1. Material List
Model Qty Description
RXQ10TAYM 3 Cooling only VRV IV STANDARD
RXQ12TAYM 6 Cooling only VRV IV STANDARD
RXQ14TAYM 1 Cooling only VRV IV STANDARD
RXQ16TAYM 1 Cooling only VRV IV STANDARD
FXAQ25PVE 4 VRV AP - Wall Mounted(Flat Panel)
FXFQ125LUV1 3 VRV FLU - Ceiling Mounted Cassette(Round Flow)
FXFQ125SVM 24 VRV FS(SVM) - Ceiling Mounted Cassette(Round Flow with Sensing)
KHRP26A22T 4 Refnet branch piping kit
KHRP26A33T 4 Refnet branch piping kit
KHRP26A72T 8 Refnet branch piping kit
KHRP26A73T + KHRP26M73TP 11 Refnet branch piping kit
BRC1E62 31 Wired Remote Controller (Navigation Remote Controller)
BYCP125K-W1 3 Decoration panel
BYCQ125B-W1 24 Decoration Panel
BHFP22P100 1 Outdoor unit multi connection piping kit
BHFP22P151 3 Outdoor unit multi connection piping kit
The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.
Page 1
2. Indoor Unit Details
2.1. Table of Abbreviations
Name Logical name of the device
FCU Device model name
▼ indicates a model size down due to tolerance
Tmp C Indoor conditions in cooling (dry bulb temp. / wet bulb temp.)
Rq TC Required total cooling capacity
Applied indoor capacity safety factor or tolerance
Max TC Available total cooling capacity
Rq SC Required sensible cooling capacity
Max SC Available sensible cooling capacity
Tevap Evaporating temperature of indoor unit coil
Tdis C Indoor unit discharge air temperature in cooling
Tmp H Indoor temperature in heating
Rq HC Required heating capacity
Applied indoor capacity safety factor or tolerance
Max HC Available heating capacity
Tdis H Indoor unit discharge air temperature in heating
Airflow Supplied airflow
Sound Sound pressure low and high
PS Power supply (voltage and phases)
MCA Minimum Circuit Amps
WxHxD WidthxHeightxDepth
Wght Weight of the device
The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.
Page 2
2.2. OU-1 - RXQ30TANYM
Capacity data at conditions and connection ratio (103%) as entered
Name FCU Tmp C Rq TC Max TC Rq SC Max SC Tevap Tdis C Tmp H Rq HC Max HC Tdis H Airflow
°C BTU/h BTU/h BTU/h BTU/h °C °C °C BTU/h BTU/h °C l/s
IU-1-01 FXFQ125SVM 27,0 / 18,9 n/a 47702 n/a 35258 Auto 12,4 n/a n/a n/a n/a 575
IU-1-02 FXFQ125SVM 27,0 / 18,9 n/a 47702 n/a 35258 Auto 12,4 n/a n/a n/a n/a 575
IU-1-03 FXFQ125SVM 27,0 / 18,9 n/a 47702 n/a 35258 Auto 12,4 n/a n/a n/a n/a 575
IU-1-04 FXFQ125LUV1 27,0 / 18,9 n/a 47702 n/a 35503 Auto 11,6 n/a n/a n/a n/a 550
IU-1-05 FXFQ125LUV1 27,0 / 18,9 n/a 47702 n/a 35503 Auto 11,6 n/a n/a n/a n/a 550
IU-1-06 FXFQ125LUV1 27,0 / 18,9 n/a 47702 n/a 35503 Auto 11,6 n/a n/a n/a n/a 550
IU-1-07 FXAQ25PVE 27,0 / 18,9 n/a 9554 n/a 7592 Auto 13,4 n/a n/a n/a n/a 133
The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.
