (Cooling) Water In/Out 23℃/18℃, Outdoor Air DB 35℃
- A2W Condition#2: (Heating) Water In/Out 40℃/45 ℃, Outdoor Air DB/WB 7℃/6℃; (Cooling) Water In/Out 12℃/7℃, Outdoor Air DB 35℃
- A2A Condition#3: (Heating) Indoor Air DB/WB 20℃/15 ℃, Outdoor Air DB/WB 7℃/6℃; (Cooling) Indoor Air DB/WB 27℃/19℃, Outdoor Air DB/WB 35℃/24℃
* Specifications are subject to change without prior notice for product improvement
21
09 Specification – Outdoor Unit (2/2)
ITEM UNIT RD060PHXEA RD070PHXEA RD080PHXEA RD110PHXEA RD140PHXEA RD160PHXEA

Max. A2A Indoor ID Number EA 3↓ 3↓ 3↓ 4↓ 4↓ 4↓


Connection Max Capa kW 6.0 ↓ 7.0 ↓ 8.0 ↓ 11.0 ↓ 14.0 ↓ 14.0 ↓
(Cooling) Min Capa kW 3.0 ↑ 3.5 ↑ 4.0 ↑ 6.0 ↑ 6.4 ↑ 6.4 ↑
Cooling ℃ 10 ~ 46 10 ~ 46 10 ~ 46 10 ~ 46 10 ~ 46 10 ~ 46
Operating Range
Heating ℃ -20 ~ 35 -20 ~ 35 -20 ~ 35 -20 ~ 35 -20 ~ 35 -20 ~ 35
(A2W)
DHW ℃ -20~43 -20~43 -20~43 -20~43 -20~43 -20~43
Operating Range Cooling ℃ 10 ~ 43 10 ~ 43 10 ~ 43 10 ~ 43 10 ~ 43 10 ~ 43
(A2A) Heating ℃ -20 ~ 24 -20 ~ 24 -20 ~ 24 -20 ~ 24 -20 ~ 24 -20 ~ 24
NOISE Cooling 58 58 58 61 61 61
dB(A)
(Sound Pressure) Heating 59 59 59 63 63 63

NET mm 798x880x310 798x880x310 798x880x310 1128x932x375 1128x932x375 1128x932x375


DIMENSION
(HxWxD)
GROSS mm 891x1023x413 891x1023x413 891x1023x413 1286x1091x472 1286x1091x472 1286x1091x472

NET Kg 71 71 71 108 108 108


WEIGHT
GROSS Kg 79 79 79 116 116 116
Max Trip A 13.5 16 18 25 28 30
Current Down A 12.5 14.8 16.6 30 30 30
Liquid mm 9.52 9.52 9.52 9.52 9.52 9.52
Connecting Pipe
Gas mm 15.88 15.88 15.88 15.88 15.88 15.88
Length m 30 30 30 70 70 70
Pipe(Max.)
Level m 15 15 15 30 30 30
MCCB (field scope) A 25 25 25 40 40 40

* Specifications are subject to change without prior notice for product improvement

