You are on page 1of 64

Human contact currents induced by electrical field in

Swedish 400 kV substations


Master of Science Thesis

JONAS CEDERGREN

Department of Signals and Systems


CHALMERS UNIVERSITY OF TECHNOLOGY
Göteborg, Sweden, 2006
Report No. EX070/2006
Thesis for the degree of Master of Science

Human contact currents induced by electrical field in


Swedish 400kV substations

Jonas Cedergren, Gothenburg, Sweden 2006

In Corporation with

The Swedish National Electrical Grid

Chalmers University of Technology


Department of Signals and Systems
SE – 412 96 Gothenburg

Examinator at Chalmers:
Prof. Yngve Hamnerius

Supervisor at Svenska Kraftnät:


Kjell-Åke Persson

August 2006
Abstract
Due to a new European directive 2004/40/EC of the European Parliament and of the Council,
the demand of knowledge about exposure to electromagnetic fields for workers has increased.
This thesis focus on the contact current exposure levels in Swedish 400 kV substations.

Earlier studies have been performed in the substation in Stenkullen (Fracke & Åke 2004) and
(Pettersson & Österlund 2005). The outcome of those studies showed the magnetic fields to
be within the restrictions (500 µT), but the electrical field strengths were exceeded in several
positions according to the action value of 10 kV/m stated in the directive.

The directive is directly based on ICNIRP’s guidelines from 1998. ICNIRP’s guidelines give
the opportunity to increase the action value to 20 kV/m under some conditions. Such
conditions are when adverse indirect effects from contact with charged conductors can be
excluded.

The action value for contact current is set to maximum 1 mA in the directive. The main
purpose of this thesis is to study the contact current for different work tasks, to see for which
situations this action value is fulfilled. If 1 mA not is exceeded, the possibility of increasing
the field strength to 20 kV/m can be used.

The highest contact current value obtained in this study was 180 µA when a person touches a
single grounded object. To touch a van exposed to an electric field and a grounded object at
the same time gave a current of 1.17 mA.

Spark discharges at pre contact with a grounded object was found to cause the most
annoyance by their stimulation of muscle nerves, but such discharges are not limited in the
regulations. Levels of 1.75 A in a fraction of a second where obtained.

Induced open circuit voltage potentials at a person were measured and found to fluctuate
between 200 and 2400 V depending on position, soil and weather condition during work.

The effect of available protective clothing were studied and found to protect well from spark
discharges.
Sammanfattning
Kravet på kunskap om elektromagnetiska fält i arbetslivet har ökat efter att ett nytt EU
direktiv, 2004/40EG, antagits. Denna studie fokuserar på kontaktströmmar i svenska 400 kV
ställverk.

Tidigare studier har genomförts i ett ställverk i Stenkullen (Fracke och Åke 2004) &
(Pettersson och Österlund 2005). Resultatet från dessa studier visade på att det magnetiska
fältet låg inom insatssvärdet (500 µT), men det elektriska fältet överskred det föreskrivna
värdet på 10 kV/m.

EU-direktivet är baserat på ICNIRP’s riktlinjer från 1998, vilka ger en möjlighet att öka
insatsvärdet hos det elektriska fältet till 20 kV/m om ett annat insatsvärde, kontaktström, ej
överskrider 1 mA. Syftet med detta examensarbete är att undersöka nivån på kontaktströmmar
som en arbetare utsätts för. Om det inte överskrider maxinivån kan möjligheten att öka den
elektriska fältstyrkan till 20 kV/m tillämpas.

Det högsta värde på kontaktström mellan en arbetare och ett jordat föremål uppmättes till 180
µA. Vid samtidig beröring av en skåpbil exponerad i ett elektriskt fält och en jordat föremål
uppmättes en ström på 1.17 mA

Gnisturladdningar precis innan kontakt etablerats med ett jordat föremål upplevs som det mest
besvärande för arbetare. Dessa förorsakar ofrivilliga muskelrörelser genom stimulering av
nerver men är ej reglerade i direktivet. Strömstyrkor på 1.75 A uppmättes under en bråkdel av
en sekund.

Inducerade spänningar i en person mättes under olika arbetspositioner. Resultatet visade på


fluktuationer mellan 200 och 2400 V beroende på position, underlag och väder.

Skyddskläders skärmande verkan uppmättes också och befanns skydda väl från
gnisturladdningar.
Acknowledgements
I would like to express my gratitude towards all the persons who have made this master
thesis possible by all their support and guidance. First of all we would like to thank my
supervisors, Kjell Åke Persson at Svenska Kraftnät for the opportunity to perform this thesis
and Yngve Hamnerius at Chalmers for excellent guidance and support.

I owe the kind people in Stenkullen and Lindome substations a great deal. Specially Kjell-Åke
Elfving and JB Mårtensson for always helping me out when I needed support for my
measurements. Kjell Hertzberg, Thorbjörn Karlsson and Peter Karlsson have also helped me a
lot.

At Chalmers, I specially want to show my gratitude towards Yuriy Serdyuk for patiently and
skilfully answered all my questions. At the same institution as Yuriy, Jörgen Blennow and
Björn Sonerud have also been very helpful. Thanks to Wilgot Bokhede for guidance and help
with the measuring equipment, Ralf Berntsson for support and help with my room at
Chalmers. Mikael Persson for reviewing the report.

Two companies have been kind to support be with equipment; Caparol (Lars Bengtsson) for
their paint “electro shield” and Shopservice in Stenkullen for giving me a great discount of a
dummy.

Also, I wish to thank;

Göran Olsson at STRI and Anette Larsson, Vattenfall for helpful discussion and support with
literature.

Kari Jokela and Jarmo Elovaara at STUK in Finland for guidance and interpretation of EU
and ICNIRP regulations.

Kjell Hansson Mild at the “National Institute for Working Life” for the idea of voltage
measurement.

Rasmus Anthin for help with signal treatment and Matlab difficulties.

Last but not least; thanks to my lovely girlfriend Suzanne always being there for me and my
family for their support.

Thank you all!

Gothenburg, Chalmers August 2006.


Table of Contents
1 Introduction .................................................................................................................... - 1 -
2 Background .................................................................................................................... - 2 -
2.1 Regulations.................................................................................................................. - 2 -
2.1.2 Current density ......................................................................................................... - 4 -
2.1.3 Explanation of contact current .................................................................................. - 4 -
2.1.4 Contact current in the 2004/40/EC directive.............................................................. - 5 -
2.2 The Body impedance ................................................................................................... - 6 -
2.3 The impedance versus contact area .............................................................................. - 7 -
2.4 Impedance for transients or higher frequency current................................................... - 8 -
2.5 Earlier studies and calculations based on empirical data............................................... - 9 -
2.6 Contact current from large objects ............................................................................. - 10 -
2.7 Spark discharges from humans................................................................................... - 12 -
2.8 Perception levels and current effects on humans ........................................................ - 12 -
3 Methodology ................................................................................................................ - 15 -
4 Basic theory and technology ......................................................................................... - 17 -
4.1 Electromagnetic fields ............................................................................................... - 17 -
4.2 The wave ................................................................................................................... - 17 -
4.3 Electric fields............................................................................................................. - 18 -
4.4 Magnetic fields .......................................................................................................... - 19 -
4.5 The substation............................................................................................................ - 20 -
5 Work performed in a substation .................................................................................... - 22 -
5.1 Inspection and small work ......................................................................................... - 22 -
5.2 Maintenance, mounting and service at breakers ......................................................... - 24 -
5.3 Work with disconnectors ........................................................................................... - 25 -
6 Measuring equipment ................................................................................................... - 27 -
6.1 Electric field measurement......................................................................................... - 27 -
6.2 Stationary contact current measurement..................................................................... - 29 -
6.3 Contact current flowing through the body from a vehicle to a grounded object. ......... - 30 -
6.4 Transient contact current measurement ...................................................................... - 31 -
6.5 Using a phantom........................................................................................................ - 33 -
6.7 Protective clothing..................................................................................................... - 33 -
7 Measuring positions...................................................................................................... - 35 -
7.1 Stenkullen.................................................................................................................. - 35 -
7.2 Lindome .................................................................................................................... - 37 -
8 Measurement results ..................................................................................................... - 39 -
8.1 Measurements in Stenkullen ...................................................................................... - 39 -
8.1.1 Contact currents and open circuit voltage................................................................ - 39 -
8.1.2 Measurements with protective clothing ................................................................... - 43 -
8.2 Measurements in Lindome......................................................................................... - 44 -
8.3 Measurements in Strömma......................................................................................... - 45 -
8.4 Transient analysis – spark discharges......................................................................... - 45 -
8.5 Weather dependence.................................................................................................. - 49 -
9 Discussion and Conclusion ........................................................................................... - 50 -
9.1 Contact current .......................................................................................................... - 50 -
9.1.1 Uncertainty of the contact current measurements. ................................................... - 51 -
9.2 Voltage measurement ................................................................................................ - 51 -
9.3 Electric field measurements ....................................................................................... - 52 -
9.4 Current discharge measurements................................................................................ - 53 -
9.5 Protective clothing..................................................................................................... - 53 -
9.6 General conclusions................................................................................................... - 54 -
References....................................................................................................................... - 55 -
Chalmers University of Technology

1
Introduction
Workers in a high voltage substation can be exposed to high electric and magnetic field
strength, due to the high voltage and high current.

During the years, there has been a raising concern about the health effect when being exposed
to high electromagnetic fields. The issue of whether electromagnetic fields affect general
health is still today a debate for scientists throughout the world. There are several
recommendations, standards and directives that restrict the exposure levels of electromagnetic
fields. Often, there are different regulations for exposure of the general public and for
occupational exposure. This difference is due to better controllability for occupational
workers.

A new directive, 2004/40/EC, initiated by the European Parliament and of the Council of 29,
April 2004 has been adopted for countries in the European Union (EU 2004). The directive is
titled “minimum health and safety requirements regarding the exposure of workers to the risks
arising from physical agents (electromagnetic fields)”. The member countries have, according
to the directive, at most four years to implement the directive in their national legalisation.
Thus, the levels stated in the directive shall be regulated at latest 29 April 2008.

The limits in the directive are based on the International Commission on Non-Ionizing
Radiation Protection (ICNIRP) guidelines (ICNIRP 1998). ICNIRP’s main function is to
investigate the hazards with exposure of non-ionizing radiation and make recommendations
and guidelines based on present science. The directive of 2004/40/EC is only directed towards
short time EMF (electromagnetic field) exposure that causes health effects in the human body.
Since little is yet known about long time exposure and no unambiguous scientific evidence
has been shown about long time exposure hazards, such restrictions are not included. The
directive includes contact currents, induced currents and SAR-limitations (energy absorption
rate at high frequencies).

