You are on page 1of 10

2204 IEEE TRANSACTIONS ON INSTRUMENTATION AND MEASUREMENT, VOL. 65, NO.

10, OCTOBER 2016

A Method for Accurate Transmission Line


Impedance Parameter Estimation
Deborah Ritzmann, Student Member, IEEE, Paul S. Wright, William Holderbaum, Member, IEEE,
and Ben Potter, Member, IEEE

Abstract— Real-time estimation of power transmission line These methods are not able to track short-term changes
impedance parameters has become possible with the availability in impedance parameters, which may occur due to Joule
of synchronized phasor (synchrophasor) measurements of voltage heating and ambient temperature variations. Nowadays, it is
and current. If sufficiently accurate, the estimated parameter
values are a powerful tool for improving the performance of possible to calculate the impedance parameters of transmission
a range of power system monitoring, protection, and control lines online and in real time from synchronized phasor
applications, including fault location and dynamic thermal line (synchrophasor) measurements of voltage and current at both
rating. The accuracy of the parameter estimates can be reduced line ends. The synchrophasors are usually reported by phasor
by unknown errors in the synchrophasors that are introduced in measurement units (PMUs) that are installed in substations [6].
the measurement process. In this paper, a method is proposed
with the aim of obtaining accurate estimates of potentially Synchrophasor-based transmission line impedance deter
variable impedance parameters, in the presence of systematic mination has been investigated by many researchers since
errors in voltage and current measurements. The method is based the 1990s. Early studies demonstrated the feasibility of the
on optimization to identify correction constants for the phasors. concept and advantages over the traditional methods [7]–[9].
A case study of a simulated transmission line is presented to The determined parameter values are only useful if they
demonstrate the effectiveness of the new method, which is better
in comparison with a previously proposed method. The results, satisfy accuracy requirements, which depend on the specific
as well as limits, and the potential extensions of the new method applications. For fault location [2] and dynamic thermal line
are discussed. rating [10], it is desirable to detect thermally induced variation
Index Terms— Accuracy, admittance measurement, of the line resistance, which ranges from 1% to 20% [11].
impedance measurement, optimization methods, parameter Parameter accuracy may be expressed in terms of minimum
estimation, phasor measurement unit (PMU), transmission line and maximum limits that are derived from the accuracy of the
measurements. synchrophasor measurements [1]. The accuracy of the reported
I. I NTRODUCTION synchrophasors is influenced by the entire measurement
chain.
C ONTINUOUS electricity supply has become one of
the backbones of many economies worldwide. For this
reason, reliable and efficient operation of power networks
PMUs themselves often exceed the requirements of 1%
total vector error (TVE) and 1-μs time-tagging to UTC,
given in IEEE Standard C37.118.1-2011 [12]; for instance,
is a crucial challenge that needs to keep pace with their
PMUs with the accuracies of ±0.03% in phasor magnitude
increasingly complex nature. Reliability and efficiency are
and ±0.01° in phase angle (±0.6 μs at 50 Hz) have been
ensured through careful monitoring, protection, and control
manufactured [13]. Hence, if only the accuracy of PMUs is
of power systems, which requires a range of electrical
considered, uncertainties in impedance parameter estimates of
measurements as inputs. One of these inputs is the impedance
<2% are possible [1].
parameter of transmission lines; for example, in current
It is important to recognize that additional systematic
differential protection [1] and fault location [2].
errors of up to 1% in the magnitude and 1° in the phase
Traditionally, parameters were calculated off-line using
angle of the synchrophasors may be introduced by the
handbook formulas based on tower geometry and conductor
remaining measurement chain, as is recognized in IEEE
properties [3], [4] or through fault record analysis [5].
Standard C37.242-2013 [14]. The remaining measurement
Manuscript received November 9, 2015; revised January 28, 2016; chain includes instrument transformers, cables, burdens, and
accepted March 22, 2016. Date of current version September 12, external time synchronization equipments, such as GPS
2016. This work was supported by the Climate Knowledge and
Innovation Community within the European Institute of Innovation and antennae and connection cables.
Technology. The Associate Editor coordinating the review process was Ideally, these errors should be characterized and corrected
Dr. Carlo Muscas. before the impedance parameter estimation process. For
D. Ritzmann, W. Holderbaum, and B. Potter are with the School
of Systems Engineering, University of Reading, Reading RG6 6UR, example, in addition to the nominal transformer ratios,
U.K. (e-mail: d.ritzmann@pgr.reading.ac.uk; w.holderbaum@reading.ac.uk; transformer correction factors should be applied, and
b.a.potter@reading.ac.uk). time-tagging adjusted for delays in the synchronization signal.
P. S. Wright is with the National Physical Laboratory,
Teddington TW11 0LW, U.K. (e-mail: paul.wright@npl.co.uk). However, the actual correction factors may differ from their
Digital Object Identifier 10.1109/TIM.2016.2556920 values at the time of characterization due to aging or
0018-9456 © 2016 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission.
See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
RITZMANN et al.: METHOD FOR ACCURATE TRANSMISSION LINE IMPEDANCE PARAMETER ESTIMATION 2205

