Condensate Drain Installation SAIC-K-4007 30-Apr-13 HVAC
PROJECT TITLE WBS / BI / JO NUMBER CONTRACTOR / SUBCONTRACTOR

EQUIPMENT ID NUMBER(S) EQUIPMENT DESCRIPTION EQPT CODE SYSTEM ID. PLANT NO.

LAYOUT DRAWING NUMBER REV. NO. PURCHASE ORDER NUMBER EC / PMCC / MCC NO.

SCHEDULED INSPECTION DATE & TIME ACTUAL INSPECTION DATE & TIME QUANTITY INSP. MH's SPENT TRAVEL TIME
SAUDI ARAMCO USE ONLY
SAUDI ARAMCO TIP NUMBER SAUDI ARAMCO ACTIVITY NUMBER WORK PERMIT REQUIRED?

SAUDI ARAMCO INSPECTION LEVEL CONTRACTOR INSPECTION LEVEL

ITEM
ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-INSP DATE
No.

(Exception) Drain piping for condensate waste from air conditioning


SAES-S-060
A1 cooling coils shall be indirectly connected to a floor drain, or shall be
Para 807.2
indirectly connected into the inlet side of a P-trap.

Evaporators of air handling units shall be mounted a minimum of 150 SAES-K-001


A2
mm (6 inch) of the floor, to allow room for condensate trap. Para 5.3.4.1
Condensate drain line shall be of corrosion-resistant type. SAES-K-100
A3
(UMC Para 309.1) Section 1

Condensate drain line (discharge piping) shall not be smaller than the SAES-K-100
A4
drain pan connection. (UMC Para 309.1). Section 1

Drain pans shall extend completely under the coil sections and shall
SAES-K-001
A5 have minimum 1-¼ inch threaded drain connections for AHUs with the
Para 4.8.8.9 (g)
total supply air equal to or greater than 5,000 cfm.
SAES-K-001
A6 Drain pan shall be sloped toward drain connection.
Para 4.8.8.9 (g)
Condensate drain line shall maintain a minimum horizontal slope in the SAES-K-100
A7
direction of discharge not less than 1%. (UMC para 309.1) Section 1

The drain pipe trap shall have a water seal height equal to or larger
than the fan's External Static Pressure (ESP) but not less than 50 mm
SAES-K-001
A8 (2").
Para 5.3.4.2 (d)
Note:ESP can be read from the Construction drawings or
Specifications

Condensate drain pipe shall discharge or connect indirectly to the


SAES-K-001
nearest floor drain in accordance with the requirements of ASHRAE
Para 5.3.4.2 (e)
A9 Equipment Handbook.
Exception: HVAC units installed outside of buildings may discharge
condensate onto the ground or roof, but not onto walkways.

Drains pan shall be sealed, double wall steel construction with rigid SAES-K-001
A10
glass fiber insulation and Type 316 stainless steel inner pan. Para 4.8.8.9 (g)

REMARKS:

REFERENCE DOCUMENTS:
1-SAES-K-001 -- Heating, Ventilating and Air Conditioning (HVAC), 05 Dec 2012
2-SAES-K-100 -- Saudi Aramco Mechanical (HVAC) Code, 20 Oct, 2012
3-SAES-S-060 -- Saudi Aramco Plumbing Code, 28 March 2013
4-Uniform Mechanical Code (UMC), 2009

Contractor / Third-Party Saudi Aramco


Construction Representative* PMT Representative
Work is Complete and Ready for Inspection: T&I Witnessed QC Record Reviewed Work Verified
Name, Initials and Date: Name, Initials and Date:

Page 1 of 2
QC Inspector PID Representative
Performed Inspection Work / Rework May Proceed T&I Witnessed QC Record Reviewed Work Verified
Name, Initials and Date: Name, Initials and Date:

QC Supervisor Proponent and Others


Quality Record Approved: T&I Witnessed QC Record Reviewed Work Verified
Name, Organization,
Name, Sign and Date:
Initials and Date:

*Person Responsible for Completion of Quality Work / Test Y = YES N = NO F = FAILED

Page 2 of 2

You might also like