Two earlier studies, performed in a 400 kV substation in Stenkullen, showed that the electric
field strength exceeded the “action values” (10 kV/m) stated in the directive (Fracke & Åke
2004) and (Pettersson & Österlund 2005).

This gave raise to a concern; will the workers be able to continue to work without violating
the limitations in the directive in 400 kV high voltage substations? The main focus in this
thesis will be on contact currents, one of the restraints in the directive that has not been well
investigated in Swedish substations. The action values in the directive are set, not to exceed
the human current density limitation prescribed. If the contact currents are shown to be low, it
might be possible to enhance the allowance of the electric field strength to the double as
ICNIRP suggest.

-1-
Chalmers University of Technology

2
Background
This chapter tries to sort out the concept and give a background to the limitations in the
directive.

A human body exposed to a time varying electrical field obtain charges at the surface of the
body. The distribution of surface charges depends of the strength of the field as well as size
and shape of the body and its location within the field.

Currents caused by the surface charges flows in the body. For a human standing in an
electrical field from a overhead power line, the field induces a current flowing from the head
down the body and out through the feet.

2.1 Regulations
There are limitations for allowed body currents which are established by ICNIRP and the
European Union. These limitations are given as current density (mA/m2) within the body. The
limitations distinguish between occupational exposure and exposure for general public. This
is because workers generally are considered more aware of their exposure and they act in
accordance with this. Also workers are considered better observed than the general public.

Table 2.1 shows the current density limits for 50 Hz electromagnetic field exposure and the
action values appurtenant.

Category of people Action values; electric Action values; Limitation; current


field exposure [kV/m] magnetic field density for head and
exposure [µT] trunk [mA/m2]
Occupational workers 10 500 10
General public 5 100 2

Table 2.1 Limits and action values for different category of people. Source: ICNIRP’s guidelines (1998),
recommendations adopted by the European Council (1999).

In directive 2004/40/EC of the European parliament and of the council of 29 April 2004, the
occupational exposure for current density given in table 2.1 was established. The directive
forces the member countries to institute national laws containing the above limitations.

The directive is based on ICNIRP’s recommendations from 1998. Table 2.2 shows exposure
limit values in the directive for occupational exposure. Data are exactly the same as the basic
restrictions from ICNIRP.

-2-
Chalmers University of Technology

Table 2.2 Exposure limit values from directive 2004/40/EC of the European parliament and of the council of 29
April 2004. Note that this is the limits and shall under no circumstances be exceeded. Yellow marks indicate
limits at 50 Hz.

The action values in table 2.3 shows exposure values established if the limits in table 2.2 not
shall be exceeded. They are set because there is no easy way to directly measure the current
density within the head and trunk. Instead other measurable units are used. They are the same
as ICNIRP’s reference values but are referred as “action values” in the directive.

Table 2.3 Action values from the directive 2004/40/EC for occupational exposure. Values are given as rms for
unperturbed field. Yellow marks indicates limits at 50 Hz.

The maximum contact currents for 50 Hz is 1 mA according to table 2.3

In ICNIRP (1998), reference levels are explained as follows:

Reference levels of exposure are provided for comparison with measured levels of
physical quantities; compliance with all reference levels given in these guidelines will

-3-
Chalmers University of Technology

ensure compliance with the basic restrictions. If measured values are higher than the
reference levels, it does not necessarily follow that the basic restrictions have been
exceeded, but a more detailed analysis is necessary to assess compliance with the basic
restrictions.

ICNIRP further writes:

The reference levels are intended to be spatially averaged values over the entire body of
the exposed individual, but with the important proviso that the basic restrictions on
localized exposure are not exceeded.

2.1.2 Current density


For low frequencies, induced current density is the only limitation that is restricted as a “limit
value”. Current density, denoted (J), is defined as “the current flowing through a unit cross
section perpendicular to its direction in a volume conductor such as the human body or part of
it, expressed in amperes per square metre (A/m2)” (EU 2004). The following quotations from
ICNIRP’s guidelines explain how the action values, or by terms of ICNIRP; the reference
levels, are set.

In the frequency range up to 1 kHz, the general public reference levels for electric
fields are one-half of the values set for occupational exposure. The value of 10
kV/m for a 50-Hz or 8.3 kV/m for a 60-Hz occupational exposure includes a
sufficient safety margin to prevent stimulation effects from contact currents under
all possible conditions. Half of this value was chosen for the general public
reference levels, i.e., 5 kV/m for 50 Hz or 4.2 kV/m for 60 Hz, to prevent adverse
indirect effects for more than 90% of exposed individuals.

Further down in the guidelines, one can read:

For the specific case of occupational exposures at frequencies up to 100 kHz, the
derived electric fields can be increased by a factor of 2 under conditions in which
adverse indirect effects from contact with electrically charged conductors can be
excluded.

This means if one can state that contact currents do not have adverse indirect effects, i.e. if the
action value of contact current does not exceed the maximum value, the maximum electric
field strength for occupational exposure may be doubled from 10 kV/m to 20 kV/m at 50 Hz.

Current density limits are given in the basic restrictions in ICNIRP. They are in the frequency
range 1 Hz to 10 MHz set to prevent effects on nervous system functions (ICNIRP 1998).

2.1.3 Explanation of contact current


Contact current occurs when a human touches or grasps two objects with different potentials,
resulting in a current flowing through the body. If the person is grounded, contacts current
occur when touching a potential that is different from the ground. A third alternative is when
the person is being exposed to an electrical field, and touches a grounded object. Here the

-4-
Chalmers University of Technology

induction object resulting in a potential would be the person herself (Reilly 1998 p 343).

It is important to distinguish between transient current and steady state current when dealing
with contact currents. A person exposed to a high electrical sinusoidal field carries a potential
induced by the field which vary along with the period. If the potential is high enough, a spark
will fly from either the person or the grounded object, just before contact has been
established, resulting in a transient discharge current. This will happen every time the voltage
is high enough to overcome the gap.

2.1.4 Contact current in the 2004/40/EC directive


The question whether the action values for contact currents should include pre contact i.e. the
spark discharges or only the stationary contact came to an issue. Kari Jokela1 at “STUK”,
(Finnish “Radiation and Nuclear Safety Authority”) answers in a mail;

The current limit values in the directive can in my opinion be applied only for continuous
current when the contact has been established.

He continues:

However, also the spark discharge currents are important because they cause discomfort
and even maybe some cellular damage in the finger. Therefore it is important to reduce
them in the working environment. It is a good idea to try to measure both of them by the
same time.

In a second mail, when asking how the current limitations in ICNIRP 1998 were set, he
declares:

I should know something of the setting the ICNIRP 1998 limits because I was involved in
that work. The current limit 1 mA was simply based on classical data on the perception
threshold of electric current. However, according to the recent study of Leitgeb et
al.(2005) some people may sense considerably lower currents even below 0,1 mA. This
does not look to me a big health problem.

Jarmo Elovaara2, leading specialist at STUK adds:

We have carried out contact current measurements in places where 400 kV line cross
over public roads and where people have contacted us because of nuisance they have
experienced. Even people moving with bicycles have made complaints due to the
transient contact currents. We have not tried to find a correlation between the 50 Hz
contact current amplitudes and the transient current amplitudes but we wanted show the
effectiveness of the shield wires installed along the road at the crossing area.
Unfortunately the measurement report is written only in Finnish. We have not either
carried out these kinds of measurements in substations. In few lines I can tell that the
field strength 7 kV/m for sure causes unpleasant sensations within some individuals. In a
400 kV substation this level is regularly exceeded. In the described conditions the peak
value of the transient current (has approximately a double exponential form) can be

1
Kari Jokela, research professor at STUK, (Radiation and Nuclear Safety Authority, Finland), mail contact
January 16 and 17, 2006.
2
Jarmo Elovaara, leading specialist at STUK, (Radiation and Nuclear Safety Authority, Finland), mail contact
January 16 and 17, 2006.

-5-
Chalmers University of Technology

about three orders of magnitudes higher than the peak value of the continuous current.
Our experience is also, that the measurement of the transients is not completely simple
task.

In principle when a person touches the in field a grounded object he might be exposed to
several current pulses. However, the pulses can cause so much pain or unpleasantness,
that the person draws e.g. his hand away in "safe area" or takes a grip from the charged
object causing that current pulses are transformed to a continuous current. My own
experience is, that nobody is willing to sense repeatedly transient contact currents, they
can be so unpleasant. In practice the workers ground themselves with a piece of copper
wire when they have to work in conditions where the electric field strength is high. Of
course, conductive protective clothing might be a solution but one should be able to earth
it.

Concluding the information above, one can state that the action values in the 2004/40/EC
directive can only be applied for stationary contact current, but it is of great importance to
protect the workers from spark discharges as well.

2.2 The Body impedance


When a current flows through the human body, the impedance of the body itself is depending
of the current path within the body, the applied voltage and the frequency of the current. For
DC or low frequency steady state current, the impedance is dependent of the resistive part of
the body. Figure 2.1 shows this relationship.

Figure 2.1 The hand to hand body resistance as a function of applied voltage. Source: IEE Proc. Gener. Transm.
Distrib. (1999). Data from IEC 479-1 (1984).

The diagram above can be applied for hand to hand voltage at 50 Hz, the grid frequency. The
three different curves in the picture indicate body resistance which is not exceeded by five

-6-
Chalmers University of Technology

percent, 50 percent and 95 percent of the population respectively.

If the current path differs from one hand to the other, figure 2.2 can be used.

Figure 2.2 Distribution of internal impedance of the human body. The numbers indicate percentage of the total
internal impedance for hand to hand contacts. Numbers within brackets are the impedance from the specific
place to both hands. Data from IEC 479-1 (1984).

Deducting of information from figure 2.1 and 2.2, one can make a rough estimation of the
lowest impedance from hand to hand or hand to foot. At a voltage level above 200 Volt, the
impedance would be slightly below 1000 ohm. The impedance for upper body current to one
hand would be approximately 500 ohm. According to Reilly (1998 p 21), the skin impedance
is the primary factor that limits the current through the body if the applied voltage is below
200 V.