modification of the instrumentation channel. Consequently, the


measured synchrophasors can be subject to unknown errors,
which can have an adverse impact on parameter estimation
accuracy.
A number of approaches have been proposed to reduce
the impact of random errors in synchrophasor measurements
on impedance parameter determination: unbiased linear
least squares (LS) estimation [15], [16], non-linear
LS algorithms [17]–[19], total LS estimation [20], and
optimization procedures [7], [21]. On the other hand, the Fig. 1. Nominal pi circuit diagram for a medium length transmission line.
impact and reduction of systematic errors in the synchrophasor It shows the lumped impedance and admittance components, as well as the
sending and receiving end voltages and currents.
measurements with regards to impedance parameter estimation
has received less attention.
One solution is to estimate individual correction factors The circuit consists of a series impedance component Z ,
for both magnitude and phase angle of voltage and current as well as shunt admittance Y , which is split into two equal
along with the parameters in an optimization procedure [21]. components at either end of the line, as shown in Fig. 1.
However, this approach makes use of a wide range The series impedance Z has resistance R and inductance L,
of measurements and assumes time-invariant impedance while the shunt admittance Y consists of conductance G and
parameters. Hence, there is a need to develop effective capacitance C. The conductance G is normally considered
methods for the reduction of the impact of systematic negligible and omitted from the model; however, it is useful
errors in synchrophasor measurements on real-time impedance for the consideration and correction of systematic errors, as
parameter estimation. shown in Section II-C. The measured currents and voltages
In [22], a potential solution for this problem has been at either end of the line are modeled by Vs , Is , Vr , and Ir ,
proposed. It consists of a method that assumes linear which are assumed to be phasors at the nominal power system
variation of the impedance parameters over short periods frequency f ; subscript s refers to sending and subscript r to
of time. Correction constants for the synchrophasors are receiving end. By Kirchhoff’s voltage and current laws, the
identified by minimizing the residuals of an LS fit of circuit equations are
 
the calculated parameters to a linear model. The method Y
was shown to effectively reduce the impact of systematic Vs = Is − Vs Z + Vr (1)
2
errors in voltage measurements of a short transmission line, Y
neglecting shunt admittance. However, for longer lines, shunt Is = (Vs + Vr ) + Ir (2)
2
admittance is significant as it causes the current to vary
where Vs , Is , Vr , Ir , Z , Y ∈ C, Z = R + j X, X = 2π f L,
along the line, and, thus, needs to be considered in parameter
Y = G + j B, B = 2π f C, and R, X, G, B, L, C, f ∈ R>0 . X
calculations. Furthermore, systematic errors can also occur in
is the inductive reactance, and B is the capacitive susceptance.
synchrophasor measurements of current.
Substitution of (2) into (1) leads to the following formulas
The aim of this paper is to propose an extension of the
for impedance Z and admittance Y :
method, such that it can effectively reduce the impact of
systematic errors in all synchrophasor measurements for the Vs2 − Vr2
Z = (3)
general transmission line modeled by the lumped pi circuit, Vs Ir + Vr Is
which has both series impedance and shunt admittance. Is − Ir
The rest of this paper is structured as follows. In Section II, Y =2 . (4)
Vs + Vr
the models for the transmission line and systematic errors are
If a single set of synchronized measurements, Vs , Is , Vr , and
defined and the proposed method is presented. In Section III,
Ir , is available from a PMU or equivalent device, the values
a case study of a simulated line is considered, and
of Z and Y can be calculated; parameters R, X, G, and B
a comparison with an existing linear LS-based method is made.
are obtained from the real and imaginary parts of Z and Y,
Section IV is a discussion of the case study results, as well
respectively.
as strengths and limits of the proposed method. Section V
concludes this paper.
B. Systematic Errors in the Synchrophasor Measurements
II. M ETHODS In this paper, systematic errors in the form of a proportional
error in the phasor magnitude and additive offset in the phase
A. Transmission Line Model angle are considered. Let Ṽs be a synchrophasor measurement
The nominal pi circuit, as shown in Fig. 1, is the standard of the sending end voltage Vs with systematic errors as in
model for the electrical parameters of a medium length magnitude and φs in phase angle. Vs and Ṽs are related to
transmission line (80–240 km) [3]. For medium length lines,
Vs = Ṽs (1 + as ) exp( j φs ) (5)
the effects of shunt admittance cannot be ignored, but lumped
components are still a good approximation for the actual, where Ṽs ∈ C and as , φs ∈ R. This structure is chosen
distributed parameters [3]. in line with transformer correction factors, which are the
2206 IEEE TRANSACTIONS ON INSTRUMENTATION AND MEASUREMENT, VOL. 65, NO. 10, OCTOBER 2016

