01

Cast Resin Transformers

Tricast - up to 3 150 kVA eco


design

Standard fittings

Tricast without enclosure (IP00):


• HV voltage variation by off circuit tapping links
• 4 bi-directional flat rollers
• 4 lifting holes
• 4 haulage holes on the underbase
PM102297

• 2 earthing points
• 1 rating plate (on HV side)

Tricast with IP31 metal enclosure (except


underframe IP21):
- 2 lifting lugs for transformer and enclosure
Description assembly
- 1 earthing point on enclosure
Cast resin, 50 Hz , three-phased distribution
- HV tapping by removing a bolted
transformers with the following characteristics:
panel
Therm
- enclosure final colour RAL9002
• Indoor use / Outdoor use with properly
designed enclosure
Ecodesign regulation EU 548-2014
• Thermal class F - Temperature rise 100 K
• Ambient ≤ 40 °C, altitude ≤ 1000 m
• Maximal Loss levels
• MV windings encapsulated in cast resin
• Statement on Loss tolerances:
• Pre-impregnated LV windings
- No tolerance on transformer design
• Natural air cooling system (AN type)
- 5% tolerance for end user checks
• Core and frame covered with protective coating
• Additional data requested on the name plates
- Loss level and measured values
Standards - Type and weight of mail materials used
- CE Marking is MANDATORY
These transformers comply with standards:

• IEC 60076-11, PrEN 50588
• Ecodesign Directive EU 548-2014
Dry Type Transformers maximum loss
levels according to Ecodesign:
A0
Schneider Electric guarantees that its transformers
are:
• Insulation voltage MV ≤ 24 kV & LV ≤ 1.1 kV
Ak
• C2 Climatic class
- A0Bk up to 630 kVA
• E2 Environment class according to
- A0Ak over 630 kVA Bk
IEC 60076-16
• Insulation voltage: MV ≤ 36 kV & LV ≤ 1.1 kV
• F1 Fire behaviour class
- A0 +15% Bk +10% ≤ 630 kVA Ck
• Almost partial discharge free - Acceptance level:
- A0 +15% Ak +10% > 630 kVA
- ≤ 10 pC Routine Test
02
Cast Resin Transformers Tricast - 7.2 kV and 12 kV A0Ak

Electrical characteristics
Rated power (kVA) 250 315 400 500 630 800 1000 1250 1600 2000 2500 3150

Rated frequency (Hz) 50 50 50 50 50 50 50 50 50 50 50 50

Primary voltage (V) 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000

Isolation level (kV) 12 12 12 12 12 12 12 12 12 12 12 12

Secondary voltage at no-load (V) 400 400 400 400 400 400 400 400 400 400 400 400

Tappings (%) +/- 5 +/- 5 +/- 5 +/- 5 +/- 5 +/- 5 +/- 5 +/- 5 +/- 5 +/- 5 +/- 5 +/- 5

Vector groups Dyn Dyn Dyn Dyn Dyn Dyn Dyn Dyn Dyn Dyn Dyn Dyn

Losses (W) - no-load losses 520 620 750 900 1100 1300 1550 1800 2200 2600 3100 3800

Losses (W) - load losses at 120°C 3400 3900 4500 5630 7100 8000 9000 11000 13000 16000 19000 22000

Rated impedance voltage (%) 6 6 6 6 6 6 6 6 6 6 6 6

Max altitude (m) 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000

Max ambiental temperature (C) 40 40 40 40 40 40 40 40 40 40 40 40

Nature of HV/LV windings AI/AI AI/AI AI/AI AI/AI AI/AI AI/AI AI/AI AI/AI AI/AI AI/AI AI/AI AI/AI
E/2
J J L I
Dimensions and weights without
enclosure housing (IP00)
Dimensions and weights are for guidance only,
and are provided for a single-voltage transformer Ø 13
tapping
links
with the following HV insulation levels and low C

voltages. Only the definitive drawings following M


H

from the order will commit us contractually. For B


other voltages, impedance voltages and dual- earthing
terminal
voltages, weights and dimensions are different. D
40 (50)
Ø 125 (160) D
A E

Tricast IP00

Insulation level: 7.2 kV and 12 kV- low voltage 400 V to 433 V


Rated power (kVA) 250 315 400 500 630 800 1000 1250 1600 2000 2500 3150

Dimensions (mm) - Lenght A 1290 1350 1370 1420 1500 1530 1620 1700 1830 1880 2050 2330

