You are on page 1of 1

NOTES:

ALL RIGHTS ARE RESERVED. THIS


DRAWING AND
ALL INFORMATION CONTAINED HEREIN

BASE FOUNDATION OF GENERATOR ARE THE PROPERTY OF CONSOLIDATED


CONSULTANTS,
SLAB FOUNDATION THICKNESS=250mm AND CANNOT BE COPIED , REPRODUCED.
TOP AND BOTTOM REINFORCEMENT UTILIZED OR MODIFIED IN WHOLE OR IN
MATERIAL: PART FOR PURPOSES OTHER THAN
CHARACTERISTIC COMPRESSIVE STRENGTH OF CONCRETE =25 N/mm² THOSE FOR WHICH THE DRAWING
CHARACTERISTIC TENSILE STRENGTH OF STEEL REINF. =420 N/mm² HAS BEEN ISSUED. FAILURE TO COMPLY
WHITH THE ABOVE WILL RESULT IN
TAKING LEGAL ACTION TO PROTECT THE
1140
2590 RIGHTS OF CONSOLIDATED
DIESEL ENGINE110 KVA CONSULTANTS. IT IS FORBIDDEN TO USE
THE CAD FILES TO CHANGE OR/AND
2490x1149x1440mm MODIFY THE
DESIGN WITHOUT WRITTEN APPROVAL.
FROM CONSOLIDATED CONSULTANTS.
REINFORCED CONCRETE
FOUNDATION BASE
1440

1440
3390X1950mm
WELL-COMPACTED TOP SOIL

PROJECT NAME

200 200 400 400

DRAWING NAME

FOUNDATION OF GENERATOR

SECTION i--------i 1550 PLOT AREA TOTAL BUILT AREA


.......... ........
8Ø16@200mm SECTION ii--------ii CLIENT NAME

.............
PLOT NO.
............
TOP & BOTTOM LONGITUDINAL REINFORCEMENT
( 3200mm LENGTH 150mm HOOKED BOTH ENDS)
2900 2900
ARCHITECT ID NO.
150 150
HAYMAN SAEED AHMED
2709
8Ø16@200mm
2990 15Ø16@200mm TOP & BOTTOM LONGITUDINAL REINFORCEMENT STRACTURAL DESIGNER
TOP & BOTTOM TRANSVERSE REINFORCEMENT ( 3600mm LENGTH 150mm HOOKED BOTH ENDS) HAYMAN SAEED AHMED 6260
400

(1750mm LENGTH 150mm HOOKED BOTH ENDS)


ELECTRICAL DESIGNER
150
400 30Ø16@200mm 12304
400 1450
TOP & BOTTOM TRANSVERSE REINFORCEMENT
MECHANICAL DESIGNER
(1750mm LENGTH 150mm HOOKED BOTH ENDS)
150 4549
1550
1550

SHEET TITLE

Scale SHEET NO.

Date

8Ø16@200mm
Revision No.
TOP & BOTTOM LONGITUDINAL REINFORCEMENT
400

( 3200mm LENGTH 150mm HOOKED BOTH ENDS)


2900
150

30Ø16@200mm
TOP & BOTTOM TRANSVERSE REINFORCEMENT
(1750mm LENGTH 150mm HOOKED BOTH ENDS)

FOUNDATION LAYOUT 150

1850

You might also like