Professional Documents
Culture Documents
CHILLERS | 2015
MEP 513D1
T.I.P. BASKETBALL COURT HVAC DESIGN
Designed by:
Rev D. Bugayong
Elmer F. Cacho
James Aljondino M. Milan
Rollymar A. Nicolas
Reggiemund C. Raymundo
ME51FB1
1st Semester
Approved by:
Engr. Armando C. Emata, PME
Faculty
Page i
MEF 513D1 – Air-Conditioning & Ventilation Systems ii
CHILLERS | 2015
PREFACE
This thesis is designed for students to easily understand and analyze the
HVAC Systems, Load Calculations, Design Conditions, External Load Factors,
Internal Load factors, Ventilation, Infiltration, Psychometric Processes, Distribution of
Air, and Air Handling, Chiller and Ducting Selection. This design is an application of
the course, Air-Conditioning & Ventilation Systems (MEF 513D1). Each part of this
compilation is designed to deal with the concepts, principles and theories of Heating,
Ventilating and Air-Conditioning Systems.
The tables, charts, figures, illustrations, and other references are also
included for the readers to easily comprehend this study. Care has been taken to
minimize errors in writing this study and the authors would highly appreciate any
feedbacks and constructive criticism for the improvement of this work. The authors
hope that this book would fill its purpose and thus will be useful for the college
students.
CHILLERS
ACKNOWLEDGEMENTS
The authors wish to convey their deepest appreciation and gratitude to the
significant people who contributed much to the success of this design:
CHILLERS
TABLE OF CONTENTS
TITLE PAGE
Preface .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. ii
Acknowledgements .. .. .. .. .. .. .. .. .. .. .. .. iii
Chapter 1: Introduction .. .. .. .. .. .. .. .. .. .. .. 1
1.1 Background of the Study .. .. .. .. .. .. .. .. 2
1.2 Statement of the Problem .. .. .. .. .. .. .. .. 3
1.3 Definition of Terms .. .. .. .. .. .. .. .. .. .. 4
1.4 Purposes of HVAC Systems .. .. .. .. .. .. .. 8
1.4 Purpose of Load Calculations .. .. .. .. .. .. .. 9
1.5 Principles of Cooling Loads .. .. .. .. .. .. .. .. 9
Appliances .. .. .. .. .. .. .. .. .. .. 62
Summary of Internal Heat Gain .. .. .. .. .. 63
Chapter 9: Summary .. .. .. .. .. .. .. .. .. .. .. .. 89
9.1 Conclusion .. .. .. .. .. .. .. .. .. .. 90
9.2 Maintenance .. .. .. .. .. .. .. .. .. .. 91
9.3 Troubleshooting .. .. .. .. .. .. .. .. .. 96
9.4 Recommendation .. .. .. .. .. .. .. .. .. 97
Fan Coil Equipment Schedule .. .. .. .. .. 101
Chiller Equipment Schedule .. .. .. .. .. 103
Bibliography .. .. .. .. .. .. .. .. .. .. .. .. .. .. 112
References .. .. .. .. .. .. .. .. .. .. .. .. .. ..
INTRODUCTI
ON
1
CHAPTER
T.I.P. Basketball Court HVAC Design
MEF 513D1 – Air-Conditioning & Ventilation Systems 2
CHILLERS | 2015
Introduction
the surrounding surfaces; air motion; odors; dust; aesthetics; acoustics; and
lighting.
The emerging technology of the twentieth century paved way for the
development of HVAC systems capable of maintaining fully controlled indoor
environments. Air-conditioning is then defined as the simultaneous control of
temperature, humidity, air movement, and the quantity of air in space. On
account of these advancements, technological innovations are continuously
pushing the limits of air-conditioning and refrigeration systems to meet the wide
range of demands in order to provide safe, healthful and comfortable
environments that can operate at low energy consumption.
1. Air Change. A quantity of fresh air equal to the volume of the room or
building being ventilated.
4. Air Handling Unit (AHU). A central air-conditioner station that regulates the
conditioned air that is generally supplied into the space through ventilation
or ducting system.
9. Centrifugal Fan. A fan in which the air is turned from parallel to the axis of
rotation on entry to a direction tangential to the arc described by the tips of
the rotating blades or vanes.
11. Condensate. Moisture removed from the air when it is cooled below its
dew point; normally associated with moisture removal during
dehumidification process. The liquid formed by condensation of vapor.
12. Condensation. The precipitation of liquid from its vapor phase resulting
from the lowering of temperature at constant pressure; especially the
deposition of water from moist, warm air onto a relatively cold surface of
between two surfaces such as within a cavity wall.
13. Conductance, Thermal. The time rate of heat flow through a body
(frequently per unit area) from one of its bounding surfaces to the other for
a unit temperature difference between the two surfaces, under steady
conditions.
15. Conductivity, Thermal. The time rate of heat flow through unit area and
unit thickness of a homogenous material under steady conditions when a
unit temperature gradient is maintained in the direction perpendicular to
area. Materials are considered homogenous when the value of the thermal
conductivity is not affected by variation in thickness or in size of sample
within the range normally used in construction.
16. Cooling Load. The rate at which heat must be extracted from a space to
maintain a desired room condition.
18. Dehumidification. The process of reducing the moisture content of the air
(humidity ration decreases); serves to increase the cooling power of the
air and can contribute to occupant comfort.
19. Dehumidifier. (1) An air cooler or washer used for lowering the moisture
content of the air passing through it; (2) An absorption or adsorption
device for removing moisture from air.
