16/09/2017 Airtightness measurements in Passive Houses [ ]

Airtightness measurements in Passive Houses


Instructions for carrying out measurements
Airtightness measurements in Passive House buildings are carried out in accordance with the EN 13829 standard. Supplementary information by the FLiB (specialists'
association for airtightness in building construction) can be found in the supplementary sheet for this standard. The measurement can also be carried in accordance with ISO
9972, but with an adapted calculation of the volume.
The differences (which are not of a fundamental nature), specifications and additions to the standards in relation to Passive Houses are described here.

1. Comparison of designations

The norms EN 13829 and ISO 9972 use different designations in some places. For a better overview, the most important are compared here:

For measurements in Passive House buildings, the designation in accordance with EN 13829 should continue to be used.

2. Calculation of volumes

The air volume Vn50 used for calculating the Vn50 value inside the heated building envelope should be determined and comprehensibly documented Room by room
separately for each room. In doing so, the base area of the room should be multiplied by the average clear height of the room. Overall assumptions for
determining the internal volume of the enclosed space (gross volume) by means of a reduction factor are not permissible.
Note: not TFA,
The base area to be used for this calculation differs from the treated floor area which is normally used. The air volume Vn50 is not the same as the not VV
“enclosed volume”, nor is it the same as the volume of air in a heated zone as used in the PHPP sheet “Annual Heating Demand” (overall room height instead, Vn50
2.5 m). For this reason, the calculated volume Vn50 from the test report must also be transferred into the PHPP.
Irrespective of the degree of completion of the building, the dimensions used should always be those of the finished building (e.g. where there is Final
no screed). Air volumes above suspended ceilings do NOT count towards the total air volume. This is regardless of whether the ceiling already exists, is dimensions
tightly connected with the wall, or has different types of holes (“acoustic ceiling”). The reduction of the volume by layers of plaster does not have to be only
taken into account.
A full and comprehensible room-by-room calculation of the volume must be provided for each airtightness measurement. Auxiliary Documentation
calculations may also be necessary; these must also be provided. For example, in the case of inclined roofs, the air volume is determined by means of
triangular or prism calculations. A proportional factor such as those used in the table below (Figure 1) can be taken into account.

Figure 1: Example of documentation for room by room volume calculation.

https://passipedia.org/planning/airtight_construction/airtightness_measurements_in_passive_houses 1/5
16/09/2017 Airtightness measurements in Passive Houses [ ]

The total air volume within the thermal envelope will thus be taken into account. Special features are shown in Figure 2 for more detailed explanation.

Figure 2: Guidelines for calculating the air volume inside the airtight layer of a building.
The red dashed line all around represents the air tight layer.

https://passipedia.org/planning/airtight_construction/airtightness_measurements_in_passive_houses 2/5
16/09/2017 Airtightness measurements in Passive Houses [ ]

Visible rafters, beams, plasterboard encasings, wall-mounted installations (if these do not have the same height as the room) and the like are not Rafters, beams wall-
taken into account; in the calculation they are not deducted for simplification. They are thus treated as if they did not exist (= air space). mounted
installations.
The volume of window reveals (see Figure 3) is not taken into account either (measured only up to the inner wall surface). The same applies in the Window reveals
case of doors and openings.
These stipulations are for the purpose of simplification. Any deviations occurring as a result are usually small.

Figure 3: The volume of window reveals is not taken into account in the volume
calculation

Stairs No deduction of
The volume of a stairwell is part of the air volume and is fully taken into account. The volume of the stairs themselves (building component) is not the stairwell
taken into account, therefore it is not deducted. The base area of the stairwell can thus be multiplied with the clear height of the storey. volume

3.Time of measurement

Airtightness of the finished building is relevant, therefore it is obvious that the measurement should be carried out after completion of the building;
however, by this time, all installations, screed, cladding etc. will have been completed already. It will not be possible to access many important connections
and penetrations of the airtight layer in a non-destructive manner. Remaining leaks in the airtight layer can no longer be remedied, which would not be
practical.
For this reason, carrying out measurement preferably directly after completion of the airtight layer (e.g. window installation, airtightness sheeting in the Measurement
roof etc.) will be more effective. In this way, leaks in the airtight layer can be localised directly and essential corrections can be carried out. At the time of directly after
the measurement, building components of the building envelope (e.g. entrance door) may be missing only in exceptional cases; in such cases, these must be completion of
sealed up temporarily. All seals and preparations must be mentioned in the test report in an understandable way. the airtight
layer
After the measurement, the construction manager in charge must ensure that damage to the airtight layer is not caused during subsequent construction Second
work. Should there be cause for concern about this due to various reasons, then another measurement should be carried out. measurement?
In most cases however, one airtightness measurement is sufficient.