- Width B 680 800 800 800 800 800 950 950 950 1230 1230 1270

- Height C 1340 1430 1510 1550 1570 1720 1880 1940 2140 2220 2250 2680

- Roller pitch D 520 670 670 670 670 670 820 820 820 1070 1070 1070

- Frame width E 645 795 795 795 795 795 945 945 945 1195 1195 1195

- Roller diam. F 125 125 125 125 125 125 125 125 125 160 160 200

- Roller width G 40 40 40 40 40 40 40 40 40 50 50 70

Weight without enclosure (kg) 1180 1400 1600 1780 2080 2400 3020 3600 4180 5160 6240 10060

Dimensions and weights with IP31 metal I

enclosure
Dimensions and weights are for guidance only, Ø 13

and are provided for a single-voltage transformer


tapping
with the following HV insulation levels and low links C

voltages. Only the definitive drawings following


from the order will commit us contractually. For
other voltages, impedance voltages and dual- earthing

voltages, weights and dimensions are different. terminal 40 (50)


D
Ø 125 (160) D
A B

Tricast IP31
© 2015 Schneider Electric. All rights reserved.

Insulation level: 7.2 kV and 12 kV- low voltage 400 V to 433 V


Rated power (kVA) 250 315 400 500 630 800 1000 1250 1600 2000 2500 3150

Dimensions (mm) - Lenght A 1650 1700 1800 1800 1800 1900 2150 2150 2130 2180 2350 2630

- Width B 950 1020 1020 1020 1020 1100 1170 1170 980 1230 1230 1270

- Height C 1750 1900 2050 2050 2050 2480 2480 2480 2440 2620 2650 3080

- Roller pitch D 520 670 670 670 670 670 820 820 820 1070 1070 1070

- Frame width E 645 795 795 795 795 795 945 945 945 1195 1195 1195

- Roller diam. F 125 125 125 125 125 125 125 125 125 160 160 200

- Roller width G 40 40 40 40 40 40 40 40 40 50 50 70

Weight with enclosure (kg) 1340 1580 1790 1870 2270 2620 3320 3900 4470 5470 6565 10470

NRJED315633EN 03 2015
03
Cast Resin Transformers Tricast - 7.2 kV and 12 kV A0Bk

Electrical characteristics
Rated power (kVA) 250 315 400 500 630

Rated frequency (Hz) 50 50 50 50 50

Primary voltage (V) 10000 10000 10000 10000 10000

Isolation level (kV) 12 12 12 12 12

Secondary voltage at no-load (V) 400 400 400 400 400

Tappings (%) +/- 5 +/- 5 +/- 5 +/- 5 +/- 5

Vector groups Dyn Dyn Dyn Dyn Dyn

Losses (W) - no-load losses 520 623 750 900 1100

Losses (W) - load losses at 120°C 3800 4550 5500 6425 7600

Rated impedance voltage (%) 6 6 6 6 6

Max altitude (m) 1000 1000 1000 1000 1000

Max ambiental temperature (C) 40 40 40 40 40

Nature of HV/LV windings AI/AI AI/AI AI/AI AI/AI AI/AI


E/2
J J L I
Dimensions and weights without
enclosure housing (IP00)
Dimensions and weights are for guidance only,
Ø 13
and are provided for a single-voltage transformer tapping
links
with the following HV insulation levels and low C

voltages. Only the definitive drawings following M


H

from the order will commit us contractually. For B

other voltages, impedance voltages and dual- earthing


terminal

voltages, weights and dimensions are different. Ø 125 (160)


D
40 (50)
D
A E

Tricast IP00

Insulation level: 7.2 kV and 12 kV- low voltage 400 V to 433 V


Rated power (kVA) 250 315 400 500 630

Dimensions (mm) - Lenght A 1270 1290 1320 1370 1410

- Width B 680 800 800 800 800

- Height C 1340 1410 1510 1530 1660

- Roller pitch D 520 670 670 670 670

- Frame width E 645 795 795 795 795

- Roller diam. F 125 125 125 125 125

- Roller width G 40 40 40 40 40

Weight without enclosure (kg) 1140 1260 1460 1640 1880

Dimensions and weights with IP31 metal I

enclosure
Dimensions and weights are for guidance only,
Ø 13
and are provided for a single-voltage transformer
with the following HV insulation levels and low tapping
links C

voltages. Only the definitive drawings following


from the order will commit us contractually. For
other voltages, impedance voltages and dual-
voltages, weights and dimensions are different. earthing
terminal
D
40 (50)
Ø 125 (160) D
A B

Tricast IP31
© 2015 Schneider Electric. All rights reserved.