2.3 The impedance versus contact area


A large grasping area (i.e. contact area), generally implies better contact with increased
current to the body as a result. However, the importance of contact area is decreasing with
applied increasing voltage. Biegelmeier (1985) has made experiments of the influence of the
contact area size. Figure 2.3 shows the total hand to hand body impedance for dry skin with a
various set of electrode sizes.

-7-
Chalmers University of Technology

Figure 2.3 Body impedance as a function of applied voltage for different size of electrode areas. Source:
Biegelmeier (1985).

For low voltage levels, the impedance is almost inversely proportional to the area. The curves
converge towards each other as voltage is increased. At a voltage level of 225 V, the total
body impedance vary only about 4:1 for a dramatic change in electrode area of 8200:1
according to Reilly’s interpretation of the figure above (Reilly 1998 p 35).

For low frequency and DC, experiment shows that wet or dry skin plays a significant role to
the body impedance at low voltages, but the importance is decreasing with a raise in applied
voltage (Freiberger 1934).

2.4 Impedance for transients or higher frequency current


For higher frequencies, body impedance plays an important role when spark discharges occur
to the skin. A spark has a very short duration and has high frequency components.

When grasping or touching a conducting device with a potential different from the body, a
spark will ignite if the differences in voltage is over 500 V (peak voltage) according to Reilly
(1998 p 54-56). This can be explained by the dielectric strength of the skins outermost layer,
the corneum. This layer consists of dead body cells. The spark lowers the impedance of the
skin for the fraction of a second it will last. At higher voltages, a spark will ignite before
contact is mad. Thus, the spark will overcome both the gap in the air and the skin.

However, breakdown of skin impedance has been reported for voltages as low as between 100
and 200 V (Reilly 1998 p 56-57). In those experiments, a small contact area was used.
Breakdown of skin impedance can not be directly compared to spark discharges, but shows its
complex nonlinear impedance behaviour. Reilly mentions that breakdown of skin and spark

-8-
Chalmers University of Technology

discharges can be related to skin having different “plateau voltages”. Those are approximately
100 V and 500 V. For capacitors discharges to the skin, the 100 V contact plateau suggests a
level were the impedance becomes very high, implying that a capacitor cannot completely
discharge through the skin. The 500 V plateau on the other hand states a level above which a
spark discharge can occur. Translating this into terms of the environment in a switchyard
means that one will not experience any spark discharges if the initial voltage difference is
below 500 V. In further chapters, the initial voltage is presented as open circuit voltage, but is
then given in RMS (root mean square) values, see equation 2.1.

T
1
U eff =
T0∫ U 2 (t )dt

Equation 2.1 The rms value of a voltage U.

2.5 Earlier studies and calculations based on empirical data


The American Electric Power Research Institute (EPRI) has in its “Transmission Line
Reference book” performed a large number of experiments on voluntary people regarding
their sensitivity for contact currents (EPRI 1983). EPRI has also carried out studies of the
current from vehicles to ground, human to ground and human to vehicle. All objects were
exposed to a high electric field from power lines. The obtained data from those studies
resulted in empirical formulas how to calculate the current from different objects.

A well studied case is the current to ground from a person with height h, standing upright in a
vertical and homogenous electric field. The field strength is denoted E and the frequency is f.
The geometry of the human within the field is with the arms close to the body. Then, the
induced body current flowing to perfect ground through electrodes fitted under the feet can be
calculated as:

Equation 2.2 Ic = 9.0ּ10-11 h2 f E

Where: Ic = short circuit current (A)


h = body height (head to feet) (m)
f = frequency (Hz)
E = electrical field strength (V/m)

For instance, the author with a body height of 1.83 m standing in a vertical electric field at 50
Hz with a strength of 10 kV/m yields a current Ic =150.7 µA.

If one is wearing shoes which are not perfectly isolated, i.e. normal working shoes, a smaller
part of the body current flows through the soles. The soles of the shoes have both capacitive
and resistive impedance. The capacitance human to ground is depending of the thickness of
the soles. According to EPRI (1983), the current flowing across the soles equals to:

-9-
Chalmers University of Technology

Equation 2.3 Is = 26.1ּ10-22 h3 f E / C

Where C is the capacitance over the soles. Equation 2.3 implies that shoes with a thickness of
1 cm (C = 180 pF) reduce the short circuit current with approximately one third.

Fracke and Åke (2004) have in the switchyard in Stenkullen measured the unperturbed
electric field strength at ground level. At one point, the maximum field strength was 17.94
kV/m. According to a latter work performed by Pettersson and Österlund (2005), using more
adequate measurements by reducing the geometry influence of the E-field meter with a
grounded plate, the electric field strength at this point was 13.6 kV/m.

Fracke and Åke measured a body current to ground of 147.8 µA in this point. The girl who
performed the measurement has a height of 1.60 m. Using EPRI’s formula, one can calculate;
Ic = 9.0ּ10-11ּ1.62ּ50ּ13.4 ≈ 154 µA which corresponds well to the measured value.

2.6 Contact current from large objects


Large objects like cars or trucks in a substation have larger areas exposed to the electric field.
This, in contrast to a person, results in more charges at the surface, and gives a much larger
currents when short circuit to ground. In the former part, the factor 9.0ּ 10-11 in equation 2.2 is
suitable for an erect human and implies the size of the exposed charge obtaining surface.

For short circuit current in larger objects, placed close to ground, one can use equation 2.4
reproduced from Transmission Line Reference Book (EPRI 1983).

Equation 2.4 Ic = j ω ε E S

Where ε ≈ 8.84ּ 10-12


S = the equivalent charge obtaining surface
ω = 2ּπּf
j indicates the current is capacitive coupled

S can be calculated when simple geometry is present; otherwise it has to be estimated. Figure
2.4 shows a diagram from EPRI how to calculate the equivalent surface having a simple
geometry form.

Using the diagram in figure 2.4, it is easy to calculate the maximum short circuit current from,
for instance, a large van, which is used in the substation in Stenkullen. The size of the van is
5.25 m length (A), 1.90 m width (B) and has a height (H) of 1.95 m. Then:

A / B = 2.76
H / B = 1.03

- 10 -
Chalmers University of Technology

Figure 2.4 Diagram for calculating the equivalent surface S of a simple object. Source: EPRI (1983).

The curves in the diagram gives S / (A x B) ≈ 5. S = 5 x 5.25 x 1.90 ≈ 50 m2. Assume the van
is exposed to a field strength of 10 kV /m. Then, the current can be calculated applying
equation 2.4, which gives Ic ≈1.4 mA

This is the highest short circuit current that will flow through the van when exposed to an
electric field with a strength of 10 kV/m. In reality, resistive losses through the tyres make a
part of the current flowing through them. The ground resistance (type of soil and weather
conditions) plays a significant role according to EPRI (1983).

In a study of the weather and soil dependence by EPRI (1983), three types of soil were
chosen; dirt, gravel, and black top (asphalt). Different types of vehicles were placed under an
overhead line and the current to a human standing on the same soil were measured twice a
month during a year. The result showed a dramatic difference in the current levels with a
spread of almost none to 100 % of the theoretical maximum current (dirt). Soil of asphalt and
gravel showed a smaller current spread where no current level exceeded 30 % of the
maximum.

Calculations of short circuit current according to equations 2.2 - 2.4 assume the electric field
to be homogenous over the complete equivalent area exposed. Such large areas of
homogenous fields are rarely to be found in a substation and average values is necessary to
use.

- 11 -
Chalmers University of Technology

2.7 Spark discharges from humans


A person standing on an insulating ground exposed to an electric field is charged by the field.
At touch contact with a grounded object, discharges occur by the means of sparks. If contact
remains, the current will turn in to steady state current (short circuit). The open circuit voltage
(Uc) a person will obtain, is a function of the electric field strength E, where the person is
situated in relation to ground and potential as well as the impedance between the person and
ground (level of insulation).

Assuming perfect insulation to ground, the maximum voltage is determined by the human
body’s capacitance to ground (EPRI 1983). The voltage (Uc) can then be calculated using the
impedance formula for a capacitance and applying ohms law, which yields

Equation 2.5 Uc = Ic / ω C

Where Ic is the short circuit current to ground (equation 2.4).

In general, the capacitance for a person to ground in equation 2.5 can be estimated to 100 -
150 pF, Reilly (1998 p 343). EPRI (1983) has performed more detailed studies of the
capacitance as a function of the soles height above ground. At 2 cm, the capacitance is
approximately 150 pF, 180 pF at 1 cm and 210 pF at 0.5 cm.

If the author (1.83 m) is exposed to 10 kV/m and has 2 cm thick soles (C = 150 pF), then the
maximum open voltage will be Uc = Ic / ω C = 9.0ּ10-11 h2 f E / ω x C which equals to Uc =
3.2 kV.

Resistive losses through the soles and (humid) air reduce this voltage and only in exceptional
cases are the levels above reached (EPRI 1983). Their study showed that in reality, the
voltage vary between 0 and Uc = 0.3 times the electric field strength. That means if a field
strength of 10 kV/m is present, the highest obtained voltage potential is 3 kV for a human
within the field. The study was performed in varying weather conditions and with a variation
of test persons.

2.8 Perception levels and current effects on humans


The restraints for contact currents given in ICNIRP (1998) and the European Union's directive
2004/40/EC (EU 2004) are based on perception levels. The International Labour Organization
ILO (1994) has in a publication “Protection of workers from power frequency electric and
magnetic fields” compiled information from several investigations regarding perception levels
for current and indirectly the electric field. A summary of the result is shown in table 2.1 and
table 2.2.

- 12 -
Chalmers University of Technology

Effects of currents (50/60 Hz) passing through the human Contact current (mA)
body. Experimental data for 50 % of men, woman and Men Woman Children
children. (Touch area ~ 1cm2, Grasp area ~ 15 cm2)
Touch perception 0,36 0,24 0,18
Grip perception 1,1 0,7 0,55*
Shock, not painful (grasp contact) 1,8 1,2 0,9*
Pain, finger contact 1,8x 1,2* 0,9*
Shock, painful, muscle control (let go threshold for 0.5 percent 9 6 4,5
of the population)
Painful shock, let go threshold 16 10,5 8*
Severe shock, breathing difficulty 23 15 12*

Table 2.1 Source: International Labour Organization (1994).


(*) indicates calculated values assuming thresholds for women two thirds of those of men. Children’s thresholds
are assumed to be one half of men’s. (x) indicates values calculated from other frequency.