Page 3
2.3. OU-2 - RXQ34TANYM
Capacity data at conditions and connection ratio (106%) as entered
Name FCU Tmp C Rq TC Max TC Rq SC Max SC Tevap Tdis C Tmp H Rq HC Max HC Tdis H Airflow
°C BTU/h BTU/h BTU/h BTU/h °C °C °C BTU/h BTU/h °C l/s
IU-2-01 FXFQ125SVM 27,0 / 18,9 n/a 47702 n/a 35258 Auto 12,4 n/a n/a n/a n/a 575
IU-2-02 FXFQ125SVM 27,0 / 18,9 n/a 47702 n/a 35258 Auto 12,4 n/a n/a n/a n/a 575
IU-2-03 FXFQ125SVM 27,0 / 18,9 n/a 47702 n/a 35258 Auto 12,4 n/a n/a n/a n/a 575
IU-2-04 FXFQ125SVM 27,0 / 18,9 n/a 47702 n/a 35258 Auto 12,4 n/a n/a n/a n/a 575
IU-2-05 FXFQ125SVM 27,0 / 18,9 n/a 47702 n/a 35258 Auto 12,4 n/a n/a n/a n/a 575
IU-2-06 FXFQ125SVM 27,0 / 18,9 n/a 47702 n/a 35258 Auto 12,4 n/a n/a n/a n/a 575
IU-2-07 FXFQ125SVM 27,0 / 18,9 n/a 47702 n/a 35258 Auto 12,4 n/a n/a n/a n/a 575
IU-2-08 FXAQ25PVE 27,0 / 18,9 n/a 9554 n/a 7592 Auto 13,4 n/a n/a n/a n/a 133
The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.
Page 4
2.4. OU-3 - RXQ34TANYM
Capacity data at conditions and connection ratio (106%) as entered
Name FCU Tmp C Rq TC Max TC Rq SC Max SC Tevap Tdis C Tmp H Rq HC Max HC Tdis H Airflow
°C BTU/h BTU/h BTU/h BTU/h °C °C °C BTU/h BTU/h °C l/s
IU-3-01 FXFQ125SVM 27,0 / 18,9 n/a 47702 n/a 35258 Auto 12,4 n/a n/a n/a n/a 575
IU-3-02 FXFQ125SVM 27,0 / 18,9 n/a 47702 n/a 35258 Auto 12,4 n/a n/a n/a n/a 575
IU-3-03 FXFQ125SVM 27,0 / 18,9 n/a 47702 n/a 35258 Auto 12,4 n/a n/a n/a n/a 575
IU-3-04 FXFQ125SVM 27,0 / 18,9 n/a 47702 n/a 35258 Auto 12,4 n/a n/a n/a n/a 575
IU-3-05 FXFQ125SVM 27,0 / 18,9 n/a 47702 n/a 35258 Auto 12,4 n/a n/a n/a n/a 575
IU-3-06 FXFQ125SVM 27,0 / 18,9 n/a 47702 n/a 35258 Auto 12,4 n/a n/a n/a n/a 575
IU-3-07 FXFQ125SVM 27,0 / 18,9 n/a 47702 n/a 35258 Auto 12,4 n/a n/a n/a n/a 575
IU-3-08 FXAQ25PVE 27,0 / 18,9 n/a 9554 n/a 7592 Auto 13,4 n/a n/a n/a n/a 133
The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.
Page 5
2.5. OU-4 - RXQ34TANYM
Capacity data at conditions and connection ratio (106%) as entered
Name FCU Tmp C Rq TC Max TC Rq SC Max SC Tevap Tdis C Tmp H Rq HC Max HC Tdis H Airflow
°C BTU/h BTU/h BTU/h BTU/h °C °C °C BTU/h BTU/h °C l/s
IU-4-01 FXFQ125SVM 27,0 / 18,9 n/a 47702 n/a 35258 Auto 12,4 n/a n/a n/a n/a 575
IU-4-02 FXFQ125SVM 27,0 / 18,9 n/a 47702 n/a 35258 Auto 12,4 n/a n/a n/a n/a 575
IU-4-03 FXFQ125SVM 27,0 / 18,9 n/a 47702 n/a 35258 Auto 12,4 n/a n/a n/a n/a 575
IU-4-04 FXFQ125SVM 27,0 / 18,9 n/a 47702 n/a 35258 Auto 12,4 n/a n/a n/a n/a 575
IU-4-05 FXFQ125SVM 27,0 / 18,9 n/a 47702 n/a 35258 Auto 12,4 n/a n/a n/a n/a 575
IU-4-06 FXFQ125SVM 27,0 / 18,9 n/a 47702 n/a 35258 Auto 12,4 n/a n/a n/a n/a 575
IU-4-07 FXFQ125SVM 27,0 / 18,9 n/a 47702 n/a 35258 Auto 12,4 n/a n/a n/a n/a 575
IU-4-08 FXAQ25PVE 27,0 / 18,9 n/a 9554 n/a 7592 Auto 13,4 n/a n/a n/a n/a 133
The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.
