1 Operation
Start the heat generator when the plant is cold. Heed the instructions for the heat
generator in the manufacturer's documentation.
In case of danger:
Press the "Emergency Stop button" of the plant and interrupt the fuel supply!
1
For burners with ignition medium
SAACKE GmbH SAACKE GmbH Tel.: +49 421 64 95 0 Technical Documentation
Südweststraße 13 Postfach 210261 Fax: +49 421 64 95 5224
28237 Bremen 28222 Bremen E-Mail: info@saacke.de
Germany Germany Internet: www.saacke.com
0-2279-4249c-02
2015-06-04 1/7
Operation SKVG-A
Switch off the burner. Follow the instructions in the manufacturer's documentation
for the burner control system.
For Maintenance
2
Interrupt the fuel supply and the supply with the ignition medium as well (for
example manual shut-off valves in the supply system). Follow the instructions in
the manufacturer's documentation for the corresponding supply systems.
Note
This section describes only the steps relevant for the burner. Follow the
instructions in the manufacturer's documentation on the fuel supply system and
burner control system as well as the other subsystems in the plant.
Reset the burner control system. Follow the instructions in the manufacturer's
documentation for the burner control system.
2
For burners with ignition medium
Technical Documentation
If Troubleshooting is Necessary:
Reset the burner control system. Follow the instructions in the manufacturer's
documentation for the burner control system.
Note
You will find more information on this topic in the operator´s manual for your plant
(manufacturer´s documentation on the oil flow meter).
3
For burners with ignition medium
Technical Documentation
2 P&I Diagrams
2.1 SKVG-A, Variant with Mechanical Compound Regulation
G
F
30
28
15
27
H
29
13
14
25
26
17
31
21
16
12
C
11
18.2
10
20
18.1
9
E
8
19
D
6
5
PZAH
4
B
1
3
A
2
A255
Fig. 1: P&I diagram SKVG-A, variant with mechanical compound regulation,
example: gaseous ignition media
Technical Documentation
Device Device
Reference Reference
number 4 number4
A --- Main fuel inlet (oil) 13 3Y2 Central valve ZV16 (safety shut-off valve)
Servomotor and mechanical compound
B --- Main fuel outlet (oil) 14 6Y1
regulator
C --- Main fuel inlet (gas) 15 --- Secondary air control damper
D --- Ignition medium inlet 1 16 --- Primary air control damper
Differential pressure monitor (L) for primary
E --- Ignition medium inlet 2 (optional) 17 17 F 1
air
Ignition medium gas pressure controller 1,
F 2T1 Igniter 18.1 ---
e.g. natural gas (gas igniters only)
Ignition medium gas pressure controller 2,
G --- Heat generator 18.2 ---
e.g. LPG (gas igniters only, optional)
Manual shut-off fitting for ignition medium
H --- Combustion air inlet 19 --- (one or two pcs., depending on whether one
or two ignition media are used)
Various heaters,
1 Various 20 --- Pressure gauge with shut-off valve
enabled in heavy oil operation only
Double temperature monitor (L/H) main fuel (oil), 2Y1 Rapid shut-off valves for ignition medium
2 18 A 1 21
enabled in heavy oil operation only 2Y2 (2 pcs.)
3 --- Pressure gauge 25 External Drive motor of the rotary cup atomizer
Oil pressure monitor (H)
4 18 F 4 Alternative: Pressure transducer or dummy 26 19 S 1 Swing-out switch
flange
5 --- Thermometer 27 40 B 1 Flame scanner
Oil pressure controller
6 --- 28 17 F 2 Air pressure monitor (L) for combustion air
Alternative: Oil throttle or dummy flange
7 --- Oil flow controller 29 --- Fan (optionally with silencer)
8 45 B 5 Oil flow meter 30 Extern Drive motor for fan
9 --- Bypass oil flow meter 31 --- Gas control damper
10 --- Manual shut-off fitting for main fuel (oil) --- --- ---
11 --- Dirt trap --- --- ---
Rapid shut-off valve ESVN-A
12 3Y1 --- --- ---
(safety shut-off valve)
Table 1: Legend for the figure "P&I diagram SKVG-A, variant with mechanical
compound regulation, example: gaseous ignition media"
4
Cp. Component connection diagram
Technical Documentation
G
F
28
30
15
27
H
29
25
12 13
26
17
21
16
31
11
10
C
18.2
9
20
18.1
14
8
E
19
7
D
6
PZAH
5
4
B
1
3
A
2
A256
Fig. 2: P&I diagram of SKVG-A, Variant with electronic compound regulation,
example: gaseous ignition media
Technical Documentation
Double temperature monitor (L/H) for main fuel 2Y1 Rapid shut-off valves for ignition medium
2 18 A 1 21
(oil), enabled in heavy oil operation only 2Y2 (2 pcs)
3 --- Pressure gauge 25 External Drive motor of the rotary cup atomizer
Oil pressure monitor (H)
4 18 F 4 Alternative: Pressure transducer or dummy 26 19 S 1 Swing-out switch
flange
5 --- Thermometer 27 40 B 1 Flame scanner
Oil pressure controller
6 --- 28 17 F 2 Air pressure monitor (L) for combustion air
Alternative: Oil throttle or dummy flange
6
7 6M1 Oil flow controller with servomotor 29 --- Fan (optionally with silencer)
8 45 B 5 Oil flow meter 30 External Drive motor for fan
6
9 --- Bypass for oil flow meter 31 7M2 Gas control damper with actuator
10 --- Manual shut-off fitting for main fuel (oil) --- --- ---
11 --- Dirt trap --- --- ---
Rapid shut-off valve ESVN-A
12 3Y1 --- --- ---
(safety shut-off valve)
Table 2: Legend for the figure "P&I diagram SKVG-A, variant with electronic
compound regulation, example: gaseous ignition media"
5
Cp. the component connection diagram
6
Only for variant with se@vis firing management system with se@vis FSM servomotors! In the case of other
electronic compound regulators (e.g. Etamatic), the servomotors are connected externally.
Technical Documentation