STANDARD DRAWINGS |For Public Works Construction|Edition


STANDARD
DRAWINGS
For Public Works Construction
Public Works Department 2016 Edition
PROJECT IMPLEMENTATION DIVISION
STANDARDS & CONTRACT
DOCUMENTS SECTION
525 B STREET STE. 750
SAN DIEGO, CA 92101
DOCUMENT NUMBER: PWPI070116-03

2016

Please adjust this spine guide marks when thickness of the book is determined before printing.
 

City of San Diego


Standard Drawings
For
Public Works Construction
2016 Edition

Prepared by

Public Works Department

Project Implementation Division

Standards and Contract Documents Section

 
 

INTRODUCTION

These "Standard Drawings for Public Works Construction 2016 Edition" (Standard
Drawings) have been prepared and adopted by the City of San Diego. They are for use in
concert with the “2015 WHITEBOOK – Standard Specifications for Public Works
Construction” and the 2015 Edition of the “GREENBOOK - Standard Specifications for
Public Works Construction”. The Standard Drawings include some San Diego Regional
Standard Drawings that have been adopted by the City of San Diego.

The electronic copy of the Standard Drawings is available for download from the City’s
website: http://www.sandiego.gov/publicworks/edocref/standarddraw/

Updates to the Standard Drawings will be posted to this website as they are adopted by the
City of San Diego:
http://www.sandiego.gov/publicworks/edocref/standarddraw/updates.shtml

Users of the Standard Drawings are encouraged to submit corrections and proposed changes
to the Standards Drawings to Public Works Department, Standards and Contract Documents
Section at engineering@sandiego.gov.

The Standard Drawings has discontinued the use of dual units and adopted U.S. Standard
Measures, also referred to as Customary System Units or English Units. The 2015 Greenbook
continues to have U.S. Customary System Units followed by International System of Units
also referred to SI or metric units in parenthesis.

 
TABLE OF CONTENTS

CONCRETE STRUCTURES
SDC-103 Structure Excavation & Backfill (2)
SDC-105 Masonry Wall
SDC-107 Retaining Wall Notes
SDC-108 Retaining Wall Details

C-1 Masonry Retaining Wall Type 1 (Level Backfill)


C-2 Masonry Retaining Wall Type 2 (Live Load Surcharge or Slope
Backfill)
C-3 Masonry Retaining Wall Type 3 (Level Backfill)
C-4 Masonry Retaining Wall Type 4 (Live Load Surcharge or Slope
Backfill)
C-5 Masonry Retaining Wall Type 5 (Level Backfill)
C-6 Masonry Retaining Wall Type 6 (Live Load Surcharge or Slope
Backfill)
C-9 Gravity Retaining Walls
C-10 General Notes and Details for Gravity Retaining Walls
C-11A Reinforced Concrete Retaining Wall Type 1
C-11B Reinforced Concrete Retaining Wall Type 1
C-11C Reinforced Concrete Retaining Wall Type 1
C-11D Reinforced Concrete Retaining Wall Type 1
C-12A Reinforced Concrete Retaining Wall Type 1A
C-12B Reinforced Concrete Retaining Wall Type 1A
C-13A Reinforced Concrete Retaining Wall Details No. 1
C-13B Reinforced Concrete Retaining Wall Details No. 1
C-13C Reinforced Concrete Retaining Wall Details No. 1
C-13D Reinforced Concrete Retaining Wall Details No. 1
C-14 Reinforced Concrete Retaining Wall Details No. 2
C-15 Reinforced Concrete Retaining Wall Details No. 3

i
DRAINAGE SYSTEM
SDD-101 Typical Ford (2)
SDD-102 Curb Inlet Opening
SDD-103 Slotted Drain Connections to Standard Inlets
SDD-104 Rip Rap Energy Dissipator
SDD-105 Concrete Energy Dissipator (2)
SDD-106 Drainage Ditches
SDD-107 Minor Drainage Channel
SDD-108 Major Drainage Channel
SDD-109 Graded Earth Channel
SDD-110 Pipe Bedding and Trench Backfill for Storm Drains
SDD-111 Box Culvert Wingwall (6)
SDD-112 Box Culvert Warped Wingwall (3)
SDD-113 Concrete Lug
SDD-114 Inlets and Cleanouts Notes and Details (2)
SDD-115 Curb Inlet – Type A
SDD-116 Curb Inlet – Type B
SDD-117 Curb Inlet – Type C
SDD-118 Median Curb Inlet – Type J
SDD-119 Catch Basin – Type F

D-03B Concrete Apron for Type C Curb Inlet

D-09 Storm Drain Cleanout – Type A


D-10 Storm Drain Cleanout – Type B
D-13 Welded Steel Grate Frame
D-15 Drainage Structure Grate
D-16 Corrugated Steel Pipe Inlets Types A and B
D-17A Corrugated Steel Pipe Inlets, Details
D-17B Corrugated Steel Pipe Inlets, Details
D-18 Slotted Corrugated Steel Pipe Drains 12” Through 24”

ii
D-22 Asphalt Concrete Spillway
D-23 Tapered Inlet and Downdrain Flume
D-25 Curb Outlet – Type A
D-27 Sidewalk Underdrain Pipe
D-29 Catch Basin – Type I
D-30 Straight Headwall – Type A [Circular Pipe]
D-31 Straight Headwall – Type A [Corrugated Steel Pipe – Arch]
D-32 Straight Headwall – Type B [Circular Pipe]
D-33 Straight Headwall – Type B [Corrugated Steel Pipe. – Arch Pipe]
D-34 Wing and U Type Headwalls for 18” to 36” Pipes
D-35A Wing and U Type Headwalls for 42” to 84” Pipe
D-35B Wing and U Type Headwalls for 42” to 84” Pipe
D-36 L Type Headwalls [Circular Pipes]
D-37 L Type Headwalls [Corrugated Steel Pipe. Arch]
D-38 Curtain Wall
D-39 Inlet Apron for Culverts Up to 42” Diameter
D-42 Concrete Energy Dissipator (Reinforcement) 18” to 30” Diameter
Pipe
D-43A Concrete Energy Dissipator (Reinforcement) 36” to 72” Diameter
Pipe
D-43B Concrete Energy Dissipator (Reinforcement) 36” to 72” Diameter
Pipe
D-43C Concrete Energy Dissipator (Reinforcement) 36” to 72” Diameter
Pipe
D-44A Pipe Culvert – Headwalls, Endwalls & Warped Wingwalls
D-44B Pipe Culvert – Headwalls, Endwalls & Warped Wingwalls
D-44C Pipe Culvert – Headwalls, Endwalls & Warped Wingwalls
D-44D Pipe Culvert – Headwalls, Endwalls & Warped Wingwalls
D-61 Rounded Pipe Ends in Drainage Structures
D-62 Pipe Collar
D-72 Cutoff Wall for Drainage Channel
D-73 Pipe to Channel Connection
D-76A Single Box Culvert Details No. 1
D-76B Single box Culvert Details No. 1
iii
D-76C Single Box Culvert Details No. 1
D-76D Single Box Culvert Details No. 1
D-76E Single Box Culvert Details No. 1
D-76F Single Box Culvert Details No. 1
D-76G Single Box Culvert Details No. 2
D-77A Double Box Culvert Details No. 1
D-77B Double Box Culvert Details No. 1
D-77C Double Box Culvert Details No. 1
D-77D Double Box Culvert Details No. 1
D-77E Double Box Culvert Details No. 1
D-77F Double Box Culvert Details No. 1
D-77G Double Box Culvert Details No. 2
D-78A Triple Box Culvert Details No. 1
D-78B Triple Box Culvert Details No. 1
D-78C Triple Box Culvert Details No. 1
D-78D Triple Box Culvert Details No. 1
D-78E Triple Box Culvert Details No. 1
D-78F Triple Box Culvert Details No. 1
D-78G Triple Box Culvert Details No. 2
D-81A Box Culvert Miscellaneous Details No. 1
D-81B Box Culvert Miscellaneous Details No. 2
D-82 Debris Fence

ELECTRICAL SYSTEM

SDE-101 Street Lighting Standard


SDE-102 Model 336 Cabinet
SDE-103 Pedestrian Barricade
SDE-104 Type E Modified Loop (2)

E-2 Grounding of Concrete Lighting Standards


E-3 Pedestal for Electrical Equipment

iv
GENERAL SURFACE IMPROVEMENTS

SDG-102 Bus Stop Slab


SDG-106 Cold Milling Asphalt Concrete Pavement Detail
SDG-107 Trench Resurfacing for Asphalt Concrete Surfaced Streets
SDG-108 Trench Resurfacing for PCC Surfaced Streets
SDG-109 Sidewalk Joint Locations
SDG-110 Inlet Transition Profile (2)
SDG-112 Raised Center Median (2)
SDG-113 Pavement Design Standards Schedule “J” (4)
SDG-115 Existing Historical Stamp or Impression Placement
SDG-117 Narrow Trench Resurfacing for Asphalt Concrete Surface Streets
SDG-118 Narrow Trench Resurfacing for PCC Surfaced Streets
SDG-119 Trench Types G, H & I Backfill for Dry Utility
SDG-120 Alley Apron
SDG-130 Detectable Warning Tiles
SDG-131 General Curb Ramp Notes
SDG-132 General Curb Ramp Notes and Supplemental Details
SDG-133 Curb Ramps – Type A and B
SDG-134 Dual Curb Ramps
SDG-135 Curb Ramps – Type C1 and C2
SDG-136 Curb Ramps – Type C1 and C2 More Details
SDG-137 Curb Ramp - Type D
SDG-138 General Curb Ramps
SDG-139 Island and Passageway Details
SDG-140 Curb Ramp Barricade
SDG-150 Curb and Gutter – Separate
SDG-151 Curb and Gutter – Combined
SDG-154 Curb and Gutter – Medians
SDG-155 Sidewalk – Typical Sections
SDG-156 Concrete Curb, Gutter, Sidewalk and Pavement Removal and
Replacement
SDG-157 Cross Gutter
v
SDG-158 Mid-Block Cross Gutter
SDG-159 Concrete Driveway (Contiguous Sidewalk) (2)
SDG-160 Concrete Driveway (Non-Contiguous Sidewalk)
SDG-161 Residential Concrete Driveway (Parkway Less Than 10’ In Depth)
SDG-162 Concrete Driveway (For Confined Right-of-Way)
SDG-163 Commercial Concrete Driveway
SDG-164 Driveway Location and Width Requirements

G-5 Dikes – Asphalt Concrete


G-10 Concrete Joint Details
G-15 Driveway Location – Adjacent to Curb Returns and Street Lines
G-18 Concrete Pavement Width 40’ or Less
G-19 Concrete Pavement Width 40’ to 62’
G-20 Concrete Pavement, Alley Section Width 53’ to 69’
G-21 Concrete Pavement Alley Section, Width 40’ or Less
G-22 Cutoff Wall at End of Pavement
G-23 Cutoff Wall at End of Alley Pavement
G-36 Slurry Backfill

SPRINKLER IRRIGATION SYSTEMS

SDI-101 Shrub Spray Head on Fixed Riser


SDI-102 Rotor or Impact Head on Fixed Riser
SDI-103 Rotor, Spray, or Bubbler Pop-up Head
SDI-104 Tree Bubbler Tube
SDI-105 Quick Coupling Valve
SDI-106 Isolation Glove Valve 2” or Smaller
SDI-107 Isolation Glove/Gate Valve 2 ½” and Larger
SDI-110 Irrigation Trench PVC or Copper Pipe
SDI-111 Master Valve
SDI-112 Flow Sensor
SDI-114 Remote Control Valve
SDI-115 Electrical Pull Box for Direct Burial Control Wires and Splice Notes

vi
SDI-116 Solar Irrigation Controller
SDI-117 Automatic Irrigation Controller Pedestal Mounted
SDI-118 Automatic Irrigation Controller Indoor Wall Mounted
SDI-119 Control Wire Installation
SDI-120 On-Grade Pipe Stabilization Temporary installation
SDI-123 Swing Joint and Pipe Installation on Slopes Above Ground Pipe
Installations
SDI-125 Remote Control Valve Manifold Assembly with PVC Pipe (Temporary
Systems)
SDI-126 Remote Control Valve Manifold Assembly with Brass Pipe
SDI-127 Remote Control Valve Drip Irrigation
SDI-128 Air / Vacuum Relief Valve
SDI-129 Drip Irrigation Flush Valve (Automatic)

LANDSCAPING

SDL-101 Tree Planting and Staking


SDL-102 Shrub Planting/Ground Cover Spacing
SDL-103 Concrete Mowing Strip
SDL-104 Tree Grate
SDL-105 Light Pole Pad in Turf Areas
SDL-106 Root Control Barrier
SDL-107 Palm Tree Planting (2)

MISCELLANEOUS

SDM-101 Left Turn Median Transition


SDM-102 Street Name Sign (4)
SDM-103 Joint Trench Locations
SDM-104 Break-Away Sign Post
SDM-105 Warning / Identification Tape Installation
SDM-107 Dual Height Drinking Fountain (New Construction)
SDM-108 Dual Height Drinking Fountain Non-Alcove (For Existing Structures)
SDM-109 Underground Typical Location (New Construction)

vii
SDM-111 Utility Locations in Local and Major Streets Prime Arterials and
Expressways
SDM-112 Vinyl Coated Chain Link Fence
SDM-113 Manhole Cover – Locking Device
SDM-114 Chain Link Gate (2)
SDM-115 Pedestrian Ramp and Protective Railing (3).
SDM-116 Continental Crosswalk Markings Layout and Notes (3)
SDM-117 Accessible Parking (8)
SDM-118 Pedestrian Protective Railing & Stair Handrail (3)
SDM-119 Tennis Court Fence Chain Link
SDM-130 Guardrail

M-1 24” Manhole Frame and Cover Heavy Duty


M-2 24” Manhole Frame and Cover Light Duty
M-3 36” Manhole Frame and Two Concentric Covers Heavy Duty
M-9 Guard Post and Barricade
M-10 Street Survey Monument
M-10A Street Survey Monument Overlay Adjustment
M-10B Street Survey Monument Notes
M-11 Bench Mark – Brass Plug
M-12 Datums
M-13 Survey Monuments
M-14 Metric Equivalents
M-16 Demountable Post
M-20 Chain Link Fence Details
M-21 Underground Typical Location Conversion/Replacement/Upgrade
M-45 Break – Away Sign Post

RECYCLED WATER SYSTEMS

SDRW-101 Pipe Bedding and Trench Backfill for Recycled Water Mains
SDRW-102 2” Recycled Water Service Installation and Marking (2)
SDRW-103 Recycled Water Valve and Valve Box (Light Duty)

viii
SDRW-104 Recycled Water Valve and Valve Box (Heavy Duty)
SDRW-105 Recycled Water Valve Well Cover
SDRW-106 Recycled Water Valve Key Extension
SDRW-108 Recycled Water Signs (4)
SDRW-109 Sign / Tag for Recycled Water Irrigation Remote Control Valve
SDRW-110 Sign / Tag for Recycled Water Irrigation Valve
SDRW-111 Sign / Tag for Identification of Recycled Water Control Devices
SDRW-112 Sign / Tag for Recycled Water Irrigation Box Cover / Lid
SDRW-113 Sign / Tag for Recycled Water Automatic Irrigation Controller
SDRW-114 Recycled Water Tag
SDRW-115 Recycled Water Quick Coupling Valve (2)
SDRW-116 Cross Connection Control Test Station
SDRW-120 Threshold Bypass Piping
SDRW-121 Typical Curb Marker Installation Location

SEWER SYSTEM

SDS-101 Permissible Depth of Cover for PVC Pipe


SDS-102 Sewer Lateral Cleanout (In Paved Alley, Side Walk, or Other Areas
Subject to Traffic)
SDS-103 Sewer Lateral Cleanout
SDS-104 4” Backwater Device (2)
SDS-105 House Connection (Sewer Lateral)
SDS-106 Manhole 5’ x 3’ Diameter
SDS-107 Manhole – 4’ x 3’ Diameter (For 15” Maximum Diameter Pipe)
SDS-108 Manhole Pipe Connectors
SDS-109 Cleanout – Sewer Force Main
SDS-110 Pipe Bedding and Trench Backfill for Sewers
SDS-112 Concrete Encasement
SDS-113 Concrete Backfill
SDS-114 Concrete Anchor
SDS-115 Cutoff Wall
SDS-116 Concrete Protection for Existing Sewer Pipe

ix
SDS-117 Concrete Support for Undercut Sewer Pipe
SDS-118 House Connection Sewer Repair
SDS-119 Pipe Bedding and Trench Backfill for Sewers in Groundwater
SDS-120 Sewer Manhole Base
SDS-121 Sewer Main Cleanout

SC-01 Sewer Cleanout


SM-07 Manhole Coating and Lining System
SM-08 Existing Manhole Abandonment

WATER SYSTEMS

SDW-101 Typical Outlet for SCRW Pipe Steel Pipe and Pipe Specials

SDW-103 Access Manhole

SDW-104 Fire Hydrant Installation (3)

SDW-105 Backflow Preventer for 4” and Larger Fire Service (2)

SDW-106 Blow-Off Assemblies at the End of PVC and Cast Iron Mains

SDW-107 Narrow Trench for 1” & 2” Water Services

SDW-108 Field Welded Joints

SDW-109 Valve Key Extensions

SDW-110 Pipe Bedding and Trench Backfill for Potable Water Mains

SDW-111 Spigot Ring & Gasket Joint for Welded Steel Pipe

SDW-113 Concrete Water Meter Box for 1 ½” or 2” Water Meter

SDW-114 2” Meter, Backflow and Coffer Box (3)

SDW-115 Read Hole Cap & Chain Detail (For Metal Meter Vault Covers)

SDW-116 Bonding Strap for Steel and SCRW Pipe

SDW-117 Air and Vacuum Valve Enclosure & Location (2)

SDW-118 Fire Service Connection & Assembly

SDW-119 Dual Above Ground Meter With City Backflow Preventer (2)

SDW-120 Backflow Preventer Reduced Pressure Principle Detector Assembly


for Fire Service 3” and Larger
x
SDW-121 At-Grade Cathodic Protection Test Station Installation for Roadways

SDW-122 Joint Bonding of Non-Welded Pipe Joints & Fittings

SDW-123 Insulating Flange and Mechanical Joints External Protection

SDW-124 Post-Mounted Test Station Wire Termination Detail

SDW-125 Exothermic Welding of Cables and Coating of Welding

SDW-126 Installation of Directly Buried Cables and Conduit

SDW-127 Above Ground Cathodic Protection Test Station Installation for


Undeveloped Areas

SDW-128 At-Grade Concrete Test Box

SDW-129 At-Grade Cathodic Protection Test Station Wiring Diagram for


Roadways

SDW-130 Insulating Flange Four-Wire Test Station Installation

SDW-131 Wire Identification

SDW-132 Post-Mounted Cathodic Protection Warning Decal

SDW-133 Symbols Cathodic Protection

SDW-134 Polymer Concrete Water Meter Box for 1” Water Service

SDW-135 Polymer Concrete Water Meter Box for 2” Water Service

SDW-136 Meter Box Polymer Concrete Cover (2)

SDW-137 Traffic Rated Cover and Meter Box Installation

SDW-138 Multiple Service Assembly Dead End Main

SDW-139 Split Butt Strap

SDW-141 Backflow Preventers Wet Utility Room Installation (2)

SDW-143 2” Blow-off Installation

SDW-144 4” & 6” Blow-off Installation Type A

SDW-145 4” & 6” Blow-off Installation Type B

SDW-146 Blow-off Installation from End of Main & from Steel Main

SDW-149 2” Water Service Installation

SDW-150 1” Water Service Installation

SDW-151 Concrete Thrust and Anchor Block Installations (3)

SDW-152 Gate Well Identification

xi
SDW-153 Gate Well Cap & Can Installation for Valves 4” and Larger

SDW-154 Water Valve Bypass Details for Mainlines 16” and Larger

SDW-155 Backflow Preventer for 3/4” to 2” Metered Service

SDW-156 Backflow Preventer for 3” and Larger Metered Service

SDW-157 Dual Above Ground Meter with Private Backflow (2)

SDW-158 2” Manual Air Valve

SDW-159 2” Automatic Combination Air Release & Air/Vacuum Valve


Installations

SDW-160 4” & 6” Automatic Combination Air Release & Air/Vacuum Valve


Installations

SDW-161 Pipe Support for Undercut Sewer Mains or Sewer Laterals

SDW-162 Pipe Support for Undercut AC Water Main

SDW-170 2” Fire Hydrant Highlining Connection

SDW-171 4” Fire Hydrant Highlining Connection

SDW-172 Residential User Highlining Connection

SDW-173 Highlining Crossing & Run at Driveways and Curbs

SDW-174 Highlining Crossing & Run at Curb Ramps

WB-05 Temporary 2” Blow-Off Installation

WM-04 Protection Post Installation

WP-03 Cutting and Plugging Abandoned Water, Recycled Water and Sewer
Mains

WP-05 Slope Protection Installations

WP-07 Cut-Off Wall Installation in Traveled Areas

WS-03 Meter Box Locations for Water and Recycled Water Appurtenances

WS-04 4” or 6” Fireline/Master Meter Installation (2)

WV-05 Steel Valve Stem Extension for Valves 2” and Smaller

xii
ABBREVIATIONS AND SYMBOLS

ABS Acrylonitrile – butadiene – CSP Corrugated steel pipe


styrene
CTB Cement treated base
AC Asphalt Concrete
CV Check valve
ACI American Concrete Institute
CY Cubic Yard
ACP Asbestos Cement Pipe
D Diameter or Load of Pipe
ADA Americans with Disabilities
DIA Diameter
Act
DWG Drawing
ADAS Americans with Disabilities
Act Standards EA. Each
AGG Aggregates ELEV Elevation
ANSI American National Standards EX Existing
Institute EXP Expansion
ASCE American Society of Civil F Fahrenheit or Flange
Engineers
FG Finished grade
ASTM American Society for Testing
and Materials FL Flow line

AWWA American Water Work GA Gauge


Association GALV Galvanized
CAL/OSHA California Occupational GFI Ground Fault Interrupter
Safety and Health
Administration H High or height

CalTrans California Department of HEX Hexagonal


Transportation HORIZ Horizontal
CATV Cable/TV HPS High pressure sodium (Light)
CC Calcium Chloride HT Height
C/C Center to Center ID Inside diameter or
CF Cubic Foot Identification Joint

CFS Cubic Foot per second JT Joint


LAP Overlap
CL Center Line
CLR Clear LOL Layout line
MAX Maximum
CLSM Controlled low strength
material MJ Mechanical Joint
CONC Concrete MIN Minimum
CONST Construct, Construction MVL Mercury vapor light

xiii 
 
ABBREVIATIONS AND SYMBOLS

OC On center TYP Typical


OD Outside diameter VERT Vertical
PC Point of curvature W Water, Wider or width
PCC Portland cement concrete W/ With
PCC Point of compound curvature WWF Welded wire fabric
PCF Pounds per cubic foot
PCR Point of curb return
PL Property line or Place @ At
PO Push on % Percent
PPB Pedestrian Push Button ‘ Feet or minutes
PSF Pound per square foot “ Inches or seconds
PUD Public Utilities Department 1
Number
PVC Polyvinyl Chloride / Per or (between words)
R Radius o
Degree
RCV Remote Control Valve ø Diameter
R/W Right-of-way, Recycled water PL Property line
REINF Reinforced or reinforcement CL Centerline
RPDA Reduced pressure detector
assembly
RWGV Resilient wedge gate valve
RW Recycled water
S Slope or second
SCRW Steel cylinder rod wrapped
SD Storm drain
SE Sand Equivalent
SI International System of Units
(Metric)
Sqft Square foot
STD Standard
STR Straight
TOT Total

xiv 
 
CHAPTER 1
CONCRETE
STRUCTURES
EXCAVATION BACKFILL
EXCAVATION BACKFILL ORIGINAL GROUND
OR CUT SLOPE
SU BG RADE
SLOPE OR
SUBGRADE

r---IWl-r 1·---l ~ ~ 1-r


DITCH & CHANNEL RETAINING WALLS
EXCAVATION
PIPE HEADWALLS

EXCAVATION BACKFILL

PLAN OF WING WALL

EXCAVATION BACKFILL
CULVERT IN TRENCH
ROADWAY
EMBANKMEN
ORIGINAL
GROUND
ORIGINAL GROUND

1' -I 1--1 I- 1'


SECTION A-A

CULVERT IN EMBANKMENT

• • • • • • •. -i'~

CULVERT CULVERT

ROADWAY DITCH & CHANNEL


GRADE TOP CULVERT EMBANKMENT EXCAVATION ___j l-1·
ORIGINAL GROUND
BOX CULVERTS SECTION B-B
LEGEND WING WALLS
~ STRUCTURE EXCAVATION
~ STRUCTURE BACKFILL ORIGINAL
GROUND BACKFILL
~ DITCH & CHANNEL EXCAVATION
ITIIIIIIIIill ROADWAY EXCAVATION CHANNEL OR
ORIGINAL GROUND
~ ROADWAY EMBANKMENT
EMBANKMENT OR
EMBANKMENT OR
ORIGINAL GROUND
ORIGINAL GROUND
DITCH &
CHANNEL
EXCAVATION
TOP LIMIT OF STRUCTURE EXCAVATION AND BACKFILL IS ORIGINAL
NOTE:
GROUND IF CHANNEL IN NOT EXCAVATED
SUBGRADE SHALL BE LOWEST SUBGRADE AS
DEFINED IN THE STANDARD SPECIFICATIONS
MONOLITHIC CONCRETE SLOPE PAVING: RIPRAP
SHEET 1 OF 2

REVISION BY APPROVED DATE RECOMMENDED BY THE CITY OF SAN DIEGO

ORIGINAL J. CASEY
CITY OF SAN DIEGO - STANDARD DRAWING rl/. . ~;:D:/~ .cOMMITIEE
~ ~ 1/31/2012
UPDATED KA OV12
COORDINATOR R.C.E. 65271 DATE
STRUCTURE EXCAVATION
DRAWING
& BACKFILL NUMBER
SDC-103
C C
EXCAVATI
ON 1’ C C 1’ 1’ C
C C
C
1’
CONCRETE SLOPE PAVI
NG
C

TOP LI
MIT OF STRUCTURE EXCAVATI
ON
C
D D AND BACKFILL I
S ORIGI
NAL GROUND
B

C
C

I
F CHANNEL IS NOT EXCAVATED
C
B

CONCRETE SLOPE PAVI


NG
C C A A D D
C

C
C
C

C
B
C
B
EXCAVATI
ON BACKFI
LL
GROUND SURFACE AT SI
DE SLOPE
TI
ME STRUCTURE OR SUBGRADE
BACKFI
LL EXCAVATI
ON IS MADE
EXCAVATI
ON

C
ROADW AY ORI
GINAL GROUND
ORI
GINAL ORI
GINAL
EXCAVATI
ON GROUND GROUND

C
C

C
C

C
C
1’ C
C
C
C
1’ 1’ C
C C
C 1’ 1’ C
C
C
C
1’ 1’ C
C C
C
1’ ROADW AY
EMBANKMENT
SUBGRADE
SECTI
ON B-B
SECTI
ON A-A
ROADW AY SI
DE SLOPE
EXCAVATI
ON ORI
GINAL
OR SUBGRADE
ROADW AY SUBGRADE GROUND

C
GROUND SURFACE AT EMBANKMENT

C
TI
ME STRUCTURE

C
C
EXCAVATI
ON IS MADE

C
ORI
GINAL SUBGRADE
GROUND

C
SUBGRADE ROADW AY

C
EMBANKMENT

C
C
C C
C C C C
1’ C C 1’ 1’ C
C C
C
1’
1’ C C 1’ ROADW AY 1’ C C 1’
EXCAVATI
ON
SECTI
ON C-C SECTI
ON D-D
BRI
DGE ABUTMENTS & ADJOI
NING W I
NG W ALLS
LEGEND
STRUCTURE EXCAVATI
ON ROADW AY EXCAVATI
ON
STRUCTURE BACKFI
LL ROADW AY EMBANKMENT
DI
TCH & CHANNEL EXCAVATI
ON
NOTE:
SUBGRADE SHALL BE LOW EST SUBGRADE AS DEFI
NED
I
N THE STANDARD SPECIFICATIONS
SHEET 2 OF 2
RECOMMENDED BY THE CI
TY OF SAN DI
EGO
REVI
SION BY APPROVED DATE
STANDARDS COMMITTEE
CI
TY OF SAN DI
EGO - STANDARD DRAW I
NG
ORI
GINAL J.CASEY 6-3-83
1/
31/
2012
UPDATED KA J.NAGELVOORT 01/
12
COORDI
NATOR R.
C.E.65271 DATE
STRUCTURE EXCAVATI
ON
DRAW I
NG
& BACKFI
LL NUMBER
SDC-
103
FOR RETAINING WALL (6' MAXIMUM HEIGHT) I LEVEL BACKFILL,
REFER TO DEVELOPMENT SERVICES DEPARTMENT INFORMATION
BULLETIN NO. 221. (WWVV.SANDIEGO.GOV I DEVELOPMENT-SERVICES)

FOR RETAINING WALL (5' MAXIMUM HEIGHT) I SLOPING BACKFILL,


REFER TO DEVELOPMENT SERVICES DEPARTMENT INFORMATION
BULLETIN NO. 222. (WWVV.SANDIEGO.GOV I DEVELOPMENT-SERVICES)

FOR MASONRY FENCES (6' MAXIMUM HEIGHT), REFER TO


DEVELOPMENT SERVICES DEPARTMENT INFORMATION BULLETIN
NO. 223. (WWVV.SANDIEGO.GOV I DEVELOPMENT-SERVICES)

REVISION BY APPROVED DAlE RECOMMENDED BY THE CI1Y OF SAN DIEGO


STANDARDS COMMITTEE
CllY OF SAN DIEGO - STANDARD DRAWING
ORIGINAL KA ~. NAGELVOOR OVI2
,;II.~ 1/31/2012
COORDINATOR R.C.E. 65271 DAlE

MASONRY WALL DRAWING


NUMBER SDC-105
REFERENCES: FENCI
NG:
THIS DRAW I
NG IS TO BE USED I
N CONJUNCTION SAFETY FENCING SHALL BE INSTALLED AT THE TOP
WITH SAN DI EGO REGI
ONAL STANDARD DRAW I
NGS C-1 OF W ALL GREATER THAN 4'HIGH W HEN AREA BEHIND
THROUGH C-6 AND C-9 THROUGH C-15,AND CI TY OF THE W ALL I
S ACCESSIBLE TO THE PUBLIC OR
SAN DIEGO STANDARD DRAW ING SDC-108. MAINTENANCE CREW S.
DESI GN CONDI TI
ONS: I
NSPECTI ONS:
W ALLS ARE TO BE USED FOR THE LOADI NG CALL FOR I NSPECTI
ONS AS FOLLOW S:
CONDI TI
ONS SHOW N FOR EACH TYPE W ALL.DESI GN H A. W HEN THE FOOTI NG HAS BEEN FORMED,W I TH THE
SHALL NOT BE EXCEEDED.FOOTI NG KEY IS REQUIRED STEEL TIED SECURELY IN FI NAL POSITION,AND IS
EXCEPT AS SHOW N OTHERW I SE OR W HEN FOUND READY FOR THE CONCRETE TO BE PLACED.
UNNECESSARY BY THE ENGI NEER.SPECIAL FOOTI
NG B. W HERE CLEANOUT HOLES ARE NOT PROVI DED:
(1) AFTER THE BLOCKS HAVE BEEN LAI D UP TO A
DESIGN I S REQUIRED W HERE FOUNDATION MATERI AL
HEIGHT OF 4'OR FULL HEI GHT FOR W ALLS UP TO
IS I
NCAPABLE OF SUPPORTI NG TOE PRESSURE LISTED
5',W I
TH STEEL IN PLACE BUT BEFORE THE GROUT
IN TABLE.
I
S POURED AND. .
.
DESIGN DATA:
(2)AFTER THE FI RST LI
FT I
S PROPERLY GROUTED,THE
REI
NFORCED CONCRETE: BLOCKS HAVE BEEN LAI D UP TO THE TOP OF
Fc= 1,200 psi F'
c= 3,000 psi THE W ALL W I
TH THE STEEL TI ED SECURELY IN
Fs= 20,000 psi n= 10 PLACE BUT BEFORE THE UPPER LI FT I
S GROUTED.
REI
NFORCED MASONRY: W HERE CLEANOUT HOLES ARE PROVI DED:
F'm= 600 psi Fm= 200 psi AFTER THE BLOCKS HAVE BEEN LAI D UP TO
Fs= 20,
000 psi n= 50 THE TOP OF THE W ALL,W ITH THE STEEL TIED
EARTH= 120 pcfAND EQUI VALENT FLUID SECURELY IN PLACE,BUT BEFORE GROUTI NG.
PRESSURE= 36 psfPER FOOT OF HEI GHT. C. AFTER GROUTI NG IS COMPLETE AND AFTER ROCK
W ALLS SHOW N FOR 11/2:1UNLI MITED SLOPING OR RUBBLE W ALL DRAI NS ARE I N PLACE BUT
SURCHARHGE ARE DESI GNED I N ACCORDANCE BEFORE EARTH BACKFI LL I
S PLACED.
WITH RANKI NE'S FORMULA FOR UNLI MITED D. FINAL I NSPECTION W HEN ALL W ORK HAS BEEN
SLOPING SURCHARGE W I TH A ?=42°. COMPLETED.
REINFORCEM ENT: CONCRETE GROUT AND M ORTAR M I
XES:
INTERMEDIATE GRADE,HARD GRADE,OR RAI L STEEL CONCRETE GROUT SHALL ATTAI N A MI NIMUM
DEFORMATI ON SHALL CONFORM TO ASTM A615,A6161, COMPRESSI VE STRENGTH OF 2, 000 PSIIN 28 DAYS
A617.BARS SHALL LAP 40 DI
AMETERS,W HERE SPLI
CED, AND MORTAR SHALL ATTAI N 1,800 PSIIN 28 DAYS.
UNLESS OTHERW ISE SHOW N ON THE PLANS.BENDS ALL CELLS SHALL BE FI
LLED W ITH GROUT.ROD OR
SHALL CONFORM TO THE MANUAL OF STANDARD VI
BRATE CONSOLI DATION.BRING GROUT W I THIN 10
PRACTICE,A.C.
I.BACKI
NG FOR HOOKS I S FOUR MINUTES OF POURI NG TO ENSURE GROUT TO A
DIAMETERS.ALL BAR EMBEDMENTS ARE CLEAR POINT 2" FROM THE TOP OF MASONRY UNI TS W HEN
DISTANCES TO OUTSI DE OF BAR.SPACI
NG FOR GROUTING OF SECOND LI FT I
S TO BE CONTI NUED
PARALLEL BARS IS CENTER TO CENTER BARS. AT ANOTHER TI ME.
M ASONRY: M ORTAR KEY:
ALL REI
NFORCED MASONRY RETAINI
NG W ALLS SHALL TO ENSURE PROPER BONDI NG BETW EEN THE
FOOTING AND THE FI RST COURSE OF BLOCK,A
BE CONSTRUCTED OF REGULAR OR LIGHT W EI
GHT
MORTAR KEY SHALL BE FORMED BY EMBEDDI NG A
STANDARD UNITS CONFORMING TO THE "STANDARD
FLAT 2 X 4 FLUSH W ITH AND AT THE TOP OF THE
SPECIFI
CATI
ONS FOR PUBLI
C W ORKS CONSTRUCTION."
FRESHLY POURED FOOTI NG.THE 2 X 4 SHOULD BE
JOINTS: REMOVED AFTER THE CONCRETE HAS STARTED TO
VERTICAL CONTROL JOI
NTS SHALL BE PLACED AT 32'
HARDEN ( APPROXI MATELY 1HOUR) .A MORTAR KEY MAY
INTERVALS MAXI
MUM.JOI NTS SHALL BE DESI
GNED TO
BE OMITTED I F THE FIRST COURSE OF BLOCK I S SET
RESIST SHEAR AND OTHER LATERAL FORCES W HILE I
NTO THE FRESH CONCRETE W HEN THE FOOTI NG I S
PERMITTING LONGITUDI
NAL MOVEMENT.VERTI CAL POURED,AND A GOOD BOND I S OBTAI NED.
EXPANSION JOINTS SHALL BE PLACED AT 96'
W ALL DRAI NS:
INTERVALS MAXI
MUM.
W ALL DRAINS SHALL BE PROVI
DED IN ACCORDANCE
CONCRETE: WI TH STANDARD DRAW ING SDC-108.
FOOTING CONCRETE SHALL BE 560-C-3250,
DRAI
NAGE DI
TCHES:
USING TYPE B AGGREGATE W HEN PLACI NG
BROW DI TCHES W ILL BE REQUI RED ON SLOPED
CONDITIONS PERMI T.
BACKFI LLS.SDD 106 TYPE A W ITH THE MASONRY
BACKFI LL:
W ALL HEIGHTS ABOVE DI TCH TO BE AT A MI NIMUM
NO BACKFI LL MATERIAL SHALL BE PLACED AGAI NST
OF 1'.THE BROW DI TCH W ILL LEAD TO A W ALL
MASONRY RETAI NING W ALLS UNTIL GROUT HAS REACHED
DRAIN DETAI L AS SHOW N ON C-14.
DESIGN STRENGTH OR UNTI L GROUT HAS CURED FOR
A MINIMUM OF 28 DAYS.COMPACTI ON OF BACKFI LL SOIL:
MATERIAL BY JETTING OR PONDI NG W ITH W ATER W ILL ALL FOOTI
NGS SHALL EXTEND AT LEAST 12" I
NTO
UNDISTURBED NATURAL SOIL OR APPROVED
NOT BE PERMI TTED.EACH LAYER OF BACKFI LL SHALL BE
COMPACTED FILL.SOI
L SHOULD BE DAMPENED PRI OR
MOISTENED AS DI RECTED BY THE ENGI NEER AND
TO PLACING CONCRETE IN FOOTINGS.
THOROUGHLY TAMPED,ROLLED OR OTHERW I SE
COMPACTED UNTI L THE RELATI
VE COMPACTI NG I S NOT CABLE RAI LI
NG:
LESS THAN 90%. USE CALTRANS STANDARD PLAN B11-47.
RECOMMENDED BY THE CI
TY OF SAN DI
EGO
REVI
SION BY APPROVED DATE
STANDARDS COMMITTEE
CI
TY OF SAN DI
EGO - STANDARD DRAW I
NG
ORI
GINAL AR J.NAGELVOORT 02/
16
2/
25/
16
COORDI
NATOR R.
C.E.56523 DATE

RETAI
NING W ALL NOTES DRAW I
NG

NUMBER
SDC-
107
NO SURCHARGE LOADS
WITHI
N THIS AREA FOR
LEVEL BACKFI
LL DESI
GN
C
C
H

C
C

C
C
12"
12"

C
C
SEE NOTE 4
C 12"
C
FI
LTER MATERI
AL,1" MAX. C 12"
C
CRUSHED AGGREGATE.
H

C
6" MIN.
COVER

±6"

C FI
LTER MATERI
AL W RAPPED I
N TYPI
CAL SECTI
ON
GEOTEXTI
LE FI
LTER FABRIC SLOPED BACKFI
LL
C
C
C

C
C
C

4" DI
A.DRAI
N WITH 1/
4" GALV.
WIRE MESH SCREEN,8'ON
LI
NE OF CENTER,OR ONE HORI ZONTAL
UNDISTURBED ROW OF OPEN HEAD JOI NTS.
NATURAL SOIL
TYPI
CAL SECTI
ON
LEVEL BACKFI
LL
C 5 1/
4" 8" BLOCK W ALL
C

C 9" C 12" BLOCK W ALL


MORTAR OR CAST I
N
PLACE CONCRETE
1"

FI
NISHED
C VERTI
CAL
C
C

GROUND REI
NFORCEMENT
2"

C
C

H
C

C VERTI
CAL TOP OF
REI
NFORCEMENT FOOTI
NG
C GROUT FI
LLED
H

BLOCK CELLS
C
C

C
HORIZONTAL
C

REI
NFORCEMENT THRU
BOND BEAM BLOCK

2" X 4"
(NOMI NAL)KEY
CAP DETAI
L KEY DETAI
L

NOTES:

1.ALL MASONRY RETAI


NING W ALLS SHALL BE CONSTRUCTED W I
TH CAP,KEY AND DRAI
NAGE DETAI
LS AS SHOW N.

2.4" DI
AMETER DRAI
N MAY BE FORMED BY PLACI
NG A BLOCK ON I
T'S SI
DE.

3.ALL MASONRY W ALLS SHALL BE W ATERPROOFED W I


TH COAL TAR EMULSI
ON SYSTEM AS APPROVED BY THE CI
TY.

4.FOR MORE I
NFORMATI
ON SEE SDC-107.

5.I
F H I
S GREATER THAN 6 FT,THE RETAI
NING W ALL W I
LL NEED TO BE ENGI
NEERED AND DESI
GNED.

6.H= HEI
GHT.SEE PLANS FOR HEI
GHT AND FOOTI
NG DETAI
LS.

RECOMMENDED BY THE CI
TY OF SAN DI
EGO
REVI
SION BY APPROVED DATE
STANDARDS COMMITTEE
CI
TY OF SAN DI
EGO - STANDARD DRAW I
NG
ORI
GINAL AR J.NAGELVOORT 02/
16

2/
25/
16
COORDI
NATOR R.
C.E.56523 DATE

RETAI
NING W ALL DETAI
LS DRAW I
NG

NUMBER
SDC-
108
PLAN

H=8'-0" •I• H=5'-4" •I• H=3'-8" •I

..><:

..q-x o0
_I E::c
cX 10 •
co
E
X
c
E
=:.r
I
10
II
::c 0::
...J
u

D@ 12·
--==--#4
I
,., •,.,
ELEVATION lYPICAL SECTION
Horizontal reinf. not shown 5'-4" max
TYPICAL SECTION
over 5'-4"
DIMENSIONS AND REINFORCING STEEL
H (max) 3'-8" 5'-4" 8'-o"
T (min) o'-8" 0'-10" 1'-0"
W (min) 2'-4" 3'-6" 5'-4"
®Bars #4@32" #4@32" #4@32"
@Bars -- #4@32" #4@32"
©Bars -- -- #6@16"
©Bars #4 Total 4 #4 Total 5 #4 Total 6
max soil
500psf 600psf 800psf
pressure

NOTES: 1. See C-7 and C-8 for additional notes and details.
2. Fill all block cells with grout.
Revision By Approved Date RECOMMENDED BY THE SAN DIEGO
SAN DIEGO REGIONAL STANDARD DRAWING REGIONAL STANDARDS COMMITTEE
ORIGINAL Kercheval 2 75
Add Metric T. Stanton 03/03
Delete Metric S.S. T. Shell 03/11 MASONRY RETAINING WALL TYPE 1
(LEVEL BACKFILL) DRAW1NG
NUMBER C-1
PLAN
1 1/2 : 1 sloping backfill 1 1/2 : 1 sloping backfill
or 250/sf or 250 psf
live loa surcharge live load surcharge
H=5'-4" H=3'-8"

.
..q-
1

1'-6"

#4 §o 12"

#4 @ 12"
..., •.., lYPICAL SECTION
7 3'-8" max

w ELEVATION
Horizontal reinf. not shown
lYPICAL SECTION
over 3'-8" DIMENSIONS AND REINFORCING STEEL
H (max) 5'-4" 3'-8"
T (min) o'-1o" o'-1o·
W (min) 5'-o" 3'-9"
®Bars #4@16" --
@Bars #6@16" #4@16"
max sail
700psf 550psf
pressure

NOTES:
1. See C-7 and C-8 for additional notes and details.
2. Fill all block cells with grout.

Revision By Approved Date RECOMMENDED BY THE SAN DIEGO


SAN DIEGO REGIONAL STANDARD DRAWING REGIONAL STANDARDS COMMITTEE
ORIGINAL Kercheval 2 75
Add Metric T. Stanton 03/03
Delete Metric S.S. T. Shell 03/11 MASONRY RETAINING WALL TYPE 2
(LIVE LOAD SURCHARGE OR SLOPING BACKFILL) DRAW1NG
NUMBER C-2
PLAN

Mortar cop

X
c
E X
c
X ":q- E ~
C I 0

.
0
E in ":q-
I
::c
•0 It) co
I II
co c: ::I:
II .E
::I:
bars--~

@ bars ffi~~tfflt::!::;~l] 1-

1
1-
~=--z:;:~~ •..,

t------------1"'
.(..)

..., TYPICAL SECTION


5'-4" max
ELEVATION
TYPICAL SECTION Horizontal reinf. not shown
over 5'-4"

DIMENSIONS AND REINFORCING STEEL


H (max) 3'-8" 5'-4" 8'-o"
T (min) o'-8" 0'-10" 1'-o·
W (min) 2'-4" 3'-2" 4'-9"
®Bars #4@32" #4@32" #4032"
@Bars -- #4@32" #4032"
©Bars -- -- #6016"
@Bars #4@32" #4@16" #6016"
©Bars #4 total 4 #4 total 5 #4 total 6
max soil
pressure 1100psi 1600psi 2200psi

NOTES: 1. See C-7 and C-8 for additional notes and details.
2. Fill all block cells with grout.
Revision By Approved Date RECOMMENDED BY THE SAN DIEGO
SAN DIEGO REGIONAL STANDARD DRAWING REGIONAL STANDARDS COMMITTEE
ORIGINAL Kercheval 2 75
Add Metric T. Stanton 03/03
Delete Metric S.S. T. Shell 03/11 MASONRY RETAINING WALL TYPE 3
(LEVEL BACKFILL) DRAW1NG
NUMBER C-3
Layout Line

PLAN
1-1/2:1 sloping backfill or
---1-1/2:1 sloping backfill or 250 psf live load surcharge
250 psf live load surcharge

H=3'-8"

X X
c c
E .><
0
0 @Bars E ~
X
•CIO ::c =
CIO
0
::0
c I I
E 'N •CIO 'irJ ~
•..... ::c
II
I 2
in
II
::c
.Ec: .><0
•CIO ::c0
I
'N 1'-6"
4 lf@ 12"
w

lYPICAL SECTION
3'-8" max

ELEVATION
Horizontal reinf. not shown
w

lYPICAL SECTION
aver 3'-8"

DIMENSIONS AND REINFORCING STEEL


H (max) 5'-4" 3'-8"
T (min) 0'-10" 0'-8"
W (min) 4'-0" 3'-0"
@Bars #4016" #4016"
@Bars #6016" --
Surcharge sloping live load sloping live load
@Bars #608" #6016" #6016" #6016"
K (min) 1'-0" 0'-8" 1'-0" 0'-8"
Toe Press. 2700 psf 1900 psf 1700 psf 1430 psf

NOTES:
1. See C-7 and C-8 for additional notes and details.
2. Fill all block cells with grout.

Revision By Approved Date RECOMMENDED BY THE SAN DIEGO


SAN DIEGO REGIONAL STANDARD DRAWING REGIONAL STANDARDS COMMITTEE
ORIGINAL
Add Metric T. Stanton
Reformatted T. Stanton MASONRY RETAINING WALL TYPE 4
Delete Metric S.S. T. Shell DRAW1NG
(LIVE LOAD SURCHARGE OR SLOPING BACKFILL) C-4
NUMBER
Edge of Footing

Layout Line

PLAN
Mortar Cap

H=8'-o" H=5'-4" H=3'-8"

X
c
E ~
0
0
• :a
""'I" •110
X io
c II
E :::c
ixl
II
:::c .Ec:
•110
I
't-'1

I- w
~
lYPICAL SECTION
3'-8" max

lYPICAL SECTION ELEVATION


over 5'-4" Horizontal reinf. not shown

DIMENSIONS AND REINFORCING STEEL


H (max) 3'-8" 5'-4" 8'-0"
T (min) o'-8" o'-1o" 1'-o"
W (min) 2'-1" 3'-1" 4'-3"
R 0'-9" 1'-2" 1'-5"
s o'-8 1/2" 1'-1/2" 1'-7 1/2"
K 0'-8" 0'-8" 1'-0"
®Bars #4@32" #4032" #4032"
@Bars -- #4032" #4032"
@Bars -- -- #7016"
@Bars #4@32" #4016" #4016"
®ears #4 total 5 #4 total 5 #4 total 6
Max Toe
774 psf 1,030 psf 1,660 psf
Pressure

NOTES:
1. See C-7 and C-8 for additional notes and details.
2. Fill all block cells with grout.

Revision By Approved Date RECOMMENDED BY THE SAN DIEGO


SAN DIEGO REGIONAL STANDARD DRAWING REGIONAL STANDARDS COMMITTEE
ORIGINAL Parkinson 2 95
Add Metric T. Stanton 03/03
Delete Metric S.S. T. Shell 03/11 MASONRY RETAINING WALL TYPE 5
(LEVEL BACKFILL) DRAW1NG
NUMBER C-5
Edge of Footing

Layout Line

PLAN
1-1/2:1 sloping backfill or
1-1/2:1 sloping backfill or
250 psf live load
250 psf live load surcharge
surcharge

Mortar Cap H=3'-8~

I· ·I
)(
)(
c ~
c
E u0 1/4 total E~
u
•co ::0 • 0
c • I •co
)(
@Bars--H ,::0
E t'l
• 7~
::c
""'I"
io r::::
II
::c
.E
@Bars

w
lYPICAL SECTION
3'-8~ max
•t'l

w ELEVATION
Horizontal reinf. not shown
lYPICAL SECTION
over 3'-8~

DIMENSIONS AND REINFORCING STEEL


H (max) 5'-4. 3'-8"
T (min) 0'-10" 0'-8"
W (min) 3'-10" 2'-9"
®ears #4016" --
@Bars #6016" #4016~

Max Toe
2,000 psf 1,400 psf
Pressure

NOTES:
1. See C-7 and C-8 for additional notes and details.
2. Fill all block cells with grout.

Revision By Approved Date RECOMMENDED BY THE SAN DIEGO


SAN DIEGO REGIONAL STANDARD DRAWING REGIONAL STANDARDS COMMITTEE
ORIGINAL Parkinson 2/95
Add Metric T. Stanton 03/03
Delete Metri S.S. T. Shell 03/11 MASONRY RETAINING WALL TYPE 6
(LIVE LOAD SURCHARGE OR SLOPING BACKFILL) DRAW1NG
NUMBER C-6
1'-o"
1" Chamfer

Chamfer
There shall be no
loadings extending
I
......II
.Ec above top of wall
..r::. within a distance
•0 equal to height of
'Q)
I .......I the wall.

TYPE-A WALL
(Applicable for all types
of backfill loadings)
I.
H/2+10"
.I I. H/2

TYPE-8 WALL TYPE-C WALL

Expansion joint @ 30' -0"±


centers (max) and/or @ Finished Ground Line
each step.

Oc Level Reference
I·-
~E

ELEVATION

WALL CONCRETE
HEIGHT BASE
TYPE CF/FT
1'-6" 1'-o" 1.50 cu ft.
A
2'-o" 1'-0" 2.00 cu ft.
3'-o" 2'-4" 4.99 cu ft.
4'-o" 2'-10" 7.66 cu ft.
B
5'-o" 3'-4" 10.82 cu ft.
6'-o" 3'-10" 14.49 cu ft.
3'-0" 1'-6" 3.75 cu ft.
4'-o"
c 5'-0"
2'-0"
2'-6"
6.00 cu ft.
8.75 cu ft.
6'-o" 3'-o" 12.00 cu ft.

NOTE:
See C-1 0 for Section A-A, notes and details.

Revision By Approved Date RECOMMENDED BY THE SAN DIEGO


SAN DIEGO REGIONAL STANDARD DRAWING REGIONAL STANDARDS COMMITTEE
ORIGINAL Kercheval 12 75
Add Metric T. Stanton 03/03
Delete Metric s.s. T. Shell 03/11
GRAVITY RETAINING WALLS
DRAW1NG
NUMBER C-9
CONCRETE
Concrete shall be 560-C-3250. Top extension if specified

Filler Material: 1" max crushed


DESIGN CONDITIONS aggregate 4 cu. ft. min at each
Walls are to be used for the loading drain.
conditions shown for each type wall.
Design H may be xceeded by six 4" dia. drains with 1/4" galv. wire
inches before going to next size. mesh screen, 8" above outside
ground surface, slope 1/2" per ft.
DESIGN DATA Locate drains @ 15' -0" center to
Fe = 1200 psi center or as directed by the
F' c = 3000 psi Engineer.
Earth = 120 pcf
and equivalent fluid pressure = 36 psf per
foot of height TYPICAL DRAINAGE
WHEN H IS GREATER
Walls shown for 1-1/2:1 unlimited sloping THAN 4'-0"
sucharge are designed in accordance with
Rankine's Formula for unlimited sloping
surcharge with f/J = 42'. 1/2" Expansion joint, fill with premolded
Note: Maximum toe pressure under wall expansion joint filler. Locate joints at approx.
footing = 1-1/2 tons/sq. ft. Special 30' -0" centers or as directed by the Engineer.
design required where footing material is
incapable of supporting this pressure.

EXCAVATION AND BACKFILL


Compaction of backfill material by jetting or
ponding with water will not be permitted.
1/2" Water stop, use only when
Each layer of backfill shall be moistened as chamfer watertight joint is required,
directed by the Engineer and thoroughly see water stop detail.
tamped, rolled or otherwise compacted until
the relative compaction is not less than 90 SECTION A-A
percent.

No backfill material shall be deposited against


concrete retaining walls until the concrete has
developed a strength of 2,500 psi in
compression as determined by test cylinders, Embedment 2-3/8"
or until 28 days after wall has been placed .
l_c_ "I"
.s
3/8" d1a. :3/8"
RUBBER WATERSTOP

\_Split permitted

Use only when watertight


joint is required.

Revision By Approved Date RECOMMENDED BY THE SAN DIEGO


SAN DIEGO REGIONAL STANDARD DRAWING REGIONAL STANDARDS COMMITTEE
ORIGINAL Kercheval 2 75
Add Metric T. Stanton 03/03
Delete Metric S.S. T. Shell 03/11 GENERAL NOTES AND DETAILS
FOR GRAVITY RETAINING WALLS DRAW1NG
NUMBER C-10
H=30'

H=28'

~
..-H-=_26---i' V-i ~

H=22'
b

--
I
b
H=20'
'b I c-.~
I
~

H=18' ~~ 1
1-"~ 15'+3"
Number above(£) ~---""VI 14'-6" 14'-9" ,~....__short@
bars indicates
H=16'
J,_ v vV
12'-6"
13'-o" 1
,__...., 1- 1-
1-1- 1-
distance from top
H=14' ~v ~---'"'" 1--1 .,
of footing to ~--~ 11'-6" ~
upper end of(£)
bars.
H=12' 1--i--'~11 'b ~ J f.-~ ~
I~ ~vi\ 11'-o· J t!.. 1-h ~t;.. 11'-o·

10·-~:. v-~6 ~~~..


1
H=1o· 1 1 ._ ..
9 6
11 : 9'-6"

H=8' a·-o· ~ 4JI~e- a'-o'

H=6'
1\
I.J.---- ~J..--
IU 5' -6"
1-- •
6 -0
.. I 6' -6"
I
7' -6"
1-1-1- i-1- r
,_ j-1-1-

H=4' 5'-o" I I..... ~~--


~ f-l-j1
1--1- 1- f-
~~ ~
1 I' Bundle
V @bars

Y,..~ ~ ,.lf ?,.T :f ~ .~LV~ 8 1/2" 8"

ELEVATION

NOTES:
1. For SPREAD FOOTING SECTION see C-11 B
2. For TYPICAL LAYOUT EXAMPLE see C-11C
3. For 45T PILE FOOTING SECTION see C-11C
4. For TABLE OF REINFORCING STEEL DIMENSIONS AND DATA see C-11 D

Revision By Approved Date RECOMMENDED BY THE SAN DIEGO


SAN DIEGO REGIONAL STANDARD DRAWING REGIONAL STANDARDS COMMITTEE
ORIGINAL Kercheval 12/75

~-~:~:. . .etMeM. . ,. t~. . ,. i;i+cs-.4s ~:. . .: :. :.:~:-~ t_on-+~. . .:~ -~- ~ REINF 0 RCED
....... ....... ........ CONCRETE RETAINING WALL l-c:.;,;~-=~ pe:.:. :rs=a"~R.-=c.;.:;. :E19:. :.; . ;.: .6;.r.z:.: . :.~:.:. :.e_- l
.

TYPE 1 DRAW1NG
C-11A
NUMBER
For design limits of
surcharge and slope see
"Retaining Wall Details
No. 1"

of slope intersection
Appropriate details at top
of wall are shown
elsewhere.
#4@ 18"

:::c
c:
0"1
·u;
GJ
0

C=1'-o"
IF H=20' to 30'
C=2'-6"

for H ~10'

SPREAD FOOTING SECTION

NOTES:
1. For details not shown and drainage notes see "Retaining Wall Details No.1".
Standard Drawings C-13A to C-13D.
2. Quantities apply to Design H portion and exclude the added portion above "Gutter Elevation".

Revision By Approved Date RECOMMENDED BY THE SAN DIEGO


SAN DIEGO REGIONAL STANDARD DRAWING REGIONAL STANDARDS COMMITTEE
ORIGINAL Kercheval 12/75

7(Z6(ZOIZ

DRAW1NG
NUMBER C-118
.-------Top of Wall
Use Reinforcement
for H= 16' Optional Footing Line
Top of Slope ---
...
'b
I
•co 'b Layout Line
I
I a, II
0 :;;::
N

Co
----
I C=3'-8" 8=7'-4"
Top of N
•.,.j- Footing
1

TYPICAL LAYOUT EXAMPLE


For joints required, see Details 3-3 and 3-4, drawing C-15

~ _.
Q)

#4 @ 18± lap (.) ~


c:: u
with @bars 0 #4 @ 18± lap c
0
c B
(_)
with tal bars (.)
.....
w c B 0

w Q)
_.
Q)
(/)

45T PILE FOOTING SECTION 45T PILE FOOTING SECTION


H=24' Thru H=30' H=4' Thru H=22'

Revision RECOMMENDED BY lHE SAN DIEGO


SAN DIEGO REGIONAL STANDARD DRAWING REGIONAL STANDARDS COMMITTEE
ORIGINAL
Add Metric 7(Z6(ZOIZ
Delete Metric S.S. T. Shell

DRAWING
NUMBER C-11C
c 0
CD ~ ::::0
a. :;o CD
~ ;;:: G) s.
Cl)
s::: ~ (5' TABLE OF REINFORCING STEEL DIMENSIONS AND DATA
!a. :::1.
n ~ ::I
1l· r Design H *4' 6' 8' 10' 12' 14' 16' 18' 20' 22' 24' 26' 28' 30'
Ul CJ
fn '"< w 3'-2" 4'-2" 5'-2" 6'-2" 7'-2" 8'-o" 9'-o" 10'-0" 11' -0" 12'-0" 13'-3" 14'-3" 15'-3" 16'-9"
;-1 ;-1 A >
ID '"0
Ul '"0
::r ~ c 1'-0" 1'-4" 1'-8" 2'-0" 2'-4" 2'-8" 3'-0" 3'-4" 3'-8" 4'-0" 4'-5" 4'-9" 5'-1" 5'-5"
g, :::J~ :::T 0
csS"
:::J
-~ c.. B 2'-2" 2'-10" 3'-6" 4'-2" 4'-10" 5'-4" 6'-0" 6'-8" 7'-4" 8'-0" 8'-10" 9'-6" 10'-2" 11'-4"
0 0 0
t.l c t.l

CD
~ a ~ .....
t.l
F Spread Ftg. 1'-2" 1'-2" 1'-2" 1'-2" 1'-2" 1'-3" 1'-3" 1'-4" 1'-4" 1'-6" 1'-8" ,._,,. 2'-2" 2'-4"

en Batter 1/2:12 1/2:12 1/2:12 1/2:12 1/2:12 1/2:12 1/2:12 1/2:12 1/2:12 1/2:12 5/8:12 3/4:12 3/4:12 7/8:12
m
= :1>
-z: z
"T1 - - - - - - - - - - - #6@24 #6@17 #6@16
0 !2 @bars
m
G)
0= 0 @bars
m - - - - #4@18 #6@30 #6@22 #7@22 #8@20 #8@16 #8@14 #8@12 #BOB-1/2 #8@8
c ::u
m
0 G)
0 @bars
0 #5@24 #5@24 #5@16 #5@9 #6@9 #9@15 #9@11 w10@11 U11®10 #11@8 #11@7 #11@6 W100B-1/2l #10@811
--IZ z
-<0 :1>
"'CCI::::ICI r-
mm @bars
en #5@24 #5@24 #4@16 #4@9 #5@9 #8@15 #8@11 #10@11 #10@11 #10@8 #10@7 #10@6 #9@8-1/211 #9@811
-rri -1
:1>
z Tatal@ bars 6-#6 6-#6 10-#7 10-#7 10-#7 10-#7 6-#7 6-#7 6-#7 6-#7 4-#7 4-#7 4-#7 4-#7
m c
=
..... :1>
::ltl Total <D bars
> c 4-#7 4-#7 4-#7 4-#7 4-#7 4-#7 4-#7 2-#7 2-#7 2-#7 2-#7
3!: c 2' Level Toe
z: ::ltl 5.3
C) :1> surcharge Pressure k/sf 1.6 1.9 2.2 2.3 2.8 3.3 3.5 4.0 4.3 4.6 4.9 5.7 6.2
~ 2:1 Toe
::e z unlimited Pressure k/ sf 1.1 1.5 2.0 2.5 2.7 3.3 3.6 4.2 4.7 5.5 5.9 6.5 7.1 7.5
G) slope
> 1-1/2:1 Toe
!::: limited 1.3 1.7 2.1 2.5 2.9 3.4 3.8 4.3 4.8 5.4 5.8 6.5 7.2 7.5
(") slope Pressure k/ sf
:z:o ~
c: ::::0 .:a oO 147 449
s::::::> ~ zS:::: 17 20 28 37 51 80 105 187 246 303 407 507
CJ~ >I:
8R Spread Steel lbs/ft.
rrl:z: "'0
:::J
r!;2
:::CG') cno Footing 77.0 104.8
:;o 8.9 12.5 16.3 20.2 25.4 30.1 34.6 40.1 45.0 52.1 63.3 88.1
p
!""
I ~8
z
Cal
>-<
:;o
Cone cf/ft
29 32 41 70 84 113 140 172 212 270 322 427 469 528
0I <0 Steel lbs/ft.
"'
~ :7::!!
fT1
Pile ftg.
~ ~ 8~ 10.2 12.7 16.7 20.8 25.2 30.1 34.8 40.6 45.7 53.1 64.7 78.6 89.9 107.0
c Cone cf/ft
0 ~ ~z
- c
~ ~ ffi~ Note: Reinforcement detailed is to be placed in addition to that shown for spread footing. All piles not shown,
0 see Pile Layout on plans. *For pile footing Design H=4' use same footing dimensions as Design H=6' HDenotes a bundle of 2 bars
CASE I ,/;--CASE II
Place 1'-o" 2' -0" ,/"~ 2:1 Slope
Gutter elev or
toe of slope waterstop as Surchag~,, unlimited
#4@18" intersection shown when ~ Gutter El. or Toe of
Vertical required
Slope intersection
#4@36" -.~~...- Backfill
sufficiently to
0
prevent pending
C1l To be done
en
..a·
::I
after removal of
I
wall forms and
before backfilling Design H
:a behind walls
en
m :1>
z z
'T1
0 2
:a m
C) +
0 0 3"
m CLR J #4
c ;:ltl
m Total 7
0 C)
..... o 0z c B DESIGN
-<z w For drainage notes and other
.,o :1> details, see "Retaining Wall Details
m::a r-
m en SPREAD FOO]NG SEC]ON No.1" Drawing C-13A to C-13D
..... -1
> m
- :1> Place concrete in toe against undisturbed material, Numbers above © bars H=12'
:a z except as permitted by the Engineer. indicate distance from
m c
..... :1> NOTES: top of footing to upper H=10'
;:ltl end of© bars
:!:: c Design H may be exceeded by 6" before going to the next size. Footing
key is required except when found unnecessary by Engineer.
~ c Special footing design is required where foundation material is incapable of H=8'
z ;:ltl
C) :1> supporting toe pressure loads listed in table.
:e Design Data: H=6'
z
C) fc = 1300 psi f'c= 3250 psi fs= 24,000 psi n= 10 earth 120 pcf

Case I - Equivalent fluid pressure= 36 psf max for determination of toe H=4'
- ::0::0

pressure. 27 psf min for determination of heel pressure.
~§ ~
0~ 3'-3" ~hart©
z~ Case II - Earth pressure determined from Rankine's formula with 3'-o"
~!:2 0 = 33"-42'.
1110
~
U-
f-t---l-1 ~
~8
zm
~-< NOTE:
0 L_
I ~:I!
lllfT'I Reinforcement detailed is to be placed in addition to that
~ v v ~ 'II
1\) ~ 0111 shown for spread footing. All piles not shown. see Pile 24" 22" 11" g" "'¥/
~~ 7 1/2"
~
-
> ~i\;
~~
Layout on plans. ELEVA] ON
fT18
Cl
!L ~ 0 ::::0
~ a. :::0 CD
CD ;;:: G') :S.
;r: <D C/)
o· Use Reinforcement for H= 6' 8' 10'
~ c;· ~
n "~ p - T o p of Wall
Vl
CD CD @ 8" ®@ 8"
0 '< Top;fWoll~ -- ~
;-i ;-i >
:><: ~
CD
gl ~
c n ~ -+- ·l_
~ ----
- ---:1
~
~ ~ X ..
.f ~
~ :::J :::r 0 Vr Construction joint 0
C) ~ 11 • I o -co,E ~
:::J [ c.. 10 bars =x'
~ ~ v{ <olE 2E
0 0 0 4 bars?J
c H 6 bars
~ "' I \ ::::::;; :::c Top of Footing
~§ -CD .....,
. I
___ .._.-=1 __ ~#4@18"
~~~
~
~
I.
1- 'b N I Optional Footing Line~
::ICI en en I ~

..5!:! "N
m :1> a: ---
z z
..'!l
-· -- 'b
"TT ~ L+J :_, .NI~ -N ,I R
~I
..
I ~I
I
2 u B- u I o Layout Line ' - "N ":..t- Co
0 c I N II
::ICI
m
C) u
0

~
Lf! w 'ln
":..t-1 ,-
f---~1-.;.!._-.::::::::::::. u
~,
~'
0
0 0 --- ~~
m a:; ~ Note:
c ;:ltl ..'!l I
(/) ~
m Bar cut-offs may be varied
0 C)
in increments of 6"
...,.o 0z 45T PILE FOOTING SECTION
-<z TYPICAL LAYOUT EXAMPLE
"'Co :1>
m= r- For joints required, see Details 3-3 and 3-4,
m en Std Dwg C-15
.........
>m -1
:1> TABLE OF REINFORCING STEEL DIMENSIONS AND DATA
::ICI z
m c Design H * 4' 6' 8' 10' 12'
..... :1> w 3'-2" 4'-2" 5'-2" 6'-2'' 7'-2"
;:ltl
> c c 1'-0" 1'-4" 1'-8" 2'-o· 2'-4"
z c B 2'-2" 2'-10" 3'-6" 4'-2" 4'-10"
z ;:ltl
C)
:1>
~ ©bars #5@24" #5@22" #5@11" #6@9" #7@7-1/2"
~ z
C)
@bars #5@24" #5@22" #5@22" #7@18" #8@15
r- Total ® bars 6-#6 6-#6 6-#6 10-#7 10-#7
r-
0
Total CD bars 4-#7 4-#7
:z:o I~ Case I - Toe Press. 1590psf 1930psf 2240psf 2550psf 2840psf
c: ::::0-tl O;r::
s:::::> z;r:: Case II - Toe Press. 1060psf 1460psf 1860psf 2280psf 2700psf
c:o:§ !!lrn >rrl
rrl:z: 0 rz
:::J Spread f>teel lbs/ft 151b 211b 271b 461b 701b
:::CG">
::0
~ a§ 1110
8.61b 11.81b 14.91b 18.11b 21.31b
~8 Footing ~one CF/ft
~ z
['1 Cal 251b 321b 381b 751b 1011b
>-<
::0 Pile Ftg f:i~eel lbs/ft
0I <0 ronc CF/ft 9.91b 11.91b 15.31b 18.81b 22.21b
.... "'
~ :7::!!
rr1
1"1.) ~ ~ 8111
lCD 0
~ ;r::~ Note:
1::> ;r::
c
<D i\; ~~ Quantities apply to Design H portion and exclude the added portion above
m8 "Gutter Elevation". *For pile footing Design H=4' use same footing dimensions as Design H=6'.
Place waterstop
as shown when
required
FG
1" chamfer
Backfill sufficiently to
prevent pending. To be 11-1/2"
done after removal of
wall forms and before FG~
ackfilling behind wall

I 1/2"
c: Exp jt if
01
"iii required
Q)
Cl

Standard batter

Place concrete Dimensions CD ,


@ and G) to be as shown
in toe against elsewhere in the project plans
undisturbed
material except 3" f/J Holes @ Stem width at base of haunch to be
as permitted by _ _ __., when ordered determined as shown
the Engineer by the Engineer
DESIGN AND DRAINAGE STEM WIDTH AT BASE OF HAUNCH

Level + 2'
surcharge

-....::::-----------
20' VC AT TOP OF CASE I
WALL SLOPE CHANGE
Where shown on the plans
surcharge

CASE JI[
- H=4' to 22'
1'-6"
H=24' to 36'
DETAIL OF DESIGN LOADING CASES
I
CASE I Level + 2' surcharge
I
~
;... I
7 CASE JI 2:1 unlimited slope
I
- 1--·
I
"" ~Layout
·-
line
CASE JI[ 1-1/2:1 limited slope (7' -0" max
I
height) + 2' surcharge

FOOTING STEP NOTE: Surcharge limits shown apply to


retaining walls Type 1 and 3
Revision By Approved Date RECOMMENDED BY THE SAN DIEGO
SAN DIEGO REGIONAL STANDARD DRAWING REGIONAL STANDARDS COt.lt.IITTEE
ORIGINAL Kercheval 12 75
Add Metric T. Stanton 03/03
Delete Metric S.S. T. Shell 03/11 REINFORCED CONCRETE
RETAINING WALL DETAILS No. 1 DRAWING
NUMBER C-13A
(Top of wall level
FG 2-#4l:l ~·_,--=.L_""""'-~L-
n•n' ,;d, ~11;: 14' mn• ~ '~ LOL

"-... --- -- 1~~ Top of wall level1

,~ '-..r--.
. . ,'/<_.~~+~:=r~ 2-#4@18"
I - FG near side
.1 3'-o"
u--J.-- LOL
18" mirJ i-..::::. I'--- :
"'1-l=~-lr-i- r-- 2- #4
Il-l-++-++;- b_ ~-b_ Total 4

T_____ j n
4'-0"
ELEVATION
ELEVATION RETURN WALL TYPE D
Use where H=6' or less
RETURN WALL TYPE A
Use where H=8' or less

2-#4l_1 r·--:;--;16;-;-'~m::a::-:::x~~~---Top
L of wall levelr-·I~LOL L
10' max LOL
FG ' I it=::::;::::=t====t====t====t~=i FG near side 1
-~~l.'L_+--+--+-+-+~I1f-
0
1
near side __ r==.==~=1J:::jf=
.=t==t==t==tF:=
'' 2-#4"--- 0 • "1\\~ f--t---t---+---ttl-
- -- h
!'-..._ 1- """[I-~ ,.M I r-

_.___ _""T t ~ ~~ I 1' -6" mi f ~ th


!.._~:";::::::<~~,'I:::::::.H--l-1---t-14----1-.._-i_,_1-=+-2-#4@18"
1' -6" min _j
11
2 ~~@
18 .. ___. 1--~~ I'
Offset -----j-1tJ14'--+-tl_ ~
1'-0" min / 1- I
6'
-
o"
max~~
/ '/
II -
~;~o~
1 r

ELEVATION ELEVATION
RETURN WALL TYPE B RETURN WALL TYPE C
Use where H= 10' or more on offset walls Use where H= 10' or
more on straight walls

Revision By Approved Date RECOMMENDED BY THE SAN DIEGO


SAN DIEGO REGIONAL STANDARD DRAWING REGIONAL STANDARDS COMMITTEE
ORIGINAL Kercheval12/75
Add Metric T. Stanton 03/03 ~7(Z6/ZOfZ
Delete Metric S.S T. Shell 03/11 REINFORCED CONCRETE C~rperson R.C.E. 19246 Date

RETAINING WALL DETAILS No. 1 DRAW1NG C-13C


NUMBER
1-1 /2"
Premolded
expansion
joint PLAN OF WALL WITH DETAIL 3-4
filler-----.. (see C-15)

I
I
I

PLAN OF WALL WITH EXPANSION JOINT ONLY

Offset as follows:
H 4'=1/4"
Vertical
H 6'=3/8"
LOL /7 H 8'=1/2"
it H 10'=5/8"
/ / H 12'=3/4"
/ H 14'=1"
Stem as L' ' H 16'=1-1 /4"
constructed
--h,'H"T/ H 18'=1-1/2"
/ / H 20'=1-3/4"
I I H 22'=2"
H 24'=2-1/4"
H 26' thru 36'=2-1/2"

APPROX. WALL OFFSET VALUES


Not required for wall Types 3 and 4.
Values for offsetting forms to be determined by the Engineer.

NOTES
Design Conditions:
Design H may be exceeded by 6" before going to the next size. Special footing design is
required where foundation material is incapable of supporting toe pressure listed in table.
Return wall not required unless shown elsewhere.
Design Data:
fc = 1300 psi f' c = 3250 psi fs = 24,000 psi
n = 10 earth = 120 pcf
2' Surcharge:
Equivalent fluid pressure =
36 pcf maximum for determination of toe pressure.
27 pcf minimum for determination of heel pressure.

Earth pressures for 2:1 unlimited slope, 1-1/2:1 slope, and 1-1/2:1 unlimited slope,
determined from Rankine's formula with ¢=33"-42'.

Revision By Approved Date RECOMMENDED BY THE SAN DIEGO


SAN DIEGO REGIONAL STANDARD DRAWING REGIONAL STANDARDS COMMITTEE
ORIGINAL Kercheval12/75
Add Metric T. Stanton 03/03 ~ 7(Z6/ZOfZ
Delete Metric S.S. T. Shell 03/11 REINFORCED CONCRETE Ch6irperson R.C.E. 19246 Date

RETAINING WALL DETAILS No. 1 DRAW1NG


NUMBER C-13D
3" x 1'-o·
Overflow scupper where shown
on plans

RETAINING WALL,
FACE OF WALL OUTLET RETAINING WALL, GUTTER OUTLET WALL DRAIN DETAIL

Top of wall

Gutter FL

WALL DRAINAGE
PLAN-OFFSET WALL PLAN-CONTINUOUS WALL WHERE GUTTER NOT REQUIRED
DRAIN THROUGH RETURN WALL SECTION A-A

-
5"
·e
1:
3"J 2'-0" l .5
3-1/2"
E
'0
I
-;...
J 2" 1'-o· 2· I -:...
.I
~
min

.;

""~
r-::....
."" \I
r,·
j

4._j
- -~'---
~

"'-
"
·c:

Gutter
el evation
Rectangular
opening

Area of opening to be not less than that of pipe from


wall gutter. Make oeening transition in wall. Edge opening
in curb face to 3/4 minimum radius.
OUTLET DETAIL - SECTION 8-8
TYPICAL GUTTER DETAIL

~~4.
- - - ,.... ~~
, .? ~
~
48" max
reinf

standard vertical reinforcement plus additional vertical


bars corresponding in size and number to bars
cut by the opening. Place half on each side.
Extend the additional bars into the footing
the same as ather vertical wall reinforcement and to
a minimum of 60 bar diameters above the top
of utility opening if wall height permits.
tilH!11Hl PJ Bundle bars as required.
Horizontal reinf to be standard except as shown.
GRATE DETAIL All reinf to clear opening by 2" minimum.
Sizes to fit standard hubs Expansion joints shall not be located within
the limits of special reinforcing.
2-#8x{A+4'-0") Total 4
{omit for "A" less than 12")

RETAINING WALL UTILITY OPENING


Max size of opening {A) = 48" to be used in conjunction with C-13

Revision By Approved Date RECOMMENDED BY THE SAN DIEGO


SAN DIEGO REGIONAL STANDARD DRAWING REGIONAL STANDARDS COMMITTEE
ORIGINAL Kercheval 12 7
Add Metric T. Stanton 03/03
Delete Metric S.S. T. Shell 03/11 REINFORCED CONCRETE Date

RETAINING WALL DETAILS No. 2 DRAW1NG


NUMBER C-14
6" min
See note D Joint may be formed with
#4 x 2'-o· Cut or butt every 1/8" hardboard and cut back
total 2 ea face other front face to the root of the chamfer
on the exposed face.
horizontal bar~
detail 3-2
.:>;..:·. ·~:·•·. 3/4"
1-1/2J·:.:.:.~~~ :fer
8
See note B
--~
note C
' - - See detail A .
SECTION DETAIL A

WEAKENED PLANES
DETAIL 3-2

ELEVATION SECTION

WEEP HOLE AND PERVIOUS BACKFILL


Top of wall~
DETAIL 3-1 , \ 96' max
Detail 3-~~~ ~-=--------11
Detail 3-1 10~• f• ~Detail 3-2
f---o::ll.--+-"-ll..,_._ _._f_ ..... Detail 3-4
V
[;f-"'1•

1" min Top of footing


NOTES
max
A. 4" diameter drain 0 25' max center to center {9' c-c for Type 3 and 9'-3"
c-c for Type 4 Retaining Walls). For walls adjacent to sidewalks or curbs,
WALL EXPANSION JOINTS
provide 4 • cast iron or asbestos cement pipe under the sidewalk to discharge
thru curb face. Exposed wall drains shall be located 3" ± above finished grade. AND WEAKENED PLANES
DETAIL 3-3
B. 6" square aluminum or galvanized steel wire 4 mesh hardware cloth. {Min wire
diameter 0.03") Anchor firmly to backface.

C. One cubic foot pervious backfill material in a burlap sack, securely tied.

D. Pervious backfill material continuous behind retaining wall.


Waterstop to have 5 or more
pairs of raised ribs to provide
0. 1 sq in min rib cross-section
1/2" premolded area on each half of the water
expansion joint filler stop. Height of ribs to be
unless other thickness 3/32" min.
and/or material is
shown elsewhere

13 Ba

Holes will be permitted in the outer 1/2"


of the web for wire, rings etc.
Tie web to 13 reinforcing bars 0 12" max
WALL EXPANSION JOINT intervals to support the waterstop in
WATERSTOP proper position during concrete placement.
DETAIL 3-4 DETAIL 3-6 Alternative detail may be submitted for
approval of the engineer.

Revision By Approved Date RECOMMENDED BY THE SAN DIEGO


SAN DIEGO REGIONAL STANDARD DRAWING REGIONAL STANDARDS COMMITTEE
ORIGINAL Kercheval 12 75
Add Metric T. Stanton 03/03
Delete Metric S.S. T. Shell 03/11 REINFORCED CONCRETE Date

RETAINING WALL DETAILS No. 3 DRAW1NG


NUMBER C-15
CHAPTER 2
DRAINAGE
SYSTEM
8" MIN PCC PAVEMENT 560-C-3250

FLOW

3'MIN

2'MIN
PIPE SHALL BE ENCASED

_J 2 • LBonoM OF 12·
CUT OFF WALL
WITH 6'' OF 420-A-2000 PCC
#4 BARS@
18" VERT & HORIZ
SECTION A- A

NOTE: B_j
1. RIP RAP PER SD0-104 & STANDARD
SPECIAL PROVISIONS

2. METAL BEAM GUARD RAIL


SHALL HAVE Wl6 x 9 STEEL POST

3. SIDEWALK, CURB, PAVEMENT AND


HEADWALL'S SHALL BE TIED WITH PLAN
#4 BARS 18" OC HORIZONTAL
AND VERTICAL

4. CONCRETE JOINTS PER SDG-109 AND G-10


SHEET 1 OF 2

REVISION BY APPROVED DATE RECOMMENDED BY THE Ct1Y OF SAN DIEGO


STANDARDS COMMITTEE
CllY OF SAN DIEGO - STANDARD DRAWING
oil~
ORJGINAL J . CASEY 06'83
1/31/2012
UPDATED KA . NAGELVOOR OV12
COORDINATOR R.C.E. 65271 DATE

TYPICAL FORD DRAWING


NUMBER
SDD-101
CURB OUTLET

HEADWALL
560-A-3250 PCC

CUTOFF WALL
560-A-3250--------<-l \GUITER UNE

#4 BARS 18" OC
HORIZONTAL AND VERTICAL

SECTION B-B

·I· SECTION

NOTE:
1. HEADWALL LENGTH (L) PER D-30, D-31

SHEET 2 OF 2

REVISION BY APPROVED DATE RECOMMENDED BY THE CITY OF SAN DIEGO


STANDARDS COMMITTEE
CllY OF SAN DIEGO - STANDARD DRAWING
oil~
ORJGINAL J . CASEY 06'83
1/31/2012
UPDATED KA . NAGELVOO OV12
COORDINATOR R.C.E. 65271 DATE

TYPICAL FORD DRAWING


NUMBER
SDD-101
4" X 3" X 3-8"

V2" 0 ANCHOR BAR


@ 3'0C MAX PROTECTION
BAR

1" 0 SUPPORT BOLT

. 4

<1 . <1
4 . . 4 ..
4 '
' q ' q

<1 ·
·4 ·4
4. <\ :

I- 6"-12"
-I
NOTES:

1. FACE ANGLE SHALL BE CAST INTO STRUCTURE CONTINUOUS FOR THE FULL LENGHT "L".

2. EXPOSED METAL PARTS SHALL BE HOT-DIPPED GALVANIZED AFTER FABRICATION.

3. WHEN CURB INLET OPENING HEIGHT {H) EXCEEDS 8" INSTALL 1" 0 STEEL PROTECTION BAR.

4. INSTALL ADDITIONAL BARS AT 3 W" CLEAR SPACING ABOVE FIRST BAR WHEN OPENING EXCEEDS
16".

5. WHEN CURB INLET OPENING LENGTH EXCEEDS 8' INSTALL 1" 0 STEEL SUPPORT BOLTS,
SPACED AT NOT MORE THAN 5' OC.

REVISION BY APPROVED DAlE RECOMMENDED BY THE Ct1Y OF SAN DIEGO


STANDARDS COMMITTEE
CllY OF SAN DIEGO - STANDARD DRAWING
ORIGINAL• KA . NAGELVOOR OV12
oil~ 1/31/2012
COORDINATOR R.C.E. 65271 DAlE

CURB INLET OPENING DRAWING


NUMBER
SDD-102
CSP SLOTTED DRAI
N 4"
FI
NISH GRADE MAX
6" C
C A C
C GRATE FI
NISH GRADE C GRATE

C
C

C
198.5648

742.2051

135.1497

C
C
D

C 1" + MAX
C

6"
SEE NOTE 1
C

SQUARE W ALL,
CONCRETE PLUG,
METAL CAP,OR
BAND PLUG.

C
A SECTI
ON A-A CSP I
NLET

CSP SLOTTED
DRAI
N C CATCH BASI
N
B

C
C 6"
C
C

144.9613

577.0224
D+6"

C
C

45 ELBOW

SQUARE W ALL,
CONCRETE PLUG,
METAL CAP,OR
BAND PLUG.

C SECTI
ON B-B ALTERNATE
B
SECTI
ON B-B
I
NLETS

NOTES:
1. EI
THER FIELD JOINT W I
TH A PLIABLE MIXTURE OF SAND,PORTLAND CEMENT
EMULSIFI
ED ASPHALT (MI XTURE OF 1PART PORTLAND CEMENT,3-5 PARTS
SAND,AND 11/2 PARTS SSIEMULSIFIED ASPHALT)OR CONTINOUS W ELD.

2. SEE D-18 FOR ADDI


TIONAL NOTES AND DETAI
LS

3. SLOTTED DRAI
N INSTALLATI
ONS SHALL BE ENCASED W I
TH 6 INCH PCC 520-C-2500
ALL AROUND AND SHALL BE POURED MONOLI THI
CALLY W I
TH THE CURB AND GUTTER.

RECOMMENDED BY THE CI
TY OF SAN DI
EGO
REVI
SION BY APPROVED DATE
STANDARDS COMMITTEE
CI
TY OF SAN DI
EGO - STANDARD DRAW I
NG
ORI
GINAL* KA J.NAGELVOORT 01/
12

2/
25/
16
UPDATED HM J.NAGELVOORT 02/
16
COORDI
NATOR R.
C.E.56523 DATE
SLOTTED DRAI
N CONNECTI
ONS
DRAW I
NG
TO STANDARD I
NLETS SDD-
103
NUMBER
2D OR 2W M I
N
C ENDW ALL (
TYPI
CAL)
C
C D OR W
C

C
C

B B
C

C
2D OR 2W

0.
C5T(
MIN.
)
C #4 BARS FLOW
C
C

SLOT (T)
C
C

C
10' MIN

T
C

1.5T

C
C

C
6"
2D OR 2W

WIDE SLOT FI
LTER BLANKET

C
C MATERI
AL
A

C
C
C

6"
SILL,CLASS
420-C-2000
CONTRETE
C
C
C

SECTI
ON A-A
C
A

3D OR 3W
C NOTES:
C

1.PLANS SHALL SPECI


FY:

PLAN A)ROCK CLASS AND THI


CKNESS (
T).

D = PI
PE DI
AMETER B)FILTER BLANKET MATERI
AL,NUMBER OF LAYERS AND
W = BOTTOM WI
DTH OF CHANNEL THI
CKNESS

2.RI
P RAP SHALL BE EI
THER QUARRY STONE OR BROKEN
CONCRETE (I
F SHOW N ON THE PLANS)
.COBBLES ARE NOT
CONCRETE ACCEPTABLE.
CHANNEL
3.RIP RAP SHALL BE PLACED OVER A GEOTEXTI LE FI
LTER
FABRIC.FI
LTER BLANKET MATERIAL SHALL BE PLACED UNDER
THE FABRIC W HEN SPECIFI
ED.
C

4.SEE CI
TY SUPPLEMENT FOR SELECTI
ON OF FI
LTER MATERI
AL.
D MIN

D OR W
C

5.RI
P RAP ENERGY DI SSI
PATERS SHALL BE DESI
GNATED AS
EI
THER TYPE 1OR TYPE 2.TYPE 1SHALL BE W ITH CONCRETE
C

SI
LL;TYPE 2 SHALL BE W I
THOUT SI
LL.

6.FOR STRUCTURAL DETAI LS,SEE D-42 FOR PIPELI


NE SI
ZES FROM
18" TO 30" AND SEE D-43 FOR PI
PELINE SI
ZES FROM 36" TO
1 72".
3 MI
N
7.FOR RIP RAP SELECTI
ON SEE TABLE 200-1.
7 OF THE
W HI
TEBOOK.

SECTI
ON B-B

RECOMMENDED BY THE CI
TY OF SAN DI
EGO
REVI
SION BY APPROVED DATE
STANDARDS COMMITTEE
CI
TY OF SAN DI
EGO - STANDARD DRAW I
NG
ORI
GINAL* KA J.NAGELVOORT 01/
12

02/
16
2/
25/
16
UPDATED AB J.NAGELVOORT
COORDI
NATOR R.
C.E.56523 DATE
RI
P RAP
DRAW I
NG
ENERGY DI
SSI
PATOR SDD-
104
NUMBER
B
NOTCH 6"

TYP
C
C e

8"
FULL DEPTH

C
C
A A

C
1:
1

C
C

C
W/4 W/4

W
C

1
Tw/2

2:
/
Tw

C
PIPE COLLAR

1
e

1
(SEE NOTE 5)
C

C
C

C
C
C
C

f
C

C
B

C
SEE NOTE 7
END SI
LL
C a C b C
C C 8" CTORI
PI EW
AL VI
C L
C
NOTE:RI
P RAP NOT SHOW N
C Tw
2 - #4 REBARS HORI
ZONTAL C

AND VERTICAL AROUND FENCE POST (


TYPI
CAL)

PLAN
C
C 0.
5d

C
1:
1

C
0.75d
CONSTRUCTI
ON
JOI
NT
6"
8" TYPICAL

2X ON B-B
SECTI
CPI
PE DI
A C a C b
C C
C
4 X PI
PE DI
A
C

C C
SEE NOTE 5
C

C C
C

C d C 1'
C

Ta

AGGREGATE
C

C
C
C
C
PIPE

C CUTOFF W ALL
DIA

g
g

3" FI
LLET
H

C
c

C
C

1.
0%
C
C C
C

C
5" C
CHANNEL I
NVERT
d

C
d

Tb 0.
5%
C

C
C
C

C
C
C

C
C
C

I
NLET BOX
C

C 1
C

5"C 2
Tf

C
2'-0"

2"

MIN.THI
CKNESS
TOP OF SLAB MI
N OF 6" FACING CLASS 18"
ABOVE CHANNEL INVERT C LI
GHT CLASS 30"
8"C

FI
LTER AGGREGATE SUBBASE BOTTOM AND SI
DES
ON A-A
SECTI
CLOTH 6" THI
CK FOR FACI
NG CLASS
9" THI
CK FOR LI
GH CLASS

SEE TABLE ON SHEET 2 FOR DI


MENSI
ONS
SEE NOTES ON SHEET 2

SHEET 1OF 2

RECOMMENDED BY THE CI
TY OF SAN DI
EGO
REVI
SION BY APPROVED DATE
STANDARDS COMMITTEE
CI
TY OF SAN DI
EGO - STANDARD DRAW I
NG
ORI
GINAL* KA J.NAGELVOORT 01/
12

2/
25/
16
UPDATED BD J.NAGELVOORT 08/
15
COORDI
NATOR R.
C.E.56523 DATE
UPDATED AB J.NAGELVOORT 02/
16
CONCRETE ENERGY DI
SSI
PATOR DRAW I
NG
SDD-
105
NUMBER
PATOR DI
SSI
CONCRETE ENERGY DI ONS
MENSI

pe Di
Pi i
a (n) 18 24 30 36 42 48 54 60 72

ea (
Ar t
sq f) 77
1. 14
3. 91 7.
4. 07 62
9. 57
12. 90
15. 63
19. 27
28.

Max Q (
cfs) 21 38 59 85 115 151 191 236 339

W -6"
5' -9"
6' -0" 9'
8' -3" 10'
-6" 11'
-9" -0" 14'
13' -3" 16'
-6"

H -3"
4' -3"
5' -3" 7'
6' -3" -0"
8' -0"
9' -9" 10'
9' -9" 12'
-3"
L -4"
7' 9' -8"12'
-0" 10' -4" 14'
-0" 15'
-8" 17'
-4" 19' -0"
-0" 22'

a -3"
3' -11" 4'
3' -3"
-7" 5' -0"
6' -9"
6' -4"
7' -0"
8' -3"
9'

b -1"
4' -1"
5' -1" 7'
6' -1" -0" 8'
8' -11" 10'
-0" 11'
-0" 12'
-9"

c -4"
2' -10" 3"-4" 3'
2' -10" -5" 4'
4' -11" -5"
5' -11" 6'
5' -11"

d -11"
0' -2"
1' -4" 1'
1' -7" -9"
1' -0"
2' -2"
2' -5"
2' -9"
2'

e -6"
0' -6" 0'
0' -8" 0'
-8" -10" 0'
0' -10" -0"
1' -0"
1' -3"
1'

f -6"
1' -0" 2'
2' -6" 3'
-0" -0"
3' -0"
3' -0"
3' -0"
3' -0"
3'

g -1"
2' -6"
2' -0" 3'
3' -6" -11"
3' -5" 4'
4' -11" -4"
5' -2"
6'

Tf 8" 10" 12"


Tb 7" 2"
9 1/ 2"
10 1/

Tw 7" 2"
9 1/ 2"
10 1/

Ta 7" 8"

NOTES:

1. DESI
GN EQUI
VALENT FLUI
D PRESSURE (
EARTH LOADI
NG)= 60 pcfMAXI
MUM OUTLET VELOCI
TY = 35 f
t/s

2. CONCRETE SHALL BE 560-C-3250

3. REINFORCI
NG SHALL CONFORM TO ASTM DESI GNATI
ON A615 AND MAY BE GRADE 40 OR 60.REINFORCING SHALL BE
PLACED W I
TH 2" CLEAR CONCRETE COVER UNLESS NOTED OTHERW I
SE.SPLI
CES SHALL NOT BE PERMITTED
EXCEPT AS INDI
CATED ON THE PLANS.

4. FOR PI
PE GRADES NOT EXCEEDI
NG 20%,I
NLET BOX MAY BE OMI
TTED.

5. I
F I
NLET BOX I
S OMI
TTED,CONSTRUCT PI
PE COLLAR AS SHOW N.

6. UNLESS NOTED OTHERW ISE,ALL REI


NFORCING BAR BENDS SHALL BE FABRICATED W I
TH STANDARD HOOKS.
FOR STRUCTURAL DETAILS,SEE D-42 FOR PI
PELI
NE SI
ZES FROM 18" TO 30" AND SEE D-43 FOR PI
PELI
NE
SI
ZES FROM 36" TO 72".

7. 5'HI
GH CHAI
N LI
NK FENCI
NG,EMBED POST 18" DEEP I
N W ALLS AND ENCASE W I
TH CLASS B MORTAR.

8. I
N SANDY AND SI
LTY SOI
L:

A)RI
P RAP AND AGGREGATE BASE CUTOFF W ALL REQUI
RED AT THE END OF ROCK APRON.

B)FI
LTER CLOTH (POLYFI
LTER X OR EQUI
VALENT)SHALL BE I
NSTALLED ON NATI
VE SOI
L BASE,MI
NIMUM OF 1'
OVERLAPS AT JOI
NTS

9. RI
P RAP AND SUBBASE CLASSI
FICATI
ON SHALL BE AS SHOW N ON PLANS.

10.FOR RI
P RAP SELECTI
ON SEE TABLE 200-1.
7 OF THE W HI
TEBOOK.

SHEET 2 OF 2

RECOMMENDED BY THE CI
TY OF SAN DI
EGO
REVI
SION BY APPROVED DATE
STANDARDS COMMITTEE
CI
TY OF SAN DI
EGO - STANDARD DRAW I
NG
ORI
GINAL* KA J.NAGELVOORT 01/
12

2/
25/
16
UPDATED BD J.NAGELVOORT 08/
15
COORDI
NATOR R.
C.E.56523 DATE
UPDATED AB J.NAGELVOORT 02/
16

CONCRETE ENERGY DI
SSI
PATOR DRAW I
NG
SDD-
105
NUMBER
(!)
z
0 12" 24"
z
:::>
0 (!)
a: z
w 0
ll. z
0_J :::>
0
en a:
z w
ll.
(5 0_J
w
"'~
ID 30' MIN en
z -:::E
(5
w
ID

CVT SLOPE

3" 47D-C--2000 CONCRETE


OR 3" 2500 PSI, AIR PLACED
~
CONCRETE WITH 1 11.2" X 1 11.2"
17 GAGE STUCCO NETTING.
lYPE A TYPE B
BROW DITCH

(!)
(!)
z z
0 0
z z
:::>
0
a: ~
w
~ ll.
g
g en
en 2'MIN
z z
(5 2'
fa
ID 5'MIN
ll:l MIN 3'MIN

CUT OR ALL SLOPE

3" 47D-C--2000 CONCRETE


BOTTOM MAY BE ROUNDED OR 3" 2500PSI, AIR PLACED
AT THE OPTION OF THE CONCRETE WITH 1 11.2" X 1 11.2"
CONTRACTOR 17 GAGE STUCCO NETTING.

lYPE C TYPED
TERRACE DITCH

NOTES:

1. LONGITUDINAL SLOPE OF LINED DITCH SHALL BE 2% MINIMUM.

2. OVER SLOPE DOWN DITCHES SHALL EMPLOY 6" THICKENED


EDGE SECTION AT BOTH SIDES OF DITCH.

3. STUCCO NETTING SHALL BE GALVANIZED AND SHALL HAVE 1 11.2" COVER.


LEGEND ON PLANS

~~~

REVISION BY APPROVED DATE RECOMMENDED BY THE Ct1Y OF SAN DIEGO


STANDARDS COMMITTEE
CllY OF SAN DIEGO - STANDARD DRAWING
ORIGINAL* OV12
oil~ 1/31/2012
COORDINATOR R.C.E. 65271 DATE

DRAINAGE DITCHES DRAWING


NUMBER
SDD-106
ELEV SHOW N
C ON PLANS
L

C FENCE (
SEE NOTE 6)
6" C
C

C
C
C

C
6' MAX

12"
1 1
1/
2:

4"
2:
1 1/

4"
1

C
C
C
C
C

C
W HEN DEPTH EXCEEDS 3'-0"
W EEP HOLES MUST BE ADDED AT
560-C-3250 CONCRETE OR AI R C 8'
-0" MAX 10'ON CENTERS.(
SEE DETAIL)
C
PLACED CONCRETE.REI NFORCED SEE NOTE 4
WITH 6" X 6" - 10 /10 GAGE w.w.f
.

TYPI
CAL SECTI
ON

1" (25.4mm)
3/
16" PREMOLDED
JOINT MATERIAL OR
1/
4" GALV 1/
8" SAW ED JOI
NT.
WIRE MESH

C
SCREEN C

C
4" DI
A PLASTI
C
W EEP HOLES AT 10'OC
C
20" RADI
US C
C
C

W EAKENED PLANE JOI


NT
C

3"
C

1" MAX GRADED FI LTER MATERI


AL
C
PLACED A MI NI
MUM OF 18"
EACH SI DE OF W EEP HOLE.

OPTIONAL CONSTRUCTI
ON

1/2"
JOI
NT PREMOLDED JOI
NT
MATERI
AL

C
DETAI
L C

C
11/
2" C
C

NOTES: EXPANSI
ON JOI
NT
1. CLAY PI
PE MAY BE SUBSTI
TUTED FOR PLASTI
C PI
PE AT W EEP HOLES.

2. W EAKENED PLANE JOI


NTS SHALL BE PLACED EVERY 12'TO 15'
.EXPANSI
ON JOI
NTS SHALL BE PLACED
AT ALL CHANGES OF SECTI
ON AND AT ENDS OF CURVES.

3. CUTOFF W ALLS SHALL BE CONSTRUCTED AT EACH END OF THE CHANNEL ALONG THE FULL W I
DTH OF SECTI
ON.
SEE D-72.

4. FOR BOTTOM WI
DTHS GREATER THAN 8'SEE SDD-108.

5. REI
NFORCEMENT SHOW N I
S MI
NIMUM.

6. CHANNELI NG FENCING IS REQUI RED.UNLESS OTHERW I


SE SHOW N ON THE PLANS A CHAI N LINK FENCE (PER
SDM-112 AND SDM-114)6'I
N HEI GHT,W I
TH A TOP RAIL SET AT 6" I
NSIDE EASEMENT BOUNDARY LI NES SHALL BE
CONSTRUCTED ON BOTH SI DES,INCLUDING BOX CULVERTS OR ANY OTHER STRUCTURE AT THE END OF THE CHANNEL.
ACCESS POI NTS SHALL BE PROVIDED ON BOTH SI DES AT 500'MAXI MUM I NTERVALS.TW O 10'GATES OR ONE 20'GATE
FOR VEHICULAR ACCESS ARE REQUI RED AT A MAXIMUM OF 1000'I NTERVALS AND MAY BE PLACED ON EI THER SI
DE.
THE REMAI NI
NG ACCESS POI NTS SHALL BE 4'GATES.

LEGEND ON PLANS

RECOMMENDED BY THE CI
TY OF SAN DI
EGO
REVI
SION BY APPROVED DATE
STANDARDS COMMITTEE
CI
TY OF SAN DI
EGO - STANDARD DRAW I
NG
ORI
GINAL* KA J.NAGELVOORT 01/
12

02/
16
2/
25/
16
UPDATED RB J.NAGELVOORT
COORDI
NATOR R.
C.E.56523 DATE

MI
NOR DRAI
NAGE CHANNEL DRAW I
NG
SDD-
107
NUMBER
ELEV.SHOW N
C ON PLANS
L

C FENCE (
SEE NOTE 5)
6" C
C

C
C
C

C
C
AS SHOWN
ON PLANS

12"
1

C
1/

C
2: 1
1 2:
1/

4"

4"
1

6"
C

C
C

C
C
C C

C
W HEN DEPTH EXCEEDS 3'-0"
W EEP HOLES MUST BE ADDED AT
560-C-3250 CONCRETE OR AI R 10'ON CENTERS.(
SEE DETAIL)
C WI
DTH SHOW N C
PLACED CONCRETE.REI NFORCED W I
TH C
ON PLANS
6" X 6" - 10/
10 GAGE w.
w.f
. SEE DETAI
L

TYPI
CAL SECTI
ON

4" C
4" DI
A PLASTI
C

C
W EEP HOLES AT 10'OC X

X
20" RADI
US
C
6"

C
C

C
C 1'MI
N
C

C
C

3" C
X
1" MAX GRADED
C

C
C

FILTER MATERI
AL
3"

X
X X X X X X X
C
C

1/
4" GALV
WIRE MESH
SCREEN

OPTI
ONAL CONSTRUCTI
ON JOI
NT
4" DI
A PLASTI
C W EEP
HOLES AT 10'OC
DETAI
L
1 1/2"

3/
16" PREMOLDED OPEN BUTT JOI
NT

C
C
PREMOLDED JOI
NT JOINT MATERIAL OR
MATERI
AL C

C
1"

1/
8" SAW ED JOI
NT. C 1'MI
N
C

C
C
C
C

3"
C
C

1" MAX GRADED


11/
2" C
C FILTER MATERI
AL

ALTERNATE
EXPANSI
ON JOI
NT
W EAKENED PLANE JOI
NT CONTI
NUOUS DRAI
N

NOTES:

1. CLAY PI
PE MAY BE SUBSTI
TUTED FOR PLASTI
C PI
PE AT W EEP HOLES.

2. W EAKENED PLANE JOI


NTS SHALL BE PLACED EVERY 12'TO 15'
.EXPANSI
ON JOI
NTS SHALL BE PLACED
AT ALL CHANGES OF SECTI
ON AND AT ENDS OF CURVES.

3. CUTOFF W ALLS SHALL BE CONSTRUCTED AT EACH END OF THE CHANNEL ALONG THE FULL W I
DTH OF SECTI
ON.SEE D-72.

4. REI
NFORCEMENT SHOW N I
S MI
NIMUM.

5. CHANNELING FENCING I S REQUIRED PER SDM-112 OR SDM-114.UNLESS OTHERW I SE SHOW N ON THE PLANS,A CHAI
N LI
NK
FENCE 6'I
N HEIGHT,W I
TH A TOP RAI L SET AT 6" I
NSI
DE EASEMENT BOUNDARY LI NES SHALL BE CONSTRUCTED ON BOTH
SI
DES,INCLUDING BOX CULVERTS OR ANY OTHER STRUCTURE AT THE END OF THE CHANNEL.ACCESS POI NTS
SHALL BE PROVIDED ON BOTH SI DES AT 500'MAXI MUM INTERVALS.TW O 10'GATES OR ONE 20'GATE FOR
VEHI
CULAR ACCESS ARE REQUI RED AT A MAXIMUM OF 1000'I NTERVALS AND MAY BE PLACED ON EI THER SIDE.
THE REMAINING ACCESS POI NTS SHALL BE 4'GATES.
LEGEND ON PLANS

RECOMMENDED BY THE CI
TY OF SAN DI
EGO
REVI
SION BY APPROVED DATE
STANDARDS COMMITTEE
CI
TY OF SAN DI
EGO - STANDARD DRAW I
NG
ORI
GINAL* KA J.NAGELVOORT 01/
12

2/
25/
16
UPDATED RB J.NAGELVOORT 10/
15
COORDI
NATOR R.
C.E.56523 DATE
UPDATED HM J.NAGELVOORT 02/
16

M AJOR DRAI
NAGE CHANNEL DRAW I
NG
SDD-
108
NUMBER
FENCE FENCE

COMPACTED EMBANKMENT

WI
DTH SHOW N ON PLANS
C
C
C
L
C

C
C

1
2:

C
1/
1
DEPTH SHOWN

C
ELEV SHOW N
1
1/ ON PLANS
ON PLANS
2: 1
1 2:
1/
1

C1
8"
C
C
C
C

2'
MIN
C

SELECTED ROCKSLOPE PROTECTI


ON
PER AGENCY REQUIREMENTS

C WI
DTH SHOW N
C
ON PLANS

SECTI
ON

NOTES:

1. THE FOLLOW I
NG SHALL BE AS REQUI
RED:

A.LOW FLOW CHANNEL

B.FI
LTER BLANKET

C.CUTOFF W ALL

D.FENCE

2. CHANNELING FENCING IS REQUIRED PER DRAW ING SDM-112 OR SDM-114.UNLESS OTHERW I


SE SHOW N ON THE
PLANS,A CHAI
N LINK FENCE 6'HEIGHT,W I
TH A TOP RAIL SET AT 6" I
NSI
DE EASEMENT BOUNDARY LI NES SHALL BE
CONSTRUCTED ON BOTH SI DES,INCLUDI
NG BOX CULVERTS OR ANY OTHER STRUCTURE AT THE END OF THE
CHANNEL.ACCESS POINTS SHALL BE PROVI DED ON BOTH SIDES AT 500'MAXIMUM INTERVALS.TW O 10'GATES OR
ONE 20'GATE FOR VEHI
CULAR ACCESS ARE REQUI RED AT A MAXIMUM OF 1000'INTERVALS AND MAY BE PLACED
ON EITHER SI
DE.THE REMAINING ACCESS POI NTS SHALL BE 4'GATES.

LEGEND ON PLANS

RECOMMENDED BY THE CI
TY OF SAN DI
EGO
REVI
SION BY APPROVED DATE
STANDARDS COMMITTEE
CI
TY OF SAN DI
EGO - STANDARD DRAW I
NG
ORI
GINAL* KA J.NAGELVOORT 01/
12

02/
16
2/
25/
16
UPDATED RB J.NAGELVOORT
COORDI
NATOR R.
C.E.56523 DATE

GRADED EARTH CHANNEL DRAW I


NG
SDD-
109
NUMBER
FOR TRENCH RESURFACING
ON IMPROVED STREETS,
SEE SDG-107 OR SDG-108.

w
z
0
N•
a::f ~------T_R_E_N_C_H__W_I_D_T_H______~~
wM
~~
a..
a..
::::>

.....J
.....J
u:::
~
0
<{
I ID
f- w
a.. z
w
0 0
N
I w
0 _J
z
w
0
a:
f-
0
~

8" MIN
.~ ~~ • - .. ~ .. 0 12" MAX
12"
C\J
MIN
C) w
z b w ...
0 z
0
z eft.
w w 0 0
N 0>
ID w
en w
a..
a..

4" CLEARANCE MIN

314" CRUSHED ROCK

SECTION

NOTES:

1. (*)INDICATES MINIMUM RELATIVE COMPACTION.

2. BEDDING MATERIAL SHALL BE SAND, CRUSHED AGGREGATE. OR NATIVE FREE-DRAINING GRANULAR MATERIAL.100%
SHALL PASS NO. 4 SIEVE AND HAVE A SAND EQUIVALENT OF NOT LESS THAN 30.

REVISION BY APPROVED DATE RECOMMENDED BY THE Ct1Y OF SAN DIEGO


STANDARDS COMMITTEE
CllY OF SAN DIEGO - STANDARD DRAWING
ORIGINAL' KA . NAGELVOOR W12
oil~ 1/31/2012
COORDINATOR R.C.E. 65271 DATE
PIPE BEDDING AND TRENCH BACKFILL
FOR STORM DRAINS DRAWING
SDD-110
NUMBER
EXTEND ALL LONGI TUDINAL BARS
I
N BOX W ALLS 2'-0" I
NTO W INGS,
EXCEPT W HERE EXPANSI ON JOINT
OCCURS. 3 - #4
DETAI
LX C

C
C

C
"ANGLE OF #4 @ 12"
FLARE"
C

C
R= T3(
OMITIF "ANGLE OF FLARE" Det
ailX
C o
I
S LESS THAN 30 )
C

M
C

C
TYPE "B"
TOE OF SLOPE TYPE "A"
ELEV "a" PLAN 3-#4
#4 @ 12"

C C
W HERE DESI
GN "H" EXCEEDS 9'OR LENGTH C

C
OF W I
NG W ALL EXCEEDS 1.
5 "H" PLACE 1/
2" EXP JT

JOI
NT FI
LTER AT JUNCTI
ON
BOX W ALL 3'
C-0" MI
N
C
WI
NGW ALL "H"
C

I
NSI
DE
C

Det
ailY
C

GROUND
4'-0"

LI
NE

ELEV."a"
C
C

C
C
CUT-OFF

C #4 @ 18"
MAY BE VARI
ED BY ENGI
NEER TO #4 @ C
WALL

SUI
T CONDITI
ONS I
N THE FI
ELD. 18" ON CENTER C
C 1'
-0"

SEC B-B
TYPE "A" TYPE "B"

END ELEVATI
ON
C "L"
C

PARAPET 3'
-0" MI
N C
C
C

DETAI
LY

C
1
2:
C

1/
ANGLE OF FLARE 1
S MATCH GROUND
E R
RI TE LI
NE
NOTE: VA AT
L
W HERE 11/
2:1 PE F 1'
-0"
C

C
O R C
C

SURCHARGE EXCEEDS
C
C SL O 2'
-0"
#4 @ 12"
C

5'
,USE TYPE 2 C
"N"
"

C
RETAI
NING W ALL.
C
M
"

2-#4 C
C

ELEV "a"
C 5'
-0" MAX
C
C

2'
-0"
1'
-6" MAX C
C #4 @ 12"
2'
-0"
TYPE "C"
ELEVATI
ON
NOTE:

CHANNEL FENCI
NG IS REQUI
RED PER SDM-112 OR SDM-114.UNLESS OTHERW I
SE SHOW N ON THE PLANS,A CHAI
N LI
NK
FENCE 6'I
N HEI
GHT,W I
TH A TOP RAI
L SET AT 6" I
NSI
DE EASEMENT BOUNDARY LINES SHALL BE CONSTRUCTED
ON BOTH SIDES,I
NCLUDING BOX CULVERTS OR ANY OTHER STRUCTURE AT THE END OF THE CHANNEL.
ACCESS POI
NTS SHALL BE PROVI
DED ON BOTH SI
DES AT 500'MAXI
MUM INTERVALS.TW O 10'GATES OR
ONE 20'GATE FOR VEHICULAR ACCESS ARE REQUI
RED AT A MAXI
MUM OF 1000'INTERVALS AND SHALL BE
PLACED ON EITHER SI
DE.THE REMAINING ACCESS POI
NTS SHALL BE 4'GATES. SHEET 1OF 6

RECOMMENDED BY THE CI
TY OF SAN DI
EGO
REVI
SION BY APPROVED DATE
STANDARDS COMMITTEE
CI
TY OF SAN DI
EGO - STANDARD DRAW I
NG
ORI
GINAL* KA J.NAGELVOORT 01/
12

2/
25/
16
UPDATED RB J.NAGELVOORT 02/
16
COORDI
NATOR R.
C.E.56523 DATE

BOX CULVERT W I
NGW ALL DRAW I
NG
SDD-
111
NUMBER
MATCH
PARAPET
FI
LL SLOPE
1'
-0" C
C

C
#4 ALONG 5'MAX FOR
TOP OF W ALL

C
11/
2:1FILL SLOPES,
C C
C UNLIMITED FOR
FLATTER THAN 11/2:1

C
C
C

GUTTER OR SHOULDER

VERTI
CAL "c" BARS
C C

#4 @ 36"
DESIGN "H"

#4 @ 18" C
C
C

C 2" CL
C

2" CL C
C 3" HOLE 15'OC 1'ABOVE
OUTSIDE GROUND
SHORT "c"
C
BARS C

35 DI
A C VERTI
CAL UNLESS ADJACENT
C
TO BATTERED SECTION,THEN MATCH
C
2" CL
"d" BARS
C

C C

C
C
F

C
9" R
C
C

C
C

3" CL

8"
#4 TOTAL 7
C 8"
C

C 8"
C

C 1'
-0"
C C W/
3
C

C C C B
C C

C W
C

TYPICAL SECTION
H= 4'
-0" THRU 12'
-0"

SHEET 2 OF 6

RECOMMENDED BY THE CI
TY OF SAN DI
EGO
REVI
SION BY APPROVED DATE
STANDARDS COMMITTEE
CI
TY OF SAN DI
EGO - STANDARD DRAW I
NG
ORI
GINAL* KA J.NAGELVOORT 01/
12

2/
25/
16
UPDATED AR J.NAGELVOORT 02/
16
COORDI
NATOR R.
C.E.56523 DATE

BOX CULVERT W I
NGW ALL DRAW I
NG

NUMBER
SDD-
111
MATCH
PARAPET
FI
LL SLOPE
1'
-0" C
C

C
#4 ALONG 5'MAX FOR

C
TOP OF W ALL 1-11/
2:1FI
LL SLOPES,
C C
C UNLI MI
TED FOR
FLATTER THAN 11/2:
1

C
C
C

GUTTER OR SHOULDER

2" CL C
C

C BATTER 1/
2:12
VERTI
CAL C
"c" BARS

C
C C 2" CL
Design "H"

#4 @ 18" C C

#4 @ 36"

SHORT "c" BARS


C

3" HOLE 15'O.


C.,1'ABOVE
OUTSIDE GROUND
C

35 DI
A C C
CONSTRUCTI
ON JOI
NT
2" CL
"d" BARS
C

C
C
F

C
9" R
C
C

C
3" CL

1'
#4 TOTAL 7
1'
-0" C
C

C 1'
-0"
C

1'
-0" C S
C C

C W/
3
C

C C C B
C C

C W
C

TYPICAL SECTION
H= 13'
-0" THRU 16'
-0"

SHEET 3 OF 6

RECOMMENDED BY THE CI
TY OF SAN DI
EGO
REVI
SION BY APPROVED DATE
STANDARDS COMMITTEE
CI
TY OF SAN DI
EGO - STANDARD DRAW I
NG
ORI
GINAL* KA J.NAGELVOORT 01/
12

2/
25/
16
UPDATED AR J.NAGELVOORT 02/
16
COORDI
NATOR R.
C.E.56523 DATE

BOX CULVERT W I
NGW ALL DRAW I
NG

NUMBER
SDD-
111
H= 16'

H= 15'

FI
GURES AT TOP OF "c" BARS
H= 14'
I
NDI
CATE DI
STANCE TO UPPER
END OF "c" BARS. H= 13'

H= 12' "c" BARS

H= 11'

H= 10'

H= 9'

7'-0"
H= 8'

6'-9"
6'-6"
H= 7'

6'-3"
H= 6'
4'-0"
3'-9"

H= 5'
3'-6"

H= 4' SHORT
3'-3"

"c"BARS
3'-0"

24" 20" 10" 7 1/


2" 6" 15" 11"

18" 14" 7" 8" 15" 13"

TYPI
CAL LAYOUT EXAMPLE 1

SHEET 4 OF 6

RECOMMENDED BY THE CI
TY OF SAN DI
EGO
REVI
SION BY APPROVED DATE
STANDARDS COMMITTEE
CI
TY OF SAN DI
EGO - STANDARD DRAW I
NG
ORI
GINAL* KA J.NAGELVOORT 01/
12

2/
25/
16
UPDATED AR J.NAGELVOORT 02/
16
COORDI
NATOR R.
C.E.56523 DATE

BOX CULVERT W I
NGW ALL DRAW I
NG

NUMBER
SDD-
111
USE REI
NFORCEMENT
FOR H= C 6'
-0" C 8'
-0" C 10'
-0"
C C C

TOP OF W ALL
TOE OF SLOPE

C
C

10'-6"
VARI
ES C

MAX
C

8'-6"
MAX
6'-6"
MAX
C

TOP OF FOOTI
NG
MAX.
= H+ 6"

C
C

C
C

1'
-2"

B=4'-2"
2'-10"

2'-2"
3'-2"
4'-2"

OPTI
ONAL
FOOTING LI
NES
C

C
C
C

W=6'-2"
C

C
C

C
C

C
C
C

C
C

C=2'-0"
1'-0"

1'
-4"

LAY-OUT LI
NE

TYPI
CAL LAYOUT EXAMPLE 2

NOTES:

1. UNI
T STRESSES:f
s= 20,
000 PSI
,fc= 1,
200 PSI
,n= 10
MAXIMUM TOE PRESSURE = 11/
2 TONS/SQ.FT.
ELEVATI
ONS,LENGTH AND ANGLE OF FLARE OF W I
NGS MAY BE VARI
ED BY THE ENGI
NEER
TO SUIT CONDI
TIONS ENCOUNTERED I
N THE FIELD.

