You are on page 1of 11

ASHIDA Numerical 3OC + 1EF Type: ADR141C

( AD I T Y AS e r i e s )
Protection Relay (Preliminary)

Protection Features: Relay Design Features:


9 4 Element (3 Phase + EF) Non Directional 9 16 x2 LCD Backlit display for Parameter
Over current IDMT/DMT. and setting display
9 Selection of Curve: Five selectable curve 9 Online display of CB status and other digital
(Normal Inverse1 (C1), Normal Inverse2, and logical status.
(C2) Very inverse (C3), Extremely inverse 9 Continuous monitoring of module’s internal
(C4), Long time inverse (C5)) and Define hardware and alarm generation in case of
Time (C6) failure of any critical components.
9 Instantaneous Over-Current Protection with 9 4 Digital Output contacts for local alarm as
adjustable timer. Trip
9 Breaker Failure detection 9 2 dedicated status input for Trip Circuit
9 In-built CB Trip Circuit Supervision function Monitoring
during pre closing and post closing of CB. 9 5 nos of Fault data stored with keypad
9 On site CT Secondary selection 1A or 5A. interface and time stamping.
9 Internal calculation of zero seq. current
Description:
(3Io) for Earth fault
ADR141C is second generation Numerical 3OC
9 Wide range Power supply input 18V to
+ 1EF Over Current Relay. It consist all the
250V AC/DC
necessary protection and monitoring functions
9 Cold Load Pickup
required for Normal feeder It consist of

Note: Due to our policy to upgrade our products constantly, we reserve the right to
supply products which may vary slightly from that indicated above.

ASHIDA ELECTRONICS PVT LTD.


ASHIDA HOUSE, Plot No. A-308, Road No. 21, Ref.:ADR141C
Wagle Industrial Estate,Thane (W)-400 604. INDIA.
E-mail: sales@ashidaelectronics.com Issue: 05 07.03.2011
Web: www.ashidaelectronics.com Page 1 / 9
ASHIDA Numerical 3OC + 1EF Type: ADR141C
( AD I T Y AS e r i e s )
Protection Relay (Preliminary)

1. High Speed Digital DSP Controller station battery. The power supply module is
2. Analog Measuring Module design using very advance PWM controller
3. Power supply Module which allow very wide input supply variation i.e.
4. Digital Input output module. 18V to 250VAC/DC covering 24Vdc, 30Vdc,
110Vdc and 220Vdc station battery
The High speed Digital Signal Controller
requirement.
continuously monitors phase, E/F current along
with different optical isolated status The relay is having total 4 nos of high intensity
connections. The high-speed micro-controller dual LED for easy identification of type of fault
samples these current signals through a A/D for easy user interface. All LEDs and control
converter. The Digital Signal performs output R1 to R4 are fully programmable via
powerful Numerical Algorithms to find out keypad interface
RMS of fundamental & harmonic contents of
Main Functions
the current then this value is used for protection
The ADR141C are having following protection
and metering function. All measurement is
functions.
tuned to fundamental frequency i.e 50Hz, thus
1. Non Directional phase Over current
relay remain stable during distorted waveform
element. (Ip>, and Ip>> )
generated electronics loco-motive. All these
2. Non Directional 3Io (Internally derived EF)
measure values are then used for different
(3Io> and 3Io>>).
protection function such as IDMT/DMT Over
3. Trip Circuit Super vision.
current protection, Instantaneous Over current
4. Breaker Failure Detection.
protection, Earth Fault protection, etc. These
5. Monitoring Functions.
measured values are also displayed on large
Each of these functions are independently
16 x 2 LCD display for metering purpose. The
programmable and can be enable or disable by
DSC also monitors different digital input
user depending upon requirement.
through optical isolator and perform some
monitoring function such trip circuit supervision,
Over Current & EF Element:
and control potential free contact for control CB
The ADR141C is member of Ashida Numerical
and generate ALARM and Tele-signalling
Relay family design for protection general
feeder. The relay has one stage of IDMT/DMT
The power supply module is basically DC – DC
setting and one stage of instantaneous setting.
converted designed using modern PWM based
(Ip>, IP>>, 3Io>, 3Io>>). All major international
Switching mode technique to convert station
IDMT curves are available. Range for first stage
battery supply to the 12V and 24Vdc low
is 10% to 200% and 50% to 3000% for
voltage supply for relay electronics and control
instantaneous stage for phase and 3Io.
circuit. It also provides necessary isolation from

Note: Due to our policy to upgrade our products constantly, we reserve the right to
supply products which may vary slightly from that indicated above.