Table 2.2 gives a summary of the different effects a person may experience when exposed to
an electric field ranging from 0 to 50 kV/m.

Table 2.2 Different effects on humans exposed to 50 Hz electric fields. The persons and objects charged in the
fields are insulated from ground. The percentages indicate part of the group affected. Source: IEEE (1978),
Zaffanella and Deno (1978), UNEP/WHO/IRPA (1984), table compiled by the International Labour
Organization (1994).

- 13 -
Chalmers University of Technology

In a recent study; “Electric current perception of the general population including children
and the elderly” by Leitgeb et. al. (2005), even lower perception levels among the general
public have been established. The study included a large number of persons, well representing
the population. Table 2.3 shows the result of this study.

Table 2.3 Perception levels for 50 Hz current (Iw) for different perception probabilities (p) including men,
woman, children and the general population overall. Source: Leitgeb et. al. (2005).

ICNIRP’s (1998) states that the ambition is to protect 90 % of the exposed individuals from
adverse indirect effects (establishing the reference level for electric field exposure to 5 kV/m
for the general public). The reference level for contact current level is as earlier discussed set
to 1 mA for occupational exposure and half of that for general public (0.5 mA). As seen in
table 2.3, 90 percent of the population will notice a current level of 0.553 mA and 10 % even
as low as 0.111 mA. Conclusion to be drawn is that the existing regulations of current levels
are set to high to protect from current perception. On the other hand, those low current levels
are not considered harmful according to Kari Jokela3.

3
Kari Jokela, research professor at STUK, (Radiation and Nuclear Safety Authority, Finland), mail contact
January 16 and 17, 2006.

- 14 -
Chalmers University of Technology

3
Methodology
This chapter gives a short description how the work presented in this report was performed.

A 400 kV switchyard in Stenkullen was chosen for the study, since earlier studies of electric
fields have been performed here, showing the electric field being above the action value of 10
kV/m (Pettersson & Österlund 2005). The switchyard is old and will soon be out of service.
The new switchyard is already under construction in the vicinity of the present location.

The work began with the author taking part in the daily business to a substation in order to
observe what the workers are touching and what contact current they are exposed to. Since the
European directive 2004/40/EC (EU 2004) only deals with stationary contact current; i.e.
when contact has been established, focus has been laid on a method of measuring those
currents. Several measurements were performed in order to validate the measured values.

The current flowing from a person when touching a large number of objects at different places
in the 400 kV substation in Stenkullen has been measured. A vehicle often used when driving
in the substation was placed near grounded poles right under the phase lines. The contact
current when touching the vehicle was measured.. These situations occasionally occur
according to Kjell-Åke Elfving4, service technician at Vattenfall.

Touching the car and the grounded pole at the same time induces a current flow through the
body, larger then only touching the grounded pole, since the vehicle has greater surface and
can carry a lot more charges induced by the electrical field.

In some points, where the contact current was high, the electrical field were measured with an
electric field instrument

The same kind of switchyard, like the one being constructed in Stenkullen, is operational in a
substation in Lindome, south of Gothenburg. Here, one half of a cubicle was mapped with
nine measuring points for the electrical field. The stationary currents were measured from an
upright standing person touching the control units of the combined breakers and
disconnectors.

As a reference, some measurements were conducted in the 400 kV switchyards of Kilanda


and Strömma.

Protective clothing, manufactured by former SwedPower, (now Vattenfall Power Consultant)


has earlier been used as protection against spark discharges at work in high voltage structures.
According to J-B Mårtensson5, there are only a few dresses left together with semi conducting

4
Kjell-Åke Elfving, service technician at Vattenfall Syd, personal contact spring 2006.
5
J-B Mårtensson, service technician at Vattenfall Syd, personal contact, spring 2006.

- 15 -
Chalmers University of Technology

boots. The workers seem to never use them, due to lack of effort and knowledge about them.
The shielding effect on contact current with such an outfit was tested.

Finally, an attempt was made to measure spark discharges from the authors hand to a
grounded pole to observe the magnitude and shape of such discharges.

- 16 -
Chalmers University of Technology

4
Basic theory and technology
Below is a short introduction to the theory of electric and magnetic fields. In order to give the
reader a better understanding of the construction of a substation, such a description is also
included.

4.1 Electromagnetic fields


Electromagnetic waves consist of both an electric and a magnetic component. At high
frequencies they are referred to as electromagnetic radiation. This is valid when the distance
from the source is more than one wavelength. In figure 3.1, the fundamentals of a wave are
outlined.

At lower frequency, the wavelength is greater and we are often in the near field region, within
a wavelength from the source. Here, the electric and magnetic field has a very loose
connection, almost independent of each other. It is necessary to measure both the electric and
the magnetic component.

4.2 The wave


Electric and magnetic fields are waves that can be characterized by their strength (amplitude)
and their number of oscillations (maxima or minima) per second in one point, the frequency,
denoted hertz (Hz). There is a distinct relation between frequency, velocity and wavelength
given by equation 3.1. The velocity c in vacuum or air is equal to 3*108 m/s

c
Equation 4.1 f =
λ

Figure 4.1 shows the characteristic of a wave. It can be seen from equation 4.1 that high
frequencies correspond to short wavelengths and low frequencies correspond to long ones.
The wavelength for a 50 Hz wave is for instance 6000 km long.

- 17 -
Chalmers University of Technology

Figure 4.1 The fundamentals of a propagating wave.

4.3 Electric fields


A system with electrical charges, such as a high voltage overhead line produces an electrical
field throughout the space. The general term is E, implying its vector quantities. E is
characterized by its magnitude and its direction.

The field’s strength is measured in Volts per meter [V/m]. It arises from voltage, even if no
current is present. It is relatively easy to shield an electric field using grounded net or wires
since the electric field bends toward a conducting object with lower potential. An adverse
effect of an electric field is that it also bends toward a grounded person, amplifying the
strength as shown in figure 4.2

Figure 4.2 An upright person exposed to an electric field. The field strength close to the person is amplified due
to his grounded geometry.

- 18 -
Chalmers University of Technology

Between two metal plates with different potential, an electric field arise as shown in figure 4.3
Separating the plates with a distance of 1 m and applying a voltage of 1000 V at one plate and
0 V at the other, a field strength of 1000 V/m arise. The electric field in between the plates far
from the edges are homogenous; it does not matter of what height above the zero potential
plate one measure.

Figure 4.3 Electric field arises between two metal plates with different potential. The arrows indicate the electric
field lines and the colour scale demonstrates the electric potential. Figure is produced using Femlab.

4.4 Magnetic fields


While electric fields arise from voltages (charge particles), the magnetic fields arise from
currents (charged particles in motion). The unit of the magnetic field strength, denoted H, is
ampere per meter, [A/m]. A more commonly used unit is the magnetic flux density B,
measured in Tesla [T]. The relation between them can be written B=µ*H where µ is the
magnetic permeability of the material that carries the field. Since Tesla is a large unit, the
more practical micro tesla (µT) is generally used.

As shown in figure 4.3, the magnetic field lines form closed paths around the currents that
give rise to them. If one ampere is flowing in the conductor in figure 4.3, a magnetic flux
density of 0.2 µT one metre from the centre of the conductor can be measured.

- 19 -
Chalmers University of Technology

Figure 4.3 The magnetic field around a straight conductor where current is moving out of the picture. Arrows is
indicating the direction of the field (anti-clockwise). Colours indicate the magnetic field strength. Figure is
produced using Femlab.

The magnetic flux density from a current flow in a conductor can be calculated using equation
4.2. The material surrounding the conductor has permeability µ0 (permeability in space, air
and most other material),

I
Equation 4.2 B = µ0 *
2πr

Where I is the current within the conductor and r is the distance from its centre.

Magnetic fields are much more difficult to reduce than electric fields. One way is to
encapsulate the source within a material that has a µ that deviates a lot from µ0, (magnetic
material like iron). Another more realistic approach is to have parallel conductors with
currents flowing in opposite directions, cancelling out the fields.

4.5 The substation


A switchyard is a part of a substation where electrical energy is gathered and distributed.
They usually consist of two or three bus-bars, called A, B and C (where C often is used as an

- 20 -
Chalmers University of Technology

auxiliary bus-bar when service is needed or when failure occur at the other). Cubicles are
situated perpendicular to the bus-bars and distribute the energy to incoming or outgoing lines.
Each cubicle consists of three phases, R, S and T.

Planned connections, automatic fault clearance, measurement of voltage, current and effect as
well as communication with the central radio office are the main functions in a switchyard. In
many cases, the switchyard is part of a larger transforming station (which transforms voltage
to different levels and balances active and reactive effect).

Two common designs of a 400 kV switchyard are the ABC type and the two breaker design.
Figure 4.3 shows a schematic sketch of the types. L1, L2 and L3 indicate the incoming lines,
each consisting of tree phases.

(a) ( b)
Figure 4.3. Two usual kinds of switchyard design. The first (a) switchyard is of ABC-type and the second (b) of
two breaker design. Source: Elkraftteknisk handbok 3. p 192.

- 21 -
Chalmers University of Technology

5
Work performed in a substation
In this chapter, the reader will be presented to the daily kind of work that is performed in a
substation. Every kind of task will give exposure to different levels of electric and magnetic
field as well as contact currents. According to J-B Mårtensson6 and Kjell-Åke Elfving7,
service technicians at Vattenfall Syd, who has long time experiences working in substations,
the major part of exposure levels and time will occur for those people that work with
maintenance of breakers. This work requires special skill and most of their time, they are
working with breakers. Peter Karlsson8, a technician who works with service at breakers,
estimates his time in a 400 kV switchyard to 25-30 % of total time at work.

5.1 Inspection and small work


Inspections are carried out in the substation at regular basis to check the function of every
control unit and check gas pressure of the breakers in order to gain high reliability. The
control boxes of the disconnectors are checked as well. The works involve a lot of touching of
control units of circuit breakers and disconnectors as well as other grounded metallic objects
exposed to high electrical fields.

When inspections of the 400 kV switchyard in Stenkullen are performed, the checklist
includes a visit to a big three-phase transformer used for reactive and inductive power
distribution, see figure 5.1. This implies exposure for high magnetic fields, sometimes over
100 µT due to high currents in big reactance coils. According to Kjell-Åke Elfving, complete
inspections are not carried out that often, maximum four times a year.

Smaller inspections are conducted more often when there is a need. Elfving states that he
sometimes needs to bring a grounded wire attached to his hand when climbing up a ladder to
get within reach to a broken light bulb or device high above ground level, to avoid painful
spark discharges.