20. Dew Point, Apparatus. The temperature which would result if the
psychometric process occurring in a dehumidifier, humidifier or surface-
cooler were carried to the saturation condition of the leaving air while
maintaining the same ratio of sensible to total heat load in the process.
21. Duct. A passageway made of sheet metal or other suitable material, not
necessarily leak tight, used for conveying air or other gas at low
pressures.
22. Duct Air Leakage. Air which leaks of out from supply air ducts.
23. Enthalpy. The enthalpy of a mixture of dry air and water vapor is the sum
of the enthalpy of dry air and the enthalpy of water vapor.
24. Entropy. The ratio of the heat added to a substance to the absolute
temperature at which it is added.
26. Heat, Latent. Refers to the heat added or removed during a change of
state of a substance wherein the temperature remains constant.
28. Heat, Specific. The ratio of the amount of heat required to raise the
temperature of a given mass of any substance one degree to the quantity
required to raise the temperature if an equal mass of a standard
substance.
29. Heat Transfer. The movement of heat energy from one body to another
(gas, liquid or solid or combinations thereof) by means of radiation,
convection or conduction.
30. Humidification. The process of increasing the moisture content of the air
(humidity ratio increases); transferring a mass of water to the atmospheric
air.
31. Humidity. It is defined as the amount of moisture or water vapor in the air.
32. Humidity, Absolute. The amount of water vapor present in a unit volume of
air, expressed in kilograms per cubic meter.
33. Humidity, Specific. The amount of water vapor actually present in the air
expressed in kg of water vapor per kg of dry air. It is also called humidity
ratio.
34. Humidity, Relative. The ratio of the actual partial pressure exerted by the
water vapor in any volume of air to the saturation pressure corresponding
to the dry bulb temperature of the air, expressed in percentage.
35. Infiltration. The air flowing inward through a wall, crack, etc.
37. Psychrometry. The branch of physics that deals with the measurement of
atmospheric conditions and the study of the properties of mixtures of air
and water vapor.
38. Saturation Ratio / Degree of Saturation. The ratio of the actual specific
humidity to the specific humidity of saturated air at the same dry bulb
temperature.
39. Temperature, Dew Point. The temperature where the water vapor content
of moist or humid air becomes saturated and any further cooling will cause
condensation.
42. Vapor. A gas, particularly one near to equilibrium with the liquid phase of
the substance and which does not follow the gas laws. Usually used
instead of gas for a refrigerant, and in general, for any gas below the
critical temperature.
To maintain air quality within acceptable limits of carbon dioxide, oxygen and
odor content;
To remove airborne contaminants produced by processes and occupants;
To remove internal heat gain by processes, building services and occupants;
and/or
To provide special environment control for equipment and processes.
Heat gain, or perhaps more correctly, instantaneous rate of heat gain, is the
rate at which heat enters or is generated within a space at a given instant of time.
There are two (2) ways that heat gain is classified – the manner in which heat
enters the space and the type of heat gain.
The components of the load source which enters a space can be summarized
as follows:
1. Heat conduction through exterior walls and roof;
2. Solar radiation and heat gain through transparent surfaces such as
windows;
3. Heat conduction through interior partition walls, ceilings, and floors;
4. Loads as a result of ventilation and infiltration of outdoor air;
5. Heat generated within the space by occupants, lights, appliances,
equipment and processes; and
6. Other miscellaneous heat gains.
Sensible heat gain is the direct addition of heat to a space, which shall result
in an increase in space temperature. The factors influencing sensible heat loads
are:
1. Solar and transmission heat gain through exterior walls, roof, floors, etc.;
2. Transmission eat gain through partition walls;
3. Ventilation and infiltration through cracks in the building, doors, and
windows;
4. Occupants;
5. Heat generated by appliances and equipment; and
6. Lights.
Latent heat gain is the heat contained in water vapor. Latent heat does not
cause a temperature rise, but it constitutes a load on the cooling equipment.
Latent load is the heat that must be removed to condense the moisture out of
the air. The factors influencing latent heat loads are:
DESIGN
CONDITIONS
2
CHAPTER
Design Conditions
The design indoor air temperature may vary in accordance with the nature of
the activity engaged in and with the intended use of the building. For this
purpose, the authors were tasked design an air-conditioning system for a
basketball court given the following indoor design conditions:
𝑇𝐼𝑁𝑆𝐼𝐷𝐸 = 24℃
𝑅𝐻 = 50%
where:
𝑇𝐼𝑁𝑆𝐼𝐷𝐸 = Indoor Air Temperature (℃)
𝑅𝐻 = Relative Humidity (%)
However, it is essential to take the value of the wet bulb temperature in this
manner, and nit the value of the maximum wet bulb temperature as that would
lead to an erroneously high cooling load. This is because the relative humidity is
the lowest when the dry bulb temperature is the highest, and vice versa.
In choosing the outdoor design conditions, the authors determined the time of
day and decided the month of year to design an air-conditioning system for a
basketball court from published data for the specific location of Quezon City,
based on the available weather bureau records. The following are the outdoor
design conditions and are presented in Figure 1: Temperature Graph for
February 2015:
𝑅𝐻 = 73%
where:
𝑇𝑂𝑈𝑇𝑆𝐼𝐷𝐸 = Outdoor Air Temperature (℃)
𝑅𝐻 = Relative Humidity (%)
ARCHITECTUR
AL
LAYOUTS
3
CHAPTER
Architectural Layouts
3.1 INTRODUCTION
This chapter of the study presents the technical drawings of the proposed
HVAC design for an indoor basketball court situated at the T.I.P. campus
premises. These architectural drawings are made according to a set of
conventions, which include particular views such as sectional views and floor
layouts, vicinity map or location map, elevations, and isometric projections.
