ITP list for electrical Works(chimney)

Inspection object chimney

ITP NO. ITP name

Inspection and Test


ITP-CHI-ELE-1.1 Plan for Light &
Sockets

Inspection and Test


ITP-CHI-ELE-1.2
Plan for Grounding
ITP list for electrical Works(chimney)

Scope of Work remark

1、 Inspection of light wire protection ducts;2、 Inspection of


junction box installation;3、 Inspection of wire laying;4、
Inspection of lamps and sockets mounting

1、 Installation of grounding grid;


Inspection and Test Plan for Light & Sockets
The Insp
Specification Inspection
ITP NO. Item of test and inspection Acceptance Criteria proportion/Freque Sub-
Reference Method
ncy of inspections con

1 PREPARATION WORK CONTROL


documentatio
1.1 Approved DFE drawing DFE040-04 complete and valid 100% R
n check
Vendor document list
Vendor documentation(including testing documentatio
1.2 and EQCP's outing Reviewed by FIDIC 100% P
report、drawing) n check
document list

Activities on the
site,Official Gazette of
1.3 Construction log meet the requirements
the Republic of
Serbia", No. 22/2015

2 EXECUTION CONTROL
Inspection of light wire protection ducts
2.1
preparation
Conform to design On-site
2.1.1 Model, specifications, materials spot check P
documents Inspection
DFE Drawing、RPS EN No damage or serious On-site
2.1.2 Inspection of ducts appearance spot check P
60364-5-51 corrosion Inspection
On-site
2.1.3 Inspection of inner surface of ducts Smooth, without burrs spot check P
Inspection
Inspection of light wire protection ducts
2.2
laying
Conform to design On-site
2.2.1 Ducts position and mode spot check P
documents Inspection
DFE Drawing、RPS EN Conform to the On-site
2.2.2 Ducts bending radius spot check P
60364-5-51 standard requirements Inspection
On-site
2.2.3 The incision of the ducts Flat, smooth spot check P
Inspection
2.3 Inspection of junction box installation
On-site
2.3.1 Junction box model Matching with ducts spot check P
Inspection
DFE Drawing、RPS EN Easy to install the On-site
2.3.2 Installation location spot check P
60364-5-51 lighting line Inspection
Firmly, not easy to On-site
2.3.3 Fixing spot check P
damage Inspection
2.4 Inspection of protection ducts connection
Tightness and no On-site
2.4.1 Ducts fastening(Screw) spot check P
DFE Drawing、RPS EN loosening Inspection
60364-5-51 Tightness and no On-site
2.4.2 Connection between ducts and Junction box spot check P
loosening Inspection
2.5 Wire check before laying
Conform to design On-site
2.5.1 Model, voltage and specifications spot check P
DFE Drawing、RPS EN documents Inspection
60364-5-51 On-site
2.5.2 Insulating layer No damage spot check P
Inspection
2.6 Inspection of wire laying and connection P
No stagnant water, No On-site
2.6.1 Inspection of sundries in duct spot check P
sundries, unblocked Inspection
Conform to design On-site
2.6.2 Loop arrangement spot check P
DFE Drawing、RPS EN documents Inspection
60364-5-51 On-site
2.6.3 Wire through the ducts No damage, no knot spot check P
Inspection
Tighten and contact On-site
2.6.4 Single wire splice connection. spot check P
well. Inspection
2.7 Wire check after laying spot check P
Insulation between conductors and DFE Drawing、RPS EN meet the design and On-site
2.7.1 spot check P
Insulation between conductors with earth 60364-5-51 standards requirements Inspection
2.8 Lamps and sockets check before mounting
Conform to design On-site
2.8.1 Model, specifications, materials spot check P
documents Inspection

DFE
Drawing、Manufacture
r's manual
On-site
2.8.2 Accessory DFE Matching and complete spot check P
Inspection
Drawing、Manufacture
r's manual On-site
2.8.3 Appearance No defect spot check P
Inspection
On-site
2.8.4 Connector Matching, flexible spot check P
Inspection
2.9 Lamps and sockets assembly P

DFE Conform to
On-site
2.9.1 Assembly sequence Drawing、Manufacture manufacturer's spot check P
Inspection
r's manual reguirements
Inspection of connection of wire and
2.10
lamp/socks
On-site
2.10.1 Connecting Firmly spot check P
Inspection
DFE Drawing、RPS EN On-site
2.10.2 Insulation treatment at junction Bind tightly and evenly spot check P
60364-5-51 Inspection
On-site
2.10.3 Lamp wiring Correct spot check P
Inspection
2.11 Inspection of lamp fixing
Conform to design On-site
2.11.1 Location spot check P
documents Inspection
DFE
Conform to
Drawing、Manufacture On-site
2.11.2 Fixed mode manufacturer's spot check P
r's manual 、RPS EN Inspection
reguirements
60364-5-51
On-site
2.12 Inspection of lamp grounding Good connected spot check P
Inspection
2.13 Cable check before laying
Conform to design On-site
2.13.1 Model, voltage and specifications spot check P
documents Inspection
DFE Drawing、 RPS EN
No mechanical On-site
2.13.2 Visual inspection 60227-1、RPS EN spot check P
damage Inspection
60227-3
meet the design and On-site
2.13.3 Insulation inspection spot check P
standards requirements Inspection
2.14 Inspection of cable laying
Comply with the On-site
2.14.1 Bending radius of cable spot check P
standard Inspection
meet the design and On-site
2.14.2 Distance from the heat preservation layer spot check P
standards requirements Inspection
DFE Drawing、 IEC Neatly
On-site
2.14.3 Cable arrangement appearance Check 60227-1 arranged,curvature spot check P
Inspection
、IEC 60227-3 consistent
Comply with the On-site
2.14.4 AC single-core cable arrangement spot check P
standard Inspection
On-site
2.14.5 Cable label Cable terminals spot check P
Inspection