6
J-B Mårtensson, service technician at Vattenfall Syd, personal contact, spring 2006.
7
Kjell-Åke Elfving, service technician at Vattenfall Syd, personal contact spring 2006
8
Peter Karlsson, technician at Vattenfall, phone contact June 12, 2006.

- 22 -
Chalmers University of Technology

Figure 5.1 Kjell-Åke Elfving checks that everything is right with the cooling system for a three phase
transformer in Stenkullen. In the background one can see the reactive power compensation.

Figure 5.2 shows the control unit of a breaker in Stenkullen. When reaching to touch the
handle, the person is discharged through repeatedly occurring sparks.

Figure 5.2 Kjell-Åke Elfving is just about to open the door to the control unit of a breaker. He feels pain right
before contact is established due to spark discharges. The stationary contact current through his hand was
measured to around 120 µA.

- 23 -
Chalmers University of Technology

The situation where workers are exposed to spark discharges might be a hazard, not by the
sparks directly, but indirect when working high above ground. In figure 5.3, a control unit to a
breaker in Strömma are placed high above ground. Repeatedly sparks between the grounded
ladder and the worker makes it a very unpleasant and hazardous place working at.

Figure 5.3 A grounded ladder in Strömma is necessary to use during inspection of the breakers. It is hard not to
be a subject of spark discharges.

5.2 Maintenance, mounting and service at breakers


Breaker maintenance is the most exposed kind of work from the electric field point of view. It
often involves work of long duration. The breakers are sometimes in operation during work
with high voltages a few meters above ones head. A working platform is often used to get
within reach. It is a dangerous situation since it is easy to fall down from the platform if one
may lean towards the pole and inevitable getting a number of spark discharges.

- 24 -
Chalmers University of Technology

Figure 5.4 Thorbjörn Karlsson serves a 400 kV breaker in Kilanda with isolative SF6-gas. He is standing on a
working platform with the insulating porcelain starting a few centimetres above his head. Even though wet and
snowy weather conditions, he here experiences a contact current of 160 µA through his hand when touching the
grounded pole.

5.3 Work with disconnectors


When service and maintenance at high voltage disconnecting switches are performed, the
power is disconnected and the device well grounded. For security reason, a ground wire is
always attached to the incoming phase wire during work. The electrical field is low since the
sources are from surrounding wires and bus bars. Often, a sky lift is used; elevating the
worker closer to the higher overhead lines, but the distance to line voltage is still large.

- 25 -
Chalmers University of Technology

Figure 5.4 A closed disconnecting switch in Stenkullen. When the switch is open and voltage applied, noisy
coronas may occur in rainy weather.

- 26 -
Chalmers University of Technology

6
Measuring equipment
This chapter describes the different equipment used for acquiring the data.

6.1 Electric field measurement


The instrument used for electric field measurement is an EMM-4 from EnviroMentor AB in
Gothenburg. It consists of a circular plate of glass fibre laminate with a thin circular surface of
conducting copper. The electrical field coming towards the surface induces a current flowing
from the surface to a virtual ground produced by an operation amplifier. Virtual ground is also
feasible to connect to ground in order to obtain an accurate result. The current flowing from
the plate is converted to a voltage using an integrated current / voltage converter (the
operation amplifier circuit). This voltage is then amplified and filtered. Two outputs are
available, one RMS-signal output and one direct output. Both outputs have voltages that are
linear proportional to the incoming electrical field. The output is then attached to a voltmeter
for readout of the electric field strength. The instrument is shown in figure 6.1.

The instrument was originally constructed to intercept the field a human being is exposed to,
for instance the field from a CRT screen towards a human. The instrument has later been
rebuilt to extend its range; it now handles fields up to 20 kV/m. To measure the undisturbed
field at ground level in accordance to ICNIRP restrictions, a large grounded metal sheet with
a hole for the instrument is necessary to achieve a correct result (Pettersson and Österlund
2005). This is because the instruments geometry intensifies the electric field strength. What
the sheet does is simply to raise ground level to the same height as the measuring surface of
the instrument. In this way, the electric field lines do not bend towards the instrument,
enhancing the field. The size of the sheet was approximately two and a half times larger then
the instrument.

- 27 -
Chalmers University of Technology

(a) (b)

Figure 6.1 (a) the working principle of the electrical field instrument; (b) the instrument itself.

Figure 6.2 The electrical field measurement with a large grounded metal sheet in the same height as the
instrument. The output is connected to a voltmeter with large display for distance readout using binoculars (the
field is being disturbed if a human is standing close to the measurement setup)

- 28 -
Chalmers University of Technology

6.2 Stationary contact current measurement


For stationary contact current, i.e. when contact has been established, the current was
measured using a very sensitive true RMS ampere meter, Metrahit 29S. The ampere meter
was then attached to a short fishing rod (with adjustable length to match the length of one’s
arm). A small copper electrode placed on top of the rod act as a contact device when pushing
it toward a grounded object. A larger copper electrode (~15 cm2) transfers the body current
from the hand through the instrument.

The open circuit voltage (the potential difference between ground and a person being isolated
from ground within an electric field) was measured using a resistance of 90 Mohm in
conjunction with a sensitive voltmeter, Meterman 38X. This instrument has an impedance of
10 Mohm. Together with the resistance, it forms a 10:1 ratio voltage divider and an
impedance of 100 Mohm is reached. This implies smaller load to the circuit and better
accuracy. This equipment was attached to the fishing rod in the same way as the Metrahit.

Figure 6.3 shows the two types of measurement. Figure 6.4 shows two photos of the Metrahit
instrument attached to a short fishing rod.

(a)

(a) (b)

Figure 6.3 The measurement circuits: (a) open circuit voltage measurement, the resistance represents the voltage
divider’s resistance. (b) short circuit current measurement.

- 29 -
Chalmers University of Technology

Figure 6.4 Photo (a) and (b) shows the measuring instrument for stationary contact current.

6.3 Contact current flowing through the body from a


vehicle to a grounded object.
In this kind of measurement, the Metrahits ampere meter was used. Due to really high current
peaks when establishing contact, a human was excluded and only the short circuit current to
the vehicle was measured. In figure 6.5, the short circuit current from a van is measured.

- 30 -
Chalmers University of Technology

Figure 6.5 Kjell -Åke Elfving is measuring the current floing from his working car parked near a grounded pole,
right under a phase line, his body is not included in the circuit. Measurement performed in the 400 kV
switchyard in Strömma.

6.4 Transient contact current measurement


Spark discharge current was measured using a 100 ohm metal film shunt resistor, which has
very good high frequency characteristics. A 100 MHz 10:1 Tektronix P6105 probe with an
internal impedance of 10 Mohm in parallel with a 13 pF capacitance was attached to the
resistance. A copper electrode leads the discharge current to the resistor. Everything was
encapsulated in a metallic box to prevent external EMF noise to disturb the measurement, see
schematic picture in figure 6.6. The oscilloscope, a Tektronix TDS 220 was also shielded in a
grounded conducting box (covered with Electroshield, a conductive paint) to avoid EMF
disturbance.

- 31 -
Chalmers University of Technology

Figure 6.6 The equipment for acquiring spark discharges from a human’s hand to ground. The current is induced
to the body by a high electric field.

Figure 6.7 shows the setup in use at a pole of a 400 kV breaker (BA400). The field is about 10
kV/m and touching the pole or the electrode means painful sparks to the hand.

- 32 -
Chalmers University of Technology

(a) (b)
Figure 6.7 The pictures show how the spark discharge measurement was performed; (a) picture of the measuring
equipment. (b) a mechanic from the construction of a new switchyard in Stenkullen holds his hand on the
discharge electrode. He is charged from the electric field (10 kV/m) from a suspended phase line above his head.

6.5 Using a phantom


A dummy named Lennart serves as a phantom model for contact current that is capacitively
induced by low frequency electric fields. It is based on a dummy body used for showing
dresses in a cloth store. The body is of size L (or 50) with a height of 185 cm. He is covered
partly in aluminium foil to enhance the conductivity and totally covered with a conductive
paint, “Electroshield” from Caparol. The paint is generally used to shield walls and office
rooms from electric noise, and has very good conducting characteristics (Hamnerius 2005).
According to Yngve Hamnerius at Chalmers9, the phantom mimics the influence of the
human body in low frequency electric fields. The idea of using him is to get a good reference
when performing measurement, not only using the author’s body. The pictures in figure 6.8
shows the phantom at different measuring points in Stenkullen. Protective clothing is worn by
the phantom in 6.8 (b).

6.7 Protective clothing


The spark protecting dress is an overall of cotton with conductive strips stitched together with
the fabric. The strips, shown in figure 6.8 (b), shields the electric field when they are
connected to ground. The strips are located at both sides of the dress and connect to each
other at the back. Ground connection can be done by an alligator clip on a wire attached to the

9
Yngve Hamnerius, professor at Chalmers, personal contact spring 2006.

- 33 -
Chalmers University of Technology

strips. The strips are also possible to connect to a protective (metal) helmet via a wire and to
the boots (metal snap fastener). The boots are semi conductive (0.5 – 5 Mohm) and supposed
to lead induced charges towards ground.

(a) (b)
Picture 6.8; (a) The phantom standing close to a disconnector in Stenkullen. The setup is for contact current
measurement. The yellow boots shown are semi conducting and used for protection of sparks. (b) Phantom is
wearing dress for protective clothing. The yellow string at the dress is conductive and possible to connect to
ground for shielding of the electric field.

- 34 -
Chalmers University of Technology

7
Measuring positions
The positions where the measurements have been performed are discussed in this chapter. In
short, every place where a grounded control unit, breaker, switch etc is situated, the stationary
contact current from a human to ground has been measured. This is valid for Stenkullen. In
the recently built 400 kV switchyard in Lindome, one cubicle and a few other places has been
investigated. In the switchyards in Strömma and Stenkullen only a few measuring points were
chosen.

7.1 Stenkullen
The switchyard in Stenkullen has three outgoing, three incoming and two connecting cubicles,
where the latter are used for connecting the bus bars. There are three suspended overhead
wires for each cubicle at a height of 19 m above ground. Each phase in a cubicle has its own
circuit breakers and switches. The ground in the area around the circuit breakers is covered
with asphalt. Diagonally to each breaker cubicle, there is a line with three switches, one for
each phase in the cubicle. A road separates the breakers from the switches and bus bars area.

