SIGA-DMP Duct Detector Mounting

Plate Installation Sheet


Description Figure 1: Installation options

The Signature Series SIGA-DMP Duct Detector Mounting Plate (DMP) is used to Installation Options
mount a smoke detector inside an air duct. The DMP provides screws for ALARM

mounting the detector base and includes a rubber gasket which forms an airtight
seal between the mounting plate and the duct. (2)
Refer to the installation sheets provided with the detector, base, remote LED (1)
(5)
alarm indicator, or control relay module for specific wiring instructions.
(3) (6)
Installation
Cautions (4)

• For proper operation, only the specified detectors should be used with this
mounting plate. A detector that is not rated for the air velocities produced in 8 7 6

air ducts will not operate properly and may result in loss of life.
• The DMP is intended for use only in the three configurations shown in (7)
4 3 2 1

Figure 1. For other duct sizes, refer to the appropriate manufacturer's


documentation. (5) ALARM

• Do not mount the DMP on the bottom side of a duct. This position will result (3)
in excessive dirt buildup in the detector and will adversely affect proper
(6)
operation.
(6)
To install the DMP:
1. Refer to the technical bulletin (P/N 270145) for installation guidelines.

2. Using the template provided in Figure 2, drill eight 1/16 in. (1.58 mm) holes
and cut out the 4-3/4 in. (12.07 cm) circle. (7)
3. Make sure the holes in the duct correctly align with the holes in the DMP. (5) ALARM

4. Remove the appropriate conduit knockout on the DMP.


(6) (3)
5. Mount the base on the DMP as shown in Figure 1 and wire the base
according to the instructions provided with the base.
(6)
6. Choose installation option A, B, or C as shown in Figure 1, and mount the
components as shown.
(8)
7. Mount the DMP on the duct using eight #8-32 × 1/2 self-tapping screws
(provided). (9)

(10)
Specifications
(11)
Electrical box (included): Standard 4 in. (102 mm) square box, 1-1/2 in. (38 mm)
deep with single-gang cover
Compatible bases: SB, RB, IB
Compatible detectors: PS, PHS, PHSB, IPHS
(12)
Compatible remote annunciator: LED
Duct wall thickness: Up to 3/4 in. (19.05 mm)
Air velocity
PS, PHS, PHSB: 0 to 4,000 ft./min (0 to 20.32 m/s) (13)
IPHS: 0 to 500 ft./min (0 to 2.54 m/s)
Operating relative humidity: 0 to 93% noncondensing
Construction: Steel, high-gloss red (A) Remote LED alarm indicator (4) 36 in. (91.44 cm) max. 72 in.
Related documents: Technical bulletin (P/N 270145) (LED) mounted on DMP (182.88 cm) max. if two
(B) Control relay module (CR) detectors are used
mounted directly on DMP (5) 2.8 in. (7.11 cm)
Contact information
(C) Blank cover plate (standard (6) 36 in. (91.44 cm) max.
For contact information, see www.edwardsutcfs.com. electrical) mounted on DMP (7) LED at remote location
(8) LED
(1) Side of duct. The DMP can be (9) Blank cover plate and CR
mounted on either side of the (10) Blank cover plate
duct in all options. (11) DMP
(2) Top of duct (12) Compatible base
(3) Center line (13) Compatible detector

© 2013 UTC Fire & Security Americas Corporation, Inc. 1/2 P/N 387053P-EN • REV 07 • ISS 02JUL13