Insulation level: 7.2 kV and 12 kV- low voltage 400 V to 433 V


Rated power (kVA) 250 315 400 500 630

Dimensions (mm) - Lenght A 1650 1700 1800 1370 1900

- Width B 950 1020 1020 800 1100

- Height C 1750 1900 2050 1530 2300

- Roller pitch D 520 670 670 670 670

- Frame width E 645 795 795 795 795

- Roller diam. F 125 125 125 125 125

- Roller width G 40 40 40 40 40

Weight with enclosure (kg) 1300 1440 1650 1830 2100

NRJED315633EN 03 2015
04
Cast Resin Transformers Tricast - 17.5 kV and 24 kV A0Ak

Electrical characteristics for insulation level


Rated power (kVA) 250 315 400 500 630 800 1000 1250 1600 2000 2500 3150

Rated frequency (Hz) 50 50 50 50 50 50 50 50 50 50 50 50

Primary voltage (V) 2000 2000 2000 2000 2000 2000 2000 2000 2000 2000 2000 2000

Isolation level (kV) 24 24 24 24 24 24 24 24 24 24 24 24

Secondary voltage at no-load (V) 400 400 400 400 400 400 400 400 400 400 400 400

Tappings (%) +/- 5 +/- 5 +/- 5 +/- 5 +/- 5 +/- 5 +/- 5 +/- 5 +/- 5 +/- 5 +/- 5 +/- 5

Vector groups Dyn Dyn Dyn Dyn Dyn Dyn Dyn Dyn Dyn Dyn Dyn Dyn

Losses (W) - no-load losses 520 620 750 900 1100 1300 1550 1800 2200 2600 3100 3800

Losses (W) - load losses at 120°C 3400 3900 4500 5630 7100 8000 9000 11000 13000 16000 19000 22000

Rated impedance voltage (%) 6 6 6 6 6 6 6 6 6 6 6 6

Max altitude (m) 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000

Max ambiental temperature (C) 40 40 40 40 40 40 40 40 40 40 40 40

E/2
J J L I
Dimensions and weights without
enclosure housing (IP00)
Dimensions and weights are for guidance only,
and are provided for a single-voltage transformer Ø 13
tapping
links
with the following HV insulation levels and low C

voltages. Only the definitive drawings following M


H

from the order will commit us contractually. For


B
other voltages, impedance voltages and dual- earthing
terminal
voltages, weights and dimensions are different. D
40 (50)
Ø 125 (160) D
A E

Tricast IP00

Insulation level: 17.5 kV and 24 kV- low voltage 400 V to 433 V


Rated power (kVA) 250 315 400 500 630 800 1000 1250 1600 2000 2500 3150

Dimensions (mm) - Lenght A 1320 1365 1410 1460 1480 1630 1660 1740 1850 1960 2050 2320

- Width B 730 810 820 830 830 850 950 950 970 1230 1230 1270

- Height C 1430 1520 1600 1640 1770 1810 1970 2140 2180 2280 2500 2660

- Roller pitch D 520 670 670 670 670 670 820 820 820 1070 1070 1070

- Frame width E 645 795 795 795 795 795 945 945 945 1195 1195 1195

- Roller diam. F 125 125 125 125 125 125 125 125 125 160 160 200

- Roller width G 40 40 40 40 40 40 40 40 40 50 50 70

Weight without enclosure (kg) 1180 1400 1600 1780 2000 2840 2840 3460 4180 5120 6160 8520

Dimensions and weights with IP31 metal I

enclosure
Dimensions and weights are for guidance only, Ø 13

and are provided for a single-voltage transformer


with the following HV insulation levels and low tapping
links C

voltages. Only the definitive drawings following


from the order will commit us contractually. For
other voltages, impedance voltages and dual-
voltages, weights and dimensions are different.
earthing
terminal 40 (50)
D
Ø 125 (160) D
A B

Tricast IP31
© 2015 Schneider Electric. All rights reserved.