(a) (b)
Figure 7.1 (a) shows a satellite photo of the 400 kV switchyard in Stenkullen (Google earth), (b) shows a
drawing of the lines and connections.

The disconnecting switches are placed over an area covered with grass.

- 35 -
Chalmers University of Technology

At each grounded unit along the southwest side of the road (close to the long yellow line in
figure 7.1(a)), the contact current to a human was measured several times. Using the
equipment attached to the fishing rod, simulating the reach of ones arm, the highest obtained
value for contact current and open circuit voltage was noted. In the area with disconnectors,
the same procedure was conducted. The transient discharge measurement was done behind the
most northern breaker in the northern cubicle BA 400. The breakers rest on large iron girders.
A low suspended high voltage wire goes overhead to a current transformer which makes it a
more exposed area although it is mainly visited during inspections. The place can be observed
in figure 7.2.

Figure 7.2 Photo of the place where the transient current measurement was performed, right behind a circuit
breaker. The field is here approximately 10 kV/m even close to the grounded pole (presumably due to the
inclination of the high voltage wire).

The point where the highest electric field was measured according to a former study,
performed by Fracke and Åke (2004), was right below the R-phase of bus bar A and between
R and S phase of incoming cubicle number three. The name of the switchgears in this cubicle
is T4-A400.

- 36 -
Chalmers University of Technology
Fracke and Åke (2004) measured the electric field strength to 17, 5 kV/m in this area, not
using any equipment cancelling out the field enhancement caused by the instruments
geometry. Pettersson and Östlund (2005) later obtained a value of 13, 6 kV/m using a
grounded metal sheet. As a reference, the place was measured again (07-05-2006) with a new
metal sheet, gaining a maximum value of 13.4 kV/m. This value is within the interval of
uncertainty for the instrument EMM-4. The maximum value was obtained several meters
away from any grounded unit. Closer to the grounded disconnector poles (within arm's length)
the field decreased to 7-8 kV/m.

7.2 Lindome
The 400 kV switchyard in Lindome is recently built and has a compact design, using breakers
and switches in the same unit. The distances to the phase lines are about the same as in
Stenkullen, with suspended wires (duplex) between the switchgears. The design is of the so
called two breaker type. The eastern part of the most southern cubicle was measured both
regarding contact current to a person and the electric field in some points. Here, the high
voltage lines from Strömma go overhead. The names of the switchgears are FL2 S4. Contact
current from a person to the R S and T units were noted (poles of breakers and current
measuring transformers). The distance between the phase lines is 5.5 meters and 8.5 meter
between the breakers and the current measuring transformers, see figure 7.3. Six places for
contact current and the electric field in nine points were measured.

(a)

- 37 -
Chalmers University of Technology

(b)

Picture 7.3 (a) shows the measuring points in the switchyard in Lindome, (b) measuring points seen from above.

The older part of the switchyard was measured in three places. The electric fields close to the
circuit breakers connected to a transformer noted T2 were measured. Also measured was the
contact current from a person to the control units as shown in figure 7.4.

Figure 7.4 The older part of the switchyard in Lindome. Measured breaker units are shown.

- 38 -
Chalmers University of Technology

8
Measurement results
In this chapter, measurement results from the various locations are presented.

8.1 Measurements in Stenkullen


The measurements in the switchyard in Stenkullen were performed during several occasions
from January to June 2006.

8.1.1 Contact currents and open circuit voltage


The results from contact current measurement performed in Stenkullen are given below. The
person conducting the measurement is the author with body size 52 and a height of 183 cm. A
plastic protection helmet is always worn due to the safety regulations in a substation. The
same shoes (Ecco working shoes with 1.5 cm thick sole) are also worn throughout all the
measurements in order not to affect the outcome. Since the phase to phase voltage at the lines
has very small fluctuations, no effort was spent to note those levels. Line voltage, phase to
phase rms, fluctuate between 405 and 410 kV according to J-B Mårtensson10

As mentioned in the previous chapter, each breaker unit was measured several times. The
result from contact current and open circuit voltage for a person touching the breakers are
shown in diagram 8.1. The numbers indicate that the breaker units along the road, starting
from north. Note that the continuous curves only are used for easier readout of the
information.

10
J-B Mårtensson, service technician at Vattenfall Syd, personal communication, spring 2006.

- 39 -
Chalmers University of Technology

Current Januari 18
Short circuit current (rms) Current March 14
160
Current May 3
Current May 7
140

120

100
[uA]

80

60

40

20

0
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
Breaker unit

Diagram 8.1 All current measurements from a person to a breaker unit are here shown.

Open circuit voltage (rms)


2500
Voltage June 10
Current May 7
2000
[V] and [uA]

1500

1000

500

0
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
Breaker unit

Diagram 8.2 The measured voltage levels. As a reference, the measured currents from May 7 are included

- 40 -
Chalmers University of Technology

(square marks).

To see if there are any differences between the types of breakers, table 8.1 presents an average
value for the contact current and voltage in each group of breakers (three breakers). All
measurements are included and an average has been calculated. Note that the breakers in
group ABC 400 S are not in operation, and only the surrounding electric field give raise to the
measured values.

Group (3 Number Average Average


breaker units voltage [V] current [uA]
in each)
BA – 400 - J 1-3 1860 94

ABC 400 S 4-6 * 580 25

FL 15 S5 - S 7-9 1410 88

T2 – 400 - S 10-12 1667 92


FL5 S4 - S 13-15 1583 101
T3 – 400 - S 16-18 1953 113
FL 18 - S 19-21 1613 97
T400 - S 22-24 1267 84

Table 8.1 The averaged value for each group of circuit breakers. Values calculated by taking an average value
for R, S and T phase within each type/group of breakers. The asterisk (*) indicates that this cubicle was not in
use as one can see from the value of the current.

The diagram 8.2 below shows the contact current and voltage measured when standing in
front of the control unit to each disconnector. The numbers indicate the measuring path with
the disconnectors. The path starts from north at bus bar B, diagonally along each group of
disconnectors to the southern part of the switchyard, and then continues along the
disconnectors at bus bar A back to the northern part.

- 41 -
Chalmers University of Technology

Short circuit current and open circuit voltage (rms)

2000
Voltage [V] 5 Mohm
1800
Voltage [V] 100 Mohm
1600 Current [uA]
1400

1200

1000

800

600
400

200

0
1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 45 47
Disconnector unit

Diagram 8.2 Contact current and voltage standing in front of the control unit to a disconnector. The values
indicated with triangles are from an additional measurement series using a voltage divider with higher
impedance.

First, open circuit voltages were measured with the MetraHits 5 Mohm internal impedance
but found to be inaccurate. Supplementary measuring series using equipment with 100 Mohm
internal impedance was performed in June 10.

In a few places with high obtained current values, the electric field was measured at ground
level. The EMM-4 and the grounded sheet were placed at the position of the person’s
footprint from the former measurements.

Vehicles (workers vans) were also placed within reach to the grounded pole of the breakers.
Then, short circuit current was measured. Placing the vans under the phase lines, right below
the bushing insulators of the breakers, gives the result shown in table 8.3.

- 42 -
Chalmers University of Technology

Object Soil place Current Voltage Electric field


[µA] [V] [kV/m]
Human 1,83m Dry grass Disconnector FL 18 BF (s) 161 950 8.2
size 52
Human 1,83m Wooden well cover Disconnector ABC 400 BF
(n)
110 2060 5.6
size 52
Phantom 1,85m Wooden well cover Disconnector ABC 400 BF
(n)
117 1870 5.6
size 50
Human 1,83m Rubber carpet (1cm
thick) on steel
Behind breaker BA400
(unit 1)
166 3290 9.74
size 52 girder
Phantom 1,85m Rubber carpet (1
cm thick) on steel
Behind breaker BA400
(unit 1)
150 3160 9.74
size 50 girder

Table 8.2 The measured open circuit voltage, short circuit current and electric field strength.. The “s” within the
brackets indicates the most southern disconnector and “n” indicates the most northern breaker in the group.

Object Soil place Current


[µA]
Large van asphalt Placed under
bushing insulator of breaker
725
(1.95x1.90x5.25) T3 400-S (unit 18)
Large van asphalt Placed under
bushing insulator of breaker
1079
(1.95x1.90x5.25) T3 400-S (unit 16)
Large van asphalt Placed under
bushing insulator of breaker
791
(1.95x1.90x5.25) T3 400-S (unit 19)

Large van asphalt Placed under


bushing insulator of breaker
1169
(1.95x1.90x5.25) BA400 (unit 1)
Large van asphalt Placed under
bushing insulator of breaker
636
(1.95x1.90x5.25) BA400 (unit 2)
Large van asphalt Placed under
bushing insulator of breaker
980
(1.95x1.90x5.25) BA400 (unit 3)

Small van asphalt Placed under the


bushing insulator of breaker
410
T3 400-S (unit 18)

Table 8.3 Short circuit current from a small and a large van.

8.1.2 Measurements with protective clothing


Shown here are the results of the measurements using the protective clothing from
Swedpower. The phantom was used, standing on the grounded girder behind breaker BA400
with and without an insulating rubber carpet (1 cm thick) placed under the semi-conducting
boots. Each boot has a resistance of 0.5-5 Mohm (according to the labelling on the boots).

- 43 -
Chalmers University of Technology

Action taken Short circuit Open circuit Electric field strength


current [µA] voltage [V] [kV/m]
Totally insulated on carpet 163 2720 9.74
(with clothes not grounded)
Grounded boots 157 310 9.74
Grounded clothes 131 760 9.74
Grounded clothes and boots 128 223 9.74
Grounded clothes and 92 514 9.74
helmet
Grounded clothes, boots and 90 100 9.74
helmet

Table 8.4 The effect of protective clothing. The helmet is of plastic but covered with conductive paint to
simulate the old shielding helmets (appurtenant to the dress). The helmet is connected to the metal strips in the
dress when noted as “grounded”.

Between the rubber carpet and the boots were two foot-shaped metal plates put for easy
grounding ability. The metal plates were grounded by a wire to the pole of the breaker when
boots were noted as grounded in table 8.4. When clothes were grounded, an alligator clip
attached to the shielding metal strips within the dress was connected to the breaker’s pole
(ground).