EXTERNAL
LOAD
FACTORS
4
CHAPTER
T.I.P. Basketball Court HVAC Design
MEF 513D1 – Air-Conditioning & Ventilation Systems 36
CHILLERS | 2015
4.1 INTRODUCTION
External load factors are those involved in the calculation of components of
the cooling load which arise from influences external to the space being cooled.
These components of cooling load came from:
1. Heat conduction through walls and roof;
2. Solar radiation and transmission heat gain through transparent surfaces
such as windows; and
3. Heat conduction through interior partition walls, ceilings, and floors.
4.2 FORMULAS
The calculation of external load factors are achieved using the following basic
formulas enumerated below:
𝑄𝑊𝐴𝐿𝐿 = 𝑈𝐴 (𝐶𝐿𝑇𝐷)
where:
𝑄𝑊𝐴𝐿𝐿 = Heat Flow through Wall (𝑘𝑊)
𝑈 = Overall Coefficient of Heat Transfer (𝑊/𝑚2 𝐾)
𝐴 = Cross-Sectional Area (𝑚2 )
𝐶𝐿𝑇𝐷 = Cooling Load Temperature Difference (℃)
𝑄𝑅𝑂𝑂𝐹 = 𝑈𝐴 (𝐶𝐿𝑇𝐷)
where:
𝑄𝑅𝑂𝑂𝐹 = Heat Flow through Roof (𝑘𝑊)
𝑈 = Overall Coefficient of Heat Transfer (𝑊/𝑚2 𝐾)
𝐴 = Cross-Sectional Area (𝑚2 )
𝐶𝐿𝑇𝐷 = Cooling Load Temperature Difference (℃)
𝑄𝑊𝐼𝑁𝐷𝑂𝑊𝑆 = 𝑈𝐴 (𝐶𝐿𝑇𝐷)
where:
𝑄𝑊𝐼𝑁𝐷𝑂𝑊𝑆 = Heat Flow through Window Glass (𝑘𝑊)
𝑈 = Overall Coefficient of Heat Transfer (𝑊/𝑚2 𝐾)
𝐴 = Cross-Sectional Area of Glass (𝑚2 )
𝐶𝐿𝑇𝐷 = Cooling Load Temperature Difference (℃)
𝑄𝐹𝐿𝑂𝑂𝑅 = 𝑈𝐴 (𝐶𝐿𝑇𝐷)
where:
𝑄𝐹𝐿𝑂𝑂𝑅 = Heat Flow through Floor (𝑘𝑊)
𝑈 = Overall Coefficient of Heat Transfer (𝑊/𝑚2 𝐾)
𝐴 = Cross-Sectional Area (𝑚2 )
𝐶𝐿𝑇𝐷 = Cooling Load Temperature Difference (℃)
𝑄𝐷𝑂𝑂𝑅 = 𝑈𝐴 (𝐶𝐿𝑇𝐷)
where:
𝑄𝐷𝑂𝑂𝑅 = Heat Flow through Door (𝑘𝑊)
𝑈 = Overall Coefficient of Heat Transfer (𝑊/𝑚2 𝐾)
𝐴 = Cross-Sectional Area (𝑚2 )
WALL
Thermal Thermal
Material Thickness (m) Conductivity Resistance
(W / m K) (m2 K / W)
8 ’’ Concrete
0.2032 1.33 0.075
Block
5/8 ’’ Gypsum
0.0159 0.16 0.18
Board
Total 3.764
RT = 3.764 m2 K/ W
Difference NE 23
(CLTD)
NW 12
SE 29
SW 16
*The CLTD values can be refereed in the 1997 ASHRAE Fundamentals Handbook.
NORTH EAST
Area (A) = (W) (H)
QNE = UA (CLTDCORRECTED)
QNE = (0.26567 W/ m2 K) (149.37053 m2) (23.3 °C)
QNE = 924.62016 W
QNE = 0.92462 kW
NORTH WEST
Area (A) = (L) (H)
Area (A) = (43.6801 m) (4.8768 m)
Area (A) = 213.01911 m2
QNW = UA (CLTDCORRECTED)
QNW = (0.26567 W/ m2 K) (213.01911 m2) (12.3 °C)
QNW = 696.09127 W
QNW = 0.69609 kW
SOUTH EAST
Area (A) = (L) (H)
QSE = UA (CLTDCORRECTED)
QSE = (0.26567 W/ m2 K) (213.01911 m2) (29.3 °C)
QSE = 1,658.16865 W
QSE = 1.65816 kW
SOUTH WEST
Area (A) = (W) (H)
Area (A) = (30.6288 m) (4.8768 m)
Area (A) = 149.37053 m2
QSW = UA (CLTDCORRECTED)
QSW = (0.26567 W/ m2 K) (149.37053 m2) (16.3 °C)
QSW = 646.83727 W
QSW = 0.64683 kW
QNE = 0.92462 kW
QNW = 0.69609 kW
QSE = 1.65816 kW
QSW = 0.64683 kW
QWALL = 3.92570 kW
QWALL = 3.92570 kW
ROOF
Thermal Thermal
Material Thickness (m) Conductivity Resistance
(W / m K) (m2 K / W)
Asph Roll Roof
– – 0.02642
(AR01)
Bldg Paper Felt
– – 0.01057
(BP01)
Wood Sft ¾ ’’
0.019049 0.115440 0.16501
(WD01)
Minwool Batt R11
– – 1.54096
with 2x4 Frame
Gypsum Board
0.015879 0.160266 0.09908
5/8 ’’ (GP02)
Total 1.84204
*The Overall U-Value can be referred in the Table E1.2: Resistances and U-Values for some Typical Walls.
