abcd ALSTOM Power HTGD680559

Responsible department: Take over department: Revision: Doc. type: File no.:

9665 - C HTGD RK02-24-200


Prepared: Checked: Approved: Language: Page:
2010-10-01 krapebl 2010-10-01 krahuwe
2010-09-22 fzenuni en 1/3
Valid for: Derived from: Replaces: Data set:

HTGD680357

Product description

TBVS90A 2-out-of-3 tripblock with sequence valve

Contents
1 Zweck ............................................................................................................................................................1
2 Geltungsbereich ............................................................................................................................................1
3 Mitgeltende Dokumente ................................................................................................................................1
4 Abkürzungen .................................................................................................................................................1
5 TBVS90A limit of application.........................................................................................................................2
6 Beschreibung ................................................................................................................................................2
7 Available options ...........................................................................................................................................2
2010-10-01 EN Approved

8 Unavailable options .......................................................................................................................................2


Lng. Status

9 3D views........................................................................................................................................................3

1 Zweck
Rev. Released

This document describes the the TBVS90A 2-out-of-3 tripblock with sequence valve..
-

2 Geltungsbereich
Type
C

This document applies to the TBVS90A 2-out-of-3 tripblock with sequence valve..

3 Mitgeltende Dokumente
9665 HTGD680559
Dept. Document No.

HTGD680237 TBVS90A 2-out-of-3 tripblock with sequence valve, limits of application


HTGD680560 TBVS90A 2-out-of-3 tripblock with sequence valve, technical data
HTGD680495 TBVO90A 2-out-of-3 tripblock, product description
HTGD680067 Product description combined hydraulic and lube oil supply
HTGD680074 Product description separate hydraulic supply MTHV014
HTGD 90117 Lubricating and control oils for gas and steam turbines
HTGD690149 Flame resistant hydraulic fluid HFD-R

4 Abkürzungen
S90 Hydraulic safety and control system S90

We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without
express authority is strictly forbidden. © ALSTOM 2010
Revision: Language: Page:

abcd - en 2/3
HTGD680559

5 TBVS90A limit of application


The following conditions are valid for the TBVS90A
• Operation temperature of the hydraulic medium: +40° to +60 °C
• Ambient temperature: +25°C to +60°C
• Design pressure (nominal pressure): 42 bar
• Operation pressure: 40 bar
• Hydraulic medium: Lube oil or HFD-R (fire resistant fluid)
• Life time: 30 years

6 Beschreibung
The 2-out-of-3 tripblock TBVS90A with sequence valve is acc. to IEC61511/61508 suitable for
using in a safety related system up to SIL 3 level (tested by TÜV Rheinland).
The TBVS90A acts as interface between the elektronic and hydraulic safety system of the and
constist out of the TBOS90A and the sequence valve.
2010-10-01 EN Approved

The trip signal lead 3-channelled and de-energise to trip to the trip valves. Die 2-out-of-3 voting
Lng. Status

is realised in the hydraulic part of the TBOS90A and allow an easy testing of the system.
The sequence valve consists out the a slider and a parallel installed discharge amplifier as plate
valve type. The slider has four positions/functions:
Rev. Released

• Position trip: The slider separates in this position the pumps from the safety system. Start-up
(reset) is just possible only in this state.
-

• Position filling the pipe system: In order to avoid hydraulic shocks the pipe system has to be
Type
C

filled smoothly.
• Position normal operation: The slider fully opens in this position the connection between
pumps and safety system.
9665 HTGD680559
Dept. Document No.

• Channel testing: De-energising one trip solenoid (or putting one isolating valve into test
position) the slider moves to ist tests test position indicated by two position sensors.
Energising the solenoid valve (resp. when the isolating valve is turned back in ist operation
position) the slider moves back into ist operation position. Channel testing is succesfull when
both sensors indicate operation position again.
In order to gain an easy draining of the TBVS90A it is mounted horizontally on the tank.

7 Available options
7.1 Magnetventile
• Standard = Wandfluh solenoid valve
• Option = Bosch-Rexroth solenoid valve
7.2 Connection to mechanical overspeed device
TBVS90A allows to connect a mechanical overspeed device.

8 Unavailable options
• TBVS90A is designed for an operation pressure of 40 bar.
• Smaller pressure levels (≥ 35, ≥ 25, ≥ 16, ≥ 7 and ≥ 5 bar) shall be prepared later.
Revision: Language: Page:

abcd - en 3/3
HTGD680559

9 3D views
Fig. 1: 3D view TBOS90A 2-out-of-3 tripblock

1 2
3
4

1 Trip solenoid valve 3 Position indication of the gate valve


2010-10-01 EN Approved
Lng. Status

2 Isolating valve 4 Gate valve


Rev. Released

Fig. 2: 3D view TBVS90A 2-out-of-3 tripblock with sequence valve


-
Type
C
9665 HTGD680559
Dept. Document No.

1 Trip solenoid valve 5 Slider (sequence valve)


2 Isolating valve 6 Position indication of the slider
3 Position indication of the gate valve 7 Discharge ampifier
4 TBOS90A 2-out-of-3 8