Page 6
3. Outdoor Unit Details
3.1. Table of Abbreviations
Name Logical name of the device
Model Device model name
Tmp C Outdoor temperature in cooling
CC Available cooling capacity
Rq CC Required cooling capacity
Tmp H Outdoor conditions in heating (dry bulb temp. / wet bulb temp.)
HC Available heating capacity (integrated heating capacity)
Rq HC Required heating capacity
Piping Largest distance from indoor unit to outdoor unit
Bse Refr Standard factory refrigerant charge (5m actual piping length)
excluding extra refrigerant charge
For calculation of extra refrigerant charge refer to the databook
PS Power supply (voltage and phases)
MCA Minimum Circuit Amps
WxHxD WidthxHeightxDepth
Wght Weight of the device
The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.
Page 7
3.2. Outdoor Details
Name Model Comb Tmp C CC Rq CC Tmp H HC Rq HC
% °C BTU/h BTU/h °C BTU/h BTU/h
OU-1 RXQ30TANYM 103 35,0 291306 236612
OU-2 RXQ34TANYM 106 35,0 327120 274773
OU-3 RXQ34TANYM 106 35,0 327120 274773
OU-4 RXQ34TANYM 106 35,0 327120 274773
Sufficient distance should be respected between the modules according to the service & operation space rules as
mentioned in the databook.
The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.
Page 8
4. Piping Diagrams
Pipes marked with * in the diagrams must be connected to the device with a reducing joint.
Warning: The pipe diameter values are purely indicative. Depending on the required pipe lengths, a
different pipe diameter might be required.
The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.
Page 9
4.2. Piping OU-2
Warning: The pipe diameter values are purely indicative. Depending on the required pipe lengths, a
different pipe diameter might be required.
The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.
Page 10
4.3. Piping OU-3
Warning: The pipe diameter values are purely indicative. Depending on the required pipe lengths, a
different pipe diameter might be required.
The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.
Page 11
4.4. Piping OU-4
Warning: The pipe diameter values are purely indicative. Depending on the required pipe lengths, a
different pipe diameter might be required.
The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.
Page 12
5. Wiring Diagrams
P1P2 = Please select the cable type and size in accordance with the databook.
F1F2 = Please select the cable type and size in accordance with the databook.
P1,P2
IU-1-04 BRC1E62
FXFQ125LUV1
F1,F2 L,N 1,5A 1ph
P1,P2
IU-1-05 BRC1E62
FXFQ125LUV1
F1,F2 L,N 1,5A 1ph
P1,P2
IU-1-06 BRC1E62
FXFQ125LUV1
F1,F2 L,N 1,5A 1ph
P1,P2
IU-1-07 BRC1E62
FXAQ25PVE
F1,F2 L,N 0,4A 1ph
The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.
