MULTITIMER
Multifunction Relay
MK 7850N/200
Your Advantages
• Up to 10 functions in one unit
• Simplified storage
• Increased flexibility
0239280
Features
• According to IEC/EN 61 812-1
• 8 functions settable via rotational switch:
-- Delay on energisation (AV)
-- Fleeting on make (EW)
-- Delayed pulse (IE)
-- Flasher, start with pulse (BI)
-- Delay on de-energisation (RV)
-- Pulse forming function (IF)
-- Fleeting on break (AW)
-- Delay on energisation and de-energisation (AV / RV)
Circuit Diagrams • 8 time ranges from 0.02 s to 300 h selectable via rotational switches
• Voltage range AC/DC 12 ... 240 V
t • With time interruption / time adding input for all functions
Z1 Z2 • Suitable for 2-wire proximity sensor control
• 2 changeover contacts, one programmable as instantaneous contact
25 B1 25 B1
A1 15
21 (+)
A1 15
21 (+)
• LED indicators for operation, contact position and time delay
• Wire connection: also 2 x 1.5 mm2 stranded ferruled, or
X3 Z1 Z2 X3 2 x 2.5 mm2 solid DIN 46 228-1/-2/-3/-4
• as option with pluggable terminal blocks for easy exchange
A1 B1 15 25 A1 B1 Z1 15 25
21 21 of devices
-- with screw terminals
-- or with cage clamp terminals
26 28 26 28 • 22.5 mm width
A2 16 18 22 24 A2 Z2 16 18 22 24
26 28
X1 X2
26 28
X1 X2
MK 7850N/500: as MK 7850N/200 but with
22 24 M8100_a 22 24 M8676_a • 2 additional functions:
16 18 A2 16 18 A2 -- Cyclic timer, start with break (TP)
-- Fleeting on make and break (EW / AW)
• second time setting t2 for functions
MK 7850N.82/200 MK 7850N.82/300 -- Cyclic timer, start with pulse (TI) or break (TP), based on the
t1
separate setting of pulse and break time the flasher function
Z1 can be used as cyclic timer
Z2 -- Fleeting on make and break (EW/AW)
Z3
t2 -- Delay on energisation and de-energisation (AV / RV)
25 B1 - Delay pulse (IE) and setting of pulse length
A1 15
21 (+) • Connection facility for 2 external potentiometers
Z1 Z2 Z3 X3
Approvals and Markings
A1 B1 Z1 15 25
21
*
26 28
A2 Z2 Z3 16 18 22 24 Canada / USA A025518
26 28 * see variants
X1 X2
22 24 M8101_a
16 18 A2 Application
Time dependent controls for industrial and railway applications.
MK 7850N.82/500
Indicators
green LED: on when voltage connected
yellow LED "R/t": shows status of output relay and time
delay:
-Continuously off: output relay not active;
no time delay
-Continuously on: output relay active;
no time delay
-Flashing (short on, long off) output relay not active;
time delay
-Flashing (long on, short off) output relay active;
time delay
All technical data in this list relate to the state at the moment of edition. We reserve the right for
technical improvements and changes at any time. 1 15.03.17 en / 843
Function Diagram Function Diagram
UH UN
USt UN
B1-A2
0
ta tb tc td
UH UN
position function switch
A1-A2
0 15-18
1 AV t1
t1=ta+tb+tc
USt UN 15-16
B1-A2
0 15-18
ta tb tc td 2 EW t1
t1=ta+tb+tc
15-16
t 15-18 IE t1 t2 15-18
2 EW t=ta+tb+tc t1=ta+tb+tc t2=te+tf
15-16 S1: B* 15-16
