You are on page 1of 243

l i nda b | c ei l i ng di ff u ser s

Ceiling diffusers

About Lindab 1

Comfort and Design 2

Product overview / symbols 3

Theory 4

Ceiling diffusers 5

Ceiling diffusers - visible 6

Plenum boxes 7

Wall diffusers 8

Nozzles 9

Ventiduct 10

Grilles 11

Displacement diffusers 12

Pascal and VAV 13

Constant- / variable 14
flow dampers

Air valves 15

Fresh air valves/overflow units 16

Cleanroom diffusers 17

Contents 18

© 11.2013 Lindab Ventilation A/S. All forms of copying without written permission are forbidden. is Lindab AB’s registered trademark. 49
Lindab’s products, systems and product group and product designations are protected by intellectual property rights (IPR).
lin d a b | c e i l i n g d i ff u s e r s

Ceiling diffusers
Formo Lineo
1 Aesthetic design Clean lines
Product Page Product Page

2 Introduction 51 Introduction 261


Overview of combinations 53 MTL 265

3 PKA 57 STB 272


PCA 69 STU 272
LKA 81
4 LCA 93
CRL 105
Extraction above ceiling
5
Product Page

6
Integra PCY 273
Integrated design PKY 273
7 Product Page

Introduction 117
8 Overview of combinations 121
Ceiling tile adaption 274
PC6 125

9 PC7 135
RC14 141
RC15 151
10 NC19 161
RCG 169
11 LCC 176
LKP/LCP 177

12
Versio
13 Countless opportunities
Product Page

14 Introduction 187
Overview of combinations 188
PS1 195
15
PS8 205
RS14 213
16 RS15 227
RS16 239

17 NS19 247
GS23 255

18

50 Right to alterations reserved


lindab | ceiling diffusers

Lindab Formo a series of architectuallly designed diffusers

10

11
PCA, Terminal 3 - Copenhagen Airport

Lindab Formo Functionality


12
Mixed ventilation is the most used principle of ventilation Formo mixed ventilation diffusers are known by the dif-
there is. Mixed ventilation is typically used in offices and fusers being suspended from the ceiling with a single
similar rooms, where you wish to maintain low velocities slot around the diffusers. The diffusers are offered in 13
in the occupied zone as well as low temperature gradients circular, or square designs with perforated or plain front
from floor to ceiling. The best results with mixed ventila- plates. The diffusers have a very high capacity and are
tion is obtained by spreading the air over the entire ceiling available with several different types of accessories. The 14
area, so that the velocity can subside as much as pos- circular diffusers are normally cut directly into the ceiling
sible before reaching the occupied zone. There is a large when mounted, but can by using tileplates be adapted
selection of ceiling diffusers in different designs and with for the most common 600x600 mm ceiling systems. 15
different functions, which can be the used depending on On the next few pages, is
the room’s dimensions. illustrated a combination
overview which will pro- 16
vide for a good insight
to the series.
17

18
PCA, ceiling diffuser

Right to alterations reserved 51


lindab | ceiling diffusers

Lindab Formo a series of architectual designed diffusers

Design Accessories
See Comfort and design Details, see productpages 1
DKZ/DDZ/ LM DAZ DRZ/CAZ MBB

Supp./Exhau.
Ventilations -
DCZ

principle
2

Size
Product
Perforated - square mm El. - motor Bracket Module pl. 1, 2, 3 way Damper MBB box

PKA
125 3
160
200
250
315
400 4
Perforated - circular mm El. - motor Bracket Module pl. 1, 2, 3 way Damper MBB box
100
PCA 125
160
5
200
250

6
315
400

Plain - square mm El. - motor Bracket Module pl. 1, 2, 3 way Damper MBB box

125
LKA 160
200
7
250
315

8
400

Plain - circular mm El. - motor Bracket Module pl. 1, 2, 3 way Damper MBB box

100
LCA 125
160
200
9
250
315
400

Plain - circular mm El. - motor Bracket Module pl. 1, 2, 3 way Damper MBB box
10
100
CRL 125
160
200
11
250
315
400
12
1. Product and tech. data depicted in catalogue.
Electrical motor:
See VAV chapter for further documentation.
2. Combination possible. Tech. data depicted in catalogue. 13
3. Combination possible. Tech. data not in catalogue.
4. If space is empty, combination is not possible.

14

15

16

17
Example of order Diffuser + MBB box

PCA 160 + MBB 125 160 S


18

Right to alterations reserved 53


lin d a b | c e i l i n g d i ff u s e r s

Lindab Formo a series of architectual designed diffusers

Ceiling tile adaption


1 Details, see Chapter ceiling tile adaption
1 3 4 5 6 7

2
Product Size
Ceiling types Danotile T24/T15 Permanent Dampa Clip-In Dampa Clip-In Luxalon SQ Danotile Contur
3 Ecophon T24
Rockfon A24.
ceiling bevelled edge square edge Clip-In Ecophon D
Rockfon D-XL
Perforated - square mm F: 595 mm A x A mm F: 600 mm F: 600 mm F: 600 mm F: 599 mm
125 Standard
4 PKA 160
200
Standard
Standard
250 Standard
F 315 Standard *

5
400 Standard *

Perforated - circular mm F: 595 mm ØD mm F: 600 mm F: 600 mm F: 600 mm F: 599 mm


100 Standard
PCA 125 Standard
6 160
200
Standard
Standard
F 250 Standard
315 Standard
400 Standard
7 Plain - square mm F: 595 mm A x A mm F: 600 mm F: 600 mm F: 600 mm F: 599 mm
125 Standard
LKA 160 Standard
8 200
250
Standard
Standard
F 315 Standard *
400 Standard *

9 Plain - circular mm F: 595 mm ØD mm F: 600 mm F: 600 mm F: 600 mm F: 599 mm


100 Standard
LCA 125 Standard
160 Standard

10 F
200
250
Standard
Standard
315 Standard
400 Standard

11 Plain - circular mm F: 595 mm ØA mm F: 600 mm F: 600 mm F: 600 mm F: 599 mm


100 Standard
CRL 125 Standard
160 Standard

12 F
200
250
Standard
Standard
315 Standard
400 Standard

13
* In other ceiling systems the overpart of the diffuser 1. Product and tech. data depicted in catalogue.
is adapted to the ceiling. No seperate Modulplatte. 2. Combination possible. Tech. data depicted in catalogue.
14 3. Combination possible. Tech. data not in catalogue.
4. If space is empty, combination is not possible.

15

16

17
Example of order Moduleplate

18 LM 1 PCA 160

54 Right to alterations reserved


lindab | ceiling diffusers

Lindab Formo a series of architectual designed diffusers

Ceiling tile adaption


Details, see Chapter ceiling tile adaption 1
8 9 10 11 14

2
Product Size
Ceiling types Ecophon Focus Rockfon E10 24 Rockfon E10 15 Danotile Markant Ecophon
DG Ecophon -E / T24

Ecophon -
E / T15
Focus edge DS
3
Perforated - square mm F: 592mm F: 575mm F: 584 mm F: 575 mm F: 599 mm
125
PKA 160
200
4
250
F 315

5
400

Perforated - circular mm F: 592mm F: 575mm F: 584 mm F: 575 mm F: 599 mm


100
PCA 125
160
200
6
F 250
315
400

Plain - square mm F: 592mm F: 575mm F: 584 mm F: 575 mm F: 599 mm


7
125
LKA 160
200
250
8
F 315
400

Plain - circular mm F: 592mm F: 575mm F: 584 mm F: 575 mm F: 599 mm 9


100
LCA 125
160

F
200
250
10
315
400

Plain - circular mm F: 592mm F: 575mm F: 584 mm F: 575 mm F: 599 mm


11
100
CRL 125
160

F
200
250 12
315
400

13
1. Product and tech. data depicted in catalogue.
2. Combination possible. Tech. data depicted in catalogue.
3. Combination possible. Tech. data not in catalogue. 14
4. If space is empty, combination is not possible.

15

16

17

18

Right to alterations reserved 55


lindab | ceili ng dif fusers

Perforated diffuser PKA


Dimensions
UxU
1
Ød

50
22
38
AxA 3
PKA Ød A U* Free area A Weight
mm mm mm m2 kg 4
125 235 200 0,018 1,10
160 295 260 0,023 1,80
200 395 360 0,03 2,80
250 495 460 0,043 4,20
5
315 595 560 0,057 5,70
400 595 560 0,075 5,70

Description * U x U = Ceiling grid opening 6


PKA is a square diffuser with perforated face plate. PKA can
be used for both supply and exhaust air. PKA is suitable for
horizontal supply of cooled air and can be equipped with 7
accessories of various types in order to achieve optimal
function. Installing a PKA diffuser in a plenum box type MBB
can help to achieve a stable airflow to the diffuser as well as 8
realise the potential for individual ajustment.

• Suitable for both supply and exhaust air


• Suitable for horizontal supply of cooled air 9
• Option of 1, 2 and 3-way supply air

Maintenance 10
The face plate can be removed to enable cleaning of internal
parts or to gain access to the duct or box. The visible parts
of the diffuser can be wiped with a damp cloth. 11

12

13

14

15

16
Order code
Product PKA aaa Materials and finish
Type Material: Galvanised steel
PKA Standard finish: Powder-coated 17
Connection dim. Ød Standard colour: White RAL 9010, gloss 30
Ød 125-400
The diffuser is available in other colours. Please contact 18
Example: PKA-200 Lindab’s sales department for further information.

We reserve the right to make changes without prior notice 57


lindab | ceil ing di ffusers

Perforated diffuser PKA


Accessories MBB - Plenum box
1
DRZ - Balancing damper

3
Blending profiles (set)

PKA + MBB
4
10 LxB

10
5

Ød1

C
H
Ød2

6
F E
7
MBZ - Extension piece PKA + MBB
duct PKA B C E F H* L
Ød1 mm Ød2 mm mm mm mm mm mm mm
8 100 125 260 159 216 50 180 - 220 310
DKZ - Mounting brackets (set)
100 160 260 159 216 50 180 - 220 310
125 125 310 184 262 50 205 - 245 376
9 125 160 310 184 262 50 205 - 245 376
125 200 310 184 262 50 205 - 245 376
160 160 380 220 323 50 239 - 279 459
160 200 380 220 323 50 239 - 279 459
10 160 250 380 220 323 50 239 - 279 459
200 200 460 259 396 70 280 - 320 565
200 250 460 259 396 70 280 - 320 565
11 200 315 460 259 396 70 280 - 320 565
250 250 540 309 486 70 330 - 370 698
250 315 540 309 486 70 330 - 370 698
Order code - accessoreies
12 Product aaa bbb
250 400 540 309 486 70 330 - 370 698
315 315 540 373 646 70 395 - 435 858
Type 315 400 540 373 646 70 395 - 435 858
Size
13 * Using accessory MBZ the H dimension will increase:
Ød2 = 125 - 200 mm => H +40 mm
Example: DRZ-200
Ød2 = 250 - 315 mm => H +60 mm
Ød2 = 400 mm => H +80 mm
14 LM - Module plate

Order code
15 Product MBB aaa bbb c
Type
MBB
16 Order code - module plate Duct connection Ød1
Product LM a PKA ccc Ø100-315
Type Diffuser dimension Ød2
Ceiling system Ø125-400
17 Diffuser Function
Size S = Supply air
E = Exhaust
18 Example: LM-1-PKA-200
Ceiling system - see introductory summary. Example: PKA-200+MBB-160-200-S

58 We reserve the right to make changes without prior notice


lindab | ceili ng dif fusers

Perforated diffuser PKA


Technical data
1
Capacity Balancing
Air flow qv [l/s] and [m3/h], total pressure Δpt [Pa], throw l0.2 Balancing data is contained in a separate brochure.
[m] and sound power level LWA [dB(A)] can be seen in the
diagrams.
2
Throw l0.2
The throw is specified at a terminal velocity of 0.2 m/s.
Frequency-related sound effect level
The sound effect level in the frequency band is defined as l0.2 [m] PKA 160 250 400
125 200 315
3
10
LWA+Kok. Kok values are specified in charts beneath the dia-
grams on the following pages.
8
7

Quick selection, supply air


6 4
5

4
PKA + MBB Δpt ≥ 50 Pa Δpt ≥ 50 Pa
duct PKA 30 dB(A) 35 dB(A)
3
5
Ød1 Ød2 l/s m3/h l/s m3/h 2
100 125 33 119 39 140
100 160 39 140 47 169
l0.2 [m]
6
125 125 40 144 48 173 1
qV [l/s]
125 160 51 184 61 220 30 40 50 60 70 80 100 150 200 300 500 700
125 200 58 209 70 252 qV [m3/h]

160 160 59 212 70 252


100 150 200 300 500 700 1000 1500 2000 7
160 200 67 241 84 302
160 250 77 277 99 356
Correction throw l0.2
200 200 83 299 100 360
PKA Ød 1 - ways 2 - ways 3 - ways
8
200 250 96 346 118 425
125 2.6 1.8 1.4
200 315 112 403 139 500
160 2.5 1.7 1.3
250 250 118 425 139 500
200 2.4 1.7 1.3
9
250 315 133 479 163 587
250 400 128 461 174 626 250 2.3 1.7 1.3
315 315 145 522 173 623 315 2.2 1.7 1.2
315 400 173 623 209 752 400 2.3 1.7 1.2 10
Sound attenuation Air jet distribution
Sound attenuation of the diffuser ΔL from duct to room, lb = Distance from the diffuser to the point where there is 11
including end reflection, see table below. maximum dispersal.
bv = Depth of the air jet on a vertical plane.
PKA + MBB bh = Width of the air jet on a horizontal plane. 12
duct PKA Centre frequency Hz
bv

Ød1 Ød2 63 125 250 500 1K 2K 4K 8K lb


100 125 19 16 7 19 18 18 18 21 lb = 0.6 × l02 bv = 0.05 × l02 13
100 160 21 16 5 15 17 18 16 19
125 125 18 13 9 20 13 19 18 19
bh

125 160 12 13 8 19 13 16 17 19
125 200 16 11 5 16 13 15 15 17 lb
14
160 160 17 17 11 19 18 17 20 20 lb = 0.4 × l02 bh = 1.3 × l02
160 200 14 14 7 21 15 16 18 19
160 250 15 15 5 17 13 15 16 18 15
bh

bh

200 200 15 10 6 16 17 15 19 18
200 250 12 9 5 14 17 15 17 17 lb lb
200 315 12 7 4 11 15 14 16 15
250 250 14 8 8 14 16 17 17 18
lb = 0.5 × l02 bh = 1.0 × l02
16
250 315 12 6 6 15 15 15 16 17
250 400 13 5 4 13 14 14 15 15
315 315 7 9 8 14 17 16 17 21 17
315 400 7 8 8 12 16 16 16 18
bh

lb lb
lb = 0.5 × l02 bh = 0.4 × l02 18

We reserve the right to make changes without prior notice 59


lindab | ceil ing di ffusers

Perforated diffuser PKA


Technical data
1
PKA without box - Supply air PKA 125 + MBB - Supply air

2 ǻpt [Pa] PKA


100
125 160 200 250 315 ǻpt [Pa] PKA-125+MBB-125-125-S
250
200
70
150
400
3 50
100 50
50 45
30 70
45 40
40 50
20 35
4 15
35
30 30
30
25
10 25 20
20
20 15
5 7
LWA dB(A) LWA dB(A)
5 10
qV [l/s] qV [l/s]
30 40 50 60 70 80 100 150 200 300 400 500 20 25 30 40 50 60 70 80 100
3
qV [m /h] qV [m3/h]
80 100 150 200 300
6 150 200 300 400 500 700 1000 1500 2000

Hz 63 125 250 500 1K 2K 4K 8K


Kok 9 5 -1 -4 -3 -11 -20 -26
7
ǻpt [Pa] PKA-125+MBB-100-125-S
250
200
8 150 50
45
100
40
70
9 50
35

30

30 25

10 20 20
15
LWA dB(A)
10
qV [l/s]
11 10 15 20 25 30 40 50 60 70
qV [m3/h]
40 50 60 70 80 100 150 200

12 Hz 63 125 250 500 1K 2K 4K 8K


Kok 11 7 3 -5 -5 -11 -18 -25

13

14

15

16

17

18

60 We reserve the right to make changes without prior notice


lindab | ceili ng dif fusers

Perforated diffuser PKA


Technical data
1
PKA 160 + MBB - Supply air PKA 200 + MBB - Supply air

ǻpt [Pa] PKA-160+MBB-160-160-S


250
¨pt [Pa] PKA-200+MBB-200-200-S
250
2
200 200
150 150

100
50
100 3
70 70 50
45
45
50 40 50
40

30
35
30
35 4
30 30
20 25 20 25
15 20 15 20
LWA dB(A) LWA dB(A) 5
10 10
qV [l/s] qV [l/s]
30 40 50 60 70 80 100 120 140 160 50 60 70 80 100 120 140 160 180 200 240
qV [m3/h] qV [m3/h]
150 200 300 400 500 200 300 400 500 700
6
Hz 63 125 250 500 1K 2K 4K 8K Hz 63 125 250 500 1K 2K 4K 8K
Kok 8 5 -2 -4 -3 -11 -21 -29 Kok 11 5 -3 -3 -3 -11 -22 -29
7
ǻpt [Pa] PKA-160+MBB-125-160-S ǻpt [Pa] PKA-200+MBB-160-200-S
250 250
200 200 8
150 150
50
100 45 100
50
70 40 70 45 9
40
50 35 50
35
30
30 30 30
25 25
10
20 20
20 20
15 15
LWA dB(A) LWA dB(A)
10
qV [l/s]
10
qV [l/s] 11
20 25 30 40 50 60 70 80 100 120 30 40 50 60 70 80 100 120 140 160
qV [m3/h] qV [m3/h]
80 100 150 200 300 400 150 200 300 400 500

Hz 63 125 250 500 1K 2K 4K 8K Hz 63 125 250 500 1K 2K 4K 8K


12
Kok 9 5 1 -4 -4 -10 -17 -25 Kok 10 5 -2 -4 -3 -10 -20 -26

13
ǻpt [Pa] PKA-160+MBB-100-160-S ǻpt [Pa] PKA-200+MBB-125-200-S
250 250
200 50 200
150 45 150 50 14
100 40 100 45
40
70 35 70

50 30 50
35 15
30
25
30 30 25
20
20 20 20
16
15 15
LWA dB(A) LWA dB(A)
10 10
qV [l/s] qV [l/s]
10 15 20 25 30 40 50 60 70 80 100
qV [m3/h]
20 25 30 40 50 60 70 80 100 120 140
qV [m3/h]
17
40 50 60 70 80 100 150 200 300 80 100 150 200 300 400 500

Hz 63 125 250 500 1K 2K 4K 8K Hz 63 125 250 500 1K 2K 4K 8K


18
Kok 9 4 1 -3 -5 -10 -15 -19 Kok 10 5 1 -4 -5 -10 -15 -22

We reserve the right to make changes without prior notice 61


lindab | ceil ing di ffusers

Perforated diffuser PKA


Technical data
1
PKA 250 + MBB - Supply air PKA 315 + MBB - Supply air

2 ǻpt [Pa] PKA-250+MBB-250-250-S


250
ǻpt [Pa] PKA-315+MBB-315-315-S
250
200 200
150 150

3 100 100

70 50 70
50
50 45 50 45

4 30
40
30
40
35 35

20 30 20 30
25 25
15 15
5 20 LWA dB(A) 20 LWA dB(A)
10 10
qV [l/s] qV [l/s]
50 60 70 80 100 120 140 160 180 200 240 280 50 60 70 80 90 100 150 200 250 300 350 400
3
qV [m /h] qV [m3/h]
200 300 400 500 700 1000 200 300 400 500 700 1250
6
Hz 63 125 250 500 1K 2K 4K 8K Hz 63 125 250 500 1K 2K 4K 8K
Kok 11 3 -4 -3 -3 -12 -22 -30 Kok 12 2 -3 -2 -3 -13 -23 -33
7
ǻpt [Pa] PKA-250+MBB-200-250-S ǻpt [Pa] PKA-315+MBB-250-315-S
250 250
8 200 200
150 150

100 100
50
9 70 45 70
50
45
50 40 50
40
35
30 30 35
10 30
30
20 25 20
25
15 15
20 20
LWA dB(A) LWA dB(A)
11 10
50 60 70 80 100 120 140 160 180 200 240
qV [l/s]
10
qV [l/s]
50 60 70 80 90 100 150 200 250 300 350 400
qV [m3/h] qV [m3/h]
200 300 400 500 700 200 300 400 500 700 1250

12 Hz 63 125 250 500 1K 2K 4K 8K Hz 63 125 250 500 1K 2K 4K 8K


Kok 10 5 -2 -3 -3 -11 -20 -28 Kok 11 3 -2 -3 -4 -11 -18 -27

13
ǻpt [Pa] PKA-250+MBB-160-250-S ǻpt [Pa] PKA-315+MBB-200-315-S
250 250
200 200
14 150 150
50
100 45 100 50
70 40 70 45
15 50 35 50
40
35
30
30 30 30
25
25
16 20
20
20
20
15 15
LWA dB(A) LWA dB(A)
10 10
qV [l/s] qV [l/s]
17 30 40 50 60 70 80 100 120 140 160 180
qV [m3/h]
50 60 70 80 100 120 140 160 180 200 240 280
qV [m3/h]
150 200 300 400 500 200 300 400 500 700 1000

18 Hz 63 125 250 500 1K 2K 4K 8K Hz 63 125 250 500 1K 2K 4K 8K


Kok 8 5 0 -4 -4 -10 -17 -23 Kok 10 5 -1 -3 -4 -11 -19 -25

62 We reserve the right to make changes without prior notice


lindab | ceili ng dif fusers

Perforated diffuser PKA


Technical data
1
PKA 400 + MBB - Supply air PKA + MBB - Supply air

ǻpt [Pa] PKA-400+MBB-315-400-S Correction sound power level ( LWA ) 2


250
200
and pressure loss ( Δpt )
150

100
50
PKA + MBB 3
70 duct PKA 1 - ways 2 - ways 3 - ways
45
50 Ød1 Ød2 LWA Δpt LWA Δpt LWA Δpt
40
100 125 + 10 x 1.3 +4 x 1.1 +2 x 1.05
30
35
100 160 +5 x 1.1 +2 x 1.05 +1 x1
4
30
20
25
125 125 + 10 x 1,35 +6 x 1,1 +4 x 1,05
15
20
125 160 + 10 x 1.4 +4 x 1.1 +1 x1

10
LWA dB(A)
125 200 +4 x 1.2 +2 x 1.05 +1 x1 5
qV [l/s]
70 80 90 150 200 250 300 350 400 500 600
160 160 + 13 x 1.8 +6 x 1.3 +2 x 1.1
qV [m3/h] 160 200 + 16 x 1.7 + 10 x 1.2 +4 x 1.05
300 400 500 700 1250 1500 2000
160 250 + 10 x 1.3 +6 x 1,1 +3 x1 6
200 200 + 17 x 2.3 + 11 x 1.4 +7 x 1.1
Hz 63 125 250 500 1K 2K 4K 8K
200 250 + 13 x 1.8 +6 x 1.2 +4 x 1.1
Kok 14 2 0 -2 -5 -13 -17 -26
200 315 +9 x 1.5 +4 x 1.1 +0 x 1.05
250 250 + 21 x 2.1 + 11 x 1.4 +7 x 1.2
7
250 315 + 19 x 1.8 +7 x 1.2 +3 x 1.1
ǻpt [Pa] PKA-400+MBB-250-400-S
250
250 400 + 10 x 1.5 +6 x 1.2 +0 x1
200 315 315 + 21 x 2.1 + 10 x 1.3 +4 x 1.1 8
150 315 400 + 21 x 1.8 +8 x 1.5 +3 x 1.2

100 50

70 45 9
50 40

35
30

20
30
10
25
15 20
LWA dB(A)
10
50 60 70 80 90 100 150 200 250 300 350 400
qV [l/s] 11
qV [m3/h]
200 300 400 500 700 1250

Hz 63 125 250 500 1K 2K 4K 8K 12


Kok 10 4 0 -2 -4 -11 -17 -24

13

14

15

16

17

18

We reserve the right to make changes without prior notice 63


lindab | ceil ing di ffusers

Perforated diffuser PKA


Technical data
1
PKA without box - Exhaust air PKA 125 + MBB - Exhaust air

2 ǻpt [Pa] PKA


150
125 160 200 250 315 ǻpt [Pa] PKA-125+MBB-125-125-E
250
200
100 45
400 150
50
70 40
3 50
45 100

40 35
70
30 35 30
50
30
4 20
25 30
25
15
20 20
10 20
15
5 7
LWA dB(A) LWA dB(A)
5 10
qV [l/s] qV [l/s]
30 40 50 60 70 100 150 200 300 400 500 700 1000 10 15 20 25 30 40 50 60 80 100 120 140
3
qV [m /h] qV [m3/h]
40 50 60 70 80 100 150 200 300 400 500
6 150 200 300 400 500 700 1000 1500 2000 3000

Hz 63 125 250 500 1K 2K 4K 8K


Kok 13 5 -1 -4 -4 -11 -15 -20
7
ǻpt [Pa] PKA-125+MBB-100-125-E
250
50
200
8 150 45

100
40
70
9 50
35

30
30

10 20
25

15 20
LWA dB(A)
10
qV [l/s]
11 5 10 15 20 25 30 40 50 60 80
qV [m3/h]
20 30 40 50 60 70 80 100 150 200

12 Hz 63 125 250 500 1K 2K 4K 8K


Kok 13 -1 3 -3 -6 -10 -16 -19

13

14

15

16

17

18

64 We reserve the right to make changes without prior notice


lindab | ceili ng dif fusers

Perforated diffuser PKA


Technical data
1
PKA 160 + MBB - Exhaust air PKA 200 + MBB - Exhaust air

ǻpt [Pa] PKA-160+MBB-160-160-E


250
ǻpt [Pa] PKA-200+MBB-200-200-E
250
2
200 200 50
45
150 150 45
40
100 100 40 3
35
70 70 35
30
50 50
30

30
25
30 25
4
20
20 20 20

15 15
LWA dB(A) LWA dB(A) 5
10 10
qV [l/s] qV [l/s]
10 15 20 25 30 40 50 60 80 100 150 200 20 25 30 40 50 60 80 100 150 200 250
qV [m3/h] qV [m3/h]
40 50 60 70 80 100 150 200 300 400 500 700 80 100 150 200 300 400 500 700
6
Hz 63 125 250 500 1K 2K 4K 8K Hz 63 125 250 500 1K 2K 4K 8K
Kok 16 6 -1 -5 -4 -10 -15 -19 Kok 15 4 -1 -4 -5 -9 -16 -25
7
ǻpt [Pa] PKA-160+MBB-125-160-E ǻpt [Pa] PKA-200+MBB-160-200-E
250 250
200
50
200
50 8
150 45 150 45

100 40 100 40
70
35
70 9
35
50 50
30 30
30 30
25 25 10
20 20
20 20
15 15
LWA dB(A) LWA dB(A)
10
qV [l/s]
10
qV [l/s] 11
10 15 20 25 30 40 50 60 80 100 120 140 10 15 20 25 30 40 50 60 80 100 150 200
3
qV [m3/h] qV [m /h]
40 50 60 70 80 100 150 200 300 400 500 40 50 60 70 80 100 150 200 300 400 500 700

Hz 63 125 250 500 1K 2K 4K 8K Hz 63 125 250 500 1K 2K 4K 8K


12
Kok 13 5 0 -3 -5 -11 -15 -22 Kok 15 6 -1 -5 -5 -9 -14 -20

13
ǻpt [Pa] PKA-160+MBB-100-160-E ǻpt [Pa] PKA-200+MBB-125-200-E
250 250
200 200 50
150
50
150 14
45
100 45 100
40
70 40 70

50 50 35
15
35
30
30 30 30

20
25
20 25
16
15 15 20
20 LWA dB(A) LWA dB(A)
10 10
qV [l/s] qV [l/s]
5 10 15 20 25 30 40 50 60 80
3
qV [m /h]
10 15 20 25 30 40 50 60 80 100 120 140
qV [m3/h]
17
20 30 40 50 60 70 80 100 150 200 300 40 50 60 70 80 100 150 200 300 400 500

Hz 63 125 250 500 1K 2K 4K 8K Hz 63 125 250 500 1K 2K 4K 8K


18
Kok 10 -1 5 -3 -8 -11 -18 -25 Kok 9 3 1 -4 -5 -10 -14 -21

We reserve the right to make changes without prior notice 65


lindab | ceil ing di ffusers

Perforated diffuser PKA


Technical data
1
PKA 250 + MBB - Exhaust air PKA 315 + MBB - Exhaust air

2 ǻpt [Pa] PKA-250+MBB-250-250-E


250
ǻpt [Pa] PKA-315+MBB-315-315-E
250
200 50 200 50
150 45 150
45
3 100 40 100
40
70 70
35
35
50 50
30
4 30 30
30

25
25
20 20 20
20
15 15
5 LWA dB(A) LWA dB(A)
10 10
qV [l/s] qV [l/s]
20 25 30 40 50 60 80 100 150 200 250 300 400 20 25 30 40 50 60 80 100 150 200 250 350 500
3
qV [m /h] qV [m3/h]
80 100 150 200 300 400 500 700 1250 80 100 150 200 300 400 500 700 1250 2000
6
Hz 63 125 250 500 1K 2K 4K 8K Hz 63 125 250 500 1K 2K 4K 8K
Kok 10 5 2 -3 -5 -11 -16 -25 Kok 13 5 3 -4 -6 -10 -16 -26
7
ǻpt [Pa] PKA-250+MBB-200-250-E ǻpt [Pa] PKA-315+MBB-250-315-E
250 250
8 200 50 200
50
150 150
45
100 100 45

9 70
40
70 40

50 35 50
35
30
30 30
10 25
30

20 20 25
15 15
20
LWA dB(A) 20 LWA dB(A)
11 10
qV [l/s]
10
qV [l/s]
20 25 30 40 50 60 80 100 150 200 250 300 20 25 30 40 50 60 80 100 150 200 250 300 400
qV [m3/h] qV [m3/h]
80 100 150 200 300 400 500 700 1000 80 100 150 200 300 400 500 700 1250

12 Hz 63 125 250 500 1K 2K 4K 8K Hz 63 125 250 500 1K 2K 4K 8K


Kok 12 5 0 -3 -5 -10 -14 -23 Kok 7 5 2 -3 -6 -10 -16 -24

13
ǻpt [Pa] PKA-250+MBB-160-250-E ǻpt [Pa] PKA-315+MBB-200-315-E
250 250
200 200
14 150
50
150
50

45
100 100 45

40
70 70 40
15 50 35 50
35
30
30 30 30
25
16 20 20 25
15 20 15
LWA dB(A) 20 LWA dB(A)
10 10
qV [l/s] qV [l/s]
17 10 15 20 25 30 40 50 60 80 100 150 200
qV [m3/h]
20 25 30 40 50 60 80 100 150 200 250 300
qV [m3/h]
40 50 60 70 80 100 150 200 300 400 500 700 80 100 150 200 300 400 500 700 1000

18 Hz 63 125 250 500 1K 2K 4K 8K Hz 63 125 250 500 1K 2K 4K 8K


Kok 16 6 0 -5 -5 -9 -15 -21 Kok 13 5 0 -3 -5 -9 -15 -23

66 We reserve the right to make changes without prior notice


lindab | ceili ng dif fusers

Perforated diffuser PKA


Technical data
1
PKA 400 + MBB - Exhaust air

ǻpt [Pa] PKA-400+MBB-315-400-E


250
2
200
150 50

100 45 3
70 40

50 35

30 30
4
20 25

15
20
LWA dB(A) 5
10
qV [l/s]
20 25 30 40 50 60 80 100 150 200 250 350 500
qV [m3/h]
80 100 150 200 300 400 500 700 1250 2000
6
Hz 63 125 250 500 1K 2K 4K 8K
Kok 10 4 2 -3 -6 -9 -14 -25
7
ǻpt [Pa] PKA-400+MBB-250-400-E
250
200 8
150 50

100 45
70
40
9
50
35

30
30 10
20
25
15
20 LWA dB(A)
10
qV [l/s] 11
20 25 30 40 50 60 80 100 150 200 250 300 400
3
qV [m /h]
80 100 150 200 300 400 500 700 1250

Hz 63 125 250 500 1K 2K 4K 8K


12
Kok 10 5 2 -4 -5 -10 -15 -23

13

14

15

16

17

18

We reserve the right to make changes without prior notice 67


li ndab | ceiling diffusers

Perforated diffuser PCA


Dimensions
ØU
1
Ød

50
22
37
ØD
3
PCA Ød ØD ØU* Free area A Weight
mm mm mm m2 kg 4
100 240 200 0.016 1,00
125 240 200 0.018 1,00
160 300 260 0.023 1,50 5
200 360 320 0.03 2,30
250 460 420 0.042 3,40
315 540 500 0.058 4,60
Description 400 540 500 0.066 4,60
6
PCA is a circular diffuser with perforated face plate. PCA * ØU = Ceiling grid opening
can be used for both supply and exhaust air. PCA is suitable
for horizontal supply of cooled air and can be equipped with 7
accessories of various types in order to achieve optimal
function. Installing a PCA diffuser in a plenum box type MBB
can help to achieve a stable airflow to the diffuser as well as 8
realise the potential for individual ajustment.

• Suitable for both supply and exhaust air


• Suitable for horizontal supply of cooled air 9
• Option of 1, 2 and 3-way supply air

Maintenance 10
The face plate can be removed to enable cleaning of internal
parts or to gain access to the duct or box. The visible parts
of the diffuser can be wiped with a damp cloth. 11

12

13

14

15

16
Order code
Product PCA aaa
Materials and finish
Type Material: Galvanised steel
PCA Standard finish: Powder-coated 17
Connection dim. Ød Standard colour: White RAL 9010, gloss 30
Ød 100-400
The diffuser is available in other colours. Please contact 18
Example: PCA-200 Lindab’s sales department for further information.

We reserve the right to make changes without prior notice 69


l indab | ceiling diff users

Perforated diffuser PCA


Accessories MBB - Plenum box
1
DRZ - Balancing damper

3
Blending profiles (set)

PCA + MBB
4
10 LxB

5 10

Ød1

C
H
Ød2
6

F E
7 MBZ - Extension piece
PCA + MBB
duct PCA B C E F H* L
8 DDZ - Mounting brackets (set) Ød1 mm Ød2 mm mm mm mm mm mm mm
100 100 260 159 216 50 180 - 220 310
100 125 260 159 216 50 180 - 220 310
100 160 260 159 216 50 180 - 220 310
9
125 125 310 184 262 50 205 - 245 376
125 160 310 184 262 50 205 - 245 376
125 200 310 184 262 50 205 - 245 376
10 160 160 380 220 323 50 239 - 279 459
160 200 380 220 323 50 239 - 279 459
160 250 380 220 323 50 239 - 279 459
11 200 200 460 259 396 70 280 - 320 565
200 250 460 259 396 70 280 - 320 565
200 315 460 259 396 70 280 - 320 565
Order code - accessoreies
250 250 540 309 486 70 330 - 370 698
12 Product aaa bbb
250 315 540 309 486 70 330 - 370 698
Type
250 400 540 309 486 70 330 - 370 698
Size
315 315 540 373 646 70 395 - 435 858
13 Example: DRZ-200
315 400 540 373 646 70 395 - 435 858

* Using accessory MBZ the H dimension will increase:


Ød2 = 100 - 200 mm => H +40 mm
LM - Module plate Ød2 = 250 - 315 mm => H +60 mm
14
Ød2 = 400 mm => H +80 mm

Order code
15 Product MBB aaa bbb c
Type
MBB
16 Order code - module plate Duct connection Ød1
Product LM a PCA ccc Ø100-315
Type Diffuser dimension Ød2
Ceiling system
17 Diffuser
Ø100-400
Function
Size S = Supply air
E = Exhaust
18 Example: LM-1-PCA-200
Ceiling system - see introductory summary. Example: PCA-200+MBB-160-200-S

70 We reserve the right to make changes without prior notice


li ndab | ceiling diffusers

Perforated diffuser PCA


Technical data
1
Capacity Balancing
Air flow qv [l/s] and [m3/h], total pressure Δpt [Pa], throw l 0.2 Balancing data is contained in a separate brochure.
[m] and sound power level LWA [dB(A)] can be seen in the
diagrams
2
Throw l0.2
The throw is specified at a terminal velocity of 0.2 m/s.
Frequency-related sound effect level
The sound effect level in the frequency band is defined as l0.2 [m] PCA 125 200 315
100 160 250 400
3
10
LWA+Kok. Kok values are specified in charts beneath the dia-
grams on the following pages.
8
7
6 4
Quick selection, supply air 5

4
PCA + MBB Δpt ≥ 50 Pa Δpt ≥ 50 Pa
duct PCA 30 dB(A) 35 dB(A) 3
5
Ød1 Ød2 l/s m3/h l/s m3/h
2
100 100 26 94 31 112
100 125 33 119 39 140
6
100 160 39 140 47 169 l0.2 [m]
1
125 125 40 144 48 173 qV [l/s]
20 30 40 50 60 70 100 150 200 300 500 700
125 160 51 184 61 220 qV [m3/h]
125 200 58 209 70 252 80 100 150 200 300 500 700 1000 1500 2000 7
160 160 57 207 71 255 Correction throw L0.2
160 200 67 241 84 302
160 250 77 277 99 356 PCA Ød 1 - ways 2 - ways 3 - ways 8
200 200 83 299 100 360 100 2.3 1.7 1.3
200 250 96 346 118 425 125 2.6 1.8 1.4
200 315 112 403 139 500 160 2.5 1.7 1.3
250 250 118 425 139 500 200 2.4 1.7 1.3
9
250 315 133 479 163 587
250 2.3 1.7 1.3
250 400 146 526 193 695
315 2.2 1.7 1.2
315 315 145 522 173 623
400 2.3 1.7 1.2
10
315 400 187 673 225 810
Air jet distribution
Sound attenuation lb = Distance from the diffuser to the point where there is 11
Sound attenuation of the diffuser ΔL from duct to room, maximum dispersal.
including end reflection, see table below. bv = Depth of the air jet on a vertical plane.
bh = Width of the air jet on a horizontal plane.
PCA + MBB 12
bv

duct PCA Centre frequency Hz lb


Ød1 Ød2 63 125 250 500 1K 2K 4K 8K lb = 0.6 × l02 bv = 0.05 × l02
100 100 18 17 8 20 19 20 19 23 13
100 125 19 16 7 19 18 18 18 21
bh

100 160 21 16 5 15 17 18 16 19
125 125 18 13 9 20 13 19 18 19 lb 14
125 160 12 13 8 19 13 16 17 19 lb = 0.4 × l02 bh = 1.3 × l02
125 200 16 11 5 16 13 15 15 17
160 160 17 17 11 19 18 17 20 20
15
bh

bh

160 200 14 14 7 21 15 16 18 19
160 250 15 15 5 17 13 15 16 18 lb lb
200 200 15 10 6 16 17 15 19 18 lb = 0.5 × l02 bh = 1.0 × l02
200 250 12 9 5 14 17 15 17 17 16
200 315 12 7 4 11 15 14 16 15
250 250 14 8 8 14 16 17 17 18
250 315 12 6 6 15 15 15 16 17
250 400 13 5 4 13 14 14 15 15
17
bh
bh

315 315 7 9 8 14 17 16 17 21
lb lb
315 400 7 8 8 12 16 16 16 18
lb = 0.5 × l02 bh = 0.4 × l02
18

We reserve the right to make changes without prior notice 71


l indab | ceiling diff users

Perforated diffuser PCA


Technical data
1
PCA without box - supply air PCA 100 + MBB - Supply air

2 ǻpt [Pa] PCA


100
100 125 160 200 250 315 ǻpt [Pa] PCA-100+MBB-100-100-S
250
200
70 400
150
50 50 50
3 45 100
45
30 40
70
40
20 35
50 35
15 30
4 10
25
30
30
20
25
7 20
20
5 15
5 LWA dB(A) LWA dB(A)
3 10
qV [l/s] qV [l/s]
20 30 40 50 60 70 100 150 200 300 400 500 700 5 10 15 20 25 30 40 50 60 70
3
qV [m /h] qV [m3/h]
20 30 40 50 60 70 80 100 150 200
6 80 100 150 200 300 400 500 700 1000 1500 2000

Hz 63 125 250 500 1K 2K 4K 8K


Kok 12 5 2 -5 -4 -11 -20 -26
7

10

11

12

13

14

15

16

17

18

72 We reserve the right to make changes without prior notice


li ndab | ceiling diffusers

Perforated diffuser PCA


Technical data
1
PCA 125 + MBB - Supply air PCA 160 + MBB - Supply air

ǻpt [Pa] PCA-125+MBB-125-125-S ǻpt [Pa] PCA-160+MBB-160-160-S


250 250 2
200 200

150 150

100
45
50 100
50 3
70 70
45
40
50 50 40
35

30 30 30
30
35
4
25
20 20 25
20
15 15 20

10
LWA dB(A)
10
LWA dB(A) 5
qV [l/s] qV [l/s]
20 25 30 40 50 60 70 80 100 30 40 50 60 70 80 100 120 140 160
qV [m3/h] qV [m3/h]
80 100 150 200 300 150 200 300 400 500
6
Hz 63 125 250 500 1K 2K 4K 8K Hz 63 125 250 500 1K 2K 4K 8K
Kok 9 5 -1 -4 -3 -11 -20 -26 Kok 8 5 -2 -4 -3 -11 -21 -29
7
ǻpt [Pa] PCA-125+MBB-100-125-S ǻpt [Pa] PCA-160+MBB-125-160-S
250 250
200 200 8
150 50 150
50
45
100 100 45
40
70
35
70 40 9
50 50 35
30
30
30 25 30

20 20 20
25 10
20
15 15
LWA dB(A) LWA dB(A)
10 10
10 15 20 25 30 40 50 60 70
qV [l/s]
20 25 30 40 50 60 70 80 100 120
qV [l/s] 11
qV [m3/h] qV [m3/h]
40 50 60 70 80 100 150 200 80 100 150 200 300 400

Hz 63 125 250 500 1K 2K 4K 8K Hz 63 125 250 500 1K 2K 4K 8K 12


Kok 11 7 3 -5 -5 -11 -18 -25 Kok 9 5 1 -4 -4 -10 -17 -25

13
ǻpt [Pa] PCA-160+MBB-100-160-S
250
200 50

150 45
14
100 40

70 35

50 30 15
25
30
20
20
15
16
LWA dB(A)
10
qV [l/s]
10 15 20 25 30 40 50 60 70 80 100
qV [m3/h] 17
40 50 60 70 80 100 150 200 300

Hz 63 125 250 500 1K 2K 4K 8K


Kok 9 4 1 -3 -5 -10 -15 -19
18

We reserve the right to make changes without prior notice 73


l indab | ceiling diff users

Perforated diffuser PCA


Technical data
1
PCA 200 + MBB - Supply air PCA 250 + MBB - Supply air

¨pt [Pa] PCA-200+MBB-200-200-S ǻpt [Pa] PCA-250+MBB-250-250-S


2 250 250
200 200
150 150

3 100 100

70 50 70 50
45
50 50 45
40
4 30
35
30 35
40

30
20 20 30
25
15 15 25
20
5 10
LWA dB(A)
10
20 LWA dB(A)
qV [l/s] qV [l/s]
50 60 70 80 100 120 140 160 180 200 240 50 60 70 80 100 120 140 160 180 200 240 280
qV [m3/h] qV [m3/h]
200 300 400 500 700 200 300 400 500 700 1000
6
Hz 63 125 250 500 1K 2K 4K 8K Hz 63 125 250 500 1K 2K 4K 8K
Kok 11 5 -3 -3 -3 -11 -22 -29 Kok 11 3 -4 -3 -3 -12 -22 -30
7
ǻpt [Pa] PCA-200+MBB-160-200-S ǻpt [Pa] PCA-250+MBB-200-250-S
250 250
8 200 200
150 150

100 100
50 50
9 70 45 70 45
40
50 50 40
35
35
30 30 30
10 20
25
20
30

20 25
15 15
20
LWA dB(A) LWA dB(A)
10 10
11 30 40 50 60 70 80 100 120 140 160
qV [l/s]
50 60 70 80 100 120 140 160 180 200 240
qV [l/s]

qV [m3/h] qV [m3/h]
150 200 300 400 500 200 300 400 500 700

12 Hz 63 125 250 500 1K 2K 4K 8K Hz 63 125 250 500 1K 2K 4K 8K


Kok 10 5 -2 -4 -3 -10 -20 -26 Kok 10 5 -2 -3 -3 -11 -20 -28

13
ǻpt [Pa] PCA-200+MBB-125-200-S ǻpt [Pa] PCA-250+MBB-160-250-S
250 250
200 200

14 150 50 150
50
100 45 100 45
40
70 70 40
15 50
35
50 35
30
30
30 25 30
25
20
16 20
15
20
15
20

LWA dB(A) LWA dB(A)


10 10
qV [l/s] qV [l/s]
20 25 30 40 50 60 70 80 100 120 140 30 40 50 60 70 80 100 120 140 160 180
17 qV [m3/h] qV [m3/h]
80 100 150 200 300 400 500 150 200 300 400 500

Hz 63 125 250 500 1K 2K 4K 8K Hz 63 125 250 500 1K 2K 4K 8K


18 Kok 10 5 1 -4 -5 -10 -15 -22 Kok 8 5 0 -4 -4 -10 -17 -23

74 We reserve the right to make changes without prior notice


li ndab | ceiling diffusers

Perforated diffuser PCA


Technical data
1
PCA 315 + MBB - Supply air PCA 400 + MBB - Supply air

ǻpt [Pa] PCA-315+MBB-315-315-S ǻpt [Pa] PCA-400+MBB-315-400-S


250 250
2
200 200
150 150

100 100
50
3
70 70
50 45
50 45 50
40

30 35
40
30
35 4
30
20 30 20
25
25
15 15
20

10
20 LWA dB(A)
10
LWA dB(A) 5
qV [l/s] qV [l/s]
50 60 70 80 90 100 150 200 250 300 350 400 70 80 90 150 200 250 300 350 400 500 600
qV [m3/h] qV [m3/h]
200 300 400 500 700 1250 300 400 500 700 1250 1500 2000

Hz 63 125 250 500 1K 2K 4K 8K


6
Hz 63 125 250 500 1K 2K 4K 8K
Kok 14 2 0 -2 -5 -13 -17 -26
Kok 12 2 -3 -2 -3 -13 -23 -33
ǻpt [Pa] PCA-400+MBB-250-400-S
250
7
200
ǻpt [Pa] PCA-315+MBB-250-315-S 150
250
200 100 50 8
150 70 45

100 50 40

70
45
50
30
35
9
30
50
40 20 25
30 35 15 20

20
30
10
LWA dB(A) 10
25 qV [l/s]
15 50 60 70 80 90 100 150 200 250 300 350 400
20 LWA dB(A) qV [m3/h]
10 200 300 400 500 700 1250

50 60 70 80 90 100 150 200 250 300 350 400


qV [l/s]
Hz 63 125 250 500 1K 2K 4K 8K
11
qV [m3/h]
200 300 400 500 700 1250 Kok 10 4 0 -2 -4 -11 -17 -24

Hz 63 125 250 500 1K 2K 4K 8K 12


Correction sound power level (LWA) and pressure loss (ΔPt)
Kok 11 3 -2 -3 -4 -11 -18 -27
PCA + MBB
duct PCA 1 - ways 2 - ways 3 - ways 13
ǻpt [Pa] PCA-315+MBB-200-315-S Ød1 Ød2 LWA Δpt LWA Δp t LWA Δpt
250
200
100 100 + 10 x 1,35 +6 x 1,1 +4 x 1,05
100 125 + 10 x 1.3 +4 x 1.1 +2 x 1.05
150 14
100 160 +5 x 1.1 +2 x 1.05 +1 x1
100 50 125 125 + 10 x 1,35 +6 x 1,1 +4 x 1,05
70 45
125 160 + 10 x 1,4 +4 x 1,1 +1 x1
50
40
125 200 +4 x 1,2 +2 x 1,05 +1 x1 15
35
160 160 + 13 x 1,8 +6 x 1,3 +2 x 1,1
30 30
160 200 + 16 x 1,7 + 10 x 1,2 +4 x 1,05
25
20
15
20
160 250 + 10 x 1,3 +6 x 1,1 +3 x1 16
200 200 + 17 x 2,3 + 11 x 1,4 +7 x 1,1
LWA dB(A)
10 200 250 + 13 x 1,8 +6 x 1,2 +4 x 1,1
qV [l/s]
50 60 70 80 100 120 140 160 180 200 240 280 200 315 +9 x 1,5 +4 x 1,1 +0 x 1,05
qV [m3/h] 250 250 + 21 x 2,1 + 11 x 1,4 +7 x 1,2
17
200 300 400 500 700 1000
250 315 + 19 x 1,8 +7 x 1,2 +3 x 1,1
250 400 + 10 x 1,5 +6 x 1,2 +0 x1
Hz 63 125 250 500 1K 2K 4K 8K
Kok 10 5 -1 -3 -4 -11 -19 -25
315 315 + 21 x 2,1 + 10 x 1,3 +4 x 1,1 18
315 400 + 21 x 1,8 +8 x 1,5 +3 x 1,2

We reserve the right to make changes without prior notice 75


l indab | ceiling diff users

Perforated diffuser PCA


Technical data
1
PCA without box - Exhaust air PCA 100 + MBB - Exhaust air

2 ǻpt [Pa] PCA


100
100 125 160 200 250 315 ǻpt [Pa] PCA-100+MBB-100-100-E
250
400 200
70 45
50 150
40
3 50
45 100
35
30 70
40
50 30
20 35
4 15
30 30
25

20
10 25 20
15
5 7 20
LWA dB(A) LWA dB(A)
5 10
qV [l/s] qV [l/s]
30 40 50 60 70 100 150 200 300 400 500 700 1000 5 10 15 20 25 30 40 50 60 80
3
qV [m /h] qV [m3/h]
20 30 40 50 60 70 80 100 150 200
6 150 200 300 400 500 700 1000 1500 2000 3000

Hz 63 125 250 500 1K 2K 4K 8K


Kok 11 0 3 -3 -6 -10 -15 -22
7

10

11

12

13

14

15

16

17

18

76 We reserve the right to make changes without prior notice


li ndab | ceiling diffusers

Perforated diffuser PCA


Technical data
1
PCA 125 + MBB - Exhaust air PCA 160 + MBB - Exhaust air

ǻpt [Pa] PCA-125+MBB-125-125-E


250
ǻpt [Pa] PCA-160+MBB-160-160-E
250 50
2
200 200
45 45
150 150
40 40
100 100 3
35 35
70 70

30 30
50 50

30
25
30
25 4
20
20
20 20
15 15
LWA dB(A) LWA dB(A) 5
10 10
qV [l/s] qV [l/s]
10 15 20 25 30 40 50 60 80 100 120 140 10 15 20 25 30 40 50 60 80 100 150 200
qV [m3/h] qV [m3/h]
40 50 60 70 80 100 150 200 300 400 500 40 50 60 70 80 100 150 200 300 400 500 700
6
Hz 63 125 250 500 1K 2K 4K 8K Hz 63 125 250 500 1K 2K 4K 8K
Kok 13 5 -1 -4 -4 -11 -15 -20 Kok 16 6 -1 -5 -4 -10 -15 -19
7
ǻpt [Pa] PCA-125+MBB-100-125-E ǻpt [Pa] PCA-160+MBB-125-160-E
250 250
200
50
200
50 8
150 45 150 45

100 100 40
40
70 70
35
9
35
50 50
30
30
30 30
25
25 10
20 20
20
15 20 15
LWA dB(A) LWA dB(A)
10
qV [l/s]
10
qV [l/s] 11
5 10 15 20 25 30 40 50 60 80 10 15 20 25 30 40 50 60 80 100 120 140
qV [m3/h] qV [m3/h]
20 30 40 50 60 70 80 100 150 200 40 50 60 70 80 100 150 200 300 400 500

Hz 63 125 250 500 1K 2K 4K 8K Hz 63 125 250 500 1K 2K 4K 8K


12
Kok 13 -1 3 -3 -6 -10 -16 -19 Kok 13 5 0 -3 -5 -11 -15 -22

13
ǻpt [Pa] PCA-160+MBB-100-160-E
250
200
150
50 14
100 45

70 40

50
15
35

30 30

20
25 16
15
20 LWA dB(A)
10
qV [l/s]
5 10 15 20 25 30 40 50 60 80
qV [m3/h]
17
20 30 40 50 60 70 80 100 150 200 300

Hz 63 125 250 500 1K 2K 4K 8K


18
Kok 10 -1 5 -3 -8 -11 -18 -25

We reserve the right to make changes without prior notice 77


l indab | ceiling diff users

Perforated diffuser PCA


Technical data
1
PCA 200 + MBB - Exhaust air PCA 250 + MBB - Exhaust air

2 ǻpt [Pa] PCA-200+MBB-200-200-E


250
ǻpt [Pa] PCA-250+MBB-250-250-E
250
200 50 200 50

150 45 150 45

3 100 40 100 40

70 35 70
35
50 50
30 30
4 30 25 30 25

20 20 20 20
15 15
5 LWA dB(A) LWA dB(A)
10 10
qV [l/s] qV [l/s]
20 25 30 40 50 60 80 100 150 200 250 20 25 30 40 50 60 80 100 150 200 250 300 400
3
qV [m /h] qV [m3/h]
80 100 150 200 300 400 500 700 80 100 150 200 300 400 500 700 1250
6
Hz 63 125 250 500 1K 2K 4K 8K Hz 63 125 250 500 1K 2K 4K 8K
Kok 15 4 -1 -4 -5 -9 -16 -25 Kok 10 5 2 -3 -5 -11 -16 -25
7
ǻpt [Pa] PCA-200+MBB-160-200-E ǻpt [Pa] PCA-250+MBB-200-250-E
250 250
8 200
50
200 50

150 45 150
45
100 40 100
9 70 70
40

35
50 50 35

30
30
30 30
10 25
25
20 20
20
15 15
20
LWA dB(A) LWA dB(A)
11 10
qV [l/s]
10
qV [l/s]
10 15 20 25 30 40 50 60 80 100 150 200 20 25 30 40 50 60 80 100 150 200 250 300
3
qV [m /h] qV [m3/h]
40 50 60 70 80 100 150 200 300 400 500 700 80 100 150 200 300 400 500 700 1000

12 Hz 63 125 250 500 1K 2K 4K 8K Hz 63 125 250 500 1K 2K 4K 8K


Kok 15 6 -1 -5 -5 -9 -14 -20 Kok 12 5 0 -3 -5 -10 -14 -23

13
ǻpt [Pa] PCA-200+MBB-125-200-E ǻpt [Pa] PCA-250+MBB-160-250-E
250 250
200 50 200
14 150 150
50

45 45
100 100
40 40
70 70
15 50 35 50 35

30 30
30 30
25
16 20 25
20
15 20 15 20
LWA dB(A) LWA dB(A)
10 10
qV [l/s] qV [l/s]
17 10 15 20 25 30 40 50 60 80 100 120 140
qV [m3/h]
10 15 20 25 30 40 50 60 80 100 150 200
qV [m3/h]
40 50 60 70 80 100 150 200 300 400 500 40 50 60 70 80 100 150 200 300 400 500 700

18 Hz 63 125 250 500 1K 2K 4K 8K Hz 63 125 250 500 1K 2K 4K 8K


Kok 9 3 1 -4 -5 -10 -14 -21 Kok 16 6 0 -5 -5 -9 -15 -21

78 We reserve the right to make changes without prior notice


li ndab | ceiling diffusers

Perforated diffuser PCA


Technical data
1
PCA 315 + MBB - Exhaust air PCA 400 + MBB - Exhaust air

ǻpt [Pa] PCA-315+MBB-315-315-E


250
ǻpt [Pa] PCA-400+MBB-315-400-E
250
2
200 50 200
150 150 50
45
100
40
100 45 3
70 70 40
35
50 50 35

30
30
30 30
4
25
20 20 25
20
15 15
LWA dB(A)
20
LWA dB(A) 5
10 10
qV [l/s] qV [l/s]
20 25 30 40 50 60 80 100 150 200 250 350 500 20 25 30 40 50 60 80 100 150 200 250 350 500
qV [m3/h] qV [m3/h]
80 100 150 200 300 400 500 700 1250 2000 80 100 150 200 300 400 500 700 1250 2000
6
Hz 63 125 250 500 1K 2K 4K 8K Hz 63 125 250 500 1K 2K 4K 8K
Kok 13 5 3 -4 -6 -10 -16 -26 Kok 10 4 2 -3 -6 -9 -14 -25
7
ǻpt [Pa] PCA-315+MBB-250-315-E ǻpt [Pa] PCA-400+MBB-250-400-E
250 250
200 200 8
50
150 150 50

100 45 100 45
70 40 70
40
9
50 50
35
35

30 30
30 30 10
20 25 20
25
15 15
20 LWA dB(A) 20 LWA dB(A)
10
qV [l/s]
10
qV [l/s] 11
20 25 30 40 50 60 80 100 150 200 250 300 400 20 25 30 40 50 60 80 100 150 200 250 300 400
3 3
qV [m /h] qV [m /h]
80 100 150 200 300 400 500 700 1250 80 100 150 200 300 400 500 700 1250

Hz 63 125 250 500 1K 2K 4K 8K Hz 63 125 250 500 1K 2K 4K 8K


12
Kok 7 5 2 -3 -6 -10 -16 -24 Kok 10 5 2 -4 -5 -10 -15 -23

13
ǻpt [Pa] PCA-315+MBB-200-315-E
250
200
150
50 14
100 45

70 40

50
15
35

30 30

20 25 16
15
20 LWA dB(A)
10
qV [l/s]
20 25 30 40 50 60 80 100 150 200 250 300
qV [m3/h]
17
80 100 150 200 300 400 500 700 1000

Hz 63 125 250 500 1K 2K 4K 8K


18
Kok 13 5 0 -3 -5 -9 -15 -23

We reserve the right to make changes without prior notice 79


lindab | ceili ng dif fusers

Plain diffuser LKA


Dimensions
UxU
1
Ød

50
22
38
AxA 3
LKA Ød A U* Free area A Weight
mm mm mm m2 kg 4
125 235 200 0,011 1,10
160 295 260 0,016 1,80
200 395 360 0,022 2,80
250 495 460 0,033 4,20
5
315 595 560 0,041 5,70
400 595 560 0,042 5,70

Description * U x U = Ceiling grid opening 6


LKA is a square diffuser with an unperforated face plate that
can be used for both supply and exhaust air. LKA is suitable
for the horizontal supply of cooled air where a high impulse 7
is required. It can be equipped with accessories of various
types. Installing an LKA diffuser in a plenum box type MBB
can help to achieve a stable airflow to the diffuser as well as 8
realise the potential for individual adjustment.

