You are on page 1of 4

F E AT U R E

Power Factor Correction and Power Quality Issues


..............................................................................................................................................................................................................................

By: Engr. Mohamed Fuad bin Faisal, M.I.E.M., P.Eng

1. INTRODUCTION average power factors as low as 0.7 or 0.6 4. WHY IS POWER FACTOR
Motors and other inductive equipment in or even less. These power factor values IMPORTANT?
a plant require two kinds of electric are accessible in the monthly electricity Power factors in industrial plants are
power. One type is working power, bills. The typical electricity bill for a usually lagging due to the inductive nature
measured by the term kilowatt (kW). customer with low power factor of induction motors, transformers, welding
This is what actually powers the comprises of: equipment, ballasts, lighting, induction
equipment and performs useful work. heating furnaces, etc. This lagging power
Secondly, inductive equipment needs Electricity bill (RM) factor has two costly disadvantages for the
magnetising power to produce the flux = Energy Consumption (kWh) power user. Firstly, it increases the cost
necessary for the operation of inductive + Power Factor Penalty (1) incurred by the power company because
devices. The unit of measurement of more current must be transmitted than is
magnetising or reactive power is term as In essence, power factor is an actually used to perform useful work. This
kilovar (kVAR). The working power indication of the cost effectiveness of the increased cost is passed on to the industrial
(kW) and reactive power (kVAR) customer’s electricity purchase. If the customer by means of power factor
together make up apparent power, which customer has a low power factor, he may adjustments to the rate schedules.
is measured in kilovolt-amperes (kVA). be paying more than necessary for his Secondly, it reduces the load handling
electricity consumption. capability of the industrial plants
electrical distribution system which
2. WHAT IS POWER FACTOR? means that the industrial power user
Power factor is the ratio of the active (or must spend more on distribution lines
useable) power measured in kilowatts and transformers to get a given amount
(kW), to the total (active and reactive) of useful power through his plant.
power measured in kilovolt amperes All current will cause losses in the
Resistive Inductive Motors Capacitive Power (kVA), which includes the reactive power supply and distribution system. A load
Incandescent Transformers Factor Correction
lighting Heating Chokes Filtering
being used (kVAR). Power factor is with a power factor of 1.0 results in the
Element commonly referred to in percent, with most efficient loading of the supply and a
100% being a perfect power factor, also load with a power factor of 0.5 will result in
Figure 1: Types of loads
called unity. At unity power factor, the much higher losses in the supply system.
Power utility companies will provide kVA = kW, therefore the utility company
a limited amount of reactive power does not supply any reactive power. See 5. POWER FACTOR
(kVAR) at no cost, however, customers Figure 2. CORRECTION OVERVIEW
with high reactive power loads are Industrial customers and commercial
charged for the additional power. Power 3. WHAT CAUSES POWER customers (except domestic and street
factor penalties (or power factor FACTOR TO BE LOW? lighting tariffs) need to implement power
surcharges) will be inflicted to the A poor power factor can be the result of factor correction to reduce electricity
customers if their average power factors either a significant phase difference bills, transformer loading, reduce losses
are less than 0.85 lagging. between the voltage and current at the and to improve voltage regulation.
load terminals, or it can be due to a high Power factor correction is achieved
harmonic content or distorted or by the addition of capacitors in parallel
discontinuous current waveform.
Poor load current phase angle is
generally the result of an inductive load
such as an induction motor, power
transformer, lighting ballasts, welding
equipment or induction furnace. A
distorted current waveform can also be
Figure 2: A Power Triangle
the result of a rectifier, variable speed
There are many commercial and drive, switched mode power supply,
industrial customers in Malaysia having discharge lighting or other electronic load. Figure 3: The concept of power factor correction

