You are on page 1of 19

ASHIDA Numerical 3OC + 1EF Protection Relay Type: ADR241B

(ADITYA–V2 S eries)

Protection Features : Relay Design Features :


9 4 Element (3 Phase + EF + Sensitive EF) 9 Large 20x4 LCD display for Parameter and
Over current IDMT/DMT with instant trip. setting display.
9 Programmable (Non- Volatile) Setting by 9 Disturbance Recorder. Up to 3 sec of actual
local keys as well as remote setting by waveform of current along with logical and
communication port. physical status, are captured & saved in the
9 Selection of Curve: Five selectable curve built-in memory with Date Time stamping,
(Normal Inverse 1 (C1), Normal Inverse 2 for analyzing fault condition & fault location.
(C2), Very Inverse (C3), Extremely Inverse 9 Fully communicable with IEC standard open
(C4), Long Time Inverse (C5)) and Define protocol. IEC60870-5-103,MODBUS & IEC
Time (C6). 61850.
9 Instantaneous Over-Current Protection with 9 Separate Communication Port for SCADA
adjustable Timer. (RS485) as well as Local Testing (RS232C)
9 Breaker Failure Detection. 9 Very low burden on CT (less than 0.5VA).
9 In-built CB Trip Circuit Supervision function 9 2 Setting Groups.
during pre closing and post closing of CB. 9 Continuous monitoring of module’s internal
9 Negative Sequence Over Current (46). hardware and alarm generation in case of
9 Breaker TRIP/CLOSE operation directly failure of any critical components.
from relay keypad. 9 Facility to synchronised Relay time from
SCADA.

Note: Due to our policy to upgrade our products constantly, we reserve the right to
supply products which may vary slightly from that indicated above.

ASHIDA ELECTRONICS PVT LTD.


ASHIDA HOUSE, Plot No. A-308, Road No. 21,
Ref.:ADR241B_V2
Wagle Industrial Estate,Thane (W)-400 604. INDIA. Issue: 06 15.11.2013
E-mail: sales@ashidaelectronics.com
आिशदा Web: www.ashidaelectronics.com
Page 1 / 15
ASHIDA Numerical 3OC + 1EF Protection Relay Type: ADR241B
(ADITYA–V2 S eries)

9 11 Digital Output contacts for local alarm as protection function such as IDMT Over current
well as tele-signalling protection, Instantaneous Over current
9 10 Optically isolated digital status input for protection, E/F protection etc. These measured
monitoring of status to avoid use of external values are also displayed on large 20 x 4 LCD
relay logic. display for metering purpose. The DSC also
9 5000 nos of event memory, event such CB monitors different digital input through optical
close, Trip, digital status change, relay pkp isolator and perform some monitoring function
etc. All events are with date and time such trip circuit supervision, and control
stamped up to 1ms. potential free contact for control CB and
9 10 nos of Fault data stored with keypad generate ALARM and Tele-signalling.
interface and time stamping. The power supply module is basically DC – DC
converted designed using modern PWM based
Description :
Switching mode technique to convert 110Vdc
ADR241B is second generation of Numerical
station battery supply to the 12V and 24Vdc low
Over Current IDMT/DMT Relay. It consist all the
voltage supply for relay electronics and control
necessary protection and monitoring functions
circuit. It also provides necessary isolation from
required for Normal feeder, it consist of
station battery. There are two types of power
1. High Speed Digital DSP Controller
supply modules available 1) having range of
2. Analog Measuring Module
77Vdc – 250Vdc. Covering requirement of
3. Power supply Module
110Vdc and 220Vdc station battery system 2)
4. Digital Input output module.
Wide range setting 18Vdc – 250Vdc.
The High speed Digital Signal Controller
The relay is having total 8 nos of dual LED of
continuously monitors line phase current and
high intensity for easy identification of type of
E/F current. Along with different status input,
fault for easy user interface. LEDs L2 to L8 and
through CTs, and optical isolated status
Relay R1 to RB, digital status inputs and
connections. The high-speed micro-controller
controlled outputs are fully programmable via
samples these current signals through a A/D
key pad interface.
converter. The Digital Signal performs powerful
Numerical Algorithms to find out RMS of
Main Functions :
fundamental & harmonic contents of the current.
The ADR241B are having following protection
All measurement is tuned to fundamental
functions.
frequency i.e 50Hz or 60Hz depending upon
1. 4 stages of Phase Over Current element.
setting, thus relay remain stable during distorted
(Ip1>, Ip2>, Ip>> and Ip>>>).
waveform by various industrial load. All these 2. 3 stages of 3Io (Internally derived EF)
measure values are then used for different (3Io>, 3Io>> and 3Io>>>).