general model for expressing errors caused by instrument In Section II-C, a method for estimating values of a, φ, b
transformers [23]. The systematic errors are assumed to be and θ is presented.
constant, because in real-time applications, the utilized voltage
and current measurements span only a limited part of the C. Proposed Method for Identification of
instrument ranges and instrumentation channels are designed Correction Constants
for long-term stability. To reduce the deviations in the estimated parameters Z̃
On the basis of accuracy classes of instrument transformers and Ỹ due to systematic errors that were described in
and previous characterization of instrumentation channels, the Section II-B, synchrophasor measurements should be corrected
errors are assumed to be <1% in magnitude and <0.01 rad in before parameter estimates are calculated. A method has been
phase angle [14]. Thus, it is assumed that |as |, |φs | < 0.01, designed to identify such correction constants, and is presented
and the following small angle approximation is made: in the following paragraphs.
exp( j φs ) ≈ 1 + j φs . (6) The method assumes no knowledge of the true values
of impedance and admittance parameters. Instead, it is
Substituting (6) into (5) gives assumed that the behavior of the resistance and reactance is
Vs = Ṽs (1 + as )(1 + j φs ) = Ṽs (1 + as + j φs + j as φs ). (7) approximately linear over short periods relative to the thermal
time constant of overhead line conductors (5–20 min according
The lower order term j as φs will be omitted. Hence to IEEE Standard 738-2012 [24]) because of slow variation in
the rate of change of resistance and reactance. Conductance
Vs = Ṽs (1 + as + j φs ). (8)
and susceptance are assumed to be constant. Therefore, the
Define the overall error δVs ∈ C in the synchrophasor calculated parameters are fitted to linear models with respect
measurement Ṽs as to time. Let the models for R, X, G, B be f R , f X , f G , and
f B : R+ → R, respectively, where
δVs = Vs − Ṽs = (as + j φs )Ṽs . (9)
f R (ti ) = q R ti + r R (12)
Similarly, I˜s , Ṽr , I˜r ∈ C are defined as synchrophasor
f X (ti ) = q X ti + r X (13)
measurements that have systematic errors ar , φr , bs , θs , br ,
and θr , such that Vr = Ṽr (1 + ar + j φr ), Is = I˜s (1 + bs + f G (ti ) = r G (14)
j θs ), Ir = I˜r (1 + br + j θr ), and δ Is , δVr , δ Ir ∈ C are overall f B (ti ) = r B (15)
errors defined as δVr = (ar + j φr )V˜r , δ Is = (bs + j θs ) I˜s , δ Ir =
and q R , r R , q X , r X , r G , r B ∈ R are constants, which are
(br + j θr ) I˜r .
estimated in a LS sense from a set of N ∈ N parameter
Suppose that the values of as , φs , ar , φr , bs , θs , br , and θr
values Ri , X i , G i , Bi ∈ R, calculated at time instants
are unknown. Then, the impedance and admittance estimates
ti , i = 1, . . . , N, with ti = i t and t ∈ R the constant
from synchrophasors with systematic errors are given by
time interval between synchrophasor measurements. The time
2
Ṽs − V˜r
2 interval t N − t1 is a moving window that is chosen to be
Z̃ = (10) less than the thermal time constant of the line. The details
Ṽs I˜r + Ṽr I˜s
of the estimation of q R , r R , q X , r X , r G , and r B are given in
I˜s − I˜r Appendix A.
Ỹ = 2 (11) Suppose that Ri , X i , G i , and Bi are calculated from
Ṽs + Ṽr
synchrophasor measurements with systematic errors, then the
where Ṽs , I˜s , Ṽr , and I˜r have been substituted into (3) and (4). goodness of fit of f R , f X , f G , and f B is reduced. To measure
Z̃ and Ỹ deviate from Z and Y , respectively, and, thus, the the goodness of fit, the sum of the squared residual is
estimated parameters are in error. This loss of accuracy can be calculated as
reduced by estimating the values of as , φs , ar , φr , bs , θs , br ,  N

and θr to correct the phasor measurements. The following SR = (Ri − f R (ti ))2 (16)
observations are used to simplify the problem. i=1

1) Since Z is proportional to (Vs2 −Vr2 ), it is more sensitive where S R ∈ R+ . Equivalent expressions are assumed for
to as , φs , ar , and φr than to bs , θs , br , and θr , and the S X , S B , SG ∈ R+ , in terms of X i , f X , G i , f G , Bi , and f B ,
error in Z caused by as , φs is approximately equal and respectively. By minimizing S R , S X , SG and S B , correction
opposite to the error caused by ar , φr (see Appendix C). constants can be found that maximize the goodness of fit
2) Since Y is proportional to (Is − Ir ), it is more sensitive of f R , f X , f G and f B , and, thus, result in impedance and
to bs , θs , br , and θr than to as , φs , ar , and φr , and the admittance parameter estimates that are more consistent with
error in Y caused by bs , θs is approximately equal and the expected physical behavior of the line over time.
opposite to the error caused by br , θr (see Appendix C). S R and S X are sensitive to errors in Ṽs and Ṽr , and can be
Therefore, it is assumed that error constants as , ar , φs , and φr minimized by finding optimal values of correction constants
can be combined into “net” errors a and φ in V˜r , where a = a, φ for V˜r . Hence, optimization problem 1 is formulated
ar − as , φ = φr − φs , and |a|, |φ| < 0.02. Similarly, bs , θs , br , min g Z (a, φ) = S R + S X
and θr are combined into errors b and θ in I˜r , where b = a,φ (17)
br − bs , θ = θr − θs , and |b|, |θ | < 0.02. s.t. |a| < 0.02, |φ| < 0.02
RITZMANN et al.: METHOD FOR ACCURATE TRANSMISSION LINE IMPEDANCE PARAMETER ESTIMATION 2207

with initial values a = 0, φ = 0. The objective function


g Z : R2 → R+ is evaluated using correction constants a, φ to
recalculate the impedance parameters as follows:
∂ Z 
Z i = Ri + j X i = Z̃ i +  δVri (18)
∂ Vr Vr =V˜ri

where δVri = (a + j φ)V˜ri , and Z̃ i is calculated using (10)