ASHIDA ELECTRONICS PVT LTD.


ASHIDA HOUSE, Plot No. A-308, Road No. 21, Ref.:ADR141C
Wagle Industrial Estate,Thane (W)-400 604. INDIA.
E-mail: sales@ashidaelectronics.com Issue: 05 07.03.2011
Web: www.ashidaelectronics.com Page 2 / 9
ASHIDA Numerical 3OC + 1EF Type: ADR141C
( AD I T Y AS e r i e s )
Protection Relay (Preliminary)

B+
Although the curves tend towards infinite when TCCOM
1

6 To Relay CPU
the current approaches Is (general threshold), 2

S4
CB NO
the minimum guaranteed value of the operating
B-
1
current for all the curves with the inverse time 6 To Relay CPU
S3 2
TC
characteristic is 1.1Is (with a tolerance of ± CB NC

0.05Is). Fig. Trip Circuit Logic

Relay monitor Trip coil continuity through CB


Inverse Time Curves:-
NO during close condition and through CB NC
The each stage thresholds for phase (earth)
during Trip condition. If any discontinuity
over current can be selected with an Inverse
observed it generate Alarm signal.
Definite Minimum Time (IDMT) characteristic.
The output can be assigned to any of 4 relay
The time delay is calculated with a
RL1 to RL4, The Trip circuit supervision logic
mathematical formula
set reset PROTH (Protection healthy) bit, it
K * a normally ON and become OFF at following
t= b condition
I
1 9 When DC supply is not sufficient (DC fail)
Iref
9 When CB NO and CB NC both active or
both inactive. CB NO as will as CB NC are
Curve Description a b
Type both close or open.
C1 Standard 0.14 0.02 9 Relay detects any internal hard ware Error.
Inverse_1
C2 Standard 0.06 0.02 Breaker Failure Detection:-
Inverse_2
Normally after tripping current should become
C3 Very Inverse 13.5 1
Zero within 100 – 200ms time depend upon
C4 Extremely inverse 80 2
type of fault and breaker mechanism. After
C5 Long Time Inverse 120 1
Fault ADR141C trigger internal timer (settable
C6 Define Time - -
from 50ms to 800m) if fault is not cleared during
Trip circuit Supervision:- this time then relay declare as Breaker fail (LBB
The ADR141C is having 2 separate digital opto- function) and set BF bit. This bit can be
coupler status input which can be used to assigned to any of the output relay.
continuously monitor continuity of trip-circuit.
The general scheme is as shown in fig. 4. Cold Load pickup:-
When the Circuit breaker is closed on load, A
load current take sudden inrush current. This
inrush current may be more than 4 to 5 times of

Note: Due to our policy to upgrade our products constantly, we reserve the right to
supply products which may vary slightly from that indicated above.

ASHIDA ELECTRONICS PVT LTD.


ASHIDA HOUSE, Plot No. A-308, Road No. 21, Ref.:ADR141C
Wagle Industrial Estate,Thane (W)-400 604. INDIA.
E-mail: sales@ashidaelectronics.com Issue: 05 07.03.2011
Web: www.ashidaelectronics.com Page 3 / 9
ASHIDA Numerical 3OC + 1EF Type: ADR141C
( AD I T Y AS e r i e s )
Protection Relay (Preliminary)

rated load current. The duration can be as high


as 200ms. Due to this inrush current many
times relay get operate which is undesirable.
General practice is to keep normal setting to
such high value so that it will not mal operate at
initial closing which result increase in fault
clearance time. To avoid such problem relay is
equipped with special features known as clod
load pickup. Whenever a circuit breaker is turn
on relay sense through CB auxiliary contact
and start internal timer known as CL timer.
During this time it takes separate set of setting,
so that relay will not mal operate on inrush
current

Programmable DI/DO and LED:-


The ADR141C has 4 digital outputs, 2 opto-
isolated input and 8 general purpose LEDs.
These can be programmed by local key board.
Any logical of physical status can be assigned to
any relay contact The logic of digital status input
as well as logical status can be formed and
assigned to any of the relay output. The RL1
relay is by default assign to TRIPING CB.

Note: Due to our policy to upgrade our products constantly, we reserve the right to
supply products which may vary slightly from that indicated above.

