You are on page 1of 8

PO1918491 DOI: 10.

2118/1918491-PA Date: 8-May-15 Stage: Page: 156 Total Pages: 8

Tubing Anchors Can Reduce Production


Rates and Pump Fillage
James N. McCoy, O. Lynn Rowlan, and Carrie A. Taylor, Echometer Company; and A.L. Podio, University of Texas
at Austin

Summary PBHPs, which decrease the production from the reservoir and
Modern completion techniques have greatly increased the produc- result in a decline in production reaching the surface.
tion-rate capability of wells. Many wells have the potential to pro-
duce more liquid and gas, but the use of tubing anchors in certain Producing Bottomhole Pressures (PBHPs) Impact
wellbore locations chokes the gas flow up the casing and results Well Performance
in increased backpressure against the formation, which restricts Fig. 1 displays the analysis of a typical fluid-level shot, with cas-
production from the well. A gaseous liquid column can form ing-pressure-buildup rate, PBHP, and pump-intake-pressure (PIP)
above the tubing anchor and cause high pressure in the gas below calculations, as well as the potential production available as deter-
the tubing anchor that restricts the liquid and gas flow from the mined by the Vogel inflow-performance-relation (IPR) curve,
reservoir. which compares PBHP to static bottomhole pressure (SBHP) or
Often, low pump fillage and low production rates are blamed reservoir pressure. To obtain an accurate IPR determination, the
on a poor gas separator, when actually the separator is operating current PBHP and well test must be obtained and SBHP must be
efficiently and is separating the liquid from the gas. In the condi- representative of current reservoir conditions. To accurately deter-
tion described, all of the liquid in the wellbore below the tubing mine SBHP, the well must be shut in for a period of time suffi-
anchor falls to the pump and is being removed by the pump. The
cient for the fluid level and casinghead pressure to stabilize.
problem is that high pressure in the gas column below the tubing
When PBHP increases enough to cause the flow rate from the
anchor is restricting production from the well. Additional produc-
formation to decrease, measures should be taken to determine
tion is available if the high pressure that is restricting production
the major cause of high PBHP and adjustments should be made to
from the formation is removed. The accumulation of a gaseous
the pumping system to lower PBHP and increase production. For
liquid column above the tubing anchor when constant low pump
example, a high gas-free fluid level on a producing well will
fillage is observed indicates that liquid exists above the tubing
increase PBHP, which in turn decreases the drawdown on the for-
anchor whereas only free gas exists from the tubing anchor down
mation, slowing the desired inflow performance from the reser-
to the pump. Limited liquid production falls down the casing
voir. When a high fluid level exists and pump volumetric
wall, while the casing annulus is almost completely filled with gas
efficiency is high (McCoy et al. 2002), meaning maximum effec-
if the pump is set below the formation (McCoy et al. 2013).
tive plunger travel is used and full pump loads are produced to
Field testing with automated fluid-level-measurement equip-
ment to perform liquid-depression tests verifies that a gaseous liq- surface, adjustments can be made to the pumping system (i.e.,
uid column exists (Rowlan et al. 2008) above the tubing anchor increasing pumping-unit speed or increasing pump size) to lower
and a gas column exists below the tubing anchor in wells with the fluid level to the pump intake thereby lowering the PBHP and
high fluid levels, with low pump fillage, and with the tubing increasing inflow from the formation. However, when a high fluid
anchor located above the pump. These field data were acquired on level exists and pump volumetric efficiency is low because of a
several wells and are shown to verify the preceding analysis of mixture of fluid and gas at the pump intake, indicating incomplete
the well’s performance. This fluid-distribution condition is not pump fillage because of gas interference (McCoy et al. 2010), fur-
generally known. Locating the tubing anchor below the pump pre- ther measures must be considered to deal with the problem of gas
vents this condition and will improve production in these wells. separation below the pump. Low pump fillage because of gas in-
terference causes produced fluids to accumulate in the wellbore
rather than being delivered by the pump into the bottom of the
Introduction tubing at the desired rate. The annular fluid level then increases
When a naturally flowing well is no longer capable of performing and expands into a high gaseous liquid column.
per its desired or designed production rate, artificial-lift methods The most-effective solution for incomplete pump fillage
are installed to improve performance and increase production. To because of gas interference is to locate the pump intake below the
optimize rod-pumped well performance, pumping-system designs gas- and fluid-entry zone of the formation (McCoy et al. 2002;
ideally match pump displacement to the inflow of fluids from Lisigurski et al. 2005; Bohorquez et al. 2007). Consider the sche-
the formation by controlling pumping-unit speed, stroke length, matic shown in Fig. 2.
plunger diameter, and pumping-unit run time. Sufficiently match- Fig. 2 illustrates the relation of wellbore-pressure distribution
ing fluid inflow from the formation to pump displacement will of a producing well operating in a stabilized condition with the
typically keep fluid levels a few hundred feet above the pump pump intake set a few feet below the fluid-entry zone. The fluid
intake. When the fluid level is located just above the pump intake, level and casinghead pressure are constant, and all fluids (oil,
the majority of producing bottomhole pressure (PBHP) then water, and gas) entering the wellbore are being produced at the
comes from the pressure exerted at the gas/liquid interface, which surface at a constant rate. A gaseous liquid column (oil and gas)
results in a lower backpressure against the reservoir, yielding a exists above the pump intake, while fluid below the pump intake
higher drawdown and better production. Generally, high casing is primarily brine with very low free-gas concentration. The dia-
pressure and/or high fluid levels are the main causes of high gram on the right-hand side of the schematic displays the pres-
sure-vs.-depth relationship of the casinghead pressure (Pc), the
gas-column pressure, and the fluid-column pressure to the stabi-
lized producing drawdown capabilities (SBHP – PBHP) of the
Copyright V
C 2015 Society of Petroleum Engineers
well. It can be deduced from the diagram that for a given casing-
This paper (SPE 1918491) was accepted for presentation at the SPE/AAPG/SEG head pressure (Pc), a fluid level just above the pump intake results
Unconventional Resources Technology Conference, Denver, 25–27 August 2014, and
revised for publication. Original manuscript received for review 12 May 2014. Revised
in a lower PBHP and a higher drawdown on the formation
manuscript received for review 30 November 2014. Paper peer approved 4 December 2014. (SBHP) (McCoy et al. 1987).