42 JURUTERA, May 2007


F E AT U R E

with the connected motor circuits and 6. INDUSTRIES WITH LOW (kVARh) consumption. The kVAR and
can be applied at the starter, or applied at POWER FACTORS BENEFIT kWh values are then used to calculate the
the switchboard or distribution panel. MORE FROM POWER FACTOR average power factor for the billing
The resulting capacitive current is CORRECTION period. The following equation is used to
leading current and is used to cancel the Low power factor results when motors calculate average power factor for
lagging inductive current flowing from are operated at less than full load. This customers:
the supply. often occurs in cycle processes such as
those using circular saws, ball mills, Average Power Factor = PFavg =
conveyors, compressors, grinders, punch = kWh/√(kWh2 + kVARh2) = cos (2)
presses, etc – where motors are sized for
the heavier load. Examples of situations If assumed an energy meter has
where low power factors (from 0.3 to 0.5) recorded kWh values of 123,345.24 and
occur include a surface grinder kVarh values of 87,453.23, the average
performing a light cut, unloaded air power factor is 0.82. Referring this value
compressor and a circular saw spinning to the Tariff, the customer will be
without cutting. imposed a power factor penalty, as the
Figure 4: Capacitors at the distribution panel (1) value is less than the allowable power
The following industries typically also factor value of 0.85.
On the spot delivery of magnetising exhibit low power factors (PF): The size of capacitor needed to
current provided by capacitors means improve the power factor can be
that kilovars do not have to be sent all the Industry Uncorrected PF determined using this equation:
way from the utility system to the Saw Mills 0.45 to 0.6
customer’s. This relieves both the Plastic (esp Extruder) 0.55 to 0.7 KVAR = kWx(Tangent 1 – Tangent 2 )
customer and the utility of the cost of Machine tools 0.6 to 0.7 (3)
carrying this extra kilovar load. Plating, textile 0.65 to 0.75
Hospitals, granaries 0.7 to 0.8 1 – The original power factor angle

1 = cosine-1 (power Factor Value)

2 - The proposed power factor angle

kW – Maximum Demand (Loads)

8. HARMONIC DISTORTION
ISSUES
System harmonics should be considered
when applying power factor correction
capacitors. Although capacitors do not
Figure 5: A low voltage capacitor bank at the Figure 6: Benefits obtained from Power Factor
Correction
generate harmonics, under certain
distribution panel (2)
conditions they can amplify existing
It is important to note that a poor Including power capacitors in one’s harmonics. Harmonics are generated
power factor due to an inductive load can new construction and expansion plans when non-linear loads are applied to
be improved by the addition of power can reduce the size of transformers, power systems. These non-linear loads
factor correction, but a poor power factor busses, switches etc, and bring one’s include: adjustable speed drives,
due to a distorted current waveform project in at a lower cost. programmable controllers, induction
requires a change in equipment design or Note: Raising the power factor from
expensive harmonic filters to gain an 0.7 to 0.9, releases 0.32 kVA per kW. On a
appreciable improvement. 400 kW load, 128 kVA are released.
Many inverters are quoted as having
a power factor of better than 0.95 when in 7. CALCULATION OF KVAR
reality, the true power factor is between REQUIREMENT TO REDUCE
0.5 and 0.75. The figure of 0.95 is based ELECTRIC BILLS
on the cosine of the angle between the An average power factor is calculated for
voltage and current but does not take each month using data recorded by an
into account that the current waveform is energy meter installed at the customer ’s
discontinuous and therefore contributes premises. The energy meter records the
to increased losses on the supply. kW-hours (kWh) and kVar-hours Figure 7: Typical Harmonic waveforms