t t 15-18 TP t2 t1 t2 15-18
4 BI t=ta+tb+tc t=te + tf t2=ta+tb+tg t1=th+ti
15-16 S1: B* 15-16
UH UN UH UN
A1-A2 A1-A2
0 0
USt UN USt UN
B1-A2 B1-A2
0 0
15-18 t1 t1 t1 15-18
5 RV t t t 5 RV
15-16 15-16
15-18 t1 t1 t1 t1 15-18
6 IF t t t t 6 IF
15-16 15-16
15-18 AW t1 t1 t1 15-18
7 AW t t t
15-16 S1: A* 15-16
7
15-18 EW/AW t2 t1 t2 t1 t2 15-18
8 AV/RV t t t t
15-16 S1: B* 15-16
M8290
t1 t2 t1 t2 15-18
8 AV/RV
15-16
M8291
MK 7850N/200 MK 7850N/500
... = position of function switch ... = position of function switch
AV = Delay on energisation RV = Delay on de-energisation AV = Delay on energisation RV = Delay on de-energisation
EW = Fleeting on make IF = Pulse forming function EW = Fleeting on make IF = Pulse forming function
IE = Delayed pulse AW = Fleeting on break IE = Delayed pulse AW = Fleeting on break
BI = Flasher, AV/RV = Delay on energisation and S1 in positon A: S1 in position A
start with pulse de-energisation t1: adjustable, t2 = 0.5 s fixed EW/AW = Fleeting on make
S1 in position B: and break
t1 and t2 adjustable S1 in position B
TI = Cyclic timer, AV/RV = Delay on energisation
start with pulse and de-energisation
S1 in position A
TP = Cyclic timer,
start with break
S1 in position B
2 15.03.17 en / 843
Connection Terminals Notes
The series resistor must not be selected higher than necessary. Setting
Max. values are:
Operating voltage: 48 V 60 V 110 V 230 V
Series resistor Rv max: 270 Ω 390 Ω 680 Ω 1.8 kΩ (1 W) Bridge, if extern potentiometer
not used
(only for MK7850N/300 and /500)
Instantaneous contact green LED
By external wire links the output function of the device can be altered from on when voltage
connected
2 delayed contacts to 1 delayed and 1 instantaneous contact. The contact
25-26-28 is delayed without bridge on X1-X2, it is instantaneous with bridge
yellow LED
on X1-X2. The legend term is 21-22-24. The instantaneous contact swit- function see range selector switch
ches when the operating voltage is connected. To terminals X1 and X2 no indicators
other voltage potentials must be connected, as the unit might be damaged. time setting t1
function setting
Adjustment assistance
The flashing period of the yellow LED is 1 s ± 4 % and can be used to
slide switch S1 time setting t2
adjust the time. Especially on the lower end of scale and for long times it (only with MK7850N/500) (only with MK7850N/500)
is suitable as the multiplication factors between the different time ranges
are exact without tolerance.
Example:
The required time is 40 min. It has to be adjusted within range
3 ... 300 min.The time check takes too long as several timing cycles would
be necessary for a precise value. For faster adjustment the setting is made
to 0.03 ... 3 min. On this range the potentiometer should be set to 0.4 min
(= 24 sec.). With the right potentiometer setting the LED must show 24
flashing cycles. After that the time range is switched over to 3 ... 300 min. M8302_d
and the setting is complete.