Note: Due to our policy to upgrade our products constantly, we reserve the right to
supply products which may vary slightly from that indicated above.

ASHIDA ELECTRONICS PVT LTD.


ASHIDA HOUSE, Plot No. A-308, Road No. 21,
Ref.:ADR241B_V2
Wagle Industrial Estate,Thane (W)-400 604. INDIA. Issue: 06 15.11.2013
E-mail: sales@ashidaelectronics.com
आिशदा Web: www.ashidaelectronics.com
Page 2 / 15
ASHIDA Numerical 3OC + 1EF Protection Relay Type: ADR241B
(ADITYA–V2 S eries)

3. 3 stages of Ie (Externally EF or REF) (Ie>, Earth Fault Element :


Ie>> and Ie>>>). The Relay has two different type of Earth Fault
4. Trip Circuit Supervision. one is marked as 3Io and another is marked as
5. Breaker Failure Detection. Ie. The 3Io is derived internally by software
6. Monitoring Functions. through phase current while Ie is measured from
7. Auto Recloser Relay (ARR). external CT. Thus Ie can be used as Core
8. Negative Phase Sequence. Balance CT (CBCT) or Restricted EF (REF)
9. Relay / Led configuration. each EF is having 3 stages (>, >>, & >>>).
Each of these functions are independently Stage 1 (>) stage 2 (>>) can be programmed as
programmable and can be enabled or disabled IDMT or definite time. All major international
by user depending upon the requirement. IDMT curves are available. Stage 3 (>>>) can
be programmed instantaneous or define time.
Over Current Element :
Range of stage 1 and stage 2 for 3Io is 10% to
The ADR241B is member of Ashida Numerical
100%, and for stage 3 of 3Io is 50% to 1200%.
Relay family design for protection general
The Range for EF is from 5% to 80% for stage 1
feeder. The relay has four independent stages
and stage 2 and 50% to 1200% for stage 3. The
of Over Current (Ip1>, Ip2>, Ip>> & Ip>>>).
output of stage 1 (Ie> or 3Io>), stage 2 (Ie>> or
Stage 1 (>) Stage 2 (>>) can be programmed as
3Io>>) and stage 3 (Ie>>> or 3Io>>>) can be
IDMT or definite time. All major international
assigned to any of 11 programmable relay
IDMT curves are available. Stage 3 (>>>) can
through key board. Thus I> can be used as
be programmed instantaneous or define time.
ALARM before TRIP or can be used to TRIP
Range of for stage 1 and 2 is 10% to 250% for
another CB before Tripping main CB.
Phase. The output of stage 1 (Ip1>, Ip2>), stage
2(Ip>>) and stage 3(Ip>>>) can be assigned to Inverse Time Curves :
any of 11 programmable relay through key The each stage thresholds for phase (earth)
board. Thus Ip1>, Ip2> can be used as ALARM over current can be selected with an Inverse
before TRIP or can be used to TRIP another CB Definite Minimum Time (IDMT) characteristic.
before tripping main CB. The Time Delay is calculated with a
Although the curves tend towards infinite when mathematical formula
the current approaches Is (general threshold),
the minimum guaranteed value of the operating
K * a
current for all the curves with the inverse time t= b
I
characteristic is 1.1Is (with a tolerance of ± 1
I r ef
0.05Is).

Note: Due to our policy to upgrade our products constantly, we reserve the right to
supply products which may vary slightly from that indicated above.

ASHIDA ELECTRONICS PVT LTD.