156 May 2015 SPE Production & Operations

ID: jaganm Time: 16:38 I Path: S:/3B2/PO##/Vol00000/150002/APPFile/SA-PO##150002


PO1918491 DOI: 10.2118/1918491-PA Date: 8-May-15 Stage: Page: 157 Total Pages: 8

Fluid Above Pump 1,148 ft


Liquid Level 4,276 ft Gas Free Above Pump 269 ft

Production Modify...
Gun
Date Entered 05/06/02
Sec ft Current Potential
0 0 Oil 4 4 B/D
Water 33 35 B/D
Gas 0.1 0.1 Mscf/D

IPR Method Vogel


Producing Efficiency 96.22%
1,000
2 Casing Pressure
Pressure 117.3 psi (g)

Annular Gas Flow


2,000
Gas Flow 78.6 Mscf/D

4 Fluid Properties
% Liquid Above Pump 23.46%
% Liquid Below Pump 49.74%
3,000
Wellbore Pressures
PIP 233.3 psi (g) @ 5,424 ft
PBHP 238.5 psi (g) @ 5,448 ft
6 SBHP 2000.0 psi (g) @ 5,430 ft
4,000 Gas/Liq interface 146.4 psi (g) @ 4,276 ft
LL:4,276 ft
Depths
Pump Intake Depth 5,424 ft
Formation Depth 5,448 ft
5,000
8 Sensor Serial No.
WG Unknown

Collar Analysis (Automatic) Casing-Pressure Buildup


124
122
120
118
0 0.5 1 1.5 2 2.5 3
Delta Time (minutes)
Casing Pressure 117.3 psi (g)
Average Acoustic Velocity 1293 ft/sec Buildup 7.1 psi (g)
Average Joints Per Second 20.39 joints/sec Buildup Time 2 min 45 sec
Joints To Liquid 134.90 joints Gas Gravity 0.6540 Air = 1

Fig. 1—Example fluid-level analysis to obtain gas/liquid-interface pressure, percentage of liquid above the pump, PBHP, and PIP.

Pt

Pc Pc
Pressure

Gas

Fluid Level

Drawdown
Oil + Gas

Brine
PBHP Gradient
PBHP SBHP
Depth

Fig. 2—Wellbore-pressure distribution in a stabilized producing well by use of a natural gas separator.

