Flexys Panel TX4 / Flexys Rail PLC - Flexible IO solution

Features :
l Flexible card selection
l Compact PLC with built-in HMI
l 4 line x 16 characters LCD display for Flexys Panel TX4
l Windows based user friendly software for ladder programming & HMI configuration
l RTC with Time Switch function (Optional)
l RS485 based communication with MODBUS RTU Protocol
l Expandable via IO Expansions

Certifications :

Display Specifications Analog Inputs

Item Specifications
Flexys Panel TX4 Flexys Rail
Module TC RTD Voltage Current NTC
Display LCD (backlight) 4 line X 16 12 LEDs to indicate card
Character, status for selectable slot, No of Channels
per Cards As per Card Selected
Font size 5X7 mm One 7 segment display to
indicate slot number, J,K,T,R,S,C,E,B,N, NTC
card failure indicated by Sensor L,U,W,Platinel II, PT100 0 - 10V 0 - 20mA (-40 to 95OC)
blinking display mV (-5 to 65mV)
Input impedance
18 (10 Numeric Keys) One key to scroll through in signal range 470kΩ 470kΩ 330kΩ 170kΩ 330kΩ
No. of keys
(14 User Configurable) different slot status
Resolution 12 bit

Conversion time 100ms 300ms 100ms


Input Specifications Analog input 0.15% of F.S. 0.1% of F.S.
±1°C ±1°C ±0.25% of F.S. ±2OC
error at 25°C
Fast Counter Input (on power supply card only) (Optional)
Protection against
polarity inversion Yes NA Yes Yes
No of Digital Inputs 4 (Uni) / 2(Bi / Quad ) / 4 Standard digital input
Operating Mode Unidirectional / Bidirectional /
Quadrature / Dual Uni (5kHz for all) / None

Mode Output Specifications


CH DI
UNI BI QUAD DUAL UNI NONE Transistor Output
No. of outputs per card 8
I0 RT RT 1st IP* RT Digital Input
Output Type Transistorized output DC, PNP
FC0
Digital Rated voltage 18 to 30V DC (External)
I1 Input Direction 2nd IP* T Digital Input
Response time 10ms
I2 RT RT 1st IP* RT Digital Input Short circuit protection Yes
FC1
Digital
Digital Input
Isolation 2.5kV (between CPU & outputs)
I3 Input Direction 2nd IP* T
Protection against polarity Yes
*900 Phase shift signals ; RT - Rate Totalizer, T - Totalizer Inversion
Digital Input Output Current 100mA maximum per output
Relay Outputs
No. of Inputs per card 4/10/14
No of Outputs per card 4/8
Input type DC, PNP
Response time 20ms
Input Voltage Range 6 - 30V DC (V+) Isolation 2.5kV (between CPU & outputs)
Maximum Counting Frequency 40Hz ( With <6ms debounce time) Output Current 5.5A @ 30V DC; 5.5A @ 230V AC (Resistive)
Response Time Default 10ms (Based on ladder scan time) Note : 230V model, supports up to 2 no. of FL-SC-RO08-CE / FL-SC-DI04-RO04
Isolation between 230V Yes cards only
Power Supply and Inputs
Protection against Yes
Polarity Inversion