ASHIDA HOUSE, Plot No. A-308, Road No. 21,
Ref.:ADR241B_V2
Wagle Industrial Estate,Thane (W)-400 604. INDIA. Issue: 06 15.11.2013
E-mail: sales@ashidaelectronics.com
आिशदा Web: www.ashidaelectronics.com
Page 3 / 15
ASHIDA Numerical 3OC + 1EF Protection Relay Type: ADR241B
(ADITYA–V2 S eries)

Curve Description a B 9 When DC supply is not sufficient (DC Fail).


Type 9 When T1 and T2 both active and both
C1 Standard Inverse_1 0.14 0.02 inactive. i.e CB NO as will as CB NC are
C2 Standard Inverse_2 0.06 0.02
both close or open. Relay detects any
C3 Very Inverse 13.5 1
internal hard ware Error.
C4 Extremely inverse 80 2
C5 Long Time Inverse 120 1 Auto Recloser Logic:
C6 Define Time - -
The ADR241B is provided with 4 Shot Auto

The separate output contact allows to use each Recloser function. There are 5 timer for auto

stage for independent function such as stage 1 recloser 1) Dead Time for shot 1 (DT1) 2) Dead

can be used for ALARM stage 2 for tripping or Time for shot 2 (DT2) 3) Dead Time for shot 3

both can be use for tripping independent CB. (DT3) 4) Dead Time for shot 4 (DT4) and 5)

Each stage can enable or disable depend upon Reclaim Time (RT). After clearing of fault

application. ADR241B trigger dead Time 1 i.e DT1. After the


time delay Relay provides reclose command
Trip Circuit Supervision : and start reclaim timer RT. If Second fault occur
The ADR241B is having 2 separate digital opto- during RT relay trigger Dead Time 2 i.e DT2. If
coupler status input which can be used to Third fault occur during RT relay trigger Dead
continuously monitor the continuity of trip-circuit. Time 3 i.e DT3, If Fourth fault occur during RT
The general scheme is as shown in fig.4 relay trigger Dead Time 4 i.e DT4 and after Time
Relay monitors Trip coil continuity through CB Delay it again provide reclose command and
NO during close condition and through CB NC retrigger RT. If Fifth fault occur during RT, Relay
during Trip condition. If any discontinuity is generates Lock-Out alarm and block further
observed it generate ALARM signal. reclose. The Lock-Out condition can be reset
The output marked as PROTH (Protection locally as well remotely by SCADA through
Healthy) is normally is ON and become OFF at communication digital status input.
following condition.
Breaker Failure Detection :
Normally after tripping, current should become
B+ TCCOM
1
Zero within 100 – 1000ms in steps of 50ms time
6 To Relay CPU
2

T1
depending upon type of fault and breaker
CB NO

B-
mechanism. After Fault ADR241B trigger
1

T2 2
6 To Relay CPU internal timer (settable from 0.1s to 1.0s) if fault
TC
CB NC is not cleared during this time then Relay
Fig.4 Trip Circuit Logic declares as Breaker Fail (LBB function) and
change another contacts. This contact is marked

Note: Due to our policy to upgrade our products constantly, we reserve the right to
supply products which may vary slightly from that indicated above.

ASHIDA ELECTRONICS PVT LTD.


ASHIDA HOUSE, Plot No. A-308, Road No. 21,
Ref.:ADR241B_V2
Wagle Industrial Estate,Thane (W)-400 604. INDIA. Issue: 06 15.11.2013
E-mail: sales@ashidaelectronics.com
आिशदा Web: www.ashidaelectronics.com
Page 4 / 15
ASHIDA Numerical 3OC + 1EF Protection Relay Type: ADR241B
(ADITYA–V2 S eries)

as Breaker Fail can be used to TRIP back up and MODBUS command and respond in
breaker or can be used to generate ALARM respective language. There is no any specific
signal. setting which define protocol. (Please note
MODBUS by design do not support event
Negative sequence over current (46)
functionality)
The ADR241B relay will be provided with Apart from basic protection functions. Relay
programmable function to detect Unbalanced
continuously monitors all substations operation
Fault conditions. When Earth Fault elements do
through status, it internal functions, internal
not operated or not sufficiently sensitive. The
ADR241B relay is included with Negative Phase hardware etc. if any change is observed it is
Sequence Over Current element it can be marked as event. These events are stored in
programmed as IDMT or Definite Time. internal non-volatile memory along with time