22
Line-Up & Specification
Product Line-up – Model Codes
Model codes for outdoor unit

1 2 3 4 5 6 7

1 Product group 4 Mode 6 Rating voltage 7 Version


RD Single piping FJM C Cooling only A 115V, 60Hz 1~9 Domestic
H Heat pump B 220V, 60Hz A~Z Export
2 Capacity (3DIGIT)
R Heat Recovery C 208~230V, 60Hz
kW
T Tropical cooling only D 200~220V, 50Hz
3 Product notation
Q Tropical heat pump E 220~240V, 50Hz
RD Single piping FJM
F 208~230V, 60Hz, 3P
5 Refrigerant
S GHP
G 380~415V, 50Hz, 3P
R R22
M Mini
M 127V, 50Hz
X R410A
J Home
H 380V, 60Hz, 3P
D W-DVM
J 460V, 60Hz, 3P
E GEO
P ECO Heating
Product Map
Line-ups
Outdoor units and Indoor units
Product Line-up
Line-ups
Accessories
Specification - 2010
Outdoor units (1/2)
ITEM UNIT RD060PHXEA RD070PHXEA RD080PHXEA RD110PHXEA RD140PHXEA RD160PHXEA
Function A2A/A2W Multi A2A/A2W Multi A2A/A2W Multi A2A/A2W Multi A2A/A2W Multi A2A/A2W Multi
POWER SOURCE Ph/V/Hz 1P,230~,50 1P,230~,50 1P,230~,50 1P,230~,50 1P,230~,50 1P,230~,50
CAPACITY Cooling 7,000 7,500 8,000 11,300 14,200 15,500
W
(A2W Condition#1) Heating 6,000 7,000 8,000 11,000 14,000 16,000
CONSUMPTION Cooling 1,945 2,205 2,540 2,900 3,940 4,700
W
(A2W Condition#1) Heating 1,305 1,590 1,925 2,420 3,210 3,900
R/CURRENT Cooling 8.9 10.1 11.6 12.9 17.5 20.8
A
(A2W Condition#1) Heating 6.0 7.3 8.8 10.7 14.2 17.3
EER or COP Cooling W/W 3.60 3.40 3.15 3.90 3.60 3.30
(A2W Condition#1) Heating W/W 4.60 4.40 4.15 4.55 4.36 4.10
ESEER Condition#1 W/W 5.20 5.50 4.90 5.96 5.66 5.50
CAPACITY Cooling 5,000 5,300 5,800 8.50 10.20 10.70
kW
(A2W Condition#2) Heating 5,300 6,200 7,200 10.00 12.90 14.50
CONSUMPTION Cooling 1,850 2,040 2,320 2,700 3,520 4,040
W
(A2W Condition#2) Heating 1,555 1,875 2,250 2,860 3,850 4,530
R/CURRENT Cooling 8.5 9.3 10.6 12.0 15.6 17.9
A
(A2W Condition#2) Heating 7.1 8.6 10.3 12.7 17.1 20.1
EER or COP Cooling W/W 2.70 2.60 2.50 3.15 2.90 2.65
(A2W Condition#2) Heating W/W 3.40 3.30 3.20 3.50 3.35 3.20
ESEER Condition#2 W/W 3.60 3.70 3.70 4.91 4.82 4.29
EER Cooling W/W 3.21 3.21 3.21 3.46 3.46 3.46
(A2A Condition#3) Heating W/W 4.04 4.04 4.04 3.94 3.94 3.94

- A2W Condition#1: (Heating) Water In/Out 30℃/35 ℃, Outdoor Air DB/WB 7℃/6℃; (Cooling) Water In/Out 23℃/18℃, Outdoor Air DB 35℃
- A2W Condition#2: (Heating) Water In/Out 40℃/45 ℃, Outdoor Air DB/WB 7℃/6℃; (Cooling) Water In/Out 12℃/7℃, Outdoor Air DB 35℃
- A2A Condition#3: (Heating) Indoor Air DB/WB 20℃/15 ℃, Outdoor Air DB/WB 7℃/6℃; (Cooling) Indoor Air DB/WB 27℃/19℃, Outdoor Air DB/WB 35℃/24℃
* Specifications are subject to change without prior notice for product improvement
Specification - 2010
Outdoor units (2/2)
ITEM UNIT RD060PHXEA RD070PHXEA RD080PHXEA RD110PHXEA RD140PHXEA RD160PHXEA