8.2 Measurements in Lindome


In this part, the results from the electric field and contact current measurement in Lindome (a
modern 400 kV switchyard) are presented. Current and voltage are measured from a person to
grounded objects shown in table 8.4

Measuring point Current Voltage Electric field


[µA] [V] [kV/m]
1 70 1160 3.97
2 54 970 2.83
3 66 1290 4.51
4 57 810 3.95
5 44 605 4.38
6 60 870 4.31
a - - 7.00
b - - 5.90
c - - 6.79
Old breaker T2400S (L1) 90 1420 4.95
Old breaker T2400S (L2) 65 970 3.30
Old breaker T2400S (L3) 95 1620 4.50
Staircase along phase down to transformer 97 1690 -
Highest value under overhead line L1 7.5
from Strömma (open yard)
Table 8.4 Measured values of short circuit current, open circuit voltage and electric field strength in Lindome.

- 44 -
Chalmers University of Technology

8.3 Measurements in Strömma


Contact currents in a few places were measured here. Those are shown in table 8.5.

Object Short circuit current [µA]


Car shown in figure 5.5 to breaker pole 610
Human 1.83 m on ladder to breaker, figure 4.3 180
Human 1.70 m on ladder to breaker, figure 4.3 170

Table 8.5 Contact currents measured in Strömma

8.4 Transient analysis – spark discharges


In this part, the results from the spark discharges are presented. All measurements are
performed at the same place behind a breaker. The person (1.83 m height) is exposed to an
electric field with strength of 9.7 kV/m. The initial open voltage was measured to about 2.5
kV. Body discharges from fingertip, hand and arm was performed.

In figure 8.1, the current through a 100 ohm metal film resistance is shown. The sparks are
captured with a digital oscilloscope acquiring the voltage over the resistance. The stored
signals are then after treated with Mathworks Matlab.

Figure 8.1 Repeatedly spark discharges from a fingertip. The spark gap is enlarged to a maximum, right before
the discharges stop. The last discharge has a current peak over 1 A.

Figure 8.2 shows a single discharge in higher time resolution.

- 45 -
Chalmers University of Technology

Figure 8.2 A single discharge with a time base of 1 us / div at the oscilloscope.

The signal in figure 8.2 was transformed using Matlabs’s fast Fourier transform in order to get
the frequency-response characteristics. The result is shown in figure 8.3, plotted in dB scale.

Figure 8.3 Frequency spectrum of the spark discharge in figure 8.2. The current is plotted in dB scale.

As shown in figure 8.3, the signal has significant frequency components up to about 10 MHz.

- 46 -
Chalmers University of Technology

When the spark gap distance is lowered to almost contact, a larger number of sparks
overcomes the gap at a lower potential. This can be observed in figure 8.4.

Figure 8.4 A larger number of sparks occur when the distance is lowered.

Eventually, when placing the hand on the electrode, the stationary contact current is achieved.
Still partial discharges occur, as shown in figure 8.5.

- 47 -
Chalmers University of Technology

Figure 8.5 The stationary current when tha hand is placed on the electrode can be seen. Calculating the RMS
value gives a current of about 176 µA which correspond well to the one obtained with the ampere meter. Partial
discharges occur when voltages are high.

In an attempt to reach highest possible current peaks, the authors arm was placed closed to the
discharge electrode. This resulted in high current discharges as observed in figure 8.6 and 8.7.

Figure 8.6 High current peaks from the authors arm, peaks of 1.75 A is reached.

- 48 -
Chalmers University of Technology

Figure 8.7 One of the peaks in figure 8.6 at higher time resolution. Signal is filtered in Matlab to improve clarity
and suppress digitizing errors.

8.5 Weather dependence


The workers experiences different levels of annoyance from spark discharges throughout a
day. To observe the influence of wet and dry soil and shoes, the phantom was used and 10
litres of water poured at the soil below the shoes. Finally, the shoes were soaked as well. The
result is given in table 8.6.

Soil Short circuit Open circuit voltage


current [µA] [V]
Dry grass 110 1060
Wet grass 110 340
Wet shoes and 109 180
grass
Table 8.6 Simulated influence of weather. The position is in front of the most northern disconnector BA 400-BF.

- 49 -
Chalmers University of Technology

9
Discussion and Conclusion
In this chapter, the results are discussed and conclusions are drawn. Sources of error are also
treated.

9.1 Contact current


The maximum measured contact currents from a person to a grounded object was 180 µA.
This is a low value in comparison with the action value of 1 mA stated in the directive.

Regarding the measurements in Stenkullen, touching a breaker gave lower contact current
than touching a disconnector. Presumably, this is due to higher electric field strength in the
area with disconnectors. The average contact current, human to breaker was 86 µA and
human to disconnector gave an average of 116 µA.

Other 400 kV switchyards of older design (Strömma and Kilanda) showed similar values
regarding contact current.

In Lindome, the new switchyard has a very compact design. This implies reduction of the
electric field strength due to all grounded objects within the area. Contact current
measurements showed significant lower values (about 44 - 70 µA) in this switchyard. The old
part of the yard gave values similar to the ones in Stenkullen.

The contact current measured from hand to grounded objects doesn’t vary much from one
measuring occasion to another. The weather dependence plays a small role; resistive ways of
losses through shoes have high resistance compared to impedance between hand and
grounded object. Thickness of the soles plays some role due to capacitive coupling to ground.
Thin soles reduce the measured current flowing through the hand. This is because some of the
current induced in the body instead takes the path through the shoes. The shoes used in the
measurements have thick soles (~1.5 cm). During the measurements, noticeable differences in
the measured current (~10 µA higher at one foot) were shown if one was standing on either
one or both feet. All measurements were performed standing on both feet.

The contact current from a van to a grounded person did exceed the action value of 1 mA at
some positions. This situation is on the other hand easy to avoid, keeping in mind to park the
car out of reach to grounded objects when high field strength is present. Very often, those
situations occur at maintenance. Extra high currents (and voltages) are reached at maintenance
when the service car is placed close to the grounded object and the service doors are opened
upwards, extending the charge collecting area of the car. JB Mårtensson11 tells that this is a
standard procedure to protect instruments in rainy weather conditions. The difference in
measured current gave an increase of up to 20 % when one service door was opened (lifted
upwards).

11
J-B Mårtensson, service technician at Vattenfall Syd, personal communication, spring 2006

- 50 -
Chalmers University of Technology

Studies at the former NRPB, (National Radiological Protection Board), now part of the Health
protection agency in Great Britain, has studied the relation between electric field strength and
current density in the human body The computerized anatomical models “Norman”
(Dimbylow 2000) and “Naomi” (Dimbylow 2005) have been used to calculate current density
within the CNS (Central Nervous System) when exposed to 50 Hz electric field. In an electric
field strength of 10 kV/m, the models showed a current density of approximately 1.84 mA/m2
in the CNS and about 2.17 mA/m2 in the retina in the eyes. The values were the maximum
taken after forming mean values over an area of 1 cm2.

Those studies, together with the measured contact current of 170 µA in approximately 10
kV/m, show a significant safety margin between action values and limitations. Enhancing the
field strength with a factor 4 will exceed neither the contact current of 1 mA nor the current
density of 10 mA/m2 in CSN. This is valid when the human acts as a charge collecting object
and discharge herself to ground. If one is using the formula in equation 2.2 from EPRI (1983),
the short circuit current from a human with a height of 1.80 m is about 15 µA/kV/m, which
also shows a large margin to the 1 mA action value.

Regarding ICNIRP’s suggestion of increasing the electric field strength to 20 kV/m for
occupational exposure, this could be applied also in the European directive since it only deals
with contact current after contact has been established.

A field strength of 20 kV/m would on the other hand induce higher potential at the body and
spark discharges will be of greater magnitude. Discharges to ground in a field strength of 10
kV/m is pretty much the level the author could handle without unintentional muscle
movements.

9.1.1 Uncertainty of the contact current measurements.


The contact current measurements have high accuracy using the instrument MetraHit 29s
which has a low uncertainty range of 0.5 % for AC current measurement. The measured
current does change with different positions and type of soil. But it is still the current that a
worker is exposed to.

The relation of 15 µA/kV/m is not valid over all measured positions since the field is not
homogenous close to conducting objects. In a switchyard, many high voltage sources
contribute to the field and make the distribution of the field vary in a complex way. The field
measured at ground level doesn’t necessary correspond to the field 1 m above ground where
the major part of the charge collecting area of the body is. A more accurate correlation might
be given if the electric field measurements were performed at a higher level above ground.

9.2 Voltage measurement


The voltages measured fluctuated a lot depending on soil. Soil of grass gave raise to the
largest fluctuations.

Also higher humidity in the air plays some role; surface charges are being transported away
from the body. All kind of resistive losses to ground lowers the initial voltage before contact

- 51 -
Chalmers University of Technology

is made. In general, voltage levels fluctuate from about 200 to 2400 volt (rms) in Stenkullen.
Only in extraordinary conditions, those levels were exceeded. All measurements were
performed in similar, dry, weather conditions. Lindome switchyard had significant lower
voltage levels due to better shielding of the electric field as discussed in 9.1 above. To touch
most of these switchgear units means insignificant annoyance from spark discharges. A
voltage level exceeding 350 V (rms) implies the possibility for spark discharges through the
skin. An ever higher voltage level means that sparks will ignite over the air gap found at pre
contact.

First, measurements were performed using the MetraHit 29s but found not to be accurate at
high voltage levels since the paths of losses to ground are in the same order of impedance
magnitude as the instruments internal 5 Mohm. The capacitive coupling from the overhead
line to the body will also discharge considerably through 5 Mohm. Additional measurements
were performed using a 10:1 voltage divider in conjunction with a multipurpose instrument;
Meterman 38 XR which has an impedance of 10 Mohm and an uncertainty range of 1.2 %.
With this equipment, the impedance was extended to 100 Mohm. An attempt using a voltage
divider with 100:1 ratio (1 Gohm) gave result similar to the 100:1 divider but was found
sensitive for high field strengths (induced charges). High impedance in the equipment means
that the capacitive coupling from the power lines to the measuring wires has greater influence.

The instrument was shielded with grounded metal foil, but cables to the instrument and the
voltage divider could still be a subject of induced charges from the electrical field. This will
give a higher readout of the potential than the real one. The highest obtained potential was
3290 Volt in a field strength of 10 kV/m. This was achieved by standing on an insulating
rubber carpet.

The voltages given are, besides instrument uncertainty, to be considered very approximately.
To lean the head means several hundred volts difference in a measurement. Wet or dry soil
and shoes imply considerably changes in the voltage levels. A straw of grass at ones leg
during a measurement lowers the voltage significant.