4. Carrying out the measurement

Method A or B? Building as
In the PHPP the state of building use during normal operation is relevant for the energy balance of a building, therefore the airtightness measurements in used
Passive House buildings must be carried out according to Method A. Normally there is no difference between Method A (in use) and Method B (building
envelope test) in the case of Passive Houses. As a rule, the only intended openings are the outdoor air and exhaust air openings of the ventilation system
which must be sealed for the measurement. In a Passive House building, openings which are sealed according to Method B should generally be
implemented so that these can be closed (e.g. smoke extraction in elevator shafts). What matters is the exact and comprehensible documentation of each
temporarily sealing measure that is carried out for the measurement.
Sealing the ventilation system Residential
Controlled ventilation in residential buildings should be operated continuously during the heating period for reasons of hygiene. Because a balanced buildings:
ventilation system does not constitute a source of leaks, it is temporarily closed off for the measurement (e.g. by taping over or using a sealing balloon). In sealing the
doing so, the outdoor air and exhaust air sides should be sealed if possible, in order to avoid measuring the leakages of the duct network and the ventilation ventilation
unit as well. system
In non-residential Passive House buildings (schools, kindergartens etc.), ventilation systems are often not operated during the night or at the weekend Non-
(intermittent operation). In such cases, ventilation systems must have tightly shutting flaps at the outdoor air and exhaust air ends to prevent the building residential
from losing additional heat due to thermal lift and strong winds while the ventilation system is not running. For certified units, leaks within the ventilation buildings:
unit itself are already taken into account in the device test, i.e. the heat recovery efficiency. closed flaps
only
In buildings with intermittent operation, the existing sealing flaps must be closed during the airtightness measurement, but they must not be
taped over in addition.
https://passipedia.org/planning/airtight_construction/airtightness_measurements_in_passive_houses 3/5
16/09/2017 Airtightness measurements in Passive Houses [ ]

Fans for mechanical summer ventilation that are present in a building may not be taped over either.
Further sealing No further
No further openings (keyholes, leaks in windows, cat flaps etc.) in the building envelope may be sealed off for the measurement. Features that are sealing
problematic in terms of airtightness, such as an open fireplace or a room-sealed boiler etc., cannot be used/operated in a Passive House as a rule.\\
The only exceptions may be temporarily taping over openings for missing building components, as described above, which affect the airtightness (e.g. Exception:
missing door sill, missing odour trap in the waste water pipe). Again, an exact record should be kept about such sealing. Missing
building
components
The aim is to obtain realistic results reflecting the building’s airtightness in use, rather than to create an “artificially” improved situation. Building as
used
Negative AND excess pressure measurement Measurement
Unlike in the EN 13829 and ISO 9972 standards, both negative pressure AND excess pressure are generally required when measuring the airtightness in with negative
Passive Houses. In this way, the reliability of the measurement results is significantly improved, with a minimum of extra effort. Finally, the airtightness and excess
parameter of the building is determined as an average value from the negative and excess pressure results. pressure

5. Special features of large buildings (q50-value)

In large buildings it is necessary to calculate the airtightness value with reference to the envelope area (q50-value) in addition. The n50-value alone is no Exterior
longer significant on account of the more favourable A/V ratio (surface area to volume ratio). surface
In the case of large buildings it is therefore recommended that the exterior surface of the building should also be ascertained. This is also determined
according to EN 13829 or the identical ISO 9972.
Buildings with an air volume Vn50 ≥ 1500m³ are defined as large buildings. ≥ 1500m³

For such large buildings, as a result both values, i.e. the n50-value and the q50-value, will then need to be indicated in the measurement report. n50 and q50
values
required
Instructions regarding the procedure for calculating the envelope area according to EN 13829 and ISO 9972:
The envelope area is the total area of all floors, walls and ceilings enclosing the volume under consideration, including all walls and floors that are below
ground level. Interior dimensions from the inner edge are used; the facing areas of intersecting interior walls are not deducted. See Figure 4.
In deviation from EN 13829 and ISO 9972, the envelope area used in the PHPPP can also be used for simplification. The exterior dimensions used in
the PHPP only lead to negligible differences.

Figure 4: Interior dimensions from inner edge for calculating the envelope area (according
to EN 13829).

In terraced houses, the partition walls of the building also count as the envelope area; in apartments in multi-storey buildings this also applies to all Terraced houses
floors, walls and ceilings adjoining neighbouring apartments. These areas must only be taken into account if each accommodation unit is measured and multi-storey
separately. buildings
Recommended target value for the q50 requirement Target value q50
An n50-value smaller than or equal to 0.6 h-1 has been set as a limit value for the certification of Passive House buildings (see certification criteria on
www.passivehouse.com [http://www.passivehouse.com]).

https://passipedia.org/planning/airtight_construction/airtightness_measurements_in_passive_houses 4/5
16/09/2017 Airtightness measurements in Passive Houses [ ]
The requirements for the envelope area of smaller buildings can be used as a reference for the target value for larger buildings (≥ 1500 m³), resulting
in a target value of:

q50 ≤ 0.6 m³/(h m²)

Numerous measurements in large and very large buildings have shown that this target value (or even lower values) can be achieved with an
appropriate airtightness concept. Higher requirements may apply for special types of buildings (e.g. swimming pool).
Note: In smaller buildings, more meticulous airtightness measures may be necessary in order to meet the n50 < 0.6 h-1 requirement. Compliance The q50-value alone
with the q50 criterion alone is thus not sufficient. is not enough

See also
Airtightness test

planning/airtight_construction/airtightness_measurements_in_passive_houses.txt · Last modified: 2017/05/30 10:26 by speper