Max. A2A Indoor ID Number EA 3↓ 3↓ 3↓ 4↓ 4↓ 4↓


Connection Max Capa kW 6.0 ↓ 7.0 ↓ 8.0 ↓ 11.0 ↓ 14.0 ↓ 14.0 ↓
(Cooling) Min Capa kW 3.0 ↑ 3.5 ↑ 4.0 ↑ 6.0 ↑ 6.4 ↑ 6.4 ↑
Cooling ℃ 10 ~ 46 10 ~ 46 10 ~ 46 10 ~ 46 10 ~ 46 10 ~ 46
Operating Range
Heating ℃ -20 ~ 35 -20 ~ 35 -20 ~ 35 -20 ~ 35 -20 ~ 35 -20 ~ 35
(A2W)
DHW ℃ -20~43 -20~43 -20~43 -20~43 -20~43 -20~43
Operating Range Cooling ℃ 10 ~ 43 10 ~ 43 10 ~ 43 10 ~ 43 10 ~ 43 10 ~ 43
(A2A) Heating ℃ -20 ~ 24 -20 ~ 24 -20 ~ 24 -20 ~ 24 -20 ~ 24 -20 ~ 24
NOISE
Heating dB(A) 47 47 48 48 50 52
(Sound Pressure)

NET mm 880x798x310 880x798x310 880x798x310 932x1128x375 932x1128x375 932x1128x375


DIMENSION
(WxHxD)
GROSS mm 1023x891x413 1023x891x413 1023x891x413 1091x1286x472 1091x1286x472 1091x1286x472

NET Kg 71 71 71 108 108 108


WEIGHT
GROSS Kg 79 79 79 116 116 116
Max Trip A 13.5 16 18 25 28 30
Current Down A 12.5 14.8 16.6 30 30 30
Liquid mm 9.52 9.52 9.52 9.52 9.52 9.52
Connecting Pipe
Gas mm 15.88 15.88 15.88 15.88 15.88 15.88
Length m 30 30 30 70 70 70
Pipe(Max.)
Level m 15 15 15 30 30 30
MCCB (field scope) A 25 25 25 40 40 40

* Specifications are subject to change without prior notice for product improvement
Specification - 2010
Hydro units
ITEM UNIT NH080PHXEA NH160PHXEA
POWER SOURCE Ph/V/Hz 1P,230,50 1P,230,50
Capacity Cooling W 7,000 7,500 8,000 11,300 14,200 15,500
(A2W condition#2) Heating W 6,000 7,000 8,000 11,000 14,000 16,000
Operating Range Cooling ˚C 5~25 5~25
(Water) Heating ˚C 15~55 (H/P : 25~55) 15~55 (H/P : 25~55)
Cooling dB(A) 40 40
Sound Pressure
Heating dB(A) 35 35
Dimensions Net mm 850 x 510 x 315 850 x 510 x 315
(WxHxD) Gross mm 1024 x 412 x 564 1024 x 412 x 564
Net kg 45 48
Weight
Gross kg 55 58
Connecting Pipe Liquid Inch 3/8" 3/8"
[Refrigerant] Gas Inch 5/8" 5/8"
Connecting Pipe Liquid Inch BSPP male 1 1/4" BSPP male 1 1/4"
[Water] Gas Inch BSPP male 1 1/4" BSPP male 1 1/4"
Flow rate kg/min 17.0 20.5 23.0 31.5 40.1 45.9
Water Pump
E.Static Pressure kPa 53 51 45 64 59 54
Electric Heater Input power W 4,000 6,000
Expansion Vessel Volume Liter 8.0 8.0
Pressure Relief valve Relief Pressure bar 2.9 2.9
Air purge valve Size Inch BSPP male 3/8" BSPP male 3/8"
Service valve Size Inch BSPP male 1 1/4" BSPP male 1 1/4"
Total Water Volume Liters 5.0 5.5
Back up Boiler - 230VAC 1A (DO) 230VAC 1A (DO)
Room Thermostat - 230VAC 1A (DI) 230VAC 1A (DI)
External Control
Solar Pump - 230VAC 1A(DI) 230VAC 1A(DI)
Valves, 2/3way - 230VAC 1A(DO) 230VAC 1A(DO)
Specification - 2010
DHW tanks
Standard Solar Connected
ITEM Unit
NH200WHXEA NH300WHXEA NH200WHXES NH300WHXES
Material quality AISI 444 / DIN 1.4521
Pressure vessel
Volume capacity Liters 198 287 198 287
Capacity kW 2.6
Electric element Material INCOLOY 825
Voltage Ph/V/Hz 1P, 230~, 50
Material quality Duplex LDX 2101
Heating coil
Heating Area ㎡ 0.71
Material quality - - Duplex LDX 2101 Duplex LDX 2101
Heating coil for Solar
Heating Area ㎡ - - 0.47 0.47
Material quality Polyurethane form
Insulation
Thickness mm 40
Insulation jacket Material quality Epoxy-coated mild steel - white
Diameter mm 585 585 585 585
Dimensions overall
Height mm 1130 1580 1130 1580
Cold water inlet Inch 3/4" FBSP
Hot water outlet Inch 3/4" FBSP
Connections Recirculation mm ø 22 mm straight tube (for compression fitting)
Flow & return mm 2 x 3/4" female
Sensor pocket(s) mm ø 8.05 mm inside, 1/2" thread
Weight Overall kg 47 61 51 65
Max. Water temperature ℃ 70
Packaging Eco Foam - PUF
Other
Adjustable legs pcs 3
Specification - 2010
Indoor units - Slim duct