Programmable DI/DO and LED:- stamped. Following are some of the events
recorded, Relay PKP, Relay Reset, CB Trip, CB
The ADR241B Relay is provided with 11 digital
Close, Change of any digital status input, Relay
outputs, 10 opto-isolated inputs and 7 general
purpose LEDs. These can be programmed by setting changed etc. Up to 5000 such events

local key board. Any logical of physical status can can be stored and can be download for detailed
be assigned to any relay contact The logic of analysis. Apart from Event record Relay also
digital status input as well as logical status can record actual waveform of current along with all
be formed and assigned to any of the relay digital and logical status during fault condition.
output. The disturbance record can be trigger Up to 10 such waveforms can be recorded; the
from external logical input. duration of disturbance record is 3sec. The
Setting Group: disturbance record can be trigger from

The ADR241B Relay is provided with two setting physical status input as well as from pick,
groups i.e. G1 and G2. Any One group is active trip operation of relay. This waveform can be
at a time. The setting group can be changed from downloaded through communication port for
digital input, this allow user to change relay further analysis.
setting dynamically as per the outgoing CB load
condition. Relay Talk Software:

The general communication software is provided


Monitoring Functions (Event, Disturbance
to communicate with relay, known as Relay
Record):-
Talk. By using this software data such as event
Relay support IEC60870-5-103 / IEC61850 and
log, disturbance records etc can be down loaded
modbus protocol. The In communicable version for further analysis. The disturbance record data
IEC61850 is optional and need to specify while can be saved in standard COMTRADE Format
ordering while IEC60870-5-103 and MODBUS is which is understandable by numbers of relay
default. The relay auto detect IEC-60870-5-103 testing units for play back.

Note: Due to our policy to upgrade our products constantly, we reserve the right to
supply products which may vary slightly from that indicated above.

ASHIDA ELECTRONICS PVT LTD.


ASHIDA HOUSE, Plot No. A-308, Road No. 21,
Ref.:ADR241B_V2
Wagle Industrial Estate,Thane (W)-400 604. INDIA. Issue: 06 15.11.2013
E-mail: sales@ashidaelectronics.com
आिशदा Web: www.ashidaelectronics.com
Page 5 / 15
ASHIDA Numerical 3OC + 1EF Protection Relay Type: ADR241B
(ADITYA–V2 S eries)

Following as some of software clips


All The data can view at time

Event list with real time

The waveform and logical and physical status latched by relay can be view and analysed

Note: Due to our policy to upgrade our products constantly, we reserve the right to
supply products which may vary slightly from that indicated above.

ASHIDA ELECTRONICS PVT LTD.


ASHIDA HOUSE, Plot No. A-308, Road No. 21,
Ref.:ADR241B_V2
Wagle Industrial Estate,Thane (W)-400 604. INDIA. Issue: 06 15.11.2013
E-mail: sales@ashidaelectronics.com
आिशदा Web: www.ashidaelectronics.com
Page 6 / 15
ASHIDA Numerical 3OC + 1EF Protection Relay Type: ADR241B
(ADITYA–V2 S eries)

Data can be viewed as raw sine wave

or RMS value

Note: Due to our policy to upgrade our products constantly, we reserve the right to
supply products which may vary slightly from that indicated above.

ASHIDA ELECTRONICS PVT LTD.