• Suitable for both supply and exhaust air


• Suitable for the horizontal supply of cooled air 9
• High impulse
• Option of 1, 2 and 3-way supply air
10
Maintenance
The face plate can be removed to enable cleaning of internal
parts or to gain access to the duct or box. The visible parts 11
of the diffuser can be wiped with a damp cloth.

12

13

14

15

16
Order code
Product LKA aaa
Materials and finish:
Type Material: Galvanised steel
LKA Standard finish: Powder-coated 17
Connection dim. Ød Standard colour: White RAL 9010, gloss 30
Ød 125-400
The diffuser is available in other colours. Please contact 18
Example: LKA-200 Lindab’s sales department for further information.

We reserve the right to make changes without prior notice 81


lindab | ceil ing di ffusers

Plain diffuser LKA


Accessories MBB - Plenum box
1
DRZ - Balancing damper

3
Blending profiles (set)

LKA + MBB
4
10 LxB

10
5

Ød1

C
H
Ød2
6
F E
7
MBZ - Extension piece LKA + MBB
duct LKA B C E F H* L
8 Ød1 mm Ød2 mm mm mm mm mm mm mm
DKZ - Mounting brackets (set) 100 125 260 159 216 50 180 - 220 310
100 160 260 159 216 50 180 - 220 310
125 125 310 184 262 50 205 - 245 376
9 125 160 310 184 262 50 205 - 245 376
125 200 310 184 262 50 205 - 245 376
160 160 380 220 323 50 239 - 279 459
10 160 200 380 220 323 50 239 - 279 459
160 250 380 220 323 50 239 - 279 459
200 200 460 259 396 70 280 - 320 565
200 250 460 259 396 70 280 - 320 565
11 200 315 460 259 396 70 280 - 320 565
250 250 540 309 486 70 330 - 370 698
250 315 540 309 486 70 330 - 370 698
Order code - accessoreies
12 Product aaa bbb
250 400 540 309 486 70 330 - 370 698
315 315 540 373 646 70 395 - 435 858
Type
315 400 540 373 646 70 395 - 435 858
Size
13 * Using accessory MBZ the H dimension will increase:
Example: DRZ-200 Ød2 = 125 - 200 mm => H +40 mm
Ød2 = 250 - 315 mm => H +60 mm
Ød2 = 400 mm => H +80 mm
14 LM - Module plate

Order code
15 Product MBB aaa bbb c
Type
MBB
16 Order code - module plate Duct connection Ød1
Product LM a LKA ccc Ø100-315
Type Diffuser dimension Ød2
Ceiling system Ø125-400
17 Diffuser Function
Size S = Supply air
E = Exhaust
18 Example: LM-1-LKA-200
Ceiling system - see introductory summary. Example: LKA-200+MBB-160-200-S

82 We reserve the right to make changes without prior notice


lindab | ceili ng dif fusers

Plain diffuser LKA


Technical data
1
Capacity Balancing
Air flow qv [l/s] and [m3/h], total pressure Δpt [Pa], throw l0.2 Balancing data is contained in a separate brochure.
[m] and sound power level LWA [dB(A)] can be seen in the
diagrams.
2
Throw l0.2
The throw is specified at a terminal velocity of 0.2 m/s.
Frequency-related sound effect level
The sound effect level in the frequency band is defined as l0.2 [m] LKA 125 160 200 250 315
3
LWA+Kok. Kok values are specified in chart beneath the dia-
10
400

grams on the following pages. 8


7
6 4
5
Quick selection, supply air 4

LKA + MBB Δpt ≥ 50 Pa Δpt ≥ 50 Pa


3
5
duct LKA 30 dB(A) 35 dB(A) 2
Ød1 Ød2 l/s m3/h l/s m3/h
100 125 31 112 38 137 6
l0.2 [m]
100 160 40 144 49 176 1
qV [l/s]
125 125 42 151 50 180 15 20 30 40 50 60 70 100 150 200 300 500
125 160 53 191 64 230 3

125 200 63 227 75 270


60 70 100 150 200 300 500 700 1000 1500
qV [m /h]
7
160 160 60 216 73 263
160 200 70 252 88 317
Correction throw L0.2
160 250 94 338 115 414
LKA Ød 1 - ways 2 - ways 3 - ways
8
200 200 98 353 118 425
125 2.3 1.8 1.3
200 250 106 382 129 464
160 2.3 1.8 1.3
200 315 133 479 159 572
200 2.3 1.9 1.3
9
250 250 116 418 141 508
250 315 136 490 167 601 250 2.3 2 1.3
250 400 139 500 182 655 315 2.3 2 1.3
315 315 153 551 183 659 400 2.2 2.1 1.3 10
315 400 169 608 200 720
Air jet distribution
Sound attenuation lb = Distance from the diffuser to the point where there is 11
Sound attenuation of the diffuser ΔL from duct to room, maximum dispersal.
including end reflection, see table below bv = Depth of the air jet on a vertical plane.
bh = Width of the air jet on a horizontal plane. 12
LKA + MBB
bv

duct LKA Centre frequency Hz lb


Ød1 Ød2 63 125 250 500 1K 2K 4K 8K lb = 0.6 × l02 bv = 0.05 × l02 13
100 125 20 17 6 16 19 20 18 22
100 160 21 17 5 12 19 20 18 21
bh

125 125 17 14 9 19 15 21 18 20
125 160 13 13 9 18 18 18 18 20 lb 14
125 200 14 12 7 15 16 18 17 19 lb = 0.4 × l02 bh = 1.3 × l02
160 160 18 17 11 16 21 19 20 21
160 200 15 14 9 20 21 20 20 20 15
bh

bh

160 250 16 16 7 17 13 18 19 20
200 200 14 11 8 15 21 18 20 18 lb lb
200 250 13 10 8 16 20 17 19 17 lb = 0.5 × l02 bh = 1.0 × l02
200 315 15 9 6 14 17 17 18 17
16
250 250 16 9 9 17 20 19 19 19
250 315 15 8 9 16 18 16 18 18
250 400 13 6 6 14 16 17 17 17 17
315 315 8 10 10 16 20 19 18 23
bh

315 400 8 10 10 13 19 19 17 21
lb lb
lb = 0.5 × l02 bh = 0.4 × l02 18

We reserve the right to make changes without prior notice 83


lindab | ceil ing di ffusers

Plain diffuser LKA


Technical data
1
LKA without box - Supply air LKA 125 + MBB - Supply air

2 ǻpt [Pa] LKA


100
125 160 200 250 315
400
ǻpt [Pa] LKA-125+MBB-125-125-S
250
200
70
150 50
50

3 50
45 100 45

30 40 70 40
35 50 35
20
4 15
30
30
30
25
25
10 20 20
15 20
5 7
LWA dB(A) LWA dB(A)
5 10
qV [l/s] qV [l/s]
30 40 50 60 70 80 100 150 200 300 400 500 15 20 25 30 40 50 60 70 80 100
3
qV [m /h] qV [m3/h]
60 70 80 100 150 200 300
6 150 200 300 400 500 700 1000 1500

Hz 63 125 250 500 1K 2K 4K 8K


Kok 12 6 1 -4 -4 -13 -20 -28
7
ǻpt [Pa] LKA-125+MBB-100-125-S
250
200
8 150
50

45
100
40
70
9 50
35

30

30 25

10 20 20

15
LWA dB(A)
10
qV [l/s]
11 10 15 20 25 30 40 50 60 70 80 100
qV [m3/h]
40 50 60 70 80 100 150 200 300

12 Hz 63 125 250 500 1K 2K 4K 8K


Kok 11 7 3 -4 -5 -14 -18 -24

13

14

15

16

17

18

84 We reserve the right to make changes without prior notice


lindab | ceili ng dif fusers

Plain diffuser LKA


Technical data
1
LKA 160 + MBB - Supply air LKA 200 + MBB - Supply air

ǻpt [Pa] LKA-160+MBB-160-160-S


250
ǻpt [Pa] LKA-200+MBB-200-200-S
250
2
200 200
150 150
50
100
45
100
50
3
45
70 70
40 40
50 35 50
35

30
30
30 30
4
25
25
20 20
20
15 15 20
LWA dB(A) LWA dB(A) 5
10 10
qV [l/s] qV [l/s]
30 40 50 60 70 80 100 120 140 160 50 60 70 80 100 120 140 160 180 200 240
qV [m3/h] qV [m3/h]
150 200 300 400 500 200 300 400 500 700
6
Hz 63 125 250 500 1K 2K 4K 8K Hz 63 125 250 500 1K 2K 4K 8K
Kok 11 11 0 -2 -7 -15 -22 -28 Kok 12 6 -1 -1 -5 -15 -21 -26
7
ǻpt [Pa] LKA-160+MBB-125-160-S ǻpt [Pa] LKA-200+MBB-160-200-S
250 250
200 200 8
50
150 150
45
45
100 100
40
70 70
40 9
35
35
50 50
30
30
30 25 30
25 10
20 20 20 20
15 15
LWA dB(A) LWA dB(A)
10
qV [l/s]
10
qV [l/s] 11
15 20 25 30 40 50 60 70 80 100 125 30 40 50 60 70 80 100 120 140 160
qV [m3/h] qV [m3/h]
60 70 80 100 150 200 300 400 150 200 300 400 500

Hz 63 125 250 500 1K 2K 4K 8K Hz 63 125 250 500 1K 2K 4K 8K


12
Kok 13 8 1 -3 -6 -12 -17 -25 Kok 12 9 0 -2 -6 -12 -19 -24

13
ǻpt [Pa] LKA-160+MBB-100-160-S ǻpt [Pa] LKA-200+MBB-125-200-S
250 250
200 200 50
150
45
150 45 14
40
100 100 40
35
70 70 35

50
30
50 30
15
25
25
30 30
20
20
20 20 16
15 15
LWA dB(A) LWA dB(A)
10 10
qV [l/s] qV [l/s]
10 15 20 25 30 40 50 60 70 80 90
3
qV [m /h]
20 25 30 40 50 60 70 80 100 120 140
qV [m3/h]
17
40 50 60 70 80 100 150 200 300 80 100 150 200 300 400 500

Hz 63 125 250 500 1K 2K 4K 8K Hz 63 125 250 500 1K 2K 4K 8K


18
Kok 12 5 1 -2 -6 -10 -14 -20 Kok 12 7 1 -3 -6 -11 -15 -21

We reserve the right to make changes without prior notice 85


lindab | ceil ing di ffusers

Plain diffuser LKA


Technical data
1
LKA 250 + MBB - Supply air LKA 315 + MBB - Supply air

2 ǻpt [Pa] LKA-250+MBB-250-250-S


250
ǻpt [Pa] LKA-315+MBB-315-315-S
250
200 200
150 150

3 100 50 100 50

70 45 70 45

50 40 50 40

4 30
35
30
35

30 30
20 20
25 25
15 15
5 10
20 LWA dB(A) 20 LWA dB(A)
10
qV [l/s] qV [l/s]
50 60 70 80 100 120 140 160 180 200 240 280 50 60 70 80 90 100 150 200 250 300 350 400
3
qV [m /h] qV [m3/h]
200 300 400 500 700 1000 200 300 400 500 700 1250
6
Hz 63 125 250 500 1K 2K 4K 8K Hz 63 125 250 500 1K 2K 4K 8K
Kok 12 3 -4 0 -4 -17 -24 -31 Kok 13 5 -2 -1 -4 -17 -25 -36
7
ǻpt [Pa] LKA-250+MBB-200-250-S ǻpt [Pa] LKA-315+MBB-250-315-S
250 250
8 200 200
150 150
50
50
100 45 100
45
9 70 40 70
40
50 35 50
35
30
30 30
10 25
30

20 20 25
15 20 15
LWA dB(A) 20 LWA dB(A)
11 10
qV [l/s]
10
qV [l/s]
50 60 70 80 100 120 140 160 180 200 240 50 60 70 80 90 100 150 200 250 300 350 400
qV [m3/h] qV [m3/h]
200 300 400 500 700 200 300 400 500 700 1250

12 Hz 63 125 250 500 1K 2K 4K 8K Hz 63 125 250 500 1K 2K 4K 8K


Kok 12 6 -2 -1 -5 -14 -19 -23 Kok 14 5 -2 -2 -4 -13 -19 -26

13
ǻpt [Pa] LKA-250+MBB-160-250-S ǻpt [Pa] LKA-315+MBB-200-315-S
250 250
200 200
14 150
45
150 50

45
100 40 100
40
70 35 70
15 50 30 50
35

30
25
30 30 25
20
16 20 20 20

15 15
LWA dB(A) LWA dB(A)
10 10
qV [l/s] qV [l/s]
17 30 40 50 60 70 80 100 120 140 160 180
qV [m3/h]
50 60 70 80 100 120 140 160 180 200 240 280
qV [m3/h]
150 200 300 400 500 200 300 400 500 700 1000

18 Hz 63 125 250 500 1K 2K 4K 8K Hz 63 125 250 500 1K 2K 4K 8K


Kok 9 7 -2 -3 -5 -10 -15 -21 Kok 13 6 -2 -3 -4 -11 -17 -22

86 We reserve the right to make changes without prior notice


lindab | ceili ng dif fusers

Plain diffuser LKA


Technical data
1
LKA 400 + MBB - Supply air LKA + MBB - Supply air

ǻpt [Pa] LKA-400+MBB-315-400-S Correction sound power level ( LWA ) 2


250
200
and pressure loss ( Δpt )
150

100 50 LKA + MBB 3


45 duct PKA 1 - ways 2 - ways 3 - ways
70

50
40
Ød1 Ød2 LWA Δpt LWA Δp t LWA Δpt
35
100 125 + 10 x 1.3 +4 x 1.1 +2 x 1,05
30 30
100 160 +5 x 1.1 +2 x 1.05 +1 x1
4
25
20 125 125 + 10 x 1,35 +6 x 1,1 +4 x 1,05
20
15 125 160 + 10 x 1,4 +4 x 1,1 +1 x1

10
LWA dB(A)
125 200 +4 x 1,2 +2 x 1,05 +1 x1 5
qV [l/s]
70 80 90 100 150 200 250 300 350 400
160 160 + 16 x 1,8 +9 x 1,3 +4 x 1,1
qV [m3/h] 160 200 + 16 x 1,7 + 10 x 1,2 +4 x 1,05
300 400 500 700 1250
160 250 + 10 x 1,3 +6 x 1,1 +3 x1 6
200 200 + 17 x 2,3 + 11 x 1,4 +7 x 1,1
Hz 63 125 250 500 1K 2K 4K 8K
200 250 + 13 x 1,8 +6 x 1,2 +4 x 1,1
Kok 14 6 1 -1 -6 -16 -21 -27
200 315 +9 x 1,5 +4 x 1,1 +0 x 1,05
250 250 + 21 x 2,1 + 11 x 1,4 +7 x 1,2
7
250 315 + 19 x 1,8 +7 x 1,2 +3 x 1,1
ǻpt [Pa] LKA-400+MBB-250-400-S
250
250 400 + 10 x 1,5 +6 x 1,2 +0 x1
200 315 315 + 21 x 2,1 + 10 x 1,3 +4 x 1,1 8
150 315 400 + 21 x 1,8 +8 x 1,5 +3 x 1,2
50
100
45
70 40 9
50 35

30
30

20
25 10
20
15
LWA dB(A)
10
50 60 70 80 90 100 150 200 250 300 350 400
qV [l/s] 11
qV [m3/h]
200 300 400 500 700 1250

Hz 63 125 250 500 1K 2K 4K 8K 12


Kok 12 7 0 -2 -6 -12 -19 -26

13

14

15

16

17

18

We reserve the right to make changes without prior notice 87


lindab | ceil ing di ffusers

Plain diffuser LKA


Technical data
1
LKA without box - Exhaust air LKA 125 + MBB - Exhaust air

2 ǻpt [Pa] LKA


100
125 160 200 250 315
400
ǻpt [Pa] LKA-125+MBB-125-125-E
250
50
200
70
150 45
50
3 50
100 40

30 45 35
70
40
20 50 30

4 15
35
30
25
30
10 20
25 20
7
15
5 5
20
LWA dB(A) LWA dB(A)
10
qV [l/s] qV [l/s]
30 40 50 60 70 80 100 150 200 300 400 500 10 15 20 25 30 40 50 60 80 100 120
3
qV [m /h] qV [m3/h]
40 50 60 70 80 100 150 200 300 400
6 150 200 300 400 500 700 1000 1500

Hz 63 125 250 500 1K 2K 4K 8K


Kok 13 4 1 -2 -5 -12 -15 -22
7
ǻpt [Pa] LKA-125+MBB-100-125-E
250
50
200
8 150
45
100
40
70
9 50 35

30 30

10 20 25
15
20 LWA dB(A)
10
qV [l/s]
11 5 10 15 20 25 30 40 50 60 80
qV [m3/h]
20 30 40 50 60 70 80 100 150 200 300

12 Hz 63 125 250 500 1K 2K 4K 8K


Kok 13 0 4 -2 -8 -11 -16 -22

13

14

15

16

17

18

88 We reserve the right to make changes without prior notice


lindab | ceili ng dif fusers

Plain diffuser LKA


Technical data
1
LKA 160 + MBB - Exhaust air LKA 200 + MBB - Exhaust air

ǻpt [Pa] LKA-160+MBB-160-160-E


250
ǻpt [Pa] LKA-200+MBB-200-200-E
250
2
200 200
50
150 150 50
45
100
40
100
45
3
40
70 70
35 35
50 50
30

30
30
30 25
4
25

20 20 20
20
15 15
LWA dB(A)
10
LWA dB(A) 5
10
qV [l/s] qV [l/s]
10 15 20 25 30 40 50 60 80 100 150 200 20 25 30 40 50 60 80 100 150 200 250
qV [m3/h] qV [m3/h]
40 50 60 70 80 100 150 200 300 400 500 700 80 100 150 200 300 400 500 700
6
Hz 63 125 250 500 1K 2K 4K 8K Hz 63 125 250 500 1K 2K 4K 8K
Kok 16 6 1 -4 -5 -11 -17 -24 Kok 14 6 0 -3 -5 -10 -19 -27
7
ǻpt [Pa] LKA-160+MBB-125-160-E ǻpt [Pa] LKA-200+MBB-160-200-E
250 250
200
50
200
50
8
150 45 150 45

40 40
100 100

70 35 70 35 9
50 50 30
30
25
30 25 30
20
10
20 20 20
15 15
LWA dB(A) LWA dB(A)
10
qV [l/s]
10
qV [l/s] 11
10 15 20 25 30 40 50 60 80 100 120 140 10 15 20 25 30 40 50 60 80 100 150 200
qV [m3/h] qV [m3/h]
40 50 60 70 80 100 150 200 300 400 500 40 50 60 70 80 100 150 200 300 400 500 700

Hz 63 125 250 500 1K 2K 4K 8K Hz 63 125 250 500 1K 2K 4K 8K


12
Kok 12 6 2 -2 -7 -12 -14 -19 Kok 16 7 -1 -4 -6 -10 -14 -20

13
ǻpt [Pa] LKA-160+MBB-100-160-E ǻpt [Pa] LKA-200+MBB-125-200-E
250 250
50 50
200 200
150
45
150
45
14
100 100
40 40
70 70

50 35 50
35 15
30
30 30 30
25
20 25 20 16
15 15 20
20 LWA dB(A) LWA dB(A)
10 10
qV [l/s] qV [l/s]
5 10 15 20 25 30 40 50 60 80
3
qV [m /h]
10 15 20 25 30 40 50 60 80 100 120 140
qV [m3/h]
17
20 30 40 50 60 70 80 100 150 200 300 40 50 60 70 80 100 150 200 300 400 500

Hz 63 125 250 500 1K 2K 4K 8K Hz 63 125 250 500 1K 2K 4K 8K


18
Kok 11 -1 5 -2 -9 -13 -18 -24 Kok 11 3 0 -2 -5 -11 -14 -21

We reserve the right to make changes without prior notice 89


lindab | ceil ing di ffusers

Plain diffuser LKA


Technical data
1
LKA 250 + MBB - Exhaust air LKA 315 + MBB - Exhaust air

2 ǻpt [Pa] LKA-250+MBB-250-250-E


250
ǻpt [Pa] LKA-315+MBB-315-315-E
250
200 200
50
150 150
50 45
3 100
45
100
40
70 70
40 35
50 50
35 30
4 30 30 30 25

25 20 20
20
15 20 15
5 LWA dB(A)
10
LWA dB(A)
10
qV [l/s] qV [l/s]
20 25 30 40 50 60 80 100 150 200 250 300 20 25 30 40 50 60 80 100 150 200 250 350 500
qV [m3/h] qV [m3/h]
80 100 150 200 300 400 500 700 1000 80 100 150 200 300 400 500 700 1250 2000
6
Hz 63 125 250 500 1K 2K 4K 8K Hz 63 125 250 500 1K 2K 4K 8K
Kok 12 4 -1 -3 -3 -12 -19 -30 Kok 13 5 2 -2 -6 -12 -17 -27
7
ǻpt [Pa] LKA-250+MBB-200-250-E ǻpt [Pa] LKA-315+MBB-250-315-E
250 250
8 200
50
200
50
150 150
45 45
100 100
40
9 70
40
70
35
35
50 50
30
30
30 30
10 25
25

20 20 20
20
15 15
LWA dB(A) LWA dB(A)
11 10
qV [l/s]
10
qV [l/s]
20 25 30 40 50 60 80 100 150 200 250 20 25 30 40 50 60 80 100 150 200 250 300 400
qV [m3/h] qV [m3/h]
80 100 150 200 300 400 500 700 80 100 150 200 300 400 500 700 1250

12 Hz 63 125 250 500 1K 2K 4K 8K Hz 63 125 250 500 1K 2K 4K 8K


Kok 13 3 -1 -3 -4 -11 -15 -24 Kok 10 5 1 -2 -6 -10 -16 -24

13
ǻpt [Pa] LKA-250+MBB-160-250-E ǻpt [Pa] LKA-315+MBB-200-315-E
250 250
50 50
200 200
14 150 45 150
45

100 40 100
40
70 35 70
15 50
30
50
35

30
30 25 30
25
16 20 20 20
20
15 15
LWA dB(A) LWA dB(A)
10 10
qV [l/s] qV [l/s]
17 10 15 20 25 30 40 50 60 80 100 150 200
3
qV [m /h]
20 25 30 40 50 60 80 100 150 200 250 300
qV [m3/h]
40 50 60 70 80 100 150 200 300 400 500 700 80 100 150 200 300 400 500 700 1000

18 Hz 63 125 250 500 1K 2K 4K 8K Hz 63 125 250 500 1K 2K 4K 8K


Kok 14 6 0 -3 -5 -11 -15 -19 Kok 14 5 0 -2 -6 -12 -14 -22

90 We reserve the right to make changes without prior notice


lindab | ceili ng dif fusers

Plain diffuser LKA


Technical data
1
LKA 400 + MBB - Exhaust air

ǻpt [Pa] LKA-400+MBB-315-400-E


250
2
200
150

100 50 3
70 45

50 40

30
35 4
30
20
25
15
20 LWA dB(A) 5
10
qV [l/s]
20 25 30 40 50 60 80 100 150 200 250 300
qV [m3/h]
80 100 150 200 300 400 500 700 1000
6
Hz 63 125 250 500 1K 2K 4K 8K
Kok 10 5 0 0 -6 -15 -20 -27
7
ǻpt [Pa] LKA-400+MBB-250-400-E
250
200 8
150
50
100
45
70
40
9
50
35

30 30
10
20 25

15 20
LWA dB(A)
10
qV [l/s] 11
20 25 30 40 50 60 80 100 150 200 250 300
3
qV [m /h]
80 100 150 200 300 400 500 700 1250

Hz 63 125 250 500 1K 2K 4K 8K


12
Kok 12 5 1 -1 -7 -12 -16 -24

13

14

15

16

17

18

We reserve the right to make changes without prior notice 91


lindab | ceili ng dif fusers

Plain diffuser LCA


Dimensions
ØU
1
Ød

50
22
37
ØD
3
LCA Ød ØD ØU* Free area A Weight
mm mm mm m2 kg 4
100 240 200 0,010 1,00
125 240 200 0.011 1,00
160 300 260 0.0165 1.50 5
200 360 320 0.023 2.30
250 460 420 0.03 3.40
315 540 500 0.037 4.60
Description 400 540 500 0.037 4.60
6
LCA is a circular diffuser with an unperforated face plate * ØU = Ceiling grid opening
that can be used for both supply and exhaust air. LCA is
suitable for the horizontal supply of cooled air where a high 7
impulse is required. It can be equipped with accessories of
various types in order to achieve optimum function. Install-
ing an LCA diffuser in a plenum box type MBB can help to 8
achieve a stable airflow to the diffuser as well as realise the
potential for individual adjustment.

• Suitable for both supply and exhaust air 9


• Suitable for the horizontal supply of cooled air
• High impulse
• Option of 1, 2 and 3-way supply air 10
• Discrete design

Maintenance 11
The face plate can be removed to enable cleaning of internal
parts or to gain access to the duct or box. The visible parts
of the diffuser can be wiped with a damp cloth.
12

13

14

15

16
Order code
Product LCA aaa
Materials and finish
Material: Galvanised steel
Type
LCA Standard finish: Powder-coated
17
Connection dim. Ød Standard colour: White RAL 9010, gloss 30
Ød 100-400
The diffuser is available in other colours. Please contact 18
Example: LCA-200 Lindab’s sales department for further information.

We reserve the right to make changes without prior notice 93


lindab | ceil ing di ffusers

Plain diffuser LCA


Accessories MBB - Plenum box
1
DRZ - Balancing damper

3
Blending profiles (set)
LCA + MBB
4 10 LxB

10
5

Ød1

C
H
Ød2

6
F E

7 LCA + MBB
MBZ - Extension piece
duct LCA B C E F H* L
Ød1 mm Ød2 mm mm mm mm mm mm mm
8 100 100 260 159 216 50 180 - 220 310
DDZ - Mounting brackets (set) 100 125 260 159 216 50 180 - 220 310
100 160 260 159 216 50 180 - 220 310
125 125 310 184 262 50 205 - 245 376
9
125 160 310 184 262 50 205 - 245 376
125 200 310 184 262 50 205 - 245 376
160 160 380 220 323 50 239 - 279 459
10 160 200 380 220 323 50 239 - 279 459
160 250 380 220 323 50 239 - 279 459
200 200 460 259 396 70 280 - 320 565
11 200 250 460 259 396 70 280 - 320 565
200 315 460 259 396 70 280 - 320 565
250 250 540 309 486 70 330 - 370 698
Order code - accessoreies 250 315 540 309 486 70 330 - 370 698
12 Product aaa bbb 250 400 540 309 486 70 330 - 370 698
Type 315 315 540 373 646 70 395 - 435 858
Size 315 400 540 373 646 70 395 - 435 858
13 * Using accessory MBZ the H dimension will increase:
Example: DRZ-200 Ød2 = 100 - 200 mm => H +40 mm
Ød2 = 250 - 315 mm => H +60 mm
14 LM - Module plate Ød2 = 400 mm => H +80 mm

Order code
15 Product MBB aaa bbb c
Type
MBB
16 Order code - module plate Duct connection Ød1
Product LM a LCA ccc Ø100-315
Type Diffuser dimension Ød2
Ceiling system
17 Diffuser
Ø100-400
Function
Size S = Supply air
E = Exhaust
18 Example: LM-1-LCA-200
Ceiling system - see introductory summary Example: LCA-200+MBB-200-200-S

94 We reserve the right to make changes without prior notice


lindab | ceili ng dif fusers

Plain diffuser LCA


Technical data
1
Capacity Balancing
Air flow qv [l/s] and [m3/h], total pressure Δpt [Pa], throw l0.2 Balancing data is contained in a seperate brochure.
[m] and sound power level LWA [dB(A)] can be seen in the
diagrams.
2
Throw l0.2
The throw is specified at a terminal velocity of 0.2 m/s .
Frequency-related sound effect level
The sound effect level in the frequency band is defined as l0.2 [m] LCA 100 125 160 200 250 315
3
10 400
LWA+Kok. Kok values are specified in charts beneath the dia- 8
grams on the following pages. 7
6
4
Quick selection, supply air 5

4
LCA + MBB Δpt ≥ 50 Pa Δpt ≥ 50 Pa
3
duct LCA 30 dB(A) 35 dB(A) 5
Ød1 Ød2 l/s m3/h l/s m3/h 2
100 100 27 97 33 119
100 125 31 112 38 137
l0.2 [m]
6
100 160 40 144 49 176
1
qV [l/s]
125 125 42 151 50 180
15 20 30 40 50 60 70 100 150 200 300 500
125 160 53 191 64 230 qV [m3/h]
125 200 59 212 70 252
60 70 100 150 200 300 500 700 1000 1500 7
160 160 60 216 73 263 Correction throw l0.2
160 200 70 252 88 317
LCA Ød 1 - ways 2 - ways 3 - ways
160 250 94 338 115 414
100 2.4 1.8 1.4
8
200 200 98 353 118 425
200 250 106 382 129 464 125 2.3 1.8 1.3
200 315 133 479 159 572 160 2.3 1.8 1.3
250 250 116 418 141 508 200 2.3 1.9 1.3 9
250 315 136 490 167 601 250 2.3 2 1.3
250 400 139 500 182 655 315 2.3 2 1.3
315 315 153 551 183 659 400 2.2 2.1 1.3 10
315 400 169 608 200 720
Air jet distribution
lb = Distance from the diffuser to the point where there is
Sound attenuation maximum dispersal. 11
Sound attenuation of the diffuser ΔL from duct to room, bv = Depth of the air jet on a vertical plane.
including end reflection, see table below. bh = Width of the air jet on a horizontal plane.

LCA + MBB 12
bv

duct LCA Centre frequency Hz lb


lb = 0.6 × l02 bv = 0.05 × l02
Ød1 Ød2 63 125 250 500 1K 2K 4K 8K
100 100 18 17 9 19 20 23 22 23 13
100 125 20 17 6 16 19 20 18 22
bh

100 160 21 17 5 12 19 20 18 21
lb
125 125 17 14 9 19 15 21 18 20
lb = 0.4 × l02 bh = 1.3 × l02
14
125 160 13 13 9 18 18 18 18 20
125 200 14 12 7 15 16 18 17 19
160 160 18 17 11 16 21 19 20 21
bh

bh

160 200 15 14 9 20 21 20 20 20 15
lb lb
160 250 16 16 7 17 13 18 19 20
lb = 0.5 × l02 bh = 1.0 × l02
200 200 14 11 8 15 21 18 20 18
200 250 13 10 8 16 20 17 19 17 16
200 315 15 9 6 14 17 17 18 17
250 250 16 9 9 17 20 19 19 19
250 315 15 8 9 16 18 16 18 18
250 400 13 6 6 14 16 17 17 17
17
bh
bh

315 315 8 10 10 16 20 19 18 23 lb lb
315 400 8 10 10 13 19 19 17 21 lb = 0.5 × l02 bh = 0.4 × l02
18

We reserve the right to make changes without prior notice 95


lindab | ceil ing di ffusers

Plain diffuser LCA


Technical data
1
LCA without box - Supply air LCA 100 + MBB - Supply air

2 ǻpt [Pa] LCA


150
100 125 160 200 250 315
400
ǻpt [Pa] LCA-100+MBB-100-100-S
250
200
100 50
50 150
70 45
3 50 40
45
100
40
70
35
30 35
30 50

4 20 25
30
30

15
20 25

10 20 20
15
5 7
LWA dB(A) LWA dB(A)
5 10
qV [l/s] qV [l/s]
20 30 40 50 60 70 80 100 150 200 300 400 500 5 10 15 20 25 30 40 50 60 70
qV [m3/h] qV [m3/h]
80 100 150 200 300 400 500 700 1000 1500 20 30 40 50 60 70 80 100 150 200
6
Hz 63 125 250 500 1K 2K 4K 8K
Kok 9 7 3 -5 -5 -12 -16 -23
7

10

11

12

13

14

15

16

17

18

96 We reserve the right to make changes without prior notice


lindab | ceili ng dif fusers

Plain diffuser LCA


Technical data
1
LCA 125 + MBB - Supply air LCA 160 + MBB - Supply air

ǻpt [Pa] LCA-125+MBB-125-125-S ǻpt [Pa] LCA-160+MBB-160-160-S


250 250 2
200 200

150 150
50
50
100 45 100
45 3
70 40 70
40
50 35 50
35

30
30
30
30 4
25 25
20 20
20
15 20 15

10
LWA dB(A)
10
LWA dB(A) 5
qV [l/s] qV [l/s]
15 20 25 30 40 50 60 70 80 100 30 40 50 60 70 80 100 120 140 160
qV [m3/h] qV [m3/h]
60 70 80 100 150 200 300 150 200 300 400 500
6
Hz 63 125 250 500 1K 2K 4K 8K Hz 63 125 250 500 1K 2K 4K 8K
Kok 12 6 1 -4 -4 -13 -20 -28 Kok 11 11 0 -2 -7 -15 -22 -28
7
ǻpt [Pa] LCA-125+MBB-100-125-S ǻpt [Pa] LCA-160+MBB-125-160-S
250 250
200
50
200
50
8
150 150
45 45
100 100
40 40
70
35
70
35
9
50 50
30 30

30 25 30 25

20 20 20 20
10
15 15
LWA dB(A) LWA dB(A)
10 10
10 15 20 25 30 40 50 60 70
qV [l/s]
15 20 25 30 40 50 60 70 80 100 125
qV [l/s] 11
qV [m3/h] qV [m3/h]
40 50 60 70 80 100 150 200 60 70 80 100 150 200 300 400

Hz 63 125 250 500 1K 2K 4K 8K Hz 63 125 250 500 1K 2K 4K 8K 12


Kok 11 7 3 -4 -5 -14 -18 -24 Kok 13 8 1 -3 -6 -12 -17 -25

13
¨pt [Pa] LCA-160+MBB-100-160-S
250
200
45
150
40
14
100
35
70

50
30
15
25
30
20
20
15
16
LWA dB(A)
10
qV [l/s]
10 15 20 25 30 40 50 60 70 80 90
qV [m3/h] 17
40 50 60 70 80 100 150 200 300

Hz 63 125 250 500 1K 2K 4K 8K


Kok 12 5 1 -2 -6 -10 -14 -20
18

We reserve the right to make changes without prior notice 97


lindab | ceil ing di ffusers

Plain diffuser LCA


Technical data
1
LCA 200 + MBB - Supply air LCA 250 + MBB - Supply air

ǻpt [Pa] LCA-200+MBB-200-200-S ǻpt [Pa] LCA-250+MBB-250-250-S


2 250 250
200 200
150 150
50
3 100
45
100 50

70 70 45
40
50 50 40
35
4 30 30 30
35

30
25
20 20
25
15 20 15
5 10
LWA dB(A)
10
20 LWA dB(A)
qV [l/s] qV [l/s]
50 60 70 80 100 120 140 160 180 200 240 50 60 70 80 100 120 140 160 180 200 240 280
qV [m3/h] qV [m3/h]
200 300 400 500 700 200 300 400 500 700 1000
6
Hz 63 125 250 500 1K 2K 4K 8K Hz 63 125 250 500 1K 2K 4K 8K
Kok 12 6 -1 -1 -5 -15 -21 -26 Kok 12 3 -4 0 -4 -17 -24 -31
7
ǻpt [Pa] LCA-200+MBB-160-200-S ǻpt [Pa] LCA-250+MBB-200-250-S
250 250
8 200 200
150 150
50
45
100 100 45

9 70
40
70 40
35
50 50 35
30
30
30 30
10 20
25

20
25
20
15 15 20
LWA dB(A) LWA dB(A)
10 10
11 30 40 50 60 70 80 100 120 140 160
qV [l/s]
50 60 70 80 100 120 140 160 180 200 240
qV [l/s]

qV [m3/h] qV [m3/h]
150 200 300 400 500 200 300 400 500 700

12 Hz 63 125 250 500 1K 2K 4K 8K Hz 63 125 250 500 1K 2K 4K 8K


Kok 12 9 0 -2 -6 -12 -19 -24 Kok 12 6 -2 -1 -5 -14 -19 -23

13
ǻpt [Pa] LCA-200+MBB-125-200-S ǻpt [Pa] LCA-250+MBB-160-250-S
250 250
200 50 200

14 150 45 150
45
100 40 100 40

70 35 70 35
15 50 30 50 30
25 25
30 30
20 20
16 20
15
20
15
LWA dB(A) LWA dB(A)
10 10
qV [l/s] qV [l/s]
20 25 30 40 50 60 70 80 100 120 140 30 40 50 60 70 80 100 120 140 160 180
17 qV [m3/h] qV [m3/h]
80 100 150 200 300 400 500 150 200 300 400 500

Hz 63 125 250 500 1K 2K 4K 8K Hz 63 125 250 500 1K 2K 4K 8K


18 Kok 12 7 1 -3 -6 -11 -15 -21 Kok 9 7 -2 -3 -5 -10 -15 -21

98 We reserve the right to make changes without prior notice


lindab | ceili ng dif fusers

Plain diffuser LCA


Technical data
1
LCA 315 + MBB - Supply air LCA 400 + MBB - Supply air

ǻpt [Pa] LCA-315+MBB-315-315-S ǻpt [Pa] LCA-400+MBB-315-400-S


250 250
2
200 200
150 150

100 50 100 50
3
45 45
70 70
40
50 40 50
35

30
35
30 30 4
30
25
20 20
25 20
15 15

10
20 LWA dB(A)
10
LWA dB(A) 5
qV [l/s] qV [l/s]
50 60 70 80 90 100 150 200 250 300 350 400 70 80 90 100 150 200 250 300 350 400
qV [m3/h] qV [m3/h]
200 300 400 500 700 1250 300 400 500 700 1250

Hz 63 125 250 500 1K 2K 4K 8K


6
Hz 63 125 250 500 1K 2K 4K 8K
Kok 14 6 1 -1 -6 -16 -21 -27
Kok 13 5 -2 -1 -4 -17 -25 -36
ǻpt [Pa] LCA-400+MBB-250-400-S
250
7
200
ǻpt [Pa] LCA-315+MBB-250-315-S 150
250 50
200 100
45
8
150 70
50 40
100 50 35
45
70
40 30
30 9
50 25
35 20
20
30 15
30

20 10
LWA dB(A) 10
25 qV [l/s]
15 50 60 70 80 90 100 150 200 250 300 350 400
20 LWA dB(A) qV [m3/h]
10 200 300 400 500 700 1250

50 60 70 80 90 100 150 200 250 300 350 400


qV [l/s]
Hz 63 125 250 500 1K 2K 4K 8K
11
qV [m3/h]
200 300 400 500 700 1250 Kok 12 7 0 -2 -6 -12 -19 -26

Hz 63 125 250 500 1K 2K 4K 8K Correction sound power level (LWA) and pressure loss (Δpt) 12
Kok 14 5 -2 -2 -4 -13 -19 -26
LCA + MBB
duct LCA 1 - ways 2 - ways 3 - ways
Ød1 Ød2 LWA Δpt LWA Δpt LWA Δpt
13
ǻpt [Pa] LCA-315+MBB-200-315-S
250 100 100 + 12 x 1,5 +8 x 1,2 +4 x 1,1
200 100 125 + 10 x 1.3 +4 x 1.1 +2 x 1,05
150 50
100 160 +9 x 1.3 +2 x 1.1 +1 x1 14
45
100 125 125 + 12 x 1,5 +8 x 1,2 +4 x 1,1
40
70 125 160 + 14 x 1,5 +7 x 1,2 +2 x 1,1
35
50
125 200 +9 x 1,4 +6 x 1,2 +3 x 1,1 15
30 160 160 + 16 x 1,8 +9 x 1,3 +4 x 1,1
30 25 160 200 + 21 x 1,9 + 10 x 1,3 +4 x 1,1
20 160 250 + 12 x 1,4 +6 x 1,1 +2 x 1,05
20
15 200 200 + 24 x 2,5 + 10 x 1,5 +5 x 1,2
16
LWA dB(A) 200 250 + 18 x 1,9 +7 x 1,2 +2 x 1,05
10
qV [l/s] 200 315 + 17 x 1,6 +9 x 1,2 +3 x 1,1
50 60 70 80 100 120 140 160 180 200 240 280
qV [m3/h] 250 250 + 21 x 2,3 + 10 x 1,4 +5 x 1,1 17
200 300 400 500 700 1000
250 315 + 20 x 1,9 + 11 x 1,2 +5 x 1,2
250 400 + 10 x 1,5 +6 x 1,2 +0 x1
Hz 63 125 250 500 1K 2K 4K 8K 315 315 + 21 x 2,4 + 12 x 1,6 +6 x 1,2
Kok 13 6 -2 -3 -4 -11 -17 -22 315 400 + 21 x 1,8 +8 x 1,5 +3 x 1,2
18

We reserve the right to make changes without prior notice 99


lindab | ceil ing di ffusers

Plain diffuser LCA


Technical data
1
LCA without box - Exhaust air LCA 100 + MBB - Exhaust air

2 ǻpt [Pa] LCA


150
100 125 160 200 250 315 ǻpt [Pa] LCA-100+MBB-100-100-E
250
400
200 45
100
50 150
70 40
3 50
40
45
100
35
30 35 70

20 30 50 30

4 15 25
30
25
10 20

7 20 20

5 15
5 4 LWA dB(A) LWA dB(A)
3 10
qV [l/s] qV [l/s]
20 30 40 50 60 70 80 100 150 200 300 400 500 5 10 15 20 25 30 40 50 60 80
qV [m3/h] qV [m3/h]
80 100 150 200 300 400 500 700 1000 1500 20 30 40 50 60 70 80 100 150 200
6
Hz 63 125 250 500 1K 2K 4K 8K
Kok 13 1 3 -2 -7 -10 -15 -22
7

10

11

12

13

14

15

16

17

18

100 We reserve the right to make changes without prior notice


lindab | ceili ng dif fusers

Plain diffuser LCA


Technical data
1
LCA 125 + MBB - Exhaust air LCA 160 + MBB - Exhaust air

ǻpt [Pa] LCA-125+MBB-125-125-E


250
¨pt [Pa] LCA-160+MBB-160-160-E
250
2
50
200 200
50
150 45 150
45
100 40 100
40
3
70 35 70
35
50 30 50

30
25
30
30
4
25
20
20 20 20
15 15
LWA dB(A) LWA dB(A) 5
10 10
qV [l/s] qV [l/s]
10 15 20 25 30 40 50 60 80 100 120 140 10 15 20 25 30 40 50 60 80 100 150 200
qV [m3/h] qV [m3/h]
40 50 60 70 80 100 150 200 300 400 500 40 50 60 70 80 100 150 200 300 400 500 700
6
Hz 63 125 250 500 1K 2K 4K 8K Hz 63 125 250 500 1K 2K 4K 8K
Kok 13 4 1 -2 -5 -12 -15 -22 Kok 16 6 1 -4 -5 -11 -17 -24
7
ǻpt [Pa] LCA-125+MBB-100-125-E ǻpt [Pa] LCA-160+MBB-125-160-E
250 250
200
50
200
50
8
150 150 45
45
100 100 40

70
40
70 35 9
50 35 50
30

30 30 30 25
10
20 25 20 20
15 15
20 LWA dB(A) LWA dB(A)
10
qV [l/s]
10
qV [l/s] 11
5 10 15 20 25 30 40 50 60 80 10 15 20 25 30 40 50 60 80 100 120 140
3
qV [m /h] qV [m3/h]
20 30 40 50 60 70 80 100 150 200 300 40 50 60 70 80 100 150 200 300 400 500

Hz 63 125 250 500 1K 2K 4K 8K Hz 63 125 250 500 1K 2K 4K 8K


12
Kok 13 0 4 -2 -8 -11 -16 -22 Kok 12 6 2 -2 -7 -12 -14 -19

13
ǻpt [Pa] LCA-160+MBB-100-160-E
250
50
200
150
45
14
100
40
70

50 35
15
30 30

20 25 16
15
20 LWA dB(A)
10
qV [l/s]
5 10 15 20 25 30 40 50 60 80
qV [m3/h]
17
20 30 40 50 60 70 80 100 150 200 300

Hz 63 125 250 500 1K 2K 4K 8K


18
Kok 11 -1 5 -2 -9 -13 -18 -24

We reserve the right to make changes without prior notice 101


lindab | ceil ing di ffusers

Plain diffuser LCA


Technical data
1
LCA 200 + MBB - Exhaust air LCA 250 + MBB - Exhaust air

2 ǻpt [Pa] LCA-200+MBB-200-200-E


250
ǻpt [Pa] LCA-250+MBB-250-250-E
250
200 200
150 50 150
50
3 100
45
100
45
40
70 70
35 40
50 50
30 35
4 30 30 30
25

20 25
20 20
15 15 20
5 LWA dB(A) LWA dB(A)
10 10
qV [l/s] qV [l/s]
20 25 30 40 50 60 80 100 150 200 250 20 25 30 40 50 60 80 100 150 200 250 300
qV [m3/h] qV [m3/h]
80 100 150 200 300 400 500 700 80 100 150 200 300 400 500 700 1000
6
Hz 63 125 250 500 1K 2K 4K 8K Hz 63 125 250 500 1K 2K 4K 8K
Kok 14 6 0 -3 -5 -10 -19 -27 Kok 12 4 -1 -3 -3 -12 -19 -30
7
ǻpt [Pa] LCA-200+MBB-160-200-E ǻpt [Pa] LCA-250+MBB-200-250-E
250 250
8 200
50
200
50
150 45 150
45
40
100 100
9 70 35 70
40

35
50 30 50
30
25
30 30
10 20
25
20 20
20
15 15
LWA dB(A) LWA dB(A)
11 10
qV [l/s]
10
qV [l/s]
10 15 20 25 30 40 50 60 80 100 150 200 20 25 30 40 50 60 80 100 150 200 250
qV [m3/h] qV [m3/h]
40 50 60 70 80 100 150 200 300 400 500 700 80 100 150 200 300 400 500 700

12 Hz 63 125 250 500 1K 2K 4K 8K Hz 63 125 250 500 1K 2K 4K 8K


Kok 16 7 -1 -4 -6 -10 -14 -20 Kok 13 3 -1 -3 -4 -11 -15 -24

13
ǻpt [Pa] LCA-200+MBB-125-200-E ǻpt [Pa] LCA-250+MBB-160-250-E
250 250
50
200 50 200
14 150
45
150 45

100 100 40
40
70 70 35
15 50
35
50
30
30
30 30 25
25
16 20 20 20

15 20 15
LWA dB(A) LWA dB(A)
10 10
qV [l/s] qV [l/s]
17 10 15 20 25 30 40 50 60 80 100 120 140
qV [m3/h]
10 15 20 25 30 40 50 60 80 100 150 200
qV [m3/h]
40 50 60 70 80 100 150 200 300 400 500 40 50 60 70 80 100 150 200 300 400 500 700

18 Hz 63 125 250 500 1K 2K 4K 8K Hz 63 125 250 500 1K 2K 4K 8K


Kok 11 3 0 -2 -5 -11 -14 -21 Kok 14 6 0 -3 -5 -11 -15 -19

102 We reserve the right to make changes without prior notice


lindab | ceili ng dif fusers

Plain diffuser LCA


Technical data
1
LCA 315 + MBB - Exhaust air LCA 400 + MBB - Exhaust air

ǻpt [Pa] LCA-315+MBB-315-315-E


250
ǻpt [Pa] LCA-400+MBB-315-400-E
250
2
200 50 200
150 150
45
100
40
100 50 3
70 70 45
35
50 50 40
30

30 25 30
35 4
30
20 20 20
25
15 15
LWA dB(A) 20 LWA dB(A) 5
10 10
qV [l/s] qV [l/s]
20 25 30 40 50 60 80 100 150 200 250 350 500 20 25 30 40 50 60 80 100 150 200 250 300
qV [m3/h] qV [m3/h]
80 100 150 200 300 400 500 700 1250 2000 80 100 150 200 300 400 500 700 1000
6
Hz 63 125 250 500 1K 2K 4K 8K Hz 63 125 250 500 1K 2K 4K 8K
Kok 13 5 2 -2 -6 -12 -17 -27 Kok 10 5 0 0 -6 -15 -20 -27
7
ǻpt [Pa] LCA-315+MBB-250-315-E ǻpt [Pa] LCA-400+MBB-250-400-E
250 250
200
50
200 8
150 150
45 50
100 100
40 45
70 70
40
9
35
50 50
30 35

30 30 30
25
10
20 20 20 25

15 15 20
LWA dB(A) LWA dB(A)
10
qV [l/s]
10
qV [l/s] 11
20 25 30 40 50 60 80 100 150 200 250 300 400 20 25 30 40 50 60 80 100 150 200 250 300
3 3
qV [m /h] qV [m /h]
80 100 150 200 300 400 500 700 1250 80 100 150 200 300 400 500 700 1250

Hz 63 125 250 500 1K 2K 4K 8K Hz 63 125 250 500 1K 2K 4K 8K


12
Kok 10 5 1 -2 -6 -10 -16 -24 Kok 12 5 1 -1 -7 -12 -16 -24

13
ǻpt [Pa] LCA-315+MBB-200-315-E
250
200 50

150
45
14
100
40
70

50
35 15
30
30
25
20
20
16
15
LWA dB(A)
10
qV [l/s]
20 25 30 40 50 60 80 100 150 200 250 300
qV [m3/h]
17
80 100 150 200 300 400 500 700 1000

Hz 63 125 250 500 1K 2K 4K 8K


18
Kok 14 5 0 -2 -6 -12 -14 -22

We reserve the right to make changes without prior notice 103


li ndab | ceiling diffusers

Plain diffuser CRL


Dimensions
ØU
1
Ød

C
3

B
ØE
ØA

CRL Ød ØA B C ØE ØU* Weight


4
mm mm mm mm mm mm kg
100 188 15 60 146 170 0.30
125 238 20 65 180 210 0.50 5
160 288 25 65 220 255 0.60
200 388 28 72 300 355 1.10

Description
250 488 33 82 380 390 1.60 6
315 588 33 97 490 465 2.50
CRL is a circular diffuser with an unperforated adjustable 400 720 40 100 590 670 3.80
face plate. CRL can be used both for supply and exhaust
air. The diffuser can be switched between horizontal and * ØU = Ceiling grid opening 7
vertical supply air, and is therefore suitable for the horizontal
supply of cooled air or vertical supply of heated air. Install- Dispersal patterns
ing a CRL diffuser in a plenum box type MBB can help to CRL is supplied with vertical supply air as standard. 8
achieve a stable airflow to the diffuser as well as realise the The dispersal pattern can be changed to horizontal supply
potential for individual adjustment. It is also possible to air by moving the face plate.
install a damper directly in the diffuser to enable adjustment
without a box. 9
• Suitable for both supply and exhaust air
• Suitable for horizontal or vertical supply air patterns 10
• A damper can be installed on the diffuser to achieve
adjustment
11
Maintenance Vertical supply air.
The face plate can be removed to enable cleaning of internal
parts or to gain access to the duct or plenum box. The visi-
ble parts off the diffuser can be wiped with a damp cloth.
12

13

Horizontal supply air. 14

15

Materials and finish:


16
Order code
Product CRL aaa Grille box: Aluminium
Type Face plate: Galvanised steel
CRL Standard finish: Powder-coated 17
Connection dim. Ød Standard colour: White RAL 9010, gloss 30
Ød 100-400
The diffuser is available in other colours. Please contact 18
Example: CRL-200 Lindab’s sales department for further information.