RT = 1.84204 m2 K/ W
Cooling Load
Description of Solar Time
Temperature
Construction (15 hours)
Difference
(CLTD)
Steel Sheet with 1 ’’
77 °F
(or 2 ’’) Insulation
*The CLTD values can be refereed in the 1997 ASHRAE Fundamentals Handbook.
QROOF = UA (CLTD)
QROOF = (0.54287 W/m2 K) (2,797.00256 m2) [(5/9) (77 °F – 32)]
QROOF = 37,960.21949 W
QROOF = 37.96021 kW
WINDOW
AWINDOW = (3 ft x 2 ft) = 6 ft2 = 3.34 m2
*The Overall Coefficient of Heat Transfer (U) can be referred in the 1997 ASHRAE Fundamentals Handbook on Table 34,
Page 28.49.
QWINDOW = UA (CLTDCORRECTED)
QWINDOW = (4.60 W/ m2 K) (3.34 m2) (9.3 °C)
QWINDOW = 142.88520 W
FLOOR
Thermal Thermal
Thickness Conductivity Resistance
Components
(mm)
(W / m K) (m2 K / W)
Concrete
150 4.300 0.930
(High)
Total 2.920
*The Overall U-Value can be referred in the Table E1.2: Resistances and U-Values for some Typical Walls.
RT = 2.920 m2 K/ W
TOUT = 34 °C
TIN = 24 °C
DOOR
AGLASS = 1.11482 m2
AGLASS = 1.11482 m2
AGLASS = 1.11482 m2
ADOOR = 3.14011 m2
QNE = 1.04757 kW
QSW = 2.09514 kW
QNW = 2.09514 kW
QSE = 2.09514 kW
QWALL = 7.35308 kW
QWALL = 7.35308 kW
QWALL = 3.92570 kW
QROOF = 37.96021 kW
QWINDOW = 1.71462 kW
QFLOOR = 4.58166 kW
QDOOR = 7.35308 kW
QEXT = 55.53527 kW
QEXT = 55.53527 kW
INTERNAL
LOAD
FACTORS
5
CHAPTER
T.I.P. Basketball Court HVAC Design
MEF 513D1 – Air-Conditioning & Ventilation Systems 55
CHILLERS | 2015
5.1 INTRODUCTION
Internal load factors are those involved in the calculation of components of
the cooling load which arise from influences internal to the space being cooled.
These components of cooling load came from:
4. Lightings;
5. Occupants;
6. Appliances and Equipment; and
7. Other Internal Loads.
5.2 FORMULAS
The calculation of internal load factors are achieved using the following basic
formulas enumerated below:
where:
𝑄𝐿𝐼𝐺𝐻𝑇𝑆 = Sensible Heat Gain due to Lighting (𝑘𝑊)
𝑊 = Total Lamp Wattage (𝑊)
𝐹𝑈𝑇 = Lighting Use Factor
𝐹𝐵𝐹 = Special Ballast Allowance Factor
𝐶𝐿𝐹 = Cooling Load Factor
𝑄𝑆 = 𝑁 (𝑄𝑆 ) (𝐶𝐿𝐹)
𝑄𝐿 = 𝑁 (𝑄𝐿 )
where:
𝑄𝑆 = Sensible Heat Gain due to Occupants (𝑘𝑊)
𝑁 = Number of Occupants in Space
𝑄𝑆 = Sensible Heat Gain per Person (𝑘𝑊)
𝐶𝐿𝐹 = Cooling Load Factor
𝑄𝐿 = Latent Heat Gain due to Occupants (𝑘𝑊)
𝑄𝐿 = Latent Heat Gain per Person (𝑘𝑊)
𝑄𝑆 = 𝑁 (𝑄𝑆 )
where:
𝑄𝑆 = Sensible Heat Gain due to Appliances (𝑘𝑊)
𝑄𝑆 = Sensible Heat Gain per Equipment (𝑘𝑊)
𝑁 = Quantity of Equipment in Space
LIGHTINGS
At Table 4.1: Average Values for Ballast Factors on Cooling and Heating
Load Calculation Manual (Page 4.1), use:
FBF = 1.08
FUT = 1.00
Table 4.1 Average Values of Ballast Factor, FBF, for Fluorescent Lights
35
2 1.20
40
60
1 1.30
75
60
2 1.20
75
110 1 1.25
110 2 1.07
160 1 1.15
160 2 1.08
185
1 1.08
215
185
2 1.06
215
At Table 4.3 “a”: Classification for Lights on Cooling and Heating Load
Calculation Manual (Page 4.1), use:
0.55: Recessed lights which are not vented. Medium to high air supply
rate – more than 0.5 cfm/ft2 of floor area. Supply and return diffusers
below ceiling or through celling space and grill.
Recessed lights which are not vented. Low air supply rate – less than 0.5
0.45
cfm/ft2 of floor area. Supply and return diffusers below ceiling.
Recessed lights which are not vented. Medium to high air supply rate –
0.55 more than 0.5 cfm/ft2 of floor area. Supply and return diffusers below
ceiling or through celling space and grill.
Vented or free hanging lights. Supply air through ceiling or wall but return
0.65
air flows around light fixtures and through a ducted return.