ASHIDA ELECTRONICS PVT LTD.


ASHIDA HOUSE, Plot No. A-308, Road No. 21, Ref.:ADR141C
Wagle Industrial Estate,Thane (W)-400 604. INDIA.
E-mail: sales@ashidaelectronics.com Issue: 05 07.03.2011
Web: www.ashidaelectronics.com Page 4 / 9
ASHIDA Numerical 3OC + 1EF Type: ADR141C
( AD I T Y AS e r i e s )
Protection Relay (Preliminary)

While Ordering Specify the following Information for ADR141C Relay

Definition of Model No of Aditya Series of Relays

AM XXX–XX – X – X – XX – X

Reserved for Future Use

Auxiliary Supply
PT Secondary 01 = 18 – 52 V dc 04 = 30 V dc
0 = NO PT 02 = 77 – 250 V dc 05 = 48 V dc
03 = 24 V dc 06 = 18 – 250 V dc

CT Secondary
1 = 1 Amp.
2 = 5 Amp.
3 = 1 Amp. / 5 Amp. Selectable

AM XXX XX X
Over Current Earth Fault Relay
For Adity-V2 series start from 201. For V1 series refer respective document
201 01 Obsolete Version CSE – H – 150 3
201 02 Relay with standard Back Connection (not CSF – H – 136 3
Recommended)
201 03 Relay with Ring Type Back Connections CSF – H – 136 3

Ordering information:

A D R 1 4 1 C - A M - X X X - X X - X - X - X X - X

Example
AD R 1 4 1 C – AM - 2 0 1 - 0 2 - 3 - 1 - 0 6 - 0
T yp e : A D R 1 4 1 C
St. Back terminal layout
C a b i n e t T yp e : C S F - 1 5 0 H
Auxiliary Supply: 18-250Vdc
C T s e c : 1 Amp. / 5 Amp selectable

Note: Due to our policy to upgrade our products constantly, we reserve the right to
supply products which may vary slightly from that indicated above.

ASHIDA ELECTRONICS PVT LTD.


ASHIDA HOUSE, Plot No. A-308, Road No. 21, Ref.:ADR141C
Wagle Industrial Estate,Thane (W)-400 604. INDIA.
E-mail: sales@ashidaelectronics.com Issue: 05 07.03.2011
Web: www.ashidaelectronics.com Page 5 / 9
ASHIDA Numerical 3OC + 1EF Type: ADR141C
( AD I T Y AS e r i e s )
Protection Relay (Preliminary)

Technical Specifications:
General specifications
Sr. No. Specification Particulars
I. Current Input : Suitable for CT secondary 5Amp. Or 1Amp site selectable
II. Aux. Supply : 18 - 250VDC.
III. VA burden on CT : Less than 0.2VA
IV. VA burden on Aux. : Less than 10 Watts
V. Operating Temp. range : -10 deg. To + 65 deg.
VI. Continuous carrying capacity : 2 x of rated for CT and 1.5 x of rated for PT
VII. Pick up : Within 1.1 times of set value.
VIII. Reset Value : 95% to 90% of pick up.
IX. Output Contact : 4 Trip duty user assignable
X. Contact Rating : Continuous: 5A
: Make & carry for 0.5 sec : 30A
: Make carry for 3 sec : 15A
XI. Opto Isolated input : 1 for CB NO & 1 for CB NC
XII. Thermal With stand for CT : 20 x of rated for 3.0 sec.
General Settings
XIII. General setting : New PassWord 0 – 99 in steps of 1
: Unit Id 0 – 250 in steps of 1
: CT Sec 1A or 5A
: CT Primary 10 - 2000in steps of 10
: Test Block 01: YES, 02: NO
: Trip Ckt. 01: YES, 02: NO
:BF Enable 01: YES, 02: NO
: BF Delay 50-800 mS steps of 50ms
Relay Settings
XIV. Phase Section (Ip) : IP> Settings 10% – 250% in steps of 1%.
: IP> Time Multiplier (TMS) x0.01 – x1.00 in steps of 0.01
: IP> Curve (Operating Time) C1 – C6 ( IDMT curve C1 – C5 or Define
Time C6 )
: IP> C6 Delay 0 – 99.9 Sec in steps of 0.1Sec.
: IP>> Settings 00% – 3000% insteps of 50% 00 means
block
: IP>> Delay 0 – 2.00 Sec in steps of 0.01Sec.
XV. Earth Fault Section (3Io) : 3Io> Settings 10% – 250% insteps of 1%
: 3Io> Time Multiplier (TMS) x0.01 – x1.00 in step of 0.01.
: IE> Curve (Operating Time) C1 – C6 ( IDMT curve C1 – C5 or Define
Time C6 )
: 3IO> C6 Delay 0 – 99.9 Sec in steps of 0.1Sec.
: 3IO>> Settings 00% – 3000% insteps of 50% 00 means
block

Note: Due to our policy to upgrade our products constantly, we reserve the right to
supply products which may vary slightly from that indicated above.