2. W ALLS DESI
GNED FOR 2' -0" LI
VE LOAD SURCHARGE,11/ 2:
1SLOPING SURCHARGE
NOT TO EXCEED 5' -0" I
N ELEVATI ON PLUS 2'-0" LI
VE LOAD SURCHARGE,OR
UNLIMITED 2:1SURCHARGE.DI MENSIONS "H","L","M","N",ELEVATI
ON "A" AND "ANGLE OF FLARE"
(
AS APPLY)ARE SHOW N ON THE PLANS.

3. W ALL HEI
GHT MAY BE EXCEEDED BY 6" BEFORE GOING TO NEXT GREATER "H".
O

ELIMINATE CUTOFF W ALL I


F ADJACENT CHANNEL I
S PAVED AND SKEW I
S 20 MAXIMUM.

SHEET 5 OF 6

RECOMMENDED BY THE CI
TY OF SAN DI
EGO
REVI
SION BY APPROVED DATE
STANDARDS COMMITTEE
CI
TY OF SAN DI
EGO - STANDARD DRAW I
NG
ORI
GINAL* KA J.NAGELVOORT 01/
12

2/
25/
16
UPDATED AR J.NAGELVOORT 02/
16
COORDI
NATOR R.
C.E.56523 DATE

BOX CULVERT W I
NGW ALL DRAW I
NG

NUMBER
SDD-
111
ORI
REVI

GI
SI

UPDATED
ON

NAL*
BY
APPROVED

KA J.NAGELVOORT

AR J.NAGELVOORT
02/
01/

16
12
DATE
CI
REINFORCED CONCRETE WINGWALLS - US

"H" 4' 5' 6' 7' 8' 9' 10' 11' 12' 13' 14' 15' 16'
W 3'-2" 3'-8" 4'-2" 4'-8" 5'-2" 5'-8" 6'-2" 6'-8" 7'-2" 7'-8" 8'-2" 8'-8" 9'-2"
C 1'-0" 1'-2" 1'-4" 1'-6" 1'-8" 1'-10" 2'-0" 2'-2" 2'-4" 2'-6" 2'-8" 2'-10" 3'-0"

TY OF SAN DI
B 2'-2" 2'-6" 2'-10" 3'-2" 3'-6" 3'-10" 4'-2" 4'-6" 4'-10" 5'-2" 5'-6" 5'-10" 6'-2"
F 1'-2"
Batter None 1/2 : 12
S 1'-0" 1'-0" 1'-0" 1'-0" 1'-0" 1'-0" 1'-0" 1'-0" 1'-0" 1'-6 1/ 2" 1'-7" 1'-7 1/2" 1'-8"

BOX CULVERT W I
"c"Bars #4@24 #4@18 #5@20 #5@14 #5@10 #5@7 #6@7 1/ 2" #7@8 #7@6 #9@15 #10@15 #10@13 #10@11
"d" Bars #4@24 #4@18 #5@20 #5@14 #5@10 #6@14 #7@15 #8@16 #7@12 #8@15 #9@15 #10@13 #9@11
Conc cy/
lf 0.32 0.38 0.44 0.49 0.55 0.61 0.67 0.73 0.79 1.02 1.10 1.18 1.26
# /
Reinf lf 13 16 19 25 30 37 49 62 76 73 90 104 125

NGW ALL
NOTE: Quantities do not include that portion above the design "H" limit.

EGO - STANDARD DRAW I


NG

DRAW I

NUMBER
NG
COORDI
R.
C. NATOR

SDD-
RECOMMENDED BY THE CI
STANDARDS COMMI

111
E.56523
TTEE

2/
TY OF SAN DI

DATE
25/
EGO
SHEET 6 OF 6

16
C
VERT
ICAL

OR
ELEM

E
ENT

OP
NF F
L
41S
I

C
C
E
C :
OR R

C
2:
1ELE
M ENT

"L"
OP
NF F

"
L

L
"
3S
EI
:
R C
C 4 C 1:
1ELE C C
OR

C
M ENT
E

C
OP
NF F
5S L

C
#4 @ 18"
I

C
E
:
R
4

ELEMENTS PARALLEL TO
C

CUTOFF W ALLS ARE


NF

C
2:
3 EL STRAI
GHT LINE.
I

EM EN
E

C
LR

C
S)

C
L
CE
A

1'
-0"
OF W
A

TOE OF
LS P

C "W " SLOPE C


C
OUT
QUA

PLAN
Y
E
(
A

C
TYPL

TOE OF SLOPE

C PARAPET

C
ELEV "a"
C

C
C ELEV."a"
#4 @ 18"
"H"

"H"
#4 @ 18"

C 2'
-6" C 2'
-0"
FL C
C C
2'
-0"
C

C C 2'
-6"
C C
C

C
C
C
C

C
ON ROCK

C
C

FL
4'-0" MIN

C
C
UNLESS

C
C

C
C

#9

ON ROCK
C

UNLESS
CC

4'-0"
C

CONST JOI
NT #9 C

MIN
C
C 6"
EXTEND CULVERT 6"
#4 @ 18" MAX CONST JOI
NT
I
NVERT SLAB SPACERS

C
C C
C 2'-0" I
NTO APRON #4 @ 18" MAX C

1'
-0" CUTOFF W ALL C
C

1'
-0" CUTOFF W ALL
TYPI
CAL W I
TH STI
FFENI
NG BEAM TYPI
CAL W I
THOUT STI
FFENI
NG BEAM

PART LONGI
TUDAL SECTI
ON

C PARAPET
C

B B
C
C
CCC

SLOPE OF FI
LL OR CHANNEL
C SLOPE APRON TO MATCH
3-#9 CHANNEL AND INVERT
C C
C
"

3-#9
-0

C
4'

C 4'
C

3-#9 C
C

C #4 @ 18",STR BACK FACE


C C
4'

C
C C C C
C C #4 @ 18",FRONT FACE,BEND
C

C
C

4' 2'
-6" I
NTO W ALL OR APRON
C

C
C

C
C
C

C CUTOFF W ALL
2-#4
2-#4 I
F ALTERNATI
VE BOTTOM I
S USED
ALTERNATI
VE BOTTOM OF CUTOFF W ALL

END ELEVATI
ON

SHEET 1OF 3

RECOMMENDED BY THE CI
TY OF SAN DI
EGO
REVI
SION BY APPROVED DATE
STANDARDS COMMITTEE
CI
TY OF SAN DI
EGO - STANDARD DRAW I
NG
ORI
GINAL KA J.NAGELVOORT 01/
12

2/
25/
16
UPDATED RB J.NAGELVOORT 02/
16
COORDI
NATOR R.
C.E.56523 DATE

BOX CULVERT W ARPED W I


NGW ALL DRAW I
NG
SDD-
112
NUMBER
"A" C
C
#4 @ 12"
#4

C
C
C

C
"B"
"D"

C
C

C
SEE SHEET 3

C
6"

C
C

C
C C
FOR TRANSVERSE REINF

>10'
C

< 10'
I
N W ARPED W I
NGW ALL,
STI
FFENI
NG BEAM

1'-0" FOR MAX "H"


SEE SHEET 3

-
C

9" FOR MAX "H"


"H"
FOR NUMBER AND SI ZE OF
C SLOPE VARI
ES
BARS SEE SHEET 3. C
EXTEND AND HOOK I NTO 1-1/
2" DI
A CL
CUTOFF W ALL AND PARAPET. 1" MIN

C
C C
WITHOUT

C
STI
FFENING 1-1/
2" DI
A CL C
BEAM 1" MIN C 6" #4 @ 18"
C
2" 3"

C
C
C
#4 SPACERS @ 12" C
C

C
#4 X 5'
-0" DOW ELS @ 12" CENTERS

C
C
C

C
#4 @ 18"

C
C

"
C

6
C

C
SECTI
ON C-C #4 1'
-4" FOR MAX
C "H"<10'
C -
2'
-0" FOR MAX
"H">10'

CULVERT W ALL

2'
C
C
C

PARAPET

C
"N"
"

C
C
"M

LEVEL
#4

C
C
C

C
C

C
C

C
C "ANGLE CONST JOI
NT
ELEV."a" C
OF FLARE"
C C
C

2' C
#4 @ 12",LAP
C

WI
TH W ALL SPACERS

C
C

W ARPED W I
NGW ALL
TOE OF SLOPE

ALTERNATI
VE W ARPED W I
NGW ALL SECTI
ON B-B

USE W HERE ADDI


TIONAL PROTECTI
ON
TO TOE OF EMBANKMENT I S REQIRED

NOTES:

1. W ALLS DESIGNED FOR 2'SURCHAGE;EARTH DENSI


TY= 120 #/
CU.FT.
;
EQUI VALENT FLUI
D PRESSURE = 36 #/
CU.FT.

2. VARY "D" OF W ARPED W ALL UNI


FORMLY FROM THAT CUTOFF W ALL TO THAT AT CULVERT,
FOR MAXI MUM "H" > 12'(3.
66)

3. W HERE ABRASION I
S ANTICI
PATED I
NCREASE APRON THI
CKNESS TO 7" MI
NIMUM TO
PROVIDE 2" MI
NIMUM REINFORCEMENT COVERAGE.

4. DI
MENSIONS "L","W ","H","N",ELEVATI
ON "a","ANGLE OF FLARE",AND END "SLOPE (
AS APPLY)
ARE SHOW N ON THE PLANS.

5. CONCRETE SHALL BE 560-C-3250.

6. CHANNEL FENCING I
S REQUIRED PER SDM-112 OR SDM-114.UNLESS OTHERW I
SE SHOW N ON THE PLANS,A
CHAI
N LINK FENCE 6'I
N HEIGHT,W I
TH A TOP RAI
L SET AT 6" I
NSI
DE EASEMENT BOUNDARY LI NES SHALL BE
CONSTRUCTED ON BOTH SI DES,I
NCLUDING BOX CULVERTS OR ANY OTHER STRUCTURE AT THE END OF THE
CHANNEL.ACCESS POINTS SHALL BE PROVI
DED ON BOTH SI DES AT 500'MAXI
MUM I NTERVALS.TW O 10'GATES
OR ON 20'GATE FOR VEHICULAR ACCES ARE REQUIRED AT A MAXIMUM OF 1000'INTERVALS AND BE PLACED
ON EITHER SI
DE.THE REMAINI
NG ACCESS POINTS SHALL BE 4'GATES.

SHEET 2 OF 3

RECOMMENDED BY THE CI
TY OF SAN DI
EGO
REVI
SION BY APPROVED DATE
STANDARDS COMMITTEE
CI
TY OF SAN DI
EGO - STANDARD DRAW I
NG
ORI
GINAL* KA J.NAGELVOORT 01/
12

02/
16
2/
25/
16
UPDATED RB J.NAGELVOORT
COORDI
NATOR R.
C.E.56523 DATE

BOX CULVERT W ARPED W I


NGW ALL
DRAW I
NG
SDD-
112
NUMBER
ORI
REVI

GI
SI

UPDATED
ON

NAL*
BY
APPROVED

KA J.NAGELVOORT

RB J.NAGELVOORT
01/

02/
12

16
DATE
CI
WARPED WINGWALLS - U.S. MEASUREMENT TABLE ONLY

WALL DIMENSIONS AND REINFORCING STIFFENING BEAM DIMENSIONS AND REINFORCING

TY OF SAN DI
Element
"H" 8'or less 10' 12' 14' 16' 18' 20' "H" "L" 12' 14' 16' 18' 20' 25' 30' 35' 40' or more
Slope max
Front face reinf #4@12 #4@7 #5@7 #5@5 #6@6 #7@7 #7@6 6' No beam. Place 2-#6 in each
1/4:1 Rear face reinf #4@12 #4@12 #4@12 #4@12 #4@12 #4@12 #4@12 8' face along top of
wall. "A"=1'-0"
Front face reinf #4@12 #4@12 #4@12 #4@12 #4@10 #4@8 #4@6 10' "A"=1'-6"
3/4:1
Rear face reinf #4@12 #4@12 #4@12 #4@10 #4@7 #4@6 #5@8 12' "B"=9"
Front face reinf #4@12 #4@12 #4@12 #4@12 #4@12 #4@12 #4@12 14' Total 6-#6 "A"=1'-10"
1-1/4:1 "B"=1'-0"
Rear face reinf #4@8 #4@8 #4@5 #5@6 #6@7 #6@6 #7@6 16' "B"=1'-0" "A"=2'-0"
"D" at Cutoff Wall 6" 6" 6" 7-1/2" 8" 11" Total 6-#7
9-1/2" 18' Total 6-#8 "B"=1'-6"

BOX CULVERT W ARPED W I


"D" at Culvert 6" 6" 6" 8" 9-1/2" 11" 1'-1" 20' Total 8-#9

EGO - STANDARD DRAW I


NG

NGW ALL
DRAW I

NUMBER
NG
COORDI
R.
C. NATOR
RECOMMENDED BY THE CI

SDD-
STANDARDS COMMI

E.56523

112
TTEE
SHEET 3 OF 3

2/
TY OF SAN DI

DATE
25/
EGO

16
A B B

L L _j

L
tz

PLAN
j 6" MIN
(o~

SKEWED CONNECTION PLAN


PERPENDICULAR CONNECTION

....·:·:.- ......... :_... ....·:·:,-.·_,.:,.:_-..


... ...
.··. .·· .··:·· ··-· ···.-· ."··
ROUNDED PIPE ENDS,
SEE D-61.

. ... . . .. : ..·

SECTION A-A SECTION B-B

NOTES:

1. THE END OF CONNECTING PIPE SHALL NOT PROJECT INTO THE WATERWAY OF THE LARGER PIPE.

2. THE LARGER PIPE SHALL NOT BE LESS THAN 24" ID. LEGEND ON PLANS
3. THE OD OF SMALLER PIPE SHALL NOT BE MORE THAN 21.3 THE SIZE OF THE LARGER PIPE ID.

4. CONCRETE SHALL BE 470-C-2000.

REVISION BY APPROVED DATE RECOMMENDED BY THE CITY OF SAN DIEGO


STANDARDS COMMITIEE
CITY OF SAN DIEGO - STANDARD DRAWING
UPDATED* KA J. NAGELVOO OV12
1/.cJ/-M£--
COORDINATOR R.C.E. 65271
1/31/2012
DATE

