8000 CFM
1
EcoloAir™ System
Form#: SS031_8000CFM
Date: 05-2017 - Rev3
FILTER WITH ODOR CONTROL INTERIOR RH MODULE
1070 lbs / 504 kg FIRE DAMPER HANGER BRACKET c/w
9/16"Ø DIA. HOLE
FILTER No. 1
CLEARANCE
24.569"
SERVICE
30" [624]
[762]
FILTER
INTEGRITY
PLAN VIEW MONITOR (FIM)
ECOLO ODOUR CONTROL SYSTEM
ENCLOSURE TO HOUSE ECOLO
ODOUR CONTROL COMPRESSOR
NOZZLE & "SCENTRY" LIQUID
CONTAINER, (PROGRAMMERS HANGER RODS
6" SERVICE CLEARANCE LOCATED IN ELCOLOGY PANEL)
(BY OTHERS)
REQUIRED FOR ACCESS 12.307" 48"
HANGER RODS [313] [1219]
48" 12.307" TO TRANSDUCER PORTS
(BY OTHERS) [1219] [313]
FILTER
INTEGRITY
MONITOR (FIM)
LEFT END VIEW RIGHT HAND ACCESS SIDE ELEVATION RIGHT END VIEW
(LEFT SIDE)
AIR
FLOW 56" 51.118"
[1422] [1298]
1"
[25]
3.441"
CLEARANCE
[87]
SERVICE
30"
[762] 0.504"
[13]
PLAN VIEW
2.453" 48" 2.453" VFD BOX
[62] [1219] [62] 22.059" HANGER RODS
3.799" 3" [560] (BY OTHERS)
[97] [76]
HANGER RODS
(BY OTHERS)
49.394"
[1255]
18.905"
[480]
7.938"
3" [202]
[76]
58" 0.504" 58.794" 0.504" 56"
[1473] [13] [1493] [13] [1422]
LEFT END VIEW RIGHT HAND ACCESS SIDE ELEVATION RIGHT END VIEW
8000 CFM
2
EcoloAir™ System
EXTERNAL STATIC PRESSURE TO ECOLOAIRTM SYSTEM
Form#: SS031_8000CFM
Date: 05-2017 - Rev3
1.0” ESP 1.5” ESP 2.0” ESP 2.5” ESP
MODEL
BHP BHP BHP BHP
NUMBER RPM RPM RPM RPM
HP KW HP KW HP KW HP KW
6400 2162 7.9 5.7 2245 8.6 6.3 2325 9.3 6.8 2403 10.1 7.4
B8 7200 2229 9.1 6.6 2308 9.8 7.2 2384 10.6 7.8 2459 11.4 8.3
8000 2305 10.4 7.6 2380 11.3 8.2 2453 12.1 8.8 2525 12.9 9.4
Note:
Fan calculations are based on interior/ducted blower arrangement. For exterior/free arrangement data, please contact the factory.
Above stated for design guidelines only, actuals may vary. Please contact factory for project specific details.
Consultant Specification
The EcoloAirTM Ecology System shall be a Model • The second stage filter shall be constructed from
________, as manufactured by Halton, supplied HEPA grade medium, 12-inch deep Mini-Pleat
complete with Filter and Odor Control Module, Fan V-Bank MERV 16 performance per ASHRAE
Module, and Control Panel. System mounting to be 52.2 and classified to UL900 standard. The filter
designed for; Interior/Exterior, Suspended/Floor/Roof. clean resistance shall not exceed 0.6 in.w.g.
The system shall deliver _________ CFM (_______ with efficiency of at least 95% at 0.4 microns.
m3/s) at ________in.wg. (________Pa) External Static
Pressure (ESP). The Halton EcoloAir unit shall be ETL • Filter module will include Filter Integrity Monitor,
Listed. a grease monitoring system that detects when
grease bypassing the final filter in the Halton
EcoloAir system. It shall detect if the absolute
Filter Module filter in the EcoloAir unit is partially missing due
The unit casing shall be fully painted and be a double to filter gaps or if a lower efficiency final filter is
wall construction reinforced and braced for maximum being used than specified.
rigidity. Inner walls shall be 16-gauge liquid tight welded
and construction and outer walls shall be minimum A UL/ULC Listed fire damper actuated by fusible link
20-gauge steel. Filter sections to be insulated with 1.5” (212°F UL / 212°F ULC) shall be located at the outlet.
(38mm) insulation to the requirements of UL/ULC. The This module to be complete with three pressure
unit shall be complete with two stages of filtration. transducers to monitor the condition of each of the three
stages of filtration, and a fourth pressure transducer
• The first stage filter shall be a . 15” deep to monitor overall airflow cfm. Hinged access doors
combination Extended Life Filter, MERV 14 shall be provided to allow easy access to the filters.
rated and classified to UL 900 standard. The
filter clean resistance will not exceed 1.04”
w.g. and have an overall holding capacity of
7.9 lbs. A combination of a MERV 8 2” pleated
filter and MERV 14 Bag filter shall not be used.
8000 CFM
3
EcoloAir™ System
Odor Control Module ECOSystem
Form#: SS031_8000CFM
Date: 05-2017 - Rev3
The EcoloAirTM Odor Control Module shall consist ECOsystem will be standard with all EcoloAir
of a housing and a self contained odor reducing systems and will consist of 3 pressure transducers, a
system. The housing shall be fully painted and be microprocessor and VFD. The 3 Pressure Transducers
constructed of 16 gauge (minimum) steel with all joints will monitor the pressure drop across each filter as well
suitably reinforced and braced for rigidity. The “Ecolo as overall pressure to provide the status of each filter
ScentryTM” liquid spray odor reducing system shall as a % loaded as well as notify the operator with an
produce an atomized spray that permeates the filtered early warning of when the filters need to be replaced.
exhaust air to attack and neutralize airborne odors. The On start up, the main pressure transducer is calibrated
system housing shall be constructed of heavy steel with the Capture Jet® Testing and Balancing Ports to
with locking hinged access door and two security design airflow. The setting will be stored in the system
bolts. The system shall be complete with an atomizing memory and acts as the reference point for design
spray nozzle, 5-gallon liquid reservoir. Timers mounted exhaust. The Microprocessor will read the signals
in the EcoloAirTM control panel to switch on, off and from the pressure transducer and control the VFD to
cycle control to provide for infinite adjustment. maintain constant airflow in the system regardless
Option: Carbon, Bonded, activated carbon panels are of the filter conditions. The V.F.D. (Variable Frequency
furnished to remove a broad range of both base and acid Drive) will control the RPM of the fan module based on
gases. Panels are held in place by gasketed, extruded the signal received from the microprocessor.
aluminum tracks arranged in a V-bank configuration
The company has a policy of continuous product development, For more information, please contact your nearest Halton
therefore we reserve the right to modify design and agency. To find it: www.halton.com
specifications without notice.