Vented or free hanging lights. Supply air through ceiling or wall but return
0.75
air flows around light fixtures and through a ducted return.
At Table 4.4B: Cooling Load Factors when Lights are on for 10 Hours on
Cooling and Heating Load Calculation Manual (Page 4.4), use:
Cooling Load Factor (CLF) = 0.89
Table 4.4B Cooling Load Factors when Lights are on for 10 Hours
0.55 C 0.89
OCCUPANCY
Number of Sensible Heat Latent Heat
Activity
People (W) (W)
540 Seating 75 40
840 Standing 82 68
Equipment
20 100 135
Operating
At Table 4.6: Sensible Heat Cooling Load Factors for People on Cooling and
Heating Load Calculation Manual (Page 4.6), use:
Cooling Load Factor (CLF) = 0.60
Hours after
Total Hours
Each Entry
in Space
into Space
6 0.60
QS TOTAL = 78.16 kW
QS = 78.16 kW
QL TOTAL = 109.82 kW
QL = 109.82 kW
APPLIANCES
Wide Voltage
Shot Clock Basketball Stadium 70 W – 1 pc 70 W
Electronic
Microphone
Pyle Home PT110 70 W – 1 pc 70
Amplifier
TOTAL 6,924 W
QLIGHTS = 32.77692 kW
QOCCUPNY = 78.16000 kW
QAPPLIANCES = 6.92400 kW
QINT S = 117.86092 kW
VENTILATION
AND
INFILTRATIO
N
6
CHAPTER
6.1 INTRODUCTION
Outdoor Air is assumed to be fresh, clean air made up of the right
combination of oxygen (21%), nitrogen (78%), and other gases (1% hydrogen,
argon, carbon dioxide, water vapor). People and all animal life needs oxygen to
live. Nitrogen and the other gases are inert and are not harmful to animal life.
People breathe in oxygen and breathe out carbon dioxide. The oxygen level in an
enclosed occupied space must therefore be replenished by supplying outdoor air.
The outdoor air must be cleaned and filtered before it is supplied.
Indoor Air in an enclosed occupied space loses its oxygen due to the
occupants and it can also be contaminated from within the space with organisms
such as bacteria and viruses and with pollutants from the processes that occur in
the space. Indoor air must therefore be cleaned and its oxygen content
maintained by adding outdoor air. For a typical building structure, the outdoor air
supply quantity is determined on the basis of the number of occupants and
process pollution.
6.2 VENTILATION
Ventilation Air can be natural or mechanical. In modern commercial
structures, the term ventilation refers to mechanical ventilation. It is the
intentional controlled introduction of outdoor air into an enclosed occupied space.
Ventilation is provided using mechanical systems such as fans. The entry of
outdoor air through an open door or window is considered infiltration and not
ventilation. The total air supplied to a space consisting of outdoor air and indoor
recirculation air is not ventilation air either. It is referred to as supply air.
6.3 INFILTRATION
Infiltration Air refers to the unintentional and uncontrolled entry of outdoor air
into an enclosed space. Infiltration occurs through cracks in the building envelope
and due to pressure differences between the inside and outside conditions. The
outdoor air entering through open doors and windows is considered infiltration
although the purpose of opening the door or window might be ventilation.
Generally, infiltration occurs mainly in winter when the air outside is colder and
heavier than the air inside. However, it factors such as wind velocity, wind
direction and the air-tightness of the building envelope affects infiltration air. In
the case of high-rise building structures, the stack effect also causes infiltration.
Exfiltration Air refers to the flow of indoor air from an enclosed building space
to the outdoor air. Commercial air-conditioned building structures are designed to
be air-tight (windows cannot be opened) and pressurized. In summer, the air
inside is colder (air-conditioned) and therefore denser (heavier) than the hotter
air outside. The natural air flow direction then moves from the inside to outside
air. Since commercial building structures are pressurized, the air flow leakage is
from the inside to the outside. However, the amount of exfiltration is small, hence
it is usually neglected in HVAC calculations.
6.4 FORMULAS
The calculation of ventilation and infiltration are achieved using the following
basic formulas enumerated below:
where:
𝑂𝐴𝑆𝐻 = Outdoor Air Sensible Heat (𝑘𝑊)
𝑄𝑉 = Ventilation (𝑐𝑚𝑚)
∆𝑇 = Inside and Outside Temperature Difference (℃)
where:
𝑂𝐴𝐿𝐻 = Outdoor Air Latent Heat (𝑘𝑊)
𝑄𝑉 = Ventilation (𝑐𝑚𝑚)
∆𝑇 = Inside and Outside Humidity Ratio Difference (𝑘𝑔𝑤 ⁄𝑘𝑔𝑑𝑎 )
where:
𝑂𝐴𝑇𝐻 = Outdoor Air Total Heat (𝑘𝑊)
𝑂𝐴𝑆𝐻 = Outdoor Air Sensible Heat (𝑘𝑊)
𝑂𝐴𝐿𝐻 = Outdoor Air Latent Heat (𝑘𝑊)
where:
𝑅𝑆𝐻 = Room Sensible Heat (𝑘𝑊)
𝐴𝑖𝑟 𝐹𝑙𝑜𝑤 = Infiltration Air Flow (𝑚3 ⁄𝑠)
∆𝑇 = Inside and Outside Temperature Difference (℃)
where:
𝑅𝑆𝐻 = Room Latent Heat (𝑘𝑊)
𝐴𝑖𝑟 𝐹𝑙𝑜𝑤 = Infiltration Air Flow (𝑚3 ⁄𝑠)
∆𝑇 = Inside and Outside Humidity Ratio Difference (𝑘𝑔𝑤 ⁄𝑘𝑔𝑑𝑎 )
VENTILATION
Area (A) = 1,337.87 m2
Volume (V) = 6,817.12 m3
QV/ person = 0.21 cmm (Table 16.2, Page 518. C.P. Arora)
Occupancy = 1500 persons (Maximum)
Outside 34 °C 73 0.02481
Inside 24 °C 50 0.00930
*The values for Dry Bulb Temperature, Relative Humidity and Humidity Ratio can be referred in the Psychometric Chart.