May 2015 SPE Production & Operations 157

ID: jaganm Time: 16:38 I Path: S:/3B2/PO##/Vol00000/150002/APPFile/SA-PO##150002


PO1918491 DOI: 10.2118/1918491-PA Date: 8-May-15 Stage: Page: 158 Total Pages: 8

is set above the formation, and other gas-separation options must


Tubing
be considered.
Casing The key to choosing and installing an efficient downhole gas
separator is to choose a separator that will maximize the area used
for separation. An efficient downhole gas separator will increase
the pump liquid-fillage percentage over the percentage of liquid
present in the wellbore at the pump intake. Setting the pump
intake above the fluid-entry zone (McCoy and Podio 1999) in a
Gaseous
liquid well will create difficulties with gas separation, but a number of
column gas separators exist to assist in increasing pump fillage and pro-
duction of fluids to the surface.
Casing
perforations
Field Study of Downhole Gas-Separator
Effectiveness
Seating
nipple At least Often, low pump fillage and low-production rates are blamed on a
8 ft poor gas separator, when actually, the separator is operating effec-
from casing
Open pump or perforations Gas - free tively and is separating the liquid from the gas. Proper gas-separa-
short perforated to anchor tor selection, when the pump intake is above the formation, must
liquid
nipple perforations
take into account casing-annulus gas-production rate and the net
pump capacity (pump displacement – pump slippage) of the well.
Gas-anchor The percentage of pump liquid fillage on rod-pumped wells is
perforations
computed routinely from downhole-pump dynamometer-card
analysis. Fluid-level and dynamometer measurements can be per-
formed to determine gas-separation effectiveness by comparing
the fluid-level-survey analysis of gas-flow rate and percent liquid
in the annulus, and the effective pump displacement from the
downhole pump dynamometer card.
Fig. 3—Natural downhole gas separator with pump intake set Using fluid-level and dynamometer-analysis comparisons for a
below the fluid-entry zone. number of producing wells in the Sprayberry trend located in the
Permian basin in west Texas, an effectiveness study was per-
formed to measure the performance of wells completed with both
Downhole Gas Separation natural and packer-type gas separators (McCoy et al. 2013; Lisi-
All gas separators for rod-pumped wells work on the basic princi- gurski et al. 2005). In Fig. 4, the performance-evaluation graph on
ple of gravity separation. A natural downhole gas separator, as the right-hand side plots the percentage of liquid in the annulus
shown in Fig. 3, takes advantage of natural separation caused by from the fluid-level survey vs. the percentage of effective pump
gravity segregation of the gas and liquid phases when the pump fillage from the dynamometer pump card. The symbols indicate
intake is set below the fluid-entry zone (McCoy and Podio 1999; the type of downhole gas separator installed in each well. The di-
McCoy et al. 2013). By use of natural gas separation, liquids flow agonal line represents the boundary where the percent liquid in
downward from the perforations to the tubing intake, while the the annulus at the pump intake is equal to the percent pump fil-
majority of the gas flows up through the annulus and to the lage. Wells with the pump intake set high above the fluid-entry
surface. zone have been completed with packer-type separators and are
The ability of the gas to efficiently separate from the liquid in indicated by circles. Wells that use a natural gas separator with
any gas-separation system is dependent upon the downward liquid the pump intake below the fluid-entry zone or “in the rathole” are
velocity in the casing annulus (Bohorquez et al. 2007). Downward indicated by triangles.
annular liquid velocity less than or equal to 6 in./sec (Walker To the left of the graph in Fig. 4, the fluid-level survey and dy-
1939) allows the majority of gas entering the wellbore from the namometer pump card measurement for one of the evaluated
formation to overcome drag forces from the downward flowing wells, typical for the region, is shown. This well, located in the
liquid and move upward so that mainly liquid is present at the Wolfberry formation near Big Spring, Texas, USA, has a forma-
pump intake. When downward liquid velocity exceeds 6 in./sec, tion depth of 10,400 ft, a gas/oil ratio of 3,941 scf/bbl, with a
gas is unable to effectively separate from the liquid, and the effi- water cut of 43.1%. The fluids are oil at 41.2  API, water at 1.035
ciency of the gas separator is greatly reduced. Gas-separation fail- specific gravity, and gas at .831 specific gravity.
ure causes a larger volume of gas to be dragged into the pump, The casing-pressure-buildup measurement from the fluid-level
resulting in decreased volumetric efficiency. The downward liquid survey equates to a very high gas-flow rate of 511 Mscf/D and a
velocity can be determined by comparing the ratio of the pump- low 19% liquid concentration in the annulus above the pump
flow rate to the annular area. For example, the liquid-separation intake. The percent liquid concentration is the calculated percent-
capacity of a pumping well completed with 51/2-in. 17-lbm/ft cas- age of liquid present in the annular gaseous liquid column
ing and 23/8-in. 4.6-lbm/ft tubing, with the pump intake set below (McCoy et al. 1987). The effective pump fillage computed from
the fluid-entry zone (natural downhole gas separator) and an annu- the dynamometer measurement is approximately 62%. While
lar area of 14.4 in.2, is 769 B/D. pump fillage does not reach a desired 100%, 62% pump fillage on
The most-effective downhole gas separators locate the pump this well with the pump set several thousand feet above the fluid-
intake below the lowest gas-entry point. Gas is not pulled down to entry zone, where the liquid concentration is a low 19%, indicates
the pump perforations unless the liquid velocity is greater than 6 that the downhole gas separator is effectively increasing the liquid
in./sec. Maximum annular capacity is used when a pumping sys- concentration in the pump by a factor of three. The packer-type
tem is designed with a natural downhole gas separator because gas separator on this well is significantly improving pump volu-
nothing can be run in the wellbore that will provide more separa- metric efficiency.
tion area than the annulus itself. Viewing each variable on the graph similarly, wells plotted
Downhole gas separation is one of the biggest problems in above the diagonal line had poor gas separation, resulting in low
medium- and high-volume producing wells. Fluid is present in the pump-fillage percentages compared with the liquid concentration
annulus, but because of the gas producing from the formation, available in the annuli. The gas separators are even preventing flu-
low pump fillage caused by gas interference limits production ids from reaching the pump. Wells plotted below the diagonal line
capabilities and overall well performance. Often, the pump intake had a pump-fillage percentage that was higher than the percent

158 May 2015 SPE Production & Operations

ID: jaganm Time: 16:38 I Path: S:/3B2/PO##/Vol00000/150002/APPFile/SA-PO##150002


PO1918491 DOI: 10.2118/1918491-PA Date: 8-May-15 Stage: Page: 159 Total Pages: 8

Well State:
Producing 100
Average all packer Average all in rathole
Annular Packer-type separators—7,300 ft Pump in rathole—10,300 ft
Gas Flow 90

