You are on page 1of 5

Date: 27/10/2018 www.komfovent.

com

Air handling unit model:

VERSO-S-20-X-H-PM/IE5/1.4/X-F7-X-X-R1-C5.1-X

TECHNICAL SPECIFICATION

AHU size 20
Typology NRVU
UVU
Type of HRS none

AHU parameters
RLT class B

Supply
Nominal flow rate [m³/h] / [m³/s] 4000 / 1,11
Nominal external pressure (ΔPs, ext) [Pa] 250

Int. pressure drop of ventilation components (ΔPs, int) [Pa] 135


Int. pressure drop of non-ventilation components (ΔPs, add) [Pa] 46

Design outdoor temprature winter [°C] -23


Face velocity at design flow rate [m/s] 2,10
SFPv [kW/m³/s] 0,76
Atmosphere pressure [Pa] 101325
Air density [kg/m³] 1,2
Full load I (3x400V) [A] 3,5
Effective electric power input [kW] 0,85

COMMISSION REGULATION (EU) No 1253 (ecodesign requirements)


Value 2018
The fan efficiency, ȠVu [%] 51,42 ≥ 41

UAB Komfovent, Ozo g. 10, LT-08200 Vilnius, tel. +370 (5) 230 05 85, www.komfovent.com Verso 1.5.5/14 27/10/2018

LT 1/5
VERSO-S-20-X-H-PM/IE5/1.4/X-F7-X-X-R1-C5.1-X www.komfovent.com

Internal specific fan power, SFPint_limit [W/m³/s] 263 ≤ 230


Type of drive - variable speed Installed Necessary
Warning - filter is clogged Exist Necessary
Unit conformity assessment Non complies

Basic construction STANDART


Panels from two galvanized steel sheets,filled with thermal and sound insulation
fire-resistant min.wool (λ=0,036 W/mK).
AHU painted C3 class, RAL 7035.
Indoor unit.
When filters gets dirty, unit control panel gives notice to change the filters.
Dirty filters cause increased energy consumption, which decreases performance and energy efficiency of the
unit, so it is very important to change the filters regularly.
AHU shall operate with variable speed drive.
www.komfovent.com/manuals/verso-manuals
Verso manual version: V2-C5.1-18-09

Casing air leakage (Model Box, EN 1886)


-400 Pa [dm³/(s·m²)] 0,05
+700 Pa [dm³/(s·m²)] 0,09

Maximum external leakage rate at - 400 Pa [%] <1


Maximum external leakage rate at + 400 Pa [%] <1

AHU configuration
Separate sections with base frame connected to each section

Panels thickness [mm] 45

Unit weight
Weight (netto) [kg] 169

Pallets
V [mm] 950x1300(169kg)

Accessories
Adjustable feet (RegKoj)

Control automatics
Type C5.1

ACOUSTIC DATA

Sound power level Lw to the air ducts to surrounding


Supply air volume [dB] [dB]

UAB Komfovent, Ozo g. 10, LT-08200 Vilnius, tel. +370 (5) 230 05 85, www.komfovent.com Verso 1.5.5/14 27/10/2018

LT 2/5
VERSO-S-20-X-H-PM/IE5/1.4/X-F7-X-X-R1-C5.1-X www.komfovent.com

F[Hz] Inlet Outlet


63 63,3 69,0 62,0
125 61,5 68,7 66,1
250 68,1 79,6 69,7
500 64,7 78,3 51,7
1000 65,2 82,3 51,0
2000 56,3 77,4 44,6
4000 53,7 73,6 35,0
8000 47,8 69,5 28,9
dB(A) 68 85 62

SUPPLY AIR VOLUME

Damper with actuator


Aluminium profile air damper
Actuator type ON/OFF (AC/DC 24V)
Torque [Nm] 5
Pressure drop [Pa] 7

Air filter
Filter correction (F), (EU 1253) 0
Type Bag filter
Energy efficiency class
Air velocity class (EN13053) V4
Filter class (EN 779:2012) F7
Filter class (EN ISO 16890) ePM1 60%
Dimensions bxhxl [mm] 490x490x500
Energy performance [kWh/a] 2287
Quantity of bags 6
Quantity of filters 2
Pressure drop (clean filter) [Pa] 72
Pressure drop [Pa] 111
Recomended max. pressure drop (EN 137792007) [Pa] 150
Velocity in the AHU filter section [m/s] 2,10

Impeller
Type RH31C.CR
Wheel diameter [mm] 315
Air volume [m³/h] 4000
Built-in loss [Pa] 64
Static pressure [Pa] 431
Total pressure [Pa] 511
Efficiency [%] 61
Shaft power [kW] 0,79

UAB Komfovent, Ozo g. 10, LT-08200 Vilnius, tel. +370 (5) 230 05 85, www.komfovent.com Verso 1.5.5/14 27/10/2018

LT 3/5
VERSO-S-20-X-H-PM/IE5/1.4/X-F7-X-X-R1-C5.1-X www.komfovent.com

Shaft power (clean filters) [kW] 0,71


Speed [1/min] 2714
Max. speed [1/min] 4245
K-value 95

Motor PM
Motor efficiency class IE5 (Ultra Premium)
Motor power [kW] 1,4
Speed [1/min] 3400
Efficiency [%] 90
Rated current at 400V 50Hz [A] 3,3

FOP [Hz] 226


Frequency converter [kW] 1.4

Fan
SFPv [kW/m³/s] 0,76
SFP class (EN16798-3) SFP 3
Electric power to motor (Pm) [kW] 0,93
Electric power to motor (clean filters) [kW] 0,85
Electric power to motor class (EN13053) P4
Pm ref (EN13053) [kW] 0,98
Total fan efficiency [%] 60,95
Static fan efficiency [%] 51,42
Overall efficiency ErP [%] 63,74

UAB Komfovent, Ozo g. 10, LT-08200 Vilnius, tel. +370 (5) 230 05 85, www.komfovent.com Verso 1.5.5/14 27/10/2018

LT 4/5
VERSO-S-20-X-H-PM/IE5/1.4/X-F7-X-X-R1-C5.1-X www.komfovent.com

Ventilation equipment installation specification 27/10/2018

Ventilation device model VERSO-S-20-X-H-PM/IE5/1.4/X-F7-X-X-R1-C5.1-X


Notes
Worked-out:
Nr. Code: Name Description Quantity Units Notes
1 Control automatics 1 Unit

Supply air volume


2 Air filter: 2 Unit
F7 490x490x500/6/2
3 Motor PM 1 Unit
1,4 [kW]

UAB Komfovent, Ozo g. 10, LT-08200 Vilnius, tel. +370 (5) 230 05 85, www.komfovent.com Verso 1.5.5/14 27/10/2018

LT 5/5