ITEM UNIT NH022LHXEA NH028LHXEA NH036LHXEA NH045LHXEA NH056LHXEA


POWER SOURCE Ph/V/Hz 1P, 230~,50 1P, 230~,50 1P, 230~,50 1P, 230~,50 1P, 230~,50
COOL W 2,200 2,800 3,600 4,500 5,600
CAPACITY
HEAT W 2,500 3,200 4,000 5,000 6,300

POWER CONSUMPTION COOL 80 80 80 90 100


W
at SP 2mmAq HEAT 80 80 80 90 100

R/CURRENT COOL 0.40 0.40 0.40 0.60 0.60


A
at SP 2mmAq HEAT 0.40 0.40 0.40 0.60 0.60

NOISE HIGH 31 32 32 33 33
dB(A)
(Sound Pressure) LOW 26 27 27 30 30

DIMENSION NET mm 900x199x600 900x199x600 900x199x600 1100x199x600 1100x199x600


(WxHxD) GROSS mm 1133x333x722 1133x333x722 1133x333x722 1324x315x713 1324x315x713
NET kg 25.5 25.5 25.5 32 32
WEIGHT
GROSS kg 32 32 32 39 39
Liquid mm 1/4" (Pi6.35) 1/4" (Pi6.35) 1/4" (Pi6.35) 1/4" (Pi6.35) 1/4" (Pi6.35)
Connecting Pipe
Gas mm 1/2" (Pi12.7) 1/2" (Pi12.7) 1/2" (Pi12.7) 1/2" (Pi12.7) 1/2" (Pi12.7)
Static Pressure (Low/Std./High) mmAq 0/2/4 0/2/4 0/2/4 0/2/4 0/2/4
Specification - 2010
Indoor units - Vivace

ITEM UNIT NH022VHXEA NH028VHXEA NH036VHXEA NH056VHXEA NH071VHXEA


POWER SOURCE PhV/Hz 1P, 230~,50 1P, 230~,50 1P, 230~,50 1P, 230~,50 1P, 230~,50
COOL W 2,200 2,800 3,600 5,600 6,800
CAPACITY
HEAT W 2,500 3,200 4,000 6,300 7,000
COOL 30 30 35 50 50
POWER CONSUMPTION W
HEAT 30 30 35 50 50
COOL 0.13 0.18 0.19 0.30 0.30
R/CURRENT A
HEAT 0.13 0.18 0.19 0.30 0.30