3 15.03.17 en / 843
Technical Data Technical Data
Time circuit General Data
Time ranges: 8 time ranges in one unit, settable Operating mode: Continuous operation
via rotational switch Temperature range
0.02 ... 1 s 0.3 ... 30 min Operation: - 40 ... + 60 °C
0.06 ... 6 s 3 ... 300 min (higher temperature see
0.3 ... 30 s 0.3 ... 30 h quadratic total current limit curve)
0.03 ... 3 min 3 ... 300 h Storage: - 40 ... + 70 °C
Time setting t1, t2: continuous, 1:100 on relative scale Relative air humidity: 93 % at 40 °C
(t2 only at MK 7850N/500) Altitude: < 2.000 m
Recovery time: Clearance and creepage
at DC 24 V: approx. 15 ms distances
at DC 240 V: approx. 50 ms rated impulse voltage /
at AC 230 V: approx. 80 ms pollution degree: 4 kV / 2 (basis insulation) IEC 60 664-1
Repeat accuracy: ± 0.5 % of selected Overvoltage category: III
end of scale value + 20 ms Insulation test voltage,
Voltage and type test: 2.5 kV; 1 min
temperature influence: < 1 % with the complete EMC
operating range Electrostatic discharge: 8 kV (air) IEC/EN 61 000-4-2
HF-irradiation
Input 80 MHz ... 1 GHz: 20 V / m IEC/EN 61 000-4-3
1 GHz ... 2.7 GHz: 10 V / m IEC/EN 61 000-4-3
Nominal voltage UN: AC/DC 12 ... 240 V Fast transients: 2 kV IEC/EN 61 000-4-4
Voltage range: 0.8 ... 1.1 UN Surge voltages
Release voltage (A1/A2) between
Delayed contact wires for power supply: 2 kV IEC/EN 61 000-4-5
AC 50 Hz: approx. 7.5 V between wire and ground: 4 kV IEC/EN 61 000-4-5
DC: approx. 7 V HF-wire guided: 10 V IEC/EN 61 000-4-6
Instantaneous contact Interference suppression: Limit value class B EN 55 011
AC 50 Hz: approx. 3 V Degree of protection
DC: approx. 3.3 V Housing: IP 40 IEC/EN 60 529
Max. permitted residual Terminals: IP 20 IEC/EN 60 529
current with 2-wire proximity Housing: Thermoplastic with V0 behaviour
sensor control (A1-A2) according to UL subject 94
up to AC/DC 150 V: AC resp. DC 5 mA Vibration resistance: Amplitude 0.35 mm,
up to AC/DC 264 V: AC resp. DC 3 mA frequency 10 ... 55 Hz, IEC/EN 60 068-2-6
Control current B1: approx. 1mA, over complete voltage Climate resistance: 40 / 060 / 04 IEC/EN 60 068-1
range Terminal designation: EN 50 005
Min. on/off time of Wire connection DIN 46 228-1/-2/-3/-4
control input B1(+): Screw terminals
AC 50 Hz: approx. 15 ms / approx. 60 ms (integrated): 1 x 4 mm2 solid or
DC: approx. 5 ms / approx. 60 ms 1 x 2.5 mm2 stranded ferruled or
Release voltage (B1/A2) 2 x 1.5 mm2 stranded ferruled or
AC 50 Hz: approx. 3.5 V 2 x 2.5 mm2 solid
DC: approx. 3 V Insulation of wires
Nominal power consumption or sleeve length: 8 mm
AC 12 V: approx. 1.5 VA Plug in with screw terminals
AC 24 V: approx. 2 VA max. cross section
AC 240 V: approx. 3 VA for connection: 1 x 2.5 mm2 solid or
DC 12 V: approx. 1 W 1 x 2.5 mm2 stranded ferruled
DC 24 V: approx. 1 W Insulation of wires
DC 240 V: approx. 1 W or sleeve length: 8 mm
Nominal frequency: 45 ... 400 Hz Plug in with cage
clamp terminals
Output max. cross section
for connection: 1 x 4 mm2 solid or
Contacts 1 x 2.5 mm2 stranded ferruled
MK 7850N.82: 2 changeover contacts, one min. cross section
programmable as instantaneous for connection: 0.5 mm2
contact: Insulation of wires
without bridge X1-X2: 25-26-28 delayed changeover contact or sleeve length: 12 ±0.5 mm
with bridge X1-X2: 21-22-24 instantaneous contact at Wire fixing: Plus-minus terminal screws M 3.5
UN on A1-A2 box terminals with wire protection or
Contact material: AgNi cage clamp terminals