Page 13
5.2. Wiring OU-2
P1,P2
OU-2 IU-2-01 BRC1E62
RXQ34TANYM FXFQ125SVM
IN F1,F2 F1,F2 L,N 1,6A 1ph
RXQ12TAYM
Q1,Q2 L1,L2,L3,N P1,P2
IU-2-02 BRC1E62
24A 3ph
FXFQ125SVM
RXQ12TAYM F1,F2 L,N 1,6A 1ph
Q1,Q2 L1,L2,L3,N
24A 3ph P1,P2
IU-2-03 BRC1E62
RXQ10TAYM FXFQ125SVM
Q1,Q2 L1,L2,L3,N F1,F2 L,N 1,6A 1ph
22A 3ph
P1,P2
IU-2-04 BRC1E62
FXFQ125SVM
F1,F2 L,N 1,6A 1ph
P1,P2
IU-2-05 BRC1E62
FXFQ125SVM
F1,F2 L,N 1,6A 1ph
P1,P2
IU-2-06 BRC1E62
FXFQ125SVM
F1,F2 L,N 1,6A 1ph
P1,P2
IU-2-07 BRC1E62
FXFQ125SVM
F1,F2 L,N 1,6A 1ph
P1,P2
IU-2-08 BRC1E62
FXAQ25PVE
F1,F2 L,N 0,4A 1ph
The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.
Page 14
5.3. Wiring OU-3
P1,P2
OU-3 IU-3-01 BRC1E62
RXQ34TANYM FXFQ125SVM
IN F1,F2 F1,F2 L,N 1,6A 1ph
RXQ12TAYM
Q1,Q2 L1,L2,L3,N P1,P2
IU-3-02 BRC1E62
24A 3ph
FXFQ125SVM
RXQ12TAYM F1,F2 L,N 1,6A 1ph
Q1,Q2 L1,L2,L3,N
24A 3ph P1,P2
IU-3-03 BRC1E62
RXQ10TAYM FXFQ125SVM
Q1,Q2 L1,L2,L3,N F1,F2 L,N 1,6A 1ph
22A 3ph
P1,P2
IU-3-04 BRC1E62
FXFQ125SVM
F1,F2 L,N 1,6A 1ph
P1,P2
IU-3-05 BRC1E62
FXFQ125SVM
F1,F2 L,N 1,6A 1ph
P1,P2
IU-3-06 BRC1E62
FXFQ125SVM
F1,F2 L,N 1,6A 1ph
P1,P2
IU-3-07 BRC1E62
FXFQ125SVM
F1,F2 L,N 1,6A 1ph
P1,P2
IU-3-08 BRC1E62
FXAQ25PVE
F1,F2 L,N 0,4A 1ph
The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.
Page 15
5.4. Wiring OU-4
P1,P2
OU-4 IU-4-01 BRC1E62
RXQ34TANYM FXFQ125SVM
IN F1,F2 F1,F2 L,N 1,6A 1ph
RXQ12TAYM
Q1,Q2 L1,L2,L3,N P1,P2
IU-4-02 BRC1E62
24A 3ph
FXFQ125SVM
RXQ12TAYM F1,F2 L,N 1,6A 1ph
Q1,Q2 L1,L2,L3,N
24A 3ph P1,P2
IU-4-03 BRC1E62
RXQ10TAYM FXFQ125SVM
Q1,Q2 L1,L2,L3,N F1,F2 L,N 1,6A 1ph
22A 3ph
P1,P2
IU-4-04 BRC1E62
FXFQ125SVM
F1,F2 L,N 1,6A 1ph
P1,P2
IU-4-05 BRC1E62
FXFQ125SVM
F1,F2 L,N 1,6A 1ph
P1,P2
IU-4-06 BRC1E62
FXFQ125SVM
F1,F2 L,N 1,6A 1ph
P1,P2
IU-4-07 BRC1E62
FXFQ125SVM
F1,F2 L,N 1,6A 1ph
P1,P2
IU-4-08 BRC1E62
FXAQ25PVE
F1,F2 L,N 0,4A 1ph
The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.
Page 16
6. Device Options
6.1. Outdoor Unit Options
Model Description Used by
BHFP22P151 Outdoor unit multi connection piping kit OU-4 [RXQ34TANYM] OU-3 [RXQ34TANYM] OU-2 [RXQ34TANYM]
BHFP22P100 Outdoor unit multi connection piping kit OU-1 [RXQ30TANYM]
The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.
Page 17