Insulation level: 17.5 kV and 24 kV- low voltage 400 V to 433 V


Rated power (kVA) 250 315 400 500 630 800 1000 1250 1600 2000 2500 3150

Dimensions (mm) - Lenght A 1720 1800 1900 1900 1900 1900 2150 2140 2250 2360 2450 2720

- Width B 990 1020 1100 1100 1100 1100 1170 1130 1170 1230 1230 1270

- Height C 1730 2050 2300 2300 2300 2300 2480 2440 2480 2680 2900 3060

- Roller pitch D 520 670 670 670 670 670 820 820 820 1070 1070 1070

- Frame width E 645 795 795 795 795 795 945 945 945 1195 1195 1195

- Roller diam. F 125 125 125 125 125 125 125 125 125 160 160 200

- Roller width G 40 40 40 40 40 40 40 40 40 50 50 70

Weight with enclosure (kg) 1360 1590 1820 2000 2220 3060 3140 3810 4530 5495 6560 8970

NRJED315633EN 03 2015
05
Cast Resin Transformers Tricast - 17.5 kV and 24 kV A0Bk

Electrical characteristics for insulation level


Rated power (kVA) 250 315 400 500 630

Rated frequency (Hz) 50 50 50 50 50

Primary voltage (V) 20000 20000 20000 20000 20000

Isolation level (kV) 24 24 24 24 24

Secondary voltage at no-load (V) 400 400 400 400 400

Tappings (%) +/- 5 +/- 5 +/- 5 +/- 5 +/- 5

Vector groups Dyn Dyn Dyn Dyn Dyn

Losses (W) - no-load losses 520 620 750 900 1100

Losses (W) - load losses at 120°C 3800 4550 5500 6425 7600

Rated impedance voltage (%) 6 6 6 6 6

Max altitude (m) 1000 1000 1000 1000 1000

Max ambiental temperature (C) 40 40 40 40 40

E/2

Dimensions and weights without


J J L I

enclosure housing (IP00)


Dimensions and weights are for guidance only,
and are provided for a single-voltage transformer Ø 13
tapping
with the following HV insulation levels and low links
C

voltages. Only the definitive drawings following M


H
from the order will commit us contractually. For
B
other voltages, impedance voltages and dual- earthing
terminal
voltages, weights and dimensions are different. D
40 (50)
Ø 125 (160) D
A E

Tricast IP00

Insulation level: 17.5 kV and 24 kV- low voltage 400 V to 433 V


Rated power (kVA) 250 315 400 500 630

Dimensions (mm) - Lenght A 1300 1330 1360 1430 1480

- Width B 730 810 810 820 830

- Height C 1430 1520 1600 1640 1790

- Roller pitch D 520 670 670 670 670

- Frame width E 645 795 795 795 795

- Roller diam. F 125 125 125 125 125

- Roller width G 40 40 40 40 40

Weight without enclosure (kg) 1140 1360 1520 1720 2040

Dimensions and weights with IP31 metal I

enclosure
Dimensions and weights are for guidance only, Ø 13

and are provided for a single-voltage transformer


with the following HV insulation levels and low tapping
links C

voltages. Only the definitive drawings following


from the order will commit us contractually. For
other voltages, impedance voltages and dual-
earthing
voltages, weights and dimensions are different. terminal
D
40 (50)
D
Ø 125 (160)
A B

Tricast IP31
© 2015 Schneider Electric. All rights reserved.

Insulation level: 7.2 kV and 12 kV- low voltage 400 V to 433 V


Rated power (kVA) 250 315 400 500 630

Dimensions (mm) - Lenght A 1650 1700 1800 1370 1900

- Width B 950 1020 1020 800 1100

- Height C 1750 1900 2050 1530 2300

- Roller pitch D 520 670 670 670 670

- Frame width E 645 795 795 795 795

- Roller diam. F 125 125 125 125 125

- Roller width G 40 40 40 40 40

Weight with enclosure (kg) 1300 1440 1650 1830 2100

NRJED315633EN 03 2015
06
Cast Resin Transformers Tricast - 36 kV A0Ak

Electrical characteristics for insulation level: up to 36 kVA


Rated power (kVA) 250 315 400 500 630 800 1000 1250 1600 2000 2500 3150

Rated frequency (Hz) 50 50 50 50 50 50 50 50 50 50 50 50

Primary voltage (V) 30000 30000 30000 30000 30000 30000 30000 30000 30000 30000 30000 30000