Average Liquid Concentration Annulus (%)


511 Mscf/D
%Liquid 80
19
70

60
50

40

30
Pump Intake Pressure
521.4 psi (g) 20
PBHP
1178.2 psi (g) 10

Reservoir Pressure (SB) 0


psi (g) 0 10 20 30 40 50 60 70 80 90 100
Average Liquid Fillage in Pump (%)

Fig. 4—Field-study evaluation graph of gas-separator performance.

liquid concentration in the annulus, indicating good gas separation better understand why natural downhole gas-separation perform-
and improved production. Wells plotted farthest to the right corre- ance was much less effective than expected.
spond to the highest percentage pump liquid fillage and the most- With the initial concentration on wells in Table 1 exhibiting low
efficient gas separators. run times and low pump fillage, long-term dynamometer measure-
ments were acquired along with a series of fluid-level surveys with
the pump operating “on-hand” rather than by pump-off controller.
What If Natural Downhole Gas Separation Does The dynamometer pump card and fluid-level-measurement compar-
Not Work? ison in Fig. 5 shows dynamometer results from Well B listed in Ta-
As previously discussed, the best gas-separation performance is ble 1. The pump intake is set 135 ft below the fluid-entry zone.
obtained by locating the pump intake below the gas-entry point Setting the pump intake below the perforations or in the rathole is
because the largest separation area is achieved with the casing considered the most-effective form of downhole gas separation.
annulus. The highest pump volumetric efficiency (100% pump The following observations were made from the measured
liquid fillage) would be expected on wells that use a natural gas data acquired from Well B:
separator. However, of the 17 wells shown in Fig. 4, which were • The fluid-level analysis showed a high fluid level because of
completed with the pump intake below the fluid-entry zone, nine a gaseous liquid column extending 3,193 ft above the pump.
have between 60 and 90% pump liquid fillage and maintain fluid • 28% liquid concentration existed in the casing annulus at the
levels several thousand feet above the pump—further indication pump intake, with a 59-Mscf/D gas-flow-rate measurement
of low effective pump displacement and questionable gas from the casing-pressure buildup during the fluid-level survey.
separation. • The high pump fillage (near-full pump at almost 100%
Further testing and evaluations were performed on 10 addi- pump liquid fillage) observed when the pumping unit was
tional wells in the Wolfberry formation (Table 1) that exhibited started up lasts only 10 strokes.
the same performance and had wellbore characteristics similar to • Pump liquid fillage dropped immediately to approximately
those tested in the downhole gas-separator-effectiveness study 25%, at which point it stabilized for the remainder of the dy-
described in the preceding section. The testing was performed to namometer survey.

Well Inside Run Time Pump Fillage Tubing Anchor Above


Diameter (hr/D) Produced (B/D) (%) Perforations
A 10 22 28–100 cycles Y
B 3 21 15 N
C 4 30 30 N
D 20 67 12–75 cycles Y
E 11 71 22–100 cycles Y
F 24 190 100 cycles N
G 24 81 100 cycles N
H 10–24 82 37 N
I 4–6 26 30 Y
J 24 165 100 constant N

Table 1—Summary of production performance and the wellbore characteristics of wells with
natural gas separation.

May 2015 SPE Production & Operations 159

ID: jaganm Time: 16:39 I Path: S:/3B2/PO##/Vol00000/150002/APPFile/SA-PO##150002


PO1918491 DOI: 10.2118/1918491-PA Date: 8-May-15 Stage: Page: 160 Total Pages: 8

25.00 25.00
7.5

5.0
21.88
Wrf + FoMax Wrf + FoMax
2.5 20.00
Load (Kbs)

0 18.75

–2.5
Wrf
15.00 15.63 Wrf
–5.0

–7.5 12.50
0 100.00 200.00 300.00 400.00
Time (seconds)
10.00 Stroke 1 Stroke 9
Full Partial fillage
9.38

25.0 FoMax
5.00 6.25 F Max
22.5 o
Fo From Fluid Level
20.0 3.13
17.5 0
110.2
15.0
0
99.1
12.5
–5.00 –3.13
0 120.0 0 120.0
10.0
0

Fig. 5—Well B dynamometer measurement—high fluid level and natural gas separation.