ASHIDA HOUSE, Plot No. A-308, Road No. 21,
Ref.:ADR241B_V2
Wagle Industrial Estate,Thane (W)-400 604. INDIA. Issue: 06 15.11.2013
E-mail: sales@ashidaelectronics.com
आिशदा Web: www.ashidaelectronics.com
Page 7 / 15
ASHIDA Numerical 3OC + 1EF Protection Relay Type: ADR241B
(ADITYA–V2 S eries)

While Ordering Specify the following Information for ADR241B Relay

Definition of Model No of Aditya Series of Relays


AM XXX–XX –XX –XX –XX – XX–XX

Communication protocol
02= IEC 103 +MODBUS
Sub Type
330 = NUMERICAL OVER
CURRENT PROTECTION PT Secondary
RELAY 00= Not applicable
CT Secondary
03 = 1 Amp. / 5 Amp. Selectable

C a b i n e t Size Auxiliary Supply


05=CSD-H (282 X 138MM) 08 = 18 – 250 V dc

C a b i n e t Type
01 = Non-drawout

Ordering information:

A D R 2 4 1 B - A M 3 3 0 - 0 5 - 0 1 - 0 8 - 0 3 - 0 0 - 0 2

ADR245B – AM330–05–01–08–03–00–02
T y p e : A D R 2 4 5 B w i t h I E C 1 0 3 C o m m u n i c a t i o n P r o to c o l
Cabinet Size: CSD-H (282 X 138MM)
Cab ine t Typ e : Non- dr awou t
Auxiliary Supply: 18-250Vdc
C T s e c :1Amp. / 5Amp. Selectable

Note: Due to our policy to upgrade our products constantly, we reserve the right to
supply products which may vary slightly from that indicated above.

ASHIDA ELECTRONICS PVT LTD.


ASHIDA HOUSE, Plot No. A-308, Road No. 21,
Ref.:ADR241B_V2
Wagle Industrial Estate,Thane (W)-400 604. INDIA. Issue: 06 15.11.2013
E-mail: sales@ashidaelectronics.com
आिशदा Web: www.ashidaelectronics.com
Page 8 / 15
ASHIDA Numerical 3OC + 1EF Protection Relay Type: ADR241B
(ADITYA–V2 S eries)

Technical Specifications:

General specifications
Sr. No. Specification Particulars
I. Current Input : Suitable for CT secondary 5 Amp. or 1 Amp site selectable
II. Aux. Supply : 77 – 250VDC. Or 18 – 250VDC to be specified.
III. VA burden on CT : Less than 0.2VA
IV. VA burden on Aux. : Less than 10 Watts
V. Operating Temp. range : -10 deg. To + 65 deg.
VI. Continuous Current : 2 x of rated CT
carrying capacity
VII. Pick up : Within 1.1 times of set value
VIII. Reset Value : 95% to 90% of pick up.
IX. Output Contact : 11 for General Programmable
X. Contact Rating : Continuous: 5A
: Make & carry for 0.5 sec : 30A
: Make carry for 3 sec : 15A
XI. Opto Isolated input : 1 for CB NO
: 1 for CB NC
: 10 as general programmable
XII. Thermal With stand for : 20 x of rated for 3.0 sec.
CT
XIII. Setting Group : Two (G1 and G2)
XIV. Numbers of Event :5000

General Settings
XV. : Unit ID 1 – 250 in steps of 1
: Baud Rate 1200 – 57600
: Com Port RS232 / RS485
: Set Parity None / Even / Odd
: Freq Selection 50Hz / 60Hz
: Group Selection G1 / G2
: BF Enable INT / EXT / BYP
: Extbf_I 10 – 80%
: BF Delay 100 – 1000msec in steps of 50msec

Note: Due to our policy to upgrade our products constantly, we reserve the right to
supply products which may vary slightly from that indicated above.

ASHIDA ELECTRONICS PVT LTD.


ASHIDA HOUSE, Plot No. A-308, Road No. 21,
Ref.:ADR241B_V2
Wagle Industrial Estate,Thane (W)-400 604. INDIA. Issue: 06 15.11.2013
E-mail: sales@ashidaelectronics.com
आिशदा Web: www.ashidaelectronics.com
Page 9 / 15
ASHIDA Numerical 3OC + 1EF Protection Relay Type: ADR241B
(ADITYA–V2 S eries)

: OC CT Sec 1A / 5A
: CT Primary 10 – 2000 in steps of 1
: EF CT Sec 1A / 5A
: EF CT Primary 10 – 2000 in steps of 1
: Local Control YES / NO
: Trip Ckt Test YES / NO
: Post Trigger 10 – 90%

Phase Section (Ip)