from synchrophasor measurements V˜si , I˜si , V˜ri , and I˜ri taken
at time ti . The first-order Taylor approximation of Z is taken,
because δVri is small and in this way Z i remains linear in
a, φ. The partial derivative ∂ Z /∂ Vr is given in Appendix B.
Once Ri and X i have been recalculated using (18), new values
for q R , r R , q X , r X , r G , and r B are estimated, and S R and S X
are updated to give a new value of g Z .
Similarly, SG and S B are sensitive to errors in I˜s and I˜r .
Optimization problem 2 is defined to identify optimal values
of correction constants b, θ ∈ R for I˜r that minimize
SG and S B
min gY (b, θ ) = μ(SG + S B )
b,θ (19)
s.t. |b| < 0.02, |θ | < 0.02
with initial values b = 0 and θ = 0. Because G and B
are of the order of 10−6 and 10−4 , respectively, SG and
S B can become very small, and factor μ is introduced to
avoid bad scaling. The objective function gY : R2 → R+
is evaluated using correction constants b and θ to recalculate
the admittance parameters as follows:
∂Y 
Yi = G i + j Bi = Ỹi +  δ Ir (20)
∂ Ir Ir = Ir˜i i Fig. 2. Flow chart illustrates how values for correction constants and
impedance parameters are estimated by the proposed method.
where δ Iri = (b + j θ ) I˜ri , and Ỹi is calculated using (11)
from synchrophasor measurements V˜si , I˜si , V˜ri , and I˜ri taken
at time ti . The first-order Taylor approximation of Y is taken,
because δ Ir is small and Yi remains linear in b and θ . The
partial derivative ∂Y /∂ Ir is given in Appendix B.
Both (17) and (19) are nonlinear constrained optimization
problems, for which minima can be obtained with a range
of algorithms. In this instance, the interior-point method was
chosen [25]. g Z and gY are convex, and, thus, the local minima
are global in the feasible regions. The reason is that Z i and Yi
are linear in the respective correction constants and estimation
of q R , r R , q X , r X , r G , and r B (see Appendix A), as well as
evaluation of g Z and gY preserve convexity.
Fig. 2 shows a flow chart that summarizes the processes Fig. 3. Graph shows the magnitude of the sending and receiving end voltages
over the period of the simulation.
of identifying correction constants and estimating values of
the line parameters. The final parameter estimates at a given
time t N are obtained by fitting functions f R , f X , and f B to the
parameter values calculated from corrected measurements and the proposed method as well as an existing linear LS-based
evaluating f R (t N ), f X (t N ), and f B (t N ). The aim of this step method are presented.
is to give parameter estimates with reduced random variation,
which occurs in the individually calculated parameter values. A. Transmission Line Simulation
In Section III, the effectiveness of the proposed method is
A single phase of the 400-kV, 102-km-long transmission
demonstrated in a case study.
line located between substations Grendon and Staythorpe, East
Midlands, England [26], was simulated in MATLAB. The
III. C ASE S TUDY nominal parameter values are R0 = 2.96 , X 0 = 32.4 ,
In this section, the specifications of the transmission line and B0 = 3.69 × 10−4 S. The resistance was assumed
simulation are given, and the results of the application of to vary sinusoidally within ±4% of the nominal value,
2208 IEEE TRANSACTIONS ON INSTRUMENTATION AND MEASUREMENT, VOL. 65, NO. 10, OCTOBER 2016

currents are related to

Vs = A ∗ Vr + B ∗ Ir (21)
Is = C ∗ Vr + D ∗ Ir (22)

where A, B, C, D ∈ C are constants. For the eight


measurement sets in a given window, (21) was expanded into
two equations by taking the real and imaginary parts to give
16 real equations in total. The real and imaginary parts of A
and B were computed through unbiased linear LS estimation.
By assuming a pi circuit (Fig. 1) inside the two-port
network, the constants A, B, C, and D can be expressed in
Fig. 4. Graph shows the magnitude of the sending and receiving end currents terms of impedance Z and admittance Y
over the period of the simulation. Their difference is very small compared with
the absolute magnitudes. A = 1 + Y Z /2 (23)
B = Z (24)
which corresponds to a change in the line temperature of C = Y (1 + Y Z /4) (25)
approximately ±10 ◦C over the period of the simulation. D = 1 + Y Z /2. (26)
The network at either end of the line was modeled
by an equivalent voltage source; Fig. 3 shows the Z and Y are calculated from LS estimates of A and B using
root-mean-square (rms) magnitude of the sending and (23) and (24)
receiving end voltages. A variable load profile ranging from
Z = B (27)
15% to 100% of rated current was assumed to occur over a
7-h period; the rms values of current magnitude are shown Y = 2(A − 1)/B. (28)
in Fig. 4. Synchronized measurements of steady-state current
and voltage phasors at each line end were taken at the time C. Metrics for Evaluation of Method Performance
intervals of t = 2min for blocks of 10 s.
In order to reflect the measurement uncertainty that would Two metrics are used to evaluate the accuracy of the
be present in practice, the measurements were contaminated impedance and admittance parameter estimates over the
with Gaussian noise of mean zero and the standard deviations simulation period. The first is the rms error E P calculated
of 0.03% and 0.04% in magnitudes of voltage and current, over all parameter estimates; it indicates how far the estimates
respectively, and 0.3 mrad in all phase angles. are from the true values.
Systematic errors in both sending and receiving end voltages Let the errors in the individual parameter estimates be
and currents as modeled in Section II-B were applied to all Pi = Pi − P0 , where Pi refers to the parameter estimates
synchrophasor measurements. The mean of the synchrophasors Ri , X i , and Bi at each time instant ti , i = [1 . . . 196] and P0
was taken over each 10-s block to generate an individual to the nominal parameter values R0 , X 0 , and B0 . Then

set of measurements every 2 min; in total, there were 
1 1 
196
203 measurement sets. A moving window of N = 8 E P =  Pi2 . (29)
measurement points, spanning 16 min, was used to estimate P0 196
i=1
the impedance and admittance parameters of the line in real
time. Thus, 196 estimated values were computed for each of The second metric is P , the standard deviation of the
R, X, and B. parameter errors as a fraction of the nominal values. This
In order to test the effectiveness of the method, different sets metric indicates the variability of the parameter error over the
of systematic errors were applied to the measurements. In each simulation period. P is given by
case, the magnitude and phase errors were selected randomly 

1 1 
196
from a uniform distribution in the interval [−0.01, 0.01].
P =  (Pi − μP )2 (30)
In total, 100 000 cases were studied, giving sufficiently small P0 195
i=1
confidence intervals on the relevant metrics, which will be
defined in Section III-C. 196
where μP = 1/196 ∗ i=1 Pi is the mean parameter error.
E P and P are not defined for conductance G as its
B. Existing Linear Least Squares Method nominal value is zero.