With the high fluid level and with the pump set below the perfora- The tubing anchor and the gaseous liquid column combine to
tions, it is most interesting that the pump is not filled with liquid. create a choke mechanism that regulates gas flowing up the
The stabilized 25% pump fillage of the dynamometer card is char- casing annulus. Gas accumulates beneath the tubing anchor,
acteristic of a well that is pumped off (McCoy et al. 2010), sug- where sufficient gas flowing up the annulus is regulated to
gesting there is not sufficient liquid in the annulus to fill the pump maintain the gaseous liquid column above the anchor, plus
barrel. Sufficient liquid to fill the pump should be available, as free gas fills the annular volume below the anchor to the
shown by the high gaseous liquid column remaining constant pump. The pressure at the tubing anchor controls the gas
above the pump. Fluid-level and dynamometer surveys performed column contained in the annular volume between the anchor
in other wells yielded similar conclusions. Repetition of cyclical and the pump. High pressure in the free-gas column between
pump-liquid-fillage behavior (full-pump liquid fillage decreasing the tubing anchor and the pump inhibits the inflow of fluids
to partial liquid fillage then increasing again) observed in some of from the formation, resulting in a “pumped off” diagnostic
the wells occurred even though no cycle change in the liquid level pump card shape.
occurred during the time of the dynamometer survey. Fig. 6 illustrates the annular fluid distribution above and below
The following is a summary of initial tests and observations of the tubing anchor, and the scenario is further described in the fol-
wells in Table 1: lowing paragraphs.
• Wells A, D, and E: Long-term dynamometer tests observed Fluid enters the wellbore from the formation. The pump is set
cyclical full-to-partial liquid pump fillage, with constant below the fluid-entry zone for natural separation of liquid and gas.
high fluid level. The separated gas rises past the tubing anchor in the annulus
• Wells B, C, H, and I: Long-term dynamometer tests to the surface. A vapor condensate is created from the cooling
observed a full pump for a few initial strokes at pumping- hydrocarbon gases as they rise toward the surface. Fluid entering
unit startup, and then dropping and stabilizing at low partial the wellbore from perforations above the tubing anchor (plus
liquid fillage, with constant high fluid level. these condensed liquids) cannot fall past the tubing anchor to the
• Wells F, G, and J: Testing proved to be consistent with pump intake and will accumulate on top of the tubing anchor.
100% constant pump fillage. The accumulated liquid sitting on top of the tubing anchor
Another reason for low volumetric efficiency (or partial liquid increases the fluid gradient of the gaseous liquid column (Rowlan
fillage) is incomplete pump fillage because of some type of flow et al. 2003) above the tubing anchor “plate.” As the fluid gradient
restriction (McCoy et al. 2010). In a restricted-flow scenario, an- increases, the separated gas from the formation fluids begins to
nular fluids are obstructed from entering through the pump intake accumulate below the tubing anchor until the annular space
at a sufficient rate to fill the pump barrel with liquid during the below the tubing anchor and extending to the pump is almost
plunger upstroke. Possible sources of annular obstructions include completely filled with gas. Thus, the gradient below the tubing
scale, paraffin, sand, rust, or even obstructions caused by mechan- anchor is essentially equal to the gradient of a gas column.
ical configurations creating a “choked pump.” Any of these possi- Regulated flow of free gas, which has accumulated below the tub-
ble obstructions would restrict fluid from flowing from the ing anchor, now maintains the gaseous liquid column above the
wellbore into the pump. A comparison of the wellbore schematics tubing anchor.
while searching for similarities in the downhole designs of the Liquid produced through the perforations slides down the cas-
wells showed a tubing anchor located above the fluid-entry zone ing wall on the low side of the wellbore and falls to the pump set
in Wells A, D, E, and I. The tubing anchor common in these wells below the fluid-entry zone. The pump removes the accumulated
provided a small 2.9-in.2 flow area as compared with the large fluids until the pump-displacement rate exceeds the liquid inflow
14.4-in.2 annular flow area used as the natural gas separator in the from the formation and partial liquid fillage occurs. Even though
wellbore. the well appears to have “pumped off,” the gaseous liquid column
Further analysis of the data, while considering the common above the tubing anchor remains constant. This fluid-distribution
factor of a tubing anchor above the pump, resulted in the follow- behavior correlates to the fluid-level survey and dynamometer
ing possible scenario: measurements observed on the field-tested wells. Thus, a tubing

160 May 2015 SPE Production & Operations

ID: jaganm Time: 16:39 I Path: S:/3B2/PO##/Vol00000/150002/APPFile/SA-PO##150002


PO1918491 DOI: 10.2118/1918491-PA Date: 8-May-15 Stage: Page: 161 Total Pages: 8

7,000 350
Depth to liquid (ft)
Casing pressure (psig)
7,500 300

Casing pressure (psig)


8,000 250

Depth to liquid (ft)


Casing 14:19 6-9-2013
8,500 200
TAC at 9140
Tubing 9,000 150
2:21 AM
9,500 100
Detected liquid
level 2:36 AM
10,000 50
Pump at 10181
Gaseous liquid column 10,500 0
with 59 Mcf/D and 0 100 200 300 400 500 600 700 800
28% liquid. Time (minutes)

Gas flow is restricted Fig. 7—Example 1: Summary of the liquid-level-depression test


