New Maternity Hospital

1. Requirement of Antimicrobial finishes for power socket outlets, Tel/Data outlets, Light switches
etc. (local and lighting dimming control switches) shall be clearly specified. In DD electrical
system report section 4.8.3 mentioned only for Lighting dimming switches. Also advice the
manufacturer details of tel/data outlets with Antimicrobial finish
For GFCI power switch sockets- specify circuit type (Active or passive)
2. As per design specs III-2/16613-2.1 A-Duplex isolation power panels are for Operating rooms
only. But the requirement for other critical areas but not limited to ICUs, CCUs, NICUs etc. are
not included. The manufacturer details of cables & accessories not specified.
3. For Network service provider (Ooredoo, Zain & Viva)-The location, space, route, power
requirement etc. shall be considered for their equipment and specify with proper details
4. For Chiller HT 11KV DG panels outgoing breaker sizing & breaking capacity calculation shall be
submitted and select the breaker accordingly.
For 180.42 A X 8 Nos =1443.36 A, 1250A breaker is selected, Clarification needed.
5. The bus coupler shall be with 4P ACB instead of 3P to isolate neutral during maintenance
6. All bus bar rating and breaking capacity of MLTPs, EMLTPs etc 100kA is specified but drawings
shows 65kA.Clarification and calculation is required.
7. For critical loads & medical areas RCBOs shall be used in final DBs for Both light & power circuits.
(As per DD RCBOs considered only for power circuits)
8. Bed Head Unit/head wall shall have 3 separate compartment for normal, emergency & ELV
services.
9. The submitted RDS in III-7-2, The system voltage indicated for majority of the equipment
/system/devices is 120 V & frequency 60 Hz. Clarification needed
10. In loaded layout following needs to be indicated
*Shall include both Medical & General purpose Electrical & ELV services & equipment/devices
complete with installation levels, locations (Wall, ceiling, Floor,on Booms) ,types etc for each
equipment/devices .
*For Booms clearly indicate total number of Critical & normal power sockets & its JBs required
with cable size & type details
* For Booms clearly indicate how many Data & NCS points are required.
*For Booms, surgical light & its power requirement shall be indicated
*In the event of student’s study conference, for Operation room booms, the details of cameras
& and cable requirement shall be clearly indicated. The integration details & raceways
requirement/routes to the conference room /auditorium shall be clearly indicated in the
drawings.
11. Power requirement for Electrically operated doors, automatic doors, automatic curtain, PTS
(Pneumatic Tube system), PWCS, hold open doors, TVs, STBs, Interface modules, projectors,
Screens, Public toilet hand dryers, general cleaning purpose outlets etc and installation details of
outlets shall be clearly specified
12. For central kitchen & laundry the power requirement & installation levels shall be clearly
specified.
13. For Bariatric lift- JB with individual circuit from critical DB shall be provided.
14. Loading & unloading dock area 3phase industrial socket shall be considered. Specify installation
details
15. Enough lighting shall be considered for loading bay or loading dock area(External)
16. Power socket outlets, Lights, Switches requirement for Elevator PIT, shaft etc shall be clearly
specified with installation details
17. Hospital entrances & canopies –Proper lighting shall be provided
18. For Medical gas, Generator room etc hazardous/explosion proof material shall be considered
19. Installation levels of TVs, Clocks, NCS-GRSS, card readers shall be clearly specified (FFL to center)
20. Installation levels/heights (FFL to bottom or FFL center of the device, floor box/furniture
mounted etc) of each electrical & ELV services shall be clearly specified
21. Manufacturer details for the following are not specified
*Ceiling roses for Carpark and other areas
*Cables glands & accessories
*Cable ties
*MICC Cables & Accessories
*CWZ category cables/wires & accessories
*Flexible cables
*PVC & GI FLEXIBLE CONDUITS
*IP 65 rated boxes
*Galvanized steel casing for external wall
*Hazardous/explosion proof wiring devices & accessories
*Materials for Shelter
22. Power requirement ELV services & cabinets and installation details shall be clearly specified.
23. Power requirement for Data centers, CRAC units, UPS, Engineering control room etc shall be
clearly specified
24. Power requirement & installation levels for Dispensers, Icemaker, refrigerator, microwave oven,
Coffee maker etc shall be clearly specified
25. Power requirement for hands free hand washing sink (as per FGI) shall be included and
indicated.
26. For Travellators/Elevators S/F is recommended instead of Isolator.
27. All schematic diagram shall indicate complete with details and its legends
28. Specification & plan for with installation details of all signage fittings needed.
29. All light fitting design Cut sheets not available.
30. For façade-Light fittings, control gear, power supply, installation location & routes etc shall be
clearly specified & indicated.
31. Light fittings legends shall be complete with specific symbolic representation and description
32. In the event glass panels are used provision for light fittings installation shall be considered not
limited to entrance, canopy, ground floors etc
33. Power requirement for Hospital Name Signage shall be considered
34. For the Bridges-EL & ELV services shall be clearly indicated.
35. For Auditorium detailed design shall incorporate all required EL & ELV services complete with
installation details. Please note special attention is required in selection of light fittings (curved
areas), Fire alarm system, AV-speaker system (installation provisions, routes etc), screen, floor
box requirements, communication cables and routes from stage lecture desk to auditorium
control room etc.
36. For both primary & secondary Data centers detailed design shall incorporate all required EL &
ELV services complete with installation details.
37. It is recommended to use 500mm indoor installation level for power & data outlets as standard,
except as otherwise required.
38. For Shelter 2Nos of 800 kVA generator is not indicated in the drawing. Separate design drawing
is recommended for shelter area for EL & ELV services.
39. For Infant pediatric protection heat map is required to submit along with design. Also separate
exciter shall be included for the designated zones/routes as assigned for the system. For
emergency & fire exit delayed egress door contact as per NFPA 101 shall be considered.
40. For security surveillance System-Camera distribution & coverage shall be as per latest MOI
regulation (Shall include/cover but not limited to all the Entrances, Exits areas, Lobbies,
corridors etc)
41. For Integrated services shall include the below along with ICT report list
*Infant pediatric system
*Security CCTV/Surveillance system
*Access control system
*Parking control management system
*Master clock system
*Audio visual system-Public address system
*Digital Signage
*PV system
*UPS system
*Fire alarm system
*ICT system
* Medical system (MRI, Medical gas, PTS, PWCS, etc.)
*Isolated power panels

Integration system shall clearly specify /indicate for one way or 2 way communications