XVI. Phase (OC – G1 ) : IP1> Enable YES / NO
: IP1> Settings 10% – 250% in steps of 1%.
: IP1> Time Multiplier x0.02 – x1.00 in steps of 0.01
(TMS)
: IP1> Curve C1 – C6
(Operating Time) ( IDMT curve C1 – C5 or Define Time C6)
: IP1> C6 Delay 0 – 1899.9 Sec in steps of 0.1Sec.
: IP2> Enable YES / NO
: IP2> Settings 10% – 250% in steps of 1%
: IP2> Time Multiplier x0.02 – x1.00 in step of 0.01
(TMS)
: IP2> Curve C1 – C6
(Operating Time) ( IDMT curve C1 – C5 or Define Time C6)
: IP2> C6 Delay 0 – 1899.9 Sec in steps of 0.1Sec.
: IP>> Enable YES / NO
: IP>> Settings 10% – 250% in steps of 1%
: IP>> Time Multiplier x0.02 – x1.00 in step of 0.01
(TMS)
: IP>> Curve C1 – C6
(Operating Time) ( IDMT curve C1 – C5 or Define Time C6)
: IP>> C6 Delay 0 – 99.9 Sec in steps of 0.1Sec.
: IP>>> Enable YES / NO
: IP>>> Settings 50% – 3000% in steps of 10%
: IP>>> C6 Delay 0 – 90.00 Sec in steps of 0.01Sec.

Note: Due to our policy to upgrade our products constantly, we reserve the right to
supply products which may vary slightly from that indicated above.

ASHIDA ELECTRONICS PVT LTD.


ASHIDA HOUSE, Plot No. A-308, Road No. 21,
Ref.:ADR241B_V2
Wagle Industrial Estate,Thane (W)-400 604. INDIA. Issue: 06 15.11.2013
E-mail: sales@ashidaelectronics.com
आिशदा Web: www.ashidaelectronics.com
Page 10 / 15
ASHIDA Numerical 3OC + 1EF Protection Relay Type: ADR241B
(ADITYA–V2 S eries)

External Earth Fault Section (Ie)


XVII. EF – G1 : IE> Enable YES / NO
: IE> Settings 5% – 80% in steps of 1%
: IE> Time Multiplier x0.02 – x1.00 in step of 0.01.
(TMS)
: IE> Curve C1 – C6
(Operating Time) ( IDMT curve C1 – C5 or Define Time C6)
: IE> C6 Delay 0 – 99.9 Sec in steps of 0.1Sec.
: IE>> Enable YES / NO
: IE>> Settings 5% – 80% in steps of 1%
: IE>> Time Multiplier x0.02 – x1.00 in step of 0.01.
(TMS)
: IE>> Curve C1 – C6
(Operating Time) ( IDMT curve C1 – C5 or Define Time C6)
: IE>> C6 Delay 0 – 99.9 Sec in steps of 0.1Sec.
: IE>>> Enable YES / NO
: IE>>> Settings 50% – 1200% in steps of 10%
: IE>>> C6 Delay 0 – 3.00 Sec in steps of 0.01Sec.

Internally derived Earth Fault Section (3Io)


XVIII. 3Io – G1 : 3Io> Enable YES / NO
: 3Io> Settings 10% – 100% in steps of 1%
: 3Io> Time Multiplier x0.02 – x1.00 in step of 0.01.
(TMS)
: 3Io> Curve C1 – C6
(Operating Time) ( IDMT curve C1 – C5 or Define Time C6)
: 3Io> C6 Delay 0 – 99.9 Sec in steps of 0.1Sec.
: 3Io>> Enable YES / NO
: 3Io>> Settings 10% – 100% in steps of 1%
: 3Io>> Time Multiplier x0.02 – x1.00 in step of 0.01.
(TMS)
: 3Io>> Curve C1 – C6
(Operating Time) ( IDMT curve C1 – C5 or Define Time C6)
: 3Io>> C6 Delay 0 – 99.9 Sec in steps of 0.1Sec.

Note: Due to our policy to upgrade our products constantly, we reserve the right to
supply products which may vary slightly from that indicated above.