ASHIDA ELECTRONICS PVT LTD.


ASHIDA HOUSE, Plot No. A-308, Road No. 21, Ref.:ADR141C
Wagle Industrial Estate,Thane (W)-400 604. INDIA.
E-mail: sales@ashidaelectronics.com Issue: 05 07.03.2011
Web: www.ashidaelectronics.com Page 6 / 9
ASHIDA Numerical 3OC + 1EF Type: ADR141C
( AD I T Y AS e r i e s )
Protection Relay (Preliminary)

: 3IO>> Delay 0 – 2.00 Sec in steps of 0.01Sec.


Cold Load settings
XVI. Phase Section (Ip) :CL Enable 01: YES, 02: NO
: CL Timer 0-2.00S in steps of 0.01 sec
: IP> Settings 10% – 250% in steps of 1%.
: IP> Time Multiplier (TMS) x0.01 – x1.00 in steps of 0.01
: IP> Curve C1 – C6
(Operating Time) ( IDMT curve C1 – C5 or Define Time C6 )
: IP> C6 Delay 0 – 99.9 Sec in steps of 0.1Sec.
: IP>> Settings 00% – 3000% insteps of 50% 00 means
block
: IP>> Delay 0 – 2.00 Sec in steps of 0.01Sec.
XVII. Earth Fault Section (3Io) : 3Io> Settings 10% – 250% insteps of 1%
: 3Io> Time Multiplier (TMS) x0.01 – x1.00 in step of 0.01.
: IE> Curve C1 – C6
(Operating Time) ( IDMT curve C1 – C5 or Define Time C6 )
: 3IO> C6 Delay 0 – 99.9 Sec in steps of 0.1Sec.
: 3IO>> Settings 00% – 3000% insteps of 50% 00 means
block
: 3IO>> Delay 0 – 2.00 Sec in steps of 0.01Sec.
Operational Indicators (Flags) 4 user assignable bicolour output LED Default assignment
XVIII. LED1 - PROT.H /ON : Green LED indicates Relay OK (Protection Healthy)
: Red LED indicates Fault in following conditions.
1. Problem in relay Hardware.
2. Trip Circuit Fault
LED 2 - PICK-UP : Red LED indicate Start of timer Self Reset (SR) Type
LED 3 - FAULT : Red LED indicate Relay Operated Flag (HR)
LED 4 - TRIP : Red LED indicates Output TRIP relay contact closer (SR) Type
XIX. Drawing References : For Typical External connection - ADV02703
: For Cabinet Type - MAC01501 (CSF)

Note: Due to our policy to upgrade our products constantly, we reserve the right to
supply products which may vary slightly from that indicated above.

ASHIDA ELECTRONICS PVT LTD.


ASHIDA HOUSE, Plot No. A-308, Road No. 21, Ref.:ADR141C
Wagle Industrial Estate,Thane (W)-400 604. INDIA.
E-mail: sales@ashidaelectronics.com Issue: 05 07.03.2011
Web: www.ashidaelectronics.com Page 7 / 9
ASHIDA Numerical 3OC + 1EF Type: ADR141C
( AD I T Y AS e r i e s )
Protection Relay (Preliminary)