We reserve the right to make changes without prior notice 105


lindab | ceil ing di ffusers

Plain diffuser CRL


Accessories MBB - Plenum box
1
CAZ - Balancing damper

3
MBZ - Extension piece CRL + MBB

4 10 LxB

DCZ - Mounting brackets (set) 10

Ød1

C
H
Ød2

6
F E

7 CRL + MBB
duct CRL B C E F H* L
Ød1 mm Ød2 mm mm mm mm mm mm mm
8 100 100 260 159 216 50 175 - 210 310
Order code - accessoreies 100 125 260 159 216 50 175 - 205 310
100 160 260 159 216 50 175 - 205 310
Product aaa bbb 125 125 310 184 262 50 200 - 230 376
9 Type 125 160 310 184 262 50 200 - 230 376
Size 125 200 310 184 262 50 210 - 245 376
160 160 380 220 323 50 235 - 265 459
10 Example: CAZ-125 160 200 380 220 323 50 245 - 280 459
160 250 380 220 323 50 250 - 290 459
200 200 460 259 396 70 285 - 320 565

11 200 250 460 259 396 70 290 - 332 565


200 315 460 259 396 70 290 - 345 565
250 250 540 309 486 70 340 - 380 698
250 315 540 309 486 70 340 - 395 698
12 250 400 540 309 486 70 370 - 400 698
315 315 540 373 646 70 405 - 460 858
315 400 540 373 646 70 435 - 465 858
13 USING CRL + MBB => ALWAYS USE MBZ
* Using accessory MBZ the H dimension will increase:
Ød2 = 100 - 200 mm => H +40 mm
14 Ød2 = 250 - 315 mm => H +60 mm
Ød2 = 400 mm => H +80 mm

Order code
15 Product MBB aaa bbb c
Type
MBB
16 Duct connection Ød1
Ø100-315
Diffuser dimension Ød2
17 Ø100-400
Function
S = Supply air
E = Exhaust
18
Example: CRL-200+MBB-160-200-S

106 We reserve the right to make changes without prior notice


li ndab | ceiling diffusers

Plain diffuser CRL


Technical data
1
Capacity Throw l0.2
Air flow qv [l/s] and [m3/h], total pressure Δpt [Pa], throw l0.2 The throw is specified at a terminal velocity of 0.2 m/s.
[m] and sound power level LWA [dB(A)] can be seen in the Diagram below shows throw l0.2 for horizontal supply air.
diagrams.
2
CRL 125 200 315
l0.2 [m] 100 160 250 400
Frequency-related sound effect level 10

The sound effect level in the frequency band is defined as


8 3
7
LWA+Kok. Kok values are specified in charts beneath the 6

diagrams on the following pages. Kok values for CRL without 5

a box are available on request. 4 4


3

Quick selection, supply air


2
5
CRL + MBB Δpt ≥ 50 Pa Δpt ≥ 50 Pa
duct CRL 30 dB(A) 35 dB(A) l0.2 [m]
1
Ød1 Ød2 l/s m3/h l/s m3/h
15 20 30 40 50 60 70 100 150 200 300 400 500
qV [l/s]
6
100 100 26 94 31 112 qV [m3/h]
100 125 35 126 42 151 60 70 100 150 200 300 500 700 900 1500 2000

100 160 42 151 50 180


125 125 46 166 54 194 7
125 160 58 209 68 245 Correction throw l0.2 for vertical supply air
125 200 62 223 75 270
CRL Ød Correction factor
160 160 67 241 81 292 8
160 200 86 310 105 378 100 3,1
160 250 96 346 121 436 125 2,7
200 200 107 385 127 457 160 2,7
200 250 135 486 160 576 200 2,7
9
200 315 146 526 177 637 250 2,6
250 250 151 544 183 659
315 2,4
250 315 161 580 215 774
400 2,3 10
250 400 185 666 252 907
315 315 206 742 263 947
315 400 227 817 309 1112
Air jet distribution 11
Sound attenuation lb = Distance from the diffuser to the point where there is
maximum dispersal.
Sound attenuation of the diffuser ΔL from duct to room,
bv = Depth of the air jet on a vertical plane. 12
including end reflection, see table below.
bh = Width of the air jet on a horizontal plane
CRL + MBB
duct CRL Centre frequency Hz Horizontal supply air pattern 13
Ød1 Ød2 63 125 250 500 1K 2K 4K 8K
100 100 20 17 7 20 19 20 20 22
bv

100 125 21 16 6 18 19 18 19 21
100 160 21 16 5 15 17 18 18 18
lb 14
lb = 0,6 × l0,2 bv = 0,05 × l0,2
125 125 18 13 7 20 12 19 19 20
125 160 15 14 8 19 12 17 17 19
125 200 14 12 6 16 14 16 17 16 15
160 160 18 17 10 18 16 18 21 20 Vertical supply air pattern
160 200 15 14 7 19 17 18 19 19
160 250 15 15 4 15 13 14 16 18
200 200 14 10 7 14 19 16 20 17
lb = 0,7 × l0,2 16
200 250 15 9 5 14 19 16 17 16
lb

200 315 13 8 4 11 16 15 16 15
250 250 16 8 7 16 18 18 18 17 17
250 315 11 7 6 16 17 17 16 16
250 400 15 6 5 10 14 16 15 15
315 315 8 10 9 14 18 18 17 21 18
bh bh = 0,3 × l0,2
315 400 8 8 8 11 16 17 16 19

We reserve the right to make changes without prior notice 107


lindab | ceil ing di ffusers

Plain diffuser CRL


Technical data
1
Throw l0.2 / turning point l0.0 CRL without box - Supply air
Throw l0.2 [m] is specified at a speed of 0.2 m/s. Turning
2 point l0.0 [m] is specified for +5 K, +10 K respectively.
Supply air - horizontal

L;M= #2 , ISOTERM        ǻpt [Pa] CRL 100 125 160 200 250 315
 150
3 
 100 400
 50
70

45
4 
50
40
 30
35
20
5 
15
30

25
10
L;M= 20 LWA dB(A)
6 
           
Q6 ;LS=
7
30 40 50 60 70 100 150 200 300 400 500 700
qV [l/s]
1200
Q6 ;MH= 3
qV [m /h]
            150 200 300 400 500 700 1000 1500 2000 3000

7 Supply air - vertical

l0.0 [m] CRL +5K 100 160 200 250 315 400 ǻpt [Pa] CRL 100 125 160 200 250 315
8 10

8
150

7 100 400
6 50
70
5 45
9 4 50
40

3 35
30
30
10 2 20
25
15
20
10
l0.0 [m] LWA dB(A)
11 1
qV [l/s] 7
qV [l/s]
10 15 20 30 40 50 60 70 100 150 200 300 400
3
15 20 30 40 50 60 70 100 150 200 300 400 500 700
qV [m /h] 3
qV [m /h]
40 50 60 70 100 150 200 300 500 700 1000
70 100 150 200 300 400 500 700 1000 1500 2000

12
l0.0 [m] CRL +10K 100 160 200 250 315 400
10

13 8
7
6
5

14 4

15 2

l0.0 [m]
1
16 10 15 20 30 40 50 60 70 100 150 200 300
qV [l/s]
400
3
qV [m /h]
40 50 60 70 100 150 200 300 500 700 1000

17

18

108 We reserve the right to make changes without prior notice


li ndab | ceiling diffusers

Plain diffuser CRL


Technical data
1
CRL 100 + MBB - Supply air CRL 125 + MBB - Supply air

ǻpt [Pa] CRL-100+MBB-100-100-S ǻpt [Pa] CRL-125+MBB-125-125-S


250 250
2
200 200
150 50 150 50

100 45 100 45
3
40 40
70 70
35 35
50 50
30
30
30
30 25
4
25
20
20 20
20
15 15

10
LWA dB(A)
10
LWA dB(A) 5
qV [l/s] qV [l/s]
5 10 15 20 25 30 40 50 60 70 15 20 25 30 40 50 60 70 80 100
qV [m3/h] qV [m3/h]
20 30 40 50 60 70 80 100 150 200 60 70 80 100 150 200 300
6
Hz 63 125 250 500 1K 2K 4K 8K Hz 63 125 250 500 1K 2K 4K 8K
Kok 12 8 5 -7 -8 -14 -17 -22 Kok 11 9 3 -5 -6 -14 -20 -24
7
ǻpt [Pa] CRL-125+MBB-100-125-S
250
200
50 8
150
45
100 40

70 35 9
50 30

25
30

20
20 10
15
LWA dB(A)
10
10 15 20 25 30 40 50 60 70 80 100
qV [l/s]
11
qV [m3/h]
40 50 60 70 80 100 150 200 300

Hz 63 125 250 500 1K 2K 4K 8K 12


Kok 13 8 3 -5 -7 -11 -15 -19

13

14

15

16

17

18

We reserve the right to make changes without prior notice 109


lindab | ceil ing di ffusers

Plain diffuser CRL


Technical data
1
CRL 160 + MBB - Supply air CRL 200 + MBB - Supply air

ǻpt [Pa] CRL-160+MBB-160-160-S ǻpt [Pa] CRL-200+MBB-200-200-S


2 250 250
200 200

150 150
50
50
3 100
45
100 45

70 70 40
40
50 35 50 35

4 30
30
30
30
25
25
20 20
20
20
15 15
5 10
LWA dB(A)
10
LWA dB(A)
qV [l/s] qV [l/s]
30 40 50 60 70 80 100 120 140 160 50 60 70 80 100 120 140 160 180 200 240
qV [m3/h] qV [m3/h]
150 200 300 400 500 200 300 400 500 700
6
Hz 63 125 250 500 1K 2K 4K 8K Hz 63 125 250 500 1K 2K 4K 8K
Kok 11 12 3 -7 -7 -15 -20 -23 Kok 12 11 1 -3 -7 -15 -20 -24
7
ǻpt [Pa] CRL-160+MBB-125-160-S ǻpt [Pa] CRL-200+MBB-160-200-S
250 250
8 200
50
200
150 150
45 45
100 100
40 40
9 70
35
70
35
50 50
30 30
25
30 30 25
10 20
20
20 20

15 15
LWA dB(A) LWA dB(A)
10 10
11 20 25 30 40 50 60 70 80 100 120
qV [l/s]
30 40 50 60 70 80 100 120 140 160
qV [l/s]

qV [m3/h] qV [m3/h]
80 100 150 200 300 400 150 200 300 400 500

12 Hz 63 125 250 500 1K 2K 4K 8K Hz 63 125 250 500 1K 2K 4K 8K


Kok 12 8 3 -5 -6 -11 -17 -22 Kok 12 8 1 -4 -5 -10 -18 -22

13
ǻpt [Pa] CRL-160+MBB-100-160-S ǻpt [Pa] CRL-200+MBB-125-200-S
250 250
200 200
45 50
14 150
40
150
45
100 100
40
35
70 70
35
30
15 50 50
30
25

30 30 25
20
20
16 20
15
20
15
LWA dB(A) LWA dB(A)
10 10
qV [l/s] qV [l/s]
10 15 20 25 30 40 50 60 70 80 100 20 25 30 40 50 60 70 80 100 120 140
17 40 50 60 70 80 100 150 200 300
qV [m3/h] qV [m3/h]
80 100 150 200 300 400 500

Hz 63 125 250 500 1K 2K 4K 8K Hz 63 125 250 500 1K 2K 4K 8K


18 Kok 9 3 1 -3 -5 -9 -15 -19 Kok 10 5 1 -4 -5 -10 -16 -20

110 We reserve the right to make changes without prior notice


li ndab | ceiling diffusers

Plain diffuser CRL


Technical data
1
CRL 250+ MBB - Supply air CRL 315 + MBB - Supply air

ǻpt [Pa] CRL-250+MBB-250-250-S


250
50
ǻpt [Pa] CRL-315+MBB-315-315-S
250
2
200 200
150 150
50
100
45 100
45
3
70 40 70
40
50 50
35
35
30
30
30
4
30
25
20 20 25
20
15 15 20
10
LWA dB(A)
10
LWA dB(A) 5
qV [l/s] qV [l/s]
50 60 70 80 100 120 140 160 180 200 240 280 50 60 70 80 90 150 200 250 300 350 400
qV [m3/h] qV [m3/h]
200 300 400 500 700 1000 200 300 400 500 700 1250 1500
6
Hz 63 125 250 500 1K 2K 4K 8K Hz 63 125 250 500 1K 2K 4K 8K
Kok 15 7 0 -2 -6 -12 -16 -21 Kok 15 4 1 -2 -6 -13 -17 -16
7
ǻpt [Pa] CRL-250+MBB-200-250-S ǻpt [Pa] CRL-315+MBB-250-315-S
250 250
200 200 8
150 150 50

100 45 100 45

70
40
70 40 9
35
50 50 35
30
30
30 25 30
20 25
10
20 20
20
15 15
LWA dB(A) LWA dB(A)
10
qV [l/s]
10
50 60 70 80 90 100 150 200 250 300 350 400
qV [l/s] 11
50 60 70 80 100 120 140 160 180 200 240
qV [m3/h] qV [m3/h]
200 300 400 500 700 200 300 400 500 700 1250

Hz 63 125 250 500 1K 2K 4K 8K Hz 63 125 250 500 1K 2K 4K 8K


12
Kok 11 7 -1 -2 -5 -12 -17 -22 Kok 13 6 -1 -2 -5 -12 -17 -23

13
ǻpt [Pa] CRL-250+MBB-160-250-S ǻpt [Pa] CRL-315+MBB-200-315-S
250 250
200 200
150 150
50
14
45
100 100 45
40
40
70 35 70

50 50
35 15
30
30
30 25 30 25

20 20 20 20 16
15 15
LWA dB(A) LWA dB(A)
10 10
qV [l/s] qV [l/s]
30 40 50 60 70 80 100 120 140 160 180
qV [m3/h]
50 60 70 80 100 120 140 160 180 200 240 280
qV [m3/h]
17
150 200 300 400 500 200 300 400 500 700 1000

Hz 63 125 250 500 1K 2K 4K 8K Hz 63 125 250 500 1K 2K 4K 8K


18
Kok 11 6 1 -3 -5 -10 -15 -21 Kok 11 7 0 -3 -6 -10 -16 -21

We reserve the right to make changes without prior notice 111


lindab | ceil ing di ffusers

Plain diffuser CRL


Technical data
1
CRL 400+ MBB - Supply air CRL + MBB - Supply air

2 ǻpt [Pa] CRL-400+MBB-315-400-S Correction vertical supply air,


250
200
sound power level ( LWA )
150
50
and pressure loss ( Δpt )
3 100
45
70 40
CRL + MBB Correction factor
50
35
duct CRL Vertical supply air
4 30
Ød1 Ød2 LWA Δpt
30
100 100 +6 x 1,3
25
20 100 125 +8 x 1,3
20
15 100 160 +3 x 1,1
5 10
LWA dB(A)
125 125 +1 x1
qV [l/s]
70 80 90 150 200 250 300 350 400 500 600 125 160 +8 x 1,2
qV [m3/h] 125 200 +1 x1
300 400 500 700 1250 1500 2000
6 160 160 + 10 x 1,5
160 200 +3 x 1,1
Hz 63 125 250 500 1K 2K 4K 8K
160 250 +0 x1
Kok 11 3 0 -3 -5 -10 -14 -23
200 200 +7 x 1,3
7 200 250 +0 x1
200 315 +1 x1
ǻpt [Pa] CRL-400+MBB-250-400-S 250 250 + -2 x1
250
8 200 50
250 315 +0 x1
150 250 400 +0 x 1,1
45
315 315 + -2 x 1,1
100
40 315 400 +3 x 1,2
9 70
35
50
30

30
10 25

20 20
15
LWA dB(A)
11 10
qV [l/s]
70 80 90 150 200 250 300 350 400 500
qV [m3/h]
300 400 500 700 1250 1500 2000

12 Hz 63 125 250 500 1K 2K 4K 8K


Kok 8 4 -1 -3 -4 -10 -14 -20

13

14

15

16

17

18

112 We reserve the right to make changes without prior notice


li ndab | ceiling diffusers

Plain diffuser CRL


Technical data
1
CRL without box - Exhaust air CRL 100 + MBB - Exhaust air

ǻpt [Pa] CRL-100+MBB-100-100-E


ǻpt [Pa] CRL
100
100 125 160 200 250 315
400
250
2
200
70 45
150
50 50 40

45
100
35
3
30 70
40
50 30
20 35
15 30 30
25
4
20
25
10 20
20 15
7

5
LWA dB(A)
10
LWA dB(A) 5
qV [l/s] qV [l/s]
20 30 40 50 60 70 100 150 200 300 400 500 700 1000 5 10 15 20 25 30 40 50 60 80
3
qV [m /h] qV [m3/h]
80 100 150 200 300 400 500 700 1000 1500 2000 3000 20 30 40 50 60 70 80 100 150 200
6
Hz 63 125 250 500 1K 2K 4K 8K
Kok 11 0 2 -2 -6 -11 -15 -22
7

10

11

12

13

14

15

16

17

18

We reserve the right to make changes without prior notice 113


lindab | ceil ing di ffusers

Plain diffuser CRL


Technical data
1
CRL 125 + MBB - Exhaust air CRL 160 + MBB - Exhaust air

ǻpt [Pa] CRL-125+MBB-125-125-E ǻpt [Pa] CRL-160+MBB-160-160-E


2 250 250
200 200 50
45
150 150
45
40
3 100 100
40
70 35
70
35
50 30 50
30
4 30
25
30 25

20 20
20 20
15 15
5 10
LWA dB(A)
10
LWA dB(A)
qV [l/s] qV [l/s]
10 15 20 25 30 40 50 60 80 100 120 10 15 20 25 30 40 50 60 80 100 150 200
qV [m3/h] qV [m3/h]
40 50 60 70 80 100 150 200 300 400 40 50 60 70 80 100 150 200 300 400 500 700
6
Hz 63 125 250 500 1K 2K 4K 8K Hz 63 125 250 500 1K 2K 4K 8K
Kok 14 5 -1 -3 -4 -12 -15 -21 Kok 14 4 -1 -4 -4 -10 -16 -24
7
ǻpt [Pa] CRL-125+MBB-100-125-E ǻpt [Pa] CRL-160+MBB-125-160-E
250 250
8 200 200
50

150 45 150 45

100 40 100 40
9 70
35
70
35
50 50
30 30
30 30
10 25 25
20 20
20 20
15 15
LWA dB(A) LWA dB(A)
10 10
11 5 10 15 20 25 30 40 50 60 80
qV [l/s]
10 15 20 25 30 40 50 60 80 100 120 140
qV [l/s]

qV [m3/h] qV [m3/h]
20 30 40 50 60 70 80 100 150 200 40 50 60 70 80 100 150 200 300 400 500

12 Hz 63 125 250 500 1K 2K 4K 8K Hz 63 125 250 500 1K 2K 4K 8K


Kok 13 0 4 -3 -8 -11 -17 -22 Kok 13 6 1 -3 -5 -12 -15 -21

13
ǻpt [Pa] CRL-160+MBB-100-160-E
250
200 50
14 150
45
100
40
70
15 50 35

30 30

16 20 25
15
20 LWA dB(A)
10
qV [l/s]
5 10 15 20 25 30 40 50 60 80
17 qV [m3/h]
20 30 40 50 60 70 80 100 150 200 300

Hz 63 125 250 500 1K 2K 4K 8K


18 Kok 13 0 5 -3 -9 -12 -19 -23

114 We reserve the right to make changes without prior notice


li ndab | ceiling diffusers

Plain diffuser CRL


Technical data
1
CRL 200 + MBB - Exhaust air CRL 250 + MBB - Exhaust air

ǻpt [Pa] CRL-200+MBB-200-200-E ǻpt [Pa] CRL-250+MBB-250-250-E


250 250
2
200 200 50
50
150 150
45 45
100
40
100
40
3
70 35 70
35
50 30 50
30
30
25
30
4
20 25
20 20
20
15 15

10
LWA dB(A)
10
LWA dB(A) 5
qV [l/s] qV [l/s]
20 25 30 40 50 60 80 100 150 200 250 20 25 30 40 50 60 80 100 150 200 250 300 400
qV [m3/h] qV [m3/h]
80 100 150 200 300 400 500 700 80 100 150 200 300 400 500 700 1250
6
Hz 63 125 250 500 1K 2K 4K 8K Hz 63 125 250 500 1K 2K 4K 8K
Kok 15 5 -1 -3 -6 -9 -16 -25 Kok 11 6 2 -2 -7 -11 -15 -24
7
ǻpt [Pa] CRL-200+MBB-160-200-E ǻpt [Pa] CRL-250+MBB-200-250-E
250 250
200
50
200 8
150 45 150
45
100 40 100
40
70 35 70 9
50 50 35
30
30
30 25 30

20 25
10
20 20
15 15 20
LWA dB(A) LWA dB(A)
10 10
10 15 20 25 30 40 50 60 80 100 150 200
qV [l/s]
20 25 30 40 50 60 80 100 150 200 250
qV [l/s] 11
qV [m3/h] qV [m3/h]
40 50 60 70 80 100 150 200 300 400 500 700 80 100 150 200 300 400 500 700

Hz 63 125 250 500 1K 2K 4K 8K Hz 63 125 250 500 1K 2K 4K 8K 12


Kok 14 5 0 -3 -5 -9 -15 -20 Kok 13 5 1 -3 -6 -10 -13 -22

13
ǻpt [Pa] CRL-200+MBB-125-200-E ǻpt [Pa] CRL-250+MBB-160-250-E
250 250
200 50 200 50
150
45
150 14
45
100 100
40 40
70 70

50 35
50 35 15
30 30
30 30
25 25
20
20
20 16
15 15 20
LWA dB(A) LWA dB(A)
10 10
qV [l/s] qV [l/s]
10 15 20 25 30 40 50 60 80 100 120 140
qV [m3/h]
10 15 20 25 30 40 50 60 80 100 150 200
qV [m3/h]
17
40 50 60 70 80 100 150 200 300 400 500 40 50 60 70 80 100 150 200 300 400 500 700

Hz 63 125 250 500 1K 2K 4K 8K Hz 63 125 250 500 1K 2K 4K 8K


Kok 9 2 1 -2 -5 -9 -14 -19 Kok 13 5 1 -3 -5 -11 -14 -20
18

We reserve the right to make changes without prior notice 115


lindab | ceil ing di ffusers

Plain diffuser CRL


Technical data
1
CRL 315 + MBB - Exhaust air CRL 400 + MBB - Exhaust air

ǻpt [Pa] CRL-315+MBB-315-315-E ǻpt [Pa] CRL-400+MBB-315-400-E


2 250 250
200 50 200
150 150 50
45
45
3 100
40
100

70 70 40

50 35 50 35

4 30
30
30
30

25 25
20 20
15 20 20
15
5 10
LWA dB(A)
10
LWA dB(A)
qV [l/s] qV [l/s]
20 25 30 40 50 60 80 100 150 200 250 350 500 20 25 30 40 50 60 80 100 150 200 250 350 500
qV [m3/h] qV [m3/h]
80 100 150 200 300 400 500 700 1250 2000 80 100 150 200 300 400 500 700 1250 2000
6
Hz 63 125 250 500 1K 2K 4K 8K Hz 63 125 250 500 1K 2K 4K 8K
Kok 13 5 2 -3 -6 -10 -15 -25 Kok 11 5 2 -2 -7 -11 -15 -25
7
ǻpt [Pa] CRL-315+MBB-250-315-E ǻpt [Pa] CRL-400+MBB-250-400-E
250 250
8 200 200
50
150 150 50

100 45 100 45
9 70 40 70
40
50 50
35
35
30 30 30
10 30
20 25 20
25
15 15
20 LWA dB(A) LWA dB(A)
20
10 10
11 20 25 30 40 50 60 80 100 150 200 250 300 400
qV [l/s]
20 25 30 40 50 60 80 100 150 200 250 300 400
qV [l/s]

3
qV [m /h] qV [m3/h]
80 100 150 200 300 400 500 700 1250 80 100 150 200 300 400 500 700 1250

12 Hz 63 125 250 500 1K 2K 4K 8K Hz 63 125 250 500 1K 2K 4K 8K


Kok 9 5 2 -3 -6 -10 -16 -22 Kok 9 6 2 -2 -6 -12 -16 -24

13
ǻpt [Pa] CRL-315+MBB-200-315-E
250
200
14 150 50

100 45

70 40
15 50
35

30 30

16 20 25
15
20
LWA dB(A)
10
qV [l/s]

17 20 25 30 40 50 60 80 100 150 200 250 300


qV [m3/h]
80 100 150 200 300 400 500 700 1000

Hz 63 125 250 500 1K 2K 4K 8K


18 Kok 13 5 0 -3 -5 -10 -15 -22

116 We reserve the right to make changes without prior notice


l i nda b | c ei l i ng di ff u ser s

Lindab Integra

10

11

12

13

14

15

16

17

18
PC7,Integrated in Luxalon Clip-In ceiling with adapted module plate type LM.

Right to alterations reserved 117


lin dab | ce ili n g d i ffu s e r s

Lindab Integra a series of flush diffusers

Mixed ventilation diffusers


1
Product Functions Page

2
PC6 125

3
PC7 135
4

5
RC14 141

RC15 151
7

8
NC19 161

10 RCG 169

11
LCC 176

12
LCP 177
13

14
LKP 177

15

16

17

18

118 Right to alterations reserved


l i nda b | c ei l i ng di ff u ser s

Lindab Integra a series of flush diffusers

10

11
PC7, Integrated in Luxalon Clip-In ceiling with adapted module plate, type LM.

Lindab Integra Functionality 12


Integra is a series of flush mounted ceiling diffusers for Integra has a unique magnetic mounting system of the
mixed ventilation. The diffusers are primarily offered in face plates on all circular diffusers with exception of RCG.
circular, but are also available in square forms with a large This ensures an incredibly easy access to all the internal 13
selection of face plates in different designs, which satisfy components, which can be detached without the use of
requirements as well as function. The circular diffusers tools, and gives free access to the air duct system for
are normally cut directly into the ceiling when mounted, cleaning. 14
but can by using module plates be adapted for the most
common 600x600 ceiling systems. The square diffusers
in this series are adapted to the system-ceiling. The dif- 15
fusers can be mounted in a plenum box type MBB with
great advantage, in order to obtain a stable air flow to the
diffuser and the possibility for individual adjustments. 16

17

PC6, ceiling diffusers


18

Right to alterations reserved 119


l i nda b | c ei l i ng di ff u ser s

Lindab Integra a series of flush diffusers

Design Accessories
See Comfort and design See product pages 1

Supply/exhaust
DKZ LM MBB

Ventilation
principle
2

Size
Product
Perforated mm El. - motor Bracket Module pl. MBB box

PC6
125 3
160
200
250
315
4
Perforated swirl mm El. - motor Bracket Module pl. MBB box

PC7 160
200
5
250
315

Swirl mm El. - motor Bracket Module pl. MBB box


6
RC14 160
200
250 7
315

Swirl mm El. - motor Bracket Module pl. MBB box


8
RC15 160
200

9
250
315

Nozzle mm El. - motor Bracket Module pl. MBB box

NC19 125
160
10
200
250

11
315

Swirl mm El. - motor Bracket Module pl. MBB box

125
RCG
12
160
200
250
315
400

Plain mm El. - motor Bracket Module pl. MBB box 13


LCC 125
160
200 Special brackets
250
315
included
14
Plain mm El. - motor Bracket Module pl. MBB box

LCP 125 15
160
/ 200
LKP 250
315
16
Electric motor: 1. Product and tech. data depicted in catalogue.
See VAV chapter for futher documentation 2. Combination possible. Tech. data depicted in catalogue. 17
3. Combination possible. Tech. data not in catalogue.
Examaple of order Diffuser + MBB box 4. If space is empty, combination is not possible.
18
PC6 S 160 + MBB 125 160 S

Right to alterations reserved 121


lin dab | ce ili n g d i ffu s e r s

Lindab Integra a series of flush diffusers

Ceiling tile adaption


1 Details, see Chapter Ceiling tile adaption
1 3 4 5 6 7

2
Product Size
Ceiling types Danotile T24/T15 Plasterboard Dampa Clip-In Dampa Clip-In Luxalon SQ Danotile Contur
3 Ecophon T24
Rockfon A24.
ceiling bevelled edge square edge Clip-In Ecophon D
Rockfon D-XL
Perforated mm F: 595 mm ØA mm F: 600 mm F: 600 mm F: 600 mm F: 599 mm
125 Standard
4 PC6 160
200
Standard
Standard
250 Standard
315 Standard

5
Perforated swirl mm F: 595 mm ØA mm F: 600 mm F: 600 mm F: 600 mm F: 599 mm

PC7
6 160
200
Standard
Standard
250 Standard
315 Standard

7 Swirl mm F: 595 mm ØA mm F: 600 mm F: 600 mm F: 600 mm F: 599 mm

RC14 160 Standard


8 200
250
Standard
Standard
315 Standard

9 Swirl mm F: 595 mm ØA mm F: 600 mm F: 600 mm F: 600 mm F: 599 mm

RC15
160 Standard
10 200
250
Standard
Standard
315 Standard

11 Nozzles mm F: 595 mm ØA mm F: 600 mm F: 600 mm F: 600 mm F: 599 mm

NC19 125 Standard


160 Standard

12 200
250
Standard
Standard
315 Standard

13 Swirl mm F: 595 mm ØD mm F: 600 mm F: 600 mm F: 600 mm F: 599 mm


125 Standard
RCG 160 Standard
200 Standard

14 250
315
Standard
Standard
400 Standard

Plain mm F: 595 mm 595 x 595 mm F: 600 mm F: 600 mm F: 600 mm F: 599 mm

15 LCP 125 Standard*


No seperate 160 Standard*
module plate 200 Standard*
( Integrated in design )
16 250
315
Standard*
Standard*

Plain mm F: 595 mm 595 x 595 mm F: 600 mm F: 600 mm F: 600 mm F: 599 mm

17 LKP 125 Standard*


No seperate 160 Standard*
module plate 200 Standard*
( Integrated in design )
18
250 Standard*
315 Standard*

* In other ceiling systems the grille box is adapted to the ceiling

122 Right to alterations reserved


l i nda b | c ei l i ng di ff u ser s

Lindab Integra a series of flush diffusers

1
8 9 10 11 14

2
Product Size
Ceiling types Ecophon Focus Rockfon E10 24 Rockfon E10 15 Danotile Markant Ecophon
DG Ecophon -
E / T24
Ecophon -
E / T15
Focus edge DS 3
Perforated mm F: 592 mm F: 575 mm F: 584 mm F: 575 mm F: 599 mm
125
PC6 160
200
4
250
315

5
Perforated swirl mm F: 592 mm F: 575 mm F: 584 mm F: 575 mm F: 599 mm

PC7
160
200
6
250
315

Swirl mm F: 592 mm F: 575 mm F: 584 mm F: 575 mm F: 599 mm


7
RC14 160
200
250
8
315

Swirl mm F: 592 mm F: 575 mm F: 584 mm F: 575 mm F: 599 mm 9


RC15
160
200
250
10
315

Nozzles mm F: 592 mm F: 575 mm F: 584 mm F: 575 mm F: 599 mm 11


NC19 125
160
200
250 12
315

Swirl mm F: 592 mm F: 575 mm F: 584 mm F: 575 mm F: 599 mm


13
125
RCG 160
200
250
315 14
400

Plain mm F: 592 mm F: 575 mm F: 584 mm F: 575 mm F: 599 mm

LCP
15
125
No seperate 160
module plate
200
( Integrated in design )
250
315 16
Plain mm F: 592 mm F: 575 mm F: 584 mm F: 575 mm F: 599 mm

LKP 125
17
No seperate 160
module plate 200
( Integrated in design ) 250
315 18

Right to alterations reserved 123


lind ab | cei ling di ffusers

Perforated diffuser PC6


Dimensions
ØU
1
Ød

2
11

60
3

30
ØA

PC6 Ød ØA H ØU* Weight 4


mm mm mm mm kg
125 360 140 370 3.90
160 460 140 470 5.30
200 460 140 470 5.40
5
250 540 140 550 7.40
315 540 140 550 8.10

* ØU = ceiling grid opening


6
Description
PC6 is a circular perforated diffuser that can be used for
Ød 315, No mounting holes for MBB !
both supply air and exhaust. The diffuser is suitable for the
horizontal supply of cooled air. The diffuser can also be used
7
for low impulse and is therefore useful for the supply of PC6-S
replacement air in environments with high rates of air
exchange. Installing this diffuser in a plenum box type MBB 8
can help to achieve a stable flow of air to the diffuser as well
as realise the potential for individual adjustment.
9
• Suitable for both supply and exhaust air
• Discrete design
• Can be used for low impulse supply air
10
Maintenance
The face plate can be removed to enable cleaning of internal
parts or to gain access to the duct or box. The visible parts 11
of the diffuser can be wiped with a damp cloth.

12

13

14

Order code 15
Product PC6 a bbb
Type
PC6 16
Functional use Materials and finish
S = Supply air
E = Exhaust Material: Galvanised steel
L = Low-impulse Standard finish: Powder-coated 17
Connection dim. Standard colour: RAL 9010 Gloss 30
Ød 125-315
The diffuser is available in other colours. Please contact 18
Example: PC6-S-200 Lindab’s sales department for further information.

We reserve the right to make changes without prior notice 125


28-10-2013
lindab | ceil ing di ffusers

Perforated diffuser PC6


Accessories
1
Mounting brackets DCZ Plenum box MBB

4
PC6 + MBB

5 Extension piece MBZ 10 LxB

10

Ød1
6

C
H
Ød2

7
F E

Order code - accessoreies


8 Product aaa bbb
PC6 + MBB
duct PC6 B C E F H* L
Type
Ød1 mm Ød2 mm mm mm mm mm mm mm
Size
100 125 260 159 216 50 250 - 290 310
9 100 160 260 159 216 50 250 - 290 310
Example: MBZ-200
125 125 310 184 262 50 275 - 315 376
125 160 310 184 262 50 275 - 315 376
10 125 200 310 184 262 50 275 - 315 376
160 160 380 220 323 50 309 - 349 459
160 200 380 220 323 50 309 - 349 459
11 160 250 380 220 323 50 309 - 349 459
200 200 460 259 396 70 350 - 390 565
200 250 460 259 396 70 350 - 390 565
200 315 460 259 396 70 350 - 390 565
12 250 250 540 309 486 70 400 - 440 698
250 315 540 309 486 70 400 - 440 698
315 315 540 373 646 70 465 - 505 858
13 * Using accessory MBZ the H dimension will increase:
Module plate LM
Ød2 = 125 - 200 mm => H +40 mm
Ød2 = 250 - 315 mm => H +60 mm
14

Order code
15 Product MBB aaa bbb c
Type
MBB
Order code - module plate
16 Duct connection Ød1
Product LM a PC6 ccc Ø100-315
Type Diffuser dimension Ød2
Ceiling system Ø125-315
17 Diffuser Functional use
Size S = Supply air
E = Exhaust
18 Example: LM-1-PC6-200
Ceiling system - see introductory summary Example: PC6-S-200-MBB-160-200-S

126 We reserve the right to make changes without prior notice


28-10-2013
lind ab | cei ling di ffusers

Perforated diffuser PC6


Technical data
1
Capacity Throw l0.2
Air flow qv [l/s] and [m3/h], total pressure Δpt [Pa], throw l0.2 Throw l0.2 [m] is specified at a terminal velocity of 0.2 m/s.
[m] and sound power level LWA [dB(A)] can be seen in the
diagrams. l0.2 [m] PC6-S
160
125 200 250
2
10 315
8
Frequency-related sound effect level 7

The sound effect level in the frequency band is defined as


6 3
5
LWA+Kok. Kok values are specified in charts beneath the dia- 4
grams on the following pages.
3
4
Quick selection, supply air 2

PC6 + MBB Δpt ≥ 50 Pa Δpt ≥ 50 Pa


l0.2 [m]
5
duct PC6 30 dB(A) 35 dB(A) 1
qV [l/s]
Ød1 Ød2 l/s m3/h l/s m3/h 20 30 40 50 60 70 80 100 150 200 300 500
qV [m3/h]
100 125 32 115 38 137 80 100 150 200 300 500 700 1000 1500 6
100 160 39 140 46 166
125 125 39 140 46 166 L;M= 0# , 
 
125 160 48 173 62 223  
125 200 56 202 66 238 
 7

160 160 53 191 62 223 
160 200 66 238 78 281 

160 250 74 266 95 342  8


200 200 71 256 85 306

200 250 92 331 112 403
200 315 113 407 138 497
250 250 110 396 130 468

9
250 315 122 439 152 547
315 315 156 562 188 677 L ;M=

          
Q6;LS=
10
Low-impulse         
Q6;MH=

Correction sound power level (LWA) and


pressure loss (Δpt) Sound attenuation 11
On the following pages you can find diagrams for all sizes Sound attenuation of the diffusers ΔL from duct to room,
PC6+MBB supply air. When low-impulse values are wanted including end reflection, see table below.
use the correction factors in the table below. 12
PC6 + MBB
PC6-L + MBB Low-impulse duct PC6 Centre frequency Hz
duct PC6-L Correction factor Ød1 Ød2 63 125 250 500 1K 2K 4K 8K
13
Ød1 Ød2 LWA Δpt 100 125 19 16 7 15 19 18 19 21
100 125 -1 x1 100 160 17 15 4 14 17 17 17 18
100 160 1 x1 125 125 17 15 9 19 17 19 18 20
125 125 -4 x1 125 160 15 14 8 18 15 16 17 19 14
125 160 -1 x1 125 200 13 11 4 14 13 15 16 17
125 200 -2 x1 160 160 15 15 10 21 17 18 19 20
160 160 -5 x 0,9 160 200 18 15 8 21 17 17 18 19 15
160 200 -3 x1 160 250 16 14 5 17 13 15 17 18
160 250 -2 x1 200 200 13 11 8 16 18 16 19 17
200 200 0 x1 200 250 13 9 5 14 16 15 18 16
200 250 0 x1 200 315 13 8 3 10 16 14 16 16
16
200 315 -1 x1 250 250 14 8 7 15 17 17 18 17
250 250 -5 x 0,9 250 315 13 7 6 14 16 15 16 17
250 315 -2 x1 315 315 8 9 8 14 17 16 17 21 17
315 315 0 x1
Balancing
Balancing data is contained in a separate brochure. 18

We reserve the right to make changes without prior notice 127


28-10-2013
lindab | ceil ing di ffusers

Perforated diffuser PC6


Technical data
1
PC6 without box - Supply air PC6 125 + MBB - Supply air

2 ǻpt [Pa] PC6-S


100
125 160 200 250 ¨pt [Pa] PC6-S-125+MBB-125-125-S
250
200
70
315 150

3 50
50
100 50

30 70 45
45
40
40 50
20
4 15
35
30
35

30
30
10 25 20 25

15 20
5 7 20
LWA dB(A) LWA dB(A)
5 10
qV [l/s] qV [l/s]
30 40 50 60 70 80 100 150 200 300 400 500 15 20 25 30 40 50 60 70 80 100
qV [m3/h] qV [m3/h]
60 70 80 100 150 200 300
6 150 200 300 400 500 700 1000 1500

Hz 63 125 250 500 1K 2K 4K 8K


Kok 7 2 -4 0 -4 -14 -23 -32
7
¨pt [Pa] PC6-S-125+MBB-100-125-S
250
8 200
50
150
45
100
40
9 70
35
50
30

30 25
10 20 20

15
LWA dB(A)
10
11 10 15 20 25 30 40 50 60 70 80 100
qV [l/s]

qV [m3/h]
40 50 60 70 80 100 150 200 300

12 Hz 63 125 250 500 1K 2K 4K 8K


Kok 10 6 1 -2 -5 -12 -18 -25

13

14

15

16

17

18

128 We reserve the right to make changes without prior notice


28-10-2013
lind ab | cei ling di ffusers

Perforated diffuser PC6


Technical data
1
PC6 160 + MBB - Supply air PC6 200 + MBB - Supply air

ǻpt [Pa] PC6-S-160+MBB-160-160-S


250
ǻpt [Pa] PC6-S-200+MBB-200-200-S
250
2
200 200
150 150

100 100 3
50
70 70 50
45
50 50 45
40

30 35 30 35
40
4
30 30
20 20
25 25
15 15
20 LWA dB(A) 20 LWA dB(A) 5
10 10
qV [l/s] qV [l/s]
30 40 50 60 70 80 100 120 140 160 50 60 70 80 100 120 140 160 180 200 240
qV [m3/h] qV [m3/h]
150 200 300 400 500 200 300 400 500 700
6
Hz 63 125 250 500 1K 2K 4K 8K Hz 63 125 250 500 1K 2K 4K 8K
Kok 10 3 -5 -1 -3 -15 -23 -29 Kok 11 2 -5 -1 -4 -15 -22 -27
7
¨pt [Pa] PC6-S-160+MBB-125-160-S ǻpt [Pa] PC6-S-200+MBB-160-200-S
250 250
200 200 8
150 150
50

100 45 100 50
70 40 70 45 9
50 35 50 40
30 35
30 25 30

20 20 20
30
10
25
15 15 20
LWA dB(A) LWA dB(A)
10 10
20 25 30 40 50 60 70 80 100 120
qV [l/s]
30 40 50 60 70 80 100 120 140 160
qV [l/s] 11
qV [m3/h] qV [m3/h]
80 100 150 200 300 400 150 200 300 400 500

Hz 63 125 250 500 1K 2K 4K 8K Hz 63 125 250 500 1K 2K 4K 8K


12
Kok 9 5 0 -2 -5 -12 -17 -25 Kok 11 4 -2 -2 -3 -12 -20 -27

13
ǻpt [Pa] PC6-S-160+MBB-100-160-S ¨pt [Pa] PC6-S-200+MBB-125-200-S
250 250
200 50 200
150 45 150 50
14
100 40 100 45

35 40
70 70
35
50 30 50 15
30
25
30 30 25
20
20 20 20
15 15
16
LWA dB(A) LWA dB(A)
10 10
qV [l/s] qV [l/s]
10 15 20 25 30 40 50 60 70 80 90 20 25 30 35 40 50 60 70 80 100 120 140

40 50 60 70 80 100 150 200 300


qV [m3/h]
80 100 150 200 300 400 500
qV [m3/h] 17
Hz 63 125 250 500 1K 2K 4K 8K Hz 63 125 250 500 1K 2K 4K 8K
Kok 7 4 0 -1 -5 -11 -16 -22 Kok 6 5 0 -2 -5 -10 -16 -22 18

We reserve the right to make changes without prior notice 129


28-10-2013
lindab | ceil ing di ffusers

Perforated diffuser PC6


Technical data
1
PC6 250 + MBB - Supply air PC6 315 + MBB - Supply air

2 ¨pt [Pa] PC6-S-250+MBB-250-250-S


250
ǻpt [Pa] PC6-S-315+MBB-315-315-S
250
200 200
150 150

3 100 100
50
70 70
50
45
50 45 50
40
4 30
40
30 35
35
30
20 30 20
25
15 25 15
5 20 LWA dB(A) 20 LWA dB(A)
10 10
qV [l/s] qV [l/s]
50 60 70 80 100 120 140 160 180 200 240 280 50 60 70 80 90 100 150 200 250 300 350 400
3
qV [m /h] qV [m3/h]
200 300 400 500 700 1000 200 300 400 500 700 1250
6
Hz 63 125 250 500 1K 2K 4K 8K Hz 63 125 250 500 1K 2K 4K 8K
Kok 9 -1 -6 0 -4 -16 -25 -30 Kok 13 1 -2 -2 -4 -13 -23 -29
7
ǻpt [Pa] PC6-S-250+MBB-200-250-S ¨pt [Pa] PC6-S-315+MBB-250-315-S
250 250
8 200 200
150 150

100 100
50 50
9 70
45
70
45
50 50
40 40
35
35
30 30
10 20 25
30

20
30

25
15 20 15
LWA dB(A) 20 LWA dB(A)
10 10
11 50 60 70 80 100 120 140 160 180 200 240
qV [l/s]
50 60 70 80 90 100 150 200 250 300 350 400
qV [l/s]

qV [m3/h] qV [m3/h]
200 300 400 500 700 200 300 400 500 700 1250

12 Hz 63 125 250 500 1K 2K 4K 8K Hz 63 125 250 500 1K 2K 4K 8K


Kok 11 3 -3 -2 -3 -14 -22 -29 Kok 11 2 -3 -2 -3 -13 -19 -26

13
ǻpt [Pa] PC6-S-250+MBB-160-250-S ¨pt [Pa] PC6-S-315+MBB-200-315-S
250 250
200 200

14 150
50
150
50
100 100
45 45
70 70
40
40
15 50 35 50
35
30
30 30
25 30
20 20
16 15
20
15
25

LWA dB(A) 20 LWA dB(A)


10 10
qV [l/s] qV [l/s]
30 40 50 60 70 80 100 120 140 160 180 50 60 70 80 100 120 140 160 180 200 240 280
17 150 200 300 400 500
qV [m3/h]
200 300 400 500 700 1000
qV [m3/h]

Hz 63 125 250 500 1K 2K 4K 8K Hz 63 125 250 500 1K 2K 4K 8K


18 Kok 12 3 -1 -4 -4 -10 -18 -24 Kok 10 6 -1 -2 -4 -12 -20 -26

130 We reserve the right to make changes without prior notice


28-10-2013
lind ab | cei ling di ffusers

Perforated diffuser PC6


Technical data
1
PC6 without box - Exhaust air PC6 125 + MBB - Exhaust air

ǻpt [Pa] PC6-E


100
125 160 200 250 ¨pt [Pa] PC6-E-125+MBB-125-125-E
250
2
315 200
50 45
70
150

50 45
100
40
3
40 70 35
30
35 50 30

20
30 30 25
4
15
25 20 20

10 15
20
LWA dB(A) LWA dB(A) 5
7 10
qV [l/s] qV [l/s]
50 60 70 80 100 150 200 300 400 500 600 800 10 15 20 25 30 40 50 60 80 100 120
qV [m3/h] qV [m3/h]
40 50 60 70 80 100 150 200 300 400
200 300 400 500 700 1000 1500 2000 2500
6
Hz 63 125 250 500 1K 2K 4K 8K
Kok 12 5 0 -2 -5 -11 -14 -21
7
¨pt [Pa] PC6-E-125+MBB-100-125-E
250
50
200 8
150 45

100
40
70
35
9
50

30
30

20
25 10
15 20
LWA dB(A)
10
5 10 15 20 25 30 40 50 60 80
qV [l/s] 11
qV [m3/h]
20 30 40 50 60 70 80 100 150 200 300

Hz 63 125 250 500 1K 2K 4K 8K


12
Kok 11 -1 4 -2 -8 -11 -16 -23

13

14

15

16

17

18

We reserve the right to make changes without prior notice 131


28-10-2013
lindab | ceil ing di ffusers

Perforated diffuser PC6


Technical data
1
PC6 160 + MBB - Exhaust air PC6 200+ MBB - Exhaust air

2 ¨pt [Pa] PC6-E-160+MBB-160-160-E


250
¨pt [Pa] PC6-E-200+MBB-200-200-E
250 50
200 45 200
150 150 45
40
3 100
35
100 40

70 70 35
30
50 50
30
25
4 30 30 25
20

20 20 20

15 15
5 LWA dB(A) LWA dB(A)
10 10
qV [l/s] qV [l/s]
10 15 20 25 30 40 50 60 80 100 150 200 20 25 30 40 50 60 80 100 150 200 250 300
qV [m3/h] qV [m3/h]
40 50 60 70 80 100 150 200 300 400 500 700 80 100 150 200 300 400 500 700 1000
6
Hz 63 125 250 500 1K 2K 4K 8K Hz 63 125 250 500 1K 2K 4K 8K
Kok 20 8 -1 -4 -6 -12 -18 -21 Kok 14 4 0 -3 -5 -9 -15 -23
7
¨pt [Pa] PC6-E-160+MBB-125-160-E ¨pt [Pa] PC6-E-200+MBB-160-200-E
250 250
8 200
50
200
50

150 45 150 45

100 40 100 40

9 70
35
70
35
50 50
30 30
30 30
10 20
25
20
25

20 20
15 15
LWA dB(A) LWA dB(A)
10 10
11 10 15 20 25 30 40 50 60 80 100 120 140
qV [l/s]
10 15 20 25 30 40 50 60 80 100 150 200
qV [l/s]

qV [m3/h] qV [m3/h]
40 50 60 70 80 100 150 200 300 400 500 40 50 60 70 80 100 150 200 300 400 500 700

12 Hz 63 125 250 500 1K 2K 4K 8K Hz 63 125 250 500 1K 2K 4K 8K


Kok 12 6 1 -2 -6 -11 -14 -21 Kok 15 6 -1 -3 -5 -9 -15 -21

13
¨pt [Pa] PC6-E-160+MBB-100-160-E ¨pt [Pa] PC6-E-200+MBB-125-200-E
250 250
200 50 200
50
14 150
45
150
45
100 100
40
70 70 40

15 50 35 50 35

30
30 30 30

20 25 20 25
16 15 15
20 20
LWA dB(A) LWA dB(A)
10 10
qV [l/s] qV [l/s]
5 10 15 20 25 30 40 50 60 80 10 15 20 25 30 40 50 60 80 100 120 140
17 20 30 40 50 60 70 80 100 150 200 300
3
qV [m /h]
40 50 60 70 80 100 150 200 300 400 500
qV [m3/h]

Hz 63 125 250 500 1K 2K 4K 8K Hz 63 125 250 500 1K 2K 4K 8K


18 Kok 9 3 3 -1 -8 -11 -16 -22 Kok 10 3 1 -2 -5 -10 -16 -22

132 We reserve the right to make changes without prior notice


28-10-2013
lind ab | cei ling di ffusers

Perforated diffuser PC6


Technical data
1
PC6 250+ MBB - Exhaust air PC6 315+ MBB - Exhaust air

¨pt [Pa] PC6-E-250+MBB-250-250-E


250
¨pt [Pa] PC6-E-315+MBB-315-315-E
250
2
50
200 200 50
150 45 150
45
100 40 100
40
3
70 70
35 35
50 50
30

30
30
30
4
25 25

20 20 20
20
15 15
LWA dB(A) LWA dB(A) 5
10 10
qV [l/s] qV [l/s]
20 25 30 40 50 60 80 100 150 200 250 300 400 20 25 30 40 50 60 80 100 150 200 250 350 500
qV [m3/h] qV [m3/h]
80 100 150 200 300 400 500 700 1250 80 100 150 200 300 400 500 700 1250 2000
6
Hz 63 125 250 500 1K 2K 4K 8K Hz 63 125 250 500 1K 2K 4K 8K
Kok 10 5 2 -3 -5 -11 -17 -24 Kok 13 5 3 -3 -6 -10 -16 -27
7
¨pt [Pa] PC6-E-250+MBB-200-250-E ¨pt [Pa] PC6-E-315+MBB-250-315-E
250 250
200 200
50
8
150 150
45
45
100 100
40
70 70 40 9
50 35 50
35
30
30 30 30

20
25
20
10
25
15 20 15
LWA dB(A) 20 LWA dB(A)
10 10
20 25 30 40 50 60 80 100 150 200 250
qV [l/s]
20 25 30 40 50 60 80 100 150 200 250 300 400
qV [l/s] 11
qV [m3/h] qV [m3/h]
80 100 150 200 300 400 500 700 80 100 150 200 300 400 500 700 1250

Hz 63 125 250 500 1K 2K 4K 8K Hz 63 125 250 500 1K 2K 4K 8K


12
Kok 13 4 0 -3 -5 -10 -14 -21 Kok 8 5 2 -3 -5 -11 -17 -25

13
¨pt [Pa] PC6-E-250+MBB-160-250-E ¨pt [Pa] PC6-E-315+MBB-200-315-E
250 250
200 200
50 50
150
45
150
14
45
100 100
40
70 70 40

50 35 50
35 15
30
30 30 30
25
20 20 25
15 20 15
16
LWA dB(A) 20 LWA dB(A)
10 10
qV [l/s] qV [l/s]
10 15 20 25 30 40 50 60 80 100 150 200 20 25 30 40 50 60 80 100 150 200 250 300

40 50 60 70 80 100 150 200 300 400 500 700


qV [m3/h]
80 100 150 200 300 400 500 700 1000
qV [m3/h] 17
Hz 63 125 250 500 1K 2K 4K 8K Hz 63 125 250 500 1K 2K 4K 8K
Kok 14 6 0 -4 -6 -9 -14 -19 Kok 13 5 1 -3 -5 -9 -14 -22 18

We reserve the right to make changes without prior notice 133


28-10-2013
lind ab | cei ling di ffusers

Perforated diffuser PC7


Dimensions
ØU
1
Ød

2
11

60
3

30
ØA

PC7 Ød ØA H ØU* Weight 4


mm mm mm mm kg
160 460 140 470 5.30
200 460 140 470 5.40
250 540 140 550 7.40
5
315 540 140 550 8.10

* ØU = ceiling grid opening


6
Description
Ød 315, No mounting holes for MBB !
PC7 is a circular diffuser with perforated face plate and inte-
grated swirl insert. The diffuser is suitable for the horizontal
supply of very cold air. The integrated swirl insert ensures PC7-S
7
optimum distribution and high induction. Installing this dif-
fuser in a plenum box type MBB can help to achieve a sta-
ble flow of air to the diffuser as well as realise the potential 8
for individual adjustment.

• High induction 9
• Discrete design
• Suitable for cooling at very low temperatures

Maintenance 10
The face plate and swirl insert can be removed to enable
cleaning of internal parts or to gain access to the duct or
box. The visible parts of the diffuser can be wiped with a 11
damp cloth.

12

13

14

15
Order code
Product PC7 S aaa 16
Type Materials and finish
PC7
Material: Galvanised steel
Functional use
S = Supply air Standard finish: Powder-coated 17
Connection dim. Standard colour: RAL 9003, 9010 Gloss 30
Ød 160-315
The diffuser is available in other colours. Please contact 18
Example: PC7-S-200 Lindab’s sales department for further information.

