9 11 Digital Output contacts for local alarm as protection function such as IDMT Over current
well as tele-signalling protection, Instantaneous Over current
9 10 Optically isolated digital status input for protection, E/F protection etc. These measured
monitoring of status to avoid use of external values are also displayed on large 20 x 4 LCD
relay logic. display for metering purpose. The DSC also
9 5000 nos of event memory, event such CB monitors different digital input through optical
close, Trip, digital status change, relay pkp isolator and perform some monitoring function
etc. All events are with date and time such trip circuit supervision, and control
stamped up to 1ms. potential free contact for control CB and
9 10 nos of Fault data stored with keypad generate ALARM and Tele-signalling.
interface and time stamping. The power supply module is basically DC – DC
converted designed using modern PWM based
Description :
Switching mode technique to convert 110Vdc
ADR241B is second generation of Numerical
station battery supply to the 12V and 24Vdc low
Over Current IDMT/DMT Relay. It consist all the
voltage supply for relay electronics and control
necessary protection and monitoring functions
circuit. It also provides necessary isolation from
required for Normal feeder, it consist of
station battery. There are two types of power
1. High Speed Digital DSP Controller
supply modules available 1) having range of
2. Analog Measuring Module
77Vdc – 250Vdc. Covering requirement of
3. Power supply Module
110Vdc and 220Vdc station battery system 2)
4. Digital Input output module.
Wide range setting 18Vdc – 250Vdc.
The High speed Digital Signal Controller
The relay is having total 8 nos of dual LED of
continuously monitors line phase current and
high intensity for easy identification of type of
E/F current. Along with different status input,
fault for easy user interface. LEDs L2 to L8 and
through CTs, and optical isolated status
Relay R1 to RB, digital status inputs and
connections. The high-speed micro-controller
controlled outputs are fully programmable via
samples these current signals through a A/D
key pad interface.
converter. The Digital Signal performs powerful
Numerical Algorithms to find out RMS of
Main Functions :
fundamental & harmonic contents of the current.
The ADR241B are having following protection
All measurement is tuned to fundamental
functions.
frequency i.e 50Hz or 60Hz depending upon
1. 4 stages of Phase Over Current element.
setting, thus relay remain stable during distorted
(Ip1>, Ip2>, Ip>> and Ip>>>).
waveform by various industrial load. All these 2. 3 stages of 3Io (Internally derived EF)
measure values are then used for different (3Io>, 3Io>> and 3Io>>>).
Note: Due to our policy to upgrade our products constantly, we reserve the right to
supply products which may vary slightly from that indicated above.
Note: Due to our policy to upgrade our products constantly, we reserve the right to
supply products which may vary slightly from that indicated above.
The separate output contact allows to use each Recloser function. There are 5 timer for auto
stage for independent function such as stage 1 recloser 1) Dead Time for shot 1 (DT1) 2) Dead
can be used for ALARM stage 2 for tripping or Time for shot 2 (DT2) 3) Dead Time for shot 3
both can be use for tripping independent CB. (DT3) 4) Dead Time for shot 4 (DT4) and 5)
Each stage can enable or disable depend upon Reclaim Time (RT). After clearing of fault
T1
depending upon type of fault and breaker
CB NO
B-
mechanism. After Fault ADR241B trigger
1
T2 2
6 To Relay CPU internal timer (settable from 0.1s to 1.0s) if fault
TC
CB NC is not cleared during this time then Relay
Fig.4 Trip Circuit Logic declares as Breaker Fail (LBB function) and
change another contacts. This contact is marked
Note: Due to our policy to upgrade our products constantly, we reserve the right to
supply products which may vary slightly from that indicated above.
as Breaker Fail can be used to TRIP back up and MODBUS command and respond in
breaker or can be used to generate ALARM respective language. There is no any specific
signal. setting which define protocol. (Please note
MODBUS by design do not support event
Negative sequence over current (46)
functionality)
The ADR241B relay will be provided with Apart from basic protection functions. Relay
programmable function to detect Unbalanced
continuously monitors all substations operation
Fault conditions. When Earth Fault elements do
through status, it internal functions, internal
not operated or not sufficiently sensitive. The
ADR241B relay is included with Negative Phase hardware etc. if any change is observed it is
Sequence Over Current element it can be marked as event. These events are stored in
programmed as IDMT or Definite Time. internal non-volatile memory along with time
Programmable DI/DO and LED:- stamped. Following are some of the events
recorded, Relay PKP, Relay Reset, CB Trip, CB
The ADR241B Relay is provided with 11 digital
Close, Change of any digital status input, Relay
outputs, 10 opto-isolated inputs and 7 general
purpose LEDs. These can be programmed by setting changed etc. Up to 5000 such events
local key board. Any logical of physical status can can be stored and can be download for detailed
be assigned to any relay contact The logic of analysis. Apart from Event record Relay also
digital status input as well as logical status can record actual waveform of current along with all
be formed and assigned to any of the relay digital and logical status during fault condition.