Isolation level (kV) 36 36 36 36 36 36 36 36 36 36 36 36

Secondary voltage at no-load (V) 400 400 400 400 400 400 400 400 400 400 400 400

Tappings (%) +/- 5 +/- 5 +/- 5 +/- 5 +/- 5 +/- 5 +/- 5 +/- 5 +/- 5 +/- 5 +/- 5 +/- 5

Vector groups Dyn Dyn Dyn Dyn Dyn Dyn Dyn Dyn Dyn Dyn Dyn Dyn

Losses (W) - no-load losses 598 712 862 1037 1265 1495 1782 2070 2530 2990 3565 4370

Losses (W) - load losses at 120°C 3740 4264 4950 6193 7810 8800 9900 12100 14300 17600 20900 24200

Rated impedance voltage (%) 6.5 6.5 6.5 6.5 6.5 6.5 6.5 6.5 6.5 6.5 6.5 6.5

Max ambiental temperature (C) 40 40 40 40 40 40 40 40 40 40 40 40

E/2
J J L I
Dimensions and weights without
enclosure housing (IP00)
Dimensions and weights are for guidance only,
Ø 13
and are provided for a single-voltage transformer tapping
links
with the following HV insulation levels and low C

voltages. Only the definitive drawings following M


H

from the order will commit us contractually. For B

other voltages, impedance voltages and dual- earthing


terminal

voltages, weights and dimensions are different. Ø 125 (160)


D
40 (50)
D
A E

Tricast IP00

Insulation level: up to 36 kV - low voltage 400 V to 433 V


Rated power (kVA) 250 315 400 500 630 800 1000 1250 1600 2000 2500 3150

Dimensions (mm) - Lenght A 1490 1490 1530 1530 1580 1740 1810 1870 1950 2280 2500 2840

- Width B 800 870 880 880 890 920 1000 1010 1030 1230 1260 1340

- Height C 1790 1790 1950 1950 1990 2160 2230 2420 2460 2630 2710 2750

- Roller pitch D 520 670 670 670 670 670 820 820 820 1070 1070 1070

- Frame width E 645 795 795 795 795 795 945 945 945 1195 1195 1195

- Roller diam. F 125 125 125 125 125 125 125 125 125 160 160 200

- Roller width G 40 40 40 40 40 40 40 40 40 50 50 70

Weight without enclosure (kg) 1660 1660 1960 2000 2240 2960 3420 3980 4700 7220 9260 13180

Dimensions and weights with IP31 I


metal enclosure
Dimensions and weights are for guidance only,
and are provided for a single-voltage transformer Ø 13

with the following HV insulation levels and low tapping


links
voltages. Only the definitive drawings following
C

from the order will commit us contractually. For


other voltages, impedance voltages and dual-
voltages, weights and dimensions are different. earthing
terminal 40 (50)
D
Ø 125 (160) D
A B

Tricast IP31
© 2015 Schneider Electric. All rights reserved.

Insulation level: up to 36 kV - low voltage 400 V to 433 V


Rated power (kVA) 250 315 400 500 630 800 1000 1250 1600 2000 2500 3150

Dimensions (mm) - Lenght A 1990 1990 2030 2030 2080 2240 2310 2370 2450 2780 3000 3340

- Width B 1220 1220 1230 1240 1250 1310 1330 1350 1380 1490 1560 1670

- Height C 2090 2090 2250 2250 2290 2460 2530 2720 2760 3030 3110 3150

- Roller pitch D 520 670 670 670 670 670 820 820 820 1070 1070 1070

- Frame width E 645 795 795 795 795 795 945 945 945 1195 1195 1195

- Roller diam. F 125 125 125 125 125 125 125 125 125 160 160 200

- Roller width G 40 40 40 40 40 40 40 40 40 50 50 70

Weight with enclosure (kg) 1890 1895 2200 2245 2500 3260 3740 4320 5060 7650 9760 13760

NRJED315633EN 03 2015
07
Cast Resin Transformers Tricast - 36 kV A0Bk

Electrical characteristics for insulation level


Rated power (kVA) 250 315 400 500 630

Rated frequency (Hz) 50 50 50 50 50

Primary voltage (V) 30000 30000 30000 30000 30000

Isolation level (kV) 36 36 36 36 36

Secondary voltage at no-load (V) 400 400 400 400 400

Tappings (%) +/- 5 +/- 5 +/- 5 +/- 5 +/- 5

Vector groups Dyn Dyn Dyn Dyn Dyn

Losses (W) - no-load losses 598 712 862 1037 1265

Losses (W) - load losses at 120°C 4180 4990 6050 7054 8360

Rated impedance voltage (%) 6.5 6.5 6.5 6.5 6.5

Max ambiental temperature (C) 40 40 40 40 40


E/2
J J
Dimensions and weights without
L I

enclosure housing (IP00)