CONCRETE LUG DRAWING


NUMBER
SDD-113
_L---1 T ~f------__:_:X_ _~--1~ T r-
,-----------------------~

1- .Q__Q_Q____J)_.Q__S)_.Q_-f-

~ VERTICAL REINFORCING @ I T: 6" MIN

I
d 18" MAX. FOR HORIZONTAL
I REINFORCING, SEE TABLE f
>- d ON PAGE 2 I
~~~ 1--1 V2" CLEARANCE, lYP I
1- -d---a-o-----o-o----n-u-~
T 2" lYPICAL ___j ~
TYPICAL BOX SECTION
10"
14"
I • • I

R L...__ _ __ _ j
FV APPROVED STEEL
REINFORCED
POLYPROPYLENE
STEP

STEP DETAIL

NOTES:

1. CONCRETE SHALL BE 560-G-3250 UNLESS OTHERWISE NOTED.

2. REINFORCING STEEL SHALL COMPLY WITH THIS DRAWING UNLESS OTHERWISE SPECIFIED.

3. REINFORCING STEEL SHALL BE INTERMEDIATE GRADE DEFORMED BARS CONFORMING TO LATEST ASTM
SPECIFICATIONS.

4. BENDS SHALL BE IN ACCORDANCE WITH LATEST ACI CODE.

5. MINIMUM SPLICE LENGTH FOR REINFORCING SHALL BE 30 DIAMETERS.

6. FLOOR SHALL HAVE A WOOD TROWEL FINISH AND, EXCEPT WHERE USED AS JUNCTION BOXES, SHALL HAVE A
MINIMUM SLOPE OF 1:12 TOWARD THE OUTLET.

7. DEPTH V IS MEASURED FROM THE TOP OF THE STRUCTURE TO THE FLOWLINE OF THE BOX.

8. WALL THICKNESS AND REINFORCING STEEL REQUIRED MAY BE DECREASED IN ACCORDANCE WITH TABLE
LOCATED ON SHEET 2.

9. WALL THICKNESS SHALL BE STEPPED ON THE OUTSIDE OF THE BOX.

10. WHEN THE STRUCTURE DEPTH V EXCEEDS 4', STEPS SHALL BE CAST INTO THE WALL AT 15" INTERVALS FROM
15" ABOVE FLOOR TO WITHIN 12" OF TOP OF STRUCTURE. PLACE STEPS IN WALL WITHOUT PIPE OPENING,
OTHERWISE OVER OPENING OF SMALLEST DIAMETER.

11. ALTERNATE STEP MAY BE AN APPROVED STEEL REINFORCED POLYPROPYLENE STEP.

12. UPON APPROVAL OF THE ENGINEER, AS DEFINED BY SECTION 6703 OF THE BUSINESS AND PROFESSIONS
CODE, THE USE OF PRECAST STORM STRUCTURES IS ACCEPTABLE A AN ALTERNATE TO CAST-IN-PLACE.
PRECAST UNITS SHALL CONFORM TO ASTM STANDARDS AND BE MANUFACTURED IN A PERMANENT FACILilY
DESIGNED FOR THAT PURPOSE.

13. lYPICAL REINFORCEMENT LAP SHALL BE 30 TIMES THE BAR DIAMETER MINIMUM. DIMENSION T SHALL BE 6"
MINIMUM.

14. MARK EVERY STORM DRAIN INLET WITHIN THE PROJECT BOUNDARIES WITH ADHESIVE DECAL-DISCS ON
EXISTING INLETS OR AN IMBEDED CONCRETE STAMP ON NEW INLETS.

15. ON CURB INLETS, PLACE MARKER ON TOP OF THE INLET ROOF. ON CATCH BASIN, IMPRINT STAMP NEXT TO
INLET GRATE.
SHEET 1 OF 2
16. NO RECYCLED WATER SHALL ENTER INTO STORM DRAIN.

CllY OF SAN DIEGO -STANDARD DRAWING

DRAWING
NUMBER
SDD-114
BOX SECTION HORIZONTAL REINFORCEMENT

MAXIMUM SPAN DEPTH THICKNESS HOR. & FLR.


X OR Y v T REIN F.
3'-0" TO 4'-0" 6" #4 18"
4'-1" TO 7'-0" 4'-0" 6" #4 12"
7'-0" TO 8'-0" 6" #4 8"
3'-0" TO 4'-0" 6" #4 18"
4'-1" TO 5'-0" 6" #4 12"
4'-1" TO 8'-0"
5'-1" TO 6'-0" 6" #4 8"
6'-1" TO 8'--0" 6" #4 6"
3'-0" TO 4'-0" 6" #4 15"
4'-1" TO 5'--0" 8" #4 12"
8'-1" TO 12'-0"
5'-1" TO 6'--0" 8" #4 8"
6'-1" TO 8'--0" 8" #4 6"
3'-0" TO 4'-0" 8" #4 12"
4'-1" TO 5'--0" 8" #4 12"
5'-1" TO 6'--0" 12'-1" TO 16'--0" 8" #4 8"
6'-1" TO 7'--0" 8" #4 6"
7'-1" TO 8'--0" 8" #5 8"
3'-0" TO 4'-0" 8" #4 12"
4'-1" TO 5'--0" 10" #4 12"
5'-1" TO 6'--0" 16'-1" TO 20'--0" 10" #4 8"
6'-1" TO 7'--0" 10" #4 6"
7'-1" TO 8'--0" 10" #5 8"
3'-0" TO 4'-0" 8" #4 12"
4'-1" TO 5'--0" 10" #4 12"
5'-1" TO 6'--0" 20'-1" TO 24'-0" 10" #4 8"
6'-1" TO 7'--0" 10" #4 6"
7'-1" TO 8'--0" 12" #5 8"

SHEET 2 OF 2

REVISION BY APPROVED DATE RECOMMENDED BY THE CITY OF SAN DIEGO


CITY OF SAN DIEGO - STANDARD DRAWING ~MITTEE
ORIGINAL* KA . NAGELVOOR OV12

UPDATED FR . NAGELVOOR 07115


7/2V15
COORDINATOIY R.C.E. 56523 DATE
INLETS AND CLEANOUTS
DRAWING
NOTES AND DETAILS NUMBER
SDD-114
C A
TRANSI
TION TO NORMAL
CURB HEIGHT I
N 10'ON
BOTH SIDES UNLESS GALV.STEEL ANGLE
MANHOLE FRAME #4 AROUND OPENI
NG OTHERW I
SE NOTED CONTINUOUS AND
AND COVER
SEE M-1
C B PROTECTION BAR,
SEE NOTE 6 SEE SDD-102

C C #4 @ 6"
C

C
C
C

9"
C

C
C

6"
C
CURB LI
NE
C

C
O O

C C
C

C
4" RADI
US 4" RADI
US C C 1'
-0"
#4 @ 12"
C EDGE OF
C

GUTTER
12" WING W HERE
C

C C C
C C T C 6"
OCCURS ONE
1'
-6"
OR BOTH SIDES

C
SECTI
ON B-B
C
C C T
12" C A

C C B
C T L

CURB LINE
C
C
LENGTH SHOW N ON PLANS
SLOPE GUTTER 3"
PLAN

2'-0"
OR MATCH EXI STI
NG
#4 @ 6" ROADW AY SURFACE
11/
2" CLEAR
C

10" UNLESS
C

1'
-9"
C

C
SHOW N
C
C

1'-4"

C
C

C
30 DIA

OTHERW ISE
C
LAP

C
C

C
#4
C

9" C

C 9"
C

10 8"

C
C

CC
C 2"
C

6" MI
N C 1

C
C

C
3" CLR 2#6
V

7-1/
2" #4@ 12"
C 2#7
C
D

ROUNDED PIPE
C

C ENDS SEE D-61


30 DIA

C
C
LAP

#4 AROUND PI
PE ELEV.SHOW N
C

ON PLANS
C

OPTIONAL
CONSTRUCTION
C
C

SLOPE FLOOR 12:


1 1
12: JOI
NT 6" ABOVE
TOW ARDS OUTLET
I
NVERT
C

C Y C
T

C T C T
C 4'
-0" C
Y I
S DETERMI
NED BY PI
PE SI
ZE:4'MI
N,8'MAX C T C T

SECTI
ON C-C
SECTI
ON A-A
NOTES
1. TYPES ARE DESI
GNATED AS FOLLOW S:(
NO W I
NG)
A,(
ONE W I
NG)
A-1,(
TW O W I
NGS)
A-2.
2. EXPOSED EDGES OF CONCRETE SHALL BE ROUNDED W I
TH A RADI
US OF 1/
2".
3. W HEN V EXCEEDS 4'
,STEPS SHALL BE I
NSTALLED. LEGEND ON PLANS

4. CONCRETE GUTTER TO MATCH ADJACENT GUTTERS


5. AN EXPANSION JOI NT SHALL BE PLACED AT THE ENDS OF THE I
NLET W HERE THE CURB I
S
TO ADJOIN PER G-10.
6. PROVI
DE 1/4" TOOLED GROOVE I N TOP SLAB IN LI
NE W I
TH BACK OF ADJACENT CURB.
7. SURFACE OF TOP SLAB BE SI
DEW ALK FI
NISHED TO DRAI
N TOW ARD STREET AT A SLOPE OF
1/
4" PER FOOT.
8. ELEVATI
ON SHALL BE SHOW N ON THE PLANS W HERE I
NDI
CATED "O" SYMBOL.
9. SEE SDD-102 AND SDD-114 FOR ADDI
TIONAL NOTES AND DETAI
LS.

RECOMMENDED BY THE CI
TY OF SAN DI
EGO
REVI
SION BY APPROVED DATE
STANDARDS COMMITTEE
CI
TY OF SAN DI
EGO - STANDARD DRAW I
NG
ORI
GINAL* KA J.NAGELVOORT 01/
12

2/
25/
16
UPDATED RB J.NAGELVOORT 10/
15
COORDI
NATOR R.
C.E.56523 DATE
UPDATED HN J.NAGELVOORT 02/
16

CURB I
NLET -TYPE A DRAW I
NG
SDD-
115
NUMBER
MANHOLE FRAME
AND COVER SEE C A
M-1
#4 AROUND OPENI
NG

C
C 12"
TRANSI
TION TO NORMAL GALV.STEEL ANGLE
C

WI
NG,W HERE CURB HEIGHT I
N 10'ON CONTINUOUS AND
BOTH SIDES UNLESS PROTECT BAR,SEE
C

C OCCURS ONE OR
C
C

C OTHERW I
SE NOTED SDD-102
BOTH SIDES
#4 @ 6"
12" C

C B SEE NOTE 5

C
4'-3"

C C C
C

C 9"
C

6"
C
C

C
C
C

C
O CURB LI
NE #4 @ 12" C 1'
-0"
O O

C
C
4" RADI
US C 6"
C
C T
C
C C
C T C 6" 1'
-6"

C
EDGE OF GUTTER SECTI
ON B-B
C A C B
C
PLAN #4 @ 6" Y+ 10"
CURB LI
NE

C L 10" UNLESS
C #4 @ 12"
LENGTH SHOW N ON PLANS OTHERW ISE
3-#4 SHOW N
11/
2" CLEAR
C

C
C
2" C

C
C

C
C9"
C
C
C

C
1'-4"
30 DIA

C
LAP

C
C
C

#4
10
#4
C

C
1
C

C C 1'
-0"
C

6" C
MIN
V
C

3" CLR
C
OPTIONAL
C ROUNDED PIPE
7-1/
2" CONSTRUCTI ON
ENDS SEE D-61
JOI
NT 6" MIN
D

C
ELEV.SHOW N ABOVE INVERT
C

ON PLANS
30 DIA

C
LAP

C
#4 AROUND PI
PE
1
12:
C

C
C
C

SLOPE FLOOR 12:


1
C
T

TOW ARDS OUTLET


C Y C C 4'
-0" C
C T C T C T C T
Y I
S DETERMI
NED BY PI
PE SI
ZE-4'MI
N,8'MAX

SECTI
ON C-C SECTI
ON A-A

NOTES
1.TYPES ARE DESI
GNATED AS FOLLOW S:(
NO W I
NG)
B,(
ONE W I
NG)
B-1,(
TW O W I
NGS)
B-2.
2.EXPOSED EDGES OF CONCRETE SHALL BE ROUNDED W I
TH A RADI
US OF 1/
2".
3.W HEN V EXCEEDS 4'
,STEPS SHALL BE I
NSTALLED.
4.CONCRETE GUTTER TO MATCH ADJACENT GUTTERS. LEGEND ON PLANS

5.AN EXPANSI
ON JOINT SHALL BE PLACED AT THE ENDS OF THE I
NLET W HERE THE CURB
I
S TO ADJOIN PER G-10.
6.PROVI
DE 1/
4" TOOLED GROOVE I
N TOP SLAB I
N LI
NE W I
TH BACK OF ADJACENT CURB.
7.SURFACE OF TOP SLAB BE SI
DEW ALK FI
NISHED TO DRAI
N TOW ARD STREET AT A SLOPE OF
1/
4" PER FOOT.
8.ELEVATI
ONS SHALL BE SHOW N ON THE PLANS W HERE I
NDI
CATED BY "O" SYMBOL.
9.SEE SDD-102 AND SDD-114 FOR ADDI
TIONAL NOTES AND DETAI
LS.

RECOMMENDED BY THE CI
TY OF SAN DI
EGO
REVI
SION BY APPROVED DATE
STANDARDS COMMITTEE
CI
TY OF SAN DI
EGO - STANDARD DRAW I
NG
ORI
GINAL* KA J.NAGELVOORT 01/
12

UPDATED RB J.NAGELVOORT 10/


15
2/
25/
16
COORDI
NATOR R.
C.E.56523 DATE
UPDATED HN J.NAGELVOORT 02/
16
CURB I
NLET -TYPE B DRAW I
NG

NUMBER
SDD-
116
C
A
GALVANI
ZED STEEL
ANGLE CONTINOUS
AND PROTECTION
C B
BAR,SEE SDD-102
SEE NOTE 6 #4 @ 6"
C C
C

C
C
CURB LI
NE

C
C

C6"
C
#4 @ 12" C
O O O

C
C

C
C
1'
-0"
4" RADI
US

C C
TRANSI
TION TO C T C 6"
NORMAL CURB 1'
-6"
C HEI
GHT IN 10'ON
A C B
BOTH SIDES UNLESS
PLAN OTHERW I
SE NOTED.
SECTI
ON B-B

CURB LINE
10" UNLESS
C L OTHERW ISE
C SHOW N
LENGTH SHOW N ON PLANS C 1'
-9"
C C C
C T 11/
2" CLEAR C 6" C

C
C

C 3"

C
C
30 DIA.

C
C

1'-4"
LAP

2'-0"
C

C
C

C
#4
C

AT GRATE
#4 @ 6"

3 1/2"
C
C

C
10
C

1
3" CLR

V
C 6"
C ROUNDED
N
MI 7-1/
2"
PI
PE ENDS
SEE DRAW I
NG
4-#4 AROUND PI
PE OPTIONAL D-61 C
C C
CONSTRUCTION
C
ELEV SHOW N
JOI
NT 6" MI
N
30 DIA.

D ON PLANS
C

ABOVE INVERT
LAP

C
C
12:
1

C
C

C
C

T
SLOPE FLOOR 12:
1 C -6"
3' C
C 3'
-0" C C T C T
C T C T TOW ARDS OUTLET

SECTI
ON C-C SECTI
ON A-A

LEGEND ON PLANS
NOTES
1. TYPES ARE DESI GNATED AS FOLLOW S:( NO W ING)C,( ONE W I
NG)C-1,(TW O W INGS)C-2.
2. EXPOSED EDGES OF CONCRETE SHALL BE ROUNDED W I TH A RADIUS OF 1/2".
3. W HEN V EXCEEDS 4' ,STEPS SHALL BE I NSTALLED.
4. CONCRETE GUTTER TO MATCH ADJACENT GUTTERS.
5. AN EXPANSI ON JOI NT SHALL BE PLACE AT THE ENDS OF THE I NLET W HERE THE CURB IS TO ADJOIN PER G-10.
6. PROVIDE 1/4" TOOLED GROOVE I N TOP SLAB I N LINE W I
TH BACK OF ADJACENT CURB.
7. SURFACE OF TOP SLAB SHALL BE SI DEW ALK FI NI
SHED TO DRAI N TOW ARD STREET AT A SLOPE OF 1/4" PER FOOT.
8. W HERE INLET IS TO BE CONSTRUCTED ON GRADE AND D-3B CONCRETE APRON I S REQUIRED,LI
FT DOW N-GRADE END
OF GRATE.
9. SEE SDD-102 AND SDD-114 FOR ADDI TI
ONAL NOTES AND DETAI LS.
10. ELEVATI
ON SHALL BE SHOW N ON PLANS W HERE I NDI
CATED BY "O" SYMBOL.
11. DIAMETER D SHALL BE 24" MAXI MUM. FOR LARGER DI AMETER PI PES THIS DRAW I
NG MUST BE MODI FI
ED.

RECOMMENDED BY THE CI
TY OF SAN DI
EGO
REVI
SION BY APPROVED DATE
STANDARDS COMMITTEE
CI
TY OF SAN DI
EGO - STANDARD DRAW I
NG
ORI
GINAL* KA J.NAGELVOORT 01/
12

2/
25/
16
UPDATED RB J.NAGELVOORT 10/
15
COORDI
NATOR R.
C.E.56523 DATE
UPDATED HN J.NAGELVOORT 02/
16

CURB I
NLET -TYPE C DRAW I
NG
SDD-
117
NUMBER
MANHOLE FRAME
AND COVER SEE C B
M-1
#4 AROUND OPENI
NG

C
C 12"
C

C
C

C
12" C

SEE NOTE 7

A A
C

C
C
CURB LI
NE

C
4" RADI
US
6" C
C
C

EDGE OF
C B GUTTER
CURB LI
NE
PLAN

C
C
#4 @ 6" Y+ 10" CURB LI
NE
3-#4
#4 @ 12"
L C 4'
-0"
C
4" C C 4 1/
2"
C
LENGTH SHOW N C 6"

C
4" C C
ON PLANS

C
C
C6"
C

C
C

C
9"
#4
#4
6" C
C C1'-10"
C
MIN SEE C 2'
-0"
V

C
NOTE 2
C 1/
2" R TYP
ROUNDED PIPE SEE NOTE 3
ENDS SEE D-61

ELEV.SHOW N
C

ON PLANS
30 DIA

LAP

C
4-#4 AROUND PI
PE
1
12:
C

C
C
C

SLOPE FLOOR 12:


1
TOW ARDS OUTLET
C Y C
6" C C 6"
DETERMINED BY PI
PE SECTI
ON B-B
SIZE-4'MI
N,8'MAX

SECTI
ON A-A

NOTES
1. DI
MENSI
ON SHOW N BECOMES 2'
-0" W HEN OPENI
NG ON BOTH SI
DES. ADJUST MANHOLE AS REQUI
RED.
2. EXPOSED EDGES OF CONCRETE SHALL BE ROUNDED W I
TH A RADI
US OF 1/
2"
3. W HEN V EXCEEDS 4'
,STEPS SHALL BE I
NSTALLED.
4.CONCRETE GUTTER TO MATCH ADJACENT GUTTERS.
5.AN EXPANSI
ON JOINT SHALL BE PLACED AT THE ENDS OF THE I
NLET W HERE THE CURB
I
S TO ADJOIN PER G-10. LEGEND ON PLANS

6. PROVI
DE 1/
4" TOOLED GROOVE I
N TOP SLAB I
N LI
NE W I
TH BACK OF ADJACENT CURB.
7. MAI
NTAI
N 11/
2" CLEAR SPACI
NG BETW EEN REI
NFORCI
NG AND SURFACE UNLESS OTHERW I
SE NOTED.
8.SEE SDD-114 FOR ADDI
TIONAL NOTES AND DETAI
LS.

RECOMMENDED BY THE CI
TY OF SAN DI
EGO
REVI
SION BY APPROVED DATE
STANDARDS COMMITTEE
CI
TY OF SAN DI
EGO - STANDARD DRAW I
NG
ORI
GINAL* BB J.NAGELVOORT 01/
12

2/
25/
16
UPDATED RB J.NAGELVOORT 10/
15
COORDI
NATOR R.
C.E.56523 DATE
UPDATED HN J.NAGELVOORT 02/
16

M EDI
AN CURB I
NLET -TYPE J DRAW I
NG
SDD-
118
NUMBER
MANHOLE FRAME AND

4 1/2"
COVER SEE M-1.

ELEV.SHOW N ON
#4 @ 6" C B
PLANS

C
C
BOTH W AYS

C
C

C
C

C
C

C
11" UNLESS SHOW N

C 9"
C

C
9" OTHERW ISE ON
C

PLANS

V
ROUNDED PIPE 4-#4 AROUND
ENDS SEE D-61 PIPE
ELEV SHOW N
C OPTIONAL C C ON PLANS
C

CONSTRUCTION

T
C
JOI
NT 6" MI
N
D

ABOVE INVERT
C

D
C C
12:
1
C

C
C
C
SLOPE FLOOR

C
30 D 12:
1TOW ARDS
C C
LAP C OUTLET C 30 D
C C C C
T C C T T C LAP C T
(TYP)
C B

SECTI
ON A-A SECTI
ON B-B

4- (
#4)
AROUND
OPENING C 2"
C

C
C

A A
C

C
C

3'-5"
C

C 4'
C

PLAN

NOTES
1. W HEN V EXCEEDS 4'
,STEPS SHALL BE I
NSTALLED.
2. EXPOSED EDGES OF CONCRETE SHALL BE ROUNDED W I
TH A RADI
US OF 1/
2".
3. CONSTRUCT OPENI
NGS ON BOTH SI
DES UNLESS OTHERW I
SE SHOW N ON PLANS.
4.MAI
NTAI
N 1-1/
2" CLEAR SPACI
NG BETW EEN REI
NFORCI
NG AND SURFACE.
5.I
NSTALL 1" STEEL PROTECTI
ON BAR.
LEGEND ON PLANS
6. DI
AMETER "D" SHALL BE 18" MAX,FOR LARGER DI
AMETER PI
PES THI
S DRAW I
NG MUST
BE MODI
FIED.
7.SEE SDD-114 FOR ADDI
TIONAL NOTES AND DETAI
LS.

RECOMMENDED BY THE CI
TY OF SAN DI
EGO
REVI
SION BY APPROVED DATE
STANDARDS COMMITTEE
CI
TY OF SAN DI
EGO - STANDARD DRAW I
NG
ORI
GINAL* KA J.NAGELVOORT 01/
12

2/
25/
16
UPDATED RB J.NAGELVOORT 10/
15
COORDI
NATOR R.
C.E.56523 DATE
UPDATED HN J.NAGELVOORT 02/
16

CATCH BASI
N -TYPE F DRAW I
NG
SDD-
119
NUMBER
10'
12"
Type C-1
curb inlet
r B Top of
curb line

r------------,,------,
A I1 Ii I1 A
l_ l======t=======================:::::::;====:t::Z::=--=-=-=-=-=-=-=-=--=-~:h:mrrmrrrrrt!F~:;;~~;-~ t

Match slope and g'


profile of pavement

PLAN

Variable gutter depression

Normal curb face 10' I cur


10"
ace
\

SECTION A-A

6'

Meet normal crown


or existing pavement
NOTES
SECTION 8-8
1. Curb and apron to be placed monolithically.
2. Use of false header at valleys and slope
break line is optional.
3. Extend vertical steel from inlet structure
into concrete apron as shown on Section 8-8 of D-03A. LEGEND ON PLANS
4. Concrete shall be 520-C-2500.

Revision RECOMMENDED BY THE SAN DIEGO


SAN DIEGO REGIONAL STANDARD DRAWING REGIONAL STANDARDS COMMITITE
ORIGINAL Kercheval 2 75
Add Metric T. Stanton 03/03 7(c6(ZOIZ

Reformatted T. Stanton 04/ 0 6


CONCRETE APRON FOR TYPE C CURB INLET
Replaced D-2 T. Stanton 02/09 DRAWING
Edited S.S. T. Regello 03/1 1 NUMBER D-038
FOR DRAWING D-3A SEE DRAWING SDD-117
2-#4 bar

#4 bars
placed diagonally I-

A A

L J >-

I-

PLAN
TYPE PIPE DIAMETER (01) x y z
{See Note 8)
A4 up to 39" 4• 4' 6'
to 42" to 48" 5• 4• 6'
A6 51" to 60" 6' 4' 6'
A7 53• to 66" 7' 4' 7'
"8 69" to 78" 8' 4• 8'

Bend down---~ See M-3 for manhole


15" (typ) frame and cover

See D-1 1A for step details

Diagonal bars 4-#4 around pipe


2-#4 bars-----+-......... Optional construction j oint
6" min above invert
Slope floor 12:1
towards outlet

Elev shown
on plans

I-
1 .---~-.30 D Lap (typ 11
I • - - x - - - - -·iTI--
--i1-..
NOTES SECTION A- A
1. See D-11 A & D-11 B for additional notes and details.
2. Concrete base shall be 560-C- 3250.
3. All precast components shall be reinforced with 1/4"
diameter steel, wound spirally on 4" centers.
4. All joints shall be set in Class C mortar.
5. Maintain 1-1 ;2· clear spacing between reinforcing and concrete
surface unless otherwise noted. LEGEND ON PLANS
6. Exposed edges of concrete shall be rounded with a radius of 1/2".
7. Manhole cover to be marked •storm Drain".
8. Modifications to "Y" dimension required if pipe (02) exceeds 39".
==@):::=
9. If constructed adjacent to sidewalk. top of manhole to match sidewalk slope.

Revision RECOMMENDED BY THE SAN DIEGO


SAN DIEG O REGIONAL STANDARD DRAWING REGIONAL STANDARDS COMMITTEE
ORIGINAL Ker cheval 12 75
Add l.letric 7(c6(ZOIZ
T. Stanton 03/03
Reformatted T. Stanton 04/06 STORM DRAIN CLEANQUT - TYPE A
Edited T. Stanton 02/09 ORA\li1NG
Edited S.S T. Regello 03/11 NUMBER D-09
FOR DRAW INGS D-1 1A A ND D-1 1 B, SEE DRAW ING SDD-114
#4 @ 6" oc #4 bars placed diagonally

I-

I-

--h,___
I _ Y_ _ lr~
A ---1
PLAN
TYPE PIPE DIAMffiR (01 ) x y z
B5 up to 51" 5' 4' 5'
B6 54" to 60" 6' 4' 6'
B7 63" to 69" 7' 4' 7'
See M-3 far manhole
BS 7r to s1· 8' 4' 8' frame and cover
89 84" to 90" 9' 4' 9'
(

• x
3' co c
~:::::;:

See D- 1lA for


step detail _ _ ....,._,,.'---. ;.,,
NOTES ... c "'0
1. See D-11 A & 0-11 B for . 0
(._)

additional notes and details.


2. All joints shall be set in
""
Class C mortar. Bend down
4' Dia ---I-
(/)
>
Q)
3. All precast components 15" (typ)
shall be reinforced with ~
1/4" diameter steel wound 4-#4
Rounded pipe around pipe
spirally on 4" centers. ends see D-61
4. Maintain 1-1 /2" clear Slope floor 12:1
spacing between reinforcing towards outlet
and concrete surface. Elev shown
5. Concrete base shall be on plans -r-=:1::--.tr
560-C-3250.
6. Exposed edges of concrete I-
shall be rounded with a
1/2" radius.
7. Manhole cover to be
marked "Storm Drain".
SECTION A- A
8. Modifications to "Y" dimension
required if pipe (02) exceeds 39". LEGEND ON PLANS
9. If constructed adjacent to sidewalk,
top of manhole to match sidewalk slope. = =l£F =
Revision Date RECOMMENDED BY THE SAN DIEGO
SAN DIEGO REGIONAL STANDARD DRAWING REGIONAL STANDARDS COMMITTEE
ORIGINAL Kercheval 12 75
Add Metric T. Stanton 03/03 7/Z6/ZOIZ

Reformatted T. Stanton 04/06 STORM DRAIN CLEANOUT TYPE B


Edited T. Stanton 02/09 DRAWING
Edited s.s T. Regella 03/11 NUMBER D-10
FOR DRAWINGS D-11AAND D-1 18, SEE DRAWING SDD-114
A-,
___j_
f
~
'
.--

D
I I
I I
I I
L.J
~L4" X 3" X 1/4"
D
I I
I I
I I
L.J

•.--
I
"c-.1

r,
I I
r,
I I
I I (\ 3/16. I I
I I r--.... 3/16" I I
r) v
~
r)
4/
~ "\

3.

I
3'-5 3/8.

A__I
I :I
PLAN

~[ ~ ~
~0".#1 w~
~
~

•co
I~ '-" v
3/16. (typ)

4.
~ r- ~1/2"mo. Anchors
I 2. I

SECTION A-A
NOTE
Hot dip galvanize all parts after fabrication.

Revision By Approved Date RECOMMENDED BY THE SAN DIEGO


SAN DIEGO REGIONAL STANDARD DRAWING RE~ COMMITTEE
ORIGINAL Kercheval 12/75
Add Metric T. Stanton D3/03 ' .}J1:J((,IAA7uvJ 7/Z6/ZO/Z
Reformatted T. Stanton 04/06
WELDED STEEL GRATE FRAME Chairperson R.C.E. 19246 Date
Edited T. Stanton 02/09 DRAWING
Edited s.s. T. Regello 03/11 NUMBER D-13
5-5/8" 3/8" dia. round bars
I. .I. .I
4"

! -
~

•OCl
' '
r-...
l()

..-
..-
f
•OCl
I
..-
'
A
' A

/~ 1/2"x 3/8"
end bars

...-
I

~
8 ...,
..- /_
'
0)
.L
L I z
t
3-1 /2" x 3/8" bors ~ 8J 77 3/16" fillet weld full
depth each side on
3'-4" outside bars & every
3rd internal bearing
terminal bar
PLAN

3/8" dia.
" 1/8"
round b a r s \ / v (typ) 7/16"
11·
u • u
('J

2-1/2" X 3/8"_/
'
..-
I"")
I

end bars 2-1/2" X 3/8"


end bars
SECTION A-A SECTION 8-8

NOTES
1. Hot dip galvanize all parts after fabrication.
2. Dimensions are to centerline of bars unless otherwise noted.
3. Not to be used in pedestrian areas.
4. Weight: 2001bs +/-

Revision By Approved Date RECOMMENDED BY THE SAN DIEGO


SAN DIEGO REGIONAL STANDARD DRAWING RE~ COMMITTEE
ORIGINAL Kercheval 2/75
Add Metric T. Stanton 03/03 ' .}J1:J((,IAA7uvJ 7/Z6/ZO/Z

Reformatted T. Stanton 04/06


DRAINAGE STRUCTURE GRATE Chairperson R.C.E. 19246 Date
Edited T. Stanton 02/09 DRAWING
Edited s.s. T. Regello 03/11 NUMBER D-15
l 3" X 2-112" X
318" rivet, spot weld
or tack weld at 1IB
better to CSP

Punch 1" hole in CSP.


Place pipe so bars of

~
grate will be parallel with
main surface flow.
318" rivets, spot weld

See Detail "A"


r or tack weld at 1IB
points or better

ID = 3'
Inlet pipe
4"
L I". . II See Detail "8"

a" r --~ ~ (S ee Section A-A


fo r bottom design)
SECTION C-C
TYPE 8
Join dia base

SECTION A-A
lYPE A 112" dia. min.
Slot 314" x

1-3116"
~ 1-9 16
I ..
1I 4" checkered plate ~
.314"
.3IB" rivets, spot weld or tack
weld at 1IB points or better
I I

I SECTION F-F

112" die. x 3"


9116" hole in angle
DETAIL "8" Slot .314" X 2"
1I 4" checkered plate

NOTES
1. All components shall be galvanized. 1-118"
~1"--=o\.!fi'Jt--....1~ i
Tack weld 18" of 114"
2. Inlet and outlet pipes shall be set at factory and heat-treated chain to frame
positioned as shown on plans. and cover (See Note 5)
3. See D-178 for ladder and step details.
4. See D-17A for additional grate details.
5. Grate to be provided when specified.
6. Grate detail shall be as shown on D-17A unless 318" rivets, spot weld or tack weld at
otherwise approved by Agency. 1IB points or better

DETAIL "A"
Revision RECOMMENDED BY THE SAN DIEGO
SAN DIEGO REGIONAL STANDARD DRAWING REGIONAL STANDARDS COMMITTEE
ORIGINAL
Add Metric T. Stanton 03/03 7/Z6/ZO/Z

Reformatted T. Stanton 04/06 CORRUGATED STEEL PIPE INLETS


Edited S.S. T. Regella 03/11
TYPES A AND B DRAWING
NUMBER D-16
3,;'16"

Provide
cross bars
optional spacing
4" or 6"

L 3" X 2-1/2'' X 3/8"

GRATE DETAILS

2-1/2'' 2'' clr H j-1/2"


L 3" x 2-1/2" x 3/8" or 3"
or L 3" x 3" x 3/8"
Standard end finish~ss::t:5r---,:::::n
Lug 3/4" dia. x 1 1/2"-~~____E;:U
1" hole in pipe
to receive lug
2.:fJ11JJlSECTION 8-B

DETAIL A ALTERNATIVE CAST NODULAR IRON GRATE


OR CAST STEEL GRATE

1 - - - - - - 1 "'6-----IT--< 118
3/8" dia. cross bars may be fillet welded,
resistance welded or electroforged to
bearing bars. CROSS BAR DETAIL
CROSS BAR DETAIL lYPE ALTERNATIVE CAST NODULAR
WELDED STEEL GRATE IRON GRATE OR CAST STEEL GRATE

GRATE BAR SPACING TABLE


y
NO. OF CLEAR BAR X 4" 6"
lYPE BARS SPACING SPACING SPACING
Welded Steel 15 2" 9/16" 3-3/4" 5-3/4"
Cast 13 2" 2-1/8" 3-3/4" 5-3/4"

Revision By Approved Date RECOMMENDED BY THE SAN DIEGO


SAN DIEGO REGIONAL STANDARD DRAWING REGIONAL STANDARDS COMMITTEE
ORIGINAL Kercheval 2/75
Add Metric T. Stanton 03/03 7/Z6/ZO/Z

Reformatted T. Stanton 04/06 CORRUGATED STEEL PIPE INLETS, Chairperson R.C.E. 19246 Date
Edited T. Stanton 02/09
DETAILS DRAWING
Edited .s. T. Regello 03/11 NUMBER D-17A
Grind all exposed
corners 1I 4" radius

6" x 1I 4" x 6" plate washer


with 7 18" dia. hole
1'-4" min
L.
0

";q.

1"

2-112" X Splice Plate


rails 2-112" X 318" X 10"

314" or 1' dia.


galv. steel rungs SIDE VIEW
FRONT VIEW
314" dia. bolt
1" dia.
holes in pipe ----,...~ =---- 2" x 3116" x 2" plate washer

7"

LADDER DETAIL
H=5' or greater

7"
314"~~
~ t]f
•~
+
SIB" dia. hales
foe 1/2" dio. bo"'

314" dia. Plate


galv. steel step
NOTE 2-112" X 318" X 1'
See Note 3 on D-16 for STEP DETAIL
ladder requirements.
H=3'-6" to 4'-11"
Revision RECOMMENDED BY THE SAN DIEGO
SAN DIEGO REGIONAL STANDARD DRAWING REGIONAL STANDARDS COMMITTEE
ORIGINAL Kercheval 2/75
Add Metric T. Stanton 03/03 7/Z6/ZO/Z

Reformatted T. Stanton 04/06 CORRUGATED STEEL PIPE INLETS,


Edited T. Stanton 02/09
DETAILS DRAWING
Edited s.s. T. Regello 03/11 NUMBER D-178
2' min s• PCC 2' min
plug or metal cap

ELBOW TEE
I
TEE-SAG CONDmON

See Note 8 Standard band

BAND PLUG
OVERSIDE DRAIN /4• galvanized pipe
~E o.o79· square sheet
Cross bar s~cer T k weld Nate:
see Note 3 "D.· equals [IOminal
\r-~~
j_ p1pe iliameter
3/16• X
1-1/2.
fillet weld
Tack weld circular

J I~-J/~E
4~ ll:s/16. SECllON E-E
METAL CAP DETAIL
bgnd to flat sheet
at B equar spaces

SEcnON_D-0 NOTES
GRATE SLOT DETAIL 1. Drain seams may be constructed by riveting or resistance spot-
Min weld length
welding, continuous helical lock seam or helical welding
1-1/2•; weld
size 3/16• min seam at equal centers.
ea cross bar 2. Each drain section shall be assembled with standard coupling
bands.
3. Cross bar spacer of grate shall be pressure fused or plug
welded to bearing bars in such a manner os to develop
the strength of the cross bar spacer.
4. Cross bar spacer (Section E-E) may differ from that
L.-o GRATE SLOT WELDING DETAIL
shown provided section area is equal or greater.
5. Grate material shall be a weldable grade of steel complying
to the requirements of ASTM A 36.
20' Unit 6. The maximum variance from a straight line from the

l t-~
1
" ~Grate slot welded~ pif!e • ---1 ~"
!~I
erlreme top comers of the bearing bar shall be
1/2• in 20'.

r=
7. Installation lengths shall be 10' or multiples thereof.
8. Either field joint sealed with a pliable mixture of sand,
portland cement and emulsified asphalt (Mixture of 1 port
portland cement. 3 - 5 parts sand and 1-1 /2 ports SSI
GRATE SLOT DRAIN emulsif~ed asphalt), or continuous weld.

RECOMMENDED BY lHE SAN DIECO


SAN DIEGO REGIONAL STANDARD DRAWING REGIONAL STANDARDS COMMITIEE
ORIGINAL
Add Metric: T. stanton 7/Z6/Z0/Z

Reformatted T. Stanton 04/08


SLOTTED CORRUGATED STEEL PIPE DRAINS
Edited T. stanton 02/09 12• THROUGH 24• DRA'MNG
Edited S.S T. Regello 03/11 NUMBER D-18
Q)

~
.....
Q)
:::::
::::J ~I
~I
(.!)

~I
c
t31
I
I SECTION A-A
.::::
0
:eUl
s:::::
.E .::::
c
..........
0 .....
~
::::J
(.!)

l
SECTION 8-8

PLAN
3'
Type 8 AC dike - j 6" 1· •16" f--
(per G-5) ~ 1 ____1_ I ~

~ ALTERNATE SECTION 8-8


2" AC

NOTES
1. AC spillway may be used when fill is 10' or less,
and where fill slope 1-1/2:1 or flatter.
2. Use 10' min length of gutter transition on each
side of downdrain in sag condition. LEGEND ON PLANS
3. Cross sectional area of ditch {Section 8-8) may be
trapezoidal or semi-circular; semi-circular sectional
area must provide an equal flow capacity as trapezoidal. sag condition J-~~
Revision RECOMMENDED BY THE SAN DIEGO
SAN DIEGO REGIONAL STANDARD DRAWING REGIONAL STANDARDS COMMITTEE
ORIGINAL
Add Metric T. Stanton 7/Z6/ZO/Z

Reformatted T. Stanton 04/06


ASPHALT CONCRETE SPILLWAY
Edited T. Stanton 02/09 DRAWING
Edited S.S. T. Regello 03/11 NUMBER D-22
0.64" galvanized
corrugated metal
flume--7

10' max
4'

PLAN
0.1 09" thick
Weld galv bulkhead

Top of AC dike

0.064• thick galv

5/16" X 3/4" 5/16" galv metal


slotted holes for band in 3/8" x 1"
galv bolts slotted holes

TAPERED INLET
SECTION A-A

3/4" '
Drill and tap for 1/2" _ t f t l 3-1/2" X 2"

.gnr=Rt--2"
x 1-1 /2" bolt-----IJil
t x 1/4" min galv
dia hole
i
< ~
1-1/2"
1-1 /2'' Pipe stake
~
-1 1--1-1/2"

6' long each side of flume

Flatten or point

NOTES ANCHOR-DETAIL
1. Downdrain flume may be used where fill slope is LEGEND ON PLANS
1 1/2:1 or flatter.
2. Use 10' min length of gutter transition on each _/···---~ , -
side of downdrain in sag condition. . 1
3. All metal parts to be galvanized after fabrication. sag condition

Revision RECOMMENDED BY THE SAN DIEGO


SAN DIEGO REGIONAL STANDARD DRAWING REGIONAL STANDARDS COMMITTEE
ORIGINAL Kercheval 12 75
Add Metric T. Stanton 03/03 7/Z6/ZO/Z

Reformatted T. Stanton 04/06


Edited T. Stanton 02/09 DRAWING
Edited s.s. T. Regello 03/11 NUMBER D-23
Monolithic
gutter

1-41---+--Curb line
Dimensions shown on plans

PLAN
8
f403"0C 1
Manhole frame and cover, see M-2
May be
open 4" min I
channel~ #4 0 3" OC total 4
4 0 6" OC both ways
continuous

Slope---~.--.------L~....:.....;
I")

La ~~ ex;sting
curb and gutter
SECTION A-A and construct
gutter monolithic
with curb outlet

...

6
.j lle3-14
1--y--1
I 2-1/2" X 2" X 1/4"
x 4' gaiVCJnized steel
ANCHOR DETAIL angle
SECTION 8-8
NOTES
1. Concrete shall be 560-C-3250.
2. D=inside diameter of pipe or depth of channel.
3. Section to be sloped laterally with top conforming to the grades of the LEGEND ON PLANS
existing sidewalk and curb.
4. Manhole frame and cover may be deleted with open channel.
5. Trowel finish top surface and reproduce maricings of existing sidewalk and curb. ---~
---~
6. Trowel finish floor of outlet.
7. Provide 1/4" tooled groove in top slab in line with back of curb.

RECOMMENDED BY lHE SAN DIEGO


SAN DIEGO REGIONAL STANDARD DRAWING REGIONAL STANDARDS COMMIT1EE

7(Z6(ZOIZ

CURB OUTLET - TYPE A


DRAWING
Edited S.S. T. Regello NUMBER D-25
A~
\_ Sidewalk cuts

-_-_-_ P" G-1/ ---------J-_--


8

E r-
j
Q)
:§ A~
Q)

~
Q)
PLAN :§
c.. ..c
..... Gutter
e :::l

t D... (..)

6 1/2" min ~

.. .. ·,· .. .: .
...
1\
..
... ·. ·.
t l: ~ ~-

SECTION
-e:::l
(..)

Pipe to be finished
flush with curb.

min
. ...,
_l_ <I . ~..
.
4ft': . 4

. .,

SECTION 8-8
SECTION A-A

~
Q)
APPROVED DRAIN PIPE SIZES c..
e
D...
PIPE SIZE CURB HEIGHT AT CURB FACE
3" 6" to a·
4" 8" T
6" 10"

NOTES
1. Pipe shall be one continuous length from property line to curb line.
2. Multiple pipes to be set a minimum distance of D/2 apart (3 max). Drain shall not occupy
3. Concrete shall be 520-C-2500. the hatched area
4. Pipe shall be circular rigid plastic, or approved equal.
5. Coring of existing curb may be used as an alternative. BLOCK CORNER
6. Provide 1/4" tooled groove in top slab in line with back of adjacent curb.

Revision By Approved Date RECOMMENDED BY THE SAN DIEGO


SAN DIEGO REGIONAL STANDARD DRAWING REGIONAL STANDARDS COMMITTEE
ORIGINAL Kercheval 2 75
7(26(2012
Add Metric T.Stanton 03 03
eformatted
Edited
T.Stanton 04/06
S.S. T. Regello 03/11
SIDEWALK UNDERDRAIN PIPE
DRAW1NG
NUMBER D-27
~B

A I I A

l j
I I
L_______ J

~B
PLAN

See D-13 & D-15 for


Top of grate frame and grate detail ------,.
elevation shown
on plans

"h'11o=-1--#7 bend down


"'
§ 3" Fillet
a~ into wall
. ~; a.
.. > c:
• ' ·; 0
c:
:I:
0
.i=
0
::;:; 0..
"'
0
0,...., _J

. .. . .
·
I I

Tj 3' j T ,,___ 3'-3 1/2" _


I
1 1/2" typ
• I T It---

4-#4 around
pipe opening
SECTION A-A SECTION 8-8

NOTES LEGEND ON PLANS


1. See D- 1lA &: D- 118 for additional notes and details.
2. When V exceeds 4', steps shall be installed per D-1 1A. ===~
Revision By Ap roved Date RECOMMENDED BY THE SAN DIEGO
REGIONAL STANDARDS COMMITTEE
SAN DIEGO REGIONAL STANDARD DRAWING
ORIGINAL Solomon 7 79
Add Metric T. Stanton 03/03 7(26( 2012

Reformatted T. Stanton 04/06 CATCH BASIN TYPE I


Edited s.s T. RegeUo 03;11 DRA'MNG
t-----+--+-----+--~
NUMBER D-29
FOR DRAWINGS D-11A AND D-118, SEE DRAWING SDD-11 4
FRONT ELEVATION FRONT ELEVATION
SINGLE HEADWALL DOUBLE HEADWALL

9"-11i-
II
cl! ~7I 1/2"
Rounded pipe ends,
see D-61 6
Flowline elev
shown on plans
7 1/2"
b-.ttl~··
~--y
t
SECTION, SINGLE &
DOUBLE HEADWALLS

SINGLE DOUBLE
D H
L 1t~: 1 Concrete
C.Y. L tteel
s.
Concrete
C.Y.
12" 2'-8" 5' 35 0.60 8' 50 0.94
15" 2'-11" 6' 40 0.75 9'-6" 60 1.17
18" 3'-2" 7' 50 0.91 10'-6" 75 1.35
21" 3'-5" 7'-6" 60 1.02 11'-6" 90 1.52
24" 3'-8" 8'-6" 75 1.20 12'-6" 100 1.72
27" 3'-11" 9'-6" 85 1.39 14' 115 2.00
30" 4'-2" 10' 85 1.52 15' 126 2.21
33" 4'-5" 11' 100 1.73 16' 130 2.42
36" 4'-8" 12' 105 1.95 17' 145 2.65
39" 4'-11" 12'-6" 130 2.09 18' 170 2.88
42" 5'-2" 13'-6" 140 2.34 19' 185 3.13
45" 5'-5" 14'-6" 150 2.60 20' 195 3.38
48" 5'-8" 15' 160 2.75 21' 200 3.64
51" 5'-11" 16' 180 3.03 22'-6" 225 4.02
54" 6'-2" 17' 190 3.31 23'-6" 240 4.30
NOTES
1. Concrete shall be 560-C-3250.
2. All reinforcing shall be #4 bars. All vertical and horizontal tie bars @ 18" maximum spacing. LEGEND ON PLANS
3. Exposed corners shall be 3/4" chamfered.
-----=[]
-----
Revision By Approved Date RECOMMENDED BY THE SAN DIEGO
SAN DIEGO REGIONAL STANDARD DRAWING RE~ COMMITTEE
ORIGINAL Kercheval 2/75
r===~~~==~~~----------------------------------~~,~~7~
Add Metric T. Stanton 03/03 ~~ao~
Reformatted T. Stanton 04/06 STRAIGHT HEADWALL • TYPE A
Chairperson R.C.E. 19246 Dote
Edited T. Stanton 02/09 DRAW1NG
Edited s.s. T. Regello 03/11
!CIRCULAR PIPE]
NUMBER D-30
S/2(1'~ ·-
~ ~Chamfer
\--.-=-------.-'"-...-

'-fll~IThfi )__,___J_I ~~ill~ll- •


I I I
t
I i I 1 s -{ .c ~ ~ i 1 l , s·l I i i ~ s ) i ! l
I I I I I I ----.---_,__til I I I I I I

~---------------~
L 8•) l L J
ELEVATION - DOUBLE HEADWALL ELEVATION - SINGLE HEADWALL

Flowline elev
shown on plans

SECTION, SINGLE &


DOUBLE HEADWALLS

C.S.P. SINGLE DOUBLE


ARCH L
SIZE H L Steel Concrete Steel Concrete
inches ft/in ft/in Lbs. C.Y. ft/in Lbs. C.Y.
18x11 2 -7" 5'-6" 37 0.64 8' 52 0.91
21x15 2'-11" 6'-6" 45 0.80 10' 60 1.22
24x18 3'-2" 7'-6" 50 0.96 11 '-6" 70 1.45
28x20 3'-4" 8'-6" 60 1.12 13 -6" 90 1.76
35x24 3'-8" 10'-6" 85 1.47 15-6 120 2.16
42x29 4'-1" 12'-6" 110 1.76 18' 145 2.57
49x33 4'-5" 14'-6" 130 2.26 21' 170 3.13
57x38 4'-10" 17' 155 2.81 24-6 210 3.86
64x43 5'-3" 19' 175 3.31 27' 230 4.42
71x47 5'-7" 21' 195 3.81 30' 255 5.09

NOTES
1. Concrete shall be 560-C-3250.
2. All reinforcing shall be #4 bars. All vertical and horizontal tie bars @ 18" maximum spacing. LEGEND ON PLANS
3. Exposed corners shall be 3/4" chamfered.
-----=[]
-----

Revision By Approved Date SAN DIEGO REGIONAL STANDARD DRAWING ~~g?~~i~Ec~":t.u~~o


ORIGINAL Kercheval 2/75 ~
rA~dd=M~~~ric~-rT=.S~ta~nt~on=r0=3/~03~-----------------__,l'~~7~ ~~ao~

Reformatted T. Stanton 04/06 STRAIGHT HEADWALL • TYPE A Chairperson R.C.E. 19246 Date

Edited T. Stanton 02/09 !CORRUGATED STEEL PIPE - ARCHJ DRAW1NG


D-31
Edited S.S. T. Regello 03/11 NUMBER
3/4" chamfer

AI- r-D/2 (1' min) 10"


II
•0
-
~
I ~
......-1
. ~see D-61 for
rounded pipe ends
- ,.--
lf ~ ft= ~~ c
\~ ~I \~ ~I
"- - ::c - f--

~
< .1'----- Flowline
elev
·:~.:· ~· ::·. ·~~:·. shown on plans
·.·,;:·: .~·: . ~.
•..... ~ .\

I. A~
L
·I n
DOUBLE PIPE SECTION A-A
ELEVATION
AI 3/4" chamfer

/f1\\
\~ ~I
"-

I· A~
L
.I
SINGLE PIPE
ELEVATION

SINGLE DOUBLE
D A B H
L
~crete
L conc.~e
C.Y.
12 2 1 4 4 0.45 5-8 .62
15" 2 1-1" 4-3" 5 0.63 7 -1" .85
18" 2 1-2" 4-6" 6 0.83 8-6" 1.12
24 2-6 1-5 5-6 8 1.54 11-4 2.09
30" 2-6" 1-9" 6 10 2.41 14-T 3.26
36 3 2 7 12 3.74 17 5.05

LEGEND ON PLANS
NOTES
1. Concrete shall be 560-C-3250.
2. Exposed comers shall be 3/4" chamfered.
---=O
---

Revision By Approved Date RECOIAIAENDED BY THE SAN DIEGO


SAN DIEGO REGIONAL STANDARD ORA WING RE~ COIAMimE
ORIGINAL Kercheval h2/75
Add Metric T. Stanton 03/03 . . . ._ _;pp.Jti0IIfl-t) 7/26/20/2
Reformatted T. Stanton 04/06 STRAIGHT HEADWALL - TYPE B Chairperson R.C.E. 19246 Date
Edited T. Stanton 02/09
!CIRCULAR PIPEI DRAWING
Edited s.s. T. Regello 03/11 NUMBER D-32
AI
3/4" chamfer
- i-S/2 (1' min) -j1o"f-
~Rounded p;pe ends,
see D-61
-
~

(;'\ ~ :::c
I
I
I
I
I -
'---"" '---"" I
I

~I'-- Flowline
<(

..•··. elev
shown on plans
I. ·I
8

I· A~
L
·I
DOUBLE PIPE SECTION A-A
ELEVATION

3/4" chamfer AI

0
I· A~
L
·I
SINGLE PIPE
ELEVATION

SINGlE DOUBLE
CSP ARCH SIZE A B H Concrete Concrete
L L
CY CY
18" X 11" 2 1'-2" 3'-11" 6' 0.83 7'-3" 0.97
2,. X 15" 2' 1'-4" 4'-3" 7' 1.08 9'-8" 1.46
24" X 18" 2' 1'-6" 4'-6" 8' 1.41 11'-6" 1.98
28" X 20" 2'-6" 1'-8" 5'-2" 9' 1.97 12'-6" 2.66
35" X 24" 2'-6" 2' 5'-6" 10' 2.56 14'-5" 3.60

NOTES LEGEND ON PLANS


1. Concrete shall be 560-C-3250.
2. Exposed comers to be 3/4" chamfered.
----=[]
----

Revision By Approved Date RECOMMENDED BY THE SAN DIEGO


SAN DIEGO REGIONAL STANDARD DRAWING RE~ COMMITTEE
ORIGINAL Kercheval 2/75
Add Metric T. Stanton 03/03 I.....__ _}!:f;Ftr,u<7~ 7(26(2012
Reformatted T. Stanton 04/06 STRAIGHT HEADWALL - TYPE B Chairperson R.C.E. 19246 Date
Edited T. Stanton 02/09
!CORRUGATED STEEL PIPE - ARCH! DRAW1NG
Edited s.s. T. Regello 03/11 NUMBER D-33
- 1-#
,....,..,..,
:~. ••.. 2. CLR
#4@ 12" oc
-
(both ways) '/1 .:·.~·
:.;:·~:·
....
J t
~

.. •·. ~. ::
:
.
SECTION A-A

#4 0 12" oc
(both ways)
U TYPE WING TYPE
PLAN 8"
r8
WING WALL
REINFORCING

Alternate 1'
Detail C
'--8
ELEVATION 8-8 ALT DETAIL C

lliiNSIONS SNli.E PIPE DIXB.E PfE


IliA UlYPE WING lYPE UlYPE WING lYPE
OF
w c~. w
~ c(~· rn~ ~~· ~ c(w· rn~
PfE L E F

18" 2'-3 1/8" 1'-3" 1'-10 1/2" 2' 0.55 35 0.63 43 0.82 53 0.90 61
V>

~
c...
24" 3'-1 7/8" 1'-9" 2'-7 1/2" 2'-6" 0.79 47 0.93 60 :z: 1.22 73 1.36 86
C>

30" 4'-5/8" 2'-3" 3'-4 1/2" 3' 1.05 71 1.29 85 ~ 1.66 109 1.92 123
=
V>

~
36" 4'-11 1/2" 2'-9" 4'-1 1/2" 3'-6" 1.33 88 1.69 114 2.19 136 2.55 162

NOTES
1. Concrete shall be 560-C-3250.
2. Exposed corners to be 3/4" chamfered. LEGEND ON PLANS
3. Multiple pipes to be set a distance of D/2, with a 1' minimum between outside diameters of pipes.
4. Top of headwall shall be placed approximately parallel to profile grade when the grade is 3% or more.
5. Skewed pipes: Dimension W to be increased in width or length due to skew or multiple pipes. ----r;:::::l
---~
6. For pipe wall thickness greater than 3" use Alternate Detail C.

Revision By Approved Date RECOMMENDED BY THE SAN DIEGO


SAN DIEGO REGIONAL STANDARD DRAWING REGIONAL STANDARDS COMMITTEE
ORIGINAL Kercheval 2 75
Add Metric T. Stanton 03/03 7(26(2012

Reformatted T. Stanton 04/06 WING AND U TYPE HEADWALLS


02/09 DRAW1NG
Edited
s.s.
T. Stanton
FOR 18• TO 35• PIPES D-34
Edited T. Regello 03/11 NUMBER
w
L ==::"T"=--=---.==--==~=.
~
1 1/2" ~ I
CLR---u-.....1 <b
s·-1 1-
u TYPE
~
1-----=---E
WING TYPE
v
PLAN Varies

#5 @ 12"
(both ways) 5 @ 12"

:
SECTION A-A IX)

#5 @ 12"
(both ways)

B
ELEVATION

.f..l:I<1~-See D-61 for rounded pipe end


Elev shown on plans

LEGEND ON PLANS
NOTE
See D-358 for Dimension Table and General Notes.
:~ ==ill
Revision By Approved Date RECOMMENDED BY THE SAN DIEGO
SAN DIEGO REGIONAL STANDARD DRAWING REGIONAL STANDARDS COMMITTEE
ORIGINAL Kercheval 12 75
Add Metric T. Stanton 03/03 7(26(2012

Reformatted T. Stanton 04/06 WING AND U TYPE HEADWALLS


02/09
Edited
s.s.
T. Stanton
FOR 42• TO 84. PIPE DRAW1NG
D-35A
Edited T. Regello 03/11 NUMBER
TABLE OF DIMENSIONS AND QUANTITIES
FOR HEADWALLS SHOWN ON D-35A

DIMENSIONS SINGLE PIPE DOUBLE PIPE


DIA
OF U lYPE WING lYPE U lYPE WING lYPE
PIPE L E F w CONC. STEEL CONC. STEEL
w CONC. STEEL CONC. STEEL
(CY) (LBS) (CY) (LBS) (CY) (LBS) (CY) (LBS)
42" 3'-7 1/4" 2' 3' 4' 1.57 117 1.90 135 10' 2.69 190 3.16 214

48" 4'-6" 2'-6" 3'-9" 4'-6" 1.97 153 2.48 184 11'-4" 3.43 252 4.06 288

54" 5'-4 7/8" 3' 4'-6" 5' 2.41 190 3.07 246 12'-8' 4.24 319 5.06 368

so· 6'-3 3/4" 3'-6" 5'-3" 5'-6" 2.88 239 3.75 294 14' 5.13 386 6.17 442

66" 7'-2 1/2" 4' 6' 6' 3.38 294 4.52 356 15'-4" 6.08 454 7.20 516

72" 8'-1 3/8" 4'-6" 6'-9" 6'-6" 3.93 368 5.52 417 16'-8" 7.11 522 8.30 588

78" 9' 5' 7'-6" 7' 4.50 444 6.70 503 18' 8.20 595 9.50 693

84" 9'-10 3/4" 5'-6" 8'-3" 7'-6" 5.21 540 8.15 619 19'-4" 9.50 687 10.80 786

Note: Dimensions E and L apply to wing type only.

NOTES
1. Skewed Pipes: Dimension W to be increased to take care of increased width or length due to skew of multiple pipes.
2. Top of headwall shall be placed approximately parallel to profile grade when the grade is 3% or more.
3. Concrete shall be 560-C-3250.
4. Exposed comers shall be 3/4" chamfered.
5. Multiple pipes shall be set a distance of D/2, with a 1' minimum, between outside diameters of pipes.
6. For pipe wall thickness greater than 3" use Alternate Detail C.

LEGEND ON PLANS

==© ::::(g

Revision By Approved Date RECOMMENDED BY THE SAN DIEGO


SAN DIEGO REGIONAL STANDARD DRAWING RE~ COMMITTEE
ORIGINAL Kercheval 12/75
Add Metric T. Stanton 03/03 I.....__ _}!:f;Ftr,u<7~ 7(26(2012
Reformatted T. Stanton 04/06 WING AND U TYPE HEADWALLS Chairperson R.C.E. 19246 Date
Edited T. Stanton 02/09
FOR 42• TO 84. PIPE DRAW1NG
D-358
Edited S.S. T. Regello 03/11 NUMBER
--j j-5"

r
CORNER STEEL
DETAIL

ELEVATION SECTION

w
3'-4" 4'-10" 6'-4" 7'-10" 9'-4"
D H L/2 STEEL CONC. STEEL CONC. STEEL CONC. STEEL CONC. STEEL CONC.
(LBS) (CY) (LBS) (CY) (LBS) (CY) (LBS) (CY) {LBS) {CY)
12" 2'-8" 2'-6" 50 0.79 60 0.98 - - - - - -

15" 2'-11" 3' 55 0.91 65 1.11 - - - - - -

18" 3'-2" 3'-6" 65 1.04 75 1.25 - - - - - -

21" 3'-5" 3'-9" 75 1.15 90 1.36 - - - - - -

24" 3'-8" 4'-3" 85 1.29 100 1.51 110 1.74 - - - -

27" 3'-11" 4'-9" 90 1.44 105 1.67 115 1.91 - - - -

30" 4'-2" 5' 95 1.55 110 1.80 120 2.05 135 2.29 - -

33" 4'-5" 5'-6" 105 1.71 120 1.97 135 2.23 150 2.48 - -

36" 4'-8" 6' 110 1.88 125 2.15 140 2.41 155 2.68 170 2.95
39" 4'-11" 6'-3" - - 150 2.28 170 2.56 185 2.84 200 3.12
42" 5'-2" 6'-9" - - 155 2.42 175 2.76 190 3.05 210 3.34

45" 5'-5" 7'-3" - - - - 180 2.97 200 3.27 215 3.57

48" 5'-8" 7'-6" - - - - 190 3.13 216 3.44 230 3.75

51" 5'-11" 8' - - - - - - 220 3.67 235 3.99

54" 6'-2" 8'-6" - - - - - - 235 3.91 250 4.24

NOTES
1. Concrete shall be 560-C-3250.
2. All reinforcing steel shall be #4 bars. All vertical and horizontal tie
bars shall have 18" maximum spacing. LEGEND ON PLANS
3. When multiple pipes are used, the distance between pipes shall be D/2
(1' min). The dimension L/2 is from the center of the pipe to the
_____ -f?
end of the headwall as shown. ------u
4. Exposed comers shall be 3/4" chamfered.

Revision By Approved Date SAN DIEGO REGIONAL STANDARD DRAWING ~~g~~~~~Ec~~NM 1We:~o
ORIGINAL Kercheval 2/75 ~
rA=dd=M=e~tri=c+-~T.=S=ta=nta~n=r0=~~03,________________________________________,l'~~7~ ~z6aO~

Reformatted T. Stanton 04/06 L TYPE HEADWALLS Chairperson R.C.E. 19246 Date


Edited T. Stanton 02/09 DRAW1NG
Edited S.S. T. Regello 03/11
!CIRCULAR PIPES! NUMBER D-36
w
9"---j
3/4S L/2 I. ---1" ~g·
3 111·~ j

lF
[ " t-11111
I U-Q-1---L---t
II I I I _j_
+-t--t- rHI .~!. •<0
___l
s I I I
T H~---~-~-
II I I I
. I. 1/
:..s
t. ·..· --~T
CORNER STEEL I co
t
DETAIL 7 1/2"~7 1/2" t 7 1/2"~71/2"
2' Elev sh own 2'
on pans
1

ELEVATION SECTION

LENGTH OF W
CSP 3'-4" 4'-10" 6'-4" 7'-10" 9'-4"
ARCH H Lj2 STEEL CONC. CONC. CONC. CONC. CONC.
SIZE STEEL STEEL STEEL STEEL
(LBS) (CY) (LBS) (CY) (LBS) (CY) (LBS) (CY) (LBS) (CY)

18"x11" 2'-7" 2'-9" 50 0.84 60 1.03 70 1.21 80 1.39 90 1.57

21 "x15" 2' -11" 3'-3" 60 1.00 65 1.18 75 1.38 90 1.58 100 1.77

24"x18" 3'-2" 3'-9" 60 1.07 70 1.32 80 1.53 95 1.74 110 1.94

28"x20" 3'-4" 4'-3" 70 1.26 80 1.47 90 1.68 100 1.90 115 2.11

35"x24" 3'-8" 5'-3" 100 1.51 110 1.74 120 1.97 140 2.20 155 2.42

42"x29" 4'-1" 6'-3" 115 1.82 130 2.06 140 2.31 155 2.55 170 2.83

49"x33" 4'-5" 7'-3" 130 2.12 145 2.37 155 2.64 170 2.90 185 3.15

57"x38" 4'-10" 8'-6" 145 2.52 160 2.79 175 3.07 190 3.35 205 3.61

64"x43" 5'-3" 9'-6" 185 2.89 200 3.11 215 3.48 235 3.77 250 4.06

71"x47" 5'-7" 10'-6" 200 3.25 215 3.56 235 3.86 250 4.17 270 4.48

NOTES
1. Concrete shall be 560-C-3250.
2. All reinforcing steel shall be #4 bars. All vertical and horizontal tie
bars shall have 18" maximum spacing. LEGEND ON PLANS
3. When multiple pipes are used, the distance between pipes shall be S/2
(1' min). The dimension L/2 is from the center of the pipe to the
end of the headwall as shown.
-----:[J
-----
4. Exposed corners shall be 3/4" chamfered.

Revision By Approved Date RECOMMENDED BY THE SAN DIEGO


SAN DIEGO REGIONAL STANDARD DRAWING RE~ COMMITTEE
ORIGINAL Kercheval 12/le
Add Metric T. Stanton 03/03 1--...... .J!t:fT< 7~ 7/26/2012
Reformatted T. Stanton 04/06 L TYPE HEADWALLS Chairperson R.C.E. 19246 Date
Edited s.s. T. Regello 03/11 DRAW1NG
!CORRUGATED STEEL PIPE - ARCH! NUMBER D-37
>-
10• min

FACE ELEVATION SIDE ELEVATION

PIPE DIAMffiR X y z
12" TO 24" 1• 2' 10"

21" TO 36" 1"-6" 2"-6" 12"

39" TO 48" 2' 3' 12"

51" TO 60" 2'-6" 3' 14"

63" & LARGER 3' 3' 14"

NOTES
1. A curtain wall shall be used in place of a headwall at culvert ends where
extension of the culvert is considered imminent or, no fill is retained.
2. Concrete shall be 560-C-3250. LEGEND ON PLANS
3. Keep the pipe-end clear of obstructions to permit easy placing of culvert
---------LJ,
extension. ---------o-'

Revision By Approved Date RECOMMENDED BY THE SAN DIEGO


SAN DIEGO REGIONAL STANDARD DRAWING REGIONAL STANDARDS COMMITTEE
ORIGINAL Kercheval 12 75
Add Metric T. Stanton 03/03 7(26(2012

Reformatted
Edited
T. Stanton 04/06
CURTAIN WALL
S.S. T. Regello 03/11 DRAW1NG
NUMBER D-38
•0)
+
A c A

L __ - 'l1
---- --=~=~~- ~~~~ J
•0)
+
y--560-C-3250
~~----= J
c
Lq Concrete or air placed concrete,l

~c PLAN ~B
6 - W1.4 X W1.4 WWR

>-
>-

SECTION A-A in 5• around


pipe inlet

1.5 D + g• Inlet construction


symbol about t
except for
multiple pipe
installations
(see Note 1)

i
'I x6 - W1.4 x W1.4 nR
SECTION B-B SECTION C-C

NOTES
1. When more than one pipe is used the profile view shown shall hold for the distance across
all pipe openings. Section A-A and B-B shall be from the outermost pipe. The distance
between pipes shall be D/2 for round and Span/3 for arch pipe (12• minimum).
2. Culvert shall be cut off even with apron surface when required by the Agency. LEGEND ON PLANS
J. Use Inlet Apron only where a flared and section can not be utilized. []):::::~
4. Place weep holes when required by the Agency.

RECOMMENDED BY lHE SAN DIEGO


SAN DIEGO REGIONAL STANDARD DRAWING REGIONAL STANDARDS COMMIT1EE
ORIGINAL
Add Metric T. Stanton 7(Z6(ZOIZ

Reformatted T. Stanton INLET APRON FOR CULVERTS


Edited S.S T. Regello DRAWING
UP TO 42• DIAMETER NUMBER D-39
r Symmetrical about

1'-o·-
I
1-

r-3-#5
1- Symmetrical about centerline
I
r
I
·- rr
I
centerline

___r3" CLR
---,
I
I
See Sec. D-D -3-#5 typ I I
~
I I ¥ I
t I ! t A
I
4-#4 2" (typ) !
Ill- fil I I
___ J I #4@ 7" ..... I

3-#4
- 2 f-- -
,_
--- 1---------_j
II
I (Note 1) I t -~

?'I.
Pipe Opening
2-#s
each face 1
I
t IV 3-#5 typ L_ ·-- ·-- 1--------.J

3- #5 J I

I
END SILL ELEVATION HEADWALL ELEVATION

#4 @ 7" (Note 2)
#41
<tr Symmetrical about
centerline
@ 8"
#4

4-#4
(Note 1)

#51@ 12"

#4 L@ 8" c.J See End Sill Elev.


Note 1
#5 u@ 8"
SECTION A-A SECTION C-C

#4-@7 (Note 1)

.. .··
:

2-#8 (full ht.)


NOTES
1. Place reinforcing, as noted, at center of wall (or slab). SECTION 0-D
2. Match location of reinforcing with that in headwall,
end sill and foundation slab.
3. All reinforcing shall be placed with 2"
concrete cover, unless noted otherwise.

Revision By Approved Date RECOMMENDED BY THE SAN DIEGO


SAN DIEGO REGIONAL STANDARD DRAWING REGIONAL STANDARDS COMMITTEE
ORIGINAL Kercheval 12 7
Add Metric T. Stanton 03/03 7(26(2012

Reformatted T. Stanton 04/06


CONCRETE ENERGY DISSIPATER
Edited T. Stanton 02/09 IREINFORCEMENT! DRAW1NG
Edited s.s. T. Regello 03/11 18• TO 30• DIAMETER PIPE NUMBER D-42
r-
q_

I
S)m~ ltout cenbrfne

2" (typ)~ ~

-----j r--s- Section A-A on D-438


r-- - I~ - r-- --
y

'h I
~---------------,
f5["" D 12' {outside face) I '\. II
#4 0 12' {inside face) r1
: •
v;~~ " \
I
i
I /
14 LO 10' (oubiide face)
14 0 lo' {inside face)
!
I
'\ r---
r'\.\
!2-#6 ea f~
I

~-+-
!
See Section D-D and I

Note 1 on IHJC I '\ll


L.-- - - - r-- ---- ~---------------~
I

HEADWALL ELEVATION
~
Symmetrical about Clrltlrlina ----j
rS..Stdm7
on D-43C
I
I

!
+-#4 ~~14. 10' ( . - fll:e llllfl
outside foce on~
I
18' / f501~
I
I ,,, ,. l~ I

I,
l:.f'
L
, ,. l
I

-- ......
I
I
I
.J
I' I
I I-- -- -r -
J

14 0 10' (outside face on~)


~

'
...,
y
L
END SILL ELEVATION

Revision By Approved Date RECOMMENDED BY lHE SAN DIEGO


REGIONAL SI_ANDARDS COMMIT1EE
SAN DIEGO REGIONAL STANDARD DRAWING
ORIGINAL Kercheval 2ns ~L;o..
Add Metric T. stanton 03/03 -.. . . ~lN 7/Z6/ZO/Z
Refom~attad T. Stanton 04/06
CONCRETE ENERGY DISSIPATER Olalrparaon R.C.E. 19248 Data
Edited T. stanton 02/09
(REINFORCEMENT) DRAWING
Edited s.s. T. Regello 03/11 36• TO 72• DIAMETER PIPE NUMBER D-43A
c~ I
#5 0 12" (each face)---,
#5 cant I match location of transverse
reinforcing in foundation slab
#5,0 12" -.JtA==?-=>r-----------t-1-~
4 0 10"
#4CO 10"
#4 0 12"
(Note 1 on D-43C) 1======1
2-#6--.:=~
horizontal reinforcing
in baffle wall, headwall
and end sill

See End Sill


CL bar
Elevation
{Note 3
on D-43A
on D-43C)

q_ Bottcm Oob ~
I
J DU bar
(Note 1 on D-43C)

SECTION A-A

#5 cant
r- Sjnlnelri:ol about """""'

#4 0 10"
(See Section D-D
on D-43C)

3" CLR

SECTION C-C
Revision By Approved Date RECOMMENDED BY THE SAN DIEGO
SAN DIEGO REGIONAL STANDARD DRAWING REGIONAL STANDARDS COMMITTEE
ORIGINAL Kercheval 12 7
Add Metric T. Stanton03/03 7(26(2012

Reformatted T. Stanton 04/06


CONCRETE ENERGY DISSIPATER
Edited T. Stanton 02/09 IREINFORCEMENT! DRAW1NG
Edited s.s. T. Regello 03/11 36• TO 12· DIAMETER PIPE NUMBER D-438
, - <i. between baffle wall and end sill
Add #4 0 20" vertical spacing
(
to reinforcing shown ea. face )-----i:::-- 7'
f5C.O 10"
4- G bars-- ~Lu;;.
(full ht.) ~ --- 18" f-- ~~
.. .............................................. ·t
ltil ...................... ·..-·-..-· ..,. . :n rF. ....... ....,........,... .......................................... ~.f!Ji
II$~ ~.~.~.~~~

-118"1-- min. lap

SECTION D-D

Pipe dia. (in.) 36" 42"I 48" I54" 60" I 72"


A bar #50 12" #6 0 12" #7 0 12"
B bar #50 12" #6 0 12"
C bar # 4 0 12" #50 12"
D bar # 4 0 12" #50 12" #6 0 12"
E bar # 4 0 12" #50 12"
F bar 1 4 o g• #50 g• 1 #6 o g•
G bar #7 I # 11

NOTES
1. Match location of sidewall reinforcing.
2. Dowels having same size and spacing as wall reinforcing may be used in lieu of continuous bars at contractors option.
3. Match location of headwall or end sill reinforcing.

Revision By Approved Date RECOMMENDED BY THE SAN DIEGO


SAN DIEGO REGIONAL STANDARD DRAWING RE~ COMMITTEE
ORIGINAL Kercheval 12/7f'
Add Metric T. Stanton 03/03 I.....__ _}!:f;Ftr,u<7~ 7(26(2012
Reformatted T. Stanton 04/06
CONCRETE ENERGY DISSIPATER
Chairperson R.C.E. 19246 Date
Edited T. Stanton 02/09
IREINFORCEMENT! DRAW1NG
Edited s.s. T. Regello 03/11 36• TO 12• DIAMETER PIPE NUMBER D-43C
PLAN
5-#4 t;l@
Headwall or endwall
12"
2-#4, str, @

2-#4 @ ±12" 12", backface

1/2" exp joint face


Wall slope to
match channel 4 @ 18", str, both faces

"Slope" of fill or channel


3-#8::....1-k-
Q
2'

3-#9

2-#4 ~~~~f::=~~~4l@ 18"


.:......-+--+--1--++---+ Front face, bend
2' -6" into wall or apron

2-#4 If alternative bottom is used


Alternative bottom of cutoff wall

lYPICAL FOR MAXIMUM H > 10' lYPICAL FOR MAXIMUM H < 10'
END ELEVATION
NOTE
See notes on D-440. If at upstream end, fillet is not shown

Revision By Approved Date RECOMMENDED BY THE SAN DIEGO


SAN DIEGO REGIONAL STANDARD DRAWING REGIONAL STANDARDS COMMITTEE
ORIGINAL Kercheval 12 75
7(26(2012
Add Metric T. Stanton 03/03
Reformatted T. Stanton 04/06 PIPE CULVERT - HEADWALLS,
Edited S.S T. Regello 03/11 DRAW1NG
ENDWALLS & WARPED WINGWALLS NUMBER D-44A
9" min

5-#4 0©12"
g"
Slope apron
FL to match channel FL

#9

Construction joint
Construction joint
18" max Detail E #4 @ 18" max
J,J
~1'
TYPICAL FOR MAXIMUM TYPICAL FOR MAXIMUM
H > 10' H ~ 10'
Cutoff wall 1' Cutoff wall

PART LONGITUDINAL SECTION

A 6"
n
Stiffening beam
"D" - see table on D-44D

b
~
WITHOUT STIFFENING BEAM
a~
For number & size of ~A
bars see table on D-440. :r: VI :r:
I X
Extend and hook into X C
c:::::!:
cutoff wall and headwall :::::!: ....
or endwall. 1-1/2 dia CLR .... 0
c..,_
1" min .......~

#4 Spacers @ 12"
#4 @ 18"
#4 x 5' Dowels @ 12" OC
#4
=~~~~=!;;~~
#4@ 18"
1'-4" for Max H::::;1 0'
2 for Max H>10
SECTION C-C

NOTES
1. RCP is shown. When using metal pipe eliminate the expansion joint and use hook bolts @ 19"±
spacing (size and length provided by manufacturer).
2. Where abrasion is anticipated, increase apron thickness to 7" minimum to provide 2" minimum
reinforcement coverage.
Revision By Approved Date RECOMMENDED BY THE SAN DIEGO
SAN DIEGO REGIONAL STANDARD DRAWING REGIONAL STANDARDS COMMITTEE
ORIGINAL Kercheval 12 75
7(26(2012
Add Metric T. Stanton 03/03
Reformatted T. Stanton 04/06 PIPE CULVERT - HEADWALLS,
Edited s.s T. Regello 03/11 DRAW1NG
ENDWALLS & WARPED WINGWALLS NUMBER D-448
Pipe wall
to 3-#8
Slope varies, 1:1 ~~1'
@ headwall
to flat @ l/2 Construction joint
#4 Dowels L @ 12" OC Warped
Length varies to match wingwall
Warped fillet transition, 2" CLR spacers 2'± into
wingwall headwall or endwall. Rotate if necessary .
. - - - - - 4 X 4-W1.4 X W1.4 WWR
(for max "H" > 1a') (Near spring line, eliminate face
extension and hook rear extension
outward, if possible.)

SECTION B-B

Angle
of flare
1
---------- -

ALTERNATIVE WARPED WINGWALL


Use where additional protection to toe of embankment
is required. If at upstream end, fillet is not shown.

1/2" exp joint filler,


where H max > 1a·
a. 1'
w~v-
X
v

1/2" exp joint filler L..V #4 @ 18"

r;;::;&';~:::::;il-1-h g"
1'-3"

Construction joint Dim is 1' where H ~ 1a·


Dim is 2' where H > 1a·
DETAIL E

SECTION A-A
Revision By Approved Date RECOMMENDED BY THE SAN DIEGO
SAN DIEGO REGIONAL STANDARD DRAWING REGIONAL STANDARDS COMMITTEE
ORIGINAL Kercheval 12 75
Add Metric T. Stanton 03/03 7(26(2012

Reformatted T. Stanton 04/06 PIPE CULVERT - HEADWALLS,


Edited S.S. T. Regello 03/11 DRAW1NG
ENDWALLS & WARPED WINGWALLS NUMBER D-44C
en
m :1>
z WARPED WINGWALLS (all measurements in feet and/ or inches unless otherwise noted)
z WALL DIMENSIONS AND REINFORCING STIFFENING BEAM DIMENSIONS AND REINFORCING
CI""C'C 2 Element 10'
:e=e m Slope H 8'or less 12' 14' 16' 18' 20' 12· 114· 116' l1a· 1 2o· 1 25· 1 30' 135' 14o· or more
:J>m C) I~
r- 0 Front face reinf #4012 #4@ 7 #50 7 #5@ 5 #6@ 6 #7@ 7 #7@ 6 6' No beam. Place 2-#6 in each I
1/4:1
r-(") Rear face reinf #4012 #4@12 #4@12 #4012 #4012 #4@12 #4@12 8' face along top of I
;:ltl A= 1'
cnc Front face reinf #4012 #4@12 #4@12 #4012 #4010 #4@ 8 #4@ 6 10' wall.
I
m 3/4:1 B= 9"
C) Rear face reinf #4012 #4@12 #4012 #4010 #4@ 7 #4@ 6 #50 8 12'
QO!;: Front face reinf #4@12 #4012 #4012 #4@12 #4@12 #4@12 #4012
m 1-1/4:1 14'
0z Rear face reinf #4@ 8 #40 8 #40 5 #50 6 #6@ 7 #6@ 6 #7@ 6 '""'' 6-/6 8= J~_,...
16'
:1> D at Cutoff Wall 6" 6" 6" 7-1/2" 8" 9-1/2" 11" Total 6-#7 ,~;.2
~~ r- 18'
:lei I D at Culvert 6" 6" 6" 8" 9-1/2" 11" 1'-1" 20'
C/) 9
""C'C
m :::z::: -1
em :1>
z NOTES
:e~ c
:1> 1. Walls designed for 2' surcharge; earth density = 120 # / cu. ft.; equivalent fluid pressure = 36 #/cu. ft.
:z:e ;:ltl
2. Vary "D" at warped wall uniformly from that at cutoff wall to that at culvert, for maximum H > 12'.
G):J> c
:er- 3. Dimensions "L", ''W", "H", "M", "N", "Eiev a", "Angle of flare", and end "slope" (as apply) are shown on the plans.
,_r- c 4. All exposed concrete edges to be chamfered 3/4".
;:ltl
r- ..cn :1>
r- ~
cn z
C)
Face of drainage structure Face of drainage structure Face of drainage structure

Concrete pipe Concrete pipe

BELl. END SPIGOT END CUT END

R = Thickness of pipe

Face of drainage structure

CUT END

R = Inside diameter of pipe


10

NOTE
The rounded areas may be built up of cement mortar or poured in place with the drainage structure.

RECOMMENDED BY lHE SAN DIEGO


SAN DIEGO REGIONAL STANDARD DRAWING REGIONAL STANDARDS COMMIT1EE

7(Z6(ZOIZ

Reviewed T. Stanton 04/06 ROUNDED PIPE ENDS


Edited OJ/11 DRAWING
IN DRAINAGE STRUCTURES NUMBER D-61
t ~A
ELEVATION

6" min overlap on each pipe

!iii
E

Cut pipe end

SECTION A-A
NOTES
1. Pipe collar does not have to be finished if covered.
2. Concrete shall be 560-C-3250.
3. Where gap exceeds 3• but is not more than s• LEGEND ON PLANS
on intemal form shall be used. ----n---
---u---
RECOMMENDED BY lHE SAN DIEGO
SAN DIEGO REGIONAL STANDARD DRAWING REGIONAL STANDARDS COMMIT1EE

Add Metric T. stanton OJ/03 7(Z6(ZOIZ

Reviewed
Edited
T. Stanton
S.S. T. Regello
0+/06
OJ/11
PIPE COLLAR
DRAWING
NUMBER D-62
-~ ~-
', See D-70 & D-71 //
',, for lined channel ///
'' /
'' /
/

'' /
/

'' /
/

' /
/
', '-~~~~~~--~~~~~~--' //
'------ - ------ ____________
__/

LA
ELEVATION

------------1
I
I
I
I
Flow line of channel 1
I
I
I

~ '.

SECTION A- A

LEGEND ON PLANS
NOTES
1. Thickness and wall depth shall be as shown on pion.
2. Reinforcing in cutoff wall shall be the some os that required in channel.
3. Concrete shall be 560-C-3250.
1:::::::::::::::::::11

Revision By Ap roved Dote RECOMMENDED BY TI1E SAN DIEGO


SAN DIEGO REGIONAL STANDARD DRAWING REGIONAL STANDARDS COMMITTEE
ORIGINAL Kercheval 2 75
Add Metric T. Stanton 03/03 7/Z6/ZOIZ
Reviewed
T. Stanton
4
0 /06 CUTOFF WALL FOR DRAINAGE CHANNEL 1----=------------1
Edited S.S. T. Regello 03/11 DRAVt1NG
NUMBER D-72
FOR DRAWINGS D-70 AND D-71, SEE DRAWINGS SDD-107 AND SDD-108
r---------7]
1l-_i ------( I c:

11-j----£<1 I
0

II N E I I ~
Q)
c:
---------- c:
0

-ct ------- 11--- - 1-+--


0

---------- 11-- I I ~
II c-.. 5 I I 6
IJ- '=-._ ____ ~ I . §
L ~roo E
------- ~

PLAN

Ground line 1:1

ELEVATION

NOTES:
1. Concrete shall be 560-C-3250.
2. Pipe shall connect to channel as high as possible and
not be constructed directly above a weep hole. LEGEND ON PLANS
3. The maximum angle of connection is 60" downstream.

~I
In no case shall a pipe angle upstream.
4. Install 6 x 6-W1.4 x W1.4 WWR in concrete around pipe.

Revision By Approved Date RECOMMENDED BY THE SAN DIEGO


SAN DIEGO REGIONAL STANDARD DRAWING REGIONAL STANDARDS COMMITTEE
ORIGINAL Kercheval 2 75
Add Metric T. Stanton 03/03 7(26(2012

Reviewed T. Stanton 04/06


PIPE TO CHANNEL CONNECTION
Edited S.S. T. Regello 03/11 DRAW1NG
NUMBER D-73
..,a. .., ;;c
a. <D ~ 0 ::::0
;= ;=,: a. :;o CD
<D i·
a. a. :E s::: G) :S.
<D en
a. z o·
9:
()
)> ~
r
(J)
tD
!n '<
;-I ;-I ;-I ;-I ~ )>
;;c
-o
CD -o
<D ""
<C ::J
~ ::J~ ::J~ n
~ ::::r 0
(j (j (j CiS
0 ::J ::J ::J ~ c..
c
0 0
"' c
~ ~ ~ ~ -5 ..- CD
tTl
"' "' "' SPANS UP TO 5' (all measurements in feet and/or inches)
en
:1> SPAN 2' 3' 4' 5'
z
2 HEIGHT 1'-6 2' 2' 3' 2' 3' 4' 2' 3' 4' 5'
m
G) STRENGTH CLASSIFICATION A A A A B A A B A B c A B A B A B c D A B c D
CJ) 0 MAX FILL OVER TOP 66 38 38 66 28 28 37 2837 50 12 27 12 27 11 2635 46 11 25 35 46
z ::u c...)
Top Slob T, 6 6 6 1/4 6 1/4 8 7 7 8 7 8 9 7 1/2 8 7 1/2 8 7 1/28 9 1/2 10 1/2 7 1/2 8 9 1/2 10 1/2
C) m :z: Bottom Slab T2 6 6 6 1/4 6 1/4 8 7 7 8 7 8 9 6 8 6 8 6 8 10 10 3/4 6 8 10 10 3/4
G) 0
c r- u
m m Sidewalls l3 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6
II
.....
)>al
0z
a:;
, , Size Bar 4 4 4 4 5 5 5 5 5 5 6 5 5 5 5 5 5 6 6 5 5 6 6
:1> CL>
a Spacing 3 1/2 3 1/2 3 1/2 3 1/2 4 5 5 4 1/2 5 4 1/2 5 4 4 4 4 4 4 5 4 1/2 4 4 5 4 1/2
r- L___j
-o VJ
~>< - C"
Length 3-2 3-2 4-2 4-2 4-3 5-3 5-3 5-3 5-3 5-3 5-2 6-3 6-3 6-3 6-3 6-3 6-3 6-2 6-2 6-3 6-3 6-2 6-2
en <::
Top Slab-No. of 2 2 3 3 2 3 5 3 3 3 3 7 3 7 3 7 3 3 7 3 3
-1 ·~ "d" Dist.
z 0 :1> .E Bars Bottom Slab-No. of 2 2 2 2 2 3 3 3 3 3 3 3 3 3 3 3
!=> c:
r- z .,
.<:: "e" Bars Spacing 18 18 18 18 12 1/4 18 18 18 17 13 9 1/2 18 18 18 18 18 17 13 11 18 12 8 1/2 6 1/2
c 0:::
- < :1> Spacers Number 12 12 12 12 12 12 14 14 14 14 16
m ::u :Z
::a c <( Concrete: C.Y. per lin. ft. 17 18 23 27 31 29 33 36 36 40 43 32 37 36 41 40 44 51 54 43 48 55 57
..... :::::>
c 0 Reinf. lbs per lin. ft. 27 29 34 36 46 44 45 47 48 52 64 57 56 59 57 61 60 68 75 63 65 77 87
::u
:1>
~ NOTE
z
G) For boxes of height less than that shown in table, use next greater table height slabs, wall dimensions and reinforcing steel, and
make necessary changes in bar lengths, number of spacers and quantities.
'!)/ ;;c;;c
:z:: 0 0
c: ::::0 ~§
OS::
s::::::> .a
t:c:§ zs:::
~ >rrl
rrl:z:: g rz
:::CG"> 1110
::0
~8
r> z
~~ Cal
f'l ::::--1 >-<
cI ~:I!
Ill..,
......
CJ)
~ [ ()Ill
,.. 0 ~ ~~
s:::
g. ~
CD
"N ~~
..,8
\0
i\;
;;c
~ ~ E:: 0 ::::0
a. :;o CD
~ ~ "'~·
a. a. ::e ;;::: C) :S. C/)
~ z o·
)> ~
n r
"'a. "'·
Ill tD
0 '<
;-1 ;-1 ;-1 ;-1 ~ >
:;>;; -o
;;c Ill Ill Ill CD -o
El El n 0El
"'!!."'0 "'0 "'0 "'0 :::;,-
~ CiS
"' "' "' c c..
0 0 0 0 0
c
..-
~ ~ t ~ <>I
~
(JI CD
"'
SPANS 6' (all measurements in feet and/or inches)
en
:1>
z SPAN 6'
2 HEIGHT 2' 3' 4' 5' 6' 7'
m
C)
0 STRENGTH CLASSIFICATION A B A B A B c A B c D A B c D E A B c D E
en MAX FILL OVER TOP 10 18 10 18 10 18 25 9 18 25 36 9 17 25 36 45 9 17 25 36 45
z ;:ltl
C) m <...) Top Slab T, 8 1/4 8 1/4 8 1/4 8 1/4 8 1/4 8 1/4 9 1/4 8 1/4 8 1/4 9 1/4 11 8 1/4 8 1/4 9 1/4 11 12 8 1/4 8 1/4 9 1/4 11 12
C) :z: Bottom Slab 6 3/4 8 6 3/4 8 6 3/4 8 9 3/4 7 1/4 8 1/4 10 11 1/4 7 1/4 8 1/4 10 1/2 11 1/4 12 1/4 7 1/4 8 1/4 10 1/2 111/4 12 1/4
c r- 0 T2
m m u
Sidewalls T3 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 1/4 7 6 6 6 1/4 7 7 3/4
II
.....
,..al
0z
,. ,. Size Bar 5 5 5 5 5 5 6 5 5 6 6 5 5 6 7 7 5 5 6 7 7
:1> a:; a
-o r- CL> Spacing 4 4 4 4 4 4 5 4 4 5 4 1/2 4 4 5 5 1/2 5 4 4 5 5 1/2 5
~>< en L___j
en - 0>
Length 7-3 7-3 7-3 7-3 7-3 7-3 7-2 7-3 7-3 7-2 7-2 7-3 7-3 7-2 7-3 7-5 7-3 7-3 7-2 7-5 7-6
-1 <::
z 0 :1> ·~ "d" Dist.
Top Slab-No. of 7 4 7 4 7 4 7 4 4 7 4 4 4 7 4 4 4
!=> c: z Bars Bottom Slab-No. of 4 4 4 4 4 4 4 4 4 4 4
r- c .,
..E<:: "e" Bars Spacing 18 18 18 18 18 18 17 18 15 1/211 1/2 8 1/2 17 10 1/2 7 1/2 6 5 12 7 1/2 7 5 4 1/2
-< :1> 0:::
m ;:ltl Spacers Number 12 12 14 16 16 18
:a c z<( Concrete: C.Y. per lin. ft. 40 42 43 46 47 50 58 52 54 60 66 56 58 65 71 78 59 61 70 78 88
..... c ::::>
Reinf. lbs per lin. ft.
;:ltl 0 64 63 66 65 69 67 74 70 70 80 91 73 78 92 112 127 81 90 99 126 139
:1>
~ NOTE
z
C) For boxes of height less than that shown in table, use next greater table height slabs, wall dimensions and reinforcing steel, and
make necessary changes in bar lengths, number of spacers and quantities.
'!)/ ;;c;;c
0 ITIITI
:z:: 0 CH">
c: ::::0 .a 0~
s::::::> z;;:::
t:c:§ ~ >,.,
rrl:z:: g rz
:::CG"> VIC
::0
~9
r> z
~~ Ctll
f'l ::::--1 >-<
c I ~:I!
Ill,.,
...... ~ [ 0111
en 0>
al CJ
~ ~z
g. ~
"' "N ~~
\0 1'18
i\;
,..,a. ,..,a. ;;u
CD 5: 0 ::::0
~- a. :;o CD
<D ~ CD
""a. a. :oE 3:: G) :S.
Cl)
CD ~
a. :::l.
z (5"
0 )> ~
r
Ul
tD
Y> '<
;-1 ;-1 ;-1 ;-1 ~ )>
;;u -o
CD -o
CD ""
~ ~ :::3~ n SPAN
"'!!. :::3c; c;:::3 c; ::::r 0 7' (all measurements in feet and/or inches unless otherwise noted)
0 :::3 :::3 :::3
~ CiS c..
c
0 0 0 0 0 SPAN 7'
CD
~ ~ 'S ~
VI
-5 ..-c
tTl
"' "' HEIGHT 3' 4' 5' 6' 7'
en STRENGTH CLASSIFICATION A B A B A B c A B c A B c
:1> MAX FILL OVER TOP 16 26 16 26 16 26 35 16 26 35 16 26 35
z T1 7 1/4 8 1/4 7 1/4 8 1/4 7 1/4 8 1/4 9 3/4 7 1/4 8 1/4 9 3/4 7 1/4 8 1/4 9 3/4
c..) Top Slab
:z Bottom Slab T2 7 1/2 8 3/4 7 1/2 8 3/4 7 1/2 8 3/4 10 1/2 7 1/2 8 3/4 10 1/2 7 1/2 8 3/4 10 1/2
2 0
m (..)
G) Sidewalls T3 6 7 6 7 6 7 8 1/2 6 7 8 1/2 6 7 8 1/2
CJ) 0 Size Bar " 5 5 5 5 5 5 6 5 5 6 5 5 6
"a"
::u Spacing 9 7 9 7 9 7 9 9 7 9 9 7 9
z m --
C) Length 6-8 6-9 6-8 6-9 6-8 6-9 6-10 6-8 6-9 6-10 6-8 6-9 6-10
c r- G)
"b" Size Bar " 5 5 5 5 5 5 6 5 5 6 5 5 6
m m
..... 0z Spacing 9 7 9 7 9 7 9 9 7 9 9 7 9
:!:: all :1> Dimension ''X'' 1-3 1-4 1-3 1-4 1-3 1-4 1-8 1-3 1-4 1-8 1-3 1-4 1-8
r- 0 r- I Length 3-1 3-2 3-1 3-2 3-1 3-2 3-10 3-1 3-2 3-10 3-1 3-2 3-10
CJ) >< en a;
-1 "c" Size Bar " 5 5 5 5 5 5 6 5 5 6 5 5 6
~
z 0 :1> Spacing 9 7 9 7 9 7 9 9 7 9 9 7 9
!=> c: z c:
""
r- -~
Dimension ''y" 1-10 1-11 1-10 1-11 1-10 1-11 2-3 1-10 1-11 2-3 1-10 1-11 2-3
c 0
- < :1> c:
Length 5-2 5-4 6-2 6-4 7-2 7-4 7-10 8-2 8-4 8-10 9-2 9-4 9-10
m ::u "Q;
- I Size Bar " 5 5 5 5 5 5 6 5 5 6 5 5 6
::a c 0::: "c;'
..... Spacing 9 7 9 7 9 7 9 9 7 9 9 7 9
c Dimension ''y" 1-10 1-11 1-10 1-11 1-10 1-11 2-3 1-10 1-11 2-3 1-10 1-11 2-3
::u L
:1> Length 3-8 3-10 3-8 3-10 3-8 3-10 4-6 3-8 3-10 4-6 3-8 3-10 4-6
~ "d" Top Slab-No. of 7 4 7 4 7 4 4 7 4 4 7 4 4
z
G) Bars Bottom Slab-No. of 4 4 4 4 4 4 4 4 4 4 4 4 4
"e" Bars Spacing 18 18 18 18 18 18 18 18 18 18 18 18 18
'!)/ ;;u;;u
Spacers Total Number 24 28 28 32 36
:z:o 0 :Z Concrete: C.Y. per lin. ft. 47 56 51 60 55 64 78 58 68 84 62 73 89
~§ <(
c: ::::0 0~ :::::>
s::::::> .a ~ z~ 0 Reinf lbs per lin. ft. 107 130 114 138 118 143 168 125 150 176 132 158 184
t:c:§ . >rrl
rrl:z: 0 rz
:::3
:::CG"> 1110 NOTE
::0
~8 For boxes of height less than that shown in table, use next greater table height slabs,
r> z
~~ Cal
['1 ::::--1 >-< wall dimensions and reinforcing steel, and make necessary changes in bar lengths,
c I ~:I! number of spacers and quantities.
[ lllrrl
..... ~
g) ()Ill

0 0 ~ ~~
~
0 ~
...... "N
\0
~~
,..,8
i\;
,..., ,..., ;:c
c.. c.. <D ~ 0 :::0
;::;: < c.. :;o C1)
~ <D ;;;·
c.. c.. :E s::: G) :S.
Cl)
<D
c.. 9: z
)>

n ~
r
Ul CD
0 '<
;-i ;-i ;-i ;-i ~ >
:;>;; -.::;1
;:c CD -.::;1
<D
::>
C'l
~ ::>~ ::>~ :::;,- a
"'!!!.0 S" S" S" CiS
SPAN 8' (all measurements in feet and/or inches unless otherwise noted)
::> ::> ::> c~ c..
0 0 8'
SPAN
~ a~ ~ a~ ~ c C1)
tO Vol tTl -
"' HEIGHT 3' 4' 5' 6' 7' 8'
en STRENGTH CLASSIFICATION A B A B A B A B c A B c A B c
:1> MAX FILL OVER TOP 13 21 13 21 13 21 13 21 31 13 21 31 13 21 31
z T, 7 1/4 8 1/2 7 1/4 8 1/2 7 1/4 8 1/2 7 1/4 8 1/2 10 1/4 7 1/4 8 1/2 10 1/4 7 1/4 8 1/2 10 1/4
<..) Top Slab
2 :z Bottom Slab
0 T2 7 1/4 9 1/2 7 1/4 9 1/2 7 1/4 9 1/2 7 1/4 9 1/2 11 1/2 7 1/4 9 1/2 11 1/2 7 1/4 9 1/2 11 1/2
m u
C) Sidewalls T3 6 1/2 7 1/2 6 1/2 7 1/2 6 1/2 7 1/2 6 1/2 7 1/2 9 3/4 6 1/2 7 1/2 9 3/4 6 1/2 7 1/2 9 3/4
en 0 Size Bar " 5 5 5 5 5 5 5 5 6 5 5 6 5 5 6
"a"
z ;:ltl Spacing 9 7 9 7 9 7 9 7 8 9 7 8 9 7 8
C) m --
C) Length 7-7 7-8 7-7 7-8 7-7 7-8 7-7 7-8 7-10 7-7 7-8 7-10 7-7 7-8 7-10
c r- Size Bar " 5 5 5 5 5 5 5 5 6 5 5 6 5 5 6
m m "b"
..... Spacing 9 7 9 7 9 7 9 7 8 9 7 8 9 7 8
0z
)loal :1> Dimension "X" 1-6 1-7 1-6 1-7 1-6 1-7 1-6 1-7 1-8 1-6 1-7 1-8 1-6 1-7 1-8
-o r- I Length 3-4 3-5 3-4 3-5 3-4 3-5 3-4 3-5 3-10 3-4 3-5 3-10 3-4 3-5 3-10
~>< en Q)
-1 Size Bar " 5 5 5 5 5 5 5 5 6 5 5 6 5 5 6
0 U'i
:1>
"' "c'' Spacing 9 7 9 7 9 7 9 7 8 9 7 8 9 7 8
o>
z c:
~ r- z c::::
Dimension 'Y" 2 2-5 2 2-5 2 2-5 2 2-5 2-8 2 2-5 2-8 2 2-5 2-8
c ·~
< :1> c Length 3-4 3-10 6-4 6-10 7-4 7-10 8-4 8-10 9-3 9-4 9-10 10-3 10-4 10-10 11-3
c::::
- m
:a c
;:ltl
"Qi
- I
0:::: ",.
c,
Size Bar " 5 5 5 5 5 5 5 5 6 5 5 6 5 5 6
..... c Spacing 9 7 9 7 9 7 9 7 8 9 7 8 9 7 8
;:ltl Dimension 'Y" 2 2-5 2 2-5 2 2-5 2 2-5 2-8 2 2-3 2-8 2 2-5 2-8
:1> L Length 3-9 4-5 3-9 4-5 3-9 4-5 3-9 4-5 5 3-9 4-5 5 3-9 4-5 5
~ "d" Top Slab-No. of 7 5 7 5 7 5 7 5 5 7 5 5 7 5 5
z
C) Bars Bottom Slab-No. of 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5
"e" Bars Spacing 18 18 18 18 18 18 18 18 18 18 18 18 18 18 18
'!)/ ;:c;:c Spacers Total Number 28 32 32 36 40 40
:z:o c ~§ ;;;i Concrete: C.Y. per lin. ft. 52 65 56 70 60 74 65 79 100 69 83 106 73 88 112
c: :::0 <C
OS:: :::::>
s::::::> .a
!!l zs::: 0 Reinf lbs per lin. ft. 118 146 125 154 129 139 136 167 211 143 174 220 147 179 225
c:o:§ rn >rrl
rrl:z: 0 rz
::>
:::OG"> VIC NOTE
::0
~
~ ~8
z For boxes of height less than that shown in table, use next greater table height slabs,
['1 Cal
>-< wall dimensions and reinforcing steel, and make necessary changes in bar lengths,
c I
<0 ~:I! number of spacers and quantities.
lllrrl
...... ~
[ C) VI
CJ) 0>
c 0
~ ~z
c
..... ~
<D
1\;-
\;:, ffi~ 0
i\)
rro rro ;;c
a. a. i'i:
a. 0 ::::0
:;o CD
~
a.
"'c;;·< G) :S.
:E 31:: C/)
"""'a.
m
z (5"
"'a. :r. )> ~
0
r
Ul tD
!n '<
;-I ;-I ;-I ;-I ~ >
;;c CD -o
!a
c
!a
c ~ ""C'l -o
"'
"'!!. :::J :::J
:::J :::;,- 0 SPAN 10' (all measurements in feet and/or inches unless otherwise noted)
() () () CiS
0 :::J :::J :::J ~ c..
c
0 0 0 0
c
..- SPAN 10'
~ a"" ~ t ~ CD
VI tTl
"' "' HEIGHT 4' 5' 6' 7' 8' g' 1o·
en STRENGTH CLASSIFICATION A B A B A B A B A B c A B c A B c
:1> MAX FILL OVER TOP 9 18 9 18 9 18 9 18 8 18 28 8 18 28 8 18 28
z
<...) Top Slab T1 8 9 1/2 8 1/4 9 3/4 8 1/4 9 3/4 8 1/2 9 3/4 8 1/2 9 3/4 12 1/4 8 1/2 9 3/4 12 1/4 8 1/2 9 3/4 12 1/4
2 :z Bottom Slab
0 T2 8 3/4 10 1/2 9 10 3/4 9 10 3/4 9 1/4 11 9 1/4 11 13 1/4 9 1/4 11 13 1/4 9 1/4 11 13 1/4
m u
C) Sidewalls T3 7 1/4 9 1/2 7 1/4 9 1/2 7 1/4 9 1/2 7 1/4 9 1/2 7 1/4 9 1/2 11 1/2 8 9 1/2 11 1/2 9 9 1/2 11 1/2
en 0 II II Size Bar " 6 6 6 6 6 6 6 6 6 6 7 6 6 7 6 6 7
;:ltl
a Spacing
z 11 8 11 8 11 8 11 8 11 8 9 11 8 9 11 8 9
C) m --
C) Length 9-5 9-8 9-5 9-8 9-5 9-8 9-5 9-8 9-5 9-8 9-9 9-6 9-8 9-9 9-5 9-8 9-9
c r- Size Bar " 5 6 5 6 5 6 5 6 5 6 6 5 6 6 5 6 6
m m "b"
.....
)lloal
0z
Spacing 11 8 11 8 11 8 11 8 11 8 9 11 8 9 11 8 9
:1> Dimension "X" 2 2 2 2 2 2 2 2 2 2 2-6 2 2 2-6 2 2 2-6
-o r-
~>< en a:;
I Length 3-10 4-2 3-10 4-2 3-10 4-2 3-10 4-2 3-10 4-2 4-8 3-10 4-2 4-8 3-10 4-2 4-8
-1 .. Size Bar " 5 6 5 6 5 6 5 6 5 6 6 5 6 6 5 6 6
z 0 :1> 05 c Spacing 11 8 11 8 11 8 11 8 11 8 9 11 8 9 11 8 9
!=> c: z C>
r- c
c ·~
Dimension Y 2-8 3-4 2-8 3-4 2-8 3-4 2-8 3-4 2-8 3-4 3-6 2-8 3-4 3-6 2-8 3-4 3-6
< :1> 0 Length
- m ;:ltl
6-11 7-10 8-1 8-10 9-1 9-10 10-1 10-10 11-1 11-10 12-3 12-1 12-10 13-3 13-1 13-10 14-3
:a c .c Size Bar " 5 6 5 6 5 6 5 6 5 6 6 5 6 6 5 6 6
0:::
.....
-., I"c:
c Spacing 11 8 11 8 11 8 11 8 11 8 9 11 8 9 11 8 9
;:ltl Dimension "y" 2-8 3-4 2-8 3-4 2-8 3-4 2-8 3-4 2-8 3-4 3-6 2-8 3-4 3-6 2-8 3-4 3-6
:1> L Length 4-7 5-8 4-7 5-8 4-7 5-8 4-7 5-8 4-7 5-8 6 4-7 5-8 6 4-7 5-8 6-2
~ ''d'' Top Slab-No. of 9 5 9 5 9 5 9 5 9 5 5 9 5 5 9 5 5
z
C) Bars Bottom Slab-No. of 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5
"e" Bars Spacing 18 18 18 18 18 18 18 18 18 18 18 18 18 18 18 18 18
'!)/ ::0::0 Spacers Total Number 32 34 36 40 40 44 48
:z:o c ~§ Concrete: C.Y. per lin. ft. 75 94 82 108 86 108 92 115 97 121 150 106 126 157 118 132 165
c: ::::0 .a 0~ ~
s::::::> !!l z~ ::>
t:c:§ rn >rrl Cl Reinf lbs per lin. ft. 143 221 148 228 154 235 160 244 164 250 265 170 259 273 178 267 281
rrl:z: 0 rz
:::J
:::CG"> 1110
::0 NOTE
~8
~ z
~~ Cal For boxes of height less than that shown in table, use next greater table height slabs,
['1 ;:::--.1 >-< wall dimensions and reinforcing steel, and make necessary changes in bar lengths,
c I ~:I!
lllrrl
...... ~ [ number of spacers and quantities.
0111
m ~ ~~
m 0 ~
c
.... ~
m ~~
"N
\0 m8
i\;
..... ;;o >
a. .....
a. a. 0 ::::0
;::;: a. :;o CD
~
a.
"'~·
"'a. :e s::: G) :S.
C/)
~ z (5'
"'a. ::l, )>
0 ~
r
!I)
tD
0 '<
:-< :-< :-< ~ > :-<
"0
;;o CD "0
~ ""
C'l 0
"'"'!!!. ;a~ ;a~ ;a :::;,.-
0 0 0 CiS
0 :::J :::J :::J ~ c.. SPAN 12' (all measurements in feet and/or inches unless otherwise noted)
c
0 0 0 0 0
c
~
"' ~ ~ ~ ~ ..-
~
SPAN 12'
0'1 tTl CD
"' "' 8' 9'
HEIGHT 6' 7' 10' 12'
en STRENGTH CLASSIFICATION A B A B A B A B c A B c A B c
:1>
z MAX FILL OVER TOP 5 16 5 16 5 16 5 16 24 5 16 24 5 16 24
2 u Top Slab T, 8 3/4 11 1/4 8 3/4 11 1/4 8 3/4 111/4 9 11 1/4 13 1/4 9 11 1/4 13 1/4 9 11 1/4 13 1/4
m :z: Bottom Slab
0 T2 8 3/4 12 1/4 8 3/4 12 1/4 8 3/4 12 1/4 9 12 1/4 14 3/4 9 12 1/4 14 3/4 9 12 1/4 14 3/4
C) u
0 Sidewalls T3 7 1/2 10 1/2 7 1/2 10 1/2 7 1/2 10 1/2 8 10 1/2 12 1/2 9 10 1/2 12 1/2 9 10 1/2 12 1/2
en .
Size Bar 6 7 6 7 6 7 6 7 7 6 7 7 6 7 7
z ;:ltl "a"
C) m Spacing 11 10 11 10 11 10 11 10 8 11 10 8 11 10 8
C) - - Length
c r- 11-3 11-6 11-3 11-6 11-3 11-6 11-4 11-6 11-8 11-5 11-6 11-8 11-5 11-6 11-8
m m
..... 0z "b"
.
Size Bar 6 7 6 7 6 7 6 7 7 6 7 7 6 7 7
)loal :1> Spacing 11 10 11 10 11 10 11 10 8 11 10 8 11 10 8
-o r- Dimension "X" 2-8 3 2-8 3 2-8 3 2-8 3 3 2-8 3 3 2-8 3 3
~>< en I Length 4-10 5-7 4-10 5-7 4-10 5-7 4-10 5-7 5-7 4-10 5-7 5-7 4-10 5-7 5-7
-1 (i)
Q)
z 0 :1> ......
(/) ''c" Size
.
Bar 6 7 6 7 6 7 6 7 7 6 7 7 6 7 7
!=> c:
r- z C'l
Spacing 11 10 11 10 11 10 11 10 8 11 10 8 11 10 8
c c:
< :1> -~
Dimension ''y" 3-9 3-9 3-9 3-9 3-9 3-9 3-9 3-9 3-9 3-9 3-9 3-9 3-9 3-9 3-9
0
- m
:a
;:ltl
c c:
'(i)
Lenqth 10-2 10-4 11-2 11-4 12-2 12-4 13-2 13-4 13-6 14-2 14-4 14-6 16-2 16-4 16-6
II n
..... c
- I
0:::: c,
Size Bar " 6 7 6 7 6 7 6 7 7 6 7 7 6 7 7
;:ltl
Spacinq 11 10 11 10 11 10 11 10 8 11 10 8 11 10 8
:1> Dimension ''y" 3-9 3-9 3-9 3-9 3-9 3-9 3-9 3-9 3-9 3-9 3-9 3-9 3-9 3-9 3-9
~
L Lenqth 5-11 6-5 5-11 6-5 5-11 6-6 5-11 6-6 6-8 5-11 6-6 6-8 5-11 6-6 6-8
z
C)
''d'' Top Slab-No. of 10 6 10 6 10 6 10 6 6 10 6 6 10 6 6
Bars Bottom Slab-No. of 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6
"e" Bars Spacing 18 18 18 18 18 18 18 18 18 18 18 18 18 18 18
'!)/ ;;o;;o
:z:: 0 c Spacers Total Number 36 44 44 44 48 52
c: ::::0 ~§
.a OS:: Concrete: C.Y. per lin. ft. 99 138 103 144 108 152 118 158 190 130 165 198 141 178 213
s::::::> !!l
t:c:§ rn zs::: ~
:::::>
0
>1'11
f'Tl:z:: :::J
rz 0 Reinf lbs per lin. ft. 203 293 213 304 218 311 223 317 387 231 326 397 243 341 415
:::CG") 1110
::0 NOTE
~8
~ z
~~ Cal For boxes of height less than that shown in table, use next greater table height slabs,
['1 ;:::--.1 >-<
c wall dimensions and reinforcing steel, and make necessary changes in bar lengths,
I ~:I!
1111'11 number of spacers and quantities.
......
m
~ [ 0111
"T1 0 ~ ~~
s:::
c
..... ~
"' "N ~~
\0 rro8
i\;
For cover less than 2'
provide #4 0 18" eo
S way &: adjust quantities
,.-ll ~·a· Bars( "' -#4 spacers
.,: : ,..-- t:t:;~~===~·'-.__..../::::::::::::!==~tVlj'n Provide paving notch when top is
.r p- #4 --......._ t- J1 . exposed and where PCC pavement
I
1: .25 I •d" Bars I .2?"--- ·. ! or approach slob is used
:~ ~ #5 - I\)
:z: :fl -Invert e~:: ~ ~ """'3/4" min fillets
l [z5 ~d" trs . 25 -#4 spacer bars @ 18" max
u\
,____~"-
I 1[4 : 12 f-o:: ""'\ Optional construction joint
® For reinforcement clearance, except
~ "f ·/ 1 #4 spacers at bottom, see "Miscellaneous Details,"
,____ "-"a" Bars -= on D-81A and D-81B

lYPICAL SECTIONS 2' THRU 6' SPANS

For cover less than 2'


provide #4 @ 18" eo
T3 1 ~ S 1
T3
way &: adjust quantities r 1
--- "y"l -- \ (See det "A~~ #4 spacers
0 18" :t
1--~"·x" ).-#13 (#4) spacers
\ /
.,: : .-----:.== = (J. \ "a~ I/ /"" Construction joint
.2 1, • / ~ Provide paving notch
" ,. ,.... .___3/4" min fillets___...,... ~ / , - when top is exposed and
~
1 ,
.2S #4"d"Borsl .2S
~ J
: l 'N
:-~ 0:0
where PCC pavement
or approach slab is used
1 ~#4 spacer bars ,.- 1 1=-L
~ • @ 18" max 1 - - # 5 "e" Bars
~ Invert elev See det "A" ~ 6.1--:_
~ /2s #4"d"Bors .2S D .,..:::::..-------optional construction joint
~
II
It ;a• 1[4 : 12
• •
a'- '
'-' 24" dio
6" 1
~ . JC\ 4lo. \. '----#4 spacers
2" clr .J 0 "C1" Bars #4 spacers @ 18"±

lYPICAL SECTIONS 7' THRU 12' SPANS

.,....., .. .. >
Q)

_l= ~ elev·~ ~
a;

s. .
Invert -e
6:2-~ ~
_l.:~ a. s... :r: .... Slope
· :r:
.· SlopeA 4:2·~'---:

:.........;~::::=:::P.§~~::::::l!~:;:.-~·=t---___l....=..:::....!:===jF-~~~:::4
~
. . . . ·T. "" . .do :
r-:-· ~ ~ ~··. -~

T FLAT INVERT V INVERT lrRAPEZOIDAL INVERT

ALTERNATIVE INVERTS
(When specified)

Revision By Approved Date RECOMMENDED BY THE SAN DIEGO


SAN DIEGO REGIONAL STANDARD DRAWING RE~ COMMITTEE
ORIGINAL Kercheval 12/7f
r===~~~==~~~-----------------~~,~~7~
Add Metric T Stanton 03/03 ~~ao~
Reviewed T Stanton 04/06 SINGLE BOX CULVERT Chairperson R.C.E. 19246 Date
s.s. 03/11 DRAW1NG
Edited T. Regello
DETAILS N0.2 NUMBER D-76G
:::0
~ ~ CD 6: 0 ::::0
;+ ;+ < c.. ;;u
CD CD ;;;· CD
c.. c.. 3:: G5 :S.
CD en
"'c.. ~
:::l.
0
z o·
> ~
r
en tD
0 '<
;-1 ;-1 ;-1 ;-1 ;:o;: )>
CD -o
CD
en en ~ (l -o
..,:::0 8"
::J
8"
::J
c
::J :::T 0
!!. CD
0 8"
::J
8"
::J
8"
::J
CiS SPAN 4' (all measurements in feet and/or inches unless otherwise noted)
[ c..
~
0 0 0 0 0
tH c
~ ~
~
0
~
0 ..- SPAN 4'
~
a~
tH
-....J CD
"' 01
"' HEIGHT 2' 3' 4'
en STRENGTH CLASSIFICATION A B c A B c D A B c D
:1>
z MAX FILL OVER TOP 11 21 32 11 23 34 46 11 23 34 46
..; Top Slab T1 6 1/2 6 1/2 7 1/4 6 1/2 6 1/2 7 1/2 8 1/2 6 1/2 6 1/2 7 1/2 8 1/2
2 § Bottom Slab 6 7 1/4 8 1/2 6 7 1/2 8 1/2 9 1/2 6 7 1/2 8 1/2 9 1/2
m u
T2
C)
Sidewalls T3 6 6 6 6 6 6 6 6 6 6 6
c 0
0 Size Bar# 5 4 4 5 4 4 4 5 4 4 4
;:ltl "a"
c: m ~
Spacing 11 11 9 11 10 1/2 8 1/2 7 1/2 11 10 1/2 8 1/2 7 1/2
c 1:1:11 C) Length 10-3 10-2 10-2 10-3 10-2 10-2 10-2 10-3 10-2 10-2 10-2
r-
Size Bar# 5 5 5 5 5 5 5 5 5 5 5
m m
..... "b"
.../""""'--
0z
,. 1:1:11 :1> Spacing 11 11 9 11 10 1/2 8 1/2 7 1/2 11 10 1/2 8 1/2 7 1/2
Q;
or
F r- "b," Lenqth "b" 9-4 9-4 9-6 9-4 9-4 9-6 9-7 9-4 9-4 9-6 9-7
2 ......____,
en 0 VJ Lenqth "b1' 9-4 9-5 9-6 9-4 9-4 9-6 9-7 9-4 9-4 9-6 9-7
>< en
-1 C">
z (") c Size Bar# 4 5 5 4 5 5 5 4 5 5 5
:1> ·~ "c''
z 0 Spacing 11 11 9 11 10 1/2 8 1/2 7 1/2 11 10 1/2 8 1/2 7 1/2
p c:
r- c -
c ·a:;
- Length 4-6 4-6 4-6 4-6 4-6 4-6 4-6 4-6 4-6 4-6 4-6
< :1> c::
- m ;:ltl "d" Dist Top Slab-Tot. No. 10 6 6 10 6 6 6 10 6 6 6
:a c Bars Bottom Slab-Tot. No. 6 6 6 6 6 6 6 6 6 6 6
..... c ''e" Size Bar# 4 4 4 4 4 4 4 4 4 4 5
;:ltl
:1> Bars Spacing 18 18 18 18 18 16 12 18 12 9 10
~ Spacers Number 23 26 29
z g Concrete: C.Y. per lin. ft. 0.47 0.51 0.57 0.53 0.57 0.63 0.69 0.59 0.63 0.69 0.75
C) ::::l
0 Reinf. lbs per lin. ft. 81 74 84 84 79 91 101 87 85 99 111
'!)/ :::0:::0
:z:o 0
c: ::::0 ~§ NOTE
0~
s::::::> .a
t:c:§ ~ z~
rrl:z:
.
0 >rrl
rz For boxes of height less than that shown in table, use next greater
::J
:::CG"> 1110 table height slobs, wall dimensions and reinforcing steel, and make
::0
~8 necessary changes in bar lengths, number of spacers and quantities.
r> z
~~ Cal
['1 ;:::--.1 >-< Number of "d" bars in table is slob total for both cells.
c I ~:I!
lllrrl
......
......
~ [ ()Ill
,. 0 ~ ~~
~
0 ~
.....
CD
"N ~~
\0 m8
i\;
::0
~ ~ Eia.: 0 ::::0
;: ~ :5. ;;o CD
a. a. ;;:::
..
G5 s.
en
.:e
a. ~ c;·
:l.
0 ~ :;::,
r
(/)
OJ
!n '<
:-1 :-1 :-1 :-1 ;;o;;; )>
CD -o
::0 -o
. sssn
!!.
:::r 0 SPAN 5' (all measurements in feet and/or inches unless otherwise noted)
0 ~
"' s s s
::J ::J ::J c..
~
~
0 0 0
2 SPAN 5'
""
~ CD
0>
a"' ~ a"" ~-..101 ......c
"" HEIGHT 2' 3' 4' 5'
C/) STRENGTH CLASSIFICATION A 8 c A 8 c A 8 c D A 8 c D
>
z MAX FILL OVER TOP 6 36 36 6 24 36 6 23 34 46 6 23 34 46
0
Top Slab T1 6 3/4 7 3/4 9 1/4 6 3/4 7 3/4 9 1/4 6 3/4 7 3/4 9 1/4 10 1/4 6 3/4 7 3/4 9 1/4 10 1/4
c :5 Bottom Slab T2 6 1/2 8 3/4 10 1/4 6 1/2 8 3/4 10 1/4 6 1/2 8 3/4 10 1/4 11 1/4 6 1/2 8 3/4 10 1/4 11 1/4
iii u
C) Sidewalls T3 6 6 6 6 6 6 6 6 6 6 6 6 6 6
c 0 . .. Size Bar# 5 4 4 5 4 4 5 4 4 4 5 4 4 4
0 :a a Spacing 10 8 1/2 10 10 8 1/2 10 10 8 1/2 10 9 10 8 1/2 10 1/2 9
c: '-------..:)
m Length 12-3 12-2 12-2 12-3 12-2 12-2 12-3 12-2 12-2 12-2 12-3 12-2 12-2 12-2
D:l
cm r- C)
m 0 "b" Size Bar# 5 5 6 5 5 6 5 5 6 6 5 5 6 6
..... ...r--\....
z Spocinq 10 8 1/2 10 10 8 1/2 10 10 8 1/2 10 9 10 8 1/2 10 1/2 9
~ D:l )to -a:;
or
r- 0 r- Q} "b1" Length "b" 11-5 11-6 11-7 11-5 11-6 11-7 11-5 11-6 11-7 11-8 11-5 11-6 11-7 11-8
VJ ......____, Length "b1 tf 11-4 11-6 11-7 11-4 11-6 11-7 11-4 11-6 11-7 11-8 11-4 11-6 11-7 11-8
en >< C/)
..... c
"" Size Bar# 4 5 6 4 5 6 4 5 6 6 4 5 6 6
z 0 )to -~ "c"
~ 0 Spacing 10 8 1/2 10 10 8 1/2 10 10 8 1/2 10 9 10 8 1/2 10 1/2 9
c: z c -
r- ·c;:;
- Length 5-6 5-6 5-6 5-6 5-6 5-6 5-6 5-6 5-6 5-6 5-6 5-6 5-6 5-6
Ck::
c)to
- <
m ::ltl
"d" Dist Top Slob-Tot. No. 12 6 6 12 6 6 12 6 6 6 12 6 6 6
:a c Bars Bottom Slob-Tot. No. 6 6 6 6 6 6 6 6 6 6 6 6 6 6
..... c ''e" Size Bar# 4 4 4 4 4 4 4 4 4 5 4 4 5 6
::ltl Bars Spacing 18 18 18 18 18 16 18 12 10 10 1/2 18 8 1/2 9 9
)to
Spacers Number 23 26 29 32
~ 0.58 0.69 0.80 0.63 0.75 0.86 0.69 0.80 0.89 0.98 0.74 0.86 0.97 1.04
z
C)
g:::::1 Concrete: C.Y. per lin. ft.
0 Reinf :lbs per lin. ft. 99 100 109 103 104 112 106 109 119 133 109 116 126 148

91/ ::0::0
ITIITI NOTE
:zo !:!. C)()
c: ::::0 -a of!
3:: )> ..iil z;;::: For boxes of height less than that shown in table, use next greater table height slabs, wall
OJ~ )>ITI
0 dimensions and reinforcing steel, and make necessary changes in bar lengths, number of spacers and
~:z :J 'z
G') cnc
::0 quantities. Number of "d" bars in table is slab total for both cells.
~
['1
i8
CDl
>-<
c I N
~[ el:J!
cniTI
....... "'""en
....... ~
"en
o,.
D:l 0 ~z
~ ~
.. ~
I:>
~~
ITI8
i\i
,.,., ,.,., ::<!
a. a. CD ~ 0 :::0
< a. ;;u CD
s= s= ;;;·
a. a. liE s::: G5 :S.
CD (I)
a. ~ z (5"
::!.
n > ~
r
(/)
co
0 '<
:-< :-< :-< :-< ;;o;: )>
CD ""0
::<! ~ ~ ""0
CD c c ~ ~
::> ::> ::> :::T a
CD
CiS
"'!!..0 S" <
::>
S" ::>
S" ::>
Q. c..
~
SPAN 6' (all measurements in feet and/or inches unless otherwise noted)
0 0 0 0 0
"' ~ c
-....J CD
~a
"' ~ a
"' 0> "' 01 - SPAN 6'
en HEIGHT 3' 4' 5' 6'
STRENGTH CLASSIFICATION A B c A B c A B c D A B c D
,.z
MAX FILL OVER TOP 4 20 34 4 20 34 4 19 33 43 4 19 33 43
c 7 1/4 8 1/4 10 1/2 7 1/4 8 1/4 10 1/2
m t.i Top Slob T1 7 1/4 8 1/4 10 1/2 12 7 1/4 8 1/4 10 1/2 12
G) § Bottom Slab T2 7 1/4 9 1/2 11 1/2 7 1/4 9 1/2 11 1/2 7 1/4 9 1/2 11 1/2 12 3/4 7 1/4 9 1/2 11 1/2 12 3/4
c 0 u
Sidewalls T3 6 6 6 6 6 6 6 6 6 6 6 6 6 7 1/2
0 ;:a:J Size Bar# 5 4 4 5 4 4 5 4 4 4 5 4 4 4
c: m ''a''
c 1:1:11 G) c....______:)
Spacing 9 1/2 11 8 1/2 9 1/2 11 8 1/2 9 1/2 11 8 1/2 10 1/2 9 1/2 11 8 1/2 10 1/2
m m r- Length 14-3 14-2 14-2 14-3 14-2 14-2 14-3 14-2 14-2 14-2 14-3 14-2 14-2 14-8
.....
,. 0z
"b" Size Bar# 5 6 6 5 6 6 5 6 6 7 5 6 6 7
1:1:11 .../""""""'-
Spacing 9 1/2 11 8 1/2 9 1/2 11 8 1/2 9 1/2 11 8 1/2 10 1/2 9 1/2 11 8 1/2 10 1/2
F
,.r-
m
or
en 0 >< en "b( Length "b" 13-6 13-6 13-8 13-6 13-6 13-8 13-6 13-6 13-8 13-9 13-6 13-6 13-8 14-2
z -1 ~ ............., Length "b1" 13-5 13-7 13-8 13-5 13-7 13-8 13-5 13-6 13-8 13-9 13-6 13-6 13-8 14-2
(") cr>
c: Size Bar:tt 4 6 6 4 6 6 4 6 6 7 4 6 6 7
"c"
p c: ,.z -~
r- 0 Spacing 9 1/2 11 8 1/2 9 1/2 11 8 1/2 9 1/2 11 8 1/2 10 1/2 9 1/2 11 8 1/2 10 1/2
,.c c: -
<
m ;:a:J "(i)
- Lenqth 6-6 6-6 6-6 6-6 6-6 6-6 6-6 6-6 6-6 6-6 6-6 6-6 6-6 6-8
0::::
- ::a
.....
c
c
"d" Dist Top Slab-Tot. No.
Bars Bottom Slab-Tot. No.
12
6
6
6
6
6
12
6
6
6
6
6
12
6
6
6
6
6
6
6
12
6
6
6
6
6
6
6
;:a:J Size Bar# 4 4 4 4 4 4
,. "e" 4 4 5 5 4 5 6 6
Bars Spacing 18 18 16 18 14 8 1/2 18 10 9 1/2 7 18 11 9 6
~ Spacers Number 30 33 36 36
z
G) g Concrete: C.Y. per lin. ft. 0.77 0.90 1.08 0.82 0.96 1.13 0.88 1.01 1.19 1.30 0.93 1.07 1.25 1.47
:::>
C1 Reinf :lbs per lin. ft. 121 119 147 125 124 155 128 131 164 175 129 137 177 201
91 :<I ::<I
,.,.,,.,.,
:z:o c C>C>
c: :::0 .a 0~
s::::::> ~ zs::: NOTE
co:§ ~ >rrl
rrl:z: ::> rz For boxes of height less than that shown in table, use next greater table height
:::OG"> VIC
::0 slabs, wall dimensions and reinforcing steel, and make necessary changes in bar
0
~ ~8
z
tn Cal lengths, number of spacers and quantities. Number of "d" bars in table is slab
>-<
c co ~:I! total for both cells.
I [ VI,.,
.....
..... "'~ (')VI
0>
(") 0
~ ~z
c ~
....
CD
1\;-
\;:, ffi~0
i\)
;;c
~ ~ ~ 0 ::::0
:5.
"' a. ;;u CD
~ ~ (5 :S.
a. a. :E ;;:::
~
en
(5'
"'a. z
"' :::J.
0 > ~
r
(/) tD
(n '<
;-i ;-i ;-i ;-i ;:o;: )>
<D "0
;;c (/) (/) (/) "0
(l .....,
8" 8" 8" ::J" 0
<D
"'!:!!."'0 "0 "0 "0 CiS SPAN 8' (all measurements in feet and/or inches unless otherwise noted)
c..
" " " [ ~
0 0 0 0 0
c
..- SPAN 8'
~ ~
en
-...J CD
~ ~~ 01
HEIGHT 4' 5' 6' 7' 8'
en STRENGTH ClASSIFICATION A B c A B c A B c A B c D A B c D
:1>
z MAX FILL OVER TOP 3 14 25 3 14 25 3 14 25 3 14 25 37 3 14 25 37
u Top Slab T1 8 1/2 9 1/2 12 8 1/2 9 1/2 12 8 1/2 9 1/2 12 8 1/2 9 1/2 12 1/4 14 1/4 8 1/2 9 1/2 12 1/4 14 1/4
2 5 Bottom Slab T2 7 1/210 1/2 12 3/4 7 1/210 1/2 12 3/4 7 1/2 10 1/2 12 3/4 7 1/2 10 3/4 13 15 7 1/2 10 3/4 13 15
m u
C) Sidewalls T3 6 6 6 6 6 6 6 6 6 7 7 7 8 7 7 8 8 1/2
c 0 Size Bar# 6 4 4 6 4 4 6 4 4 6 4 4 4 6 4 4 4
0 "a"
;:ltl Spacing 12 9 1/2 10 1/2 12 9 1/2 10 12 9 1/2 10 11 1/2 9 1/2 10 8 1/2 11 1/2 9 1/2 10 8 1/2
c: c...._____:)

1:1:11
m Length 18-4 18-2 18-2 18-4 18-2 18-2 18-4 18-2 18-2 18-7 18-5 18-5 18-8 18-7 18-5 18-8 18-10
c C)
m m r- "b" Size Bar# 6 6 7 6 6 7 6 6 7 6 6 7 7 6 6 7 7
..... ....r--'<....
Spacing 12 9 1/2 10 1/2 12 9 1/2 10 12 9 1/2 10 11 1/2 9 1/2 10 8 1/2 11 1/2 9 1/2 10 8 1/2
0z
,. Qj
or
1:1:11 :1> "b( Length "b" 17-7 17-8 17-9 17-7 17-8 17-9 17-7 17-8 17-9 17-10 17-10 18 18-5 17-10 17-10 18-3 18-6
F r- (/}
B ........._,
en 0 Length "b1" 17-5 17-8 17-9 17-5 17-8 17-9 17-5 17-8 17-9 17-10 17-10 18 18-5 17-8 17-11 18 18-7
>< en C'>
c II II Size Bar# 4 6 7 4 6 7 4 6 7 4 6 7 7 4 6 7 7
z -1 ·~ c
(") :1> .E Spacing 12 9 1/2 10 1/2 12 9 1/2 10 12 9 1/2 10 11 1/2 9 1/2 10 8 1/2 11 1/2 9 1/2 10 8 1/2
c -
p c: z ·;;:; Length 8-6 8-6 8-6 8-6 8-6 8-6 8-6 8-6 8-6 8-7 8-7 8-7 8-8 8-7 8-7 8-8 8-9
r- c 0:::

< :1> "d" Dist Top Slab-Tot. No. 16 8 8 16 8 8 16 8 8 16 8 8 8 16 8 8 8


- m ;:ltl Bars Bottom Slab-Tot. No. 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8
:a c "e" Size Bar# 4 4 5 4 4 5 4 5 6 4 5 6 7 4 5 7 7
..... c Bars Spacing 18 18 10 1/2 18 12 10 18 11 1/2 10 14 9 1/2 7 1/2 8 1/2 11 1/2 8 1/2 7 1/2 9
;:ltl
:1> Spacers Number 41 44 44 47 56 50 60
g Concrete: C.Y. per lin. ft. 1.08 1.30 1.55 1.14 1.37 1.61 1.19 1.42 1.66 1.32 1.56 1.83 2.14 1.39 1.62 1.99 2.27
~ ::I
z 0 Reinf :lbs per lin. ft. 169 175 200 172 181 218 173 188 229 185 199 248 299 191 207 284 314
C)

'!)/ ;;c;;c
:z:o 0
c: ::::0 ~§
0;;:::
s::::::> -a
t:c:§ ~ z;;::: NOTE
f'Tl:z:
.
0 >rrl
rz
:::CG"> "';;c 1110 For boxes of height less than that shown in table, use next
~8 greater table height slobs, wall dimensions and reinforcing
r> z
~~ Cal
['1 ::::--1 >-< steel, and make necessary changes in bar lengths, number of
c I ~:I! spacers and quantities. Number of "d" bars in table is slob
1111"1
...... ~ [ ()Ill
total for both cells .
...... ~ ~~
c 0 ;;:::
0 ~
....... "N
\0
~~
m8
i\;
SPAN 10' {all measurements in feet and/or inches unless otherwise noted)

SPAN 10'
HEIGHT 5' 6' 7' 8' 10'
en STRENGTH CLASSIFICATION A B c A B c A B c A B c D A B c D
:1>
z MAX FILL OVER TOP 2 17 30 2 17 30 2 17 30 2 16 29 36 2 16 29 36
..; Top Slab T1 8 3/4 12 3/4 16 8 3/4 12 3/4 16 8 3/4 12 3/4 16 8 3/4 12 3/4 16 17 1/4 8 3/412 3/4 16 17 1/2
2 5 Bottom Slab T2 8 1/4 13 1/2 16 1/2 8 1/4 13 1/2 16 1/2 8 1/4 13 3/4 16 3/4 8 3/4 13 1/2 16 1/2 18 1/4 8 3/413 1/2 16 1/2 18 1/2
m (_)
C) Sidewalls T3 6 6 6 6 6 6 6 6 1/2 7 7 7 7 1/2 7 1/2 8 8 9 10
c 0 Size Bar# 6 4 4 6 4 4 6 4 4 6 4 4 4 6 4 4 4
0 "a"
;:ltl Spacing 11 10 10 11 9 1/2 10 11 9 1/2 10 11 10 10 9 11 10 10 9
c: ~
m Lenqth 22-4 22-2 22-2 22-4 22-2 22-2 22-4 22-4 22-5 22-7 22-5 22-7 22-10 22-10 22-8 22-11 23-2
CCCI C)
mr- "b" Size Bar# 6 7 8 6 7 8 6 7 8 6 7 8 8 6 7 8 8
..... m __,.........._
Spacing 11 10 10 11 9 1/2 10 11 9 1/2 10 11 10 10 9 11 10 10 9
or
0z
a;
., "b1" Length "b" 21-7 21-10 22 21-7 21-10 22 21-7 21-11 22-3 21-10 22-1 22-4 22-9 22-1 22-4 22-9 23-1
~CCI :1>
r-o r- Vi --...........r- Lenqth "b1" 21-5 21-10 22 21-5 21-10 22 21-5 21-11 22-3 21-9 22 22-4 22-9 22 22-3 22-8 23-2
(/)>< C/) c:
"" Size Bar# 6 7 8 6 7 8 6 7 8 6 7 8 8 6 7 8 8
-~ "c''
-1 ~ Spacing 11 10 10 11 9 1/2 10 11 9 1/2 10 11 10 10 9 11 10 10 9
:1> c:
·a;
- Length 10-6 10-6 10-6 10-6 10-6 10-6 10-6 10-7 10-7 10-7 10-7 10-8 10-9 10-8 10-8 10-9 10-10
~g z CkO
_r- c "d" Dist Top Slab-Tot. No. 18 10 10 18 10 10 18 10 10 18 10 10 10 18 10 10 10
< :1> Bars Bottom Slab-Tot. No. 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10
m ;:ltl
c "e" Size Bar# 4 4 5 4 4 5 4 4 6 4 5 6 7 4 6 6 7
::a Bars Spacing 18 10 10 18 6 6 1/2 14 6 8 11 8 1/2 6 6 7 1/2 7 5 1/2 5
..... c Spacers Number 48 48 51 54 64 68
;:ltl
:1> g:::l Concrete: C.Y. per lin. ft. 1.40 2.05 2.46 1.45 2.07 2.48 1.51 2.18 2.64 1.68 2.27 2.74 3.04 1.92 2.51 3.05 3.41
0 Reinf :lbs per lin. ft. 236 254 310 238 274 324 243 280 339 252 278 355 430 279 327 400 476
~
z
C)

NOTE
For boxes of height less than that shown in table, use next greater table height slabs, wall dimensions and reinforcing steel, and make
necessary changes in bar lengths, number of spacers and quantities. Number of "d" bars in table is slab total for both cells.
:;c
~ ~ CD ~ 0 ::::0
Q.
::0 CD
s= s= s. CD
a. a. :E ;;::: G'5 :S.
CD Cl)
a. ~ z (5'
n )>
"'· ~
r
Ill
tD
0 '<
;-i ;-i ;-i ;-i :;o;: )>
CD "0
:;c Ill Ill Vl "0
CD
cr cr cr n .....,
::::r 0
"'~ CD
0 s- s- s-
:::> :::> :::> < CiS
Q. c..
~
0 0 0 0 0
~ ~ ~~ c
..-
0 0 0 ~
-...J CD
co en t.l 01
SPAN 12' (all measurements in feet and/or inches unless otherwise noted)
--
en SPAN 12'
:1> HEIGHT 6' 7' 8' 9' 10' 12'
z
STRENGTH CLASSIFICATION A B C A B C A B C A B C D A B C D A B C D
2 MAX FILL OVER TOP 2 14 26 2 14 26 2 14 26 2 14 26 36 2 14 26 36 2 14 26 36
m . Top Slob T1 10 14 17 1/2 10 14 1/.417 1/2 10 1/4 14 1/4 17 3/4 10 1/4 14 1/2 17 3/4 20 3/410 1/414 1/2 17 3/4 20 3/4 10 1/414 1/2 18 1/4 21 1/4
G)
§ Bottom Slab T2 9 1/4 14 3/4 18 9 1/4 15 18 1/4 9 3/4 15 18 1/2 10 15 1/4 18 3/4 21 1/4 10 1/4 15 1/4 18 3/4 21 1/2 10 1/215 1/4 19 1/4 22
c 0 '-' Sidewalls T3 6 6 6 1/2 7 7 7 8 8 8 1/2 9 9 9 10 9 9 9 1/2 11 9 10 11 12
0 ::u Size Bar# 6 4 4 6 4 4 6 4 4 6 4 4 4 6 4 4 4 6 4 4 4
c: m "a"
D:l <....____J
Spacing 9 11 1/2 9 9 11 1/2 9 9 11 8 1/2 9 11 8 1/2 9 9 11 8 1/2 9 9 11 8 1/2 9
c G)
r- Length 26-4 26-2 26-4 26-7 26-5 26-5 26-10 26-8 26-10 27-1 26-11 26-11 27-1 27-1 26-11 27-3 27-5 27-1 27-2 27-5 27-8
Size Bar# 6 8 8 6 8 8 6 8 8 6 8 8 9 6 8 8 9 6 8 8 9
m m
..... "b"
...r-->....
0z
Spacing 9 11 1/2 9 9 11 1/2 9 9 11 8 1/2 9 11 8 1/2 9 9 11 8 1/2 9 9 11 8 1/2 9
~ D:l :1> or
Ol 25-8 25-10 26-3 25-11 26-1 26-4 26-2 26-4 26-9 26-5 26-8 26-10 27-4 26-5 26-8 27-2 27-6 26-5 26-11 27-5 27-10
r- 0 r- .!l "b1" Lenqth "b"
Vl ............r Length "b,· 25-6 25-10 26-3 25-9 26-2 26-4 26-1 26-5 26-9 26-4 26-8 26-11 27-4 26-4 26-8 27-2 27-7 26-4 26-11 27-5 27-11
c::
en >< en "' Size Bar# 5 8 8 5 8 8 5 8 8 5 8 8 9 5 8 8 9 5 8 8 9
-1 -~ "c"
z (") Spacing 9 11 1/2 9 9 11 1/2 9 9 11 8 1/2 9 11 8 1/2 9 9 11 8 1/2 9 9 11 8 1/2 9
? :1> ~
·;;:;
- Length 12-6 12-6 12-7 12-7 12-7 12-7 12-8 12-8 12-9 12-9 12-9 12-9 12-10 12-9 12-9 12-10 12-11 12-9 12-10 12-11 13
c: z <>:::
r- c 'd' Dist Top Slab-Tot. No. 24 10 10 24 10 10 24 10 10 24 10 10 10 24 10 10 10 24 10 10 10
< :1> Bars Bottom Slab-Tot. No. 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10
- m ::u 'e" Size Bar# 4 4 5 4 4 5 4 4 5 4 5 7 8 4 7 8 8 6 7 8 9
:a c Bars Spacing 18 8 8 15 6 6 1/2 12 5 1/2 6 9 7 1/2 8 1/2 8 8 1/2 11 8 1/2 9 12 8 7 7
..... c Spacers Number 52 55 68 68 72 76
::u g Concrete: C.Y. per lin. ft. 1.84 I 2.59 3.16 1.97 2.77 I 3.28 2.19 I 2.93 3.59 2.38 I 0.74 I 3.69 I 4.25 2.48 3.23 I 3.86 I 4.49 2.67 3.53 4.30 I 4.92
:1> 6 Reinf :lbs per lin. ft. 309 1 317 401 316 330 1 415 336 1 363 460 345 1 374 1 485 1 578 351 394 1 519 1 582 371 427 567 1 673
~
z
G)
NOTE
For boxes of height less than that shown in table, use next greater table height slobs, wall dimensions and reinforcing steel, and make
necessary changes in bar lengths, number of spacers and quantities. Number of "d" bars in table is slob total for both cells.
For cover less than 2' Provide paving notch when top is exposed ond
provide #4 @ 18" eo c Bars-- where PCC pavement or approach slab is used
way & adjust quantities

s
#4 spacers @ 18"- -~~ 1\ I I
t=
----r-r-~~~~~~~~~~~------r-.-7~
/ - ./ ~ 12" f
,...... .... rLaBars (______)f- .25sl #4"d"I.25S_l_ 12•
#4
I
spacers ~
I

~ ~~~ru~ J_ @ ±18" -
.2, t .....-#4018" ~·
:::c t;; '-t-#4spacers0±18" ,....- · Ij
g ~ ~ H
\ v- e Bars Invert elev ·255 d Bars ·255 ~ Optional const joint ~ _ _..s•
'-.., p 1/4 : 12 \ I I ~ 6" L :..--1 I
~~ -~ '_/ . l t {F====::!...J....=:=-d==t
#4 spacers ' ( c Bars __ l '--a Bars ~ 1
I
® '-b1 Bars --.........r- Reinforcement for interior
~~ walls under 8"

lYPICAL SECTION
(Showing reinforcement for interior walls 8" and over)

® For reinforcement clearance, except at bottom, see "Miscellaneous Details," on D-81A and D-81 B.

. ~
~.
.4 ~-

. ~ ~.. :4 4. A ~·

•FLAT INVERT• ALTERNATIVE


(When specified)

Revision By Approved Date RECOMMENDED BY THE SAN DIEGO


SAN DIEGO REGIONAL STANDARD DRAWING RE~ COMMITTEE
ORIGINAL Kercheval 12/75
Add Metric T. Stanton 03/03 I.....__ _}!:f;Ftr,u<7if"!1) 7(26(2012
Reviewed T. Stanton 04/06 DOUBLE BOX CULVERT Chairperson R.C.E. 19246 Date
s.s.
Edited T. Regello 03/11
DETAILS NO. 2 DRAW1NG
NUMBER D-77G
;;o
~ ~ ~ 0 ::::0
;:;: ;:;: ~- a. ::0 CD
~ 31:: (5 :S.
"'a. "'a. "' ~
en
"'a. ~- ~ o· ~
r
en tD
!n '<
;-1 ;-1 ;-1 ;-1 :;"i: )>
CD -o
;;o en en -o
0 0 .....,
"' sn ::r 0
"'!!.. ;:!. CD
0 s- s- 0 CiS
::J ::J ::J [ c..
0 0 0 0 0
SPAN 4' (all measurements in feet and/or inches)
1\.)
c
..-
~ ~ ~ ~ t::r (.N
CD
<0 0> 01 SPAN 4'
en HEIGHT 2' 3' 4'
:1>
z STRENGTH CLASSIFICATION A B c A B c A B c
MAX FILL OVER TOP 10 24 38 10 24 38 10 24 38
2 c..i Top Slab T1 6 1/4 6 1/4 7 1/4 6 1/4 6 1/4 7 1/4 6 1/4 6 1/4 7 1/4
m
C) § Bottom Slab T2 6 7 8 1/4 6 7 8 1/4 6 7 8 1/4
..... 0 u
Sidewalls T3 6 6 6 6 6 6 6 6 6
:!! ;:ltl , , Size Bar# 5 4 5 5 4 5 5 4 5
"'CC m a
cm r- C) ~
Spacing 11 11 1/2 13 11 11 1/2 13 11 11 1/2 13
..... m Length 14-9 14-8 14-9 14-9 14-8 14-9 14-9 14-8 14-9
:lrb:lr Size Bar# 5 5 6 5 5 6 5 5 6
0z
all
~
i!:
r- 0 :1> Spacing 11 11 1/2 13 11 11 1/2 13 11 11 1/2 13
r- -..,.., or Lenqth "b"
en >< 14-2 14-2 14-3 14-2 14-2 14-3 14-2 14-2 14-3
(")
en ~
cr; "b1 Length ''t>, " 14 14-2 14-3 14 14-2 14-3 14 14-2 14-3
-1 0'1
:1> c: Size Bar# 4 5 6 4 5 6 4 5 6
z c:
~ z -~ . "c
r- 0 Spacing 11 11 1/2 13 11 11 1/2 13 11 11 1/2 13
< c c: -
m :1> ·a;
- Lenqth 9 9 9 9 9 9 9 9 9
;:ltl 0:::
:a c "d" Dist Top Slab-Tot. No. 15 9 9 15 9 9 15 9 9
- .....
Bars Bottom Slab-Tot. No. 9 9 9 9 9 9 9 9 9
c "e'' Size Bar# 4 4 4 4 4 4 4 4
;:ltl 5
:1> Bars Spacinq 18 18 18 18 18 13 18 11 1/2 13
~ Spacers Number 34 38 42
z
C)
g::::1 Concrete: C.Y. per lin. ft. 0.67 0.71 0.81 0.75 0.79 0.89 0.82 0.86 0.96
0 Reinf :lbs per lin. ft. 122 110 133 127 115 138 131 122 147
'!)/ ;;o;;o
:z:o 0
c: ::::0 ~§ NOTE
0~
s::::::> .a
t:c:§ ~ z~
.
0 >rrl
rz
rrl:z: ::J For boxes of height less than that shown in table, use next greater
:::CG"> 1110
::0 table height slabs, wall dimensions and reinforcing steel, and make
~8
r> z
~~ Cal necessary changes in bar lengths, number of spacers and quantities.
['1 ::::--1 >-<
c I ~:I! Number of "d" bars in table is slab total for all cells.
lllrrl
...... ~ [ ()Ill
co ~ ~~
0 ~
> 0 ~
.....
"' "N ~~
\0 m8
i\;
SPAN 5' (all measurements in feet and/or inches)

SPAN 5'

en HEIGHT 2' 3' 4' 5'


l> STRENGTH CLASSIFICATION A B C A B C A B C D A B C D
z
MAX FILL OVER TOP 8 17 26 8 17 26 8 17 26 35 8 17 26 35
c cJ Top Slab T1 6 3/4 6 3/4 7 1/2 6 3/4 6 3/4 7 1/2 6 3/4 6 3/4 7 1/2 8 1/2 6 3/4 6 3/4 7 1/2 8 1/2
iii
C) g Bottom Slab
..... 0 u Sidewalls ~ 6 6 6 6 6 6 6 6 6 6 6 6 6 6
:a :a , , Size Bar# 5 4 5 5 4 5 5 4 5 5 5 4 5 5
:;; m a Spacinq 10 11 1/2 13 10 11 1/2 13 10 11 13 11 1/2 10 11 13 11 1/2
Cr- C) '--------:1
mm Length 17-9 17-8 17-9 17-9 17-8 17-9 17-9 17-8 17-9 17-9 17-9 17-8 17-9 17-9
..... 0 "b" Size Bar# 5 5 6 5 5 6 5 5 6 6 5 5 6 6
>m z
r-0 l> _~Spacing • • 10 11 1/2 13 10 11 1/2 13 10 11 13 11 1/2 10 11 13 11 1/2
r 17-3 17-3 17-3 17-3 17-3 17-3 17-3 17-3 17-3 17-3 17-3 17-3 17-3 17-5
en>< Jl "b 1• Lenqth b
en Vl ~ Length "t>," 17 17-2 17-4 17 17-2 17-4 17 17-2 17-4 17-5 17 17-2 17-4 17-5
zo .....
~ l> g' .. " Size Bar# 4 5 6 4 5 6 4 5 6 6 4 5 6 6
c: ·u c ~~-~------~~~~~~~~~~~~=+~~~~~~~~~~~~~7-+-~-+~~~~~
r- z ~ Spac1ng 10 11 1/2 13 10 11 1/2 13 10 11 13 11 1/2 10 11 13 11 1/2
c ~ --- r.L~en~lQ~Ith~------~~17 1-+~11~~1~1~~1~1-+~11~~1~1~~7-+-7~~~~~~~~~~~~~~-+~~
11 11 11 11 11 11 11 11
-~ l>
:a :ltl o:::
"d" Dist Top Slab-Tot. No. 18 9 9 18 9 9 18 9 9 9 18 9 9 9
..... c Bars BottomSiab-Tot.No. 9 9 9 9 9 9 9 9 9 9 9 9 9 9
c "e" Size Bar# 4 4 4 4 4 4 4 4 4 54 4 4 6
:ltl
l> Bars Spacing 18 18 18 18 18 18 18 17 11 1/2 11 1/2 18 11 4 11 1/2
:s; Spacers Number 34 38 38 42
z g Concrete: C.Y. per lin. ft. 0.82 0.87 0.98 0.90 0.95 1.05 0.97 1.02 1.13 1.23 1.04 1.11 1.20 1.31
C)
5 Reinf :lbs per lin. ft. 150 126 153 155 130 157 157 136 161 181 161 143 171 192

NOTE
For boxes of height less than that shown in table, use next greater
table height slabs, wall dimensions and reinforcing steel, and make
necessary changes in bar lengths, number of spacers and quantities.
Number of "d" bars in table is slab total for all cells.
,.,a. ,.,a. :;u
<D ~ 0 ::::0
~- a. ::0 CD
s= s= <D
a. a. =e l!:: (5 :S.
<D !a. en
a.
~· r ~ o· ~

!/)
tD
!n '<
;-i ;-i ;-i ;-i :;"i: )>
CD -o
:;u -o
<D
.a ::3
~ ::3~ ::3~ ::r
n 0
~
C) C) CD C)
0 ::3 ::3 ::3
CiS
[ c..
0 0 0
SPAN 6' (all measurements in feet and/or inches)
El 1\.) 0
c
..-
~ ~ ~ ~ t::r CD
Cl (,j
"' 01 SPAN 6'
en HEIGHT 3' 4' 5' 6'
:1> STRENGTH CLASSIFICATION A B c A B c A B c D A B c D
z
MAX FILL OVER TOP 3 13 23 3 13 23 3 13 23 30 3 13 23 30
2 u Top Slab T1 7 1/2 7 1/2 8 1/4 7 1/2 7 1/2 8 1/4 7 1/2 7 1/2 8 1/4 9 1/4 7 1/2 7 1/2 8 1/4 9 1/4
m
C) g Bottom Slab T2 6 7 3/4 9 1/4 6 7 3/4 9 1/4 6 8 9 1/4 10 6 8 9 1/4 10 1/4
(_)
..... 0 Sidewalls T3 6 6 6 6 6 6 6 6 6 6 f) 6 6 6
:!! ;:ltl Size Bar# 6 5 5 6 5 5 6 5 5 5 6 5 5 5
"'CC m ··a·· Spacinq 11 1/2
c r- C) c;...._____;,
13 14 13 14 11 1/2 13 14 11 1/2 10 13 14 11 1/2 10
m m Length 20-10 20-9 20-9 0-10 20-9 20-9 20-10 20-9 20-9 20-9 20-10 20-9 20-9 20-9
..... 0z IIlib Size Bar# 6 6 6 6 6 6 6 6 6 6 6 6 f) 6
:I> CCI ~
-o :1> Spacing 13 14 11 1/2 13 14 11 1/2 13 14 11 1/2 10 13 14 11 1/2 10
r- Q)
or
~>< "b( Lenqth "b" 20-3 20-3 20-5 20-3 20-3 20-5 20-3 20-3 20-5 20-6 20-3 20-3 20-5 20-6
(")
en Ol ~ Length "t>, " 20 20-2 20-5 20 20-2 20-5 20 20-2 20-5 20-6 20 20 20-5 20-7
-1 C>
:1> c II II Size Bar# 4 6 6 4 6 6 4 6 6 6 4 6 6 6
z c:
~ ·c::; c
r- z ....
0 Spacing 13 14 11 1/2 13 14 11 1/2 13 14 11 1/2 10 13 14 11 1/2 10
< c c -
m :1> ·a;
- Lenqth 13 13 13 13 13 13 13 13 13 13 13 13 13 13
~
;:ltl 18 18 9 9 18 9 9 9 9
:a "d" Dist Top Slab-Tot. No. 9 9 18 9 9
c
- ..... Bars Bottom Slab-Tot. No. 9 9 9 9 9 9 9 9 9 9 9 9 9 9
c .. e Size Bar# 4 4 4 4 4 4 4 4 5 5 4 4 6 6
;:ltl
:1> Bars Spacing 18 18 18 18 18 11 1/2 18 11 1/2 12 10 18 8 12 10
~ Spacers Number 40 40 52 48
z g Concrete: C.Y. per lin. ft. 1.05 1.15 1.29 1.12 1.23 1.37 1.19 1.32 1.44 1.55 1.27 1.39 1.52 1.64
C) ::1
C1 Reinf :lbs per lin. ft. 181 168 196 183 170 200 187 177 209 235 192 187 221 249

'!)/ :;u:;u
:z:o 0
c: ::::0 ~§ NOTE
0~
s::::::> .a
t:c:§ ~ z~
.
0
>,.,
rrl:z: ::3
rz For boxes of height less than that shown in table, use next greater
:::CG"> VlO
::0 table height slabs, wall dimensions and reinforcing steel, and make
~8
r> z
~~ Cal necessary changes in bar lengths, number of spacers and quantities.
['1 ;:::--.1 >-<
c I ~:I! Number of "d" bars in table is slab total for all cells.
rn,.,
...... ~ [ OVl
co ~ ~~
(") 0 ~
0 ~
....... "N
\0
~~
,.,8
i\;
::0
~ ~ ~ 0 ::::0
a. ::0 CD
01 01 ~·
"'a. "'a. ~ 31:: (5 :S.
01 ~
en
a.
~- ~ o· ~
r
(/)
tD
0 '<
;-1 ;-1 ;-1 ;-1 :;"i: )>
CD -o
::0 (/) (/) -o
CD g- g-
CD
0 sn
CiS
"'!!..0 8- 8- 8- ::r
::J ::J
[ c.. ::J

0 0 0 0 1\.) 0 SPAN 8' (all measurements in feet and/or inches)


c
~ ~ ~ CD
t::r ..-
VI 01
~ "' SPAN 8'
en HEIGHT 4' 5' 6' 7' 8'
:1>
z STRENGTH CLASSIFICATION A B c A B c A B c A B c D A B c D
MAX FILL OVER TOP 2 11 20 2 11 20 2 11 20 2 11 20 28 2 11 20 28
2 u Top Slab T1 8 1/4 8 1/4 10 1/4 8 1/4 8 1/4 10 1/4 8 1/4 8 1/4 10 1/4 8 1/4 8 1/4 10 1/4 11 1/2 8 1/4 8 1/4 10 1/4 11 1/2
m
C) § Bottom Slab T2 6 1/2 9 11 6 1/2 9 1/4 11 6 1/2 9 1/4 11 6 3/4 9 1/4 11 12 1/4 6 3/4 9 1/4 11 12 1/4
u
..... 0 Sidewalls T3 6 6 6 6 6 6 6 6 6 6 6 6 1/2 6 1/2 7 7 7 1/2 8 1/2
:!! ;:ltl ··a" Size Bar# 6 5 5 6 5 5 6 5 5 6 5 5 6 6 5 5 6
"'CC m Spacing 11 1/2 12 12 11 1/2 12 12 11 1/2 12 12 11 1/2 12 12 10 1/2 11 1/211 1/2 12 10 1/2
r- C) '-------...:)
Length 26-10 26-9 26-9 26-10 26-9 26-9 26-10 26-9 26-9 26-10 26-9 26-11 27-4 27-2 27-1 27-3 27-8
cm
..... m 0z "b" Size Bar# 6 6 7 6 6 7 6 6 7 6 6 7 7 6 6 7 7
all ~
i!: :1> Spacing 11 1/2 12 12 11 1/2 12 12 11 1/2 12 12 11 1/2 12 12 10 1/2 11 1/211 1/2 12 10 1/2
r- 0 r- (ij
or
"b( Length "b" 26-5 26-5 26-7 26-5 26-5 26-7 26-5 26-5 26-7 26-5 26-5 26-9 27-3 26-9 26-9 27-1 27-7
en >< en ~ ~ Length "bl • 26 26-4 26-7 26 26-5 26-7 26 26-5 26-7 26-1 26-5 26-9 27-3 26-5 26-9 27-1 27-7
(") en
-1 c: Size Bar# 4 6 7 4 6 7 4 6 7 44 6 7 7 4l- 6 7 7
z c: :1> ·~ "c"
~ .!2 Spacing 11 1/2 12 12 11 1/2 12 12 11 1/2 12 12 11 1/2 12 12 10 1/2 11 1/211 1/2 12 10 1/2
r- z c: -
< c ·a; Length 17 17 17 17 17 17 17 17 17 17 17 17-1 17-3 17-2 17-2 17-3 17-5
m :1> .::.:
;:ltl
"d" Dist Top Slab-Tot. No. 24 12 12 24 12 12 24 12 12 24 12 12 12 24 12 12 12
:a c Bars Bottom Slab-Tot. No. 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12
- .....
"e" Size Bar# 4 4 4 4 4 5 4 5 6 4 6 7 7 4 6 7 7
c Bars Spacing 18 18 12 18 12 12 18 12 12 11 1/2 12 12 10 1/2 11 1/211 1/2 12 10 1/2
;:ltl
:1> Spacers Number 58 62 62 66 70 88
~ g Concrete: C.Y. per lin. ft. 1.47 1.67 1.99 1.54 1.76 2.06 1.62 1.84 2.14 1.71 1.91 2.26 2.57 1.90 2.10 2.46 2.79
::I
z
C)
0 Reinf :lbs per lin. ft. 261 250 301 266 257 310 267 264 320 276 277 336 409 283 295 347 441

'!)/ ::0::0
:z:o 0
c: ::::0 ~§
0~ NOTE
s::::::> .a
t:c:§ ~ z~
.
0 >rrl
rz
rrl:z: ::J For boxes of height less than that shown in table, use next greater
:::CG"> 1110
::0 table height slabs, wall dimensions and reinforcing steel, and make
~8
r> z
~~ Cal necessary changes in bar lengths, number of spacers and quantities.
['1 ::::--1 >-<
c ~:I! Number of "d" bars in table is slab total for all cells.
I lllrrl
...... ~ [ ()Ill
co ~ ~~
c 0 ~
0 ~
.....
CD
"N ~~
\0 m8
i\;
:::0
CD 0 ::::0
"";:;:a. "";:;:a.
CD CD
<
a;·
ia.1i:
::0 CD
a. a. :IE 31:: (5 :S.
CD en
a.
0 ~
"'s: ~ o·
r
(/)
tD
!n '<
:--' :--' :--' :--' :;"i: )>
CD -o
:::0 !a !a -o
c c .....,
<C ::r 0
:::l :::l
"'
!!.. C) C)
sn
:::l
C) CD
0 :::l :::l :::l
CiS
[ c..
SPAN 10' (all measurements in feet and/or inches)
0 0 0 0 1\.) 0
"' c
..-
~ a"" ~ ~ t::r CD
cc 0> 01 SPAN 10'
"'
en HEIGHT 5' 6' 7' 8' 10'
:1> STRENGTH CLASSIFICATION A B c A B c A B c A B c D A B c D
z MAX FILL OVER TOP 2 11 20 2 11 20 2 11 20 2 11 20 28 2 11 20 28
2 cJ Top Slab T1 9 10 12 9 10 12 9 10 12 9 10 12 14 1/4 9 10 1/4 12 1/2 14 1/2
m § Bottom Slab T2 7 1/2 10 3/4 13 7 1/2 10 3/4 13 7 1/2 10 3/4 13 7 3/4 11 13 15 8 11 13 1/2 15
C) u
..... 0 Sidewalls T3 6 6 6 6 6 6 6 6 6 1/2 7 7 7 1/2 8 1/2 8 8 1/2 9 10
Size Bar# 6 6 6 6 6 6 6 6 6 6 6 6 7 6 6 6 7
:!! ;:ltl "a''
"'CC m c:....____:)
Spacing 10 1/2 13 10 10 1/2 13 10 10 1/2 13 10 10 1/2 13 10 11 10 1/2 13 10 11
c
m r- C) Length 32-10 32-10 32-10 32-10 32-10 32-10 32-10 32-10 32-10 33-2 33-2 33-4 33-8 33-6 33-8 33-10 34-2
..... m "b" Size Bar# 6 7 7 6 7 7 6 7 7 6 7 7 8 6 7 7 8
....r-"'--.f"""
Spacing 10 1/2 13 10 10 1/2 13 10 10 1/2 13 10 10 1/2 10 1/2
0z
all or 13 10 11 13 10 11
i!:
r- 0 :1> -.:; 32-6 32-7 32-10 32-6 32-7 32-10 32-6 32-7 33 32-10 32-11 33-4 33-11 32-2 33-5 33-11 34-5
r- "b1" Length "b"
en >< ~ ~ Lenqth "b1 " 32-2 32-7 32-11 32-2 32-7 32-11 32-2 32-7 33-1 32-6 32-11 33-5 33-11 32-11 33-5 33-11 34-5
en 0">
c: Size Bar# 5 7 7 5 7 7 5 7 7 5 7 7 8 5 7 7 8
(") -1 -~ ··c·
:1> Spacing 10 1/2 13 10 10 1/2 13 10 10 1/2 13 10 10 1/2 13 10 11 10 1/2 13 10 11
z c:
~ .E
c: -
r- z "Q) Lenqth 21 21 21 21 21 21 21 21 21-1 21-2 21-2 21-3 21-5 21-4 21-5 21-6 21-8
c 0:::
<
m :1> "d" Dist Top Slab-Tot. No. 27 15 15 27 15 15 27 15 15 27 15 15 15 27 15 15 15
:a ;:ltl Bars Bottom Slab-Tot. No. 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15
c "e" Size Bar# 4 4 5 4 5 6 4 6 7 4 6 7 8 5 6 8 8
- .....
c Bars Spacing 18 13 10 18 13 10 13 13 10 10 1/2 12 10 11 10 1/2 9 10 9
;:ltl
Spacers Number 68 68 72 76 94 102
:1>
g::::J Concrete: C.Y. per lin. ft. 1.98 2.40 2.82 2.06 2.48 2.90 2.13 2.55 3.03 2.34 2.77 3.23 3.78 2.68 3.18 3.73 4.22
~ C!J Reinf :lbs per lin. ft. 358 372 470 359 379 482 367 391 502 377 402 514 590 421 453 577 632
z
C)

'!)/ :::0:::0
:z:o c ~§
c: ::::0 0~ NOTE
s::::::> .a
t:c:§ ~ z~
.
0
>...,
rz
rrl:z: :::l For boxes of height less than that shown in table, use next greater
:::CG"> 1110
:::0 table height slabs, wall dimensions and reinforcing steel, and make
~8
r> z
~~ Cal necessary changes in bar lengths, number of spacers and quantities.
['1 ;:::--.1 >-<
c ~:I! Number of "d" bars in table is slab total for all cells.
I Ill..,
......
co
~ [ ()Ill

m 0 ~ ~~
~
c ~
....
"' "N ~~
\0 ""8
i\;
SPAN 12' (all measurements in feet and/or inches)
SPAN 12'
HEIGHT 6' 7' 8' 9' 10' 12'
en STRENGTH CLASSIFICATION A B c A B c A B c A B c D A B c D A B c D
:1> MAX FILL OVER TDP 2 10 18 2 10 18 2 10 18 2 11 20 30 2 11 20 30 2 11 20 30
z .; Top Slab 11 1/2 14 10 1/4 11 1/2 14 10 1/4 11 1/2 14 10 1/4 12 14 3/4 17 3/410 1/4 12 14 3/4 17 3/4 10 1/4 12 14 3/4 17 3/4
T1 10 1/4
2 :5 Bottom Slab T2 8 1/4 12 14 1/2 8 1/2 12 14 3/4 8 1/2 12 14 3/4 8 3/4 12 1/2 15 1/2 18 1/48 3/4 12 1/2 15 1/2 18 1/4 9 12 3/4 15 3/4 18 1/4
m '-' Sidewalls T3 6 6 6 1/2 6 6 7 7 7 7 1/2 8 8 9 10 8 8 9 10 1/2 9 9 10 1/2 12
C) Size Bar# 7 6 7 7 6 7 7 6 7 7 6 7 8 7 6 7 8 7 6 7 8
0 "a"
..... <-------..:)
Spacing 12 11 11 1/2 12 11 11 1/2 12 11 11 1/2 12 10 1/2 11 11 1/2 12 10 1/2 11 11 1/2 12 10 1/2 11 11 1/2
:!! ;:ltl Length 39-1 38-10 39-3 39-1 3a-10 39-5 39-5 39-2 39-7 39-9 39-6 40-1 40-10 39-9 39-6 40-1 41 40-1 39-10 40-7 41-6
m "b" Size Bar# 7 7 8 7 7 a 7 7 a 7 7 8 9 7 7 a 9 7 7 8 9
c;:s! ~
C) Spacing 12 11 11 1/2 12 11 11 1/2 12 11 11 1/2 12 10 1/2 11 11 1/2 12 10 1/2 11 11 1/2 12 10 1/2 11 11 1/2
- or
~m 1l "b,. Length "b" 38-7 38-9 39-3 38-7 38-9 39-5 3a-11 39-1 39-7 39-3 39-6 40-2 40-10 39-3 39-6 40-2 41 39-7 39-10 40-8 41-6
"'~ Length "b1 • 38-3 38-7 39-2 38-3 38-9 39-5 38-7 39-1 39-7 39 39-6 40-2 40-10 39 39-6 40-2 41 39-4 39-10 40-9 41-6
0z
:I> CCI c:::
"' Size Bar# 6 7 a 6 7 a 6 7 a 6 7 8 9 6 7 a 9 6 7 8 9
-o :1> -~ "c"
r- .E - Spacing 12 11 11 1/2 12 11 11 1/2 12 11 11 1/2 12 10 1/2 11 11 1/2 12 10 1/2 11 11 1/2 12 10 1/2 11 11 1/2
~>< .!;; Length 25 25 25-1 25 25 25-2 25-2 25-2 25-3 25-4 25-4 25-6 25-8 25-4 25-4 25-6 25-9 25-6 25-6 25-9 26
C/) CD

z(") -1 c:: "d" Dist Top Slab-Tot. No. 36 15 15 36 15 15 36 15 15 36 15 15 15 36 15 15 15 36 15 15 15


~ c: :1> Bars Bottom Slab-Tot. No. 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15
r- z .. e Size Bar# 4 4 6 4 4 6 4 4 6 4 6 7 8 5 7 a 8 6 7 9 9
-< c Bars Spacing 1a 7 11 1/2 12 5 3/4 11 1/2 12 5 1/2 9 10 10 1/2 11 11 1/2 12 10 1/2 11 6 1/2 12 9 11 9
m :1> Spacers Number 76 80 84 104 110 116
:a ;:ltl
c g Concrete: C.Y. per lin. ft. 2.60 3.1a I 3.82 2.10 I 3.26 3.9a 2.aa I 3.45 I 4.13 3.13 3.79 4.61 5.45 3.23 I 3.a9 4.72 5.65 3.62 I 4.2a I 5.24 6.18
..... 5 Reinf :lbs per lin. ft. 489 505 I 62a 497 I 516 637 505 I 527 I 654 536 5a2 719 a72 548 I 606 745 939 575 I 636 I 793 963
c
;:ltl
:1>
~ NOTE
z
C) For boxes of height less than that shown in table, use next greater
table height slabs, wall dimensions and reinforcing steel, and make
necessary changes in bar lengths, number of spacers and quantities.
Number of "d" bars in table is slab total for all cells.
For cover less than 2', extend c bars Provide paving notch when top is exposed and
full length, top slab only. Provide additional where PCC pavement or approach slab is used
#4 0 18" :1: and adjust quantities

TJ s TJ s
(#4 spacers @ 18" :1: ( b Bars a Bars c...........J

1..,.... t / -
~tl_--~~~====~~~='i~~~/==~b=~=_\~====~!~17~-
p- #4 - \ ' - c Bars -~1, 1-
r--
.....c:
.255 d Bars .255
3/4" fillets min 11 12"

I( H4
1

:Q, Dist bars "'-' Jt • J '----


"1;; spacers 0 18" :1: -.
....;: ,...~r4 0 18 :1: e Bars----. /I 6"

1 r=h-~..
c:
0
(..)
#4
~
.255 d Bars .255 ; -optional
Invert elev ~I canst joint
Dist Bars 1/4: 12
~ ~)
:.L.:

~t .L "\. / /
/ 4 spacers
c Bars_) b1 Bars w_} ® 4 spacers '-- a Bars C""""J

Reinf for interior walls under 8" 2" CLR- Reinf for interior walls 8" and over
lYPICAL SECTION

®For reinforcement clearance, except at bottom, see "Miscellaneous Details" on D-81A and D-81 B.

. "'~ .. !:>·· ..
~

..
· . .
.. ~
: l!to.,.., ..

FLAT INVERT ALTERNATIVE


{When specified)

NOTES
1. Spacers shall be #4 @ 18" oc in top slab and sidewall mats.
2. Remaining #4 Spacers shall be equally distributed in bottom slab mats.

Revision By Approved Date RECOMMENDED BY THE SAN DIEGO


SAN DIEGO REGIONAL STANDARD DRAWING RE~ COMMITTEE
ORIGINAL Kercheval 2/75
Add Metric T. Stanton 03/03 I.....__ _}!:f;Ftr,u<7~ 7(26(2012
Reviewed T. Stanton 04/06 TRIPLE BOX CULVERT Chairperson R.C.E. 19246 Date
Edited s.s T. Regello 03/11 DRAW1NG
DETAILS N0.2 NUMBER D-78G
GENERAL NOTES DESIGN NOTES
QUANTITIES: Quantities are for the sloped invert slab and do not SPECIFICATIONS
include splices in the longitudinal bars, nor temperature DESIGN: MSHTO's publication titled A Policy on Geomeric Design of
reinforcement for exposed top culvert, nor concrete or Highways, dated 1984, with revisions as supplemented by State of
reinforcement for parapets or cutoff walls. California Bridge Planning and Design Manual.

SPECIAL COVERAGE: Box standard plans are not to be used Sections designed for culvert in a trench on hard foundation or culvert
for culverts in a corrosive environment or where there is a severe untrenched on yielding foundation. Special design will be required for
abrasive flow condition. culverts on piles or rock foundations.

DESIGNATION: Show on plans as span x height-strength LOADING


classification x length (e.g. 4 x 4-A x 60' ), followed by LIVE LOAD: For legal highway loads, use HS20-44 or alternative with 30%
alternatives. impact for all cover depths with no impact on invert.

ALTERNATIVES: Invert will be sloped unless "Trapezoidal COVER LESS THAN 2': Wheel load distribution on the top slab is
Invert", "Flat Invert" or "V Invert" is included in designation. Ends E=0.175S+3.2' longitudinally and concentrated along the span. Wheel load
of culvert will be rounded unless "Square Ends" are designated. distribution on the invert slab is 7.5' longitudinally and uniformly over the
Parapets will be as shown unless "__ ft. parapet" is designated breadth of the culvert.
in plans. Such designations may be different for inlet and outlet
ends. COVER 2' OR MORE: Wheel loads distributed uniformly over a square,
the sides of which are 1. 75 times the depth of cover, but not less
REINFORCEMENT PLACEMENT: Main Reinforcement is longitudinally thanE on the top slab, or 7.5' on the invert slab when such
positioned transverse or, for curved culverts, radial. When radial, areas from several wheel concentrations overlap. The total load shall be
reinforcing spacing is measured along C/L. considered as uniformly distributed over the area defined by the outside
limits of the individual areas, but the overall longitudinal dimension shall
not exceed the total length of the supporting slab. Neglect live load, on
CONSTRUC~ON NOTES
single spans when cover is more than 8' and exceeds span, and on
CONCRETE: Bottom slab & walls shall be Class 560-B-3250. multiple spans when cover exceeds distance between exterior walls.
Top slab shall be Class 560-C-3250.
DEAD LOAD: Earth load of 120 pcf and an equivalent fluid pressure of 36
EXPANSION JOINTS: Bottom Slab- No expansion joints shall be pcf, reduced to 84 pcf and 25 pcf respectively for clear spans of 20' or less.
placed.
Top Slab and Walls- When cover is less than span length, place UNIT STRESSES: Fs = 20,000 psi, N = 10
1/2" expansion joint filler at 50'± centers outside the paved Fe = 1,200 psi
roadway lanes and place weakened plane joints per Detail A of
Weakened Planes Detail 3-2 of C-15 at 30'± centers under paved Reinforcement embedment is 1-1/2 dia. clear, min 1" and in 1/4"
roadway lanes. When cover depth is greater than span length, increments, except as noted.
place 1/2" expansion joint filler at 30'± centers and additional 1/2"
expansion joints at locations of change of foundation character as Distribution "d" bars expressed as a percent of main positive reinforcement.
directed by the Engineer.
Classification "A" top slab=~· max. 50% (unless traffic longitudinaO
CONSTRUCTION LOADS: Not permitted until concrete has
reached a strength of 3,000 p.s.i. or age of 28 days, whichever Classification "B" to "E": Top and bottom slabs #4@ 18" max.
occurs first, and falsework plans have been submitted by the
Contractor to the Engineer and approved. USE OF STANDARD DRAWING
"Strength Classification," as symbolized by the letters ("A", "B", "C" or
CONSTRUCTION JOINTS: Temporary joints may be permitted if
normal (or radiaO to C/L of RCB. Otherwise, the Contractor is "D'' at the top of the data table is merely a convenient designation for a
particular structural section for a culvert of any given opening. It is
to submit a proposal for consideration.
dictated by the cover or depth of fill over the the top slab.

Joint may be formed with 1/B"


LIVE LOAD c!c R.C.B. DIREC~ONAL TERMINOLOGY

II'LE
hardboard and cut back ta the root af
, / the cha_.mfer an the exposed face.

1-1/2" " 1 C/L RCB__j


nLongitudinal
l -
Transverse
~
J
Breadth
3/1," chamfe;lj [ 1/B"
~~==-=~~~~=-==~===~=u

DETAIL A OF WEAKENED PLANES DETAIL 3-2


(Portion of Standard Drawing C-15) ....
Lateral
....:;.::.---

Revision By Approved Date RECOMMENDED BY THE SAN DIEGO


SAN DIEGO REGIONAL STANDARD DRAWING RE~ COMMITTEE
ORIGINAL Kercheval 2/75
Add Metric T. Stanton 03/03 I' jf:fJtr,uA7;::,) 7(26(2012
Reviewed T. Stanton 04/06 BOX CULVERT Chairperson R.C.E. 19246 Date
Edited s.s. T. Regello 03/11 DRAW1NG
MISCELLANEOUS DETAILS No. 1 NUMBER D-81A
~~:: '"~1. "d" b:~.:~ ;' \ I
® t--
1"CLR---l-llll
~~.r--#4 bars t Culve·rtri'_A'\-d=fi:l\-=r=FFA=r=F=r_ _
f / .J'-""' ® h (inches)=Span (feet), 6" min \1. ~ r- t-- Main reinforcement
#4 hoops@12"....:.,...--} '\._
_J -----...: __ "f" Bars, 3 total _\~ttt±±:::I-
R=T3
PART PLAN-SKEWED
PART SECTION
PARAPET DETAILS FOR SINGLE SPAN CULVERTS 4' #4 #4 #4
6' #4 #4 #5
8' #4 /15 #6
10' #5 /16 #7
,Length of Culvert, .. 12' #6 117 #8
#7 #8 #9
l 1"CLR d . 1---12"
1-+ "f" Bars I I
Skew ----;(t-~ R=T
T- 14'

®h ~total Note: .\LS:


,4 h .. • foe
oops " 12 :__}
/1tF
U Interior wa111
(treat extenor
Hook reinfobrcement""'~=~~-
same as a ove ,\)(
'\)
~

'\ \ r---t Interior Wall


R=T walls as above)
3
PART SECTION PART PLAN-SKEWED
PARAPET DETAILS FOR MULTIPLE SPAN CULVERTS

to of p<rape1
Eodface of parapeto~ - -R.C.
------------
- 9
PARAPET DETAIL FOR SKEWED CULVERTS W/0 WINGWALLS

Cover slab
Place an expansion:\
_2' .2' #408" max joint per G-1 0 a mi~ir_n~m
Remove parapet~ r6" 2S or 2H from JOining
and hoops flush _1 h" Optional extension ~
___Ll.~/2" exp jt filler, secured with ~~~~ ~---~~,.......,').
L
Existing construction \
-
7
8d nails @ 18" max roof &: walls
New const ruet'1on Existing construction~
........._
~
...ii
1
.
New cpnstrucbon
1
~~=t~==~s ~~~ ').
-J 1-
12"
Remove and splice to existing
longitudinal rebar in invert
_J

1- Remove and splice to existing
longitudinal rebar in all members
12
COVER: 1' AND GREATER COVER: EXPOSED TOP AND LESS THAN 1'
CULVERT EXTENSION
20' SKEW MAXIMUM
Revision By Approved Date RECOMMENDED BY THE SAN DIEGO
SAN DIEGO REGIONAL STANDARD DRAWING RE~ COMMITTEE
ORIGINAL Kercheval 2/75
r===~~~==~~~----------------------------------~~,~~7~
Add Metric T. Stanton 03/03
~~ao~
Reviewed T. Stanton 04/06 BOX CULVERT
Chairperson R.C.E. 19246 Date
Edited s.s. T. Regello 03/11 DRAW1NGMISCELLANEOUS DETAILS NO. 2 NUMBER D-818
3• steel posts\ Ground line

Backfill to natural 5' max


ground after fence
installation

Len h and ost la out shown on Ions

ELEVATION

Stream flow

..
C,
~

560-C-3250 concret~
/ I •
2' min.

1L3•
See D-40 for rip rap size ann----'
length to be shown on plans.

SECTION
NOTES
1. Fence fabric shall be r
mesh, 9 gage galvanized steel wire,
placed on the upstream side of the posts and tension cables.
2. Tension cable shall be 5/16" dia. steel ot 18" OC, secured ot ends with
cable clamps. Secure fence to cable with 12 gage galvanized steel wire
looped at 6" OC.
3. Posts shall be 3" steel pipe, 5.79 lb/ft. Fill with mortar after placing.
4. Fence fabric shall be secured to posts with 9 gage wire clips at 9" OC.
LEGEND ON PLANS
0 11 0 • 0 11 ouo

Revision RECOMMENDED BY THE SAN DIEGO


REGIONAL STANDARDS COMMITI'EE
SAN DIEGO REGIONAL STANDARD DRAWING
ORIGINAL 0 82
Add Metric T. Stanton 03/03 7(26(2012

Reviewed T. Stanton 04/06


DEBRIS FENCE
Edited .s. T. Regello 03/11 DRA'MNG
NUMBER D-82
FOR DRAWING D-40, SEE DRAWING SDD-104
CHAPTER 3
ELECTRICAL
SYSTEM
ARM LENGTH 8'MAX.FOR CONCRETE OR FI BERGLASS,
12'FOR TYPE 15 UNLESS NOTED OTHERW I
SE.

C LUMI
NAI
RE
C
C C

C
POLE TOP
POLE TOP

C
C
C

FOR 10500 TO 22500L - 33' + 1' (CALTRANS TYPE 15)


C

EDGE OF PAVEMENT
C

MAST ARM
LI
GHT STANDARD,
TYPE 15 SHALL BE
STEEL,OTHER MAY
BE CONCRETE OR

FOR 7500 TO 9500L - 27' + 1'


MOUNTING HEIGHT
LI
GHT STANDARD,
FI
BERGLASS.
C CONCRETE OR
FI
BERGLASS. C

C
FOR 7500 TO 9500L- 25' + 2'

C
MI
N.1'OVERHANG C
POLE HEIGHT

C 15" C 18" CORE 5" DI


A.
C C 12" HI
GH MIN

HAND HOLE TO FACE STREET

C
C C
SLOPE 30:
1 C

C
FI
NISH GRADE
C

C
C
C
C 4"

7"
C

C
UNDI
STURBED EARTH

4'-6"
5'

SELECT SAND,95%
MINI
MUM RELATI VE
COMPACTION
C

C
560-C-3250 PCC ANCHOR BASE
C 18" SQUARE OR ROUND,ADD 1'TO EACH
C DIMENSION FOR LOOSE SOIL OR SOFT C 2'
-6"
C
CLAY CONDI TI
ONS.

DI
RECT BURI
AL FOUNDATI
ON
ANCHOR BASE FOUNDATI
ON

ANCHOR BOLTS ( 4 REQ.)1"x 36"x 4" HOOK,


GALV.USE TW O LEVELING NUTS W I TH
1/
4" MI
NIMUM
W ASHERS (
ALL GALV.)ON EACH BOLT.
BOLT CLEARANCE
3-1/ 4"
3"

FI
NISHED GRADE FOR
CONCRETE POLE
C
C

C
C

FI
NISHED GRADE FOR STEEL
C
7"

AND FIBERGLASS STANDARDS.


C

PROVIDE ANCHOR BOLT NUT


C

COVERS.
C
C

RECOMMENDED BY THE CI
TY OF SAN DI
EGO
REVI
SION BY APPROVED DATE
STANDARDS COMMITTEE
CI
TY OF SAN DI
EGO - STANDARD DRAW I
NG
ORI
GINAL J.CASEY 06/
83

2/
25/
16
UPDATED KA J.NAGELVOORT 01/
12
COORDI
NATOR R.
C.E.56523 DATE
UPDATED KA J.NAGELVOORT 02/
16
STREET LI
GHTI
NG STANDARD DRAW I
NG
SDE-
101
NUMBER
24"

VENT HOOD DOOR OPENING


32'x 22'

170 CONTROLLER

POWER DISTR.
ASSY . D
M
0 u T p UT 0
N
I
T
F ILE 0
R
' '
0 ', INPUT FILE
'
' '
\...... 0' ------------ ---- - 1
\...... \......
\......\..._.\......
1<"
I
'J------------~-~~
~~\......
\......~
\......
BASE ADAPTER a·
VENT OPENINGS
WITH FILTER,
BOTH SIDES. 23 V4"

11 SIS"
19 318"
S!
~
~
"' ts·
~ ~
S!
"'
4 112" NUTS WELDED
TO ADAPTER

1' UP lYPICAL
TOP UP SHADED

BASE ADAPTOR PLAN VIEW

REVISION BY APPROVED DAlE RECOMMENDED BY THE CITY OF SAN DIEGO


STANDARDS COMMITTEE
CllY OF SAN DIEGO - STANDARD DRAWING
ORIGINAL KA . NAGELVOO OV12
oil~ 1/31/2012
COORDINATOR R.C.E. 65271 DAlE

MODEL 336 CABINET DRAWING


NUMBER
SDE-102
ROUND HEAD SCREW AND NUT
SCREW HEAD FACING SIDEWALK

s·-o· CAP WITH SET SCREW

1' x 1 'V4" GALV STEEL CHAIN

NO PED CROSSING
~~-usE CROSSWALK
ATTACH WITH
42" ROUND HEAD SCREW AND
42" NYLOCK NUT OR WELD

1 3'4" SQUARE SIGNPOST

RIVET
(TOTAL (2) 90°APART)
24"

2" SQ.x24" LONG SIGNPOST ANCHOR INSIDE


A 2 1/4" SQ.x18" LONG SIGNPOST BASE
(TYPICAL)

NOTES:

1. POSTS TO BE SET 1'-6" BEHIND FACE OF CURB


UNLESS OTHERWISE SPECIFIED.

2. IN EXISTING SIDEWALK AREA SET POSTS INTO


4" CORE BORING, PACK WITH GROUT.

3. R49 SIGNS ON ALUMINUM SHEETING CENTERED


BETWEEN POSTS.

REVISION BY APPROVED DATE RECOMMENDED BY THE Ct1Y OF SAN DIEGO


STANDARDS COMMITTEE
CllY OF SAN DIEGO - STANDARD DRAWING
oil~
ORJGINAL J . CASEY 0696
1/31/2012
UPDATED KA . NAGELVOOR OV12
COORDINATOR R.C.E. 65271 DATE

PEDESTRIAN BARRICADE DRAWING


NUMBER
SDE-103
PLAN DRAW I
NG SYMBOL

C
16
"
C

24
"
C

C C

C
DI
RECTI
ON
OF TRAVEL
S
C

N
R

C
TU
4

C C
S
E
C

IR

C
W

C
F

ROUND CORNERS
O

C
TO REDUCE W EAR
OF LOOP W I
RES C
C

C C

NOTES:

1. LOOP DI
AMETER = 6'TYP

2. DEPTH OF CUT = 3 1/
8" MI
N SAW CUT & W I
NDI
NG DETAI
L

3. NO LOOPS SHALL BE CUT I


NTO BRI
DGE
DECKS

MODI
FIED TYPE E LI
MIT LI
NE /CROSSW ALK DETECTOR

SHEET 1OF 2

RECOMMENDED BY THE CI
TY OF SAN DI
EGO
REVI
SION BY APPROVED DATE
STANDARDS COMMITTEE
CI
TY OF SAN DI
EGO - STANDARD DRAW I
NG
ORI
GINAL KA J.NAGELVOORT 01/
12

2/
25/
16
UPDATE KA J.NAGELVOORT 02/
16
COORDI
NATOR R.
C.E.56523 DATE

TYPE E M ODI
FIED LOOP DRAW I
NG
SDE-
104
NUMBER
W HI
TE CROSSW ALK

NOTES:
W HEN B<
- 12
1. ALL FRONT LOOPS SHALL BE MODI
FIED A C
C
TYPE "E" LOOPS 2 W HEN C>
- 12
B C
C
2
2. FRONT LOOPS,SHALL BE I
NSTALLED C
I
N FRONT OF THE LI
MIT LI
NE OR C C 6'
CROSSW ALK ACTI
NG AS A LI
MIT LI
NE
C C
A C C
B C C

CASE "1"

YELLOW CROSSW ALK


C

3'
C W HI
TE LI
MIT
LI
NE
C

W HEN B<
- 12
A C
C
2
C W HEN C>
- 12
C 6'

C C
A C C C

CASE "2"

FRONT LOOP REPLACEMENT

SHEET 2 OF 2

RECOMMENDED BY THE CI
TY OF SAN DI
EGO
REVI
SION BY APPROVED DATE
STANDARDS COMMITTEE
CI
TY OF SAN DI
EGO - STANDARD DRAW I
NG
ORI
GINAL KA J.NAGELVOORT 01/
12

2/
25/
16
UPDATE KA J.NAGELVOORT 02/
16
COORDI
NATOR R.
C.E.56523 DATE

TYPE E M ODI
FIED LOOP DRAW I
NG

NUMBER
SDE-
104
wire
to pole steel #B copper wire
grounded to pole
steel with lug.

STEEL CONDUIT NON-METALUC CONDUIT

DIRECT BURIAL FOUNDATION

Attach ground wire


under anchor nut.

See Detail A 1/2" Rigid


Conduit

STEEL CONDUIT NON-METALUC CONDUIT


ANCHOR BASE FOUNDATION

CD 3/ 4" x 8' copper covered steel ground rod. Steel Conduit Anchor Rods

0 Alternate Ground: 15' no. 4 stranded copper


wire, coiled.

0 Approved non-metallic conduit.

8 Steel conduit.
DETAIL A

Revision By Approved Date RECOMMENDED BY THE SAN DIEGO


SAN DIEGO REGIONAL STANDARD DRAWING REGIONAL STANDARDS COMMITTEE
ORIGINAL Kercheval 12 7
Add Metric T. Stanton 03/03
Reformatted T. Stanton 04/06 GROUNDING Ch
Delete Metric D. Gerschoffe 06/12
OF CONCRETE LIGHTING STANDARDS DRAW1NG
NUMBER E-2
1 1/2"min. cover ~8
for bars and --~
conduits

Galvanized steel
conduits. Size and 1" galvanized steel
number as required. conduit for service ground
(where required). /Pone I Boord
PLAN
1/4" X 2"
galvanized steel ----..
bars. !r--JMeter
0 Grout cap L{
10" Diameter,
protrusion I .J ------,-
to be 1 1
use Sonotube
for smooth o o
slo~ed for~ _j_
dramage. '
finish (Class 1~

~ c
.E e•
•«>•
I '7
":.t<o

Permissable to
auger hole and c
pour against soil. ·E


«> ""'"
N
I"')

1-----3/4" X 8"
16" dia.
copper covered
steel ground rod.
SECTION A-A SECTION 8-8
STEEL & CONCRETE CONDUIT & EQUIPMENT
DIMENSIONS

NOTE: Concrete shall be class 560-C-3250

Revision By Approved Date RECOMMENDED BY THE SAN DIEGO


SAN DIEGO REGIONAL STANDARD DRAWING REGIONAL STANDARDS COMMITTEE
ORIGINAL Kercheval 12 7
Add Metric T. Stanton 03/03
Reviewed T. Stanton 04/06 PEDESTAL FOR Ch
06/12 DRAW1NG
Delete Metric D. Gerschoffe
ELECTRICAL EQUIPMENT NUMBER E-3
CHAPTER 4
GENERAL
SURFACE
IMPROVEMENTS
- A

.. ~ .. , , ' .... ,
• : .. · . : 1. . . . \ : · . : .. · . : •.. • .....
., : .. ·.: ......
.". : • : .. ·. : ~ •.. :..: #·.: ..·. : ·. •• \
CfJ
z
cn:'S
<(0. ~
:::>
z ~
IO z
I-
oz :a
-~
~0 ~
I
... CfJ

~A

LENGTH SHOWN ON PLANS

75' MINIMUM I 100' MAXIMUM

12' MINIMUM

9"
• .
. ·. :.·. : ·• • ••
: . : .
:.··.·~.--
•. ~~ • ~~.~~~ : :. •• • • : :.: : : . •.... ~ 560-C-3250 CONCRETE
: . · · . · •• • • • • ••• • • • •• CfJ
· . . ·. · . . .·.·1 - z
• .ll. : ... :. • • • • • • .ll. • • • • • • .ll • • : • • • • • •• ..; : < :5
•• • .ll. •. . . . 4 • . .11. · ••• · . ·:
. ' .ll: • •• • • • .ll·.
• •• •• • • • zocn<(a.
t
• •• A • •• • •

.· .. - .......... · .. · ...... d.· . ·. · ' ..... : .... . ··.·,' <C__.z


: • '.11 :,-• . .'.11·.'.-'.'.·
• •.ll
. •._;.·::.
'.ll'. • •
·..ll:

.{!·::

..~:.:·~.··>
• •• • . .....
I$a:o
. . 4 ······.·: •. ·· .• · •.. · . . •.·• . •·: ..11·._·:.· · .
: ..11···. • · • • • • • • • 4 • 'A' •.11 · · • · • twz
w!:;(~
~ • . •• . .•••. .

• •. • • • • • • •• ••· ,4.1, • ...
' . · + •·••
.. . .•. .
• • , •• •• ·.;
~ • • ' ·•
. o1.;;::
~
• .ll ' .' ' ,' 4 .' ' • • • • ' · • ' ' .' ' . , a ' • ' • .ll • • ' •' ' 4 • , 0
I
• • • • • • • • • • • • •• ••••••• ~ :· • • • : • • • • ••• • • • • • • ._ CfJ

SECTION A-A

NOTE

1. BROOM FINISH PARALLEL WITH TRAFFIC.

REVISION BY APPROVED DATE RECOMMENDED BY THE Ct1Y OF SAN DIEGO


STANDARDS COMMITTEE
CllY OF SAN DIEGO - STANDARD DRAWING
oil~
ORJGINAL G. PARKINSON 0580
1/31/2012
REVISION J.CASEY 06e3
COORDINATOR R.C.E. 65271 DATE
DRAWNING LC A.OSKOUI 0694
BUS STOP SLAB DRAWING
MAX GP F. BELOCK 4o96
NUMBER
SDG-102
UPDATED I<A ~· NAGELVOOR' OV12
~MILL EXISTING
PAVEMENT
~
I w
z ~
r-1 le' BELOW UP I ::::; w
0..
ow
OF GUTIER I co
a: a:Z

~
::> O..::::i
()

I I

\ I
-t---J~~-------.--...
~EXISTING CURB
& GUTIER
1----6'--{)" - 1---6'--{)" -

PAVING
GRINDING & PREPARATION

TYPICAL SECTION

EX CONC
CURB ~------------------ 6'--{)"-----------------~

~~ \~==========~~===M=IL=L=~=.M~V~ING==========::::::::==========~~
-r- fL-------------------------~--ISTI_N_G__M_V-IN-G~
TAPER AT END

~.CONC.

GumR\
CURB &
6'--{)"

rMILLEXPAWIG

~L_---------------------EX1-S_TI_N_G_P_A-~-N-G~

TAPER AT END
TYPICAL PAVEMENT COLD MIWNG

REVISION BY APPROVED DATE RECOMMENDED BY THE Ct1Y OF SAN DIEGO


STANDARDS COMMITTEE
CITY OF SAN DIEGO - STANDARD DRAWING
ORIGINAL KA J. NAGa VooRT OV12
oil~ 1/31/2012
COORDINATOR R.C.E. 65271 DATE
COLD MILLING ASPHALT
DRAWING
CONCRETE PAVEMENT DETAIL NUMBER
SDG-106
MILL AND PAVE RESURFACE MILL AND PAVE RESURFACE
3/
4" TYPE I
IICLASS B3 FLUSH FLUSH TO MATCH EXI STI
NG 3/
4" TYPE II
ICLASS B3 FLUSH FLUSH TO MATCH EXI STI
NG
TO MATCH EXI STI
NG SURFACE, OR OVERLAY PER NOTE 2 TO MATCH EXI STI
NG SURFACE OR OVERLAY PER NOTE 2
SEE TABLE FOR DEPTH OF PLUS 1" BELOW EXI STI
NG,SEE
ASPHALT TABLE FOR DEPTH OF ASPHALT EXI
STI
NG A.
C.PAVEMENT

EXI
STI
NG BASE OR OLD
EXI
STI
NG A.
C.PAVEMENT
CONCRETE PAVEMENT
C C
6" TYPI
CAL C 6" TYPI
CAL C
C

C
C

C
1 1/2"

1 1/2"
C

C
C
C

C
C

C
C

C
C

C
C

C
C
TACK EDGES EXI
STI
NG BASE OR OLD
WITH ASPHALTI
C CONCRETE PAVEMENT TACK EDGES
EMULSION WITH ASPHALTI
C
COMBINE ASPHALT
EMULSION
PLUS BASE 18" MI
N

CLASS I
IBASE

TYPE 1 TYPE 2

TYPE 1 TYPE 2

ASPHALT ASPHALT PLUS BASE


MI
X DESI
GN 3/
4" TYPE I
IICLASS B3 3/
4" TYPE I
IICLASS B3 PLUS CLASS I
IBASE
ALLEYS 8.
0" ASPHALT THI
CKNESS TO EQUAL

LOCAL THROUGH 4 LANE COLLECTORS 10.


0" EXI
STI
NG PLUS 1",MI
N 4" TO MAX.9".
MAJOR 12.
0" COMBI
NED ASPHALT PLUS BASE 18" MI
N.

NOTES:

1. ANY STREET TRENCH 7 FEET I


N WIDTH OR GREATER AND LONGER THAN 100 FEET I
N
OVERALL LENGTH SHALL BE RECONSTRUCTED W I
TH THE PAVEMENT SECTI
ON FOR THE
STREET CLASSI
FICATI
ON PER SCHEDULE "J" (
SDG-113)
.

2. ASPHALT TRENCH CAPS I


N STREETS NOT RECEIVI
NG A FULL W I
DTH OVERLAY PRI OR TO
ACCEPTANCE SHALL BE MILLED AS SHOW N AND RESURFACED W I
TH 1/2" TYPE I
IICLASS C2
ASPHALT NO LESS THAN 30 CALENDAR DAYS AFTER I
NITI
AL ASPHALT PLACEMENT.

3. W HEN DI
RECTED BY CI
TY ENGINEER OR SHOW N ON THE PLANS,CONCRETE PER SDG-108
(
NOTE #5)MAY BE PLACED;A 1/
8" - 1/
4" W EARI
NG SURFACI
NG OF TYPE I
IICLASS F ASPHALT
CONCRETE W I
LL BE REQUI
RED.

RECOMMENDED BY THE CI
TY OF SAN DI
EGO
REVI
SION BY APPROVED DATE
STANDARDS COMMITTEE
CI
TY OF SAN DI
EGO - STANDARD DRAW I
NG
ORI
GINAL J.
P.CASEY 1/
24/
89

UPDATED KA J.NAGELVOORT 01/


12
2/
19/
16
COORDI
NATOR R.
C.E.56523 DATE
UPDATED KA J.NAGELVOORT 4/
13
TRENCH RESURFACI
NG FOR ASPHALT
UPDATED BB J.NAGELVOORT 1/
14 DRAW I
NG
CONCRETE SURFACED STREETS SDG-
107
NUMBER
UPDATED LS J.NAGELVOORT 02/
16
560--C-3250
CONCRETE

---,--,-(-S-.EErr-N--.-O~T-E--.-6~)~-----'----.,....,-------,-.,-----.---.~.,----,......,--~/- EXISTING CONCRETE PAVEMENT


l>.
. ··.
~~o"·

EXISTING COLD JOINT,


EDGE OF GUTIER OR SUBGRADE 95% RELATIVE COMPACTION
CONTRETE TRENCH
CUT PATCH

0
NOTES

1. EXISTING CONCRETE PAVEMENT SHALL BE REMOVED. CONCRETE PAVEMENT


RESTORATION SHALL EXTEND TO THE FULL WIDTH OF THE CONCRETE PANEL (BETWEEN
COLD JOINTS OR COLD JOINT TO EDGE OF GUTIER) AROUND THE PERIMETER OF THE
EXCAVATION. FOR CONCRETE PAVEMENT WITH EXISTING TRENCH CUT PATCHING,
CONCRETE PAVEMENT RESTORATION SHALL INCLUDE, AS PART OF THE RESTORATION,
THE EXISTING TRENCH CUT PATCHES IF THOSE PATCHES ARE WITHIN 4 FEET OF THE
CONCRETE PANEL TO BE REPLACED.

2. PRIOR TO PLACING CONCRETE, PAVEMENT EDGES SHALL BE TRIMMED TO NEAT


HORIZONTAL AND VERTICAL LINES.

3. UNLESS OTHERWISE SPECIFIED, CONCRETE TRENCH COVER SHALL BE A MINIMUM


OF 5 V2" FOR ALLEYS, 7" FOR LOCAL THROUGH FOUR LANE
COLLECTOR STREETS AND 9" THICK FOR ALL MAJOR OR GREATER STREET
CLASSIFICATIONS.

4. ANY STREET TRENCH 7 FEET IN WIDTH OR GREATER AND LONGER THAN 100 FEET IN LENGTH
SHALL BE RECONSTRUCTED WITH THE PAVEMENT SECTION FOR THE STREET
CLASSIFICATION PER SCHEDULE "J" (SDG-113). STREET TRENCH SECTIONS 7 FEET IN WIDTH
OR GREATER BUT LESS THAN 100 FEET IN OVERALL LENGTH SHALL BE RESURFACED TO A
THICKNESS OF 1" GREATER THAN REQUIRED BY NOTE 3 ABOVE.

5. 560--C-3250 CONCRETE TREATED WITH A MINIMUM 2% CALCIUM CHLORIDE SOLUTION IN


ACCORDANCE WITH 201-1 OR 650--CW-4000 fYV;O CC) CONCRETE MAY BE OPENED TO
TRAFFIC 3 DAYS AFTER IT IS PLACED. 650--CW-4000 CONCRETE TREATED IN SAME MANNER
(WCC) MAY BE OPENED TO TRAFFIC 24 HOURS AFTER IT IS PLACED. CONCRETE SPECIFIED
BY ALTERNATE CLASS OR OTHERWISE CONTAINING FLY ASH IS NOT ALLOWED.

6 IN FOUR-LANE MAJOR OR GREATER STREETS, AN APPROVED SET ACCELERATING


ADMIXTURE SUCH AS CALCIUM CHLORIDE, SHALL BE USED IN THE CONCRETE.

REVISION BY APPROVED DATE


CITY OF SAN DIEGO - STANDARD DRAWING
ORIGINAL J.CASEY OV89
3123115
UPDATED KA . NAGELVOOR OV12
DATE
UPDATED BB . NAGELVOOR OV14 TRENCH RESURFACING FOR PCC
DRAWING
UPDATED BB . NAGELVOOR 03115
SURFACED STREETS NUMBER
SDG-108
PCR

MI
D POI
NT OF CURB RETURN

c
B
C
R= B

c
C

=A

C
US
DI
RA
LK 5'
A C
C
W
TYP
F
O

A
K
BAC

C
C

PCR C A
C

NOTES
1. EXPANSI
ON JOINTS PER G-10 AT CURB RETURNS,ADJACENT TO STRUCTURES AND AT 45'
I
NTERVALS,SEE G-10.

2. W EAKENDED PLANE JOI


NTS AT MID POI
NT OF CURB RETURN,W HEN REQUI
RED,AND AT
15'I
NTERVALS FROM PCR'S ABSENT A CURB RAMP,SEE G-10.

3. TOOLED JOI
NTS 1/
4" GROOVES W I
TH 1/
4" RADI
US EDGES AT 5'I
NTERVALS.

4. FOR DESI
GNATED URBANI
ZED COMMUNITI
ES,SI
DEW ALK SCORI
NG (GROOVES)PATTERN SHALL
BE I
N CONFORMANCE W I
TH HI
STORI
C DESIGN ON ADJACENT PROPERTI
ES.

RECOMMENDED BY THE CI
TY OF SAN DI
EGO
REVI
SION BY APPROVED DATE
STANDARDS COMMITTEE
CI
TY OF SAN DI
EGO - STANDARD DRAW I
NG
ORI
GINAL* KA J.NAGELVOORT 01/
12

UPDATED RB J.NAGELVOORT 10/


15
2/
25/
16
COORDI
NATOR R.
C.E.56523 DATE
UPDATED HM J.NAGELVOORT 02/
16

SI
DEW ALK JOI
NT LOCATI
ONS DRAW I
NG
SDG-
109
NUMBER
6'MAXIMUM

4.5'
TOP OF
- 0.5'

---------~~~~~-C~UR~B~~/1.1.
55
2% NORMAL
CROWN
%%1 ~ -
=- - 1= ~
2 % NORMAL CROWN
I 9.4%-..~ ~

~
6' MAXIMUM

4.22'
- 0.5'
1.5%-
2
- % NORMAL
(o -
CRO'"N
•• ---------- 6.75 % <D ('I)

0 ~
- --I-'-
I 13.3%
LIP OF GUTTER

GUTIER

GUTIER TRANSITION
<t GUTIER TRANSITION
10' I 10'
I
I
TOP OF CURB ' I
I
I
0
I ll)

I (o 0
Co? <D
CXl
0
I 0
I

- -- --
I - - L
I
.....__

--
I
GUTIERJ
- - 1- _L.
I
_L
INLET WIDTH
~
--
SHOWN ON
PLANS

ELEVATION

G CURB PROFILE - INLET TRANSITION

SHEET 1 OF 2

REVISION BY APPROVED DATE RECOMMENDED BY THE Ct1Y OF SAN DIEGO


STANDARDS COMMITTEE
CllY OF SAN DIEGO - STANDARD DRAWING
oil~
ORJGINAL J . CASEY 1168
1/31/2012
UPDATED KA J. NAGELVOOR OV12
COORDINATOR R.C.E. 65271 DATE
INLET TRANSITION
DRAWING
PROFILE NUMBER
SDG-110
6'MAXIMUM

4.0'

2 % NORMAL CROWN

6' MAXIMUM

4.06'

i.o
r-..
1.5% ~ -
2 % NORMAL CROWN
Ct>
--- - - f-'-<X!
0

0
UP OF GUTTER

GUTTER
INLET

GUTTER TRANSITION
<t GUTTER TRANSITION
10' 10'

TOP OF CURB'

0
ll)
0
Ct>
~IP GUTIE~
CXl

- -- ---
- - '-- OF 0
- L-

.....__

GUTTER_/'"
- - -I- _ L _L.-
INLET WIDTH
~ - f- - -
SHOWN ON
PLANS

ELEVATION

H CURB PROFILE - INLET TRANSITION

SHEET 2 OF 2

REVISION BY APPROVED DATE RECOMMENDED BY THE Ct1Y OF SAN DIEGO


STANDARDS COMMITTEE
CllY OF SAN DIEGO - STANDARD DRAWING
oil~
ORJGINAL J . CASEY 1168
1/31/2012
UPDATED KA ~. NAGELVOOR" OV12
COORDINATOR R.C.E. 65271 DATE
INLET TRANSITION
DRAWING
PROFILE NUMBER
SDG-110
C 4'MI
N
C
14'TYP (
24'FOR DUAL LEFT TURNS)

COLORED
C 1.
5% 1.
5%
STAMPED 4" PCC

C
C

12" NATI
VE
95% COMPACTI ON

C
TYPI
CAL SECTI
ON
TYPE '
B-2'CURB
RAI
SED PAVED MEDIAN
TYPE '
B-2'CURB

LOCATI
ON OF STREET
TREES W HEN PERMI
TTED

C
7'MI
N 7'MI
N

C
C C
C C

LANDSCAPI
NG
2'MI
N 2'MI
N
C C VARI
ES 4'MIN. C
C C C
6" MI
N TO 9" MAX

1.
5% MEDI
AN DRAI
N
C 1.
5%

C
C
I
NVERT

C
C

C
2" MAX
C

C
C

C
C

TYPE '
B-2'CURB COLORED STAMPED 6" PCC TYPE '
B-2'CURB
MAI
NTENANCE ACCESS SECTION

TYPI
CAL SECTI
ON
LANDSCAPED MEDIAN

CONCRETE BARRIER TYPE 50.


END ATTENUATI
ON
C
AS SHOW N ON PLANS

C 6'TYP C 6'TYP
C C

TRAVEL LANE
TRAVEL LANE

18" SLOTTED CMPC C

WITH 6" HIGH SLOT


W HERE REQUIRED FOR
DRAI NAGE,SEE
SHEET 2 OF 2 TYPI
CAL SECTI
ON
CONCRETE BARRIER

NOTES:

1.CONCRETE SHALL BE 520-C-2500.

2.COLOR & PATTERN OF COLORED STAMPED CONCRETE SHALL BE SHOW N ON PLANS.

3.CONCRETE COLOR SHALL BE I


NTEGRATED THROUGHOUT.

4.SEE SDG-109 AND G-10 FOR JOI


NT DETAI
LS. SHEET 1OF 2

RECOMMENDED BY THE CI
TY OF SAN DI
EGO
REVI
SION BY APPROVED DATE
STANDARDS COMMITTEE
CI
TY OF SAN DI
EGO - STANDARD DRAW I
NG
ORI
GINAL J.CASEY 11/
88

UPDATED KA J.NAGELVOORT 01/


12
2/
25/
16
COORDI
NATOR R.
C.E.56523 DATE
UPDATED HM J.NAGELVOORT 02/
16
RAI
SED CENTER M EDI
AN DRAW I
NG
SDG-
112
NUMBER
C
C

C
SIX 18" SLOTTED DRAI
N
18" 6" SLOT
(CMPC)LENGTH SHOW N
18" CMPC-14 GA
ON PLANS

C
TYPE "I
" CATCH BASI
N
C

o
10 MAX.W I
TH ELBOW
C 3'
C

DETAI
LED LOCATI
ON OF TYPE "I
"
CATCH BASI
N WITH GRATE PER D-29
CONCRETE BARRI
ER

TYPE G-4 GRATE


ANCHOR GRATE W ITH M-4 BOLTS PER D-15
GRATE FRAME. ALL GRATES SHALL SAW CUT
BE ANCHORED. 1.
5" C C
C
C

3'
STUB OUT
18" CMPC-14 GA
FROM CATCH
BASIN

TYPE "I
" CATCH BASI
N

C
L

TYPICAL FOR ALL


18" SLOTTED CMPC

0"-1" C
C
SAW CUT AC
SAW CUT AC FOR REMOVAL
C

FOR TRENCH EDGE


3"
C
C
C

C
C
EXISTING PAVEMENT

6"
C

C
LI
MIT OF
PCC BEDDING
C
C
C

18" SLOTTED CMPC-14 GA


C

WITH 6" HIGH SLOT


C

3"
C

PCC BEDDI
NG 420-C-2000

SHEET 2 OF 2

RECOMMENDED BY THE CI
TY OF SAN DI
EGO
REVI
SION BY APPROVED DATE
STANDARDS COMMITTEE
CI
TY OF SAN DI
EGO - STANDARD DRAW I
NG
ORI
GINAL J.CASEY 11/
88

UPDATED KA J.NAGELVOORT 01/


12
2/
25/
16
COORDI
NATOR R.
C.E.56523 DATE
UPDATED HM J.NAGELVOORT 02/
16
RAI
SED CENTER M EDI
AN DRAW I
NG
SDG-
112
NUMBER
SCHEDULE "J" PAVEMENT

THE FOLLOWING TABLES ARE TO BE USED TO DETERMINE THE SCHEDULE "J" PAVEMENT
DESIGN SECTIONS FOR STREETS, ALLEYS, PARKING LOTS FOR PUBLIC FACILITIES,
DRIVEWAYS, AND EASEMENTS, INCLUDING PUBLIC ACCESS EASEMENTS. THESE DESIGNS
SHALL BE USED IN THE PUBLIC RIGHT-OF-WAY, OR PRIVATE PROPERTY IN THE AREAS
WHERE PUBLIC EASEMENTS ARE GRANTED.

1. RESISTANCE VALUES (A-VALUES) WILL BE DETERMINED FROM SAMPLES TAKEN FROM


THE 12" MATERIAL LOCATED IMMEDIATELY BELOW THE FIRST LAYER OF
SUBBASE, BASE OR PAVEMENT. THIS 12" SECTION SHALL REPRESENT THE TOP
36 INCHES OF UNIFORM SOILS BELOW THE SUBBASE, OR PAVEMENT. IF A LOWER
BEARING SOIL IS ENCOUNTERED IN THIS 36" SECTION, THE A-VALUE WILL BE
DETERMINED FROM THE LOWEST BEARING SOIL. DETERMINATION OF THE A-VALUE
SHALL BE IN ACCORDANCE WITH CALTRANS TEST METHODS 301-F AND 301-G.

2. AVERAGE DAILY TRAFFIC (ADn IS THE MAXIMUM AVERAGE ANNUAL ADT EXPECTED
AT BUILDOUT. FUNCTION SHALL ALSO BE CONSIDERED WHEN DETERMINING THE
MINIMUM SCHEDULE "J" PAVEMENT SECTION PER THE ENGINEER.

3. RIGID PAVEMENTS: THE DESIGN THICKNESS SHOWN IN THE TABLES ARE BASED ON
A MODIFIED PORTLAND CEMENT ASSOCIATION (PCA) DESIGN. PROJECTS REQUIRING
CALTRANS REVIEW SHOULD UTILIZE THE DESIGN METHODS PRESCRIBED IN THE
CALTRANS HIGHWAY DESIGN MANUAL.

4. PORTLAND CEMENT CONCRETE (PCC) PAVEMENT SHALL BE CONSTRUCTED IN STREETS


ON GRADES GREATER THAN 12.0 PERCENT AND IN ALLEYS AND IN ALLEY
INTERSECTIONS. THE PAVEMENT SHALL BE CLASS 560--B-3250 CONCRETE WITH A
MINIMUM MODULES OF RUPTURE (MOR) OF 600.

5. NEW PAVEMENT, LESS THAN 6' IN WIDTH, SHALL BE PAVED WITH


PORTLAND CEMENT CONCRETE PAVEMENT SECTION NOTED IN SCHEDULE "J" FOR THE
STREET CLASSIFICATION PLUS A 118" TO V4" CLASS F ASPHALT CONCRETE CAP.
AN EQUIVALENT SECTION OF LEAN CONCRETE SHALL BE SUBSTITUTED FOR ANY
REQUIRED CTB SUBBASE.

6. PERSONNEL FROM THE CITY'S ENGINEERING LABORATORY WILL DESIGNATE WHERE A


PRIVATE LABORATORY SHALL SAMPLE FOR A-VALUES.

SHEET 1 OF 4

REVISION BY APPROVED DATE RECOMMENDED BY THE CITY OF SAN DIEGO


STANDARDS COMMITIEE
CITY OF SAN DIEGO - STANDARD DRAWING
ORIGINAL

NOTES
M.ROLLINGER

G. PARKINSON
0592

0295
dl~ 1/31/2012
COORDINATOR R.C.E. 65271 DATE
UPDATED KA ~· NAGELVOOR O'V12 PAVEMENT DESIGN STANDARDS
DRAWING
SCHEDULE ""J"" NUMBER
SDG-113
MAX STANDARD CONCRETE FULL
STREET MAX TRAFFIC "R" SECTIONS M.O.R. 600 MIN DEPTH
CLASSIFICATION ADT INDEX VALUE
A.C. (IN) CTB (IN) PCC (IN) CTB (IN) A.C. (IN)
CUL-DE-8AC 200 5.0 3.0 5.0 6.0 - 4.5

LOCAL (L.V.R.) 700 5.5 3.0 5.0 6.5 - 5.0

LOCAL (RES.) 1200 6.0 3.0 5.0 6.5 - 5.5

LOCAL (RES.) 2200 6.5 3.0 5.0 6.5 - 6.0

LOCAL (IND.) 2000 8.5 3.0 7.5 7.5 - 8.5

COLLECTOR (RES.) 3500 7.0 50.0 OR 3.0 5.0 7.0 - 6.5

COLLECTOR (RES.) 5000 7.5 GREATER 3.0 5.5 7.0 - 7.5

COLLECTOR (COMM.\IND.) 5000 9.5 3.0 8.5 7.5 - 9.0

COLLECTOR (NO FRT) 7500 8.0 3.0 6.5 7.0 - 8.0

COLLECTOR 15000 9.0 3.0 7.5 7.5 - 8.5

MAJOR (4-LANE) 30000 10.5 3.0 10.0 8.0 - 10.5

MAJOR (6-LANE) 40000 11.0 3.5 10.5 8.0 - 11.0

PRIMARY ARTERIAL 50000 11.5 3.5 11.5 8.0 - 11.5

EXPRESSWAY 60000 12.0 3.5 11.5 8.5 - 12.0

EXPRESSWAY 80000 12.5 4.0 12.0 8.5 - 12.5

EXPRESSWAY 100000 13.0 4.0 12.5 9.0 - 13.0

MAX STANDARD CONCRETE FULL


STREET MAX TRAFFIC "R"
SECTIONS M.O.R. 600 MIN DEPTH
CLASSIFICATION ADT INDEX VALUE
A.C. (IN) CTB (IN) PCC (IN) CTB (IN) A.C. (IN)

CUL-DE-8AC 200 5.0 3.0 5.0 6.5 - 5.0

LOCAL (L.V.R.) 700 5.5 3.0 5.0 6.5 - 6.0

LOCAL (RES.) 1200 6.0 3.0 5.5 7.0 - 6.5

LOCAL (RES.) 2200 6.5 3.0 6.0 7.0 - 7.0

LOCAL (IND.) 2000 8.5 3.0 9.5 7.5 - 9.5

COLLECTOR (RES.) 3500 7.0 40.0 TO 3.0 6.5 7.0 - 8.0

COLLECTOR (RES.) 5000 7.5 49.9 3.0 7.5 7.5 - 8.5

COLLECTOR (COMM.\IND.) 5000 9.5 3.0 11.0 8.0 - 11.0

COLLECTOR (NO FRT) 7500 8.0 3.0 8.5 7.5 - 9.0

COLLECTOR 15000 9.0 3.0 10.5 8.0 - 10.0

MAJOR (4-LANE) 30000 10.5 3.5 12.5 8.5 - 12.0

MAJOR (6-LANE) 40000 11.0 4.0 12.5 8.5 - 12.5

PRIMARY ARTERIAL 50000 11.5 4.0 13.5 9.0 - 13.0

EXPRESSWAY 60000 12.0 4.5 13.5 9.0 - 13.5

EXPRESSWAY 80000 12.5 4.5 14.5 9.5 - 14.0

100000 -
EXPRESSWAY 13.0 5.0 15.0 10.0 15.0

SHEET 2 OF 4

REVISION BY APPROVED DATE RECOMMENDED BY THE CITY OF SAN DIEGO


STANDARDS COMMITIEE
CITY OF SAN DIEGO - STANDARD DRAWING
dl~
ORIGINAL M.ROLLINGER 05-92
1/31/2012
NOTES G. PARKINSON Oa-95
COORDINATOR R.C.E. 65271 DATE
UPDATED KA J. NAGELVOOR OV12 PAVEMENT DESIGN STANDARDS
DRAWING
SCHEDULE ""J"" NUMBER
SDG-113
MAX STANDARD CONCRETE FULL
STREET MAX TRAFFIC "R" SECTIONS M.O.R. 600 MIN DEPTH
CLASSIFICATION ADT INDEX VALUE A.C. (IN) CTB (IN) PCC (IN) CTB (IN) A.C. (IN)

CUL-DE-8AC 200 5.0 3.0 5.0 6.5 - 6.0

LOCAL (L.V.R.) 700 5.5 3.0 5.5 7.0 - 6.5

LOCAL (RES.) 1200 6.0 3.0 6.5 7.0 - 7.0

LOCAL (RES.) 2200 6.5 3.0 7.5 7.0 - 8.0

LOCAL (IND.) 2000 8.5 3.0 11.5 8.0 - 10.5

COLLECTOR (RES.) 3500 7.0 30.0 TO 3.0 8.5 7.5 - 8.5

COLLECTOR (RES.) 5000 7.5 39.9 3.0 9.5 7.5 - 9.0

COLLECTOR (COMM.\IND.) 5000 9.5 3.5 13.0 8.5 - 12.0

COLLECTOR (NO FRT) 7500 8.0 3.0 10.5 7.5 - 10.0

COLLECTOR 15000 9.0 3.5 12.0 8.0 - 11.0

MAJOR (4-LANE) 30000 10.5 4.0 14.5 8.5 - 13.5

MAJOR (6-LANE) 40000 11.0 4.5 15.0 9.0 - 14.0

PRIMARY ARTERIAL 50000 11.5 5.0 15.5 9.0 - 14.5

EXPRESSWAY 60000 12.0 5.0 16.5 9.5 - 15.0

EXPRESSWAY 80000 12.5 5.5 17.0 9.5 - 16.0

EXPRESSWAY 100000 13.0 6.0 17.0 10.0 - 17.0

MAX STANDARD CONCRETE FULL


STREET MAX TRAFFIC "R" SECTIONS M.O.R. 600 MIN DEPTH
CLASSIFICATION ADT INDEX VALUE A.C. (IN) CTB (IN) PCC (IN) CTB (IN) A.C. (IN)
CUL-DE-8AC 200 5.0 3.0 5.5 7.0 - 6.5

LOCAL (L.V.R.) 700 5.5 3.0 7.0 7.0 7.5

LOCAL (RES.) 1200 6.0 3.0 8.0 7.0 - 8.0

LOCAL (RES.) 2200 6.5 3.0 9.0 7.5 - 8.5

LOCAL (IND.) 2000 8.5 3.5 13.0 8.0 - 11.5

COLLECTOR (RES.) 3500 7.0 20.0 TO 3.0 10.0 7.5 - 9.0

COLLECTOR (RES.) 5000 7.5 29.9 3.0 11.5 7.5 - 10.0

COLLECTOR (COMM.\IND.) 5000 9.5 4.0 15.0 8.5 - 13.0

COLLECTOR (NO FRT) 7500 8.0 3.5 12.0 8.0 - 11.0

COLLECTOR 15000 9.0 4.0 13.5 8.5 - 12.0

MAJOR (4-LANE) 30000 10.5 5.0 16.0 8.5 5.0 14.5

MAJOR (6-LANE) 40000 11.0 5.0 17.0 8.5 5.0 15.5

PRIMARY ARTERIAL 50000 11.5 5.5 17.5 9.0 5.0 16.0

EXPRESSWAY 60000 12.0 6.0 18.0 9.0 5.0 17.0

EXPRESSWAY 80000 12.5 6.0 19.5 8.5 5.0 17.5

EXPRESSWAY 100000 13.0 6.5 20.0 10.0 5.0 18.5

SHEET 3 OF 4

REVISION BY APPROVED DATE RECOMMENDED BY THE CITY OF SAN DIEGO


STANDARDS COMMITIEE
CITY OF SAN DIEGO - STANDARD DRAWING
dl~
ORIGINAL M.ROLLINGER 05-92
1/31/2012
NOTES G. PARKINSON Oa-95
COORDINATOR R.C.E. 65271 DATE
UPDATED KA . NAGELVOORT OV12 PAVEMENT DESIGN STANDARDS
DRAWING
SCHEDULE ""J"" NUMBER
SDG-113
MAX STANDARD CONCRETE FULL
STREET MAX TRAFFIC "R" SECTIONS M.O.R. 600 MIN DEPTH
CLASSIFICATION ADT INDEX VALUE A.C. (IN) CTB (IN) PCC (IN) CTB (IN) A.C. (IN)

CUL-DE-SAC 200 5.0 3.0 7.0 7.0 - 7.5

LOCAL (L.V.R.) 700 5.5 3.0 8.0 7.0 - 8.0

LOCAL (RES.) 1200 6.0 3.0 9.0 7.5 - 8.5

LOCAL (RES.) 2200 6.5 3.0 10.5 7.5 - 9.0

LOCAL (IND.) 2000 8.5 4.0 14.5 8.0 5.0 12.5

COLLECTOR (RES.) 3500 7.0 10.0 TO 3.0 12.0 7.5 - 10.0

COLLECTOR (RES.) 5000 7.5 19.9 3.5 12.5 8.0 - 11.0

COLLECTOR (COMM.\IND.) 5000 9.5 4.5 16.5 8.5 5.0 14.0

COLLECTOR (NO FRT) 7500 8.0 3.5 14.0 8.0 - 11.5

COLLECTOR 15000 9.0 4.5 15.0 8.0 5.0 13.0

MAJOR (4-LANE) 30000 10.5 5.5 18.0 8.5 6.0 15.5

MAJOR (6--LANE) 40000 11.0 6.0 18.5 9.0 6.0 16.5

PRIMARY ARTERIAL 50000 11.5 6.0 20.0 9.0 6.0 17.5

EXPRESSWAY 60000 12.0 6.5 20.5 9.0 6.0 18.5

EXPRESSWAY 80000 12.5 7.0 21.5 9.5 6.0 19.0

EXPRESSWAY 100000 13.0 7.5 22.5 10.0 6.0 20.0

MAX STANDARD CONCRETE FULL


STREET MAX TRAFFIC "R" SECTIONS M.O.R. 600 MIN DEPTH
CLASSIFICATION ADT INDEX VALUE A.C. (IN) CTB (IN) PCC (IN) CTB (IN) A.C. (IN)
CUL-DE-SAC 200 5.0 3.0 8.0 7.0 - 8.5

LOCAL (L.V.R.) 700 5.5 3.0 9.5 7.5 - 9.0

LOCAL (RES.) 1200 6.0 3.0 10.5 7.5 - 9.5

LOCAL (RES.) 2200 6.5 3.0 12.5 7.5 - 10.5

LOCAL (IND.) 2000 8.5 4.5 16.0 8.0 5.0 14.0

COLLECTOR (RES.) 3500 7.0 0.0 TO 3.5 13.0 7.5 - 11.5

COLLECTOR (RES.) 5000 7.5 9.9 3.5 14.5 8.0 - 12.5

COLLECTOR (COMM.\IND.) 5000 9.5 5.0 18.5 8.5 6.0 15.5

COLLECTOR (NO FRT) 7500 8.0 4.0 15.5 8.0 5.0 13.0

COLLECTOR 15000 9.0 5.0 17.0 8.5 5.0 14.5

MAJOR (4-LANE) 30000 10.5 6.0 20.0 9.0 6.0 17.5

MAJOR (6--LANE) 40000 11.0 6.5 21.0 9.0 6.0 18.5

PRIMARY ARTERIAL 50000 11.5 7.0 22.0 9.0 6.0 19.5

EXPRESSWAY 60000 12.0 7.0 23.0 9.5 6.0 20.5

EXPRESSWAY 80000 12.5 7.5 24.0 10.0 6.0 21.5

EXPRESSWAY 100000 13.0 8.0 25.0 10.5 6.0 22.0

SHEET 4 OF 4

REVISION BY APPROVED DATE RECOMMENDED BY THE CITY OF SAN DIEGO


STANDARDS COMMITIEE
CITY OF SAN DIEGO - STANDARD DRAWING
dl~
ORIGINAL M.ROLLINGER 05-92
1/31/2012
NOTES G. PARKINSON Oa-95
COORDINATOR R.C.E. 65271 DATE
UPDATED KA ~· NAGELVOORT OV12 PAVEMENT DESIGN STANDARDS
DRAWING
SCHEDULE ""J"" NUMBER
SDG-113
FORMED OR SAWCUT
EDGE ON ALL SIDES

PCC 52o-C-2500

EDGE OF CURB AND


NEW BACKFILL & GUTIER
(OR EX) REPLACE EX
SIDEWALK VEGETATION
OR (TYP)
CURB RAMP ----l 2"
A r----'-r------,----l~ L A
I I 2"
- EXISTING +- -
STAMP I I
-1-
- IMPRESSION -
2"

2" I
rc- STAMP
(LOCATION PER
ENGINEER)

PLAN VIEW

6" MIN 6" MIN

.
1.5%

DEPTH OF •••• " •


'" .to • . ", ...
• • to
. .... ..
CURB AND
STAMP I IMPRESSION·· •• ". •• .~ ,; ....... " ..
"' .. .
GUTIER
4" MIN
...
•• • • •• ' •••
. ... ~

. . . .. ~

...
... •
'"
.....
...
.......
"'.
",.
. .~
... .• ....... ..... .........
6·· '" ;...... .~ .. ~..
.. • .... •

.... .. ~. .......... ....... .. .... ..... . ........ ~. .. ... .. .... ..


• o· o· o· o · o· o· o· o · o · o · o · o · 0·0_----
o. o. o . o . o. o. o. o. o. o. o. o. o . 0
12" MIN • o· o · o · o· o· o· o· o· o· o· o· 0. 0 •
0000000000000

SECTION VIEW A-A SUBGRADE AT 90% RELATIVE


COMPACTION TO 12"

NOTES:

1. ALL STAMP IIMPRESSION (STREET NAME, CONTRACTOR, NAME AND lOR DATE) LOCATIONS AND ORIENTATIONS
SHALL BE PRE-APPROVED BY THE ENGINEER.

2. SINGLE STAMP IIMPRESSION SHALL BE PLACED AS CLOSE TO ITS ORIGINAL LOCATION AS CONSTRUCTION
ALLOWS.

3. MULTIPLE STAMPS I IMPRESSIONS (EXISTING AND lOR NEW) SHALL BE EVENLY SPACED ALONG THE NEWLY
CONSTRUCTED SIDEWALK.

4. EXISTING STAMP IIMPRESSION SHALL BE SAWCUT TO NO LESS THAN 2" FROM STAMP LETIERING OR SYMBOL.

REVISION BY APPROVED DATE RECOMMENDED BY THE CITY OF SAN DIEGO


STANDARDS COMMITIEE
CITY OF SAN DIEGO - STANDARD DRAWING
ORIGINAL

DETAIL
NZ

SM
J. SHOAF
A. OSKOUI
800

1W3
IJ·cJ/-ML--
COORDINATOR R.C.E. 65271
1/31/2012
DATE
UPDATED KA . NAGELVOORT OV12 EXISTING HISTORICAL STAMP OR
DRAWING
IMPRESSION PLACEMENT NUMBER
SDG-115
MILL AND PAVE 4"
RESURFACE OVERLAY
PER NOTE 4

TACK ALL EDGES W I


TH
ASPHATI
C EMULSION C PLANE 18"
C EXI
STING A.
C.
MI
N
PAVEMENT

C
C
C
C

C
C

C
C
1/
2" TO 1" DEPTH
CONCAVE SLURRY
4" C SURFACE W I TH A SHOVEL

EXI
STI
NG BASE OR
OLD CONCRETE PAVEMENT
18" MIN
36" MAX

W ARNI
NG TAPE PER SDM-105

CEMENT SLURRY BACKFI


LL 100-D-100
UP TO THE FI
NISH GRADE
C
C

1" MI
C N-6" MAX
C

NOTES:

1. CEMENT SLURRY BACKFI


LL SHALL BE THOROUGHLY CONSOLI
DATED,HAVE A MAXI
MUM SLUMP
OF 4 I
NCHES.FLY ASH MEETI
NG THE REQUI
REMENTS OF 201-1.
2.5.
3 MAY BE ADDED
(
NOT AS A SUBSTI
TUTE)TO THE MI
NIMUM CEMENT REQUI
REMENTS.SLURRY COMBI
NED
GRADI
NG SHALL MEET REQUI
REMENTS OF 201-1.
3.2(
A)GRADI
NG D.

2.BALL DROP TEST PER ASTM D 6024 SHALL BE PERFORMED ON SLURRY AND ACHI
EVE A MAXI
MUM
I
NDENTATI
ON DI
AMETER OF 3" PRI
OR TO PLACEMENT OF ASPHALT CONCRETE.SLURRY PLACED I
N
NARROW TRENCHES W HERE BALL DROP TEST CANNOT BE PERFORMED SHALL BE CURED A MI
NIMUM
OF 48 HOURS PRI
OR TO PLACEMENT OF ASPHALT CONCRETE.

3.CUTS SHALL BE STRAI


GHT.EXI
STI
NG A.
C.PAVEMENT W I
LL NOT REQUI
RE SAW CUTTI
NG W HEN USI
NG
ROCKW HEEL FOR EXCAVATI
ON.

4.TRENCH SHALL BE MI
LLED TO A DEPTH OF 4" AND A MI
NIMUM OF 18" W I
DE OR 12" W IDER
THAN TRENCH W I
DTH,W HI
CHEVER I
S GREATER,AND RESURAFCED W I
TH 1/2" TYPE I
IICLASS C2 ASPHALT.

5.W HEN PCC TRENCH RESURFACI


NG I
S DI
RECTED BY CI
TY ENGI
NEER,SHOW N ON THE PLANS,OR REQUI
RED
FOR A PCC SURFACED STREET,FOR ASPHALT STREETS SEE SDG-107 (
NOTE #3)AND FOR PCC SURFACED
STREETS SEE SDG-108.

6.FOR ELECTRI
CAL SUPPLY CABI
NETS,SEE CALI
FORNI
A PUBLI
C UTI
LITY COMMI
SSI
ON GENERAL ORDER NO.128,
RULE 33.
4 CLEARANCES AND DEPTHS.

7.FOR DRY UTI


LITI
ES (
ELECTRI
CAL,COMMUNI
CATI
ON,GAS,ETC.
)SEE SDG-119.

RECOMMENDED BY THE CI
TY OF SAN DI
EGO
REVI
SION BY APPROVED DATE
STANDARDS COMMITTEE
CI
TY OF SAN DI
EGO - STANDARD DRAW I
NG
ORI
GINAL BAHMANI
AN 04/
86

2/
25/
16
UPDATED KA J.NAGELVOORT 01/
12
COORDI
NATOR R.
C.E.56523 DATE
UPDATED KA J.NAGELVOORT 04/
13 NARROW TRENCH RESURFACI
NG FOR
UPDATED KA J.NAGELVOORT 01/
14 DRAW I
NG
ASPHALT CONCRETE SURFACE STREETS SDG-
117
NUMBER
UPDATED AA J.NAGELVOORT 02/
16
CONCRETE TRENCH COVER
560-C-3250

EXI
STI
NG CONCRETE
PAVEMENT

C
C

24" MIN
EXI
STI
NG BASE OR OLD
CONCRETE PAVEMENT

MAX
36"
C

C
SAND CEMENT
SLURRY BACKFI
LL
100-D-100

C
C
C

1" MI
N - 6" MAX

NOTES:

1. CEMENT SLURRY BACKFI


LL SHALL BE THOROUGHLY CONSOLI DATED,HAVE A MAXI
MUM SLUMP
OF 4 I
NCHES,AND MAY CONTAIN 30% MAXI MUM 3/8" ROCK.

2. CONCRETE SHALL BE PLACED AND FI


NISHED I
N ACCORDANCE W I
TH 306-6. CONCRETE MAY BE PLACED I
MMEDI
ATELY
FOLLOW I
NG SLURRY BACKFILL

3. CONCRETE TRENCH COVER SHALL BE A MI NIMUM OF 5 1/


2" THI
CK I
N ALLEY OR LOCAL RESI
DENTIAL STREETS
AND 7" THI
CK I
N ALL OTHER STREETS. SEE NOTE #5 I
N SDG-108 FOR CONCRETE CLASS OPTIONS AND CURI NG
REQUI
REMENTS.

4. EXI
STI
NG PORTLAND CEMENT CONCRETE PAVEMENT W I
LL REQUI
RE SAW CUTTI
NG.

5. FOR ELECTRICAL SUPPLY CABLES,SEE CALI


FORNI
A PUBLI
C UTI
LITY COMMI
SSI
ON GENERAL ORDER NO.128,
RULE 33.
4 CLEARANCES AND DEPTHS.

6. FOR DRY UTI


LITI
ES (
ELECTRI
CAL,COMMUNI
CATI
ON,GAS,ETC.
)SEE SDG-119.

RECOMMENDED BY THE CI
TY OF SAN DI
EGO
REVI
SION BY APPROVED DATE
STANDARDS COMMITTEE
CI
TY OF SAN DI
EGO - STANDARD DRAW I
NG
ORI
GINAL BAHMANI
AN 04/
86

TI
TLE BLOCK A.OSKOUI 12/
06
2/
25/
16
COORDI
NATOR R.
R.
C.
C.
EE
..
55
66
55
22
33 DATE
UPDATED KA J.NAGELVOORT 01/
12
NARROW TRENCH RESURFACI
NG
UPDATED KA J.NAGELVOORT 08/
13 DRAW I
NG
FOR PCC SURFACED STREETS SDG-
118
NUMBER
UPDATED AB J.NAGELVOORT 02/
16
SEE NOTE 2

C
1SACK SLURRY CAP

C
C NOT ENCASING ANY CONDUI
TS.
SEE SDG-117.
C

3" MI
N
C

ZERO SACK SAND


SLURRY W HERE
COMMUNI CATI
ONS C CONDUITS ARE 4" OR
C

PACKAGE
C
LESS.ENCASEMENT
SEE NOTE 2
PER SDG&E
C

STANDARDS

C
4"
1'
-0" SEPARATI
ON BETW EEN
COMMUNI CATI
ON CONDUI T&
C

C
ELECTRIC PACKAGE
3" MI
N
C

C
C

C
C
ELECTRI
CAL 1SACK SLURRY CAP
3" MI
N
PACKAGE

C
NOT ENCASING ANY CONDUI
TS.
SEE SDG-117.
DEPTH OF TRENCHES COMMUNI CATI
ONS C

C
VARY UPON EXI
STI
NG PACKAGE
CONDITI
ON

C
ZERO SACK C 1'
-0" SEPARATI
ON BETW EEN
TYPE G
SAND SLURRY COMMUNI CATI
ON CONDUI T&
5" ELECTRIC PACKAGE
ELECTRI
CAL C
PACKAGE C

SEE NOTE 2 1SACK SLURRY ENCASI NG

C
ELECTRICAL CONDUITS 5"
3" MI
N

C
C
OR GREATER.NO LESS THAN
C

3" ENCASEMENT PER


SDG&E STANDARDS
C

C 1SACK SLURRY CAP NOT


DEPTH OF TRENCHES VARY
ENCASING ANY CONDUI TS OR
UPON EXI
STING CONDITION
NATI
VE SOI L;YELLOW
C

BACKFILL MATERIAL;CLASS I
I
3" MI
N BASE.SEE SDG-117
TYPE H
C
C

3" MI
N
C

C
C

ZERO SACK SAND SLURRY FROM


BOTTOM OF TRENCH COVERING
COMMUNICATI
ONS PACKAGE
COMMUNI CATI
ONS
PACKAGE TRENCH DEPTH VARI
ES
UPON EXI
STING CONDITI
ONS

TYPE I

NOTES:

1. FOR TRENCHES GREATER THAN 6",AND LESS THAN 7'


-0" I
N WI
DTH

2.RESURFACI
NG PER SDG-107 TYPE 1& SDG-108

3.ANY CITY UTILI


TY CROSSI
NG THE TRENCH LI
NE SHOULD NOT BE ENCASED I
N SLURRY,I
F ENCOUNTERED I
T SHOULD BE
SLEEVED W ITH PVC.

4.W ARNI
NG TAPE SHALL BE I
NSTALLED ABOVE THE CONDUI
TS PER SDM-105.

5.CEMENT SLURRY BACKFILL SHALL BE THOROUGHLY CONSOLI DATED,HAVE A MAXIMUM SLUMP OF 4 I NCHES.FLY ASH
MEETI
NG THE REQUI REMENTS OF 201-1.2.
5.3 MAY BE ADDED (
NOT AS A SUBSTITUTE)TO THE MINIMUM CEMENT
REQUIREMENTS.SLURRY COMBI NED GRADI NG SHALL MEET REQUIREMENTS OF 201-1.
3.2 GRADI
NG D.

6.BALL DROP TEST PER ASTM D 6024 SHALL BE PERFORMED ON SLURRY AND ACHIEVE A MAXIMUM I
NDENTATI
ON
DIAMETER OF 3 I
NCHES PRIOR TO PLACEMENT OF ASPHALT CONCRETE.SLURRY PLACED IN NARROW TRENCHES W HERE
BALL DROP TEST CANNOT BE PERFORMED SHALL BE CURED A MINIMUM OF 48 HOURS PRIOR TO PLACEMENT OF
ASPHALT CONCRETE.

RECOMMENDED BY THE CI
TY OF SAN DI
EGO
REVI
SION BY APPROVED DATE
STANDARDS COMMITTEE
CI
TY OF SAN DI
EGO - STANDARD DRAW I
NG
ORI
GINAL BB J.NAGELVOORT 07/
15

2/
25/
16
UPDATED LA J.NAGELVOORT 07/
15
COORDI
NATOR R.
C.E. 56523 DATE
UPDATED JN J.NAGELVOORT 02/
16 TRENCH TYPES G,H & I
DRAW I
NG
BACKFI
LL FOR DRY UTI
LITY NUMBER
SDG-
119
C
A

L ALLEY
PROPERTY

C
LI
NE
C

C
D C

C
D

D
560-C-3250
CURB LI
NE
CONCRETE C

C
C
C
R R
GUTTER LI
NE
C D

C
D

C C
D C D C D

C
A

PLAN

PROPERTY LINE
GUTTER LINE

GUTTER ELEVATI
ON
SHOW N ON PLANS

ELEVATI
ON SHOW N ON PLANS

TOE OF GUTTER ELEVATI


ON
5 1/
2"
1.
5%
C
C

C
C
C

C
C

1/
2" R

11/
2" EXCEPT W HERE ELEVATI
ONS SHOW N I
NDI
CATE OTHERW I
SE

SECTI
ON A-A

NOTES

1. CURB RAMPS SHALL BE I


NSTALLED AS SHOW N ON THE PLANS.

2. D= DI
STANCE SHOW N ON PLANS.

3. R= RADI
US SHOW N ON PLANS 3'MI
NIMUM.

4. O= ELEVATI
ONS SHOW N ON PLANS (
TOP OF CURB AND GUTTER ELEV.
).
LEGEND ON PLANS

5. = 1/
2" EXPANSI
ON JOI
NTS.

6. CONSTRUCTI
ON OF ALLEY APRON I
NCLUDES THE ADJACENT 6" CURB.

7. REFER TO CURB RAMP DETAI


L,SDG-137.

RECOMMENDED BY THE CI
TY OF SAN DI
EGO
REVI
SION BY APPROVED DATE
STANDARDS COMMITTEE
CI
TY OF SAN DI
EGO - STANDARD DRAW I
NG
ORI
GINAL* KA J.NAGELVOORT 01/
12

2/
25/
16
UPDATED RB J.NAGELVOORT 10/
15
COORDI
NATOR R.
C.E.56523 DATE
UPDATED FC J.NAGELVOORT 02/
16
ALLEY APRON DRAW I
NG
SDG-
120
NUMBER
C TI
LE SHALL EXTEND TO THE
DETAI
L1 C
FULL W I
DTH OF CURB RAMP

C
A1

C
3'-0"
C

A1

PLAN - TI
LE

C
2.
3-2.
4"
C NOTES:

1. THE DETECTABLE W ARNI


NG TILE SHALL BE SLI
P
RESI
STANT AND CONSI ST OF AN I
NLINE PATTERN
OF RAI
SED TRUNCATED DOMES.

2.COLOR:THE DETECTABLE W ARNI


NG TI
LE SHALL BE
YELLOW CONFORMI NG TO FEDERAL STANDARDS
595C TABLE I
V,COLOR NO.33538.
C

3.MATERI
AL:STAI
NLESS STEEL I
S THE REQUI
RED
C

MATERIAL FOR THE DETECTABLE W ARNI


NG TI LE.
2.35"

THE TYPE OF MATERIAL SELECTED SHALL BE


0.
65" MI
N I
NDI
CATED ON THE CURB RAMP DRAW I
NGS.
C

EXCEPTI
ON:CAST-I
N-PLACE DETECTABLE W ARNI
NG
TI
LE OF COMPOSITE MATERI
AL MAY BE USED ON
C

RESI
DENTI
AL AREAS ONLY. W HEN RESI
DENTI
AL AREAS
ARE W I
THI
N THE BOUNDARY OF A MI
X-USE OR
OTHER NON-RESIDENTI
AL ZONES,STAI
NLESS STEEL
I
S REQUIRED AT CURB RAMPS.

DETAI
L1
4.DETECTABLE W ARNI
NG TI
LE PRODUCTS SHALL BE PER
THE CI
TY'S APPROVED MATERI
ALS LI
ST.

R= 0.
06" 0.
45-0.
47" 0.
18-0.
22"
C 0.
18-0.
22" 0.
45-0.
C
47"
C C
R= 0.
06"
C

C
C
C

C
C

C
1.375"

C
C
0.
90-0.
92" C
MIN

C
0.
90-0.
92"
C
C

0.
060" C
C
MI
N 0.
25" MI
N DIAMETER VENT HOLES
SPACING PER MANUFACTURER COMPOSITE
STAI
NLESS STEEL
SECTI
ON A1-A1
SECTI
ON A1-A1

REVI
SION BY APPROVED DATE RECOMMENDED BY THE CI
TY OF SAN DI
EGO
CI
TY OF SAN DI
EGO - STANDARD DRAW I
NG STANDARDS COMMITTEE
ORI
GINAL FC A.OSKOUI 12/
03

UPDATE A.OSKOUI
2/
29/
16
FC 12/
06
COORDI
NATOR R.
C.E.56523 DATE
UPDATE FC A.OSKOUI 02/
07
DETECTABLE W ARNI
NG TI
LES DRAW I
NG
UPDATE FC A.OSKOUI 12/
08

NUMBER
SDG-
130
UPDATE FC J.NAGELVOORT 02/
16
NOTES:
1. TW O CURB RAMPS ARE REQUI
RED AT EACH SI
DEW ALK CORNER FOR NEW CONSTRUCTI
ON OF ENTI
RE I
NTERSECTI
ON,EACH
CURB RAMP SHALL CONNECT THE PEDESTRI
AN ACCESS ROUTE AT EACH PEDESTRI
AN STREET CROSSI
NG.I
N ALTERATI
ONS
W HERE EXI
STI
NG PHYSICAL CONSTRAI
NTS PREVENT TW O CURB RAMPS FROM BEI NG I
NSTALLED AT A STREET CORNER,A
SINGLE PEDESTRI
AN CURB RAMP IS PERMI
TTED.SEE DETAIL A AND B ON SDG-132.

2. OPPOSI
NG CURB RAMPS AT A SI
NGLE CROSSI
NG SHALL LI
NE UP.ALI
GN THE CURB RAMP W I
TH THE CROSSW ALK SO THERE
I
S A STRAI
GHT PATH OF TRAVEL FROM THE TOP OF THE RAMP TO THE CURB RAMP ON THE OTHER SI
DE,TO THE MAXI
MUM
EXTENT FEASI
BLE.

3. PULL BOXES,MANHOLES,VAULTS,AND OTHER UTI


LITI
ES SHALL BE RELOCATED OR INCORPORATED ONTO THE CURB RAMP
AREA PROVIDED THAT THE ACCESS COVER I
S STABLE,FI
RM,SLIP RESI
STANT,AND FLUSH OR ADJUSTED TO GRADE.
COORDINATE THE W ORK W I
TH THE ENGI
NEER

4. UTI
LITY POLES MAY BE I
NCORPORATED I
NTO THE FLARES OF THE CURB RAMP PROVI
DED THAT THE REQUI
RED ACCESSI
BLE
ROUTE W I
DTH I
S COMPLI
ANT.

5. THE RUNNI
NG SLOPE OF THE CURB RAMP SHALL BE 5% MI
NIMUM AND 8.
33% MAXI
MUM. I
F THE CONDI
TION OF THE STREET
AND SIDEW ALK I
S SUCH THAT THE EXI
STI
NG SLOPES DO NOT ALLOW THE I NSTALLATI
ON OF THE REQUIRED CURB RAMP
SLOPE,THEN THE RAMP LENGTH SHALL BE EXTENDED TO 15 LI
NEAR FEET TO CATCH THE REQUIRED SLOPE EVEN I
F THE
REQUI
RED SLOPE I
S NOT ACHI
EVED. COORDI
NATE W I
TH THE ENGI
NEER PRI
OR TO DEMOLI
TION OR CONSTRUCTI
ON.

6. GRADE BREAKS AT THE TOP AND BOTTOM OF THE RAMPS AND CURB RAMPS SHALL BE PERPENDI
CULAR TO THE DI
RECTI
ON
OF THE RAMP RUN.GRADE BREAKS SHALL NOT BE PERMI TTED ON THE SURFACE OF RAMP RUNS AND TURNI
NG SPACES.
SURFACE SLOPES THAT MEET AT GRADE BREAKS SHALL BE FLUSH.

7. PROVI
DE A 1/
4" DEEP TOOLED JOI
NT W I
TH 1/
4" RADI
US EDGES AS SHOW N ON DRAW I
NGS.

8. I
NSTALL A 1/
4" EXPANSI
ON JOI
NT FI
LLER BETW EEN THE NEW CURB RAMP GUTTER AND THE EXI
STI
NG SI
DEW ALK.

9. PONDI
NG I
S NOT ALLOW ED W I
THI
N THE CURB RAMP LI
MITS,AND THE DRAI
NAGE PATTERN SHALL NOT BE ALTERED.

10.THE ADJUSTMENT OF THE CROSS SLOPE AT THE RAMP OPENI


NG SHALL NOT CAUSE GUTTER TRI
CKLE FLOW TO SPI
LL ONTO
TRAVELLED LANES OR PONDI
NG ANYW HERE.

11.TRANSI
TIONS FROM RAMPS TO W ALKS AND SI
DEW ALK GUTTER OR STREET SURFACE SHALL BE FLUSH AND FREE OF ABRUPT
CHANGES. PAVEMENT AT THE STREET SURFACE SHALL BE MI
LLED TO ACHI
EVE FLUSH CONDI
TION.

12.THE REMOVAL OF EXI


STI
NG PAVEMENT,CONCRETE CURB,GUTTER,SI
DEW ALK,AND EXI
STI
NG CURB RAMP FOR THE
I
NSTALLATI
ON OF A NEW CURB RAMP SHALL COMPLY W I
TH SDG-156.

13.DIAGONAL OR CORNER TYPE CURB RAMPS W I


TH RETURNED CURBS OR OTHER W ELL-DEFINED EDGES SHALL HAVE THE
EDGES PARALLEL TO THE DI
RECTION OF PEDESTRI
AN FLOW .DI
AGONAL CURB RAMPS W I
TH FLARED SIDES SHALL HAVE A
SEGMENT OF CURB 24" LONG MINIMUM LOCATED ON EACH SI DE OF THE CURB RAMP AND W I
THI
N THE MARKED CROSSI NG.

14.DI
AGONAL CURB RAMPS SHALL HAVE A CLEAR 4'X 4'MI
NIMUM TURNI
NG SPACE BEYOND THE BOTTOM GRADE BREAK
WITHI
N THE W I
DTH OF THE PEDESTRI
AN STREET CROSSI
NG AND W HOLLY OUTSI
DE THE ACTI
VE TRAFFI
C LANES OF THE
ROADW AY (
VEHI CULAR AND BI
KE LANES)
.

15.CURB RAMP AND FORM W ORK SLOPES SHALL BE CHECKED W I


TH A DI
GITAL LEVEL OF AN APPROPRI
ATE LENGTH.NO
PORTI
ON OF A RAMP RUN SHALL EXCEED THE MAXIMUM SLOPE REQUIREMENT.

16.THE COUNTER SLOPE W I


THI
N 4'OF THE CURB RAMP SHALL BE 5% MAXI MUM. I
N ALTERATI
ONS I
F THE COUNTER SLOPE OF
5% MAXIMUM CANNOT BE ACHI EVED,THEN ADJUST THE SLOPE OR ELEVATI
ON OF THE RAMP SO THE COMBINED COUNTER
SLOPE AND RAMP SLOPE DOES NOT EXCEEDS 13.
3%.

17.THE SLOPE OF THE RAMP SHALL BE UNI


FORM ALONG EACH RAMP RUN.

18.THE CROSS SLOPE SHALL BE MEASURED PERPENDI


CULAR TO THE PATH OF TRAVEL.

19.ANY DEVI
ATI
ON FROM THESE PROVI
SIONS REQUI
RES PRI
OR APPROVAL FROM THE ENGI
NEER.

RECOMMENDED BY THE CI
TY OF SAN DI
EGO
REVI
SION BY APPROVED DATE
STANDARDS COMMITTEE
CI
TY OF SAN DI
EGO - STANDARD DRAW I
NG
ORI
GINAL SS A.OSKOUI 12/
03

12/
06
2/
29/
16
UPDATE FC A.OSKOUI
COORDI
NATOR R.
C.E.56523 DATE
UPDATE FC A.OSKOUI 12/
08

UPDATE KA J.NAGELVOORT 01/


12 GENERAL CURB RAM P NOTES DRAW I
NG
SDG-
131
NUMBER
UPDATE FC J.NAGELVOORT 02/
16
LEGEND:
TOOLED JOI
NT

PROPERTY LINE
EXI
STI
NG
SI
DEW ALK

LANDI
NG

CROSSWALK IF
PROVIDED
LANDI
NG

PROPERTY
LI
NE -0
"

FLOWLINE
EXI
STI
NG 6" W I
DE RETAI
NING
4'

GUTTER
IN

SI
DEW ALK CURB I
F SPECI
FIED
M

OR REQUI
RED

6" MI
N COUNTER
SLOPE
8" MAX
CROSSW ALK I
F
PROVI
DED 4'
-0" MI
N 4'
3'
-0"
LANDI
NG
1.
5%
8.
33%
DETAI
LA M AX
5% MAX
2" MI
N ABOVE
TW O CURB RAMP FI
NISH GRADE
4" THI
CK MI
N.
CORNER I
NSTALLATI
ON

WARNING TILE
DETECTABLE

DETECTABLE
W ARNI
NG TI
LE

EDGE OF
SI
DEW ALK
PROPERTY LINE

SECTI
ON A-A

W HERE A FLARED
SI
DE OCCURS
PROVI
DE 2'
-0" CURB
WI
THI
N THE
CROSSW ALK TYPI
CAL
A AT BOTH ENDS

LANDI
NG
CROSSWALK
IF PROVIDED

PROPERTY LI
NE

A
4'
M -0
SI
DEW ALK IN "

CROSSW ALK
I
F PROVI
DED

DETAI
LB
TYPI
CAL ONE CURB RAMP
CORNER I
NSTALLATI
ON

RECOMMENDED BY THE CI
TY OF SAN DI
EGO
REVI
SION BY APPROVED DATE
STANDARDS COMMITTEE
CI
TY OF SAN DI
EGO - STANDARD DRAW I
NG
ORI
GINAL FC J.NAGELVOORT 02/
16

2/
29/
16
COORDI
NATOR R.
C.E.56523 DATE
GENERAL CURB RAM P NOTES
DRAW I
NG
& SUPPLEM ENTAL DETAI
LS SDG-
132
NUMBER
PROPERTY LINE
SI
DEW ALK NOTES:
1.6" W I
DE RETAI
NING CURB MAY BE OMI
TTED
I
F THE GROUND SURFACE W I
LL BE AT THE
FACE OF CURB
SAME ELEVATI
ON AS THE CURB RAMP
SURFACE.

A
LEGEND:
TOOLED JOI
NT
LI
P OF GUTTER
6" W I
DE RETAI
NING CURB
I
F SPECI
FIED OR REQUI
RED 1.
5%

PROPERTY LI
NE 5%
1. %
33 CROSSW ALK
8. AX

%
1.
5% M

10

X
A
BACK OF CURB

M
IN " STRAI
GHT EDGE
M -0
4'

SI
DEW ALK A
%
10

SEE SDG-132 FOR


X
A

SECTI
ON A-A DETAIL.
M
CROSSWALK

PROPERTY LI
NE PROPERTY LI
NE
TRANSI
TION AREA
SEE TYPE A SEE TYPE A

PLAN - TYPE A

B SI
DEW ALK
PROPERTY LI
NE

CROSSW ALK
DI
RECTI
ONAL DI
RECTI
ONAL
CURB RAMP "T" I
NTERSECTI
ON CURB RAMP

FLOWLINE
10% 4'
-0" 10%
LI
P OF GUTTER

GUTTER
MAX MI
N MAX

SI
DEW ALK SI
DEW ALK
6" W I
DE RETAI
NING
1.
5% 33%
8. 1.
5% COUNTER
CURB I
F SPECI
FIED 6" MI
N
MAX
8" MAX SLOPE
4'
-0" OR REQUI
RED
MIN
5%
1.
4'
-0" MI
N 4'
2" MI
N ABOVE 3'
PROPERTY LI
NE LANDI
NG
FI
NISH GRADE
TRANSI
TION 1.
5% 8.
33% M AX
AREA 5% MAX

6" W I
DE RETAI
NING B 4" THI
CK MI
N.
CURB I
F SPECI
FIED
OR REQUI
RED DETECTABLE
W ARNI
NG TI
LE

PLAN - TYPE B SECTI


ON B-B

RECOMMENDED BY THE CI
TY OF SAN DI
EGO
REVI
SION BY APPROVED DATE
STANDARDS COMMITTEE
CI
TY OF SAN DI
EGO - STANDARD DRAW I
NG
ORI
GINAL FC J.NAGELVOORT 02/
16

2/
29/
16
COORDI
NATOR R.
C.E.56523 DATE

CURB RAM PS -TYPE A AND B


DRAW I
NG
SDG-
133
NUMBER
PROPERTY LI
NE

EXI
STI
NG SI
DEW ALK LEGEND:
TOOLED JOI
NT
TRANSI
TION AREA
LANDI
NG
1.
5%

X
%
%

0
MA

CROSSWALK IF
5

1
.
1

MA 3%
X
3
8.
LANDI
NG

PROVIDED
M %
AX
0
TRANSI
TION AREA 1.

1
5%

PROPERTY LI
NE 5%
1.

%
33
8. %
X 10 X
EXI
STI
NG MA A
M
"
-0
SI
DEW ALK 1.
5%
4'

10%
IN
X
MA
M

COUNTER SLOPE
5% MAX

CROSSW ALK I
F
PROVI
DED

TW O CURB RAMPS CORNER

EXI
STI
NG 48" MI
N
TRANSI
TION
SI
DEW ALK AREA
EXISTI
NG
SI
DEW ALK

LANDI
NG TRANSI
TION C
AREA 1.
5%
10%

C
RAMP
C

MAX
6" W I
DE LANDI
NG
8.
33%
C C RETAI NI
NG C
MAX RAMP
LANDI
NG 5% 8.
1. 33% CURB

C
MAX 10% MAX
C

C
TOOLED COUNTER SLOPE LANDI
NG 1.
5%
MAC

C
0%
X

JOI
NT
C

5% MAX 8.
33%
1

1.
5%
C
TRANSI
TION MAX

C
10%
MAX
AREA
C
C

C
1.
5%
1.
5%
C

8.
33% C
C C
EXI
STI
NG 48" 1.
5% MAX
8.
33% COUNTER
C

1.
5%
C

C
C

MAX MI
N
C

SI
DEW ALK
SLOPE
% 8.
33%
10% 10
C
C X EXISTI
NG MAX 5% MAX
MAX MA SI
DEW ALK %
C

10
C
10% X
MA
C
RAMP MAX
COUNTER SLOPE
C

TRANSI
TION
AREA 5% MAX
COUNTER SLOPE
RAMP 5% MAX

CURB RAMPS ADJACENT TO NON-


TW O CURB RAMPS CORNER CONTI
GUOUS SIDEW ALK< 10'ROW

RECOMMENDED BY THE CI
TY OF SAN DI
EGO
REVI
SION BY APPROVED DATE
STANDARDS COMMITTEE
CI
TY OF SAN DI
EGO - STANDARD DRAW I
NG
ORI
GINAL FC J.NAGELVOORT 02/
16

2/
29/
16
COORDI
NATOR R.
C.E.56523 DATE

DUAL CURB RAM PS DRAW I


NG
SDG-
134
NUMBER
PROPERTY LINE

SIDEWALK
EXISTING
6" W I
DE
RETAI NI
NG
LI
P OF
CURB
GUTTER PROPERTY
A PROPERTY LI
NE
FACE OF LI
NE
CURB

TRANSI
TION 8.
33%
1.
5%
1.
5% 8.
33% 1.
5%
EXI
STI
NG ~ ~ EXI
STI
NG
AREA ~ ~
~ 1.
5% 1.
5%
SI
DEW ALK SI
DEW ALK

N
"MI
TOP LANDI
NG

~
Y
0
T
1. TRANSI
TION

-
5%

'
IN M
1.
5%

4
N TO

G
LA OT AREA LI
P OF
1.
D GUTTER
5%
B

IN "
TOP LANDI
NG
M -0

M 3%
4'
FACE OF
TOP

3
AX
8.
COUNTER SLOPE CURB
6" W I
DE RETAI
NING CURB LANDI
NG
5% MAX
TRANSI
TION

GRADE BREAK
AREA

%
CROSSW ALK

10
%

X
33

FLOWLINE
PROPERTY LI
NE

A
8.

IN "
M
%

GUTTER
M -0
AX
.5

4'
M
1

~ 5%
1.
EXI
STI
NG ~
%
10

SI
DEW ALK
A
M

A
X 4'
-0"

PL
COUNTER
CROSSWALK

6" 4'
-0" MI
N SLOPE
6" W I
DE RETAI
NING
TRANSI
TION AREA CURB 6"-8"
3'
-0"
2" MIN ABOVE DETECTABLE
TOP LANDI
NG FI
NI SH GRADE W ARNI
NG TI
LE
5% MAX
1.
5%
BACK OF CURB
STRAI
GHT EDGE

PLAN - TYPE C1 4" THI


CK MI
N. 7% SLOPE

SECTI
ON A-A

NOTES:
PROPERTY LINE

SIDEWALK

1. TYPE C1CURB RAMP SHALL ONLY BE USED W HERE


EXISTING

I
NADEQUATE RI
GHT OF W AY EXI
STS.TYPE C1SHALL
BE USED W HEN X< 8'AND ONLY W I
TH PRI
OR
B
APPROVAL FROM THE ENGI
NEER.X= DI
STANCE FROM
FACE OF CURB TO PROPERTY LI
NE.

FACE OF CURB 2. GRADE BREAK AT THE TOP AND BOTTOM OF


RAMP RUNS SHALL BE PERPENDI
CULAR TO THE
~

TRANSI
TION AREA
DI
RECTI
ON OF THE RAMP RUN.

TOOLED JOI
NT
4'-0" MIN

LEGEND:
TOP LANDI
NG
TYP

6" W I
DE RETAI
NING CURB MEET 1.
5% TOOLED JOI
NT
~

SI
DEW ALK ELEVATI
ON BACK
OF SI
DEW ALK
A %
M 33
8.

1. X

1.
5%
5%

FLOWLINE
GUTTER
~

PROPERTY LI
NE
A %
33

BOTTOM LANDI
NG
8.

%
1.5%

10
M

5%

X
A
1.

IN "
M

X 4'
-0"
M -0

CROSSW ALK
4'

PL

~
EXI
STI
NG COUNTER
6" 4'
-0" MI
N L= X-(
4'-6")
%
10

SI
DEW ALK SLOPE
X
A

LANDI
NG
M

B 3'
-0"
DETECTABLE
CROSSWALK

W ARNI
NG TI
LE
TRANSI
TION AREA 1.
5%
8.
33%
M AX
5% MAX
2" MI
N ABOVE
FI
NISH GRADE
4" THI
CK MI
N.
6" W I
DE
RETAI
NING
CURB
PLAN - TYPE C2 SECTI
ON B-B

RECOMMENDED BY THE CI
TY OF SAN DI
EGO
REVI
SION BY APPROVED DATE
STANDARDS COMMITTEE
CI
TY OF SAN DI
EGO - STANDARD DRAW I
NG
ORI
GINAL FC J.NAGELVOORT 02/
16

2/
29/
16
COORDI
NATOR R.
C.E.56523 DATE

CURB RAM PS -TYPE C1 AND C2


DRAW I
NG
SDG-
135
NUMBER
SIDEWALK
EXISTING
LEGEND:

PROPERTY LINE
TOOLED JOI
NT

TRANSI
TION
AREA

PROPERTY LINE
6" W I
DE TOP LANDI
NG

SIDEWALK
RETAI
NING 1.
5%
CURB RAMP

~~
RAMP

NO
3%
X
1.
5% BOTTOM

3
MA
8.
LANDI
NG
BOTTOM
RAMP 8.
33%
1.
5% LANDI
NG

~
MAX
BOTTOM CROSSW ALK

M 3%
LANDI
NG

~
3
AX
8.
RAMP
RAMP 4' COUNTER
6" W I
DE

5%
TOP LANDI
NG SLOPE

1.
~
RETAI
NING

~
4'(
TYP) 5% MAX

~
~ ~

MA %
CURB

3
%

X
33

3
COUNTER SLOPE

.
8. X

8
A 5% MAX RAMP
EXI
STI
NG 1.
5% M
~ ~ 33%
8.
SI
DEW ALK

~
5%
MAX EXI
STI
NG TOP

1.
SI
DEW ALK LANDI
NG

~
TRANSI
TION TRANSI
TION
)

~
TYP AREA
AREA 4'(
TOP LANDI
NG
CROSSW ALK

DOUBLE TYPE C1 PLAN - TYPE C1(


MODI
FIED)
PROPERTY LINE

SIDEWALK
EXISTING

SIDEWALK
EXISTING
FACE OF CURB TRANSI
TION
AREA
~

TRANSI
TION AREA
4'-0" MIN

~
LANDI
NG
~

1.
5%
LANDI
NG TOP
LANDI
NG

~
M 3%

6" W I
DE RETAI
NING CURB 1.
5%
3
AX
8.

COUNTER SLOPE 6" W I


DE
5%
1.

5% MAX RETAI
NING
PROPERTY LI
NE RAMP
CURB
~
1.
5% 33%
8.
%

MAX
10

CROSSW ALK
X
A
IN "
M
M -0
4'

EXI
STI
NG
~ BOTTOM
SI
DEW ALK
%
10

STRUCTURE 5' LANDI


NG
X
A

PROPERTY LI
NE
M

EXI
STI
NG 1.
5%
CROSSWALK

33%
8.
EXI
STI
NG JOI
NT SI
DEW ALK 1.
5%
MAX COUNTER
SLOPE
TRANSI
TION 5% MAX
TRANSI
TION AREA AREA

TOP LANDI
NG

TYPE A/
C2 COMBI
NATI
ON TYPE C1(
CORNER W I
TH BUI
LDI
NG OR STRUCTURE)

RECOMMENDED BY THE CI
TY OF SAN DI
EGO
REVI
SION BY APPROVED DATE
STANDARDS COMMITTEE
CI
TY OF SAN DI
EGO - STANDARD DRAW I
NG
ORI
GINAL FC J.NAGELVOORT 02/
16

2/
29/
16
COORDI
NATOR R.
C.E.56523 DATE
CURB RAM PS -TYPE C1 AND C2
DRAW I
NG
M ORE DETAI
LS SDG-
136
NUMBER
4'
-0" LANDI
NG
MI
N
PROPERTY LI
NE COUNTER SLOPE
6" W I
DE RETAI
NING CURB
5% MAX

MAX
10%
PLANTI
NG AREA
PROPERTY LI
NE
O

45

4'-2"
4'-0"

ALLEY
1.
5% EXISTI
NG

MIN
MIN
~ NON-CONTIGUOUS

~
SI
DEW ALK
1.
5%

MAX

MAX
10%

10%
8.
33%
8.
33% TRANSI
TION AREA
MAX MAX
EXI
STI
NG 4'
-0" MI
N LANDI
NG
CONTI
GUOUS
~

SI
DEW ALK PLANTI
NG AREA

STREET TRANSI
TION AREA
TYPI
CAL PLAN

LEGEND:
TOOLED JOI
NT

C C
MAX
10%
4'-0"

1.
5%
MIN

~ ~
~
MAX
10%

8.
33% EXI
STI
NG SI
DEW ALK
MAX
TRANSI
TION AREA

4'
-0" MI
N LANDI
NG

PLAN VI
EW
FLOWLINE
GUTTER

4'
-0" 4'
-0" MI
N LANDI
NG TRANSI
TION AREA EXI
STI
NG SI
DEW ALK

COUNTER SLOPE

5%
1.

5% MAX 33% M AX
8.

4" THI
CK MI
N.
DETECTABLE
W ARNI
NG TI
LE

SECTI
ON C-C

RECOMMENDED BY THE CI
TY OF SAN DI
EGO
REVI
SION BY APPROVED DATE
STANDARDS COMMITTEE
CI
TY OF SAN DI
EGO - STANDARD DRAW I
NG
ORI
GINAL FC J.NAGELVOORT 02/
16

2/
29/
16
COORDI
NATOR R.
C.E.56523 DATE

CURB RAM P -TYPE D


DRAW I
NG
SDG-
137
NUMBER
6" W I
DE RETAI
NING CURB
I
F SPECI
FIED OR REQUI
RED LANDI
NG LANDI
NG
4'-0" 4'
-0" MI
N 4'
-0" MI
N

4'-0"
1.
5% 1.
5% 1.
5% 1.
5%

1.5%

1.5%
MIN

MIN
FRONT EDGE 1.
5% 33%
8. 33%
8. 1.
5%

1.5%

1.5%
ES TA TA ES ES TA
OF SI
DEW ALK MAX MAX

8.33%
PLANTING

PLANTING
3
MAX

MAX
83
.
6" W I
DE RETAI
NING
AREA

AREA
CURB (
BOTH SI
DES
10% 10%
OF RAMP W HEN
MAX MAX
FLARES CANNOT BE
I
NSTALLED DUE TO
SI
TE CONSTRAI
NTS)

COUNTER SLOPE
5% MAX
CROSSW ALK I
F CROSSW ALK I
F
PROVI
DED PROVI
DED
4'
-2" I
F RAMP HAS
RETAI
NING CURB
CASE A 4'
-0" I
F RAMP HAS CASE B
WI
NGS

6" W I
DE RETAI
NING CURB 5'MI
N 4'
-0"
I
F SPECI FI
ED OR REQUIRED LANDI
NG

TRANSI
TION AREA I
F
CROSSWALK IF

33%
8. EXI
STI
NG SI
DEW ALK HAS
MAX 1.
5% A CROSS SLOPE THAT
1.
5%
PROVIDED

EXCEEDS 2%

TA ES
1.5%

COUNTER SLOPE
5% MAX

CROSSW ALK I
F
PROVI
DED

CASE C

NOTES:

1.CASE A THROUGH C MAY BE USED ONLY W I


TH APPROVAL OF THE ENGI
NEER.

2.ABBREVIATIONS:
ES-EXISTI
NG SIDEW ALK
TA-TRANSITION AREA

LEGEND:
TOOLED JOI
NT

RECOMMENDED BY THE CI
TY OF SAN DI
EGO
REVI
SION BY APPROVED DATE
STANDARDS COMMITTEE
CI
TY OF SAN DI
EGO - STANDARD DRAW I
NG
ORI
GINAL FC J.NAGELVOORT 02/
16
2/
29/
16
COORDI
NATOR R.
C.E.56523 DATE

GENERAL CURB RAM PS DRAW I


NG
SDG-
138
NUMBER
C 4'
-0"
C

MI
N RAI
SED I
SLAND SLOPE PASSAGEW AY
TO DRAI
N 1.
5%
3'
-0"

C
C
SI
DEW ALK
3'
-0" DETECTABLE C

C
W ARNI
NG TI
LE

C
A
C C
C

5'-4"C
CURB RAMP,

C
4'-0"
C

MIN
TRAVELED W AY SDG-133 C
C

C
SLOPE PASSAGEW AY

C
"
-4

Y
TO DRAI
N 1.
5%

A
5'
SEE NOTE 1

W
RAI
SED I
SLAND
C
A

C
2'
-0" MI
N

D
C

LE
SEE NOTE 2

VE
A
TR
TRAVELED WAY
C

C
C

SIDEWALK
C
C

C
C

C
A C 5'
-4"C A
DETECTABLE C 3'
-0"
C
W ARNI
NG TI
LE MI
N
RAI
SED ANGULAR PASSAGEW AY
SEE NOTES
I
SLAND
C 4'
-0"
C

TRAVELED W AY MI
N 3'
-0"
RAI
SED I
SLAND
C

C 5'
-4"C
SEE NOTE 2
C

C
C

C
SI
DEW ALK DETECTABLE
C
CURB RAMP, W ARNI
NG A

C
SDG-133 TI
LE C

5'-4"C

Y
C
C

A
W
C

D
C
STRAI
GHT PASSAGEW AY

"

LE
-4
5'

VE
C
A

A
C

TR
C 5'
-0"C
3'
-0"
RAI
SED I
SLAND MI
N
TRAVELED WAY

SLOPE
C

PASSAGEW AY
C

TO DRAI
N
1.
5% C

"
N C
-0
4'
C

I
M
C
4'
-0" MI
N

LK
DETECTABLE

A
C

W
W ARNI
NG TI
LE

E
ID
S
TRI
ANGULAR PASSAGEW AY

CURB RAMP AT ISLAND


CLEAR
PER SDG-133
PASSAGEW AY

SURFACE OF
NOTES: RAI
SED I
SLAND 5'
-4" OPENI
NG

1.W HERE THE I


SLAND OR CUT-THROUGH LENGTH IS 8 FT OR MORE,THE C C
C 6"
TYP
DETECTABLE W ARNI
NGS SHALL BE 36 I
NCHES I
N DEPTH EXTENDI
NG THE
C
C

FULL W I
DTH OF THE PEDESTRI
AN PATH OR CUT-THROUGH,LESS 2 I
NCHES
C
C

C
C
C

4" MI
N
C

MAXIMUM ON EACH SI DE.


VARIES

2.W HERE THE ISLAND OR CUT-THROUGH LENGTH I S LESS THAN 8 FT,THE 5'W I
DE DETECTABLE
W ARNI
NG TI
LE
DETECTABLE W ARNINGS SHALL BE 24 I
NCHES.I
F THE ISLAND I
S LESS THAN
6 FT,DETECTABLE W ARNI
NGS ARE NOT REQUIRED.
RETAI
NING CURB

3.DETECTABLE W ARNI
NGS SHALL BE PLACED AT THE EDGES OF THE
SECTI
ON A-A
PEDESTRI
AN ISLAND OR CUT-THROUGH MEDI AN,EXCEPT FOR RAISED
I
SLANDS W HERE THE PLACEMENT SHALL COMPLY W I
TH THE REQUIREMENTS
OF THE CURB RAMPS.

RECOMMENDED BY THE CI
TY OF SAN DI
EGO
REVI
SION BY APPROVED DATE
STANDARDS COMMITTEE
CI
TY OF SAN DI
EGO - STANDARD DRAW I
NG
ORI
GINAL FC J.NAGELVOORT 02/
16

2/
29/
16
COORDI
NATOR R.
C.E.56523 DATE

I
SLAND AND PASSAGEW AY DETAI
LS DRAW I
NG
SDG-
139
NUMBER
1-3/
4" GALVANI
ZED
STEEL SQUARE TUBE,
1/
8" THICK (
TYP)
7'
-0" MAX (
TYP)
I
NSTALL GALVANI
ZED
EQUAL EQUAL EQUAL
STEEL NUT,BOLT, CAP W I
TH SET
AND W ASHER (
TYP) SCREW ( TYP)

GALVANIZED STEEL
PLATE,W ELD TO
36"-38"
ENDS (TYP)

SI
DEW ALK
SURFACE

SEE DETAI
LA (
TYP)
3-1/
2" FROM FACE
OF BOTTOM RAI
L TO
SI
DEW ALK SURFACE
RAI
LING
PROPERTY LINE

SI
DEW ALK

7'
-0" MAX (
TYP)
RAI
LING
1.
5%

OBSTRUCTI
ON

6" CURB
LANDI
NG A
PROPERTY LI
NE
CURB RAMP LANDI
NG
12"
1.5%

GUTTER

5% MAX

SI
DEW ALK
A 8.
33% MAX
OBSTRUCTI
ON
SECTI
ON A-A
RAI
LING 6" CURB

RAI
LING FOR CURB RAMP
WI
TH OBSTRUCTI
ON
1-3/
4" GALVANI
ZED
STEEL SQUARE TUBE,
1/
8" THICK (
TYP) 1-3/
4" SQUARE POST
(TYP)
C

3" FROM TOP OF


ANCHOR SLEEVE TO I
NSTALL GALVANI
ZED STEEL
NOTES:
SI
DEW ALK SURFACE NUT,BOLT,AND W ASHER.
C

1. POSTS TO BE SET 12" BEHI


ND THE FACE OF CURB. C GALVANIZED STEEL
C

PLATE,W ELD TO ENDS.


C

2.I
N EXI
STI
NG SI
DEW ALK AREA SET POSTS I
NTO
C
C

4" CORE BORI


NG.

3.POSTS SHALL BE W RAPPED I


N 6 MI
L VI
SQUEEN PLASTI
C 12"
18"
C

PRI
OR TO POURI
NG CONCRETE OR GROUTI
NG.
RI
VET (TOTAL (
2)
C

90 APART)
4.HORI
ZONTAL 1-3/
4" GALVANI
ZED STEEL SQUARE POST TO C
24"
2-1/
4" ANCHOR
BE MOUNTED ON THE SI
DE OF THE BREAK-AW AY
SLEEVE
POSTS,OPPOSI
TE TO THE RAMP. NOTE 2 C
C

C
C 2" ANCHOR POST

DETAI
LA

RECOMMENDED BY THE CI
TY OF SAN DI
EGO
REVI
SION BY APPROVED DATE
STANDARDS COMMITTEE
CI
TY OF SAN DI
EGO - STANDARD DRAW I
NG
ORI
GINAL FC J.NAGELVOORT 02/
16

2/
29/
16
COORDI
NATOR R.
C.E.56523 DATE

CURB RAM P BARRI


CADE DRAW I
NG
SDG-
140
NUMBER
CURB LINE

CURB LINE
1.
5% 1.
5%
C C
C 6" C 6"
C C
1/
2" R 2" W EAKENED 1/
2" R 2" W EAKENED
PLANE JOI NT PLANE JOI NT
C

C
C C
C

C
6" UNLESS NOTED

8" UNLESS NOTED


C C

C 1 C 1
3 3
OTHERWISE

OTHERWISE
NE
LI NE
LI
GUTTER GUTTER

18"
C

C
15"

2" 2"
C

C
C 12"
C
C 11"
C

8" CURB
6" CURB AREA= 1.
09 SQ FT
AREA= 0.89 SQ FT
CURB LINE

C WI
DTH SHOW N ON PLANS
C
18" MI
N

C
C

C 1/
2"
6" UNLESS NOTED

C
OTHERWISE
C

2"
C
C

6"
C

W EAKENED PLANE JOI


NT

EXI
STI
NG CURB
11/
2" EXCEPT W HERE ELEVATI
ONS
SHOW N INDICATE OTHERW ISE

GUTTER

NOTES:

1. CONCRETE SHALL BE 520-C-2500.

2. SEE SDG-109 AND G-10 FOR JOI


NT DETAI
LS.

3. ALL HI
STORI
CAL STAMPS /I
MPRESSIONS (STREET NAME,CONTRACTOR NAME, LEGEND ON PLANS
AND /OR DATE)SHALL BE PRESERVED PER SDG-115.
6" CURB

RECOMMENDED BY THE CI
TY OF SAN DI
EGO
REVI
SION BY APPROVED DATE
STANDARDS COMMITTEE
CI
TY OF SAN DI
EGO - STANDARD DRAW I
NG
ORI
GINAL* KA J.NAGELVOORT 01/
12

10/
15
2/
25/
16
UPDATED RB J.NAGELVOORT
COORDI
NATOR R.
C.E.56523 DATE
UPDATED HM J.NAGELVOORT 02/
16
CURB AND GUTTER -SEPARATE DRAW I
NG
SDG-
150
NUMBER
1 1/2" EXCEPT WHERE ELEVATIONS
SHOWN INDICATE OTHERWISE
CURB LINE
C 6"
C

1.
5%
C
C

C 2" W EAKENED
1 PLANE JOI NT
C
1/
2" R
3

C
1" R

C
C
C

6"
7"

C
C

C W C 1/
2"
C

TYPE W *AREA

G 24" 1.
34 SQ FT

H 30" 1.
61SQ FT

* WI
TH 6" CURB FACE

NOTES:

1. CONCRETE SHALL BE 520-C-2500.

2. SEE JOI
NT DETAI
L DRAW I
NG SDG-109 AND G-10.

3. ON THE SI
DE OF OF SUPER ELEVATED CURVES THE GUTTER SHALL BE SLOPED TO MATCH CROSS SECTI
ON
GRADE OF THE ROADW AY.

4. PLACE EXPANSION JOI


NTS AT CURB RETURNS ADJACENT TO STRUCTURES AND AT NO GREATER THAN
45'I
NTERVALS.

5 PLACE W EAKENED PLANE JOI


NTS AT DRI
VEW AYS AND AT 15'I
NTERVALS FROM POI
NT OF CURB RETURN.

6. ALL HI
STORI
CAL STAMPS /I
MPRESSI
ONS SHALL BE PRESERVED PER SDG-115.

LEGEND ON PLANS

RECOMMENDED BY THE CI
TY OF SAN DI
EGO
REVI
SION BY APPROVED DATE
STANDARDS COMMITTEE
CI
TY OF SAN DI
EGO - STANDARD DRAW I
NG
ORI
GINAL* KA J.NAGELVOORT 01/
12

10/
15
2/
25/
16
UPDATED RB J.NAGELVOORT
COORDI
NATOR R.
C.E.56523 DATE
UPDATED HM J.NAGELVOORT 02/
16
CURB AND GUTTER -COM BI
NED DRAW I
NG
SDG-
151
NUMBER
GUTTER LINE
CURB LINE
CURB LINE
C 5" C 4"
C C C 5" C 4" C 15"
C C C
2" W EAKENED
PLANE JOI NT

C
C

2
C

C
C
C

C
3

6"
2
TOP OF 3

6"
C PAVEMENT
1/
2" R
14"

C
1/
2" R

C
C

C
2"

12"

C
8"

6"
1" R
2" W EAKENED
PLANE JOI NT
C

C
C

C 9"
C C 24" C 1/
2"
C

B-1 B-2
AREA= 0.79 SQ FT AREA= 1.
29 SQ FT

CURB LINE
CURB LINE

3 1/
2" 3 1/
2"

C 5" C
C C
C 5" C 3 1/
2"
C C

1/
2" R

1/
2" DI
A CONTI
NUOUS
C

C STEEL BAR
C

2
C
C

2
C

2" W EAKENDED 2 2" W EAKENDED


3 PLAN JOI NT 3
C PLAN JOI NT
6"

C 3
3/
4"
6"

C
C

C
C

C
TOP OF PAVEMENT C
C

TOP OF PAVEMENT
C

C
C 8 1/
2"
C
3/4"
5"

C 3" 1/
2" R
C
C

1/
2" DI
A STEEL DOW EL @ 4'C.C.
MIN LENGTH 8" SEE NOTE 3. C 12"
C

B-3 B-4
AREA= 0.
29 SQ FT AREA= 0.
35 SQ FT

NOTES:

1. CONCRETE SHALL BE 520-C-2500.

2. SEE JOI
NT DETAI
L DRAW I
NGS SDG-109 AND G-10. LEGEND ON PLANS

EXTRUDED TYPE B-3 CURB SHALL BE ANCHORED TO EXI


STI
NG PAVEMENT. TYPE B-2 CURB AND GUTTER
3.

4. ALL HI
STORI
CAL STAMPS /I
MPRESSIONS (STREET NAME,CONTRACTOR NAME, TYPE B-1,B-3,B-4 CURB
AND /OR DATE)SHALL BE PRESERVED PER SDG-115.

RECOMMENDED BY THE CI
TY OF SAN DI
EGO
REVI
SION BY APPROVED DATE
STANDARDS COMMITTEE
CI
TY OF SAN DI
EGO - STANDARD DRAW I
NG
ORI
GINAL* KA J.NAGELVOORT 01/
12

10/
15
2/
25/
16
UPDATED RB J.NAGELVOORT
COORDI
NATOR R.
C.E.56523 DATE
UPDATED HM J.NAGELVOORT 02/
16
CURB AND GUTTER -M EDI
ANS DRAW I
NG
SDG-
154
NUMBER
C VARI
ES C WI
DTH AS SHOW N ON THE PLANS (
4'MI
N)
C C

4" MI
N 1/
2" R
THICKNESS
1/
2" R 1.
5%

C
C

C
C

C
C
2" W EAKENED
PLANE JOI NT

NON-CONTI
GUOUS

C WI
DTH AS SHOW N ON THE PLANS (
4'MI
N)
C

4" MI
N 1/
2" R
THICKNESS
1/
2" R C1.
5%

C
C
C

C
C

2" W EAKENED
PLANE JOI
NT

CONTI
GUOUS

NOTES:

1. CONCRETE SHALL BE 520-C-2500.

2. SEE JOI
NT DETAI
L DRAW I
NGS SDG-109 AND G-10.

3. SI
DEW ALK SHALL MAI
NTAI
N A MI
NIMUM CLEAR W I
DTH OF 4'OF TRAVEL FROM ANY OBSTRUCTI
ON.

4. ALL HI
STORICAL STAMPS /I
MPRESSIONS (
STREET NAME,CONTRACTOR NAME,AND/
OR DATE)
SHALL BE PRESERVED PER SDG-115.

5. FOR DESIGNATED URBANIZED COMMUNI


TIES,SI
DEW ALK DESI
GN (
SCORING PATTERN,COLOR,
TEXTURE)SHALL BE I
N CONFORMANCE W I
TH HISTORIC DESI
GN ON ADJACENT PROPERTI
ES. LEGEND ON PLANS

RECOMMENDED BY THE CI
TY OF SAN DI
EGO
REVI
SION BY APPROVED DATE
STANDARDS COMMITTEE
CI
TY OF SAN DI
EGO - STANDARD DRAW I
NG
ORI
GINAL* KA J.NAGELVOORT 01/
12

UPDATED RB J.NAGELVOORT 10/


15
2/
25/
16
COORDI
NATOR R.
C.E.56523 DATE
UPDATED HM J.NAGELVOORT 02/
16
SI
DEW ALK -TYPI
CAL SECTI
ONS DRAW I
NG
SDG-
155
NUMBER
EXI
STI
NG SCORE MARK C AREA TO BE REMOVED EXI
STI
NG JOI
NT
C
5'
,OR FROM
JOI
NT TO JOINT I
N PANEL

C
W HI
CHEVER IS LESS

C
CUT
SI
DEW ALK PLAN

EXI
STI
NG SCORE MARK
EXI
STI
NG JOI
NT
C AREA TO BE REMOVED
C C
C
CUT

SI
DEW ALK SECTI
ON

AREA TO BE REMOVED EXI


STI
NG JOI
NT OR EDGE
C C 30" MIN
C C
5'
,OR FROM FROM EXISTING JOI
NT
JOI
NT TO JOINT I
N PANEL OR EDGE OF CURB

C
W HI
CHEVER IS LESS

C CURB LI
NE
C

GUTTER LI
NE
CUT

CUT

CURB PLAN
EXI
STI
NG JOI
NT OR EDGE
C AREA TO BE REMOVED C 5',MIN FROM
EXI
STI
NG SCORE MARK C C
5'
,MI
N EXISTING JOINT OR
EDGE OF PAVEMENT
C
C

CUT
CUT

REMAI
NING EDGE TO BE
SMOOTH AND TRUE W I
TH
PAVEMENT SECTI
ON NO SHATTER

11/
2" MI
N
C
C

NOTES: CONCRETE
TO BE REMOVED
1. SI
DEW ALK CROSS SLOPE SHALL BE 1.
5%.
C
C
C

2. W HEN DI
STANCE FROM "AREA TO BE REMOVED" TO EXISI
TNG JOI
NT,EDGE OR
SCORE MARK IS LESS THAN MINI
MUM SHOW N."AREA TO BE REMOVED" SHALL SAW CUT
BE EXTENDED TO JOINT,EDGE OR SCORE MARK.

3. ALL HI
STORICAL STAMPS / I
MPRESSIONS (
STREET NAME,CONTRACTOR NAME,AND DATE)
SHALL BE PRESERVED PER SDG-115.

SECTION
4. FOR DESIGNATED URBANIZED COMMUNI
TIES,SI
DEW ALK DESI
GN (
SCORING PATTERN,COLOR,
SHOW I
NG CUT
TEXTURE)SHALL BE I
N CONFORMANCE W I
TH HISTORIC DESI
GN ON ADJACENT PROPERTI
ES.

RECOMMENDED BY THE CI
TY OF SAN DI
EGO
REVI
SION BY APPROVED DATE
STANDARDS COMMITTEE
CI
TY OF SAN DI
EGO - STANDARD DRAW I
NG
ORI
GINAL* KA J.NAGELVOORT 01/
12

2/
25/
16
UPDATED RB J.NAGELVOORT 10/
15
CONCRETE CURB,GUTTER, COORDI
NATOR R.
C.E.56523 DATE
UPDATED HM J.NAGELVOORT 02/
16
SI
DEW ALK AND PAVEM ENT DRAW I
NG
SDG-
156
REM OVAL AND REPLACEM ENT NUMBER
PCR PCR

/
4(TYP)

US
DI
RA
R
A
D
IU
S

A
PCR

PCR
C
C
A

SEE NOTE 4

PLAN CONTACT JOI


NTS PER
G-10 W HEN SEPARATE
POURS ARE MADE

10'
UNLESS OTHERW I
SE
SHOW N ON PLANS 1/
2" R TYPI
CAL
C
C

7"
C

ING
1.
5% C 5%
1. TOP OF PAV
C
C

SECTI
ON A-A

NOTES:

1. CONCRETE SHALL BE 560-C-3250.

2. W EAKENED PLANE JOI


NTS.

3. TYPI
CAL FLOW LI
NES.

4 o = ELEVATI
ONS TO BE SHOW N ON PLANS.

5 RETURN SEGMENTS TO BE 7" THI


CK.

6. CURB BETW EEN POI


NT OF CURB RETURNS (
PCR)SHALL BE A MONOLI
THI
C POUR W I
TH
THE CROSS GUTTER.

7. I
N ALL CASES SUBGRADE SHALL BE COMPACTED TO 95% MI
N RELATI
VE
COMPACTION TO A DEPTH OF 12"

8. ALL HI
STORICAL STAMPS /I
MPRESSIONS (
STREET NAME,CONTRACTOR NAME,AND DATE)
SHALL BE PRESERVED PER SDG-115. LEGEND ON PLANS

RECOMMENDED BY THE CI
TY OF SAN DI
EGO
REVI
SION BY APPROVED DATE
STANDARDS COMMITTEE
CI
TY OF SAN DI
EGO - STANDARD DRAW I
NG
ORI
GINAL* KA J.NAGELVOORT 01/
12

2/
25/
16
UPDATED AR J.NAGELVOORT 10/
15
COORDI
NATOR R.
C.E.56523 DATE
UPDATED HM J.NAGELVOORT 02/
16
CROSS GUTTER DRAW I
NG
SDG-
157
NUMBER
TRANSI
TIONAL CROSS SLOPE OF GUTTER
TO MATCH CROSS GUTTER SLOPE

C
L
CURB CURB

C
C

C
C

C
GUTTER CROSS
SLOPE

C 5' C 10' C 5'


C C C

CROSS GUTTER
C

C
A A

SLOPE
C
PLAN

C 10'
C

1/
2" R TYP
7" UNLESS OTHERW I
SE
C

SHOW N ON PLANS 1.
5% 1.
5%
C
C
C

SECTI
ON A-A

NOTES:

1. CROSS GUTTER TO BE CONSTRUCTED W HERE THE DRAI


NAGE I
S CARRI
ED ACROSS STREET.

2. MI
NIMUM ALLOW ABLE CROSS GUTTER SLOPE I
S 0.
5%.

3. CONCRETE SHALL BE 560-C-3250.

4 I
N ALL CASES SUBGRADE SHALL BE COMPACTED TO 95% MI
N RELATI
VE
COMPACTION TO A DEPTH OF 12".
LEGEND ON PLANS
5 ALL HI
STORICAL STAMPS / I
MPRESSIONS (
STREET NAME,CONTRACTOR NAME,AND DATE)
SHALL BE PRESERVED PER SDG-115.

RECOMMENDED BY THE CI
TY OF SAN DI
EGO
REVI
SION BY APPROVED DATE
STANDARDS COMMITTEE
CI
TY OF SAN DI
EGO - STANDARD DRAW I
NG
ORI
GINAL* KA J.NAGELVOORT 01/
12

UPDATED HM J.NAGELVOORT 02/


16
2/
25/
16
COORDI
NATOR R.
C.E.56523 DATE

MI
D-BLOCK CROSS GUTTER DRAW I
NG
SDG-
158
NUMBER
P/
L,RW OR
PLACE 1/
4INCH EXPANSI
ON JOI
NT FI
LLER MATERI
AL C A
EDGE OF
C
C EASEMENT

C
2:
1TRANSI
TION
1.
5% 1.
5% 1.
5% C

4'-6"
PATH OF TRAVEL

C
C
C

C
C
C
1.

SIDEWALK
5%

9.67%
5%
1.

4'-0"
C
C

5'-6"
1.

C
5%
1.
5% 5%
1. 1.
5%

C
C
C

C
C
C
C
DEPRESSED CURB C

C C
CURB LI
NE C GUTTER

C C C
C
3'
-0" C A 3'
-0"
MIN MIN
PLAN

C DRI
VEW AY CURB OPENI
NG
C

C DRI
VEW AY W I
DTH
C
SHOW N ON PLANS

BOTTOM OF CURB ELEVATI


ON
12" R TYP

EDGE OF SI
DEW ALK
C

1.
5%
C

C 9.
67%
C
C

C 1" ABOVE GUTTER


C

5 1/
2" RESI
DENTAL
C

7 1/
2" COMMERICAL
C

SECTION A-A
C
NOTES: TYPE - A 1/
2" R
1. NO CONCRETE SHALL BE PLACED UNTI
L FORMS AND SUBGRADE ARE I
NSPECTED.

2. CONCRETE SHALL BE 520-C-2500 FOR RESI


DENTI
AL USE;560-C-3250 FOR COMMERCI
AL USE.

3. SEE STANDARD DRAW I


NGS SDG-164 AND G-15 FOR W I
DTH AND LOCATI
ON REQUI
REMENTS.

4. SEE SDG-151AND G-10 FOR CURB AND JOI


NT DETAI
LS.

5. DRI
VEW AY SHALL BE CONTI
NUOUS POUR FROM BACK OF CURB TO PROPERTY LI
NE.

6. METER BOXES SHALL NOT BE LOCATED W I


THI
N DRI
VEW AY.

7. DRI
VEW AY I
N EXCESS OF 150'I
N LENGTH FROM CURB FACE SHALL HAVE 7 1/
2" MI
NIMUM CONCRETE THI
CKNESS.

8. ALL HI
STORICAL STAMPS /I
MPRESSIONS (
STREET NAME,CONTRACTOR NAME,AND DATE)
SHALL BE PRESERVED PER SDG-115.

9. FOR DESIGNATED URBANIZED COMMUNI


TIES,SI
DEW ALK DESI
GN (
SCORING PATTERN,COLOR,
TEXTURE)SHALL BE I
N CONFORMANCE W I
TH HISTORIC DESI
GN ON ADJACENT PROPERTI
ES. SHEET 1OF 2

RECOMMENDED BY THE CI
TY OF SAN DI
EGO
REVI
SION BY APPROVED DATE
STANDARDS COMMITTEE
CI
TY OF SAN DI
EGO - STANDARD DRAW I
NG
ORI
GINAL* KA J.NAGELVOORT 01/
12

2/
23/
16
UPDATED FC J.NAGELVOORT 10/
15
COORDI
NATOR R.
C.E.56523 DATE
UPDATED FC J.NAGELVOORT 2/
16 CONCRETE DRI
VEW AY
DRAW I
NG
(
CONTIGUOUS SIDEW ALK) SDG-
159
NUMBER
P/
L,RW OR
EDGE OF
C
EASEMENT

3'
2:
1 TRANSI
TION

1.5%
1.

4'

5%
5%

1.
8.
% 33
3 M
.3 AX %
8 AX

SIDEWALK
1.
M

4" MIN
5%

1.5%

1.5%
1.5%

1.5%

5%

1.
9.67%

3'
DEPRESSED CURB

CURB LI
NE GUTTER
3' MI
N 3' MI
N

PLAN
DRI
VEWAY CURB OPENI
NG

DRI
VEWAY WI
DTH

SHOW N ON PLANS

BOTTOM OF CURB
ELEVATI
ON
12" R (TYP)

SI
DEW ALK
2% M AX
1. 9.67%
5% 1" ABOVE
M AX GU TTER

5 1/2" RESI
DENTI
AL
7 1/2" COM M ERCI
AL

SECTION
NOTES: TYPE - B 1/2" R

1. NO CONCRETE SHALL BE PLACED UNTI


L FORMS AND SUBGRADE ARE I
NSPECTED.

2. FOR RESI
DENTIAL USE,CONCRETE SHALL BE 520-C-2500;FOR COMMERCI
AL USE,
CONCRETE SHALL BE 560-C-3250.

3. SEE STANDARD DRAW I


NGS SDG-164 AND G-15 FOR W I
DTH AND LOCATI
ON REQUI
REMENTS.

4. DRI
VEW AY RAMP TO EXTEND TO 10'FROM CURB FACE OR TO RI
GHT-OF-W AY,W HI
CHEVER I
S LESS.(
FOR COMMERCI
AL
USE ONLY).

5. PLACE EXPANSI
ON JOI
NT AT RI
GHT-OF-W AY OR 10'
,W HI
CHEVER I
S LESS.

6. SEE SDG-151AND G-10 FOR CURB AND JOI


NT DETAI
LS.

7. DI
MENSI
ONS SHOW N REFLECT A 6" CURB HEI
GHT.

8. METER BOXES SHALL NOT BE LOCATED W I


THI
N DRI
VEW AY.

9. DRI
VEW AY I
N EXCESS OF 150'I
N LENGTH FROM CURB FACE SHALL HAVE 7 1/
2" MI
NIMUM CONCRETE THI
CKNESS.

10. ALL HI
STORI
CAL STAMPS /
IMPRESSI
ONS (
STREET NAME,CONTRACTOR NAME,AND DATE)SHALL BE PRESERVED PER
SDG-115.

11. FOR DESI


GNATED URBANI
ZED COMMUNITI
ES,SI
DEW ALK DESI
GN (SCORI
NG PATTERN,COLOR,TEXTURE)SHALL SHEET 2 OF 2

BE I
N CONFORMANCE W I
TH HI
STORI
C DESIGN ON ADJACENT PROPERTIES.
RECOMMENDED BY THE CI
TY OF SAN DI
EGO
REVI
SION BY APPROVED DATE
STANDARDS COMMITTEE
CI
TY OF SAN DI
EGO - STANDARD DRAW I
NG
ORI
GINAL* KA J.NAGELVOORT 01/
12

2/
23/
16
UPDATED FC J.NAGELVOORT 10/
15
COORDI
NATOR R.
C.E.56523 DATE
UPDATED FC J.NAGELVOORT 2/
16 CONCRETE DRI
VEW AY
DRAW I
NG
(
CONTIGUOUS SIDEW ALK) SDG-
159
NUMBER
PLACE 1/
4INCH EXPANSI
ON JOI
NT FI
LLER MATERI
AL P/L,RW OR
2:
1TRANSI
TION
C A
C
EDGE OF
EASEMENT

C
C

C
SIDEWALK
1.5%

1.5%

1.5%

4'-0"
C

C
C

C
PARKWAY

9.67%
5'-0"

5'-6"
C
C

C
C
DEPRESSED CURB C

C C
C GUTTER
CURB LI
NE
C 3'
-0"
C C A C 3'
-0"
C
MIN PLAN MIN

C DRI
VEW AY CURB OPENI
NG
C

C DRI
VEW AY W I
DTH
C
SHOW N ON PLANS

BOTTOM OF CURB
ELEVATI
ON 12" R TYP

EDGE OF SI
DEW ALK
C

1.
C

5%
C 9.
67%
C
1"
C

C ABOVE GUTTER
C

5 1/
2"
C

C
NOTES: SECTI
ON A-A 1/
2" R
1. NO CONCRETE SHALL BE PLACED UNTI
L FORMS AND SUBGRADE ARE I
NSPECTED.

2. CONCRETE SHALL BE 520-C-2500.

3. SEE STANDARD DRAW I


NGS SDG-164 AND G-15 FOR W I
DTH AND LOCATI
ON REQUI
REMENTS.

4. SEE SDG-151AND G-10 FOR CURB AND JOI


NT DETAI
LS.

5. DRI
VEW AY SHALL BE CONTI
NUOUS POUR FROM BACK OF CURB TO PROPERTY LI
NE.

6. METER BOXES SHALL NOT BE LOCATED W I


THI
N DRI
VEW AY.

7. DRI
VEW AY I
N EXCESS OF 150'I
N LENGTH FROM CURB FACE SHALL HAVE 7" MI
NIMUM CONCRETE THI
CKNESS.

8. ALL HI
STORICAL STAMPS /I
MPRESSIONS (
STREET NAME,CONTRACTOR NAME,DATE)
SHALL BE PRESERVED PER SDG-115.

9. FOR DESIGNATED URBANIZED COMMUNI


TIES,SI
DEW ALK DESI
GN (
SCORING PATTERN,COLOR,
TEXTURE)SHALL BE I
N CONFORMANCE W I
TH HISTORIC DESI
GN ON ADJACENT PROPERTI
ES.

RECOMMENDED BY THE CI
TY OF SAN DI
EGO
REVI
SION BY APPROVED DATE
STANDARDS COMMITTEE
CI
TY OF SAN DI
EGO - STANDARD DRAW I
NG
ORI
GINAL* KA J.NAGELVOORT 01/
12

10/
15
2/
25/
16
UPDATED BD J.NAGELVOORT
COORDI
NATOR R.
C.E.56523 DATE
UPDATED FC J.NAGELVOORT 02/
16 CONCRETE DRI
VEW AY
DRAW I
NG
(
NON-
CONTI
GUOUS SIDEW ALK) SDG-
160
NUMBER
NON-CONTI
GUOUS SI
DEW ALK C A

C
R/
W

1.5%

1.5%
4' MIN

C
C
C

9.67%
CONTI
GUOUS SI
DEW ALK
5'-0" MIN

C
C

C
DEPRESSED CURB C

C
CURB LI
NE C GUTTER

C C
C C
3'
-0" C A 3'
-0"
MIN MIN
PLAN

C DRI
VEW AY CURB OPENI
NG
C

C DRI
VEW AY W I
DTH
C
SHOW N ON PLANS

BOTTOM OF CURB
ELEVATI
ON 12" R TYP

EDGE OF SI
DEW ALK
C

1.
5%
C

C
1"
C

C ABOVE GUTTER
C

5 1/
2"
C

SECTI
ON A-A C
NOTES:
1/
2" R
1. NO CONCRETE SHALL BE PLACED UNTI
L FORMS AND SUBGRADE ARE I
NSPECTED.

2. CONCRETE SHALL BE 520-C-2500.

3. SEE STANDARD DRAW I


NG SDG-164 FOR W I
DTH AND LOCATI
ON REQUI
REMENTS.

4. DRI
VEW AY RAMP TO EXTEND TO 10'FROM CURB FACE OR TO PROPERTY LI
NE W HI
CHEVER
I
S LESS.(FOR COMMERCIAL DRI
VEW AYS ONLY)

5. SEE SDG-151AND G-10 FOR CURB AND JOI


NT DETAI
LS.

6. METER BOXES SHALL NOT BE LOCATED W I


THI
N DRI
VEW AY.

7. ALL HI
STORICAL STAMPS /I
MPRESSIONS (
STREET NAME,CONTRACTOR NAME,AND DATE)
SHALL BE PRESERVED PER SDG-115.

8. FOR DESIGNATED URBANIZED COMMUNI


TIES,SI
DEW ALK DESI
GN (
SCORING PATTER,COLOR,
TEXTURE)SHALL BE I
N CONFORMANCE W I
TH HISTORIC DESI
GN ADJACENT PROPERTI
ES.

RECOMMENDED BY THE CI
TY OF SAN DI
EGO
REVI
SION BY APPROVED DATE
STANDARDS COMMITTEE
CI
TY OF SAN DI
EGO - STANDARD DRAW I
NG
ORI
GINAL* KA J.NAGELVOORT 01/
12

2/
25/
16
UPDATED RB J.NAGELVOORT 10/
15
RESI
DENTI
AL COORDI
NATOR R.
C.E.56523 DATE
UPDATED HM J.NAGELVOORT 02/
16
CONCRETE DRI
VEW AY DRAW I
NG

(
PARKW AY LESS THAN 10'I
N DEPTH) SDG-
161
NUMBER
RETAI
NING CURB I
F
SPECI
FIED OR REQUI
RED
PRI
VATE DRI
VEW AY
A C

C
R/
W

C
SIDEWALK

1.5%

1.5%

1.5%
4' MIN

8.
33% C 8.
33%
C
MAX MAX

C
C

C
C
C
C
C
CURB
C

LI
NE C
DEPRESSED CURB
C

C
C
GUTTER

TOOLED JOI
NT C A
TOOLED JOI
NT
PLAN

PLAN

C DRI
VEW AY CURB OPENI
NG
C

Y C DRI
VEW AY W I
DTH Y C
C C
SEE SHOW N ON PLANS SEE
TABLE A TABLE A

C
CX

BOTTOM OF CURB
ELEVATI
ON 12" R TYP

RETAI
NING CURB I
F
SPECI
FIED OR REQUI
RED EDGE OF SI
DEW ALK

C
1.
5%
C
C

C
1"
C ABOVE GUTTER
C

C
C

5-1/
2" RESI
DENTI
AL
7-1/
2" COMMERCIAL C
SECTI
ON A-A

NOTES:

1. NO CONCRETE SHALL BE PLACED UNTI


L FORMS AND SUBGRADE ARE I
NSPECTED.

2. CONCRETE SHALL BE 520-C-2500 FOR RESI


DENTI
AL USE;560-C-3250 FOR COMMERCI
AL USE.

3. SEE STANDARD DRAW I


NG SDG-164 FOR W I
DTH AND LOCATI
ON REQUI
REMENTS.

4. SEE SDG-151AND G-10 FOR CURB AND JOI


NT DETAI
LS.

5. ALL HI
STORICAL STAMPS /I
MPRESSIONS (
STREET NAME,CONTRACTOR NAME,AND DATE)
SHALL BE PRESERVED PER SDG-115.

6. FOR DESIGNATED URBANIZED COMMUNI


TIES,SI
DEW ALK DESI
GN (
SCORING PATTERN,COLOR,
TEXTURE)SHALL BE I
N CONFORMANCE W I
TH HISTORIC DESI
GN ON ADJACENT PROPERTI
ES.

RECOMMENDED BY THE CI
TY OF SAN DI
EGO
REVI
SION BY APPROVED DATE
STANDARDS COMMITTEE
CI
TY OF SAN DI
EGO - STANDARD DRAW I
NG
ORI
GINAL* KA J.NAGELVOORT 01/
12

UPDATED RB J.NAGELVOORT 10/


15
2/
23/
16
COORDI
NATOR R.
C.E.56523 DATE
UPDATED FC J.NAGELVOORT 02/
16 CONCRETE DRI
VEW AY
(
FOR CONFI
NED RI
GHT-
OF-
W AY) DRAW I
NG
SDG-
162
NUMBER
C A

NON-CONTI
GUOUS
SI
DEW ALK
C DRI
VEW AY W I
DTH SHOW N
C
PROPERTY LI
NE
ON PLANS

C
C
C

C
C
2 TO 1TRANSI
TION

SLOPE
SLOPE
4'-6"

1.5%
1.5%

E
%

P
5
.

C
1
LO

c
S

6"
10'

c
c
'-

4
C

N
I CONTI
GUOUS SI
DEW ALK

M
c
5% E
C
1 1.
I
NSTALL /
4" EXPANSI
ON OP

SLOPE
SL
c
JOI
NT FI
LL MATERIAL

1.5%
BETW EEN SLABS

DEPRESSED CURB

c
C

C
C

C
CURB GUTTER
C

3'
-0" 3'
-0" PLAN C 3'
-0" C 3'
-0"
C
C C
C C
A C

MIN
C

MIN

C CURB OPENI
NG = DRI
VEW AY W I
DTH + 12'
C

C DRI
VEW AY W I
DTH SHOW N
C
12"R (
TYP)
ON PLANS
DEPRESSED CURB
C

C
C
C

ELEVATI
ON 12"R (
TYP)
BOTTOM OF CURB

EDGE OF SI
DEW ALK C

7 1/
2" 1.
5% SLOPE
C
C

1" ABOVE GUTTER


C
C

C
C

SECTI
ON A-A 1
2" R
NOTES:

LEGEND ON PLANS
1. CONCRETE SHALL NOT BE PLACED UNTI
L FORMS AND SUBGRADE ARE I
NSPECTED
AND APPROVED BY THE RESI DENT ENGI
NEER.
2. CONCRETE SHALL BE 560-C-3250.
3. SEE STANDARD DRAW I
NG SDG-164 FOR W I
DTH AND LOCATI
ON REQUI
REMENTS.
4. SEE SDG-151AND G-10 FOR CURB AND JOI
NT DETAI
LS.
CONTI
GUOUS
C
5. METER BOXES SHALL NOT BE LOCATED W I
THI
N DRI
VEW AY.SEE W S-03. L
DRI
VEW AY
6. DRI
VEW AY I
N EXCESS OF 150'I
N LENGTH FROM CURB FACE SHALL
BE A MINI
MUM OF 7" PCC.
7. DRI
VEW AY SHALL BE CONTI
NUOUS POUR FROM BACK OF CURB TO PROPERTY LI
NE.
8. ALL HI
STORI
CAL STAMPS /I
MPRESSI
ONS (
STREET NAME,CONTRACTOR NAME,
AND DATE)SHALL BE PRESERVED PER SDG-115. NON-CONTI
GUOUS
C
L
9. FOR DESI
GNATED URBANI
ZED COMMUNI
TIES,SI
DEW ALK DESI
GN (
SCORI
NG PATTERN, DRI
VEW AY

COLOR,TEXTURE)SHALL BE I
N CONFORMANCE W I
TH HI
STORI
C DESI
GN ON ADJACENT
PROPERTI
ES.

RECOMMENDED BY THE CI
TY OF SAN DI
EGO
REVI
SION BY APPROVED DATE
STANDARDS COMMITTEE
CI
TY OF SAN DI
EGO - STANDARD DRAW I
NG
ORI
GINAL M.
V.R 5/
92

NOTES SM A.OSKOUI 12/


03 & 8/
06 2/
25/
16
UPDATE FC A.OSKOUI 12/
06 COORDI
NATOR R.
C.E.56523 DATE
REPLACED KA J.NAGELVOORT 01/
12 COM M ERCI
AL CONCRETE
SDG-114
DRAW I
NG
UPDATED RB J.NAGELVOORT 10/
15
DRI
VEW AY NUMBER
SDG-
163
UPDATED HM J.NAGELVOORT 02/
16
ALLEY

OBSTRUCTI
ON

C
3'MI
N FROM
ANY DRI
VEW AY C
6'MI
N FROM ALLEY OR DRAI
NAGE OUTLET

C
C

C
DRIVEWAY WIDTH
CURB OPENING
DRI
VEW AY
RESI
DENTI
AL DRI
VEW AY W I
DTH--(
12'MI
N,25'MAX)

C
C
45'LENGTH OF FULL-HEI
GHT CURB BETW EEN DRI
VEW AY SERVI
NG
C

SAME PREMI
SES.
PROPERTY LINE

C
C

C
DRIVEWAY WIDTH
CURB OPENING

DRI
VEW AY
COMMERCI
AL DRI
VEW AY W I
DTH--(
14'MI
N,30'MAX)

3'MI
N
C
C

C
C

OBSTRUCTI
ON

CURB RADI
US
C
CURB C
NOTES:
CURB RADIUS

1. CURB OPENI
NGS,EXCEPT FOR JOI
NT-USE DRI
VEW AYS AND DRI
VEW AYS ON
LOTS HAVI
NG 21'- FRONTAGE OR LESS,SHALL BE LOCATED AT LEAST 3'
FROM THE SI
DE PROPERTY LINE EXTENDED.

5
-1 2. NOT MORE THAN 40% OF THE PROPERTY FRONTAGE ON RESI DENTI
AL
G
G LOTS,NOR 60% OF THE PROPERTY FRONTAGE ON COMMERCI AL LOTS
N
I
W MAY BE ALLOCATED FOR DRIVEW AY CURB OPENINGS,EXCEPT THAT LOTS
A
R HAVING FRONTAGE OF LESS THAN 45'ARE ENTITLED TO ONE 12'
D
E DRI
VEW AY.(
18'CURB OPENI
NG)
.
E
S
C
3. ALL DRI
VEW AYS AND CURB OPENI NGS SHALL BE A MI
NIMUM OF 3'FROM
ANY OBSTRUCTION,i.
e.,POLES,HYDRANTS,ETC.

STREET 4. NO PORTI ON OF ANY DRIVEW AY SHALL BE ALLOW ED ACROSS A LI NE


EXTENDI NG NORMAL TO THE ROADW AY FROM THE FRONT OF THE
PROPERTY,CORNER OF THE PROPERTY,EXCEPT THAT JOI NT-USE
DRIVEW AYS MAY BE PERMI
TTED IN SPECI AL I
NSTANCES W HERE W RITTEN
APPROVAL OF BOTH PROPERTY OW NERS I S FILED W I
TH THE CITY.

RECOMMENDED BY THE CI
TY OF SAN DI
EGO
REVI
SION BY APPROVED DATE
STANDARDS COMMITTEE
CI
TY OF SAN DI
EGO - STANDARD DRAW I
NG
*ORI
GINAL KA J.NAGELVOORT 01/
12

UPDATED AB J.NAGELVOORT 02/


16
2/
25/
16
COORDI
NATOR R.
C.E.56523 DATE
DRI
VEW AY LOCATI
ON
DRAW I
NG
AND W I
DTH REQUI
REM ENTS NUMBER
SDG-
164
4"
3"

lYPE A
I· 13"

lYPE 8
·I
171 l_ ---1 r--4·
~-~./---.--
"/ZZZ>V
1· 2H + 6" .1 tl. 8" ·I
lYPE D
lYPE C
1'-8"
R=1"

R=1"

Level Line

1'-4"
~-·_____:_______.:-!•
I
1 =:..-
I 2'-2"
I---•- - - - = - - - - = - - - - - - 1 •
IT 'N
TYPE E TYPEF
(MOUNTABLE DIKE) (MOUNTABLE DIKE)

. . . SLOPE END OF DIKE 1,1


· '7 WHEN NOT JOINING APPROX. DIKE QUANTITIES
OTHER IMPROVEMENTS
TYPE REQD PER LIN. FT.

ALL lYPES - SIDE VIEW A 0.0250 TON


B 0.0375 TON
C-6" 0.0375 TON
C-8" 0.0583 TON
NOTES: C-9" 0.0702 TON
1. DIKES SHALL BE PLACED ON A 2" SECTION OF A.C. SURFACING, D 0.0062 TON
EXTENDING THROUGHOUT THE WIDTH OF THE DIKE. E 0.0407 TON
2. PG-70-1 0 GRADE ASPHALT TO BE USED FOR ALL DIKES. F 0.0623 TON
3. SHAPE AND COMPACT DIKES WITH AN EXTRUSION MACHINE OR
OTHER EQUIPMENT CAPABLE OF SHAPING AND COMPACTING THE
MATERIAL TO THE REQUIRED CROSS-SECTION. LEGEND ON PLANS

REVISION BY APPROVED DATE RECOMMENDED BY THE SAN DIEGO


SAN DIEGO REGIONAL STANDARD DRAWING REGIONAL STANDARDS COMMITTEE
ORIGINAL KERCHEVAL 12/75
ADD METRIC T. STANTON 03/03 7(26(2012

T. STANTON 04/06
DIKES - ASPHALT CONCRETE DATE
MR/CV 11/11 DRAW1NG
NUMBER G-5
EXPANSION JOINT FILLER MATERIAL

1/8" R 1/8" R
.. . ..
. ~ ·~

·.....
T
. . . •
.....

-l ~ 11/2" (PAVEMENT)
I 4 MIN - 1/2" MAX (SIDEWALK)
n
1/2" (#4) x 24" SMOOTH,
GREASED OR OILED BAR,
30" ON CENTER

EXPANSION JOINT CONTACT JOINT

PREFORMED JOINT FILLER


1/8" R
. . . . . . . ·. . . : . , ..
.. ·.... : .
:
. .. : . ... ·.
. ··•
. ...

·.·· .....
-l f----1/4" .: :· ... -~ ..... ~· .... ~- ... ~

WEAKENED PLANE JOINT WEAKENED PLANE JOINT


CURB AND SIDEWALK GUTTER AND CONCRETE PAVEMENT

1-1/2"
1/8"
.
•.·· .·
.
... :
.
.. · .•.. . .
·.. · ...·
... : .....

KEYED JOINT

REVISION BY APPROVED DATE RECOMMENDED BY THE SAN DIEGO


SAN DIEGO REGIONAL STANDARD DRAWING REGIONAL STANDARDS COMMITTEE
ORIGINAL PARKINSON 02/95
ADD METRIC T. STANTON 03/03 7/26/2012

T. STANTON 04/06
CONCRETE JOINT DETAILS DATE
DRAWING
NUMBER G-10
w

-~--i_l________
I 6'
REQUIREMENT 1
NO PORTION OF ANY CURB OPENING SHALL BE PERMmED
WITHIN 6' OF THE INTERSECTION OF THE PROLONGED
PROPERTY LINES AND THE CURB SHOWN BY ARC A.

CURB LINE

w
:z:
:::J

REQUIREMENT 2
NO PORTION OF ANY CURB OPENING SHALL BE PERMmED
IN THE CURB RETURN WHERE THE RADIUS OF CURB IS 25'
OR LESS, AS SHOWN BY ARC B.
CURB LINE

REQUIREMENT 3
ON ALL CURB RETURNS WHERE THE RADIUS IS MORE THAN
25', CURB OPENINGS MAY ENCROACH UPON EACH END OF THE
RETURN A DISTANCE EQUAL TO 12.5% (OR 1/8) OF THE TOTAL
LENGTH OF THE ARC ON THE CURB RETURN, THUS LEAVING AT
CURB LINE LEAST 75% (or 3/4) OF THE LENGTH OF ARC ON THE RETURN
FACE FREE FROM DRIVEWAY ENCROACHMENT, PROVIDED
12.5X (OR 1/8) OF------1 REQUIREMENT 1 IS MET.
TOTAL LENGTH OF ARC

REQUIREMENT 4
NO PORTION OF ANY CURB OPENING SHALL BE PERMITTED
IN THE CURB RETURN WHERE A SEPARATE TURNING
MOVEMENT IS PROVIDED, AS SHOWN BY ARC C.

CURB LINE

REVISION BY APPROVED DATE RECOMMENDED BY THE SAN DIEGO


SAN DIEGO REGIONAL STANDARD DRAWING REGIONAL STANDARDS COMMITTEE
ORIGINAL KERCHEVAL 12/75
ADD METRIC T. STANTON 03/03
7(26(2012

REVIEWED T. STANTON 04/06 DRIVEWAY LOCATION - ADJACENT TO DATE


UPDATED MR MR/CV 02/12 DRAW1NG
CURB RETURNS AND STREET LINES NUMBER G-15
THICKNESS SHOWN -
ON PLANS
CONTACT JOINT~
1/2" R "'- 1/2" R