output. The disturbance record can be trigger Up to 10 such waveforms can be recorded; the
from external logical input. duration of disturbance record is 3sec. The
Setting Group: disturbance record can be trigger from
The ADR241B Relay is provided with two setting physical status input as well as from pick,
groups i.e. G1 and G2. Any One group is active trip operation of relay. This waveform can be
at a time. The setting group can be changed from downloaded through communication port for
digital input, this allow user to change relay further analysis.
setting dynamically as per the outgoing CB load
condition. Relay Talk Software:
Note: Due to our policy to upgrade our products constantly, we reserve the right to
supply products which may vary slightly from that indicated above.
The waveform and logical and physical status latched by relay can be view and analysed
Note: Due to our policy to upgrade our products constantly, we reserve the right to
supply products which may vary slightly from that indicated above.
or RMS value
Note: Due to our policy to upgrade our products constantly, we reserve the right to
supply products which may vary slightly from that indicated above.
Communication protocol
02= IEC 103 +MODBUS
Sub Type
330 = NUMERICAL OVER
CURRENT PROTECTION PT Secondary
RELAY 00= Not applicable
CT Secondary
03 = 1 Amp. / 5 Amp. Selectable
C a b i n e t Type
01 = Non-drawout
Ordering information:
A D R 2 4 1 B - A M 3 3 0 - 0 5 - 0 1 - 0 8 - 0 3 - 0 0 - 0 2
ADR245B – AM330–05–01–08–03–00–02
T y p e : A D R 2 4 5 B w i t h I E C 1 0 3 C o m m u n i c a t i o n P r o to c o l
Cabinet Size: CSD-H (282 X 138MM)
Cab ine t Typ e : Non- dr awou t
Auxiliary Supply: 18-250Vdc
C T s e c :1Amp. / 5Amp. Selectable
Note: Due to our policy to upgrade our products constantly, we reserve the right to
supply products which may vary slightly from that indicated above.
Technical Specifications:
General specifications
Sr. No. Specification Particulars
I. Current Input : Suitable for CT secondary 5 Amp. or 1 Amp site selectable
II. Aux. Supply : 77 – 250VDC. Or 18 – 250VDC to be specified.
III. VA burden on CT : Less than 0.2VA
IV. VA burden on Aux. : Less than 10 Watts
V. Operating Temp. range : -10 deg. To + 65 deg.
VI. Continuous Current : 2 x of rated CT
carrying capacity
VII. Pick up : Within 1.1 times of set value
VIII. Reset Value : 95% to 90% of pick up.
IX. Output Contact : 11 for General Programmable
X. Contact Rating : Continuous: 5A
: Make & carry for 0.5 sec : 30A
: Make carry for 3 sec : 15A
XI. Opto Isolated input : 1 for CB NO
: 1 for CB NC
: 10 as general programmable
XII. Thermal With stand for : 20 x of rated for 3.0 sec.
CT
XIII. Setting Group : Two (G1 and G2)
XIV. Numbers of Event :5000
General Settings
XV. : Unit ID 1 – 250 in steps of 1
: Baud Rate 1200 – 57600
: Com Port RS232 / RS485
: Set Parity None / Even / Odd
: Freq Selection 50Hz / 60Hz
: Group Selection G1 / G2
: BF Enable INT / EXT / BYP
: Extbf_I 10 – 80%
: BF Delay 100 – 1000msec in steps of 50msec
Note: Due to our policy to upgrade our products constantly, we reserve the right to
supply products which may vary slightly from that indicated above.
: OC CT Sec 1A / 5A
: CT Primary 10 – 2000 in steps of 1
: EF CT Sec 1A / 5A
: EF CT Primary 10 – 2000 in steps of 1
: Local Control YES / NO
: Trip Ckt Test YES / NO
: Post Trigger 10 – 90%
Note: Due to our policy to upgrade our products constantly, we reserve the right to
supply products which may vary slightly from that indicated above.
Note: Due to our policy to upgrade our products constantly, we reserve the right to
supply products which may vary slightly from that indicated above.
Note: Due to our policy to upgrade our products constantly, we reserve the right to
supply products which may vary slightly from that indicated above.
Drawing References
XXII. : For Cabinet Type - MAC01914
: For Back Terminal Connections - ADV02516
: For Electrical Connection Diagram - ADV02611
Note: Due to our policy to upgrade our products constantly, we reserve the right to
supply products which may vary slightly from that indicated above.
Note: Due to our policy to upgrade our products constantly, we reserve the right to
supply products which may vary slightly from that indicated above.
Note: Due to our policy to upgrade our products constantly, we reserve the right to
supply products which may vary slightly from that indicated above.