3 Final control
Check for functional
Lighting and small power test report by According to relevant On-site
3.1 after 24 hours of power- 100% P
certified company standard Inspection
on
(as in design
3.2 Lighting level test report DFE Design documentation
calculation part)
Completeness check of construction documentatio
3.3 complete and valid 100% P
documentation n check
LEGEND
P/T Perform/Testing
W Witness Point
S Spot Witness
H Hold with Inspection Record/Report
R Inspection & Test Document Review
√ Signed
ts No: ITP-CHI-ELE-1.1
Inspection by
CMEC/CE SUPVI Remark
NO BO TMS TPI FIDIC OWNER
GROUP SION

P R

R R

S S

S S

S S

S S

S S

S S
S S

S S

S S

S S

S S

S S

S S

S S

S S

S S

S S

S S

S S

S S

S S
S S

S S

S S

S S

S S

S S

S S

S S

S S

S S

S S

S S

S S

S S
S S

S S

S S

S S

S S

W S

P R R
Inspection and Test Plan for Grounding
The Inspection by检查
Specification Acceptance proportion/Fr Inspection
ITP NO. Item of test and inspection Sub- CMEC/CE
Reference Criteria equency of Method NO BO TMS
con GROUP
inspections

PREPARATION WORK
1
CONTROL
complete and documentatio
1.1 Approved DFE drawing DFE040-04 100% R P
valid n check

Vendor document list


material documentations and complete and documentatio
1.2 and EQCP's outing 100% P R
certificate (by manufacturer) valid n check
document list

Activities on the
site,Official Gazette meet the documentatio
1.3 Construction log P
of the Republic of requirements n check
Serbia", No. 22/2015

2 EXECUTION CONTROL
Inspection of vertical
2.1 grounding electrode
laying(outdoor)
Conform to
Inspection of material On-site
2.1.1 design spot check P S
specification Inspection
documents
Visual inspection of vertical On-site
2.1.2 Surface intact spot check P S
grounding electrode Inspection
DFE Drawing Conform to
Depth of buried vertical On-site
2.1.3 design spot check P S
grounding electrode Inspection
documents
Conform to
Distance between vertical On-site
2.1.4 design spot check P S
grounding electrode Inspection
documents
Inspection of horizontal
2.2
grounding laying(outdoor)
Conform to
Cross-section of horizontal On-site
2.2.1 design spot check P S
grounding conductor Inspection
documents
Conform to
Depth of buried horizontal On-site
2.2.2 design spot check P S
grounding conductor Inspection
documents
Conform to
Distance between horizontal On-site
2.2.3 design spot check P S
grounding conductor Inspection
documents
Distance between horizontal Conform to
DFE Drawing 、SRPS design On-site
2.2.4 grounding conductor and spot check P S
N.B2 754 Inspection
building documents
SRPS N.B2 762 Steel pipe or
Protective measures when On-site
2.2.5 SRPS EN 62305-1~3 other sturdy spot check P S
passing through walls Inspection
protection
Conform to
Number of connection points On-site
2.2.6 design spot check P S
with other grounding devices Inspection
documents
No stones or On-site
2.2.7 The quality of backfill soil spot check P S
debris Inspection
Conform to
On-site
2.2.8 Grounding resistance design spot check P S
Inspection
documents
Inspection of horizontal
2.3
grounding laying(indoor)

DFE Drawing 、SRPS


N.B2 754
When laying along walls or Parallel to the On-site
2.3.1 spot check P S
buildings wall or building Inspection
SRPS N.B2 762
SRPS EN 62305-1~3

Inspection of lightning
2.4 spot check
conductor laying
Conform to
Inspection of material On-site
2.4.1 design spot check P S
specification Inspection
documents
Galvanized layer On-site
2.3.2 Visual inspection spot check P S
Intact Inspection
Conform to
Cross-section and thickness of On-site
2.3.3 design spot check P S
flat steel Inspection
documents
meet the design
DFE Drawing 、SRPS and standards On-site
2.3.4 Lap length of flat steel spot check P S
N.B2 754 Inspection
requirements
SRPS N.B2 762
SRPS EN 62305-1~3
DFE Drawing 、SRPS
N.B2 754
SRPS N.B2 762
On-site
2.3.5 Inspection of welding position SRPS EN 62305-1~3 Firmly spot check P S
Inspection
Surface treatment of welding Brush anti- On-site
2.3.6 spot check P S
parts corrosion paint Inspection
Connection mode of lead line On-site
2.3.7 Welding spot check P S
with grounding Inspection
Galvanized On-site
2.3.8 Fastener spot check P S
products Inspection

3 Final control
Conform to
Measurement of grounding resistance On-site
3.1 design 100% P W
( By Certificed) Inspection
documents
Completeness check of complete and documentatio
3.2 this ITP 100% P P
construction documentation valid n check

LEGEN
D
P/T Perform/Testing
W Witness Point见证点
S Spot Witness
H Hold with Inspection
Inspection & Test Document
R
Review
√ Signed
No: ITP-CHI-ELE-1.2
nspection by检查
SUPVISI Remark
TPI FIDIC OWNER
ON

加基础施
工的防雷
接地

S
S

S
S

construction
R R
log