~~~~~~------~--~~~~~--~~~,
~T 20' MAX.
10' MIN.
PAVEMENT WIDTH = 40' OR LES

SECTION

:
WEAKENED PLANE JOINTS

CONTACT JOINTS ) lI io

TRANSVERSE CONTACT JOINfs


BE CONSTRUCTED AT END ~F POUR
SHALL~

''\.....p<PANSION
. JOINTS
II SHALL BE
CONSTRUCTED AT LOCATIONS SHOWN
ON PLANS. :1

PLAN

NOTES:
1. CONCRETE SHALL BE 560-C-3250.
2. SEE STANDARD DRAWING G-10 FOR JOINT DETAILS.
3. ADJUST 15' INTERVAL BETWEEN TRANSVERSE JOINTS TO MATCH ADJACENT EXISTING IMPROVEMENTS.

REVISION BY APPROVED DATE RECOMMENDED BY THE SAN DIEGO


SAN DIEGO REGIONAL STANDARD DRAWING REGI?NAL~S COMMITTEE
ORIGINAL KERCHEVAL 12/75 ~
rA-DD--M8-R-IC+-+T-.-~-AN_ffi_N+-03~/0-3r-------------------------------------_,l'~~7~ ~z6 aO~

REVIEWED T. STANffiN 04/06 CONCRETE PAVEMENT CHAIRPERSON R.C.E. 19246 DATE

UPDATED MR MR/CV 03/12 WIDTH 40' OR LESS DRAW1NG


G-18
NUMBER
THICKNESS SHOWN
ON PLANS

1/2" R 1/2" R

11' 11' 20' MAX


10' MIN
PAVEMENT WIDTH = 62' OR LESS, BUT MORE THAN 40'

SECTION

i.n

CONTACT JOINTS i.n

i.n

EXPANSION JOINTS sJu. BE CONSTRUCTED


AT LOCATIONS SHOWN ON PLANS.
I

PLAN

NOTES:
1. CONCRETE SHALL BE 560-C-3250.
2. SEE STANDARD DRAWING G-10 FOR JOINT DETAILS.
3. ADJUST 15' INTERVAL BETWEEN TRANSVERSE JOINTS TO MATCH ADJACENT EXISTING IMPROVEMENTS.

REVISION BY APPROVED DATE RECOMMENDED BY THE SAN DIEGO


SAN DIEGO REGIONAL STANDARD DRAWING REGIONAL STANDARDS COMMITTEE
ORIGINAL KERCHEVAL 12/75
ADD METRIC T. STANTON 03/03 7(26(2012

REVIEWED T. STANTON 04/06 CONCRETE PAVEMENT DATE


UPDATED MR MR/CV 03/12 DRAW1NG
WIDTH 40' TO 62' NUMBER G-19
1/2" R

PAVEMENT WIDTH = 69' OR LESS, BUT MORE THAN 53'

SECTION

WEAKENED PLANE JOINTS

TRANSVERSE CONTACT
JOINTS SHALL BE
CONSTRUCJED AT
END OF POUR

EXPANSION JOINTS SHALL BE CONSTRUCTED


AT LOCATIONS SHO ON PLANS

PLAN

NOTES:
1. CONCRETE SHALL BE 560-C-3250.
2. SEE STANDARD DRAWING G-1 0 FOR JOINT DETAILS.
3. ADJUST 15' INTERVAL BETWEEN TRANSVERSE JOINTS TO MATCH ADJACENT EXISTING IMPROVEMENTS.

REVISION BY APPROVED DATE RECOMMENDED BY THE SAN DIEGO


SAN DIEGO REGIONAL STANDARD DRAWING REGIONAL STANDARDS COMMITTEE
ORIGINAL KERCHEVAL 12/75
ADD METRIC T. STANTON 03/03
7(26(2012

REVIEWED T. STANTON 04/06 DATE


UPDATED MR MR/CV 03/12 DRAW1NG
NUMBER G-20
1/2" R I
I!)
1/2" R

r£:~~;1.:~~·:-..:!~a~~/~~~.. ~
I. t PAVEMENT WI~TH ~ 40' OR LESS .I
SECTION

~WEAKENED PlANE JOINTS~ ~


,--GONTACT JOINTS)-~

\ TRAVERSE CONTACT
'-~~WsTRa~~rb ~f
END OF POUR

\EXPANSION JOINTS SHALL BE C~NSTRUCTED AT LOCATIONS J


SHOWN ON PLANS I
PLAN

NOTES:
1. CONCRETE SHALL BE 560-C-3250.
2. SEE STANDARD DRAWING G-1 0 FOR JOINT DETAILS.
3. ADJUST 15' INTERVAL BETWEEN TRANSVERSE JOINTS TO MATCH ADJACENT EXISTING IMPROVEMENTS.

REVISION BY APPROVED DATE RECOMMENDED BY THE SAN DIEGO


SAN DIEGO REGIONAL STANDARD DRAWING REGI?NAL~S COMMITTEE
ORIGINAL KERCHEVAL 12/75 ~
rA-DD_M_IT_R-IC+-+T-.-~-AN_ffi_N~0-3~/0-3r-------------------------------------_,l'~~7~ ~z6 aO~

REVIEWED T. STANTON 04/06 CONCRETE PAVEMENT ALLEY SECTION, CHAIRPERSON R.C.E. 19246 DATE

UPDATED MR MR/CV 03/12 WIDTH 40' OR LESS DRAW1NG


G-21
NUMBER
~CURB AND GUTIER

-----.- Lt-'---------;-

•<0
...-I

5'-o"

ELEVATION

0000.;. l
\

0.. 0 0 0~
. .,. ..

I· a" ·I
SECTION A-A
LEGEND ON PLANS

L
REVISION By APPROVED DATE RECOMMENDED BY THE SAN DIEGO
SAN DIEGO REGIONAL STANDARD DRAWING REGI?NAL~S COMMITTEE
ORIGINAL KERCHEVAL 12/75 ~
~A-DD_M_IT_R-IC+-+T~o~~~AN~ro~N~0~3~/0~3r--------------------------------------;l'~~~- ~z6 aO~

REVIEWED To STANroN 04/06 CUTOFF WALL ~AIRPERsoN RocoEo 19246 DATE

UPDATED MR MR/CV 03/12 AT END OF PAVEMENT DRAW1NG


G-22
NUMBER
ct
I
WIDTH AS SHOWN ON PLAN

ALLEY PAVEMENT ~

L J
..
..
. ~ . ~- . . .. ·. ~ .. · 1'-6•

3'-0"
6'-o"

• A

ELEVATION

r THICKNESS SHOWN ON PLANS

~--------~----~~
• t
560-C-3250 CONCRETE -~:·.
(0
I

SECTION A-A

LEGEND ON PLANS

I I
REVISION By APPROVED DATE RECOMMENDED BY THE SAN DIEGO
SAN DIEGO REGIONAL STANDARD DRAWING REGI?N~L~S COMMITTEE
ORIGINAL KERCHEVAL 12/75 ~
~~-D-M-Ern--IC+-+T~.~ST~A~-O-N~0-3~/0-3r--------------------------------------;l,~0 ~- ~z6aO~

REVIEWED T. STANTON 04/06 CUTOFF WALL ~AIRPERSON R.C.E. 19246 DATE

UPDATED MR MR/01 03/12 AT END OF ALLEY PAVEMENT DRAW1NG


G-23
NUMBER
~---TRENCH RESURFACING

SLURRY BACKFILL----+-)
. . ..
·
100-E-100

' c - - - - - + - - - PIPE ZONE

NOTES
1. TRENCH RESURFACING SHALL BE DONE ACCORDING TO AGENCY'S REQUIREMENTS.
2. THE SAND USED FOR THE SLURRY BACKFILL SHALL MEET THE REQUIREMENTS
(SUBSECTION 200-1.5.3) LISTED IN THE STANDARD SPECIFICATIONS FOR PUBLIC
WORKS CONSTRUCTION. SLURRY SHALL CURE FOR SEVEN DAYS PRIOR TO TRENCH
RESURFACING.
3. SLURRY BACKFILL SHALL NOT BE USED WHERE IT WILL IMPEDE SUBSURFACE
DRAINAGE.

REVISION BY APPROVED DATE RECOMMENDED BY THE SAN DIEGO


SAN DIEGO REGIONAL STANDARD DRAWING REGIONAL STANDARDS COMMITTEE
ORIGINAL PARKINSON 09/88
ADD METRIC T. STANTON 03/03 7(26(2012

REVIEWED T. STANTON 04/06


SLURRY BACKFILL DATE
UPDATED MR MR/CV 03/12 DRAW1NG
NUMBER G-36
CHAPTER 5
SPRINKLER
IRRIGATION
SYSTEMS
WALL, FENCE OR BUILDING

24" MIN
CLEARANCE

RISER

STAINLESS STEEL HOSE CLAMPS


2 PLACES

ANTI-DRAIN VALVE

#3 OR #4 REBAR WITH
PLASTIC REBAR END CAP

TEE OR ELBOW
FITTING
ELBOW

NIPPLE 3" MIN

NOTES:
1. FITTINGS SHALL BE PVC SCH 40.

2. NIPPLES AND RISERS SHALL BE PVC SCH 80. LEGEND ON PLANS


3. TEFLON TAPE SHALL BE USED ON THREADED CONNECTIONS.

4. CLOSE NIPPLES SHALL NOT BE USED.


SHOW A NUMBER TO~
INDICATE TYPE HEAD u
5. NO FIXED RISERS IN RIGHT-OF-WAY OR WITHIN 10' OF VEHICULAR
OR PEDESTRIAN TRAFFIC.

6. ANTI-DRAIN VALVES SHALL BE INSTALLED UNDER ALL HEADS.

REVISION BY APPROVED DATE RECOMMENDED BY THE CITY OF SAN DIEGO


STANDARDS COMMITTEE
CITY OF SAN DIEGO - STANDARD DRAWING
oil~
ORIGINAL* RH . NAGELVOOR OY12
1/31/2012
COORDINATOR R.C.E. 65271 DATE
SHRUB SPRAY HEAD
DRAWING
ON FIXED RISER NUMBER
SDI-101
SxSxT TEE

STREET ELL

STREET ELL
#3 OR #4 REBAR------<>
WPLASTIC REBAR
END CAP THREADED ELL

PLAN

J - - - - - - - - 2 4" MIN FROM WALLS,--------1


FENCES & BUILDINGS

GEAR DRIVEN SHRUB ROTOR OR IMPACT HEAD


(ADJUST HEAD PERPENDICULAR TO SLOPE)

#3 OR #4 REBAR WITH PLASTIC REBAR


END CAP
STAINLESS STEEL HOSE CLAMPS
(2 PLACES)

ANTI-DRAIN VALVE-
SEE NOTE #5 BELOW

.
(\j

MIN 12" NIPPLE

NOTES:

1. FITIINGS SHALL BE PVC SCH 40.

2. NIPPLES AND RISERS SHALL BE PVC SCH 80.

3. TEFLON TAPE SHALL BE USED ON THREADED ELEVATION


CONNECTIONS.
4. CLOSE NIPPLES SHALL NOT BE USED.

5. ANTI- DRAIN VALVES SHALL BE INSTALLED UNDER


OR IN ALL HEADS. LEGEND ON PLANS

6. NO FIXED RISERS ALLOWED IN RIGHT-OF- WAY OR


WITHIN 10' OF VEHICULAR OR PEDESTRIAN TRAFFIC.
SHOW A NUMBER TO
INDICATE HEAD TYPE
--o
REVISION BY APPROVED DATE RECOMMENDED BY THE Ct1Y OF SAN DIEGO
STANDARDS COMMITTEE
CITY OF SAN DIEGO - STANDARD DRAWING
oil~
ORIGINAL• RH . NAGELVOOR OV12
1/31/2012
COORDINATOR R.C.E. 65271 DATE
ROTOR OR IMPACT HEAD
DRAWING
ON FIXED RISER NUMBER
SDI-102
SxSxT TEE

STREET ELL

STREET ELL

PLAN
1-----24" MIN-----
CLEARANCE

FLUSH IN TURF AREAS


MULCH DEPTH IN SHRUB AREAS

POP-UP
BODY

SHORT
NIPPLE
ANTI-DRAIN VALVE
(FIPT X FIPT)

THREADED ELL

STREET ELL

STREET ELL

12" MIN NIPPLE INSTALLED


AT AN UPWARD ANGLE

ELEVATION
NOTES:
1. FITTINGS SHALL BE PVC SCH 40.

2. NIPPLES AND RISERS SHALL BE PVC SCH 80.

3. TEFLON TAPE SHALL BE USED ON THREADED CONNECTIONS. LEGEND ON PLANS

TO~
4. CLOSE NIPPLES SHALL NOT BE USED.

5. ANTI-DRAIN VALVES SHALL BE INSTALLED UNDER OR IN ALL HEADS. SHOW A NUMBER


INDICATE TYPE HEAD
6. LATERAL DEPTH SHALL BE 18" WHEN 12" POP-UP BODIES ARE USED.