OATH = 308.5425 kW
INFILTRATION
Estimates of Infiltration Airflow (Air Changes/ Flow)
Outside 34 °C 73 0.02481
Inside 24 °C 50 0.00930
*The values for Dry Bulb Temperature, Relative Humidity and Humidity Ratio can be referred in the Psychometric Chart.
PSYCHROMET
RIC
PROCESSES
7
CHAPTER
Psychrometric Processes
7.1 INTRODUCTION
After the cooling and heating loads are calculated, these loads must be
picked up and applied to a specific system to be able to select the proper HVAC
equipment. One of the most useful tools available for this step is the
psychrometric chart. The psychrometric processes and the calculations can
provide the data for equipment selection.
7.2 FORMULAS
The calculation of psychrometric processes are achieved using the following
basic formulas enumerated below:
where:
𝐸𝑅𝑆𝐻 = Effective Room Sensible Heat (𝑘𝑊)
𝑅𝑆𝐻 = Room Sensible Heat (𝑘𝑊)
𝑂𝐴𝑆𝐻 = Outdoor Air Sensible Heat (𝑘𝑊)
𝐵𝑃𝐹 = By Pass Factor
where:
𝐸𝑅𝐿𝐻 = Effective Room Latent Heat (𝑘𝑊)
𝐸𝑅𝑆𝐻
𝐸𝑆𝐻𝐹 =
𝐸𝑅𝑆𝐻 + 𝐸𝑅𝐿𝐻
where:
𝐸𝑆𝐻𝐹 = Effective Sensible Heat Factor
𝐸𝑅𝑆𝐻 = Effective Room Sensible Heat (𝑘𝑊)
𝐸𝑅𝐿𝐻 = Effective Room Latent Heat (𝑘𝑊)
QWALL = 3.92570 kW
QROOF = 37.96021 kW
QWINDOW = 1.71462 kW
QFLOOR = 4.58166 kW
QDOOR = 7.35308 kW
QLIGHTS = 32.77692 kW
QAPPLIANCES = 6.92400 kW
A 5% allowance of heat load is needed for safety for both on RSH and RLH,
therefore:
Room Sensible Heat (RSH):
RSH = QTOTAL SH + (5% Allowance) (QTOTAL SH)
RSH = 180.27007 kW + (0.05) (180.27007 kW)
RSH = 189.28357 kW
AIR-CONDITIONING CALCULATION
OUTSIDE
CONDITIONS
TDB = 34°C
RH = 73%
BASKETBALL
COURT
T4 = 24°C
RH = 50%
○
1 ○
2 ○
3 ○
4 ○
5 ○
6
CONDITIONER FAN
Table 19.8 Typical Bypass Factors of Finned Coils for Various Applications
0.2 to 0.3 Low SHF and Large Total Residence, Small Retail,
Application Factory
But 0.5769 is low for ESHF is too low. Use the ESHF value commonly used in
air-conditioning practices are ranging from 0.75 to 0.80 for economical use. Use
0.75. The intersection with the saturation curve gives the ADP as 11 °C.
ERSH + Reheat
0.75 =
ERSH + ERLH + Reheat
192.49657 kW + Reheat
0.75 =
192.49657 kW + 155.37251 kW + Reheat
Reheat = 273.62096 kW
ERSH + Reheat
cmm =
(0.0204) (TINSIDE + TADP ) (1 – BFP)
192.49657 + 273.62096
cmm =
(0.0204) (24 – 11) (1 – 0.05)
cmm = 1,850.11324 cmm
Reheat
MBP =
CP AIR (∆T)
273.62096 kJ/s
MBP =
(1.0062 kJ/kg K) (24 – 11) °C
MBP = 20.91807 kg/s
RHS = 189.28357 kW
RHL = 143.15839 kW
OASH = 64.26 kW
OALH = 244.28250 kW
273.62096 kW
Reheat =
GTH = 914.60542 kW
1 TR
GTH = 914.60542 kW x
3.516 kW
GTH = 260.12668 TR
DISTRIBUTIO
N
OF AIR
8
CHAPTER
Distribution of Air
8.1 INTRODUCTION
The design and selection of air distribution equipment in today’s building
structures presents one of the more unique challenges for mechanical designers.
Unlike any other mechanical equipment required for these environmental
systems, the air distribution equipment selection must combine a proper choice
of engineered products efficiently providing conditioned air to the space while
adding architectural features which complement the interior design. Air outlet
selection and application is no less important than any other facet of the HVAC
system. However, if the air outlets are improperly applied or selected, the entire
system could be considered a failure.
Blow-through Units are the opposite of draw-through. The coils are located on
the high-pressure or outlet side of the fan. Because of fan-discharge air is
turbulent; the coil must be far enough downstream from the fan to ensure
sufficiently laminar air flow for effective heat transfer. These systems are usually
larger than draw-through units. Alternately, a pressure plate can be installed
downstream from the fan discharge to ensure laminar air flow across the coil.