The proposed method was applied to identify correction


constants a, φ, b, and θ to improve the accuracy of the D. Results
calculated Z and Y values. For comparison, an existing The results of the case study are presented in two parts: first,
linear LS method was also applied to each window to obtain one individual case with a specific set of systematic errors is
parameter estimates [15]. This method models the transmission considered; then the aggregated results from 100 000 cases of
line as a general two-port network, in which voltages and systematic errors are presented.
RITZMANN et al.: METHOD FOR ACCURATE TRANSMISSION LINE IMPEDANCE PARAMETER ESTIMATION 2209

TABLE I
S YSTEMATIC E RRORS IN THE S YNCHROPHASOR M EASUREMENTS

Fig. 7. Plot shows the nominal and estimated values of reactance X over
time for the individual simulation case.

Fig. 5. Plot shows the values of the identified correction constants over time
for the individual simulation case.

Fig. 8. Plot shows the nominal and estimated values of susceptance B over
time for the individual simulation case.

TABLE II
PARAMETER E RRORS FOR O NE I NDIVIDUAL C ASE

Fig. 6. Plot shows the nominal and estimated values of resistance R over
time for the individual simulation case.

1) Individual Case: Table I lists the values of one set


of systematic errors that was applied to the voltage and
current phasors, as well as the resulting TVEs. The plot in
Fig. 5 shows the values of the correction constants that were of the distributions of the rms and standard deviation of
identified using a moving window of N = 8 measurements parameter errors are listed to give an indication of the level
as described in Section II-C. It can be observed that of accuracy and consistency of the applied methods. For each
a ≈ −0.003 ≈ ar − as (from Table I), which is consistent percentile, the 95% confidence interval is given in brackets.
with the assumption that a corrects the net error. Similar For resistance R (Table III), the distributions of rms error
observations can be made for φ, b, and θ . Figs. 6–8 show occupy a similar range for both the proposed and existing
the final parameter estimates over the simulation period. methods, with the 95th percentile at 17%. However, the
In Table II, the rms and standard deviation of the parameter proposed method yields significantly lower standard deviations
errors are given. For R, X, and B, the rms error of the of error at ∼1%, whereas the existing method yields 2.9%.
proposed method is significantly smaller than for the existing Both methods produce lower errors in reactance X (Table IV),
estimator. Similarly, the standard deviation of the error is with rms errors of the order of 1% and standard deviation of
lower, indicating less variability in the parameter estimates. error of ∼0.1%. In contrast, for susceptance B (Table V), the
2) Large Number of Cases: Tables III–V summarize the level of error differs greatly between the methods. While the
results from the simulation of 100 000 different cases of proposed method gives the rms errors of 1%–2%, the existing
systematic error sets. The 50th, 75th, and 95th percentile method results in the rms errors of >100%. The standard
2210 IEEE TRANSACTIONS ON INSTRUMENTATION AND MEASUREMENT, VOL. 65, NO. 10, OCTOBER 2016

TABLE III pi line. The advantage of this approach over estimating the
E RRORS IN R ESISTANCE R FOR 100 000 C ASES pi line parameters directly is that it makes use of redundant
measurements such that constant systematic errors, as modeled
in this paper, either cancel or only cause a constant offset
in the estimated parameters. However, the linear LS method
also assumes constant parameters in time, and even small
variations over a moving window lead to variable parameter
errors. This robustness to systematic errors, yet weak accuracy
for variable parameters, explains the relatively similar results
in the accuracy of the resistance and reactance parameters in
the case study for both methods. Therefore, it may appear
that there is no significant advantage in the suggested method.
However, one of the crucial differences is that the proposed
method has demonstrated ∼50% less variability in the errors
of resistance values. The resistance is the parameter with
TABLE IV the highest temperature sensitivity; hence, it is desirable to
E RRORS IN R EACTANCE X FOR 100 000 C ASES monitor changes in its value. This can be done to good
accuracy even if there is a constant error in the estimated
values; however, the accuracy of the estimated changes
deteriorates quickly with increasing error variability.
In field applications, the true value of the impedance
and admittance parameters can never be known; thus, the
accuracy of estimated parameters has to be assessed on
their repeatability and consistency with expected physical
variations. Based on these criteria, the proposed method has
clear advantages over other estimation techniques.