REVISION BY APPROVED DATE RECOMMENDED BY THE CITY OF SAN DIEGO


STANDARDS COMMITIEE
CITY OF SAN DIEGO - STANDARD DRAWING
dl~
ORIGINAL* RH . NAGELVOOR OV12
1/31/2012
COORDINATOR R.C.E. 65271 DATE
ROTOR, SPRAY, OR BUBBLER
DRAWING
POP-UP HEAD NUMBER
SDI-103
~~~3"FROM EDGE
OF ROOTBALL
BUBBLER TUBE ~GREEN FLAT
DRAIN GRATE, FLUSH ~OP OF
TREE MULCH.
BERM

DRILL HOLE IN PERFORATED


ROOTBALL OF TREE BACKFILL MATERIAL PIPE lWICE THE DIAMETER OF
THE LATERAL PIPE.
4" PERFORATED PIPE
RESTING ON BOTTOM OF
PLANT PIT. FILL PIPE FROM
BOTTOM OF PIPE TO
BOTTOM OF ANTI-DRAIN
VALVE WITH 3-8" PEA GRAVEL.
WRAP ENTIRE PERFORATED
PIPE WITH ONE LAYER OF
FILTER FABRIC.

NOTES:
1. FOR BUBBLER LOCATION, REFER TO TREE PLANTING AND STAKING DRAWING.

2. EACH TREE SHALL HAVE A 2" POP-UP HEAD WITH BUBBLER NOZZLE PER SDI-103, AND A FIXED BUBBLER
NOZZLE IN A PERFORATED PIPE.

3. NIPPLES AND RISERS SHALL BE PVC SCH 80.

4. FITTINGS SHALL BE PVC SCH 40.

5. TEFLON TAPE SHALL BE USED ON THREADED CONNECTIONS.

6. CLOSE NIPPLES SHALL NOT BE USED.

7. ANTI-DRAIN VALVES SHALL BE INSTALLED UNDER ALL HEADS.

REVISION BY APPROVED DATE RECOMMENDED BY THE Ct1Y OF SAN DIEGO


STANDARDS COMMITTEE
CITY OF SAN DIEGO - STANDARD DRAWING
oil~
ORIGINAL• RH . NAGELVOOR OV12
1/31/2012
COORDINATOR R.C.E. 65271 DATE

TREE BUBBLER TUBE DRAWING

NUMBER
SDI-104
9" MIN

r
.. ., ·' ' .. .,
., .,
.. ., . -:~

z
~
..
"' . ;.

l
,,
., '
..., ..
... ..

COUPLING 8" NIPPLE TO


ISOLATION VALVE
PLAN
MULCH DEPTH
PER PLAN
• -- --. _----------------------r
. , . '-- - '- - . .' ~. '- - · -~ ~; ~ SEE NOTE 1

1" QUICK COUPLING VALVE

NIPPLE:
(LENGTH TO ADJUST TO GRADE)

COUPLING

NIPPLE:
(4" LONG) -----------------l

90 ELBOW

470-C-2000 CONCRETE THRUST


BLOCK. CONCRETE SHALL NOT --------------------------;~1
EXTEND BEYOND COUPLING, AS
SHOWN C\1::2:
'--------+---+-------,7"-' ------------------ -----------------------------------•--

COUPLING

ELEVATION

NOTES:
1. QUICK COUPLING VALVES SHALL BE SET FLUSH IN LAWN AND PER
MULCH DEPTH ABOVE FINISH GRADE IN SHRUB /GROUNDCOVER AREAS.

2. CLOSE NIPPLES SHALL NOT BE USED.

3. NIPPLES, COUPLINGS, AND ELBOWS SIZE SHALL BE 1" RED BRASS.


LEGEND ON PLANS
4. TEFLON TAPE SHALL BE USED ON THREADED CONNECTIONS.

5. UPON PROJECT ACCEPTANCE, THE CONTRACTOR SHALL PROVIDE TWO QCV @


SETS OF APPROPRIATE QUICK CUPLER VALVE KEY WITH 1" BRASS BALL
VALVE AND SWIVEL ADAPTER INCLUDED IN THE ASSEMBLY.

REVISION BY APPROVED DATE RECOMMENDED BY THE CITY OF SAN DIEGO


STANDARDS COMMITIEE
CITY OF SAN DIEGO - STANDARD DRAWING
ORIGINAL* RH . NAGELVOOR OV12
1/.cJ/-M£--
COORDINATOR R.C.E. 65271
1/31/2012
DATE

QUICK COUPLING VALVE DRAWING


NUMBER
SDI-105
HINGED LOCKING BRASS CAP, -------
SOLVENT WELDED TO SLEEVE
(SHOWN WITH CAP KEY)

TURF, FINISHED GRADE

MULCH DEPTH TOP OF MULCH


PER PLANS

5"

2" PVC PIPE, SCH 40

21"

1" PVC CAP, SCH 40

1" PVC PIPE, SCH 40

2" x 2" x 1" TEE, PVC, SCH 40

SLEEVE - INSTALL PERPENDICULAR,


CENTERED OVER VALVE STEM.

ALL BRASS TO QUICK COUPLER OR


REMOTE CONTROL VALVE MANIFOLD
PVC MALE ADAPTER, SCH 80
(TYP)
RED BRASS NIPPLE RED BRASS COUPLING, TEE, OR ELBOW
(8" LONG) (TYP)
VALVE,PER LEGEND BRASS NIPPLE (8" LONG)
(1YP)

NOTES:
1. GLOBE VALVES SHALL BE FURNISHED WITH A STANDARD
BRONZE CROSS HANDLE, CENTERED IN PIPE SLEEVE.

2. VALVES SHALL BE INSTALLED WITHIN 12" OF HARDSCAPE.

3. GLOBE VALVES SHALL BE FURNISHED WITH A REMOVABLE BONNET AND PACKING GLAND NUT.

4. CLOSE NIPPLES SHALL NOT BE USED.


5. LOCKING CAP SHALL BE MOUNTED FLUSH WITH FINISHED GRADE IN TURF AREAS AND ABOVE
FINISHED GRADE IN SHRUB AREAS, PER DEPTH OF MULCH.

6. PROVIDE APPROPRIATE LOCKING CAP KEY AND VALVE KEY TO OPERATE VALVE AT DEPTH. LEGEND
7. LOCATE OUTSIDE OF TURF WHEN POSSIBLE.
8. TEFLON TAPE SHALL BE USED ON ALL THREADED CONNECTIONS. GV

9. WHEN INSTALLED AS MAINLINE ISOLATION VALVE, NIPPLES AND FITIINGS MAY BE SCH 80 PVC.

REVISION BY APPROVED DAlE RECOMMENDED BY THE Ct1Y OF SAN DIEGO


STANDARDS COMMITTEE
CllY OF SAN DIEGO - STANDARD DRAWING
oil~
ORIGINAL• RH . NAGELVOOR OV12
1/31/2012
COORDINATOR R.C.E. 65271 DAlE
ISOLATION GLOBE VALVE
DRAWING
2" AND SMALLER NUMBER
SDI-106
UNMORTARED STANDARD BRICKS (4)
FOUNDATION ON COMPACTED SUBGRADE
CONCRETE VALVE BOX (USE 6 BRICKS FOR OVERSIZED BOXES)

ISOLATION VALVE
CENTERED IN BOX

PLAN

4 UNMORTARED STANDARD BRICKS


FOUNDATION ON COMPACTED
SUBGRADE

VALVE CENTERED IN
6" PVC SLEEVE NOTCHED ' - - - - - - - 6" PVC SLEEVE
TO FIT OVER THE PIPE

SCH 80 PVC MALE SCH 80 PVC MALE


ADAPTER (TYP) ADAPTER (TYP)

NOTES

1. GLOBE VALVES SHALL BE FURNISHED WITH A STANDARD BRONZE CROSS HANDLE, CENTERED IN PIPE SLEEVE.

2. VALVE SHALL BE INSTALLED WITHIN 12" OF HARDSCAPE.

3. GLOBE VALVES SHALL BE FURNISHED WITH A REMOVABLE BONNET AND PACKING GLAND NUT.

4. TEFLON TAPE SHALL BE USED ON THREADED CONNECTIONS.

5. VALVE BOX SHALL BE MOUNTED FLUSH WITH FINISH GRADE IN TURF AREAS AND PER MULCH DEPTH IN
SHRUB AREAS.

6. LOCATE OUTSIDE OF TURF WHEN POSSIBLE.

7. GATE VALVE SHALL BE USED ONLY ON LOOPED MAINLINE.


LEGEND ON PlANS

8
8. VALVE BOX SHALL BE SET PERPENDICULAR TO HARDSCAPE.

9. PROVIDE TWO VALVE KEYS TO OPERATE VALVE AT DEPTH. @


GATE VALVE GLOBE VALVE

REVISION BY APPROVED DAlE RECOMMENDED BY THE Ct1Y OF SAN DIEGO


STANDARDS COMMITTEE
CllY OF SAN DIEGO - STANDARD DRAWING
ORIGINAL' KA . NAGELVOOR OV12
oil~ 1/31/2012
COORDINATOR R.C.E. 65271 DAlE
ISOLATION GLOBE/GATE VALVE
DRAWING
2 1/2" AND LARGER NUMBER
SDI-107
FI
NISHED GRADE

9"-12"

BACKFI
LL FREE OF ROCK AND DEBRI
S.

15" FOR LATERALS


24" UNDER PAVEMENT I
NSTALL W ARNI
NG/
IDENTI
FICATI
ON TAPE PER SDM-105.

21" FOR MAINLI


NE
(36" UNDER PAVEMENT)

4" BEDDI
NG

SE5O PLASTER OR MORTAR SAND.

2" BEDDI
NG
PVC OR COPPER PI
PE

CONTROL W I
RES

6" MI
N 6" MI
N

MAI
NLI
NE TRENCH

6" MI
N 6" MI
N 6" MI
N 6" MI
N

4"
BEDDING

2"
BEDDING

MULTI
PLE PI
PE I
NSTALLATI
ON DETAI
L

NOTES:

1. BACKFI
LL MATERI
AL SHALL BE COMPACTED TO A RELATI
VE COMPACTI
ON OF 90% MI
NIMUM.

2.PI
PE SHALL LAY FREE I
N THE TRENCH W I
TH NO I
NDUCED STRAI
N AND W I
TH SUFFI
CIENT ALLOW ANCE
FOR EXPANSION AND CONTRACTION.

3.PVC PI
PE UNDER PAVEMENT SHALL BE I
NSTALLED I
N A SCH 40 PVC SLEEVE TW I
CE THE DI
AMETER
OF THE PI
PE (
2" MI
NIMUM SI
ZE)AND EXTEND 12" MINI
MUM BEYOND THE EDGE OF PAVEMENT.

4.THE LETTER "W " SHALL BE STAMPED OR CHI


SELED ON THE I
MPROVEMENT (
CURB/
SIDEW ALK)DI
RECTLY ABOVE THE
PRESSURE PIPELINE SLEEVE.

5.NO PVC PRESSURE PI


PELI
NE SHALL BE I
NSTALLED W I
THI
N 3'OF ANY UTI
LITY,UNLESS OTHERW I
SE SPECI
FIED.

RECOMMENDED BY THE CI
TY OF SAN DI
EGO
REVI
SION BY APPROVED DATE
STANDARDS COMMITTEE
CI
TY OF SAN DI
EGO - STANDARD DRAW I
NG
ORI
GINAL* RH J.NAGELVOORT 01/
12

2/
25/
16
UPDATED AR J.NAGELVOORT 02/
16
COORDI
NATOR R.
C.E.56523 DATE
I
RRI
GATI
ON TRENCH PVC
DRAW I
NG
OR COPPER PI
PE SDI
-110
NUMBER
CONCRETE VALVE BOX UNMORTARED STANDARD BRICKS (4)
FOUNDATION ON COMPACTED SUBGRADE
(USE 6 BRICKS FOR OVERSIZED BOXES)

PLAN
CONCRETE RECTANGULAR VALVE BOX WITH CAST IRON,
SELF-LOCKING LID, PAINT "MV" AND CONTROLLER ID
LETTER ON LID.
FINISHED GRADE CONTROL WIRES 24" LEAD LENGTH
(COILED WITH ID TAG)

MULCH DEPTH,----,
PER PLAN

SCH 80
(LENGTH 10 x PIPE
DIAMETER MIN (-
FROM ADAPTER TO
FLOW SENSOR) PEA GRAVEL '- j 1
/ /

4" MIN DEPTH __/ RED BRASS


FLOWSENSOR WIRE WITH
2' EXPANSION LOOP ELBOW WITH COUPLING (lYP)
CONCRETE THRUST
BLOCK 9" x 9" x 9"

CONDUIVSWEEP CONDUIT!SWEEP FOR FLOW SENSOR


FLOW SENSOR WIRE AND MASTER VALVE WIRES.

ELEVATION
NOTES:
1. SPLICING SHALL BE MADE IN VALVE BOXES AND PULL BOXES ONLY. SEE STANDARD DRAWING
SDI- 115 FOR SPLICE /SOLDERING NOTES.
2. SPLICES SHALL BE SOLDERED WITH A PROPERLY SET MECHANICAL SPLICE CONNECTOR,
ENTIRELY ENCLOSED IN SELF-CURING RESIN AND SHALL BE COMPLETELY WATER-PROOF.
3. SEAL CONDUIT OPENINGS WITH ELECTRICAL CONDUIT SEALANT AS APPROVED BY THE ENGINEER.
4. PVC CONDUIT SHALL BE 1" MINIMUM.
5. VALVE /CONTROLLER IDENTIFICATION SHALL BE LABELED OUTSIDE ON THE VALVE BOX LID AND
TAGGED INSIDE THE BOX ON THE VALVE.
6. KNOCK OUTS SHALL NOT BE ENLARGED.
7. INSTALL ONLY ONE VALVE PER BOX.
8. VALVE BOXES SHALL BE SET PERPENDICULAR TO HARDSCAPE, ABOVE FINISHED GRADE IN SHRUB I
GROUNDCOVER AREAS,.. PER MULCH DEPTH. IF NECESSARY TO BE SET IN TURF, VALVE BOXES SHALL
BE SET FLUSH WITH riNISHED GRADE.
9. CLOSE NIPPLES SHALL NOT BE USED. LEGEND ON PLANS
10. NIPPLES, ELBOWS\ AND FmiNGS SHALL BE THREADED RED BRASS, FROM COUPLING THROUGH THE
MASTER VALVE. P PE AND FITTINGS DOWNSTREAM SHALL BE SCH 80 PVC. T MV
11. TEFLON TAPE SHALL BE USED ON THREADED CONNECTOR.
REVISION BY APPROVED DATE RECOMMENDED BY THE Ct1Y OF SAN DIEGO
STANDARDS COMMITTEE
CITY OF SAN DIEGO - STANDARD DRAWING
oil~
ORIGINAL• RH . NAGELVOOR OV12
1/31/2012
COORDINATOR R.C.E. 65271 DATE

MASTER VALVE DRAWING

NUMBER
SDI-111
CONCRETE VALVE BOX UNMORTARED STANDARD BRICKS
(4) FOUNDATION ON COMPACTED
SUBGRADE (USE 6 BRICKS FOR
OVERSIZED BOXES)

FLOWSENSOR CENTERED IN BOX

PLAN

CONCRETE RECTANGULAR VALVE BOX WITH CAST IRON, SELF-LOCKING


LID. PAINT "FS" AND CONTROLLER I.D. LETTER ON LID.

FINISHED GRADE

SOIL
AROUND VALVE BOX
~"f;:T"~r-~-L---~r:....=..;:::..:.;:::;r--.1(,~ 1" MIN BETWEEN TOP OF
PIPE AND VALVE BOX
KNOCK OUTS
(BOTH SIDES)

SCH 80 PVC MAINLINE


FROM MASTER VALVE
10 X PIPE DIAMETER
WNO FITIING

ELBOW WITH SCH 80 PVC


CONCRETE BLOCK LENGTH 5X PIPE 1" MIN PVC CONDUIT FOR FLOW
9" X 9" X 9" DIAMETER SENSOR DATA CABLE TO CONTROLLER.
ELEVATION

NOTES:
1. SPLICES SHALL BE SOLDERED WITH A PROPERLY SET MECHANICAL SPLICE CONNECTOR,
ENTIRELY ENCLOSED IN SELF-CURING RESIN AND SHALL BE COMPLETELY WATER-PROOF.
2. SEAL CONDUIT OPENINGS WITH ELECTRICAL SEALANT.
3. KNOCK OUTS SHALL NOT BE ENLARGED.
4. INSTALL ONLY ONE FLOW SENSOR PER BOX.
5. VALVE BOXES SHALL BE SET PERPENDICULAR TO HARDSCAPE PER MULCH DEPTH IN SHRUB I
GROUNDCOVER AREAS. IF NECESSARY TO BE SET IN TURF, VALVE BOXES SHALL BE SET FLUSH
WITH FINISHED GRADE.
LEGEND ON PLANS

® FS

REVISION BY APPROVED DAlE RECOMMENDED BY THE Ct1Y OF SAN DIEGO


STANDARDS COMMITTEE
CITY OF SAN DIEGO - STANDARD DRAWING
oil~
ORIGINAL• RH . NAGELVOOR OV12
1/31/2012
COORDINATOR R.C.E. 65271 DAlE

FLOW SENSOR DRAWING

NUMBER
SDI-112
UNMORTARED STANDARD BRI
CKS (
4)
FOUNDATI
ON ON COMPACTED
SUBGRADE (
USE 6 BRI
CKS FOR
CONCRETE VALVE BOX OVERSI
ZED BOXES)
WITH LOCKI
NG TOP
AS APPROVED BY THE
ENGINEER

VALVE
CENTERED
I
N BOX

PLAN

CONCRETE RECTANGULAR VALVE BOX W I


TH HINGED
12" MAX
CAST I
RON,SELF-LOCKI
NG,LI
D.IMPRI
NTED W /RCV AND
CONTROLLER I
D LETTER ON LID.

FI
NISHED GRADE CONTROL W I
RES 24" FINI
SHED
LEAD LENGTH ( COI
LED GRADE SI
DEW ALK OR
WITH VALVE ID TAG) (TURF) MOW CURB
MULCH DEPTH, 3" MI
N
PER PLAN

1" MI
N CLEARANCE BETW EEN
TOP OF PIPE AND VALVE BOX
COMPACT SOIL
KNOCK OUTS ( BOTH SIDES)
AROUND VALVE BOX
15"
PVC PI
PE AND ELBOW , NI
PPLE,ELBOW AND RI SER FROM
2" MI
N
SCH 40 MANIFOLD TEE OR ELBOW ,AS
SHOW N /NOTED ON SDI-126
UNLESS OTHERW I
SE SPECIFI
ED.

3/
8" PEA GRAVEL
4" MIN DEPTH

PVC UNION, RED BRASS


NI
PPLES,AND ELBOW , FROM ISOLATI
ON
SCH 80 VALVE

ELEVATI
ON

NOTES:
1. SPLI
CING SHALL BE MADE I
N VALVE BOXES AND PULL BOXES ONLY.SEE SDI
-115 FOR
SPLI
CE /SOLDERI
NG NOTES.

2. SPLI
CES SHALL BE SOLDERED W I
TH A PROPERLY SET MECHANI
CAL SPLI
CE CONNECTOR,
ENTI
RELY ENCLOSED IN SELF-CURING RESI
N AND SHALL BE COMPLETELY W ATER-PROOF.

3. KNOCK OUTS SHALL NOT BE ENLARGED.

4. I
NSTALL ONLY ONE VALVE PER BOX.

5. VALVE BOXES SHALL BE SET PERPENDICULAR TO HARDSCAPE,ABOVE FI


NISHED GRADE IN
SHRUB /GROUNDCOVER AREAS,PER MULCH DEPTH.I F NECESSARY TO BE SET I
N TURF,
VALVE BOXES SHALL BE SET FLUSH W I
TH FINI
SHED GRADE.

6. CLOSE NI
PPLES SHALL NOT BE USED.
LEGEND ON PLANS
7. NI
PPLES,ELBOW S,AND FI
TTI
NGS SHALL BE THREADED RED BRASS FROM I
SOLATI
ON VALVE
THROUGH THE VALVE,UNLESS OTHERW I
SE SPECIFI
ED. RCV

8. TEFLON TAPE SHALL BE USED ON THREADED CONNECTI


ONS

RECOMMENDED BY THE CI
TY OF SAN DI
EGO
REVI
SION BY APPROVED DATE
STANDARDS COMMITTEE
CI
TY OF SAN DI
EGO - STANDARD DRAW I
NG
ORI
GINAL* RH J.NAGELVOORT 01/
12

2/
25/
16
UPDATED AR J.NAGELVOORT 02/
16
COORDI
NATOR R.
C.E.56523 DATE

REM OTE CONTROL VALVE DRAW I


NG
SDI
-114
NUMBER
C

C
UNMORTARED STANDARD BRI CKS (
4)
FOUNDATION ON COMPACTED SUBGRADE
(USE 6 BRI
CKS FOR OVERSI
ZED BOXES)

12"
C
WI
RE RUN
C

CONCRETE PULL BOX

C
C
18" C

PLAN VI
EW

LOCKABLE HINGED CAST I


RON OR CONCRETE TOP
FI
NISHED GRADE
I
MPRINTED "ELECTRI
C"
C

C
C

4" MI
N
C

LOOP 24" MI
N OF CONTROL W I
RES
I
NTO PULL BOXES
C

C BEDDI
NG MATERI
AL
C

2"
C

CONTROL W I
RE RUN
ELEVATI
ON
BOTTOM OF TRENCH
NOTES:
1. I
NSTALL PULL BOXES AS SHOW N ON PLANS AND AT EACH END OF PI
PE SLEEVES RUNNI
NG
UNDER PAVEMENT.

2. PULL BOX COVER SHALL BE PERMANENTLY MARKED "ELECTRI


C".

3. CONDUCTORS FOR EACH CONTROLLER CLOCK SHALL BE HARNESSED SEPARATELY AND AT


SUFFI
CIENT I
NTERVALS TO MAI
NTAI
N A DEFI
NITE BUNDLE.

4. SPLI
CES SHALL ONLY BE MADE I N PULL BOXES,W I
TH A PROPERLY SET MECHANICAL SPLI
CE
CONNECTOR,SOLDERED W I TH METALLI
C ALLOY,ENTI RELY ENCLOSED I
N SELF-CURI
NG RESI N AND
SHALL BE COMPLETELY W ATER-PROOF.

5. SPARE W I
RE ENDS SHALL BE I
NSULATED I
N THE SAME MANNER AS W I
RE SPLI
CES.

6. MI
NIMUM SI ZE PULL BOX SHALL BE AS SHOW N ABOVE.LARGER BOXES MAY BE NECESSARY TO
MEET 4" CLEARANCE REQUI RED.

7. NO SPLI
CES SHALL BE PERMI
TTED ON W I
RE RUNS OF LESS THAN 300'
. LEGEND ON PLANS

8. THE LETTER "E" SHALL BE STAMPED OR CHI


SELED ON THE I
MPROVEMENT (
CURB-SI
DEW ALK)
DIRECTLY ABOVE THE CONTROL W IRE.
PB
9. BEDDI
NG MATERI
AL SHALL BE SE 50 PLASTER OR MORTAR SAND.

RECOMMENDED BY THE CI
TY OF SAN DI
EGO
REVI
SION BY APPROVED DATE
STANDARDS COMMITTEE
CI
TY OF SAN DI
EGO - STANDARD DRAW I
NG
ORI
GINAL* RH J.NAGELVOORT 01/
12

2/
25/
16
UPDATED JW J.NAGELVOORT 02/
16
COORDI
NATOR R.
C.E.56523 DATE
ELECTRICAL PULL BOX
FOR DI
RECT BURI AL CONTROL W I
RES DRAW I
NG

AND SPLI
CING NOTES SDI
-115
NUMBER
HEAVY-DUTY STAINLESS STEEL
ENCLOSURE WITH UGHT ACCESS
THROUGH GRID ON TOP, AND
INTERNAL CLAMP FOR COLUMN

HIGH SECURITY STAINLESS


STEEL DISC LOCK

SOLAR IRRIGATION
CONTROLLER
GALV STEEL COLUMN PER
MANUFACTURER SPECS

RAIN SENSOR ENCLOSED IN


STAINLESS STEEL VANDAL
RESISTANT ENCLOSURE, MOUNT
ON POST MIN 30' ABOVE
GRADE

FINISH GRADE
ELECTRICAL
PULL BOX CONCRETE PAD TO
SLOPE AWAY FROM
; [CONTROLLER COLUMN

~---3~·-~----~~--------~-+--~~

SWEEP CONDUIT
INTO PULL BOX
24' SERVICE LOOP 12"X12' x12' CONCRETE
IN PULL BOX ANCHOR 520--C--2500

3'MAX 18'

NOTES: I · •'- ------.;....,.


ELECTRIC[]
PULL BOX
1. PROVIDE SOLENOID ADAPTOR TO SUPPORT SOLAR CLOCK

o~
FUNCTION ON VALVE.

2. MAXIMUM RUN OF CONTROL WIRE TO REMOTE CONTROL VALVE


(RCV) IS 1500' UNLESS OTHERWISE SPECIFIED.
CONTROLLER
3. SEAL CONDUIT OPENINGS WITH ELECTRICAL SEALANT. ON THE
COLUMN
CONCRETE
PAD

REVISION BY APPROVED DAlE RECOMMENDED BY THE Ct1Y OF SAN DIEGO


STANDARDS COMMITTEE
CllY OF SAN DIEGO - STANDARD DRAWING
ORIGINAL' KA . NAGELVOOR OV12
oil~ 1/31/2012
COORDINATOR R.C.E. 65271 DAlE

SOLAR IRRIGATION CONTROLLER DRAWING


NUMBER
SDI-1 16
8" 3'MAX

8"
PULL BOX

C
L

STAI
NLESS STEEL ENCLOSURE
4'
ENCLOSURE MOUNTI
NG ANCHORS

W EAKENED PLANE JOI


NT
PAD - 6" THI
CK FOR CONTROLLER ENCLOSURE,
PAD TO SLOPE AW AY FROM CONTROLLER

PAD - 6" THI


CK FOR CONTROLLER ACCESS

PLAN VI
EW (
FOR CONCRETE PAD)

LABEL ENCLOSURE DOOR CONTROLLER AND STAI


NLESS STEEL ENCLOSURE
WITH CONTROLLER ASSEMBLY.
DESI
GNATI ON USI NG 2" BLACK
VINYL LETTERS /
NUMBERS.

A CONTROL W I
RE TERMI
NAL STRIP AS PRE-ASSEMBLED
PROVI
DE RAI
N SENSOR IN ON BACKBOARD.LABELED W I
TH STATION /FUNCTION
AN APPROVED LOCATI
ON. NUMBER

POW ER SW I
TCH AND GFI CONDUI TS - PVC SCH 40
RECEPTACLE ON (1)FOR CONTROL W I RES (
SEE NOTE #3 BELOW )
PRE-ASSEMBLED BACKBOARD. (1)1" FOR MASTER VALVE W I
RE.
(1)1" FOR FLOW SENSI NG CABLE
(2)1" SPARE
CONDUIT FROM POW ER SOURCE, SEAL AND W ATERPROOF CONDUI TS (
BOTH ENDS)
PER LOCAL CODES.SEAL AND
W ATERPROOF BOTH ENDS. GROUNDING ROD PER MANUFACTURER'
S
SPECI
FICATI
ONS.
CONCRETE ANCHORS PER
ASSEMBLY TEMPLATE SHALL COMPACTED SUBGRADE,AS REQUI
RED.
BE STAINLESS STEEL.

PROVI
DE SI
LICONE SEALANT
AROUND BASE OF PULL BOX I NSTALLED W I
THI
N 3'OF
CONTROLLER ENCLOSURE. CONTROLLER ENCLOSURE,PER
SDI-115 AND LABEL W /
CONTROLLER
DESIGNATI ON.
1"

6"
MIN

CONCRETE BASE

FRONT VI
EW
NOTES: CONDUIT SW EEPS TO TRENCH DEPTH.
REFER TO TRENCH DETAI L,SDI
-110.
1. ALL CONTROLLER ASSEMBLIES AND OPTI
ONS SHALL BE COMPLETELY
PRE-ASSEMBLED IN A STAI
NLESS STEEL ENCLOSURE.

2. CONTROL W I
RE CONDUI
T SHALL BE TW I
CE THE DI
AMETER OF THE W I
RE BUNDLE,2" MI
NIMUM.

3. PROVI
DE SEPARATE CI
RCUI
T BREAKER FOR CONTROLLER(
S)AT ELECTRI
CAL CONTOL PANEL AND LABEL. LEGEND ON PLANS

4. SEAL CONDUI
T OPENI
NGS W I
TH ELECTRI
CAL SEALANT,AS APPROVED BY THE ENGI
NEER.

RECOMMENDED BY THE CI
TY OF SAN DI
EGO
REVI
SION BY APPROVED DATE
STANDARDS COMMITTEE
CI
TY OF SAN DI
EGO - STANDARD DRAW I
NG
ORI
GINAL* RH J.NAGELVOORT 01/
12

2/
25/
16
UPDATED AR J.NAGELVOORT 02/
16
COORDI
NATOR R.
C.E.56523 DATE
AUTOM ATI
CIRRI
GATI
ON CONTROLLER
DRAW I
NG
PEDESTAL M OUNTED SDI
-117
NUMBER
BUI
LDI
NG W ALL

CONTROLLER ASSEMBLY

POW ER SW I
TCH AND GFIRECEPTACLE

LEGEND ON PLANS

CONDUI
TS

STEEL CONDUI
T STRAPS AND FASTENERS
5'- 6"

GROUNDI
NG ROD PER MANUFACTURER'
S SPECS

PULL BOX

3'MAX

PRE ASSEMBLED STAI


NLESS
STEEL BACK BOARD MOUNTED
PER MANUFACTURERS
RECOMMENDATI ONS
CONTINUOUS CONDUIT WITH 3'
SW EEPS TO TRENCH DEPTH.
REFER TO TRENCH DETAIL,SDI
-110.
3'

SI
DE VI
EW A
BUI
LDI
NG W ALL

LABEL ENCLOSURE DOOR W ITH CONTROLLER DESI GNATI


ON
USING 2" BLACK VI
NYL LETTERS/
NUMBERS.

CONTROLLER

POW ER SOURCE CONDUI


T

POW ER SW I
TCH AND GFIRECEPTACLE

CONDUI TS - PVC SCH 40


SEAL CONDUI TS AT BOTH ENDS
(1)FOR CONTROL W I RES.
SEE NOTE #1BELOW .
(
1)1" FOR MASTER VALVE W I RE.
(
1)1" FOR FLOW SENSI NG CABLE.
(
2)1" SPARE.

STEEL CONDUI
T STRAPS AND FASTENERS,
4 PER CONDUI
T.

NOTES: GROUNDING ROD


PER MANUFACTURER SPECS

1. CONTROL W IRE CONDUI


T SHALL BE TW I
CE THE DI
AMETER
OF THE W I
RE BUNDLE,2" MI
NIMUM.

2. PROVIDE SEPARATE CI
RCUIT BREAKERS FOR CONTROLLER(
S)
AT ELECTRI
CAL CONTROL PANEL,AND LABEL.

3. PROVI
DE RAI
N SENSOR AND I
NSTALL I
N AN APPROVED LOCATI
ON.
FRONT VI
EW

RECOMMENDED BY THE CI
TY OF SAN DI
EGO
REVI
SION BY APPROVED DATE
STANDARDS COMMITTEE
CI
TY OF SAN DI
EGO - STANDARD DRAW I
NG
ORI
GINAL* RH J.NAGELVOORT 01/
12

2/
25/
16
UPDATED AR J.NAGELVOORT 02/
16
COORDI
NATOR R.
C.E.56523 DATE
AUTOM ATI
CIRRI
GATI
ON CONTROLLER
DRAW I
NG
I
NDOOR W ALL M OUNTED SDI
-118
NUMBER
FI
NISHED GRADE
C

I
MPORTED TOPSOIL OR AMENDED NATI
VE
SOI
L,FREE OF ROCK AND DEBRI
S
9" TO 12"

CONTI
NUOUS TAPE OVER ELECTRI
CAL
CONTROL W I
RES PER SDM-105

18" MI
N
C

CONTI
NUOUS TAPE OVER W ATER
C

PI
PELI
NE PER SDM-105

4" MI
N
BEDDI
NG MATERI
AL
C

I
RRI
GATI
ON MAI
NLI
NE PER SDI
-110
C

C
C

2" MI
N DI
RECT BURIAL CONTROL W I
RE,BUNDLED
WITH PLASTI
C TAPE EVERY 10'COLOR
KEYED TO CONTROLLER

NOTES:

1. BEDDI
NG MATERI
AL SHALL BE SE 50 PLASTER OR MORTAR SAND.

2. W I
RES W HI
CH RUN UNDER PAVED AREAS SHALL BE I NSTALLED I
N PVC PI
PE SLEEVES TW I
CE THE DI
AMETER
OF THE W I
RE BUNDLE (
2" MI
NIMUM SI ZE)
,EXTENDING 12" MI
NIMUM BEYOND EDGE OF PAVEMENT.INSTALL ELECTRI
CAL
PULL BOX AT EACH END OF PIPE SLEEVES PER SDI
-115.

3. THE LETTER E SHALL BE STAMPED OR CHI


SELED ON THE I
MPROVEMENT(
CURB-SI
DEW ALK)DI
RECTLY ABOVE
THE CONTROL W I
RE /CABLE.

4. W HEN CONTROL W I
RING CANNOT BE INSTALLED I
N A PI
PE TRENCH,I
T SHALL BE I
NSTALLED A MI
NIMUM 18" BELOW
FI
NISH GRADE BUNDLED W ITH PLASTI
C TAPE.

RECOMMENDED BY THE CI
TY OF SAN DI
EGO
REVI
SION BY APPROVED DATE
STANDARDS COMMITTEE
CI
TY OF SAN DI
EGO - STANDARD DRAW I
NG
ORI
GINAL* RH J.NAGELVOORT 01/
12

2/
25/
16
UPDATED JW J.NAGELVOORT 08/
15
COORDI
NATOR R.
C.E.56523 DATE
UPDATED AR J.NAGELVOORT 02/
16
CONTROL W I
RE
DRAW I
NG
I
NSTALLATI
ON SDI
-119
NUMBER
UV RESISTANT PVC PIPE

GRADE

#3 OR #4 REBAR BENT AS SHOWN


OR PRE-BENT STABILIZERS

SIDE VI'CW

NOTE:

STABILIZERS SHALL BE PLACED NO GREATER THAN 10' APART,


AT EACH RISER AND AT All FITTINGS.

REVISION BY APPROVED DATE RECOMMENDED BY THE CITY OF SAN DIEGO


STANDARDS COMMITTEE
CllY OF SAN DIEGO - STANDARD DRAWING
oil~
ORIGINAL• RH . NAGELVOOR OV12
1/31/2012
COORDINATOR R.C.E. 65271 DATE
ON-GRADE PIPE STABILIZATION
DRAWING
TEMPORARY INSTALLATION NUMBER
SDI-120
ON-GRADE PIPE
STABILIZER

SHORT NIPPLE

90° ELLS SCH 40 UV RESISTANT


PVC PIPE ON-GRADE PIPE
STABILIZER

ON-GRADE PIPE
STABILIZER 90° ELLS

ON-GRADE PIPE
STABILIZER

PLAN

ON-GRADE PIPE
STABILIZER

SWING JOINT ON-GRADE PIPE SWING JOINT


STABILIZER
SCH 40 lN RESISTANT
PVC PIPE

ELEVA TI ON

NOTE: LEGEND ON PLANS

SWING JOINTS SHALL BE USED AT EACH CHANGE OF GRADE.


'*
'--l-1- -

REVISION BY APPROVED DATE RECOMMENDED BY THE Ct1Y OF SAN DIEGO


STANDARDS COMMITTEE
CllY OF SAN DIEGO - STANDARD DRAWING
ORIGINAL• RH • NAGELVOOR 01112
oil~ 1/31/2012

SWING JOINT AND PIPE INSTALLATION COORDINATOR R.C.E. 65271 DATE

ON SLOPES ABOVE GROUND DRAWING


SDI-1 23
PIPE INSTALLATIONS NUMBER
PVC MAINLINE PVC TEE (LINE SIZE)

SCH 40 PVC TEE OR


ELL AT TERMINAL END.
TYPICAL

BALL VALVE AND


VALVE BOX.

PLASTIC ROUND ALVE BOX FOR


QUICK COUPLING VALVE

TEE UP TO MANIFOLD DEPTH. USE SCH PVC 80 IPPLES FOR MANIFO


CONNECTIONS TO CONTROL VALVES.

18" - - - 1 - - - - 18" - - - + - - - 18" - - - + - - - 18" - --l


TYPICAL TYPICAL TYPICAL TYPICAL

RCV RECTANGULAR VALVE BOX FOR CONTROL VALVES.

NOTES:

1. PVC PIPE USED IN MANIFOLD ASSEMBLIES SHALL BE THE SAME CLASS AS


SPECIFIED FOR THE MAINLINE.

2. VALVE BOXES SHALL BE HEAT BRANDED WITH CONTROLLER AND VALVE IDENTIFICATION.

REVISION BY APPROVED DATE RECOMMENDED BY THE CITY OF SAN DIEGO


STANDARDS COMMITTEE
CITY OF SAN DIEGO - STANDARD DRAWING
oil~
ORIGINAL• RH . NAGELVOOR OV12
1/31/2012
REMOTE CONTROL VALVE MANIFOLD COORDINATOR R.C.E. 65271 DATE

ASSEMBLY WITH PVC PIPE DRAWING


(TEMPORARY SYSTEMS) NUMBER
SDI-125
NOTES:

1. ALL PIPES, NIPPLES, AND FITIINGS AFTER MALE ADAPTER SHALL BE RED BRASS.

2. VALVE AND CONTROLLER IDENTIFICATION SHALL BE LABELED OUTSIDE ON THE VALVE BOX LID
AND TAGGED INSIDE THE BOX ON THE VALVE.

3. TEFLON TAPE SHALL BE USED ON THREADED CONNECTIONS.

REVISION BY APPROVED DAlE RECOMMENDED BY THE Ct1Y OF SAN DIEGO


STANDARDS COMMITTEE
CllY OF SAN DIEGO - STANDARD DRAWING
oil~
ORIGINAL• RH . NAGELVOOR OV12
1/31/2012
COORDINATOR R.C.E. 65271 DAlE
REMOTE CONTROL VALVE
DRAWING
MANIFOLD ASSEMBLY WITH BRASS PIPE NUMBER
SDI-1 26
REMOTE CONTROL CONTROL W I
RES 24" SCH PVC 80 NI
PPLE PRESET PRESSURE REGULATOR
VALVE LEAD LENGTH (
THREADED)TYP PER LEGEND
(
W/I
D TAG)

3" MI
N CLEAR FI
LTER SCH 80 PVC UNI
ON
(
THREADED)TYP
MULCH DEPTH
PER PLAN TURF,FI
NISHED
GRADE
FI
NISHED GRADE

SCH 80 PVC
MALE ADAPTER
1" CLEAR BETW EEN
TOP OF PI
PE AND
PVC OR POLY
VALVE BOX KNOCK
FLOW LATERAL LI
NE
OUTS (
BOTH SI
DES)

FLOW PVC OR POLY


LATERAL LI
NE
1" MI
N CLEAR
MAI
NLI
NE 2" MI
N CLEAR

JUMBO VALVE BOX


SCH 80 PVC
MALE ADAPTER

3/
8" PEA GRAVEL STANDARD BRI
CK SUPPORTS
4" MI
N DEPTH (
4 EACH SI
DE)

ELEVATI
ON

NOTES:

1. WI
RE SPLI
CING SHALL BE MADE I
N VALVE BOXES AND PULL BOXES ONLY.SEE SDI
-115 FOR SPLI
CE /SOLDERI
NG NOTES.

2. SPARE W I
RES TERMI
NATI
NG I
N VALVE BOXES SHALL HAVE THEI
R ENDS I
NSULATED,THE SAME AS FOR A SPLI
CE.

3. W HEN TW O OR MORE VALVES ARE I


NSTALLED I
N THE SAME LOCATI
ON,SEE REMOTE CONTROL VALVE
MANIFOLD ASSEMBLY,SDI
-125 AND SDI-126.

4. VALVE /CONTROLLER I
DENTI
FICATI
ON SHALL BE PERMANENTLY LABELED EXTERNALLY ON THE VALVE BOX AND
I
NTERNALLY,W I
TH A PERMANENT I
DENTI
FICATI
ON TAG ATTACHED TO THE VALVE.

5. KNOCK OUTS SHALL NOT BE ENLARGED UNLESS APPROVED BY THE ENGI


NEER.

6. I
NSTALL ONLY ONE VALVE ASSEMBLY PER BOX.

7. VALVE BOXES SHALL BE SET PERPENDICULAR TO HARDSCAPE,A MAXIMUM 12 I


NCHES FROM EDGE OF HARDSCAPE,
2" ABOVE FI
NISHED GRADE IN SHRUB /GROUNDCOVER AREAS,PER MULCH DEPTH.I F NECESSARY TO BE
SET IN TURF,VALVE BOXES SHALL BE SET FLUSH W I
TH FI
NISHED GRADE.

8. CLOSE NI
PPLES SHALL NOT BE USED.

9. FI
LTER SHALL BE I
NSTALLED TO ALLOW FOR MAI
NTENANCE ACCESS.

10. TEFLON TAPE SHALL BE USED ON THREADED CONNECTI


ONS.

LEGEND ON PLANS

RECOMMENDED BY THE CI
TY OF SAN DI
EGO
REVI
SION BY APPROVED DATE
STANDARDS COMMITTEE
CI
TY OF SAN DI
EGO - STANDARD DRAW I
NG
ORI
GINAL* RH J.NAGELVOORT 01/
12

2/
25/
16
UPDATED RB J.NAGELVOORT 02/
16
COORDI
NATOR R.
C.E.56523 DATE
REM OTE CONTROL VALVE
DRAW I
NG
DRI
PIRRI
GATI
ON SDI
-127
NUMBER
MULCH DEPTH PER P L A N - - - - -
FINISHED GRADE

AIR I VACUUM RELIEF VALVE-----2-J~--J:1


PER LEGEND
W" PVC COUPLING (TxT) ----__:_____:__jrJ__ __J

6" ROUND VALVE B O X - - - - - - 1 1


WITH LOCKING LID
1----t-1--.------ 3" MIN CLEAR
W " SCH 80 RISER ---_,.....:~:-{1---­
(LENGTH AS REQUIRED)

PVC SCH 40
SxSxT TEE

LATERAL P.V.C. PIPING PER LEGEND

PLUMBED TO PVC

MULCH DEPTH PER PLAN-----, FINISHED GRADE

DRIPPER LINE

AIR /VACUUM RELIEF VALVE ----~:------.:--11----~


PER LEGEND 1" CLEAR BETWEEN
TOP OF PIPE AND
6" ROUND VALVE BOX -------'~11 VALVE BOX KNOCK OUTS
WITH LOCKING LID 1---~-.. (BOTH SIDES)

CLEAR

PLUMBED TO DRIPPER LINE

NOTES:
LEGEND ON PLANS
1. INSTALL AIR /VACUUM RELIEF VALVE AT HIGH POINT(S) IN VALVE CIRCUIT.

2. HEAT- BRAND VALVE BOX LID "AR". 0


3. VALVE SHALL BE CENTERED IN BOX.

4. TEFLON TAPE SHALL BE USED ON THREADED CONNECTIONS.

REVISION BY APPROVED DATE RECOMMENDED BY THE Ct1Y OF SAN DIEGO


STANDARDS COMMITTEE
CllY OF SAN DIEGO - STANDARD DRAWING
oil~
ORIGINAL• RH . NAGELVOOR OV12
1/31/2012
COORDINATOR R.C.E. 65271 DATE

AIR I VACUUM RELIEF VALVE DRAWING

NUMBER
SDI-128
MULCH DEPTH PER PLAN------, FINISHED GRADE

6" ROUND VALVE BOX-~


WILOCKING LID . - - - - 1" CLEAR BETWEEN TOP OF PIPE
AND VALVE BOX KNOCK OUTS
LINE FLUSHING VALVE-~
PER LEGEND

PVC LATERAL

SCH 40 PVC MALE ADAPTER


STANDARD BRICK SUPPORTS (3) WITH REDUCER

PLUMBED TO PVC

FINISHED GRADE

6" ROUND VALVE BOX


WILOCKING LID .----- 1" CLEAR BETWEEN TOP OF PIPE
AND VALVE BOX KNOCK OUTS
LINE FLUSHING VALVE
PER LEGEND

DRIPPER LINE

STANDARD BRICK SUPPORTS (3)

3-S" PEA GRAVEL S U M P . - - - - - - -


(1 CUBIC FOOT)
PLUMBED TO DRIPPER LINE

NOTES:
1. INSTALL FLUSH VALVE(S) AT THE LOWEST POINTS IN THE VALVE CIRCUIT
LEGEND ON PLANS
2. HEAT BRAND VALVE BOX LIDS "FV".

3. VALVE SHALL BE CENTERED IN BOX. ®

REVISION BY APPROVED DAlE RECOMMENDED BY THE Ct1Y OF SAN DIEGO


STANDARDS COMMITTEE
CllY OF SAN DIEGO - STANDARD DRAWING
oil~
ORIGINAL• RH . NAGELVOOR OV12
1/31/2012
COORDINATOR R.C.E. 65271 DAlE
DRIP IRRIGATION
DRAWING
FLUSH VALVE {AUTOMATIC) NUMBER
SDI-129
CHAPTER 6
LANDSCAPING
RUBBER TREE TIES
LOOPED IN A 'FIGURE 8'
AROUND TRUNK AND
STAKE.

EACH TREE TIE SHALL BE


NAILED TO STAKE USING
2" DIA. LODGEPOLE GALVANIZED NAILS.
P L AN
STAKE. MIN 10'
LENGTH.
NOT REMOVE SIDE GROWTH
ALONG TRUNK. PRUNE ONLY AS
DIRECTED BY ENGINEER.

2-2" DIA 10' MIN LENGTH LODGEPOLE


STAKES AND 4 TIES. TOP TREE TIES SHALL
BE 3" BELOW TOP OF STAKE. TIES SHALL
PROVIDE FLEXIBILITY OF TRUNK BUT NOT
ALLOW RUBBING OF TRUNK OR BRANCHES
AGAINST STAKE.

TOP OF ROOT BALL 1" ABOVE


FINISHED GRADE.

CHAMFER AS -3" MULCH, 3" CLEAR FROM


MAX
NEEDED TO
ELIMINATE SOIL
SLOUGHING.
1:1 MAX
4" HIGH BERM FIRMLY COMPACTED
SLOPE.

4" PERFORATED PVC BREATHER


TUBE W/ BLACK FLAT GRATE CAP
FASTENED STAINLESS STEEL
SCREW (2) WRAPPED IN FILTER
FABRIC & EX TENDING TO THE
BOTTOM OF PLANTING PIT.

......___ _ BACKFILL--~---

PLAN T T BOTTOM
PER SPECS.. EDGES OF PLANT PIT.
MAX 3" DEEP.
TREE BUBBLERS ON
UNDISTURBED NATIVE TREE BUBBLERS
UP HILL SIDE OF 4" PVC RIGID (SDI- 104)
TRUNK (SDI-1 04) PERFORATED
BREA THER TUBE
TREE STAKES TREE TRUNK
TREE TRUNK
(TYP)
4" PVC RIGID TREE STAKES
PERFORA TED

L
(TYP)
BREATHER TUBE
PLANTER HOLE PLAN TER HOLE
A - SLOPES
B - LEVEL GROUND
NOTES
1. DOUBLE STAKE 15 GAL. AND LARGER TREES. SINGLE STAKE TREES SMALLER THAN 15 GAL.
2. FOR SINGLE STAKED TREES, PLACE STAKE ON WINDWARD SIDE OF TREE.
3. LOCA TE STAKES OU TSIDE OF ROO TB ALL.
4. PROVIDE MINIMUM DISTANCE FROM O THER OBJECTS AS FOLLOWS:
20' TRAFFIC SIGNALS, 12' STREET LIGH TS, 10' FIRE H YDRAN TS, SEWER LINES AND SDG&E FOR
PAD MOUNTED EQUIPMENT. AND 5' UNDERGROUND SDG&E ELECTRIC AND GAS LINES.

REVISION BY APPROVED DAlE RECOMMENDED BY THE Ct1Y OF SAN DIEGO


STANDARDS COMMITTEE
CllY OF SAN DIEGO - STANDARD DRAWING
ORIGINAL• SG . NAGELVOOR OV12
oil~ 1/31/2012
COORDINATOR R.C.E. 65271 DAlE

TREE PLANTING AND STAKING DRAWING


NUMBER
SDL-101
CHAMFER AS
NEEDED TO
ELI
MINATE SOIL TOP OF ROOT BALL 1"
SLOUGHING.1:
1 ABOVE FI
NISHED GRADE
MAX SLOPE.

2" MULCH,3" CLEAR


FROM TRUNK
SL
OP
E
4" HI
GH BERM,
FI
RMLY COMPACTED

4"
DEPTH OF
ROOTBALL

ROOTBALL
DEPTH OF
PLANT TABLETS BURI
ED,
MAX 3" DEEP

BACKFI
LL

2 x BALL W I
DTH 2 x BALL W I
DTH
MIN SCARI
FY BOTTOM AND MI
N
EDGES OF PLANT PI
T

SHRUB PLANTI
NG - SLOPES SHRUB PLANTI
NG - LEVEL GROUND

EQUAL TRI
ANGULAR SPACI NG (EQ)
C
REQUIRED BETW EEN PLANTS AS
EQ

EQ

SHOW N ON PLANS

EQ
C

DISTANCE FROM EDGE OF


PLANTER TO CENTER OF PLANT
TO BE 1/
2 THE SPECI
FIED
C

GROUND COVER SPACI NG (EQ)


C

EDGE OF PLANTI
NG AREA

GROUND COVER SPACI


NG

RECOMMENDED BY THE CI
TY OF SAN DI
EGO
REVI
SION BY APPROVED DATE
STANDARDS COMMITTEE
CI
TY OF SAN DI
EGO - STANDARD DRAW I
NG
ORI
GINAL* KA J.NAGELVOORT 01/
12

2/
25/
16
UPDATED AR J.NAGELVOORT 02/
16
COORDI
NATOR R.
C.E.56523 DATE
SHRUB PLANTI
NG/
GROUND
DRAW I
NG
COVER SPACI
NG SDL-
102
NUMBER
8"
8" 8"
4" V2" R TYP - - - .

---
MULCH DEPll-t

--
FINISHED PER PlAN 2% 2%
GRADE
V2"TYP

#3 OR
'------- #4 REBAR------"

lYPE A lYPE B
ALL AREAS UNDER FENCES
EXCEPT UNDER
FENCES

PROVIDE SEALANT
AS SPECIFIED OR
AS APPROVED BY
ENGINEER

'1t2" PREFORMED
JOINT FILLER

WEAKENED PlANE JOINT EXPANSION JOINT


MAX 20'0C MAX 120' OC

NOTES
1. REBAR SHALL BE CONTINUOUS WITH 12" OVERLAP WHERE SPLICED.
2. CONCRETE SHALL BE CLASS 520-~2500 AND SAME COLOR AS ADJACENT CONCRETE AND
HAVE A SMOOTH TROWEL FINISH.
3. INSTALL WEAKENED PLANE JOINTS AT EACH FENCE POST.
4. INSTALL EXPANSION JOINTS WHERE THE MOWING STRIP ABUTS CONCRETE IMPROVEMENT AND
AT LOCATION APPROVED BY ENGINEER.

REVISION BY APPROVED DATE RECOMMENDED BY THE Ct1Y OF SAN DIEGO


STANDARDS COMMITTEE
CITY OF SAN DIEGO - STANDARD DRAWING
ORIGINAL* KA . NAGELVOOR OV12
oil~ 1/31/2012
COORDINATOR R.C.E. 65271 DATE

CONCRETE MOWING STRIP DRAWING


NUMBER
SDL-103
EXPANSION JOINT TYP

EXISTING CURB
#3 OR #4 SMOOTH DOWEL 8",
GREASED ON ONE END,
18" OC, TYP.

CLASS 520-C-2500
CONCREnE

TREE GRATE FRAME


ANCHORED INTO ADJACENT
CONCRETE PAVING
PER MANUFACTURE'S
" ~\_SPECIFIED
··.·.' . . '-----------/
. ....
BACKFILL MIX /
/
CONTINUOUS
RECOMMENDATION COMPACTED SUBGRADE.:::/
ROOT BARRIER
ON All SIDES
ELEVATION

TOP OF
CURB

SIDEWALK

6"
A A

#3 OR #4 - BARS ON FOUR
SIDES, LAP 15" AT
CORNERS, 2 l2" MIN
CONCREnE COVER OVER
L J
REINFORCEMENT

SECTION A-A
(CONCRETE SUPPORTS)

NOTES:

1. CONCREnE TO BE REMOVED FOR EACH TREE PLANTING SHALL BE SAW CUT FULL DEPTH.

2. BOLTS, NUTS AND WASHERS SHALL BE GRADE 316 STAINLESS STEEL. GRATE FRAME SHALL BE HOT DIPPED GALVANIZED AFTER FABRICATION. All GRATES
SHALL BE REMOVABLE & FASTENERS SHALL BE ACCESSIBLE TO MAINTENANCE .

3. GRATES SHALL BE MINIMUM 40 SQUARE FEET IN SIZE, AND 2 SEPARATE PIECES, UNLESS OTHERWISE SPECIFlED ON THE PLANS. SLOT OPENINGS IN GRATE
DESIGN SHALL HAVE 31!' MAXJMUM WIDTH. GRATE DESIGNS AND INSTALLATION SHALL BE IN ACCORDANCE WrTH CURRENT ADA STANDARDS AND THE LATEST
EDITION OF THE CAUFORNIA BUILDING CODE, WITH A MINIMUM UNIFORM LIVE LOAD OF 250 POUNDS PER SQUARE FOOT IN SIDEWALKS.

4. IMMEDIATE NOTIFICATION SHALL BE GIVEN TO THE ENGINEER OF ANY BELOW GRADE IMPROVEMENTS ENCOUNTERED.

5. SET GRATE IN FRAME PRIOR TO PLACEMENT OF PAVEMENT. ANY WARPED OR NON-FLUSH FITTING GRATES SHALL BE REPLACED.

6. TREE SHALL BE CENTERED IN GRATE OPENING. GRATES SHALL HAVE A PERMANENT SUP RESISTANT FlNISH.

7. ADJACENT SIDEWALK SHALL HAVE A MINIMUM CLEARANCE WIDTH OF 4' FROM THE EDGE OF GRATE.

8. GRATE SHALL BE UNIFORM WrTH ADJACENT GRADE.

9. PROVIDE MINIMUM DISTANCE FROM OTHER OBJECTS AS FOLLOWS: 12' STREET UGHTS, 10' FIRE HYDRANTS, 10' SEWER UNES, AND 20' TRAFFIC SIGNALS.

10. SUBMIT GRATE DESIGN FOR APPROVAL

REVISION BY APPROVED DATE RECOMMENDED BY THE Ct1Y OF SAN DIEGO


STANDARDS COMMITTEE
CllY OF SAN DIEGO - STANDARD DRAWING
ORIGINAL' KA . NAGELVOOR OV12
oil~ 1/31/2012
COORDINATOR R.C.E. 65271 DATE

TREE GRATE DRAWING

NUMBER
SDL-104
24"
24"
MI
N CLEAR
MI
N CLEAR
C C C
C

6'
-
R
A
D
IU I
RRIGATION
S
HEAD (TYP)

W EAKENED C
NEW
C
CONCRETE
PLANE JOINT C TURF
C W ALK
FI
NISH
TURF FI
NI SH C C GRADE 1/
2" C C
C

C
PULL BOX PULL BOX
MAX

MAX
12"

12"
GRADE 1/2" BELOW
BELOW CONCRETE
C

C
C W EAKENED
CONCRETE PLANE JOINT
C
W EAKENED
C

C
C
PLANE JOINT
18" DI
A X
6" DEEP
C
C

C
MORTAR

C
R 2'
-3" CAP W ITH R 2'
-3"
LI
GHT POLE TROW EL LI
GHT POLE MIN 3 - #3
FINISH OR #4 (12")
STEEL DOW ELS,
SQUARED W HEN GREASED ON
POURED NEXT TO ONE END
EXI
STI
NG W ALK

A - MONOLITHI
C CONCRETE B - PAD W HEN ADJACENT TO
PLACEMENT EXI
STING CONCRETE

NOTES:

1.USE MONOLI
THI
C PLACEMENT FOR NEW CONSTRUCTI
ON.

2.POLE PADS SHALL DRAI


N AT 1.
5% MI
NIMUM I
N SAME DI
RECTI
ON AS SI
DEW ALK.

3.CONCRETE PAD SHALL BE THE SAME AS SPECI


FIED FOR SI
DEW ALK.

4.LOCATE LI
GHT POLES OUTSI
DE OF TURF AREAS AND AW AY FROM TREES
AS APPROVED BY THE ENGI
NEER UNLESS SPECIFI
ED OTHERW ISE.

5.PULL BOX W I
TH BOLT-DOW N LI
D MINIMUM 6" FROM ALL EDGES
(POLYMER EDGED BOX W I
TH BRI CK FOUNDATI
ON).

6.I
RRIGATI
ON HEAD SHALL BE CLEAR OF CONCRETE W ALK OR PAD
PER SECTI
ON 801-5.
5.2 OF THE W HI
TEBOOK.

RECOMMENDED BY THE CI
TY OF SAN DI
EGO
REVI
SION BY APPROVED DATE
STANDARDS COMMITTEE
CI
TY OF SAN DI
EGO - STANDARD DRAW I
NG
ORI
GINAL* KA J.NAGELVOORT 01/
12

UPDATED KC J.NAGELVOORT 02/


16
2/
25/
16
COORDI
NATOR R.
C.E.56523 DATE

LI
GHT POLE PAD I
N TURF AREAS DRAW I
NG
SDL-
105
NUMBER
ROOT BARRIER REQUIRED WITHIN
10' OF TREE TRUNK, SEE NOTE 2

1~ ~----,1<'-
r

10' MIN

( ~TREE TRUNK

\ .../
10'MIN

ROOT BARRIER j i ;y

PLAN VIEW

ROOT BARRIER REQUIRED


WITHIN 10' OF TREE TRUNK

~--TOP OF ROOT BARRIER ~·


ABOVE FINISHED GRADE
HARDSCAPE, WALLS, BUILDINGS,- , \ - -- - 1
BROW DITCHES, OR OTHER
IMPROVEMENTS

.. .
_;. ···· ·'>::-.:.:~ :
~II {~:I II:UJ ~:
'==II'
TTl- _,' I 24" DEPTH ROOT BARRIER

SECTION

NOTE:
1. ROOT BARRIER SHALL BE INSTALLED ADJACENT TO THE IMPROVEMENT AND NOT AROUND THE ROOTBALL.
2. ROOT BARRIER REQUIRED WHEN TREE TRUNK IS WITHIN 10' OF HARDSCAPE, WALLS, BUILDINGS, BROW DITCHES, OR OTHER
IMPROVEMENTS.

3. FOR ROOT BARRIER INSTALLAnON WITH THE TREE GRATES SEE SDL- 104.

REVISION BY APPROVED DAlE RECOMMENDED BY THE Ct1Y OF SAN DIEGO


STANDARDS COMMITTEE
CllY OF SAN DIEGO - STANDARD DRAWING
ORIGINAL• I<A ~- NAGELVOOR OV12
oil~ 1/31/2012
COORDINATOR R.C.E. 65271 DAlE

ROOT CONTROL BARRIER DRAWING


NUMBER
SDL-106
CROWN -SET 1"
ABOVE FINISH GRADE
lASER TUBING OR POLY
TUBING WITH EMITIERS.
4" HIGH BERM ROOTBALL - DO NOT TRIM

PlANT TABLETS (TYP)


BURIED 3" BELOW
GRADE

I
PLANT PIT 1
""'=- -W'ROUGHENEDI
SIDES I
I

NOTES:

1. TIE PALM FRONDS TOGETHER WITH BIODEGRADABLE SISAL TWINE. TWINE SHALL BE REMOVED AFTER 90 DAYS
OF TRANSPLANTING UNLESS UNLESS OTHERWISE DIRECTED BY THE ENGINEER.

2. PALM TRUNKS SHALL BE SKINNED, TRIMMED, AND VERTICAL.

3. STEM DIAMETER REQUIREMENT APPLIES ONLY TO PHOENIX SPECIES.

SHEET 1 OF 2

REVISION BY APPROVED DAlE RECOMMENDED BY THE CI1Y OF SAN DIEGO


STANDARDS COMMITTEE
CITY OF SAN DIEGO - STANDARD DRAWING
ORIGINAL• KA • NAGELVOOR OV12
oil~ 1/31/2012
COORDINATOR R.C.E. 65271 DAlE

PALM TREE PLANTING DRAWING


NUMBER
SDL-107
FLAT, BLACK SLOTIED GRATE
(FASTEN TO PIPE WITH
STAINLESS STEEL SCREWS (2))

DUCT TAPE OVER HOLES


WITHIN 6" OF FINISHED GRADE
4" HIGH BERM
FIRMLY COMPACTED 4" PVC RIGID PERFORATED PIPE WRAPPED IN
FILTER FABRIC FOR ENTIRE LENGTH
FINISH GRADE
AT ROOTBALL

FINISH GRADE

PLANT-----
BACKFILL

PLANTING
HOLE DEPTH

DETAIL- A
BREATHER TUBE

SHEET 2 OF 2

REVISION BY APPROVED DATE RECOMMENDED BY THE CITY OF SAN DIEGO


STANDARDS COMMITIEE
CITY OF SAN DIEGO - STANDARD DRAWING
ORIGINAL* KA . NAGELVOOR OV12
dl~ 1/31/2012
COORDINATOR R.C.E. 65271 DATE

PALM TREE PLANTING DRAWING


NUMBER
SDL-107
CHAPTER 7
MISCELLANEOUS
C

C
C
W D'
4 C
C

C
C'
MEDIAN

T
GEN
X TAN

W
C
C
C 3W
C
W 4
C
B' BASE LI
NE
C

Y 4 C

C
C
C C

CA L/
3 C B L/
3 C
C L/
3 D
C C C

C L
C

2
X
Y = 2.
25 W (L)
L = LENGTH OF TRANSITI
ON
W = MAXIMUM OFFSET DISTANCE
X = DISTANCE ALONG BASELINE
Y = OFFSET FROM BASELINE

L DI
STANCE X

60' 5' 10' 15' 20' 25' 30' 35' 40' 45' 50' 55' 60'

90' 7.
5' 15' 22.
5' 30' 37.
5' 45' 52.
5' 60' 67.
5' 75' 82.
5' 90'

120' 10' 20' 30' 40' 50' 60' 70' 80' 90' 100' 110' 120'

W OFFSET Y

10' 0.
16' 0.
62' 1.
41' 2.
50' 3.
75' 5.
00' 6.
25' 7.
50' 8.
59' 9.
38' 9.
84' 10.
00'

11' 0.
17' 0.
69' 1.
55' 2.
75' 4.
13' 5.
50' 6.
88' 8.
25' 9.
45' 10.
31' 10.
83' 11.
00'

20' 0.
31' 1.
25' 2.
81' 5.
00' 7.
50' 10.
00' 12.
50' 15.
00' 17.
19' 18.
75' 19.
69' 20.
00'

22' 0.
34' 1.
38' 3.
09' 5.
50' 8.
25' 11.
00' 13.
75' 16.
50' 18.
91' 20.
62' 21.
66' 22.
00'

NOTE: 2
X
TO DETERMI NE OFFSET DI
STANCE FOR ANY LENGTH OF TRANSITI
ON USE THE FORMULA Y = 2.
25W ()
L
FOR THE PORTIONS AB'AND C'D'W HI
CH ARE PARABOLIC CURVES.THE PORTION B'C'I
S A
TANGENT.W HEN THE BASELINE I
S CURVED,THE OFFSETS ARE APPLI
ED TO THE CURVED BASELI
NE,
AND B'C'I
S NO LONGER A TANGENT.

RECOMMENDED BY THE CI
TY OF SAN DI
EGO
REVI
SION BY APPROVED DATE
STANDARDS COMMITTEE
CI
TY OF SAN DI
EGO - STANDARD DRAW I
NG
ORI
GINAL JQ G.PARKI
NSON 2/
95

2/
25/
16
UPDATED KA J.NAGELVOORT 02/
16
COORDI
NATOR R.
C.E.56523 DATE

LEFT TURN M EDI


AN TRANSI
TION DRAW I
NG
SDM -
101
NUMBER
==r2 V2"
10"

48" - - - - - - - - - - - - - 1
LENGTH AS NECESSARY

BLADES

SPACER TELSPAR

NOTES

1. LETTER STYLE: FUTURA BOLD CONDENSED

2. LEDER SIZE: 6" 5" 2 V2"

3. CITY SEAL: 4"

4. BACKGROUND: TYPE IV PRISMATIC SHEETING

5. ELECTRO CUT BLUE OVER WHITE

6. .065 ALUMINUM

7. MOUNTED TO TELSPAR WITH 3-8" DRIVE RIVETS

8. 4" TALL BY 1 V4" SQ. CHANNEL SPACER HELD WITH VHB 4950 TAPE

9. CONTACT CITY OF SAN DIEGO SIGN SHOP, (619) 527-7528 FOR A LIST OF APPROVED
VENDORS FOR CITY SEAL.

SHEET 1 OF 4

REVISION BY APPROVED DATE RECOMMENDED BY THE CITY OF SAN DIEGO


STANDARDS COMMITIEE
CITY OF SAN DIEGO - STANDARD DRAWING
dl~
ORIGINAL J. CASEY 111&88
1/31/2012
UPDATED KA . NAGELVOOR OV12
COORDINATOR R.C.E. 65271 DATE

STREET NAME SIGN DRAWING


NUMBER
SDM-102
PERMANENT STREET NAME SIGNS

GENERAL:

STREET NAME SIGN ASSEMBLY FOR POST TOP MOUNTING SHALL CONSIST OF NAME BLADE UNITS,

24" LONG 1 V2" SQUARE TELESPAR EXTENSION AND DRIVE RIVETS. ALL AS INDICATED ON THE

STANDARD DRAWINGS ANIYOR SPECIFIED IN THESE NOTES. ASSEMBLIES SHALL BE MOUNTED

TO 1 314" SQUARE TELESPAR POSTS.

NAME BLADE UNITS:

NAME BLADE UNITS SHALL BE SINGLE FACED AND MADE FROM 10" WIDE (TOP TO BOTIOM)

ALUMINUM SHEET STOCK, MILL FLAT, 6061- T6 OR 5052 ALLOY, .063 THICK. ENDS OF BLADE

SHALL BE PERPENDICULAR TO TOP BOTIOM EDGES. EDGES SHALL BE FREE OF SHARP BURRS.

EACH BLADE SHALL BE DRILLED WITH TWO 7116" HOLES, ONE AT TOP AND AT BOTIOM

EDGE OF SIGN. HOLES TO BE CENTERED ON BLADE AND V2" FROM EDGE.

BLADE SHALL BE COVERED WITH TYPE IV PRISMATIC WHITE REFLECTIVE SHEETING.

LETTERING:

STREET NAME SHALL BE CUT FROM BLUE E.C. FILM MATERIAL AND APPLIED OVER THE WHITE BACKGROUND,

CREATING A SIGN WITH A BLUE BACKGROUND AND WHITE LETTERING. TYPE FONT SHALL BE FUTURA BOLD

CONDENSED. LETIERING HEIGHT OF STREET NAME SHALL BE 6" FOR FIRST LETIER AND 5" FOR THE

REST OF THE NAME. STREET AND BLOCK NUMBER SUFFIX SHALL BE 2 V2" FUTURA BOLD CONDENSED.

LAYOUT TO BE AS SHOWN ON SHEET 1 OF 4 ON THE STANDARD DRAWING.

MOUNTING OF SIGN:

EACH NAME BLADE SHALL BE MOUNTED TO THE 1 V2" TELESPAR EXTENSION WITH A 3-8" DRIVE RIVET.

EACH STREET NAME SHALL BE MOUNTED BACK TO BACK WITH THE TELESPAR SANDWICHED IN

BETWEEN AND THE ENDS FASTENED TOGETHER WITH VHB DOUBLE STICK TAPE.

A SQUARE CHANNEL SPACER IS REQUIRED ON BLADES SHORTER THAN 36".

THE EXTENSION IS TO BE PLACED INSIDE THE 1 314" TELESPAR POST AND FASTENED WITH A DRIVE RIVET.

SHEET 2 OF 4

REVISION BY APPROVED DATE RECOMMENDED BY THE Ct1Y OF SAN DIEGO


STANDARDS COMMITTEE
CITY OF SAN DIEGO - STANDARD DRAWING
oil~
ORJGINAL J . CASEY 1168
1/31/2012
UPDATED KA ~- NAGELVOOR OV12
COORDINATOR R.C.E. 65271 DATE

STREET NAME SIGN DRAWING


NUMBER
SDM-102
STREET NAME SIGN STANDARDS

SUFFIX AND PREFIX ABBREVIATIONS :

AVENUE AVE
STREET ST
COURT CT
DRIVE DR

ROAD RD
BOULDEVARD BLVD
TERRACE TER
MOUNTAIN MTN
MOUNT MT
POINT PT
CAMINITO CMTO
CAMINO CAM
RANCHO RCHO

SPELL OUT "FIRST AVE THROUGH TWELFTH AVE"

THEN : 13TH ST -14TH ST ETC.

NOTE:
FOR A COMPLETE LIST OF SUFFIX AND PREFIX ABBREVIATIONS REFER
TO THE OFFICIAL USPS ABBREVIATION. SHEET 3 OF 4

REVISION BY APPROVED DATE RECOMMENDED BY THE Ct1Y OF SAN DIEGO


STANDARDS COMMITTEE
CllY OF SAN DIEGO - STANDARD DRAWING
oil~
ORJGINAL XX J.P. CASEY 1168
1/31/2012
REV. - 1 TH 7,00
COORDINATOR R.C.E. 65271 DATE
UPDATED KA . NAGELVOOR 01112
STREET NAME SIGN DRAWING
NUMBER
SDM-102
CURB & SIDEWALK
SIDEWALK SETBACK
WIDTH

r
CONTIGUOUS 6'0R LESS SIDEWALK
WIDTH SETBACK
CONTlGUOUS MORE (SEE TABLE)

J-
2'- 6" SLOPE TO V4"
THAN 6' mw
a:z
SEPARATE 2'- 6" 3~ N
I
,....
ABOVE GRADE

i
:: ~
~\ r
----
10" DIAMETER FOOTING
: ~· . OF 520-C-2500
!< CONCRETE

.
:~·­

--'--t-r-....... :: ~

L2"MIN


LEGEND ON PLAN

LOCATION NOTES

1. ALONG MAJOR OR PRIMARY STREETS


THERE SHALL BE 2 SIGN INSTALLATlONS
PER INTERSECTION PLACED ON • Lna>-
CI:<(~
<Co
tJ:j
w
a:
f-
(f) .2
za:~
OPPOSITE CORNERS <(WQ
1--'0..()
MINOR ::J~w STREET
2. ALONG A COLLECTOR OR LOCAL 0 (f)

STREETS THERE SHALL BE ONE ~a: a:


a:~o

.4
SIGN INSTALLATION PER INTERSECTION
IJJ~a:
~
:::iEIO
oa:~
1-0:::E

'
STREET NAME SIGN LOCATION
(NUMBERS INDICATE PRIORITY OF LOCATION
SELECTION WHEN THERE IS A CONFLICT
WITH OTHER IMPROVEMENTS)

SHEET 4 OF 4

REVISION BY APPROVED DATE RECOMMENDED BY ll-IE Ct1Y OF SAN DIEGO


STANDARDS COMMITTEE
CITY OF SAN DIEGO - STANDARD DRAWING
oil~
ORJGINAL J.P. CASEY
1/31/2012
REV.-1 ll-1 7,00
COORDINATOR R.C.E. 65271 DATE
UPDATED KA ~- NAGELVOORl OV12
STREET NAME SIGN DRAWING

NUMBER
SDM-102
PROPERTY PROPERTY PROPERTY PROPERTY
SIDE s~ SIDE~ Sl~
24" -=- 24" 24"
~
~ ~
1l
- - .r - 2· -
liE
~2"
MAX Fill liE
- MAX
1§2"
311

- Ill=

r 2·
MAX !=Ill

" ~-r':
[ -r 12I 12I 12r
u

u
j·· u

1 J
12" uo ±- 1-9
g•

m{ . . ·ry:
9"
~0 ..:ry. !" .·cy..
0 . ...
~ :-o .. . ·. 12"
2"
11112

~ . .·ME ."·
.
• . ·..
.•
..
. .
• : • •
3

~It:::
HWI . . .
• · . ME · .
.. .
.. .. .. ... II==
3"
.
-b ·· ·o·
· · ME · .
. . ill==
..bxe
:: :' ,-, :,.·-:,:·:,:·;·:
11ffi 11ffi II iii 11
iii\_:SL I 3"

lYPE A TYPE B lYPE C lYPE D

PROPERTY PROPERTY PROPERTY


Sl~ ~ Sl~ ~ s~ MINIMUM COVER
~ LEGEND

- t2" - ~2"
GM
GS
p
GAS MAIN
GAS SERVICE
PRIMARY ELECTRIC
30'
30'
42"

~~~ ~~~
s SECONDARY ELECTRIC 30"

]9" ES ELECTRIC SERVICE 30"

c;
00

p p p
2"

n:· .
=n ffi\_SL
~
~ 3
(.i ____!_
.· :· .. : ... ..~- ...
t
MULTIPLE ELECTRIC
ME (P, S OR ES IN SPACERS)
CONCRETE ENCASED
SL STREET UGHT (NOT SERIES)
CATV
24"

30'
24"
3" u 24"
TELCO
lYPE E TYPEF lYPE G
SERVICE TRENCH
ON
PUBLIC PROPERTY

NOTES
1. ALL DIMENSIONS ARE lYPICAL UNLESS OTHERWISE NOTED.

2. THE LOCATION OF UTILITIES AS SHOWN BY THE STANDARD DRAWING SHALL IN NO WAY VIOLATE EXISTING CODES OR
REGULATIONS APPLICABLE TO INDIVIDUAL UTILITIES.

3. INSTALLATION OF SEWER OR WATER UTILITIES ARE NOT PERMITTED IN THE JOINT TRENCHES SHOWN ABOVE.

4. MINIMUM DEPTH OF GAS PIPE MAY, SUBJECT TO GAS COMPANY INSPECTORS APPROVAL, BE REDUCED TO 24" WHERE
NECESSARY TO CLEAR STRUCTURE CROSSINGS.

5. DEPTH AND WIDTH OF TRENCH VARIES.

6. CATV MAIN OR TRUCK LINE CONDUIT REQUIRED ALONG ALL STREETS, EXCEPT CUL-DE-SAC STREETS LESS THAN 1000' IN
LENGTH WHICH MAY BE SERVED BY FEEDER LINES ONLY.

7. CATV 1 V2" FEEDER CONDUIT SHALL RUN ACROSS STREETS WITH EACH POWER SERVICE LINE AND CAPPED AT EDGE OF
SIDEWALK.

8. ALL CATV TERMINALS AND CONDUITS SHALL BE TERMINATED AT GENERALLY ACCEPTED LOCATIONS AND MARKED. A MAP
SHALL BE FILED WITH THE CllY SHOWING THE LOCATIONS OF THE CATV SYSTEM.

9. IN NO CASE SHALL CATV CONDUITS BE PLACED WITHIN 12" OF GAS LINES, ALSO CONDUITS SHALL NOT BE PLACED
DIRECTLY OVER GAS LINES.

10. CATV CONDUIT MAY BE PLACED WITH THE TELCO CONDUIT PROVIDED THE TELCO MINIMUM DEPTH IS HELD.

11. TRAFFIC SIGNAL CONDUIT SHALL BE PLACED WHERE STREET LIGHT CONDUIT IS SHOWN.

REVISION BY APPROVED DATE RECOMMENDED BY THE CI1Y OF SAN DIEGO


STANDARDS COMMITTEE
CllY OF SAN DIEGO - STANDARD DRAWING
ORIGINAL* BY ~- NAGELVOOR1 01112
oil~ 1/31/2012
COORDINATOR R.C.E. 65271 DATE

JOINT TRENCH LOCATIONS DRAWING

NUMBER
SDM-103
NOTES 6'
C C 13/4" X 13/
4"
(
UNLESS OTHERW I
SE SHOW N ON PLANS) 12 GAUGE POST
1. STRUCTURAL STEEL TUBI
NG USED
FOR POST & SLEEVES SHALL BE
GALVANIZED 12 GAUGE COLD ROLLED
STEEL OF THE NOMINAL DI
MENSIONS
SHOW N HERE,AND MEET THE
REQUIREMENTS OF ASTM A653.

C
2" + /
-

C
2. GALVANI ZI
NG SHALL BE PER ASTM
A653.POSTS & SLEEVES SHALL
HAVE 7/ 16" DIA.HOLES SPACED
1" O.C.1/
8" & + / - 1/
8" & SHALL

C
HAVENO MORE VARI ATION I N
STRAI GHTNESS THAN 1/ 16" I
N 3'.
POSTS SHALL BE SQUARE W I THIN
+/ - 0.
014",HAVE TW I ST NO GREATER
THAN 0. 62" I
N 3'AND HAVE CORNER C

C
RADIOF 5/ 32" + /
- 1/64".

MAXIMUM 8' 1/4" TO CENTER OF SIGN


3/
8" RI
VET TYP.
3. THE SIGNS SHALL BE MOUNTED ON
POSTS IN ACCORDANCE W I TH
SECTION 56,"SI
GNS" OF THE STATE
STANDARD SPECI FI
CATI
ONS.ALL RI
VET SPECIFI
CATION
FASTENING HARDW ARE IS TO BE DI
MENSI ON:3/
8" DIA.SHANK
PROVIDED BY THE CONTRACTOR. 7/
8" DIA.HEAD
GRIP RANGE:.200-.356
4. MAXI
MUM SI
GN SI
ZE 5.
2 SQ.FT.
FI
NISH:ELECTRO-GALVANI
ZE
5. TO AVOI D CONCRETE INTRUSION ASTM-B-633
I
N THE POST HOLES,ALL METAL TYPE I
IISCI
I
N CONTACT W I TH CONCRETE SHALL
7'

BE W RAPPED IN 10 MI
L POLYETHYLENE
W RAPPI
NG TAPE W ITH EACH W RAP OF 3/
8" RI
VET TYP.
TAPE TO OVERLAP THE PREVIOUS W RAP
BY 1/
3 THE W I
TH OF THE TAPE
(I
NCLUDI NG THE BOTTOM).
SLOPE TO 1/
4"
ABOVE GRADE

EXI
STI
NG GROUND
C

C
3"
C
C

C
C

12"

18"

C
C

2 1/
4"X 2 1/
4"-12 GAUGE
C

ANCHOR POST
32"

C
C

2"X2"-12 GAUGE
ANCHOR POST
C

MINIMUM
2"

10" MI
NIMUM
DIAMETER FOOTI
NG
CONCRETE 520-C-2500

RECOMMENDED BY THE CI
TY OF SAN DI
EGO
REVI
SION BY APPROVED DATE
STANDARDS COMMITTEE
CI
TY OF SAN DI
EGO - STANDARD DRAW I
NG
ORI
GINAL BB J.NAGELVOORT 05/
15

2/
25/
16
UPDATED MM J.NAGELVOORT 08/
15
COORDI
NATOR R.
C. 56523
E. DATE
UPDATED AR J.NAGELVOORT 02/
16
BREAK-
AW AY SI
GN POST DRAW I
NG
SDM -
104
NUMBER
W ATER METER
OR CLEANOUT

FI
RE HYDRANT

C
T

6" TRENCH MARKER TAPE PLACED AT 4" C

C
BELOW PAVEMENT SECTI
ON

C
P/
L,RW OR
EDGE OF
OVERLAP TAPE C SEE NOTE 3
EASEMENT
C
C

C APPURTENANCES
C

WATER MAIN
LATERAL SERVI
CE
C
W ATER SERVI
CE

C
MAI
N C
W

TYPI
CAL SECTI
ON

MAIN
T
C

C P/
L,RW OR
EDGE OF
EASEMENT

CURB
T AI
R VALVE

PLAN

NOTES:
1.TRENCH MARKER TAPE SHALL BE 6" W I
DE AND CONSI ST OF A MI
NIMUM 5.0 MI
L,FI
VE-PLY 100% VI RGI
N POLYETHYLENE
W HI
CH IS ACID,ALKALINE,AND CORROSION RESISTANT.ELONGATION PROPERTIES AND TENSI LE STRENGTH OF NOT LESS
THAN 7,800 PSISHALL BE IN ACCORDANCE W I
TH ASTM D882-80A.THE TRENCH MARKER TAPE FOR W ATER LI NES SHALL
HAVE A MINIMUM 20 GAUGE SOLI D ALUMINUM FOI L CORE,ADHERED TO A 2.55 MIL POLYETHYLENE BACKING.

2.TAPE SHALL BE I
NSTALLED ABOVE THE PI
PE AS SPECI
FIED AND RUN CONTI
NUOUSLY ALONG THE LENGTH OF THE PI
PE
AND ALL RELATED APPURTENANCES.

A.BLUE W I
TH "CAUTI
ON POTABLE W ATER LI
NE BURI
ED BELOW " FOR W ATER MAI
NLI
NES AND OVER PI
PE SLEEVES.

B.PURPLE W I
TH "CAUTI
ON RECYCLED/
RECLAI
MED W ATER LI
NE BURI
ED BELOW " FOR RECYCLED W ATER AND I
RRI
GATI
ON
MAINLI
NES.

C.RED W I
TH "CAUTION ELECTRI
C LINE BURIED BELOW " FOR ELECTRI
CAL LI
NES,I
NCLUDING,BUT NOT LI
MITED TO,110/
220V
POW ER TO I
RRIGATION CONTROLLERS AND PUMPS,TRAFFI C SIGNALS AND STREETLI
GHTS,COMMUNI CATI
ON CABLES AND
I
RRIGATION DIRECT BURI
AL CONTROL W I
RES TO REMOTE CONTROL VALVES.

D.GREEN W I
TH "CAUTI
ON SEW ER LI
NE BURI
ED BELOW " FOR SEW ER MAI
NLI
NES AND OVER PI
PE SLEEVES.

E.GREEN W I
TH "CAUTI
ON STORM DRAI
N LI
NE BURI
ED BELOW " FOR STORM DRAI
N MAI
NLI
NES AND OVER PI
PE SLEEVES.

3.ELECTRI
CALLY BOND W ATER SERVI
CE TAPE AND W ATER MAI
N TAPE TOGETHER.TAPE SHALL EXTEND W I
THI
N METER BOX
I
TSELF TO ALLOW MARKOUT BY CONTI NUI
TY TESTER.

RECOMMENDED BY THE CI
TY OF SAN DI
EGO
REVI
SION BY APPROVED DATE
STANDARDS COMMITTEE
CI
TY OF SAN DI
EGO - STANDARD DRAW I
NG
ORI
GINAL KA J.NAGELVOORT 01/
12

2/
25/
16
UPDATED BB J.NAGELVOORT 06/
15
COORDI
NATOR R.
C.E.56523 DATE
UPDATED BD J.NAGELVOORT 02/
16 W ARNI
NG / I
DENTIFI
CATION
DRAW I
NG
TAPE I
NSTALLATION SDM -
105
NUMBER
LEGEND:
DUAL - HEIGHT DRINKING FOUNTAIN I>S APPROVED
BY THE CITY ENGINEER.

(2_._) W ' X 4" LOOP ANCHORS AND W' X 1 W' BOLTS AT ALL
LOCATIONS OR PER MANUFACTURER'S RECOMMENDATION.

(J..) 1 V4" P.V.C. PIPE WITH SWEEP 90 DEGREE ELBOW


•...•• CONNECTION TO FOUNTAIN DRAIN.

PLAN 9 W ' X 16" CONCRETE YARD BOX WITH HINGED LOCKING


TOP (BROOKS NO. 3HL OR EQUAL) SET ON RED BRICK
FOUNDATION.

4' X 40' PERFORATED PLASTIC UNDERDRAIN PIPE,


ENCI>SED IN 314" CRUSHED ROCK.
2'~
1' GATE VALVE WITH RED BRI>SS CROSS HANDLE AND
0 UNION.

T~ L-..,-- - --1 40'


2' DIA PIPE SLEEVE WITH RED BRASS LOCK CAP.

RIGID COPPER PIPE FROM GATE VALVE TO FOUNTAIN


;:.; ASSEMBLY CONNECTION .

SECTION B-8

'~T'·~·l
SLOPE WITHIN LANDING SHALL
·>----------+----~ BE 1.5% IN ANY DIRECTION

TOOLED JOINT V4' DEEP GROOVE


WITH V4' RADIUS EDGES

I• LANDING

SLIP-BESISTANT FINISH
PLAN AT ALCOVE ALONG
CONCRETE WALKWAY

NOTES:
1. INSTALL DRINKING FOUNTAINS SO THAT RIGKT HAND SIDE FACES PREVAILING WIND.

2. HAND FORM A CONCRETE BOWL AT BOTIOM OF YARD BOX TO FACILITATE SAND CLEAN OUT.

3. PERFORATED DRAIN PIPE AND TRENCH SHALL DRAIN AWAY FROM FOUNTAIN.

4. USE RED BRI>SS BUSHING REDUCERS TO ADAPT TO FEED PIPE.


LEGEND ON PLANS
5. LOCATE DRINKING FOUNTAINS IN AN ALCOVE OR AT AREI>S OUTSIDE THE PATH-OF-TRAVEL OTHERWISE
PROVIDE PROTECTIVE RAILING PER SDM-108.

6. NO WATER PONDING IS ALLOWED IN LANDING AND ALCOVE AREI>S.

REVISION BY APPROVED DATE RECOMMENDED BY THE CITY OF SAN DIEGO


STANDARDS COMMITTEE
CITY OF SAN DIEGO - STANDARD DRAWING
oil~
ORJGINAL SM A. OSKOUI 1W3
1/31/2012
UPDATE FC A. OSKOUI 1206
COORDINATOR R.C.E. 65271 DATE
DUAL HEIGHT DRINKING FOUNTAIN DRAWING
OV12 (NEW CONSTRUCTION) NUMBER
SDM-107
z 12"
~a.
=
co
.,....
~ lYP WALL

18" MIN 18" MIN SEE NOTE #1

I NO PONDING ALLOWED

it
IN LANDING AREA
~I
EDGE OF ~ ~t I
I
l_L LANDING--------
______ _j
I

PLAN

ISOMETRIC VIEW

NOTES:
1. UNLESS LOCATED IN AN ALCOVE, WING WALLS OR PROTECTIVE RAILINGS ARE REQUIRED
ON BOTH SIDES OF DRINKING FOUNTAINS THAT PROJECT INTO THE PATH OF TRAVEL.

2. HANDRAILS AND GUARDRAILS MATERIAL & FINISH:

A. PIPE RAILINGS SHALL BE HOT DIPPED GALVANIZED OR AUSTENITIC (NON-CORROSIVE)


STAINLESS STEEL.

B. PIPE RAILINGS SHALL BE SEAMLESS STEEL, ASTM A53 GRADE B.


LEGEND ON PLANS
3. THE LANDING SHALL BE PAVED WITH A SOLID AND STABLE MATERIAL WITH A
SLIP-RESISTANT FINISH.

REVISION BY APPROVED DATE RECOMMENDED BY THE Ct1Y OF SAN DIEGO


STANDARDS COMMITTEE
CITY OF SAN DIEGO - STANDARD DRAWING
oil~
ORJGINAL SS A. OSKOUI 1W3
1/31/2012
UPDATE FC A. OSKOUI 1200
COORDINATOR R.C.E. 65271 DATE
UPDATE FC A.OSKOUI 1200 DUAL HEIGHT DRINKING FOUNTAIN
OV12 DRAWING
UPDATE KA . NAGELVOOR
NON-ALCOVE {FOR EXISTING STRUCTURES) NUMBER
SDM-108
10'TYPI
CAL PROPERTY LI
NE
C
C
PEDESTAL C

TRENCH
LOCATI
ON

C
*JOINT TRENCH

C
C 4' PULLBOX SERVI
CE CONDUI
T
C

CONDUI
T

SECTI
ON VI
EW

TRENCH LOCATI
ON

PROPERTY LI
NE
C

10'
C
C C

4'
C
C

PEDESTAL /
PULLBOX
C

4'OR 5' C
C

SERVI
CE CONDUI
T

CONDUI
T

CURB
JOINT TRENCH

C
C

* JOI
NT TRENCH

1. GAS

2. STREET LI
GHTS

3. UNDERGROUND ELECTRI
C

4. TELEPHONE
PLAN VI
EW
5. CATV

NOTE:

SI
DEW ALK SHALL HAVE A MI
NIMUM OF FOUR ( 4)FOOT
CLEAR (PATH)PASSI
NG PEDESTALS,PULLBOXES AND
OTHER STRUCTURES.

RECOMMENDED BY THE CI
TY OF SAN DI
EGO
REVI
SION BY APPROVED DATE
STANDARDS COMMITTEE
CI
TY OF SAN DI
EGO - STANDARD DRAW I
NG
ORI
GINAL J.
P.CASEY 8/
86

01/
12
2/
25/
16
UPDATED KA J.NAGELVOORT
COORDI
NATOR R.
C.E.56523 DATE
UPDATED AR J.NAGELVOORT 02/
16 UNDERGROUND TYPI
CAL LOCATI
ON
(
NEW CONSTRUCTION) DRAW I
NG

NUMBER
SDM -
109
NEW CONSTRUCTION
'

4' TO 6' ffi i 4_'-__1o_· ~_. : __10


_' ---1 4'TO 6' ttl
~I3l: I
;I t-__ ;

- I
I
'
I
I
I II
w w

~ I~~~=====z=l=====---@-~-----~-1~!-----ffi~~~=====z=,=====C~~
z z
::J ::J

m
-0
-,
~t>l0! ~:
a::l ffi: ~ ~~ 0t;l~!
t:;
0
(f)
:o
0-,
LOCAL AND MAJOR STREET

~ 4 6
'TO ' i ~ ,:.,.__4_,__1~o·_ .t i4'TO 6' ~
I 3l: I ' I
~ ~~~c::::~::l:a::::::~-ow--~------ffi~i--------~====::~::la:::::::C~r-~~
m 6
-,
~!!~ a::l~:
o o
1--10
w ~
w
~~ I
PRIME ARTERIAL
~~!~
ol--Io
w ~
0
:o
o
-,

. 5'

~ 4'TO 6' i 7 i 4'TO 6' ~


~w I ' I - ~
~ ~~~~====z=~====~------~~~------=====Z==I====~~~
w
a... a...
0 0
a: a:

;o :o
a... a...

!:
~I
iI ~ :~ o
'6 t>l EXPRESSWAY
~I '

NOTES:

1. AT CATCH BASIN LOCATIONS, JOINT TRENCH SHALL BE 7' MINIMUM FROM BACK OF CURB TO INSIDE WALL OF TRENCH.

2. SEWER AND RECLAIMED WATER MAINS AND LATERALS SHALL BE DESIGNED TO CROSS UNDER POTABLE WATER
MAINS WITH A MINIMUM VERTICAL SEPARATION OF 12".

3. SEWER AND RECLAIMED WATER MAINS SHALL MAINTAIN A 10' MINIMUM HORIZONTAL SEPARATION FROM ANY POTABLE WATER.

REVISION BY APPROVED DATE RECOMMENDED BY THE Ct1Y OF SAN DIEGO


STANDARDS COMMITTEE
CITY OF SAN DIEGO - STANDARD DRAWING
oil~
ORJGINAL J . CASEY 0096
1/31/2012
UPDATE KA U.NAGELVOORl W12
UTILITY LOCATIONS IN LOCAL COORDINATOR R.C.E. 65271 DATE

AND MAJOR STREETS, PRIME DRAWING


ARTERIALS AND EXPRESSWAYS NUMBER
SDM-111
C 10'MAX C 10'MAX
C C CORNER OR
POST TOP C
END POST

C
TOP RAI
L
C

C
HEIGHT SHOWN ON PLANS
C STRECHER
BAR
C

C LI
NE POST W I
TH C
3/
8" TRUSS ROD
C
FASTENDERS
C

GALV.CAP WI
TH TENSI
ONER

CROW N FOR
GALV.CHAI
N-LI
NK
DRAI
NAGE
2" MESH
GROUND
C
BOTTOM RAI
L
LI
NE

C
C

C
C

C
CROW N FOR DRAI
NAGE
C
FOOTI
NG C
DEPTH = 2'- 6" FOR FENCE
HEI
GHT OF 5'OR UNDER. C
DEPTH = 3'- 0" FOR FENCE
HEI
GHT OF OVER 5'
2" 2" 2"
C

C
C
C

C
C
C
DI
AMETER OF FOOTI
NG = 4 TI
MES C
MID-RAI
LI F FENCE
OUTSI
DE DI
AMETER OF POST.
HEIGHT EXCEEDS 8'

NOTES:

1. ALL FOOTI
NGS SHALL BE 520-C-2500 CONCRETE.

2. THE FOLLOW I
NG I
TEMS SHALL BE FURNI
SHED AND
I
NSTALLED ONLY W HEN SHOW N ON THE PLANS
OR CALLED FOR IN THE SPECI
AL PROVI
SIONS:
A. BARBED W I
RE
B. EXTENSI
ON ARM

3. CHAIN LI
NK FENCE SHALL CONFORM TO THE
STANDARD SPECIFI
CATIONS FOR PUBLIC W ORKS CONSTRUCTI
ON
UNLESS SPECI
FICALLY NOTED ON THIS DRAW I
NG.

4. CHAIN LI
NK FENCE AND ALL FI
TTINGS SHALL BE BLACK 22 MI
L
PRESSURE - BONDED OR 7 MIL THERMALLY - FUSED VI
NYL COATED
OVER 9 GAUGE ALUMINI
ZED STEEL CORE FABRI C PRIOR
TO COATING.POSTS AND RAI LS SHALL BE GALVANIZED STEEL
PVC VI
NYL BONDED,10 - 14 MIL(COLOR SHALL MATCH FABRI C).

5. CHAI
N LI
NK FABRI
C SHALL HAVE KNUCKLED FI
NISH ON TOP EDGE.
LEGEND ON PLANS
6. SEE M-20 FOR ADDI
TIONAL DETAI
LS.
X X X X X

RECOMMENDED BY THE CI
TY OF SAN DI
EGO
REVI
SION BY APPROVED DATE
STANDARDS COMMITTEE
CI
TY OF SAN DI
EGO - STANDARD DRAW I
NG
ORI
GINAL J.
P.CASEY 06/
92

2/
25/
16
UPDATE KA J.NAGELVOORT 01/
12
COORDI
NATOR R.
C.E.56523 DATE
UPDATE HM J.NAGELVOORT 02/
16
VI
NYL COATED CHAI
N LI
NK FENCE DRAW I
NG
SDM -
112
NUMBER
DRILL AND TAP FOR 0.625" X 20
PENTA BOLT SIS UNC THREAD,
1.50" DEEP C BORE 1.625" DIA
X 0.625"

~+---t-- 0.75"

LIFTING HOOP
0.625" WIDTH NEOPRENE 0-RING
COVER GROOVE DETAIL

DRILL AND TAP FOR 0.625" X 20


PENTA BOLT SIS UNC THREAD,
1.50" DEEP C BORE 1.625" DIA
1" OPENING X 0.625" 2"
DRILL ALL THE WAY DRILL AND TAP FOR
UP TO THE END 0.375" X 16 THREADS
3.25" IN LENGTH
WEDGE ANCHORS
L!
M- 1 DETAIL OUTER LIFTING HOOP
COVER TO FRAME 0.625" WIDTH

DRILL AND TAP FOR 0.625" X 20

! PENTA BOLT SI S UNC THREAD,


1.50" DEEP C BORE 1.625" DIA
X 0.625" DEEP
,_..:__ _ _ 6.94"----t
DRILL ALL THE WAY
UP TO THE END
-'V------36" DIA ,...,... ,_, _ _. 1" OPENING
INNER
COVER ----'\r--36.32" UIA- - - 1
SEE 0-RING DRILL AND TAP FOR
GROOVE DETAIL 0.375" X 16 THREADS
3.25" IN LENGTH WEDGE
-'y- DIA DRILL ALL THE WAY ANCHORS-----J
UP TO THE END
M- 3B DETAIL:
M-3A DETAIL:
OUTER COVER TO FRAME
INNER COVER TO OUTER COVER

HOLES LOCATlON BOLT POSITION


4 EACH- - - . . . INDICATOR
NOTES:
OUTER 1. 0.625" X 20 PENTA BOLT SIS UNC THREAD,
COVER 316 STAINLESS STEEL SOCKET HEAD CAP SCREW AND
1.50" OD x 0.687" ID X 0.078 THICK
316 STAINLESS STEEL WASHER.

2. 0.25" NEOPRENE 0--RING GASKET SHALL BE GLUED


INTO MACHINED GROOVE. GLUE SHALL MEET THE
REQUIREMENTS OF MIL- M-a1288 (AMEND. 1)

3. BOLTDOWN PATTERNS:
• M-1 DETAIL (24" COVER & FRAME):
INSTALL TWO (2) BOLTS AT 180 DEGREES.
M-3A DETAIL (CONCENTRIC COVERS):
LIFTING HOOP BETWEEN INNER AND OUTER COVERS INSTALL
3 EACH TWO (2) BOLTS AT 180 DEGREES.
2" X 1.625" X 1.25" M-3B DETAIL (OUTER COVER & FRAME):
@ 120 DEGREES DEEP WITH 1.125" BETWEEN OUTER COVER & FRAME INSTALL FOUR (4)
LIFTER IN BETWEEN BOLTS AT 90 DEGREES.
M- 1 COVER AND FRAME FOR M-1 AND M-3 OUTER COVER FRAME DRILL
BOLT PLACEMENT M-3 CONCENTRIC COVERS 4 HOLES FOR 0.375"x16 STAINLESS STEEL WEDGE
(SEE NOTE 3) AND FRAME BOLT PLACEMENT ANCHORS 3.75"1N LENGTH AT 90 DEGREES.
(SEE NOTE 3)

REVISION BY APPROVED DATE RECOMMENDED BY THE Ct1Y OF SAN DIEGO


STANDARDS COMMITTEE
CITY OF SAN DIEGO - STANDARD DRAWING
oil~
ORJGINAL A. OSKOUI 1W3
1/31/2012
UPDATE 01112
COORDINATOR R.C.E. 65271 DATE

MANHOLE COVER - LOCKING DEVICE DRAWING


NUMBER
SDM-113
DISTANCE BETWEEN GATE POSTS IS GATE LENGTH SHOWN ON PLANS

LENGlH OF GATE L . E A F - - - - - - - - - - - 1

REPEAT
OPPOSITE
SIDE

ROADWAY OR GROUND
..
~

10" DIAMETER STOP FOOTING


OMIT IF ROADWAY IS CONCRETE

HALF ELEVATION DOUBLE SWING GATE

. ·. 2.

z~~OF FOOONG •
TIMES OUTSIDE DIAMETER
OF POST.
4

CHAIN LINK VEHICULAR GATE

NOTES:

1. All FOOTINGS SHALL BE 520-C-2500 CONCRETE.

2. EXTENSION POST SHALL BE FURNISHED AND INSTALLED ONLY WHEN SHOWN ON lHE PLANS
OR CALLED FOR IN THE SPECIAL PROVISIONS:

3. CHAIN UNK FENCE SHALL CONFORM TO lHE STANDARD SPECIFICATIONS FOR PUBUC WORKS CONSTRUCTION
UNLESS SPECIFICALLY NOTED ON THE DRAWING.
LEGEND ON PLANS
4. CHAIN UNK FABRIC SHALL HAVE KNUCKLED FINISH ON TOP EDGE.

SHEET 1 OF 2

REVISION BY APPROVED DATE RECOMMENDED BY THE Ct1Y OF SAN DIEGO


STANDARDS COMMITTEE
CllY OF SAN DIEGO - STANDARD DRAWING
oil~
ORJGINAL SM A. OSKOUI 1W3
1/31/2012
UPDATE KA • NAGELVOOR OV12
COORDINATOR R.C.E. 65271 DATE

CHAIN LINK GATE DRAWING


NUMBER
SDM-1 14
LEVER PUSH I PULL PANIC BAA

ACCEPTABLE GATE HARDVVARE


DASHED LINES INDICATE

3'-0' MIN
12" HINGE SIDE
CLEARANCE
TO OBSTRUCTION
T
.- L ----,
EXTENT OF MANlNERING
CLEARANCE AREA.
SEE NOTE 2 AND 9

TRUSS PANEL
CLEAR WlDTH I
4'0' MAX
ACCEPTABLE
GATE HARDWARE
I I I
ISA SIGN
SEE NOTE 8 > ~
.,;<.:. r:
~ 10' SOUD BOTTOM
I @ BOTH SIDES
g X:
- __J

2'-'
CLEAR LEVEL MANElNERING CLEARANCE
b
I .. ' ' ..
"' .. '·
j_ ...
·' ·.
- .:....:........
2" 12' MIN DIA

MOUNTING DETAIL

INTERNATIONAL SYMBOL OF
ACCESSIBIUTY SIGN (ISA)
CHAIN LINK PEDESTRIAN GATE
NOTES
1. GATES THAT ARE ACCESSIBLE TO AND USABLE BY PERSONS WITH DISABILITIES SHALL BE PROVIDED W1TH AT LEAST ONE
INTERNAnONAL SYMBOL OF ACCESSIBILITY SIGN AS SHOWN ABOVE.

2. THE RUNNING AND CROSS SLOPE WITHIN THE LEVEL MANElNERING CLEARANCE AREA SHALL BE 1.5% AND DESIGNED
TO PREVENT WATER FROM ACCUMULATING WlTHIN THE ENnRE SURFACE.

3. IF THE GATE IS NOT SELF - CLOSING, PROVIDE ACCEPTABLE GATE HARDWARE ON BOTH SIDES.

4. PROVIDE :W" DIAMETER TENSION ROD AND TIGHTENER FOR GATES THAT ARE OVER 3' IN WlDTH.

5. IF PROVIDED, TIE FABRIC TOP AND FRAME WITH 11 GAUGE WlRE.

6. LATCHING AND LOCKING GATES THAT ARE HAND OPERATED SHALL BE OPERABLE WlTH A SINGLE
EFFORT NOT TO EXCEED 5-POUND PRESSURE.

7. THE SYMBOL CONTRAST ON SIGN SHALL BE UGHT ON DARK OR DARK ON UGHT.

8. MOUNnNG HEIGHT - THE SIGN SHALL BE INSTALLED ON THE FENCE I'NALL ADJACENT TO THE LATCH OLITSIDE LEGEND ON PLANS
OF THE DOOR. IT SHALL BE MOUNTED TO THE CENTERUNE OF THE ACCEPTED GATE HARDWARE.
MOUNnNG LOCATION SHALL BE DETERMINED SO THAT A PERSON MAY APPROACH WITHIN 3' OF
SIGNAGE WlTHOUT ENCOUNTERING PROTRUDING OBJECTS OR STANDING WITHIN THE SWING DOOR.

9. LANDING & APPROACH SPACE SHALL COMPLY WITH CURRENT CBC nTLE 24 AND ADA lADAS. SHEET 2 OF 2

REVISION BY APPROVED DAlE RECOMMENDED BY THE Ct1Y OF SAN DIEGO


STANDARDS COMMITTEE
CITY OF SAN DIEGO - STANDARD DRAVVING
oil~
ORJGINAL SM A. OSKOUI 1W3
1/31/2012
ORIGINAL FC A. OSKOUI 1200
COORDINATOR R.C.E. 65271 DAlE
UPDAlE KA • NAGELVOOR OV12
CHAIN LINK GATE DRAWING
NUMBER
SDM-1 14
c c c c c 72" MI
N
60" MI
N c L c 60" MI
N c L c c

A A

C
c

c
SEE SECTI
ON
ON SHEET 2
TOP BOTTOM
60" DOW N I
NTERMEDIATE DOW N LANDI
NG
LANDI
NG c c W
MIN c LANDI
NG
c

90° RAMP RUN RAMP RUN 90°

c
c

c
c
STRAI
GHT RUN RAMP

c c c
60" MI
N c L c 72" MI
N c
c

c
90°
60" c DOW N I
NTERMEDI
ATE
c RAMP RUN
MIN TOP
LANDI
NG
c
c

BOTTOM DOW N
c DOW N
c LANDI
NG
RAMP RUN
c
W LANDI
NG
90°

c
c

c c c
72" MI
N c L c 72" MI
N c

"U" SHAPED RAMP

c c
L
c
60" MI
N c c 72" MI
N c
c

c
I
NTERMEDIATE
60" TOP DOW N LANDI
NG 60"
c
MIN LANDI
NG RAMP RUN MIN
c

DOWN

c
90°
c

c
c
HANDRAI
L

RAMP

"L" SHAPED RAMP


RUN

c
c

c
90°
72"
MIN
BOTTOM
LANDI
NG
c

c
W c

LENGTH OF EACH SEGMENT OF RAMP RUN

MAXIMUM LENGTH OF MAXIMUM RI SE


MAX SLOPE EACH RAMP SEGMENT (
L) BETW EEN LANDINGS
1:
13 (
7.69%) 32.
5' 30"
1:
14 (
7.14%) 35' 30"
1:
15 (
6.67%) 37.
5' 30"
1:
16 (
6.25%) 40' 30"
1:
17 (
5.88%) 42.
5' 30"
1:
18 (
5.55%) 45' 30"
1:
19 (
5.26%) 47.
5' 30"
NOTES:

1. (
W )THE W I
DTH OF THE RAMPS THAT ARE PART OF THE MEAN OF EGRESS W I
LL ALSO HAVE TO MEET THE ADDI
TIONAL CODE REQUI
REMENTS.

2. THE W I
DTH AT THE BOTTOM LANDI
NG SHALL BE AS W I
DE AS THE RAMP.

3. SPECI
FY THE LEAST POSSI
BLE SLOPE BELOW THE MAXI
MUM TO PROVI
DE A CONSTRUCTI
ON TOLERANCE AND TO OFFER BETTER USABI
LITY.

SEE ADDI
TIONAL NOTES ON SHEET 3 SHEET 1OF 3

RECOMMENDED BY THE CI
TY OF SAN DI
EGO
REVI
SION BY APPROVED DATE
STANDARDS COMMITTEE
CI
TY OF SAN DI
EGO - STANDARD DRAW I
NG
ORI
GINAL SM A.OSKOUI 12/
03

2/
25/
16
UPDATE FC A.OSKOUI 12/
06
COORDI
NATOR R.
C.E.56523 DATE
UPDATE KA J.NAGELVOORT 01/
12 PEDESTRI
AN RAM P AND
02/
16 DRAW I
NG
UPDATE FC J.NAGELVOORT
PROTECTI
VE RAI
LING NUMBER
SDM -
115
c 60" MI
N c

W ALL POST
C
11/
2" MI
N HANDRAI LS
CLEARANCE 11/
2" AT RAMPS

c
C

C
C

C
C W ALL
48" MI
N C
C

C
C SEE RAMP
C
NOTE 6 ON
SHT.3

60" MIN
ABOVE FINISHED

W ALL EDGE
C
MOUNTED PROTECTI
ON
34"-38"

42"
FLOOR

DETAI
L1

C
FLOOR C
MOUNTED
ADJACENT ADJACENT
GROUND GROUND

c
C

C
SURFACE SURFACE
C

C
RAMP W I
c DTH AS c
SHOW N ON THE
PLANS (48" MI
N)
SECTI
ON B-B
NOTE:
DETAILIN LI
EU OF
THE HEIGHT OF THE HANDRAI
L SHALL BE SKATE STOPPERS SI
DE
CONSISTENT AT EACH RAMP RUN. APPROACH
LANDING

c 3" 1/2"
c

W ALL

C
C

c
c

c
24" MI
N @ EXTERI
OR RAMP

C
18" MI
N @ I
NTERIOR RAMP

42" MIN
CURB
3" c c

MAX
C

c 60" MI
N
c

c
C

2" MI
N
C

c RAMP W I
DTH ASc
SHOW N ON THE
DETAI
L1 PLANS (48" MI
N)

FRONT APPROACH LANDI


NG

ADJACENT
W ALL W HERE
OCCURS
C 5' C 5'
C C C
11/
2" MI
N
CLEARANCE C
AT THE GRI
P C
EXTENSI
ON 12" B-B EXTENSI
ON 12" MI
N
MIN ALONG ALONG HORIZONTAL
c
c HORIZONTAL PORTION
PORTION c
c
c

POST
C

34"-38"
26-1/2" MAX

TYP
TYP

CURB
C

W HEEL GUI
DE RAI
L
c

C
CENTERED AT
C CONCRETE
3" + /
- 1" HI
GH
SLAB
C

SECTI
ON A-A
DETAI
L 2 - W HEEL GUI
DE I
N LI
EU OF CURB
CONCRETE SLAB PER SPEC

SHEET 2 OF 3

RECOMMENDED BY THE CI
TY OF SAN DI
EGO
REVI
SION BY APPROVED DATE
STANDARDS COMMITTEE
CI
TY OF SAN DI
EGO - STANDARD DRAW I
NG
ORI
GINAL SM A.OSKOUI 12/
03

2/
25/
16
UPDATE FC A.OSKOUI 12/
06
COORDI
NATOR R.
C.E.56523 DATE
UPDATE KA J.NAGELVOORT 01/
12
PEDESTRI
AN RAM P AND
02/
16 DRAW I
NG
UPDATE FC J.NAGELVOORT
PROTECTI
VE RAI
LING SDM -
115
NUMBER
RAM P:

1. ANY W ALKI
NG SURFACE THAT I
S PART OF AN ACCESSI
BLE ROUTE W I
TH THE SLOPE GREATER THAN 5% SHALL BE
CONSIDERED A PEDESTRI
AN RAMP AND MUST COMPLY W ITH THE PEDESTRI
AN RAMP STANDARDS.

2. THE LEAST POSSI


BLE SLOPE SHALL BE USED W I
THOUT EXCEEDI
NG 7.
7%,PER CI
TY OF SAN DI
EGO ACCESS MEMO.

3. THE RUNNI
NG SLOPE SHALL BE UNI
FORM ALONG EACH RAMP SEGMENT.

4. CROSS SLOPE SHALL NOT EXCEED 1.


5%.

5. LANDI
NGS SHALL HAVE A 1.
5% SLOPE I
N BOTH DI
RECTI
ONS.

6. W ALKI
NG SURFACE MUST BE STABLE,FI
RM,AND SLI
P RESI
STANT.CONCRETE SHALL HAVE A MEDI
UM BROOM
TRANSVERSE FI
NISH.

7. LANDI
NGS MUST BE DESI
GNED TO PREVENT PONDI
NG.

8. W HERE THE CHANGE OF SLOPE OCCURS,GRADE BREAKS MUST BE PERPENDI


CULAR TO THE DI
RECTI
ON OF THE
RAMP RUNS TO PREVENT CROSS SLOPE ISSUES.

HANDRAI
L:

1. HANDRAI
LS ARE REQUI
RED ON BOTH SI
DES OF A PEDESTRI
AN RAMP.

EXCEPTI
ONS:
a. RAMPS AT EXTERIOR DOOR LANDINGS THAT RI
SE LESS THAN 6 I
NCHES OR HAVE LESS THAN 72 I
NCHES LENGTH.
HOW EVER,LEVEL LANDI
NGS SHALL BE PROVI
DED AT THE TOP AND BOTTOM.

b. RAMPS I
MMEDI
ATELY ADJACENT TO SEATI
NG I
N ASSEMBLY AREAS.

2. HANDRAI
LS SHALL BE CONTI
NUOUS FOR THE FULL LENGTH OF THE RAMP RUN PLUS THE EXTENSI
ON.

3. I
NSI
DE HANDRAI
LS AT "U" SHAPED AND "L" SHAPED RAMPS SHALL BE CONTI
NUOUS.

4. HANDRAI
LS SHALL EXTEND 12 I
NCHES MI
NIMUM BEYOND THE TOP,I
NTERMEDIATE AND BOTTOM OF EACH RAMP SEGMENT
I
N THE DIRECTI
ON OF THE RAMP RUN,THE HANDRAI
L EXTENTI
ON SHALL BE PARALLEL TO THE LANDI
NG SURFACE.

5. HANDRAI L EXTENSI
ON SHALL NOT EXTEND I
NTO THE REQUIRED W I
DTH OF AN ADJACENT ROUTE OF TRAVEL.I
N EXI
STI
NG
FACILI
TIES W HERE THE ENCROACHMENT OF THE EXTENSI
ON IN THE DI
RECTI
ON OF THE RAMP CREATES A HAZARD,THE
EXTENSION SHALL BE BENT 90 DEGREES TO THE RUN OF THE RAMP.

6. END OF HANDRAI
L EXTENSI
ON SHALL BE TURNED TO THE W ALL,FLOOR OR POST.

7. END OF HANDRAIL EXTENSI


ON SHALL BE TURNED TO THE FLOOR W HEN EXTENSI
ON I
S PROTRUDI
NG PERPENDI
CULAR I
NTO
PATH OF TRAVEL.

8. TOP GRI
PPI
NG SURFACE OF THE HANDRAI
L SHALL BE UNI
FORM I
N HEI
GHT.THE GRI
PPI
NG SURFACE SHALL BE CONTI
NUOUS
AND SMOOTH (
NO SHARP CORNERS) .

9. THE GRI
PPING PORTI
ON SHALL BE 4 I
NCHES MI
N TO 6-1/
4INCHES MAX PERIMETER DI
MENSI
ON,1-1/
4INCHES TO 2-1/
4
I
NCHES IN CROSS SECTI
ONAL NOMINAL DI
MENSI
ON OR SHAPED W I
TH EQUIVALENT GRI
PPI
NG SURFACE.

10. DESI
GN AND SHOP DRAW I
NGS SHALL BE APPROVED BY THE CI
TY ENGI
NEER AND ACCESS COMPLI
ANCE OFFI
CER PRI
OR TO
FABRICATI
ON.

11. ADJACENT W ALL OR OTHER SURFACES SHALL BE FREE OF ANY SHARP OR ABRASI
VE ELEMENT (
SMOOTH FI
NISH)
.

12. A GUARDRAI L 42 I
NCHES ABOVE FINI
SHED FLOOR SHALL BE I
NSTALLED ALONG OPEN EDGES OF THE RAMP AND LANDI
NGS
THAT ARE 30 INCHES OR MORE I N HEI
GHT FROM THE ADJACENT GROUND SURFACE AND THE RAMP IS NOT BOUNDED BY
A W ALL OR FENCE.SEE SDM-118.

13. PROVI
DE A CONTINUOUS GUIDE CURB OR GUIDE RAI
LIF POSTS ARE I
NSTALLED ON THE RAMP SURFACE OR I
F THE FI
NISH
SURFACE I
S GREATER THAN 4INCHES HIGHER THAN THE ADJACENT GROUND SURFACE.

14. FOR HANDRAI


L AND GUARDRAI
L MATERI
AL,FI
NISHES AND ADDI
TIONAL DETAI
LS,SEE RELATED DETAI
L DRAW I
NGS.