www.selec.com 1
Flexys Panel TX4 / Flexys Rail PLC - Flexible IO solution

Power Supply
Analog Outputs
Item Specifications Flexys Rail / Flexys Rail /
Parameter Flexys Panel TX4-230V AC Flexys Panel TX4-24V DC
Module Voltage Type Current Type
No. of channels per card Supply Voltage 230V AC (90-270V AC) 24V DC (±10%V DC)
4 4
Range 0 - 10V 0 - 20mA Sensor Supply (SS) 10V (100mA) NA
Load Limit 1KΩ < 800Ω Power Consumption 13 VA 12 W
Digital Resolution 0.0 - 100.0% = 0 - 10V 0.0 - 100.0% = 0 - 20mA
Protection against
Conversion time 100ms NA Yes
Polarity Inversion
Analog output error at 25°C ±0.25% of F.S.
None Linearity ±0.25% of F.S.
Note : 1) 230V model, supports one FL-SC-AO04-V-CE or FL-SC-AO04-I-CE card only General Specification
2) In 230V model, combination of FL-SC-RO08-CE / FL-SC-DI04-RO04 &
FL-SC-AO04-V-CE / FL-SC-AO04-I-CE cards are not supported Ambient Operating 0 to 550C
3) In 230 model only support combination of FL-SC-AI03-U-AO02-U & 2 nos of
Temperature
FL-SC-RO08 and does not support combination of FL-SC-AI03-U-AO02-U and
Humidity 95%
FL-SC-AO04-V or FL-SC-AO04-I
4) 230V AC Model only support 2 nos of FL-SC-AI03-U-AO02-U Ambient Storage Temperature -20 to 700C
Earthing No

Mounting Flexys Panel TX4 : Panel Mount


Flexys Rail : Din Rail Mount
Functional Specifications (CPU)
Weight Flexys Panel TX4 : 225.6 gms (Logic + Housing )
Programming Language Window based software for Ladder Flexys Rail : Approx. 135 gms (Base Card + Housing)
programming & HMI Configuration Dimensions in mm Flexys Panel TX4 : 99 X 95.6 X 90.5
Program Memory 351kB Flexys Rail: 140 X 93.4 X 72
Data Memory 20kB
Upload Memory 96kB
EEPROM Memory 4kB
Ladder Scan - Cycle Time 1ms (typical 400µs) Outline Dimensions (in mm) Panel Cutout (in mm)
Memory Retention 10 years
RTC Yes
Battery Life 10 years for RTC only

90.5
99

Front bezel Side view

92
99 95.55 92
Communication 9

Flexys Rail I O Plate IO Plate IO Plate Common


Communication Port 1: RS485 Slave
9.4 9.4
(Port 1) 2: RS485 Master for MODBUS Expansion 140 72
Modules (IO610 series) & EXP FLEX 2M
3: Proprietary Master for proprietary Expansion
93.6

93.6
76

Modules (IO630 series)


17.6

Communication Protocols Modbus RTU, Proprietary Protocol


27.17 21.85 21.85
PS LG

Functional Features
Port Description
Timer Operational Modes On Delay, Off Delay, Pulse,
Special [Up/Down] Timer [1ms] Port 1 (6 pin jack)
PIN Description
Timer Resolution 1 ms (Accurate only for 1 msec Timer block)
Timer Display Format Sec, Min, Hr, Day, Min.Sec, Hr.Min, RS485 Slave +ve
Day.Hr, Hr.Min.Sec, Day.Hr.Min.Sec RS485 Master +ve
Counter Up Counter, Down Counter, Up/Down Counter, RS485 Master -ve
Special [Up/Down] Counter, Proprietary Expansion +ve
Fast Counter [up to 10 digits] Uni/Bi/Quad Proprietary Expansion -ve
Other Blocks Array, For next, PID Control with autotune, RS485 Slave -ve
Hysteresis, Scaling, Time switch,
Communication, RTC
Serial Printing Interface Yes
Flexys Panel TX4 / Flexys Rail PLC - Flexible IO solution