B. Requirements of the Proposed Method


While the proposed method has strong potential to improve
TABLE V the accuracy of impedance parameter estimation, it also has
E RRORS IN S USCEPTANCE B FOR 100 000 C ASES some limitations. The method relies on increased residuals
that are caused by systematic measurement errors to identify
correction constants. In the case where the errors have the
same size at both line ends (as = ar , φs = φr , bs = br , and
θs = θr ), there would be no increase in residuals and, hence,
the method would not yield any improvement. However, in
these cases, the error in the estimated parameters is constant
and only of the order of the systematic errors; therefore, the
overall effect is small. Increased residuals only occur if there
is variation in the load of the transmission line, which is, thus,
a requirement for the method to identify correction constants.
The required level of load variation depends on the magnitude
of the systematic errors, as well as the random noise in the
synchrophasor measurements. Measurement noise is, in turn,
related to the overall load level, as the noise increases toward
deviation of errors is also an order of magnitude larger for the lower end of instrument scales. A conservative estimate of
the existing method. the minimum load variation would be 10% of maximum line
loading. Furthermore, the method assumes that over the time
window that spans the utilized measurements the parameters
IV. D ISCUSSION
are either constant or varying linearly. This implies that the
A. Comparison of Methods minimum load variation has to occur within this time, which
Based on the results presented in Section III-D, the proposed is limited by the thermal time constant. Depending on the
method demonstrated equal or better performance compared load profile of the transmission line, not all time windows
with the existing linear LS-based method. may satisfy these requirements; one possibility of overcoming
The linear LS method finds an optimal estimate for the this issue is to reuse correction constants from previous
parameters of a two-port network; these are then used time windows with higher load variation. To summarize,
to calculate impedance and admittance parameters of the the applicability and effectiveness of the proposed method
RITZMANN et al.: METHOD FOR ACCURATE TRANSMISSION LINE IMPEDANCE PARAMETER ESTIMATION 2211

depends on the specific circumstances of the transmission The N-dimensional model R, based on the theoretical model
line operation and measurement instruments, as well as the f R (ti ) = q R ti + r R , is given by the matrix equation
accuracy requirement for the estimated parameter values.
Further work is needed to better understand and predict the R = HZ QR + ε (31)
relationship between these factors. where ε = [ε1 , . . . , ε N ]T are error terms. To satisfy the LS
N
criterion, min i=1 εi2 , QR is computed using
C. Limiting Assumptions
In presenting the new method in this paper, some QR = (HZT HZ )−1 HZT R. (32)
assumptions have been made. First, the method has been In the same manner, q X and r X are calculated
defined on a single-phase transmission line model. Most
T
using vectors X ∈ RN , X = X1 . . . X N ,
transmission lines in power networks have three phases, which
T
couple and, thus, require more complex models. In the case and QX ∈ R2 , QX = q X r X .
of identical conductors and symmetric geometry, the method To estimate qG from G i , i = [1, . . . , N], vectors G, HY ∈
may be applied to the positive sequence components, provided R N , and QG ∈ R are defined, where
that the behavior of the systematic error can be modeled as
T
T

G = G 1 . . . G N , HY = 1 . . . 1 , QG = r G .
a proportional error in amplitude and additive in phase angle.
Further research is required to confirm whether the method can The N-dimensional model G, based on the theoretical model
be effective for various three-phase transmission line systems. f G (ti ) = r G , is given by
The systematic errors were assumed to be constant, directly
proportional in magnitude and additive in the phase angle. The G = HY QG + ε (33)
systematic errors may follow different, nonlinear models. Over where ε = [ε1 , . . . , ε N ]T are error terms. To satisfy the LS
small ranges, these variations may still be approximated well N
criterion, min i=1 εi2 , QG is computed by
by the error model in this paper. More work is required to
investigate if and how the method can be adapted to identify QG = (HY
T
HY )−1 HY
T
G. (34)
correction constants for other models and if it can be used to
select the most appropriate error model. In the same

manner,
vector B ∈
T r B is calculated using
R N , B = B1 . . . B N and QB ∈ R, QB = r B .
V. C ONCLUSION
The contribution of this paper is in the field of accurate, A PPENDIX B
real-time synchrophasor-based transmission line impedance PARTIAL D ERIVATIVES OF Z AND Y
parameter estimation. Let Vs , Is , Vr , Ir ∈ C,  = C4 \ {Vs Ir + Vr Is = 0} , and
A method was proposed for estimating the impedance = C4 \{Vs + Vr = 0}. Define complex functions Z :  → C
parameters of medium-length transmission lines in the and Y : → C, where
presence of systematic errors in the utilized synchrophasor
measurements of voltage and current. The method assumes Z = (Vs2 − Vr2 )/(Vs Ir + Vr Is ) (35)
constant or linearly changing parameters over short periods of Y = 2(Is − Ir )(Vs + Vr ). (36)
time and identifies correction constants through optimization.
The effectiveness of the proposed method was compared Rewrite Z as Z = h 1 / h 2 and Y as Y = h 3 / h 4 , where
with that of an existing linear LS method in a case study of h 1 : C2 → C, h 2 :  → C, h 3 : C2 → C, h 4 : C2 \
a simulated transmission line. The results are promising and {Vs + Vr = 0} → C,
suggest that the method has significant potential to improve
h 1 = Vs2 − Vr2 , h 2 = Vs Ir + Vr Is (37)
parameter estimation accuracy in practical field applications.
Limits of the method and future work have been discussed. h 3 = 2(Is − Ir ), h 4 = Vs + Vr . (38)
Accurate, real-time synchrophasor-based transmission line Since h 1 , h 2 , h 3 , and h 4 are complex polynomials, Z and Y
impedance parameter estimation is a powerful factor in are rational functions. By the differentiability of complex
improving the performance of power system monitoring, polynomials and the quotient rule, Z and Y are differentiable
protection, and control applications, and, thus, in creating more at all points in  and , respectively. The partial derivatives
reliable and resilient electricity networks. of Z with respect to Vs and Vr are
A PPENDIX A ∂Z 2Vs (Vs2 − Vr2 )Ir
E STIMATION OF C ONSTANTS IN ∂ Vs = −
Vs Ir + Vr Is (Vs Ir + Vr Is )2
L INEAR PARAMETER F UNCTIONS (39)
∂Z −2Vr (Vs2 − Vr2 )Is
To estimate q R and r R from Ri , i = [1, . . . , N], vectors ∂ Vr = − .
R ∈ R N and QR ∈ R2 , and matrix HZ ∈ R N×2 are defined, Vs Ir + Vr Is (Vs Ir + Vr Is )2
where The partial derivatives of Y with respect to Is and Ir are
T