SHEET 3 OF 3

RECOMMENDED BY THE CI
TY OF SAN DI
EGO
REVI
SION BY APPROVED DATE
STANDARDS COMMITTEE
CI
TY OF SAN DI
EGO - STANDARD DRAW I
NG
ORI
GINAL SM A.OSKOUI 12/
03

2/
25/
16
UPDATE FC A.OSKOUI 12/
06
COORDI
NATOR R.
C.E.56523 DATE
UPDATE KA J.NAGELVOORT 01/
12
PEDESTRI
AN RAM P AND
02/
16 DRAW I
NG
UPDATE FC J.NAGELVOORT
PROTECTI
VE RAI
LING SDM -
115
NUMBER
TYPICAL CONTINENTAL CROSSWALK MARKINGS

..J

~ \ : LI:INE AT
CONTROLLED
0 CROSSINGS
z
0
;::
frla:
iS
SINGLE RAMP CORNER DUAL RAMP CORNER

I
'\ MIN 12"

MIN 12" I
RAMP TYP.
r\ FLARE TYP.
FLARE TYP

CENTER OF
CURB RAMP
~~ : : LEGEND
· · · · CONSTRUCTION LINE
=-:= CURB & GUTIER
- CROSSWALK BAR (24" WIDE)
GENERAL NOTES:
1. ALL MARKED CROSSWALKS SHALL HAVE CONTINENTAL MARKINGS UNLESS APPROVED OTHERWISE.
2. MARKED CROSSWALK LOCATIONS CONSISTING OF BRICK PAVERS OR OTHER DECORATIVE PAVING SHALL
BE PROVIDED WITH A LIMIT LINE ON LY.
3. SIGNALIZED INTERSECTIONS SHALL BE PROVIDED WITH A MARKED CROSSWALK ACROSS EACH LEG WHERE
PEDESTRIANS ARE PERMITIED TO CROSS.
4. CONTINENTAL CROSSWALK MARKINGS SHALL BE ALIGNED PARALLEL TO THE DIRECTION OF VEHICULAR
TRAVEL.
5. LIMIT LINES SHALL BE INSTALLED A MINIMUM OF 4 FEET IN ADVANCE OF MARKED CROSSWALKS FOR
THE APPROACH LANES AT ALL CONTROLLED CROSSINGS.
6. MARKED CROSSWALKS SHOULD BE A MINIMUM OF 10 FEET IN WIDTH. PLACEMENT OF CONTINENTAL
CROSSWALKS SHALL COMPLY WITH ACCESSIBILITY REGULATIONS PER THE MOST RECENT VERSION OF
AM ERICANS WITH DISABILITIES ACT (ADA) STANDARDS.
7. THE CROSSWALK BETWEEN A DUAL RAMP CORN ER AND A SINGLE RAMP CORNER SHALL BE AT LEAST 10
FEET WIDE AND SATISFY THE MINIMUM OF 2 FEET BEYOND THE FLARE REQUIREMENT FOR THE SINGLE
RAMP .
8. CONTINENTAL CROSSWALK BARS SHALL BE UNIFORM WITHIN THE SAME CROSSING. NO PARTIAL BARS
SHALL BE INSTALLED.
9. A CROSSWALK BAR SHALL BE CENTERED IN THE CENTER OF THE CROSSING.
10. CROSSWALK MARKINGS SHALL BE CALIFORNIA MANUAL ON UNIFORM TRAFFIC CONTROL DEVICES
(CA-MUTCD) RETROREFLECTIVITY COMPLIANT AND SKID RESISTANT.
SHEET I OF 3

RECOMMENDED BY THE CITY OF SAN DIEGO


REVISION BY APPROVED DATE STANDARDS COMMirJEE
CITY OF SAN DIEGO - STANDARD DRAWING
ORIGINAL JF J. NAGELVOORT 02/15
2/ 5/ 2015
DATE

CONTINENTAL CROSSWALK DRAWING


MARKINGS LAYOUT AND NOTES NUMBER SDM-116
CASE 1 - SINGLE RAMP ORTHOGONAL CASE 2 - SINGLE RAMP SKEWED

• I.

J l I

~~/ 111111111 \~~


-- - - <-
-- -- - --- ..::r----~--

=- - -
----------=-
·- -L
=
----
~---
-

~=
=====-=J= =- ---- --:-----1::
~= =,.:-=-=-::;;.:::..:;=-=
-
_ _ ~ . ~\llllllllll~~..,:' ~'~) 11111111~~,..,:'---
) r 1' r

CASE 3 - DUAL RAMP ORTHOGONAL CASE 4 - DUAL RAMP SKEWED

---- =c---
'

--- -

---
.

LEGEND
· · · · · · CONSTRUCTION LINE
I =-:::: CURB & GUTIER
I
I - CROSSWALK BAR (24" WIDE) I I
' I I ' • I

SHEET 2 OF 3

REVISION BY APPROVED DATE


CITY OF SAN DIEGO - STANDARD DRAWING
ORIGINAL JF J. NAGELVOORT 02/ 15

CONTINENTAL CROSSWALK DRAWING


MAR~NGSLAYOUTANDNOTES NUMBER SDM-116
CASE 5 - DUAL AND SINGLE RAMP ORTHOGONAL

I
I '
I

---
-
------.---
- --
--
--......."'\ 1111111';.~~---

i:~
I!~ ~
CASE 6 - DUAL AND SINGLE RAMP SKEWED

----
]_§ ---
~\11111111 /'
I I I LEGEND
I I · · · · · · CONSTRUCTION LINE
=-:= CURB & GUITER
- CROSSWALK BAR (24" WIDE)

SHEET 3 OF 3

RECOMMENDED BY TliE CITY OF SAN OIEGO


REVISION BY APPROVED DATE ST;l.NOARDS Cm.U.4mEE
CITY OF SAN DIEGO -STANDARD DRAWING
ORIGINAL JF J. NAGELVODR OV15

CONTINENTAL CROSSWALK DRAWING


MAR~NGSLAYOUTANDNOTES NUMBER SDM-116
PARKI
NG REQUI
REM ENTS:
1. W HERE PARKI
NG IS PROVI
DED ON EACH FACI
LITY (
LOT OR STRUCTURE)
,ACCESSI
BLE PARKI
NG SPACES
SHALL BE PROVI
DED.

2. PARKI
NG SPACES USED EXCLUSI VELY FOR BUSES,TRUCKS,OTHER DELI
VERY VEHI
CLES,OR VEHICULAR I
MPOUND SHALL
NOT BE REQUI RED TO COMPLY W I
TH THE PARKI
NG RATI O PROVI
DED THAT LOTS ACCESSED BY THE PUBLI
C ARE
PROVIDED W I
TH A PASSENGER LOADING ZONE COMPLYI NG W I
TH PASSENGER LOADING ZONE STANDARDS.SEE
SDM-117 SHEET 8.

MI
NIMUM REQUI
RED PARKI
NG RATI
O FOR ACCESSI
BLE PARKI
NG SPACES

TOTAL NUMBER OF
MINI
MUM NUMBER OF
PARKING SPACES
REQUIRED ACCESSI
BLE
PROVI
DED IN PARKING
PARKI
NG SPACES
FACI
LITY

1-25 1
26-50 2
51-75 3
76-100 4
101-150 5
151-200 6
201-300 7
301-400 8
401-500 9
501-1,000 2% OF TOTAL
20,PLUS 1FOR EACH 100,
1,
001AND OVER OR FRACTION THEREOF,OVER 1000

EXCEPTI
ONS:
A. 10% OF THE TOTAL NUMBER OF PARKI
NG SPACES AT OUTPATI
ENT UNI
TS AND FACI
LITI
ES SHALL BE ACCESSI
BLE.

B. 20%OF THE TOTAL NUMBER OF PARKI


NG SPACES AT UNI TS AND FACI
LITI
ES SPECI
ALI
ZING I
N TREATMENT OR SERVI
CES
FOR PERSONS W I
TH MOBILI
TY I
MPAIRMENTS SHALL BE ACCESSIBLE.

C.THE REQUI
RED PARKI
NG RATI
O FOR ACCESSI
BLE PARKI
NG STALLS I
S PROVI
DED FOR EACH PARKI
NG LOT ON THE SI
TE.

D.AT LEAST ONE VAN PARKI


NG SPACE I
S REQUI
RED FOR EVERY 6 OR FRACTI
ON OF SI
X PARKI
NG SPACES.

E. I
N BUI LDI
NGS OR FACI
LITI
ES W I
TH MULTI
PLE ACCESSI
BLE ENTRANCES W ITH ADJACENT PARKING SPACES SHALL BE
DISPERSED AND LOCATED CLOSEST TO THE ACCESSIBLE ENTRANCES.A VAN ACCESSIBLE SPACE SHALL BE PROVI
DED
AT EACH LOCATI
ON.

3. VERTI
CAL CLEARANCE - PARKING SPACES FOR VANS AND ACCESS AI
SLE AND VEHI
CULAR ROUTES SERVI
NG THEM SHALL
PROVIDE A VERTI
CAL CLEARANCE OF 98" MI
NIMUM.

4. THE SURFACE OF THE ENTI


RE AREA OF THE ACCESSI
BLE PARKI
NG SPACE(
S)AND ACCESS AI
SLE(
S)SHALL HAVE A SLOPE OF
1.
5% IN ANY DI
RECTION.

A. GUTTERS AND SW ALES SHALL NOT BE I


NCLUDED I
N THE OVERALL DI
MENSIONS OF THE ACCESSI
BLE PARKI
NG SPACES
AND ACCESS AISLES,UNLESS SLOPE AND CROSS SLOPE I
S 2% MAXIMUM.

B. THE SURFACE SLOPE OF THE AREA I


MMEDI
ATELY SURROUNDI
NG THE ACCESSI
BLE PARKI
NG SPACE SHALL BE 1.
5%
FOR A W I
DTH OF 4'
-0".

C. ADEQUATE DRAI
NAGE SHALL BE PROVIDED SO THAT W ATER DOES NOT ACCUMULATE W I
THI
N THE ACCESSI
BLE
PARKI
NG SPACE AND ACCESS AISLE.

D. THE GUTTER SLOPE AT THE OPENI


NG OF THE CURB RAMPS SERVI
NG THE ACCESS AI
SLES SHALL BE 1.
5%.

SHEET 1OF 8

RECOMMENDED BY THE CI
TY OF SAN DI
EGO
REVI
SION BY APPROVED DATE
STANDARDS COMMITTEE
CI
TY OF SAN DI
EGO - STANDARD DRAW I
NG
ORI
GINAL FC A.OSKOUI 12/
06

01/
12
2/
25/
16
UPDATED KA J.NAGELVOORT
COORDI
NATOR R.
C.E.56523 DATE
UPDATED FC J.NAGELVOORT 02/
16
ACCESSI
BLE PARKI
NG NOTES
DRAW I
NG
SDM -
117
NUMBER
5. ACCESS AI
SLES (
LOADI
NG AND UNLOADI
NG AREAS)SHALL BE PROVI
DED FOR SI
NGLE AND DOUBLE ACCESSI
BLE
PARKI
NG SPACES.

A. THE ACCESS AI
SLE SHALL BE CONNECTED TO AN ACCESSI
BLE ROUTE.

B. FOR REGULAR ACCESSI


BLE SPACE,THE ACCESS AI
SLE SHALL BE ON EI
THER SI
DE OF THE VEHI
CLE W HEN THE
VEHI
CLE I
S GOING FORW ARD I
NTO THE PARKING SPACE.

C.FOR VAN SPACE,THE ACCESS AI


SLE SHALL BE PLACED ON THE SI DE OPPOSI
TE THE DRIVER'S SIDE W HEN THE
VEHI
CLE I
S GOING FORW ARD INTO THE PARKING SPACE (i
.e.PASSENGER SIDE OF THE VEHICLE).

D.THE CURB RAMP MAY NOT ENCROACH I


NTO THE REQUI
RED DI
MENSI
ONS FOR THE ACCESSI
BLE PARKI
NG SPACE AND
ACCESS AI
SLE.

E. CURB RAMPS SERVI


NG THE ACCESS AI
SLES SHALL COMPLY W I
TH THE APPROPRI
ATE CURB RAMP STANDARDS.

6. I
N EACH PARKI
NG AREA,A W HEEL STOP SHALL BE PROVI
DED TO PREVENT VEHI
CLES FROM OBSTRUCTI
NG THE
REQUI
RED CLEAR W I
DTH OF ADJACENT ACCESSIBLE ROUTES.

7. EACH ACCESSIBLE PARKING SPACE SHALL BE LOCATED SO THAT PERSONS W I


TH DI
SABI
LITI
ES ARE NOT COMPELLED
TO W HEEL OR W ALK BEHI
ND PARKING SPACES OTHER THAN THEIR OW N.

8. SI
GNAGE:
A.PAVEMENT PARKING SIGNS SUCH AS THE INTERNATIONAL SYMBOL OF ACCESSI
BILI
TY (
ISA)AND "NO PARKI NG" AT THE
ACCESS AISLES SHALL BE PLACED SO THAT THEY ARE VISI
BLE TO TRAFFI
C ENFORCEMENT OFFICIALS W HEN THE
VEHICLE I
S PARKED PROPERLY.SEE DETAIL ON SDM-117 SHEET 4.

B.W HEN POSTED I N A PATH OF TRAVEL,THE SI


GN SHALL BE MOUNTED 80 INCHES PER SDM-104.I
F I
NSTALLED ON A
W ALL,THE SIGN MAY BE CENTERED ON THE W ALL AT THE I
NTERIOR END OF THE PARKI
NG SPACE 5 FT ABOVE
GRADE.I F SI
GN IS I
NSTALLED W I
THI
N THE CIRCULATION AREAS,I
NSTALL 80 I
NCHES ABOVE FI
NISH FLOOR.

C.A TOW AW AY SI
GN SHALL BE INSTALLED AND VISI
BLE AT EACH ENTRANCE TO THE OFF STREET PARKI
NG FACI
LITY
OR IMMEDI
ATELY ADJACENT TO THE ACCESSIBLE PARKI
NG SPACE.

9. I
F THE ACCESSI
BLE ROUTE CROSSES OR ADJOI
NS THE VEHI
CULAR W AY AND THE W ALKI
NG SURFACE I
S NOT
SEPARATED BY CURBS,RAILI
NGS,OR OTHER ELEMENTS BETW EEN THE PEDESTRIAN AREAS AND VEHI CULAR AREAS,
THE BOUNDARY BETW EEN THE AREAS SHALL BE DEFINED BY A 36 I
NCH W I
DE DETECTABLE W ARNI
NG TILES.
DETECTABLE W ARNI
NG TILES SHALL BE PER SDG-130.

10.PASSENGER LOADI
NG ZONE:
A.W HERE PROVI
DED,AT LEAST ONE ACCESSI
BLE PASSENGER LOADI
NG ZONE SHALL BE ACCESSI
BLE.

B.AN ACCESSIBLE PASSENGER LOADI


NG ZONE SHALL BE PROVI
DED I
N EVERY CONTI
NUOUS 100 LI
NEAR FEET OF LOADI
NG
SPACE,OR FRACTION THEREOF.

C.VEHI
CLE PULL-UP SPACE - PASSENGER LOADI
NG ZONES SHALL PROVI
DE A VEHI
CULAR PULL-UP SPACE 96 I
NCHES W I
DE
MINI
MUM AND 20' -0" LONG MI
NIMUM.

D.ACCESS AISLE - PASSENGER LOADING ZONES SHALL BE PROVI


DED W I
TH ACCESS AI
SLES ADJACENT TO THE VEHI
CLE
PULL-UP SPACE.ACCESS AISLES SHALL CONNECT DI
RECTLY TO AN ACCESSI
BLE ROUTE AND SHALL NOT OVERLAP THE
VEHICULAR W AY.

E.ACCESS AI
SLES SHALL BE MARKED AS REQUI
RED FOR ALL ACCESS AI
SLES FOR ACCESSI
BLE PARKI
NG SPACES.

F.PASSENGER LOADING ZONES SHALL BE IDENTI


FIED BY A REFLECTORI
ZED SIGN POSTED IMMEDI
ATELY ADJACENT TO AND
VI
SIBLE FROM THE PASSENGER DROP-OFF AND LOADI NG ZONE STATING "PASSENGER LOADI
NG ZONE ONLY".W HEN
LOCATED IN A PATH OF TRAVEL,THE SI
GN SHALL BE MOUNTED PER SDM-104.

G.VEHI
CLE PULL-UP SPACES AND ACCESS AI
SLES SERVI
NG THEM SHALL BE AT THE SAME LEVEL AS THE VEHI
CLE PULL-UP
SPACES THEY SERVE.ANY CHANGES I
N ELEVATI
ON SHALL BE SERVED BY A CURB RAMP(
S).

H.VEHI
CLE PULL-UP SPACE AND ACCESS AISLE SLOPES SHALL BE 1.
5% IN ANY DI
RECTI
ON.ADEQUATE DRAI
NAGE SHALL BE
PROVIDED SO THAT W ATER DOES NOT POND IN THE ACCESS AISLE.

. A MI
I NIMUM OF 114 I
NCHES VERTI
CAL CLEARANCE SHALL BE PROVI
DED AT ACCESSI
BLE PASSENGER DROP-OFF AND LOADI
NG
ZONES AND ALONG AT LEAST ONE VEHI
CLE ACCESS ROUTE TO SUCH AREAS FROM SI TE ENTRANCE(
S)AND EXI
T(S)
.

J.PARKI
NG FACI
LITI
ES THAT PROVI
DE VALET PARKI
NG SERVI
CES SHALL PROVI
DE AT LEAST ONE ACCESSI
BLE PASSENGER
LOADI
NG ZONE.
SHEET 2 OF 8

RECOMMENDED BY THE CI
TY OF SAN DI
EGO
REVI
SION BY APPROVED DATE
STANDARDS COMMITTEE
CI
TY OF SAN DI
EGO - STANDARD DRAW I
NG
ORI
GINAL FC A.OSKOUI 12/
06

UPDATED KA J.NAGELVOORT 01/


12
2/
25/
16
COORDI
NATOR R.
C.E.56523 DATE
UPDATED FC J.NAGELVOORT 02/
16
ACCESSI
BLE PARKI
NG NOTES DRAW I
NG
SDM -
117
NUMBER
CURB RAMP

PARKI
NG SI
GN
C C RETAI
NING CURB
C
I
F NECESSARY

3'
- 0" SI
DEW ALK SI
DEW ALK
UNOBSTRUCTED

C
AREA
C

o EDGE OF GUTTER
C 45 C (CURB I
F NO GUTTER)

C
C
C
C W HEEL STOP

*
18'- 0"

C 4" BLUE LI
NE BORDER
L
MIN

4" HATCHED DIAGONAL LINES


AT 36" MAX ON-CENTER
PAINTED A CONTRASTING
COLOR W ITH THE PARKING
C SURFACE,W HITE ON AC
4" BLUE LI
NE
BLUE ON CONCRETE.
C

4" W HI
TE LI
NE.
C C
C

NO PARKI
NG

ACCESS AISLE W I
DTH:MINI
MUM
I
SA SYMBOL WIDTH IS 5'FOR A REGULAR
C 12'
- 0" MI
N.VAN C C REGULAR
C C C ACCESSIBLE PARKING STALL;
NON-ACCESSI
BLE
8'FOR A VAN ACCESSIBLE
C NG STALL. C
PARKI
L L PARKING STALL.

SI
NGLE PARKI
NG STALL
C *18"LONG MI
N.TO EDGE
CURB RAMP OF GUTTER.OR

NON-CONTI
GUOUS
*18'LONG MI
N.TO THE EDGE
OF CURB I
F GUTTER HAS
SI
DEW ALK
2% MAX.SLOPE.
CONTI
GUOUS
C SI
DEW ALK
PARKI
NG SI
GN PARKING SI
GN
C PREFERRED LOCATI
ON
C

C
C

EDGE OF GUTTER OR
o CURB I
F NO GUTTER
45
C

C
C

C
3'
-0"
UNOBSTRUCTED
C W HEEL STOP
AREA

*
18'-0"

C C 4" BLUE LI
NE BORDER
MIN

L C L

4" HATCHED DIAGONAL LINES


NO PARKI
NG AT 36" MAX ON-CENTER
C PAINTED A CONTRASTING
COLOR W ITH THE PARKING
4" BLUE LI
NE
C SURFACE,W HITE ON AC
C BLUE ON CONCRETE

C
C

4" BLUE LI
NE

ACCESS AISLE:MINIMUM
WIDTH IS 5'FOR A REGULAR
12'
- 0" MI
N.VAN 9'
- 0" MI
N
C C C ACCESSIBLE PARKING STALL;
I
SA SYMBOL
8'FOR A VAN ACCESSI BLE
TYPI
CAL C C
L DOUBLE PARKI
NG STALL L PARKING STALL.
SHEET 3 OF 8

RECOMMENDED BY THE CI
TY OF SAN DI
EGO
REVI
SION BY APPROVED DATE
STANDARDS COMMITTEE
CI
TY OF SAN DI
EGO - STANDARD DRAW I
NG
ORI
GINAL FC A.OSKOUI 12/
06

KA J.NAGELVOORT 01/
12
2/
25/
16
UPDATED
COORDI
NATOR R.
C.E.56523 DATE
UPDATED FC J.NAGELVOORT 02/
16
OFF-
STREET ACCESSI
BLE PARKI
NG
DRAW I
NG
SDM -
117
NUMBER
CURB RAMP PARKI
NG SI
GN
PER PLAN
PARKI
NG SI
GN PREFERRED LOCATI
ON
SI
DEW ALK PER PAI
NT CURB BLUE

C
PLANS

SI
DEW ALK PER PLANS
C

C
C

C
C

3'
3'

-
-
o

o
45

0"
0"

0
-9
C

C
C W HEEL STOP W HEN

30
C C
C
REQUI
RED,TYP.

4" BLUE C
LI
NE 4" BLUE LI
NE BORDER
C C

4" HATCHED DIAGONAL


LI
NES AT 36" MAX

1
8'
ON-CENTER PAI NTED A

M
CONTRASTING COLOR W ITH

IN.
C

C THE PARKING SURFACE,


C * W HITE ON AC,
CL BLUE ON CONCRETE

4" BLUE LI
NE
1

CL
8'
M
IN.

* C
CL
"
C -0
9'
C

C
N N
I
M
I
SA SYMBOL VA
N.
C
I
"M "
'-0 -0
C
CL
12
NO 5'
N
I
PARKI
NG
C
M *18"LONG MI
N.TO EDGE
C

CL OF GUTTER.OR
CL
*18'LONG MI
N.TO THE EDGE
DI
AGONAL DOUBLE PARKI
NG STALLS OF CURB I
F GUTTER HAS
2% MAX.SLOPE.
C
C
C

I
NTERNATI
ONAL SYMBOL OF ACCESSI
BILI
TY
PAVEMENT SYMBOL SHALL BE PAI
NTED W HI
TE
ON BLUE BACKGROUND.
3' - 9"

4' - 5"
3' - 0"

BLUE COLOR TO MATCH COLOR A 15090 I


N THE
FEDERAL STANDARD 595A AS SPECI
FIED I
N
SECTI
ON 522(
B)2.

I
SA SYMBOL SHALL BE LOCATED SO THAT I
TIS
C

VI
SIBLE TO TRAFFI
C ENFORCEMENT OFFI
CER
W HEN THE VEHI
CLE I
S PARKED I
N THE SPACE.
C
C

C 2'- 8 1/
2"
C
C 3'- 9" I
NTERNATI
ONAL SYMBOL OF ACCESSI
BILI
TY (
ISA)
C
C 4'- 5"
C
C

THE W ORDS "NO PARKI


NG" SHALL BE PAI
NTED I
N
12"

W HI
TE LETTERS NO LESS THAN 12" HI
GH LOCATED
AT THE END OF THE ACCESS AI
SLE SO THAT I
TIS
C

VI
SIBLE TO TRAFFI
C ENFORCEMENT OFFI
CIALS
SHEET 4 OF 8

RECOMMENDED BY THE CI
TY OF SAN DI
EGO
REVI
SION BY APPROVED DATE
STANDARDS COMMITTEE
CI
TY OF SAN DI
EGO - STANDARD DRAW I
NG
ORI
GINAL KA J.NAGELVOORT 01/
12

2/
25/
16
UPDATED FC J.NAGELVOORT 02/
16
COORDI
NATOR R.
C.E.56523 DATE

OFF-
STREET ACCESSI
BLE PARKI
NG DRAW I
NG
SDM -
117
NUMBER
C 12" 11/
2" RADI
US
C 11/
2"
3/
8" 5/
8" RADIUS

C
C

C
C
C

C
C
1"

C
13/
4"

C C

C
UNAUTHORI
ZED VEHI
CLES PARKED

I
N DESI
GNATED ACCESSI
BLE 1"

C
8" TYP
SPACES NOT DI
SPLAYI
NG

C
DI
STI
NGUI
SHI
NG PLACARDS OR 1/
2"

C
18" SPECI
AL LI
CENSE PLATES I
SSUED TYP

C
1/
2"
FOR PERSONS W I
TH DI
SABI
LITI
ES

C
18"
3" WI
LL BE TOW ED AW AY

C
AT OW NER'
S EXPENSE
1" 11/
4" TYP

C
C
TOW ED VEHI
CLES
2 1/
2"
3"

C
MAY BE RECLAI
MED AT
C

C
(
INSERT ADDRESS)
11/
2" 2 3/
4"
C

C
C

OR BY TELEPHONI
NG
1"

C
(
INSERT TELEPHONE NUMBER OF A
LOCAL LAW ENFORCEMENT AGENCY)
C

(
619)531-2000 S.
D.P.
D. 3 1/
4"
C

C.
V.C.Sect
ion 22511.
8(d)
C

2"

C
C

2"
C

C 18"
C
C
C

9" 1"
C

2" TOW -AW AY SI


GN
C
C
C

2"
C
C
C

2"
C

NOTES:
2"
C

1. SI
GN POST:SEE SDM-104 FOR "BREAK-AW AY SI
GN POST".
C

9" 1"
C

2" 2.SI
GNS SHALL BE CONSTRUCTED ON MI
NIMUM 1/
16 I
NCH THI
CK ALUMI
NUM.
C
C
C

2"
3.COLORS:
C

MULTI
PLE SI
GNS
PARKI
NG SIGNS:
C 12" BACKGROUND - BLUE (RETROREFLECTIVE)
C 11/
2" BORDER,TEXT,AND SYMBOL - W HI
TE (
RETROREFLECTI
VE)
1/
2"
RADIUS
C

C
C

TOW AW AY SI
GN:
C

BACKGROUND - W HI
TE (
RETROREFLECTI
VE)
C

BORDER AND LEGEND - BLACK

4.FONTS:SAN SERI
F CLEARVI
EW .

8"
C

1/
2"
C

3"
C

24"
1"
C

3"
1/
2"
C

C
C

3/
4" 2"
C

C
C

2"
C

C
C

11/
4"
C

SI
NGLE SI
GN

PARKI
NG SI
GNS SHEET 5 OF 8

RECOMMENDED BY THE CI
TY OF SAN DI
EGO
REVI
SION BY APPROVED DATE
STANDARDS COMMITTEE
CI
TY OF SAN DI
EGO - STANDARD DRAW I
NG
ORI
GINAL KA J.NAGELVOORT 01/
12

2/
25/
16
UPDATED FC J.NAGELVOORT 02/
16
COORDI
NATOR R.
C.E.56523 DATE

OFF-
STREET ACCESSI
BLE PARKI
NG SI
GNS DRAW I
NG

NUMBER
SDM -
117
CURB RAMP PARKI
NG SI
GN
PER PLAN PARKING SI
GN
PREFERRED LOCATI
ON
SI
DEW ALK

C
PAI
NT CURB BLUE
PER PLANS
C SI
DEW ALK PER
PLANS

C
4" BLUE LI
NE BORDER

o
o
0
45 -9
C

o
C
4" BLUE C

30 4" HATCHED DIAGONAL LINES AT 36" MAX


C

LI
NE C
ON-CENTER PAI NTED A CONTRASTING
C
COLOR W ITH THE PARKING SURFACE,
W HITE ON AC,BLUE ON CONCRETE

C
1
6'

CL CL
4" BLUE LI
NE BORDER

C
" C
NO -0
C

9'
PARKI
NG C N
I CL
" M
-0C
5'
C
N
I CL
C M
"
-0
'
12 N CL
I
C M
DIAGONAL DOUBLE
PARKI
NG STALLS CL

BLUE CURB 20'


-0" MI
N
PARKI
NG C
C
C
C

SI
GN
CROSSW ALK
C
C
C

PCR
(TYP)
C

"
'-0 C I
NCLUDE THE FOLLOW I
NG INFORMATI
ON ON
12'
± 12
16

C
THE STRI
PING/
PLAN DETAI
L:
'
±

A. TOTAL NUMBER OF EXI


STI
NG ON-STREET
C

C
DIAGONAL PARKI
NG SPACES
C

STANDARD "
PARKI
NG -0 B. TOTAL NUMBER OF EXI
STING ON-STREET
C 5' N
I DIAGONAL ACCESSI
BLE PARKI
NG SPACES
ACCESSI
BLE M
PARKI
NG
C. TOTAL NUMBER OF NEW ON-STREET
ACCESSI
BLE PARKI
NG - CORNER DIAGONAL PARKI
NG SPACES

D. TOTAL NUMBER OF NEW ON-STREET


DIAGONAL ACCESSI
BLE PARKI
NG SPACES
PARKI
NG C BLUE CURB C 20'
-0" MI
N
C C
SI
GN
C
C

ACCESS AI
SLE
C

C
N
I ACCESSI
BLE
M PARKI
NG
0" C
12'
±
16

C '-
12
'
±
C

C
C

"
STANDARD -0
C 5' N
PARKI
NG I
M
ACCESSI
BLE PARKI
NG - CORNER
SHEET 6 OF 8

RECOMMENDED BY THE CI
TY OF SAN DI
EGO
REVI
SION BY APPROVED DATE
STANDARDS COMMITTEE
CI
TY OF SAN DI
EGO - STANDARD DRAW I
NG
ORI
GINAL FC A.OSKOUI 12/
06

2/
25/
16
UPDATED FC J.NAGELVOORT 02/
16
COORDI
NATOR R.
C.E.56523 DATE

ON STREET ACCESSI
BLE PARKI
NG DRAW I
NG
SDM -
117
NUMBER
NO PARKI
NG DI
RECTI
ON OF TRAVEL

4" BLUE LI
NE BORDER C 5'
-0" C 20'
C C
MIN I
SA MARKING AT
C CENTERREAR LI
MITS

C
C OF STALL.

C
C
REGULAR

9'
REGULAR
PARKI
NG SPACE
PARKI
NG SPACE
C

C
4" W HI
TE LINE

C
5'-0"

C
C
C o
@ 45 DI AGONAL

MIN
8.
33% C
C AND 3' -0" MAX

C
C
CURB C
MAX CURB

C
ON CENTER.

C
1:
1TYP

4'-0"
C
C C

MIN
5'
-0" MI
N
SI
DEW ALK PARKI
NG SI
GN
UNOBSTRUCTED AREA

C
CURB RAMP
ON-STREET PARKI
NG
BLUE PAI
NTED CURB WI
TH LOADI
NG ZONE

BLUE PAI
NTED
NO PARKING
CURB
AS REQUI
RED

PARKI
NG SI
GN

SI
DEW ALK
C
C

C
C
C

SEE NOTE
24'

RESTRI
CTED RI
GHT OF W AY W I
DTH
ON-STREET PARALLEL PARKI
NG

I
NCLUDE THE FOLLOW I
NG I
NFORMATI
ON ON THE STRI
PING/
PLAN DETAI
L:

A.TOTAL NUMBER OF EXI


STI
NG ON-STREET DI
AGONAL PARKI
NG SPACES

B.TOTAL NUMBER OF EXI


STI
NG ON-STREET DI
AGONAL ACCESSI
BLE PARKI
NG SPACES

C.TOTAL NUMBER OF NEW ON-STREET DI


AGONAL PARKI
NG SPACES

D.TOTAL NUMBER OF NEW ON-STREET DI


AGONAL ACCESSI
BLE PARKI
NG SPACES

SHEET 7 OF 8

RECOMMENDED BY THE CI
TY OF SAN DI
EGO
REVI
SION BY APPROVED DATE
STANDARDS COMMITTEE
CI
TY OF SAN DI
EGO - STANDARD DRAW I
NG
ORI
GINAL FC A.OSKOUI 12/
06

2/
25/
16
UPDATED FC J.NAGELVOORT 02/
16
COORDI
NATOR R.
C.E.56523 DATE

ON STREET ACCESSI
BLE PARKI
NG DRAW I
NG
SDM -
117
NUMBER
5 6 10 10 6 5

C
3 4:
1TR
I ON
TI 1.
5% ANS
ANS 5'MI
N ITI
1TR
4:
ON

C
4'MI
N

C
1
C

C
C o

C
45

C
1.
5%

C
1.
5%

C
C

C
1.
5%
C
C
8.
33% 4
C 8.
33% C
5'MI
N

C
C C A MAX
MAX 9

C
3 MI
N.PA SSENG ER LO A DI
NG ZO NE C

C
C A
9 2
8'MI
N

C
C

8 C C C
C C C

FLOWLINE (FL)
20'MI
N
CURB/GUTTER CURB/GUTTER
TRANSI
TION TRANSI
TION

GUTTER
PASSENGER LOADI
NG ZONE

C FULL LENGTH OF 5 C 5%
C
VEHI
CLE PULL-UP SPACE 1.
5%
C
1 6
C

C C SECTI
ON A-A
o
C

45
C
2
C

C C
C C
1.
5% C 5'MI
N
C

C
C

C
C
1.
5%
C

3
8'MI
N
C

3/
8" 1/
2"
C

C
C

C
C
C
C
C

20'MI
N 1.
5"

C
8

PASSENGER 2"

C
PASSENGER LOADI
NG ZONE
1"

C
1 ACCESSI
BLE PASSENGER LOADI
NG ZONE SI
GN (
18 I
NCH X 18 I
NCH - BLACK
LETTERI
NG ON W HI
TE BACKGROUND)
LOADI
NG 2"

C
1"
6I
NCH W HI
TE PAI
NTED CURB AND CURB FACE (
STENCI
LED W I
TH 4 I
NCH

C
2
BLACK GOTHI
C SCRI
PT,3 I
NCH MI
N "PASSENGER LOADI
NG ZONE")
ONLY 2"

C
18"
1"
3 4INCH W I
DTH W HI
TE STRI
PING @ 36 I
NCHES O.
C.& 45 DEGREES TO

C
CURB FACE
3MI
NUT
ELI
MIT 1.
5"

C
1.
5"
4 STRI
PED AREA SLOPES 1.
5% MAX TO GUTTER FL

C
5 CURB RAMP C 3"

6 TRUNCATED DOMES PER SDG-130


1.
5"
C

7 5% MAX SLOPE TO GUTTER FL (PER SDG-137)W I


TH MI N 6 FT TRANSI
TION C C
TO STANDARD GUTTER.HOLD CL-FL ELEVATI
ON DI FFERENCE CONSTANT 8"
C
(EDGE OF PAVEMENT TO VARY) C
18"

8 VEHI
CLE PULL UP SPACE 20 FT X 8 FT.SLOPES NOT TO EXCEED 1.
5% MAX.

9 4 FT X 5 FT ADA LANDI
NG

10 RAI
LING PER SDG-140.

11 ALL DEVI
ATI
ON FROM THIS STANDARD MAY BE ALLOW ED PROVIDED THE
DESIGN AND/OR DOCUMENTATI
ON W AS REVI
EW ED BY THE CI
TY
REPRESENTATIVE. SEE ADDI
TIONAL NOTES ON SDM-117 SHEET 2 SHEET 8 OF 8

RECOMMENDED BY THE CI
TY OF SAN DI
EGO
REVI
SION BY APPROVED DATE
STANDARDS COMMITTEE
CI
TY OF SAN DI
EGO - STANDARD DRAW I
NG
ORI
GINAL KA J.NAGELVOORT 01/
12

2/
25/
16
UPDATED FC J.NAGELVOORT 02/
16
COORDI
NATOR R.
C.E.56523 DATE

ACCESSI
BLE PASSENGER DROP-
OFF
DRAW I
NG
AND LOADI
NG ZONE SDM -
117
NUMBER
11/
2" STD PI
PE 12" MI
N
3" LEVEL
EXTENSION PARALLEL C
C C
C
TO THE FLOOR SURFACE AX C 3"

C
STARTI
NG AT THE NOSE M
7'

C
C
2 1/
4" R EXTENDS

C
C

AND FLUSH DIAGONALLY

X
AGAI NST ONE TREAD
WIDTH
THE W ALL
LEVEL
C

X
C

C
PLAN AT END C
AX

C
M
OF HANDRAIL 7'

C
NOTES:

C
EXTENDS C
DI
AGONALLY 1."X",THE TOP OF GRIPPING SURFACE

X
ONE TREAD OF HANDRAI LS SHALL BE THE SAME
WI
DTH C C HEIGHT VERTICALLY ABOVE W ALKING
C C 6"
3" SURFACES,STAIR NOSI NGS,AND

C
C
LANDING SURFACES.HANDRAI LS SHALL
X

LANDI
NG W HERE BE AT A CONSI STENT HEI
GHT ABOVE
C

OCCURS W ALKING SURFACES,STAIR NOSI NGS,


C
C

C AND LANDI NG SURFACES.SPECI FY


C ONE HEI GHT DIMENSION BETW EEN
X

C
PIPE HANDRAIL 34" AND 38".
W ALL MOUNTED
C

12" MI
N 2.BOTTOM AND TOP LANDI NGS SHALL
LEVEL BE AS W I
DE AS THE W I
DTH OF
12" PLUS C THE STAI
R,48" MI
NIMUM.
C
WIDTH OF 11/
2" STD
TREAD MI N PI
PE TYP

C
26 1/2" MAX
C
EXTENDS

C
DI
AGONALLY

X
ONE TREAD
WI
DTH
LEVEL

C
C
C C
C
C

A C

AX C
X

M
7'
X

EXTENDS POST SHALL BE


DI
AGONALLY
C

C
CENTERED IN
ONE TREAD STAI
R TREAD.
C

WI
DTH
C

26 1/2" MAX

LANDI
NG W HERE
C

OCCURS
X

C C

PIPE HANDRAI
L
C
C
C

SURFACE OF STEP POST MOUNTED


12" PLUS C NOSING LI
MIT
C
WIDTH OF
SKATE STOPPER @ 36" OC
TREAD MI N
(FOR OUTDOOR CONDI TI
ON
A 7'MAX
C
C
ONLY),W HEN REQUI
RED
C

8 1/
4" R
C

C
HANDRAI
L,W HEN
C
REQUI
RED
C

HANDRAI
L C
42" MIN

BRACKET
11/
2" STD PI
PE
TYP
X

C
C

C
C

3 7/
8" TYP
C

3 7/
8" TYP C
C

PI
PE GUARDRAI
L - POST TYPE
SHEET 1OF 3

RECOMMENDED BY THE CI
TY OF SAN DI
EGO
REVI
SION BY APPROVED DATE
STANDARDS COMMITTEE
CI
TY OF SAN DI
EGO - STANDARD DRAW I
NG
ORI
GINAL* BB J.NAGELVOORT 01/
12

2/
25/
16
UPDATED FC J.NAGELVOORT 02/
16
COORDI
NATOR R.
C.E.56523 DATE

PEDESTRIAN PROTECTIVE RAI


LING
DRAW I
NG
& STAIR HANDRAIL SDM -
118
NUMBER
1/
2"
C 11/
2"
5/8" X 11/
2"

C
2" C PLATE
1/
2" C C C
C C
3/8" X 5" DI
A
3/
16" C
C PLATE

1/
2" 11/
2"
C SLI
DING FI
T
C

C
C

C
11/
2" MI
N
3/
16" C

C
C 1/
4" EXPANSI
ON JOI
NT

C C
C
C

C 1/
2"
3/
16"

C
3/
16"

C
C

3/
16"
17/
16" X 3" LONG
ROD SLI
DING FIT 1" R
C 3/
4" DI
A C BOLTS AND
C 2" 1/
4" ANCHORS APPROVED
BY THE ENGI
NEER
W ELDI
NG DETAI
LS
HANDRAI
L BRACKET

C 11/
2"
C

C 3" MI
N
C
W HEN REQUIRED, NON-SHRI
NK
GUARDRAIL SKATE GROUT
C
STOPPER @ 36" O.
C. C GUARDRAI
L

C
(FOR OUTDOOR
C

5" MIN
CONDITI
ON ONLY)
HANDRAI
L
C

C
SEE NOTES
ON SHEET 1
FOR X
C

42" MIN
X

3" HOLE
31"

C
C

W ALKI
NG SURFACE
& LANDING
MOUNTI
NG DETAI
L

POST SHALL BE GROUTED IN


C

C
C

PLACE USI
NG NON-SHRI NK GROUT.
C
5" MIN
C

PI
PE GUARDRAI
L
C
R= 11/
2"
RAI
LING NOTES
1. 1/
4" EXPANSI
ON JOI
NTS @ 16'ON CENTER.

2. W ELD AND GRI


ND SMOOTH ALL CONNECTI
ONS. ALUMINUM GUARDRAIL
SKATE STOPPER
3. ALL RAI
LING TO BE HOT DI
P GALVANI
ZED AFTER FABI
CATI
ON.

4. PI
PE SHALL BE SEAMLESS STEEL ASTM A53 GRADE B.

5. I
NSTALL HANDRAI
LS ON BOTH SI
DES.

6. STAI
RS AND LANDINGS THAT ARE OPEN ON ONE OR BOTH SIDES AND MORE THAN 30" ABOVE
THE ADJACENT GROUND SHALL BE PROVI
DED W I
TH GUARDRAI
L. SHEET 2 OF 3

RECOMMENDED BY THE CI
TY OF SAN DI
EGO
REVI
SION BY APPROVED DATE
STANDARDS COMMITTEE
CI
TY OF SAN DI
EGO - STANDARD DRAW I
NG
UPDATE KA J.NAGELVOORT 01/
12

2/
25/
16
UPDATE FC J.NAGELVOORT 02/
16
COORDI
NATOR R.
C.E.56523 DATE

PEDESTRIAN PROTECTIVE RAI


LING
DRAW I
NG
& STAIR HANDRAIL SDM -
118
NUMBER
O
TYPI
CAL THREE I
NCH BORDER
30 MAX
OF HI
GHLY CONTRASTI
NG COLOR LEVEL

C
11/
2" STD LANDING
PLACED PARALLEL TO AND NOT
PREPOST TYP
1/
2" R MORE THAN 1" FROM C

NOSE.A PAI
NTED STRI
P WI
LL BE
C

ACCEPTABLE.

C
C

C
7" MAX
4"
4" MI
N

C
C
C TREAD
C
11" MI
N
C

BETWEEN LANDINGS OR
C C
C
C
11/
4" MAX 1/
2" R

22"
C
TREAD 11" MI
N C C
A C 3"

FLOOR LEVELS
DETAI
LA

12' MAX. RISE


C
DETAI
LA

C
C 6"
C
3"

C
520-C-2500 CONCRETE
LEVEL
LANDI
NG A #4 @ 12" OC
NOSI
NG
LI
MIT

C
C
C

C
C #4 @ 24" OC

C
C

4" 3"
C
C

C
6"
16"

C
C 3" R ON ALL BENDS
C
C

3"
C

3" C
C
6"

SECTI
ON B-B

NOTES
1.BROOM FI
NISH ON TREADS,TROW EL FI
NISH ON ALL OTHER EXPOSED SURFACES.
2.1/
4" PER 1'SLOPE ON TREADS FOR DRAI
NAGE.

11/2" STD
PIPE POST
C

B (TYP)

C
3" C 1/
2" R
C

C
14"

6"
C
C

C
C

C 6" C 48" CLEAR W I


DTH C 6"
C C C #4 @ 12" OC
#4 @ 24" OC
C 5'W I
THOUT CURB
C

SECTI
ON A-A
CONCRETE STEPS

SHEET 3 OF 3

RECOMMENDED BY THE CI
TY OF SAN DI
EGO
REVI
SION BY APPROVED DATE
STANDARDS COMMITTEE
CI
TY OF SAN DI
EGO - STANDARD DRAW I
NG
UPDATED KA J.NAGELVOORT 01/
12

UPDATED FC J.NAGELVOORT 02/


16
2/
25/
16
COORDI
NATOR R.
C.E.56523 DATE

PEDESTRIAN PROTECTIVE RAI


LING
DRAW I
NG
& STAIR HANDRAIL SDM -
118
NUMBER
6'-6' 10' MAX 10'MAX

CHAIN-l...INK FABRIC
2' 1YP 9 GAGE GALV
1 314' MESH

13 lQ" SQUARE
OR 15" CIRCULAR
52~2500 CONCRETE FOOllNG

• FOR EDGE BEAM, SLAB, AND


SELECT FILL DETAILS, SEE PLANS. ELEVATION

MIN. WEIGHT
MIN. SIZE IN
DESCRIPTION PER LIN FT
INCHES
IN LBS

Une Post 2.375 IN OD 3.65LBS


Terminal Post 2.875 IN OD 5.79LBS
Top Rail 1.660 IN OD 2.27LBS
Bra&:ing 1.660 IN OD 2.27LBS
Gate Frame 1.660 IN OD 2.27LBS

NOTE:
1. CHAIN LINK FABRIC SHALL BE ERECTED ON THE INTERIOR SIDE OF THE COURTS.
2. CHAIN LINK FABRIC SHALL HAVE KNUCKLED FINISH ON TOP EDGE.

CAUTION:
THIS STANDARD DRAWING IS NOT TO BE USED IF ANY WIND SCREEN IS TO BE APPLIED TO THE FENCE.

REVISION BY APPROVED DATE RECOMMENDED BY THE Ct1Y OF SAN DIEGO


STANDARDS COMMITTEE
CITY OF SAN DIEGO - STANDARD DRAWING
ORIGINAL* KA • NAGELVOOR OV12
oil~ 1/31/2012
COORDINATOR R.C.E. 65271 DATE
TENNIS COURT FENCE
CHAIN LINK DRAWING
SDM-1 19
NUMBER
1"

C
C
31" ± 1"

C
A A
4" SI
DEW ALK
C 7"
3" C C PER SDG-155
C

C
C
C

4" 2 SACK SLURRY

6" x 8" W OOD POST


C 1'
-6"
C

5" MI
N 4" 2 SACK SLURRY
C
TOP OF CURB

C
GUTTER

C
C
C

5" MI
N

POST KNOCKOUT PLAN DETAI


L
SECTI
ON A-A

NOTES:
1. THI
S STANDARD DRAW ING SHALL BE USED W HEN GUARDRAILIS I
NSTALLED ADJACENT TO CURB,
GUTTER,AND SI
DEW ALK. THE POST KNOCKOUT DETAI
L DOES NOT APPLY W HEN GUARDRAI
LIS
I
NSTALLED I
N A PARKW AY.

2. SEE CALTRANS STANDARD PLANS FOR ADDI


TIONAL GUARDRAI
L DETAI
LS.

RECOMMENDED BY THE CI
TY OF SAN DI
EGO
REVI
SION BY APPROVED DATE
STANDARDS COMMITTEE
CI
TY OF SAN DI
EGO - STANDARD DRAW I
NG
ORI
GINAL* KA J.NAGELVOORT 01/
12

2/
25/
16
UPDATE KA J.NAGELVOORT 08/
13
COORDI
NATOR R.
R.
C.
C.
EE
..
55
66
55
22
33 DATE
UPDATE AR J.NAGELVOORT 02/
16

GUARDRAI
L DRAW I
NG

NUMBER
SDM -
130
O F A G
E
E N
M C
A

Y
N

S E R
W E
3/4" radius lug slot Open position mark,
in both sides of rim
1/8" deep groove in both
sides of rim and cover.

2" X 1"
diamond mat,
1/8" deep

TOP OF FRAME & COVER Letters 1" high, 3/4"


no other inscription to
appear on exposed surfaces. SECTION THROUGH RIM

I' 23 5/8" outside dia. of cover 'I


V ~H 7 b uzy;r m 7 21 zcq~--.~;1 /B" 1

t~ .:..:·~··dl r% fN [~;~. :. 'J


22" Dia. Clear Opening

SECTION THROUGH FRAME & COVER 1/4" -ll=


7/8"-J
3/8"--t
SECTION THROUGH LUG

Machined Surface 13/4"1


5/8" R SECTION THROUGH
RIB AT MID RADIUS
BOTTOM OF COVER

NOTES
®~--------------------~
1. Frame and cover shall be cast iron. Cast iron shall
conform to ASTM 48, Class 30. FOR MARK
2. Frame and cover for use in non-traffic areo only.
3. Weights: Frame 29 lbs - 33 lbs. Sewer Projects Sewer
Cover 95 lbs. - 11 0 lbs. Storm Drain Projects Storm Drain
4. Imported frames and covers shall have the country of Water Projects Water
origin marked in compliance with federal regulations.

Revision By Approved Date RECOMMENDED BY THE SAN DIEGO


SAN DIEGO REGIONAL STANDARD DRAWING REGIONAL STANDARDS COMMITTEE
ORIGINAL Kercheval 12 7
Add Metric T. Stanton 03/03 7(Z6(ZOfZ

Reviewed T. Stanton 04/06 24• MANHOLE FRAME AND COVER


Delete Metric D. Gerschoffer 05/12 DRAWING
LIGHT DUTY NUMBER M-2
...,....r----S,ee Detail
12 Ribs

HALF PLAN FRAME &: COVER

38 1/8"

4"

HALF SECTION FRAME &: COVER


x
c
E

NOTES ~
1. Frame and cover shall be cast iron. Cast iron
shall conform to ASTM 48, Class 358.
1/8"-J 7/16. M l_
2. Weights: Frame 314 lbs - 363 lbs.
Outer Cover 285 lbs - 330 lbs.
Inner Cover 147 lbs - 171 lbs.
3. Machine all matching surfaces and seats of
frame and cover to prevent rocking.
4. Imported frames and covers shall have the
DETAIL
country of origin marked in compliance with
federal regulations.

Revision RECOMMENDED BY THE SAN DIEGO


SAN DIEGO REGIONAL STANDARD DRAWING REGIONAL STANDARDS COMMITTEE
ORIGINAL
dd Metric T. Stanton 03/03 7(Z6(ZOfZ
Reviewed T. Stanton 04/06
36. MANHOLE FRAME
Delete Metric D. Gerschoffer 05/12 AND TWO CONCENTRIC COVERS DRAWING
HEAVY DUTY NUMBER M-3
Varies

~ ~
Back of Back of
sidewalk sidewalk
n n
Top View
6'-0"
max.
(typical)

see note 3

I
I
I I
I I 6"x6"
l r p o s t typ.
....L-_ _ _ LJ
LJ Front View LJ t...:.._j LJ

CONTINUOUS BARRICADE End View


Location (Both
6'-0" dimension------ Barricades)
shown on ~ 1"
plans ___j_
~
•tO •tO
I I
-n -n
Ground Line

r
I I I
•tO I I
I 1114"x4"
N I I post
-'-----~
I Front View
u SEPARATE BARRICADE u _ _----l..
NOTES
1. Posts to be structural grade redwood or pressure treated (with wood preservative) Douglas Front View
Fir, surfaced four sides; cross pieces to be 2"x8" select grade Douglas Fir, surfaced four sides. GUARD
2. All exposed portions of barricades shall be painted with two coats of white exterior enamel
over prime coat. POST
3. Connections shall be made with 3/8" x 6" galvanized lag screws with one (1) washer each.
4. Reflector sign fastners to be 3/8" x 1 1/2" galvanized lag screws.
5. Reflector signs - California Type N. Size 18" x 18" - Yellow with nine (9) 3 1/4" reflectors
(center mount). LEGEND ON PLANS
a. Reflectors shall be red for use on dead end streets, in all other cases they shall be yellow. 0....,.....0
Reflector material shall be plastic or other approved reflectorized material.
Barricade
b. Sign material shall be aluminum alloy 6061-T6 or 5052-H38, aluminum thickness 0.063".
6. 6' long hat section metal post per Caltrans Std. Plan A74-A optional for guard post. R
Guard Post

Revision RECOMMENDED BY THE SAN DIEGO


SAN DIEGO REGIONAL STANDARD DRAWING REGIONAL STANDARDS COMMITTEE
ORIGINAL
Add Metric T. Stanton 03/03 7(Z6(ZOfZ
Reviewed T. Stanton 04/06
Delete Metric D. Gerschoffe 05/12
GUARD POST AND BARRICADE DRAWING
NUMBER M-9
24" min
I· ·I

C.l.

z
;;;
.
•... s· t.tiN

5" MIN

6" THICK GROUT PAD


SLOPE SURFACE OF GROUT PAD TO DRAIN AWAY
FROM COVER, AND TO MEET EXISTING GRADE.

PLAN-IN UNPAVED AREA

J ~1/4" i
1..:::
14·

"I
2"MIN ~~CI ALTERATION LOCATION OF MONUMENT.
TIE DISTANCES SHOWN ON FINAL SUB-
I 1" DIVISION t.tAP IF ALTERNATE LOCATION
IS USED
RISER RING
LOCATION OF STREET
AC PAVEMENT SURVEY MONUMENT
Cl FRAME
1/4" ---J ~

~~~Till

BRICK SUPPORT ALL AROUND


ON 2" SAND BASEED

lYPICAL MONUMENT
SECTION IN PAVED AREA
Revision By Approved Date RECOMMENDED BY THE SAN DIEGO
SAN DIEGO REGIONAL STANDARD DRAWING REGIONAL STANDARDS COMMITTEE
ORIGINAL Kercheval 12 75
Add Metric T. Stanton D3/03 7/26/2015
Reviewed
Delete Metric
T. Stanton 04/06
D. Gerschoffe 05/12
STREET SURVEY MONUMENT
Note 4 Rev D. Gerschoffe 02/14
M-10
3.5" MIN
CONCRETE RISER RING
ENCASEMENT WELDED IN
PLACE

RISER RING WELDED TO EXISTING RING

J
2"min
~ 1-1/4"
~~C.I.
i14"

I 1·
RISER RING BRICK SUPPORT ALL AROUND
ON 2" SAND BASE.

24" MIN
TYPICAL MONUMENT
SECTION IN PAVED AREA

12" MIN RADIUS


CONCRETE
ENCASEMENT
ALTERATION LOCATION OF MONUMENT.
TIE DISTANCES SHOWN ON FINAL SUB-
DIVISION MAP IF ALTERNATE LOCATION
IS USED.

6" THICK GROUT PAD


LOCATION OF STREET
SLOPE SURFACE OF GROUT PAD TO DRAIN AWAY
FROM COVER, AND TO MEET EXISTING GRADE. SURVEY MONUMENT
PLAN-IN UNPAVED AREA

STREET SURVEY MONUMENT


OVERLAY ADJUSTMENT DRA'MNG
NUMBER M-10A
NOTES

1. COVER AND FRAME TO BE CAST INTEGRALLY WITH PIPE BOX.


2. MONUMENT BASE MAY BE CAST IN PLACE OR PRECAST.
3. FORM AND TAPER EXPOSED UPPER 6" OF CAST -IN-PLACE BASE TO A TOP
DIAMETER OF 5". (PRECAST BASE SHALL BE SAN BACKFILLED)
4. MONUMENT MARKER SHALL BE A DOMED BRASS, 3" IN DIAMETER.
5. MONUMENT LOCATION:
A) SET ON ALL CENTERLINE INTERSECTIONS UNLESS ACTUAL LOCATION IS MODIFIED BY
THE AGENCY AND SHOWN IN MODIFIED LOCATION ON MAP. WHEN CENTERLINE
INTERSECTIO IS IMPRACTICAL, OFFSET 5' ON CENTERLINE OF MAJOR STREET, (SEE
DETAIL AT RIGHT). IF NEITHER CETERLINE CAN BE OCCUPIED, TWO MONUMENTS WILL
BE SET IN LINE AROUND THE FRONT ON THE PERIMETER OF A 10'
DIAMETER CIRCLE, WHOSE CENTER IS THE POINT.
B) SET ON CENTERLINE AT INTERVALS NOT EXCEEDING 1 000' ON STRAIGHT RUNS.
C) SET ON CENTERLINE AT POINTS OF CURVATURE.
D) SET ON CENTER AT CENTER POINTS OF CUL-DE-SACS.
E) SET ON CENTERLINE WHEN CENTER POINT OF CUL-DE-SAC IS OFFSET FROM
CENTERLINE.
F) THESE STANDARDS MAY BE MODIFIED AT THE DISCRETION OF THE THE AGENCY IN
CASES WHERE STRICT COMPLIANCE THEREWITH RESULTS IN MORE MONUMENTS THAN
IT CONSIDERS NECESSARY. THE FOLLOWING TECHNIQUE FOR REDUCING THE NUMBER
OF MONUMENTS WILL BE ROUTINE.
G) SUBSTITUTION OF ONE MONUMENT ON THE "POINT OF INTERSECTION" FOR
MONUMENTS AT THE "BEGINNING OF CURVE" AND THE "ENDING OF CURVE" WHEN
THE "POINT OF INTERSECTION" FALLS WITHIN THE PAVEMENT AREA.
H) DELETION OF ANY MONUMENT OTHERWISE REQUIRED BY THESE STANDARDS WHEN
ITS POSITION CAN BE DETERMINED BY TURNING ONE ANGLE FROM A POINT ON A
STRAIGHT LINE BETWEEN TWO OTHER MONUMENTS, PROVIDING SUCH POINT IS NOT
MORE THAN 300' FROM THE POINT ON WHICH THE DELETED MONUMENT
WOULD HAVE BEEN PLACED.
I) FOR RAISING STREET SURVEY MONUMENT TO FINISH GRADE, RISER RING IS TO BE
WELDED TO EXISTING RING AND BROUGHT TO SURFACE. ENCASE RISER RING IN FAST
SETTING CONCRETE WITH A MINIMUM OF 3.5" THICHNESS. CONCRETE MUST OBTAIN
1600 PSI BEFORE TRAFFIC USE, AND HAVE A MINIMUM STRENGTH OF 3250 PSI.

Revision By Approved Date RECOMMENDED BY lHE SAN DIEGO


SAN DIEGO REGIONAL STANDARD DRAWING REGIONAL STANDARDS COMMITTEE
ORIGINAL Kercheval 12/75
Add Metric
Reviewed
T. Stanton
T. Stanton
D3/03
04/06 STREET SURVEY MONUMENT Jfl- ) 7/26/2015
Choifperson R.C.E. 19246 Date
Delete Metric
Note 4 Rev
D. Gerschoffe 05/12

D. Gerschoffe 02/14
NOTES DRA'MNG
NUMBER M-108
--.---------.--
1:1 I
Epoxy grout or \
poured lead. \

~
~
~

1/p:- I I

~ w
-l"""'----1f-........,3
I

s
I _ 1,..--B·____._!
__..,1

l t 3/16"
/. t
Pitch-12 per inch _j I I ' \ l1/16"
1/16" deep ~ \.__ 45' chamfer
rod.

TYPE-A TYPE-8 INSTALLATION IN EXISTING CONCRETE


ELEVATION (Typical for Type A or B)

NOTES
1. Material- Brass A.S.T.M. B-16. All machine tolerances ± 1/64" machine finish.
2. May be installed in fresh concrete at time of installation of concrete structure.
3. Location-in most stable, permanent location in vicinity, such as in base for
street light standard or traffic signal (behind sidewalk), in curb (not near joint,
on curve or near trees), on top of drainage headwall, in foundation for building
or retaining wall or in concrete pads for transformers, pump stations etc.

Revision By Approved Date RECOMMENDED BY THE SAN DIEGO


SAN DIEGO REGIONAL STANDARD DRAWING REGIONAL STANDARDS COMMITTEE
ORIGINAL Kercheval 12/75
Add Metric T. Stanton 03/03 ~7(Z6(ZOfZ
Reviewed T. Stanton 04/06 Ctidrrperson R.C.E. 19246 Date
Delete Metric D. Gerschoffer 05/12
BENCH MARK - BRASS PLUG DRAWING
NUMBER M-11
COUNlY OF SAN DIEGO
CITY OF SAN DIEGO PORT OF SAN DIEGO OLD CITY OF
U.S.C. & G. (LAND) U.S.C. & G. SAN DIEGO STAFF
U.S.G.S. STAFF (BAY CHART) (PRIOR TO MARCH 1963)

II
~~ 6.12
I
I 9.00
I
-T-o
HIGHEST TIDE -- 4.91 - - - - - - + - + - 7 . 7 9 1.21

MEAN HIGHER WATER-t§§~


i 2 . 7 3 - - - - - - + --+-5.61-------+---1r--3.39

MEAN HIGH WATER----1~~~ 2.01 -------+--7-+- 4.89


1 1
4.11

MEAN S£A L.EVEI..--~;f-- 0 - - - - - - - - + - - + - - 2.88 ------....__,r--6.12

MEAN LOWER
LOW WATER -----tl'*l;t--
-
2.88 - - - - - - - - 1 - - + - 0 -------+--+--9.00

LOWEST TIDE---~~ 5.06 - - - - - - - + - - + - 2.18 ------....__,f---11.18

-
LEGEND
U.S.C. & G. = United States Coast and Geodetic Survey.
U.S.G.S. = United States Geological Survey.
MEAN HIGH WATER = Mean of all high water in San Diego Bay.
MEAN HIGHER WATER = Mean of all higher water in San Diego Bay.
Bay charts and topography up to the mean
high tide based on zero at the mean lower
low water.
SOURCE
Data based on U.S.C. & G. ·sea level Datum of 1929·.

Revision By Approved Date RECOMMENDED BY THE SAN DIEGO


SAN DIEGO REGIONAL STANDARD DRAWING REGIONAL STANDARDS COMMITTEE
ORIGINAL Kercheval 12/75
Add Metric T. Stanton 03/03 ~7(Z6(ZOfZ
Reviewed T. Stanton 04/06
DATUMS Ctidii-person R.C.E. 19246 Date
Delete Metric D. Gerschoffer 05/12 DRAWING
NUMBER M-12
FOUND MONUMENTS LEGEND
Found monuments must denote the character Fd 2" Iron Pipe Marked RCE XXXX or

..
of the monument, how it is identified and the per Map XXX unless otherwise noted
record, or no record as applicable.

SET MONUMENTS - Criteria for Locating and Fd Street Survey Monument Stamped
Character RCE XXXX or LS XXXX
On subdivision boundaries, permanent
monuments are required; and must be shown (Q) Set 2" x 24" Iron Pipe Marked RCE
XXXX or LS XXXX
on the map at intervals as specified by the
local agency. The location of such points that
are inacceptable or will be destroyed by D Set Lead and Disc Stamped RCE XXXX
or LS XXXX
construction may be established by ties to
permanent reference monuments shown on the
final map. 0 Set %" x 18" Iron Pipe Marked RCE
XXXX or LS XXXX
A permanent monument shall be no less Set Street Survey Monument Stamped
substantial than the following: RCE XXXX or LS XXXX per Standard
Drawing M-10
a. An iron pipe of minimum two inch diameter
not less than 2' in length placed upright in
the ground so that the top of said pipe is The addition of other symbols is permissible
flush with the surface. Said pipe shall be where such will result in a clearer map.
filled with a metal or cement plug at least
three inches in depth and centered with a The following notes should be used in the
metal tack and disc; or legend where applicable.

b. A metal plug with tack and disc set flush Unless otherwise shown on this map:
with the surface in portland cement concrete
sidewalk, curb or pavement; or other 1. All lot corners except as described below will
monument satisfactory to the City Engineer or be monumented by a %" by 18" iron pin
County Surveyor. The metal plug shall be stamped (RCE or LS number).
anchored 1" deep in sidewalk.
2. Lot corners along the sideline of dedicated
Lot corners and points of curves along street street right of way will be monumented by a
and alley right of way lines where portland disc stamped (RCE or LS number), set along
cement concrete sidewalks, curbs or pavement an extension of the lot line at an offset of
exist, or will be constructed as part of the _ in the (curb, sidewalk). The offset shall
subdivision requirements, shall be identified with be measured radially, or at right angles, to
tack and disc set flush with the surface along the right of way line. (See example below.)
an extension of the lot line at an approved
offset, to be measured radially or at right 3. All points of curve of the sidelines of
angles to the right of way line in said dedicated streets will be monumented by a
sidewalk, curb pavement. In case the sideline disc stamped (RCE or LS number), set at an
of the lot is not radial or at right angles to
offset of _ in the (curb, sidewalk). The
the right of way line a disc shall be set along
offset shall be measured radially.
an extension of the sideline at an offset to be
measured radially or at right angles to the
right of way line. Where no such concrete
work exists, and none will be required to be
constructed, all lot corners, angle points and Radial
points of curve shall be marked with a .....0
monument no less substantial than a one-half _J
inch steel rod or pipe, 18" long, set flush with
the surface.
~
I I
I I
II
II

~
EXAMPLE OF OFFSEf DISCS

Revision By Approved Date RECOMMENDED BY THE SAN DIEGO


SAN DIEGO REGIONAL STANDARD DRAWING REGIONAL STANDARDS COMMITTEE
ORIGINAL Kercheval 12/75
Add Metric T. Stanton 03/03 ~7(Z6(ZOfZ
Reviewed T. Stanton 04/06
05/12
SURVEY MONUMENTS Ch(i(rperson R.C.E. 19246 Date
Delete Metric D. Gerschoffer DRAWING
NUMBER M-13
1 Gram = 15.4324 grains 1 Grain = 0.0648 g.
1 Gram = 0.0353 oz. 1 Ounce = 28.3495 g.
1 Kg. = 2.2046 lb. WEIGHT 1 Pound = 0.4536 kg.
1 Kg. = 0.0011 ton 1 Ton = 907.1848 kg.
1 Ton (met) = 1.1023 ton 1 Ton = 0.9072 ton (met)

1 Sq. em. = 0.1550 sq. in. 1 Sq. in. = 6.4516 sq. em.
1 Sq. m. = 10. 7639 sq. ft. 1 Sq. ft. = 0.0929 sq. m.
1 Sq. m. = 1.1960 sq. yd. 1 Sq. yd. = 0.8361 sq. m.
1 Hectare = 2.4710 acres AREA 1 Acre = 0.4047 hectare
1 Sq. km. = 0.3861 sq. mile 1 Sq. mile= 2.5900 sq. km.
1 Sq. km. = 247.10 acres 1 Acre = 0.0040 sq. km.

1 Cu. em. = 0.0610 cu. in. 1 Cu. in. = 16.3872 cu. em.
1 Cu. m. = 35.3134 cu. ft. VOLUME 1 Cu. ft. = 0.0283 cu. m.
1 Cu. m. = 1.3079 cu. yd. 1 Cu. yd. = 0.7646 cu. m.

1 Uter = 61.0250 cu. in. 1 Cu. in. = 0.0164 liter


1 Uter = 0.0353 cu. ft. 1 Cu. ft. = 28.3162 liters
1 Uter = 0.2642 gal. (U.S)
CAPACilY 1 Gal. = 3.7853 liters
1 Uter = 0.0284 Bu. 1 Bu. = 35.2383 liters

1 MM. = 0.0394 in. 1 ln. = 25.4000 mm.


1 CM. = 0.3937 in. 1 ln. = 2.5400 em.
1 Meter = 3.2808 ft. LENGTH 1 Ft. = 0.3048 m.
1 Meter = 1.0936 yd. 1 Yd. = 0.9144 m.
1 Km. = 0.6214 mile 1 Mile = 1.6093 km.

MULTIPLE PREFIX MULTIPLE PREFIX


1000000 mega 1/10 deci
1000 kilo
METRIC
1/100 centi
100 hecto PREFIX 1/1000 milli
10 deka micro
1/1000000

TEMPERATURE
Degrees Fahrenheit = 9/5 (Degrees Celsius) + 32
Degrees Centigrade = 5/9 (Degrees Fahrenheit - 32)

Revision By Approved Date RECOMMENDED BY THE SAN DIEGO


SAN DIEGO REGIONAL STANDARD DRAWING REGIONAL STANDARDS COMMITTEE
ORIGINAL Kercheval 12/75
Add Metric T. Stanton 03/03 ~7(Z6(ZOfZ
Reviewed T. Stanton 04/06
METRIC EQUIVALENTS Ctidirperson R.C.E. 19246 Date
Edited T. Stanton 08/09 DRAWING
Delete Metric D. Gerschoffer 05/12 NUMBER M-14
1I 4" Steel Plate welded to top
(burrs removed). 118"

4" Diameter Steel Pipe

112" Expansion Joint

Back of
in walk--~ 5" Diameter Steel Pipe Sleeve

Concrete
as w a l k - - - - -

18" Diameter

4" Pipe

Four Links----

....
Ill
0
a. .. ~: ·i :~ ..· .• ...... .

Make bowl shaped recess


....0 :.. . '··.
. .:. ~ .:4~: .·- ~ ,.
in concrete to accommodate • E ·....
4. :. ~

three links of chain--- "'o........


~

0
.0
5" Diameter Steel Pipe Sleeve - - -
E
....e

HASP DETAIL

NOTES
LEGEND ON PLANS
1. Chain to be 1I 4" proof coil chain galvanized steel.
Weld four links to post and three links to pipe sleeve.
2. All metal to be hat-dip galvanized after fabrication. 0
Revision RECOMMENDED BY lHE SAN DIEGO
SAN DIEGO REGIONAL STANDARD DRAWING REGIONAL STANDARDS COMMITTEE
ORIGINAL
Add Metric 7/Z6/ZO/Z
Reviewed
DEMOUNT ABLE POST
Delete Metric DRAWING
NUMBER M-16
Horizontal brace with truss rod may be used
as an alternate to a diagonal brace.

Tension Wires
Max.

Portland cement
concrete
10'
10'
END AND CORNER
POST ASSEMBLY
Une Post

Tension Wires

Une posts at 1OOO'max. intervals braced


and trussed in both directions. - - - -

10'

UNE POST BRACING

Latch post
Horizontal brace with
3/8" steel truss Diagonal brace or horizontal
rods. brace with truss rods

10'

GATE ASSEMBLY

Revision RECOMMENDED BY THE SAN DIEGO


SAN DIEGO REGIONAL STANDARD DRAWING REGIONAL STANDARDS COMMITTEE
ORIGINAL
Add Metric T. Stanton 03/03 7(Z6(ZOfZ
Reviewed T. Stanton 04/06 CHAIN LINK FENCE
Delete Metric D. Gerschoffer 05/12
DETAILS DRAWING
NUMBER M-20
5' 10' Typical
Mox Pad mounted
Equipment
12" Min
Property
Line

Joint
Trench
0-' :::~,;t
1

!_ _ _ _ _ _ __,,
] _J- J_ ~::~:""
......_Lj _ Conduit
I

SIDEWALK NEXT TO CURB

5' 10' Typical


Mox Pad mounted
Equipment
12" Min 24"
Property
Min Line

:·:f/. L lL J
Joint
Trench
D-
1 1
.,...:;::..:·

/Conduit
/ _ _ _ _ __,
Jl )-
Substructure

Servic7
.....___ _ _/_l _ Conduit
I

SIDEWALK NEXT TO PROPERTY LINE

5' 10' Typical


Mox Pad mounted
Equipment
12'' Min
Property
Line

Substructure
Service
Joint Conduit
Trench

SIDEWALK NEXT TO CURB AND PROPERTY LINE

NOTES
1. Sidewa lk shall hove a minimum of 4' clear area (path,
not including curb) passing pedestals, pull boxes and
other structures.

2. See Standard Drawing M-15 for joint trench.

Revision By Approved Date RECOMMENOED BY TME SAN DIEGO


SAN DIEGO REGIONAL STANDARD DRAWING REGIONAL STANDARDS COMMITTEE
ORIGINAL Parkinson 9 88
Add Metric T. Stanton 03/03
Reviewed T. Stanton 04/06 UNDERGROUND TYPICAL LOCATION
Delete Metric 0. Gerschoffe 05/12
CONVERSION/ REPLACEMENT / UPGRADE ORAYt1NG
NUMBER M-21
FOR DRAWING M-15 SEE DRAWING SDM-103
1 3/4"x 1 3/4"

!4-------6-·-------~~

NOTES
1. Structural steel tubing used for
{Unless Otherwise Shown on Plans)
~------,
1-
lei
10 1
12_j_Gauge Post

2"±
f
post & sleeves shall be
lol
galvanized 12 gauge cold rolled lol
steel, of the nominal dimensions lol

~
shown hereon and meet the
requirements of ASTM A446
Grade A.
2. Galvanizing shall be per ASTM 0
A525. Posts & sleeves shall 3/8" Rivet (typ.)
0
have 7/16" dia. holes
spaced 1" o.c. ±1/8" c: 0
0'>

-
& shall have no more variation in ·c;; 0
straightness than 1/16" in 0 0
3'. Posts shall be square .._
.....c:
Q) o Rivet Specification
within ±0.014", have twist Q) o Dimension: 3/8" Dia. Shank
no greater than 0.062" in 3' and u
o 7/8" Dia. Head
have corner radii of 5/32" .....0 Grip Range: .200-.356
0
±1/64". in
C"'
j-...
Finish: Electro-Galvanize
0
od ASTM-8-633
3. The signs shall be mounted E
0 Type Ill SCI
::I
on posts in accordance with E
0
Section 56, "Signs" of the State ·x0 0
Standard Specifications. All :::::!: 0
fastening hardware is to be
provided by the Contractor. : lf3/B" Rivet (typ.)
4. Maximum sign size 5.2 sq. ft. 0

d 0
Iq r- 2 1/4" Anchor Sleeve

3" 4~
11°11 _ _ _
~ /~' ~ / ~ /~' /
;y>-.~"-~'
---r-"7"-o--_}~y,

~~,"
/ "'-"</
.f _j

~/~
I 11 ~
ILJI
0

0

~
-'- \: Existing
Ground

2 1/4"x 2 1/4" 0
12 Gauge Post 0
....._ --------''-
2"x 2"-12 Gauge
Post----"" -----1 1----2" Anchor Post

Revision By Approved Date RECOMMENDED BY THE SAN DIEGO


SAN DIEGO REGIONAL STANDARD DRAWING REGIONAL STANDARDS COMMITTEE
ORIGINAL G.Porkinson 2/95
Add Metric T. Stanton 03/03 ~7(Z6(ZOfZ
Reviewed T. Stanton 04/06
BREAK-AWAY SIGN POST Ch(i(rperson R.C.E. 19246 Date
Delete Metric D. Gerschoffer 05/12 DRAWING
NUMBER M-45
CHAPTER 8
RECYCLED
W ATER
SYSTEMS
TRENCH RESURFACING
PER SDG-107 /SDG-108

FINISHED TO GRADE

TRENCH WIDTH

I
I
\ I
_J
I
a:
w
_J
u:::: \ I
'~fA
I
I-
>
0
~
f
-~~
(.)
0...
w (.) <(
(D .. "'IL~ if
0 1~ If
I
(.)
I
(.)
zw (.)
zw
I * 0
0) ,,
~
~\

zw a:
a: I- a:
I- ~ 6" MIN
I- ~
><.
8" MAX

z
~
RECYCLED
C\J
(9
T""" WATER O.D.
z IMPORTED GRANULAR MATERIALS SE50
0 w
0 z
..
w 0
(D N *
0
0)

BEDDING

TRENCH SECTION

NOTES:
1. (*) INDICATES MINIMUM RELATIVE COMPACTION. IT SHALL BE 95% MIN IN THE TOP FOOT.
2. MINIMUM COVER: 4' FOR RECYCLED WATER MAIN.
3. RECYLE WATER PIPE SHALL BE PURPLE COLOR CODED INTEGRALLY STAMPED
OR MARKED AS "CAUTION -RECYCLED WATER -DO NOT DRINK".
4. WARNING I IDENTIFICATION METAL TAPE SHALL BE PLACED AT 4' BELOW TRENCH CAP AND
12" BELOW FINISH GRADE IN UNIMPROVED STREETS.
5. THE TERM RECLAIMED WATER IS THE SAME AS THE TERM RECYCLED WATER.
6. 1' SAND CUSHION OR A 6" MINIMUM SAND CUSHION WITH 1" NEOPRENE PAD SHALL BE PLACED
FOR ALL CROSSINGS UTILITIES WHEN VERTICAL CLEARANCE IS 1' OR LESS. THE NEOPRENE
PAD SHALL BE PLACED ON THE MOST FRAGILE UTILITY.

REVISION BY APPROVED DATE RECOMMENDED BY THE CITY OF SAN DIEGO


STANDARDS COMMITIEE
CITY OF SAN DIEGO - STANDARD DRAWING
dl~
ORIGINAL KA J. NAGELVOOR OV12
1/31/2012
PIPE BEDDING AND TRENCH COORDINATOR R.C.E. 65271 DATE

BACKFILL FOR RECYCLED DRAWING

WATER MAINS NUMBER


SDRW-101
3 "V2" - 4"
FINISH
GRADE

DEPTH OF MAIN
SEE SDRW-101

MIN
12"

RECYCYLED
WATER TAG

1) INSTALL CORPORATION STOP WITH KEY IN THE SIDE POSITION


2) SET TOP OF METER BOX FLUSH WITH SIDEWALK, CURB, OR FINISH GRADE
3) LOCATE METER BOX AS SHOWN ON W8-03
4) INSTALL WARNING I IDENTIFICATION TAPE AS SHOWN ON SDRW-101
5) WATER LATERALS INSTALLED FOR THE USE OF RECYCLED WATER SHALL BE
IDENTIFIED AS DESCRIBED IN SPECIFICATIONS
6) SILVER SOLDER JOINTS SHALL NOT BE USED 2"
7) ON STEEL MAINS USE WELD ON COUPLINGS, ON DUCTILE IRON MAINS USE @f----------1
DUCTILE IRON SERVICE SADDLES (INSULATING BUSHINGS ARE REQUIRED) LEGEND ON PLANS
8) TOP TAPS ARE NOT PERMITIED AND ANY GLUE JOINT SHALL BE BEVELED
PRIOR TO ASSEMBLY
SHEET 1 OF 2
9) NO RECYCLED WATER SHALL ENTER INTO THE STORM DRAIN

ITEM ITEM
SIZE AND DESCRIPTION SIZE AND DESCRIPTION
NO NO

CD SIZE x 2" BRONZE SERVICE SADDLE (DOUBLE STRAP)


® 2" BRONZE ANGLE METER STOP WITH LOCKWING

® RECYCLED WATER MAIN


0 WATER METER FURNISHED AND INSTALLED BY
THE CITY
0 2" BRONZE CORPORATION STOP

0 2" x REQUIRED LENGTH COPPER PIPE TYPE "K"


SOFT/RIGID OR UNLESS OTHERWISE SPECIFIED.
® METER BOX WITH LID, 17"x 30"

® :W" ROCK, 4" TO 6" DEEP ® CUSTOMER SHUT-OFF VALVE (LOCKABLE)

REVISION BY APPROVED DATE RECOMMENDED BY THE CITY OF SAN DIEGO


STANDARDS COMMITIEE
CITY OF SAN DIEGO - STANDARD DRAWING
ORIGINAL KA . NAGELVOOR OV12
~
COORDINATOR R.C.E. 56523 DATE
2 .. RECYCLED WATER SERVICE
DRAWING
INSTALLATION AND MARKING NUMBER
SDRW-102
"PUD RW" -------,
CHIP 2" "RW" IN CURB
EMBOSSED SIGN
FACE TO IDENTIFY
RECYCLED WATER
SERVICE LOCATION

"PURPLE"
STEEL
HINGE
HEAD
COVER

NOTES:

1. FOR ALL RECYCLED WATER SERVICE READING LID OF METER


BOX SHALL BE PAINTED WITH PURPLE PANTONE #522 FOR ALL
RECYCLED WATER SERVICE.

2. METER AND VALVES SHALL BE LABELED OR TAGGED TO


INDICATE RECYCLED WATER.

SHEET 2 OF 2

REVISION BY APPROVED DATE RECOMMENDED BY THE CITY OF SAN DIEGO


STANDARDS COMMITIEE
CITY OF SAN DIEGO - STANDARD DRAWING
ORIGINAL KA A. OSKOUI OV12
08129'13
ORIGINAL KA . NAGELVOOR 08113
COORDINATOR R.C.E. 56523 DATE
2 .. RECYCLED WATER SERVICE
DRAWING
INSTALLATION AND MARKING NUMBER
SDRW-102
VALVE W ELL COVER PER SDRW -105.
SPRAY PAI
NT LI
D & I
NSI
DE OF BOX
PURPLE-PANTONE #522

TYPE 1 TYPE 2

8" MIN
FI
NISH GRADE
C
C

3"
6" C 6"
C C
C
FI
NISH

C
C
C

C
C

C
GRADE

MAX

C
C

12"
C
CONCRETE COLLAR
48" MIN. ON LINES OVER 10"

C
C
C

8" MAX
6" MIN VALVE BOX PER SDW -153

C
8" STEEL VALVE W ELL PER SDW -153

C
BACKFI
LL AROUND
VALVE AS SPECI
FIED

STANDARD BRI
CKS (
TYP)
C

RECYCLED W ATER MAI


N
C

CONCRETE VALVE
BLOCKI
NG.SEE SDW -151.

NOTES:

1. PROVI
DE HEXAGON TYPE VALVE STEM EXTENSI
ON I
F DEPTH TO
VALVE NUT EXCEEDS 2'
.SEE SDRW -106.

2. USE FOR H10 LOADI


NG OR LESS.

3. TYPE 1INSTALLATI
ON APPLIES TO VALVES W I
THI
N ROADW AYS.
TYPE 2 I
NSTALLATION APPLI
ES TO VALVES OUTSI DE ROADW AYS.

RECOMMENDED BY THE CI
TY OF SAN DI
EGO
REVI
SION BY APPROVED DATE
STANDARDS COMMITTEE
CI
TY OF SAN DI
EGO - STANDARD DRAW I
NG
ORI
GINAL KA J.NAGELVOORT 01/
12

2/
25/
16
ORI
GINAL HM J.NAGELVOORT 02/
16
COORDI
NATOR R.
C.E.56523 DATE

RECYCLED W ATER VALVE


DRAW I
NG
AND VALVE BOX (
LIGHT DUTY) SDRW -
103
NUMBER
CONCRETE 560-C-3250 C 13" DI
A C

"PUD RW " 9 3/
8" DI
A

7/8"
C
C

C
VALVE W ELL COVER MACHI
NED

C
PER SDRW -105. SEAT

C
C

C
8 1/2"
C

C
8 1/
2" DI
A C
C

6" MI
N C
C
C 9 1/
4" DI
A
C

ROAD SURFACE (
TYP.
)
CAST I
RON VALVE
TRENCH RESURFACI
NG PER W ELL FRAME
SDG-107 AND SDG-108
SPRAY PAI
NT LI
D & I
NSI
DE
OF BOX PURPLE-PANTONE #522
VALVE W ELL COVER
PER SDRW -105
VALVE W ELL FRAME

1 1/2" OR 2"
(
SET TO SLOPE OF STREET)
8" MIN.

TYPE 1 TYPE 2 C
13" DI
A
C C
C
3"

3/4"
9 3/
8" DI
A

7/8"
C
C
C

FI
NISHED
C

MACHI
NED
C
C

GROUND
C
C

SURFACE SEAT

C
C

C
C

C
C

ROAD 8 1/
2" DI
A THRU
C
C
SUBGRADE
8" I
D x 1/
4"
C
TOP OF
C 9.
33" DI
A
THI
CK W ALL C VALVE C

STEEL CASI
NG C
BONNET
(
VALVE W ELL) SEE NOTE 1
CAST I
RON RI
SER RI
NG
W OOD BLOCKS
FOR RETROFI
TTI
NG AND
(
4 PL TYP)
OVERLAY PROJECTS
C
CONCRETE VALVE
BLOCKI
NG PER SDW -151

VALVE W ELL & FRAME


FOR NEW I
NSTALLATI
ONS

NOTES:
1. PROVI
DE RECYCLED W ATER VALVE KEY EXTENSI
ON FOR ALL VALVES.
2. THE SURFACE OF THE VALVE W ELL COVER SHALL MATCH THE STREET
CROSS SLOPE AND PROFI
LE.
3. VALVE BOX AND COVER BASED ON SOUTH BAY FOUNDRY #1208N OR
APPROVED EQUAL.

4. TYPE 1I
NSTALLATI
ON APPLI
ES TO VALVES W I
THI
N ROADW AYS.
TYPE 2 I
NSTALLATI
ON APPLI
ES TO VALVES OUTSI
DE ROADW AYS.

5. SEE SDRW -106 FOR VALVE STEM EXTENSI


ON.

RECOMMENDED BY THE CI
TY OF SAN DI
EGO
REVI
SION BY APPROVED DATE
STANDARDS COMMITTEE
CI
TY OF SAN DI
EGO - STANDARD DRAW I
NG
ORI
GINAL KA J.NAGELVOORT 01/
12

08/
13
2/
25/
16
ORI
GINAL KA J.NAGELVOORT
COORDI
NATOR R.
C.E.56523 DATE
ORI
GINAL HM J.NAGELVOORT 02/
16
RECYCLED W ATER VALVE
DRAW I
NG
AND VALVE BOX (
HEAVY DUTY) SDRW -
104
NUMBER
STANDARD DIAMOND PATIERN
TREAD WITH 31.32" WIDE X
31.32" DEEP GROOVES

1-:::J
oa::
_J:r:
C/JI-

V4" RADIUS
(BOTH ENDS
OF SLOT)
CAST IRON COVER
WEIGHT = 15 lb

DIA.

CAST IRON
RING

9.5"

_J 12"
_J
~ <(
"'a:
t--L.U
cci6
PLACE FOUNDRY
STAMP ON INSIDE
SURFACE OF COVER
7.70
DIA.

CAST IRON VALVE WELL COVER


V4-T BOX
WEIGHT = 20 lb MIN
WEIGHT = 60 lb

DETAIL 1 DETAIL 2

NOTE
COVER SHALL BE COLORED PURPLE W'RED DOT

REVISION BY APPROVED DATE RECOMMENDED BY THE CI1Y OF SAN DIEGO


STANDARDS COMMITTEE
CITY OF SAN DIEGO -STANDARD DRAWING

~
ORIGINAL BB J. NAGELVOOR OV12

ORIGINAL BB . NAGELVOORT 08113


COORDINATOR R.C.E. 56523 DATE
RECYCLED WATER VALVE
DRAWING
WELL COVER NUMBER
SDRW-105
FINISH GRADE

2' MIN~

V8" FLAT PLATE--------._


u,--
"" ' ---i
if!b._

=
1..----- 2" AWWA HEXAGONAL
OPERATING NUT

v----1 V4" DIA STEEL SHAFT


CENTERING GUIDE "'- I '\. !V EXTENSION. MACHINED

~~~
TO MATCH NUT

V8"

VS" "'v ~
- :1::1
'---"1 111----8" ID x V4" THICK WALL
-L---------~,11\ ! _ /L STEEL CASING (VALVE WELL)

I ~ADAPTOR TO FIT
I AWWA SQUARE NUT

REVISION BY APPROVED DAlE RECOMMENDED BY THE CI1Y OF SAN DIEGO


STANDARDS COMMITTEE
CllY OF SAN DIEGO - STANDARD DRAWING
ORIGINAL KA ~. NAGELVOOR1 OV12
oil~ 1/31/2012
COORDINATOR R.C.E. 65271 DAlE
RECYCLED WATER VALVE
DRAWING
KEY EXTENSION NUMBER
SDRW-106
~---------18" ------------1

WE ARE CONSERVING OUR MOST


VALUABLE RESOURCE
BY IRRIGATING OUR LANDSCAPE
WITH RECYCLED WATER

12"
RECYCLED WATER
AQUA RECICLADA

DO NOT DRINK
NO TOME EL AQUA

30"--42"

RECYCLED WATER IRRIGATION ADVISORY SIGN

SHEET 1 OF 4

REVISION BY APPROVED DAlE RECOMMENDED BY THE CI1Y OF SAN DIEGO


STANDARDS COMMITTEE
CllY OF SAN DIEGO - STANDARD DRAWING
ORIGINAL KA • NAGELVOOR OV12
oil~ 1/31/2012
COORDINATOR R.C.E. 65271 DAlE

RECYCLED WATER SIGNS DRAWING


NUMBER
SDRW-108
Recycled
Process
Water
DO NOT DRINK

SIZE: 4" HIGH x 8" WIDE


COLORS:
BACKGROUND: WHITE
LEITERS: PANTONE 522 PURPLE
CIRCL&SLASH: DARK RED OVER WATER GLASS
WATER GLASS: PANTONE 522 PURPLE
V4" WIDE BORDER: PANTONE 522 PURPLE
HOLES: 118" AT CORNERS

RECYCLED WATER PROCESS SIGN

SHEET 2 OF 4

REVISION BY APPROVED DAlE RECOMMENDED BY THE CI1Y OF SAN DIEGO


STANDARDS COMMITTEE
CllY OF SAN DIEGO - STANDARD DRAWING
ORIGINAL KA • NAGELVOOR OV12
oil~ 1/31/2012
COORDINATOR R.C.E. 65271 DAlE

RECYCLED WATER SIGNS DRAWING

NUMBER
SDRW-108
Recycled
Irrigation
Water
DO NOT DRINK

SIZE: 4" HIGH x 8" WIDE


COLORS:
BACKGROUND: WHITE
LEITERS: PANTONE 522 PURPLE
CIRCL&SlASH: DARK RED WATER TAP
WATER TAP: PANTONE 522 PURPLE
V4" WIDE BORDER: PANTONE 522 PURPLE
HOLES: W" AT CORNERS

RECYCLED WATER SIGN FOR IRRIGATION

SHEET 3 OF 4

REVISION BY APPROVED DAlE RECOMMENDED BY THE CI1Y OF SAN DIEGO


STANDARDS COMMITTEE
CllY OF SAN DIEGO - STANDARD DRAWING
ORIGINAL KA • NAGELVOOR OV12
oil~ 1/31/2012
COORDINATOR R.C.E. 65271 DAlE

RECYCLED WATER SIGNS DRAWING


NUMBER
SDRW-108
Recycled
Water used
for Toilet
and Urinal
Flushing

SIZE: 4" HIGH x 8" WIDE


COLORS:
BACKGROUND: WHITE
LETTERS: PANTONE 522 PURPLE
CIRCLE-SLASH: DARK RED OVER WATER GLASS
WATER GLASS: PANTONE 522 PURPLE
V4" WIDE BORDER: PANTONE 522 PURPLE
HOLES: W" AT CORNERS

RECYCLED WATER SIGN FOR TOILET & URINAL FLUSHING

SHEET 4 OF 4

REVISION BY APPROVED DATE RECOMMENDED BY THE Ct1Y OF SAN DIEGO


STANDARDS COMMITTEE
CllY OF SAN DIEGO - STANDARD DRAWING
ORIGINAL KA • NAGELVOOR OV12
oil~ 1/31/2012
COORDINATOR R.C.E. 65271 DATE

RECYCLED WATER SIGNS DRAWING


NUMBER
SDRW-108
FINISHED GROUND
SURFACE
RECYCLE WATER TAG

PEA GRAVEL
6" DEPTH

UN MORTARED
STANDARD BRICKS
(4PL TYP)

PVC PIPELINE

NOTES:
1. RECYCLE WATER IRRIGATION VALVE BOX COVER
SHALL BE COLOR CODED PANTONE #522

2. TEFLON SHALL BE USED ON THREADED CONNECTIONS

REVISION BY APPROVED DATE RECOMMENDED BY THE Ct1Y OF SAN DIEGO


STANDARDS COMMITTEE
CllY OF SAN DIEGO - STANDARD DRAWING
OV12
oil~ 1/31/2012
COORDINATOR R.C.E. 65271 DATE
SIGN I TAG FOR RECYCLED WATER
DRAWING
IRRIGATION REMOTE CONTROL VALVE NUMBER
SDRW-109
VALVE BOX COVER

ISOLATION VALVE--""
(3" OR SMALLER)

0
coo oo0 0 °
co 0
C) 0 0
\)0 0
0
0 0
00 C) .oo
'tJO
a. ~0 0 0~ 0 C) 0 0 00 0
0 1:)8 00.... 0 0
0 ~\J 0
"'""' C) 0
"""' 0 0
~ 8
0 Q Q"O OC)Q
C) C) " Cl

NOTE:
RECYCLE WATER IRRIGATION VALVE BOX COVER

REVISION BY APPROVED DAlE RECOMMENDED BY THE CI1Y OF SAN DIEGO


STANDARDS COMMITTEE
CllY OF SAN DIEGO - STANDARD DRAWING
ORIGINAL KA • NAGELVOOR OV12
oil~ 1/31/2012
COORDINATOR R.C.E. 65271 DAlE
SIGN I TAG FOR RECYCLED
DRAWING
WATER IRRIGATION VALVE NUMBER
SDRW-110
RECYCLED WA TER;C:\
DO NOT DRINK \!I'
NO TOME El AGUA

RECYCLED
WATER TAG

IDENTIFY WATER
USAGE DEVICE

NOTE:
ALL RECYCLED METERS, AIFWACUUM REUEF VALVES, VALVES, PRESSURE REDUCING VALVES,
PUMPS, PUMP CONTROL VALVES, ETC., SHALL BE TAGGED OR LABELED INDICATING THAT THE
DEVICES ARE ON RECYCLED WATER SYSTEM AND COLOR CODED PANTONE #522.
12" MINIMUM CLEARANCE BETWEEN GROUND AND WATER CONTROL DEVICES.

REVISION BY APPROVED DAlE RECOMMENDED BY THE CI1Y OF SAN DIEGO


STANDARDS COMMITTEE
CllY OF SAN DIEGO - STANDARD DRAWING
ORIGINAL OV12
oil~ 1/31/2012
COORDINATOR R.C.E. 65271 DAlE
SIGN I TAG FOR IDENTIFICATION OF
DRAWING
RECYCLED WATER CONTROL DEVICES NUMBER
SDRW-111
VALVE BOX VALVE BOX

r
NAME PLATE NAME PLATE
(PURPLE PANTONE (PURPLE PANTONE
#522 TAG) #522 TAG)

l
SD CITY RECYCLED
DO NOT DRINK-NO TOMAR
I
l
I
SD CITY RECYCLED
DO NOT DRINK-NO TOt.4AR
I J

NOTE:
ALL RECYCLED WATER IRRIGATION BOX COVERS AND LIDS SHALL BE
COLOR CODED PANTONE #522

REVISION BY APPROVED DATE RECOMMENDED BY THE CITY OF SAN DIEGO


STANDARDS COMMITTEE
CITY OF SAN DIEGO -STANDARD DRAWING
~
ORIGINAL KA ~- NAGELVOORT OV12
612312014
UPDATE KA ~- NAGELVOORT 09113
COORDINATOR R.C.E. 56523 DATE
SIGN I TAG FOR RECYCLED WATER
DRAWING
IRRIGATION BOX COVER I LID NUMBER
SDRW-112
CONTROLLER BOX PURPLE
(PANTONE #522) MARKER
DECAL-SHOWN AFFIXED TO
BOX EXTERIOR; PREFERABLY,
AFFIX TO INTERIOR OF BOX

~I ATTENTION
Controller Unit for
Recycled Water

ATENCION
I Unidod Con trolodoro
del Aguo Recuperodo
I~
If
I G)
IL
10
'---- I
,_
0 r;:r:Q
,---

NOTES:
RECYCLED WATER IRRIGATION SYSTEM CONTROLLER BOX SHALL BE
COLOR CODED PANTONE #522

REVISION BY APPROVED DAlE RECOMMENDED BY THE CI1Y OF SAN DIEGO


STANDARDS COMMITTEE
CllY OF SAN DIEGO - STANDARD DRAWING
ORIGINAL KA ~. NAGELVOOR1 OV12
oil~ 1/31/2012
COORDINATOR R.C.E. 65271 DAlE
SIGN I TAG FOR RECYCLED WATER
DRAWING
AUTOMATIC IRRIGATION CONTROLLER NUMBER
SDRW-113
0 0

RECYCLED WATER
DO NOT DRINK

AVISO,
AGUA IMPURA
NO TOMAR

FRONT BACK

SAMPLE WARINING TAG. BACKGROUND PURPLE (PANTONE #522)


WITH BLACK LETTERING.

REVISION BY APPROVED DATE RECOMMENDED BY THE Ct1Y OF SAN DIEGO


STANDARDS COMMITTEE
CllY OF SAN DIEGO - STANDARD DRAWING
ORIGINAL OV12
oil~ 1/31/2012
COORDINATOR R.C.E. 65271 DATE

RECYCLED WATER TAG DRAWING


NUMBER
SDRW-114
1" QUICK COUPLING VALVE (NELSON)
#7645 OR RAINBIRD #44 NP WITH
ACME THREAD KEY.

6" MIN
.. -M-AX----+---
f--------='-- EDGE OF WALK,
18 FACE OF CURB,
FENCE OR
MOW BAND

GROUND COVER LEITER

PVC SCHEDULE 80 NIPPLE 1!1o+>---- PEA GRAVEL, 6" DEPTH


(LENGTH AS REQUIRED) F...L.,_,_.__ UNMORTARED STANDARD BRICKS
PVC SCHEDULE ---~=~.ri=4!-l (4 PL lYP)
40 STREET ELL ---~~~~======;;--#4 REBAR, 24" LONG

PVC SCHEDULE PVC PIPELINE


40 90 ELL (SXT)
OR TEE (SXSXT)
PVC SCHEDULE
PVC SCHEDULE 80 NIPPLE,
40 STREET ELL 6" LONG

NOTE:

1. NEW CONSTRUCTION -ALL QUICK COUPLING VALVES SHALL HAVE NON-POTABLE


LOCKING PURPLE THERMOPLASTIC RUBBER COVERS.

2. RETROFITS - REPLACE ALL EXISTING QUICK COUPLING VALVES WITH NON-POTABLE


LOCKING PURPLE THERMOPLASTIC RUBBER COVERS.

3. TEFLON SHALL BE USED ON THREADED CONNECTIONS.

TYPE A (#4 ROD)

SHEET 1 OF 2

REVISION BY APPROVED DATE RECOMMENDED BY THE Ct1Y OF SAN DIEGO


STANDARDS COMMITTEE
CllY OF SAN DIEGO - STANDARD DRAWING
ORIGINAL OV12
oil~ 1/31/2012
COORDINATOR R.C.E. 65271 DATE
RECYCLED WATER
QUICK COUPLING VALVE DRAWING
SDRW-115
NUMBER
6' MIN-18' MAX

FINISH RECYCLED
WATER TAG

UNMORTARED BRICK
SUPPORT (2 MIN)
PEA GRAVEL
SUMP 6" DEPTH
PVC ELL OR TEE
ON MAINLINE PIPE --------

......_____ _ _ ONE CUBIC FOOT


CONCRETE THRUST
BLOCK
PVC IRRIGATION
MAINLINE PIPE
NOTE:
PURPLE COLOR
QUICK COUPLING VALVE SHALL
BE OF A TYPE APPROVED FOR
RECLAIMED WATER USE, AND
PVC ELL OR TEE COLOR DESIGNATED AS SUCH
ON MAINLINE PIPE WITH PURPLE-COLORED LID.