Tubing from below the TAC for Well B.
anchor

Mostly gas 2. Shut down the well for 10 minutes. Upon restarting, if the
entering above, pump is full for only a few strokes before it changes to
with liquid from incomplete pump fillage while the annulus maintains a liq-
below falling uid level above the tubing anchor, then the liquid-level-
Liquid down the low side depression test should be performed on the well.
of the casing 3. Close the casing valve to build casing pressure and depress
the liquid level. Continue to pump the well.
4. Obtain fluid-level measurements every 15 minutes as the
casinghead pressure builds and the liquid level is depressed.
Fig. 6—The tubing anchor and gaseous liquid column combine 5. Acquire four to five additional shots after the liquid level is
to create a choke mechanism. depressed past the tubing anchor to continue monitoring the
liquid level.
6. Run additional shots until the liquid level is stabilized.
anchor located above the pump provides a means for gas to accu-
Wells B, E, and H from Table 1 were selected for monitoring
mulate between the tubing anchor and the pump caused by back-
by use of the liquid-level-depression test. Automatic fluid-level
pressure from the gaseous liquid column above the tubing anchor.
depths and pressures were obtained in 15-minute intervals with an
The choking mechanism of the tubing anchor and the gaseous liq-
automated fluid-level instrument (Rowlan et al. 2008) once the
uid column inhibits the gas flow up the casing, which results in
casinghead valve to the flowline was closed. The pumping unit
increased backpressure against the formation and restricted flow
continued operating during the entire test.
into the wellbore.
Fig. 7 shows the 800-minute resulting plot from the liquid-
A second condition exists when the tubing anchor and the
level-depression test performed on Well B. At 2:21 AM, the liq-
pump are set above the perforations. The problem occurs when
uid level is at the tubing anchor located at 9,140 ft. Fifteen
high-pressure gas below the tubing anchor preferentially fills the
minutes later at 2:36 AM, the liquid level is at the pump intake
pump with gas, and the restricted fluid flows in at this high
depth of 10,181 ft. The liquid-level-depression test verifies the ex-
pressure.
istence of a gas column with very little liquid below the tubing
anchor.
Liquid-Level-Depression Tests Confirm Fig. 8 shows the resulting plot of the casinghead pressure and
Choke-Mechanism Hypothesis the depth to the liquid level vs. time, summarizing the liquid-level
Proof of the existence of the accumulated free-gas column below depression performed on Well H. At time 6:33:40 PM, the liquid
the tubing anchor was needed to confirm the problem created by level is at 7,659 ft and approaches the tubing anchor located at
the tubing-anchor location above the pump. Liquid-level-depres- 7,908 ft. Thirty minutes later, the liquid level has depressed
sion tests are used widely to determine the annular fluid gradient approximately 250 ft and is at the tubing anchor. Ten minutes af-
and producing bottomhole pressures (PBHPs) in pumping wells ter the liquid level depressed past the tubing anchor, the liquid
(Walker 1939). Fluid-level measurements as a function of casing- level has dropped almost 2,700 ft to the pump-intake depth of
head pressure are obtained while the well is pumping at a constant 10,599 ft, where it stabilizes for the remainder of the test. This
rate. Increasing the casinghead pressure depresses the fluid level indicates that the area of the wellbore below the tubing anchor
proportionately to the casing-pressure increase. The annular fluid was filled with gas and very little liquid.
gradient can then be estimated by equating the change in fluid- Similar behavior was observed in the liquid-level-depression
level depth to the change in casinghead pressure. test performed on Well E.
To confirm the existence of the accumulated gas column
between the tubing anchor and the pump, the absence of liquid
needed to be verified. The liquid-level-depression test would con- Tubing Anchors are Unexpected Problems
firm either a continuous gaseous liquid column extending all the The combination of the tubing anchor and the gaseous liquid col-
way to the pump intake, or a sharp drop caused by a liquid-free umn causing gas to accumulate below the tubing anchor all the
gas column because the fluid level is pushed below the depth of way down to the pump is an unexpected problem that the industry
the tubing anchor. does not realize may exist in a significant number of wells. Rather
The procedure for the liquid-level-depression tests was as than an effective separation of gas and liquid produced from the
follows: formation, the high pressure created from the accumulated gas
1. Perform fluid-level and dynamometer measurements to ver- below the tubing anchor restricts liquid inflow from the formation
ify that the liquid level is above the tubing anchor and to and forces gas directly into the pump. As a result, wells exhibit
confirm that incomplete pump fillage is occurring. incomplete pump fillage and a restriction of inflow from the

May 2015 SPE Production & Operations 161

ID: jaganm Time: 16:39 I Path: S:/3B2/PO##/Vol00000/150002/APPFile/SA-PO##150002


PO1918491 DOI: 10.2118/1918491-PA Date: 8-May-15 Stage: Page: 162 Total Pages: 8

65 7,000
Liquid level = 7,659 ft Liquid level above
Tubing anchor = 7,908 ft Tubing anchor = 7,908 ft
7/25/13 6:33:40 PM 7/25/13 7:01:24 PM

Surface Casing Pressure (psig)


60 8,000

Depth to Liquid Level (ft)


55 9,000

50 10,000
Liquid level below tubing anchor at
pump 10,599 ft 7/25/13 7:10:34 PM

45 11,000
18:14:24 18:43:12 19:12:00 19:40:48 20:09:36 20:38:24
Elapsed Time (hh:mm:ss)

Fig. 8—Example 2: Casing pressure and liquid-level depth as functions of time for Well H.