Measured nominal voltage: AC 250 V Wire fixing: Box terminals with wire protection
Thermal current Ith: see quadratic total current limit curve Fixing torque: 0.8 Nm
(max. 4 A per contact) Mounting: DIN rail IEC/EN 60 715
Switching capacity Weight: approx. 150 g
to AC 15
NO contact: 3 A / AC 230 V IEC/EN 60 947-5-1 Dimensions
NC contact: 1 A / AC 230 V IEC/EN 60 947-5-1
to DC 13 at 0.1 Hz: 1 A / DC 24 V IEC/EN 60 947-5-1 Width x heigth x depth
Electrical life IEC/EN 60 947-5-1 MK 7850N/200: 22.5 x 90 x 97 mm
to AC 15 at 1 A, AC 230 V: 1.5 x 105 switching cycles MK 7850N/200 PC: 22.5 x 111 x 97 mm
Permissible switching MK 7850N/200 PS: 22.5 x 104 x 97 mm
frequency: 36 000 switching cycles / h
Short circuit strength
max. fuse rating: 4 A gL IEC/EN 60 947-5-1
Mechanical life: ≥ 30 x 106 switching cycles
4 15.03.17 en / 843
Classification to DIN EN 50155 Options with Pluggable Terminal Blocks
Vibration and
shock resistance: Category 1, Class B IEC/EN 61 373
Ambient temperature: T1, T2 compliant
T3 and TX with operational limitations
Protective coating of the PCB: No
UL-Data
Switching capacity:
Ambient temperature 60°C: Pilot duty B300 Screw terminal Cage clamp
5A 250Vac G.P. (PS/plugin screw) (PC/plugin cage clamp)
Wire connection: 60°C / 75°C copper conductors only
Screw terminals fixed: AWG 20 - 12 Sol/Str Torque 0.8 Nm
Plug in screw: AWG 20 - 14 Sol Torque 0.8 Nm
AWG 20 - 16 Str Torque 0.8 Nm Notes
Plug in cage clamp: AWG 20 - 12 Sol/Str
Removing the terminal blocks with cage clamp terminals
Technical data that is not stated in the UL-Data, can be found
in the technical data section. 1. The unit has to be disconnected.
nfo 2. Insert a screwdriver in the side recess of the front plate.
3. Turn the screwdriver to the right and left.
4. Please note that the terminal blocks have to be mounted on the
CCC-Data belonging plug in terminations.
Switching capacity:
to AC 15
NO contact: 1.5 A / AC 230 V
Technical data that is not stated in the CCC-Data, can be found
in the technical data section.
nfo
Standard Types
MK 7850N.82/200/61 AC/DC 12 ... 240 V
Article number: 0056618
• Output: 2 changeover contacts, one
programmable as instantaneous
contact
• Nominal voltage UN: AC/DC 12 ... 240 V
• Time ranges: from 0.02 s ... 300 h
• Width: 22.5 mm
Variants
MK 7850N.82/300: 8 functions with connection facility for
1 remote potentiometer 10 kΩ (t1).
MK 7850N.82/500: second time setting t2, connection facility
for 2 remote potentiometers 10 kΩ to adjust
t1 and t2,
2 additional functions selectable via slide
switch S1:
- Cyclic timer, start with break (TP)
- Fleeting on make and break (EW/AW)
5 15.03.17 en / 843
Characteristic Connection Examples
2
I (A )
2
L(+) S1
35
A1 X2
30 AC/DC12...240V voltfree
A2
MK7850N control contact
25 N(-) S2 (stop function)
B1(+) X3
20
15 M5794
10
5
L(+)
0
T (° C)
0 10 20 30 40 50 60 70 80
S1 S2
M10875
Accessories N(-)
M8127
AD 3: External potentiometer 10 kΩ
Article number: 0028962
Control with parallel connected load
The external potentiometer is used for
remote setting of the time delay. The
internal potentiometer of the timer must L(+) AC/DC12...240V
be set to min. time delay.
DC24V
Degree of protection S1
e.g. PLC
front side: IP 60 semi-
conductor
threaded ring
A1 B1(+) output
29
MK7850N
22
13,3
2...8 standard dimension A2
31,3 24
N(-)
55,3 3,2
M8292
12,5
Z1 Z2 22,5
M6925_a
E. DOLD & SÖHNE KG • D-78114 Furtwangen • PO Box 1251 • Telephone (+49) 77 23 / 654-0 • Telefax (+49) 77 23 / 654-356