We reserve the right to make changes without prior notice 135


28-10-2013
lindab | ceil ing di ffusers

Perforated diffuser PC7


Accessories
1
Mounting brackets DCZ Plenum box MBB

PC7 + MBB
5 Extension piece MBZ
10 LxB

10
6
Ød1

C
Ød2

H
7
F E
8 Order code - accessoreies
Product aaa bbb PC7 + MBB
Type duct PC7 B C E F H* L
Size Ød1 mm Ød2 mm mm mm mm mm mm mm
9 100 160 260 159 216 50 250 - 290 310
Example: DCZ-200 125 160 310 184 262 50 275 - 315 376
125 200 310 184 262 50 275 - 315 376
10 160 160 380 220 323 50 309 - 349 459
160 200 380 220 323 50 309 - 349 459
160 250 380 220 323 50 309 - 349 459
11 200 200 460 259 396 70 350 - 390 565
200 250 460 259 396 70 350 - 390 565
200 315 460 259 396 70 350 - 390 565
250 250 540 309 486 70 400 - 440 698
12 250 315 540 309 486 70 400 - 440 698
315 315 540 373 646 70 465 - 505 858
Module plate LM * Using accessory MBZ the H dimension will increase:
13 Ød2 = 160 - 200 mm => H +40 mm
Ød2 = 250 - 315 mm => H +60 mm

14

15 Order code
Product MBB aaa bbb S
Type
Order code - module plate
16 MBB
Product LM a PC7 ccc Duct connection Ød1
Type Ø100-315
Ceiling system Diffuser dimension Ød2
17 Diffuser Ø160-315
Size Functional use
S = Supply air
18 Example: LM-1-PC7-200
Ceiling system - see introductory summary. Example: PC7-S-200-MBB-160-200-S

136 We reserve the right to make changes without prior notice


28-10-2013
lind ab | cei ling di ffusers

Perforated diffuser PC7


Technical data
1
Capacity Sound attenuation
Air flow qv [l/s] and [m3/h], total pressure Δpt [Pa], throw l0.2 Sound attenuation of the diffusers ΔL from duct to room,
[m] and sound power level LWA [dB(A)] can be seen in the including end reflection - see table below.
diagrams.
2

Frequency-related sound effect level PC7 + MBB


The sound effect level in the frequency band is defined as duct PC7 Centre frequency Hz 3
LWA+Kok. Kok values are specified in charts beneath the dia- Ød1 Ød2 63 125 250 500 1K 2K 4K 8K
grams on the following pages. 100 160 17 15 5 12 18 17 17 19
125 160 15 14 7 18 16 17 18 20 4
125 200 12 11 4 14 14 16 16 18
Quick selection, supply air
160 160 17 15 10 21 18 19 20 20
160 200 18 15 8 21 17 17 19 20
PC7 + MBB Δpt ≥ 50 Pa Δpt ≥ 50 Pa
160 250 17 14 4 16 14 16 18 19
5
duct PC7 30 dB(A) 35 dB(A)
200 200 14 10 8 16 19 16 20 18
Ød1 Ød2 l/s m3/h l/s m3/h
200 250 12 10 6 14 17 15 18 17
100 160 36 130 43 155
200 315 12 8 4 10 16 14 17 16 6
125 160 44 158 55 198
250 250 13 9 8 15 17 17 18 18
125 200 50 180 60 216
250 315 13 7 6 14 16 16 17 17
160 160 47 169 55 198
315 315 9 9 9 14 17 16 17 22
160 200 55 198 66 238 7
160 250 71 256 88 317
200 200 60 216 72 259
Balancing
200 250 84 302 99 356
Balancing data is contained in a separate brochure.
8
200 315 93 335 113 407
250 250 88 317 103 371
250 315 96 346 114 410
315 315 107 385 127 457
9

10
Throw l0.2
Throw l0.2 [m] is specified at a terminal velocity of 0.2 m/s.
11
l0.2 [m] PC7-S 160 200 250
10 315
8 12
7
6
5

4 13
3

2
14
l0.2 [m]
1
20 30 40 50 60 70 80 100 150 200 300 500
qV [l/s]
15
qV [m3/h]
80 100 150 200 300 500 700 1000 1500

16

17

18

We reserve the right to make changes without prior notice 137


28-10-2013
lindab | ceil ing di ffusers

Perforated diffuser PC7


Technical data
1
PC7 without box - Supply air PC7 160 + MBB - Supply air

2 ¨pt [Pa] PC7-S


100
160 200 250 ¨pt [Pa] PC7-S-160+MBB-160-160-S
250

315 200
70
150

3 50
50 100
50
30 45 70
45
40 50
20 40
4 15 35
30 35
30
10 30
20
25 25
15
5 7
20 LWA dB(A) 20 LWA dB(A)
5 10
qV [l/s] qV [l/s]
30 40 50 60 70 80 100 150 200 300 30 40 50 60 70 80 100 120 140 160
qV [m3/h] qV [m3/h]
150 200 300 400 500
6 150 200 300 400 500 700 1000

Hz 63 125 250 500 1K 2K 4K 8K


Kok 10 1 -4 -1 -3 -18 -26 -32
7
¨pt [Pa] PC7-S-160+MBB-125-160-S
250
8 200
150
50
100
45
9 70 40
50 35

30
30
10 25
20
20
15
LWA dB(A)
11 10
20 25 30 40 50 60 70 80 100 120
qV [l/s]

qV [m3/h]
80 100 150 200 300 400

12 Hz 63 125 250 500 1K 2K 4K 8K


Kok 10 4 -1 -1 -5 -14 -19 -25

13
¨pt [Pa] PC7-S-160+MBB-100-160-S
250
200 50

14 150
45

100 40

70 35
15 50
30

30 25

20
20
16 15
LWA dB(A)
10
qV [l/s]
10 15 20 25 30 40 50 60 70 80 100
17 40 50 60 70 80 100 150 200 300
qV [m3/h]

Hz 63 125 250 500 1K 2K 4K 8K


18 Kok 11 3 0 -1 -6 -10 -14 -20

138 We reserve the right to make changes without prior notice


28-10-2013
lind ab | cei ling di ffusers

Perforated diffuser PC7


Technical data
1
PC7 200 + MBB - Supply air PC7 250 + MBB - Supply air

¨pt [Pa] PC7-S-200+MBB-200-200-S


250
¨pt [Pa] PC7-S-250+MBB-250-250-S
250
2
200 200

150 150

100
100
3
70
70 50 50
50 45
50 45
40
30
40 30
35
4
35 20
30
20 30 15
25
15

20
25
LWA dB(A)
10
20 LWA dB(A) 5
10 7
qV [l/s] qV [l/s]
30 40 50 60 70 80 100 120 140 50 60 70 80 100 120 140 160 180 200 240 280
qV [m3/h] qV [m3/h]
150 200 300 400 500 200 300 400 500 700 1000
6
Hz 63 125 250 500 1K 2K 4K 8K Hz 63 125 250 500 1K 2K 4K 8K
Kok 11 -1 -4 0 -4 -19 -26 -31 Kok 12 -1 -5 0 -4 -18 -28 -36
7
¨pt [Pa] PC7-S-200+MBB-160-200-S ¨pt [Pa] PC7-S-250+MBB-200-250-S
250 250
200 200 8
150 150

100 100
50
70
45
70
45
50
9
50 50
40 40
35 35
30 30
30 30 10
20 20
25 25
15 15 20
20 LWA dB(A) LWA dB(A)
10
30 40 50 60 70 80 100 120 140 160
qV [l/s]
10
50 60 70 80 100 120 140 160 180 200 240
qV [l/s] 11
qV [m3/h] qV [m3/h]
150 200 300 400 500 200 300 400 500 700

Hz 63 125 250 500 1K 2K 4K 8K Hz 63 125 250 500 1K 2K 4K 8K


12
Kok 11 2 -2 -1 -4 -16 -24 -29 Kok 13 2 -3 -1 -4 -16 -24 -29

13
¨pt [Pa] PC7-S-200+MBB-125-200-S ¨pt [Pa] PC7-S-250+MBB-160-250-S
250 250
200 200
150
50
150 14
50
100 100
45
45
70 40 70
40
50 35 50
35
15
30
30
30 30
25
25
20 20
15
20
15
20 16
LWA dB(A) LWA dB(A)
10 10
qV [l/s] qV [l/s]
20 25 30 40 50 60 70 80 100 120 140 30 40 50 60 70 80 100 120 140 160 180

80 100 150 200 300 400 500


qV [m3/h]
150 200 300 400 500
qV [m3/h] 17

Hz 63 125 250 500 1K 2K 4K 8K Hz 63 125 250 500 1K 2K 4K 8K


Kok 6 5 1 -1 -5 -13 -19 -24 Kok 12 4 1 -2 -4 -13 -20 -26
18

We reserve the right to make changes without prior notice 139


28-10-2013
lindab | ceil ing di ffusers

Perforated diffuser PC7


Technical data
1
PC7 315 + MBB - Supply air

2 ¨pt [Pa] PC7-S-315+MBB-315-315-S


250
200
150

3 100

70 50
50 45

4 30
40

35
20 30
15 25
5 20
LWA dB(A)
10
qV [l/s]
50 60 70 80 90 100 150 200 250 300 350 400
qV [m3/h]
200 300 400 500 700 1250
6
Hz 63 125 250 500 1K 2K 4K 8K
Kok 12 1 -2 0 -5 -18 -23 -32
7
¨pt [Pa] PC7-S-315+MBB-250-315-S
250
8 200
150

100

9 70
50
50 45
40
30
10 35
20 30
15 25
20
LWA dB(A)
11 10
50 60 70 80 90 100 150 200 250 300 350 400
qV [l/s]

qV [m3/h]
200 300 400 500 700 1250

12 Hz 63 125 250 500 1K 2K 4K 8K


Kok 9 0 -2 0 -4 -16 -25 -34

13
¨pt [Pa] PC7-S-315+MBB-200-315-S
250
200

14 150

100
50
70 45

15 50 40
35
30
30

20 25
16 15 20
LWA dB(A)
10
qV [l/s]
50 60 70 80 100 120 140 160 180 200 240 280
17 200 300 400 500 700 1000
qV [m3/h]

Hz 63 125 250 500 1K 2K 4K 8K


18 Kok 12 4 -1 -1 -4 -14 -21 -27

140 We reserve the right to make changes without prior notice


28-10-2013
lindab | ceilin g diff users

Swirl diffuser RC14


Dimensions
ØU
1
Ød

2
11

60
3

30
ØA

RC14 Ød ØA H ØU* Weight 4


mm mm mm mm kg
160 360 140 370 5.30
200 360 140 370 5.40
250 460 140 470 7.40
5
315 540 140 550 8.10

* ØU = ceiling grid opening


6
Description
Ød 315, No mounting holes for MBB !
RC14 is a circular swirl diffuser with fixed bars. The diffuser
can be used for both supply air and exhaust. The swirl pat-
tern ensures high induction and a large dynamic range, and RC14
7
is therefore ideal for the horizontal supply of very cold air.
Installing this diffuser in a plenum box type MBB can help to
achieve a stable flow of air to the diffuser as well as realise 8
the potential for individual adjustment.

• Large dynamic range 9


• High induction
• Suitable for cooling at very low temperatures
• Can be used for both supply and exhaust air.
10
Maintenance
The face plate and swirl insert can be removed to enable
cleaning of internal parts or to gain access to the duct or 11
box. The visible parts of the diffuser can be wiped with a
damp cloth.
12

13

14

15
Order code
Product RC14 a bbb
Type 16
RC14
Functional use
Materials and finish
S = Supply air Material: Galvanised steel
E = Exhaust Standard finish: Powder-coated 17
Connection dim. Standard colour: RAL 9010 Gloss 30
Ød 160-315
The diffuser is available in other colours. Please contact 18
Example: RC14-S-250 Lindab’s sales department for further information.

We reserve the right to make changes without prior notice 141


28-10-2019
lindab | ceil ing di ffusers

Swirl diffuser RC14


Accessories Dimensions
1
Mounting brackets DCZ Plenum box MBB

RC14 + MBB
5
10 LxB

Extension piece MBZ


10
6
Ød1

C
H
Ød2

7
F E
8
RC14 + MBB
Order code - accessoreies duct RC14 B C E F H* L
Ød1 mm Ød2 mm mm mm mm mm mm mm
9 Product aaa bbb
100 160 260 159 216 50 250 - 290 310
Type
Size 125 160 310 184 262 50 275 - 315 376
125 200 310 184 262 50 275 - 315 376
10 Example: DCZ-250 160 160 380 220 323 50 309 - 349 459
160 200 380 220 323 50 309 - 349 459
160 250 380 220 323 50 309 - 349 459
11 200 200 460 259 396 70 350 - 390 565
200 250 460 259 396 70 350 - 390 565
200 315 460 259 396 70 350 - 390 565
250 250 540 309 486 70 400 - 440 698
12 250 315 540 309 486 70 400 - 440 698
315 315 540 373 646 70 465 - 505 858

Module plate LM * Using accessory MBZ the H dimension will increase:


13 Ød2 = 160 - 200 mm => H +40 mm
Ød2 = 250 - 315 mm => H +60 mm

14
Order code
15 Product MBB aaa bbb c
Type
MBB
Order code - module plate
16 Duct connection Ød1
Product LM a RC14 ccc Ø100-315
Type Diffuser dimension Ød2
Ceiling system Ø160-315
17 Diffuser Functional use
Size S = Supply air
E = Exhaust
18 Example: LM-1-RC14-250
Ceiling system - see introductory summary. Example: RC14-S-250-MBB-200-250-S

142 We reserve the right to make changes without prior notice


28-10-2019
lindab | ceilin g diff users

Swirl diffuser RC14


Technical data
1
Capacity Throw l0.2
Air flow qv [l/s] and [m3/h], total pressure Δpt [Pa], throw l0.2 Throw l0.2 [m] is specified at a terminal velocity of 0.2 m/s.
[m] and sound power level LWA [dB(A)] can be seen in the
diagrams.
2
l0.2 [m] RC14-S 160 200 250
10 315
Frequency-related sound effect level 8

The sound effect level in the frequency band is defined as


7
6
3
LWA+Kok. Kok values are specified in charts beneath the dia- 5

grams on the following pages. 4

3
4
Quick selection, supply air
2

RC14 + MBB Δpt ≥ 50 Pa Δpt ≥ 50 Pa 5


duct RC14 30 dB(A) 35 dB(A) l0.2 [m]
1
Ød1 Ød2 l/s m3/h l/s m3/h qV [l/s]
20 30 40 50 60 70 80 100 150 200 300 500
100 160 37 133 44 158 qV [m3/h] 6
80 100 150 200 300 500 700 1000 1500
125 160 44 158 54 194
125 200 50 180 62 223
160 160 48 173 57 205
160 200 56 202 67 241
Sound attenuation 7
Sound attenuation of the diffusers ΔL from duct to room,
160 250 67 241 84 302
including end reflection - see table below.
200 200 62 223 74 266
200 250 82 295 96 346 8
RC14 + MBB
200 315 102 367 126 454
250 250 92 331 106 382 duct RC14 Centre frequency Hz
Ød1 Ød2 63 125 250 500 1K 2K 4K 8K
250 315 117 421 139 500
100 160 18 15 5 11 18 19 18 19
9
315 315 141 508 166 598
125 160 15 13 8 17 17 17 18 20
125 200 13 11 6 13 14 17 17 19
160 160 16 15 11 21 18 20 21 20 10
160 200 17 15 9 21 18 19 20 20
160 250 17 14 4 18 14 16 18 19
200 200 14 11 8 15 19 17 20 18
11
200 250 14 10 5 14 18 14 18 17
200 315 14 8 3 10 16 15 17 16
250 250 14 9 7 15 18 17 19 18
250 315 12 7 6 14 16 15 17 17 12
315 315 8 9 9 13 17 16 18 22

Balancing 13
Balancing data is contained in a separate brochure.

14

15

16

17

18

We reserve the right to make changes without prior notice 143


28-10-2019
lindab | ceil ing di ffusers

Swirl diffuser RC14


Technical data
1
RC14 without box – supply air RC14 - 160 + MBB - Supply air

2 ¨pt [Pa] RC14-S


100
160 200 250 ¨pt [Pa] RC14-S-160+MBB-160-160-S
250
200
70 315 150
50
3 50
45 100
50
30 70
40 45
50
20 35 40
4 15 30 30
35

30
10 25
20
25
20 15
5 7
LWA dB(A)
20
LWA dB(A)
5 10
qV [l/s] qV [l/s]
30 40 50 60 70 80 100 150 200 300 30 40 50 60 70 80 100 120 140 160
qV [m3/h] qV [m3/h]
150 200 300 400 500
6 150 200 300 400 500 700 1000

Hz 63 125 250 500 1K 2K 4K 8K


Kok 6 2 -3 0 -4 -15 -26 -32
7
¨pt [Pa] RC14-S-160+MBB-125-160-S
250
8 200
150
50
100
45
9 70 40
50 35

30
30
10 25
20
20
15
LWA dB(A)
11 10
20 25 30 40 50 60 70 80 100 120
qV [l/s]

qV [m3/h]
80 100 150 200 300 400

12 Hz 63 125 250 500 1K 2K 4K 8K


Kok 9 5 0 -1 -5 -13 -19 -25

13
¨pt [Pa] RC14-S-160+MBB-100-160-S
250
50
200

14 150 45

40
100

70 35

15 50 30

25
30
20
20
16 15
LWA dB(A)
10
qV [l/s]
10 15 20 25 30 40 50 60 70 80 100
17 40 50 60 70 80 100 150 200 300
qV [m3/h]

Hz 63 125 250 500 1K 2K 4K 8K


18 Kok 9 4 0 0 -6 -12 -16 -20

144 We reserve the right to make changes without prior notice


28-10-2019
lindab | ceilin g diff users

Swirl diffuser RC14


Technical data
1
RC14 - 200 + MBB - Supply air RC14 - 250 + MBB - Supply air

¨pt [Pa] RC14-S-200+MBB-200-200-S


250
¨pt [Pa] RC14-S-250+MBB-250-250-S
250
2
200 200
150 150

100 100 3
50
70 70 50
45
50 50 45
40

30 35 30
40
4
35

20 30 20 30

15 25 15 25

10 20
LWA dB(A) 20 LWA dB(A) 5
10
qV [l/s] qV [l/s]
30 40 50 60 70 80 100 120 140 160 50 60 70 80 100 120 140 160 180 200 240 280
qV [m3/h] qV [m3/h]
150 200 300 400 500 200 300 400 500 700 1000
6
Hz 63 125 250 500 1K 2K 4K 8K Hz 63 125 250 500 1K 2K 4K 8K
Kok 11 3 -3 -1 -5 -12 -24 -33 Kok 10 1 -4 -1 -4 -14 -26 -37
7
¨pt [Pa] RC14-S-200+MBB-160-200-S ¨pt [Pa] RC14-S-250+MBB-200-250-S
250 250
200 200 8
150 150

100 50 100

70 45 70
45
50
9
50 40 50
40
35
35
30 30 30

25
30 10
20 20
25
20
15 15
20
LWA dB(A) LWA dB(A)
10
30 40 50 60 70 80 100 120 140 160
qV [l/s]
10
50 60 70 80 100 120 140 160 180 200 240
qV [l/s] 11
qV [m3/h] qV [m3/h]
150 200 300 400 500 200 300 400 500 700

Hz 63 125 250 500 1K 2K 4K 8K Hz 63 125 250 500 1K 2K 4K 8K


12
Kok 14 4 -2 -2 -4 -12 -22 -30 Kok 9 5 -3 -2 -3 -12 -24 -32

13
¨pt [Pa] RC14-S-200+MBB-125-200-S ¨pt [Pa] RC14-S-250+MBB-160-250-S
250 250
200 200
150
50
150
50
14
100 45 100
45
70 40 70
40
50
35
50
35
15
30
30 30 30
25
25
20 20 20
15 15 20 16
LWA dB(A) LWA dB(A)
10 10
qV [l/s] qV [l/s]
20 25 30 40 50 60 70 80 100 120 140 30 40 50 60 70 80 100 120 140 160 180

80 100 150 200 300 400 500


qV [m3/h]
150 200 300 400 500
qV [m3/h] 17

Hz 63 125 250 500 1K 2K 4K 8K Hz 63 125 250 500 1K 2K 4K 8K


Kok 8 6 1 -2 -6 -12 -17 -23 Kok 13 4 -1 -3 -4 -13 -21 -26
18

We reserve the right to make changes without prior notice 145


28-10-2019
lindab | ceil ing di ffusers

Swirl diffuser RC14


Technical data
1
RC14 - 315 + MBB - Supply air

2 ¨pt [Pa] RC14-S-315+MBB-315-315-S


250
200
150

3 100
50
70 45
50 40

4 30 30
35

25
20
20
15
5 LWA dB(A)
10
qV [l/s]
50 60 70 80 90 100 150 200 250 300 350 400
qV [m3/h]
200 300 400 500 700 1250
6
Hz 63 125 250 500 1K 2K 4K 8K
Kok 14 3 -1 -1 -4 -13 -24 -33
7
¨pt [Pa] RC14-S-315+MBB-250-315-S
250
8 200
150

100

9 70
45
50

50
40

30 35
10 30
20
25
15
20 LWA dB(A)
11 10
50 60 70 80 90 100 150 200 250 300 350 400
qV [l/s]

qV [m3/h]
200 300 400 500 700 1250

12 Hz 63 125 250 500 1K 2K 4K 8K


Kok 11 3 -2 -2 -4 -11 -21 -30

13
¨pt [Pa] RC14-S-315+MBB-200-315-S
250
200

14 150

100 50

70 45

15 50
35
40

30 30

25
20
16 15
20
LWA dB(A)
10
qV [l/s]
50 60 70 80 100 120 140 160 180 200 240 280
17 200 300 400 500 700 1000
qV [m3/h]

Hz 63 125 250 500 1K 2K 4K 8K


18 Kok 10 7 -1 -2 -4 -13 -21 -27

146 We reserve the right to make changes without prior notice


28-10-2019
lindab | ceilin g diff users

Swirl diffuser RC14


Technical data
1
RC14 without box – Exhaust air RC14 - 160 + MBB - Exhaust air

¨pt [Pa] RC14-E


250
160 200 250 ¨pt [Pa] RC14-E-160+MBB-160-160-E
250
2
200 315 200
50
150 150
50 45
100 45 100
40
3
70 40 70
35
50 50
35
30

30
30
30
4
25
25
20 20 20
20
15 15
LWA dB(A) LWA dB(A) 5
10 10
qV [l/s] qV [l/s]
30 40 50 60 70 80 100 150 200 300 10 15 20 25 30 40 50 60 80 100 150
qV [m3/h] qV [m3/h]
40 50 60 70 80 100 150 200 300 400 500
150 200 300 400 500 700 1000
6
Hz 63 125 250 500 1K 2K 4K 8K
Kok 14 4 -2 -2 -4 -13 -20 -26
7
¨pt [Pa] RC14-E-160+MBB-125-160-E
250
200
50 8
150 45

100 40

70 35
9
50
30

30 25
10
20 20
15
LWA dB(A)
10
10 15 20 25 30 40 50 60 80 100 120 140
qV [l/s] 11
qV [m3/h]
40 50 60 70 80 100 150 200 300 400 500

Hz 63 125 250 500 1K 2K 4K 8K


12
Kok 13 6 1 -1 -6 -13 -16 -22

13
¨pt [Pa] RC14-E-160+MBB-100-160-E
250
200 50

150
45
14
100
40
70

50 35
15
30
30

25
20
15
16
20
LWA dB(A)
10
qV [l/s]
5 10 15 20 25 30 40 50 60 80

20 30 40 50 60 70 80 100 150 200 300


qV [m3/h] 17

Hz 63 125 250 500 1K 2K 4K 8K


Kok 9 0 4 -1 -10 -12 -18 -24
18

We reserve the right to make changes without prior notice 147


28-10-2019
lindab | ceil ing di ffusers

Swirl diffuser RC14


Technical data
1
RC14 - 200 + MBB - Exhaust air RC14 - 250 + MBB - Exhaust air

2 ¨pt [Pa] RC14-E-200+MBB-200-200-E


250
¨pt [Pa] RC14-E-250+MBB-250-250-E
250
200 200
150 150
50 50
3 100
45
100
45
70 70
40 40
50 50
35 35
4 30 30 30 30

25 25
20 20
20 20
15 15
5 LWA dB(A) LWA dB(A)
10 10
qV [l/s] qV [l/s]
20 25 30 40 50 60 80 100 150 20 25 30 40 50 60 80 100 150 200
qV [m3/h] qV [m3/h]
80 100 150 200 300 400 500 80 100 150 200 300 400 500 700
6
Hz 63 125 250 500 1K 2K 4K 8K Hz 63 125 250 500 1K 2K 4K 8K
Kok 13 2 -4 -2 -3 -13 -22 -31 Kok 13 4 0 -2 -4 -12 -22 -31
7
¨pt [Pa] RC14-E-200+MBB-160-200-E ¨pt [Pa] RC14-E-250+MBB-200-250-E
250 250
8 200 200
150 50 150 50

100 45 100 45

9 70
40
70 40

35 35
50 50
30 30
30 30
10 25 25
20 20 20
20
15 15
LWA dB(A) LWA dB(A)
10
11 10
10 15 20 25 30 40 50 60 80 100 150
qV [l/s]
20 25 30 40 50 60 80 100 150 200 250
qV [l/s]

qV [m3/h] qV [m3/h]
40 50 60 70 80 100 150 200 300 400 500 80 100 150 200 300 400 500 700

12 Hz 63 125 250 500 1K 2K 4K 8K Hz 63 125 250 500 1K 2K 4K 8K


Kok 16 5 -2 -3 -4 -12 -21 -26 Kok 12 4 0 -2 -4 -11 -19 -27

13
¨pt [Pa] RC14-E-200+MBB-125-200-E ¨pt [Pa] RC14-E-250+MBB-160-250-E
250 250
200 50 200 50
14 150
45
150
45
100 100
40 40
70 70
35 35
15 50 50
30
30
30 30 25
25
20 20
16 15
20
15
20

LWA dB(A) LWA dB(A)


10 10
qV [l/s] qV [l/s]
10 15 20 25 30 40 50 60 80 100 120 140 10 15 20 25 30 40 50 60 80 100 150 200
17 40 50 60 70 80 100 150 200 300 400 500
qV [m3/h]
40 50 60 70 80 100 150 200 300 400 500 700
qV [m3/h]

Hz 63 125 250 500 1K 2K 4K 8K Hz 63 125 250 500 1K 2K 4K 8K


18 Kok 12 3 1 -1 -6 -12 -17 -23 Kok 15 6 0 -2 -6 -11 -16 -22

148 We reserve the right to make changes without prior notice


28-10-2019
lindab | ceilin g diff users

Swirl diffuser RC14


Technical data
1
RC14 - 315 + MBB - Exhaust air

¨pt [Pa] RC14-E-315+MBB-315-315-E


250
2
200
150

100
50
3
45
70
40
50
35

30 30
4
25
20
15 20
LWA dB(A) 5
10
qV [l/s]
20 25 30 40 50 60 80 100 150 200 250 300
qV [m3/h]
80 100 150 200 300 400 500 700 1250
6
Hz 63 125 250 500 1K 2K 4K 8K
Kok 10 3 1 -2 -4 -16 -24 -34
7
¨pt [Pa] RC14-E-315+MBB-250-315-E
250
200 8
150 50

100 45

70 40 9
50 35

30
30
25 10
20
20
15
LWA dB(A)
10
20 25 30 40 50 60 80 100 150 200 250 300
qV [l/s] 11
qV [m3/h]
80 100 150 200 300 400 500 700 1000

Hz 63 125 250 500 1K 2K 4K 8K


12
Kok 9 5 1 -2 -5 -13 -18 -26

13
¨pt [Pa] RC14-E-315+MBB-200-315-E
250
200
50
150
45
14
100
40
70

50
35
15
30
30
25
20
15
20 16
LWA dB(A)
10
qV [l/s]
20 25 30 40 50 60 80 100 150 200 250 300

80 100 150 200 300 400 500 700 1000


qV [m3/h] 17

Hz 63 125 250 500 1K 2K 4K 8K


Kok 14 6 1 -2 -6 -11 -16 -24
18

We reserve the right to make changes without prior notice 149


28-10-2019
lindab | ceilin g diff users

Swirl diffuser RC15


Dimensions
ØU 1
Ød

2
11

60
3

30
ØA

RC15 Ød ØA H ØU* Weight


mm mm mm mm kg 4
160 360 140 370 5.30
200 360 140 370 5.40
250 460 140 470 7.40 5
315 540 140 550 8.10

* ØU = ceiling grid opening


Description Ød 315, No mounting holes for MBB ! 6
RC15 is a circular swirl diffuser with adjustable bars. The dif-
fuser can be used for both supply and exhaust air. The swirl
pattern ensures high induction and a large dynamic range,
and is therefore ideal for the horizontal supply of very cold
Bar settings 7
air. The diffuser can also be set to a vertical supply air pat- Horizontal Vertical
tern, enabling supply of heated air. Installing this diffuser in a
plenum box type MBB can help to achieve a stable flow of 8
air to the diffuser as well as realise the potential for individ-
ual adjustment.
9
• Large dynamic range
• High induction
• Suitable for cooling at very low temperatures
• Horizontal or vertical supply air pattern 10
• Can be used for both supply air and exhaust

Maintenance 11
The face plate and swirl insert can be removed to enable
cleaning of internal parts or to gain access to the duct or RC15-S RC15-E
box. The visible parts of the diffuser can be wiped with a 12
damp cloth.

13

14

15
Order code
Product RC15 a bbb
16
Type Materials and finish
RC15
Material: Galvanised steel
Functional use
Standard finish: Powder-coated
S = Supply air
Standard colour: RAL 9010 Gloss 30 17
E = Exhaust Without bars
Connection dim. Bars (Only RC15-S): Black ABS plastic
Ød 160-315
The diffuser is available in other colours. Please contact 18
Example: RC15-S-160 Lindab’s sales department for further information.

We reserve the right to make changes without prior notice 151


28-10-2013
lindab | ceil ing di ffusers

Swirl diffuser RC15


Accessories
1
Mounting brackets DCZ Plenum box MBB

RC15 + MBB
5
10 LxB

Extension piece MBZ


10
6
Ød1

C
H
Ød2

7
F E
8
RC15 + MBB
Order code - accessoreies duct RC15 B C E F H* L
Ød1 mm Ød2 mm mm mm mm mm mm mm
9 Product aaa bbb
100 160 260 159 216 50 250 - 290 310
Type
Size 125 160 310 184 262 50 275 - 315 376
125 200 310 184 262 50 275 - 315 376
10 Example: DCZ-160 160 160 380 220 323 50 309 - 349 459
160 200 380 220 323 50 309 - 349 459
160 250 380 220 323 50 309 - 349 459
11 200 200 460 259 396 70 350 - 390 565
200 250 460 259 396 70 350 - 390 565
200 315 460 259 396 70 350 - 390 565
250 250 540 309 486 70 400 - 440 698
12 250 315 540 309 486 70 400 - 440 698
315 315 540 373 646 70 465 - 505 858

Module plate LM * Using accessory MBZ the H dimension will increase:


13 Ød2 = 160 - 200 mm => H +40 mm
Ød2 = 250 - 315 mm => H +60 mm

14

Order code
15 Product MBB aaa bbb c
Type
MBB
Order code - module plate
16 Duct connection Ød1
Product LM a RC15 ccc Ø100-315
Type Diffuser dimension Ød2
Ceiling system
17 Diffuser
Ø160-315
Functional use
Size S = Supply air
E = Exhaust
18 Example: LM-1-RC15-160
Ceiling system - see introductory summary Example: RC15-S-160-MBB-125-160-S

152 We reserve the right to make changes without prior notice


28-10-2013
lindab | ceilin g diff users

Swirl diffuser RC15


Technical data
1
Capacity Throw l0.2
Air flow qv [l/s] and [m3/h], total pressure Δpt [Pa], throw l0.2 Throw l0.2 [m] is specified at a terminal velocity of 0.2 m/s.
[m] and sound power level LWA [dB(A)] can be seen in the
diagrams.
2
l0.2 [m] RC15-S 160 200 250
10
315
8
Frequency-related sound effect level
The sound effect level in the frequency band is defined as
7
6 3
5
LWA+Kok. Kok values are specified in charts beneath the dia-
4
grams on the following pages.
3 4
Quick selection, supply air 2

RC15 + MBB Δpt ≥ 50 Pa Δpt ≥ 50 Pa 5


l0.2 [m]
duct RC15 30 dB(A) 35 dB(A) 1
qV [l/s]
Ød1 Ød2 l/s m3/h l/s m3/h 10 15 20 30 40 50 60 80 100 150 200 300 500
100 160 36 130 44 158 40 50 60 70 100 150 200 300 500 700 1000 1500
qV [m3/h]
6
125 160 44 158 54 194
125 200 49 176 59 212
160 160 47 169 56 202 RC15-S
160 200 54 194 64 230
l0.2 [m]
10
160 200 250 315
7
8
160 250 69 248 90 324 7
200 200 56 202 66 238 6

200 250 82 295 99 356 5 8


4
200 315 101 364 125 450
250 250 90 324 106 382 3
250 315 113 407 137 493 9
315 315 138 497 163 587 2

1
l0.2 [m] 10
qV [l/s]
10 15 20 30 40 50 60 80 100 150 200 300 500
qV [m3/h]
40 50 60 70 100 150 200 300 500 700 1000 1500
11
Sound attenuation
Sound attenuation of the diffusers ΔL from duct to room,
including end reflection - see table below.
12
RC15 + MBB
duct RC15 Centre frequency Hz 13
Ød1 Ød2 63 125 250 500 1K 2K 4K 8K
100 160 17 15 5 12 19 20 20 21
125 160 16 14 8 18 18 20 20 21
14
125 200 11 12 6 14 14 19 18 19
160 160 16 15 11 22 20 22 21 21
160 200 16 15 9 22 19 21 20 21
160 250 18 14 4 17 14 16 18 19 15
200 200 13 12 8 17 20 19 21 18
200 250 12 9 6 14 19 16 18 17
200 315 11 8 4 10 17 16 19 17 16
250 250 13 8 7 15 19 19 18 18
250 315 12 8 6 14 17 17 18 18
315 315 8 9 9 14 18 18 18 23
17
Balancing
Balancing data is contained in a separate brochure.
18

We reserve the right to make changes without prior notice 153


28-10-2013
lindab | ceil ing di ffusers

Swirl diffuser RC15


Technical data
1
Throws/Turning points RC15 without box – supply air
Throw l0.2 [m] is specified at a terminal velocity of 0.2 m/s.
Turning point l0.0 [m] is specified for +5 K and +10 K respec-
2 tively.
¨pt [Pa] RC15-S
100
160 200 250

70
315
RC15-S 50
3 l0.2 [m]
10
160 200 250 315 50

45
8 30
7 40
6
20
4 5
15
35

4 30
10
3 25

5 2
7
20 LWA dB(A)
5
qV [l/s]
30 40 50 60 70 80 100 150 200 300
qV [m3/h]

6 1
l0.2 [m] 150 200 300 400 500 700 1000

qV [l/s]
10 15 20 30 40 50 60 80 100 150 200 300 500
qV [m3/h]
40 50 60 70 100 150 200 300 500 700 1000 1500
7

l0.0 [m] RC15-S +5K


8 10
160 200 250 315

8
7
6

9 5

10 2

11 1
l0.0 [m]
qV [l/s]
10 15 20 30 40 50 60 80 100 150 200 300 500
qV [m3/h]
40 50 60 70 100 150 200 300 500 700 1000 1500

12

l0.0 [m] RC15-S +10K


13 10
160 200 250
315
8
7
6

14 5

15 2

16 1
l0.0 [m]
qV [l/s]
10 15 20 30 40 50 60 80 100 150 200 300 500
qV [m3/h]
40 50 60 70 100 150 200 300 500 700 1000 1500

17

18

154 We reserve the right to make changes without prior notice


28-10-2013
lindab | ceilin g diff users

Swirl diffuser RC15


Technical data
1
RC15 160 + MBB - Supply air RC15 - 200 + MBB - Supply air

¨pt [Pa] RC15-S-160+MBB-160-160-S


250
¨pt [Pa] RC15-S-200+MBB-200-200-S
250
2
200 200
150 150

100 50 100
50
3
70 45 70 45
50 40 50
40

30
35
30 35
4
30
30
20 20
25
15 15 25
20 LWA dB(A)
10
20
LWA dB(A) 5
10
qV [l/s] qV [l/s]
30 40 50 60 70 80 100 120 140 160 30 40 50 60 70 80 100 120 140 160
qV [m3/h] qV [m3/h]
150 200 300 400 500 150 200 300 400 500
6
Hz 63 125 250 500 1K 2K 4K 8K Hz 63 125 250 500 1K 2K 4K 8K
Kok 10 2 -4 0 -5 -17 -23 -31 Kok 8 3 -4 -1 -4 -15 -22 -31
7
¨pt [Pa] RC15-S-160+MBB-125-160-S ¨pt [Pa] RC15-S-200+MBB-160-200-S
250 250
200 200 8
150 150
50
100 45 100 50

70 40 70
45 9
40
50 35 50
35
30
30 30 30
25
25
10
20 20 20
20
15 15
LWA dB(A) LWA dB(A)
10
20 25 30 40 50 60 70 80 100 120
qV [l/s]
10
30 40 50 60 70 80 100 120 140 160
qV [l/s] 11
qV [m3/h] qV [m3/h]
80 100 150 200 300 400 150 200 300 400 500

Hz 63 125 250 500 1K 2K 4K 8K Hz 63 125 250 500 1K 2K 4K 8K


12
Kok 10 4 -1 0 -6 -13 -18 -24 Kok 9 3 -1 -2 -4 -14 -21 -29

13
¨pt [Pa] RC15-S-160+MBB-100-160-S ¨pt [Pa] RC15-S-200+MBB-125-200-S
250 250
200 200
150 150 50
14
40 45
100 100

35 40
70 70

50 30 50
35
15
30
25
30 30
25
20
20 20
15 15
20
16
LWA dB(A) LWA dB(A)
10 10
qV [l/s] qV [l/s]
10 15 20 25 30 40 50 60 70 80 100 20 25 30 40 50 60 70 80 100 120 140

40 50 60 70 80 100 150 200 300


qV [m3/h]
80 100 150 200 300 400 500
qV [m3/h] 17

Hz 63 125 250 500 1K 2K 4K 8K Hz 63 125 250 500 1K 2K 4K 8K


Kok 12 4 2 -1 -8 -12 -16 -19 Kok 7 5 0 -1 -5 -13 -17 -24
18

We reserve the right to make changes without prior notice 155


28-10-2013
lindab | ceil ing di ffusers

Swirl diffuser RC15


Technical data
1
RC15 - 250 + MBB - Supply air RC15 - 315 + MBB - Supply air

2 ¨pt [Pa] RC15-S-250+MBB-250-250-S


250
¨pt [Pa] RC15-S-315+MBB-315-315-S
250
200 200
150 150

3 100 100 50
50
70 70 45
45
50 50 40
40
4 30 35 30
35

30
30
20 20 25
15 25 15
5 20 LWA dB(A)
20
LWA dB(A)
10 10
qV [l/s] qV [l/s]
50 60 70 80 100 120 140 160 180 200 240 280 50 60 70 80 90 100 150 200 250 300 350 400
3
qV [m /h] qV [m3/h]
200 300 400 500 700 1000 200 300 400 500 700 1250
6
Hz 63 125 250 500 1K 2K 4K 8K Hz 63 125 250 500 1K 2K 4K 8K
Kok 12 1 -4 0 -4 -16 -24 -20 Kok 14 3 -2 -2 -4 -13 -22 -31
7
¨pt [Pa] RC15-S-250+MBB-200-250-S ¨pt [Pa] RC15-S-315+MBB-250-315-S
250 250
8 200 200
150 150

100 50 100
50
9 70 45 70 45
50 40 50 40
35 35
30 30
10 30 30
20 25 20 25
15 15
20 20
LWA dB(A) LWA dB(A)
11 10
50 60 70 80 100 120 140 160 180 200 240
qV [l/s]
10
50 60 70 80 90 100 150 200 250 300 350 400
qV [l/s]

qV [m3/h] qV [m3/h]
200 300 400 500 700 200 300 400 500 700 1250

12 Hz 63 125 250 500 1K 2K 4K 8K Hz 63 125 250 500 1K 2K 4K 8K


Kok 10 4 -3 -2 -3 -15 -21 -29 Kok 11 3 -2 -1 -4 -13 -19 -28

13
¨pt [Pa] RC15-S-250+MBB-160-250-S ¨pt [Pa] RC15-S-315+MBB-200-315-S
250 250
200 200

14 150
50
150

50
100 45 100
45
70 40 70
40
15 50 35 50
35
30
30 30 30
25
25
20 20
16 15
20
15
20

LWA dB(A) LWA dB(A)


10 10
qV [l/s] qV [l/s]
30 40 50 60 70 80 100 120 140 160 180 50 60 70 80 100 120 140 160 180 200 240 280
17 150 200 300 400 500
qV [m3/h]
200 300 400 500 700 1000
qV [m3/h]

Hz 63 125 250 500 1K 2K 4K 8K Hz 63 125 250 500 1K 2K 4K 8K


18 Kok 15 5 0 -3 -4 -13 -19 -25 Kok 9 7 -1 -2 -5 -13 -19 -26

156 We reserve the right to make changes without prior notice


28-10-2013
lindab | ceilin g diff users

Swirl diffuser RC15


Technical data
1
RC15 without box – Exhaust air RC15 160 + MBB - Exhaust air

¨pt [Pa] RC15-E


100
160 200 250 ¨pt [Pa] RC15-E-160+MBB-160-160-E
250
2
200 50
315
70
150 45
50
50 100 40 3
30 45 70 35
40 50
20 30

15
35
30 25
4
30
10 20
20
25
15
7
20 LWA dB(A) LWA dB(A) 5
5 10
qV [l/s] qV [l/s]
60 70 80 100 150 200 300 400 500 600 10 15 20 25 30 40 50 60 80 100 150 200
qV [m3/h] qV [m3/h]
40 50 60 70 80 100 150 200 300 400 500 700
300 400 500 700 1000 1500 2000
6
Hz 63 125 250 500 1K 2K 4K 8K
Kok 16 6 0 -3 -6 -11 -16 -21
7
¨pt [Pa] RC15-E-160+MBB-125-160-E
250
200
50
8
150 45

100 40
70 9
35
50
30
30
25 10
20
15 20
LWA dB(A)
10
10 15 20 25 30 40 50 60 80 100 120 140
qV [l/s] 11
qV [m3/h]
40 50 60 70 80 100 150 200 300 400 500

Hz 63 125 250 500 1K 2K 4K 8K


12
Kok 13 6 1 -2 -7 -12 -14 -22

13
¨pt [Pa] RC15-E-160+MBB-100-160-E
250
200 50

150
45 14
100
40
70

50
35
15
30
30
25
20
15 20
16
LWA dB(A)
10
qV [l/s]
5 10 15 20 25 30 40 50 60 80

20 30 40 50 60 70 80 100 150 200 300


qV [m3/h] 17

Hz 63 125 250 500 1K 2K 4K 8K


Kok 11 4 3 0 -9 -13 -17 -23
18

We reserve the right to make changes without prior notice 157


28-10-2013
lindab | ceil ing di ffusers

Swirl diffuser RC15


Technical data Technical data
1
RC15 200 + MBB - Exhaust air RC15 - 250 + MBB - Exhaust air

2 ¨pt [Pa] RC15-E-200+MBB-200-200-E


250
¨pt [Pa] RC15-E-250+MBB-250-250-E
250
200 200
150 50 150 50

3 100 45 100 45

70 40 70 40

50 35 50 35

4 30
30
30
30

25 25
20 20
20 20
15 15
5 LWA dB(A) LWA dB(A)
10 10
qV [l/s] qV [l/s]
20 25 30 40 50 60 80 100 150 200 250 20 25 30 40 50 60 80 100 150 200 250 300
qV [m3/h] qV [m3/h]
80 100 150 200 300 400 500 700 80 100 150 200 300 400 500 700 1250
6
Hz 63 125 250 500 1K 2K 4K 8K Hz 63 125 250 500 1K 2K 4K 8K
Kok 14 5 0 -2 -5 -11 -16 -24 Kok 12 6 2 -3 -6 -12 -17 -24
7
¨pt [Pa] RC15-E-200+MBB-160-200-E ¨pt [Pa] RC15-E-250+MBB-200-250-E
250 250
8 200 50 200
150 150
45
45
100 100
40
9 70
35
70
40

50 50 35
30
30
30 25 30
10 25
20 20 20
15 15 20
LWA dB(A) LWA dB(A)
11 10
10 15 20 25 30 40 50 60 80 100 150 200
qV [l/s]
10
20 25 30 40 50 60 80 100 150 200 250
qV [l/s]

qV [m3/h] qV [m3/h]
40 50 60 70 80 100 150 200 300 400 500 700 80 100 150 200 300 400 500 700

12 Hz 63 125 250 500 1K 2K 4K 8K Hz 63 125 250 500 1K 2K 4K 8K


Kok 17 6 -1 -3 -6 -10 -14 -19 Kok 13 5 0 -3 -6 -10 -14 -23

13
¨pt [Pa] RC15-E-200+MBB-125-200-E ¨pt [Pa] RC15-E-250+MBB-160-250-E
250 250
200 50 200
50
14 150
45
150
45
100 100
40 40
70 70

15 50 35 50
35

30
30
30 30
25
20 25 20
16 15 15
20
20
LWA dB(A) LWA dB(A)
10 10
qV [l/s] qV [l/s]
10 15 20 25 30 40 50 60 80 100 120 140 10 15 20 25 30 40 50 60 80 100 150 200
17 40 50 60 70 80 100 150 200 300 400 500
qV [m3/h]
40 50 60 70 80 100 150 200 300 400 500 700
qV [m3/h]

Hz 63 125 250 500 1K 2K 4K 8K Hz 63 125 250 500 1K 2K 4K 8K


18 Kok 14 3 1 -1 -6 -12 -15 -22 Kok 13 7 0 -3 -6 -10 -15 -19

158 We reserve the right to make changes without prior notice


28-10-2013
lindab | ceilin g diff users

Swirl diffuser RC15


Technical data
1
RC15 - 315 + MBB - Exhaust air

¨pt [Pa] RC15-E-315+MBB-315-315-E


250
2
200
50
150
45
100 3
40
70
35
50

30
30
4
25

20 20
15
LWA dB(A) 5
10
qV [l/s]
20 25 30 40 50 60 80 100 150 200 250 350 500
qV [m3/h]
80 100 150 200 300 400 500 700 1250 2000
6
Hz 63 125 250 500 1K 2K 4K 8K
Kok 12 5 3 -3 -6 -11 -16 -25
7
¨pt [Pa] RC15-E-315+MBB-250-315-E
250
200 8
50
150

45
100

70 40 9
50 35

30 30

25
10
20
15 20
LWA dB(A)
10
20 25 30 40 50 60 80 100 150 200 250 300 400
qV [l/s] 11
qV [m3/h]
80 100 150 200 300 400 500 700 1250

Hz 63 125 250 500 1K 2K 4K 8K


12
Kok 9 5 2 -3 -5 -11 -17 -25

13
¨pt [Pa] RC15-E-315+MBB-200-315-E
250
200
50
150 14
45
100

70 40

50 35 15
30 30

20 25

15
16
20
LWA dB(A)
10
qV [l/s]
20 25 30 40 50 60 80 100 150 200 250 300

80 100 150 200 300 400 500 700 1000


qV [m3/h] 17

Hz 63 125 250 500 1K 2K 4K 8K


Kok 15 5 1 -3 -5 -10 -15 -23
18

We reserve the right to make changes without prior notice 159


28-10-2013
lind ab | cei ling di ffusers

Nozzle diffuser NC19


Dimensions
ØU
1
Ød

2
11

30 60
3
ØA

NC19 Ød ØA H ØU* Weight 4


mm mm mm mm kg
125 360 140 370 3.90
160 460 140 470 5.30 5
200 460 140 470 5.40
250 540 140 550 7.40
315 540 140 550 8.10
6
Description * ØU = ceiling grid opening
NC19 is a circular diffuser with individually adjustable noz-
zles. The diffuser is suitable for the horizontal supply of Ød 315, No mounting holes for MBB !
cooled air, where great flexibility in the dispersal pattern is
7
required. The diffuser can also be set to a vertical supply air
pattern, enabling supply of heated air. Installing this diffuser
in a plenum box type MBB can help to achieve a stable flow 8
of air to the diffuser as well as realise the potential for indi-
vidual adjustment.
9
• Adjustable dispersal patterns
• No pressure change for different dispersal patterns
• Suitable for horizontal or vertical supply air patterns
10
Maintenance
The face plate can be removed to enable cleaning of internal
parts or to gain access to the duct or box. The visible parts 11
of the diffuser can be wiped with a damp cloth.

12

13

14

15
Order code
Product NC19 - S - aaa
Materials and finish
16
Type
NC19
Material: Galvanised steel
Standard finish: Powder-coated
Functional use
S = Supply air Standard colour: RAL 9010, Gloss 30 17
Connection dim. Nozzles: White ABS plastic
Ød 125-315
The diffuser is available in other colours. Please contact 18
Example: NC19-S-200 Lindab’s sales department for further information.