formation caused by backpressure created by the accumulated gas causing a reduction in well flow (on the basis of the analysis of
column and gaseous liquid column. the inflow performance of the well), the following alternative sol-
The first challenge is identifying the problem: utions may be considered:
• Natural gas separator or properly sized gas separator is 1. Locate both the tubing anchor and the pump intake below
located below the pump, but there is incomplete pump fil- the bottommost perforations or producing formation. An
lage and a high fluid level is maintained above the tubing on/off tool may be used to secure the tubing below the
anchor. fluid-entry zone.
• Pump liquid fillage increases to near full when restarting the 2. When the pump intake cannot be set below the formation,
pump after an extended shutdown period. install a properly sized downhole gas separator (Bohorquez
• After restarting the pump, the liquid fillage decreases and et al. 2007), with the separator intake located above the tub-
remains constant or oscillates between partial and full. ing anchor. When the downhole gas separator is located
When these symptoms have been observed, it is recommended above the tubing anchor, then the separator tensile and
that a liquid-level-depression test be undertaken, as described pre- shear strength must be sufficient to allow setting the tubing
viously in this paper, until the liquid level falls below the tubing- anchor by tensioning or rotating the tubing string.
anchor depth. This test will validate the presence of the flow 3. Use a packer-type separator that includes a tubing anchor
restriction caused by the tubing anchor. so that the tubing anchor cannot be a restrictor to gas flow.
It should be noted that although the distance between the tub- 4. Do not increase casing pressure with the intent to displace
ing anchor and the pump intake was several thousand feet in the the fluid level below the tubing anchor. High casing pres-
examples described in this paper, this is not a requirement for the sure contributes to the problem of low productivity because
tubing anchor to create additional backpressure. A similar prob- of its impact on the PBHP.
lem may exist whenever the pump is set above the formation and 5. The performance of a particular separator design that is
is outfitted with a downhole gas separator that is located only a below a tubing anchor should be compared with a predic-
few joints below the tubing anchor. This is the recommended con- tive simulation to determine if it is operating normally. If
figuration used by operators when installing a downhole gas sepa- the separator is not performing as predicted and there is a
rator. The presence of the flow restriction caused by the tubing tubing anchor installed in the wellbore, a liquid-level-
anchor could create a high concentration of gas at the separator depression test will confirm whether the placement of the
intake and reduce pump liquid fillage. Gas accumulation below tubing anchor has contributed to restricted inflow from the
the tubing anchor indicates that it may be more efficient to install formation.
the tubing anchor below the downhole gas separator. Each of these alternatives has to be evaluated with regard to the
The second challenge is determining whether the fluid and specific well conditions of pressure and flow rate, the production
pressure distribution resulting from the presence of the tubing of solids, corrosion and scaling problems, and overall cost.
anchor and a high gaseous liquid column is causing a reduction in
well production. The answer is dependent on the inflow-perform-
ance characteristics of the well. The liquid-level-depression test at Conclusion
the point when the fluid level drops below the tubing anchor gives The combination of the tubing anchor and the gaseous liquid col-
a very good estimate of the existing producing bottomhole pres- umn causing gas to accumulate below the tubing anchor all the
sure (PBHP). In the example shown in Fig. 7, when the casing- way down to the pump is an unexpected problem that most opera-
head pressure reaches a value of 275 psi and the liquid level is at tors may not be aware of. The tubing anchor and the gaseous liq-
the pump intake, the PBHP was estimated at 325 psi. If the 325- uid column combine to create a choke mechanism that regulates
psi PBHP is high in comparison with the static bottomhole pres- gas flowing up the casing annulus. Gas accumulates beneath the
sure, then the well is not being drawn down and high-pressure gas tubing anchor, where sufficient gas flowing up the annulus main-
is restricting inflow. tains the gaseous liquid column above the tubing anchor and fills
the annular volume below the anchor to the pump (Rowlan et al.
2003). High pressure created from the accumulated gas below the
Recommendations tubing anchor reduces liquid flow from the formation and forces
Whenever it has been determined that the present location of the gas directly into the pump. As a result, wells exhibit incomplete
tubing anchor relative to the pump intake and the formation is pump fillage and a restriction of inflow from the formation,

