Professional Documents
Culture Documents
Operating Procedures
Please refer to Figures 2-1 and 2-2 for location of the valves, pipes, switches, and other
equipment on the service and chiller units.
Filling Water Tanks
There are two water tanks in the system: hot water tank on the service unit and the cold water
tank on the chiller. Water circulates in two closed circuits (one for hot water and one for cold
water) and the tanks are filled prior to the class. Therefore, the students should not need to fill the
tanks.
In case the water tanks do need to be filled please follow these instructions:
Hot water tank
a) If the tank is empty: Add water until the low level is reached (level switch trips and the
Low Water Level warning lamp goes out). Then add 0.5 L of water with a beaker.
b) If the tank is filled but with an unknown volume above the low level: Partially drain the
tank using the Hot Water Drainage valve on the service unit until the low level is reached
(level switch trips and the Low Water Level warning lamp lights up). Then add 0.5 L of
water with a beaker.
Cold water tank
Fill the tank until you see water in the sight glass.
Start-up
1. Secure the selected heat exchanger on the base plate of the service unit. Connect the tubes for
the inlet and outlet flows. In addition, for the tubular heat exchanger, connect the temperature
sensors at the midpoint of the heat exchanger to the service unit.
2. Turn on the main switches on the chiller and the service unit.
3. Open the regulator valves V1 and V2 for cold and hot water flow rates on the service unit.
4. Set the desired temperatures Th,i and Tc,i for the hot and cold water feeds using the temperature
setpoint controllers on the service unit (for hot water) and the chiller (for cold water). Turn on
the heater and the chiller and wait until the water temperatures reach the setpoint values.
NOTE: A situation may arise in which temperature of the hot fluid in the tank is higher than
its setpoint value Th,i or temperature of the cold fluid is lower than its setpoint value Tc,i. If
temperature of water in the hot water tank is higher than Th,i, turn the heater off and run the
heat exchanger until the water in the hot circuit is cooled to the desired value. Similarly, if
necessary, warm up cold water to Tc,i by running the heat exchanger while the chiller is turned
off.
5. Turn on the pumps on the service unit and the chiller.
6. If required, bleed the heat exchanger to remove air bubbles trapped in it:
a. Detach the heat exchanger base plate while keeping all tubes connected to the heat
exchanger.
b. Turn the heat exchanger so that water is flowing upwards to push the air out.
c. Reattach the base plate
3‐1
Unit Operations Lab Heat Exchanger
3‐2