We reserve the right to make changes without prior notice 161


29-10-2013
lindab | ceil ing di ffusers

Nozzle diffuser NC19


Accessories
1
Mounting brackets DCZ Plenum box MBB

NC19 + MBB
5
10 LxB
Extension piece MBZ
6 10

Ød1

C
H
Ød2

F E
8
Order code - accessoreies NC19 + MBB
duct NC19 B C E F H* L
9 Product aaa bbb
Ød1 mm Ød2 mm mm mm mm mm mm mm
Type
100 125 260 159 216 50 250 - 290 310
Size
100 160 260 159 216 50 250 - 290 310
10 Example: DCZ-200 125 125 310 184 262 50 275 - 315 376
125 160 310 184 262 50 275 - 315 376
125 200 310 184 262 50 275 - 315 376
160 160 380 220 323 50 309 - 349 459
11 160 200 380 220 323 50 309 - 349 459
Module plate LM 160 250 380 220 323 50 309 - 349 459
200 200 460 259 396 70 350 - 390 565
12 200 250 460 259 396 70 350 - 390 565
200 315 460 259 396 70 350 - 390 565
250 250 540 309 486 70 400 - 440 698

13 250 315 540 309 486 70 400 - 440 698


315 315 540 373 646 70 465 - 505 858

* Using accessory MBZ the H dimension will increase:


14 Ød2 = 125 - 200 mm => H +40 mm
Ød2 = 250 - 315 mm => H +60 mm

15 Order code
Product MBB - aaa - bbb - S
Type
Order code - module plate
16 MBB
Product LM a NC19 ccc Duct connection Ød1
Type Ø100-315
Ceiling system Diffuser dimension Ød2
17 Diffuser Ø125-315
Size Functional use
S = Supply air
18 Example: LM-1-NC19-200
Ceiling system - see introductory summary Example: NC19-S-200-MBB-200-200-S

162 We reserve the right to make changes without prior notice


29-10-2013
lind ab | cei ling di ffusers

Nozzle diffuser NC19


Technical data
1
Capacity Throw l0.2
Air flow qv [l/s] and [m3/h], total pressure Δpt [Pa], throw l0.2 Throw l0.2 [m] is specified at a terminal velocity of 0.2 m/s.
[m] and sound power level LWA [dB(A)] can be seen in the
diagrams. l0.2 [m] NC19-S 160
125 200
2
10
250
8 315
Frequency-related sound effect level 7

The sound effect level in the frequency band is defined as


6 3
5
LWA+Kok. Kok values are specified in chart beneath the dia- 4
grams on the following pages.
3
4
Quick selection, supply air 2

NC19 + MBB Δpt ≥ 50 Pa Δpt ≥ 50 Pa l0.2 [m]


5
duct NC19 30 dB(A) 35 dB(A) 1
qV [l/s]
30 40 50 60 70 80 100 150 200 300 500
Ød1 Ød2 l/s m3/h l/s m3/h
qV [m3/h]
100 125 25 90 33 119 150 200 300 500 700 1000 1500 6
100 160 39 140 47 169
NC19-S 160 250
125 125 35 126 41 148 l0.2 [m] 125 200 315
10
125 160 48 173 59 212
125 200 54 194 64 230
8 7
7
160 160 52 187 63 227 6
5
160 200 59 212 72 259
160 250 76 274 96 346
4 8
200 200 66 238 80 288 3

200 250 92 331 112 403


200 315 97 349 120 432 2
9
250 250 100 360 119 428
250 315 109 392 131 472
l0.2 [m]
315 315 121 436 143 515 1
30 40 50 60 70 80 100 150 200 300 500
qV [l/s]
10
qV [m3/h]
150 200 300 500 700 1000 1500

Sound attenuation 11
Sound attenuation of the diffusers ΔL from duct to room,
including end reflection, see table below
12
NC19 + MBB
duct NC19 Centre frequency Hz
Ød1 Ød2 63 125 250 500 1K 2K 4K 8K
100 125 20 16 6 15 20 20 19 23
13
100 160 16 16 4 13 18 19 17 21
125 125 17 15 10 19 20 20 19 22
125 160 15 14 7 18 18 18 18 21 14
125 200 13 12 5 15 15 16 17 19
160 160 16 15 11 22 20 20 20 20
160 200 16 15 8 21 19 19 19 21
15
160 250 16 14 5 17 14 16 18 19
200 200 15 10 8 16 20 18 20 18
200 250 13 9 5 13 17 15 19 17
200 315 13 9 4 11 16 15 17 17 16
250 250 14 8 8 16 18 18 18 19
250 315 14 8 6 14 17 16 17 18
315 315 8 10 9 14 17 17 18 24 17
Balancing
Balancing data is contained in a separate brochure. 18

We reserve the right to make changes without prior notice 163


29-10-2013
lindab | ceil ing di ffusers

Nozzle diffuser NC19


Technical data
1
Throws/Turning points NC19 without box – Supply air
Throw l0.2 [m] is specified at a terminal velocity of 0.2 m/s.
Turning point l0.0 [m] is specified for +5 K and +10 K respec-
2 tively.
ǻpt [Pa] NC19-S
100
125 160 200 250
315

70

NC19-S 160 250


3 l0.2 [m]
10
125 200 315 50
50

8 30 45
7
6 40
20
4 5
15
35
4
30
10
3 25

5 2
7
20 LWA dB(A)
5
qV [l/s]
20 30 40 50 60 70 80 100 150 200 300 400
qV [m3/h]

6 1
l0.2 [m] 80 100 150 200 300 400 500 700 1000

qV [l/s]
5 10 15 20 30 40 50 60 70 100 150 200
qV [m3/h]
20 30 40 50 60 70 100 150 200 300 500 700
7

NC19-S +5K 160


l0.0 [m]
8 10
125 200 250
315
8
7
6

9 5

10 2

11 1
l0.0 [m]
qV [l/s]
10 15 20 30 40 50 60 70 80 100 150 200
qV [m3/h]
40 50 60 70 80 100 150 200 300 500 700

12

NC19-S +10K 160 250


l0.0 [m]
13 10
125 200 315

8
7
6

14 5

15 2

16 1
l0.0 [m]
qV [l/s]
10 15 20 30 40 50 60 70 100 150 200 300
qV [m3/h]
40 50 60 70 100 150 200 300 500 700 1000

17

18

164 We reserve the right to make changes without prior notice


29-10-2013
lind ab | cei ling di ffusers

Nozzle diffuser NC19


Technical data
1
NC19 - 125 + MBB - Supply air NC19 - 160 + MBB - Supply air

¨pt [Pa] NC19-S-125+MBB-125-125-S


250
ǻpt [Pa] NC19-S-160+MBB-160-160-S
250
2
200 200
150 150

100
50
100
50
3
45
70 70 45
40
50 50 40

30
35
30
35 4
30
30
20 25 20
25
15 15
20
LWA dB(A)
20
LWA dB(A) 5
10 10
qV [l/s] qV [l/s]
15 20 25 30 40 50 60 70 80 100 30 40 50 60 70 80 100 120 140 160
qV [m3/h] qV [m3/h]
60 70 80 100 150 200 300 150 200 300 400 500
6
Hz 63 125 250 500 1K 2K 4K 8K Hz 63 125 250 500 1K 2K 4K 8K
Kok 11 1 -4 0 -5 -15 -23 -35 Kok 6 5 -3 -1 -4 -14 -21 -32
7
ǻpt [Pa] NC19-S-125+MBB-100-125-S ¨pt [Pa] NC19-S-160+MBB-125-160-S
250 250
200
50
200 8
150 150
45 50
100 100 45
40
70
35
70 40 9
50 50 35
30
30
30 30
25 25 10
20 20 20 20
15 15
LWA dB(A) LWA dB(A)
10
15 20 25 30 40 50 60 70
qV [l/s]
10
20 25 30 40 50 60 70 80 100 120
qV [l/s] 11
qV [m3/h] 3
qV [m /h]
60 70 80 100 150 200 80 100 150 200 300 400

Hz 63 125 250 500 1K 2K 4K 8K Hz 63 125 250 500 1K 2K 4K 8K


12
Kok 10 3 2 0 -7 -15 -22 -27 Kok 8 5 -1 -1 -6 -13 -17 -25

13
¨pt [Pa] NC19-S-160+MBB-100-160-S
250
200 50

150 45 14
40
100

70 35

50 30 15
25
30
20
20
15
16
LWA dB(A)
10
qV [l/s]
10 15 20 25 30 40 50 60 70 80 100

40 50 60 70 80 100 150 200 300


qV [m3/h] 17

Hz 63 125 250 500 1K 2K 4K 8K


Kok 10 4 1 0 -8 -12 -16 -21
18

We reserve the right to make changes without prior notice 165


29-10-2013
lindab | ceil ing di ffusers

Nozzle diffuser NC19


Technical data
1
NC19 - 200 + MBB - Supply air NC19 - 250 + MBB - Supply air

2 ǻpt [Pa] NC19-S-200+MBB-200-200-S


250
ǻpt [Pa] NC19-S-250+MBB-250-250-S
250
200 200

150 150

3 100
100

50 70 50
70
50 45
45
50 40
40
4 30 35
30 35
20 30
20 30 15 25
15 25 20
5 20
LWA dB(A)
10

7
LWA dB(A)
10
qV [l/s] qV [l/s]
30 40 50 60 70 80 100 120 140 160 50 60 70 80 100 120 140 160 180 200 240 280
qV [m3/h] qV [m3/h]
150 200 300 400 500 200 300 400 500 700 1000
6
Hz 63 125 250 500 1K 2K 4K 8K Hz 63 125 250 500 1K 2K 4K 8K
Kok 11 2 -5 0 -4 -16 -23 -33 Kok 10 3 -4 -1 -4 -15 -23 -34
7
ǻpt [Pa] NC19-S-200+MBB-160-200-S ǻpt [Pa] NC19-S-250+MBB-200-250-S
250 250
8 200 200
150 150

100 50 100 50

9 70 45 70 45

50 40 50 40
35 35
30 30
10 30 30
20 25 20 25
15 20 15
20
LWA dB(A) LWA dB(A)
11 10
30 40 50 60 70 80 100 120 140 160
qV [l/s]
10
50 60 70 80 100 120 140 160 180 200 240
qV [l/s]

qV [m3/h] qV [m3/h]
150 200 300 400 500 200 300 400 500 700

12 Hz 63 125 250 500 1K 2K 4K 8K Hz 63 125 250 500 1K 2K 4K 8K


Kok 9 4 -2 -1 -5 -14 -20 -28 Kok 6 7 -2 -1 -4 -14 -20 -29

13
¨pt [Pa] NC19-S-200+MBB-125-200-S ǻpt [Pa] NC19-S-250+MBB-160-250-S
250 250
200 200

14 150 50 150
50

100 45 100 45

70 40 70 40

15 50
35
50 35
30
30
30 30
25
25
20 20
16 15
20
15
20

LWA dB(A) LWA dB(A)


10 10
qV [l/s] qV [l/s]
20 25 30 40 50 60 70 80 100 120 140 30 40 50 60 70 80 90 150 200 250 300
17 80 100 150 200 300 400 500
qV [m3/h]
150 200 300 400 500 700 1000
qV [m3/h]

Hz 63 125 250 500 1K 2K 4K 8K Hz 63 125 250 500 1K 2K 4K 8K


18 Kok 6 5 0 0 -6 -12 -17 -25 Kok 11 6 1 -2 -5 -12 -18 -26

166 We reserve the right to make changes without prior notice


29-10-2013
lind ab | cei ling di ffusers

Nozzle diffuser NC19


Technical data
1
NC19 - 315 + MBB - Supply air

ǻpt [Pa] NC19-S-315+MBB-315-315-S


250
2
200
150

100
70 50
3
50 45
40
30

20
35 4
30
15
25
10
20
7
LWA dB(A) 5
5
qV [l/s]
50 60 70 80 90 100 150 200 250 300 350 400
qV [m3/h]
200 300 400 500 700 1250
6
Hz 63 125 250 500 1K 2K 4K 8K
Kok 9 1 -4 -1 -3 -17 -26 -40
7
ǻpt [Pa] NC19-S-315+MBB-250-315-S
250
200 8
150

100
50
70
45
9
50
40
30 35
20 30 10
15 25
10 20
LWA dB(A)
7
50 60 70 80 90 100 150 200 250 300 350 400
qV [l/s] 11
qV [m3/h]
200 300 400 500 700 1250

Hz 63 125 250 500 1K 2K 4K 8K


12
Kok 9 4 -2 -1 -4 -15 -23 -30

13
¨pt [Pa] NC19-S-315+MBB-200-315-S
250
200
150 14
100 50
70 45

50 40
15
35
30 30
25
20
15
20 16
LWA dB(A)
10
qV [l/s]
50 60 70 80 100 120 140 160 180 200 240 280

200 300 400 500 700 1000


qV [m3/h] 17

Hz 63 125 250 500 1K 2K 4K 8K


Kok 8 7 0 -2 -5 -14 -20 -30
18

We reserve the right to make changes without prior notice 167


29-10-2013
lind ab | cei ling di ffusers

Swirl diffuser RCG


Dimensions
ØU
1

H
Ød
ØD 3
RCG Ød ØD H ØU Free area A Weight
mm mm mm mm m2 kg 4
125 200 70 150 0,0031 0,40
160 250 70 200 0,0072 0,50
200 300 70 250 0,0106 0,60 5
250 350 90 300 0,0189 0,80
315 450 100 400 0,027 1,00
400 570 150 500 0.039 1,50
6
Description * ØU = Cutting dimension
RCG is a circular swirl diffuser with fixed bars. RCG is suita-
ble for the horizontal supply of very cold air. The swirl pat- 7
tern ensures optimum distribution and high induction, as
well as a large dynamic range. Installing a RCG diffuser in a
plenum box type MBB can help to achieve a stable flow of
air to the diffuser as well as realise the potential for individ- 8
ual adjustment. RCG can also be installed directly in the
duct using the traverse bracket GRZ1, which is available as
an accessory. 9
• Large dynamic range
• High induction
• Suitable for cooling at very low temperatures
10

Maintenance
Diffusers are removed to enable cleaning of the plenum box
11
or duct system. The visible parts of the diffuser can be
wiped with a damp cloth.
12

13

14

15

Order code
16
Product RCG aaa Materials and finish
Type Material: Steel
RCG Standard finish: Powder-coated 17
Connection dim. Standard colour: RAL 9010 Gloss 30
Ød 125-400
The diffuser is available in other colours. Please contact 18
Example: RCG-315 Lindab’s sales department for further information.

We reserve the right to make changes without prior notice 169


29-10-2013
lin dab | cei ling di ffusers

Swirl diffuser RCG


Accessories Dimensions
1
Traverse bracket GRZ1 Plenum box MBB

4
10 LxB
Extension piece MBZ
5
10

Ød1

C
H
Ød2
6

F E
7
RCG + MBB
Order code - accessoreies RCG + MBB
8 Product aaa bbb
duct RCG B C E F H* L
Ød1 mm Ød2 mm mm mm mm mm mm mm
Type
100 125 260 159 216 50 185 - 215 310
Size
100 160 260 159 216 50 185 - 215 310
9 125 125 310 184 262 50 210 - 240 376
Example: GRZ1-315
125 160 310 184 262 50 210 - 240 376
125 200 310 184 262 50 210 - 240 376
10 160 160 380 220 323 50 244 - 274 459
160 200 380 220 323 50 244 - 274 459
Module plate LM 160 250 380 220 323 50 264 - 304 459
200 200 460 259 396 70 305 - 345 565
11 200 250 460 259 396 70 325 - 365 565
200 315 460 259 396 70 325 - 365 565
250 250 540 309 486 70 360 - 400 698
12 250 315 540 309 486 70 360 - 400 698
250 400 540 309 486 70 410 - 450 698
315 315 540 373 646 70 425 - 465 858
13 315 400 540 373 646 70 475 - 515 858

* Using accessory MBZ the H dimension will increase:


Ød2 = 125 - 200 mm => H +40 mm
14 Ød2 = 250 - 315 mm => H +60 mm
Ød2 = 400 mm => H +80 mm

15 Order code
Product MBB aaa bbb S
Type
Order code - module plate
16 MBB
Product LM a RCG ccc Duct connection Ød1
Type Ø100-315
Ceiling system Diffuser dimension Ød2
17 Diffuser Ø125-400
Size Functional use
S = Supply air
18 Example: LM-1-RCG-315
Ceiling system - see introductory summary Example: RCG-315-MBB-315-315-S

170 We reserve the right to make changes without prior notice


29-10-2013
lind ab | cei ling di ffusers

Swirl diffuser RCG


Technical data
1
Capacity Throw l0.2
Air flow qv [l/s] and [m3/h], total pressure Δpt[Pa], throw l0.2 Throw l0.2 [m] is specified at a terminal velocity of 0.2 m/s.
[m] and sound power level LWA [dB(A)] can be seen in the
diagrams.
2
L  ;M= 2 #'    
 

Frequency-related sound effect level 

The sound effect level in the frequency band is defined as




 3
LWA+Kok. Kok values are specified in charts beneath the dia- 

grams on the following pages. 


4
Quick selection, supply air


RCG + MBB Δpt ≥ 50 Pa Δpt ≥ 50 Pa 5


duct RCG 30 dB(A) 35 dB(A) L;M=

Ød1 Ød2 l/s m3/h l/s m3/h Q6 ;LS =
            
100 125 17 61 20 72 Q6 ;MH= 6
           
100 160 28 101 33 119
125 125 20 72 24 86
125 160 32 115 39 140
125 200 42 151 52 187
Sound attenuation 7
Sound attenuation of the diffusers ΔL from duct to room,
160 160 34 122 41 148
including end reflection - see table below.
160 200 48 173 59 212
160 250 60 216 76 274 8
RCG + MBB
200 200 50 180 63 227
200 250 67 241 84 302 duct RCG Centre frequency Hz
Ød1 Ød2 63 125 250 500 1K 2K 4K 8K
200 315 90 324 111 400
100 125 20 16 7 18 19 18 17 21
9
250 250 76 274 93 335
250 315 99 356 122 439 100 160 19 16 5 17 17 16 16 19
250 400 109 392 143 515 125 125 17 15 9 21 17 19 18 20
315 315 119 428 142 511 125 160 13 14 8 20 14 16 16 20 10
315 400 142 511 177 637 125 200 13 12 5 17 13 14 15 18
160 160 18 15 9 22 18 17 19 20
160 200 17 15 8 21 17 16 18 19
11
160 250 16 15 4 17 14 14 16 18
200 200 14 9 8 18 18 15 18 17
200 250 13 10 5 15 17 14 17 16
200 315 11 8 3 13 15 13 16 16 12
250 250 15 8 8 15 17 16 17 18
250 315 15 7 6 13 15 14 16 17
250 400 14 5 4 12 13 13 14 16 13
315 315 7 10 9 13 16 15 17 21
315 400 7 8 9 12 15 15 16 19

Balancing
14
Balancing data is contained in a separate brochure.
15

16

17

18

We reserve the right to make changes without prior notice 171


29-10-2013
lin dab | cei ling di ffusers

Swirl diffuser RCG


Technical data
1
RCG without box – supply air RCG 125 + MBB - Supply air

2 ¨PT;0A= 2#'

     ¨pt [Pa] RCG-125+MBB-125-125-S
250
200
  150
 50
3 

100 45

70 40

50
  35
4   30
30

  25
20
 15 20
5 
,7!D"!
10
LWA dB(A)

Q6;LS= qV [l/s]
             10 15 20 25 30 40 50 60 70

Q6;M H= qV [m3/h]
40 50 60 70 80 100 150 200
6             

Hz 63 125 250 500 1K 2K 4K 8K


Kok 14 5 2 -3 -7 -10 -20 -31
7
¨pt [Pa] RCG-125+MBB-100-125-S
250
8 200
150 50

100 45

9 70 40

50 35

30
30
10 25
20
15 20
LWA dB(A)
11 10
5 10 15 20 25 30 40 50 60 70
qV [l/s]

qV [m3/h]
20 30 40 50 60 70 80 100 150 200

12 Hz 63 125 250 500 1K 2K 4K 8K


Kok 9 4 4 -3 -7 -11 -22 -33

13

14

15

16

17

18

172 We reserve the right to make changes without prior notice


29-10-2013
lind ab | cei ling di ffusers

Swirl diffuser RCG


Technical data
1
RCG 160 + MBB - Supply air RCG 200 + MBB - Supply air

¨pt [Pa] RCG-160+MBB-160-160-S


250
¨pt [Pa] RCG-200-MBB-200-200-S
250
2
200 200
150 150
50
100
45
100 50 3
45
70 70
40
40
50 50
35

30 30 30
35
4
30

20 25
20 25
15 20 15 20

10
LWA dB(A) LWA dB(A) 5
10
qV [l/s] qV [l/s]
20 25 30 40 50 60 70 80 100 30 40 50 60 70 80 100 120 140 160
qV [m3/h] qV [m3/h]
80 100 150 200 300 150 200 300 400 500
6
Hz 63 125 250 500 1K 2K 4K 8K Hz 63 125 250 500 1K 2K 4K 8K
Kok 5 7 3 -2 -7 -11 -22 -34 Kok 14 7 2 -2 -6 -13 -24 -35
7
¨pt [Pa] RCG-160+MBB-125-160-S ¨pt [Pa] RCG-200+MBB-160-200-S
250 250
200 200 8
150 50 150
50
100 45 100
45
70 40 70
40
9
50 35 50
35

30 30
30 30
25 25 10
20 20
20 20
15 15
LWA dB(A) LWA dB(A)
10
15 20 25 30 40 50 60 70 80 100
qV [l/s]
10
30 40 50 60 70 80 100 120 140 160
qV [l/s] 11
qV [m3/h] qV [m3/h]
60 70 80 100 150 200 300 150 200 300 400 500

Hz 63 125 250 500 1K 2K 4K 8K Hz 63 125 250 500 1K 2K 4K 8K


12
Kok 8 5 4 -3 -7 -12 -22 -34 Kok 11 7 3 -3 -7 -12 -22 -34

13
¨pt [Pa] RCG-160+MBB-100-160-S ¨pt [Pa] RCG-200+MBB-125-200-S
250 250
200 200
50
150
45
150 50
14
100 100 45
40
70 70 40
35
50
30
50 35 15
30
30 25 30
25
20 20 20
15 15
20 16
LWA dB(A) LWA dB(A)
10 10
qV [l/s] qV [l/s]
10 15 20 25 30 40 50 60 70 80 100 20 25 30 40 50 60 70 80 100 120 140

40 50 60 70 80 100 150 200 300


qV [m3/h]
80 100 150 200 300 400 500
qV [m3/h] 17

Hz 63 125 250 500 1K 2K 4K 8K Hz 63 125 250 500 1K 2K 4K 8K


Kok 12 4 4 -3 -7 -12 -20 -27 Kok 10 5 5 -4 -8 -12 -18 -27
18

We reserve the right to make changes without prior notice 173


29-10-2013
lin dab | cei ling di ffusers

Swirl diffuser RCG


Technical data
1
RCG 250 + MBB - Supply air RCG 315 + MBB - Supply air

2 ¨pt [Pa] RCG-250+MBB-250-250-S


250
¨pt [Pa] RCG-315+MBB-315-315-S
250
200 200
150 150

3 100
50
100
50
70 45 70
45
50 40 50
40
4 30
35
30
35
30 30
20 20
25 25
15 15
5 20
LWA dB(A)
20
LWA dB(A)
10 10
qV [l/s] qV [l/s]
50 60 70 80 100 120 140 160 180 200 240 280 50 60 70 80 90 100 150 200 250 300 350 400
3
qV [m /h] qV [m3/h]
200 300 400 500 700 1000 200 300 400 500 700 1250
6
Hz 63 125 250 500 1K 2K 4K 8K Hz 63 125 250 500 1K 2K 4K 8K
Kok 10 6 2 -3 -5 -12 -21 -29 Kok 12 4 2 -3 -4 -14 -22 -32
7
¨pt [Pa] RCG-250+MBB-200-250-S ¨pt [Pa] RCG-315+MBB-250-315-S
250 250
8 200 200
150 150

100 50 100
50
9 70 45 70
45
50 40 50
40
35
30 30 35
10 30 30
20 20
25 25
15 15
20 LWA dB(A) 20 LWA dB(A)
11 10
30 40 50 60 70 80 100 120 140 160
qV [l/s]
10
50 60 70 80 90 100 150 200 250 300 350 400
qV [l/s]

qV [m3/h] qV [m3/h]
150 200 300 400 500 200 300 400 500 700 1250

12 Hz 63 125 250 500 1K 2K 4K 8K Hz 63 125 250 500 1K 2K 4K 8K


Kok 8 7 3 -2 -6 -12 -22 -34 Kok 10 7 3 -3 -6 -14 -22 -32

13
¨pt [Pa] RCG-250+MBB-160-250-S ¨pt [Pa] RCG-315+MBB-200-315-S
250 250
200 200

14 150
50
150

100 100 50
45
70 40 70 45

15 50
35
50 40

35
30
30 30
30
25
20 20 25
16 15
20
15 20
LWA dB(A) LWA dB(A)
10 10
qV [l/s] qV [l/s]
30 40 50 60 70 80 100 120 140 160 180 50 60 70 80 100 120 140 160 180 200 240 280
17 150 200 300 400 500
qV [m3/h]
200 300 400 500 700 1000
qV [m3/h]

Hz 63 125 250 500 1K 2K 4K 8K Hz 63 125 250 500 1K 2K 4K 8K


18 Kok 12 6 3 -3 -7 -12 -20 -29 Kok 9 7 3 -2 -6 -13 -22 -31

174 We reserve the right to make changes without prior notice


29-10-2013
lind ab | cei ling di ffusers

Swirl diffuser RCG


Technical data
1
RCG 400 + MBB - Supply air

¨pt [Pa] RCG-400+MBB-315-400-S


250
2
200
150

100 50 3
70 45

50 40

30
35
4
30

20 25

15 20
LWA dB(A) 5
10
qV [l/s]
70 80 90 150 200 250 300 350 400 500
qV [m3/h]
300 400 500 700 1250 1500 2000
6
Hz 63 125 250 500 1K 2K 4K 8K
Kok 10 5 2 -4 -5 -11 -20 -28
7
¨pt [Pa] RCG-400+MBB-250-400-S
250
200 8
150

100 50

70 45 9
50 40

35
30
30 10
20
25
15
20 LWA dB(A)
10
50 60 70 80 90 100 150 200 250 300 350 400
qV [l/s] 11
qV [m3/h]
200 300 400 500 700 1250

Hz 63 125 250 500 1K 2K 4K 8K


12
Kok 9 6 2 -3 -5 -11 -19 -28

13

14

15

16

17

18

We reserve the right to make changes without prior notice 175


29-10-2013
lindab | ceil ing di ffuser

Plain diffuser LCC


Dimensions
1 Ød

50
2

47
*ØU = 525
Ø = 560
3 *ØU = Ceiling grid opening = 525 mm, all sizes.

LCC Ød Weight
4 mm kg
125 1.25
160 1.50
5 200 2.30
250 3.40
315 4.60

6 Description
LCC is a flush mounted circular diffuser with a circular Ød = 125-250 => LCC has mounting holes for MBB
unperforated face plate for installation in ceiling systems
7 and permanent ceilings. LCC can be used for both supply
and exhaust air. LCC is suitable for horizontal supply of
cooled air and has a large dynamic range. Installing an LCC
8 diffuser in a plenum box type MBB can help to achieve a
stable airflow to the diffuser as well as realise the potential
for individual adjustment.

9 • Simple and aesthetic appearance


• Large dynamic range
• Can be used for both supply and exhaust air
10
Maintenance
The faceplate can be removed to enable cleaning of internal
11 parts or to gain access to the plenum box. the visible parts Ød = 315 => LCC has no mounting holes for MBB !
of the diffuser can be wiped with a damp cloth.

12 Technical data
For full documentation including Quick selection, sound dia-
grams, and Kok-values, see LCP in the Integra chapter.
13

14
Brackets included for LCC, for details, see the Integra instal-
lation instruction.
15

16
Order code Materials and finish
Product LCC aaa Upper part: Galvanised steel
Face plate: Aluminium
17 Type
LCC Face plate finish: Powder coated
Connection dim. Standard colour: RAL 9010, gloss 30
Ød 125-315
18 Other colours are available. Please contact Lindab's sales
Example: LCC-160 department for futher information.

176 We reserve the right to make changes without prior notice


29-10-2013
lindab | ceilin g diff users

Plain diffuser LCC/LKP/LCP

LKP LCP
6
Description Dimensions
LCP is a flush-mounted square diffuser with a circular LKP
unperforated face plate for installation in ceiling systems.
7
Ød
LCP can be used for both supply and exhaust air. LCP is
suitable for the horizontal supply of cooled air and has a
large dynamic range. Installing an LCP diffuser in a plenum 8
50

box type MBB can help to achieve a stable airflow to the dif-
39

fuser as well as realise the potential for individual adjust-


595 *
ment. LKP has a square face plate and the same properties
as LCP. * ceiling system 1, other ceiling systems see Integra chapter 9
page 122-123.
• Simple and stylish appearance
• Large dynamic range LCP 10
• Can be used for both supply and exhaust air Ød
• Can be adapted to most ceiling systems
11
50

Maintenance
47

The face plate can be removed to enable cleaning of internal


595*
parts or to gain access to the duct or box. The visible parts 12
Ød = 315 => LCP has no mounting holes for MBB !
of the diffuser can be wiped with a damp cloth.

LKP/LCP Ød Weight
mm kg 13
125 3.2
160 3.2
200 3.3
14
250 3.4
315 3.5

15
Order code
Product LCP/LKP aaa b
Materials and finish 16
Type Grille box: Galvanised steel
LCP/LKP Face plate LKP: Galvanised steel
Connection dim. Face plate LCP: Aluminium
Ød 125-315 Face plate finish: Powder-coated
17
Ceiling system Standard colour: RAL 9010 Gloss 30
1 - 14
The diffuser is available in other colours. Please contact 18
Example: LCP-160-1 Lindab’s sales department for further information.

We reserve the right to make changes without prior notice 177


29-10-2013
lindab | ceil ing di ffusers

Plain diffuser LCC/LKP/LCP


Accessories Accessories
1
Plenum box MBB
LCC + MBB

2 10 LxB

10

Ød1

H
Ød2

4
F E
LKP + MBB LCP + MBB
5
10 LxB 10 LxB

6 10 10
Ød1

Ød1
C

C
H

H
Ød2 Ød2

F E F E
8
LKP + MBB LCC / LCP + MBB
duct LKP B C E F H* L duct LCP B C E F H* L
9 Ød1 mm Ød2 mm mm mm mm mm mm mm Ød1 mm Ød2 mm mm mm mm mm mm mm
100 125 260 159 216 50 198 - 238 310 100 125 260 159 216 50 206 - 246 310
100 160 260 159 216 50 198 - 238 310 100 160 260 159 216 50 206 - 246 310
125 125 310 184 262 50 223 - 263 376
10 125 125 310 184 262 50 231 - 271 376
125 160 310 184 262 50 223 - 263 376 125 160 310 184 262 50 231 - 271 376
125 200 310 184 262 50 223 - 263 376 125 200 310 184 262 50 231 - 271 376
160 160 380 220 323 50 257 - 297 459 160 160 380 220 323 50 265 - 305 459
11 160 200 380 220 323 50 257 - 297 459 160 200 380 220 323 50 265 - 305 459
160 250 380 220 323 50 257 - 297 459 160 250 380 220 323 50 265 - 305 459
200 200 460 259 396 70 298 - 338 565 200 200 460 259 396 70 306 - 346 565
12 200 250 460 259 396 70 298 - 338 565 200 250 460 259 396 70 306 - 346 565
200 315 460 259 396 70 298 - 338 565 200 315 460 259 396 70 306 - 346 565
250 250 540 309 486 70 348 - 388 698 250 250 540 309 486 70 356 - 396 698
250 315 540 309 486 70 348 - 388 698 250 315 540 309 486 70 356 - 396 698
13 315 315 540 373 648 70 413 - 453 858 315 315 540 373 646 70 421 - 461 858

* Using accessory MBZ the H dimension will increase: * Using accessory MBZ the H dimension will increase:
Ød2 = 125 - 200 mm => H +40 mm Ød2 = 125 - 200 mm => H +40 mm
14 Ød2 = 250 - 315 mm => H +60 mm Ød2 = 250 - 315 mm => H +60 mm

Order code
15 Product MBB - aaa - bbb - c
Type
MBB
16 Duct connection Ød1
Ø100-315
Diffuser dimension Ød2
17 Ø125-315
Functional use
S = Supply air
E = Exhaust
18
Example: LCP-160-1+MBB-160-160-S

178 We reserve the right to make changes without prior notice


29-10-2013
lindab | ceilin g diff users

Plain diffuser LCC/LKP/LCP


Technical data
1
Capacity Throw l0.2
Air flow qv [l/s] and [m3/h], total pressure Δpt [Pa], throw l0.2 Throw l0.2 [m] can be seen in the diagram for isothermal air,
[m] and sound power level LWA [dB(A)] can be seen in the at a terminal velocity of 0.2 m/s.
diagrams.
2
160 250
Frequency-related sound effect level l0.2 [m] LCC/LKP/LCP 125 200 315

The sound effect level in the frequency band is defined as


10
3
8
LWA+Kok. Kok values are specified in charts beneath the dia- 7
6
grams on the following pages. 5

4
4
Quick selection, supply air 3

LCC/LKP/LCP + MBB Δpt ≥ 50 Pa Δpt ≥ 50 Pa 2 5


duct LKP/LCP 30 dB(A) 35 dB(A)
Ød1 Ød2 l/s m3/h l/s m3/h l 0.2 [m]
100 125 37 133 44 158
1
15 20 30 40 50 60 70 100 150 200 300 500
qV [l/s] 6
100 160 39 140 48 173 qV [m3/h]
125 125 48 173 56 202 60 70 100 150 200 300 500 700 1000 1500

125 160 56 202 66 238


125 200 61 220 73 263
7
Sound attenuation
160 160 67 241 85 306
Sound attenuation of the diffusers ΔL from duct to room,
160 200 79 284 99 356
including end reflection, see table below. 8
160 250 95 342 113 407
200 200 92 331 117 421
LCC/LCP/LKP + MBB
200 250 105 378 122 439
LCC/
200 315 118 425 145 522
duct LCP/LKP Centre frequency Hz 9
250 250 112 403 132 475
250 315 131 472 168 605 Ød1 Ød2 63 125 250 500 1K 2K 4K 8K
315 315 144 518 169 608 100 125 17 15 10 17 15 18 19 21
100 160 17 16 6 10 18 18 18 21 10
125 125 17 15 10 17 15 18 19 21
125 160 15 14 10 17 16 17 18 21
125 200 13 12 7 13 13 16 17 18
160 160 17 15 12 21 19 19 21 21
11
160 200 17 16 10 20 17 17 19 20
160 250 16 14 7 17 15 16 19 20
200 200 13 11 10 17 18 15 19 18 12
200 250 14 11 8 15 19 15 18 17
200 315 14 9 7 13 18 14 17 17
250 250 15 10 9 17 18 18 19 19 13
250 315 15 8 9 16 18 16 18 18
315 315 8 10 10 17 18 17 18 24

Balancing 14
Balancing data is contained in a separate brochure.

15

16

17

18

We reserve the right to make changes without prior notice 179


29-10-2013
lindab | ceil ing di ffusers

Plain diffuser LCC/LKP/LCP


Technical data
1
LCC/LKP/LCP without box – supply air LCC/LKP/LCP 125 + MBB - Supply air

2 ¨ST;0 A= ,##,+0,#0

   ǻpt [Pa] LCP-125+MBB-125-125-S
250
  200
 50
 150
45
3 

 100
40

 70
 35
50
 30
4  


30 25

 20
20

 15
5 
,7!D" ! LWA dB(A)
 10
Q6 ;LS= qV [l/s]
       15 20 25 30 40 50 60 70 80 100
Q6 ;MH= qV [m3/h]
60 70 80 100 150 200 300
6      

Hz 63 125 250 500 1K 2K 4K 8K


Kok 13 7 1 -2 -6 -14 -20 -25
7
ǻpt [Pa] LCP-125+MBB-100-125-S
250
50
8 200
150 45

40
100

9 70
35

50 30

25
30
10 20
20

15
LWA dB(A)
10
11 10 15 20 25 30 40 50 60 70 80 90
qV [l/s]

qV [m3/h]
40 50 60 70 80 100 150 200 300

12 Hz 63 125 250 500 1K 2K 4K 8K


Kok 10 4 2 -2 -6 -10 -17 -23

13

14

15

16

17

18

180 We reserve the right to make changes without prior notice


29-10-2013
lindab | ceilin g diff users

Plain diffuser LCC/LKP/LCP


Technical data
1
LCC/LKP/LCP 160 + MBB - Supply air LCC/LKP/LCP 200 + MBB - Supply air

ǻpt [Pa] LCP-160+MBB-160-160-S


250
ǻpt [Pa] LCP-200+MBB-200-200-S
250
2
200 200
150 150
50
50
100 45 100
45
3
40
70 70 40
35
50 50 35
30
30 25 30
30 4
25
20 20 20 20
15 15
LWA dB(A) LWA dB(A) 5
10 10
qV [l/s] qV [l/s]
30 40 50 60 70 80 100 120 140 160 50 60 70 80 90 100 150 200 250 300
qV [m3/h] qV [m3/h]
150 200 300 400 500 200 300 400 500 700 1000
6
Hz 63 125 250 500 1K 2K 4K 8K Hz 63 125 250 500 1K 2K 4K 8K
Kok 13 8 0 -3 -6 -10 -19 -25 Kok 12 8 0 -3 -5 -14 -21 -24
7
ǻpt [Pa] LCP-160+MBB-125-160-S ǻpt [Pa] LCP-200+MBB-160-200-S
250 250
200
50
200 8
150 150
45
45
100 100
40
70
35
70
40
9
35
50 50
30 30

30 25 30 25

20 20
10
20 20
15 15
LWA dB(A) LWA dB(A)
10
20 25 30 40 50 60 70 80 100 120
qV [l/s]
10
30 40 50 60 70 80 100 120 140 160
qV [l/s] 11
qV [m3/h] qV [m3/h]
80 100 150 200 300 400 150 200 300 400 500

Hz 63 125 250 500 1K 2K 4K 8K Hz 63 125 250 500 1K 2K 4K 8K


12
Kok 9 8 1 -3 -6 -11 -16 -22 Kok 12 7 -1 -3 -5 -10 -15 -21

13
ǻpt [Pa] LCP-160+MBB-100-160-S ǻpt [Pa] LCP-200+MBB-125-200-S
250 250
200 200
50
45
150 150
45 14
40
100 100 40
35
70 70 35
50 30 50
30
15
25
30 30 25
20
20 20 20

15 15
16
LWA dB(A) LWA dB(A)
10 10
qV [l/s] qV [l/s]
10 15 20 25 30 40 50 60 70 80 100 20 25 30 40 50 60 70 80 100 120 140

40 50 60 70 80 100 150 200 300


qV [m3/h]
80 100 150 200 300 400 500
qV [m3/h] 17

Hz 63 125 250 500 1K 2K 4K 8K Hz 63 125 250 500 1K 2K 4K 8K


Kok 9 5 0 -1 -7 -10 -16 -21 Kok 6 6 0 -3 -5 -9 -16 -21
18

We reserve the right to make changes without prior notice 181


29-10-2013
lindab | ceil ing di ffusers

Plain diffuser LCC/LKP/LCP


Technical data
1
LCC/LKP/LCP 250 + MBB - Supply air LCC/LKP/LCP 315 + MBB - Supply air

2 ǻpt [Pa] LCP-250+MBB-250-250-S


250
ǻpt [Pa] LCP-315+MBB-315-315-S
250
200 200
150 150
50 50
3 100
45
100
45
70 70
40 40
50 50
35 35
4 30 30 30 30

25 25
20 20
15 20 15 20
5 LWA dB(A) LWA dB(A)
10 10
qV [l/s] qV [l/s]
50 60 70 80 100 120 140 160 180 200 240 280 50 60 70 80 90 100 150 200 250 300 350 400
3
qV [m /h] qV [m3/h]
200 300 400 500 700 1000 200 300 400 500 700 1250
6
Hz 63 125 250 500 1K 2K 4K 8K Hz 63 125 250 500 1K 2K 4K 8K
Kok 15 6 -1 -1 -5 -15 -23 -29 Kok 12 4 0 -2 -4 -14 -19 -27
7
ǻpt [Pa] LCP-250+MBB-200-250-S ǻpt [Pa] LCP-315+MBB-250-315-S
250 250
8 200 200
150 150 50
50

100 45 100 45

9 70 40 70 40

50 35 50 35

30 30
30 30
10 25 25

20 20 20 20
15 15
LWA dB(A) LWA dB(A)
11 10
50 60 70 80 100 120 140 160 180 200 240
qV [l/s]
10
50 60 70 80 90 100 150 200 250 300 350 400
qV [l/s]

qV [m3/h] qV [m3/h]
200 300 400 500 700 200 300 400 500 700 1250

12 Hz 63 125 250 500 1K 2K 4K 8K Hz 63 125 250 500 1K 2K 4K 8K


Kok 13 8 -1 -2 -5 -13 -20 -26 Kok 13 7 0 -2 -6 -10 -17 -23

13
ǻpt [Pa] LCP-250+MBB-160-250-S ǻpt [Pa] LCP-315+MBB-200-315-S
250 250
200 200

14 150 45 150 50

45
100 40 100
40
70 35 70
35
15 50 30 50
30
25
30 30 25
20
20 20 20
16 15 15
LWA dB(A) LWA dB(A)
10 10
qV [l/s] qV [l/s]
30 40 50 60 70 80 100 120 140 160 180 50 60 70 80 100 120 140 160 180 200 240 280
17 150 200 300 400 500
qV [m3/h]
200 300 400 500 700 1000
qV [m3/h]

Hz 63 125 250 500 1K 2K 4K 8K Hz 63 125 250 500 1K 2K 4K 8K


18 Kok 13 7 0 -4 -5 -11 -16 -22 Kok 12 10 0 -3 -6 -12 -19 -24

182 We reserve the right to make changes without prior notice


29-10-2013
lindab | ceilin g diff users

Plain diffuser LCC/LKP/LCP


Technical data
1
LCC/LKP/LCP without box – Exhaust LCC/LKP/LCP 125 + MBB - Exhaust air

¨pt [Pa] ,##LKP/LCP


250
125 160 ǻpt [Pa] LCP-125+MBB-125-125-E
250 50
2
200
200 200
250
150 45
315 150
100
70 50
100
40
3
45 70 35
50
40 50 30
30

20 30
35
30
25 4
15 25 20
20
10 20
15
7
LWA dB(A) LWA dB(A) 5
5 10
qV [l/s] qV [l/s]
40 50 60 70 100 150 200 300 10 15 20 25 30 40 50 60 80 100 120
qV [m3/h] qV [m3/h]
40 50 60 70 80 100 150 200 300 400
150 200 300 400 500 700 1000
6
Hz 63 125 250 500 1K 2K 4K 8K
Kok 12 4 -1 -1 -6 -12 -16 -22
7
ǻpt [Pa] LCP-125+MBB-100-125-E
250
50
200 8
150 45

100 40
70
35
9
50
30
30

20
25 10
15 20
LWA dB(A)
10
5 10 15 20 25 30 40 50 60 80
qV [l/s] 11
qV [m3/h]
20 30 40 50 60 70 80 100 150 200 300

Hz 63 125 250 500 1K 2K 4K 8K


12
Kok 13 -1 3 -1 -9 -11 -17 -23

13

14

15

16

17

18

We reserve the right to make changes without prior notice 183


29-10-2013
lindab | ceil ing di ffusers

Plain diffuser LCC/LKP/LCP


Technical data
1
LCC/LKP/LCP 160 + MBB - Exhaust air LCC/LKP/LCP 200 + MBB - Exhaust air

2 ǻpt [Pa] LCP-160+MBB-160-160-E


250
ǻpt [Pa] LCP-200+MBB-200-200-E
250
200 45 200 50

150 150 45
40
3 100
35
100 40

70 70 35
30
50 50 30
25
4 30 20 30
25

20
20 20
15 15
5 LWA dB(A) LWA dB(A)
10 10
qV [l/s] qV [l/s]
10 15 20 25 30 40 50 60 80 100 150 200 20 25 30 40 50 60 80 100 150 200 250
qV [m3/h] qV [m3/h]
40 50 60 70 80 100 150 200 300 400 500 700 80 100 150 200 300 400 500 700
6
Hz 63 125 250 500 1K 2K 4K 8K Hz 63 125 250 500 1K 2K 4K 8K
Kok 16 4 -1 -2 -5 -10 -16 -21 Kok 15 5 0 -2 -6 -10 -15 -23
7
ǻpt [Pa] LCP-160+MBB-125-160-E ǻpt [Pa] LCP-200+MBB-160-200-E
250 50 250
8 200 200
50

150 45 150 45

100 40 100 40

9 70 35 70 35

50 50 30
30
25
30 30
10 25
20
20 20
20
15 15
LWA dB(A) LWA dB(A)
10
11 10
10 15 20 25 30 40 50 60 80 100 120 140
qV [l/s]
10 15 20 25 30 40 50 60 80 100 150 200
qV [l/s]

qV [m3/h] qV [m3/h]
40 50 60 70 80 100 150 200 300 400 500 40 50 60 70 80 100 150 200 300 400 500 700

12 Hz 63 125 250 500 1K 2K 4K 8K Hz 63 125 250 500 1K 2K 4K 8K


Kok 14 5 0 -1 -6 -11 -15 -21 Kok 16 5 -1 -3 -5 -10 -15 -21

13
ǻpt [Pa] LCP-160+MBB-100-160-E ǻpt [Pa] LCP-200+MBB-125-200-E
250 250
200 50 200 50

14 150
45
150
45
100 100
40 40
70 70
35
15 50 50
35

30 30
30 30
25 25
20 20
16 15
20
15 20
LWA dB(A) LWA dB(A)
10 10
qV [l/s] qV [l/s]
5 10 15 20 25 30 40 50 60 80 10 15 20 25 30 40 50 60 80 100 120 140
17 20 30 40 50 60 70 80 100 150 200 300
3
qV [m /h]
40 50 60 70 80 100 150 200 300 400 500
qV [m3/h]

Hz 63 125 250 500 1K 2K 4K 8K Hz 63 125 250 500 1K 2K 4K 8K


18 Kok 11 3 2 0 -8 -13 -17 -23 Kok 11 3 -1 -2 -5 -10 -16 -22

184 We reserve the right to make changes without prior notice


29-10-2013
lindab | ceilin g diff users

Plain diffuser LCC/LKP/LCP


Technical data
1
LCC/LKP/LCP 250 + MBB - Exhaust air LCC/LKP/LCP 315 + MBB - Exhaust air

ǻpt [Pa] LCP-250+MBB-250-250-E


250
ǻpt [Pa] LCP-315+MBB-315-315-E
250
2
200 50 200 50
150 45 150 45

100 40 100 40 3
35 35
70 70
30
50 30 50
25

30
25
30 20
4
20
20 20
15 15
LWA dB(A) LWA dB(A) 5
10 10
qV [l/s] qV [l/s]
20 25 30 40 50 60 80 100 150 200 250 20 25 30 40 50 60 80 100 150 200 250 300
qV [m3/h] qV [m3/h]
80 100 150 200 300 400 500 700 80 100 150 200 300 400 500 700 1000
6
Hz 63 125 250 500 1K 2K 4K 8K Hz 63 125 250 500 1K 2K 4K 8K
Kok 11 4 1 -2 -5 -11 -17 -25 Kok 12 4 2 -3 -6 -9 -18 -27
7
ǻpt [Pa] LCP-250+MBB-200-250-E ǻpt [Pa] LCP-315+MBB-250-315-E
250 50 250
200 200 50 8
45
150 150 45
40
100 100 40

70
35
70 35 9
50 30 50 30

25 25
30 30
20
20
10
20 20
15 15
LWA dB(A) LWA dB(A)
10
20 25 30 40 50 60 80 100 150 200 250
qV [l/s]
10
20 25 30 40 50 60 80 100 150 200 250 300
qV [l/s] 11
qV [m3/h] qV [m3/h]
80 100 150 200 300 400 500 700 80 100 150 200 300 400 500 700 1000

Hz 63 125 250 500 1K 2K 4K 8K Hz 63 125 250 500 1K 2K 4K 8K


12
Kok 14 4 0 -2 -6 -11 -16 -25 Kok 12 5 2 -3 -6 -10 -17 -24

13
ǻpt [Pa] LCP-250+MBB-160-250-E ǻpt [Pa] LCP-315+MBB-200-315-E
250 50 250
50
200 200
45
150 150 45
14
40 40
100 100
35 35
70 70

50 30 50
30
15
25
25
30 30
20
20
20 20
15 15
16
LWA dB(A) LWA dB(A)
10 10
qV [l/s] qV [l/s]
10 15 20 25 30 40 50 60 80 100 150 200 20 25 30 40 50 60 80 100 150 200 250

40 50 60 70 80 100 150 200 300 400 500 700


3
qV [m /h]
80 100 150 200 300 400 500 700
qV [m3/h] 17

Hz 63 125 250 500 1K 2K 4K 8K Hz 63 125 250 500 1K 2K 4K 8K


Kok 19 6 -1 -4 -5 -12 -18 -26 Kok 14 5 0 -3 -5 -10 -16 -25
18

We reserve the right to make changes without prior notice 185


29-10-2013
l i nda b | c ei l i ng di ff u ser s

Lindab Versio

10

11

12

13

14

15

16

17

18
RS14, adjusted ceiling type Markant.

Right to alterations reserved 187


lin dab | ce ili n g d i ffu s e r s

Lindab Versio a series of ceiling adapted diffusers

Diffusers for mixed ventilation


1
Diffusers Product Functions Page

2 PS1 195

3 PS8 205

4
RS14 213

5
RS15 227

6
RS16 239
7

8 NS19 247

9 GS23 255

10

11

12

13
NS19-V.

14
NS19-H.

15

16

17

18
NS19-R. NS19-V+MBB.

188 Right to alterations reserved


l i nda b | c ei l i ng di ff u ser s

Lindab Versio a series of ceiling adapted diffusers

10

11
CMC Biopharmaceuticals A/S, Søborg.

Lindab Versio Unique flexibility 12


Lindab Versio is a series of square ceiling diffusers for Versio gives a unique freedom of selection and flexibility.
supply and exhaust air adapted for false ceilings. The final configurated diffuser is simple to mount and is
Versio is, as the name implies, a variety of possibilities delivered finished and adapted to the individual ceiling 13
to construct the diffuser to suit the specific need. A system.
large selection of face plates with different designs meet
requirements for both design and function. Different types 14
of plenum boxes ensure the possibility to connect the dif-
fuser to the duct system, and at the same time regulate
the diffusers individually. 15
Versio can be adapted to most ceiling systems, so the
diffuser will blend in naturally with the ceiling environ-
ment, and ensure a simple mounting, which will make 16
the job easier when mounting the diffuser directly at the
construction site.
17

NS19 with plenum box type H.


18

Right to alterations reserved 189


lin dab | ce ili n g d i ffu s e r s

Lindab Versio a series of ceiling adapted diffusers

Design Plenum boxes


1 See Comfort and Design Details, see chapter Plenum boxes
V H R

(Only R box)
Ventilation

Dimension
principle
2

AxB
Size
Product
Perforated mm mm H = 95 mm H = Ød + 90 mm H = 170 mm
3 PS 125
No.: 1 160 200 x 100
200 300 x 100
250 400 x 100
4 315 500 x 100

No.: 2 125
160 200 x 100
5
No.: 3 2 3
200 300 x 100
No.: 4
250 400 x 100
4 315 500 x 100

6 Perforated rotation mm mm H = 95 mm H = Ød + 90 mm H = 170 mm

125
No.: 8 160 200 x 100
200 300 x 100

7 250
315
400
500
x
x
100
100

No.: 9 125

8 No.: 10 9 10
160
200
200
300
x
x
100
100
No.: 11
250 400 x 100
11 315 500 x 100

9 Swirl mm mm H = 95 mm H = Ød + 90 mm H = 170 mm

RS 125
160 200 x 100

10 No.: 14 200
250
300
400
x
x
100
100
315 500 x 100

11 No.: 15
125
160 200 x 100
200 300 x 100
250 400 x 100
315 500 x 100

12
125
160 200 x 100
No.: 16
200 300 x 100

13 250
315
400
500
x
x
100
100

Nozzles mm mm H = 95 mm H = Ød + 90 mm H = 170 mm

14 NS 125
160 200 x 100
No.: 19 200 300 x 100
250 400 x 100

15 315 500 x 100

Grid mm mm H = 95 mm H = Ød + 90 mm H = 170 mm

16 GS
No.: 23
125
160 200 x 100
200 300 x 100
250 400 x 100
315 500 x 100

17

18

190 Right to alterations reserved


l i nda b | c ei l i ng di ff u ser s

Lindab Versio a series of ceiling adapted diffusers

Regulation Accessories
See product pages 1
1 2 MBB

2
Patterns
Size

Type
Grille box mm Damper Damper/mea.dev. MDR ( PS1-4 ) PBB MHS MBB

V
3
160 300
200 400
250 500
315 600 4
Plenum box mm Damper Damper/mea.dev.. PBB MHS MBB

H 125
160
300
400
5
200 500
250 600
315 600
6
Rectangular connection mm Damper Damper/mea.dev. . PBB MHS MBB

R
7
200 300
300 400
400 500
500 600

1. Product and tech. data depicted in catalogue.


8
2. Combination possible. Tech. data depicted in catalogue.
3. Combination possible. Tech. data not in catalogue.
4. If space is empty, combination is not possible.
9

10
Guide to diffuser selection
Lindab Versio starts with a product- and design choice based on function and design. Ex. : PS1 or RS14. The design is numbered,
11
1 2 3
and specifically described in the chapter ”Comfort and Design”. Then a choice must be made of a grille box / plenum box depen-
ding on the type of connection, circular or rectangular, vertical or horizontal.
12
To obtain the desired function, one has to decide how the diffuser should be used: Supply (S), Exhaust (E), or Low-impulse(L). If
2 3
the plenum box type H or R is chosen, it is necessary to know which type of regulation is required: without damper and measuring
2 4
device (0), with damper without measuring device (1) or with damper and measuring device (2). 13
The connection dimension for the diffuser/plenum box is set, and finally the ceiling system is stated. The ceiling systems are num-
2 3 bered, and more specifically described in “Ceiling adaption”.
4 14
3 Lindab Versio is ready to order after making the specific choices. The final configurated product is named in the order. Ordering
4 codes are also found on the product pages as well as in the rest of the product programme.

4 15
1

Example of ordering Versio + grille box/plenum box


16
In this example the order is for:
Square diffuser with non-adjustable swirl pattern. Integrated side-connected plenum
box with connection dimension ø200. The diffuser should be supplied with damper and 17
measuring device for individual regulation of the unit. The diffuser should be adapted to
T24 600x600 system ceiling in a cleanable design.

RS14 H S 2 200 1
Diffuser being ordered in the example
18

Right to alterations reserved 191


lin dab | ce ili n g d i ffu s e r s

Lindab Versio a series of ceiling adapted diffusers

Design Ceiling tile adaption


1 See Comfort and Design Details, see chapter Ceiling tile adaption
1 2 3 4 5 6

2
Size
Product
Danotile T24/T15 Danotile T24/T15 Permanent Dampa Clip-In Dampa Clip-In Luxalon Clip-In
3 Ecophon T24
Rockfon A24.
Ecophon T24
Rockfon A24
ceiling Bevelled edge Square edge

Grille box/plenum boxes


Perforated mm V H R V H R V H R V H R V H R V H R

4 PS 125
No.: 1 160
200
250
5 315

No.: 2 125
No.: 3 160
6
2 3
200
No.: 4
250
4 315

7 Perforated rotation mm V H R V H R V H R V H R V H R V H R

125
No.: 8 160
200

8 250
315

No.: 9 125

9 No.: 10
No.: 11
9 10 160
200
250
11 315

10 Swirl mm V H R V H R V H R V H R V H R V H R

RS 125
160
No.: 14
11 200
250
315

12 No.: 15
125
160
200
250
315
13
125
160
No.: 16
200

14 250
315

Nozzles mm V H R V H R V H R V H R V H R V H R

15 NS 125
160
No.: 19
200
250
16 315

Grid mm V H R V H R V H R V H R V H R V H R

GS
17
125
160
No.: 23 200
250
315

18

192 Right to alterations reserved


l i nda b | c ei l i ng di ff u ser s

Lindab Versio a series of ceiling adapted diffusers

Design Ceiling tile adaption


See Comfort and Design Details, see chapter Ceiling tile adaption 1
7 8 9 10 11 14

2
Size
Product
Danotile Contur Ecophon Focus Rockfon E10 24 Rockfon E10 15 Danotile Markant Ecophone
Ecophon D
Rockfon D-XL
DG Ecophon -
E / T24
Ecophon -
E / T15
Focus edge DS 3
Grille box/plenum boxes
Perforated mm V H R V H R V H R V H R V H R V H R

PS 125 4
No.: 1 160
200
250
315
5
No.: 3 125
No.: 4 160
2 3
200
250
6
4 315

Perforated rotation mm V H R V H R V H R V H R V H R V H R
7
125
No.: 8 160
200
250
315
8
No.: 9 125
No.: 10
No.: 11
9 10 160
200
9
250
11 315

Swirl mm V H R V H R V H R V H R V H R V H R 10
RS 125
160
No.: 14
200
250
11
315

No.: 15
125
160 12
200
250
315
13
125
160
No.: 16
200
250
315
14
Nozzles mm V H R V H R V H R V H R V H R V H R

NS 125 15
160
No.: 19
200
250
315
16
Grid mm V H R V H R V H R V H R V H R V H R

GS
17
125
160
No.: 23 200
250
315

18

Right to alterations reserved 193


lin dab | ce ili n g d i ffu s e r s

Lindab Versio a series of ceiling adapted diffusers

10

11

12

13 NS19.

14

15

16

17

18

194 Right to alterations reserved


lindab | ceili ng dif fusers

Versio PS1

PS1 with grille box type V PS1 with plenum box type H
6
Description Dimensions
PS1 is a square perforated diffuser. PS1 can be used for
both supply and exhaust air. PS1 is suitable for the horizon-
25
200 BxB 7
E
tal supply of cooled air. PS1 can also be used for low
impulse and is therefore useful for the supply of replacement
air in environments with high rates of air exchange. 8
Ød

H
• Suitable for both supply and exhaust air
• The possibility of 1-2-3-way dispersal 9
• Can be used for low impulse AxA

10
PS1-H A B H E Weight
Ød Pattern mm mm mm mm kg 10
160 400 *- 380 250 350 5,9
200 500 *- 460 290 390 8.50
250 600 *- 560 340 420 12.3
315 600 *- 560 405 420 13.1
11
* Face plate dimension A x A depends on ceiling system.
See "Ceiling adjustment" for detailed dimensions. For fur-
Order code
ther details on plenum box - see "Plenum boxes".
12
Product PS a b c d eee f
Type
Maintenance
PS
The face plate can be removed to enable cleaning of internal
13
Design
1 - 2 - 3- 4 parts or to gain access to the duct or box. The visible parts
Box type of the diffuser can be wiped with a damp cloth.
V-H-R 14
Functional use
S = Supply air
E = Exhaust Box type R , only exhaust
L = Low-impulse 15
Damper Materials and finish
0 = No damper ( Box : H, V )
1 = Damper ( Box : H, R ) Grille box/plenum box:
2 = Damper / Meas.outlets ( Box :H) Material: Galvanised steel 16
Connection dim.
Face plate:
Ø200-315 ( Box :V)
Material: Galvanised steel
Ø160-315 ( Box :H)
Standard finish: Powder-coated 17
200x100 - 500x100 ( Box :R)
Ceiling system Standard colour: RAL 9010, gloss 30
1 - 14 Go to chapter Ceiling tile adaption
The diffuser is available in other colours. Please contact 18
Example: PS-1-V-S-0-200-1 Lindab’s sales department for further information.