162 May 2015 SPE Production & Operations

ID: jaganm Time: 16:39 I Path: S:/3B2/PO##/Vol00000/150002/APPFile/SA-PO##150002


PO1918491 DOI: 10.2118/1918491-PA Date: 8-May-15 Stage: Page: 163 Total Pages: 8

resulting from the backpressure created by the accumulated gas Walker, C.P. 1939. Method of Determining Fluid Density, Fluid Pressure
column and gaseous liquid column. A liquid-level-depression test and the Production Capacity of Oil Wells. US Patent No. 2,161,733.
confirms the existence of an accumulated gas column between the
tubing anchor and the pump. Liquid-level-depression tests should James N. McCoy is the president of Echometer Company,
be run in all wells that suffer from partial pump fillage and exhibit and has been active in optimizing production and operations
a high annular gaseous liquid column extending above a tubing in artificial-lift wells. His research includes measurements of well
anchor installed above the pump. Gas accumulation below the parameters and processing the data to improve the opera-
tubing anchor indicates that it may be more efficient to install the tor’s knowledge of a well’s performance. McCoy has auth-
tubing anchor below the downhole gas separator. ored or coauthored more than 50 technical papers and holds
more than 15 patents. He holds an MS degree in petroleum
and natural-gas engineering from Pennsylvania State Univer-
sity. McCoy is an active member of SPE. He is the recipient of
References the 1994 Southwestern Petroleum Short Course Association
Bohorquez, R.R., Lisigurski, O., Guzman, M. et al. 2007. Laboratory Test- Slonneger Award.
ing of Downhole Gas Separators. Presented at the SPE Annual Techni-
O.L. Rowlan works as an engineer for Echometer Company in
cal Conference and Exhibition, Anaheim, California, 11–14
Wichita Falls, Texas, where his primary interest is to advance
November. SPE-109532-MS. http://dx.doi.org/10.2118/109532-MS. the technology of the Echometer portable well analyzer to
Lisigurski, O., McCoy, J., Patterson, J. et al. 2005. The Effect of Geometry analyze and optimize the operation of all artificial-lift produc-
on the Efficiency of Downhole Gravity Driven Separators. Presented at tion systems. He provides training and consultation in perform-
the V International Seminar on Exploration and Production of Oil and ing well analysis to increase oil and gas production and
Gas (V INGEPET 2005), Lima, Peru, 8–11 November. EXPL-3-OL-39. reduce operating costs. Rowlan presents numerous seminars
McCoy, J.N., Becker, D.J., Rowlan, O.L. et al. 2002. Minimizing Energy and talks on the efficient operation, optimization, and trouble-
Cost by Maintaining High Volumetric Pump Efficiency. Presented at shooting of oil and gas wells. He has authored numerous
the SPE Eastern Regional Meeting, Lexington, Kentucky, 23–26 Octo- papers for the Southwestern Petroleum Short Course Associa-
tion, the Canadian Petroleum Society, and the SPE. Rowlan
ber. SPE-78709-MS. http://dx.doi.org/10.2118/78709-MS.
holds BS and MS degrees in civil engineering from Oklahoma
McCoy, J.N. and Podio, A.L. 1999. An Improved Downhole Gas Separa- State University in Stillwater, Oklahoma. He was the recipient
tor. Presented at the Annual Technical Meeting, Calgary, 14–18 June. of the 2000 J.C. Slonneger Award, bestowed by the South-
PETSOC-99-66. http://dx.doi.org/10.2118/99-66. western Petroleum Short Course Association; the 2010 SPE Dis-
McCoy, J.N., Podio, A.L., Huddleston, K.L. 1987. Analyzing Well Per- tinguished Production Operations Award; and the 2011
formance XV. Presented at the Artificial Lift Symposium sponsored Crawford Service Award from the Southwestern Petroleum
by the Gulf Coast Section of SPE, Houston, 22–24 April. Short Course Association.
McCoy, J.N., Rowlan, O.L., and Podio, A.L. 2010. The Three Causes of Carrie Anne Taylor is an engineer for Echometer Company,
Incomplete Pump Fillage and How to Diagnose Them Correctly from where she began her career as an intern in 2005. Taylor pro-
Dynamometer and Fluid Level Surveys. Proc., Southwest Petroleum vides training for well analysis, production optimization, and
Short Course, Lubbock, Texas, 19–22 April. troubleshooting with Echometer technology. She is the author
McCoy, J.N., Podio, A.L., Rowlan, O.L. et al. 2013. Evaluation and Per- of an SPE paper on troubleshooting gas lift wells with acoustic
formance of Packer-Type Downhole Gas Separators. Presented at the techniques. Taylor holds a BS degree in mechanical engineer-
SPE Production and Operations Symposium, Oklahoma City, Okla- ing from Midwestern State University in Wichita Falls, Texas.
homa, 23–26 March. SPE-164510-MS. http://dx.doi.org/10.2118/ A.L. Podio is a petroleum-engineering consultant specializing
164510-MS. in artificial lift. Formerly, he was a professor in the Petroleum
Rowlan, O.L., McCoy, J.N., Becker, D. et al. 2003. Advanced Techniques and Geosystems Engineering Department at the University of
for Acoustic Liquid-Level Determination. Presented at the SPE Pro- Texas at Austin where he taught and directed research in the
duction and Operations Symposium, Oklahoma City, Oklahoma, areas of drilling and production. Podio holds BS, MS, and PhD
degrees in petroleum engineering from the University of Texas
23–26 March. SPE-80889-MS. http://dx.doi.org/10.2118/80889-MS.
at Austin. He has been an invited distinguished speaker and a
Rowlan, O.L., Becker, D., McCoy, J.N. et al. 2008. Pressure Transient technical editor for SPE, has published numerous articles in
Testing Using Surface Based Measurements. Presented at the Cana- international journals, holds seven US patents, and is coauthor
dian International Petroleum Conference, Calgary, 17–19 June. PET- of the The Beamlift Handbook, published by The Petroleum
SOC-2008-090. http://dx.doi.org/10.2118/2008-090. Extension Service at the University of Texas at Austin.

May 2015 SPE Production & Operations 163

ID: jaganm Time: 16:39 I Path: S:/3B2/PO##/Vol00000/150002/APPFile/SA-PO##150002

You might also like