MAINLINE CONNECTION-PLAN

G)-1" QUICK COUPLING VALVE @-UNDISTURBED OR


WITH PURPLE- COLORED 90% COMPACTED
LID (SEE LEGEND AND SUBGRADE
SPECIFICATIONS)
(J)- RED BRASS ELL
@- FLUSH IN TURF AREAS,
2" IN SHRUB AND @- RED BRASS NIPPLE,
GROUND COVER AREAS. 8" LENGTH MIN

@-RED BRASS NIPPLE, @- RED BRASS STREET


6" LENGTH MIN ELL

@-RED BRASS @)- PVC ELL OR TEE ON


COUPLING, EXTEND MAINLINE PIPE
~" ABOVE TOP OF
@-SCHEDULE 80 PVC
CONCRETE THRUST NIPPLE, 4" LENGTH
BLOCK MIN
@-RED BRASS NIPPLE,
LENGTH AS REQUIRED

TYPE B (KICK BLOCK)


SHEET 2 OF 2

REVISION BY APPROVED DATE RECOMMENDED BY THE Ct1Y OF SAN DIEGO


STANDARDS COMMITTEE
CllY OF SAN DIEGO - STANDARD DRAWING
ORIGINAL OV12
oil~ 1/31/2012
COORDINATOR R.C.E. 65271 DATE
RECYCLED WATER
DRAWING
QUICK COUPLING VALVE SDRW-115
NUMBER
BRICK SUPPORTS ON--~
COMPACTED UNDISTURBED '\_
SUBGRADE (MIN OF FOUR ~
PER BOX)

PVC SCHEDULE-I--+-~---.~!~-~ ~E~r:AJ


40 SOLVENT
WELD FITIINGS ~ /
r -PURPLE COLOR
VALVE BOX AND
®'~0. r-MAIN LID
/ LINE
y r q

lo~mA
EA GRAVEL SUMP
N V2 CU F1)

n . r
1.-.J L-

REVISION BY APPROVED DAlE RECOMMENDED BY THE CI1Y OF SAN DIEGO


STANDARDS COMMITTEE
CllY OF SAN DIEGO - STANDARD DRAWING
ORIGINAL KA ~. NAGELVOOR OV12
oil~ 1/31/2012
COORDINATOR R.C.E. 65271 DAlE
CROSS CONNECTION CONTROL
TEST STATION DRAWING
SDRW-116
NUMBER
~
I I L_EX POTABLE WATER SUPPLY
I CJ, I
I o~ l I
I~~~ I EX BUILDING EXTERIOR WALL

I
--r------
1
I

NOTES:

G)- TEE SIZE TO MATCH EXISTING PIPE


@-REDUCER TO 2" DIAMETER PIPE, IF TEE IS LARGER THAN 2" DIAMETER
INCREASER TO 2" DIAMETER PIPE, IF TEE IS SMALLER THAN 2" DIAMETER
@-2" BRASS BALL VALVE
@-1 V2" FIRE HOSE CONNECTION, MIN. 4" HORIZ.
CLEARANCE 6" TO 14" ABOVE EXISTING GROUND
@--1 V2" CAP
@- MISCELLANEOUS NIPPLES AS REQUIRED
<1>- INSTALL BRASS BALL VALVE SIZE TO MATCH EXIST PIPE
@-INSTALL UNION SIZE TO MATCH EXISTING PIPE

REVISION BY APPROVED DATE RECOMMENDED BY THE Ct1Y OF SAN DIEGO


STANDARDS COMMITTEE
CllY OF SAN DIEGO - STANDARD DRAWING
ORIGINAL KA A. OSKOUI OV12
oil~ 1/31/2012
COORDINATOR R.C.E. 65271 DATE
THRESHOLD
DRAWING
BYPASS PIPING SDRW-120
NUMBER
<{_ OF METER BOX &
CURB MARKER

GRASS OR
DIRT AREA~ ~RIGHT OF WAY LINE

RW METER
BOX
5'
(TYP)

-- I
I

~
<-s-...--+-- CONCRETE
SIDEWALK
5' RECVCLED
(TYP) , WATER
I SERVICE

I
1-------------+6'_'____~3~"--~l--------------------r/~~FACE OF
l 1 A /
I--------------~------~1.~~·----------------------L-~
CURB

2'
, ~I \ ,
~- ~~~~~
~~~4~~~~~~~~
~ W~&

das CURB MARKER


NO. 2.5 NRS-R ON TOP
OF CONCRETE CURB
II'<f.. OF RW
SERVICE &
CURB MARKER
GUTTER PER
SDG- 151

REVISION BY APPROVED DATE RECOMMENDED BY THE Ct1Y OF SAN DIEGO


STANDARDS COMMITTEE
CllY OF SAN DIEGO - STANDARD DRAWING
ORIGINAL KA U.NAGELVOOR1 OV12
oil~ 1/31/2012
COORDINATOR R.C.E. 65271 DATE
TYPICAL CURB MARKER
DRAWING
INSTALLATION LOCATION SDRW-121
NUMBER
CHAPTER 9
SEW ER
SYSTEM
4" 6" 8" 10" 12" 15" 18" 21" 24" 27"

3'
5'

10' 10'
(A)

SPECIAL DESIGN a:
LlJ

15' 15'
60
LL
(B) 0
I
I-
20' 20' D...
LlJ
0

25' 25'

SPECIAL DESIGN

30' 30'

4" 6" 8" 10" 12" 15" 18" 21" 24" 27"

DIAMETER OF PIPE

(A) SDR - 35 OR PIPE STIFFNESS OF 46 PSI PER ASTM D2412

(B) SDR - 35 IF SOIL REPORT SUBSTANTIATES THE ASSUMPTIONS IN NOTE 1, OTHERWISE USE SDR-26, IN LIEU
OF THE SOIL REPORT

NOTE:

1. THIS STANDARD DRAWING SHALL BE USED ONLY WHERE EXISTING SOIL CONDITIONS ARE STABLE. STABLE SOIL IS
DEFINED AS STANDARD PENETRATION TEST BLOW COUNT EQUAL TO OR GREATER THAN 13 BLOWS PER FOOT OR
SHEAR STRENGTH GREATER THAN 750 PSF. OBTAINED FROM UNCONFINED COMPRESSION TEST.
110 750
2 STANDARD DESIGN ASSUMPTION: Kb =· · DL =1.0, E' = psi
. We =PRISM LOAD @ W=125 LBH 3
3. SEE PIPE BEDDING AND TRENCH BACKFILL DRAWING.

4. INSTALLATIONS IN GROUND WATER SHALL REQUIRE A SPECIAL DESIGN.

5. DESIGN REF.: ASCE MANUALS AND REPORTS ON ENGINEERING PRACTICE - NO. 60 "GRAVITY SANITARY
SEWER DESIGN AND CONSTRUCTION."

REVISION BY APPROVED DATE RECOMMENDED BY THE CITY OF SAN DIEGO


STANDARDS COMMITIEE
CITY OF SAN DIEGO - STANDARD DRAWING
~
ORIGINAL J. MUELLER 6-15-£3
11.3014
UPDATED J. CASEY 6-26-1!6
COORDINATOR R.C.E. 56523 DATE
UPDATED J. CASEY 11-8--68 PERMISSIBLE DEPTH OF COVER FOR
DRAWING
UPDATED KA OV12 PVC PIPE NUMBER SDS-101
UPDATED KA OV14
CLEANOUT PLUG (ABS), THREADED
'L
PUBLIC PRIVATE

PAVED ALLEY OR
OTHER TRAVELLED WAY

HAND PLACED
BACKFILL @ 95%
COMPACTION

CONCRETE BRICK (4 PL TYP)


BACKFILL TO TOP OF
45° BEND WITH 3-8"
MAXIMUM AGGREGATE
STD 45° BEND

STD WYE BRANCH


PIPE BEDDING WITH
SECTION A- A 3-8" MAXIMUM AGGREGATE
SEWER MAIN

A~
S SEWER LATERAL CLEANOUT
IN STANDARD CLEANOUT BOX

EDGE OF
SIDEWALK
OR ALLEY

CURB
...... .. ........
·
GUTTER

METAL TAPE /SEWER MAIN


_L ____ _ _____ _ _

NOTES:

1. RISER AND CLEANOUT PLUG SHALL BE SAME DIAMETER AS SEWER LATERAL.

2. CLEANOUT SHALL BE PLACED INSIDE A STANDARD CLEANOUT BOX WITH CAST


IRON LID MARKED "CLEANOUT' OR EQUAL.

3. INSTALL METAL TAPE ON TOP OF NON- METALLIC SEWER PIPE

4. LATERALS ARE NOT ALLOWED IN DRIVEWAYS.

REVISION BY APPROVED DATE RECOMMENDED BY THE Ct1Y OF SAN DIEGO


STANDARDS COMMITTEE
CITY OF SAN DIEGO - STANDARD DRAWING
oil~
ORJGINAL SS A. OSKOUI 1W3
1/31/2012
OV12
SEWER LATERAL CLEANOUT COORDINATOR R.C.E. 65271 DATE

(IN PAVED ALLEY, SIDEWALK, OR DRAWING


OTHER AREAS SUBJECT TO TRAFFIC) NUMBER
SDS-102
APPROVED MIN 6" ID CONCRETE
ROUND ENCLOSURE WITH CONCRETE
COVER MARKED "SEWER"-----.._
CITY PRIVATELY

MAINTAINED MAINTAINED
~---MATCH THE
EXISITNG SURFACE

CLEANOUT PLUG
(ABS), THREADED

~ 5" THICK LAYER OF 318"


BACKFILL TO TOP OF MAXIMUM AGGREGATE
45° BEND WITH :W"
STD 45' BEND
MAXIMUM AGGREGATE

TO PROPERTY

PIPE BEDDING WITH


:W" MAXIMUM AGGREGATE
EX. SEWER MAIN
SECTION A-A
CONNECT TO
EX. SEWER LATERAL

SEWER LA¢E~
CLEANOUT S

PARKWAY EX. SEWER LATERAL

CURB EDGE OF
SIDEWALK

f
\--
GUTIER _____}/

~-:.--1
\__EX. SEWER MAIN
PLAN

NOTES:

1. RISER AND CLEANOUT PLUG SHALL BE SAME DIAMETER AS SEWER LATERAL.

2. CLEANOUT SHALL BE LOCATED WITHIN CITY RIGHT OF WAY, BEHIND THE SIDEWALK.

REVISION BY APPROVED DATE RECOMMENDED BY THE CITY OF SAN DIEGO


STANDARDS COMMITIEE
CITY OF SAN DIEGO - STANDARD DRAWING

C~E.56523
DETAIL SS A. OSKOUI 1203
7/2V15
DATE

SEWER LATERAL CLEAN OUT DRAWING


NUMBER
SDS-103
RI
GHT-OF-W AY PROPERTY LI
NE
CLEANOUT TO BE LOCATED ON
STREET SI
DE OF RI
GHT-OF-W AY OR
PROPERTY LI
NE AND PER SDS-103

CLEANOUT
CLEANOUT PER UNIFORM
PLUMBI
NG CODE

A A
SEWER MAIN LINE

SEW ER LATERAL
C

C
C
BLDG/
RESI
DENCE
CURB & GUTTER

C
SIDEWALK

BACKW ATER
PLAN VI
EW DEVI
CE

RI
GHT-OF-W AY PROPERTY LI
NE

C 8" C

12" MAX 1 C C 1
12" C C
12" 13" X 24" X 12" PER APPROVED MATERI
AL
2 LI
ST RECTANGULAR STRUCTURAL FOAM
4
4" C
C C
C
4" POLYETHYLENE BOX W I
TH STRUCTURAL
RI
BS AND DROP I
N COVER.
SEE NOTE 1
PAVEMENT SURFACE
4
C

C
C

1"
C

UNMORTARED 3"
C
C
C

BRI
CK FOUNDATI
ON
C

C
C

VARI
ES TO I
NVERT
5 OF LATERAL
PIPE BEDDI
NG C
C

C
3
8" MAX NEW OR EX SEW ER
AGGREGATE C
LATERAL
C FROM BLDG/RESI
DENCE
FLOW
C

C
C

C
C
C

SEW ER LATERAL PER SDS-105 C PI


PE COUPLI
NG
12" C

10 1/
2"
C C

STD.W YE BRANCH REMOVABLE UNI


-DIRECTI
ONAL
FLOW FLAPPER W I
TH
3
ELASTOMERI
C GASKET
SECTI
ON A-A
NOTES:

1 W HEN BACKW ATER DEVI


CE I
S I
NSTALLED I
N THE DRI
VEW AY,SEE SHEET 2

2 I
NSTALL VALVE BOX SO THAT I
TIS FLUSH W I
TH PAVEMENT SURFACE
OR 1" ABOVE FI
NISH GRADE (
SOI
L SURFACE)
.

3 PVC BACKW ATER DEVI


CE AND ATTACHED PARTS SHALL BE PER THE
CALI
FORNIA PLUMBING CODE (CPC).

4 CLEANOUT PLUG (
ABS)THREADED.

5 STANDARD 45 BEND.

6 THE BACKW ATER DEVI


CE SHALL BE LOCATED AS CLOSE TO THE STRUCTURE
AS REASONABLY POSSI
BLE TO MI
NIMI
ZE THE DEPTH OF THE BACKW ATER DEVI
CE. SHEET 1OF 2

RECOMMENDED BY THE CI
TY OF SAN DI
EGO
REVI
SION BY APPROVED DATE
STANDARDS COMMITTEE
CI
TY OF SAN DI
EGO - STANDARD DRAW I
NG
DETAI
L CS A.OSKOUI 12/
03

UPDATED KA J.NAGELVOORT
2/
25/
16
01/
12
COORDI
NATOR R.
C.E.56523 DATE
UPDATED BB J.NAGELVOORT 07/
14
4" BACKW ATER DEVI
CE
DRAW I
NG
UPDATED HM J.NAGELVOORT 02/
16
SDS-
104
NUMBER
1 LIFT PI
N
R1 2" B

C
C (2X)
1
1 2"

C
C
SEWER 1
C 17 2"

C
C
A A NON SKID C
L
C
SURFACE 2'
' C

POLYMER CONCRETE COVER

C 1
30 2" C

C
2"

C
B 1
C 32 4" C
TOP VI
EW
3034"
C C
C 1 C
29 4"
C 1
19 4"
C 3
17 4"
C 1
16 4"
CL
C

12" CL
3 C 3
1 4" C 26 4" C

C 1
30 4" C
HEX HEAD
3 3
1 4" C
C 13 4"C BOLTBOW N SECTI
ON B-B
C 1 (
2X)
C C
17 4" LI
FT PI
N

SECTI
ON A-A
C

POLYMER CONCRETE COVER


C

C
NON SKID
SURFACE
FLOATI
NG
UNI
STRUT
BOLT
CHANNEL
RPM BOX
C

C
DETAI
L -A
C

DETAI
L -A

CONCRETE BOX C

NOTE:

1. THE BOX & COVER I


S 10K LOAD RATED.
SHEET 2 OF 2

RECOMMENDED BY THE CI
TY OF SAN DI
EGO
REVI
SION BY APPROVED DATE
STANDARDS COMMITTEE
CI
TY OF SAN DI
EGO - STANDARD DRAW I
NG
DETAI
L SS A.OSKOUI 12/
03

2/
25/
16
UPDATED KA J.NAGELVOORT 01/
12
COORDI
NATOR R.
C.E.56523 DATE
UPDATED BB J.NAGELVOORT 07/
14
4" BACKW ATER DEVI
CE
UPDATED HM J.NAGELVOORT DRAW I
NG
02/
16
SDS-
104
NUMBER
VARIABLE
VARIABLE

I - t - - CURB LINE
STANDARD
. PLUG

d============l
PROPERlY LIN~
118 BEND I

'---STANDARD WYE OR TEE

WIRE #12 OR HEAVIER.


LETTER "S" STAMPED OR EXTEND 2' TO 3' ABOVE
CHISELED IN FACE OF CURB GROUND AT TIME OF BACKFILL
NOT LESS THAN 1 V2" HIGH
6" METAL TAPE AT AND 3116" DEEP
TOP OF PIPE ZONE
4" BELOW PAVEMENT
SECTION
OVERLAP TAPE

PIPE BEDDING OF 3>8"


MAXIMUM AGGREGATE
ELEVATION

NOTES
1. IN NO CASE SHALL A LATERAL CONNECT TO THE SEWER MAIN DIRECTLY
ON TOP OF THE PIPE.

2. ALL JOINTS ON SEWER LATERAL PIPE SHALL BE COMPRESSION lYPE OR


APPROVED SOLVENT WELD.

3. LATERAL SHALL EXTEND TO PROPERlY LINE UNLESS SHOWN OTHERWISE


ON PLANS

4. DO NOT TAP HOLE AND INSERT LATERAL PIPE DIRECTLY INTO MAIN. ALL
CONNECTIONS SHALL BE MADE USING A SADDLE OR WYE CUT IN.

5. SEWER LATERAL SHALL HAVE 6" METAL TAPE WITH GREEN LETTERING
INDICATING "SEWER" INSTALLED ABOVE THE ALIGNMENT OF THE NON-METALLIC
PIPE FROM SEWER MAIN TO PROPERlY LINE.

DETAIL SHOWING THE MANNER OF


CONNECTING OPPOSITE LATERALS
TO A SEWER MAIN. TWO CONNECTIONS LEGENDS ON PLANS
SHALL NOT BE MADE IN THE SAME
LENGHT OF PIPE. !-----4 --{?)
I I
REVISION BY APPROVED DATE RECOMMENDED BY THE CITY OF SAN DIEGO
STANDARDS COMMITIEE
CllY OF SAN DIEGO - STANDARD DRAWING
DETAIL JP A. OSKOUI 1ao3

UPDATED KA J. NAGELVOO OV12


,,.,,
COORDINATOR R.C.E. DATE
HOUSE CONNECTION
DRAWING
(SEWER LATERAL) NUMBER
SDS-105
TRENCH RESURFACING
PER SDG-107 AND
SDG-108
MANHOLE FRAME AND
ROAD SURFACE COVER SEE M-3.

C
C

C
18" MAX
C
3'
-0"
C

GRADE RI
NG
OR RI
SER

"A" SEE NOTE 6


C
SLOPE 1" PER

3'-0"
FOOT

C C
C 5'
-0" 8"
C
SHAFT C
C

C
VARIES
C

C
B

C
CHANNEL SHALL BE
VERTI
CAL ABOVE
C

C
C

SPRI
NG LI
NE 3/
4INSI
DE DI
A OF PI
PE
C

LEVEL SECTI
ON B-B
4" MIN
C

C
C
10" MIN

C
B LEVEL

SECTI
ON A-A

NOTES:

1. MANHOLE FRAME AND ALL JOI


NTS SHALL BE SET I
N CLASS "C" MORTAR.

2. ALL PRECAST COMPONENTS SHALL BE MANUFACTURED I


N ACCORDANCE W I
TH ASTM C478.

3. VERTI
CAL W ALL OF CONE SHALL BE ON THE UPSTREAM SI
DE OF THE MANHOLE.

4. CONCRETE BASE SHALL BE 560-C-3250.

5. APPROVED W ATER STOP REQUI


RED FOR PLASTI
C PI
PE CONNECTORS.

6. PRECAST SECTI
ONS SHALL BE USED W I
THI
N DI
MENSI
ON "A" AS REQUI
RED,I
N ORDER OF
PREFERENCE LI
STED:

A) CONE (
NOTCHED FOR PI
PE I
F DI
MENSI
ON "A" I
S LESS THAN 3'
.)

B) 6" TO 18" OF 3'DI


AMETER GRADE RI
NGS AND/
OR RI
SERS.

C) 5'DI
AMETER SHAFT VARI
ABLE HEI
GHT.

7. FLEXI
BLE PI
PE JOINTS SHALL BE REQUI
RED W I
THI
N 12" OF I
NSI
DE FACE OF MANHOLE,EXCEPT
FOR PLASTI
C PIPE.

8. ALL PATCHI
NG W I
THI
N MANHOLE BASE SHALL BE EPOXY MORTAR.

9. PRI
OR APPROVAL OF PRECAST BASE I
S REQUI
RED BY THE ENGI
NEER.

10.MANHOLES SERVI
NG 18" DI
AMETER PIPE AND LARGER SHALL USE PRECAST RI
SERS LI
NED W ITH W HI
TE
PVC SHEETS I
MBEDDED W ITH LOCKI
NG EXTENSIONS TO THE CONCRETE W ALL.THE BASE AND ALL
REMAINI
NG EXPOSED CONCRETE SHALL BE COATED W ITH AN APPROVED POLYURETHANE COATI NG.
LEGEND ON PLANS

RECOMMENDED BY THE CI
TY OF SAN DI
EGO
REVI
SION BY APPROVED DATE
STANDARDS COMMITTEE
CI
TY OF SAN DI
EGO - STANDARD DRAW I
NG
DETAI
L SS A.OSKOUI 12/
03

UPDATE
2/
25/
16
KA J.NAGELVOORT 01/
12
COORDI
NATOR R.
C.E.56523 DATE
UPDATE GB J.NAGELVOORT 07/
15
M ANHOLE 5'X 3'DI
AM ETER DRAW I
NG
UPDATE HM J.NAGELVOORT 02/
16
SDS-
106
NUMBER
~
w
z
0
()

'""
CONCRETE
ENCASEMENT
OR BACKFILL
* EITHER CONCENTRIC OR
SECTION B-B ECCENTRIC CONE MAY BE USED

HALF SECTION SHALLOW MANHOLE

SLOPE 314 INSIDE


1" PER DIA OF PIPE
~oar

' .... I>

NOTES
1. ALL RISER JOINTS SHALL BE EPOXY MORTARED.
SECTION C-C
2. ALL PRECAST COMPONENTS SHALL BE MANUFACTURED IN ACCORDANCE
WITH ASTM C478.
TRENCH RESURFACING
PER SDG-107/SDG-108 MANHOLE FRAME 3. VERTICAL WALL OF CONE SHALL BE ON THE UPSTREAM SIDE OF THE
AND COVER M-3 MANHOLE.
ROAD
SURFACE
4. CONCRETE BASE SHALL BE 560-C-3250.

5. APPROVED WATER STOP REQUIRED FOR PLASTIC PIPE CONNECTIONS.

---~~~:. ]:::2:
1------3_'--0_" 6. PRECAST SECTIONS SHALL BE USED WITHIN DIMENSION "A" AS REQUIRED,
~··
~--------f·~~·:·
Co
~
(0
IN ORDER OF PREFERENCE LISTED:
.. 0w A) CONE (NOTCHED FOR PIPE IF DIMENSION "A" IS LESS THAN 3').
z
w
w B) 3" TO 18" OF 3' GRADE RINGS AND RISERS.
(/)

C) 4' DIAMETER SHAFT VARIABLE HEIGHT.

7. FLEXIBLE PIPE JOINTS SHALL BE REQUIRED WITHIN 12" OF INSIDE FACE


OF MANHOLE, EXCEPT FOR PLASTIC PIPE.

8. ALL PATCHING WITHIN MANHOLE BASE SHALL BE EPOXY MORTAR.

9. PRIOR APPROVAL OF PRECAST BASE IS REQUIRED BY THE ENGINEER.

LEGEND ON PLANS

SECTION A-A ----{)---- ·


REVISION BY APPROVED DATE RECOMMENDED BY THE CITY OF SAN DIEGO
STANDARDS COMMITTEE
CITY OF SAN DIEGO - STANDARD DRAWING

~
DETAIL JP A. OSKOUI 12-03

UPDATED KA . NAGELVOORT OV12 7/2V15


COOI1DiNAl"Of1:E. 56523 DATE
UPDATED . NAGELVOORT 07115 MANHOLE 4' X 3' DIAMETER
DRAWING
(FOR 15" MAXIMUM DIAMETER PIPE) NUMBER
SDS-107
WALL OF
WALL OF MANHOLE BASE
MANHOLE BASE FLEXIBLE
RUBBER GASKET STAINLESS STEEL
CAST INTO DO NOT GROUT KORBAND
MANHOLE NO
GROUT
FIELD
INSTALLED
INVERT

SEWER MAIN

PRECAST PRECAST
MANHOLE BASE MANHOLE BASE

PRECAST MANHOLE BASE 1YPE 'A' PRECAST MANHOLE BASE 1YPE 'B'

EXIST WALL
WALL OF
OF MH BASE
RUBBER 0-RING MH BASE RUBBER 0-RING
STRETCHED OVER STRETCHED OVER GROUT
SEWER PIPE SEWER PIPE SEE
NOTE1

FIELD
MANHOLE INSTALLED
INVERT INVERT

SEWER MAIN SEWER MAIN

EXISTING
MANHOLE BASE MANHOLE BASE

CAST IN PLACE MANHOLE BASE BREAKING INTO EXIST MANHOLE BASE

NOTES:
1) A RUBBER 0-RING OR A FLEXIBLE CONNECTOR (AS SHOWN IN PRECAST MANHOLE BASE
TYPE 'B') SHALL BE USED WHEN BREAKING INTO EXISTING MANHOLE
2) FOR MANHOLES REQUIRING COATING AND UNING, SEE SM-07

REVISION BY APPROVED DAlE RECOMMENDED BY THE Ct1Y OF SAN DIEGO


STANDARDS COMMITTEE
CITY OF SAN DIEGO - STANDARD DRAWING
ORIGINAl* KA . NAGELVOORT OV12
oil~ 1/31/2012
COORDINATOR R.C.E. 65271 DAlE

MANHOLE PIPE CONNECTORS DRAWING


NUMBER
SDS-108
. . - - - - - MANHOLE FRAME
AND COVER

BUND FLANGE OR MECHANICALLY


2 " RESTRAINTEND CAP WITH
TAMPER- PROOF BOLTS

__,--- STANDARD MANHOLE RISER

1 : r: .:
'------ 6" CONCRETE SLAB

,....---- FLANGE OR MECHANICAL


RESTRAIN COUPUNG

SAME SIZE AS MAIN

6" MIN

NEAT TRENCH
DOUBLE CLEANOUT TO BE
SYMMETRICAL ABOUT AXIS
1116 BEND - - - - - -- -

USE Dl WYE (BELL-SPIGOT-BELL)


OR PVC

47Q--C-2000 CONCRETE
6"
MIN

NOTES
SIMILAR POLYVINLY CHLORIDE COMPONENTS MAY BE USED IN ACCORDANCE WITH
ASTM STANDARD SPECIFICATION D2241 AND D3139.
2. CONCRETE SLAB SHALL BE 560-C--3250.
3. USE HEAW DUTY MANHOLE FRAME AND COVER, M- 1,
IN AREAS SUBJECT TO VEHICULAR TRAFFIC; USE LIGHT DUTY MANHOLE
FRAME AND COVER, M- 2, 1N ALL OTHER LOCATIONS.
4. MINIMUM PIPE PRESSURE CLASS 200. LEGEND ON PLANS

---o--
co
REVISION BY APPROVED DATE RECOMMENDED BY THE Ct1Y OF SAN DIEGO
STANDARDS COMMITTEE
CITY OF SAN DIEGO - STANDARD DRAWING
oil~
DETAIL JP A. OSKOUI 1W3
1/31/2012
UPDATED KA . NAGELVOOR 01112
COORDINATOR R.C.E. 65271 DATE

CLEANOUT - SEWER FORCE MAIN DRAWING


NUMBER
SDS-109
C
C

C
C

C
95%*
1'-0"
UPPER ZONE 3'

MAXIMUM LIMIT OF SLOPE


C

EXCAVATION ALLOWED
C
90%*
2'-0"
BACKFILL

C
C
C

C
MIDDLE ZONE
TRENCH DEPTH C TRENCH W I
DTH
C

90%*
C
C
C

C
C

C
PI
PE OD
6" MI
N -

MIN
1'
8" MAX
C
C
PIPE ZONE

C
BEDDING

4" TO
90%*

18" PI
PE
C
I
NVERT ELEVATI
ON
C

D
C BELL
C C

C
C
C
C
C

D/
4

C
C

4" MI
N TO 8" MAX
3/
8" MAX TYPE A BENEATH PI
PE OR
CRUSHED ROCK STANDARD I
NSTALLATI
ON 1'MI
N BENEATH BELL
W HI
CHEVER IS GREATER

C TRENCH W I
DTH C TRENCH W I
DTH
C C C
C

6" MI
N -
PI
PE OD PI
PE OD
8" MAX
MIN
MIN

1'

6" MI
N-
1'

C 4" TO 8" MAX


C
C

18" PI
PE
C

C 4" TO
C
BELL C
I
NVERT ELEVATI
ON 15" PI
PE

C C
C C SPRI
NGLI
NE C
D

C 3/
8" MAX
C
C 4" MIN TO 8" MAX C CRUSHED ROCK
C

BENEATH PIPE OR
C

1'MIN BENEATH BELL


C

W HICHEVER I
S GREATER D/
4
D/
4
C

C
C

3/
8" MAX 4" MIN TO 8" MAX
BELL
CRUSHED ROCK BENEATH PIPE OR
1'MIN BENEATH BELL
TYPE B TYPE C W HICHEVER I
S GREATER
ROCK TO SPRI
NGLI
NE ROCK ENVELOPE

NOTES
1. FOR TRENCH RESURFACI
NG I
N I
MPROVED STREETS,SEE STANDARD DRAW I
NGS SDG-107 AND SDG-108.

2. (
*)I
NDI
CATES MI
NIMUM RELATI
VE COMPACTI
ON.

3. MINI
MUM DEPTH OF COVER FROM THE TOP OF PI PE TO FI
NISH GRADE FOR PVC SDR 35 SEW ER MAI
N SHALL BE 5'
.
FOR SHALLOW ER DEPTH,SPECI
AL DESI
GN I
S REQUI
RED.SEE SDS-101.

4. SEE TYPE A I
NSTALLATI
ON FOR DETAI
LS NOT SHOW N FOR TYPES B AND C.

5. FOR PI
PE SI
ZE ENCASEMENT LARGER THAN 15",MAXI
MUM SI
DE W ALL CLEARANCE SHALL BE 12" OR AS SHOW N ON THE PLANS.

6. 6" METAL TAPE SHALL BE I


NSTALLED ABOVE PI
PE 4" BELOW TRENCH CAP AND 12" BELOW FI
NISH GRADE I
N UNI
MPROVED STREETS.

7. 1'SAND CUSHI
ON OR A 6" MI
NIMUM SAND CUSHI
ON W I
TH 1" NEOPRENE PAD SHALL BE PLACED FOR CROSSI
NGS UTI
LITI
ES W HEN VERTI
CAL
CLEARANCE I
S 1'OR LESS.THE NEOPRENE PAD SHALL BE PLACED ON THE MOST FRAGI
LE UTI
LITY.

RECOMMENDED BY THE CI
TY OF SAN DI
EGO
REVI
SION BY APPROVED DATE
STANDARDS COMMITTEE
CI
TY OF SAN DI
EGO - STANDARD DRAW I
NG
ORI
GINAL RA A.OSKOUI 12/
06

UPDATED KA J.NAGELVOORT 01/


12
2/
25/
16
COORDI
NATOR R.
C.E.56523 DATE
UPDATED HM J.NAGELVOORT 02/
16
PI
PE BEDDI
NG AND TRENCH BACKFI
LL
DRAW I
NG
FOR SEW ERS SDS-
110
NUMBER
1-
TRENCH WIDTH
-
,~

~~
~
1~11. ,11~1
_J
_J
u:
::0::::
0
<{
it
"0--

~
lll\11~
~ ' J
;tfiJTW
..::

* ~
CD 0
0)

I 6" MIN
I-

~
a_ 8" MAX
w
0
I 4" TO
0 18" PIPE
zw
a:
I-

_L 6 . 6 .
BELL
PIPE 00
INVERT ELEVATION

6 .

. .

470-C-2000 CONCRETE

CONCRETE BLOCK

SECTION

NOTES
1. ENCASE PIPE TO THE NEAREST FLEXIBLE JOINT. LEGEND ON PLANS
2. FOR TRENCH RESURFACING IN IMPROVED STREETS, SEE SDG-107 AND SDG-108.
3. CONCRETE ENCASEMENT SHALL BE USED FOR RIGID PIPE ONLY.
··~ · .. ............. . . . . ..... h'•'
4. 6' METAL TAPE SHALL BE INSTALLED ABOVE PIPE 4" BELOW PAVEMENT SECTION.
5. (*) INDICATES MINIMUM RELATIVE COMPLETION.

REVISION BY APPROVED DATE RECOMMENDED BY THE Ct1Y OF SAN DIEGO


STANDARDS COMMITTEE
CllY OF SAN DIEGO - STANDARD DRAWING
ORIGINAL

UPDATED
RA A. OSKOUI 1200

01112
oil~ 1/31/2012
COORDINATOR R.C.E. 65271 DATE

CONCRETE ENCASEMENT DRAWING


NUMBER
SDS-112
- TRENCH WIDTH
-
'~'~'o/

iC
<ft.
5>
1.{)
-
~
0> ..-

1~11. ,,,~'
_J
_J
u:::
~
0
~ <ft.
0
iC
~

' ~
!(11rrf

0>
I 6" MIN
1-
0.... 8" MAX
L.U
0
I 4" TO
0 18" PIPE
z
L.U
a:
1-

_L /::; . /::; .
BELL
PIPE OD
INVERT ELEVATION

/::; .

[}14 4" MIN

470-C-2000 CONCRETE
1
314" CRUSHED ROCK

SECTION

NOTE
1. FOR TRENCHING IN IMPROVED STREETS SEE SDG-107 AND SDG-108.
2. CONCRETE BACKFILL FOR PVC PIPE CAN BE USED ABOVE THE PIPE BEDDING ZONE. LEGEND ON PLANS
3. 6" METAL TAPE SHALL BE INSTALLED ABOVE PIPE 4' BELOW PAVEMENT SECTION.
4. (*)INDICATES MINIMUM RELATIVE COMPACTION.

REVISION BY APPROVED DAlE RECOMMENDED BY THE Ct1Y OF SAN DIEGO


STANDARDS COMMITTEE
CllY OF SAN DIEGO - STANDARD DRAWING
oil~
ORJGINAL RA A. OSKOUI 1200
1/31/2012
UPDATED OV12
COORDINATOR R.C.E. 65271 DAlE

CONCRETE BACKFILL DRAWING

NUMBER
SDS-113
BLOCKS TO BE LAID TIGHTLY AS
POSSIBLE TO DOWNSTREAM SIDE
OF NOTCH

PlAN

~:
~
8" X 8" X 16" CONCRETE
BLOCK, FILL CORES WITH I w
GROUT a
I

V2" EXPANSION
JOINT MATERIAL OR
JUTE AROUND PIPE

·.· :..

#9 WIRE LADDER TYPE


REINFORCEMENT IN
ALL HORIZONTAL JOINTS

FRONT ELEVATION SIDE ELEVATION

LEGEND ON PLANS
NOTE
PIPE PROTECTlON CAN ONLY BE USED ABOVE THE PIPE BEDDING ZONE FOR PVC PIPE.
---B------
1 -
REVISION BY APPROVED DAlE RECOMMENDED BY THE Ct1Y OF SAN DIEGO
STANDARDS COMMITTEE
CITY OF SAN DIEGO - STANDARD DRAWING
oil~
ORJGINAL RA A. OSKOUI 1200
1/31/2012
OV12
COORDINATOR R.C.E. 65271 DAlE

CONCRETE ANCHOR DRAWING


NUMBER
SDS-114
BLOCKS TO BE LAID TIGHTLY AS
POSSIBLE TO DOWNSTREAM SIDE
OF NOTCH
PLAN

8" X 8" X 16" CONCRETE


BLOCK, FILL CORES WITH
GROUT

~
w
a
I
0
zw
V2" EXPANSION
JOINT MATERIAL OR g:
JUTE AROUND PIPE

FRONT ELEVATION SIDE ELEVATION

LEGEND ON PLANS

---8----
i -
REVISION BY APPROVED DATE RECOMMENDED BY THE Ct1Y OF SAN DIEGO
STANDARDS COMMITTEE
CllY OF SAN DIEGO - STANDARD DRAWING
oil~
ORJGINAL RA A. OSKOUI 1200
1/31/2012
UPDATED KA • NAGELVOOR OV12
COORDINATOR R.C.E. 65271 DATE

CUTOFF WALL DRAWING


NUMBER
SDS-115
TRENCH WIDTH

:@II
,!IF

6" MIN
OUTSIDE DIAMETER
OF EXISTING PIPE

[)I4 6" MIN

[)I2

470-C-2000
CONCRETE
INVERT - EXISTING SEWER MAIN

SECTION

NOTES:

1. FOR EXISTING PVC PIPE, IT SHALL BE COVERED WITH TAR PAPER,


POLYURETHANE BAGGIE OR RUBBER MAT PRIOR TO POURING CONCRETE.

2. 6" METAL TAPE SHALL BE INSTALLED ABOVE PIPE 4"


BELOW PAVEMENT SECTION.

3. (*) INDICATES MINIMUM RELATIVE COMPACTION

REVISION BY APPROVED DATE RECOMMENDED BY THE CITY OF SAN DIEGO

ORIGINAL RA A. OSKOUI 1W6


CITY OF SAN DIEGO - STANDARD DRAWING r/J. . ~/:D:/~ .COMMITIEE
~ ~ 1/31/2012
UPDATE KA. NAGELVOOR OV12
COORDINATOR R.C.E. 65271 DATE
CONCRETE PROTECTION
DRAWING
FOR EXISTING SEWER PIPE NUMBER
SOS-116
TRENCH WIDTH

56o-G-3250
CONCRETE

r
EXISTING UNDERCUT
SEWER PIPE

~~~~~~~~~~~~~titi~~~~~

#4@ 18" oc

SOIL
2'MIN
SEE NOTE

PIPE TO BE INSTALLED
TYPICAL SECTION
OUTSIDE DIAMETER
OF PIPE / #5 BARS REQUIRED WHEN
CROSSING WATERLINE ONLY
#5 BARS REQUIRED WHEN -;"\_ .

CROSSING WATERLINE ONLY \~ •• 3" 3" ··~ I


3. ::;:t~rr======f1a=~3" 6"

#4@
oc
=r- OUTSIDE
DIAMETER
OF PIPE

3"
#5 BAR
#5 BAR
SECTION A-A

NOTES

1. FOR WATER LINE CONSTRUCTION. ENCASEMENT SHALL EXTEND TO FIRST JOINT BEYOND 2' AT
BOTH SIDES OF TRENCH OR TO A DISTANCE OF 4', WHICHEVER IS lESS.
lEGEND ON PLANS
2. WHERE CONNECTING TO FLEXIBLE PIPE, JOIN USING TWO COUPLINGS WITH A SHORT PIPE SPOOL (TYPICAL).

3. NO ENCASEMENT IS REQUIRED WHERE THE TRENCH WIDTH IS 24" OR lESS.

4. FOR EXISTING PVC PIPE, IT SHALL BE COVERED WITH TAR PAPER, POLYURETHANE BAGGIE OR RUBBER MAT
PRIOR TO POURING CONCRETE.

REVISION BY APPROVED DATE RECOMMENDED BY THE Ct1Y OF SAN DIEGO


STANDARDS COMMITTEE
CITY OF SAN DIEGO - STANDARD DRAWING
oil~
ORJGINAL RA A. OSKOUI 1200
1/31/2012
UPDATED KA . NAGELVOOR OV12
COORDINATOR R.C.E. 65271 DATE
CONCRETE SUPPORT
DRAWING
FOR UNDERCUT SEWER PIPE NUMBER
SDS-117
GROUND LINE
TRENCH WIDTH

CALDER COUPLING
NO INTERMEDIATE JOINTS
CALDER COUPLING EXISTING UNDERCUT
HOUSE CONNECTION

PVC SCH 80 PIPE


OR AN APPROVED ALTERNATE

w
0
zw
zcr:
UNDISTURBED SOIL
~LiS

J
<od

2'MIN
SEE NOTE

PROPOSED CONDUIT

SECTION

NOTE:

FOR WATER LINE CONSTRUCTION, PIPE REPAIR SHALL EXTEND TO


FIRST JOINT BEYOND 2' AT BOTH SIDES OF TRENCH OR TO A
DISTANCE OF 4', WHICHEVER IS LESS.

REVISION BY APPROVED DAlE RECOMMENDED BY THE Ct1Y OF SAN DIEGO


STANDARDS COMMITTEE
CllY OF SAN DIEGO - STANDARD DRAWING
ORIGINAL

UPDATED
RA A. OSKOUI

()11'12
oil~ 1/31/2012
COORDINATOR R.C.E. 65271 DAlE
HOUSE CONNECTION
DRAWING
SEWER REPAIR NUMBER
SDS-118
C
C

C
C

C
95%*
1'-0"
UPPER ZONE 3'

MAXIMUM LIMIT OF SLOPE


C

EXCAVATION ALLOWED
C
90%*
2'-0"
BACKFILL

C
C
C TRENCH W I
DTH
C C

C
MIDDLE ZONE
TRENCH DEPTH

90%*

C 12" MI
N
C
OVERLAP
C
C
C

C
C

PI
PE OD 6" MI
N - 8" MAX
12"
MIN

C C
C FI
LTER FABRI
C MI
RAFI
PIPE ZONE

140N OR EQUI
VALENT
C
BEDDING

90%*

4" TO 18" PI
PE

C I
NVERT ELEVATI
ON PER PLAN
C
D

C BELL
C

C C

C
C
C
C
C

D/
4

C 4" MI
N TO 8" MAX
BENEATH PI
PE OR
3/
8" ROCK ENCASEMENT
1'MI
N BENEATH BELL
W HI
CHEVER I
S GREATER

NOTES:

1. FOR TRENCH RESURFACI


NG I
N I
MPROVED STREETS SEE SDG-107 AND SDG-108.

2. (
*)I
NDI
CATES MI
NIMUM RELATI
VE COMPACTI
ON.

3. MI
NIMUM DEPTH OF COVER FROM THE TOP OF PI
PE TO FI
NISH GRADE FOR PVC SDR 35 SEW ER MAI
N SHALL BE
5'
. FOR SHALLOW ER DEPTH,SPECI
AL DESI
GN I
S REQUI
RED.SEE SDS-101.

4. I
NSTALL W ARNI
NG/
IDENTI
FICATI
ON TAPE PER SDM-105.

5. 1'SAND CUSHI
ON OR A 6" MI
N SAND CUSHI
ON W I
TH 1" NEOPRENE PAD SHALL BE PLACED FOR ALL CROSSI
NG
UTI
LITI
ES W HEN VERTI
CAL CLEARANCE I
S 1'OR LESS.THE NEOPRENE PAD SHALL BE PLACED ON THE MOST
FRAGILE UTI
LITY.

RECOMMENDED BY THE CI
TY OF SAN DI
EGO
REVI
SION BY APPROVED DATE
STANDARDS COMMITTEE
CI
TY OF SAN DI
EGO - STANDARD DRAW I
NG
ORI
GINAL KA J.NAGELVOORT 01/
12

2/
25/
16
UPDATED AR J.NAGELVOORT 10/
15
COORDI
NATOR R.
C.E.56523 DATE
UPDATED HM J.NAGELVOORT 02/
16
PI
PE BEDDI
NG AND TRENCH BACKFI
LL
DRAW I
NG
FOR SEW ERS I
N GROUNDW ATER SDS-
119
NUMBER
SEE NOTE 2

5"
C C
C
SLOPE 1:
12 RI
NG(
S)

LEVEL
W ATER TI
GHT SEAL
C

C
C

CHANNEL SHALL BE
VERTICAL ABOVE
C

SPRING LINE

C
C

C
C

CAST I
N PLACE
10" MI
N
LEVEL

6" OF 3/
4"
CRUSHED ROCK BASE

NOTES:

1. MANHOLE BASES FOR MAI


NS 18" AND LARGER SHALL BE COATED PER SM-07.

2. LOW EST POI


NT ON SHELF SHALL BE EVEN W I
TH TOP OF PI
PE.

3. CAST I
N PLACE MANHOLE BASES CAST W I
TH 560-C-3250 SHALL BE CURED A MI
NIMUM OF THREE
DAYS PRI
OR TO STACKI
NG MANHOLE. BASES CAST W I
TH 660-CW -4000 (
WITHOUT CALCI
UM CHLORI
DE
(
CC)
)OR W I
TH 560-C-3250 TREATED W I
TH A MI
NIMUM OF 2% CC SOLUTI
ON I
N ACCORDANCE W I
TH
201-1SHALL BE CURED A MI
NIMUM OF 24 HOURS. THESE CURI
NG REQUI
REMENTS APPLY TO
MANHOLES W I
TH A MAXIMUM HEI GHT OF 25'
. SHORTER CURING TIMES,DEEPER I
NSTALLATI
ONS,AND
ALTERNATE CONCRETE MIX DESI
GNS REQUIRE ENGINEER'S PRIOR APPROVAL.

4. CONCRETE SPECI
FIED BY ALTERNATE CLASS OR OTHERW I
SE CONTAI
NING FLY ASH I
S NOT ALLOW ED
FOR USE I
N CAST I
N PLACE MANHOLES.

5. CONCRETE MI
X DESI
GNS CONTAI
NING ACCELERATI
NG ADMI
XTURES OTHER THAN CC REQUI
RE A
BREAK HI
STORY AND ENGI
NEER'
S APPROVAL.

RECOMMENDED BY THE CI
TY OF SAN DI
EGO
REVI
SION BY APPROVED DATE
STANDARDS COMMITTEE
CI
TY OF SAN DI
EGO - STANDARD DRAW I
NG
ORI
GINAL* KA J.NAGELVOORT 01/
12

02/
16
2/
25/
16
UPDATED HM J.NAGELVOORT
COORDI
NATOR R.
C.E.56523 DATE

SEW ER M ANHOLE BASE DRAW I


NG
SDS-
120
NUMBER
12" Cl CLEANOUT BOX
COVER MARKED "SEWER"
CLEANOUT PLUG (ABS), THREADED

2" AC PAVEMENT
PAVED ALLEY OR
OTHER TRAVELLED WAY

~ BACKFILL @ 95%
COMPACTION

STANDARD CLEANOUT BOX


12"-PVC-C-900

CONCRETE RING

BACKFILL TO TOP OF
45° BEND WITH 313"
MAXIMUM AGGREGATE
STD 45° BEND

SEWER MAIN
~ STD 45° BEND
PIPE BEDDING WITH
313" MAXIMUM AGGREGATE

NOTES:
1. REFER TO AGENCY SPECIFICATIONS WHERE APPLICABLE.
2. CLEANOUTS TO BE INSTALLED AT THE END OF MAINS WHERE INDICATED ON THE PLANS.
3. CLEANOUT PIPE TO BE SAME SIZE AND MATERIAL AS SEWER (MAX DIA. 8")
4. BACKFILL TO TOP OF 45° BEND WITH 313" CRUSHED ROCK.
5. LATERIALS SHALL BE SELECTED FROM THE AGENCY'S APPROVED MATERIALS LIST. --0
LEGEND ON PLANS

REVISION BY APPROVED DATE RECOMMENDED BY THE CITY OF SAN DIEGO


STANDARDS COMMITTEE
CITY OF SAN DIEGO -STANDARD DRAWING

co~.56523
ORIGINAL BB J. NAGELVOOR 05115

UPDATED BB J. NAGELVOOR 07115


7/2V15
DATE

SEWER MAIN CLEANOUT DRAWING


NUMBER
SDS-121
2• /tC PAVEMENT

FINISH GRADE

• •It) •110
110 ..... .....

TYPE A TYPE B
MAINS FOR s• AND a• SEWER LAlERAL
CLEAN OUT

NOTES:
1) REFER TO AGENCY SPECIFICATIONS WHERE APPLICABLE
2) CLEANOUTS TO BE INSTALLED AT THE END OF UAINS WHERE INDICATED ON
THE PLANS
3) CLEAN OUT PIPE TO BE SAUE SIZE AND UATERIAL AS SEWER UAIN UP TO
8"
4) BACKFILL TO TOP OF 45" BEND WITH 3/4" CRUSHED ROCK
5) UATERIALS SHALL BE SELECTED FROU THE AGENCY'S APPROVED UATERIALS -----o
LIST LEGEND ON PLANS

ITEU ITEU
NO SIZE AND DESCRIPTION NO SIZE AND DESCRIPTION

<D 12" Cl CLEANOUT BOX COVER UARKED


'SEWER' AND AGENCY NAUE AS REQUIRED
45" ELBOW
3/4" CRUSHED ROCK PIPE BEDDING
SEWER UAIN
CONCRETE RING
3/4" CRUSHED ROCK SEE NOTE 4
12" PVC, C-900 x 15" LONG (CLEANOUT
BOX) STANDARD WYE BRANCH
SIZE x REQUIRED LENGTH PVC PIPE INSTALL PLUG AND CONCRETE LUG

Revision By Approved Date RECOMMENDED BY lHE SAN DIEGO


SAN DIEGO REGIONAL STANDARD DRAWING REGIONAL STANDARDS COMMITTEE
ORIGINAL Kercheval 12 75
Add Metric T. Stanton 03/03 7(Z6(ZOfZ
Replaced S-03 J. Tomasulo 03/05
Delete Metric MR B. KNOLL 03/11
SEWER CLEANOUT
DRAWING SC-01
NUMBER
PVC LINER so· DIA
SEE NOTE 3 MANHOLE SEE NOTE 2

,,,"' •' \
I
I
I . . \
I
\
' ...... ~SEE DETAIL ' B'

MANHOLE BASE
SEE NOTE 4

PVC LINER
SEE NOTE 3
DETAIL "A• MANHOLE DETAIL • 9• MANHOLE
FRAME & COVER JOINT SECTIONS

NOTES:
1~ REFER TO AGENCY SPECIFlCAllONS WHERE APPLICABLE
2 MANHOLES FOR SEWER MAINS 18" AND LARGER SHALL BE COATED AND LINED
3 MANHOLE SHAFT AND CONE SECllONS, AND GRADE RINGS SHALL HAVE A PVC LINER PLACED
WITH T-SHAPED SUPPORTS INTEGRALLY CAST INTO THE CONCRETE
4) ELASTOMERIC POLYURETHANE COAllNG SHALL BE APPLIED TO THE INTERIOR OF MANHOLE
BASES
5) MATERIALS SHALL BE SELECTED FROM THE AGENCYS APPROVED MATERIALS UST
Revision B A roved Date RECOMMENDED BY THE SAN DIEGO
SAN DIEGO REGIONAL STANDARD DRAWING REGIONAL STANDARDS COMMITIEE
ORIGINAL Kercheval 12 75
Add Metric T. Stanton 03/03
Replaced S- 02 J. Tomasulo 03/05 MANHOLE COATING AND
elete Metric MR B. KNOLL 03/11 LINING SYSTEM DRAWING
NUMBER SM- 07
FOR DRAWING SM-05 SEE DRAWINGS M-1 THRU M-3
EXIST FINISH GRADE

\
--I ~ r~~--
~t----------i~
r-~----------;~
I I I I
I I I I
// I I
I I I I
I I I I
// I I

z
en 0:::~
(!)
z
~ ~ .. .. .., .......
~ LaJ
~ ALL VOID WITH
0
:I: a: SAND/CEMENT sWRRY
I 0
~
I;; LaJ
x
LaJ ~ .. ..

CONCRETE PLUG

NOlES:
1) REFER TO AGENCY SPECIFICA llONS WHERE APPLICABLE
2lALL SALVAGED MAlERIAL BECOMES PROPERTY OF AGENCY OF JURISDICTION
3 BACKFILL PER AGENCYS REQUIREMENT
- - - {_.,'------
4 FOR CUTTING &: PLUGGING ABANDONED SEWER MAINS SEE WP-03 LEGEND ON PLANS

Revision By Approved Date RECOMMENDED BY THE SAN DIEGO


SAN DIEGO REGIONAL STANDARD DRAWING REGIONAL STANDARDS COMMITTEE
ORIGINAL Kercheval 12 75
Add Metric T. Stanton 03/03 7/Z6/ZOfZ
Replaced 5-02 J. Tomasulo 03/05 EXISTING MANHOLE Ch
elete Metric MR B. KNOLL 03/11 ABANDONMENT DRAWING
NUMBER SM-08
CHAPTER 10
W ATER
SYSTEMS
STANDARD SUP-ON OR
WELDING NECK FLANGE
(WELD PER AWWA STDS)
MORTA~If A/J)
UNING ~COATTNG
r ~ORTAR

CROTCH PLATE
DETAIL

WRAPPER OR
COUAR OVTLET I.D.

ALL WELDS TO CONFORM


ANSVAWWA 206-91
(TYP)
TYP. FOR SCRW PIPE • 1YP. FOR STEEL PIPE OR PIPE SPECIALS

lt: : :·: : : : : : : :·: : : : : : : :·: : : : : : :~: : : :.: : : : ~: : : :.: : : : ~: : : :.: : : : :~ :~~~::~:~~~~~~~~~:~::~: : : :~: : : :~: : : :~: : : :~: : : :~: : : :~: : : : ·: : :: : : : : :·: : :: : : : : :·: : :: :::::::Jl
~j RATIO OF OUTLET ID jj PIPE CLASS jj ANGLE BE1WEEN OUTLET AXIS jj lYPE OF j~
···~~-~~---
···········g··...........
1
H ·············!9
:r ·.............. ······... ············:J:-·-·
................................................
··········-···-···········-···-···········-··1JL ···-···-···········-···-···~~~---~~~~~~-~--~~~---·························J
r··............................ ····-···-···!:'.~~~~9~~~~~---·········H
········-···-···········-···-···········-···-···········-···-·······::........... ········-···-···········-···-·········::
~j 0.2 AND LESS jj ALL jj 0° to 75 jj WRAPPER ~~
;! ;! ALL !! 75 o to 90 !! COLLAR !!
~1'""'"""""'""'"""""'""'"""""1i""""""'"""'""""'"""'""""""'if'"'"""'""""'"""'""""'"""'""""'"""'""""'"""'""""'"""'"""ll"'"""'""""'"""'"""""'""'"""+
i! !! UNDER 150 !! 0° to 75 !! WRAPPER !i
i! 0.2 TO 0.6 !! UNDER 150 !! 75° to 90 !! COLLAR !!
~j jj 150 AND OVER jj 0° to 90 !! WRAPPER !~
!t................................................ J; ................................................. JL.................................................................................................!!................................................. J:
r··············································1:· ···········uNoER···1-5a················r·······························a.;········t;··········oo;;································T··············wRA?F'.ER················H
!! 0 ·6 TO 1·0 !! 150 AND OVER !! 0° to 90° !! 1 PL CROTCH !~

[":·::,:::"""'~:~·:::"""·:·::,:::J',"""'}:,~~;~;·~~;;""':Jt":'':':':'':"'':'':':':'':"~~·:·:·j~,,:,,:·:·~:··:··:·:·:··:"'':'':':':'':"'l':":""""~~;,~~"'"J
NOTES 1. COUAR OD OR WRAPPER WIDTH SHALl. BE EQUAL TO TWICE THE LENGTH OF THE OPENING IN THE MAINLINE PIPE
MEASURED ALONG THE PIPE AXIS. THICKNESS SHALL BE EQUAL TO THAT SPECIFIED FOR PIPE SPECIALS.

2. IF A CROTCH PLATE IS REQUIRED, THE OVTLET LENGTH SHALl. BE ADJUSTED TO CLEAR THE MAXIMUM LENGTH OF
BOLT USED FOR FLANGE.

3. OVTLETS LESS THAN 3" IN DIA. MAY BE INSTALLED WITHOUT COUARS PROVIDING THAT ROD REINFORCING
IS NOT CUT AND OUTLETS ARE WELDED TO RODS.

4. REINFORCING FOR OUTLETS ON PIPE, OTHER THAN SCRW PIPE OR STEEL PIPE, SHALL BE AS SHOWN ON PLANS
OR SUBMITIED FOR APPROVAL

5. NOZZLE FABRICATION DETAILS ARE 1YPICAL FOR All SIZES OF OVTLETS.

6. REPEAT NOTE 1 FOR SDW-103

7. FLANGES SHALL CONFORM TO AWWA C207 AND DRILLING SHALL MATCH THE ABOVE FLANGE DRIWNG.

8. MINIMUM UNING THICKNESS FOR OUTLETS SHALL BE:

V4" FOR 8" ID AND LESS


w• FOR 10" ID 16' ID
314" FOR 18" ID AND GREATER

9. COATING THICKNESS FOR OUTLETS SHALl. BE:

314" FOR 16" ID AND LESS


1 V4" FOR 18'' ID AND GREATER
SPECIFIED COATING THICKNESS SHALL BE REDUCED BY 50% FOR THE DISTANCE OF ONE BOLT LENGTH
BACK FROM THE FLANGE FACE.

10. REINFORCEMENT OF FfTIINGS, COLLARS, WRAPPER AND CROTCH PLATE DESIGN SHALL CONFORM TO M-11, LATEST STEEL PIPE-
GUIDE FOR DESIGN AND INSTALLATION EDITION.

REVISION BY APPROVED DAlE RECOMMENDED BY THE Ct1Y OF SAN DIEGO


STANDARDS COMMITTEE
CllY OF SAN DIEGO - STANDARD DRAWING
oil~
ORJGINAL H. HORN !HH!O
1/31/2012
J.CASEY 6-3-a3
COORDINATOR R.C.E. 65271 DAlE
J. CASEY 8-ZH!S TYPICAL OUTLET FOR SCRW PIPE
DRAWING
OV12
STEEL PIPE AND PIPE SPECIALS NUMBER
SDW-101
DRILL AND TAP FOR AIR-VALVE SIZE
(AIR RELEASE VALVE STATION ONLY)

DRILL AND TAP FOR 3'4" DIA


FORCING BOLT ADDITION
TO STANDARD BOLT HOLE

BOLT HOLES
(STUD DIA +

SECTION THROUGH COVER

HANDLE DETAIL
(lYPICAL 2 PLACES)

FLANGE OD SECTION A-A


;. BOLT CENTER
. !I

- l'H"'--- STEEL PLATE


V4" MIN
20" MIN ID REINFORCING PER
SDW-101

ct.
I
Q
TYP FOR SCRW PIPE TYP FOR STEEL PIPE OR PIPE SPECIALS w
"-
a:
SECTION ON PIPE AXIS

FURNISH: REQUIRED STUD BOLTS WIFULL LENGTH THREAD & TWO (2) HEX NUTS EACH 1116" THICK FULL FACE GASKET
AND 3'4 INCH DIA STAINLESS STEEL FORCING BOLT ON DC

NOTES: 1. APPLY TWO (2) COATS OF COAL-TAR EPOXY 16 MILS TOTAL (MIN) TO ALL EXPOSED METAL SURFACES.
AMERCOAT 78 OR KOP--COAT 300 M OR EQUAL MEETING U.S. PUBLIC HEALTH STANDARDS ARE APPROVED
FOR SUCH APPLICATION PER MANUFACTURE'S STANDARDS.

2. DETAILS OF MANHOLES ON PIPELINES LESS THAN 24" DIAMETER SHALL BE SHOWN ON DESIGN
DRAWINGS OR SUBMITIED FOR APPROVAL

3. MANHOLES SHALL BE BEVELED DURING FABRICATION, SO THAT THEY ARE TRUE TO VERTICAL UPON INSTALLATION.

4. All WELDS TO CONFORM TO ANSI/AWWA C206 - 91.

REVISION BY APPROVED DAlE RECOMMENDED BY THE CI1Y OF SAN DIEGO


STANDARDS COMMITTEE
CllY OF SAN DIEGO - STANDARD DRAWING
ORIGINAL H. HORN
oil~ 1/31/2012
COORDINATOR R.C.E. 65271 DAlE

ACCESS MANHOLE DRAWING

NUMBER
SDW-103
2"-4"
C
C 2'MI
N
C

C
PROPERTY LINE
DETAI
LA

C
2

22-24"
C
DETAI
LA

6"
3 C
8
4"

C
2

C
C FI
NISH GRADE

C
4

C
C

C
C
C
C

C
12"

4"
1:

C
4' - 0" MAX
C

5
3' - 0" MIN

6"
C
C
C C 4'- 0"
C
10 11 12
C 6 C

C
7

C
C
7 9
C

C
C

C
7

FI
RE HYDRANT I
NSTALLATI
ON

I
TEM I
TEM
DESCRI
PTI
ON DESCRI
PTI
ON
NO. NO.

1 6" W ET BARREL FI
RE HYDRANT 5 6" CAST I
RON EXTENSI
ON NON-GROOVED
SPOOL - AS REQUI
RED (
F,F)
2 .
75" X 3.
5" MI
N HEX HEAD BREAKAW AY (
SHEAR)
6 6" LONG RADI
US DIBASE ELBOW (
F,PO /MJ)
BOLTS AND NUTS (ASTM A307)SHALL BE 3/
4"
NC THREAD. HEX HEAD ON TOP OF 7 CONCRETE THRUST BLOCK PER SDW -151.
FLANGES (
ALL)
8 COLD JOI
NT STRI
P
3 6" CAST I
RON BREAKAW AY SPOOL W I
TH 0.
25"-V
(SI
NGLE OR DOUBLE)BREAK OFF GROOVE 9 PI
PE - 6" C-900 PVC

4 4'X 4'X 4" THI


CK CONCRETE PAD W I
TH 6" X 12" 10 GATE W ELL W I
TH CAP PER SDW -153.
DEEP THI
CKENED EDGE AROUND PERI
METER
11 6" GATE VALVE (
F/MJ,F)
OF CONCRETE PAD
12 TEE - SI
ZE X 6" (
MJ,MJ,F)

NOTES:
1. NUMBER OF OUTLETS SHALL BE AS SHOW N ON THE PLANS.

2. CONNECT TO BASE OF THE HYDRANT W I


TH SHEAR BOLTS I
NSTALLED W I
TH HEX HEAD ON
TOP OF THE FLANGE.(
31/
64" DI
AMETER HOLE 2" DEEP I
N BOLTS,GALVANI
ZED LEGEND ON PLANS
AFTER BORI
NG)

SHEET 1OF 3

RECOMMENDED BY THE CI
TY OF SAN DI
EGO
REVI
SION BY APPROVED DATE
STANDARDS COMMITTEE
CI
TY OF SAN DI
EGO - STANDARD DRAW I
NG
ORI
GINAL KA J.NAGELVOORT 01/
12

2/
25/
16
UPDATED KA J.NAGELVOORT 08/
13
COORDI
NATOR R.
C.E.56523 DATE
UPDATED HM J.NAGELVOORT 02/
16
FI
RE HYDRANT
DRAW I
NG
I
NSTALLATI
ON SDW -
104
NUMBER
3'MI
N FROM PROPERTY
LI
NE OR RI
GHT OF W AY

3'
-0" MI
N SI
DEW ALK TYPI
CAL

FROM EDGE OF ALTERNATE


FI
RE HYDRANT
PAVEMENT C LOCATI
ON

C
C

C
C
C
CONCRETE PAD COLD JOI
NT
C
C TYPI
CAL
STRI
P

RB
CU
NO

C
RB
CU AL
K
TH
I EW
W D
SI
S
NO OU
IGU
T
ON
N-C C
K
NO AL
o

60 S CURB
C
C EW OU
GU
D
C TYPI
CAL
SI I
NT K
CO AL STREET TYPI
CAL
W
IDE
S
C
PROTECTION POSTS
SEE W M-04 C 3'
-0"
C C

FI
RE HYDRANT W I
TH
C

6" RUN TYPI


CAL

C
o o C
30 C 30
C

NOTE:

W HEN REQUIRED,NUMBER OF POSTS AND 3-PORTS 2-PORTS 2-2 1/


2"
LOCATION TO BE SHOW N ON THE PLANS. PORTS ONLY

PROTECTI
ON POSTS PORT ORI
ENTATI
ON

FI
RE HYDRANT LOCATI
ONS AND PORT ORI
ENTATI
ON

NOTES:
1) LOCATE FI
RE HYDRANT AS SHOW N ABOVE OR AS DI
RECTED BY THE ENGI
NEER.

2) FI
RE HYDRANTS SHALL BE I
NSTALLED W I
TH THE LARGEST PORT PERPENDI
CULAR TO
THE STREET.

3) I
F THE CONCRETE SLAB I
S TO BE I
NSTALLED ADJACENT TO A CONCRETE CURB OR
SI
DEW ALK,A COLD JOI
NT STRI
P SHALL BE I
NSTALLED.

4) CONCRETE APRON SHALL BE REQUI


RED W HERE THE FI RE HYDRANT I
S INSTALLED I
N
AN UNPAVED LOCATI
ON. THE APRON SHALL BE 4" THI
CK 520-C-2500 CONCRETE.

5) W HEN DI
STANCE FROM THE FI
RE HYDRANT TO THE TOP OR TOE OF THE SLOPE OR
W ALLS I
S LESS THAN 2'
,SPECI
AL HYDRANT I
NSTALLATI
ON DETAI
L SHALL BE SHOW N ON
THE PLANS.

6) THE DI
STANCE FROM THE FACE OF THE CURB TO THE CENTERLI
NE OF THE FI
RE
HYDRANT SHALL BE 2 1/
2'MI
NIMUM.
SHEET 2 OF 3

RECOMMENDED BY THE CI
TY OF SAN DI
EGO
REVI
SION BY APPROVED DATE
STANDARDS COMMITTEE
CI
TY OF SAN DI
EGO - STANDARD DRAW I
NG
ORI
GINAL KA J.NAGELVOORT 01/
12

2/
25/
16
UPDATED KA J.NAGELVOORT 08/
13
COORDI
NATOR R.
C.E.56523 DATE
UPDATED HM J.NAGELVOORT 02/
16 FI
RE HYDRANT
DRAW I
NG
I
NSTALLATI
ON SDW -
104
NUMBER
STREET LOCATI
ONS

EDGELINE
MEDIAN

)
ENCE
SHOULDER

F
(
RW
/
FREEW AY LOCATI
ON

MARKERS - SHALL BE BLUE 2-W AY STI


MSONI
TE LI
FELI
TE 88AB OR EQUAL.

ADHESI
VE - AN AMPLE AMOUNT OF 2 (
A&B)EPOXY OR EQUAL.

6" TRAFFI
C STRI
PE
SURFACES - CLEAN AND DRY TO I NSTALLATI
ON PER MANUFACTURER'S
RECOMMENDATIONS.
I
NSTALL MARKERS W I
TH REFLECTI VE SURFACES FACI
NG ONCOMI
NG
MARKER
VEHI
CLES AND OFFSET 2" FROM LANE LI
NES TOW ARD FI
RE HYDRANT.

DETAI
L

FI
RE HYDRANT MARKERS

NOTES
1. FI
RE DEPARTMENT W I
LL PROVI
DE LOCATI
ON(S)FOR ALL MARKERS I
N PRD' S
COMMERCIAL LOTS AND OTHER AREAS OUTSIDE OF PUBLI
C RIGHT OF W AY.

2. MARKERS SHALL BE I
NSTALLED AT THE NEW AND RELOCATED HYDRANTS AND
WITHI
N ALL RESURFACING PROJECTS.

3. FOR STREETS W I
THOUT LANE LI
NES OR STREETS W ITH RAI
SED PAVEMENT MARKERS
AND NO PAINTED LANE LINES,INSTALL MARKERS 6" FROM CENTERLI
NE
OR EXI
STI
NG MARKERS.
SHEET 3 OF 3
RECOMMENDED BY THE CI
TY OF SAN DI
EGO
REVI
SION BY APPROVED DATE
STANDARDS COMMITTEE
CI
TY OF SAN DI
EGO - STANDARD DRAW I
NG
ORI
GINAL KA J.NAGELVOORT 01/
12

2/
25/
16
UPDATED KA J.NAGELVOORT 08/
13
COORDI
NATOR R.
C.E.56523 DATE
UPDATED HM J.NAGELVOORT 02/
16
FI
RE HYDRANT
DRAW I
NG
I
NSTALLATI
ON SDW -
104
NUMBER
11

12

C
C
19 17 P/
L
C

8 15

C
CI
TY PRI
VATELY 18"
C
C

C C C
C C C
MAI
NTAI
NED MAI
NTAI
NED TYP

24" MAXI
MUM C 11 12 13 11 14
DETAI
L'A' C

C
C
SEE NOTE 12

C
SEE NOTE 6

C
C
19 10 10

C
C
C

C
9
CURB 15

C
16

C
C
C
FI
NISH C
GRADE C

SEE 17
NOTE 5 C 8
3 C
5 C 8

1 4
6 7 7 18
C
C

C
1 1

C
C

C
C
C

2 C FLOW C FLOW C

C SEE NOTE 7 C SEE NOTE 8


C C

RP FS

LEGEND ON PLANS

SEE NOTES ON SHEET 2

I
TEM I
TEM
SI
ZE AND DESCRI
PTI
ON SI
ZE AND DESCRI
PTI
ON
NO NO

1 CONCRETE THRUST BLOCK SEE SDW -151 12 APPROVED REDUCED PRESSURE DETECTOR
ASSEMBLY (
RPDA)SEE NOTE 3
2 W ATER MAI
N
13 CHAI
N WI
TH KNOX LOCK SEE NOTE 3,SHEET 2
3 GATE W ELL W I
TH CAP SEE SDW -153 OF 2

4 SI
ZE x SI
ZE MJ/
FLG x FLG TEE 14 FLANGED TEE W I
TH "FDC" SEE NOTE 3,SHEET 2
OF 2
5 FLG x MJ/
FLG RW GV
15 CONCRETE SLAB MI
NIMUM 4" THI
CK x 36" W I
DE
6 C-900 PVC PI
PE x AS REQUI
RED

7 MJ x FLG 90? BEND 16 3/


4" BYPASS,METER & RP ASSEMBLY

8 FLANGED DUCTI
LE I
RON PI
PE 17 ADJUSTABLE VALVE SUPPORT

9 COLD JOI
NT STRI
P 18 PVC OR DIPI
PE SEE NOTE 8,SHEET 2 OF 2
10 FLANGED 90? BEND,SEE NOTE 6,SHEET 2 OF 2
19 FLANGED ANGLE PRESSURE REDUCI
NG VALVE
11 FLANGED OS&Y RW GV W I
TH HAND W HEEL SEE NOTE 6,SHEET 2 OF 2

SHEET 1OF 2

RECOMMENDED BY THE CI
TY OF SAN DI
EGO
REVI
SION BY APPROVED DATE
STANDARDS COMMITTEE
CI
TY OF SAN DI
EGO - STANDARD DRAW I
NG
ORI
GINAL* KA J.NAGELVOORT 01/
12

2/
24/
16
UPDATED KA J.NAGELVOORT 8/
13
COORDI
NATOR R.
C.E.56523 DATE
UPDATED FG J.NAGELVOORT 02/
16 BACKFLOW PREVENTER FOR 4" AND
DRAW I
NG
LARGER FI
RE SERVI
CE SDW -
105
NUMBER
NOTES:

1) I
NSTALL W ARNI
NG / I
DENTI
FICATI
ON TAPE PER SDM-105.

2) LOCATE BACKFLOW PREVENTI


ON ASSEMBLY I
N SUCH A MANNER THAT W I
LL ALLOW THE DEVI
CE TO BE READI
LY
ACCESSI
BLE FOR I
NSPECTI
ON,REPAI
R,AND USE.

3) TAMPER SW I
TCH,AUTOMATI
C RESET,CHAI
N WI
TH KNOX LOCK,AND FI
RE DEPARTMENT CONNECTI
ON (
"FDC")SHALL BE AS
REQUI
RED BY THE FI
RE DEPARTMENT.

4) BALL VALVE TEST COCKS AND DETECTOR ASSEMBLY SHALL BE PROVI


DED AND LOCATED PER THE MANUFACTURES
RECOMMENDATI
ONS AND CI
TY STANDARDS.

5) I
NSTALL FI
RE SERVI
CES SO THAT THE DI
STANCE BETW EEN THE BOTTOM OF THE RELI
EF DI
APHRAGM AND THE
CONCRETE SLAB OR FI
NISH GRADE I
S 12" MI
NIMUM AND 24" MAXI
MUM.

6) I
NSTALL A PRESSURE REDUCI
NG VALVE UPSTREAM OF THE FI
RST 90 BEND W HEN SYSTEM STATI
C PRESSURE EXCEEDS
150 PSIOR W HEN RECOMMENDED BY THE BACKFLOW MANUFACTURER.

7) I
NSTALL PI
PE AND RELATED APPURTENANCES I
N THI
S AREA PER THE CI
TY REQUI
REMENTS.

8) I
NSTALL PI
PE AND RELATED APPURTENENCES I
N THI
S AREA AS REQUI
RED BY THE FI
RE DEPARTMENT.

9) ABOVE GROUND APPURTENANCES SHALL BE PAI


NTED AND I
DENTI
FIED AS CALLED FOR BY THE FI
RE DEPARTMENT.

10)TESTI
NG SHALL BE CONDUCTED AS REQUI
RED BY THE PUBLI
C UTI
LITI
ES DEPARTMENT CROSS CONNECTI
ON CONTROL
UNI
T.

11)CONNECTI
ONS TO STEEL MAI
NS SHALL BE I
N ACCORDANCE W I
TH SPECI
FICATI
ONS.

12)ANY OTHER LOCATI


ON OF FI
RE SERVI
CE BACKFLOW ,AS SHOW N ON SHEET 1,MUST BE DETERMI
NED AND APPROVED BY
PUBLI
C UTI
LITI
ES DEPARTMENT,CROSS CONNECTI
ON CONTROL UNI
T.

RP FS

LEGEND ON PLANS

SHEET 2 OF 2

RECOMMENDED BY THE CI
TY OF SAN DI
EGO
REVI
SION BY APPROVED DATE
STANDARDS COMMITTEE
CI
TY OF SAN DI
EGO - STANDARD DRAW I
NG
ORI
GINAL* KA J.NAGELVOORT 01/
12

UPDATED KA J.NAGELVOORT 8/
13
2/
24/
16
COORDI
NATOR R.
C.E.56523 DATE
UPDATED FG J.NAGELVOORT 7/
15 BACKFLOW PREVENTER FOR 4" AND
UPDATED 02/
16 DRAW I
NG
AR J.NAGELVOORT
LARGER FI
RE SERVI
CE NUMBER
SDW -
105
C 12"
C
SEE NOTE 1
SEE NOTE 2
11
TOP OF BONNET

C
C
C
END OF W ATER MAI
N AS SHOW N ON PLANS C

C
C C

4" MIN.
9

18" MIN
C
C
10
10 C C

C
C
C
2

C
C
C
C 7
3 2

C W OOD BLOCKS
1 1 8

C
C

C
C
~ 6

CAP FOR PVC PI


PE 3 4 5
PLUG FOR CIPI
PE
SEE NOTE 3

DRILL AND TAP TO DRILL AND TAP TO


2" STD PI
PE THREAD 3" STD PI
PE THREAD
C

2 2

C NOTES:
1. SET TO FI
NISH GRADE

2.PROVI
DE CONCRETE PADS.

CONCENTRI C PLUG DRI LLED FOR ECCENTRI C PLUG DRI LLED FOR 3.PROVI
DE THRUST BLOCKS PER SDW -151.
2" BLOW -OFF FOR 3"-8" MAI
NS 3" BLOW -OFF FOR 10"-20" MAI
NS

SCHEDULE

I
TEM SI
ZE AND DESCRI
PTI
ON

1 W ATER MAI
N 3" - 8" I
NCL. 10" - 20" I
NCL.

2 CAST I
RON PLUG OR CAP MAI
N SI
ZE X 2" MAI
N SI
ZE X 3"

3 BRASS NI
PPLE 2" X 8" 3" X 8"

BRONZE GATE VALVE W I


TH 2" 3"
4
BRONZE W HEEL-SCREW ENDS

5 BRASS NI
PPLE AS NEEDED AS NEEDED

o
6 BRASS 90 EL 2" 3"

2" X VARI
ABLE TO 3" X VARI
ABLE TO
7 BRASS RI
SER
GRADE MI NUS 4" GRADE MI NUS 4"

8 BRASS COUPLI
NG THREAD 2" 3"

9 BRASS PLUG 2" 3"

STEEL CASI
NG FOR 8" X VARI
ABLE TO 8" X VARI
ABLE TO
10
GATE VALVE AND RI
SER GRADE MI NUS 3/
4" GRADE MI NUS 3/
4"

GATE W ELL CAP AND CAN 8"


11 8"
SEE SDW -153

REVI
SION BY APPROVED DATE
RECOMMENDED BY THE CI
TY OF SAN DI
EGO
CI
TY OF SAN DI
EGO - STANDARD DRAW I
NG STANDARDS COMMITTEE
ORI
GINAL J.MUELLER 3-3-83

NOTES SM A.OSKOUI 12-03

2/
25/
16
NOTES JS A.OSKOUI 12-06 BLOW -OFF ASSEM BLIES COORDI
NATOR R.
C.E.56523 DATE
UPDATED KA J.NAGELVOORT 12/
12 AT THE END OF
DRAW I
NG
UPDATED RB J.NAGELVOORT 10/
15
PVC AND CAST IRON M AI
NS SDW -
106
NUMBER
UPDATED HM J.NAGELVOORT 02/
16
FINISHED

.:I
Jr/
II-

_, :(~
. : .-.:-1----+-
6" MIN
(!)
z
SAND CEMENT SLURRY
BACKFILL 190-E-400 o/ / .. ·

6" MIN
OW
oz
wo
CilN

------r-------~------~-

SE 50 BEDDING

6"
~PIPEOO
MIN

TRENCH SECTION

NOTES:

1. THE PROPOSED WATER SERVICE SHALL BE SECURED IN CENTER OF THE TRENCH.

2. SAND CEMENT SLURRY BACKFILL SHALL BE THOROUGHLY CONSOUDATED TO ENCASE CONDUITS. TAMPERS OR VIBRATORS
SHALL BE USED.

3. EXISTING PAVEMENT WlLL NOT REQUIRE SAW CUTIING WHEN USING ROCKWHEEL FOR EXCAVATION EXCEPT WHEN THE
EXISTING PAVEMENT IS CONCRETE AND TRENCH FINISH IS CONCRETE.

4. CUTS SHALL BE PARALLEL OR PERPENDICULAR TO STREET CENTERUNE, WHEN PRACTICAL

5. IN MAJOR OR PRIME ARTERIAL STREETS, ON APPROVAL SET ACCELERATING ADMIXTURE, SUCH AS CALCIUM CHLORIDE, MAY BE USED
ONLY WITH PRIOR APPROVAL OF THE ENGINEER OTHERWISE THE CONTRACTOR SHALL PROTECT THE TRENCH W1TH THE
APPROVAL OF THE ENGINEER.

6. 6" METAL TAPE SHALL BE INSTALLED ABOVE PIPE 4" BELOW TRENCH CAP AND 12" BELOW FINISH GRADE IN UNIMPROVED STREETS.

REVISION BY APPROVED DAlE RECOMMENDED BY THE Ct1Y OF SAN DIEGO


STANDARDS COMMITTEE
CllY OF SAN DIEGO - STANDARD DRAWING
ORIGINAL KA ~. NAGaVOORl OV12
oil~ 1/31/2012
COORDINATOR R.C.E. 65271 DAlE
NARROW TRENCH FOR
DRAWING
1" & 2" WATER SERVICES NUMBER
SDW-107
HOLD OR CUT BACK
COATI
NG ON SPIGOT END

CONC GROUT PLACED I


N FI
ELD

C
C C
C C
3" NORMAL 3" NORMAL

C
C
C

C
C

C
C

5/
16" DI
A BAR 5/
16" DI
A BAR

W ELDED BELL AND FORMED BELL AND


SPIGOT RI
NG W ELDED SPI
GOT RI
NG

NOTE:
SEE SDW -111FOR FULL DETAI
LS OF ABOVE JOI
NTS

6" 6"
C 2 1/
2" C C C 2 1/
2"
C C C C

FORM
CONCRETE GROUT
3" MI
C N FLAT
C
CONCRETE
2" X 4" X 12 GA (
PLUS LAP FOR
MORTAR SPACER 11/
2" OD
DOUBLE W ELD)
COATI
NG
C

C
C

C
C

C
C
C
C

CC
C

1" 11/
2"
T

C C
C C
CONCRETE MORTAR 2" X 4" X 12 GAGE W I
RE MESH
LAP
C

LI
NING
C

C
C

GAP 1/
16" CEMENT MORTAR PLACED
TO 1/
32" I
N FI
ELD AND HAND POI
NTED

SINGLE OUTSI
DE W ELD
LAP = 11/
2"

DOUBLE W ELD
LAP = 5 X PLATE T (
11/
2" MI
N 3" MAX)

SLI
P JOI
NT

NOTE:

ALL W ELDS TO CONFORM TO ASNI/


AW W A C206 - 91

RECOMMENDED BY THE CI
TY OF SAN DI
EGO
REVI
SION BY APPROVED DATE
STANDARDS COMMITTEE
CI
TY OF SAN DI
EGO - STANDARD DRAW I
NG
ORI
GINAL H.HORN 5-6-80

2/
25/
16
J.CASEY 6-3-83
COORDI
NATOR R.
C.E.56523 DATE
UPDATED KA J.NAGELVOORT 01/
12
FI
ELD W ELDED JOI
NTS
DRAW I
NG
UPDATED AR J.NAGELVOORT 10/
15
SDW -
108
NUMBER
UPDATED HM J.NAGELVOORT 02/
16
Cutwasherto
STREET SURFACE
f
itpi
pe siz
e

C
3" MIN
3 1/
2"
C

24" MAX
C

C
1 1/2"

C
C

7"
C
W ELD GUI
DE SUPPORT

C
2"
1/ C C (
W ELDED TO SHAFT)

C
7
C

C
C
C
1" TO 11/
2" LOOSE
C 2 3/
4"
C
I
NSPECTI
ON HOLES C VARI
ES
C

1 3/8"1 3/8"
C
C 1/
8" OR 10 GAUGE C
C 13/
4"

C
C
W ELD 1/
8"

C
C W ELD

VARIABLE
1/
2" C
C

C
GUI
DE C SECTI
ON C-C
1" PI
PE

1/
4" W ELD 3/
16"
1/4"

C
C
C C
2 3/
4" C 2 1/
2"

1/4"

3/4"
C
C
C

3/
8" ROD

C
2 1/2"

2 1/2"
C
2 3/4"
2 1/2"

C
C

C
C
1/4"

C
C
C
C C C
TO FI
T PI
PE SI
ZE

C
C
C

C
C

C
2 1/
4"
1/
4" C 1/
4"
SI
DE BOTTOM C C
W HEEL TYPE KEY EXT.

BUTTERFLY VALVE KEY EXTENSI


ON
STREET SURFACE

C
3" MIN
C

24" MAX
C
2" X 2" X 2" OD
C

2"
7 1/

C
2"

C
1" TO 11/
2" C

7"
I
NSPECTI
ON HOLES
C

C
C W ELD TO TOP
C C
C
OF PI
PE
2"

C
C
LOOSE C
C

C
C
A A
C
C
SECTI
ON A-A C 1" PI
PE
1/
8" OR 10 GAUGE
VARIES
1/4"

C 1
/4"
C
W ELD 1/
8"
1/4"

C 21
/2"
C
C

C
2 1/2"
C

C
C

C
C
C

C
2 1/2"

B B
C
C

W ELD 1/
8"
SECTI
ON B-B
GATE VALVE KEY EXTENSI
ON FOR TURNI
NG NUT

NOTES:

1. I
NSTALL VALVE KEY EXTENSI
ONS W HEN TOP OF VALVE I
S 6'OR MORE BELOW GROUND OR PAVEMENT SURFACE.

2. PAI
NT ALL FI
NISHED SURFACES W I
TH ASPHALT VARNI
SH.

3. FOR VALVE BOX AND COVER,SEE SDW -153 AND SDW -154.

4. ALL W ELDS TO CONFORM TO ANSI/


AW W A C206 - 91.

RECOMMENDED BY THE CI
TY OF SAN DI
EGO
REVI
SION BY APPROVED DATE
STANDARDS COMMITTEE
CI
TY OF SAN DI
EGO - STANDARD DRAW I
NG
J.
P.CASEY 6-3-83

2/
25/
16
NOTES AO A.OSKOUI 12/
03
COORDI
NATOR R.
C.E.56523 DATE
NOTES JS A.OSKOUI 12/
06

UPDATED KA J.NAGELVOORT 01/


12
VALVE KEY EXTENSI
ONS DRAW I
NG
SDW -
109
NUMBER
UPDATED AR J.NAGELVOORT 02/
16
IMPROVED STREETS,
TRENCH RESURFACING
PER SDG-107 OR SDG-108
FINISHED TO GRADE

TRENCH WIDTH

N\
,...-\
/
;;-.
I
I
\ I
a: u::::
_J
I
LlJ
_J
\ I
I > ~ ~?A
I- 0 f
a... 0 ~ i<
'~».. §
LlJ
0
I
I
0
Ill
I
*
0
0'>
''L-
""\ I!!
~I

0 zLlJ 0z ~
zLlJ a: LlJ
»
~'<
6" MIN
a: I- a:I- ~
8" MAX
'~
I-
>(.

z
~
POTABLE
C\.1
C}
,...- WATER
z IMPORTED GRANULAR
0 LlJ i< MATERIALS SE50
0 z
LlJ
Ill N
0
*
0
0'>

TRENCH SECTION

NOTES:
1. (*)INDICATES MINIMUM RELATIVE COMPACTION.
2. MINIMUM COVER: 3' FOR DISTRIBUTION MAINS; 5' FOR TRANSMISSION MAINS.
3. 6" METAL TAPE SHALL BE INSTALLED ABOVE PIPE: 4" BELOW TRENCH CAP AND 12" BELOW FINISH
GRADE IN UNIMPROVED STREETS.
4. 1' SAND CUSHION OR A 6" MINIMUM SAND CUSHION WITH 1" NEOPRENE PAD SHALL BE PLACED
FOR ALL CROSSINGS UTILITIES WHEN VERTICAL CLEARANCE IS 1' OR LESS. THE NEOPRENE
PAD SHALL BE PLACED ON THE MOST FRAGILE UTILITY.
5. FOR MAINS LARGER THAN 16", TRENCH WIDTH SHALL BE AS SHOWN ON THE PLANS.

REVISION BY APPROVED DATE RECOMMENDED BY THE CITY OF SAN DIEGO


STANDARDS COMMITIEE
CITY OF SAN DIEGO - STANDARD DRAWING
dl~
ORIGINAL* KA . NAGELVOOR OV12
1/31/2012
PIPE BEDDING AND TRENCH COORDINATOR R.C.E. 65271 DATE

BACKFILL FOR POTABLE DRAWING

WATER MAINS NUMBER


SDW-110
r
3 w· MIN 1" 4 w • MIN
BELL RING - 5" X T
NORMALir-~1-·~--~2·----r--1~,.~

2" x 4" - 12 GAGE CEMENT MORTAR


WlRE MESH UNING

WELDED BELL AND SPIGOT RINGS SPIGOT RING AND ROUND RUBBER GASKET
CARNEGIE SHAPE M 3516 WlTH 21-32"
GASKET OR M 3818 WITH 13116" GASKET.

t-- t-- 1 lQ" NORMAL

CEMENT MORTAR 6 V4" MIN FLAT 8" MIN


COATING
4 11.!" NORMAL CLOSURE

2 3'4"!

REMOVE BEFORE WELD FLUSH


WELDING
DRILL AND TAP 2 - V4" HOLES
180 • APART FOR SHOP AIR AND
SOAP TEST. FILL W1TH WELD
METAL AFTER TEST

FORMED BELL END AND WELDED SPIGOT RING

ITEMS CALL OUT:

8 MAXIMUM FIELD DEFLECTION IN A JOINT IS 3-8" PULL AND 3£" PUSH, THE PULL TO BE UTIUZED FIRST.

G CONCRETE GROUT PLACED IN FIELD.

0 CEMENT MORTAR PLACED IN FIELD AND HAND POINTED.

8 TOLERANCE BETWEEN BELL ID AND SPIGOT OD TO BE '\132" TO 1116" ON THE DIAMETER.

8 ALL WELDS TO CONFORM TO ANSI/AWWA C206 - 91.

REVISION BY APPROVED DAlE RECOMMENDED BY THE Ct1Y OF SAN DIEGO


STANDARDS COMMITTEE
CllY OF SAN DIEGO - STANDARD DRAWING
oil~
ORJGINAL H. HORN ~0
1/31/2012
J.CASEY !MH!3
COORDINATOR R.C.E. 65271
NOlES SM AOSKOUI 1W6 SPIGOT RING & GASKET JOINT DAlE

DRAWING
NOlES JS AOSKOUI 1W6
FOR WELDED STEEL PIPE NUMBER
SDW-111
UPDATED KA . NAGELVOOR OV12
35"

8 =l [ 11 GA WELDED
WIRE FRAME 29 3--8"
I V4" DIA BARS EA WAY

LO
..-

3" R
B
COVER W'CONC READING LID
PlAN
1 x V2" SLOT
36"
2 314"
3 V4"

11 7~"
N
,...

DEFORMED BARS

___l .=: ;~ . 1_ _----l_,-1,1 V2"


32"
35" 1V2"11-·-f-
SECTION A-A SECTION B-B

V4" DIA BARS EA WAY


29 3-'8"
7 7~" 13 V2" 7 7~"
1 ;16"

16 13-16"

V4" DIA BARS

SECTION C-C

COVER W I Cl READING LID

NOTE:

UNLESS OTHERWISE INDICATED ON THE PLANS OR SPECIFIED IN SPECIAL


PROVISIONS, COVERS WITH CONCRETE READING LID SHALL BE USED.

REVISION BY APPROVED DAlE RECOMMENDED BY THE Ct1Y OF SAN DIEGO


STANDARDS COMMITTEE
CllY OF SAN DIEGO - STANDARD DRAWING
oil~
ORJGINAL XX H. HOM ~0
1/31/2012
J.CASEY ~
COORDINATOR R.C.E. 65271 DAlE
UPDATED KA . NAGELVOOR OV12 CONCRETE WATER METER BOX
DRAWING
FOR 1 1/2" OR 2'' WATER METER NUMBER
SDW-113
INSTALLED BY CITY INSTALLED BY CONTRACTOR

2" R.P. BACKFLOW DEVICES (PRIVATE) ,


TO MATCH METER SIZE AND
I i INSTALLED PER SDW-155

I I
I I
I I
DIRECTION I I FLOW
OF FLOW ON SITE
I I
I I CONNECT INTO
I I 3" PRIVATE WATER
SUPPLY LINE ON-SITE
I I
L _____ ___ I 2" BRASS OR COPPER
WATER SUPPLY LINE
~
m
(PRIVATE)
s::
m
METER BOX & z
-;
COVER SEE c
NOTE #3 z
m

0
:0

ENCLOSURE

18"-10' MAX
SEE NOTE 4
MIN 4" x 18"

FLOW

FLOW

NOTES:
1. ANY BACKFLOW PROTECTING A SERVICE USED FOR HUMAN CONSUMPTION SHALL BE LEAD FREE

2. ALL METEOOACKFLOW INSTALLATIONS SHALL BE APPROVED BY PUBLIC UTILITIES DEPARTMENT

3. SERVICE CONNECTIONS ON WATER MAIN SHALL BE 30" APART

4. INSTALL A CASING INCASED IN CONCRETE WHEN THE DISTANCE BETWEEN THE METER BOX AND
THE RISER TO THE BFD EXCEEDS 18". NO CONNECTIONS OF ANY KIND PERMITIED IN THIS AREA.

5. SEE SDW-155 FOR ADDITIONAL INFORMATION

2-2" METER AND 2" BACKFLOW INSTALLATION WITH SERVICE AND COFFER BOX

SHEET 1 OF 3

REVISION BY APPROVED DATE RECOMMENDED BY THE CITY OF SAN DIEGO


STANDARDS COMMITIEE
CITY OF SAN DIEGO - STANDARD DRAWING
ORIGINAL KA . NAGELVOOR
til~
()3113
:W'\113
COORDINATOR R.C. E. 65271 DATE

2 .. METER, BACKFLOW AND COFFER BOX DRAWING


NUMBER
SDW-114
CONFIGURATION BLOCK
DESCRIPTIONS HEIGHT WEIGHT

METER BOX 18" 884 LBS

PARKWAY COVER STEEL 2" 191 LBS


PARKWAY COVER STEEL
2" 182 LBS
GALVANIZED
PARKWAY COVER 2" 182 LBS
STEEL W'HOLES
PARKWAY GRATE 2" 182 LBS

PARKWAY COVER

NOTE:
BASE SECTION
J
1. CONCRETE BASE : 5000 PSI

y
~4"

36" x 40" METER BOX PARKWAY

SHEET 2 OF 3

REVISION BY APPROVED DATE RECOMMENDED BY THE CITY OF SAN DIEGO

ORIGINAL KA . NAGELVOOR 03113


CITY OF SAN DIEGO - STANDARD DRAWING rf/ . . ;;~D:m;~ _COMMITIEE
()!t' ~ 3/01113
COORDINATOR R.C.E. 65271 DATE

2"' METER, BACKFLOW AND COFFER BOX DRAWING


NUMBER
SDW-114
1------- 44"------i
I 36" I
I I I

n
-

l
I
I

I 1V16" HOLE (2)


I

l<i----,-----{>11 ~
I
I - .0.
~~
.0.

l~o ------~------ o~l


I

I
I

I
I I I j_

~r-
I ,- =I -=- - - - - L - - - - - -I 4"
2 ,_
I 314'c_j ~
I I
sl
BOX -TOP VIEW COVER - TOP VIEW

BOX - END VIEW

STEEL ARMOR
(GALVANIZED)
SEE SECTION C-C

I~

1 - - - - - 24" - - - l

REBAR FRAME

REBAR FRAME
0=
=0=0=
=o=O=O=O=
=0=0=0=0=
= 0=0 = 0=
= 0=0=

CROSS-SECTION: COVER, B
BOX & ANCHOR
B

SECTION B-B OF COVER

SHEET 3 OF 3

REVISION BY APPROVED DATE RECOMMENDED BY THE CITY OF SAN DIEGO


STANDARDS COMMITIEE
CITY OF SAN DIEGO - STANDARD DRAWING
ORIGINAL KA . NAGELVOOR 03'13
dlcJ/-ML-
COORDINATOR R.C.E. 65271
3/01113
DATE

2.. METER, BACKFLOW AND COFFER BOX DRAWING

NUMBER
SDW-114
WELD TOP OF CAP TO PIPE
4 W"

8 114"

V4" FLOOR PLATE

WELD PLATE RING TO UNDERSIDE OF COVER

3116'' STEEL PIPE

WELD CHAIN TO INSIDE OF CAP'S PIPE AND


TO UNDERSIDE OF COVER
W " STEEL PLATE RING

HOT DIPPED GALVANIZED


STEEL CHAIN

114" X 9" CHAIN

NOTES:

1. 8 114" FLOOR PlATE SHALL BE CUT OUT OF THE COVER COVER (TYP)
AND THE OPENING SHALL BE FINISHED FOR TIGHT FIT.

2. READ HOLE IN COVER SHALL BE CENTERED OVER EACH METER REGISTER.

REVISION BY APPROVED DAlE RECOMMENDED BY THE CITY OF SAN DIEGO


STANDARDS COMMITTEE
CllY OF SAN DIEGO - STANDARD DRAWING
oil~
ORJGINAL XX T. MUEUER 2~6
1/31/2012
READ HOLE COORDINATOR R.C.E. 65271 DAlE

CAP & CHAIN DETAIL DRAWING

{FOR METAL METER VAULT COVERS) NUMBER


SDW-115
THERMITE WELD

COATING NOT SHOWN

BONDING STRAP INSTALLED ON SLEEVE-lYPE COUPLING

AELD MORTAR COATING

FIELD MORTAR COATING


RUBBER ~lNG GASKET
THERMITE WELD THERMITE WELD
MORTAR PLACED
AFTER INSTALLATION

CEMENT-MOTAR LINING

BONDING STRAP FOR BELL AND SPIGOT RUBBER- GASKETED JOINT

BONDING STRAP INSTALLED ON VALVE

NOTES:
1. REMOVE COATING AND CLEAN APPROXIMATELY 2" AREA TO A BRIGHT METAL SURFACE FOR WELDING.

2. THE EXACT TYPE, SIZE AND NUMBER OF BONDING WIRE /STRAP SHALL BE DETERMINED BY PIPE SIZE AND TYPE.

3. WHERE NOT PROTECTED BY CEMENT MORTAR COATING, THERMITE WELD SHALL BE COVERED WITH COLD APPLIED COAL TAR SOLUTION.

REVISION BY APPROVED DAlE RECOMMENDED BY THE Ct1Y OF SAN DIEGO


STANDARDS COMMITTEE
CllY OF SAN DIEGO - STANDARD DRAWING
oil~
ORJGINAL T. MUEUER 2-12-86
1/31/2012
J.CASEY 8-22-86
COORDINATOR R.C.E. 65271 DAlE
UPDAlED KA . NAGELVOOR OV12 BONDING STRAP FOR
DRAWING
STEEL AND SCRW PIPE NUMBER
SDW-116
2 1-2" X 2 1-2" X V4' ANGLE BRACKETS WI
5-8" DIA HOLES FOR MOUNTING BOLTS (3 PLACES)
WELD TO CYUNDER AS SHOWN

1' X 6" ROUND STEEL UFTING


HANDLE 3'16" WELD TO STEEL
COVER

VALVE
SIZE

1" & 2"

4"

6" 30"

3'16' STEEL COVER CONTINUOUS


WELD FROM INSIDE TO CYUNDER

0 0 0
1-2" DIA HOLES (16 PLACES)
0 0 0 2 ROWS - 8 HOLES EACH ROW

,;!,-,-,-,.-,.-,.-,.-,.r 3 W" X 1 W " GALVANIZED STEEL HASP


1 (RIVET TO CYUNDER /ACCESS DOOR)
H COMBINATION
\ AIR & VACUUM
I (LOCK WILL BE PROVIDED BY CITY)

4" X 4' GALVANIZED STEEL HINGED (2 PLACES) \ VALVE I


(RIVET TO CYUNDER & ACESS DOOR) ~ ' I
', I
"- I
\ I

)~ 316 STAINLESS STEEL Ml" X 2 1-2"


ANCHOR BOLT & NUT (3 PLACES)
(COAT THREADS WITH ANTI SEIZE
COMPOUND)

PIPE THROUGH CONCRETE SHALL BE WRAPPED


IN 10 MIL POLYETHENE WRAPPING TAPE, WITH
EACH WRAP OF TAPE TO OVERLAP THE PREVIOUS
WRAP BY V3 THE WIDTH OF THE TAPE

ITEMS CALL OUT:


Q) 3'16" STEEL ENCLOSURE WITH ACCESS DOOR, MISC. HARDWARE. CABINET AND HARDWARE SHOULD BE ZINC RICH EPOXY POWDER PRIMER
(2-3 MIL DRY FILM THICKNESS) AND POLYESTER POWDER TOP COAT (2-3 MIL DRY FILM THICKNESS).

® 3'X 3'X 4" CONCRETE PAD 5~2500.

® D AND H CHANGES ONLY WITH APPROVAL OF THE CITY ENGINEER.


SHEET 1 OF 2

REVISION BY APPROVED DATE RECOMMENDED BY THE Ct1Y OF SAN DIEGO


STANDARDS COMMITTEE
CllY OF SAN DIEGO - STANDARD DRAWING
oil~
ORJGINAL M. ROU.INGER 5-2<Hl2
1/3112012
NOTES JS A OSKOUI 1:Ml6
COORDINATOR R.C.E. 65271 DATE
UPDATED KA . NAGELVOOR OV12 AIR AND VACUUM VALVE ENCLOSURE
& LOCATION DRAWING
SDW-117
NUMBER
24" FROM PROPERTY
LINE, EDGE OF PAVEMENT
OR EDGE OF RIGHT OF WAY
AIR & VACUUM VALVE ENCLOSURE
(TYPICAL)

PROTECnON STEEL POST


SEE NOTE a

STREET
TYPICAL

COLD JOINT

NOTES:
a.) PROTECn ON POSTS SHALL BE INSTALLED AS CALLED FOR ON THE PLANS OR AS DIRECTED BY THE ENGINEER PER WM-04.

b.) AIR & VACUUM VALVES & APPURTENANCES INSTALLED FOR THE USE OF RECYCLED WATER SHALL BE INDENnAED AS DESCRIBED IN
THE SPECIFICATIONS.

SHEET 2 OF 2

REVISION BY APPROVED DATE RECOMMENDED BY THE Ct1Y OF SAN DIEGO


STANDARDS COMMITTEE
CllY OF SAN DIEGO - STANDARD DRAWING
oil~
ORJGINAL KA . NAGELVOORT 01112
1/31/2012
COORDINATOR R.C.E. 65271 DATE
AIR AND VACUUM VALVE ENCLOSURE
DRAWING
& LOCATION SDW-117
NUMBER
INSTALL BACKFLOW PREVENTION PER SDW-105
6
TRENCH RESURFACI
NG
ROAD SURFACE

PROPERTY LINE
C
C

C
5
3'MI
N
4'MAX
C C 3

C
C
C

C
THRUST BLOCK
PER SDW -151
C

4
1

CONCRETE VALVE
BLOCKI
NG

I
TEMS CALL OUT:

1 W ATER MAI
N

2 FLANGED TAPPI NG SLEEVE OR TEE (


NO SI ZE-ON-SI
ZE TAPS ALLOW ED)
(4 X 4,6 X 6,ETC )
. NO EXTENSIONS ALLOW ED.

3 FULL RESILI
ENT SEAT GATE VALVE . SI
ZE OF VALVE SHALL MATCH SI
ZE
OF FIRE SERVI
CE (4" MI
NIMUM DI AMETER). SEE NOTE #1.

4 4" OR LARGER DI
AMETER OF PI
PE (
DUCTI
LE I
RON OR PVC PER APPROVED MATERI
ALS LI
ST)
.

5 VALVE W ELL PER SDW -153.

6 VALVE W ELL COVER PER SDW -153.

NOTES:

1. FOR SMALLER FI
RE SERVI
CE REQUI
REMENTS,USE REDUCER AT PROPERTY LI
NE.

2. FOR CORROSI
ON CONTROL REQUI
REMENTS,SEE PUBLI
C UTI
LITI
ES DEPARTMENT DESI
GN GUI
DE.

RECOMMENDED BY THE CI
TY OF SAN DI
EGO
REVI
SION BY APPROVED DATE
STANDARDS COMMITTEE
CI
TY OF SAN DI
EGO - STANDARD DRAW I
NG
ORI
GINAL BB OSKOUI 10/
09

NOTES AO F.BELOCK 4/
96 2/
25/
16
NOTES JS A.OSKOUI 12/
06 COORDI
NATOR R.
C.E.56523 DATE
FI
RE SERVICE CONNECTI
ON
UPDATED KA J.NAGELVOORT 01/
12
DRAW I
NG
UPDATED KA J.NAGELVOORT 12/
12 & ASSEM BLY SDW -
118
NUMBER
UPDATED HM J.NAGELVOORT 02/
16
C H
C

C 1'6" C G C A C B C C C D /E C B C F C J C G C 1'6"
C C C C C C C C C C C

C 1'
6"
C
C
I

REDUCER
C

C
REDUCER

C
36"MIN
C

C C
L L
C
C

C
C

C
3
3
C

REDUCER
REDUCER
I

C
C

C
C 6" TYP 36" GATE 6'CHAI
N LINK FENCE (ALTERNATE
TYP
6"

C C
MATERIALS MUST BE APPROVED
BY PUBLI
C UTI
LITI
ES DEPT.PRI
OR
TO CONSTRUCTION).OPTI
ONAL

FULL RESI
LIENT SEATED
GATE VALVE TYP BACK FLOW
(NO BUTTERFLY VALVES) EXTENSI
ON PI
PE PREVENTI
ON
METER
ASSEMBLY
STRAI
NER TESTI
NG TEE 1
C

1
C

C
C

(
SEE NOTE 1)
C

C
C

4" CONCRETE SLAB


C

24" MAX
18" MIN

USE 520-C-2500

VALVE BOX W /
COVER
C

C
C

C
C
4"

C
C

C
C
C

48" MAX
36" MIN
I
48" MAX
36" MIN

SCREW JACK

C
2 24" SPOOL
2

C
C
C

FLOW
FLOW
C
C

C
C

C
CONCRETE 1
1
THRUST BLOCK
VALVE SUPPORT
PER SDW -151 BLOCK

NOT TO SCALE

I
TEMS CALL OUT:

o
1 90 FLANGED DUCTI
LE I
RON ELBOW (
TYP)
.

2 FLANGED DUCTI
LE I
RON SPOOL,BOTH ENDS SHALL BE FLANGED (
UNI
-FLANGE SHALL NOT BE USED)
.

3 DI
AMETER OF TEE SHALL BE EQUAL TO THE DI
AMETER OF THE SUPPLY PI
PE.

SEE DI
MENSI
ONS AND NOTES ON SHEET 2

SHEET 1OF 2

RECOMMENDED BY THE CI
TY OF SAN DI
EGO
REVI
SION BY APPROVED DATE
STANDARDS COMMITTEE
CI
TY OF SAN DI
EGO - STANDARD DRAW I
NG
ORI
GINAL JC

REVI
SION BM A.OSKOUI 12/
03 2/
25/
16
COORDI
NATOR R.
C.E.56523 DATE
NOTES JS A.OSKOUI 12/
06 DUAL ABOVE GROUND M ETER
DRAW I
NG
UPDATED KA J.NAGELVOORT 01/
12 WI
TH CI
TY BACKFLOW PREVENTER SDW -
119
NUMBER
UPDATED FG J.NAGELVOORT 02/
16
LETTER METER SI
ZE
3" 4" 6" 8" 10"
CODE
PART DESCRI
PTI
ON

A GATE VALVE 8" 9" 10 1/


2" 111/
2" 1'- 1"

B PI
PE EXTENSI
ON 1'- 0" 1'- 0" 1'- 6" 2'- 0" 2'- 6"

C STRAI
NER * 7" 9" 9" 10" 1'- 0"

D TURBI
NE W ATER METER * 1'- 0" 1'- 2" 1'- 6" 1'- 9" 2'- 2"

E COMPOUND METER * 1'- 5" 2'- 0" 2'- 5" 3'- 1" 4'- 7"

F TESTI
NG TEE 11" 1'- 1" 1'- 4" 1'- 6" 1'- 10"

90 DEG.ELBOW (
SHORT)
G 5 1/
2" 6 1/
2" 8" 9" 11"

H OVERALL SLAB LENGTH * 11'- 10" 12'- 11" 14'- 9" 16'- 3" 18'- 10"

I
SLAB TO C/
L PI
PE 3'- 0" 3'- 0" 3'- 0" 3'- 0" 3'- 6"

J BACKFLOW * 3'- 2" 3'- 4" 4'- 1/


2" 4'
- 4 1/
2" 4'
- 7 1/
2"

*I
NDIVI
DUAL DI
MENSIONS MAY VARY PER MANUFACTURER OVERALL
DIMENSI
ONS INCREASE W I
TH USE OF THESE COMPONENTS

NOTES:
1. ALL BURIED DUCTILE I
RON PIPE,FI
TTI
NGS,VALVES AND APPURTENANCES SHALL BE COATED W ITH A DIELECTRI
C COATING.A
LI
QUI D EPOXY COATING SYSTEM PER AW W A C-210 AT 24 MI
LS MI
NIMUM DRY FILM THICKNESS (
MDFT),OR A COLD APPLIED
THREE-PART SYSTEM PETROLEUM W AX TAPE PER AW W A C-217,OR A 100% POLYURETHANE COATING OF 24 MILS (
MDFT)
SUITABLE.

2.ANY CHANGES SHALL HAVE PUBLI


C UTI
LITI
ES DEPARTMENT APPROVAL.

3.PI
PING SHALL BE SYMMETRI
CAL TO SLAB CENTERLI
NE.

4.SUPPLY PI
PE I
S ONE COMMERCI
AL SI
ZE LARGER THAN PROPOSED METER.

5.CONCRETE SLAB AND FENCE W I


LL BE I
NSTALLED BY CONTRACTOR.

6.CONTACT CORROSI
ON CONTROL SECTI
ON FOR CORROSI
ON REQUI
REMENTS.

7.ALL METAL I
N CONTACT W I
TH CONCRETE SHALL BE POLYETHYLENE W RAPPED USI
NG 2" W I
DE PLASTI
C BACKED ADHESI
VE
TAPE 8 MI
LS THI
CK W I
TH 1/2" OVERLAP.

8.BACKFLOW SHALL BE I
NSTALLED IMMEDI
ATELY DOW NSTREAM FROM METER UNLESS APPROVED BY THE CI
TY
CROSS-CONNECTI
ON SPECIALIST.

9.BACKFLOW PREVENTERS SHALL BE REDUCED PRESSURE PRI


NCI
PLE (
RP)ASSEMBLY.(I
NSTALLED ABOVE GRADE AS CLOSE TO
METER AS POSSIBLE)BACKFLOW LOCATI
ON MUST BE APPROVED BY THE CROSS-CONNECTION CONTROL SECTI
ON OF THE
PUBLI
C UTILI
TIES DEPARTMENT.

SHEET 2 OF 2

RECOMMENDED BY THE CI
TY OF SAN DI
EGO
REVI
SION BY APPROVED DATE
STANDARDS COMMITTEE
CI
TY OF SAN DI
EGO - STANDARD DRAW I
NG
ORI
GINAL JC

REVI
SION BM A.OSKOUI 12/
03
2/
25/
16
COORDI
NATOR R.
C.E.56523 DATE
NOTES JS A.OSKOUI 12/
06 DUAL ABOVE GROUND M ETER
UPDATED KA J.NAGELVOORT DRAW I
NG
01/
12
WI
TH CI
TY BACKFLOW PREVENTER SDW -
119
NUMBER
UPDATED FG J.NAGELVOORT 02/
16
P
L TAMPER SW I
TCH AND AUTOMATI
C
RESET AS REQUI
RED BY FI
RE
DEPARTMENT
CI
cTY PRI
VATELY
c
MAINTAI
NED MAINTAI
NED

c
c

VALVE
SUPPORT 2
(TYP)
4" THI
CK CONCRETE SLAB

c
2 520-C-2500
c

36" MAX
c

12" MIN
SEE NOTE 3

c
f
c

c
36"

18" MI
N

c
c
c c
(TYP)
4 3 3
4
c

c c

c
c

FLOW THRUST BLOCK


c
PER SDW -151

ELEVATI
ON

P
L
CI
cTY PRI
VATELY
c
MAINTAI
NED MAINTAI
NED
c
30"

c
1 c
c
c
30"
c

PLAN

NOTES:
1. BACKFLOW PREVENTER ASSEMBLY SHALL BE TESTED UPON INSTALLATI
ON BY A CERTIFI
ED BACKFLOW ASSEMBLY
TESTER.CONTRACTOR SHALL PROVI
DE THE ENGINEER W I
TH W RI
TTEN TEST RESULTS COMPLETED BY A CERTI
FIED
BACK FLOW TESTER PRI
OR TO BACKFLOW PREVENTER ASSEMBLY'
S ACCEPTANCE.

2. ALL PI
PE BELOW GRADE SHALL BE W RAPPED AS REQUI
RED BY THE SPECI
FICATI
ONS.

3. CONCRETE PAD SHALL BE 2" ABOVE GRADE UNLESS I


NSTALLED I
N LAW N AREA W HERE I
T WI
LL BE AT 1" ABOVE GRADE.
SLOPE TO DRAI
N.

4. VALVE SUPPORTS AS REQUI


RED BY SPECI
FICATI
ONS.

5. LOCATI
ON SHALL BE APPROVED BY PUBLI
C UTI
LITI
ES DEPARTMENT,W ATER OPERATI
ONS DI
VISI
ON,METER/
BACKFLOW GROUP AND SHOW N
ON PLANS.

I
TEMS CALL OUT:

1 REDUCED PRESSURE PRI


NCI
PLE DETECTI
ON ASSEMBLY SHALL BE I
NCLUDED I
N THE LATEST EDI
TION OF THE "APPROVED
FOR SERVI
CE ISOLATI
ON CALIFORNIA PUBLI
C W ATER SYSTEM" I
SSUED BY THE STATE OF CALI
FORNI
A DEPARTMENT OF
HEALTH SERVI
CES.OFFICE OF DRI
NKING W ATER.

O
2 90 FLANGED CAST I
RON OR DUCTI
LE I
RON ELBOW (
TYP)
.

3 FLANGED DUCTI
LE I
RON SPOOL.BOTH ENDS SHALL BE FLANGED (
UNI
-FLANGE SHALL NOT BE USED)
. LEGEND ON PLANS

4 90O DUCTI
LE I
RON FLANGED ELBOW .
FS

RECOMMENDED BY THE CI
TY OF SAN DI
EGO
REVI
SION BY APPROVED DATE
STANDARDS COMMITTEE
CI
TY OF SAN DI
EGO - STANDARD DRAW I
NG
ORI
GINAL LC J.NAVARRO 6/
00

2/
25/
16
UPDATED KA J.NAGELVOORT 01/
12

UPDATED
BACKFLOW PREVENTER REDUCED COORDI
NATOR R.
C.E.56523 DATE
HM J.NAGELVOORT 02/
16

PRESSURE PRI
NCI
PLE DETECTOR ASSEM BLY DRAW I
NG
SDW -
120
FOR FI
RE SERVI
CE 3" AND LARGER NUMBER
REFER TO SDW-126 FOR INSTAllATION
OF DIRECTLY BURIED CABLES AND
CONDUIT.

(TYP)
SEE SDW-125

METALLIC PIPELINE

TEST STATION WIRING

APWA BLUE 6' WIDE TAPE


WITH WHITE LETTERING
CONTINUOUSLY IMPRINTED
/

CAUTION CAUTION
BURIED CATHODIC PROTECTION LINE BELOW
CALL 619-615-3525

DETAIL 1
BURIED TAPE
NOTES:
1. IN PAVED, CITY-OWNED ROADWAYS, THE REPAIR OF THE ROAD SURFACE SHALL BE PER APPLICABLE SDRSD
SDG-117 OR SDG-118. IN STATE HIGHWAYS, CONFORM TO APPLICABLE CALTRANS STANDARDS.

2. FOR LOCATION OF TEST STAllON, USE REGIONAL STD DWG WS-03. EXACT LOCAllON SHALL BE APPROVED BY CORROSION ENGINEER.
3. AT ROADWAYS, USE SDW- 129 AND AT UNDEVELOPED AREAS USE SDW- 127.

4. FOR INSTAllATION OF DIRECTLY BURIED CABLES & CONDUIT SEE SDW-126.

ITEMS CALL OUT:


0 CABLE AWG #8 COPPER ASTM B3 STRANDED ASTM B8 INSULATION ASTM D1248 TYPE 1, CLASS C, GRADE 5.

0 POLYETHYLENE WARNING TAPE. SEE DETAIL 1.

0 SAND: 50 SIEVE COMPLIES WILL SECTION 200-1.5.

REVISION BY APPROVED DAlE RECOMMENDED BY THE Ct1Y OF SAN DIEGO


STANDARDS COMMITTEE
CllY OF SAN DIEGO - STANDARD DRAWING
oil~
ORJGINAL BM A.OSKOUI 1W3
1/31/2012
NOTES BM AOSKOUI 12.{)6

UPDATED
AT-GRADE CATHODIC PROTECTION COORDINATOR R.C.E. 65271 DATE
KA . NAGELVOOR OV12
TEST STATION DRAWING
INSTALLATION FOR ROADWAYS NUMBER
SDW-121
NOTES:

1. Al l BOND CABLE SHALL


BE INSTALLED AT
MINIMUM LENGTH.

2. BOND CABLES SHALL


CROSS NOT BE INSTALLED
ACROSS INSULATING

OSD SPOOL
VALVE
CROSSING
JOINTS.
3. ONE ADDITONAL CABLE
SHALL BE REQUIRED
FOR PIPE DIAMETERS
FROM 36" TO 48" AND 2
/EXOTHERMIC WELD MORE FOR DIAMETERS
( SEE SDW-125 LARGER THAN 48".

4. WELD BEFORE APPLYING


INTERNAL COATING.

5. ONLY AT THE APPROVAL


OF CITY'S CORROSION
TEE BEND ENGINEER.

6. REFER TO SDW-116, FOR


~
~~ nY1'
EXOTHERMIC WEUJ SCRW PIPE BOND DETAIL
SEE rYNG SDW->25

~ '~ ~
BELL AND SPIGOT PIPE JOINT

~ 8
FLANGED VALVE
~

~ $
FLANGED OR MECHANICAL PIPE JOINT
~
BOND ACROSS FLANGES
SEE DETAIL A~_
ITEM CALL OUT:

~ ~ ~ 8 BOND CABLE: AWG #6


STRANDED ASTM B8
COPPER ASTM B3
FLEXIBLE COUPLING PIPE JOINT BOND WIRE Wll.UG INSULATED ASTM 01248
COATED WITH TYPE 1, CLASS C, GRADE 5.
BITUMASTIC
0 STEEL PLATE: 118" THICK.
WELD TO THE PIPE.

I
NON-MORTAR LINED /

~
+
NON-MORTAR LINED
~
DETAIL A
WIRE CONNECTION TO
FLANGE BOLT
SEE NOTE 5

REVISION BY APPROVED DAlE RECOMMENDED BY THE Ct1Y OF SAN DIEGO


STANDARDS COMMITTEE
CllY OF SAN DIEGO - STANDARD DRAWING
oil~
ORJGINAL BM A.OSKOUI 1W3
1/31/2012
NOlES BM A.OSKOUI 1006
COORDINATOR R.C.E. 65271 DAlE
UPDAlE KA . NAGELVOOR OV12 JOINT BONDING OF NON-WELDED
DRAWING
PIPE JOINTS & FITTINGS NUMBER
SDW-122
NOTES:
1. WHEREVER POSSIBLE,
INSULATING FLANGE
ASSEMBLIES SHOULD BE
ASSEMBLED PRIOR TO
INSTAllATION & TESTED
ELECTRICALLY USING GAS
ELECTRONIC TOOL OR
APPROVED EQUAL TO INSURE
DETAIL 1 THAT THE INSTAllATION IS
EFFECTIVE.
MECHANICAL
COUPLING 2. WRAP FLANGE ASSEMBLY AS
SHOWN WITH :>-PART PETRO-
LATUM TAPE PER AWWA C217.
3. INSULATING FLANGE BOLT
HOLE DIAMETER SHOULD BE
W" BIGGER THAN THE
INSULATING SLEEVE OD.
4. RECOMMENDED FLANGE
INSTAllATION PROCEDURE:

CLEAN & INSPECT PIPE


FLANGE FACES, APPLY NON-
CONDUCTIVE LUBRICANT TO
ALL THREADS.
DETAIL 2 INSTALL THE GASKET, AUGN
MECHANICAL COUPLING FLANGES & GASKETS.
& FLANGE VALVE
USE ALIGNMENT PIN IN TWO
DIAMETRICALLY OPPOSITE
BOLT HOLES.

INSERT INSULATING SLEEVES


INTO BOLT HOLES.

INSERT THE BOLT WITH BOTH


INSULATING WASHES.

TIGHTEN TWO DIAMETRICALLY


OPPOSITE BOLTS TO 30%
TOTAL TORQUE.

TIGHTEN ALL BOLTS TO 50%


AFTER REPLACING TWO
ALIGNMENT PINS WITH BOLTS
AND TO 100% OF FINAL
TORQUE VALUE.

ITEMS CALL OUT:

INSULATING FLANGE JOINTS,


0 PROTECTIVE COATING:
S-PARTS PETROLATUM AWWA
UNDERGROUND INSTALLATION
C217 OR APPROVED EQUAL.
0 TAPE: WRAPAROUND 3"
WIDE, 0.050' THICK.
CROSS LINKED POLYOLEFIN.
HEAT SHRINKABLE,
PRECOATED WITH HOT MELT-
ADHESIVE.

0 WASHER: INSULATING
EPOXY GLASS

8 GASKET: 1/8' THICK EPOXY


GLASS INSULATING
MATERIALS WITH NEOPRENE
SEALING ELEMENT.

0 SLEEVE: INSULATING EPOXY


GLASS. 11.32" THICK.
DETAIL 4 ID=BOLT DIAMETER + 1 /64.
INSULATING FLANGE JOINTS,
ABOVE-GROUND INSTALLATION 0 WASHER: STEEL, 1/8'
THICK.

REVISION BY APPROVED DAlE RECOMMENDED BY THE Ct1Y OF SAN DIEGO


STANDARDS COMMITTEE
CllY OF SAN DIEGO - STANDARD DRAWING
oil~
ORJGINAL BM A. OSKOUI 1W3
1/31/2012
NOlES BM A. OSKOUI 1206
COORDINATOR R.C.E. 65271 DATE
UPDATED KA • NAGELVOOR OV12 INSULATING FLANGE AND MECHANICAL
DRAWING
JOINTS EXTERNAL PROTECTION NUMBER
SDW-123
NPT THREAD
C
C

NOTES:

1. MOUNT W I
RE TERMI-
NATI
ONS AT 90 DEGREE
13/
32"/
DIA.HOLE ORI
ENTATION,FOR
MORE THAN 4-W I
RES,
6 MOUNT W I
RE TERMINATI
ONS
4 4" BELOW .
4"
5
3 2. OFFSET MACHI
NE SCREW
HEAD BY 3/
4" FROM
3 1 PI
PE EXTERI
OR W ALL

2
2 3. TAG W I
RE W I
TH LI
NE
NAME,PIPE SI
ZE,

C
C

MATERIALS AND STATION

C
C
C

C
USING SELF-ADHESIVE
C

LABELS.LABELS SHALL
C BE W RAPPED AROUND THE
L
I
NSULATION AND ENCASED
WITH CLEAR HEAT-SHRI
NK
PER SDW -131.

7 8

C
C

WI
RE LABEL
C
SEE SDW -131
DETAI
L1
EXPLODED VIEW OF
WIRE TERMI
NATION MATERI
ALS:

1 SCREW :MACHI
NE BRASS,
C

ROUND HEAD SLOTTED,


1" 1/
4" - 20T 11/
2" LONG
4 MAX
8
C

2 NUT:BRASS 1/
4" 20 THREADS

3 W ASHER:BRASS 1/
4"
C

4 W ASHER,I
NSULATI ON
NYLON,0.719" OD.
C
0.
281" I
D.0.
062" THI
CK NATURAL

o 5 LUG:OFFSET TONGUE
90 WIRE TERMINATI
ON
SOLDERNESS,COPPER.
SEE DETAI
L1
C

6 W ASHER:I
NSULATI
NG,
SHOULDER,NYLON
C

NATURAL,0.
260" OD.
0.
625" OD FLANGE,
0.
342" OD SHANK,
0.
065" FLANGE THK.
0.
270" SHANK THK.

7 CABLE:AW G #8,COPPER
ASTM B3,STRANDED
ASTM B8,INSULATED
ASTM D1248 TYPE 1,
CLASS C.GR.5.

8 PI
PE:4" DI
AMETER SCH
40 ASTM A53,
GALVANIZED

POST-MOUNTED TEST STATI


ON
WIRE TERMI
NATI
ON DETAIL

RECOMMENDED BY THE CI
TY OF SAN DI
EGO
REVI
SION BY APPROVED DATE
STANDARDS COMMITTEE
CI
TY OF SAN DI
EGO - STANDARD DRAW I
NG
ORI
GINAL A.OSKOUI 12/
03

UPDATED
2/
25/
16
KA J.NAGELVOORT 01/
12
COORDI
NATOR R.
C.E.56523 DATE
UPDATED HM J.NAGELVOORT 02/
16
POST -M OUNTED TEST STATI
ON
DRAW I
NG
WI
RE TERM I
NATI
ON DETAI
L SDW -
124
NUMBER
ORIGINAL COATING (TYP)

SEE NOTE 3

COAT THERMOWELD AND CABLE


SEE NOTE 9 (TYP)

DETAIL 1 DETAIL 2 DETAIL 3


TYPICAL CONNECTIONS OF N0.6 AWG TYPICAL CONNECTIONS TYPICAL CONNECTIONS OF N0.2 AWG
CABLE AND SMALLER CABLES OF N0.4 AWG CABLE CABLE AND LARGER CABLES

NOTES:

1. CLEAN AREA OF STEEL SURFACE APPROXIMATELY 2"x 2"


FOR EACH THERMOWELD CONNECTION. WIRE BRUSH FILE
AND SCRAPE TO OBTAIN SSPC-SP-5 WHITE METAL
SURFACE FINISH.
2. SELECT PROPER MOLD BASED ON STRUCTURE GEOMETRY.
ORIENTATION AND MATERIAL TYPE.
3. STRIP CABLE END AND TWIST TO FfT THERMOWELD
MOLD. CABLE SIZES LARGER THAN 6 AWG SHALL BE
THERMOWELDED BY TWISTING CONDUCTORS INTO GROUPS
APPROXIMATELY NUMBER 6 AWG CABLE SIZE. MINIMUM
SPACING BETWEEN WELDS WILL BE DETERMINED BY MOLD
GEOMETRY, NOMINALLY 3".
4. HOLD MOLD FIRMLY AGAINST PIPE WITH OPENING AWAY
FROM THE OPERATOR. IGNITE WITH FLINT GUN.
5. REMOVE ALL WELD SLAG, SPLATTER, SHARP EDGES
AND BURRS WITH CHIP HAMMER AND METAL FILE.
6. TEST STRENGTH OF CONNECTION BY LIGHTLY TAPPING
WITH 1 LB HAMMER, AND PULL WITH 5 LB FORCE
PIPE WALL ON CABLE.
EXOTHERMIC CONNECTION DETAIL 7. WIPE PIPE SURFACE WITH CLEAN, OIL FREE RAGS TO
REMOVE ANY LOOSE DUST.
8. PRIME CLEANED SURFACE WITH APPROVED PRIMER.
9. COAT THERMOWELD AND 6" OF CABLE TAIL WITH
COMPATIBLE COATING, SUCH THAT ALL CORNERS ARE
FILLED. THE COATING SHALL EXTEND FOR AT LEAST 2"
AROUND THE THERMOWELD AREA.
10. THERMOWELD CARTRIDGE SIZE SHALL BE COMPATIBLE TO
STEEL MATERIALS. MULTIPLE POWDER CARTRIDGE
CHARGERS SHALL NOT BE USED. IF A THERMOWLED MUST
EXOTHERMIC CONNECTION SECTION
BE REPEATED, A NEW PIPE SURFACE MUST BE PREPARED
AT LEAST 3" FROM THE ORIGINAL WELD ATTEMPT.
CABLE STRAND DETAILS MORE THAN ONE WELD ATTEMPT ON THE SAME SPOT
SHALL NOT BE PERMITTED.
CABLE NO. OF NO.OF EXOTHERMIC GROUPS CABLE STRANDS
11. IN NON-CONCRETE UNED PIPES, ALL EXOTHERMIC WELDS
SIZE STRANDS PER CABLE CONNECTION PER GROUP
SHALL BE MADE IN A STEEL PAD.
8 19 1 19
7 7 ITEMS CALL OUT:
6 1

4
19
7
2
19
3--4
8 CABLE: AWG SIZE, ASTM 83138
ASTM [)...1248, 1YP1 1, CLASS C, GR.5 INSULATION

2
19
7
3
1G-9
3-2-2 G SLEEVE: ADAPTER

19 7~
{':;\ APPROVED PRIMER & WELD CAP OR MORTAR OVER
V WELD LOCATION

REVISION BY APPROVED DATE RECOMMENDED BY THE Ct1Y OF SAN DIEGO


STANDARDS COMMITTEE
CllY OF SAN DIEGO - STANDARD DRAWING
oil~
ORJGINAL A. OSKOUI 1W3
1/31/2012
UPDATED OV12
COORDINATOR R.C.E. 65271 DATE
EXOTHERMIC WELDING OF CABLES
DRAWING
AND COATING OF WELDING NUMBER
SDW-125
/ ,r0 I r"- SEE NOTE 2

·_t·
·
.. . . . , ._:..--~
r
I ---- BACKFILL
~

I \
.. ......,..,.......:------1---L-

.:Ct DRY SAND CUSHION.

~- ~EN0~2
DIRECT BURIED
CABLE(S) OR CONDUIT
J
2

CABLE(S) AND CONDUIT


TRENCH SECTION

NOTES:

1. MATERIAL: 8 POLYETHYLENE WARNING TAPE, REFER TO DETAIL 1 ON SDW-121.

8 SAND: 50 SIEVE COMPUES WITH 200--1.5

2. IN PAVED. CITY-QWNED ROADWAYS, THE REPAIR OF THE ROAD SURFACE SHALL BE PER
APPUCABLE SDG-117 OR SDG-118. 1N STATE HIGHWAYS, CONFORM TO APPUCABLE
CALTRANS STANDARDS.

3. CLEAN SHARP STONES AND RUBBLE FROM THE BOTTOM OF DITCH.

REVISION BY APPROVED DATE RECOMMENDED BY THE CI1Y OF SAN DIEGO


STANDARDS COMMITTEE
CllY OF SAN DIEGO - STANDARD DRAWING
oil~
ORJGINAL BM A. OSKOUI 1W3
1/31/2012
NOTES BM A. OSKOUI 1W3
COORDINATOR R.C.E. 65271 DATE
UPDATED KA ~. NAGELVOOR 01112 INSTALLATION OF DIRECTLY BURIED
DRAWING
CABLES OR CONDUIT NUMBER
SDW-126
WIRE TERMINATION, SEE SDW-124
WIRE IDENTIFICATION, SEE SDW-131

NOTES:

1. PLACE TWO DECALS,


ONE FACING ROADWAY.

2. FILL THE PIPE WnH


SEE NOTE 3 50 SIEVE SAND FROM
BOTTOM OF CONCRETE
4'-0" FOOTING TO 12" ABOVE
GRADE.

3. THIS POST-MOUNTED
EXIST. GRADE STATION IS FOR USE
SAND
SEE NOTE 2 ONLY IN AREAS WnH
NO VEHICULAR TRFFIC.

ITEM CALL OUT:

f:\ CABLE: AWG #8


\.V COPPER ASTM 83
STRANDED ASTM 68
INSULATION ASTM
D 1248 TYPE 1,
CLASS C, GR. 5.

(;:\ FOOTING: CONCRETE


\.V 12" DIA, SSPWC
SLACK (lYP) 295-C-17.

(;:\ PIPE: 4" DIAMETER,


\V SCH 40, ASTM A 53
GALVANIZED.

G)oECAL:SEE
SDW-132.

(";\ CAP: THREADED


\V4" DIAMETER
GALVANIZED.

METALLIC PIPEUNE

POST-MOUNTED TEST STATION

REVISION BY APPROVED DATE RECOMMENDED BY THE CI1Y OF SAN DIEGO


STANDARDS COMMITTEE
CllY OF SAN DIEGO - STANDARD DRAWING
oil~
ORJGINAL BM A. OSKOUI 1W3
1/31/2012
NOTES
UPDATED
ABOVE GRADE CATHODIC PROTECTION COORDINATOR R.C.E. 65271 DATE
OV12
TEST STATION INSTALLATION DRAWING
FOR UNDEVELOPED AREAS NUMBER
SDW-127
SEE PLAN
FOR LETTERING 9 11.1"

3 :w·

j_
TEST BOX COVER ISOMETRIC
TEST BOX COVER PLAN

14'

NOTES:

1. COVER WEIGHT: 12 LB.

2. BODY WEIGHT: 58 LB.

3. THE COVER SHALL HAVE


CASTED MARKING IN 11.1"
HIGH RAISED LETTERS.

11 11.1" ITEM CALL OUT:


...
•,. CD COVER: ASTM A 48
CLASS 30.

. ··.

12"
-I
TEST BOX ISOMETRIC SECTION

REVISION BY APPROVED DAlE RECOMMENDED BY THE CITY OF SAN DIEGO


STANDARDS COMMITTEE
CllY OF SAN DIEGO - STANDARD DRAWING
oil~
ORJGINAL BM A. OSKOUI 1W3
1/31/2012
NOlES A. OSKOUI 1206
COORDINATOR R.C.E. 65271 DAlE
UPDAlED OV12 AT-GRADE
DRAWING
CONCRETE TEST BOX NUMBER
SDW-128
WIRE I
DENTIFI
CATI
ON (
TYP)
PER SDM-105
TEST BOX COVER
PER SDW -128

SEE NOTE 1 C 5" MI


N
1 C

C
C 2"
2

2"

C
C

C
NOTES:
C

C
4"
1.SLOPE CONCRETE PAD
AW AY FROM COVER.