Ordering Information for loose Cards EMC


Order Code Description Certification Electromagnetic
Compatibility Reference Standard IEC61131-2
Flexys Panel TX4
Reference standard: IEC61000-6-2
230V AC operated power supply ESD Immunity Level III
FL–TX4–DI04–PS–230V-CE card with 4 digital inputs PNP type RoHS Test Setup: IEC61000-4-2
AC Power ±2KV CM
24V DC operated power supply
FL–TX4–DI04–PS–24V-CE card with 4 digital inputs PNP type RoHS Surge Immunity
Reference standard: IEC61000-6-2 ±1KV DM
Test Setup: IEC61000-4-5 DC Power ±0.5KV CM
Flexys Panel TX4. CPU with Master RS485, ±0.5KV DM
FL-TX4-LG-1-1-1-CE Proprietary IO Expansion and RTC RoHS
Reference standard: IEC61000-6-2 Level III 80 to 1000MHz
Flexys Rail Radiated
Test Setup: IEC61000-4-6 Level II 1GHz to 2GHz
Susceptibility Level I 2GHz to 2.7GHz
24V DC operated power supply
FL–RL–DI04–PS-24V-CE card with 4 digital inputs PNP type RoHS Conducted Reference standard: IEC61000-6-2
Test Setup: IEC61000-4-6 Level II
Susceptibility
FL-RL-BS-6-CE Flexys Rail Base card RoHS
Flexys Rail CPU with Master RS485, 0%, 0.5 Periods (Crit). A
FL-RL-LG-1-1-1-CE Proprietary IO Expansion and RTC RoHS
Voltage Dips 0%, 250/300 Periods (Crit. C)
Reference standard: IEC61000-6-2
FL-RL-PS-230V 230V AC Operated Power Supply Card --- 40%, 10/12 Periods (Crit. C)
and Interruption Test Setup: IEC61000-4-11
70%, 25/30 Periods (Crit. C)
80%, 250/300 Periods (Crit. C)

Conducted
CISPR 16-2-1 & CISPR 16-1-2 Crit. B
Emissions
Supported I/O Cards Radiated Emissions CISPR 16-2-3 Crit. A

Order Code Description Certitifaction Electrical Fast Reference Standard: IEC61000-6-2


Test Setup: IEC61000-4-4 Level III
Transient
I/O cards will be common for Flexys Panel TX4 & Flexys Rail
FL-SC-DI10-CE 10DI (10 Digital Inputs) RoHS

FL-SC-DI14 14DI (14 Digital Inputs) ---


FL-SC-DI04-RO04 4 Digital Inputs & 4 Relay Output ---
FL-SC-AI04-RTD-CE 4 Channel RTD – PT100 Analog inputs RoHS

FL-SC-AI06-V-CE 6 Analog Inputs (0-10V) RoHS

FL-SC-AI06-I- 6 Analog Inputs (0-20mA) RoHS

FL-SC-AIDF04-TC 4 Channel Thermocouple Analog Inputs Differential type ---


FL-SC-RO08-CE 8 Relay Outputs RoHS

FL-SC-TO08-CE 8 Transistor Outputs RoHS

FL-SC-AO04-V-CE 4 Analog Outputs (0-10V) RoHS

FL-SC-AO04-I-CE 4 Analog Outputs (0-20mA) RoHS

FL-SC-LC04 4 Channel Load Cell Card ---

Accessories
Accessories for communication
AC-USB-RS485-03 (USB to 6 pin RJ25 jack)
AC-USB-RS485-02 (USB to 2 pin open wire)
Expansion Module Cables & Adapter
ACH-004 (6 pin to 6 pin RJ25 jack) for expansion only (Cable)
1) AC-IOEXP-02 2)AC-IOEXP-03 (Port expansion adapter)
Window-Based Software for Ladder Programming
ACD-005
Relay Module
1) RLYMD-1-S4-1CO-24VDC : 4 Channel 1 change over Relay module
2) RLYMD-1-S4-2CO-24VDC : 4 Channel 2 change over Relay module
3) RLYMD-2-S8-1CO-24VDC : 8 Channel 1 change over Relay module
4) RLYMD-2-S8-2CO-24VDC : 8 Channel 2 change over Relay module

Power Supply Module


PS-CF-24V-1.1A
Expansion modules on Master RS485 / proprietary Port
EXP FLEX 2M : Expansion module on Master RS485 (I/O same as Flexys I/O cards)