ASHIDA ELECTRONICS PVT LTD.


ASHIDA HOUSE, Plot No. A-308, Road No. 21,
Ref.:ADR241B_V2
Wagle Industrial Estate,Thane (W)-400 604. INDIA. Issue: 06 15.11.2013
E-mail: sales@ashidaelectronics.com
आिशदा Web: www.ashidaelectronics.com
Page 11 / 15
ASHIDA Numerical 3OC + 1EF Protection Relay Type: ADR241B
(ADITYA–V2 S eries)

: 3Io>>> Enable YES / NO


: 3Io>>> Settings 50% – 1200% in steps of 10%
: 3Io>>> C6 Delay 0 – 3.00 Sec in steps of 0.01Sec.

Negative Phase sequence Element (46)`Section


XIX. NPS – G1 : I2>> Enable YES / NO
: I2>> Settings 10% – 100% in steps of 1%
: I2>> Time Multiplier x0.02 – x1.00 in step of 0.01.
(TMS)
: I2>> Curve C1 – C6
(Operating Time) ( IDMT curve C1 – C5 or Define Time C6)
: I2>> C6 Delay 0 – 99.9 Sec in steps of 0.1Sec.
: I2>>> Enable YES / NO
: I2>>> Settings 50% – 1200% in steps of 10%
: I2>>> C6 Delay 0 – 3.00 Sec in steps of 0.01Sec.
Additional data : C1 Std. Inverse. 1 (3.0S)
: C2 Std. Inverse 2 (1.3S)
: C3 Very Inverse
: C4 Extremely inverse
: C5 Long Time Inverse
: C6 Define Time
(00 – 99 Sec In steps of 1.0s.)

Auto Recloser Section


XX. : Numbers of shot 0–4 / 0 = bypass
: Dead Time 1, 2 , 3, 4 0.1S – 180S
: Relaim Time 200 – 300S

Operational Indicators (Flags)


XXI. PROT.H /ERR : Green LED indicates Relay OK (Protection Healthy)
: Red LED indicates Fault in following condition.
1. Problem in relay Hardware.
2. Trip Circuit Fault

Note: Due to our policy to upgrade our products constantly, we reserve the right to
supply products which may vary slightly from that indicated above.

ASHIDA ELECTRONICS PVT LTD.


ASHIDA HOUSE, Plot No. A-308, Road No. 21,
Ref.:ADR241B_V2
Wagle Industrial Estate,Thane (W)-400 604. INDIA. Issue: 06 15.11.2013
E-mail: sales@ashidaelectronics.com
आिशदा Web: www.ashidaelectronics.com
Page 12 / 15
ASHIDA Numerical 3OC + 1EF Protection Relay Type: ADR241B
(ADITYA–V2 S eries)

L2 – L8 : All LEDs Programmable

Drawing References
XXII. : For Cabinet Type - MAC01914
: For Back Terminal Connections - ADV02516
: For Electrical Connection Diagram - ADV02611

Sr. No. Title Standard no.


Electromagnetic Compatibility Type Test :
I. High Frequency test : IEC 60255-22-1, class – III
: Frequency : 1MHz Damped Oscillatory
: Longitudinal :5 KV (peak)
: Duration: sec duration 2 sec.
: Between input current Terminal
II. Electrostatic discharge : IEC 60255-22-2 Class III and IEC 61000-4-2 class III.
Direct application
: Contact discharge: 6kV,
: Air discharge: 8KV
: Polarity: both +ve and –Ve polarities.
III. Indirect application : IEC-61000-4-2, Class-III
: IEC 60255-22-4 and IEC 61000-4-4, class A
Fast transient
IV. : 1.2KV; 5/50ns; 5KHz burst duration = 15ms.
disturbance
: Repetition rate 300ms; Both polarities; Ri = 50Ω; duration 1 min.
: IEC 60255-22-5 / IEC 61000-4-6 class 4
: Differential Mode = 2kV
V. Surge immunity test
: Common Mode = 4kV
: 1.2/50uS , 5 surges of each polarity
Power frequency
VI. : IEC-60255-22-7, Class-A
immunity test
VII. Power frequency : IEC-61000-4-8, Class-V
magnetic field test
VIII. Radiated electromagnetic : IEC- 60255-22-3
field disturbance
: EN-61000-4-3
: Frequency 80MHz – 1GHz

Note: Due to our policy to upgrade our products constantly, we reserve the right to
supply products which may vary slightly from that indicated above.