T q t . . . tN ∂Y 2 ∂Y 2
R = R1 . . . R N , Q R = R , H Z = 1 . = , =− . (40)
rR 1 1 1 ∂ Is Vs + Vr ∂ Ir Vs + Vr
2212 IEEE TRANSACTIONS ON INSTRUMENTATION AND MEASUREMENT, VOL. 65, NO. 10, OCTOBER 2016

A PPENDIX C [6] J. De La Ree, V. Centeno, J. S. Thorp, and A. G. Phadke, “Synchronized


A PPROXIMATION : E RRORS AT O NE L INE E ND phasor measurement applications in power systems,” IEEE Trans. Smart
Grid, vol. 1, no. 1, pp. 20–27, Jun. 2010.
To a first-order linear approximation, the change in Z caused [7] L. Philippot and J. C. Maun, “An application of synchronous phasor
measurement to the estimation of the parameters of an overhead
by the changes in Vs and Vr is given by transmission line,” in Proc. Conf. Fault Disturbance Anal. Precise Meas.
∂Z ∂Z Power Syst., Arlington, VA, USA, Nov. 1995, pp. 1–5.
δZ = δVs + δVr [8] R. E. Wilson, G. A. Zevenbergen, D. L. Mah, and A. J. Murphy,
∂ Vs ∂ Vr “Calculation of transmission line parameters from synchronized
2(Vs δVs − Vr δVr ) (Vs2 − Vr2 )(Ir δVs + Is δVr ) measurements,” Electr. Mach. Power Syst., vol. 27, no. 12,
= − pp. 1269–1278, Nov. 1999.
Vs Ir + Vr Is (Vs Ir + Vr Is )2 [9] I.-D. Kim and R. K. Aggarwal, “A study on the on-line measurement
(41) of transmission line impedances for improved relaying protection,” Int.
J. Elect. Power Energy Syst., vol. 28, no. 6, pp. 359–366, Jul. 2006.
where the results from Appendix B have been used. [10] R. Mai, L. Fu, and X. HaiBo, “Dynamic line rating estimator with
Let the relative change in Z be synchronized phasor measurement,” in Proc. Int. Conf. Adv. Power Syst.
Autom. Protection, Oct. 2011, pp. 940–945.
δZ 2(Vs δVs − Vr δVr ) Ir δVs + Is δVr [11] M. Bočkarjova and G. Andersson, “Transmission line conductor
Z = = − . (42) temperature impact on state estimation accuracy,” in Proc. IEEE
Z Vs2 − Vr2 Vs Ir + Vr Is Lausanne PowerTech, Jul. 2007, pp. 701–706.
[12] IEEE Standard for Synchrophasor Measurements for Power Systems,
Suppose that errors are modeled at both line ends by IEEE Standard C37.118.1-2011, 2011.
δVs = (as + j φs )Ṽs and δVr = (ar + j φr )V˜r . Then, the relative [13] Arbiter Systems, Inc., “Model 1133a power sentinel,” Arbiter Syst., Paso
Robles, CA, USA, 2009.
change around Ṽs and Ṽr is [14] IEEE Guide for Synchronization, Calibration, Testing, and Installation
2 2 of Phasor Measurement Units (PMUs) for Power System Protection and
2((as + j φs )Ṽs − (ar + j φr )Ṽr ) Control, IEEE Standard C37.242-2013, 2013.
Z exact = 2 2
(43) [15] D. Shi, D. J. Tylavsky, N. Logic, and K. M. Koellner, “Identification of
Ṽs − Ṽr short transmission-line parameters from synchrophasor measurements,”
in Proc. 40th North Amer. Power Symp., Sep. 2008, pp. 1–8.
where only the first, dominant term is considered. Now, [16] D. Shi, D. J. Tylavsky, K. M. Koellner, N. Logic, and D. E. Wheeler,
suppose that all errors are modeled to be in Ṽr , such that “Transmission line parameter identification using PMU measurements,”
δVs = 0 and δVr = (a + j φ)Ṽr , where a = ar − as and Eur. Trans. Elect. Power, vol. 21, no. 4, pp. 1574–1588, 2011.
[17] C. S. Indulkar and K. Ramalingam, “Estimation of transmission line
φ = φr − φs . Then, the relative error becomes parameters from measurements,” Int. J. Elect. Power Energy Syst.,
2 vol. 30, no. 5, pp. 337–342, Jun. 2008.
−2(ar − as + j φr − j φs )Ṽr [18] Y. Liao and M. Kezunovic, “Online optimal transmission line parameter
Z app = 2 2
. (44) estimation for relaying applications,” IEEE Trans. Power Del., vol. 24,
Ṽs − Ṽr no. 1, pp. 96–102, Jan. 2009.
[19] C. Borda, A. Olarte, and H. Diaz, “PMU-based line and transformer
The difference between the exact and approximate relative parameter estimation,” in Proc. IEEE/PES Power Syst. Conf. Expo.,
errors is Mar. 2009, pp. 1–8.
[20] K. Dasgupta and S. A. Soman, “Line parameter estimation using phasor
2 2
2(as + j φs )(Ṽs − V˜r ) measurements by the total least squares approach,” in Proc. IEEE Power
Z exact − Z app = 2 2
= 2(as + j φs ). Energy Soc. General Meeting, Jul. 2013, pp. 1–5.
Ṽs − Ṽr [21] A. M. Dán and D. Raisz, “Estimation of transmission line parameters
(45) using wide-area measurement method,” in Proc. IEEE Trondheim
Hence, by modeling all errors to be in V˜r , an approximation PowerTech, Jun. 2011, pp. 1–6.
[22] D. Ritzmann, W. Holderbaum, B. Potter, and P. S. Wright, “Improving
of 2(as + j φs ) is made in the relative error of the impedance, the accuracy of synchrophasor-based overhead line impedance
which is constant and of a lower order than the overall error measurement,” in Proc. IEEE Int. Workshop Appl. Meas. Power Syst.,
Z exact . Using an equivalent expression for Y , a similar Sep. 2015, pp. 132–137.
[23] IEEE Standard Requirements for Instrument Transformers,
argument can be produced for modeling all the errors in IEEE Standard C57.13-2008, 2008.
current I˜r . [24] IEEE Standard for Calculating the Current-Temperature Relationship of
Bare Overhead Conductors, IEEE Standard 738-2012, 2013.
[25] R. H. Byrd, M. E. Hribar, and J. Nocedal, “An interior point algorithm
R EFERENCES for large-scale nonlinear programming,” SIAM J. Optim., vol. 9, no. 4,
pp. 877–900, Jan. 1999.
[1] G. Sivanagaraju, S. Chakrabarti, and S. C. Srivastava, “Uncertainty in [26] National Grid plc, Electricity Ten Year Statement 2014, UK Electricity
transmission line parameters: Estimation and impact on line current Transmission, Appendix B—System Data, Nat. Grid, Warwick, U.K.,
differential protection,” IEEE Trans. Instrum. Meas., vol. 63, no. 6, 2014.
pp. 1496–1504, Jun. 2014.
[2] J.-A. Jiang, J.-Z. Yang, Y.-H. Lin, C.-W. Liu, and J.-C. Ma, “An adaptive
PMU based fault detection/location technique for transmission lines
part I: Theory and algorithms,” IEEE Trans. Power Del., vol. 15, no. 2,
pp. 486–493, Apr. 2000.
[3] J. Zaborszky and J. W. Rittenhouse, Electric Power Transmission:
The Power System in the Steady State. New York, NY, USA: Ronald,
1954.
[4] H. W. Dommel, “Overhead line parameters from handbook formulas Deborah Ritzmann (S’15) was born in Germany. She received the
and computer programs,” IEEE Trans. Power App. Syst., vol. PAS-104, B.Sc. degree in mathematics and physics from University College London,
no. 2, pp. 366–372, Feb. 1985. London, U.K., in 2012. She is currently pursuing the Ph.D. degree with
[5] R. Schulze, P. Schegner, and R. Živanović, “Parameter identification the University of Reading, Reading, U.K., in collaboration with the National
of unsymmetrical transmission lines using fault records obtained Physical Laboratory, Teddington, U.K.
from protective relays,” IEEE Trans. Power Del., vol. 26, no. 2, Her current research interests include synchrophasor-based overhead line
pp. 1265–1272, Apr. 2011. impedance measurement for dynamic line rating applications.
RITZMANN et al.: METHOD FOR ACCURATE TRANSMISSION LINE IMPEDANCE PARAMETER ESTIMATION 2213