The Relay Confirm to following standard


Sr. No. Title Standard no.
Electromagnetic Compatibility Type Test:
1. High Frequency Test : IEC 60255-22-1, class – III
: Frequency : 1MHz Damped Oscillatory
: Longitudinal :5 KV (peak)
: Duration: sec duration 2 sec.
: Between input current Terminal
2. Electrostatic : IEC 60255-22-2 Class III and IEC 61000-4-2 class III.
Discharge Direct : Contact discharge: 6kV,
Application : Air discharge: 8KV
: Polarity: both +ve and –Ve polarities.
3. Indirect Application : IEC-61000-4-2, Class-III
Fast Transient : IEC 60255-22-4 and IEC 61000-4-4, class A
4. Disturbance : 1.2KV; 5/50ns; 5KHz burst duration = 15ms.
: Repetition rate 300ms; Both polarities; Ri = 50Ω; duration 1 min.
Surge Immunity Test : IEC 60255-22-5 / IEC 61000-4-6 class 4
: Differential Mode = 2kV
5.
: Common Mode = 4kV
: 1.2/50uS , 5 surges of each polarity
6. Power Frequency : IEC-61000-4-8, Class-V
Magnetic Field Test
7. Radiated : IEC- 60255-22-3
Electromagnetic Field : EN-61000-4-3
Disturbance : Frequency 80MHz – 1GHz
8. Conducted Disturbance : IEC 60255-22-6 / IEC 61000-4-6: 1996.
Induced By Radio : Freq. 150kHz – 80MHz, Amplitude 10 V, Modulation 80% AM
Frequency Field @ 1 KHz
9. AC Ripple In DC : IEC 60255-11
Supply Test
10. Radiated Emission : IEC 60255-25
Insulation Tests:
11. High Voltage Test : IEC 60255-5. class – III
: At 2.5kV 50Hz between all terminal connected together and
earth for 1 minutes
12. Impulse Voltage Test : IEC 60255-5. class – III
: Test voltage: 5KV (peak) 1.2 / 50us,
: Energy :0.5 J,
: Polarity : + ve and – Ve
: Nos. of impulses : 3 positive and 3 negative impulse
: Duration between Impulses : 5 sec.

Note: Due to our policy to upgrade our products constantly, we reserve the right to
supply products which may vary slightly from that indicated above.

ASHIDA ELECTRONICS PVT LTD.


ASHIDA HOUSE, Plot No. A-308, Road No. 21, Ref.:ADR141C
Wagle Industrial Estate,Thane (W)-400 604. INDIA.
E-mail: sales@ashidaelectronics.com Issue: 05 07.03.2011
Web: www.ashidaelectronics.com Page 8 / 9
ASHIDA Numerical 3OC + 1EF Type: ADR141C
( AD I T Y AS e r i e s )
Protection Relay (Preliminary)

Environmental tests:
13. Cold test Storage test : IEC 60068-2-1
14. Dry heat test : IEC 60068-2-2
Damp heat test,
15. : IEC 60068-2-3
steady state
16. Damp heat test, cyclic : IEC 60068-2-30
Mechanical tests
: IEC 60255-21-1 class 1
: Frequency Range = 10Hz – 150Hz , acceleration. = 1gn (9.8
17. Vibration
m/s2)
: Sweep rate 1 octave/min; 20 cycle in 3 orthogonal axis.
18. Bump Test : IEC 60255-21-2 Class-1
: 1000 bumps of 10gn peak acceleration and 16ms pulse
duration in each of the two opposite direction per axis as per
IEC 60255-21-2 class 1 No. of axes . 3.
19. Shock Withstand : IEC 60255-21-2 Clas-1
: 3 shocks of 15gn peak acceleration and 11ms pulse in each of
two opposite direction . No. of axis : 3
20. Seismic Test : IEC 60255-21-3
: In single axis sine sweep in X-axis
sweep (@a sweep rate of 1 octave/minute) vibration in the
frequency range (5-40 Hz) at amplitude of 3.5mm or 1.0gn
(whichever is less)
: In single axis sine sweep in Y-axis
- sweep (@a sweep rate of 1 octave/minute) vibration in the
frequency range (5-40 Hz) at amplitude of 1.5mm or 0.5gn
(whichever is less)

Revision Note

Rev. No. Date Description


01 15.08.09 Original specifications
02 01.01.10 Photograph of Relay updated
03 04.02.10 Addition of cold load pick up.
04 16.03.10 Back terminal connections changed ADV02702
05 07.03.11 Back terminal connections changed ADV02703

Note: Due to our policy to upgrade our products constantly, we reserve the right to
supply products which may vary slightly from that indicated above.

ASHIDA ELECTRONICS PVT LTD.


ASHIDA HOUSE, Plot No. A-308, Road No. 21, Ref.:ADR141C
Wagle Industrial Estate,Thane (W)-400 604. INDIA.
E-mail: sales@ashidaelectronics.com Issue: 05 07.03.2011
Web: www.ashidaelectronics.com Page 9 / 9