ASHIDA ELECTRONICS PVT LTD.


ASHIDA HOUSE, Plot No. A-308, Road No. 21,
Ref.:ADR241B_V2
Wagle Industrial Estate,Thane (W)-400 604. INDIA. Issue: 06 15.11.2013
E-mail: sales@ashidaelectronics.com
आिशदा Web: www.ashidaelectronics.com
Page 13 / 15
ASHIDA Numerical 3OC + 1EF Protection Relay Type: ADR241B
(ADITYA–V2 S eries)

IX. Conducted Disturbance : IEC 60255-22-6 / IEC 61000-4-6: 1996.


induced by Radio
: Freq. 150kHz – 80MHz, Amplitude 10 V, Modulation 80% AM @
Frequency field
1 KHz
X. AC Ripple in DC supply : IEC 60255-11
Test
XI. Radiated emission : IEC- 60255-25
Insulation tests:
XII. High Voltage Test : IEC 60255-5. class – III
: At 2.5kV 50Hz between all terminal connected together and
earth for 1 minutes
XIII. Impulse Voltage Test : IEC60255-5. class – III
: Test voltage: 5KV (peak) 1.2 / 50us,
: Energy :0.5 J,
: Polarity : + ve and – Ve
: Nos. of impulses : 3 positive and 3 negative impulse
: Duration between Impulses : 5 sec.
Environmental tests:
XIV. Cold test Storage test : IEC-60068-2-1
XV. Dry heat test : IEC-60068-2-2
Damp heat test, steady
XVI. : IEC-60068-2-3
state
XVII. Damp heat test, cyclic : IEC-60068-2-30
CE compliance
XVIII. Immunity : IEC-60255-26
XIX. Emissive Test : IEC- 60255-26
XX. Low voltage directive : EN-50178
Mechanical tests
: IEC 60255-21-1 class 1
: Frequency Range = 10Hz – 150Hz , acceleration. = 1gn (9.8
XXI. Vibration
m/s2)
: Sweep rate 1 octave/min; 20 cycle in 3 orthogonal axis.
XXII. Shock and bump : IEC- 60255-21-2
XXIII. Seismic : IEC-60255-21-3

Note: Due to our policy to upgrade our products constantly, we reserve the right to
supply products which may vary slightly from that indicated above.

ASHIDA ELECTRONICS PVT LTD.


ASHIDA HOUSE, Plot No. A-308, Road No. 21,
Ref.:ADR241B_V2
Wagle Industrial Estate,Thane (W)-400 604. INDIA. Issue: 06 15.11.2013
E-mail: sales@ashidaelectronics.com
आिशदा Web: www.ashidaelectronics.com
Page 14 / 15
ASHIDA Numerical 3OC + 1EF Protection Relay Type: ADR241B
(ADITYA–V2 S eries)

Revision Date Description


01 15.10.2009 Original Specification
02 01.02.2010 Photograph of the Modified
03 12.04.2012 Back Terminal Arrangements modified.
04 15.09.2012 Event Record increased from 100 to 5000.
Modbus Protocol add
In Monitoring Functions (Event, Disturbance Record):-
Description of protocol is added
05 17.09.2013 Technical information modified
06 15.11.2013 Cabinet Box & Back Terminal details Modified

Note: Due to our policy to upgrade our products constantly, we reserve the right to
supply products which may vary slightly from that indicated above.

ASHIDA ELECTRONICS PVT LTD.


ASHIDA HOUSE, Plot No. A-308, Road No. 21,
Ref.:ADR241B_V2
Wagle Industrial Estate,Thane (W)-400 604. INDIA. Issue: 06 15.11.2013
E-mail: sales@ashidaelectronics.com
आिशदा Web: www.ashidaelectronics.com
Page 15 / 15

You might also like