We reserve the right to make changes without prior notice 195


02-06-2014
lindab | ceil ing di ffusers

Versio PS1
Accessories
1 Blending profiles (set) MDR Plenum box MBB

4
Order code
Product MDR aaa PS1-V + MBB
5 Type
10 LxB
Pattern

6 Example: MDR-200 10

Ød1

H
Extension piece MBZ
Ød2

95
F E
8 Order code AxA

Product MBZ aaa


Type PS1-V + MBB
9 Size duct PS1-V B E F H* L
Ød1 mm Ød2 mm Pattern mm mm mm mm mm
Example: MBZ-200 125 200 400 310 262 50 280 - 320 376
160 200 400 380 323 50 314 - 354 459
10 Mounting bracket PBB
160 250 500 380 323 50 314 - 354 459
200 200 400 460 396 70 355 - 395 565
200 250 500 460 396 70 355 - 395 565
11 200 315 600 460 396 70 355 - 395 565
250 250 500 540 486 70 405 - 445 698
250 315 600 540 486 70 405 - 445 698
315 315 600 540 646 70 470 - 510 858
12
Suspension MHS * Using accessory MBZ the H dimension will increase:
Ød2 = 200 mm => H +40 mm
Ød2 = 250 - 315 mm => H +60 mm
13

14

Order code
15 Product MBB aaa bbb c
Type
MBB
16 Duct connection Ød1
Ø125-315
Diffuser dimension Ød2
17 Ø200-315
Order code Functional use
Product aaa S = Supply air
Type E = Exhaust
18
Example: MHS Example: PS-1-V-S-0-200-1+MBB-200-200-S

196 We reserve the right to make changes without prior notice


lindab | ceili ng dif fusers

Versio PS1
Technical data
1
Capacity Sound attenuation
Air flow qv [l/s] and [m3/h], total pressure Δpt [Pa], throw l0.2 Sound attenuation of the diffusers ΔL from duct to room,
[m] and sound power level LWA [dB(A)] can be seen in the including end reflection - see table below.
diagrams.
2

Frequency-related sound effect level PS1-V + MBB


The sound effect level in the frequency band is defined as
3
PS1-V + MBB
LWA+Kok. Kok values are specified in charts beneath the dia-
grams on the following pages. duct PS1-V Centre frequency Hz
Ød1 Ød2 63 125 250 500 1K 2K 4K 8K 4
125 200 14 11 4 15 15 15 16 17
Quick selection, supply air 160 200 14 14 7 22 18 17 19 20
PS1-V + MBB 160 250 14 14 4 17 15 15 16 19
200 200 13 10 7 16 19 17 19 18
5
PS1-V + MBB Δpt ≥ 50 Pa Δpt ≥ 50 Pa 200 250 11 9 6 15 17 15 18 16
duct PS1-V 30 dB(A) 35 dB(A) 200 315 13 8 3 12 16 14 16 15
Ød1 Ød2 l/s m3/h l/s m3/h 250 250 14 8 8 16 18 17 17 18 6
125 200 58 209 70 252 250 315 14 7 5 14 16 15 16 17
160 200 63 227 77 277 315 315 8 9 9 15 17 16 17 21
160 250 71 256 90 324 7
200 200 82 295 97 349 PS1 + H
200 250 88 317 108 389
200 315 108 389 139 500
250 250 106 382 124 446
PS1 + H 8
Size Ød Centre frequency Hz
250 315 124 446 150 540
mm 63 125 250 500 1K 2K 4K 8K
315 315 152 547 183 659
160 18 15 5 13 11 11 9 10
200 16 10 6 15 11 11 12 14
9
250 14 9 7 13 8 9 12 14
Supply air 315 12 8 8 14 10 9 11 14

PS1 + H 10
Mounting -and balancing instruction
PS1 + H Δpt ≥ 50 Pa Δpt ≥ 50 Pa For futher information go to www.lindQST.com and installa-
Size Ød Minimum 30 dB(A) 35 dB(A) tion -and balancing instruction. 11
mm l/s m3/h l/s m3/h l/s m3/h
160 30 108 51 184 57 205
200 49 176 69 248 83 299 12
250 49 176 93 335 114 410
315 82 295 140 504 164 590

13

14

15

16

17

18

We reserve the right to make changes without prior notice 197


lindab | ceil ing di ffusers

Versio PS1
Technical data
1
Throw l0.2 PS1-V without MBB
Throw l0.2 [m] is specified at a terminal velocity of 0.2 m/s. Supply air
2
L;M= 03  ¨pt [Pa] PS-1-V-S-0 200 250
 70
315

3 

50

40
 30 35


4 
20
25
30

15
20

10
315
5 7 250
L ;M= LWA dB(A)
 5
Q6;LS= qV [l/s]
             60 70 80 100 150 200 300 400 500
6            
Q6;MH=
300 400 500 700 1000 1500
qV [m3/h]

7 L;M= 03  Low-impulse






¨pt [Pa] PS1-V-L-0 200 250
8 

50
315

 50
30
 45
9 20 40

15 35

30
10 L ;M= 10 25

Q6;LS= 20
             7
Q6;MH= L WA dB(A)
11          
5
qV [l/s]
70 80 100 150 200 300 400 500
qV [m3/h]
300 400 500 700 1000 1500
L;M= 03 
12 



 Concerning low impulse, go to planning guide in chapter 12
13 
"Low impulse"


14 

L ;M=
15 
Q6;LS=
           
Q6;MH=
          

16

17

18

198 We reserve the right to make changes without prior notice


lindab | ceili ng dif fusers

Versio PS1
Technical data
1
PS1-V 200 + MBB - Supply air PS1-V 250 + MBB - Supply air

ǻpt [Pa] PS1-V-S-0-200+MBB-200-200-S


250
¨pt [Pa] PS1-V-S-0-250+MBB-250-250-S
250
2
200 200
150 150

100 100 3
50
70 70
45 50
50 50 45
40

30 35 30
40 4
35
30
20 20 30
25
15 15 25
20 LWA dB(A)
20
LWA dB(A) 5
10 10
qV [l/s] qV [l/s]
50 60 70 80 100 120 140 160 180 200 240 50 60 70 80 100 120 140 160 180 200 240 280
qV [m3/h] qV [m3/h]
200 300 400 500 700 200 300 400 500 700 1000
6
Hz 63 125 250 500 1K 2K 4K 8K Hz 63 125 250 500 1K 2K 4K 8K
Kok 13 0 -6 0 -4 -17 -25 -32 Kok 10 -1 -6 0 -4 -18 -25 -33
7
ǻpt [Pa] PS1-V-S-0-200+MBB-160-200-S ǻpt [Pa] PS1-V-S-0-250+MBB-200-250-S
250 250
200 200 8
150 150

100 100
50
70 45 70
45
50
9
50 40 50
40
35
35
30 30
30
30 10
20 25 20
25
15 15
20
LWA dB(A) 20 LWA dB(A)
10
30 40 50 60 70 80 100 120 140 160
qV [l/s]
10
50 60 70 80 100 120 140 160 180 200 240
qV [l/s] 11
qV [m3/h] qV [m3/h]
150 200 300 400 500 200 300 400 500 700

Hz 63 125 250 500 1K 2K 4K 8K Hz 63 125 250 500 1K 2K 4K 8K


12
Kok 8 3 -3 -1 -4 -14 -21 -27 Kok 9 4 -4 -1 -4 -15 -22 -28

13
ǻpt [Pa] PS1-V-S-0-200+MBB-125-200-S ǻpt [Pa] PS1-V-S-0-250+MBB-160-250-S
250 250
200 200
50
150 150
50
14
45
100 100
40 45
70 70
40
35
50 50
35
15
30
30 30 30
25
25
20 20
15
20
15
20 16
LWA dB(A) LWA dB(A)
10 10
qV [l/s] qV [l/s]
20 25 30 40 50 60 70 80 90 100 120 140 30 40 50 60 70 80 100 120 140 160 180

80 100 150 200 300 400 500


qV [m3/h]
150 200 300 400 500
qV [m3/h] 17

Hz 63 125 250 500 1K 2K 4K 8K Hz 63 125 250 500 1K 2K 4K 8K


Kok 9 5 1 -2 -6 -10 -15 -22 Kok 15 3 -1 -3 -4 -12 -19 -24
18

We reserve the right to make changes without prior notice 199


lindab | ceil ing di ffusers

Versio PS1
Technical data
1
PS1-V 315 + MBB - Supply air Low-impulse correction,
sound power level (LWA)
2 ǻpt [Pa] PS1-V-S-0-315+MBB-315-315-S and pressure loss (Δpt)
250
200 On the previous pages you can find diagrams for all sizes
150 PS1-V+MBB supply air. When low-impulse values are
3 100
wanted, use the correction factors in the table below.
70
50
50 PS1-V + MBB
45
4 30
40
35 PS1-V + MBB Low-impulse
20 30 duct PS1-V Correction factor
15 25 Ød1 Ød2 LWA Δpt
5 10 20
LWA dB(A)
125 200 -1 x1
qV [l/s]
50 60 70 80 90 100 150 200 250 300 350 400 160 200 -2 x 0,9
qV [m3/h]
200 300 400 500 700 1250
160 250 0 x1
6 200 200 -3 x0,9
200 250 0 x1
Hz 63 125 250 500 1K 2K 4K 8K
200 315 0 x1
Kok 12 0 -3 -1 -4 -16 -22 -28
7 250 250 0 x1
250 315 0 x1
315 315 0 x1
¨pt [Pa] PS1-V-S-0-315+MBB-250-315-S
250
8 200
150
Concerning low impulse, go to planning guide in chapter 12
"Low impulse"
100

9 70 50

50 45

40
30
10 30
35

20
15 25

20
LWA dB(A)
11 10
50 60 70 80 90 100 150 200 250 300 350 400
qV [l/s]

qV [m3/h]
200 300 400 500 700 1250

12 Hz 63 125 250 500 1K 2K 4K 8K


Kok 9 4 -3 -1 -4 -15 -22 -28

13
¨pt [Pa] PS1-V-S-0-315+MBB-200-315-S
250
200

14 150

100 50
45
70
40
15 50
35
30
30
25
20
16 15
20

LWA dB(A)
10
qV [l/s]
50 60 70 80 100 120 140 160 180 200 240 280
17 200 300 400 500 700 1000
qV [m3/h]

Hz 63 125 250 500 1K 2K 4K 8K


18 Kok 10 5 -1 -2 -4 -12 -19 -25

200 We reserve the right to make changes without prior notice


lindab | ceili ng dif fusers

Versio PS1
Technical data
1
PS1-V without MBB PS1-V 200 + MBB - Exhaust air
Exhaust air
¨pt [Pa] PS1-V-E-0-200+MBB-200-200-E
250
2
¨pt [Pa] PS-V-E-0 200 250 315 200
100
150 45
50
70
100 40 3
50 45
70 35
40 50
30
30
35
30 25
4
20
30
20 20
15
15

10
25
LWA dB(A) 5
10
20
L W A dB(A) qV [l/s]
7 20 25 30 40 50 60 80 100 150 200 250
qV [l/s] qV [m3/h]
100 150 200 300 400 500 700 1000 80 100 150 200 300 400 500 700

400 500 700 1000 1500 2000 3000


qV [m3/h] 6
Hz 63 125 250 500 1K 2K 4K 8K
Kok 15 5 1 -3 -6 -10 -14 -23
7
¨pt [Pa] PS1-V-E-0-200+MBB-160-200-E
250
200 50 8
150 45

100 40
70
35
9
50
30

30
25 10
20
20
15
LWA dB(A)
10
10 15 20 25 30 40 50 60 80 100 150 200
qV [l/s] 11
3
qV [m /h]
40 50 60 70 80 100 150 200 300 400 500 700

Hz 63 125 250 500 1K 2K 4K 8K


12
Kok 16 6 0 -3 -7 -9 -15 -21

13
¨pt [Pa] PS1-V-E-0-200+MBB-125-200-E
250
200
50
150 14
45
100
40
70

50 35 15
30
30

25
20
15 20
16
LWA dB(A)
10
qV [l/s]
10 15 20 25 30 40 50 60 80 100 120 140

40 50 60 70 80 100 150 200 300 400 500


qV [m3/h] 17

Hz 63 125 250 500 1K 2K 4K 8K


Kok 10 4 2 -2 -6 -10 -15 -22
18

We reserve the right to make changes without prior notice 201


lindab | ceil ing di ffusers

Versio PS1
Technical data
1
PS1-V 250 + MBB - Exhaust air PS1-V 315 + MBB - Exhaust air

2 ¨pt [Pa] PS1-V-E-0-250+MBB-250-250-E


250
¨pt [Pa] PS1-V-E-0-315+MBB-315-315-E
250
200 50 200 50
150 45 150
45
3 100 40 100
40
70 70
35
35
50 50
30
4 30 30
30
25
25
20 20 20
20
15 15
5 LWA dB(A) LWA dB(A)
10 10
qV [l/s] qV [l/s]
20 25 30 40 50 60 80 100 150 200 250 300 400 20 25 30 40 50 60 80 100 150 200 250 350 500
3
qV [m /h] qV [m3/h]
80 100 150 200 300 400 500 700 1250 80 100 150 200 300 400 500 700 1250 2000
6
Hz 63 125 250 500 1K 2K 4K 8K Hz 63 125 250 500 1K 2K 4K 8K
Kok 10 6 2 -3 -6 -10 -15 -23 Kok 11 5 3 -3 -7 -10 -15 -26
7
¨pt [Pa] PS1-V-E-0-250+MBB-200-250-E ¨pt [Pa] PS1-V-E-0-315+MBB-250-315-E
250 250
8 200 200
50
150 150
45
100 100 45
40
9 70 70 40
35
50 50
35
30
30 30 30
10 25
20 20 25
15 20 15
LWA dB(A) 20 LWA dB(A)
11 10
20 25 30 40 50 60 80 100 150 200 250
qV [l/s]
10
20 25 30 40 50 60 80 100 150 200 250 300 400
qV [l/s]

qV [m3/h] qV [m3/h]
80 100 150 200 300 400 500 700 80 100 150 200 300 400 500 700 1250

12 Hz 63 125 250 500 1K 2K 4K 8K Hz 63 125 250 500 1K 2K 4K 8K


Kok 14 5 1 -3 -5 -10 -15 -22 Kok 11 5 2 -3 -6 -11 -16 -23

13
¨pt [Pa] PS1-V-E-0-250+MBB-160-250-E ¨pt [Pa] PS1-V-E-0-315+MBB-200-315-E
250 250
200 200
50 50
14 150 150
45 45
100 100

70 40 70 40

15 50 35 50 35

30 30 30
30

20 25 20 25
16 15 15
20 20
LWA dB(A) LWA dB(A)
10 10
qV [l/s] qV [l/s]
10 15 20 25 30 40 50 60 80 100 150 200 20 25 30 40 50 60 80 100 150 200 250 300
17 40 50 60 70 80 100 150 200 300 400 500 700
qV [m3/h]
80 100 150 200 300 400 500 700 1000
qV [m3/h]

Hz 63 125 250 500 1K 2K 4K 8K Hz 63 125 250 500 1K 2K 4K 8K


18 Kok 15 6 0 -3 -6 -9 -14 -21 Kok 13 5 1 -3 -6 -10 -14 -22

202 We reserve the right to make changes without prior notice


lindab | ceili ng dif fusers

Versio PS1
Technical data
1
PS1+H - Supply air PS1+H - Supply air

¨pt [Pa] PS1-H-S-2-160


250
¨pt [Pa] PS1-H-S-2-315
250
2
200 200
150 150

100
50
100 3
70 70 50
45
50 50 45
40

30 35 30 35
40
4
30 30
20 20
25 25
15 15
20 LWA dB(A) 20 LWA dB(A) 5
10 10
qV [l/s] qV [l/s]
20 30 40 50 60 70 80 90 100 150 80 90 100 150 200 300
qV [m3/h] qV [m3/h]
80 90 100 150 200 300 400 500 300 400 500 700 1000
6
Hz 63 125 250 500 1K 2K 4K 8K Hz 63 125 250 500 1K 2K 4K 8K
Kok 8 4 3 -3 -6 -11 -15 -14 Kok 13 4 0 -1 -6 -13 -17 -27
7
¨pt [Pa] PS1-H-S-2-200
250
200 8
150

100
50
70
45
9
50 40
35
30
30 10
20 25
15 20
LWA dB(A)
10
40 50 60 70 80 90 100 150 200
qV [l/s] 11
qV [m3/h]
150 200 300 400 500 700

Hz 63 125 250 500 1K 2K 4K 8K


12
Kok 5 5 1 -1 -7 -12 -12 -18

13
¨pt [Pa] PS1-H-S-2-250
250
200
150 14
100
50
70 45
50 40 15
35
30
30
20
15
25 16
20
LWA dB(A)
10
qV [l/s]
50 60 70 80 90 100 150 200 300

200 300 400 500 700 1000


qV [m3/h] 17

Hz 63 125 250 500 1K 2K 4K 8K


Kok 9 5 2 -1 -7 -14 -18 -19
18

We reserve the right to make changes without prior notice 203


lindab | ceil ing di ffusers

Versio PS1
Technical data
1
PS1+H - Exhaust air PS1+H - Exhaust air

2 ǻpt [Pa] PS1-H-E-2-160


250
ǻpt [Pa] PS1-H-E-2-315
150
200
150 100

70
3 100
70 50 50
50
50 45
45 30
30 40 40
4 20 35
20
35
15
15 30
30
25 10
10
25
5 7
20
LWA dB(A)
7
20
LWA dB(A)
5 5
qV [l/s] qV [l/s]
30 40 50 60 70 80 90 100 150 200 70 80 90 100 150 200 300 400
qV [m3/h] qV [m3/h]
150 200 300 400 500 700 300 400 500 700 1000
6
Hz 63 125 250 500 1K 2K 4K 8K Hz 63 125 250 500 1K 2K 4K 8K
Kok 10 4 6 -3 -11 -12 -19 -25 Kok 11 3 1 1 -8 -16 -26 -37
7
ǻpt [Pa] PS1-H-E-2-200
250
8 200
150

100

9 70 50
50
45

30 40

10 20
35

15 30

10 25
LWA dB(A)
20
11 7
30 40 50 60 70 80 100 150 200 300
qV [l/s]

qV [m3/h]
150 200 300 400 500 700 1000

12 Hz 63 125 250 500 1K 2K 4K 8K


Kok 10 4 5 -2 -9 -13 -21 -29

13
ǻpt [Pa] PS1-H-E-2-250
250
200

14 150

100

70
50

15 50
45

30 40
35
20
30
16 15
25
10
20 LWA dB(A)
7
qV [l/s]
50 60 70 80 100 150 200 300
17 200 300 400 500 700 1000
qV [m3/h]

Hz 63 125 250 500 1K 2K 4K 8K


18 Kok 11 5 2 -2 -6 -12 -22 -32

204 We reserve the right to make changes without prior notice


li ndab | ceiling diffusers

Versio PS8

PS8 with grille box type V PS8 with plenum box type H
6
Description Dimensions
PS8 is a square perforated diffuser with swirl insert. PS8 fits
naturally into the ceiling and maintains the excellent techni-
25
200 BxB 7
E
cal properties of swirl diffusers. The swirl pattern ensures
high induction and a large dynamic range, and is therefore
ideal for the horizontal supply of very cold air. 8
Ød

H
• Discrete appearance
• Large dynamic range 9
• High induction AxA

10
• Ideal for the supply of very cold air
PS8-H A B H E Weight
Ød Pattern mm mm mm mm kg 10
125 300 *- 380 215 350 5.9
160 400 *- 380 250 350 5.9
200 500 *- 460 290 390 8.5 11
250 600 *- 560 340 420 12.3
315 600 *- 560 405 420 13.1

* Face plate dimension depends on ceiling system. See 12


"Ceiling adjustment" for detailed dimensions. For further
Order code details on plenum box - see "Plenum boxes".
Product PS a b S d eee f Maintenance 13
Type The face plate can be removed to enable cleaning of internal
PS parts or to gain access to the duct or box. The visible parts
Design of the diffuser can be wiped with a damp cloth.
8 - 9 - 10 - 11 14
Box type
V-H-R
Functional use
S = Supply air 15
Damper Materials and finish
0 = No damper ( Box : H, V )
1 = Damper ( Box : H, R ) Grille box/plenum box:
2 = Damper / Meas.outlets ( Box :H) Material: Galvanised steel 16
Connection dim.
Face plate:
Ø160-315 ( Box :V)
Material: Galvanised steel
Ø125-315 ( Box :H)
Standard finish: Powder-coated
17
200x100 - 500x100 ( Box :R)
Ceiling system Standard colour: RAL 9010, gloss 30
1 - 14 Go to chapter Ceiling tile adaption
The diffuser is available in other colours. Please contact 18
Example: PS-8-V-S-0-200-1 Lindab’s sales department for further information.

We reserve the right to make changes without prior notice 205


lindab | ceil ing di ffusers

Versio PS8
Accessories
1
Extension piece MBZ Plenum box MBB

3
Order code
4 Product MBZ aaa
Type
Size
5 PS8-V + MBB
Example: MBZ-200
10 LxB

6 Mounting bracket PBB


10

Ød1

H
Ød2
7

95
F E
8 AxA

PS8-V + MBB
9 Suspension MHS
duct PS8-V B E F H* L
Ød1 mm Ød2 mm Pattern mm mm mm mm mm
100 160 300 260 216 50 255 - 295 310
10 125 160 300 310 262 50 280 - 320 376
125 200 400 310 262 50 280 - 320 376
160 160 300 380 323 50 314 - 354 459
160 200 400 380 323 50 314 - 354 459
11 160 250 500 380 323 50 314 - 354 459
200 200 400 460 396 70 355 - 395 565
200 250 500 460 396 70 355 - 395 565
12 200 315 600 460 396 70 355 - 395 565
250 250 500 540 486 70 405 - 445 698
250 315 600 540 486 70 405 - 445 698

13 315 315 600 540 646 70 470 - 510 858

* Using accessory MBZ the H dimension will increase:


Ød2 = 160 - 200 mm => H +40 mm
14 Ød2 = 250 - 315 mm => H +60 mm

Order code
15 Product MBB aaa bbb c
Type
MBB
16 Duct connection Ød1
Ø100-315
Diffuser dimension Ød2
Ø160-315
17 Order code Functional use
Product aaa S = Supply air
Type E = Exhaust
18
Example: MHS Example: PS-8-V-S-0-200-1+MBB-200-200-S

206 We reserve the right to make changes without prior notice


li ndab | ceiling diffusers

Versio PS8
Technical data
1
Capacity Sound attenuation
Air flow qv [l/s] and [m3/h], total pressure Δpt [Pa], throw l0.2 Sound attenuation of the diffusers ΔL from duct to room,
[m] and sound power level LWA [dB(A)] can be seen in the including end reflection - see table below.
diagrams.
2
PS8-V + MBB
Frequency-related sound effect level
The sound effect level in the frequency band is defined as PS8-V + MBB
3
LWA+Kok. Kok values are specified in charts beneath the dia- duct PS8-V Centre frequency Hz
grams on the following pages. Ød1 Ød2 63 125 250 500 1K 2K 4K 8K
100 160 18 16 5 17 20 19 17 21
4
Quick selection, supply air 125 160 16 13 9 19 18 18 18 20

PS8-V + MBB 125 200 14 11 5 15 16 17 17 19


160 160 15 16 11 23 20 20 21 21 5
160 200 15 15 8 22 20 18 20 20
PS8-V + MBB Δpt ≥ 50 Pa Δpt ≥ 50 Pa
160 250 16 13 5 18 16 16 17 20
duct PS8-V 30 dB(A) 35 dB(A)
200 200 14 11 7 17 21 17 20 18
Ød1 Ød2 l/s m3/h l/s m3/h
200 250 14 9 5 14 18 15 18 17
6
100 160 31 112 38 137
200 315 13 9 3 13 17 15 17 16
125 160 36 130 43 155
250 250 13 8 7 17 18 18 18 18
125 200 48 173 60 216
250 315 16 7 5 16 16 17 17 18 7
160 160 37 133 44 158
315 315 9 9 9 16 17 17 18 23
160 200 52 187 62 223
160 250 67 241 84 302
200 200 59 212 70 252 PS8 + H 8
200 250 82 295 98 353
200 315 72 259 88 317 PS8 + H
250 250 83 299 97 349 Size Ød Centre frequency Hz 9
250 315 81 292 96 346 mm 63 125 250 500 1K 2K 4K 8K
315 315 - - 102 367 125 18 13 8 19 14 11 12 15
160 18 12 3 14 13 7 7 8
200 14 9 3 14 9 7 8 11
10
Supply air
250 14 8 7 10 8 7 9 12
PS8 + H 315 12 6 8 13 8 7 10 12
11
PS8 + H Δpt ≥ 50 Pa Δpt ≥ 50 Pa Installation -and balancing instruction
Size Ød Minimum 30 dB(A) 35 dB(A)
For futher information go to www.lindQST.com and Installa-
mm l/s m3/h l/s m3/h l/s m3/h tion -and balancing instruction. 12
125 26 93 23 83 29 104
160 33 118 46 166 54 194
200 57 204 61 220 74 266
250 71 254 - - 106 382
13
315 95 342 - - - -

14

15

16

17

18

We reserve the right to make changes without prior notice 207


lindab | ceil ing di ffusers

Versio PS8
Technical data
1
Throw l0.2 PS8-V without plenum box – Supply air
Throw l0.2 [m] is specified at a terminal velocity of 0.2 m/s.
2 The designation by the lines specifies the pattern on the ¨PT;0A= 03 6 3    
face plate. 




3 L;M=

03   
 




  
 
4 
 



 

 
5  ,7! D"!
 
Q6;LS=
           
Q6;MH=
           
6 
L ;M=
Q6;LS=
           
Q6;MH=
        
7

10

11

12

13

14

15

16

17

18

208 We reserve the right to make changes without prior notice


li ndab | ceiling diffusers

Versio PS8
Technical data
1
PS8-V 160 + MBB - Supply air PS8-V 200 + MBB - Supply air

¨pt [Pa] PS8-V-S-0-160+MBB-160-160-S


250
¨pt [Pa] PS8-V-S-0-200+MBB-200-200-S
250
2
200 200

150 150

100
100
50
3
50 70
70 45
45 50
50 40
40

30
30 35 4
35
20 30
20 30 15
25
15 25
20
LWA dB(A)
10 20
LWA dB(A) 5
10 7
qV [l/s] qV [l/s]
20 25 30 40 50 60 70 80 100 30 40 50 60 70 80 100 120 140 160
qV [m3/h] qV [m3/h]
80 100 150 200 300 150 200 300 400 500
6
Hz 63 125 250 500 1K 2K 4K 8K Hz 63 125 250 500 1K 2K 4K 8K
Kok 9 0 -2 1 -7 -17 -28 -38 Kok 13 0 -5 1 -6 -20 -29 -40
7
¨pt [Pa] PS8-V-S-0-160+MBB-125-160-S ¨pt [Pa] PS8-V-S-0-200+MBB-160-200-S
250 250
200 200 8
150 150

100 50 100 50

70 45 70 45 9
50 40 50 40
35 35
30 30
30 30 10
20 20
25 25
15 15
20 LWA dB(A) 20 LWA dB(A)
10
20 25 30 40 50 60 70 80 100 120
qV [l/s]
10
30 40 50 60 70 80 100 120 140 160
qV [l/s] 11
3
qV [m /h] qV [m3/h]
80 100 150 200 300 400 150 200 300 400 500

Hz 63 125 250 500 1K 2K 4K 8K Hz 63 125 250 500 1K 2K 4K 8K


12
Kok 8 3 -1 1 -7 -16 -24 -31 Kok 6 3 -2 1 -6 -16 -22 -30

13
¨pt [Pa] PS8-V-S-0-160+MBB-100-160-S ¨pt [Pa] PS8-V-S-0-200+MBB-125-200-S
250 250
200 200
150 50 150 50 14
45
100 100 45
40
70 70 40

50
35
50 35 15
30
30
30 30
25 25
20 20
15
20
15
20 16
LWA dB(A) LWA dB(A)
10 10
qV [l/s] qV [l/s]
10 15 20 25 30 40 50 60 70 80 100 20 25 30 40 50 60 70 80 100 120 140

40 50 60 70 80 100 150 200 300


qV [m3/h]
80 100 150 200 300 400 500
qV [m3/h] 17

Hz 63 125 250 500 1K 2K 4K 8K Hz 63 125 250 500 1K 2K 4K 8K


Kok 10 3 3 -1 -8 -14 -18 -23 Kok 6 5 2 -1 -6 -13 -19 -25
18

We reserve the right to make changes without prior notice 209


lindab | ceil ing di ffusers

Versio PS8
Technical data
1
PS8-V 250 + MBB - Supply air PS8-V 315 + MBB - Supply air

2 ¨pt [Pa] PS8-V-S-0-250+MBB-250-250-S


250
¨pt [Pa] PS8-V-S-0-315+MBB-315-315-S
250
200 200
150 150

100
3 100
70
70 50
50 50
50 45
45
40 30 40
4 30
35 20 35
20 30 15 30
15 25
25 10
20
5 10 20
LWA dB(A)
7
LWA dB(A)
7 5
qV [l/s] qV [l/s]
50 60 70 80 100 120 140 160 180 200 240 280 50 60 70 80 90 100 150 200 250 300 350 400
3
qV [m /h] qV [m3/h]
200 300 400 500 700 1000 200 300 400 500 700 1250
6
Hz 63 125 250 500 1K 2K 4K 8K Hz 63 125 250 500 1K 2K 4K 8K
Kok 8 0 -5 1 -6 -19 -28 -40 Kok 11 -4 -2 1 -7 -21 -26 -35
7
¨pt [Pa] PS8-V-S-0-250+MBB-200-250-S ¨pt [Pa] PS8-V-S-0-315+MBB-250-315-S
250 250
8 200 200
150
150
100
100
50 70
9 70 45 50
45
50

50 40
30 40
35
20 35
30
10 30 15 30
20 25 10 25
15
20 7 20
LWA dB(A) LWA dB(A)
11 10
50 60 70 80 100 120 140 160 180 200 240
qV [l/s]
5
50 60 70 80 90 100 150 200 250 300 350 400
qV [l/s]

qV [m3/h] qV [m3/h]
200 300 400 500 700 200 300 400 500 700 1250

12 Hz 63 125 250 500 1K 2K 4K 8K Hz 63 125 250 500 1K 2K 4K 8K


Kok 12 4 -2 0 -6 -16 -20 -26 Kok 8 0 -3 2 -8 -21 -29 -39

13
¨pt [Pa] PS8-V-S-0-250+MBB-160-250-S ¨pt [Pa] PS8-V-S-0-315+MBB-200-315-S
250 250
200 200

14 150
50
150

100 100
45
50
70 70
40
15 50
35
50
45

40
30
30 30 35
25
20 20 30
16 15
20
15 25
LWA dB(A) LWA dB(A)
10 10 20
qV [l/s] qV [l/s]
30 40 50 60 70 80 100 120 140 160 180 30 40 50 60 70 80 100 120 140 160 180
17 150 200 300 400 500
qV [m3/h]
150 200 300 400 500
qV [m3/h]

Hz 63 125 250 500 1K 2K 4K 8K Hz 63 125 250 500 1K 2K 4K 8K


18 Kok 15 5 1 -2 -5 -13 -20 -26 Kok 10 2 -1 1 -7 -18 -23 -29

210 We reserve the right to make changes without prior notice


li ndab | ceiling diffusers

Versio PS8
Technical data
1
PS8 + H - Supply air PS8 + H - Supply air

¨PT;0A= 03 ( 3  



¨PT;0A= 03 ( 3  

2
 
 





3

 
 

 


 
 4
 
 
 
 


,7! D"!

 ,7! D"! 5
 
Q6;LS= Q6;LS=
               
Q6;MH= Q6;MH=
             
6
Hz 63 125 250 500 1K 2K 4K 8K Hz 63 125 250 500 1K 2K 4K 8K
Kok 3 4 4 0 -10 -18 -25 -31 Kok 5 6 4 -1 -8 -18 -26 -33
7
¨PT;0A= 03 ( 3   ¨PT;0A= 03 ( 3  
 
  8
 

 



 
 9
 


  



  10
  
 
 
 ,7! D"! ,7! D"!


         
Q6;LS=

       
Q6;LS= 11
Q6;MH= Q6;MH=
           

Hz 63 125 250 500 1K 2K 4K 8K Hz 63 125 250 500 1K 2K 4K 8K


12
Kok 1 3 5 -2 -9 -19 -25 -32 Kok 7 5 3 0 -9 -21 -31 -41

13
¨PT;0A= 03 ( 3  



14





 15
 
 

 16
 
,7! D"!

Q6;LS=
         

     


Q6;MH= 17

Hz 63 125 250 500 1K 2K 4K 8K


Kok 7 7 3 -1 -7 -16 -23 -29
18

We reserve the right to make changes without prior notice 211


lind ab | cei ling di ffusers

Versio RS14

RS14 with grille box type V RS14 with plenum box type H
6
Description Dimensions
RS14 is a square swirl diffuser with fixed bars. RS14 can be
used for both supply and exhaust air. The swirl pattern
25
200 BxB 7
E
ensures high induction and a large dynamic range. It is
therefore ideal for the horizontal supply of very cold air.
8
Ød

• Large dynamic range

H
• High induction
• Suitable for cooling at very low temperatures 9
AxA
• Can be used for both supply air and exhaust

10
RS14-H A B H E Weight
Ød Pattern mm mm mm mm kg 10
125 400 *- 380 215 350 5.9
160 400 *- 380 250 350 5.9
200 500 *- 460 290 390 8.5
250 600 *- 560 340 420 12.3
11
315 600 *- 560 405 420 13.1

* Face plate dimension A x A depends on ceiling system.


See "Ceiling adjustment" for detailed dimensions. For fur- 12
Order code
ther details on plenum box - see "Plenum boxes".
Product RS 14 b c d eee f
Maintenance
Type
RS The face plate can be removed to enable cleaning of internal 13
Design parts or to gain access to the duct or box. The visible parts
14 of the diffuser can be wiped with a damp cloth.
Box type 14
V-H-R
Functional use
S = Supply air
E = Exhaust 15
Damper Materials and finish
0 = No damper ( Box : H, V )
1 = Damper ( Box : H, R ) Grille box/plenum box:
2 = Damper / Meas.outlets ( Box :H) Material: Galvanised steel 16
Connection dim.
Face plate:
Ø160-315 ( Box :V)
Material: Galvanised steel
Ø125-315 ( Box :H)
Standard finish: Powder-coated 17
200x100 - 500x100 ( Box :R)
Ceiling system Standard colour: RAL 9010, gloss 30
1 - 14 Go to chapter Ceiling tile adaption
The diffuser is available in other colours. Please contact 18
Example: RS-14-V-S-0-200-1 Lindab’s sales department for further information.

We reserve the right to make changes without prior notice 213


02-06-2014
lindab | ceil ing di ffusers

Versio RS14
Accessories
1
Extension piece MBZ Plenum box MBB

3
Order code
4 Product MBZ aaa
Type
Size
5 RS14-V + MBB
Example: MBZ-200
10 LxB

6 Mounting bracket PBB


10

Ød1

H
Ød2
7

95
F E
8 AxA

RS14-V + MBB
9 Suspension MHS
duct RS14-V B E F H* L
Ød1 mm Ød2 mm Pattern mm mm mm mm mm
100 160 300 260 216 50 255 - 295 310
10 125 160 300 310 262 50 280 - 320 376
125 200 400 310 262 50 280 - 320 376
160 160 300 380 323 50 314 - 354 459
160 200 400 380 323 50 314 - 354 459
11 160 250 500 380 323 50 314 - 354 459
200 200 400 460 396 70 355 - 395 565
200 250 500 460 396 70 355 - 395 565
12 200 315 600 460 396 70 355 - 395 565
250 250 500 540 486 70 405 - 445 698
250 315 600 540 486 70 405 - 445 698

13 315 315 600 540 646 70 470 - 510 858

* Using accessory MBZ the H dimension will increase:


Ød2 = 160 - 200 mm => H +40 mm
14 Ød2 = 250 - 315 mm => H +60 mm

Order code
15 Product MBB aaa bbb c
Type
MBB
16 Duct connection Ød1
Ø100-315
Diffuser dimension Ød2
Ø160-315
17 Order code Functional use
Product aaa S = Supply air
Type E = Exhaust
18
Example: MHS Example: RS-14-V-S-0-200-1+MBB-200-200-S

214 We reserve the right to make changes without prior notice


lind ab | cei ling di ffusers

Versio RS14
Technical data
1
Capacity Sound attenuation
Air flow qv [l/s] and [m3/h], total pressure Δpt [Pa], throw l0.2 Sound attenuation of the diffusers ΔL from duct to room,
[m] and sound power level LWA [dB(A)] can be seen in the including end reflection - see tables below.
diagrams.
2
RS14-V + MBB
Frequency-related sound effect level
The sound effect level in the frequency band is defined as RS14-V + MBB
3
LWA+Kok. Kok values are specified in charts beneath the dia- duct RS14-V Centre frequency Hz
grams on the following pages. Ød1 Ød2 63 125 250 500 1K 2K 4K 8K
100 160 20 16 5 19 20 19 18 21
4
Quick selection, supply air 125 160 16 13 9 20 18 18 19 20

RS14-V + MBB 125 200 14 12 6 17 16 16 18 19


160 160 17 16 10 24 20 20 21 21 5
160 200 15 15 7 22 21 19 20 21
RS14-V + MBB Δpt ≥ 50 Pa Δpt ≥ 50 Pa
160 250 15 14 5 20 16 16 17 19
duct RS14-V 30 dB(A) 35 dB(A)
200 200 14 11 7 18 21 17 20 18
Ød1 Ød2 l/s m3/h l/s m3/h
200 250 13 9 5 17 18 16 18 17
6
100 160 33 119 41 148
200 315 13 8 3 15 17 15 17 16
125 160 44 158 52 187
250 250 15 8 7 18 18 18 18 19
125 200 49 176 59 212
250 315 15 7 6 16 16 17 17 18 7
160 160 38 137 46 166
315 315 8 11 8 16 18 17 17 22
160 200 51 184 62 223
160 250 67 241 85 306
200 200 65 234 77 277 RS14 + H 8
200 250 77 277 95 342
200 315 100 360 124 446 RS14 + H
250 250 89 320 104 374 Size Ød Centre frequency Hz 9
250 315 110 396 132 475 mm 63 125 250 500 1K 2K 4K 8K
315 315 129 464 151 544 125 18 13 8 18 14 11 12 14
160 17 13 3 14 13 7 7 8
200 15 10 3 13 9 6 8 10
10
Supply air
250 12 9 6 11 8 7 10 12
RS14 + H 315 12 7 7 13 8 7 10 12
11
RS14 + H Δpt ≥ 50 Pa Δpt ≥ 50 Pa
RS14 + R
Size Ød Minimum 30 dB(A) 35 dB(A)
mm l/s m3/h l/s m3/h l/s m3/h
RS14 + R 12
125 26 93 28 101 34 122
Size-2 Mean frequency Hz
160 33 118 53 191 63 227
mm 63 125 250 500 1K 2K 4K 8K
200 57 204 65 234 80 288
250 71 254 89 320 107 385
200x100 19 14 9 6 5 3 3 4 13
300x100 16 11 5 5 6 5 3 4
315 95 342 - - 148 533
400x100 13 8 2 3 4 5 4 5
500x100 12 7 2 4 2 5 5 5
14
Installation -and balancing instruction
For futher information go to www.lindQST.com and installa-
tion -and balancing instruction.
15

16

17

18

We reserve the right to make changes without prior notice 215


lindab | ceil ing di ffusers

Versio RS14
Technical data
1
Throw l0.2 RS14-V without plenum box – Supply air
Throw l0.2 [m] is specified at a terminal velocity of 0.2 m/s.
2 The designation by the lines specifies the pattern of disper- ¨pt [Pa] RS14-V-S-0 160 200 250
sal. 100

70 315
50
3 23
50
45
L  ;M= 
 30 40


 20 35

4   15 30

10 25

20
5 
7
L WA dB(A)
5
qV [l/s]
 20 30 40 50 60 70 80 100 150 200 300
qV [m3/h]

6 80 100 150 200 300 400 500 700 1000

L ;M=

Q6 ;LS =
          

7        


Q6 ;MH=

10

11

12

13

14

15

16

17

18

216 We reserve the right to make changes without prior notice


lind ab | cei ling di ffusers

Versio RS14
Technical data
1
RS14-V 160 + MBB - Supply air RS14-V 200 + MBB - Supply air

¨pt [Pa] RS14-V-S-0-160+MBB-160-160-S


250
¨pt [Pa] RS14-V-S-0-200+MBB-200-200-S
250
2
200 200

150 150

100 50
100
50 3
70
70 45 45
50
50 40
40

30 35
30 35 4
20 30
30
20 15
25
15 25

20
LWA dB(A)
10 20 LWA dB(A) 5
10 7
qV [l/s] qV [l/s]
20 25 30 40 50 60 70 80 100 30 40 50 60 70 80 100 120 140 160
qV [m3/h] qV [m3/h]
80 100 150 200 300 150 200 300 400 500
6
Hz 63 125 250 500 1K 2K 4K 8K Hz 63 125 250 500 1K 2K 4K 8K
Kok 8 2 -1 1 -7 -17 -26 -36 Kok 11 0 -5 0 -4 -15 -26 -36
7
¨pt [Pa] RS14-V-S-0-160+MBB-125-160-S ¨pt [Pa] RS14-V-S-0-200+MBB-160-200-S
250 250
200 200 8
150 150

100 100 50
50
70 45 70 45 9
50 50 40
40

35 35
30 30

30 30
10
20 20
25 15 25
15
LWA dB(A) LWA dB(A)
20 20
10
qV [l/s]
10
30 40 50 60 70 80 100 120 140 160
qV [l/s] 11
20 25 30 40 50 60 80 100
3
qV [m /h] qV [m3/h]
80 100 150 200 300 400 150 200 300 400 500

Hz 63 125 250 500 1K 2K 4K 8K Hz 63 125 250 500 1K 2K 4K 8K


12
Kok 10 4 -1 1 -7 -17 -24 -29 Kok 11 2 -1 0 -6 -15 -24 -33

13
¨pt [Pa] RS14-V-S-0-160+MBB-100-160-S ¨pt [Pa] RS14-V-S-0-200+MBB-125-200-S
250 250
200 50 200
150 45 150 50 14
100 40 100 45

70 70 40
35
50
30
50 35 15
30
30 25 30
25
20
20 20
15 15
20 16
LWA dB(A) LWA dB(A)
10 10
qV [l/s] qV [l/s]
10 15 20 25 30 40 50 60 70 80 100 20 25 30 40 50 60 70 80 100 120 140

40 50 60 70 80 100 150 200 300


qV [m3/h]
80 100 150 200 300 400 500
qV [m3/h] 17

Hz 63 125 250 500 1K 2K 4K 8K Hz 63 125 250 500 1K 2K 4K 8K


Kok 10 4 2 -1 -7 -13 -18 -22 Kok 10 4 2 -1 -7 -13 -18 -22
18

We reserve the right to make changes without prior notice 217


lindab | ceil ing di ffusers

Versio RS14
Technical data
1
RS14-V 250 + MBB - Supply air RS14-V 315 + MBB - Supply air

2 ¨pt [Pa] RS14-V-S-0-250+MBB-250-250-S


250
¨pt [Pa] RS14-V-S-0-315+MBB-315-315-S
250
200 200
150 150

3 100 100

70 50 70 50
50 45 50 45

4 30
40
30
40

35 35
20 20 30
30
15 15 25
5 20
25 LWA dB(A)
20
LWA dB(A)
10 10
qV [l/s] qV [l/s]
50 60 70 80 100 120 140 160 180 200 240 280 50 60 70 80 90 100 150 200 250 300 350 400
3
qV [m /h] qV [m3/h]
200 300 400 500 700 1000 200 300 400 500 700 1250
6
Hz 63 125 250 500 1K 2K 4K 8K Hz 63 125 250 500 1K 2K 4K 8K
Kok 8 -1 -6 1 -5 -18 -29 -40 Kok 11 -1 -3 0 -5 -17 -25 -28
7
¨pt [Pa] RS14-V-S-0-250+MBB-200-250-S ¨pt [Pa] RS14-V-S-0-315+MBB-250-315-S
250 250
8 200 200
150 150

100 50 100

9 70 45 70 50
45
50 40 50
40
35
30 30 35
10 30 30
20 20
15 25 15 25
LWA dB(A) LWA dB(A)
20 20
11 10
50 60 70 80 100 120 140 160 180 200 240
qV [l/s]
10
50 60 70 80 90 100 150 200 250 300 350 400
qV [l/s]

qV [m3/h] qV [m3/h]
200 300 400 500 700 200 300 400 500 700 1250

12 Hz 63 125 250 500 1K 2K 4K 8K Hz 63 125 250 500 1K 2K 4K 8K


Kok 9 2 -3 0 -5 -17 -26 -29 Kok 12 2 -3 0 -5 -15 -22 -30

13
¨pt [Pa] RS14-V-S-0-250+MBB-160-250-S ¨pt [Pa] RS14-V-S-0-315+MBB-200-315-S
250 250
200 200

14 150
50
150

100 100 50
45
45
70 70
40
15 50
35
50
40

35
30 30 30 30
25 25
20 20
16 15 20 15 20
LWA dB(A) LWA dB(A)
10 10
qV [l/s] qV [l/s]
30 40 50 60 70 80 100 120 140 160 180 50 60 70 80 100 120 140 160 180 200 240 280
17 150 200 300 400 500
qV [m3/h]
200 300 400 500 700 1000
qV [m3/h]

Hz 63 125 250 500 1K 2K 4K 8K Hz 63 125 250 500 1K 2K 4K 8K


18 Kok 13 5 -1 -1 -5 -14 -20 -26 Kok 13 4 -1 -1 -6 -14 -19 -25

218 We reserve the right to make changes without prior notice


lind ab | cei ling di ffusers

Versio RS14
Technical data
1
RS14-V without plenum box – Exhaust air RS14-V 160 + MBB - Exhaust air

¨pt [Pa] RS14-V-E-0


150
160 200 250
315
¨pt [Pa] RS14-V-E-0-160+MBB-160-160-E
250
2
50 200
100
45 150
50
70
40 100 45 3
50 70
35 40
50
35
30
30

30 30
4
25
20
20 25
20
15 15
L WA dB(A)
20
LWA dB(A) 5
10 10
qV [l/s] qV [l/s]
20 30 40 50 60 70 80 100 150 200 250 10 15 20 25 30 40 50 60 80 100
qV [m3/h] qV [m3/h]
40 50 60 70 80 100 150 200 300
80 100 150 200 300 400 500 700
6
Hz 63 125 250 500 1K 2K 4K 8K
Kok 12 2 -1 -1 -5 -13 -22 -31
7
¨ pt [Pa] RS14-V-E-0-160+MBB-125-160-E
250
200
50
8
150
45
100

70
40
9
35
50
30
30
25 10
20
20
15
LWA dB(A)
10
qV [l/s] 11
10 15 20 25 30 40 50 60 80 100
3
qV [m /h]
40 50 60 70 80 100 150 200 300 400

Hz 63 125 250 500 1K 2K 4K 8K


12
Kok 11 4 -1 -1 -5 -13 -19 -27

13
¨pt [Pa] RS14-V-E-0-160+MBB-100-160-E
250
200 50

150 45 14
100 40

70
35
50
30
15
30 25

20
15
20
16
LWA dB(A)
10
qV [l/s]
5 10 15 20 25 30 40 50 60 80

20 30 40 50 60 70 80 100 150 200 300


qV [m3/h] 17

Hz 63 125 250 500 1K 2K 4K 8K


Kok 11 4 4 -2 -9 -13 -17 -23
18

We reserve the right to make changes without prior notice 219


lindab | ceil ing di ffusers

Versio RS14
Technical data
1
RS14-V 200 + MBB - Exhaust air RS14-V 250 + MBB - Exhaust air

2 ¨pt [Pa] RS14-V-E-0-200+MBB-200-200-E


250
¨pt [Pa] RS14-V-E-0-250+MBB-250-250-E
250
200 200
150 50 150
50
3 100 45 100 45
70 40 70 40
50 35 50 35
4 30
30
30
30

25 25
20 20
20 20
15 15
5 LWA dB(A) LWA dB(A)
10 10
qV [l/s] qV [l/s]
20 25 30 40 50 60 80 100 150 20 25 30 40 50 60 80 100 150 200 250
3
qV [m /h] qV [m3/h]
80 100 150 200 300 400 500 80 100 150 200 300 400 500 700
6
Hz 63 125 250 500 1K 2K 4K 8K Hz 63 125 250 500 1K 2K 4K 8K
Kok 13 4 -1 -1 -5 -12 -20 -28 Kok 8 5 0 -1 -5 -11 -20 -28
7
¨pt [Pa] RS14-V-E-0-200+MBB-160-200-E ¨pt [Pa] RS14-V-E-0-250+MBB-200-250-E
250 250
8 200
50
200
50
150 150
45 45
100 100
40 40
9 70 70
35 35
50 50
30 30
30 30
10 25 25

20 20 20 20
15 15
LWA dB(A) LWA dB(A)
11 10
10 15 20 25 30 40 50 60 80 100 150 200
qV [l/s]
10
20 25 30 40 50 60 80 100 150 200 250
qV [l/s]

qV [m3/h] qV [m3/h]
40 50 60 70 80 100 150 200 300 400 500 700 80 100 150 200 300 400 500 700

12 Hz 63 125 250 500 1K 2K 4K 8K Hz 63 125 250 500 1K 2K 4K 8K


Kok 16 6 0 -2 -6 -12 -18 -25 Kok 14 5 1 -2 -5 -11 -19 -26

13
¨pt [Pa] RS14-V-E-0-200+MBB-125-200-E ¨pt [Pa] RS14-V-E-0-250+MBB-160-250-E
250 250
200 50 200 50

14 150
45
150
45
100 100
40 40
70 70
35 35
15 50 50
30 30
30 30
25
25
20 20
16 15 20 15
20

LWA dB(A) LWA dB(A)


10 10
qV [l/s] qV [l/s]
10 15 20 25 30 40 50 60 80 100 120 140 10 15 20 25 30 40 50 60 80 100 150 200
17 40 50 60 70 80 100 150 200 300 400 500
qV [m3/h]
40 50 60 70 80 100 150 200 300 400 500 700
qV [m3/h]

Hz 63 125 250 500 1K 2K 4K 8K Hz 63 125 250 500 1K 2K 4K 8K


18 Kok 11 4 2 -1 -7 -12 -16 -23 Kok 15 7 1 -2 -7 -11 -17 -22

220 We reserve the right to make changes without prior notice


lind ab | cei ling di ffusers

Versio RS14
Technical data
1
RS14-V 315 + MBB - Exhaust air

¨pt [Pa] RS14-V-E-0-315+MBB-315-315-E


250
2
200
150
50
100
45
3
70
40
50
35

30 30
4
20 25

15 20
LWA dB(A) 5
10
qV [l/s]
20 25 30 40 50 60 80 100 150 200 250 300
qV [m3/h]
80 100 150 200 300 400 500 700 1250
6
Hz 63 125 250 500 1K 2K 4K 8K
Kok 11 4 1 -2 -5 -13 -22 -32
7
¨pt [Pa] RS14-V-E-0-315+MBB-250-315-E
250
200 8
150 50

100 45

70 40 9
50 35

30
30
25
10
20
15 20
LWA dB(A)
10
20 25 30 40 50 60 80 100 150 200 250 300
qV [l/s] 11
qV [m3/h]
80 100 150 200 300 400 500 700 1000

Hz 63 125 250 500 1K 2K 4K 8K


12
Kok 10 6 2 -2 -5 -12 -19 -27

13
¨pt [Pa] RS14-V-E-0-315+MBB-200-315-E
250
200
50
150
45
14
100
40
70

50 35
15
30
30
25
20
15
20 16
LWA dB(A)
10
qV [l/s]
20 25 30 40 50 60 80 100 150 200 250 300

80 100 150 200 300 400 500 700 1000


qV [m3/h] 17

Hz 63 125 250 500 1K 2K 4K 8K


Kok 14 5 2 -2 -6 -11 -16 -24
18

We reserve the right to make changes without prior notice 221


lindab | ceil ing di ffusers

Versio RS14
Technical data
1
RS14 + H - Supply air RS14 + H - Supply air

2 ǻpt [Pa] RS14-H-S-2-125


250
ǻpt [Pa] RS14-H-S-2-250
250
200 200
150 150

3 100 50 100
50
70 45 70
45
50
40 50
40
4 30 35
30 35
20 30
30
15 20
25
15 25
5 10
20 LWA dB(A)
20
LWA dB(A)
7 10
qV [l/s] qV [l/s]
15 20 30 40 50 60 70 80 50 60 70 80 90 100 150 200 300
3
qV [m /h] qV [m3/h]
60 70 80 90 100 150 200 200 300 400 500 700 1000
6
Hz 63 125 250 500 1K 2K 4K 8K Hz 63 125 250 500 1K 2K 4K 8K
Kok 14 8 5 -3 -10 -17 -23 -28 Kok 5 7 3 -1 -7 -16 -23 -31
7
ǻpt [Pa] RS14-H-S-2-160 ǻpt [Pa] RS14-H-S-2-315
250 250
8 200 200

150 150

100 50 100

9 70 45 70
50

45
50 40 50
40
35
30 30
10 30
30
35

20 25 20

15 15 25
20
LWA dB(A) LWA dB(A)
20
11 10
30 40 50 60 70 80 90 100 150
qV [l/s]
10
70 80 90 100 150 200 300
qV [l/s]

qV [m3/h] qV [m3/h]
150 200 300 400 500 300 400 500 700 1000

12 Hz 63 125 250 500 1K 2K 4K 8K Hz 63 125 250 500 1K 2K 4K 8K


Kok 2 5 5 -3 -7 -14 -20 -26 Kok 7 7 2 -1 -7 -16 -25 -35

13
ǻpt [Pa] RS14-H-S-2-200
250
200

14 150

100
50
70
45
15 50
40

30 35

30
16 20
15 25

20 LWA dB(A)
10
qV [l/s]
40 50 60 70 80 90 100 150 200
17 150 200 300 400 500 700
qV [m3/h]

Hz 63 125 250 500 1K 2K 4K 8K


18 Kok 10 7 2 -2 -6 -14 -21 -29

222 We reserve the right to make changes without prior notice


lind ab | cei ling di ffusers

Versio RS14
Technical data
1
RS14 + H - Exhaust air RS14 + H - Exhaust air

ǻpt [Pa] RS14-H-E-2-125


250
ǻpt [Pa] RS14-H-E-2-250
250
2
200 200
150 50 150
50
100 45 100
45
3
70 40 70
40
50 50
35 35

30 30 30 30
4
25 25
20 20
15 15 20
20
LWA dB(A) LWA dB(A) 5
10 10
qV [l/s] qV [l/s]
10 15 20 30 40 50 60 70 80 100 40 50 60 70 80 90 100 150 200 300
qV [m3/h] qV [m3/h]
40 50 60 70 80 100 150 200 300 150 200 300 400 500 700 1000
6
Hz 63 125 250 500 1K 2K 4K 8K Hz 63 125 250 500 1K 2K 4K 8K
Kok 3 7 3 -1 -8 -14 -19 -26 Kok 5 7 3 -2 -7 -13 -21 -31
7
ǻpt [Pa] RS14-H-E-2-160 ǻpt [Pa] RS14-H-E-2-315
250 250
200 200 8
150 150

100 100 50
50

70 45 70 45
9
50 40
50 40
35
35 30
30
30 25
30
10
20 20

15 25 15 20
LWA dB(A) LWA dB(A)
20
10
20 30 40 50 60 70 80 90 100 150
qV [l/s]
10
80 90 100 150 200 300 350
qV [l/s] 11
qV [m3/h] qV [m3/h]
80 90 100 150 200 300 400 500 300 400 500 700 1000

Hz 63 125 250 500 1K 2K 4K 8K Hz 63 125 250 500 1K 2K 4K 8K


12
Kok 2 6 5 -3 -8 -14 -22 -31 Kok 7 7 2 -2 -6 -14 -24 -35

13
ǻpt [Pa] RS14-H-E-2-200
250
200
150 14
100 50
70 45
50 40 15
35
30
30
20
15 25 16
20 LWA dB(A)
10
qV [l/s]
30 40 50 60 70 80 90 100 150 200

150 200 300 400 500 700


qV [m3/h] 17

Hz 63 125 250 500 1K 2K 4K 8K


Kok 7 7 4 -3 -7 -13 -20 -25
18

We reserve the right to make changes without prior notice 223


lindab | ceil ing di ffusers

Versio RS14
Technical data
1
RS14 + R - Supply air RS14 + R - Supply air

2 ¨PT;0A= 23 2 3  



¨PT;0A= 23 2 3  

 
 

3  


 
 

 
4  



  

 
 

5 
 , 7!D"! 
 , 7!D"!
 
