INPUT DATA

DATED = 28-02-2019
POLE HEIGHT = 3 MTR
C/C OF POLE = 2500 MM
SITE ID = DL/DL/AT/7511
SITE NAME = JHARODA DAIRY_A
JHARODA DAIRY_A

SITE ADDRESS =
NOS. OF POLE = 3 NOS.
P1 SIZE = 500 X 500 X 500 5
P2 SIZE = 500 X 500 X 500 5
DIA OF STEEL P1 = 16 MM DIA
NOS. OF U BAR P1 = 2 NOS.
DIA OF STEEL P2 = 16 MM DIA
NOS. OF U BAR P2 = 2 NOS.
SIZE OF OD BTS SLAB = 4730 X 3250 X 150
DIA /SPACING = 10 DIA 200 MM

CLIENT = M/s ATC- TELECOM TOWER CORPORATION PVT LTD


V.A.S DESIGN & INFRA CONSULTANTS PVT. LTD.
307/1, PLOT NO.108,SHAHZADABAGH INDUSTRIAL AREA,OLD ROHTAK ROAD,DELHI-
110035 PH.-9350186656
E-MAIL-vasdesign2011@gmail.com

Report Base on Tower/Pole Foundation,

( SITE NAME : JHARODA DAIRY_A )


( SITE ID : DL/DL/AT/7511
)
Site Address:-

JHARODA DAIRY_A

Client

M/s ATC- TELECOM TOWER CORPORATION PVT LTD


SITE NAME SITE ID TOWER HT.(M) DATE
V.A.S DESIGN & INFRA CONSULTANTS PVT. LTD
JHARODA DL/DL/AT/7511 3 28-02-2019
DAIRY_A
DESIGN OF BASE PLATE AND ANCHOR BOLT
TOWER HT. DETAIL OF = 3 M
MAX. COMPRESSIVE FORCE = 5.6 KN
MAX. TENSIL FORCE = 5.6 KN
MAX SIDE THRUST = 3.2 KN
NO OF H. D. BOLTS PROPOSED = 4 NOS
AXIAL FORCES IN EACH BOLTS = 1.40 KN
SHEAR FORCE IN EACH BOLTS = 0.81 KN
GRADE OF CONCRETE IN PEDESTAL = 20.00 M

DESIGN OF ANCHOR BOLT


PERMISSIBLE STRESS FOR BOLTS OF PROPERTY CLASS OF 4.6 GRADE AS PER TABLE-1, IS:802 (PART-1/SEC-2)-1992

PERMISSBLE STRESS IN SHEAR = 218.00 N/mm^2


PERMISSBLE STRESS IN AXIAL TENSION = 194.00 N/mm^2
GROSS AREA OF THE BOLT REQD. = 9.99 mm^2
1.395/194X0.72
DIAMETER OF BOLT REQUIRED = 3.51 mm

DIAMETER OF BOLT PROVIDED = 16 mm


ACTUAL AXIAL STRESS IN EACH BOLT = 9.64 N/mm^2
ACTUAL AXIAL STRESS IN EACH BOLT 4.03 N/mm^2

CHECK FOR COMBINED STRESS 0.0858 < 1.2


9.64/218+4.03/194+4.03/194 Safe

PERMISSIBLE STRESS IN BOND IN = 0.8 N/mm^2


PLANE BAR AS PER TABLE-21 OF IS: 456: 2000

CAPACITY OF PLATE
LENGTH BREDTH THICKNESS
SIZE OF THE PLATE PROVIDED = 300 300 10
AREA OF PLATE'S TOP FACE = 90000 mm^2

PERMISSIBLE STRESS IN CONCRETE IN = 5 N/mm^2


BEARING ( AS PER IS 456-2000)
CAPACITY OF PLATE IN BEARING = 450000 N
WITH CONCRETE OR = 450 KN

GROUT LENGTH OF THE BOLT REQUIRED


= 62.1 mm
SITE NAME SITE ID TOWER HT.(M) DATE
V.A.S DESIGN & INFRA CONSULTANTS PVT. LTD
JHARODA DL/DL/AT/7511 3 28-02-2019
DAIRY_A

MAX FOUNDATION FORCES ACTING ON BUILDING COLUMN:


Down Thrust = 5.58 KN
Side Thrust = 3.24 KN

Uplif = 5.58 KN
Side Thrust = 3.24 KN
DESIGN OF HILITY REBARING

Determination of Basic Anchorage Length :

Lb (reqd.) = (Ds/4)X(σst/fbd)

Where As
Ds = Diameter of Rebar
σst = Calculated Design Stress of Rebar
fbd = Design Value of ond strength

Assume Diameter of Rebar = 16 mm


Assume No of Bars = 4 mm
Calculated Design Stress of Rebar = 10.41 N/mm^2

Design value of bond strength = 1.9 N/mm^2 For 40mm Cover


As Per Hilty Manual

Lb (reqd.) = 22 mm

Lbd = ά1 x ά2 x ά3 x ά42 x ά5x Lbd(Reqd)


Where
ά1 = Effect of Form of the forms of Bars
ά2 = Effect of minimum Concrete cover
ά3 = Effect of Confinment of Transeverse Reinforcement

ά4 = Effect of infulence of one of more wleded Bars


along with Design Annchorage Length,
ά5 = Effect of Pressure Transverse to the Plane of
Splitting along with Design Anchorage Length

For compression = ά1 x ά2 x ά3 x ά4 = 1

Lbd (10xDs) = 21.9099302400386*1

lbd (min) 21.91 mm


Provide 100 mm depth for the Hilti Rebar with RE500 Compound (As per the site condition)
BAR BENDING SCHDULE

Bar No. of Length Total Unit


S.no. Beam Bar Shape a b c Peaces ofBar
One Length Wt.
Dia

A B
1 P1 16 0.45 0.575 6 1.6 9.6 1.580

C
2 RING (P1) 8 A 0.45 0.45 0.128 15 2.056 30.84 0.395
B

A B
3 P2 16 0.45 0.575 12 1.6 19.2 1.580

C
4 RING (P2) 8 A 0.45 0.45 0.128 30 2.056 61.68 0.395
B

Pole & A B
5 10 4.63 0.1 36 4.83 173.88 0.617
OD Slab

Pole & A B
6 10 3.15 0.1 50 3.35 167.5 0.617
OD Slab
Shuttering=8.394 Sq Mtr Total R.C.C=3.055875 Cu Mtr Total Steel
Total
Wt.

15.17

12.18

30.34

24.37

107.33

103.40
292.79
CERTIFICATE OF STRUCTURAL
(To whom so ever it may concern)

(SITE NAME: JHARODA DAIRY_A)


(SITE ID : DL/DL/AT/7511
)

This is to certify that the building located at JHARODA DAIRY_A has been surveyed & feasibility
checked for 3 Mtr High Pole, with od BTS. The site is found suitable in all respect as per guidelines of
BIS codes.

The above certificate has been issued for the exclusive use of the project of “M/s ATC TELECOM INDIA
PVT.LTD.” based on the drawings submitted by us...

The responsibility of the VAS Design & Infrastructures Consultants Pvt. Ltd, New Delhi shall be limited
to technical advice on matters referred by the company. All procedural/ legal / Operational matters will
be the responsibility of the company.

For VAS Design & Infrastructures Consultants Pvt. Ltd,


& feasibility
as per guidelines of

ATC TELECOM INDIA

elhi shall be limited


erational matters will