Paul S. Wright received the B.Sc. and Ph.D. degrees in electrical and Ben Potter (S’97–M’01) received the M.Eng. degree in engineering science
electronic engineering from the University of Surrey, Surrey, U.K., in 1987 from the University of Oxford, Oxford, U.K., in 2001, and the Ph.D. degree
and 2002, respectively. in modeling of induction machines from the University of Reading, Reading,
He spent three years as a Research Fellow with the University of Surrey, U.K., in 2005.
where he was involved in the field of spacecraft sensors and attitude control. He subsequently managed research and development activity for several
This was followed by three years with the Central Electricity Research years with Moog Components Group Ltd., Reading, including development
Laboratory, where he was involved in advanced control systems. In 1992, work on wireless power transfer. He joined the University of Reading in 2009,
he joined the National Physical Laboratory, Teddington, U.K., where he where he is currently an Associate Professor of Energy Systems Engineering.
is currently a Principle Research Scientist specializing in ac measurements His academic research has been focused on energy systems and power
and waveform analysis. His current research interests include ac power electronics of various flavors for over 12 years with applications, including
standards, ac/dc transfer measurements, digital sampling systems, and the energy storage, electric machines, wind turbines, and wireless power transfer.
analysis of non-sinusoidal/non-stationary waveforms applied to power quality In 2010, he founded the Energy Research Laboratory within the School of
measurements and smart grid development. Systems Engineering, University of Reading.
Dr. Wright is a Chartered Engineer and a member of the Institution of
Engineering and Technology.

William Holderbaum (M’01) received the Ph.D. degree in automatic control


from the University of Lille, Lille, France, in 1999.
He was a Research Assistant with the University of Glasgow, Glasgow,
U.K., from 1999 to 2001. He is currently a Professor with the School
of Systems Engineering, University of Reading, Reading, U.K. His current
research interests include control theory and its applications.

You might also like