Professional Documents
Culture Documents
Types of protection for electrical equipment in explosive gas atmospheres Equipment category and Equipment protection level (EPL) Groups
Type of protection Symbol Zone Diagram Main application Standard acc. to EU-directive 94/9/EG acc. to IEC/CENELEC/NEC 505 NEC 500
standard alternate (ATEX) IEC and CENELEC
Group I Mines susceptible to firedamp ––
increased e eb 1 junction boxes, control stations for installing IEC 60079-7 Group Equipment category EPL Sufficient security
Ex-components (with a different type Methane
safety of protection), squirrel-cage motors, light
EN 60079-7
fittings ISA 60079 -7 Mines susceptible to firedamp
Group II Explosive gas atmosphere Class I
I M1 Ma during rare malfunctions
flameproof d db 1 switchgears, control stations, indicating IEC 60079-1 Subdivisions Typical gas Subdivisions
enclosures equipment, control systems, motors,
EN 60079-1 I M2 Mb until de-energizing of the equipment
transformers, heating equipment, light fittings IIA Propane Propane Class I Group D
ISA 60079-1 Explosive gas atmosphere
IIB Ethylene Ethylene Class I Group C
pressurized px pxb 1 switchgear and control cabinets, analysers, IEC 60079-2 II 1G Ga Zone 0 during rare malfunctions
large motors IIC Hydrogen Hydrogen Class I Group B
enclosures py pyb 1 EN 60079-2 II 2G Gb Zone 1 during expected malfunctions
pz pzc 2 ISA 60079-2 Acetylene Acetylene Class I Group A
II 3G Gc Zone 2 in normal operation
Group III * Explosive dust atmosphere Class II/III
intrinsic safety ia ia 0 instrumentation technology, IEC 60079-11 Explosive dust atmosphere
fieldbus technology, sensors, actuators
ib ib 1 EN 60079-11 Subdivisions Typical dust Subdivisions
[Ex ib] = associated electrical apparatus
ic ic 2 – installation in the safe area ISA 60079-11 II 1D Da Zone 20 during rare malfunctions
IIIA combustible flyings fibers/flyings Class III
II 2D Db Zone 21 during expected malfunctions
intrinsically safe systems IEC 60079-25 IIIB non-conductive dust non-conductive dust Class II Group G
II 3D Dc Zone 22 in normal operation
EN 60079-25 IIIC conductive dust carbonaceous dust Class II Group F
(1)G associated apparatus – installation in non-hazardous area
FISCO: fieldbus intrinsically-safe concept IEC 60079-27
combustible metal dust Class II Group E
EN 60079-27
ISA 60079-27 * acc. to IEC (2007) and CENELEC (2009)