Q6;LS= Q6;LS=
                  
Q6;MH= 
Q6;M H=

6             

Hz 63 125 250 500 1K 2K 4K 8K Hz 63 125 250 500 1K 2K 4K 8K


Kok 6 -1 3 -1 -7 -12 -25 -33 Kok 3 -1 3 -1 -7 -11 -19 -31
7
¨PT;0A= 23 2 3  

8 




9 








10  
 

 
, 7!D"!

11 
        
Q6;LS=


Q6;M H=
       

12 Hz 63 125 250 500 1K 2K 4K 8K


Kok 7 -1 4 -1 -8 -14 -22 -31

13
¨PT;0A= 23 2 3  



14 





15 





 

16  
 
, 7!D"!
 
Q6;LS=
         
17      

Q6;M H=

Hz 63 125 250 500 1K 2K 4K 8K


18 Kok -2 -1 3 -1 -6 -11 -20 -32

224 We reserve the right to make changes without prior notice


lind ab | cei ling di ffusers

Versio RS14
Technical data
1
RS14 + R - Exhaust air RS14 + R - Exhaust air

¨PT;0A= 23 2 %  



¨PT;0A= 23 2 %  

2
 
 




3
 

  


  

4

  
   


, 7!D"!



, 7!D"! 5
 
Q6;LS= Q6;LS=
                   

Q6;M H= Q6;MH=
               
6
Hz 63 125 250 500 1K 2K 4K 8K Hz 63 125 250 500 1K 2K 4K 8K
Kok 7 -1 4 -2 -8 -10 -18 -25 Kok 1 1 1 -2 -6 -9 -16 -25
7
¨PT;0A= 23 2 %  

 8






 

9




 10



 , 7!D"!

       
Q6;LS=

11
Q6;MH=
      

Hz 63 125 250 500 1K 2K 4K 8K


12
Kok 6 1 4 -2 -7 -10 -17 -25

13
¨PT;0A= 23 2 %  


 14







15
 





16
 
, 7!D"!

Q6;LS=
          

Q6;M H=
17
       

Hz 63 125 250 500 1K 2K 4K 8K


Kok 2 0 2 -2 -5 -10 -16 -24
18

We reserve the right to make changes without prior notice 225


lindab | ceilin g diff users

Versio RS15

RS15 with grille box type V RS15 with plenum box type H
6
Description Dimensions
RS15 is a square swirl diffuser with adjustable bars that can
be used for both supply and exhaust air. The swirl pattern
25
200 BxB 7
E
ensures high induction and a large dynamic range. It is
therefore ideal for the horizontal supply of very cold air. The
diffuser can also be set to a vertical supply air pattern, ena- 8
Ød

bling supply of heated air. The diffuser is supplied as stand-

H
ard with inward swirl. For exhaust, the diffuser is supplied as
standard without bars 9
AxA

10
• Large dynamic range
• High induction RS15-H A B H E Weight
• Ideal for the supply of very cold air Ød Pattern mm mm mm mm kg 10
• Adjustable for horizontal or vertical supply air pattern 160 400 *- 380 250 350 5.9
• Can be used for both supply air and exhaust 200 500 *- 460 290 390 8.5
250 600 *- 560 340 420 12.3 11
315 600 *- 560 405 420 13.1

* Face plate dimension A x A depends on ceiling system.


See "Ceiling adjustment" for detailed dimensions. For fur- 12
Order code ther details on plenum box - see "Plenum boxes".
Product RS 15 b c d eee f Maintenance
Type The face plate can be removed to enable cleaning of internal 13
RS parts or to gain access to the duct or box. The visible parts
Design of the diffuser can be wiped with a damp cloth.
15
Box type 14
V-H-R
Functional use
S = Supply air
E = Exhaust Materials and finish 15
Damper
0 = No damper ( Box : H, V ) Grille box/plenum box:
1 = Damper ( Box : H, R ) Material: Galvanised steel
2 = Damper / Meas.outlets ( Box :H)
16
Face plate:
Connection dim.
Material: Galvanised steel
Ø200-315 ( Box :V)
Bars: Black ABS-plastic
Ø160-315 ( Box :H)
Standard finish: Powder-coated 17
300x100 - 500x100 ( Box :R)
Ceiling system Standard colour: RAL 9010, gloss 30
1 - 14 Go to chapter Ceiling tile adaption
The diffuser is available in other colours. Please contact 18
Example: RS-15-V-S-0-200-1 Lindab’s sales department for further information.

We reserve the right to make changes without prior notice 227


lindab | ceil ing di ffusers

Versio RS15
Accessories
1
Extension piece MBZ Plenum box MBB

3
Order code
4 Product MBZ aaa
Type
Size
5 RS15-V + MBB
Example: MBZ-200
10 LxB

6 Mounting bracket PBB


10

Ød1

H
Ød2
7

95
F E
8 AxA

RS15-V + MBB
9 Suspension MHS
duct RS15-V B E F H* L
Ød1 mm Ød2 mm Pattern mm mm mm mm mm
125 200 400 310 262 50 280 - 320 376
10 160 200 400 380 323 50 314 - 354 459
160 250 500 380 323 50 314 - 354 459
200 200 400 460 396 70 355 - 395 565
200 250 500 460 396 70 355 - 395 565
11 200 315 600 460 396 70 355 - 395 565
250 250 500 540 486 70 405 - 445 698
250 315 600 540 486 70 405 - 445 698
12 315 315 600 540 646 70 470 - 510 858

* Using accessory MBZ the H dimension will increase:


Ød2 = 200 mm => H +40 mm
13 Ød2 = 250 - 315 mm => H +60 mm

14

Order code
15 Product MBB aaa bbb c
Type
MBB
16 Duct connection Ød1
Ø125-315
Diffuser dimension Ød2
17 Order code Ø200-315
Functional use
Product aaa S = Supply air
Type E = Exhaust
18
Example: MHS Example: RS-15-V-S-200-1+MBB-200-200-S

228 We reserve the right to make changes without prior notice


lindab | ceilin g diff users

Versio RS15
Technical data
1
Capacity Sound attenuation
Air flow qv [l/s] and [m3/h], total pressure Δpt [Pa], throw l0.2 Sound attenuation of the diffusers ΔL from duct to room,
[m] and sound power level LWA [dB(A)] can be seen in the including end reflection - see table below.
diagrams.
2
RS15-V + MBB
Frequency-related sound effect level
The sound effect level in the frequency band is defined as RS15-V + MBB
3
LWA+Kok. Kok values are specified in charts beneath the dia- duct RS15-V Centre frequency Hz
grams on the following pages. Ød1 Ød2 63 125 250 500 1K 2K 4K 8K
125 200 14 13 6 16 18 17 18 19
4
Quick selection, supply air 160 200 15 15 8 22 21 20 20 20

RS15-V + MBB 160 250 15 14 4 20 17 18 18 20


200 200 14 11 8 17 21 18 21 18 5
200 250 14 9 5 17 18 16 18 17
RS15-V + MBB Δpt ≥ 50 Pa Δpt ≥ 50 Pa
200 315 12 9 4 16 17 16 17 16
duct RS15-V 30 dB(A) 35 dB(A)
250 250 15 9 8 19 19 18 18 18
Ød1 Ød2 l/s m3/h l/s m3/h
250 315 16 7 5 15 16 17 17 18
6
125 200 53 191 63 227
315 315 10 10 8 16 18 17 17 23
160 200 56 202 67 241
160 250 72 259 91 328
RS15 + H
7
200 200 60 216 73 263
200 250 84 302 102 367
200 315 94 338 119 428 RS15 + H
250 250 94 338 112 403 Size Ød Centre frequency Hz 8
250 315 107 385 128 461 mm 63 125 250 500 1K 2K 4K 8K
315 315 123 443 144 518 160 17 12 5 15 14 10 9 9
200 14 8 4 13 10 7 8 11 9
Supply air 250 12 8 6 9 7 7 8 10
315 12 6 7 12 6 6 8 10
RS15 + H
10
RS15 + R
RS15 + H Δpt ≥ 50 Pa Δpt ≥ 50 Pa
Size Ød Minimum 30 dB(A) 35 dB(A)
mm l/s m3/h l/s m3/h l/s m3/h
RS15 + R 11
Size-2 Mean frequency Hz
160 33 118 53 191 63 227
mm 63 125 250 500 1K 2K 4K 8K
200 57 204 65 234 80 288
300x100 16 11 5 5 6 5 3 4
250 71 254 89 320 107 385
400x100 13 8 2 3 4 5 4 5
12
315 95 342 - - 148 533
500x100 12 7 2 4 2 5 5 5

Installation -and balancing instruction 13


For futher information go to www.lindQST.com and installa-
tion -and balancing instruction.
14

15

16

17

18

We reserve the right to make changes without prior notice 229


lindab | ceil ing di ffusers

Versio RS15
Technical data
1
Throw l0.2 Throws/turning points
Throw l0.2 [m] is specified at a terminal velocity of 0.2 m/s. Throw l0.2 [m] can be seen in the diagram. The throw applies
The designation by the lines specifies the pattern of disper- for isothermal air at a terminal velocity of 0.2 m/s. Turning
2 point l0.0 (m) can be seen in the diagram for heated air, +5 K
sal.
and +10 K respectively.
Inward swirl The designation by the lines specifies the pattern of disper-
3 sal.
l0.2 [m] RS15
10
400
l0.2 [m] RS15 400 500 600
8
4 7
6
500 10

8
600
5 7
6
4
5
5 3 4

3
2

6 2

l0.2 [m]
1
qV [l/s]
30 40 50 60 70 80 100 150 200 300
l0.2 [m]
7 qV [m3/h]
1
qV [l/s]
150 200 300 500 700 1000 30 40 50 60 70 80 100 150 200 300 500
qV [m3/h]
150 200 300 500 700 1000 1500
Outward swirl
8
l0.2 [m] RS15 l0.0 [m] RS15 +5K 400 500 600
400
10 500 10

9 8
7
600
8
7
6 6
5 5

4
10 4

3 3

2 2
11
l0.2 [m] l0.0 [m]
1 1
qV [l/s] qV [l/s]
12 30 40 50 60 70 80 100 150 200 300 30 40 50 60 70 80 100 150 200 300 500
qV [m3/h]
qV [m3/h]
150 200 300 500 700 1000 150 200 300 500 700 1000 1500

13 RS15 +10K
Horizontal and vertical bars l0.0 [m] 400 500
10
600
8
7
14 6
5

15 3

16
l0.0 [m]
1
qV [l/s]
30 40 50 60 70 80 100 150 200 300 500

17 150 200 300 500 700 1000 1500


qV [m3/h]

18

230 We reserve the right to make changes without prior notice


25-05-2014
lindab | ceilin g diff users

Versio RS15
Technical data
1
RS15-V without plenum box - Supply air RS15-V 200 + MBB - Supply air

¨pt [Pa] RS15-V-S-0


100
200 250 ¨pt [Pa] RS15-V-S-0-200+MBB-200-200-S
250
2
200
70
315 150
50
50

45
100 50 3
45
30 70
40
50 40
20

15
35
30
35 4
30
30
10 20
25 25
15
7
20 L WA dB(A) 20 LWA dB(A) 5
5 10
qV [l/s] qV [l/s]
50 60 70 80 90 100 150 200 300 30 40 50 60 70 80 100 120 140 160
qV [m3/h] qV [m3/h]
150 200 300 400 500
200 300 400 500 700 1000
6
Hz 63 125 250 500 1K 2K 4K 8K
Kok 13 2 -4 0 -5 -14 -21 -29
7
¨pt [Pa] RS15-V-S-0-200+MBB-160-200-S
250
200 8
150
50

100 45

70 40 9
50
35

30 30
10
20 25

15
20
LWA dB(A)
10
30 40 50 60 70 80 100 120 140 160
qV [l/s] 11
qV [m3/h]
150 200 300 400 500

Hz 63 125 250 500 1K 2K 4K 8K


12
Kok 11 4 -2 -1 -5 -13 -19 -27

13
¨pt [Pa] RS15-V-S-0-200+MBB-125-200-S
250
200
50
150
45
14
100
40
70
35
50
30
15
30 25

20 20

15
16
LWA dB(A)
10
qV [l/s]
20 25 30 40 50 60 70 80 100 120 140

80 100 150 200 300 400 500


qV [m3/h] 17

Hz 63 125 250 500 1K 2K 4K 8K


Kok 12 5 1 -1 -6 -11 -16 -22
18

We reserve the right to make changes without prior notice 231


lindab | ceil ing di ffusers

Versio RS15
Technical data
1
RS15-V 250 + MBB - Supply air RS15-V 315 + MBB - Supply air

2 ¨pt [Pa] RS15-V-S-0-250+MBB-250-250-S


250
¨pt [Pa] RS15-V-S-0-315+MBB-315-315-S
250
200 200
150 150

3 100 50 100
50
70 45 70 45
50 40 50
40
4 30
35
30
35

30 30
20 20
25
15 25 15
5 20
LWA dB(A) 20 LWA dB(A)
10 10
qV [l/s] qV [l/s]
50 60 70 80 100 120 140 160 180 200 240 280 50 60 70 80 90 100 150 200 250 300 350 400
3
qV [m /h] qV [m3/h]
200 300 400 500 700 1000 200 300 400 500 700 1250
6
Hz 63 125 250 500 1K 2K 4K 8K Hz 63 125 250 500 1K 2K 4K 8K
Kok 10 2 -3 0 -5 -14 -20 -30 Kok 9 3 0 0 -6 -13 -20 -30
7
¨pt [Pa] RS15-V-S-0-250+MBB-200-250-S ¨pt [Pa] RS15-V-S-0-315+MBB-250-315-S
250 250
8 200 200
150 150

100 50 100 50

9 70 45 70 45

50 40 50 40

35 35
30 30
10 30 30
20 25 20
25
15 15
20 20
LWA dB(A) LWA dB(A)
11 10
50 60 70 80 90 100 150 200
qV [l/s]
10
50 60 70 80 90 100 150 200 250 300 350 400
qV [l/s]

qV [m3/h] qV [m3/h]
200 300 400 500 700 200 300 400 500 700 1250

12 Hz 63 125 250 500 1K 2K 4K 8K Hz 63 125 250 500 1K 2K 4K 8K


Kok 11 4 -1 0 -7 -14 -22 -30 Kok 10 4 -1 -1 -5 -13 -19 -28

13
¨pt [Pa] RS15-V-S-0-250+MBB-160-250-S ¨pt [Pa] RS15-V-S-0-315+MBB-200-315
250 250
200 200

14 150 50 150
50
100 45 100
45
40
70 70
40
15 50 35 50
35
30
30 30 30
25
20 20 25
16 15
20
15 20
LWA dB(A) LWA dB(A)
10 10
qV [l/s] qV [l/s]
30 40 50 60 70 80 100 120 140 160 180 50 60 70 80 100 120 140 160 180 200 240 280
17 150 200 300 400 500
qV [m3/h]
200 300 400 500 700 1000
qV [m3/h]

Hz 63 125 250 500 1K 2K 4K 8K Hz 63 125 250 500 1K 2K 4K 8K


18 Kok 12 4 0 -2 -5 -11 -18 -24 Kok 10 6 0 -1 -6 -12 -18 -27

232 We reserve the right to make changes without prior notice


lindab | ceilin g diff users

Versio RS15
Technical data
1
RS15-V without plenum box - Exhaust air RS15-V 200 + MBB - Exhaust air

¨pt [Pa] RS15-V-E-0


100
200
250
¨pt [Pa] RS15-V-E-0-200+MBB-200-200-E
250
2
200 50
70
150 45
315
50
50 100 40 3
30 45 70
35
40 50
20 30
15
35
30
4
25
30
10 20
25 20
15
7
20 L WA dB(A) LWA dB(A) 5
5 10
qV [l/s] qV [l/s]
90 100 150 200 300 400 500 20 25 30 40 50 60 80 100 150 200 250
qV [m3/h] qV [m3/h]
80 100 150 200 300 400 500 700
400 500 700 1000 1500
6
Hz 63 125 250 500 1K 2K 4K 8K
Kok 14 5 1 -3 -6 -10 -15 -23
7
¨pt [Pa] RS15-V-E-0-200+MBB-160-200-E
250
200
50
8
150 45

100 40

70 35 9
50 30

25
30

20
10
20
15
LWA dB(A)
10
10 15 20 25 30 40 50 60 80 100 150 200
qV [l/s] 11
3
qV [m /h]
40 50 60 70 80 100 150 200 300 400 500 700

Hz 63 125 250 500 1K 2K 4K 8K


12
Kok 14 6 0 -2 -7 -9 -15 -19

13
¨pt [Pa] RS15-V-E-0-200+MBB-125-200-E
250
200 50
150
45
14
100
40
70

50 35 15
30
30

25
20
15
16
20
LWA dB(A)
10
qV [l/s]
10 15 20 25 30 40 50 60 80 100 120 140

40 50 60 70 80 100 150 200 300 400 500


qV [m3/h] 17

Hz 63 125 250 500 1K 2K 4K 8K


Kok 13 4 1 -1 -7 -11 -15 -22
18

We reserve the right to make changes without prior notice 233


lindab | ceil ing di ffusers

Versio RS15
Technical data
1
RS15-V 250 + MBB - Exhaust air RS15-V 315 + MBB - Exhaust air

2 ¨pt [Pa] RS15-V-E-0-250+MBB-250-250-E


250
¨pt [Pa] RS15-V-E-0-315+MBB-315-315-E
250
200 200
50 50
150 150

3 100
45
100
45

40 40
70 70
35 35
50 50

4 30
30
30
30

25
25
20 20 20
20
15 15
5 LWA dB(A) LWA dB(A)
10 10
qV [l/s] qV [l/s]
20 25 30 40 50 60 80 100 150 200 250 300 400 20 25 30 40 50 60 80 100 150 200 250 350 500
qV [m3/h] qV [m3/h]
80 100 150 200 300 400 500 700 1250 80 100 150 200 300 400 500 700 1250 2000
6
Hz 63 125 250 500 1K 2K 4K 8K Hz 63 125 250 500 1K 2K 4K 8K
Kok 10 6 3 -4 -6 -10 -16 -24 Kok 12 6 3 -3 -6 -11 -16 -26
7
¨pt [Pa] RS15-V-E-0-250+MBB-200-250-E ¨pt [Pa] RS15-V-E-0-315+MBB-250-315-E
250 250
8 200 50 200
50
150 150
45
45
100 100
40
9 70 70
40
35
50 50 35
30
30
30 30
10 25 25
20 20
20 20
15 15
LWA dB(A) LWA dB(A)
11 10
20 25 30 40 50 60 80 100 150 200 250 300
qV [l/s]
10
20 25 30 40 50 60 80 100 150 200 250 300 400
qV [l/s]

qV [m3/h] qV [m3/h]
80 100 150 200 300 400 500 700 1000 80 100 150 200 300 400 500 700 1250

12 Hz 63 125 250 500 1K 2K 4K 8K Hz 63 125 250 500 1K 2K 4K 8K


Kok 14 5 1 -3 -6 -10 -13 -21 Kok 11 6 2 -4 -6 -10 -16 -23

13
¨pt [Pa] RS15-V-E-0-250+MBB-160-250-E ¨pt [Pa] RS15-V-E-0-315+MBB-200-315-E
250 250
200 200
50 50
14 150 150
45
45
100 100
40 40
70 70

15 50 35 50 35

30 30
30 30
25
20 20 25
16 15 20 15
20
LWA dB(A) LWA dB(A)
10 10
qV [l/s] qV [l/s]
10 15 20 25 30 40 50 60 80 100 150 200 20 25 30 40 50 60 80 100 150 200 250 300
17 40 50 60 70 80 100 150 200 300 400 500 700
3
qV [m /h]
80 100 150 200 300 400 500 700 1000
qV [m3/h]

Hz 63 125 250 500 1K 2K 4K 8K Hz 63 125 250 500 1K 2K 4K 8K


18 Kok 15 7 1 -3 -6 -10 -16 -19 Kok 14 5 1 -3 -6 -10 -14 -22

234 We reserve the right to make changes without prior notice


lindab | ceilin g diff users

Versio RS15
Technical data
1
RS15 + H - Supply air RS15 + H - Supply air

ǻpt [Pa] RS15-H-S-2-160


250
ǻpt [Pa] RS15-H-S-2-315
250
2
200 200
150 150

100 50 100 3
45 50
70 70
40 45
50 50

30
35
30
40
4
30 35

20 25 20 30

15 15 25
20
LWA dB(A)
20
LWA dB(A) 5
10 10
qV [l/s] qV [l/s]
30 40 50 60 70 80 90 100 150 80 90 100 150 200 250 300
qV [m3/h] qV [m3/h]
150 200 300 400 500 300 400 500 700 1000
6
Hz 63 125 250 500 1K 2K 4K 8K Hz 63 125 250 500 1K 2K 4K 8K
Kok 2 5 5 -3 -7 -14 -20 -26 Kok 7 7 2 -1 -7 -16 -25 -35
7
ǻpt [Pa] RS15-H-S-2-200
250
200 8
150

100
50
70
45
9
50
40

30 35

30
10
20
15 25

20 LWA dB(A)
10
40 50 60 70 80 90 100 150 200
qV [l/s] 11
qV [m3/h]
150 200 300 400 500 700

Hz 63 125 250 500 1K 2K 4K 8K


12
Kok 10 7 2 -2 -6 -14 -21 -29

13
ǻpt [Pa] RS15-H-S-2-250
250
200
150 14
100
50
70
45
50
40
15
30 35

30
20
15 25
16
LWA dB(A)
20
10
qV [l/s]
50 60 70 80 90 100 150 200 250 300

200 300 400 500 700 1000


qV [m3/h] 17

Hz 63 125 250 500 1K 2K 4K 8K


Kok 5 7 3 -1 -7 -16 -23 -31
18

We reserve the right to make changes without prior notice 235


lindab | ceil ing di ffusers

Versio RS15
Technical data
1
RS15 + H - Exhaust air RS15 + H - Exhaust air

2 ǻpt [Pa] RS15-H-E-2-160


250
ǻpt [Pa] RS15-H-E-2-315
250
200 200
150 150

3 100
50 100 50
70
45 70 45
50
40 50 40

4 30 35
30
35

20 30 30
15 20 25
25
15
5 10
20 LWA dB(A)
20
LWA dB(A)
7 10
qV [l/s] qV [l/s]
30 40 50 60 70 80 90 100 150 80 90 100 150 200 250 300 400
qV [m3/h] qV [m3/h]
150 200 300 400 500 300 400 500 700 1000
6
Hz 63 125 250 500 1K 2K 4K 8K Hz 63 125 250 500 1K 2K 4K 8K
Kok 9 7 6 -4 -10 -13 -22 -31 Kok 7 6 2 -2 -5 -12 -24 -33
7
ǻpt [Pa] RS15-H-E-2-200
250

8 200
150

100
50
70
9 50
45

40
30 35
20
10 15
25
30

10 20
LWA dB(A)
7
qV [l/s]
11 30 40 50 60 70 80 90 100 150 200 250
qV [m3/h]
150 200 300 400 500 700

12 Hz 63 125 250 500 1K 2K 4K 8K


Kok 6 9 4 -4 -8 -12 -19 -29

13 ǻpt [Pa] RS15-H-E-2-250


250
200
150

14 100
45
50

70
40
50
35
15 30 30
20 25
15 20

16 10
LWA dB(A)
7
qV [l/s]
40 50 60 70 80 90 100 150 200 250 300
qV [m3/h]

17 150 200 300 400 500 700 1000

Hz 63 125 250 500 1K 2K 4K 8K


Kok 6 7 2 -2 -6 -13 -22 -31
18

236 We reserve the right to make changes without prior notice


lindab | ceilin g diff users

Versio RS15
Technical data
1
RS15 + R - Supply air RS15 + R - Exhaust air

ǻpt [Pa] RS15-R-S-2-300


250
ǻpt [Pa] RS15-R-E-2-300
250
2
200 200
150 150

100 100
70 50
3
70
50 50 45
50
45 40
30
30 40
20
35 4
30
20 35 15
15 25
30 10
20
10
20
25
LWA dB(A) 7
LWA dB(A) 5
7 5
qV [l/s] qV [l/s]
20 30 40 50 60 70 80 90 100 150 20 30 40 50 60 70 80 90 100 150
qV [m3/h] qV [m3/h]
80 100 150 200 300 400 500 80 100 150 200 300 400 500
6
Hz 63 125 250 500 1K 2K 4K 8K Hz 63 125 250 500 1K 2K 4K 8K
Kok 7 -1 4 -1 -8 -14 -22 -31 Kok 6 1 4 -2 -7 -10 -17 -25
7
ǻpt [Pa] RS15-R-S-2-400 ǻpt [Pa] RS15-R-E-2-400
250 250
200 200 8
150 150

100 100

70

50 50
70

50
50
9
45
45
30 30 40
40
35
20
15
35 20
15
30 10
30 25
10 25 10 20
LWA dB(A) LWA dB(A)
20
7
30 40 50 60 70 80 90 100 150 200
qV [l/s]
7
20 30 40 50 60 70 80 90 150 200
qV [l/s]
250
11
qV [m3/h] qV [m3/h]
150 200 300 400 500 700 80 100 150 200 300 400 500 700

Hz 63 125 250 500 1K 2K 4K 8K Hz 63 125 250 500 1K 2K 4K 8K


12
Kok -2 -1 3 -1 -6 -11 -20 -32 Kok 2 0 2 -2 -5 -10 -16 -24

13
ǻpt [Pa] RS15-R-S-2-500 ǻpt [Pa] RS15-R-E-2-500
250 250
200 200
150

100
150
14
100
70
70
50
50 50 50
30 45 45
15
40 30
20 40
15 35 20 35
30 15
10
25
10 25
30
16
7
20 LWA dB(A) LWA dB(A)
20
5 7
qV [l/s] qV [l/s]
30 40 50 60 70 80 90 100 150 200 250 40 50 60 70 80 90 100 150 200 300

150 200 300 400 500 700


qV [m3/h]
150 200 300 400 500 700 1000
qV [m3/h] 17

Hz 63 125 250 500 1K 2K 4K 8K Hz 63 125 250 500 1K 2K 4K 8K


Kok 3 -1 3 -1 -7 -11 -19 -31 Kok 1 1 1 -2 -6 -9 -16 -25
18

We reserve the right to make changes without prior notice 237


li ndab | ceiling diffusers

Versio RS16

RS16 with upper section type V RS16 with plenum box type H
6
Description Dimensions
RS16 is a square swirl diffuser with adjustable bars that can
be used for both supply air and exhaust. The swirl pattern
25
200 BxB 7
E
ensures high induction and a large dynamic range, and is
therefore ideal for the horizontal supply of very cold air. For
exhaust, the diffuser is supplied as standard without bars. 8
Ød

H
• High capacity
• Large dynamic range 9
• High induction AxA

10
• Ideal for the supply of very cold air
• Can be used for both supply air and exhaust RS16-H A B H E Weight
Ød Pattern mm mm mm mm kg 10
250 600 *- 560 340 420 12.3
315 600 *- 560 405 420 13.1

* Face plate dimension A x A depends on ceiling system. 11


See "Ceiling adjustment" for detailed dimensions. For fur-
ther details on plenum box - see "Plenum boxes".
12
Order code Maintenance
Product RS 16 b c d eee f The face plate can be removed to enable cleaning of internal
Type parts or to gain access to the duct or box. The visible parts 13
RS of the diffuser can be wiped with a damp cloth.
Design
16
Box type 14
V-H-R
Functional use
S = Supply air
E = Exhaust Materials and finish 15
Damper
0 = No damper ( Box : H, V ) Grille box/plenum box:
1 = Damper ( Box : H, R ) Material: Galvanised steel
2 = Damper / Meas.outlets ( Box :H)
16
Face plate:
Connection dim.
Material: Galvanised steel
Ø315 ( Box :V)
Bars: Black ABS-plastic
Ø250-315 ( Box :H)
Standard finish: Powder-coated 17
500x100 ( Box :R)
Ceiling system Standard colour: RAL 9010, gloss 30
1 - 14 Go to chapter Ceiling tile adaption
The diffuser is available in other colours. Please contact 18
Example: RS-16-V-S-0-315-1 Lindab’s sales department for further information.

We reserve the right to make changes without prior notice 239


lindab | ceil ing di ffusers

Versio RS16
Accessories
1
Extension piece MBZ Plenum box MBB

3
Order code
4 Product MBZ aaa
Type
Size
5 RS16-V + MBB
Example: MBZ-315
10 LxB

6 Mounting bracket PBB


10

Ød1

H
Ød2
7

95
F E
8 AxA

RS16-V + MBB
9 Suspension MHS
duct RS16-V B E F H* L
Ød1 mm Ød2 mm Pattern mm mm mm mm mm
200 315 600 460 396 70 355 - 395 565
10 250 315 600 540 486 70 405 - 445 698
315 315 600 540 646 70 470 - 510 858

* Using accessory MBZ the H dimension will increase:


11 Ød2 = 315 mm => H +60 mm

12

13

14

Order code
15 Product MBB aaa 315 c
Type
MBB
16 Duct connection Ød1
Ø200-315
Diffuser dimension Ød2
Ø315
17 Order code Functional use
Product aaa S = Supply air
Type E = Exhaust
18
Example: MHS Example: RS-16-V-S-0-315-1+MBB-315-315-S

240 We reserve the right to make changes without prior notice


li ndab | ceiling diffusers

Versio RS16
Technical data
1
Capacity Sound attenuation
Air flow qv [l/s] and [m3/h], total pressure Δpt [Pa], throw l0.2 Sound attenuation of the diffusers ΔL from duct to room,
[m] and sound power level LWA [dB(A)] can be seen in the including end reflection - see table below.
diagrams.
2
RS16-V + MBB
Frequency-related sound effect level
The sound effect level in the frequency band is defined as RS16-V + MBB
3
LWA+Kok. Kok values are specified in charts beneath the dia- duct RS16-V Centre frequency Hz
grams on the following pages. Ød1 Ød2 63 125 250 500 1K 2K 4K 8K
200 315 13 9 3 16 16 15 17 16
4
Quick selection, supply air 250 315 12 7 5 17 16 17 17 18

RS16-V + MBB 315 315 8 10 8 17 18 17 18 23


5
RS16 + H
RS16-V + MBB Δpt ≥ 50 Pa Δpt ≥ 50 Pa
RS16 + H
duct RS16-V 30 dB(A) 35 dB(A)
Ød1 Ød2 l/s m3/h l/s m3/h
Size Ød Centre frequency Hz 6
mm 63 125 250 500 1K 2K 4K 8K
200 315 99 356 131 472
250 13 8 4 8 5 5 7 9
250 315 126 454 160 576
315 12 7 5 11 5 5 6 8
315 315 155 558 185 666 7
RS16 + R

RS16 + H RS16 + R
8
Size-2 Mean frequency Hz
RS16 + H Δpt ≥ 50 Pa Δpt ≥ 50 Pa mm 63 125 250 500 1K 2K 4K 8K
Size Ød Minimum 30 dB(A) 35 dB(A) 500x100 12 7 2 4 2 5 5 5 9
mm l/s m3/h l/s m3/h l/s m3/h
250 71 254 - - 112 403
315 95 342 - - 174 626
10

11

12

13

14

15

16

17

18

We reserve the right to make changes without prior notice 241


lindab | ceil ing di ffusers

Versio RS16
Technical data
1
Throw l0.2 RS16-V without plenum box – Supply air
Throw l0.2 [m] is specified at a terminal velocity of 0.2 m/s.
2 The designation by the lines specifies the pattern of disper- ǻpt [Pa] RS16-V-S-0-315
sal. 100

70

50
3 L;M=

23
 30
50

45

 20 40
 15 35
4 
10 30

7 25
 20
5
5 4 LWA dB(A)
 3
qV [l/s]
100 150 200 300 400
qV [m3/h]
400 500 700 1000
6 
L ;M=
Q6;LS=
         
Q6;MH=
      
7

10

11

12

13

14

15

16

17

18

242 We reserve the right to make changes without prior notice


li ndab | ceiling diffusers

Versio RS16
Technical data
1
RS16-V 315 + MBB - Supply air

¨pt [Pa] RS16-V-S-0-315+MBB-315-315-S


250
2
200
150

100 3
50
70
45
50
40

30 35
4
30
20
25
15
20 LWA dB(A) 5
10
qV [l/s]
50 60 70 80 90 100 150 200 250 300 350 400
qV [m3/h]
200 300 400 500 700 1250
6
Hz 63 125 250 500 1K 2K 4K 8K
Kok 8 1 -1 0 -6 -14 -21 -30
7
¨pt [Pa] RS16-V-S-0-315+MBB-250-315-S
250
200 8
150

100 50

70 45 9
50 40

35
30
30 10
20
25
15
20 LWA dB(A)
10
50 60 70 80 90 100 150 200 250 300 350 400
qV [l/s] 11
qV [m3/h]
200 300 400 500 700 1250

Hz 63 125 250 500 1K 2K 4K 8K


12
Kok 10 4 -1 -1 -5 -12 -19 -26

13
¨pt [Pa] RS16-V-S-0-315+MBB-200-315-S
250
200
150
50
14
100
45
70 40
50 35 15
30
30
25
20
15
20 16
LWA dB(A)
10
qV [l/s]
50 60 70 80 100 120 140 160 180 200 240 280

200 300 400 500 700 1000


qV [m3/h] 17

Hz 63 125 250 500 1K 2K 4K 8K


Kok 12 7 -1 -2 -5 -12 -18 -24
18

We reserve the right to make changes without prior notice 243


lindab | ceil ing di ffusers

Versio RS16
Technical data
1
RS16-V without plenum box – Exhaust air RS16-V 315 + MBB - Exhaust air

2 ǻpt [Pa] RS16-V-E-0-315


250
¨pt [Pa] RS16-V-E-0-315+MBB-315-315-E
250
200 200
50
150 150
50 45
3 100 45 100
40
70 40 70
35
50 35 50

4 30
30
30
30

25 25
20 20
20 20
15 15
5 LWA dB(A) LWA dB(A)
10 10
qV [l/s] qV [l/s]
200 300 400 500 700 20 25 30 40 50 60 80 100 150 200 250 350 500
qV [m3/h] qV [m3/h]
1000 1500 2000 2500 80 100 150 200 300 400 500 700 1250 2000
6
Hz 63 125 250 500 1K 2K 4K 8K
Kok 11 5 3 -4 -6 -9 -15 -26
7
¨pt [Pa] RS16-V-E-0-315+MBB-250-315-E
250
8 200
50
150

45
100

9 70 40

50 35

30 30
10 25
20
15 20
LWA dB(A)
11 10
20 25 30 40 50 60 80 100 150 200 250 300 400
qV [l/s]

qV [m3/h]
80 100 150 200 300 400 500 700 1250

12 Hz 63 125 250 500 1K 2K 4K 8K


Kok 11 6 3 -4 -6 -11 -16 -24

13
¨pt [Pa] RS16-V-E-0-315+MBB-200-315-E
250
200
50
14 150

45
100

70 40

15 50
35

30 30

20
16 15
25

20 LWA dB(A)
10
qV [l/s]
20 25 30 40 50 60 80 100 150 200 250 300
17 80 100 150 200 300 400 500 700 1000
qV [m3/h]

Hz 63 125 250 500 1K 2K 4K 8K


18 Kok 14 5 1 -3 -6 -9 -13 -21

244 We reserve the right to make changes without prior notice


li ndab | ceiling diffusers

Versio RS16
Technical data
1
RS16 + H - Supply air RS16 + H - Exhaust air

ǻpt [Pa] RS16-H-S-2-250


250
ǻpt [Pa] RS16-H-E-2-250
250
2
200 200
150 150

100 50 100 50 3
70 45 70 45

50 40 50 40

30
35
30
35 4
30 30
20 20 25
25
15 15
20 LWA dB(A)
20
LWA dB(A) 5
10 10
qV [l/s] qV [l/s]
50 60 70 80 90 100 150 200 250 300 400 50 60 70 80 90 100 150 200 250 300
qV [m3/h] qV [m3/h]
200 300 400 500 700 1000 200 300 400 500 700 1000
6
Hz 63 125 250 500 1K 2K 4K 8K Hz 63 125 250 500 1K 2K 4K 8K
Kok 5 5 2 -1 -6 -13 -19 -27 Kok 2 6 3 -2 -7 -12 -21 -30
7
ǻpt [Pa] RS16-H-S-2-315 ǻpt [Pa] RS16-H-E-2-315
250 250
200 200 8
150 150

100 100
50 50
70 45 70
45
9
50 40 50
40
35
30 30 35
30
30
10
20 20
25
15 15 25
20
LWA dB(A) 20 LWA dB(A)
10
100 150 200 250 300 400
qV [l/s]
10
80 90 100 150 200 250 300 400
qV [l/s] 11
qV [m3/h] qV [m3/h]
400 500 700 1000 300 400 500 700 1000

Hz 63 125 250 500 1K 2K 4K 8K Hz 63 125 250 500 1K 2K 4K 8K


12
Kok 8 5 1 -1 -5 -13 -21 -31 Kok 8 5 2 -2 -5 -12 -21 -32

13

14

15

16

17

18

We reserve the right to make changes without prior notice 245


lindab | ceil ing di ffusers

Versio RS16
Technical data
1
RS16 + R - Supply air RS16 + R - Exhaust air

2 ǻpt [Pa] RS16-R-S-2-500


250
ǻpt [Pa] RS16-R-E-2-500
250
200 200
150 150
100
3 100
70
70
50
50 50
30
45 50
30
4 20 35
40 20
15 40
45

15 35
30 10
30
10 7 25
25

5 7 20
LWA dB(A)
5
4
20
LWA dB(A)
5 3
qV [l/s] qV [l/s]
30 40 50 60 70 80 100 150 200 300 400 30 40 50 60 70 80 100 150 200 300 400
qV [m3/h] qV [m3/h]
150 200 300 400 500 700 1000 150 200 300 400 500 700 1000
6
Hz 63 125 250 500 1K 2K 4K 8K Hz 63 125 250 500 1K 2K 4K 8K
Kok 9 2 3 -1 -8 -12 -21 -28 Kok 8 0 0 -3 -5 -8 -18 -26
7

10

11

12

13

14

15

16

17

18

246 We reserve the right to make changes without prior notice


lindab | ceili ng diffusers

Versio NS19

NS19 with grille box type V NS19 with plenum box type H
6
Description Dimensions
NS19 is a square diffuser with individually adjustable noz-
zles. The diffuser is suitable for the horizontal supply of
25
200 BxB 7
E
cooled air, where great flexibility in the dispersal pattern is
required. The diffuser can also be set to a vertical supply air
pattern, enabling supply of heated air. The diffuser is sup- 8
Ød

plied as standard with nozzles set for swirl.

H
AxA
9
• Adjustable dispersal patterns

10
• No pressure change for different dispersal patterns
• Suitable for horizontal or vertical supply air NS19-H A B H E Weight
Ød Pattern mm mm mm mm kg 10
125 300 *- 380 215 350 3.30
Maintenance 160 400 *- 380 250 350 4.60
The face plate can be removed to enable cleaning of internal 200 500 *- 460 290 390 6.50
parts or to gain access to the duct or box. The visible parts 250 600 *- 560 340 420 9.30
11
of the diffuser can be wiped with a damp cloth. 315 600 *- 560 405 420 10.1

* Face plate dimension A x A depends on ceiling system.


See "Ceiling systems" for detailed dimensions. For further
12
Order code details on plenum box, see "Plenum boxes".
Product NS 19 b S d eee f
Type
13
NS
Design
19 14
Box type
V-H-R
Functional use
S = Supply air Materials and finish 15
Damper
0 = No damper ( Box : H, V ) Grille box/plenum box:
1 = Damper ( Box : H, R ) Material: Galvanised steel
2 = Damper / Meas.outlets ( Box :H)
16
Face plate:
Connection dim.
Material: Galvanised steel
Ø160-315 ( Box :V)
Nozzles: White, ABS.plastic
Ø125-315 ( Box :H)
Standard finish: Powder-coated
17
200x100 - 500x100 ( Box :R)
Ceiling system Standard colour: RAL 9003, gloss 30
1 - 14 Go to chapter Ceiling tile adaption
The diffuser is available in other colours. Please contact 18
Example: NS-19-V-S-0-200-1 Lindab's sales department for further information.

We reserve the right to make changes without prior notice 247


01-11-2013
lindab | ceil ing di ffusers

Versio NS19
Accessories
1
Extension piece MBZ Plenum box MBB

3
Order code
4 Product MBZ aaa
Type
Size
5
Example: MBZ-200 NS19-V + MBB

10 LxB
6
10
Ød1

H
7 Ød2

95
8 F E
Mounting bracket PBB AxA

9 NS19-V + MBB
duct NS19-V B E F H* L
Ød1 mm Ød2 mm Pattern mm mm mm mm mm
10 100 160 300 260 216 50 255 - 295 310
125 160 300 310 262 50 280 - 320 376
125 200 400 310 262 50 280 - 320 376
160 160 300 380 323 50 314 - 354 459
11 160 200 400 380 323 50 314 - 354 459
Suspension MHS 160 250 500 380 323 50 314 - 354 459
200 200 400 460 396 70 355 - 395 565
12 200 250 500 460 396 70 355 - 395 565
200 315 600 460 396 70 355 - 395 565
250 250 500 540 486 70 405 - 445 698

13 250 315 600 540 486 70 405 - 445 698


315 315 600 540 646 70 470 - 510 858

* Using accessory MBZ the H dimension will increase:


14 Ød2 = 160 - 200 mm => H +40 mm
Ød2 = 250 - 315 mm => H +60 mm

15 Order code
Product MBB aaa bbb S
Type
16 MBB
Duct connection Ød1
Ø100-315
Diffuser dimension Ød2
17 Order code Ø160-315
Product aaa Functional use
Type S = Supply air
18
Example: MHS Example: NS-19-V-S-0-200-1+MBB-200-200-S

248 We reserve the right to make changes without prior notice


01-11-2013
lindab | ceili ng diffusers

Versio NS19
Technical data
1
Capacity Sound attenuation
Air flow qv [l/s] and [m3/h], total pressure Δpt [Pa], throw l0.2 Sound attenuation of the diffusers ΔL from duct to room,
[m] and sound power level LWA [dB(A)] can be seen in the including end reflection - see table below.
diagrams.
2

Frequency-related sound effect level


The sound effect level in the frequency band is defined as
3
LWA+Kok. Kok values are specified in charts beneath the dia-
grams on the following pages.
4
Quick selection, supply air
NS19-V + MBB
5
NS19-V + MBB Δpt ≥ 50 Pa Δpt ≥ 50 Pa
duct NS19-V 30 dB(A) 35 dB(A)
Ød1 Ød2 l/s m3/h l/s m3/h 6
100 160 37 133 44 158
125 160 45 162 56 202
125 200 52 187 63 227 7
160 160 48 173 58 209 NS19-V + MBB
160 200 60 216 74 266
160 250 70 252 88 317
200 200 68 245 82 295
NS19-V + MBB 8
duct NS19-V Centre frequency Hz
200 250 80 288 97 349
Ød1 Ød2 63 125 250 500 1K 2K 4K 8K
200 315 89 320 114 410
100 160 18 16 5 17 20 19 18 21
250 250 89 320 105 378
125 160 17 13 8 20 18 18 18 21
9
250 315 104 374 128 461
125 200 13 11 5 16 17 16 17 19
315 315 129 464 152 547
160 160 17 16 11 23 21 20 21 21
160 200 13 14 8 22 21 19 20 21 10
Supply air 160 250 14 14 5 19 17 17 18 20
NS19 + H 200 200 13 10 7 17 20 17 19 18
200 250 12 9 6 16 18 17 19 17
11
200 315 12 8 3 14 17 15 17 17
NS19 + H Δpt ≥ 50 Pa Δpt ≥ 50 Pa
250 250 14 9 7 18 19 19 19 19
Size Ød Minimum 30 dB(A) 35 dB(A)
250 315 14 7 5 16 17 18 18 18
mm l/s m3/h l/s m3/h l/s m3/h
315 315 8 9 8 16 18 17 18 24 12
125 26 93 31 112 40 144
160 33 118 50 180 60 216
NS19 + H
200 57 204 60 216 77 277
250 71 254 95 342 113 407
13
NS19 + H
315 95 342 - - 147 529
Size Ød Centre frequency Hz
mm 63 125 250 500 1K 2K 4K 8K 14
125 17 15 5 12 12 7 8 12
160 17 13 4 13 14 7 7 10
200 15 9 3 14 10 8 8 14
250 12 8 5 10 7 7 8 13 15
315 12 6 5 12 6 6 8 13

Installation -and balancing instruction 16


For futher information go to www.lindQST.com and installa-
tion -and balancing instruction.
17

18

We reserve the right to make changes without prior notice 249


01-11-2013
lindab | ceil ing di ffusers

Versio NS19
Technical data
1
Throw l0.2 Air patterns
Throw l0.2 [m] is specified at a terminal velocity of 0.2 m/s.
2 The designation by the lines specifies the pattern of disper-
sal.

300
3 l0.2 [m]
10
NS19 400 500 600

8
7
6
4 5

5
2

6 1
l0.2 [m]
qV [l/s]
20 30 40 50 60 70 100 150 200 300 500 700
qV [m3/h]
80 100 150 200 300 500 700 1000 1500 2000
7 4 - ways 3 - ways
Correction throw
8
4-way 3-way 2-way 1-way
1,3 2 2,5 4,6

10 2 - ways 1 - ways

11

12

13 Fan
Rotation Fan
2 - ways corner

14

15

16

17

18

250 We reserve the right to make changes without prior notice


01-11-2013
lindab | ceili ng diffusers

Versio NS19
Technical data
1
Throws/turning points Nozzle setting - vertical
Throw l0.2 [m] can be seen in the diagram. The throw applies
for isothermal air at a terminal velocity of 0.2 m/s. Turning
point l0.0 (m) can be seen in the diagram for heated air, +5 K
2
and +10 K respectively.
The designation by the lines specifies the pattern of disper-
sal. 3
NS19 400
l0.2 [m] 300 500 600
10

8
4
7
6
5

4 5
3 NS19-V without plenum box
2
¨pt [P a] NS19-V-S-0 160 200 250
6
100

l0.2 [m] 70
315
1
5 10 15 20 30 40 50 60 70 100 150 200
qV [l/s] 50
50
7
qV [m3/h]
20 30 40 50 60 70 100 150 200 300 500 700 30 45

40
20
35
8
l0.2 [m] NS19 +5K 300 400 500 15
10 600
30
10
8
7
6
7
25
L WA dB(A)
9
20
5 5
qV [l/s]
4 30 40 50 60 70 80 100 150 200 300
qV [m3/h]
3 150 200 300 400 500 700 1000 10
2

11
l0.2 [m]
1
qV [l/s]
10 15 20 30 40 50 60 70 80 100 150 200

40 50 60 70 80 100 150 200 300 500 700


qV [m3/h] 12

400
l0.2 [m]
10
NS19 +10K 300 500
13
8 600
7
6
5 14
4

15
2

1
l0.2 [m] 16
qV [l/s]
10 15 20 30 40 50 60 70 80 100 150 200
qV [m3/h]
40 50 60 70 80 100 150 200 300 500 700
17

18

We reserve the right to make changes without prior notice 251


01-11-2013
lindab | ceil ing di ffusers

Versio NS19
Technical data
1
NS19-V 160 + MBB - Supply air NS19-V 200 + MBB - Supply air

2 ¨pt [Pa] NS19-V-S-0-160+MBB-160-160-S


250
¨pt [Pa] NS19-V-S-0-200+MBB-200-200-S
250
200 200
150 150

3 100 50 100
50
70 45 70
45
50 40 50
40
4 30
35
30
35
30 30
20 20
25 25
15 15
5 10
20 LWA dB(A) 20 LWA dB(A)
10
qV [l/s] qV [l/s]
25 30 40 50 60 70 80 100 120 140 160 30 40 50 60 70 80 100 120 140 160
qV [m3/h] qV [m3/h]
100 150 200 300 400 500 150 200 300 400 500
6
Hz 63 125 250 500 1K 2K 4K 8K Hz 63 125 250 500 1K 2K 4K 8K
Kok 10 4 -2 1 -6 -15 -22 -33 Kok 11 4 -3 0 -5 -16 -23 -33
7
¨pt [Pa] NS19-V-S-0-160+MBB-125-160-S ¨pt [Pa] NS19-V-S-0-200+MBB-160-200-S
250 250
8 200 200
150 150
50
50
100 45 100
45
9 70 40 70
40
50 35 50
35
30
30 30 30
10 25
20 20 25
20
15 15 20
LWA dB(A) LWA dB(A)
10
11 10
20 25 30 40 50 60 70 80 90 100 120 140
qV [l/s]
30 40 50 60 70 80 100 120 140 160
qV [l/s]

qV [m3/h] qV [m3/h]
80 100 150 200 300 400 500 150 200 300 400 500

12 Hz 63 125 250 500 1K 2K 4K 8K Hz 63 125 250 500 1K 2K 4K 8K


Kok 8 5 -1 0 -6 -13 -18 -28 Kok 12 5 -1 -1 -5 -13 -19 -26

13
¨pt [Pa] NS19-V-S-0-160+MBB-100-160-S ¨pt [Pa] NS19-V-S-0-200+MBB-125-200-S
250 250
200 50 200
50
14 150
45
150
45
100 40 100
40
70 35 70
35
15 50 30 50
30
25
30 30 25
20
20 20
16 15 15
20

LWA dB(A) LWA dB(A)


10 10
qV [l/s] qV [l/s]
10 15 20 25 30 40 50 60 70 80 100 20 25 30 40 50 60 70 80 100 120 140
17 40 50 60 70 80 100 150 200 300
qV [m3/h]
80 100 150 200 300 400 500
qV [m3/h]

Hz 63 125 250 500 1K 2K 4K 8K Hz 63 125 250 500 1K 2K 4K 8K


18 Kok 11 4 2 -1 -8 -12 -16 -22 Kok 8 6 2 -1 -7 -13 -18 -26

252 We reserve the right to make changes without prior notice


01-11-2013
lindab | ceili ng diffusers

Versio NS19
Technical data
1
NS19-V 250 + MBB - Supply air NS19-V 315 + MBB - Supply air

¨pt [Pa] NS19-V-S-0-250+MBB-250-250-S


250
¨pt [Pa] NS19-V-S-0-315+MBB-315-315-S
250
2
200 200
150 150

100 100 3
50 50
70 70
45 45
50 50
40
30
40
30
4
35 35

20 30 20 30
15 15 25
20
25
LWA dB(A)
20
LWA dB(A) 5
10 10
qV [l/s] qV [l/s]
50 60 70 80 100 120 140 160 180 200 240 280 50 60 70 80 90 100 150 200 250 300 350 400
qV [m3/h] qV [m3/h]
200 300 400 500 700 1000 200 300 400 500 700 1250
6
Hz 63 125 250 500 1K 2K 4K 8K Hz 63 125 250 500 1K 2K 4K 8K
Kok 8 4 -4 0 -5 -16 -24 -37 Kok 10 1 -2 0 -5 -16 -23 -34
7
¨pt [Pa] NS19-V-S-0-250+MBB-200-250-S ¨pt [Pa] NS19-V-S-0-315+MBB-250-315-S
250 250
200 200 8
150 150

100 50 100
50
70 45 70
45
9
50 40 50
40

35 35
30 30
30 30 10
20 20
25 25
15 15
LWA dB(A) 20 LWA dB(A)
20
10
50 60 70 80 100 120 140 160 180 200 240
qV [l/s]
10
50 60 70 80 90 100 150 200 250 300 350 400
qV [l/s] 11
qV [m3/h] qV [m3/h]
200 300 400 500 700 200 300 400 500 700 1250

Hz 63 125 250 500 1K 2K 4K 8K Hz 63 125 250 500 1K 2K 4K 8K


12
Kok 9 6 -2 0 -5 -15 -22 -33 Kok 10 3 -2 0 -5 -15 -21 -28

13
¨pt [Pa] NS19-V-S-0-250+MBB-160-250-S ¨pt [Pa] NS19-V-S-0-315+MBB-200-315-S
250 250
200 200
150
50
150 14
50
100 100
45
45
70 40 70
40
50 35 50
35
15
30
30 30 30
25
25
20 20
15
20
15 20
16
LWA dB(A) LWA dB(A)
10 10
qV [l/s] qV [l/s]
30 40 50 60 70 80 100 120 140 160 180 50 60 70 80 100 120 140 160 180 200 240 280

150 200 300 400 500


qV [m3/h]
200 300 400 500 700 1000
qV [m3/h] 17

Hz 63 125 250 500 1K 2K 4K 8K Hz 63 125 250 500 1K 2K 4K 8K


Kok 13 6 0 -1 -5 -12 -18 -26 Kok 9 6 -1 -1 -5 -13 -20 -28
18

We reserve the right to make changes without prior notice 253


01-11-2013
lindab | ceil ing di ffusers

Versio NS19
Technical data
1
NS19 + H - Supply air NS19 + H - Supply air

2 ǻpt [Pa] NS19-H-S-2-125


250
ǻpt [Pa] NS19-H-S-2-250
250
200 200

150 150

3 100
50 100
50
45 70
70 45
50
50 40
40

4 30
35 30 35
30 20 30
20 15
25 25
15
5 20 LWA dB(A)
10 20
LWA dB(A)
10 7
qV [l/s] qV [l/s]
15 20 30 40 50 60 70 80 90 100 50 60 70 80 90 100 150 200 300
qV [m3/h] qV [m3/h]
60 70 80 90 100 150 200 300 200 300 400 500 700 1000
6
Hz 63 125 250 500 1K 2K 4K 8K Hz 63 125 250 500 1K 2K 4K 8K
Kok 9 7 6 -4 -9 -15 -21 -28 Kok 6 7 3 -1 -7 -16 -22 -31
7
ǻpt [Pa] NS19-H-S-2-160 ǻpt [Pa] NS19-H-S-2-315
250 250
8 200 200

150 150

100
100 50
9 70 45
70 50
50 45
50
40
40
30
30 35 35
10 30
20
30
20 15
25 25
15
10
LWA dB(A) 20 LWA dB(A)
11 10
30 40
20

50 60 70 80 100 150
qV [l/s]
7
70 80 90 100 150 200 300
qV [l/s]

qV [m3/h] qV [m3/h]
150 200 300 400 500 300 400 500 700 1000

12 Hz 63 125 250 500 1K 2K 4K 8K Hz 63 125 250 500 1K 2K 4K 8K


Kok 9 7 6 -4 -9 -15 -21 -28 Kok 6 7 3 -1 -8 -17 -25 -36

13
ǻpt [Pa] NS19-H-S-2-200
250
200

14 150

100
50
70

15 50
45

40

30 35

16 20
15
30

25
LWA dB(A)
10 20
qV [l/s]

17 30 40 50 60 70 80 90 100 150 200


qV [m3/h]
150 200 300 400 500 700

Hz 63 125 250 500 1K 2K 4K 8K


18 Kok 11 6 3 -1 -7 -16 -22 -30

254 We reserve the right to make changes without prior notice


01-11-2013
li ndab | ceiling diffusers

Versio GS23

GS23 with grille box type V GS23 with plenum box type H
6
Description Dimensions
GS23 is a square diffuser with an aluminium grid. GS23 is
used for exhaust.
25
200 BxB
7
E

• High capacity 8
Ød

H
Maintenance
The face plate can be removed to enable cleaning of internal 9
parts or to gain access to the duct or box. The visible parts AxA

10
of the diffuser can be wiped with a damp cloth.
GS23-H A B H E Weight 10
Ød Pattern mm mm mm mm kg
125 300 *- 380 215 350 5.9
160 400 *- 380 250 350 5.9 11
200 500 *- 460 290 390 8.5
250 600 *- 560 340 420 12.3
315 600 *- 560 405 420 13.1
12
* Face plate dimension A x A depends on ceiling system.
Order code See "Ceiling adjustment" for detailed dimensions. For fur-
Product GS 23 b E d eee f ther details on plenum box, see "Plenum boxes".
Type
13
GS
Design
23 14
Box type
V-H-R
Functional use
E = Exhaust Materials and finish 15
Damper
0 = No damper ( Box : H, V ) Grille box/plenum box:
1 = Damper ( Box : H, R ) Material: Galvanised steel
2 = Damper / Meas.outlets ( Box :H)
16
Face plate:
Connection dim.
Ø160-315 ( Box :V)
Material: Galvanised steel
Grid: Aluminium
Ø125-315 ( Box :H)
Standard finish: Powder-coated
17
200x100 - 500x100 ( Box :R)
Ceiling system Standard colour: RAL 9010, gloss 30
1 - 14 Go to chapter Ceiling tile adaption
The diffuser is available in other colours. Please contact 18
Example: GS-23-V-E-0-200-1 Lindab’s sales department for further information.