NOISE HIGH 31 31 35 40 41
dB(A)
(Sound Pressure) LOW 21 21 21 30 30

DIMENSION NET mm 825 X 285 X 189 825 X 285 X 189 825 X 285 X 189 1065X298X218 1065X298X218
(WxHxD) GROSS mm 900 X 349 X 252 900 X 349 X 252 900 X 349 X 252 1137X377X299 1137X377X299
NET kg 9.5 9.5 9.5 13.5 13.5
WEIGHT
GROSS kg 12 12 12 17.5 17.5
Liquid mm 1/4" (φ6.35) 1/4" (φ6.35) 1/4" (φ6.35) 1/4" (φ6.35) 3/8" (φ9.52)
Connecting Pipe Gas mm 1/2" (φ12.7) 1/2" (φ12.7) 1/2" (φ12.7) 1/2" (φ12.7) 5/8" (φ15.88)
Drain mm 18 18 18 18 18
Specification - 2010
Indoor units - Neo forte

ITEM UNIT NH022NHXEA NH028NHXEA NH036NHXEA NH056NHXEA NH071NHXEA

POWER SOURCE PhV/Hz 1P, 230~,50 1P, 230~,50 1P, 230~,50 1P, 230~,50 1P, 230~,50
COOL W 2,200 2,800 3,600 5,600 7,100
CAPACITY
HEAT W 2,500 3,200 4,000 6,300 8,000
COOL 25 25 30 45 50
POWER CONSUMPTION W
HEAT 25 25 30 45 50
COOL 0.16 0.16 0.18 0.27 0.30
R/CURRENT A
HEAT 0.16 0.16 0.18 0.27 0.30

NOISE HIGH 32 32 36 40 41
dB(A)
(Sound Pressure) LOW 23 23 23 30 30

DIMENSION NET mm 825x285x189 825x285x189 825x285x189 1099x315x217 1099x315x217


(WxHxD) GROSS mm 900x349x252 900x349x252 900x349x252 1137x377x299 1137x377x299
NET kg 8.5 8.5 8.5 12.5 12.5
WEIGHT
GROSS kg 10.5 10.5 10.5 15.5 15.5
Liquid mm 1/4" (φ6.35) 1/4" (φ6.35) 1/4" (φ6.35) 1/4" (φ6.35) 3/8" (φ9.52)
Connecting Pipe Gas mm 1/2" (φ12.7) 1/2" (φ12.7) 1/2" (φ12.7) 1/2" (φ12.7) 5/8" (φ15.88)
Drain mm 18 18 18 18 18
Configuration
System Overview
Outdoor Unit
Hydro Unit
Other Components
A2W System Overview
Various A2W field applications
Under Floor Heating, Radiators, Solar Panel, 2 or 3-way Valves, Thermostat, Back-Up Boiler

Outdoor Mech. Room Indoor


T

Solar thermal Panel


E
Solar Pump
Room Controller
1) Solar Control Back-up Boiler
2) Back up Boiler 4) Zone Control
Booster Heater & Protector Operation 45℃
Supply Header
Thermistor Return Header
50~55℃
3-way Valve
T
Radiators or Convectors
[Application #3]
[Application #2] Room Thermostat
3) DHW Control
[ Supply Scope ] DHW Tank Load Thermostatic T
& Actuators
Pump #1 & Balancing Valves

Load
E T B T
Pump #2 2 40℃
Supply Header
3
Return Header
E Under-Floor Heating Coils
Mixing Tank
[Application #1] [Application #4]
Zone Thermostat Differential Pressure
& 2-way Valve bypass valve
Outdoor unit Hydro-unit
A2W Temperature Range

