STAIR CASE-01 PRESSURISATION CALCULATION

AIR LEAKAGE THROUGH

Surface Area (m2)


for walls
Height Length Width or
Location Structural Component (m) (m) (m) Gap Length (m) for
doors

Walls 3.3 7.255 2.56 64.78


Basement (Tight)
to
Roof Floor Door frame 2.2 1.1 - 6.6
(Single Leaf)

AIR FLOW THROUGH OPEN DOORS

Number of Area of open door Geometrical Area=Half Flow Total flow through
open doors m2 of actual area(AS PER velocity open doors (Q2)
ASHRAE) m/s L/s
3 2.42 1.21 1.5 5445
AIR LEAKAGE THROUGH STAIR 1

Average Leakage Air flow throgh


Total Leakage
Ratio(for walls) or Leakage Pressure Leakage area Number Total Air flow
Area of walls throgh
Crackage(for Area difference per floor of floors Leakage
and doors Area
doors) m2 (pa) Q=0.839A√(ΔP)
m2 (m3/s)
(m /s)
3

0.000014 0.00090691
0.0405 50 0.240 19 4.566
0.006 0.0396

Total flow through TOTAL AIR FLOW REQUIRED(L/S)


open doors (Q2) 10011
(Q1+Q2 )=
L/s
5445 TOTAL AIR FLOW REQUIRED
WITH SAFETY FACTOR(L/S)= 10511

AIR FLOW CONSIDERED(L/S)= 10500


Total Air flow
throgh
Leakage Area
(L/s)

4566
FAHU SCHEDULE

HEAT

SUPPLY AIR
TOTAL STATIC
SUPPLY AIR FLOW RETURN AIR FLOW SUPPLY AIR FLOW MOTOR ON WHEEL
AHU REFERENCE ESP (Pa) PRESSURE RATING
RATE (LPS) RATE (LPS) RATE (LPS) (kW) TEMP - DB /
(Pa) WB (°C)

FAHU-01 6033 5350 6033 500 1426 15.0 46.0 / 30.0

FAHU-02 5062 4548 5062 500 1413 15.0 46.0 / 30.0

1. Units shall be factory assembled and Eurovent certified for the following :
a) D1 class for mechanical strength
b) L1 class for negative (-400Pa) and positive (-700Pa) casing leakage
c) T2 class for thermal transmittance
d) TB2 class for thermal bridging using polyamide profiles
e) F9 class for filter bypass leakage.
2.Units shall be built with pentapost extruded aluminium profiles for rigid construction
3. Panels shall be of 50mm thickness with inner / outer skin of 0.7 mm GI /0.7 mm PPGI.
4. Roof exposed units to be provided with weather proof canopy.
5. Contractor shall provide static pressure calculations for all units and obtain approval before ordering the units.
6 Units shall be installed to manufacturer's installation instructions.
HEAT RECOVERY WHEEL HORSE SHOE HEAT PIPE DETAILS CO

TOTAL SENSIBLE
SUPPLY AIR AIR ON EXTRACT AIR
OFF WHEEL EXTRACT AIR ON PRE- AIR OFF PRE- AIR ON RE-HEAT AIR OFF RE-HEAT COOLING COOLING
OFF WHEEL
TEMP - DB / WHEEL TEMP - TEMP - DB / WB COOL TEMP - COOL TEMP - TEMP - DB / TEMP - DB / WB COIL COIL
DB / WB(°C) DB / WB (°C) DB / WB(°C) WB(°C) (°C) CAPACITY CAPACITY
WB(°C) (°C) (kW) (kW)

32.9 / 23.5 26.0 / 18.7 40.8 / 27.3 32.9 / 23.5 25.2 / 21.4 14.0 / 13.6 21.7 / 16.4 172.53 81.49

32.7 / 23.4 26.0 / 18.7 40.9 / 27.4 32.7 / 23.4 25.0 / 21.3 14.0 / 13.6 21.7 / 16.4 144.85 68.39
COOLING COIL DETAILS DIMENSIONAL DETA

EXTRACT
AIR ON COIL AIR OFF COIL FLUID FAN AIR ESP (Pa) TOTAL STATIC
TEMP - DB / TEMP - DB / CHW IN / OUT CHW FLOW MOTOR LENGTH
PRESSURE FLOW PRESSURE
TEMP(°C) RATE LPS RATE RATING (kW) (mm)
WB (°C) WB (°C) DROP (KPa) (Pa)
(LPS)

25.2 / 21.4 14.2 / 13.9 5.5 / 14.5 4.6 18.58 5350 500 840 11.0 5750

25.0 / 21.3 14.3 / 14.0 5.5 / 14.5 3.8 15.26 4548 500 835 7.5 5750
DIMENSIONAL DETAILS

WIDTH (mm) HEIGHT (mm) QUANTITY

2300 3290 1

2200 3060 1