JURUTERA, May 2007 43


F E AT U R E

furnaces, computers, and uninterruptible producing load, the harmonic distortion to the capacitors by the harmonic
power supplies. could become severe. The following currents, it is becoming common today to
Harmonics on the supply cause a equation can be used to determine the install detuning reactors in series with
higher current to flow in the capacitors. f requency at which the resonance the power factor correction capacitors.
This is because the impedance of the will occur. These reactors are designed to make the
capacitors goes down as the frequency correction circuit inductive to the higher
goes up. This increase in current flow fR = Resonant frequency frequency harmonics. Typically, a reactor
through the capacitor will result in = √(kVAsc/kVAR) x 50 would be designed to create a resonant
additional heating of the capacitor and circuit with the capacitors above the third
reduce it's life. kVAsc=Short circuit kVA
Table 2: Common reactor sizes for detuning the
at the capacitor location circuit
Tuned index at Detuned Reactor value
kVAR=kVAR of capacitor bank Harmonic frequency in %
2.77 138.5 13.03%
10. THE HARMONIC SOLUTION 3.78 189 7.00%
Harmonic values of 5, 7, 9, and 11 should 4.06 203 6.07%
be avoided as they correspond to the 4.4 220 5.17%
characteristic harmonics of non-linear 4.7 235 4.53%
loads. The harmonic value of 3 should 4.8 240 4.34%
also be avoided as it coincides with 4.2 210 5.67%
harmonics produced during transformer
Figure 8: Resonance condition
energisation and/or operation of the harmonic, but sometimes it is below.
transformer above rated voltage. (Never tuned to a harmonic frequency!)
Harmonic voltages can be reduced by SWITCHING SURGE ANALYSIS
9. RESONANCE CONCERNS the use of a harmonic compensator, Shunt capacitor bank switching
Capacitive power factor correction which is essentially a large inverter that transients are often a concern for utility
connected to a supply causes resonance cancels out the harmonics. This is and industrial engineers that are
between the supply and the capacitors. If however an expensive option. planning to apply capacitors at the
the fault current of the supply is very Passive harmonic filters comprising distribution voltage level. Their primary
high, the effect of the resonance will be of resistors, inductors and capacitors can area of concern is typically with how the
minimal, however in a rural installation also be used to reduce harmonic capacitor switching transients will affect
where the supply is very inductive and power quality for nearby industrial and
can be high impedance, the resonance commercial loads.
can be very severe resulting in major Switching surges occur during most
damage to plant and equipment. switching operations. They occur during
Voltage surges and transients of the transition when the system is
several times the supply voltage are not changing from one steady state operating
uncommon in rural areas with weak condition to another (this occurs during
supplies, especially when the load on the energisation and de-energisation of all
supply is low. equipment). The magnitude of the
As with any resonant system, a switching transient depends upon
transient or sudden change in current switching time and the resistive,
will result in the resonant circuit ringing, Figure 9: Capacitors with filter reactors
generating a high voltage. The
magnitude of the voltage is dependant Table 1: Common reactor sizes for tuning the
circuit
on the 'Q' of the circuit, which in turn is a
function of the circuit loading. One of the Tuned index at Tuned Reactor value
Harmonic frequency in %
problems with supply resonance is that
3 150 11.11%
the 'reaction' is often well remove from
5 250 4.00%
the 'stimulus' unlike a pure voltage drop
7 350 2.04%
problem due to an overloaded supply.
9 450 1.23%
This makes fault finding very difficult Figure 10: Capacitors switching surges
11 550 0.83%
and often damaging surges and
13 650 0.59%
transients on the supply are treated as capacitive, and inductive characteristics
'just one of those things'. voltages. This is a general and an of the system.
If this resonance occurs at a inexpensive solution. Capacitor switching and miss-
characteristic frequency of a harmonic In order to reduce the damage caused operation of switches due to re-strike and

44 JURUTERA, May 2007


F E AT U R E

pre-strike generally cause the more severe switching surges.


Some of the commonly used techniques to mitigate the problem
are to use:
• synchronous closing
• inrush reactor and
• detuning reactor

11. CAUTION FOR A SOFT STARTER SCHEME


Static Power Factor correction capacitors must not be connected
to the output of a solid-state soft starter. When a solid-state soft
starter is used, the capacitors must be controlled by a separate
contactor, and switched in when the soft starter output voltage
has reached line voltage. Many soft starters provide a “top of
ramp” or “bypass contactor control” which can be used to

Figure 11: A Soft Starter

Figure 12: Typical connection for a soft-starter scheme

control the power factor correction capacitors.


The connection of capacitors close to the input of the soft
starter can also result in damage to the soft starter if an isolation
contactor is not used. The capacitors tend to cause transients to
be amplified, resulting in higher voltage impulses applied to
the SCRs of the Soft Starter, and the energy behind the impulses
is much greater due to the energy storage of the capacitors.
Switching capacitors, Automatic bank correction etc, will
cause voltage transients and these transients can damage the
SCRs of Soft Starters if they are in the Off state without an
input contactor. The energy is proportional to the amount of
capacitance being switched. It is better to switch lots of

JURUTERA, May 2007 45

You might also like