This shortens the casing length but causes a significant pressure drop in the
system, increasing energy use.
DISTRIBUTION OF AIR
Mixing of Air:
= 26.93093°C
Total Room Air Supply = Volume Flow Rate of Room Air Supply +
Volume Flow Rate of Duck Leakage + Room Occupancy Volume Flow
Rate
Total Room Air Supply = (1,202.79032 + 60.13951 + 115.57888) (1.05)
Total Room Air Supply = 1,447.43414 cfm
Total Room Air Supply = 40.98677 cmm
Mass of Air Supply = (Total Room Air Supply) (Mass of Pressure Air)
Mass of Air Supply = (40.98677 cmm) (1.2 kg/m3)
Mass of Air Supply = 49.18412 kg/min
Mass of Air Supply = 0.81973 kg/s
Mass of Air Supply = (Total Room Air Supply) (Mass of Pressure Air)
Mass of Air Supply = (43.81845 cmm) (1.2 kg/m3)
Mass of Air Supply = 52.58214 kg/min
Mass of Air Supply = 0.87636 kg/s
SUMMARY
9
CHAPTER
T.I.P. Basketball Court HVAC Design
MEF 513D1 – Air-Conditioning & Ventilation Systems 90
CHILLERS | 2015
Summary
9.1 CONCLUSION
The matter of acceptable air quality and comfortable environmental conditions
in this building where a maximum capability of 1,500 spectators is foreseen, is
the major concern. Proper ventilation and supply of fresh air play a significant
role in controlling the indoor air quality and thermal comfort for the intense
metabolism due to the overcrowding of people.
Since the Student’s Night is always crowded, the authors come up with a
design where student will be kept comfortable while they are actively participating
in any series of events. Two (2) air-handling units (AHU) are placed to maintain
cleanliness, temperature and motion of air.
WALLS, the authors recommend that the wall must be insulated so that heat
may not able to pass through. Moreover, it should be maintained well so that
minor cracks won’t cause any infiltration in the area. The recommended wall
compositions have layers such as: External Surface, External Render, Concrete
Block, Insulation, Concrete Block, Plaster and Internal Surface.
CEILING, the authors recommend the use Metal Roof, ½ ’’ Insulation Board,
½ ’’ Exp. Polystyrene and ½ ’’ Exp. Urethane to have a low value of overall
coefficient of friction (U). This layer of materials will help to lessen the effects of
solar radiation.
DOORS, different doors are designed to for specific purposes. All of the
proposed doors are two way and has a glass window placed onto it. The purpose
of having a door like this is for the students to know if there is someone entering
or exiting the area. In addition to, placing a glass would prevent accidents.
9.2 MAINTAINANCE
Predictive Maintenance
Find, identify, and correct minor problems inexpensively, before they lead to
more complex and expensive repairs;
Avoid needless downtime and inconvenience or discomfort to occupants;
Ensure continued production when equipment is used in process application;
Control energy costs;
Prolong equipment life, deferring replacement expense;
Change your air filters regularly. A clogged or improperly installed air filter
makes your system work harder. So, if you forget to change your filters, you
might notice you’re paying more for air conditioning that you’re not enjoying
nearly as much;
Be sure not to block your floor, wall or ceiling vents. When drapes, furniture,
toys or anything else blocks the vents, it will restrict the airflow—and
decrease the system’s efficiency and life span;
Check your outside condensing unit periodically to make sure it isn’t covered
up or clogged with leaves or debris. Give it space—at least a foot—by cutting
back shrubs or tall grass. Air needs to flow in through the sides to cool the
coil;
Check the drain system to make sure it isn’t clogged. Because your air
conditioner removes humidity from your home during the cooling season, you
should notice water trickling from the condensate drain of the indoor unit.
Keep in mind that the drainage will be limited if you live in a very dry
environment;
Don’t try to turn your home into an icebox. You shouldn’t run your system in
cooling mode when outdoor temperatures are lower than 55°F/12.78°C
unless your outdoor unit is modified to handle cooling in colder weather;
Have a Carrier® expert clean your indoor coil and replace your filters
routinely. If you notice longer operating cycles and reduced energy efficiency,
the coil could be to blame;
Check for water in the base of your outdoor unit. It likely means the support
base has settled or shifted since installation and is no longer level. If that’s the
case, be sure to re-level it to assure proper drainage. Also check for standing
water or ice under the unit in and arrange for it to drain away; and
Consider having your ducts sealed or insulated. Air leaks can lead to wasted
energy and an overworked air conditioner;
Ventilator maintenance
Your ventilator is designed to remove stale and polluted air from your home,
while keeping valuable energy from escaping. We’ve included some tips here to
keep it running at its best. But, of course, you can always have your
Carrier® expert maintain your ventilation system for you.
Lubricating the bearings is not recommended. The motors are factory
lubricated;
Core maintenance: First, it’s very important to know which type of unit you
have, because core cleaning varies by type and you could cause damage
with improper cleaning. The serial number will include either the letters ERV
or HRV to tell you what you have. For Energy Recovery Ventilator (ERV)
cores, vacuum every 3 months to remove dust that would inhibit the energy
transfer. Do not use water. The core should only be serviced when the
outdoor temperature is between 60°F (16°C) and 75°F (24°C) and dry. NOTE:
If the edges of the core are soft, do not try to service the core. The air
passages can be damaged and/or closed off by handling it or trying to remove
it. For Heat Recovery Ventilator (HRV) cores, wash once a year. And handle
with care. First, soak the core for 3 hours in a bath of warm water and mild
soap. Then rinse under warm, not hot, water. Hot water and strong detergents
can damage a heat recovery core;
A dirty air filter will cause excessive strain on the blower motor. The filters in
your ventilator are washable and should be cleaned every 3 months. Use a
vacuum cleaner to remove the heaviest portion of accumulated dust, then
wash in warm water. NOTE: Do NOT clean these filters in a dishwasher or
dry them with heating appliances. This will cause permanent damage. Use
lukewarm water to clean filters. Replace filters only when they are completely
dry; and
Regularly check the screen on the exterior intake hood and clean as
necessary.
