AE-100 Coal flow monitor

Operating manual

Shenyang stock electric power equipment Co., LTD


Ⅰ.General
The coal flow monitor of AE-100 type is mainly used with
a weighing coal feeder and has the function of detecting whether
coal flow exists in a coal dropping pipe or not. If the coal flow
doesn’t exist in the coal dropping pipe, a passive contact signal
will be sent out. The coal flow monitor is an independent
monitoring system and therefore is also used for detecting fluids
of power and solid particulate matter in other fields.
Ⅱ. Principle diagram
secondary meter
a coal flow sensor

a band-pass filter

a linear amplifier

a comparator

a relay output
a trigger

Ⅲ.Working principle
When the coal flow passes through the sensor, the sensor
outputs an electric signal which is selected by the band-pass
filter and then is amplified and compared by a signal after the
electric signal output by the sensor is selected. Finally, the
on-off condition of a relay is triggered by a trigger.
Ⅳ. Technical parameter
1. power supply voltage: AC110V (-5~10)% 50HZ
2. environmental temperature: -20-50℃
3. passive contact output
4. The sensor is connected with the casing of the sensor by a
shielding cable with four cores per square meter and a shielding
layer.
Ⅴ. The detection of sensitivity and the adjustment of delayed
alarm time for coal interruption
Four potentiometers are installed in the system. A U7:6 pin
outputs negative voltage by regulating WRI. The output voltage
at the U7:6 pin is between -0.2~0 V when the sensor doesn’t
contact the coal flow. WR2 is used for adjusting the
amplification factor of the coal flow monitor to the signal of the
sensor. If the sensitivity is high, the amplification factor will be
reduced by adjusting WR2. If the sensitivity is low, the
amplification factor will be increased by adjusting WR2. WR3
is used for adjusting the threshold voltage output by a U8: 2 pin.
The output voltage at the U8: 2 pin is 0.2 V in general
conditions. The sensitivity can be improved by reducing the
threshold voltage output by the U8: 2 pin. WR4 is used for
adjusting the delayed alarm time for coal interruption, which is
set as 10 seconds when the coal flow monitor is delivered from a
factory.( The time is adjusted according to on-site need.)
Ⅵ. Terminal connection
1. power supply plate terminal connection:
1 2 3 4 5 6

N L earth GND +12V -12V

2. signal plate terminal connection:


1 2 3 4 5 6 7 8 9 10

GND +12V -12V GND Ui GND Uo normal earth normal

open close

Note: 1. Ui is the output end of a coal flow feeding sensor.


2. Without coal flow, a normally open contact is closed
while a normally closed contact is disconnected.
3. coal flow sensor terminal connection:
-12V +12V

22 11

GND Out
44 33

Ⅶ. Outline and installation sizes


Wall mounting type M6 expansion bolt installation (four)
Outline size: (width×height×thickness) 200×300×110:
1.installation size: 170×270;