The workers experience spark discharges different one day to another or even within the same
day at the same position. The explanation to this is differences in the potential due to wet
shoes (transpiration or water) and the soil. Some working shoes have very thin soles with a
protective steel mantel. When such shoes get wet, the resistance is significant lowered. The
resistive impedance, feet to ground, is in those cases considerable dependent on the socks and
transpiration. Clean and dry socks imply high resistance but are lowered to almost none when
becoming wet.

To simulate the weather dependence, 10 litres of water were poured out on the soil under the
phantoms feet. The result showed a dramatically lowering in voltage, but no change in the
short circuit current. This wetness of soil and shoes gave an outcome of no possible sensing
level (< 350 V rms) of spark discharges due to low initial voltage.

9.3 Electric field measurements


All measurements were performed at ground level using a metal sheet to avoid field
enhancements. Measurements in open yard are easier to measure accurate. Close to grounded

- 52 -
Chalmers University of Technology

conducting objects (see figure 3.2); the field strength is very inhomogeneous. By a small
displacement of the instrument, large differences in the result were shown. At ground level,
the field strength might also be very different compared to a height in level with ones head. In
this study, the attempt was to place the instrument right at the footprint from the former
measurement. Other measuring equipment, capable of measure the field higher above ground
might be better to use.

9.4 Current discharge measurements


The current discharges measured showed very high current peaks. The highest peak had a
magnitude of 1.75 A, but very short duration (~ 2 µs). This measurement was performed in an
electric field strength of about 10 kV/m, with the same shoes worn as in the other
measurements. Standing on an insulating rubber carpet gave even greater discharges due to
higher potential, but the pain was too unendurable to acquire those. The major part of the
discharge current lies below 10 MHz according to the frequency spectrum shown in figure
7.3.

The equipment used was very simple using measurements over a resistance. A lot of external
noise from the surroundings and from the digitizing process in the oscilloscope was present.
Equipment with better shielding and better resolution might show higher accuracy. Another
aspect is the non linear behaviour of the resistance at higher frequencies (above 100 MHz).

In an article “Measurements of Body Impedance for ESD” (Zhancheng Wu et. al. 2003),
current peaks from electrostatic discharges (charged capacitance) to the human body were
measured. The result showed current peaks ranging from 2 to 10 A with time constants of
0.25 to 1.25 µs at applied voltages of 1000-5000 V. A contact electrode was used to transfer
the charge to the body and not through a spark. The discharge capacitance in those
experiments was 500 pF. The sparks from ESD is found to be very similar to the ones
obtained in an alternating high voltage field. According to Reilly (p 57-58 1998), a typical
carpet spark (a person obtain negative charges walking over a carpet) would be in the order of
2-3 kV with an energy of 0.2 to 0.45 mJ.

A better way of measure, not disturbing the path of the current, would be with a current
transformer surrounding the finger or cable where the discharge flows. Such a transformer or
probe suitable would be the Pearson Electronics current monitor model 2877. This one is
capable of acquire a signal with a bandwidth of 200 MHz and has a BNC output.

9.5 Protective clothing


The old dresses from Swedpower used for protection of spark discharges works well if they
are correctly grounded. With a conducting helmet attached to the grounded strips in the dress,
as well as the alligator clip connected to ground, the contact current is reduced to almost one
half. More important, when the semi conducting boots have good contact to ground, the
voltage is dramatically reduced. This eliminates the risk of painful spark discharges.

Unfortunately, the clothes are not used today due to the inconvenience to put them on and
lack of knowledge of their ability to protect. More modern and comfortable clothing with
better shielding effect (thin metal filament within the fabric) are available today according to

- 53 -
Chalmers University of Technology

Yngve Hamnerius12. One company distributing such material in Sweden is RTK (RTK 2006).
Their fabric “Picasso” is suitable for fabrication of electric field protective clothing.

At such places like the ladder in Strömma, shown in figure 5.3 or working at a platform, like
the picture in figure 5.4, it would be compulsory to use protective clothing. There are great
risks when performing tasks high above ground. The indirect effects of spark discharges can
be fatally in such conditions. Luckily, there will be some reconstructions of hazardous
positions in several substations, including Strömma according to Lars Wallin13.

9.6 General conclusions


The action value for the electric field in the EU 2004/40/EC directive based on ICNIRP is set
with a margin in relation to the current density limitation for the direct field induced current.
To exceed the current density limit of 10 mA/m2 in CNS, body exposure of over 40 kV/m is
necessary. This margin set is to prevent effects when touching charges conductors in electric
fields. The contact current action value of 1 mA is based on classical data of perception. Even
though newer studies of perception levels among the population show a considerably higher
level of sensitivity (78 µA for 5 % of the population), this contact current is still not a big
health problem14. Only at contact with larger objects exposed to electric field strengths in the
order of the action value and ground at the same time, 1 mA is exceeded in the switchyards
studied in this report. Avoiding those situations imply the possibility to increase the electric
field strength to 20 kV/m, as suggested by ICNIRP. A human body exposed to 20 kV/m will
not experience contact currents above 1 mA when touching a grounded object. Simultaneous
contact with a large charge collecting object such as a van and ground will on the other hand
likely exceed 1 mA at 20 kV/m.

ICNIRP does not mention contact with grounded objects where the human body is exposed to
an electric field, only “effects from contact with electrically charged conductors”. At contact
with a charged conductor, such as a van exposed to an electric field, the human body must be
well grounded in order to reach contact current levels above 1 mA.

The biggest problem experienced is however not the contact current, but spark discharges at
pre contact. Those are (yet) regulated by neither ICNIRP nor the directive 2004/40/EC. It
seems very strange not to include them in the regulations. Current peeks of 1.75 A (although
short durations) as shown in this study do trigger muscle nerves much more intense than
current at established contact in the same field strength.

More knowledge is necessary to bring out to those who work in high voltage areas. A change
in the attitude towards protective clothing and information about the hazards in the work is of
great importance. In order to facilitate protection, better and easier protective clothing could
be used.

12
Yngve Hamnerius, professor at Chalmers, personal contact spring 2006.
13
Lars Wallin, Swedish national grid company (SvK) personal contact May 29.
14
Kari Jokela, research professor at STUK, (Radiation and Nuclear Safety Authority, Finland), mail contact
January 16 and 17, 2006

- 54 -
Chalmers University of Technology

References
Biegelmeier, G, 1985. New experiments with regard to basic safety measurements for
electrical equipment and installations. In J.E. Bridges, G.L. Ford, I.A. Sherman, and M.
Vainberg, Electric Shock Safety Criteria, Pergamon, New York. pp 161-171.

Dimbylow, Peter 2000. Current densities in a 2 mm resolution anatomically realistic model of


the body induced by low frequency electric fields. Physics in Medicine and Biology. Vol 45.
2000. pp 1013-1022.

Dimbylow, Peter 2005. Development of the female voxel phantom, NAOMI, and its
applications of induced current densities and electric fields from applied low frequency
magnetic and electric fields. Physics in Medicine and Biology. Vol 50. 2005. pp 1047-1070.

Deno, D. W. 1978. Electrostatic and electromagnetic effects of ulta-high voltage transmission


lines. Final report EPRI EL-802. Palo Alto, California, Electric Power Research Institute.

Elkraftteknisk handbook 3, Elanläggningar. Esselte Studium AB, 1984.

Enviromentor (1998) “Bruksanvisning Electric Field Meter EMM-4”. Gothenburg:


Enviromentor AB.

EPRI 1982, Transmission Line Reference Book. 345 kV and Above. Second Edition.
Prepared by Project UHV. 1982.

EU, 1999: European Union's recommendation The limitation of exposure of the general
public to electromagnetic fields (0 Hz to 300 GHz) (1999/519/EC), The Official Journal,
Brussels, July 12th 1999.

EU, 2004: European Union's Directive 2004/40/EC of the European Parliament and of
the Council on the minimum health and safety requirements regarding the exposure of
workers to the risks arising from physical agents (electromagnetic fields)(18th
Individual directive within the meaning of article 16(1) of directive 89/391/EEC, The
Official Journal, Brussels, April 29th 2004

Fracke, J and Åke, J: Magnetiska och elektriska fält i ställverksmiljö: Kartläggning av en


äldre anläggning. Examensarbete 2004:17. Chalmers Lindholmen University Collegie.

Freibeger, R, 1934. The electrical resistance of the human body to commercial direct and
alternating currents. Translated from German by Allen Translation Service, Maplewood, NJ,
Item no. 9005. Published by Bell Laboratories, Maplewood, NJ.

- 55 -
Chalmers University of Technology

Hamnerius,Yngve ”Uppmätning av skärmningsegenskaper hos väggar målade med Caparols


färg ElectroShield” 2005-11-06. Electronic document. www.caparol.se (Accessed: 2006-03-
29).

ICNIRP, International Commission on the limitation of Non-Ionizing Protection,


Guidelinesfor limiting exposure to time varying electric, magnetic, and electromagnetic fields
(up to 300 GHz). Health Physics April 1998, Volume 74, No 4.

IEEE (Institute of Electrical and Electronics Engineers) Committee Report. 1978. “Electric
and magnetic filed coupling from high voltage power transmission lines – Classification of
short-term effects on people”, in IEEE Transactions on Power Apparatus and System PAS-97,
pp. 2243-2252.

IEE Proc. Gener. Transm. Distrib., Vol. 146, No. 5, pp. 595-596, Sept. 1999.

International Labour Organization 1994. Protection of workers from power frequency electric
and magnetic fields. Occupational Safety and Health Series No 69.

Leitgeb, N, Schroetiner, J, Cech R 2005. “Electric current perception of the general


population including children and the elderly”. Journal of Medical Engineering &
Technology, Vol. 29, No. 5, September/ October 2005, pp 215-218.

Pettersson, A and Österlund, C: Reducering av elektriska fält i ställverksmiljö, Examensarbete


2005, Chalmers University of Technology.

Reilly J. Patrick, 1998. “Applied Bioelectricity; From Electrical Stimulation to


Electropathology”. 1998 Springer-Verlag New York Inc.

RTK, 2006: “Avskärmningsväv Picasso”. Electronic document.


www.rtk.se/Downloads/Picasso.pdf. (Accessed : 2006-08-29).

Zaffanella, L. E. 1985. Answers to the CIGRE questionnaire “Survey of the situation


concerning effects of electric and magnetic fields”, doc. 36-85 (SC) 21 IWD. Paris, CIGRE.

- 56 -

You might also like