Display Setting range Current Setting Control


Mode Target temperature
Set View Default Available display method method

• Min : 5~18℃ Hydro or


Leaving water ○ ○ 16~25℃ -50~94℃ Up/Down
• Max : 18~25℃ Indoor unit
Cooling
• Min : 18~22℃
Room ○ ○ 18~30℃ -50~94℃ Up/Down Indoor unit
• Max : 24~30℃
• Min : 15~37℃ Hydro or
Leaving water ○ ○ 25~55℃ -50~94℃ Up/Down
• Max : 37~55℃ Indoor unit
Heating
• Min : 16~22℃
Room ○ ○ 16~30℃ -50~94℃ Up/Down Indoor unit
• Max : 24~30℃
• Min : 25~35℃
Outdoor Ⅹ Ⅹ 30~40℃ -50~94℃
• Max : 35~45℃
Leaving water • Min : 18~25℃
Cooling Ⅹ Ⅹ 25~18℃ -50~94℃
(WL1-Floor) • Max : 5~18℃
Field Hydro unit
Leaving water • Min : 18~25℃ Setting or
Ⅹ Ⅹ 18~5℃ -50~94℃
(WL2-FCU) • Max : 5~18℃ Mode Thermostat
Water
• Min : -20~5℃
Law Outdoor Ⅹ Ⅹ -10~15℃ -50~94℃ SET/VIEW (Th-1 : Floor,
• Max : 10~20℃
mode Th-2 : FCU)
Leaving water • Min : 40~55℃
Heating Ⅹ Ⅹ 40~25℃ -50~94℃
(WL1-Floor) • Max : 17~37℃
Leaving water • Min : 40~55℃
Ⅹ Ⅹ 50~35℃ -50~94℃
(WL2-FCU) • Max : 17~37℃
Temperature Shifting ○ Ⅹ -5~5℃ Default - Up/Down Hydro unit
• Min : 30~40℃
DHW DHW tank ○ ○ 40~50℃ -50~94℃ Up/Down Hydro unit
• Max : 50~65℃
Outdoor temperature Ⅹ ○ - - -50~94℃ -
Operation Range
Heat Pump

Cooling Mode Heating Mode


46 35
Outdoor Temp. (℃DB)

No heat pump

Outdoor Temp. (℃DB)


operation, Back up
heater only

10
-20

5 25 15 25 44 55
Leaving water temp. (℃) Leaving water temp. (℃)

Water Temp. (℃) Water Flow rates (LPM) Air Temp. (℃, DB/WB)
Min Std Max Min Std Max Min Std Max
Cooling 5 - 25
Controller
Heating 15 - 55
Inlet - 23 (12*2) 30
Cooling 10/- 35/24 46/28
Outlet 5 18 (7*2) 25
16 (12*1) ∆ 5℃ 58 (48*1)
Inlet 10 30 (40*2) - 7/6
Heating -20/- 35/24
Outlet 25(15*4) 35 (45*2) 55 (-7/-8*3)

*1 : 11~16kW. (6~8kW) *2 : Eurovent Test Condition #2 *3 : NF PAC low temp. heating 4 : Back up heater only
Operation Range
DHW(Domestic Hot Water) Tank

Sanitary Mode
43
35

Outdoor Temp. (℃DB)


Booster heater
operation only

-20

30 44 55 70
Leaving water temp. (℃)

Water Temp. (℃) Water Flow rates (LPM) Air Temp. (℃, DB/WB)
-
Min Std Max Min Std Max Min Std Max

Controller DHW 30 - 70

Sanitary Outlet 30 - 70 -20/- - 43/26

both Hydro unit and DHW tank should be installed in a mechanical room with ambient temperature 0~40℃
Cycle Components - Outdoor
Outdoor Units - 11/14/16kW (Same with Conventional CAC)
Cycle Diagram - Outdoor
Outdoor Units - 11/14/16kW (Same with Conventional CAC)

P P
E O E O

F F
G G
D D

H
C I C
B L
S
M N M N
K K
A A
Q

J J

11/14/16 kW 6/7/8 kW
Cycle Diagram - Outdoor
Outdoor Units - 11/14/16kW (Same with Conventional CAC)

S-net 1+ View Mode Assign


Piping Diameter
A Rotary Comp
6.35
B Oil Separator
9.52
C High Pressure Sensor
12.7
D 4 Way Valve (V/V)
15.88
E Outdoor Heat Exchanger
F Main EEV 19.05