Sealing Ducts
Duct sealing can have a dramatic effect on your utility bills. By properly
insulating and sealing ducts, you reduce the amount of cool air lost to your attic or
basement. According to data on the EPA's Energy Star site, leaking ducts can cost
your heating and air conditioning system as much as 20 percent of its efficiency.
Sealing also protects the system from animal or insect invasions that could
necessitate a complete duct cleaning. Sealed ducts improve indoor air quality by
creating a barrier between your ventilation network and potential pollutants that
could find their way into the system.
Your HVAC system's ductwork is vital to its efficiency and to your comfort. If you
suspect a problem with your ducts, contact a professional duct cleaning and
maintenance service such as the team at AC Southeast for an assessment.
9.3 TROUBLESHOOTING
SYSTEM NOT RUNNING
Check to make sure that your control or thermostat is set in cooling mode.
Make sure that the temperature is set cooler than the current indoor
temperature. If it isn’t, your system won’t know to provide cooling.
Make sure your outdoor cooling (condensing) unit is running. If not, check the
circuit breakers in your home’s circuit breaker box (or electrical panel). They
should be in the ON position.
Check the main power switch for your outdoor unit, usually found within a few
feet of the unit in a box mounted to the exterior of the house. Make sure it’s in
the ON position.
Ensure that the blower motor in your furnace or air handler (fan coil) is
running. If the system is set for cooling, the blower motor should be running. If
not, check to make sure your indoor unit switch is in the ON position.
If you still don’t feel that refreshing flow of cool air throughout your home or
your system is under-delivering cooling, it’s time to contact your local Carrier
expert for service.
9.4 RECOMMENDATION
We recommend that it is best to schedule professional HVAC service before it
is needed. Generally speaking, maintenance on the cooling portion should be
done once a year, during the spring. This spring service call should include the
following maintenance tasks: Ensure that the thermostat is functioning properly,
Inspect the furnace filter, Inspect and clean the evaporator and coil, Inspect,
clean, and adjust the blower motor, Inspect the condensate drain for blockage,
Inspect and clean the condenser and coil, Inspect the fan motor and blades for
damage and proper operation, Inspect all components, wiring, and controls to
ensure that they are safe and working properly, and Inspect refrigerant piping for
leakage, repair any existing leak(s), measure and (if necessary) balance the
refrigerant level.
Caustic chemicals can be applied to break down the grease. After that, hot
water can be used to rinse away the residue. Chemicals are generally applied
with either a garden type sprayer, downstream injection through a pressure
washer or with a chemical foamer. Once the chemicals are applied, they are
allowed to dwell on the surface of the grease for a period of time, before being
washed off of the surface with hot water. In extreme situations, where grease
buildup is too heavy for a chemical application and a rinse, scrapers may be
used to remove excess buildup from the contaminated surfaces, before
chemicals are applied.
Hot water pressure-washing, machines can be used that both boil water and
then apply this water under pressures up to 2000PSI. In a common method of
preparation, heavy-duty tarps are first clipped to the hoods and then angled into
plastic garbage cans to catch the run-off. As the cans are filled the contents are
disposed of successively. The grease should be removed rather than just
emptied into the local drains to avoid clogging issues. Hand scraping is also
common technique for degreasing the exhaust system back to bare metal.
and shrubs shield your home from cold winds, reducing heat loss by 10 to 30
percent.
Window Blind
A Venetian blind (or venetian blind) has horizontal slats, one above another.
Venetian blinds are basic slatted blinds made of metal or plastic; wooden slats
are sometimes used but in the US these are now usually referred to as wood
blinds or bamboo blinds. They are suspended by strips of cloth called tapes, or
by cords, by which all slats in unison can be rotated through nearly 180 degrees.
The slats can be rotated such that they overlap with one side facing inward and
then in the opposite direction such that they overlap with the other side facing
inward. Between those extremes, various degrees of separation may be effected
between the slats by varying the rotation. There are also lift cords passing
through slots in each slat. When these cords are pulled, the bottom of the blind
moves upward, causing the lowest slats to press the underside of the next
highest slat as the blind is raised. A modern variation of the lift cords combines
them with the rotational cords in slots on the two edges of each slat. This avoids
the slots otherwise required to allow a slat to rotate despite a lift cord passing
through it, thus decreasing the amount of light passing through a closed blind.
Slat width can be between 16 and 120 mm, with 25 mm being a common width.
42BH - Horizontal
40BV - Vertical
The 42B belt drive fan coil units provide year-round comfort air conditioning with central station operating economy. The 42B units are designed for high-
static, ducted applications, using furred-in, horizontal and vertical models
PERFORMANCE FEATURES
Unit Size 06 08 10 12
Number 1 1 1 1
Hydronic Coils
Size (in.) 15 x 20 15 x 20 15 x 29 15 x 29
Coil Water Volume (approx. gal. per row of coil) 0.240 0.240 0.324 0.324
0.875OD
0.625 OD
0.625OD
0.375OD
0.875OD
Fans