We reserve the right to make changes without prior notice 255


lindab | ceil ing di ffusers

Versio GS23
Accessories
1
Extension piece MBZ Plenum box MBB

4 Order code
Product MBZ aaa
Type
5 Size
GS23-V + MBB

10 LxB
Example: MBZ-200
6 10
Mounting bracket PBB
Ød1

H
Ød2
7

95
F E
8 AxA

GS23-V + MBB
9 duct GS23-V B E F H* L
Suspension MHS Ød1 mm Ød2 mm Pattern mm mm mm mm mm
100 160 300 260 216 50 255 - 295 310
10 125 160 300 310 262 50 280 - 320 376
125 200 400 310 262 50 280 - 320 366
160 160 300 380 323 50 314 - 354 459
160 200 400 380 323 50 314 - 354 459
11 160 250 500 380 323 50 314 - 354 459
200 200 400 460 396 70 355 - 395 565
200 250 500 460 396 70 355 - 395 565
12 200 315 600 460 396 70 355 - 395 565
250 250 500 540 486 70 405 - 445 698
250 315 600 540 486 70 405 - 445 698
315 315 600 540 646 70 470 - 510 858
13
* Using accessory MBZ the H dimension will increase:
Ød2 = 160 - 200 mm => H +40 mm
14 Ød2 = 250 - 315 mm => H +60 mm

15 Order code
Product MBB aaa bbb E
Type
16 MBB
Duct connection Ød1
Ø100-315
Diffuser dimension Ød2
17 Order code Ø160-315
Product aaa Functional use
Type E = Exhaust
18
Example: MHS Example: GS-23-V-E-0-200-1+MBB-200-200-E

256 We reserve the right to make changes without prior notice


li ndab | ceiling diffusers

Versio GS23
Technical data
1
Capacity GS23-V without plenum box - Exhaust air
Air flow qv [l/s] and [m3/h], total pressure Δpt [Pa], throw l0.2
[m] and sound power level LWA [dB(A)] can be seen in the
diagrams.
¨St [Pa] GS23-V-E-0
100
160 200 250 2
70
315
50

Sound attenuation 30
50 3
45
Sound attenuation of the diffusers ΔL from duct to room, 20
including end reflection - see table below. 15
40

10
35 4
GS23 + H 30
7

5 25
GS23 + H
20 L WA dB(A) 5
Size Ød Centre frequency Hz qV [l/s]
50 60 70 80 100 150 200 300 400 500 700 1000
mm 63 125 250 500 1K 2K 4K 8K
qV [m3/h]
125 17 16 5 9 10 4 5 5 200 300 400 500 700 1000 1500 2000 3000

160 16 14 3 11 11 4 4 4
6
200 15 9 2 11 7 4 4 6
250 14 8 3 9 4 3 4 6
315 12 6 4 10 3 3 4 6 7
GS23-V + MBB
8
GS23-V + MBB
duct GS23-V Centre frequency Hz
Ød1 Ød2 63 125 250 500 1K 2K 4K 8K 9
100 160 20 16 5 19 20 19 18 21
125 160 16 13 9 20 18 18 19 20
125 200 14 12 6 17 16 16 18 19
160 160 17 16 10 24 20 20 21 21
10
160 200 15 15 7 22 21 19 20 21
160 250 15 14 5 20 16 16 17 19
200 200 14 11 7 18 21 17 20 18 11
200 250 13 9 5 17 18 16 18 17
200 315 13 8 3 15 17 15 17 16
250 250 15 8 7 18 18 18 18 19 12
250 315 15 7 6 16 16 17 17 18
315 315 8 11 8 16 18 17 17 22

Installation -and balancing instruction 13


For futher information go to www.lindQST.com and installa-
tion -and balancing instruction.
14

15

16

17

18

We reserve the right to make changes without prior notice 257


lindab | ceil ing di ffusers

Versio GS23
Technical data
1
GS23-V 160 + MBB - Exhaust air GS23-V 200 + MBB - Exhaust air

2 ¨pt [Pa] GS23-V-E-0-160+MBB-160-160-E


250
¨pt [Pa] GS23-V-E-0-200+MBB-200-200-E
250
200 200
45
150 150 45
40
3 100 100 40
35
70 70
35
50 30 50
30
4 30
25
30
25
20
20 20
20
15 15
5 LWA dB(A) LWA dB(A)
10 10
qV [l/s] qV [l/s]
10 15 20 25 30 40 50 60 80 100 150 200 20 25 30 40 50 60 80 100 150 200 250
qV [m3/h] qV [m3/h]
40 50 60 70 80 100 150 200 300 400 500 700 80 100 150 200 300 400 500 700
6
Hz 63 125 250 500 1K 2K 4K 8K Hz 63 125 250 500 1K 2K 4K 8K
Kok 15 5 0 -3 -6 -9 -14 -19 Kok 14 5 1 -3 -6 -9 -13 -21
7
¨pt [Pa] GS23-V-E-0-160+MBB-125-160-E ¨pt [Pa] GS23-V-E-0-200+MBB-160-200-E
250 250
8 200
50
200 50

150 45 150
45

100 40 100 40
9 70
35
70
35
50 50
30 30

30 30 25
10 25
20 20 20
20
15 15
LWA dB(A) LWA dB(A)
11 10
10 15 20 25 30 40 50 60 80 100 120 140
qV [l/s]
10
10 15 20 25 30 40 50 60 80 100 150 200
qV [l/s]

qV [m3/h] qV [m3/h]
40 50 60 70 80 100 150 200 300 400 500 40 50 60 70 80 100 150 200 300 400 500 700

12 Hz 63 125 250 500 1K 2K 4K 8K Hz 63 125 250 500 1K 2K 4K 8K


Kok 11 5 1 -2 -6 -11 -15 -22 Kok 14 5 0 -3 -6 -9 -14 -21

13
¨pt [Pa] GS23-V-E-0-160+MBB-100-160-E ¨pt [Pa] GS23-V-E-0-200+MBB-125-200-E
250 250
200 50 200
50
14 150
45
150
45
100 100
40
70 70 40

15 50 35 50 35

30 30
30 30

25
16 20
15
20
15
25

20 20
LWA dB(A) LWA dB(A)
10 10
qV [l/s] qV [l/s]
5 10 15 20 25 30 40 50 60 80 10 15 20 25 30 40 50 60 80 100 120 140
17 qV [m3/h] qV [m3/h]
20 30 40 50 60 70 80 100 150 200 300 40 50 60 70 80 100 150 200 300 400 500

Hz 63 125 250 500 1K 2K 4K 8K Hz 63 125 250 500 1K 2K 4K 8K


18 Kok 8 4 4 -2 -8 -12 -16 -23 Kok 9 4 1 -1 -6 -11 -15 -22

258 We reserve the right to make changes without prior notice


li ndab | ceiling diffusers

Versio GS23
Technical data
1
GS23-V 250 + MBB - Exhaust air GS23-V 315 + MBB - Exhaust air

¨pt [Pa] GS23-V-E-0-250+MBB-250-250-E


250
¨pt [Pa] GS23-V-E-0-315+MBB-315-315-E
250
2
200 50 200
50
150 150
45 45
100
40
100 3
40
70 70
35 35
50 50

30
30
30
30 4
25 25
20 20
20
15 20 15
LWA dB(A)
10
LWA dB(A) 5
10
qV [l/s] qV [l/s]
20 25 30 40 50 60 80 100 150 200 250 300 400 20 25 30 40 50 60 80 100 150 200 250 350 500
qV [m3/h] qV [m3/h]
80 100 150 200 300 400 500 700 1250 80 100 150 200 300 400 500 700 1250 2000
6
Hz 63 125 250 500 1K 2K 4K 8K Hz 63 125 250 500 1K 2K 4K 8K
Kok 10 5 2 -3 -6 -9 -15 -23 Kok 11 5 3 -4 -7 -9 -14 -25
7
¨pt [Pa] GS23-V-E-0-250+MBB-200-250-E ¨pt [Pa] GS23-V-E-0-315+MBB-250-315-E
250 250
200 50 200 8
150 150 50
45
100 100 45

70
40
70 40 9
50 35 50
35
30
30 30
25
30
10
20 20 25
15 20 15
LWA dB(A) 20 LWA dB(A)
10
20 25 30 40 50 60 80 100 150 200 250 300
qV [l/s]
10
20 25 30 40 50 60 80 100 150 200 250 300 400
qV [l/s] 11
qV [m3/h] 3
qV [m /h]
80 100 150 200 300 400 500 700 1000 80 100 150 200 300 400 500 700 1250

Hz 63 125 250 500 1K 2K 4K 8K Hz 63 125 250 500 1K 2K 4K 8K


12
Kok 13 5 1 -3 -6 -10 -14 -22 Kok 11 5 2 -3 -6 -10 -15 -24

13
¨pt [Pa] GS23-V-E-0-250+MBB-160-250-E ¨pt [Pa] GS23-V-E-0-315+MBB-200-315-E
250 250
200 200
50
150 150
50
14
45 45
100 100
40
70 70 40

50 35 50
35
15
30
30 30 30
25
20
15 20
20
15
25 16
LWA dB(A) 20 LWA dB(A)
10 10
qV [l/s] qV [l/s]
10 15 20 25 30 40 50 60 80 100 150 200 20 25 30 40 50 60 80 100 150 200 250 300
qV [m3/h] qV [m3/h] 17
40 50 60 70 80 100 150 200 300 400 500 700 80 100 150 200 300 400 500 700 1000

Hz 63 125 250 500 1K 2K 4K 8K Hz 63 125 250 500 1K 2K 4K 8K


Kok 13 5 1 -3 -6 -9 -14 -22 Kok 13 5 1 -3 -6 -9 -14 -22
18

We reserve the right to make changes without prior notice 259


lindab | ceil ing di ffusers

Versio GS23
Technical data
1
Exhaust with plenum box type H Exhaust with plenum box type H

2 ǻpt [Pa] GS23-H-E-2-125


250
ǻpt [Pa] GS23-H-E-2-250
250
200 200
150
150

3 100
70
50 100
50
50 45 70
45
40 50
30 40
4 20
35
30
35
15 30 30
25 20
10 25
15
5 7 20
LWA dB(A) 20
LWA dB(A)
5 10
qV [l/s] qV [l/s]
10 15 20 30 40 50 60 70 80 100 150 50 60 70 80 100 150 200 300
qV [m3/h] qV [m3/h]
40 50 60 70 80 100 150 200 300 400 500 200 300 400 500 700 1000
6
Hz 63 125 250 500 1K 2K 4K 8K Hz 63 125 250 500 1K 2K 4K 8K
Kok 4 4 5 -3 -9 -11 -18 -25 Kok 3 6 2 -2 -6 -12 -21 -32
7
ǻpt [Pa] GS23-H-E-2-160 ǻpt [Pa] GS23-H-E-2-315
250 250
8 200 200
150
150
100
100
70
9 50
50 70
50

45 45
50
30 40
40
20 35 30
10 15
30 30
35

20
10 25
15 25
7 20 LWA dB(A) LWA dB(A)
20
11 5
20 30 40 50 60 70 80 100 150 200
qV [l/s]
10
70 80 90 100 150 200 300 400
qV [l/s]

qV [m3/h] qV [m3/h]
80 100 150 200 300 400 500 700 300 400 500 700 1000

12 Hz 63 125 250 500 1K 2K 4K 8K Hz 63 125 250 500 1K 2K 4K 8K


Kok 6 4 6 -3 -10 -13 -20 -29 Kok 10 6 2 -3 -5 -11 -20 -31

13
ǻpt [Pa] GS23-H-E-2-200
250
200

14 150

100
70 50
50
15 30 40
45

20 35

15 30

16 10 25

7 20
LWA dB(A)
5
qV [l/s]

17 30 40 50 60 70 80 100 150 200 300


qV [m3/h]
150 200 300 400 500 700 1000

Hz 63 125 250 500 1K 2K 4K 8K


18 Kok 8 5 4 -2 -8 -11 -19 -24

260 We reserve the right to make changes without prior notice


lindab | ceiling diffusers

Lindab Lineo

10

11

12

13

14

15

16

17

18
MTL, Fingerrod C, Copenhagen Airport

Right to alterations reserved 261


lin d a b | c e i l i n g d i ff u s e r s

Lindab Lineo
Slotdiffuser
1
Product Functions Page

2 MTL 265

3 STB 272
STU

10

11

12

13

14

15

16

17

18

262 Right to alterations reserved-


lindab | ceiling diffusers

Lindab Lineo

10

11
MTL, Hotel Marriot, Copenhagen

Lindab Lineo Functionality


12
With the slim construction of the slotdiffuser, it is possible Lindab’s slot diffuser MTL is available in two different
to obtain a very simple solution for your ventilation needs, widths, depending on the requirements for function or
which can be integrated in very different environments. design. Furthermore, the corner pieces can be cut at 13
an angle to suit. Normally the lengths are available in
The slots can be mounted either in the ceiling or in the pieces up to 2 metres, but can be delivered in pieces up
wall / skirting board. The best aero-technical qualities are to 5 metres upon demand. If longer unbroken lengths 14
obtained, when the slots are mounted in the middle of the are needed, the individual diffusers can be mounted with
room with a two-way supply of air. It is also a possibility to fixing-pipes. The plenum boxes STB and STU secure an
install the slots along the wall or along the facade, partly even distribution and individual regulation of the slots. 15
in order to make the installation seem as discrete as pos-
sible, and partly to free up the other part of the ceiling for
other installations. The slots can be mounted in unbroken 16
bands, where the best result is obtained when both active
and passive - or exhaust-slots are combined in the same
length. 17

MTL, slot diffuser.


18

Right to alterations reserved 263


l indab | ceiling diff users

Linear diffuser MTL

1
A

C
3
B
4

L+D
5
L

Description 6
MTL is a rectangular linear diffuser in aluminium. MTL is
suitable for both supply and exhaust air. MTL is equipped
with air guide baffles, making it possible to use MTL for hor- 7
Both ends are equipped with flanges.
izontal supply air.

The horizontal dispersal pattern can be easily changed with- Slot width: 15 mm 8
out the use of tools by turning the air guide baffle. The air A B C D
guide baffle must be removed for vertical supply air. No. of slots mm mm mm mm
1 25 45 25 30
MTL can be supplied in two versions, 15 mm or 19 mm, 2 50 70 25 30
9
3 75 95 25 30
depending on capacity requirements or aesthetic considera- 4 100 120 25 30
tions. MTL can be installed with plenum box STB/STU in Cutout: A + 10 mm x L + 10 mm
order to achieve an even flow and individual adjustment. 10
MTL is normally supplied in lengths up to max. 2 m, but can
be supplied on request up to 5 m. MTZ-1 is a 90o joint, Slot width: 19 mm
11
when an aesthetically pleasing corner is required. A B C D
No. of slots mm mm mm mm
• Discrete appearance 1 40 75 38 56
• Used for both supply air and exhaust
2
3
79
117
113
151
38
38
56
56
12
• Horizontal and vertical supply air. 4 157 189 38 56
Cutout: A + 20 mm x L + 20 mm
Maintenance 13
MTL can be removed to enable cleaning of internal parts or
to gain access to the duct or box.
The visible parts of the diffuser can be wiped with a damp 14
cloth.

15

Order code 16
Product MTL aa b cccc Materials and finish
Type
Slot: Aluminium
Standard finish: Natural anodised 17
Slot size 15 Air guide baffle: Black ABS plastic
19
No. of slots The diffuser is available in other colours. Please contact 18
Length (L) Lindab’s sales department for further information.

We reserve the right to make changes without prior notice 265


lindab | ceil ing di ffusers

Linear diffuser MTL


Accessories
1 MTZ-1
Installation in plenum box STB/STU
B+L A self-tapping screw is fitted through the slot up into the
perforated surface of the plenum box.
2

4
B+L

5
Installation of slots in continuous strips
L

7 L

8 MTZ-1 15 L B MTZ-1 19 L B
1 150 45 1 150 75
2 150 70 2 150 113
3 150 95 3 150 151
9 4 150 120 4 150 189

MTZ is supplied as two mitred ends (not one piece).


10

11

The slots are often installed in continuous strips, where


12 there is a need to join the slots, so that it resembles a single
piece. In these cases, the full length must be specified when
ordering, and the slots will be supplied adjusted to the total
13 length. The outermost pieces will be equipped with end
pieces, and the middle pieces will be supplied without end
pieces. The slots are joined using the accompanying pins.
14

15

16 Order code

Product MTZ-1 aa b
17 Type

Slot size 15
18 19
No. of slots

266 We reserve the right to make changes without prior notice


l indab | ceiling diff users

Linear diffuser MTL


Technical data
1
Capacity Sound attenuation
Volume flow qv [l/s] and [m3/h], total pressure Δpt[Pa], throw Sound attenuation ΔL [dB] of MTL+STB including the end
l0.2 [m] and sound power level LWA [dB(A)] can be seen in the reflection, corresponding to the inlet diameter. See table 4
diagrams. below.
2

Throw l0.2 Table 4: Sound attenuation ΔL [dB]


Mean frequency Hz 3
Throw l0.2 [m] at a speed of 0.2 m/s and 1 m slot length can
No. of
be seen in the diagrams. Correction of throw at other slot
slots 63 125 250 500 1K 2K 4K 8K
lengths: see table 1. 1 19 15 11 12 8 10 11 10
2 18 14 9 11 9 9 10 10 4
3 15 10 7 9 8 8 9 10
4 14 10 7 8 8 7 8 9
Table 1: Correction of throw
Slot length 250 500 1000 1500 3000 5
Correction factor 0,7 0,85 1 1,1 1,2
Balancing
Balancing data for control of air volume is available in a sep-
arate brochure. 6
Frequency-related sound effect level
The sound effect level in the frequency band is defined as
LWA+Kok.
Kok values for MTL with box - see table 2.A and 2.B below. Sample calculation: 7
Required data: Volume of air 200 m3/h
Table 2.A: Kok values [dB] for MTL with sloth width 15. Throw 6.5 m
MTL-15-x + Box Mean frequency Hz Horizontal supply air 8
No. of slots (x) 63 125 250 500 1K 2K 4K 8K Slot length 1.5 m, i.e. 133 [(m3/h)/m]
1 8 3 6 -3 -10 -19 -27 -31
2 6 -1 5 -2 -8 -15 -23 -33 9
3 8 1 6 -2 -8 -17 -24 -31 Solution: MTL 19
4 6 -1 6 -2 -8 -15 -23 -31
2-slot version is selected:
Throw according to diagram: 5.8 m 10
Table 2.B: Kok values [dB] for MTL with sloth width 19.
MTL-19-x + Box Mean frequency Hz Throw correction according to table 1:
No. of slots (x) 63 125 250 500 1K 2K 4K 8K 1.1 x 5.8 = 6.4 m 11
1 11 8 6 -4 -12 -16 -23 -28 Pressure loss and sound level according
2 10 4 6 -4 -10 -15 -22 -28 to diagram:
3 8 2 7 -4 -11 -18 -24 -28 Open damper: 13 Pa, 15 dB(A)
4 9 3 6 -3 -10 -16 -23 -27 Closed damper: 38 Pa, 22 dB(A)
12

Correction according to table 3: 13


Table 3: Correction for other slot lengths
Slot length 250 500 1000 1500 3000 Open damper: 15 + 2 = 17 dB(A)
correction [dB(A)] -6 -3 0 2 5
Closed damper: 22 + 2 = 24 dB(A) 14

15

16

17

18

We reserve the right to make changes without prior notice 267


l indab | ceiling diff users

Linear diffuser MTL


Technical data
1
Capacity Sound attenuation
Volume flow qv [l/s] and [m3/h], total pressure Δpt[Pa], throw Sound attenuation ΔL [dB] of MTL+STB including the end
l0.2 [m] and sound power level LWA [dB(A)] can be seen in the reflection, corresponding to the inlet diameter. See table 4
diagrams. below.
2

Throw l0.2 Table 4: Sound attenuation ΔL [dB]


Mean frequency Hz 3
Throw l0.2 [m] at a speed of 0.2 m/s and 1 m slot length can
No. of
be seen in the diagrams. Correction of throw at other slot
slots 63 125 250 500 1K 2K 4K 8K
lengths: see table 1. 1 19 15 11 12 8 10 11 10
2 18 14 9 11 9 9 10 10 4
3 15 10 7 9 8 8 9 10
4 14 10 7 8 8 7 8 9
Table 1: Correction of throw
Slot length 250 500 1000 1500 3000 5
Correction factor 0,7 0,85 1 1,1 1,2
Balancing
Balancing data for control of air volume is available in a sep-
arate brochure. 6
Frequency-related sound effect level
The sound effect level in the frequency band is defined as
LWA+Kok.
Kok values for MTL with box - see table 2.A and 2.B below. Sample calculation: 7
Required data: Volume of air 200 m3/h
Table 2.A: Kok values [dB] for MTL with sloth width 15. Throw 6.5 m
MTL-15-x + Box Mean frequency Hz Horizontal supply air 8
No. of slots (x) 63 125 250 500 1K 2K 4K 8K Slot length 1.5 m, i.e. 133 [(m3/h)/m]
1 8 3 6 -3 -10 -19 -27 -31
2 6 -1 5 -2 -8 -15 -23 -33 9
3 8 1 6 -2 -8 -17 -24 -31 Solution: MTL 19
4 6 -1 6 -2 -8 -15 -23 -31
2-slot version is selected:
Throw according to diagram: 5.8 m 10
Table 2.B: Kok values [dB] for MTL with sloth width 19.
MTL-15-x + Box Mean frequency Hz Throw correction according to table 1:
No. of slots (x) 63 125 250 500 1K 2K 4K 8K 1.1 x 5.8 = 6.4 m 11
1 11 8 6 -4 -12 -16 -23 -28 Pressure loss and sound level according
2 10 4 6 -4 -10 -15 -22 -28 to diagram:
3 8 2 7 -4 -11 -18 -24 -28 Open damper: 13 Pa, 15 dB(A)
4 9 3 6 -3 -10 -16 -23 -27 Closed damper: 38 Pa, 22 dB(A)
12

Correction according to table 3: 13


Table 3: Correction for other slot lengths
Slot length 250 500 1000 1500 3000 Open damper: 15 + 2 = 17 dB(A)
correction [dB(A)] -6 -3 0 2 5
Closed damper: 22 + 2 = 24 dB(A) 14

15

16

17

18

We reserve the right to make changes without prior notice 267


lindab | ceil ing di ffusers

Linear diffuser MTL


Technical data
1
Horizontal supply air

bv
bv = 0.006 × l0,2
lb = 0.6 × l0,2 lb Vertical
l0.2 [m] MTL-15 1 2
3 10

8 3
7
6
4
4 5

4
bh
3
L

5 2

bh = 0.02 × l0,2 + L l0.2 [m]


6 lb = 0.5 × l0,2
lb
1
qV [(l/s)/m]
5 10 15 20 30 40 50 60 70 80 100
qV [(m3/h)/m]
20 30 40 50 60 70 80 100 150 200 300

7 Vertical supply air


L

8 Throw MTL 19
Horizontal
l0.2 [m] MTL-19 1 2 3 4
9 10

8
lb

lb

7
6
5
10 4

11 bh bh
2

bh = 0.02 × l0,2 + L bh = 0.2 × l0,2 l0.2 [m]


12 lb = 0.6 × l0,2 lb = 0.6 × l0,2 1
qV [(l/s)/m]
5 10 15 20 30 40 50 60 70 100 150 200
qV [(m3/h)/m]
20 30 40 50 60 70 100 150 200 300 500 700

13 Throw MTL 15
Horizontal Vertical
l0.2 [m] MTL-15 1 2 3 4 l0.2 [m] MTL-19 1 2 3
10 10
14 8
7
8 4
7
6 6
5 5

15 4 4

3 3

16 2 2

l0.2 [m] l0.2 [m]


1 1
17 5 10 15 20 30 40 50 60 70 80
qV [(l/s)/m]
100 5 10 15 20 30 40 50 60 70 100 150
qV [(l/s)/m]
200
3
qV [(m /h)/m] qV [(m3/h)/m]
20 30 40 50 60 70 80 100 150 200 300 20 30 40 50 60 70 100 150 200 300 500 700

18

268 We reserve the right to make changes without prior notice


l indab | ceiling diff users

Linear diffuser MTL


Horizontal-supply Vertical-supply

ǻpt [Pa] MTL-15-1 + STB ǻpt [Pa] MTL-15-1 + STB 1


250 250
200 200
150 150
50 50
100
45
100
45 2
70 70
40
50 40 50
35
35
30 30
30 3
20 30 20
15 15 25
25
10 10 20

7
20
LWA dB(A)
7
LWA dB(A)
4
5 5
qV [(l/s)/m] qV [(l/s)/m]
10 15 20 30 40 50 60 70 80 10 15 20 30 40 50 60 70 80 90
3
qV [(m /h)/m] qV [(m3/h)/m]
40 50 60 70 80 90 100 150 200 40 50 60 70 80 90 150 200 300
5
ǻpt [Pa] MTL-15-2 + STB ǻpt [Pa] MTL-15-2 + STB
250 250
200 200
150 150 6
50 50
100 100
70 45 70 45

50 40 50 40
7
35
30 35 30
30
20 30 20
25
15

10
25
15

10 20
8
20
7 7
LWA dB(A) LWA dB(A)
5 5
qV [(l/s)/m] qV [(l/s)/m]
20 30 40 50 60 70 80 90 100 20 30 40 50 60 70 80 90 100 150 9
3
qV [(m /h)/m] qV [(m3/h)/m]
80 90 100 150 200 300 80 90 100 150 200 300 400 500

ǻpt [Pa] MTL-15-3 + STB


250
ǻpt [Pa] MTL-15-3 + STB
250
10
200 200
150 150

100 100
70 45
50
70 45
50
11
50 50
40 40

30 30 35
35
20 30 20 30 12
15 15 25
25
10 10 20
20
7
5
LWA dB(A)
7
5
LWA dB(A) 13
qV [(l/s)/m] qV [(l/s)/m]
30 40 50 60 70 80 90 100 150 30 40 50 60 70 80 90 100 150 200
qV [(m3/h)/m] qV [(m3/h)/m]
150 200 300 400 500 150 200 300 400 500 700
14
ǻpt [Pa] MTL-15-4 + STB ǻpt [Pa] MTL-15-4 + STB
250 250
200 200
150 150 15
100 50 100 50
70 45 70 45
50 50
40
35
40
16
30 35 30

20 20 30
30
15 15 25

10
25
10 20 17
20
7 7
LWA dB(A) LWA dB(A)
5 5
qV [(l/s)/m] qV [(l/s)/m]
30 40 50 60 70 80 90 100 150 200
3
qV [(m /h)/m]
30 40 50 60 70 80 90 100 150 200
qV [(m3/h)/m]
18
150 200 300 400 500 700 150 200 300 400 500 700

We reserve the right to make changes without prior notice 269


lindab | ceil ing di ffusers

Linear diffuser MTL


Horizontal-supply Vertical-supply

1 ǻpt [Pa] MTL-19-1 + STB ǻpt [Pa] MTL-19-1 + STB


250 250
200 200
150 150
50

2 100
50
100 45
70 70
45 40
50 50
40 35

3 30 35 30 30
20 30 20 25
15 15
25 20
10 10
20
4 7
LWA dB(A)
7
LWA dB(A)
5 5
qV [(l/s)/m] qV [(l/s)/m]
10 15 20 30 40 50 60 70 80 10 15 20 30 40 50 60 70 80 100
3
qV [(m /h)/m] qV [(m3/h)/m]
5 40 50 60 70 80 90 100 150 200 40 50 60 70 80 100 150 200 300

ǻpt [Pa] MTL-19-2 + STB ǻpt [Pa] MTL-19-2 + STB


250 250
200 200
6 150 150
50
100 50 100
45
70 45 70
40
7 50
40
50
35
30 35 30 30

20 30 20 25

8 15

10
25 15

10
20

20
7 7
LWA dB(A) LWA dB(A)
5 5
qV [(l/s)/m] qV [(l/s)/m]
9 20 30 40 50 60 70 80 100 20 30 40 50 60 70 80 100 150
3
qV [(m /h)/m] qV [(m3/h)/m]
80 100 150 200 300 400 80 100 150 200 300 400 500

10 ǻpt [Pa] MTL-19-3 + STB


250
ǻpt [Pa] MTL-19-3 + STB
250
200 200
150 150

100 100
11 70
45
50
70
50

45
50 50
40 40
30 35 30 35
12 20 30 20 30
15 15
25 25
10 10
20 20

13 7
5
LWA dB(A)
7
5
LWA dB(A)
qV [(l/s)/m] qV [(l/s)/m]
30 40 50 60 70 80 100 150 200 30 40 50 60 70 80 100 150 200
3
qV [(m /h)/m] qV [(m3/h)/m]
150 200 300 400 500 150 200 300 400 500
14 700 700

ǻpt [Pa] MTL-19-4 + STB ǻpt [Pa] MTL-19-4 + STB


250 250
200 200
15 150 150

100 50 100 50
70 45 70 45
50 50
16 35
40

35
40

30 30

20 30 20 30
15 25 15 25
17 10 20 10 20

7 7
LWA dB(A) LWA dB(A)
5 5
qV [(l/s)/m] qV [(l/s)/m]
18 30 40 50 60 70 80 100 150 200
3
qV [(m /h)/m]
30 40 50 60 70 80 100 150 200
qV [(m3/h)/m]
150 200 300 400 500 150 200 300 400 500 700
700

270 We reserve the right to make changes without prior notice


l indab | ceiling diff users

Linear diffuser MTL


Exhaust air- MTL 15 Exhaust air- MTL 19

ǻpt [Pa] MTL-15-1+STU ǻpt [Pa] MTL-19-1 + STU 1


250 250
200 200
150 150
50
100
45
100 2
70 70 50
50 40 50 45
40
30 35 30
35 3
20 30 20
30
15 15
25 25
10 10
7
20
LWA dB(A)
7
20
LWA dB(A)
4
5 5
qV [(l/s)/m] qV [(l/s)/m]
10 15 20 30 40 50 60 10 15 20 30 40 50 60 70 80 100
3
qV [(m /h)/m] qV [(m3/h)/m]
40 50 60 70 80 90 100 150 200 40 50 60 70 80 100 150 200 300
5
ǻpt [Pa] MTL-15-2+STU ǻpt [Pa] MTL-19-2 + STU
250 250
200 200
150 150 6
100 100
50 50
70 70
45 45
50
40
50
40
7
30 30
35 35
20 20
30 30
15

10 25
15

10
25 8
20
7 20 7
LWA dB(A) LWA dB(A)
5 5
qV [(l/s)/m] qV [(l/s)/m]
15 20 30 40 50 60 70 80 90 100 20 30 40 50 60 70 80 100 150 200 9
3
qV [(m /h)/m] qV [(m3/h)/m]
60 70 80 90 100 150 200 300 80 100 150 200 300 400 500 700

ǻpt [Pa] MTL-15-3+STU


250
ǻpt [Pa] MTL-19-3 + STU
250
10
200 200
150 150

100 100
70 70
50 11
50
50 50 45
45
40
30 40 30

20
35
20
30
35
12
30
15 15
25 25
10 10
20 20
7
5
LWA dB(A)
7
5
LWA dB(A) 13
qV [(l/s)/m] qV [(l/s)/m]
30 40 50 60 70 80 90 100 150 30 40 50 60 70 80 100 150 200
qV [(m3/h)/m] qV [(m3/h)/m]
150 200 300 400 500 150 200 300 400 500 700
14
ǻpt [Pa] MTL-15-4+STU ǻpt [Pa] MTL-19-4 + STU
250 250
200 200
150 150 15
100 100
50
50
70 70
50 45 50 45

40 40
16
30 30
35
35
20 20
30
15 15 30

10
20
25
10 25
17
7 7 20
LWA dB(A) LWA dB(A)
5 5
qV [(l/s)/m] qV [(l/s)/m]
30 40 50 60 70 80 90 100 150 200
3
qV [(m /h)/m]
30 40 50 60 70 80 100 150 200 300
qV [(m3/h)/m]
18
150 200 300 400 500 700 150 200 300 400 500 700 1000

We reserve the right to make changes without prior notice 271


lindab | ceil ing di ffusers

Plenum box STB/STU


Dimensions
1
L/2
L/4

25
C B
2

Ød

250
3

40
A
L
4

5
Box type / Length 0-1199 1200-1799 1800-2000
6 Description Slot size
STB is a rectangular plenum box for supply air for linear dif- No. of 15 19
fuser, MTL. The plenum box ensures even distribution over slots A B A B Ød No. Ød No. Ød No.
7 the linear diffuser. STB is equipped with a damper and an 1
2
26
51
90
100
41
80
91
130
125
160
1
1
160
200
1
1
125
160
2
2
orifice plate to ensure individual regulation, and is supplied 3 76 125 118 168 200 1 200 2 200 2
with acoustic insulation. 4 101 150 158 208 200 1 200 2 200 2

8 C dimension: STB = 100 mm


STU is a rectangular plenum box for air exhaust for linear
diffuser, MTL. STU has the same properties as STB. STU = 200 mm

9 • Ensures even air distribution over the linear diffuser.


• Acoustically insulated.
• Supplied with damper and measuring device
10

11

12

13

14

15

16 Order code
Product STB/STU a ba ccc
Type
17
Slot size 15 Materials and finish
19 Plenum box: Galvanised steel
18 No. of slots Standard finish: Galvanised steel
Length Insulation: Melamine foam plastic

272 We reserve the right to make changes without prior notice


l indab | ceiling diff users

Perforated exhaust plate PKY/PCY

B×B
B×B 1
A×A
A×A
2

3
C

ØC
5

Description Dimensions 6
PKY/PCY is a “diffuser” without duct connection for installa- PKY
tion in T-rail ceilings. PKY/PCY is used in situations where
air is to be exhausted over a suspended ceiling, and a suffi- 7
Free
cient opening is required in the ceiling for the air to pass
A B C area Curve Weight
through. Size mm mm m2 no. kg
500 495 467 0,085 1 1,3 8
• Architecturally and financially attractive “diffuser” solu-
600 595 567 0,125 2 1,8
tion for exhaust of air over a suspended ceiling
625 620 597 0,138 3 1,9
• Can be adapted for many different types of ceiling
• Low pressure loss and large air capacity 9
PCY

Maintenance A B C
Free
area Curve Weight
10
The visible parts of the diffuser can be wiped with a damp Size mm mm m2 no. kg
cloth. 500 495 400 0,043 4 1,6
600 595 490 0,064 5 2,1 11
625 620 490 0,064 5 2,2
Materials and finish
Pressure loss [Pa]
12
Material: Galvanised steel
Standard finish: Powder-coated 4 5 1 2 3
40
Standard colour: RAL 9010, gloss 30 13
30 40
The diffuser is available in other colours. Please contact
35
Lindab’s sales department for further information. 20

15
30 14
25
10

20
LA dB(A)
15
7

5
l/s

400
150
500
200
700 1000
300 400
1500
500
2000
700
3000
1000
m3/h 16
Order code
Product PKY aaa 17
Type
Size
18
Ceiling system - see introductory summary.

We reserve the right to make changes without prior notice 273


lin dab | ce ili n g d i ffu s e r s

Ceiling tile adaption


Overview
1
1. T24/T15 Lay-in 278 7. Danotile Contur 283
Ecophon D
2 Rockfon D-XL

4
2. T24/T15 Lay-in not cleanable 279 8. Ecophon 284
Focus DG

7
3. Permanent ceiling 279 9. Rockfon E10 24 285
Ecophon E / T24

10 4. Dampa Clip-in bevelled edge 280 10. Rockfon E10 15 286


Ecophon E / T15

11

12

13 5. Dampa Clip-in square edge 281 11. Danotile Markant 287

14

15
6. Luxalon Clip-in 282 14. Ecophon Focus Edge DS 288
16

17

18

274 Right to alterations reserved


l i nda b | c ei l i ng di ff u ser s

Ceiling tile adaption

10

11
Versio, Competence centre, Hobro.

Ceiling systems Ceiling adaption 12


A harmonic and aesthetic ceiling solution with beautifully Most of Lindabs ceiling diffusers can be adapted to
integrated components is a must in modern construc- 600x600 ceiling systems. The individual diffusers are
tions. The individual components themselves define the adapted to the ceiling system directly in the grille box, or 13
appearance of the final solution. Lindab contributes to the by using adapted module plates / frames, depending on
holism by adapting the diffusers to most 600x600 ceiling which ceiling system is chosen. The following pages show
systems. In this way the holism of the solution is main- Lindab´s standard offering; both in terms of face plates 14
tained, and the final result will become just as planned. and ceiling tile adaptions.

In the back of this 15


chapter is an over-
view of adapted
moduleplates. 16

17

18
PC7 diffuser.

Right to alterations reserved 275


lin dab | ce ili n g d i ffu s e r s

Ceiling tile adaption


Design Ceiling systems
1 See Comfort and design 1, 3, 7, 8, 9, 10, 11, 14

2
Product
Perforated Pattern 600 Pattern 500 Pattern 400 Pattern 300
3
PS 1 - 11

4
Swirl Pattern 600 Pattern 500 Pattern 400 Pattern 300

5 RS 14 - 16

6
Nozzles Pattern 600 Pattern 500 Pattern 400 Pattern 300

NS 19
7

8 Grid Pattern 600 Pattern 500 Pattern 400 Pattern 300

GS 23
9

10 Frame Pattern 600 Pattern 500 Pattern 400 Pattern 300

R
AxA AxA AxA AxA

11
R R R R

12 Pattern
600 500 400 300
R AxA R AxA R AxA R AxA
13
No. Ceiling type
mm mm mm mm mm mm mm mm
1 Lay-in 24/15 T-rack 595 564 595 464 595 383 595 383
3 Permanent ceiling 595 564 495 464 415 383 415 383

14 7 Hidden T-bar * 599 599 464 599 383 599 383


8 Partially visible t-rack T24 * 592 592 464 592 383 592 383
9 T24 E/markant * 575 595 464 595 383 595 383
15 10 T15 E/markant * 584 584 464 584 383 584 383
11 T24 Markant * 575 575 464 575 383 575 383
14 Ecophon Focus edge DS * 599 599 464 599 383 599 383
16 Ød U Ød U Ød U Ød U
Connection diffuser/box
mm mm mm mm mm mm mm mm
Grille box type V 315 575 250 475 200 395 160 395
17 Plenum box type H 250/315 575 200 475 160 395 125 395
AxB U AxB U AxB U AxB U
Rectangular connection
mm mm mm mm mm mm mm mm

18 Plenum box type R 498 x 98 575 398 x 98 475 298 x 98 395 198 x 98 395

* shows solutions without fame, A x A shows face plate measurement in mm, R shows measurements on frame around the face plate. U shows
recess.
Ret til ændringer forbeholdes
276 Right to alterations reserved
l i nda b | c ei l i ng di ff u ser s

Ceiling tile adaption


Design Ceiling systems
See Comfort and design 2,
2, 4,
5, 5,
6, 69 1

2
Product
Perforated Pattern 600 Pattern 500 Pattern 400 Pattern 300
3
PS 1 - 11

4
Swirl Pattern 600 Pattern 500 Pattern 400 Pattern 300

RS 14 - 16 5

6
Nozzles Pattern 600 Pattern 500 Pattern 400 Pattern 300

NS 19
7

Grid Pattern 600 Pattern 500 Pattern 400 Pattern 300 8


GS 23
9

10
AxA

A x A shows face plate dimension, A x A is the outer dimension


R
of all face plates. 11

12

13
Pattern

600 500 400 300

No. Ceiling type


AxA
mm
AxA
mm
AxA
mm
AxA
mm
14
2 Lay-in 24/15 T-rack not cleanable 595 595 595 595
4 Clip-in bevelled edge 600 600 600 600
15
5 Clip-in square edge 600 600 600 600
6 Clip-in 600 600 600 600

Connection diffuser/box
Ød
mm
Ød
mm
Ød
mm
Ød
mm
16
Grille box type V 315 250 200 160
Plenum box type H 250/315

AxB
200

AxB
160

AxB AxB
125
17
Rectangular connection
mm mm mm mm

Plenum box type R 498 x 98 398 x 98 298 x 98 198 x 98


18
A x A shows face plate measurements in mm

Ret til to
Right ændringer forbeholdes
alterations reserved 277
lin dab | ce ili n g d i ffu s e r s

Ceiling tile adaption


1. Ceiling adaption T24/T15 Lay-in
1 Lindab´s ceiling diffusers adapted to T 24 / T15 Lay-in is mounted directly in
the ceiling system as depicted in the sketches. The diffuser is delivered with a
detachable face plate, so full acess to the plenum box and the
600air duct is pos-
2 sible.

3 Sketch Versio- V, H, R pattern 300,400,500


( PBB mounting brackets not included, can be ordered separately. )

6
600
600
7
600

Sketch Versio- V, H, R pattern 600


9 ( PBB mounting brackets not included, can be ordered separately. )

10

11
600
600
12
600
600
13

14 Sketch moduleplate type LM- Integra/Formo

15

16 600

17
600

18

278 Right to alterations reserved


l i nda b | c ei l i ng di ff u ser s

Ceiling tile adaption


2. Ceiling adaption T24/ T15 Lay-in not cleanable

Lindab´s diffuser adapted to T 24 / T15 Lay-in is mounted directly in the ceiling


1
system, as depicted on the sketches. The face plate is in one piece and cannot
be detached unless the diffuser is demounted from the rack-system.
2

Sketch Versio- V, H, R all sizes


3
( PBB mounting brackets not included, can be ordered separately. )

600
600
7

3. Permanent ceiling
9
Lindabs diffuser adapted to permanent ceiling is cut directly into the ceiling construction. The diffuser can be fastened with
Lindabs different types of mounting brackets, see product pages for more details.
10

11
600

12

Plenum box type H including mounting bracket type Grille box type V including mounting bracket type PBB 13
PBB

Sketch Versio- V, H, R all sizes 14


( PBB mounting brackets included as standard. )

595 / 495 / 415


15

16
600

17

595 / 495 / 415 595 / 495 / 415 18

Right to alterations reserved 279


lin dab | ce ili n g d i ffu s e r s

Ceiling tile adaption


4. Dampa Clip-in bevelled edge
1 Lindab´s diffuser adapted to Dampa Clip-in bevelled edge is mounted directly in the ceiling system, as depicted in the sketches.

5
Plenum box type H including mounting bracket type Grille box type V including mounting bracket type PBB
6 PBB

7 Sketch Versio- V, H, R all sizes


( PBB mounting brackets included as standard. )

10
600 600

11 600

12 Sketch moduleplate type LM- Integra/Formo


600

13
600 600

14

15 600

16
600

17

18

280 Right to alterations reserved


l i nda b | c ei l i ng di ff u ser s

Ceiling tile adaption


5. Dampa Clip-in square edge

Lindab´s diffuser adapted to Dampa Clip-in square edge is mounted directly in the ceiling system, as depicted in the sketches.
1

5
Plenum box type H including mounting brackets type Grille box type V including mounting bracket type PBB
PBB 6

Sketch Versio- V, H, R all sizes 7


( PBB mounting brackets included as standard. )

9
600 600
10

600 11

Sketch moduleplate type LM- Integra/Formo


600
12

13
600 600
14

15
600
16
600

17

18

Right to alterations reserved 281


lin dab | ce ili n g d i ffu s e r s

Ceiling tile adaption


6. Luxalon Clip-in
1 Lindab´s diffuser adapted to Luxalon Clip-in is mounted directly in the ceiling system, as depicted in the sketches.

4
Plenum box type H including mounting bracket type Grille box type V including mounting bracket type PBB
5 PBB

7 Sketch Versio- V, H, R all sizes


( PBB mounting brackets included as standard. )

9 600 600

10

11
600
600
12

13 Sketch moduleplate type LM- Integra/Formo

14
600 600

15

16

17
600
600
18

282 Right to alterations reserved


l i nda b | c ei l i ng di ff u ser s

Ceiling tile adaption


7. Danotile Contur, Ecophon D and Rockfon D-XL

Lindab´s diffuser adapted to the above mentioned ceiling systems, is mounted directly in the ceiling system, as depicted in the
1
sketches.

4
Plenum box type H Grille box type V
5
600
Sketch Versio- V, H, R pattern 300, 400, 500
( PBB mounting brackets not included, can be ordered separately. ) 6

9
600 600

600
600 10
Sketch Versio- V, H, R pattern 600
( PBB mounting brackets included as standard. ) 11

12
Pay attention, turn faceplate correctly.
Plenum box not placed symmetrically in ceiling
system. 13
Pins not placed symmetrically
600 600 on faceplate.
600
14
X1 X2
600
600
15
Sketch moduleplate type LM- Integra/Formo

16

X1 X1 X2 X2
17
600 600

18
600

X1 Right to alterations reserved X2 283


600
lin dab | ce ili n g d i ffu s e r s

Ceiling tile adaption


8. Ecophon Focus DG
1 Lindab´s diffuser adapted to Ecophon Focus DG ceiling systems are mounted directly in the ceiling system, as depicted in the
sketches.

5 Plenum box type H including mounting bracket type Grille box type V including mounting bracket type PBB
PBB
600

6
Sketch Versio- V, H, R pattern 300, 400, 500
( PBB mounting brackets not included, can be ordered separately. )
7

9
600
600
10
600

Sketch Versio- V, H, R pattern 600


( PBB mounting brackets included as standard. )
11

12

13
600 600

14 600
600

15
Sketch moduleplate type LM- Integra/Formo

16

17

18 600

600

284 Right to alterations reserved


l i nda b | c ei l i ng di ff u ser s

Ceiling tile adaption


9. Rockfon E10 24
Ecophon E / T24
1
Lindab´s diffuser adapted to the above mentioned ceiling system is mounted directly in the ceiling system, as depicted in the
sketches.
2

Plenum box type H including mounting bracket type Grille box type V including mounting bracket type PBB 5
PBB

6
Sketch Versio- V, H, R pattern 300, 400, 500
( PBB mounting brackets not included, can be ordered separately. )
7
10

10

8
1010
10

600 600 9
600
600
600
10
Sketch Versio- V, H, R pattern 600
( PBB mounting brackets included as standard. )
11

12
10

10
1010

13
10

600 600

600 14
600
600

15
10

10

Sketch moduleplate type LM- Integra/Formo

16
600 600
1010

17
10

600
600
18
600

Right to alterations reserved 285


lin dab | ce ili n g d i ffu s e r s

Ceiling tile adaption


10. Rockfon E10 15
Ecophon E / T15
1
Lindab´s ceiling diffusers adapted to the above mentioned ceiling systems are mounted directly in the ceiling system, as de-
picted in the sketches.
2

5
Plenum box type H including mounting bracket type Grille box type V including mounting bracket type PBB
PBB
6
Sketch Versio- V, H, R pattern 300, 400, 500
10

7 ( PBB mounting brackets not included, can be ordered separately. )


10

10
10

8 600
10

600 600

9 600

600
10
Sketch Versio- V, H, R pattern 600
11 ( PBB mounting brackets included as standard. )

12

13
600 600
600
14
600

15
600
Sketch moduleplate type LM- Integra/Formo
16
10

10
10

17
600 600
10

18 600
10

286 600 reserved


Right to alterations
l i nda b | c ei l i ng di ff u ser s

Ceiling tile adaption


11. Danotile Markant

Lindab´s ceiling diffusers adapted to the above mentioned ceiling systems are mounted directly in the ceiling system, as dep-
1
ticted in the sketches.

5
Plenum box type H including mounting bracket type Grille box type V including mounting bracket type PBB
PBB
6
13

Sketch Versio- V, H, R pattern 300, 400, 500


13

( PBB mounting brackets not included, can be ordered separately. ) 7


600
13

13

600 8
13

600 600
9
600
10
Sketch Versio- V, H, R pattern 600
( PBB mounting brackets included as standard. ) 11

12
13

13
13

13

13

600
14
600
600 600
13

15
Sketch moduleplate type LM- Integra/Formo
600 16
13

17
13

13
13

600
18
600 600
600
Right to alterations reserved 287
13
lin dab | ce ili n g d i ffu s e r s

Ceiling tile adaption


14. Ecophon Focus edge DS
1 Lindab´s diffuser adapted to Ecophon Focus edge DS ceiling systems, is mounted directly in the ceiling system, as depicted
in the sketches.

4
Plenum box type H Grille box type V
5 600

Sketch Versio- V, H, R pattern 300, 400, 500


6 ( PBB mounting brackets not included, can be ordered separately. )

9
600 600

600
10 600

Sketch Versio- V, H, R pattern 600


11 ( PBB mounting brackets included as standard. )

12

13
600 600
600
14
600
600
15
Sketch moduleplate type LM- Integra/Formo

16

17
600 600
18 600

288 Right to alterations reserved


600
l i nda b | c ei l i ng di ff u ser s

Ceiling tile adaption


Moduleplate Ceiling tile adaption
1
1 4 5 6 7

Diffuser size
Min. - max.
2
Product
Ceiling types Danotile T24/T15 Dampa Clip-In Dampa Clip-In Luxalon SQ Danotile Contur
Ecophon T24
Rockfon A24.
bevelled edge square edge Clip-In Ecophon D
Rockfon D-XL
3
Moduleplate type LM mm F: 595 mm F: 600 mm F: 600 mm F: 600 mm F: 599 mm

PKA 125 - 250


4
LKA 125 - 250

PKV F 160 - 250

LKV 160 - 250


5
Moduleplate type LM mm F: 595 mm F: 600 mm F: 600 mm F: 600 mm F: 599 mm

PCA 100 - 400

LCA 100 - 400 6


CRL F
100 - 400

RCG 125 - 315

PC6 125 - 315 7


PC7 160 - 315

RC14 160 - 315

RC15 160 - 315 8


NC19 160 - 250

PCV 160 - 250

LCV 160 - 250


9
Combination possible
10

11

12

13

14

15

16

17

18

Right to alterations reserved 289


lin dab | ce ili n g d i ffu s e r s

Ceiling tile adaption


Moduleplate Ceiling tile adaption
1
8 9 10 11 14

Diffuser size
Min. - max.
2
Product
Ceiling types Ecophon Focus Rockfon E10 24 Rockfon E10 15 Danotile Markant Ecophon Focus
3 DG Ecophon E / T24 Ecophon E / T15 edge DS

Moduleplate type LM mm F: 595 mm F: 600 mm F: 600 mm F: 600 mm F: 599 mm

4 PKA 125 - 250

LKA 125 - 250

PKV F 160 - 250

5 LKV 160 - 250

Moduleplate type LM mm F: 595 mm F: 600 mm F: 600 mm F: 600 mm F: 599 mm

PCA 100 - 400


6 LCA 100 - 400

CRL F
100 - 400

RCG 125 - 315

7 PC6 125 - 315

PC7 160 - 315

RC14 160 - 315

8 RC15 160 - 315

NC19 160 - 250

PCV 160 - 250

9 LCV 160 - 250

Combination possible
10

11

12

13

14

15

16

17

18

290 Right to alterations reserved