G Main EEV Check Valve 22.7


H Intercooler 25.4
I ESC EEV 28.7
J Accumulator
K Hot-Gas Bypass Valve
Temperature
Check Valve Solenoid Valve
L Capillary Sensor

M Discharge Temp Pressure Electronic


Service Valve
Sensor Expansion Valve
N Top Temp
O Cond. Out Temp Pressure
Intercooler Compressor
Switch
P Ambient Temp
Q Tsc
Oil Separator Accumulator Receiver
R Tso
S Liquid Bypass Valve
Physical Interfaces – Hydro Unit
Hydro Units

510 315

No Parts name Description


5
BSPP male 1 1/4"
1 Water outlet pipe
connection
BSPP male 1 1/4"
2 Water inlet pipe
850

connection

3 Ref' liquid pipe 3/8" Flare connection


7
6 4 Ref' gas pipe 5/8" Flare connection

5 Indicator LCD lamp


1 2 3 4

510
6 Manometer -
9

7 Controller -

315
8
8 Drain hole 14 mm

48 40
104 103 78
Service valve BSPP 1 1/4" 9 Service valve BSPP 1 ¼"
Cycle Diagram – Hydro Unit
Hydro Unit - 16kW

7) Pressure Relief Valve


[working 3bar]
6) Air vent

5) Heater Vessel
[2+4 kW, Incoloy 800]
Tw3 8) Flow Switch Tw2
[Min Flow 12LPM↑] 4) EEV
Tr1 Ref' In

10) Expansion Vessel 3) Heat exchanger


9) Water Pump
[8L, Pre-charge 1bar] [Plate type] Ref' Out
[46LPM x 70kPa]

Tr2
Tw1

11) Manometer 2) Strainer


[0~3bar] [STS304, Mesh #30]

1) Service Valve
[1 ¼” BSPP male]
Water Out Water In
Cycle Components – Hydro Unit
Hydro Unit - Base 16kW

No Parts name Description


8
3 1 Cabinet front Mild steel (eco white)

2 Cabinet base Galvanized steel

3 Wall mounted bracket ↑


2 4
4 Control case ↑
10 5
11 9 16 5 Control case cover ↑

17 6 Controller heat pump controller


12 7 P.H.E. assembly ANSI 316/304
13 18
8 Back-up heater INCOLOY 800, 6kW

7 9 Expansion vessel 8 Lit


1
10 Pipes of e/vessel BSPP female 3/8"
11 Water pipes BSPP female 1-1/4"
12 Flow switch set point 16 LPM

14 13 Water pump 46 LPM x 5.4mAq


15
14 Drain pan P.P.
6
15 Service valve BSPP male 1-1/4"
16 PCB -
17 Magnet contactor 1P 25A x 3ea
18 E.L.C.B 1P 40A, 20A
Functional diagram
DHW Tank

Hot water supply

System Configuration
Domestic Hot water Tank

35~45℃
20℃, 5~6 bar
manual(OSO)

Relief valve (9 bar)

50℃, 2 bar
Tundish
50℃, 0.3 bar DHW TANK
20℃, 2~3 bar

Expansion Pre-charge (8 bar)

43℃, 0.2 bar


Functional diagram
DHW Tank
Make sure that all parts below, include a relief valve, an expansion vessel, drain valve and pressure
reducing valve, must be installed according to your national standard. it's not provided from SAMSUNG.

• Pressure relief valve (9 bar) 35~45℃

20℃, 5~6 bar


• Expansion vessel
(pre-charge pressure = 8 bar) Relief valve (9 bar)

• Drain valve (manual type) 50℃, 2 bar

• Tundish 50℃, 0.3 bar DHW TANK


20℃, 2~3 bar

• Expansion relief valve


Expansion Pre-charge (8 bar)
• Pressure reducing valve
43℃, 0.2 bar
Functional diagram – DHW Tank