Professional Documents
Culture Documents
AN35.01.EN
Sufficient Voltage at
the End of Long Cables.
Michael Raspotnig
Data can be transmitted over long In this case one solution is to connect
distances without problem. However, a DC/DC converter as a “24 volt
the same cannot be said about power refresher” upstream of the load
for 24V devices. Severe voltage drops which generates a regulated 24V vol-
can occur if the wires are not sized tage to compensate for the fluctuati-
properly. These voltage drops are on. DC-UPS’s or buffer modules are
often underestimated and can cause ineffective in this situation.
control components to fail or trigger
a reset. Devices seldom draw current Decentralized power supplies
evenly. For example temporary volta- Locating the power supply unit close
ge fluctuations can occur when a to the device is one remedy as the
motor is connected and draws a high drop at the 230V or 400V end is negli-
starting current so analyzing the cau- gible due to the lower current. This
ses of the failure is therefore much would also counteract the general
harder. We get similar effects when trend for decentralization.
connecting loads with large input However, 24V power supply units for
capacities. control circuits are generally still loca-
Input Voltage
Fig. 3
Figure 2: Figure 3:
CD5.241: Soft-start without noticeable current increase CD5.241: Soft-start function. No unnecessarily high input
(24V, 5A constant current load) currents during the switch-on phase.
The benefit is best explained with the however, there is not a great deal of CD5: The New DC/DC converter
following example: A controller at choices with DC/DC converter so you family from PULS
the end of a cable has a relatively have to choose from what is availa- As well as refreshing voltage losses at
large buffer capacitor and an average ble. the end of long wire runs, the new
current consumption of 1.5A. Based The new CD5 series has addressed DC/DC converter series has many
on the low current, a correspondingly these problems. After applying the more possible uses:
small cross-section wire is selected. To input voltage, the default value for Generating a stabilized control vol-
compensate the voltage loss on the the maximum output current rises tage in battery powered devices
cable, a 5A standard DC/DC converter slowly to the required value. Loads Galvanic isolation of control current
is utilized to refresh the 24V. If we connected to the output and capaci- circuits to avoid ground (earth)
switch on the 24V power supply, the tors are thus charged gently. Of coar- loops
following takes place: The DC/DC con- se the start process takes a little lon- Mobile applications e.g. in ships,
verter will want to charge the capaci- ger but this method effectively pre- forklifts, …
tors in the control unit with its maxi- vents a high input current during the
mum possible current (typically 6.5A). switch-on phase.
In addition, the internal input capaci-
tors in the DC/DC converter also need
recharging. This naturally leads to a
high current at the input of the
DC/DC converter which forces the
DC/DC converter into an undervoltage
shut-down based on the voltage drop
on the line. The result is a sequence
of start-up attempts or no start up at
all. It would be possible to improve
this situation by selecting a 2A device,