Dimensions and weights are for guidance only,
and are provided for a single-voltage transformer Ø 13
tapping
with the following HV insulation levels and low links
C

voltages. Only the definitive drawings following M


H

from the order will commit us contractually. For


B
other voltages, impedance voltages and dual- earthing
terminal
voltages, weights and dimensions are different. D
40 (50)
Ø 125 (160) D
A E

Tricast IP00

Insulation level: up to 36 kV low voltage 400 V to 433 V


Rated power (kVA) 250 315 400 500 630

Dimensions (mm) - Lenght A 1490 1470 1470 1500 1570

- Width B 800 870 870 880 890

- Height C 1790 1790 1810 1950 1990

- Roller pitch D 520 670 670 670 670

- Frame width E 645 795 795 795 795

- Roller diam. F 125 125 125 125 125

- Roller width G 40 40 40 40 40

Weight without enclosure (kg) 1660 1640 1800 1920 2220

Dimensions and weights with IP31 metal I

enclosure
Dimensions and weights are for guidance only, Ø 13

and are provided for a single-voltage transformer


tapping
with the following HV insulation levels and low links C

voltages. Only the definitive drawings following


from the order will commit us contractually. For
other voltages, impedance voltages and dual- earthing

voltages, weights and dimensions are different.


terminal 40 (50)
D
Ø 125 (160) D
A B

Tricast IP31
© 2015 Schneider Electric. All rights reserved.

Insulation level: up to 36 kV- low voltage 400 V to 433 V


Rated power (kVA) 250 315 400 500 630

Dimensions (mm) - Lenght A 1990 1970 1970 2000 2070

- Width B 1220 1220 1220 1230 1250

- Height C 2090 2090 2110 2250 2290

- Roller pitch D 520 670 670 670 670

- Frame width E 645 795 795 795 795

- Roller diam. F 125 125 125 125 125

- Roller width G 40 40 40 40 40

Weight with enclosure (kg) 1885 1870 2040 2165 2480

NRJED315633EN 03 2015
08
Cast Resin Transformers Tricast - up to 3 150 kVA

Connections - Tricast transformers with-


out enclosure housing (IP00)
The winding resin coating and the plug-in
connectors don’t ensure any protection against
touch when the transformer is energized. The
contrator must ensure that cables and busbars
are adequately supported to prevent
mechanical stresses from being imposed on the
transformer terminals, busbars or bushings.

Minimum clearances required HV and LV standard connection

SM100019
SM100018

cable support

Insulation Dimension X (mm)


X LV n HV
LV (kV)
Full wall Grid wall

X X
7.5 90 300

12 120 300 120 120


mini mini

17.5-24 220 300


HV
X

Connections -Tricast transformers with


IP31 metal enclosure
Minimum clearances required HV and LV standard connection
SM100020

SM100021

200 mm

LV n HV
LV
200 mm

cable support

cable support
200 mm

HV

500 mm*

LV terminations HV terminations
SM100022

SM100023

70 80
23.5

23.5

40 33 33
15

Ø 14
33

33

33

4 x Ø 14 4 x Ø 14

50
160 to 400 kVA* 500 to 800 kVA* 1000 to 1250 kVA*
thickness 5 thickness 6 thickness 10

100 160
50 80 40
25

35
50

4 x Ø 14 4 x Ø 16
50

Ø 13

1600 kVA* 2000 kVA* thickness 10


thickness 12 2500 kVA* thickness 2u10
*Valid for aluminium terminations.
© 2015 Schneider Electric. All rights reserved.

The contrator must ensure that cables and


busbars are adequately supported to prevent
mechanical stresses from being imposed on the
transformer terminals, busbars or bushings.

Schneider Electric Industries SAS For more information about Ecodesign, visit:
Head Office www.schneider-electric.com/transformers eco
35, rue Joseph Monier - CS 30323
F92506 Rueil-Malmaison Cedex design
FRANCE
www.schneider-electric.com
©2014 Schneider Electric. All trademarks are owned by Schneider Electric Industries SAS or its affiliated companies. 998-1247929_GMA-GB

NRJED315633EN 03 2015