C
TEST BOX
2.FOR CONTINUATION OF
PER SDW -128
CABLES,REFER TO SDW -127
C
OR SDW -130,AS APPLI
CABLE.
C

I
TEMS CALL OUT:
C

1 CONCRETE:2'X 2'
X 4" THK.PER SSPW C
330-C-23.

2 REI
NFORCI
NG FABRI
C
NATI
VE SOI
L 4" X 4" GAUGE 10
GRAVEL WIRE.
C

3 CABLE:REFER TO
NOTE 2.
18" SLACK

3 SEE NOTE 2

TEST STATI
ON SECTI
ON

RECOMMENDED BY THE CI
TY OF SAN DI
EGO
REVI
SION BY APPROVED DATE
STANDARDS COMMITTEE
CI
TY OF SAN DI
EGO - STANDARD DRAW I
NG
ORI
GINAL A.OSKOUI 12/
03

2/
25/
16
UPDATE KA J.NAGELVOORT 01/
12
AT -GRADE CATHODI C COORDI
NATOR R.
C.E.56523 DATE
UPDATE HM J.NAGELVOORT 02/
16
PROTECTION TEST STATION DRAW I
NG

WI
RI NG DIAGRAM FOR ROADW AYS SDW -
129
NUMBER
GRADE LEVEL
SEE NOTE 1

C
C

(MIN)
12"
2'- 0"
(MIN)

C
C
C

C
C A
C TSOTATTION
EST

SEE NOTE
2,3,& 4.
C

18" SLACK (
TYP)

C
3
NOTES:

1 (
TYP)

1. I
N PAVED,CI TY OW NED
ROADW AYS,THE REPAIR
I
NSULATI
NG FLANGE
C OF THE ROAD SURFACE
SHALL BE PER APPLI
-
CABLE STANDARD
C
DRAW I
NGS.I
N STATE
HIGHW AYS,CONFORM
TO APPLICABLE CALTRANS
METALLI
C PI
PE STANDARD.
C A

ON,OF
2. FOR LOCATI
SECTI
ON ON,USE
TEST STATI
ONAL STD DW G
REGI
ON
W 15.EXACT LOCATI
2'- 6"

2'- 6"

SHALL BE APPROVED
1'- 7"

1'- 7"

ON ENGR.
BY CORROSI

C C C C 3. USE APPLI
CABLE TEST
C C C C

NG FOR
ON DRAW I
STATI
UNDEVELOPED AREAS

1 18" SLACK (
TYP)
C
(
TYP)
C

A1 A2 B1 B2
I
TEM CALL OUT:
C

1 CABLE:AW G #2
COPPER ASTM B3,
STRANDED ASTM B8,
NSULATED PER
I
ASTM D1248,TYPE 1
CLASS C,GRADE 5.
C

EXOTHERMI C W ELD (
TYP)
PER SDW -125
2 POLYETHYLENE W ARNING
I
NSULATI
NG JOI NT KI
T
TAPE PER SDW -121.
PER SDW -123

ELEVATI
ON A - A 3 EVE
SAND:50 SI

RECOMMENDED BY THE CI
TY OF SAN DI
EGO
REVI
SION BY APPROVED DATE
STANDARDS COMMITTEE
CI
TY OF SAN DI
EGO - STANDARD DRAW I
NG
ORI
GINAL A.OSKOUI 12/
03

2/
25/
16
UPDATED KA J.NAGELVOORT 01/
12
COORDI
NATOR R.
C.E.56523 DATE
UPDATED HM J.NAGELVOORT 02/
15
I
NSULATI
NG FLANGE FOUR -W I
RE
DRAW I
NG
TEST STATI
ON I
NSTALLATI
ON SDW -
130
NUMBER
)
WIRE LABEL DETAIL STATION LABEL
SEE NOTE 1

WIRE LABEL

CPTS# (CATHODIC PROTECTION TEST STATION NUMBERING)

CPTS#1, 2, 3, ......N

LEGEND
NOTES:
PIPE MATERIAL

CCI - COATED CAST IRON 1. CABLES SHALL BE TAGGED


COl - COATED DUCTILE IRON USING TIMES ROMAN 10
SCRC - STEEL CYLINDER REINFORCED CONCRETE POINT FONT.
PSCS - PRE-$TRESSED CONCRETE-$TEEL CYLINDER
RCCP - REINFORCED CONCRETE CYUNDER PIPE CNQ STEEL) 2. TEXT SHALL BE PRESENTED IN
SCRW- STEEL CYLINDER REINFORCED ROD WRAPPED THE FOLLOWING ORDER:
CMLC- CEMENT MORTAR UNED-COATED STEEL CYLINDER
CMLCT- CEMENT MORTAR LINED-COATE[)...TAPED STEEL CYLINDER * CPTS#
CSTL - COATED STEEL CYLINDER
* TYPE OF INSTALLATION
TYPE OF INSTALLATION * STATIONING

2WTS - 2-WIRE TEST STATION * FACILITY NAME


EXAMPLE: CPTS#1, 2WTS, 180+00, 30, OTAY 2, CSTL
* PIPE MATERIAL
4WIJTS - 4-WIRE INSULATING JOINT TEST STATION
EXAMPLE: CPTS#2, 4WIJTS, 180+00, 30, OTAY 2, CSTL, NORTH OR * WIRE DIRECTIONAL
SOUTH OR EAST OR WEST FOR WIRE TAGS ORIENTATION

6WTS -~WIRE TEST STATION NORTH


EXAMPLE: STRUCTURE#1 - CPTS#3, 6WTS, 180+00. 30, OTAY 2, CSTL
NORTH OR SOUTH OR EAST OR WEST FOR WIRE TAGS SOUTH
SmUCTURE#2 - CPTS#3, 6WTS, 120+60, 24, MIOCITY, SCRW
NORTH OR SOUTH OR EAST OR WEST FOR WIRE TAGS EAST
SmUCTURE#3 - CPTS#3, 6WTS, 101 + 25, 54, TROJAN, RCCP,
NORTH OR SOUTH OR EAST OR WEST FOR WIRE TAGS • WEST

CTS -CURRENT TEST STATION 3. PLACE SLEEVE AFTER


EXAMPLE: CPTS#10, CTS, 180+00, 200 FT., OTAY 2, CSTL, ATIACHMENT OF LABEL
NORTH OR SOUTH OR EAST OR WEST FOR WIRE TAGS TO CABLE.

CSGTS - CASING TEST STATION


EXAMPLE: CPT$#12, CSGTS, 180 + 00, 30, OTAY 2, CSTL
NORTH OR SOUTH OR EAST OR WEST FOR WIRE TAGS ITEM CALL OUT:

ASTA -ANODE STATION CABLE: AWG ASTM B8 & B3

BSTA
EXAMPLE: ANODE#1, 2, 3, ......N FOR ANODE WIRES;

- BOND STATION
30, OTAY 2, CSTL, 180+00, CPTS#6 FOR STRUCTURE WIRE

EXAMPLE: CPTS#18, BSTA, 30, OTAY 2, CSTL, 180+00;


54, OTAY 3, SCRW, 65+20
ffi LABEL: FILE FOLDER,
SELF ADHESIVE WHITE
2-3' X 3 7/16'.
{,';\SLEEVE: HEAT SHRINK,
FXSTA -FOREIGN CROSSING STATION V ADHESIVE LINED POLYOLEFIN,
EXAMPLE: CPTS#4, FXSTA; 30, OTAY 2, CSTL, 180+ 00; 24 SDGE CLEAR THIN WALL TUBING.

REVISION BY APPROVED DAlE RECOMMENDED BY THE CITY OF SAN DIEGO


STANDARDS COMMITTEE
CllY OF SAN DIEGO - STANDARD DRAWING
oil~
ORJGINAL A. OSKOUI 1W3
1/31/2012
NOlES BM A. OSKOUI
COORDINATOR R.C.E. 65271 DAlE
UPDAlED KA ~. NAGELVOOR OV12 WIRE
DRAWING
IDENTIFICATION NUMBER
SDW-131
II
~it;~
PUBLIC UTILITIES
Water &Wastewater
,,~

Corrosion Control

UNDERGROUND
FONT SIZE
CABLES
IN THE SEE NOTE 2
VICINITY

w NOTES:

1. 1" TEXT BOLD

A
FONT SIZE
SEE NOTE 1 2. V4" TEXT BOLD

20"
R 1
ITEM CALL OUT:

N 8 DECAL: APWA BLUE,


WITH WHITE

I REFLECTIVE LETTERS.
DECAL MATERIAL SHALL
BE UV RESISTANT
PREMIUM GRADE CAST

N VINYL SHEETING WITH


AGGRESSIVE ADHESIVE
AND UNDER PROTECTIVE
LAMINATE.

BEFORE FONT SIZE


DIGGING SEE NOTE 2
Call
FONT SIZE
619-515-3525
SEE NOTE 2

DECAL ELEVATION

REVISION BY APPROVED DATE RECOMMENDED BY THE CITY OF SAN DIEGO


STANDARDS COMMITIEE
CITY OF SAN DIEGO - STANDARD DRAWING
dl~
ORIGINAL BM A. OSKOUI IW3
1/31/2012
NOTES BM A. OSKOUI IW6
COORDINATOR R.C.E. 65271 DATE
UPDATED KA ~. NAGELVOOR OVI2 POST· MOUNTED CATHODIC
DRAWING
PROTECTION WARNING DECAL NUMBER
SDW-132
I ANODES
I I INSULATING JOINTS (IJ)
I
IJ1 ~ DIELECTRICALY INSULATED FLANGE JOI NT
AV
® Vertical AH [TI Horizon t a l
Where X: IJ2 --If--- NON-DIELECTRICALY INSULATED FLANGE JOINT
AV1
AV2
AV3
-
-
-
AI (ALUM I NUM)
Pm (POLYMERIC)
Pt (PLATINUM)
AH1
AH2
-
-
AI (ALUMINUM)
Pm (POLYMERIC)
Pt ( PLA TI NUM)
IJ3 -St- FLANGED INSULATING PROTECTIVE DEVICE
AH3 -
AV4 - Fe (SCRAP IRON) AH4 - Fe (SCRAP IRON) IJ4 --4P- BONDED INSULATED FLANGE JOI NT

~
AVS - Gr (GRAPHITE) AHS - Gr (GRAPHITE)
AV6 - Ci (HS C IRON) A H6 - Ci (HS C IRON) IJS INSU LATED FLAN GE W/ADJUSTABLE RESISTANCE
AV7 - Zn (Zinc) AH7 - Zn (ZINC)
AVB - Mg (MAGNESIUM) AHB - Mg (MAGNESIUM) IJ6 ---MI- GATE VALVE INSULATED FLANGE JOINT
AV9 - MMO (MIXED METAL AH9 - MMO (M IXED METAL
OXIDE) OXIDE) IJ7

IJB
__.___
---MI-- BUTTERFLY VALVE INSULATED FLANGE JOINT

MOV INSULATED FLANGE JOINTS


I CABLES (CB)
I - - { }---
CB1 -- t -- POSITIVE
IJ9 MONOLITHIC INSULATING JOI NT
CB2 c:::I:J POSITIVE IN CONDUIT
IJ10 Q BONDED MECHANICAL COUPLING
CB3 -- - -- NEGATIVE
CB4 ~
NEGATIVE IN CONDUIT IJ11 ----¢--- DIELECTRICALY INSULATED UN I ON

I CABLE CONNECTION (CC)


I
IJ12 ---4XP-- BONDED DIELECTRIC UN I ON

CC1 .___ EXOTHERMIC WELD


IJ13
t3- DIELECTRICALY INSULATED COUPLING

CC2 .L SPLICE TEE


I RECTIFIERS (RE)
I
CC3
- STRAIGHT SPLICE
RE1
tB PEDESTAL MOUNTED

I CASING (CS)
I RE2
JcB POST MOUNTED

CS1 ? ------ ~ UNPROTECTED CASING


I REFERENCE CELL (RC)
I
CS2
t - - - .I PROTECTED CASING
RC1 § COPPER-COPPER SULFATE CELL

I ANODE GROUNDBEDS (AG)


I RC2
® 99.9% HIGH PURITY ZINC CELL

AG1

AG2 ....+- DEEP ANODE WELL

POLYMERI C OR PLATINUM
RC3

I
6 SILVER-SILVER CHLORIDE CEL L

TEST STATION (TS)


I
AG3
• • • CONVENTIONAL - VERTI CAL

I
AG4
i i i
CONVENTIONAL - HORIZONTAL

JUNCTION BOX (JB)


I
+
ABOVE GRADE
+
AT GRADE
WHERE X:

JB cx:::J WHERE X:
TS1 - lA-FREE COUPON
JBN -NEGATIVE CABLES TS2 - 2-WIRES STATION
JBP - POSITIVE CAL BES TS3 - FOREIGN CROSSING STATION
JBR - RESISTOR TS4 - 4- WIRES STATION
JBD - DIODE TSS - CALIBRATING STATION
JBA - GALVANIC ANODE SHUNTS TS6 - 6-WIRES STATION
JBI - IMPRESSED ANODE SHUNTS TS7 - INTERFERENCE CURRENT
JBS - CABLE SPLICE TSB - 8-WIRES STATION
TS9 - ELECTRICAL RESISTANCE PROBE

REVISION BY APPROVED DAlE RECOMMENDED BY THE Ct1Y OF SAN DIEGO


STANDARDS COMMITTEE
CllY OF SAN DIEGO - STANDARD DRAWING
oil~
ORJGINAL BM A.OSKOUI 1W3
1/31/2012
NOlES BM A.OSKOUI 1206
COORDINATOR R.C.E. 65271 DAlE
UPDAlED KA ~- NAGELVOOR OV12 SYMBOLS
DRAWING
CATHODIC PROTECTION NUMBER
SDW-133
A

B
B

PLAN VI
EW

C
15 3/
4" MI
N C

C
C
14" C
25 1/
4" MI
N C

POLYMER CONCRETE

2"
COLLAR C
23 1/
2" C
C

C
3/
16" THI
CK
12" MIN

FI
BERGLASS BODY 3 1/
2"
C

C
C
C

C
C 4" (
BOTH ENDS)
4" C
C

(
BOTH ENDS) C
27 1/
2" - 29 1/
2"
11/
2"MI
N C C

C
18 1/
8" C

11/
2"MI
N

SECTI
ON A-A SECTI
ON B-B

NOTES:
1. METER BOX COLLAR AND COVER SHALL BE OF POLYMER CONCRETE
REI
NFORCED W I
TH CONTINUOUS LAYERS OF W OVEN FI
BERGLASS.

2. BOX AND COVER SHALL W I


THSTAND AASHTO H-20 (
ASTM C857)
.

3. FOR COVER DETAI


L WI
TH DROP I
N READER LI
D,SEE SDW -136.

4. SEE SDW -137 FOR I


NSTALLATI
ON PROCEDURE.

RECOMMENDED BY THE CI
TY OF SAN DI
EGO
REVI
SION BY APPROVED DATE
STANDARDS COMMITTEE
CI
TY OF SAN DI
EGO - STANDARD DRAW I
NG
ORI
GINAL SS A.OSKOUI 12/
03

2/
25/
16
UPDATED KA J.NAGELVOORT 01/
12
COORDI
NATOR R.
C.E.56523 DATE
UPDATED HM J.NAGELVOORT 02/
16 POLYM ER CONCRETE W ATER
DRAW I
NG
M ETER BOX FOR 1" W ATER SERVI
CE SDW -
134
NUMBER
A

B B

PLAN VI
EW

C
17 1/
4"MI
N C

C
15 3/
8"MI
N C
POLYMER CONCRETE C
311/
2"MI
N C

2"
COLLAR
C

C
29 5/
8" C
C

3/
16" THI
CK
C

C
FI
BERGLASS BODY
16" MIN

3 1/
2"
C

C
C
C

4" (
BOTH ENDS)
4" C
C

(
BOTH ENDS) C
C
34 1/
2" C

C
C 20 1/
4" C
11/
2"MI
N

11/
2"MI
N SECTI
ON A-A SECTI
ON B-B

NOTES

1. METER BOX COLLAR AND COVER SHALL BE OF POLYMER CONCRETE REI


NFORCED
WI
TH CONTINUOUS LAYERS OF W OVEN FI
BERGLASS.

2. BOX AND COVER SHALL W I


THSTAND AASHTO H-20 (
ASTM C857)
.

3. FOR COVER DETAI


L WI
TH READER LI
D,SEE SDW -136.

4. SEE SDW -137 FOR I


NSTALLATI
ON PROCEDURE.

RECOMMENDED BY THE CI
TY OF SAN DI
EGO
REVI
SION BY APPROVED DATE
STANDARDS COMMITTEE
CI
TY OF SAN DI
EGO - STANDARD DRAW I
NG
ORI
GINAL SS A.OSKOUI 12/
03

2/
25/
16
UPDATED KA J.NAGELVOORT 01/
12
COORDI
NATOR R.
C.E.56523 DATE
UPDATED HM J.NAGELVOORT 02/
16 POLYM ER CONCRETE W ATER
M ETER BOX FOR 2" W ATER SERVI
CE DRAW I
NG
SDW -
135
NUMBER
~
2ND LIFT PIN FOR-- t--
2" METER BOX ONLY
I
--,,
1=1
·'·
·"·>1
'\D>
o I• xx
oo
I
LJ
'
cncn
'7
a: a:
't>' wW
LOGO (SO CITY WATER)-- t---~-'
,--- tutu
:::!::::!:
'7
'. ~N
t>
a: a:
<7 oo
LLlL
'.
~~
t>
t>
t>.
LIFT PIN-- r------- . C')Ol

~:
--~_l
NN

I '7·

. ~1 .
SECTION A-A

SOLID COVER FOR TRAVELED WAY

NOTES:

1. LID SHALL WITHSTAND AASHTO H-20 (ASTM 857).

2. LID SHALL HAVE NON-SKID SURFACE.

SHEET 1 OF 2

REVISION BY APPROVED DATE RECOMMENDED BY THE CITY OF SAN DIEGO


STANDARDS COMMITTEE
CITY OF SAN DIEGO -STANDARD DRAWING

~
ORIGINAL SS A. OSKOUI 1W3
612312014
UPDATED KA ~· NAGELVOORT OV12
COORDINATOR R.C.E. 56523 DATE
UPDATED BB ~· NAGELVOORT 06114
METER BOX POLYMER CONCRETE COVER DRAWING
NUMBER
SDW-136
,---
2ND LIFT PIN FOR - - - • - - - - ~
2" METER BOX ONLY --, , v-- LOGO (SD CITY WATER) ·17
'\ I xx
~/
o I
, oo
(()(()
I>
,, a: a:
LLJLLJ
POLYMER CONCRETE- ---r;::::=:=- 314" FOR 1" II-· tiJtli
~~
READER LID METER BOX
~N
] 7 112" FOR 2" a: a:
METER BOX
v oo
u_LL

LIFT P I N -

A __ _j

13 314" FOR 1" METER BOX


15 W" FOR 2" METER BOX SECTION A-A

DROP IN COVER (OUTSIDE TRAVELLED WAY)

NOTES:

1. LID SHALL WITHSTAND AASHTO H-10 (ASTM C857-85).

2. LID SHALL HAVE NON-SKID SURFACE.

3. IF LID IS MANUFACTURED BY CDR, READER SHALL BE 6" X 9".

SHEET 2 OF 2

REVISION BY APPROVED DATE RECOMMENDED BY THE SAN DIEGO


REGIONAL STANDARDS COMMITIEE
CITY OF SAN DIEGO - STANDARD DRAWING
ORIGINAL

UPDATED
SS A. OSKOUI

KA J. NAGELVOORT
1:W3

OV12
~ 612312014
COORDINATOR R.C.E. 56523 DATE
UPDATED BB J. NAGELVOORT 06114
METER BOX POLYMER CONCRETE COVER DRAWING
NUMBER
SDW-136
560--C-3250
CONCRETE
SEE NOTE 1

1 SACK SLURRY*

NOTES:

1. REFER TO SDG-107 NOTE 3 FOR CURING REQUIREMENTS.

2. THIS DRAWING SHALL BE USED IN AREAS SUBJECT TO HEAVY


TRAFFIC INCLUDING DRIVEWAYS, PARKING LOTS AND ALLEYS.

3. (*) FOR METER BOX OUTSIDE TRAVEL WAY, USE SAND SE 30.

REVISION BY APPROVED DATE RECOMMENDED BY THE CITY OF SAN DIEGO


STANDARDS COMMITIEE
CITY OF SAN DIEGO - STANDARD DRAWING
dl~
ORIGINAL SS A. OSKOUI 12'03
1/31/2012
UPDATED KA . NAGELVOOR OV12
COORDINATOR R.C.E. 65271 DATE
TRAFFIC RATED COVER AND
DRAWING
METER BOX INSTALLATION NUMBER
SDW-137
I
TEMS CALL OUT:

1 1" W ATER SERVI


CE

2 1" CURB STOP

3 MAI
N CONNECTI
ON X MULTI
PLE BRANCH CONNECTI
ON
1
4 BRASS COUPLI
NG OR 45 DEGREE ELBOW

C
SHOW N ROTATED 5 BRASS NI
PPLE - 4" MI
N.LENGTH
90 DEGREES
FOR CLARI
TY 6 BRASS 45 DEGREE ELBOW

7 CAST I
RON CAP
2

C
8 ASBESTOS CEMENT PI
PE
C

9 THRUST BLOCK PER SDW -151

SERVI
CE CONNECTI
ON

NOTE: NI
PPLE LENGTHS TO BE SUFFI
CIENT TO ALLOW
C 3 SERVICE CONNECTION TO CLEAR THRUST BLOCK.

4
C

5
SERVI
CE MAI
N CONNECTI
ON
C

MAI
N CONNECTI
ON CONNECTI
ON I
TEM 5

2 11/
4"

6 3 11/
2"

4 2"
C

7
6 2 1/
2"

9 8 3"
C

5
C
C

A A
7
C

DRI
LL AND TAP TO STD.THREAD

C
SECTI
ON A-A
8

ELEVATI
ON

RECOMMENDED BY THE CI
TY OF SAN DI
EGO
REVI
SION BY APPROVED DATE
STANDARDS COMMITTEE
CI
TY OF SAN DI
EGO - STANDARD DRAW I
NG
ORI
GINAL JS A.OSKOUI 12/
06

UPDATED
2/
25/
16
KA J.NAGELVOORT 01/
12
COORDI
NATOR R.
C.E.56523 DATE
UPDATED HM J.NAGELVOORT 02/
16
M ULTI
PLE SERVI
CE ASSEM BLY
DRAW I
NG
DEAD END M AI
N SDW -
138
NUMBER
0
0
T
a:
w
--------~~----~
~ I I
I I

A A

ELEVATION

Q FIELD PLACED
6"
w MORTAR UNING
a. MAX STEEL TROWEL FINISH
a:

gu 2" X 4" #12


MIN GALVANIZED WELDED
HOLD SHOP COATING WIRE FABRIC
BACK 6" MIN

T
MORTAR POURED IN FIELD
SECTION A- A

NOTES:

CONTRACTOR SHALL PROVIDE HANDHOLES AS REQUIRED TO COMPLETE THE WORK

REVISION BY APPROVED DATE RECOMMENDED BY THE Ct1Y OF SAN DIEGO


STANDARDS COMMITTEE
CllY OF SAN DIEGO - STANDARD DRAWING
ORIGINAl.

UPOATEO
JS

KA
A. OSKOUI

• NAGELVOOR
1W6

OV12
oil~ 1/31/2012
COORDINATOR R.C.E. 65271 DATE

SPLIT BUTT STRAP DRAWING


NUMBER
SDW-139
C CI
TY C PRI
VATELY
C C
MAI
NTAI
NED MAI
NTAI
NED
W ET UTI
LITY ROOM (
W UR)
(
SEE NOTE 1ON SHEET 2)

ACCESS
DOORS OR
GATE W I
TH
KNOX BOX
7

6
(
STREET LEVEL)
5 7

10
METER BOX &
ASSEMBLY PER 9
9
CITY SDW - 149,
150 4

VALVE 8
8

8
8

FLOW
C

24" MAX
12" MIN
FLOW

FI
RE SERVI
CE
POLYETHYLENE FOAM TYP
CONNECTI
ON & PROPERTY
ASSEMBLY SI
DE
PER SDW -118 I
SOLATI
ON

W ATER SERVI
CE VALVE

CONNECTI
ON

PER SDW -149,

SDW -150

3 3
1
C

BUI
LDI
NG BASEMENT

CI
TY MAI
N

SHEET 1 OF 2

I
TEM I
TEM
SI
ZE AND DESCRI
PTI
ON SI
ZE AND DESCRI
PTI
ON
NO NO

1 CONCRETE THRUST BLOCK.SEE SDW -151 6 APPROVED RPDA


o
2 90 DUCTI
LE I
RON FLANGE ELBOW 7 FLANGED OS&Y RW GV W I
TH HAND W HEEL
FLANGED DUCTI
LE I
RON PIPE (
PROPERLY
3
8 BRASS OR COPPER PI
PE (
PROPERLY SUPPORTED
SUPPORTED OR RESTRAI
NED)
OR RESTRAI
NED)
4 12'
'FLANGED DUCTI
LE I
RON SPOOL 9 UNI
ONS
5 APPROVED BACKFLOW ASSEMBLY W I
TH FLEX APPROVED RP (
ALL Y-STRAI
NERS OR PRV TO BE
10
COUPLER CONNECTORS FOR SEI
SMIC REQUIREMENTS I
NSTALLED DOW NSTREAM OF BACKFLOW ASSEMBLY)

RECOMMENDED BY THE CI
TY OF SAN DI
EGO
REVI
SION BY APPROVED DATE
STANDARDS COMMITTEE
CI
TY OF SAN DI
EGO - STANDARD DRAW I
NG
ORI
GINAL BB J.NAGELVOORT 10/
14

7/
21/
15
UPDATED FG J.NAGELVOORT 07/
15
COORDI
NATOR R.
C.E.56523 DATE
BACKFLOW PREVENTERS
DRAW I
NG
W ET UTI
LITY ROOM I
NSTALLATI
ON SDW -
141
NUMBER
NOTES:

1. CI
TY W ATER METERS I
NSTALLED W I
THI
N W ET UTI
LITY ROOM (
W UR)
,REFER TO SDW -157 FOR
SEPARATI
ON OF MAI
NTENANCE RESPONSI
BILI
TIES.

2. THE W UR MUST BE APPROVED BY THE PUBLI


C UTI
LITI
ES & DEVELOPMENT SERVI
CES DEPARTMENTS.

3. THE W UR APPLI
ES ONLY TO BUI
LDI
NGS BUI
LT AT THE PROPERTY LI
NE W I
TH ZERO SETBACK.

4. I
N UTI
LIZI
NG THE W UR OPTI
ON,THE BUI
LDI
NG OW NER AGREES TO REQUI
REMENTS OF SDW -141.

5. PROVI
DE ACCESS I
NTO THE W UR BY STORI
NG KEYS W I
THI
N A KNOX KEY BOX.

6. W UR'
s MAY CONTAI
N BACKFLOW PREVENTI
ON EQUI
PMENT OR CI
TY W ATER METERS (
EASEMENT REQUI
RED)
.

7. THE W UR MUST BE DESI


GNED AT STREET LEVEL,ADJACENT TO EXTERI
OR W ALL OF THE BUI
LDI
NG,AND ALLOW
ACCESS FROM STREET LEVEL THROUGH THI
S EXTERI
OR W ALL.

8. ACCESS DOORS OR GATES MUST PROVI


DE DRAI
NAGE FOR FULL DI
SCHARGES AW AY FROM THE BUI
LDI
NG.

9. A CONCRETE FLOOR PLAN W I


TH FLOOR DRAI
NS MUST PROVI
DE DRAI
NAGE FOR I
NTERMEDI
ATE DI
SCHARGES.

10. MOI
STURE BARRI
ERS SHALL BE APPLI
ED TO ALL EXPOSED AREAS W I
THI
N THE W UR TO PREVENT DAMAGE.

11. PROVI
DE ADEQUATE CLEARANCE AROUND THE EQUI
PMENT TO ALLOW FOR TESTI
NG AND MAI
NTENANCE.

12. THE W UR MUST BE FI


RE RATED FOR ONE HOUR PER THE FI
RE & RESCUE DEPARTMENT.

13. I
DENTI
FY THE TYPE OF EQUI
PMENT CONTAI
NED W I
THI
N THE W UR W I
TH APPROPRAI
TE SI
GNAGE.

14. TO PURCHASE A KEY BOX CONTACT THE KNOX COMPANY (


800)552-5669 AND PROVI
DE
THE PUBLI
C UTI
LITI
ES DEPARTMENT,SYSTEM CODE:SS-01-0503-05-14.

15. KNOX KEY BOX TO BE I


NSTALLED ADJACENT TO THE W UR ENTRANCE W I
THI
N 4 - 6 FEET.

16. ONCE THE KNOX BOX I


S I
NSTALLED,NOTI
FY THE PUBLI
C UTI
LITI
ES DEPARTMENT,CROSS CONNECTI
ON CONTROL UNI
T
TO LOCK THE KEY BOX.

SHEET 2 OF 2

RECOMMENDED BY THE CI
TY OF SAN DI
EGO
REVI
SION BY APPROVED DATE
STANDARDS COMMITTEE
CI
TY OF SAN DI
EGO - STANDARD DRAW I
NG
ORI
GINAL BB J.NAGELVOORT 10/
14

FG J.NAGELVOORT 07/
15
7/
21/
15
UPDATED
COORDI
NATOR R.
C.E.56523 DATE
BACKFLOW PREVENTERS
DRAW I
NG
W ET UTI
LITY ROOM I
NSTALLATI
ON SDW -
141
NUMBER
1

2
C 12"
C
FI
NISH GRADE
3
C

C
C
C
C
C

7
4" TO 6"

C
C

C
C

4"

C
C

C
4 C 4"
(
TYP)

5
8
C 12
6
13

C
9 8 10 11

C
C

C
C

C
C 0.
5% MI
N

FALL

NOTES:

1. SET TOP OF METER BOX FLUSH W I


TH SI
DEW ALK,CURB OR FI
NISH GRADE

2. LOCATE METER BOX PER W S-03

3. I
NSTALL W ARNI
NG /I
DENTI
FICATI
ON TAPE PER SDM-105

4. BLOW -OFF ASSEMBLI


ES INSTALLED FOR THE USE OF RECYCLED W ATER SHALL
BE I
DENTIFIED AS DESCRIBED IN SPECI
FICATI
ONS

5. ON STEEL MAI
NS USE W ELD ON COUPLINGS,ON DUCTI
LE IRON MAI
NS USE
DUCTI
LE I
RON SERVICE SADDLES (
INSULATI
NG BUSHINGS ARE REQUI
RED)

6. CAM & GROOVE ADAPTER SHALL BE DRI


LLED AND TAPPED AS REQUI
RED FOR
THE PRESSURE PET COCK
2"
7. FOR BLOW OFF AT END OF MAI
N,SEE SDW -106.

LEGEND ON PLANS

I
TEM I
TEM
SI
ZE AND DESCRI
PTI
ON SI
ZE AND DESCRI
PTI
ON
NO NO

1 POLYMER METER BOX W I


TH LI
D 17" x 30",SEE NOTE 2 7 2" BRONZE COMP x FLG ANGLE METER STOP W I
TH LOCK W I
NG

2 2" CAM & GROOVE ADAPTER x MI


PT W I
TH LOCKI
NG DUST CAP, 8 2" x REQUI
RED LENGTH COPPER PI
PE TYPE "K" RI
GID OR SOFT
SEE NOTE 7

o
9 90 ELL (
NO SW EAT JOI
NTS ALLOW ED)

3 1/
4" PRESSURE PET COCK

o
4 2" 90 BRONZE MI
PT x FI
PT ELL 10 2" BRONZE COMPRESSI
ON COUPLI
NG COPPER TO COPPER (
IF
REQUI
RED)
5 2" OVAL METER FLANGE FLG x FI
PT,W I
TH GASKET

11 BRONZE CORPORATI
ON STOP (
INSTALL W I
TH KEY ON SI
DE AND
6 3/
8" ROCK 4" TO 6" DEEP OPEN TAP)

12 SI
ZE x 2" SERVI
CE SADDLE

13 W ATER MAI
N

RECOMMENDED BY THE CI
TY OF SAN DI
EGO
REVI
SION BY APPROVED DATE
STANDARDS COMMITTEE
CI
TY OF SAN DI
EGO - STANDARD DRAW I
NG
ORI
GINAL* KA J.NAGELVOORT 01/
12

2/
25/
16
UPDATED HM J.NAGELVOORT 02/
16
COORDI
NATOR R.
C.E.56523 DATE

2" BLOW -
OFF I
NSTALLATI
ON DRAW I
NG
SDW -
143
NUMBER
2 1
SEE SDW -153
3 TRENCH RESURFACING
C

C
PER SDG-107/
SDG-108 FI
NISH GRADE

C
C
C
4
C

C
4" TO 6"

C
C
2"

C
4"

C
C
C
C 4"
(
TYP)
5
C

10

6 11 12

C
7

13
C

C
C
7 8 9
14 C
o
45
C

C
C

C
C 0.
5% MI N

C
FALL
7 15
NOTES:
1) SET TOP OF METER BOX FLUSH W I
TH SI
DEW ALK,CURB OR FI
NISH GRADE

2) LOCATE METER BOX PER W S-03

3) I
NSTALL W ARNI
NG / I
DENTI
FICATI
ON TAPE PER SDM-105 4"

4) FOR BLOW -OFF I


NSTALLATI
ON AT END OF MAI
N SEE SDW -146.

5) BLOW -OFF ASSEMBLI


ES INSTALLED FOR THE USE OF RECYCLED W ATER SHALL 6"
BE I
DENTIFIED AS DESCRIBED IN SPECI
FICATI
ONS
o o
6) 45 BEND SHALL BE USED FOR MAI
NS UP TO 30".90 BEND
SHALL BE USED FOR MAINS I
N EXCESS OF 30" AS DI
RECTED BY LEGEND ON PLANS
THE ENGINEER

7) CAM & GROOVE ADAPTER SHALL BE DRI


LLED AND TAPPED AS REQUI
RED FOR
THE PRESSURE PET COCK

I
TEM I
TEM
SI
ZE AND DESCRI
PTI
ON SI
ZE AND DESCRI
PTI
ON
NO NO

o
1 POLYMER METER BOX W I
TH LI
D 17" x 30",SEE NOTE 2 8 4" OR 6" FLG x MJ/
PO 90 BEND

2 4" OR 6" CAM & GROOVE ADAPTER x MI


PT W I
TH LOCKI
NG 9 USE DUCTI
LE I
RON OR PVC C900
DUST CAP,SEE NOTE 7

10 VALVE W ELL FRAME AND COVER (


SEE SDW -153)

3 1/
4" PRESSURE PET COCK

11 4" OR 6" FLG x MJ/


FLG RW GV

4 4" OR 6" FLANGED COMPANI


ON x FI
PT
12 W ATER MAI
N

5 3/
8" ROCK 4" TO 6" DEEP
13 SI
ZE x 4" OR 6" MJ/
FLG x FLG TEE

o
14 4" OR 6" FLANGED 45 BEND
6 4" OR 6" FLG DIPI
PE x REQUI
RED LENGTH (
MAXI
MUM OF 2
SPOOLS)
o
15 4" OR 6" FLANGED 45 BEND

7 CONCRETE THRUST BLOCK SEE SDW -151


16 4" OR 6" x 24" FLG DISPOOL

RECOMMENDED BY THE CI
TY OF SAN DI
EGO
REVI
SION BY APPROVED DATE
STANDARDS COMMITTEE
CI
TY OF SAN DI
EGO - STANDARD DRAW I
NG
ORI
GINAL* KA J.NAGELVOORT 01/
12

2/
25/
16
UPDATED KA J.NAGELVOORT 12/
12
COORDI
NATOR R.
C.E.56523 DATE
UPDATED AR J.NAGELVOORT 10/
15 4" & 6" BLOW -OFF
DRAW I
NG
UPDATED HM J.NAGELVOORT 02/
16 I
NSTALLATI ON TYPE A SDW -
144
NUMBER
SEE SDW -153
TRENCH RESURFACI
NG
PER SDG-107/
SDG-108
2 FI
NISH GRADE

C
C
C

DI
STANCE AS SHOW N
4" TO 6"

C C

C ON DRAW I
NGS

3
C
1
4
C

CONCRETE 9 11

C
6
BLOCKS
5
12
C

C
C
6 7 8
C

13 O

C 45
C

C
C

C
C 0.
5% MI
N

C
FALL
6 10

NOTES:
1) FOR BLOW -OFF I
NSTALLATI
ON AT END OF MAI
N SEE SDW -106 AND SDW -146

2) BLOW -OFF ASSEMBLI


ES INSTALLED FOR THE USE OF RECYCLED W ATER SHALL
4"
BE I
DENTIFIED AS DESCRIBED IN SPECI
FICATI
ONS

3) ON STEEL MAI
NS USE W ELD ON COUPLINGS,ON DUCTI
LE IRON MAI
NS USE
DUCTI
LE I
RON SERVICE SADDLES (
INSULATI
NG BUSHINGS ARE REQUI
RED)
o o
6"
4) 45 BEND SHALL BE USED FOR MAI
NS UP TO 30".90 BEND
SHALL BE USED FOR MAINS I
N EXCESS OF 30" AS DI
RECTED BY
THE ENGINEER
LEGEND ON PLANS

I
TEM I
TEM
SI
ZE AND DESCRI
PTI
ON SI
ZE AND DESCRI
PTI
ON
NO NO

1 GATE W ELL W I
TH CAP SEE SDW -153 8 DUCTI
LE I
RON OR C-900 PVC

9 4" OR 6" FLG x MJ /


FLG RW GV
2 GALVANI
ZED I
RON PLUG

10 4" OR 6" x 24" FLG DISPOOL


3 GALVANI
ZED I
RON COUPLI
NG,THREADED

11 W ATER MAI
N
4 10" STEEL GATE W ELL W I
TH CAP

4" OR 6" FLG DIPI


PE x REQUI
RED LENGTH 12 SI
ZE x 4" OR 6 MJ /
FLG x FLG TEE
5
(
MAXI MUM OF 2 SPOOLS)
o

6 CONCRETE THRUST BLOCK SEE SDW -151 13 4" OR 6" FLANGED 45 BEND,SEE NOTE 4

7 FLANGE x FLANGE x 90 BEND

RECOMMENDED BY THE CI
TY OF SAN DI
EGO
REVI
SION BY APPROVED DATE
STANDARDS COMMITTEE
CI
TY OF SAN DI
EGO - STANDARD DRAW I
NG
ORI
GINAL* KA J.NAGELVOORT 01/
12

2/
25/
16
UPDATED KA J.NAGELVOORT 12/
12
COORDI
NATOR R.
C.E.56523 DATE
UPDATED AR J.NAGELVOORT 02/
16 4" & 6" BLOW -
OFF I
NSTALLATI
ON
DRAW I
NG
I
N STREET TYPE B SDW -
145
NUMBER
C 24"
C 7
MI
NIMUM 15

C
C
14
1 2 3 11 3

C
9 13
C

C
C
C

C
C

C
C

C
C
10 1
C

4
1
2" BLOWOFF

BLOW OFF ASSEMBLY END OF


C
ASSEMBLY

C
C
5 MAI
N

6 4" & 6"


BLOW OFF FROM END OF MAI
N
(
PROFI
LE VI
EW )
C

7
15
2" BLOW OFF
8

C
FROM END OF MAI
N C
14
(
PLAN VI
EW ) 9 13

C
C

C
C

C
C

10 12

1
C
BLOW OFF ASSEMBLY
C
NOTES:
1)BLOW -OFF ASSEMBLIES I
NSTALLED FOR THE USE OF
RECYCLED W ATER SHALL BE IDENTI
FIED AS DESCRI
BED
4" & 6"
I
N SPECI FI
CATIONS.
BLOW OFF FROM STEEL MAI
N
2)FOR 2" BLOW -OFFS ON STEEL MAI
NS USE W ELD ON (
PROFI
LE VI
EW )
COUPLINGS.ON DUCTI LE I
RON MAINS USE DUCTILE I
RON.

3)SERVI
CE SADDLES (
INSULATING BUSHI NGS ARE REQUI
RED)
FOR END OF MAIN DETAIL SEE SDW -106.

I
TEM I
TEM
SI
ZE AND DESCRI
PTI
ON SI
ZE AND DESCRI
PTI
ON
NO NO

1 CONCRETE THRUST BLOCKS SEE SDW -151 8 FLG x MJ/


PO/
FLG RW GV

2 DIEND CAP 9 FLG x MJ/


PO ADAPTER (
IF REQUI
RED)

3 W ATER MAI
N 10 C-900 PVC PI
PE

11 FLG x MJ/
PO ECCENTRI
C DIREDUCER
4 BRONZE SERVI
CE CLAMP (
DOUBLE STRAP)
.SI
ZE x 2" SERVI
CE
SADDLE
12 MAIN SI
ZE x BLOW OFF SI
ZE FLANGE MANUFACTURED STEEL
5 2" BRONZE MI
PT x COMP CORPORATI
ON STOP TANGENTIAL OUTLET

13 FLG x MJ/
PO BEND (
IF REQUI
RED)
6 2" x REQ'
D LENGTH COPPER PI
PE TYPE "K" RI
GID OR SOFT o

14 FLG x MJ/
PO 90 BEND

15 FLG DIPI
PE x REQUI
RED LENGTH (
MAXI
MUM OF 2 SPOOLS)
7 GATE W ELL W I
TH CAP SEE SDW -153 & SDW -154

RECOMMENDED BY THE CI
TY OF SAN DI
EGO
REVI
SION BY APPROVED DATE
STANDARDS COMMITTEE
CI
TY OF SAN DI
EGO - STANDARD DRAW I
NG
ORI
GINAL* KA J.NAGELVOORT 01/
12

2/
25/
16
UPDATED AR J.NAGELVOORT 02/
16
COORDI
NATOR R.
C.E.56523 DATE

BLOW -
OFF I
NSTALLATI
ON FROM
DRAW I
NG
END OF M AI
N & FROM STEEL M AI
N SDW -
146
NUMBER
3 1/
2" - 4"

C
C 7 8 FI
NISH
GRADE

C
C
6

C
C

C
C

C
2"

10"
3"
4"

C
DEPTH OF MAI
N SEE
SDW -110
C
C 4"
9 (
TYP)
5

MI
N RAD=
C
12"

4
1 2
O

10 MI
N
O

C
C

30 MAX
C

C
C

C
C

4
C

MI
N RAD
12"
3

NOTES:
1) I
NSTALL CORPORATI
ON STOP W I
TH KEY I
N THE SI
DE POSI
TION

2) SET TOP OF METER BOX FLUSH W I


TH SI
DEW ALK,CURB,OR FI
NISH GRADE

3) LOCATE METER BOX PER W S-03

4) I
NSTALL W ARNI
NG /I
DENTI
FICATI
ON TAPE PER SDM-105

5) ONLY APPROVED BRASS MECHANI


CAL COUPLI
NG DEVI
CES ALLOW ED FOR TYPE K COPPER PI
PE

6) ON STEEL MAI
NS USE W ELD ON COUPLI
NGS,ON DUCTI
LE I
RON MAI
NS USE
DUCTI
LE I
RON SERVI
CE SADDLES (
INSULATI
NG BUSHI
NGS ARE REQUI
RED)

7) TOP TAPS NOT PERMI


TTED.

2"
W

LEGEND ON PLANS

I
TEM I
TEM
SI
ZE AND DESCRI
PTI
ON SI
ZE AND DESCRI
PTI
ON
NO NO

1 W ATER MAI
N
6 2" BRONZE ANGLE METER STOP W I
TH LOCKW I
NG

2 2" BRONZE CORPORATI


ON STOP
7 W ATER METER FURNI
SHED AND I
NSTALLED BY THE CI
TY

3 SI
ZE x 2" BRONZE SERVI
CE SADDLE DOUBLE STRAP
8 METER BOX W I
TH LI
D,#6:35"x 21"
4 2" x REQUI
RED LENGTH COPPER PI
PE TYPE "K" SOFT/
RIGI
D
9 CUSTOMER SHUT-OFF VALVE (
LOCKABLE)FURNI
SH AND I
NSTALLED
3/
8" ROCK,4" TO 6" DEEP BY THE CI
TY
5

RECOMMENDED BY THE CI
TY OF SAN DI
EGO
REVI
SION BY APPROVED DATE
STANDARDS COMMITTEE
CI
TY OF SAN DI
EGO - STANDARD DRAW I
NG
ORI
GINAL* KA J.NAGELVOORT 2/
13

2/
25/
16
UPDATED KA J.NAGELVOORT 3/
13
COORDI
NATOR R.
C.E.56523 DATE
UPDATED HM J.NAGELVOORT 02/
16
2" W ATER SERVI
CE I
NSTALLATI
ON DRAW I
NG

NUMBER
SDW -
149
3"

C 6 7
C

FI
NISH GRADE

CC
C

C
8"

C
5

C
C

C
2" 3"

C
DEPTH OF MAI N 4"

C
SEE SDW -110 C
C
4"
8
(
TYP)

MI
N RAD= 9
12"

1 2
O

10 MI
N
O

C
C

30 MAX
C

C
C

4
C

MIN RAD
12"
3

NOTES:
1) I
NSTALL CORPORATI
ON STOP W I
TH KEY I
N THE SI
DE POSI
TION

2) SET TOP OF METER BOX FLUSH W I


TH SI
DEW ALK,CURB,OR FI
NISH GRADE

3) LOCATE METER BOX PER W S-03

4) I
NSTALL W ARNI
NG /I
DENTI
FICATI
ON TAPE PER SDM-105

5) ONLY APPROVED BRASS MECHANI


CAL COUPLI
NG DEVI
CES ALLOW ED FOR TYPE K COPPER PI
PE.

6) ON STEEL MAI
NS USE W ELD ON COUPLI
NGS,ON DUCTI
LE I
RON MAI
NS USE
DUCTI
LE I
RON SERVI
CE SADDLES (
INSULATI
NG BUSHI
NGS ARE REQUI
RED)

7) BRONZE PIPE SADDLES ARE REQUIRED FOR ALL TAPS I


NTO POLYVI
NYL CHLORI
DE
(
PVC)W ATER MAIN.TOP TAPS ARE NOT PERMI
TTED. W

LEGEND ON PLANS

I
TEM I
TEM
SI
ZE AND DESCRI
PTI
ON SI
ZE AND DESCRI
PTI
ON
NO NO

1 W ATER MAI
N 6 W ATER METER FURNI
SHED & I
NSTALLED
BY THE CI
TY
2 1" BRONZE CORPORATI
ON STOP

3 SI
ZE x 1" BRONZE SERVI
CE SADDLE DOUBLE STRAP 7 METER BOX W I
TH LI
D,
#37:28" x 18"
4 USE COPPER TUBI
NG TYPE (
K)SOFT FOR 1" SERVI
CES
ONLY.NO I
NTERMEDI
ATE JOI
NTS PERMI
TTED W I
THI
N THE FI
RST
8 CUSTOMER SHUT-OFF VALVE (
LOCKABLE)
60'FROM THE MAI
N FOR LENGTHS LONGER THAN 60
FURNI
SHED AND I
NSTALLED BY THE CI
TY
FEET USE FLARE JOI
NT UNI
ON OR LOK-PAC FI
TTI
NGS W I
TH
LOCKI
NG CLAMP AND STAI
NLESS STEEL BOLT ONLY. NO
SW EAT JOI
NTS ARE ALLOW ED 3/
8" ROCK,4" TO 6" DEEP
9
5 BRONZE ANGLE METER STOP W I
TH LOCKW I
NG DEVI
CE AND
METER COUPLI
NG ATTACHED. "FURNI
SH AND I
NSTALL BRONZE
PROPERTY VALVE.USE SPACER FOR METER"

RECOMMENDED BY THE CI
TY OF SAN DI
EGO
REVI
SION BY APPROVED DATE
STANDARDS COMMITTEE
CI
TY OF SAN DI
EGO - STANDARD DRAW I
NG
ORI
GINAL* KA J.NAGELVOORT 01/
12

2/
25/
16
UPDATED KA J.NAGELVOORT 03/
13
COORDI
NATOR R.
C.E.56523 DATE
UPDATED HM J.NAGELVOORT 02/
16
1" W ATER SERVI
CE I
NSTALLATI
ON DRAW I
NG
SDW -
150
NUMBER
W ATER MAI
N

C
ADDI
TIONAL

TH
TYPI
CAL

D
BLOCKS W HERE

I
W DI
RECTED
C

C
C WI
DTH
C

BEND TEE PLAN

STREET/
GROUND
SURFACE
C

C
BEARING AREA DEPTH

MAX
12"
C

C
DEPTH
MIN
C
C

CROSS

TEE ELEVATI
ON
C
TRENCH

WIDTH
C
C

18" MI
NIMUM
I
NTO NATI
VE MATERI
AL

REDUCER VERT BENDS PLAN


SEE NOTE
1BELOW
CAP/
PLUG
ANCHOR BLOCK
C
SEE NOTE #4 WI
TH #4 REBAR
C
C

END CAP VERT BENDS ELEVATI


ON

NOTES:
1) THE ANCHOR BLOCKS ON VERTI
CAL BENDS REQUI
RE ENGI
NEER APPROVAL.

2) A MI
NIMUM OF 6" OF CONCRETE SHALL BE POURED ON W ETTED UNDI
STURBED OR
COMPACTED SOI
L BENEATH EACH I
NSTALLATI
ON.

3) TEE SHALL BE CONCRETE BLOCKED A MI


NIMUM OF 6" ON ALL THREE SI
DES.

4) USE 12" - 18" LENGTH OF PI


PE BETW EEN THE END CAP AND THE LAST
JOI
NT AS A BOND BREAKER ON DEAD END BLOCKI NG.
SHEET 1OF 3

RECOMMENDED BY THE CI
TY OF SAN DI
EGO
REVI
SION BY APPROVED DATE
STANDARDS COMMITTEE
CI
TY OF SAN DI
EGO - STANDARD DRAW I
NG
ORI
GINAL* KA J.NAGELVOORT 01/
12

2/
25/
16
UPDATED HM J.NAGELVOORT 02/
16
COORDI
NATOR R.
C.E.56523 DATE
CONCRETE THRUST AND
DRAW I
NG
ANCHOR BLOCK I
NSTALLATI
ONS SDW -
151
NUMBER
VALVE SUPPORT BLOCK THRUST AND ANCHOR BLOCKS
VALVE DI
MENSI ON DI
MENSI ON MINIMUM BEARING AREA I
N SQUARE FOOT
SI
ZE "A" "B" (
SQUARE METERS)SEE NOTE 2
o1 o o

4" 12" 12" MAI N 90 45 22


TEES 2
6" 12" 12" SI
ZE BEND BEND
BEND
8" 13" 14" 4" 4 5 3 5
1.
10" 14" 16" 6" 8 10 5 2.
5
12" 15" 18" 8" 12 16 9 4.
5
DIMENSION "C" = TRENCH W I
DTH 10" 17 24 13 6.
5
PLUS TW O TI
MES THE PI
PE DI
AMETER
12" 24 33 19 9.
5

C
C

DIMENSION
TRENCH

"C"
C

VALVE SUPPORT
PLAN

BOTTOM OF CONCRETE BLOCK


TYPI
CAL

C
TRENCH TYP

DIMENSION
C

"B"
C

C
C C
C C

DI
MENSI
ON "A"
DI
MENSI
ON "C"
CLEAR BELL OR
FLG,SEE NOTE 4

VALVE SUPPORT
ELEVATI
ON

NOTES:
1) BEARI
NG AREA BASED ON SOI L BEARING VALUE OF 1500 PSF AND 225 PSILI
NE PRESSURE AND A MI
NIMUM OF 36" COVER:
FOR BEARI
NG= 1000 PSF,1.
5 x AREA SHOW N
FOR BEARI
NG= 500 PSF,3.
0 x AREA SHOW N

2) ENGI
NEER SHALL DETERMI
NE SI
ZES,REFER TO SPECI
FICATI
ONS FOR THRUST
AND ANCHOR BLOCK SIZI
NG.

3) THRUST BLOCKS SHALL BE CENTERED ON THE FI


TTI
NG SO THAT THE BEARI
NG AREA I
S
EXACTLY OPPOSI
TE THE RESULTANT DI
RECTI
ON OF THRUST.

4) CONCRETE SHALL BE PLACED SO THAT FI


TTI
NGS AND VALVES W I
LL BE ACCESSABLE FOR
REPAI
R OR REPLACEMENT.

SHEET 2 OF 3

RECOMMENDED BY THE CI
TY OF SAN DI
EGO
REVI
SION BY APPROVED DATE
STANDARDS COMMITTEE
CI
TY OF SAN DI
EGO - STANDARD DRAW I
NG
ORI
GINAL* KA J.NAGELVOORT 01/
12

02/
16
2/
25/
16
UPDATED HM J.NAGELVOORT
COORDI
NATOR R.
C.E.56523 DATE
CONCRETE THRUST AND
DRAW I
NG
ANCHOR BLOCK I
NSTALLATIONS SDW -
151
NUMBER
MINIMUM (TYP)
24"
MI
NIMUM (
TYP)

MIN TYPICAL

12"
24"
SECTI
ON

PLAN

TEE W I
TH GATE VALVES
GATE W ELL TYPI
CAL
SEE SDW -153

EDGE OF TRENCH
TYPI
CAL

BUTTERFLY
VALVE (
TYP)

ACTUATOR
TYPI
CAL
BEARI
NG
SAND BAGS
AREA "B" MASONRY SUPPORT
TYPI
CAL
TYPI
CAL
BEARI
NG BLOCKS,TYPICAL
WITH REDW OOD
PLAN AREA "A" (
TYP) SECTI
ON
W EDGES AS REQ'
D

TEE W I
TH BUTTERFLY VALVES ON MAI
N
GATE W ELL TYPI
CAL
SEE SDW -153

SAND BAGS

TYPI
CAL

PLAN SECTI
ON

TEE W I
TH BUTTERFLY VALVES

NOTES:
1) BEARI
NG AREA "B" MUST BE EQUAL TO OR GREATER THAN THE AREA REQUI
RED FOR A 90?
ELBOW I
NSTALLATI
ON.

2) I
NSTALL SAND BAGS AROUND BUTTERFLY VALVE ACTUATOR TO I
SOLATE I
T FROM CONCRETE.

3) BFV'
S I
NSTALLED AT CROSSES OR TEES REQUI
RE A FLANGED DUCTI
LE I
RON SPOOL TO BE
I
NSTALLED BETW EEN THE FI
TTI
NG AND VALVE I
N ACCORDANCE W I
TH THE SPECI
FICATI
ONS.

SHEET 3 OF 3

RECOMMENDED BY THE CI
TY OF SAN DI
EGO
REVI
SION BY APPROVED DATE
STANDARDS COMMITTEE
CI
TY OF SAN DI
EGO - STANDARD DRAW I
NG
ORI
GINAL* KA J.NAGELVOORT 01/
12

02/
16
2/
25/
16
UPDATED HM J.NAGELVOORT
COORDI
NATOR R.
C.E.56523 DATE
CONCRETE THRUST AND
DRAW I
NG
ANCHOR BLOCK I
NSTALLATI
ONS SDW -
151
NUMBER
13/
16"
SAN W ATER
3/16"
F
O C
4 3/
4" C
C
3 3/
4" C

C
D
3/
4"
TY

C
I

C
ABOUT AXIS
EG

SYMMETRIC
3/
16"
CI

RELI
EF 6"

O
W ATER

C
C1" C
C
1/
4"
C
C C 10/
16"
6 1/
4" C
C
7 1/
2" C

CAST I
RON VALVE W ELL CAP DETAI
L

I
NSI
DE GATE W ELL LI
D PAI
NTED I
DENTI
FICATI
ON MARKI
NG

POTABLE COLOR GATE W ELL AND LI


DS USED FOR:

W ATER RED NORMALLY CLOSED SYSTEM


VALVES (
NCV)

W HI
TE RESI
LIENT W EDGE GATE VALVES
GATE W ELL LI
D YELLOW BUTTERFLY VALVES

GATE W ELL LI
D TOP COLOR & CONDI
TION

VALVE CONDI
TION BUTTERFLY VALVE GATE VALVE

PERMANENTLY
RED RED
CLOSED

TEMPORARI
LY YELLOW W HI
TE
CLOSED W/
RED DOT W/
RED DOT

PERMANENTLY
YELLOW W HI
TE
OPEN

NOTES:
1) GATE W ELL LIDS SHALL BE CAST I
RON W ITH "CITY OF SAN DIEGO" AND THE W ORD
"W ATER" FOR USE W I
TH POTABLE W ATER SYSTEMS AND "RECYCLED" FOR USE
WITH RECYCLED W ATER SYSTEMS.LI DS SHALL INCLUDE A 1" LI
FTI
NG SLOT

RECOMMENDED BY THE CI
TY OF SAN DI
EGO
REVI
SION BY APPROVED DATE
STANDARDS COMMITTEE
CI
TY OF SAN DI
EGO - STANDARD DRAW I
NG
ORI
GINAL* KA J.NAGELVOORT 01/
12

2/
25/
16
UPDATED RB J.NAGELVOORT 02/
16
COORDI
NATOR R.
C.E.56523 DATE

GATE W ELL I
DENTI
FICATI
ON DRAW I
NG
SDW -
152
NUMBER
TRENCH RESURFACI
NG
PER SDG-107/
SDG-108
1 1
FI
NISH GRADE

C
C

C
C

C
C
C
C C

C
18" MAX

18" MAX
1" MIN
12" MIN

12" MIN
EXI
STING BASE 7 7
OR OLD CONCRETE C C
PAVEMENT 8 8

C
C

C C

C 2 C 2

SET GATE W ELL 3 3


C
ON VALVE BONNET C
3
3
C

6 5
C SET GATE W ELL
C
ON VALVE
C
OPERATOR

GATE W ELL (
GATE VALVES) GATE W ELL (
BUTTERFLY VALVES)

MACHINED
C 13"
C
SEAT
C 9.75" C
C

C
C

1.
25"
W ATER MAI
N
C

C
11.
50" C

0.
75" C
10.38" C

C
9.
75" C
STREET C
L
0.
75" C
C

8.
75"
C

C 7.
75" C
C

C
C

2" C
7.
75" C 0.
75"
C

C
9.
70" C

C
8.
50" 1.
5" - 2" SEE NOTE 7 BFV TYPI
CAL
C
C
9.
25"
SEE NOTE 3 & 4
C 10.
60"
C

CAST I
RON RI
SER RI
NG BFV OPERATOR POSI
TION
CAST I
RON VALVE W ELL FRAME

NOTES:
1) VALVES DEEPER THAN 6'REQUIRE A VALVE STEM EXTENSI
ON
2) EXTENSI
ON STEMS SHALL NOT BE ATTACHED/ BOLTED TO OPERATI
NG NUT
3) GATE W ELL AND CAP SHALL BE SET SO THAT NO MORE THAN TW O 1"
ADJUSTMENT RI NGS ARE USED
4) BFV OPERATORS TO BE LOCATED TO THE CURBLI NE SIDE OF W ATER MAIN
5) BFV'
S INSTALLED AT CROSSES OR TEES REQUI RE A FLANGED DUCTI LE I
RON
SPOOL TO BE I NSTALLED BETW EEN THE FITTI
NG AND VALVE IN ACCORDANCE
WITH THE SPECI FI
CATIONS LEGEND ON PLANS
6) FOR 8" C-900 PI
PE CASING,I
NSTALL CAST IRON RISER VALVE W ELL FRAME
7) CAST I
RON RI SER RING HEIGHT TO MATCH OVERLAY THI CKNESS NO MORE
THAN TW O (
2)RI
NGS ARE USED.

I
TEM I
TEM
SI
ZE AND DESCRI
PTI
ON SI
ZE AND DESCRI
PTI
ON
NO NO

1 GATE W ELL W I
TH CAP PER SDW -152 5 RESI
LIENT W EDGE GATE VALVE

2 VALVE STEM EXTENSI


ON SEE NOTES 1& 2 W ATER MAI
N
6

3 8" OD x 1/
8" STEEL CASI
NG x REQUI
RED LENGTH
7 VALVE W ELL FRAME SET TO SLOPE OF STREET
(
OPTI
ONAL 8" C 900 x LENGTH)
.

4 BUTTERFLY VALVE 8 CALDER COUPLI


NG (
FOR PVC W ELL)

RECOMMENDED BY THE CI
TY OF SAN DI
EGO
REVI
SION BY APPROVED DATE
STANDARDS COMMITTEE
CI
TY OF SAN DI
EGO - STANDARD DRAW I
NG
ORI
GINAL* KA J.NAGELVOORT 01/
12

2/
25/
16
UPDATED KA J.NAGELVOORT 12/
12
COORDI
NATOR R.
C.E.56523 DATE
UPDATED KA J.NAGELVOORT 5/
13 GATE W ELL CAP & CAN I
NSTALLATI
ON
DRAW I
NG
UPDATED HM J.NAGELVOORT 02/
16 FOR VALVES 4" AND LARGER SDW -
153
NUMBER
3", 4", 6" FLANGED
OUTLET OR TEE
VV!Ntv< TAPE (TYP)
MAINLINE

WATERLINE VALVE
IN/VALVE GATEWELL 3", 4", OR 6"
CAP & CAN BYPASS PIPE (TYP)
INSTALLATION (TYP)
90' BEND (TYP)

Q> GV TYP (3 TOTAL)

T-MAINLINE

90' BEND (TYP)

STRAIGHT MAINLINE

NOTES:

1. BYPASS SHALL BE SAME CLASS AS MAINLINE PIPE. MAIN SIZE BYPASS SIZE
16" TRANSMISSION 3"
2. THE VALVE SHALL BE THE SAME SIZE AS THE BYPASS PIPE.
> 16" AND =< 36" 4"
3. SEE THE APPROVED WORKING DRAWINGS FOR X, AND x,. >36" 6"

REVISION BY APPROVED DATE RECOMMENDED BY THE CITY OF SAN DIEGO


STANDARDS COMMITIEE
CITY OF SAN DIEGO - STANDARD DRAWING
OV12

12'12
dl~ 12117/2012
COORDINATOR R.C.E. 65271 DATE
WATER VALVE BYPASS DETAILS
FOR MAINLINES 16" AND LARGER DRAWING
SDW-154
NUMBER
METER BOX
EDGE OF
CI
TY PRI
VATELY
C C
C C 8 9 8 7
MAI
NTAI
NED MAI
NTAI
NED
C 10

C
4

C
4

C
C

C
7
7

C
C

C
18" 11

C
10'MAX 7 11

C
C
SEE NOTES 5,9
C 6 6
C C C

C
C 6" MI
N (
TYP)

C
C

24" MAX
12" MIN
5

FLOW

C
C

C
C

C
C

C
2
C

1 12 2 3 4 4 3
FLOW

NOTES:

1) I
NSTALL W ARNI
NG/
IDENTI
FICATI
ON TAPE PER SDM-105.

2) LOCATE BACKFLOW PREVENTI


ON ASSEMBLY I
N SUCH A MANNER THAT W I
LL ALLOW THE ASSEMBLY TO BE READI
LY
ACCESSIBLE FOR I
NSPECTI
ON AND REPAI
R.

3) STRAI
NERS SHALL NOT BE I
NSTALLED PRI
OR TO THE FI
RST SHUT-OFF VALVE.

4) ALL ABOVE GROUND PI


PING,UNI
ONS,ELBOW S,& NI
PPLES SHALL BE SOLDERED COPPER OR THREADED BRASS.

5) I
NSTALL A CASI
NG ENCASED I N CONCRETE W HEN THE DI
STANCE BETW EEN THE METER BOX AND THE RI
o

SER TO THE
ASSEMBLY EXCEEDS 18",REQUI
RES APPROVAL.

6) I
NSTALL A PRESSURE REDUCI
NG VALVE UPSTREAM OF THE FI
RST 90 DEGREE ELL W HEN SYSTEM PRESSURE EXCEEDS
150 PSI
.

7) TESTI
NG SHALL BE CONDUCTED I
N ACCORDANCE W I
TH SPECI
FICATI
ONS PRI
OR TO ACCEPTANCE.

8) BACKFLOW PREVENTION ASSEMBLY & APPURTENANCES I


NSTALLED FOR THE USE OF RECYCLED W ATER SHALL BE
I
DENTIFI
ED AS DESCRIBED I
N SPECI
FICATI
ONS.
RP W
9) PUBLI
C UTILITI
ES DEPARTMENT,CROSS CONNECTI
ON CONTROL UNI
T MUST APPROVE
LOCATION.SHOW ON PLANS.
RP RW

10)ALL RI
SER ELBOW S AND UNDERGROUND PI
PING SHALL BE TYPE (
L)OR (
M)COPPER,OR
RED BRASS. LEGEND ON PLANS

I
TEM I
TEM
SI
ZE AND DESCRI
PTI
ON SI
ZE AND DESCRI
PTI
ON
NO NO

METER BOX & METER ASSEMBLY PER SDW -149 &


1 8 BALL VALVE "SHUT-OFF"
SDW -150
2 SCHEDULE 80 PVC,RED BRASS OR COPPER PI
PE APPROVED REDUCED PRESSURE BACKFLOW ASSEMBLY
9
SI
ZED TO MATCH METER
3 CONCRETE THRUST BLOCK PER SDW -151
10 ENCLOSURE SHALL BE I
NSTALLED LEVEL AND
4 90 DEGREE BRASS ELL SEE NOTES 4 & 6 PLUMB.ENCLOSURE IS REQUI
RED.
11 UNI
ONS SEE NOTE 4
5 CONCRETE SLAB,MI
NIMUM 4" THI
CK x 18" W I
DE
12 PRESSURE REDUCI
NG VALVE SEE NOTES 4 & 6
6 BRASS OR COPPER PI
PE SEE NOTE 4

7 3" LONG NI
PPLE SEE NOTE 4

RECOMMENDED BY THE CI
TY OF SAN DI
EGO
REVI
SION BY APPROVED DATE
STANDARDS COMMITTEE
CI
TY OF SAN DI
EGO - STANDARD DRAW I
NG
ORI
GINAL* KA J.NAGELVOORT 01/
12

2/
24/
16
UPDATED KA J.NAGELVOORT 12/
12
COORDI
NATOR R.
C.E.56523 DATE
UPDATED FG J.NAGELVOORT 08/
15 BACKFLOW PREVENTER FOR 3/
4" TO 2"
DRAW I
NG
UPDATED FG J.NAGELVOORT 02/
16
M ETERED SERVI
CE SDW -
155
NUMBER
METER BOX
EDGE OF
C
CI
TY C PRI
VATELY
C C 7 8 7
MAI
NTAI
NED MAI
NTAI
NED C 9

C
C

C
6 12 6

C
18" C

10'MAX 5 5
1 SEE NOTES 4,5,8

C
C C
C
C 10 C 11

C
C
C

24" MAX
12" MIN
C
C
4 4 3 2
18" MI
N

C
(TYP)

C
FLOW FLOW
C C
C

2 3

NOTES:
1) I
NSTALL W ARNI
NG/
IDENTI
FICATI
ON TAPE PER SDM-105.

2)LOCATE BACKFLOW PREVENTION ASSEMBLY I


N SUCH A MANNER THAT W I
LL ALLOW THE
ASSEMBLY TO BE READI
LY ACCESSI
BLE FOR INSPECTI
ON AND REPAI
R

3)STRAI
NERS SHALL NOT BE I
NSTALLED PRI
OR TO THE FI
RST SHUT-OFF VALVE

4)I
NSTALL A CASI
NG ENCASED I N CONCRETE W HEN THE DISTANCE BETW EEN THE METER BOX
AND THE RISER TO THE ASSEMBLY EXCEEDS 18",REQUI
RES APPROVAL.

5)I
NSTALL A PRESSURE REDUCI NG VALVE UPSTREAM OF THE BACKFLOW ASSEMBLY W HEN SYSTEM
PRESSURE EXCEEDS 150 PSI
.

6) TESTI
NG SHALL BE CONDUCTED I
N ACCORDANCE W I
TH SPECI
FICATI
ONS PRI
OR TO ACCEPTANCE

7)BACKFLOW PREVENTI ON ASSEMBLY & APPURTENANCES INSTALLED FOR THE USE OF RECYCLED
W ATER SHALL BE I
DENTI
FIED AS DESCRI
BED IN SPECI
FICATIONS

RP W
8)PUBLI
C UTILI
TIES DEPARTMENT CROSS CONNECTI
ON CONTROL UNI
T MUST
APPROVE LOCATION AS SHOW N ON PLANS.
RP RW

LEGEND ON PLANS

I
TEM I
TEM
SI
ZE AND DESCRI
PTI
ON SI
ZE AND DESCRI
PTI
ON
NO NO

1 METER VAULT & METER ASSEMBLY PER W S-04 APPROVED REDUCED PRESSURE BACKFLOW ASSEMBLY
8
MINI
MAL SCHEDULE 80 PVC OR DUCTI
LE I
RON SI
ZED TO MATCH METER
2
PI
PE ENCLOSURE SHALL BE I
NSTALLED LEVEL AND PLUMB.
9
3 FLG x FLG OR MJ/
PO x FLG 90 DEGREE BEND ENCLOSURE I
S REQUIRED.

4 CONCRETE THRUST BLOCK PER SDW -151 10 ADJUSTABLE VALVE SUPPORT

5 FLANGED DUCTI
LE I
RON PI
PE 11 CONCRETE SLAB,MI
NIMUM 4" THI
CK x 36" W I
DE

6 FLANGED 90 DEGREE BEND,SEE NOTE 5 12 FLANGED ANGLE PRESSURE REDUCI


NG VALVE SEE NOTE 5

7 FLANGED RESI
LIENT W EDGE GATE VALVE
RECOMMENDED BY THE CI
TY OF SAN DI
EGO
REVI
SION BY APPROVED DATE
STANDARDS COMMITTEE
CI
TY OF SAN DI
EGO - STANDARD DRAW I
NG
ORI
GINAL* KA J.NAGELVOORT 01/
12

UPDATED
2/
24/
16
FG J.NAGELVOORT 08/
15
COORDI
NATOR R.
C.E.56523 DATE
UPDATED FG J.NAGELVOORT 02/
16 BACKFLOW PREVENTER FOR 3" AND
DRAW I
NG
LARGER M ETERED SERVI
CE SDW -
156
NUMBER
H

1' 6 "

6' CHAIN LINK FENCE


(ALTERNATE MATERIALS MUST BE APPROVED
BY PUBLIC UTILITIES DEPT. PRIOR TO CONSTRUCTION).
~ OPTIONAL
FULL RESILIENT SEATED
INSTALLED BY CITY FORCES c:i VALVE BOX WCOVER
GATE VALVE TYP a' SEE SDW- 153
(NO BUTIERFLY VALVES)

NOT TO SCALE
NOTES:
1. ALL BURIED DUCTILE IRON PIPE, FITIINGS, VALVES AND APPURTENANCES SHALL BE COATED
WITH A DIELECTRIC COATING . A LIQUID EPOXY COATING SYSTEM PER AWNA C-210 AT 24 MILS
MINIMUM DRY FILM THICKNESS (MDFT) , OR A COLD APPLIED THREE-PART SYSTEM PETROLEUM WAX
TAPE PER AWNA C-217, OR A 100% POLYURETHANE COATING OF 24 MILS (MDFT) SUITABLE.

2. ANY CHANGES SHALL HAVE PUBLIC UTILITIES DEPARTMENT APPROVAL.

3. PIPING SHALL BE SYMMETRICAL TO SLAB CENTER LI NE.

4. SUPPLY PIPE IS ONE COMMERCIAL SIZE LARGER THAN PROPOSED METER.

5. CONCRETE SLAB AND FENCE SHALL BE INSTALLED BY CONTRACTOR.

6. CONTACT CORROSION CONTROL SECTION FOR CORROSION REQU IREMENTS.

7. ALL METAL IN CONTACT WITH CONCRETE SHALL BE POLYETHYLENE WRAPPED USING 2" WIDE PLASTIC
BACKED ADHESIVE TAPE 8 MILS THICK WITH 112" OVERLAP.

8. BACKFLOW SHALL BE INSTALLED IMMEDIATELY DOWNSTREAM FROM METER UNLESS APPROVED BY


THE CITY CROSS-CONNECTION SPECIALIST.

9. BACKFLOW PREVENTERS SHALL BE REDUCED PRESSURE PRINCIPLE (RP) ASSEMBLY. (INSTALLED ABOVE
GRADE AS CLOSE TO METER AS POSSIBLE) BACKFLOW LOCATION MUST BE APPROVED BY THE
CROSS-CONNECTION CONTROL SECTION OF THE PUBLIC UTILITIES DEPT.

ITEMS CALL OUT:

CD 90' FLANGED DUCTILE IRON ELBOW (TYP).

® FLANGED DUCTILE IRON SPOOL, BOTH ENDS SHALL BE


FLANGED (UNI-FLANGE SHALL NOT BE USED).

@ DIAMETER OF TEE SHALL BE EQUAL TO THE DIAMETER OF THE SUPPLY PIPE. SHEET 1 OF 2

REVISION BY APPROVED DATE RECOMMENDED BY THE CITY OF SAN DIEGO

12112
CITY OF SAN DIEGO - STANDARD DRAWING rff. . ~~~D:/~ .COMMITIEE
ORIGINAL KA . NAGELVOOR
~ ~ 12/17/2012
COORD INATOR R.C.E. 65271 DATE
DUAL ABOVE GROUND METER
WITH PRIVATE BACKFLOW DRAWING
SDW-157
NUMBER
LTR . ~ZE 3" 4" 6" 8" 10"
CODE PA

A GATE VALVE 8" 9" 10 V2" 11 V2" 1'-1"

B PIPE EXTENSION 1'-0" 1'-0" 1'-0" 1'-0" 1'-0"

c STRAINER * 7" 9" 9" 10" 1'-0"

D TURBINE WATER METER * 1-0" 1-2" 1'-6" 1'-9" 2'-2"

E COMPOUND METER * 1'-5" 2'-0" 2'-5" 3'-1" 4'-7"

F TESTING TEE 11 " 1'-1 " 1'-4 " 1'-6 " 1'-10"

G 90 DEG. ELBOW (SHORT) 5 V2" 6 V2" 8" 9" 11 "

H OVERALL SLAB LENGTH *

I SLAB TO O'L PIPE 3'-0" 3'-0" 3'-0" 3'-0" 3'-0"

* NOTES :
INDIVIDUAL DIMENSIONS MAY VARY PER MANUFACTURER OVERALL
DIMENS IONS INCREASE WITH USE OF TH ESE COMPONENTS

DIMENSION CHART FOR METER ASSEMBLIES

SHEET 2 OF 2

REVISION BY APPROVED DATE RECOMMENDED BY THE CITY OF SAN DIEGO


STANDARDS COMMITIEE
CITY OF SAN DIEGO - STANDARD DRAWING
ORIGINAL KA . NAGELVOORT 12112
tJII. ~ 12/17/2012
COORDINATOR R.C.E. 65271 DATE
DUALABOVEGROUNDMETER
DRAWING
WITH PRIVATE BACKFLOW NUMBER
SDW-157
1

2 C 12"
C
FI
NISH GRADE
3
C

C
C
C
C
C

7
C

C
C
C

2"

C
C

4"
(100mm TO 150mm)

C
C
4"
C

4 C
(
TYP)
8
5 C
4" TO 6"

9 8 10
8 11
6
C

C
C

C
12

C
C 1.
0% MI
N

RI
SE C 13

NOTES:
1) SET TOP OF METER BOX FLUSH W I
TH SI
DEW ALK,CURB OR FI
NISH GRADE
C

2)LOCATE METER BOX PER W S-03 14

3)I
NSTALL W ARNI
NG/
IDENTI
FICATI
ON TAPE PER SDM-105

4)MANUAL AI
R VALVE I
NSTALLATI
ON AT END OF MAI
N TO BE SADDLED 24"
FROM END CAP

5)MANUAL AIR VALVE ASSEMBLI


ES INSTALLED FOR THE USE OF RECYCLED
W ATER SHALL BE I
DENTIFI
ED AS DESCRIBED IN SPECI
FICATI
ONS

6)ON STEEL MAI


NS USE W ELD ON COUPLINGS,ON DUCTI
LE IRON MAI
NS USE
DUCTI
LE I
RON SERVICE SADDLES (
INSULATI
NG BUSHINGS ARE REQUI
RED)

7)CAM & GROOVE ADAPTER SHALL BE DRI


LLED AND TAPPED AS REQUI
RED FOR 2"
THE PRESSURE RELEASE PET COCK

LEGEND ON PLANS

I
TEM I
TEM
SI
ZE AND DESCRI
PTI
ON SI
ZE AND DESCRI
PTI
ON
NO NO

1 POLYMER METER BOX W I


TH LI
D 17" x 30",SEE NOTE 2 7 2" BRONZE COMP x FLG ANGLE METER STOP W I
TH LOCK W I
NG

2 2" CAM & GROOVE ADAPTER x MI


PT W I
TH LOCKI
NG DUST CAP, 8 2" x REQUI
RED LENGTH COPPER PI
PE TYPE "K" RI
GID OR SOFT
SEE NOTE 7
O

9 2" 90 BRONZE COMPRESSI


ON ELL
3 1/
4" PRESSURE PET COCK

O 10 2" BRONZE COMPRESSI


ON COUPLI
NG COPPER TO COPPER (
IF
4 2" 90 BRONZE MI
PT x FI
PT ELL
REQUIRED)

5 2" OVAL METER FLANGE FLG x FI


PT,W I
TH GASKET 11
O

2" 90 BRONZE FI
PT x COMP ELL

6 3/
8" ROCK 4" TO 6" DEEP 12 2" BRONZE MI
PT x MI
PT CORPORATI
ON STOP

13 SI
ZE x 2" SERVI
CE SADDLE

14 W ATER MAI
N

RECOMMENDED BY THE CI
TY OF SAN DI
EGO
REVI
SION BY APPROVED DATE
STANDARDS COMMITTEE
CI
TY OF SAN DI
EGO - STANDARD DRAW I
NG
ORI
GINAL* KA J.NAGELVOORT 01/
12

10/
15
2/
25/
16
UPDATED AR J.NAGELVOORT
COORDI
NATOR R.
C.E.56523 DATE
UPDATED HM J.NAGELVOORT 02/
16
2" M ANUAL AI
R VALVE DRAW I
NG
SDW -
158
NUMBER
6 10
2

C
C

C
1 8
4 C

C TO MAI
N
C
2
C

3
8 C 14" C 22" C 6"
C C
C
7
C

5 C 42"
6"

MIN
3"

C
C FI
NISH
GRADE

C
C
C

C
PLAN VI
EW
C

C
C
24" MAX

C
18" MIN

C
18
4"

9
12 14
C 10 10

C
6
10

C
15

C
C

C
C

C
C C C

11 10 13 1.
0% MI
N 16
C
RI
SE

SECTI
ON VI
EW
C

17
NOTES:

1. NO DI
PS OR LOW SPOTS W I
LL BE ALLOW ED I
N I
NSTALLATI
ON.

2. LOCATE ENCLOSURE PER SDW -117.

3. I
NSTALL W ARNI
NG/
IDENTI
FICATI
ON TAPE PER SDM-105.

4. AI
R & VACUUM I
NSTALLED FOR THE USE OF POTABLE/
RECYCLED W ATER SHALL
BE SHOW N ON THE PLANS. 2"

5. ON STEEL MAI
NS USE W ELD ON COUPLI
NGS,ON DUCTI
LE I
RON MAI
NS USE
DUCTI
LE I
RON SERVI
CE SADDLES (
INSULATI
NG BUSHI
NGS ARE REQUI
RED)
. LEGEND ON PLANS

I
TEM I
TEM
SI
ZE AND DESCRI
PTI
ON SI
ZE AND DESCRI
PTI
ON
NO NO

1 2" PVC SCH 80 CLOSE NI


PPLE & 2-SCH 80 STREET 9
ELLS& INSECT SCREEN 2" X 1/
2" BLACK FOAM SLEEVE
10
2 APPROVED VALVE ENCLOSURE COPPER TUBI
NG

3 2" MI
PT X COMPRESSI
ON ADAPTER 11 90 ELL (
NO SW EAT,NO GLUED JOI
NTS ALLOW ED)

4 2" AUTOMATI
C COMBI
NATI
ON AI
R RELEASE & AI
R/VACUUM 12 2" BRONZE COMPRESSI
ON COUPLI
NG COPPER TO COPPER
VALVE (I
F REQUIRED)

5 1/
2" X 3" STAI
NLESS STEEL DROP-I
N ANCHORS 13 2" COMP BALL BALVE W /
TEE HEAD
(3 EA @ 120 APART)
o

14 2" 90 BRONZE FI
PT X COMP ELL
6 8",3/
8" STEEL GATE CASI
NG W ELL W I
TH CAP
15 2" BRONZE MI
PT X MI
PT CORPORATI
ON STOP
7 COLD JOI
NT STRI
P
16 SI
ZE X 2" SERVI
CE SADDLE
8 3'
-6" X 2'
-6" X 6" THI
CK
CONCRETE SLAB 17 W ATER MAI
N

18 VALVE STEM EXTNESI


ON

RECOMMENDED BY THE CI
TY OF SAN DI
EGO
REVI
SION BY APPROVED DATE
STANDARDS COMMITTEE
CI
TY OF SAN DI
EGO - STANDARD DRAW I
NG
ORI
GINAL* KA J.NAGELVOORT 01/
12

UPDATED KA J.NAGELVOORT 09/


13
2/
25/
16
2" AUTOM ATI
C COM BI
NATI
ON COORDI
NATOR R.
C.E.56523 DATE
UPDATED BB J.NAGELVOORT 09/
14

UPDATED AR J.NAGELVOORT 11/


15
AI
R RELEASE & AI
R/VACUUM VALVE DRAW I
NG
SDW -
159
UPDATED HM J.NAGELVOORT 02/
16 I
NSTALLATI
ONS NUMBER
1 5

6" MAX
C

4" MIN
C
3 6

C
C

4 7 SEE SDW -153


C
C C

C
C

FI
NISH GRADE

C
C
BREAK OFF GROOVES

3 11
C
12
C
8
18" WITH

10 C
13
C 13
C C
C
C

14

C 1.
0% MI
N
C
RI
SE 15
C

NOTES: C 8
1) NO DI
PS OR LOW SPOTS W I
LL BE ALLOW ED I
N PI
PING I
NSTALLATI
ON

2)LOCATE ENCLOSURE PER SDW -117

3)I
NSTALL W ARNI
NG/
IDENTI
FICATI
ON TAPE PER SDM-105

4)BREAK-AW AY BOLTS SHALL BE 5/


8" x 3" W I
TH 3/
8" 4"

HOLE DRI
LLED I
N THE SHAFT OF THE BOLT.I
NSTALL W I
TH HEX HEAD ON
TOP OF THE FLANGE.

6"
5) AI
R & VACUUM VALVES I
NSTALLED FOR THE USE OF POTABLE/
RECYCLED W ATER SHALL
BE I
DENTI
FIED AS DESCRI
BED I
N PLANS

LEGEND ON PLANS

I
TEM I
TEM
SI
ZE AND DESCRI
PTI
ON SI
ZE AND DESCRI
PTI
ON
NO NO

1 4" OR 6" AUTOMATI


C COMBI
NATI
ON AI
R RELEASE & AI
R/VACUUM 10 4" OR 6" C-900 PVC PI
PE
VALVE ASSEMBLY

2 BREAK-AW AY BOLTS,SEE NOTE 4 11 GATE W ELL W I


TH CAP PER SDW -153

3 4" OR 6" FLANGED 8-BOLT DUCTI


LE I
RON PI
PE 12 4" OR 6" FLG x MJ /
FLG RW GV
x REQ'
D LENGTH (
MAX OF 2 SPOOLS)

4 5/
8" x 3" STAI
NLESS STEEL DROP-I
N ANCHORS (
3 EA @ 120? 13
4 4" OR 6" FLANGE 90 BEND
APART)

15 SI
ZE x 4" OR 6" MJ /
FLG x FLG TEE
5 VALVE ENCLOSURE

6 42" x 42" x 6" THI


CK CONCRETE SLAB 16 W ATER MAI
N

7 COLD JOI
NT STRI
P

8 CONCRETE THRUST/
ANCHOR BLOCK

9 4" OR 6" FLG x MJ/


PO 90 BEND

RECOMMENDED BY THE CI
TY OF SAN DI
EGO
REVI
SION BY APPROVED DATE
STANDARDS COMMITTEE
CI
TY OF SAN DI
EGO - STANDARD DRAW I
NG
ORI
GINAL* KA J.NAGELVOORT 01/
12

2/
25/
16
UPDATED KA J.NAGELVOORT 12/
12
4" & 6" AUTOM ATI
C COM BI
NATI
ON COORDI
NATOR R.
C.E.56523 DATE
UPDATED AR J.NAGELVOORT 11/
15

UPDATED HM J.NAGELVOORT 02/


16
AI
R RELEASE & AI
R/VACUUM VALVE DRAW I
NG
SDW -
160
I
NSTALLATI
ONS NUMBER
NEW W ATER MAI
N OR UTI
LITY

CALDER COUPLI
NG
C
C SEE NOTE 3
3" C 3" C
C
6"
3"

C
C EXI
ST SEW ER MAI
N OR

C
C NEW SEW ER LATERAL
C

C
C

C
C
6"
C

C
3"

CONCRETE ENCASEMENT
C 24" MI
N C 24" MI
N SEE NOTE 3
C C
SEE NOTE 2 SEE NOTE 2

PLAN

C TRENCH W I
DTH EXI
ST STREET SURFACE
C
SEE SDW -110 C OR FI
NISH GRADE

CALDER COUPLI
NG
SEE NOTE 3
C
3" C 3" C
C
C A 6"
3"

C
EXI
ST SEW ER MAI
N OR
C

C
C NEW SEW ER LATERAL
C

C
C

C
C
6"
C

C
3"
C A
CONCRETE ENCASEMENT
C

TOP
4" MIN

C 24" MI
N C 24" MI
N SEE NOTE 3
C C
SEE NOTE 2 SEE NOTE 2
3" TYP C
C
C 6" TYP
C

NEW W ATER MAI


N C

OR UTI
LITY
C

ELEVATI
ON
#4 BARS 18" #4 BARS
ON CENTER 12" ON CENTER

ENCASEMENT SECTI
ON A-A
NOTES:
1)REFER TO SPECI FI
CATIONS FOR PROTECTION OF EXI STI
NG FACILITIES
2)ENCASEMENT SHALL EXTEND TO FI RST JOINT BEYOND BOTH SI DES OF TRENCH
[24" MI
N 48" MAX OF SUI
TABLE NATI
VE SUPPORT BEYOND
EDGE OF TRENCH] .
3)CONCRETE ENCASEMENT REQUI RED FOR SEW ER MAI NS ONLY.CALDER
COUPLI NGS REQUIRED FOR SEW ER LATERALS ONLY.SEW ER LATERALS
TO BE REPLACED W ITH SCH.80 PVC W ITH NO I NTERMEDI
ATE JOI NTS.
4)FOR PI PE BEDDI
NG AND TRENCH BACKFI LL,SEE OTHER STANDARD DRAW INGS.

LEGEND ON PLANS

RECOMMENDED BY THE CI
TY OF SAN DI
EGO
REVI
SION BY APPROVED DATE
STANDARDS COMMITTEE
CI
TY OF SAN DI
EGO - STANDARD DRAW I
NG
ORI
GINAL* KA J.NAGELVOORT 01/
12

02/
16
2/
25/
16
UPDATED AR J.NAGELVOORT
COORDI
NATOR R.
C.E.56523 DATE

PI
PE SUPPORT FOR UNDERCUT
DRAW I
NG
SEW ER M AI
NS OR SEW ER LATERALS SDW -
161
NUMBER
EXIST AC WATER MAIN

2'M:t SLURRY CRADLE

PLAN

TRENCH WIDTH TRENCH RESURFACING


SEE SDW-110 PEA SDG-107 & SDG-108

r
~------~----------~--------~1
A EXIST AC
WATER MAIN

T
: 4 • ••• : 6 ° •• ' : 6 • • • : ,; • • : b . • • • : 6° •• • : b • .•• -
\L._-------~~,1..:,... .k-u"""""_ _ _ _ _ _ _ __;D'2
: ..:.~:·::-:-. ::~~~ . :::~:·:.-: . :::~

... . ..IJ:
. b • • •• : 0

SLURRY CRADLE

----------o
.:..:N:::.f2N:..:........:MAI.:..:....:.:N.:....__ 1
OR UTIUTY "'/

ELEVATION

SECTION A-A

NOTES:
1) SLURRY SHALL BE CONTROLLED LOW STRENGTH MATERIAL CLSM (1QO-E-100)

2) SLURRY SHALL BE PLACED ON FIRMLY COMPACTED BACKALL

REVISION BY APPROVED DATE RECOMMENDED BY THE CITY OF SAN DIEGO


STANDARDS COMMITTEE
CllY OF SAN DIEGO - STANDARD DRAWING
ORIGINAL KA . NAGELVOOR OV12
oil~ 1/31/2012
COORDINATOR R.C.E. 65271 DATE
PIPE SUPPORT FOR UNDERCUT
AC WATER MAIN DRAWING
SDW-162
NUMBER
0 EXISTING 2-PORT FIRE HYDRANT
0 2" TE&90' ELBOW 'NI
SNAP-JOINT COUPLING(S)

0 2 V2" PORT TO 2" ADAPTER ELBOW


'N/THREADED FITTING
(2-GROOVE) 'N/DIRECTIONAL
SHUT OFF VALVE(S) (NOT SHOWN)

0 2" PIPE (GROOVED)


0 EXISTING CURB & GUTTER

8 2" 90' ELBOW 'N/THREADED


JOINT FITTINGS
0 EXISTING ROADWAY

0 2" BACKFLOW PREVENTER (ONE WAY


G EXISTING CONCRETE PAOOIDEWALK

CHECK VALVE) 'N/THREADED JOINT FITTINGS

0 SNAP-JOINT COUPLING (2-GROOVE)

REVISION BY APPROVED DATE RECOMMENDED BY THE CITY OF SAN DIEGO


STANDARDS COMMITIEE
CITY OF SAN DIEGO - STANDARD DRAWING
ORIGINAL

UPDATED
KA

KA
OVI2

12112
dl~ 12117/2012
COORDINATOR R.C.E. 65271 DATE

2" FIRE HYDRANT HIGHLINING CONNECTION DRAWING


NUMBER
SDW-170
8' MAXIMUM

0 EXISTING 3-PORT FIRE HYDRANT


0 4' SHUTOFF V/'J...VE
WITHREADED JOINT FmiNGS
0 PORT ADAPTER ELBOW
WITHREADED JOINT FITTING
0 EXISTING CURB & GUTTER

0 PIPE (GROOVED)
0 SAW CUT ROADWAY, TRENCH,
BACKFILL AND TEMPORARY
8 90" ELBOW WITHREADED
JOINT FITTINGS
ASPH/'J...T SURFACE

0 4' BACKFLOW PREVENTER


0 EXISTING ROADWAY

WITHREADED JOINT FITTINGS


0 EXISTING CONCRETE PAOOIDEWALK

REVISION BY APPROVED DATE RECOMMENDED BY THE Ct1Y OF SAN DIEGO


STANDARDS COMMITTEE
CllY OF SAN DIEGO - STANDARD DRAWING
ORIGINAL KA • NAGELVOOR OV12
oil~ 1/31/2012
COORDINATOR R.C.E. 65271 DATE

4 .. FIRE HYDRANT HIGHLINING CONNECTION DRAWING


NUMBER
SDW-171
0 GROOVED 2'x2'x1" TEE W!SNAP...JOINT
COUPUNG (2-GROOVE)
0 1" 00' ELBOW TO METER THREADS
(ADAPTERS MAY BE REQUIRED)

0 1" 00' ELBOW WITHREADED


JOINT FITIINGS
0 EXISTING WATER METER

0 1" SHUTOFF VALVE WITHREADED


0 EXISTNG WATER METER BOX

JOINT FITIINGS
0 EXISTNG SERVICE CONNECTION
FROM WATER MAIN
0 1" PIPE TO HOSE ADAPTER
® EXISTING ROADWAY
0 1" CONNECTION HOSE
0 EXISTING CURB & GLITIER

REVISION BY APPROVED DATE RECOMMENDED BY THE CITY OF SAN DIEGO


STANDARDS COMMITTEE
CllY OF SAN DIEGO - STANDARD DRAWING
ORIGINAL KA • NAGELVOOR OV12
oil~ 1/31/2012
COORDINATOR R.C.E. 65271 DATE
RESIDENTIAL USER
DRAWING
HIGHLINING CONNECTION NUMBER
SDW-172
5
C 1'- 0"
C
C 1'- 0"
C

C
1
3 2
4

C
C
C

C
DRI
VEW AY HI
GHLI
NING CROSSI
NG

7 6
C
C

8
4
C

CURB AND GUTTER HI


GHLI
NING RUN

1 HI
GHLI
NE PI
PING 5 EXI
STI
NG DRI
VEW AY

2 DRAI
N PI
PING 6 EXI
STI
NG CURB & GUTTER

3 TEMPORARY ASPHALT (
COLD MI
X) 7 EXI
STI
NG SI
DEW ALK

4 EXI
STI
NG ROADW AY 8 HI
GHLI
NE PI
PING AND SNAP COUPLI
NG (
2
GROOVE)

NOTES:
1.THE SLOPE OF THE TEMPORARY ASPHALT OVER DRI
VEW AYS SHALL BE FI
RM,STABLE,SMOOTH
AND SLOPED TO HAVE A GRADUAL TRANSI
TION TO THE STREET.THE RUNNI
NG SLOPE
SHALL NOT EXCEED 8.
33%.THE CROSS SLOPE SHALL MATCH THE EXI
STI
NG GUTTER SLOPE.

2.THE MI
NIMUM ASPHALT COVER ON HI
GHLI
NE PI
PE SHALL BE 1I
NCH.

3.SI
DEW ALK CROSSI
NG MAY BE ROUTED ABOVE GROUND AND COVERED W I
TH ADA
COMPLI
ANT CABLE COVER AND RAMP.

RECOMMENDED BY THE CI
TY OF SAN DI
EGO
REVI
SION BY APPROVED DATE
STANDARDS COMMITTEE
CI
TY OF SAN DI
EGO - STANDARD DRAW I
NG
ORI
GINAL KA J.NAGELVOORT 01/
12

02/
16
2/
25/
16
UPDATED JB J.NAGELVOORT
COORDI
NATOR R.
C.E.56523 DATE

HI
GHLI
NING CROSSI
NG & RUN
DRAW I
NG
AT DRI
VEW AYS AND CURBS SDW -
173
NUMBER
4
2% MAX 8% MAX

C
C
C

C
C
C
5 3 2 1

CURB RAMP HI
GHLI
NING CROSSI
NG
SECTI
ON A-A
EXI
STI
NG RAMP TO REMAI
N

4
SAW CUT EDGE OF
GUTTER

C
C
C

C
6"±

C
1 HI
GHLI
NE PI
PING

C
2 2 - 2" DRAI
N PI
PES
1 3

3 TEMPORARY ASPHALT (
COLD MI
X)

4 EXI
STI
NG ROADW AY
CURB RAMP UNDERGROUND HI
GHLI
NING CROSSI
NG SECTI
ON B-B

5 PROTECTI
VE PLASTI
C COVER (
OPTI
ONAL) EXI
STI
NG RAMP TO BE REPLACED

A 1.
5%
B 1.
5%
MAX
C C MAX
C SAW CUT

TRANSI
TIONAL

C
2% MAX HI
GHLI
NING
PROPERTY LI
NE PROPERTY LI
NE
1.5%

SECTI
ON
MAX

CC
C

10% MAX
C

C
1.5%

UNDERGROUND
MAX

HI
GHLI
NING
8% MAX C
C
SECTI
ON
C

C CB
C

C SI
DEW ALK C

SI
DEW ALK
CA EXI
STI
NG CURB
TRANSI
TIONAL
RAMP TO BE
HI
GHLI
NING
REPLACED
SECTI
ON

NOTES:
1.THE SLOPE OF THE TEMPORARY ASPHALT OVER CURB RAMPS AND OTHER ACCESSI
BLE ROUTES (
SIDEW ALKS,W ALKW AYS,
ETC.
)SHALL BE FI
RM,STABLE,SMOOTH AND SLOPED TO HAVE A GRADUAL TRANSI
TION TO THE STREET.THE FI
NISH
CONNECTI
ON AT THE CURB RAMPS,OTHER ACCESSI
BLE ROUTES AND ROAD SURFACES SHALL BE FLUSH.THE RUNNI
NG
SLOPE SHALL BE AS SHOW N ON THE DRAW I
NG ABOVE AND THE CROSS SLOPE SHALL NOT EXCEED 2.
0%,W I
TH NO
EXCEPTI
ONS.

2.THE MI
NIMUM ASPHALT COVER ON HI
GHLI
NE PI
PE SHALL BE 2 I
NCHES.

3.CURB RAMP UNDERGROUND HI


GHLI
NING CROSSI
NG TO BE USED ONLY W HEN EXI
STI
NG CURB RAMP I
S BEI
NG REPLACED.

4.COUPLI
NGS SHALL NOT BE LOCATED I
N FRONT OF THE CURB RAMP.

5.HI
GHLI
NE CROSSI
NG THE SI
DEW ALK ABOVE GROUND SHALL BE COVERED W I
TH ADA COMPLI
ANT CABLE COVER AND RAMP.

RECOMMENDED BY THE CI
TY OF SAN DI
EGO
REVI
SION BY APPROVED DATE
STANDARDS COMMITTEE
CI
TY OF SAN DI
EGO - STANDARD DRAW I
NG
ORI
GINAL JB J.NAGELVOORT 02/
16

2/
23/
16
COORDI
NATOR R.
C.E.56523 DATE

HI
GHLI
NING CROSSI
NG & RUN
DRAW I
NG
AT CURB RAM PS SDW -
174
NUMBER
NOTES:
1) REFER TO AGENCY SPECIFICATIONS WHERE APPLICABLE
2) SET TOP OF METER BOX 2• ABOVE FINISH GRADE
3) BLOW-OFF ASSEMBLIES INSTALLED FOR THE USE OF RECYCLED
WATER SHALL BE IDENTIFIED AS DESCRIBED IN AGENCYS
SPECIFICATIONS
4) THE CONSTRUCTION OF A TEMPORARY BLOW-OFF FOR THE USE OF
TESTING AND FLUSHING OF NEW MAINS ONLY
5) CAM & GROOVE ADAPTER SHALL BE DRILLED AND TAPPED AS
REQUIRED FOR THE PRESSURE PET COCK
6) MATERIALS SHALL BE SELECTED FROM THE AGENCYS
APPROVED MATERIALS LIST LEGEND ON PLANS
ITEM ITEM
SIZE AND DESCRIPTION SIZE AND DESCRIPTION
NO NO

CD POLYMER METER BOX WITH LID 17" x 30" ® 2" 90" BRONZE IRON PIPE THREAD BY
COMPRESSION ELL
®
~
2" CAM & GROOVE ADAPTER x MIPT 2" CLOSE NIPPLE IPT
WITH LOCKING DUST CAP, SEE NOTE 5 2" COMPRESSION x FIPT BALL VALVE WITH
HANDLE
1/4" PRESSURE PET COCK
2• x REQUIRED LENGTH COPPER PIPE
® 3/8" ROCK 6" DEEP

TYPE "K.. RIGID OR SOFT


@ DI END CAP WITH 2.5" FIPT OUTLET

® CONCRETE THRUST BLOCK SEE WT-01

~
WATER MAIN
NYLON DIELECTRIC BUSHING (2.5" x 2")

Revision RECOMMENDED BY THE SAN DIEGO


SAN DIEGO REGIONAL STANDA RD DRAWING REGIONAL STANDARDS COMMITTEE
ORIGINAL Kercheval 12 75
Add Metric T. Stanton 03/03
J. Tomasulo 10/04 TEMPORARY 2" BLOW-OFF
INSTALLATION ORA'MNG
WB-05
NUMBER
FOR DRAW ING WT-01 SEE DRAW ING SDW-151
ROUNDED CONCRETE

4" DIAMETER
GALVANIZED STEEL
POST 1/4" WALL
1I 4" WALL FILLED
WITH CONCRETE
CHAIN HASP SEE
DETAIL BELOW
•N
FINISH GRADE FINISH GRADE

•ao
CONCRETE FOOTING
5" DIAMETER
GALVANIZED PIPE
...
SLEEVE 1I 4. WALL
•CD
;!_ CONCRETE FOOTING


LEGEND ON PLANS

~DIAMETER
•CD DEMOUNTABLE PROTECTION POST
TYPE "8"
@
PROTECTION POST
TYPE "A" LEGEND ON PLANS

4-CHAIN UNK
SEGMENT WELDED GALVANIZED STEEL
TO POST POST 1/4" WALL
3-CHAIN UNK
SEGMENT WELDED
TO SLEEVE

5" DIAMETER
GALVANIZED PIPE
SLEEVE 1/4" WALL

CHAIN HASP DETAIL


NOTES:
1) TYPE "A" AND TYPE "B" PROTECTION POSTS SHALL BE INSTALLED WHERE INDICATED ON THE
APPROVED PLANS OR AS DIRECTED BY THE ENGINEER. SDGc!cE REQUIREMENTS DICTATE IN
AREAS OF SDGc!cE EQUIPMENT
2) CHAIN TO BE 1/4" PROOF COIL CHAIN GALVANIZED STEEL. WELD 4-LINK SEGMENT TO
POST AND 3-LINK SEGMENT TO SLEEVE
3) TYPE "A" AND TYPE "B" PROTECTION POSTS SHALL BE COATED USING SAFETY YELLOW IN
ACCORDANCE WITH AGENCY'S STANDARDS
Revision By Approved Date RECOMMENDED BY THE SAN DIEGO
SAN DIEGO REGIONAL STANDARD DRAWING REGIONAL STANDARDS COMMITTEE
ORIGINAL Kercheval 12 75
Add Metric T. Stanton 03/03 7/Z6/ZOIZ
J. Tomasulo 10/04
Delete Metric MR B. KNOLL 03/11
PROTECTION POST INSTALLATION
DRAWING
NUMBER WM-04
:I:
u
z
LLI
~

PLUG WITH SUITABLE


MATER~ TO HOLD CONCRETE
. ,
PLUG WITH SUITABLE CUT A 12• HOLE IN TOP
MATERIAL TO HOLD CONCRETE OF PIPE AND PLUG 24•
OF PIPE WITH CONCRETE SEE
MIDDLE OF EXIST MAIN NOTE 3 BELOW

. ,
PLUG WITH SUITABLE
MATERIAL TO HOLD CONCRETE

END OF EXIST MAIN

NOTES:
1) REFER TO AGENCY SPECIFICATIONS WHERE APPLICABLE
2) WATER AND RECYCLED WATER MAINS AND SEWER LATERALS 4• DIAMETER AND
SMALLER SHALL HAVE A SHORT SECTION OF PIPE REMOVED AND PIPE ENDS ENCASED IN
CONCRETE
3) EXISTING MAIN TO BE PLUGGED WITH CONCRETE OR PRESSURE GROUTED AT INTERVALS OF
ABOUT 200' OR AS DIRECTED BY THE ENGINEER
4) EXISTING MAINS 16• AND LARGER REQUIRE THE ENTIRE LENGTH OF THE PIPE TO BE
FILLED BY PRESSURE GROUTING OR BY BLOWN SAND
5) EXISTING VALVES SHALL BE TURNED TO THE CLOSED POSITION. REMOVE GATE WELL AND
REPLACE WITH COMPACTED BACKFILL
6) FOR ABANDONMENT OF MANHOLES SEE SM-08
7) PRIOR AGENCY APPROVAL REQUIRED FOR CUTTING AND PLUGGING

Revision By Approved Date RECOMMENDED BY lHE SAN DIEGO


SAN DIEGO REGIONAL STANDARD DRAWING REGIONAL STANDARDS COMMITTEE
ORIGINAL J. Tomasulo 10/04
Delete Metric MR B. KNOLL 03/11
CUTIING AND PLUGGING ABANDONED WATER,
RECYCLED WATER AND SEWER MAINS DRAWING
NUMBER WP-03
r*F;~~~......u.~.
co

~~---,--,-----, _l

WATER OR
SEWER MAIN
TRENCH BOTTOM
SLOPE PROTECTION
FOR GRADES OVER 50% WALL SECTION 'A' ELEVATION

FINISH GRADE
WALL SECTION 'A' PLAN

WATER OR
SEWER MAIN
TRENCH BOTTOM

SLOPE PROTECTION
FOR GRADES 20% TO 50% SEE WALL
NOTES: SECTION A
1) REFER TO AGENCY SPECIFICAliONS WHERE APPLICABLE
2) THE DETAILS SHOWN REPRESENT THE MINIMUM REQUIRED. THE ENGINEER OF WORK IS REQUIRED
TO PROVIDE A SUBMITTAL TO THE AGENCY OF JURISDICTION FOR REVIEW AND APPROVAL BY
THE AGENCY'S ENGINEER PRIOR TO INSTALLATION
3) WALLS SHALL BE REINFORCED CONCRETE OR 8" x a• x 16" CONCRETE BLOCK, REINFORCED AND
ALL CORES FILLED WITH GROUT SEE SPECIFICAliONS
4) FOR GRADES OVER 50%, SLOPE PROTECTION SHALL ALSO INCLUDE AC PAVING,
CONCRETE SLAB OR GUNITE BLANKET PLACED OVER THE PIPELINE ALIGNMENT ---+------H---
5) 4• GUNITE BLANKET WITH s• SQUARE x 10 GAGE WIRE FABRIC AT THE
ENGINEERS DISCRETION LEGEND ON PLANS
Revision By Ap roved Date RECOMMENDED BY lHE SAN DIEGO
SAN DIEGO REGIONAL STANDARD DRAWING REGIONAL STANDARDS COMMITTEE
ORIGINAL J. Tomasulo 10/04
Delete Metric MR B. KNOLL 03/11

SLOPE PROTECTION INSTALLATIONS


DRAWING
NUMBER WP-05
8" CONCRETE WALL

/14 BARS

AC PAVEMENT/
FINISH GRADE

·.. : . BACKFILL .· · . :

WATER OR
SEWER MAIN

TRENCH BOTTOM

.. ·· ..
lsE~· WALL
CUT-OFF WALL
FOR GRADES 20% TO 50% •
SECTION 'A'
WALL SECTION 'A' ELEVATION

WATER OR
SEWER MAIN
12"

WALL SECTION 'A' PLAN

NOTES:
1~ REFER TO AGENCY SPECIFICA TlONS WHERE APPLICABLE
2 FOR USE AS TRENCH BACKFILL STABILIZATlON IN TRAVELED AREAS
3 THE DETAILS SHOWN REPRESENT THE MINIMUM REQUIRED. THE ENGINEER OF WORK IS
REQUIRED TO PROVIDE A SUBMITTAL TO THE AGENCY OF JURISDICTlON FOR REVIEW AND
APPROVAL BY THE AGENCY'S ENGINEER PRIOR TO INSTALLATlON
4) WALLS SHALL BE REINFORCED CONCRETE OR 8" x 8" x 16" CONCRETE BLOCK, REINFORCED
AND ALL CORES FILLED
WITH GROUT SEE SPECIFICA TlONS ---+------+----
5) FOR GRADES OVER 50% SEE WP-05/SP-05 LEGEND ON PLANS
Revision By Approved Date RECOMMENDED BY THE SAN DIEGO
SAN DIEGO REGIONAL STANDARD DRAWING REGIONAL STANDARDS COMMITTEE
ORIGINAL J. Tomasulo 10/04
Delete Metric MR B. KNOLL 03/11 7(26(2012
CUT -OFF WALL INSTALLATION IN
TRAVELED AREAS DRAWING
NUMBER WP-07
24" FROM PROPERlY
UNE, EDGE OF PAVEMENT
OR EDGE OF RIGHT OF WAY

STREET TYP METER BOX TYPICAL


SEE NOTE 6 &: 7

NOlES:
1) REFER TO AGENCY SPECIFICATIONS WHERE APPLICABLE
2) STAMP OR CHISEL A 2" HIGH 'W' IN CURB FACE TO IDENTIFY
POTABLE WAlER SERVICE LOCATION
3) STAMP OR CHISEL A 2" HIGH 'RW' IN CURB FACE TO IDENTIFY
RECYCLED WAlER SERVICE LOCATION
4) MElER BOXES ARE NOT TO BE INSTALLED IN DRIVEWAYS, SIDEWALKS OR
WITHIN PAVED ROADWAYS
5) MULTIPLE MElER BOXES SHALL BE INSTALLED WITH A MINIMUM OF 9"
BETWEEN BOXES
6) MElER BOX SHALL BE INSTALLED 9" FROM THE BACK OF BERM, CURB, OR
SIDEWALK (TYP)
7) AN EASEMENT MAY BE NEEDED DEPENDING ON LOCATION OF MElER BOX
8) MElER BOXES INSTALLED FOR THE USE OF RECYCLED WAlER SHALL BE
IDENTIFIED AS DESCRIBED IN AGENCV'S SPECIFICATIONS
9) MAlERIALS SHALL BE SELEClED FROM THE AGENCV'S APPROVED MAlERIALS
LIST
Revision By Approved Date RECOMMENDED BY THE SAN DIEGO
SAN DIEGO REGIONAL STANDARD DRAWING REGIONAL STANDARDS COMMITTEE
ORIGINAL Kercheval 12 75
T. Stanton 03/03
J. Tomasulo 10/04 METER BOX LOCATIONS FOR WATER AND
elete Metric MR B. KNOLL 03/11 RECYCLED WATER APPURTENANCES DRAWING
NUMBER WS-03
I> • • • I>

14

JOINT R STRAINT
REQUIRED TO THE
16" I. JOINT Rf,,STRAINT
REQUIRED TO THE

MAIN LINE ALL AROUND RP DEVICE


SEE NOTE 5 SEE NOTE 5
PLAN VIEW

~~~~~~~~-~·~
JG:-- ~-·-@
I• TO THE ~p
DEVICE •
FROM E MAIN
SECTION AS REQUIRED
LINE SEE NOTE 5
SEE NOTE 5

(INDICATE SIZE)

~
FOR MATERIAL DESCRIPTIONS AND NOTES SEE WS-04 ( 2 OF 2) LEGEND ON PLANS

Revision By Approved Dote RECOMMENDED BY THE SAN DIEGO


SAN DIEGO REGIONAL STANDARD DRAWING REGIONAL STANDARDS COMMITTEE
ORIGINAL J. Tomasulo 10/04
Delete Metric MR B. KNOLL 03/11 11
4;; OR 6 FIRELINE/MASTER METER
INSTALLATION DRAWING WS 04 (l
NUMBER - OF 2>
FOR DRAWING OF THE METER INSTALLATION SEE WS-04 (SHEET 1 OF 2)

NOTES:
1) REFER TO AGENCY SPECIFICATIONS WHERE APPLICABLE
2) TO BE USED WHERE BOTI-1 DOMESTIC SERVICE AND FIRE PROTECTION ARE INSTALLED ON 11-IE
SAME PRIVATE SYSTEM
3) LOCATION OF METER SHALL BE APPROVED BY 11-IE DISTRICT ENGINEER PRIOR TO INSTALLATION
IN ACCORDANCE 'MTI-1 STANDARD DWG WS-06
4) 8" OR 10" METERS TO BE DESIGNED BY AN ENGINEER AND SUBMITTED FOR
AGENCYS APPROVAL AS NEEDED ON A CASE-BY-CASE BASIS
5l JOINT RESTRAINT SHALL BE IN ACCORDANCE 'MTI-1 AGENCY SPECIFICATIONS
6 METERS SHALL BE FURNISHED AND INSTALLED BY 11-IE AGENCY OF JURISDICTION
7 4" METER REQUIRES A 48" x 60" VAULT 6" METER REQUIRES A 48" x 72" VAULT
8 IN AREAS WHERE GROUND WATER IS PRESENT 11-IE AGENCYS ENGINEER MAY REQUIRE A
SEALED SUMP TO BE CONSTRUCTED
9) CONNECTIONS TO STEEL WATER MAINS SHALL BE IN ACCORDANCE 'MTI-1 AGENCY SPECIFICATIONS
1O)MATERIALS SHALL BE SELECTED FROM 11-IE AGENCYS APPROVED MATERIALS
LIST

ITEM ITEM
NO
SIZE AND DESCRIPTION NO
SIZE AND DESCRIPTION

<D 2" x REQUIRED LENGTI-1 TYPE "K" COPPER


PIPE
@ FRP VAULT 'MTI-1 HINGED ACCESS DOOR,
SEE NOTE 7

~
2" BRONZE CORPORATION STOP © 12" DIAMETER x 6" LONG PVC PIPE
LINE SIZE x 2" SERVICE SADDLE
4" OR 6" PVC PIPE @ 2" 90° COMPRESSION ELL (TYPICAL)
4" OR 6" FLG x MJ RWGV MECHANICALLY
RESTRAINED, SEE NOTE 5 Q1) LINE SIZE x 24" LONG FLANGED
DUCTILE-IRON SPOOL

® LINE SIZE x 6" LONG FLG x PE @ 8" GATE WELL. SEE WV- 01 & WV- 02
DUCTILE-IRON SPOOL
(?)
®
2" COMPRESSION, LOCKABLE BALL VALVE

4" OR 6" FLEXIBLE COUPLING


§ HINGED VAUl..T ACCE:SS DOOR
ADJUSTABLE PIPE SUPPORT (TYPICAL)
6" CLASS "8" CONCRETE FLOOR 'MTH #3
BARS 0 12" C.C.
®
@
LINE SIZE x 30" LONG FLG x PE
DUCTILE-IRON SPOOL
4" OR 6" FIREUNE METER SEE NOTE 6
3 6" DG BASE COMPACTED TO 903
12" DIAMETER x 12" DEEP, i°' GRAVEL
SUMP, SEE NOTE 8

Revision By Approved Date RECOMMENDED BY lHE SAN DIEGO


SAN DIEGO REGIONAL STANDARD DRAWING REGIONAL STANDARDS COMMITTEE
ORIGINAL J. Tomasulo 10/04
Delete Metric MR B. KNOLL 03/11 ~7(Z6(ZOIZ
4" OR 6" FIRELINE/MASTER METER Cfllirrpehon R.C.E. 19246 Dote
INSTALLATION DRAWING WS- 04 <2 or 2>
NUMBER
FOR DRAWINGS WV-01 AND WV-02 USE DRAW ING SDW-153.
• x 2" DISC DETAIL "A"
FLAT STACK WELDED

1" STEEL ROUND STOCK


LENGTH AS REQUIRED

NOTES:
1) REFER TO AGENCY SPECIFICATIONS WHERE APPLICABLE
2) EXTENSION STEUS SHALL BE ROUND STEEL TUBING OF SOLID DESIGN (NO PINNED
COUPLINGS PERUITTED)
3) VALVES DEEPER THAN 5' AND 2" AIR VALVES REQUIRE A VALVE STEU EXTENSION OR
AS REQUIRED BY THE AGENCY OF JURISDICTION
4) EXTENSION STEUS SHALL NOT BE ATIACHED/BOLTED TO OPERATING NUT OF THE VALVE
5) MATERIALS SHALL BE SELECTED FROU THE AGENCY'S APPROVED MATERIALS
LIST

Revision RECOMMENDED BY THE SAN DIEGO


SAN DIEGO REGIONAL STANDARD DRAWING REGIONAL STANDARDS COt.lt.IITTEE

T. Stanton
J. Tomasulo 10/04 STEEL VALVE STEM EXTENSION FOR
MR B. KNOLL 03/11 VALVES 2" AND SMALLER DRAW1NG
NUMBER WV-05
Please adjust this spine guide marks to the final determined number of pages.

STANDARD DRAWINGS |For Public Works Construction|Edition


STANDARD
DRAWINGS
For Public Works Construction
Public Works Department 2016 Edition
PROJECT IMPLEMENTATION DIVISION
STANDARDS & CONTRACT
DOCUMENTS SECTION
525 B STREET STE. 750
SAN DIEGO, CA 92101
DOCUMENT NUMBER: PWPI070116-03

2016