The above voltage and currents are rated at -25 to +55°C, continuous operation. How to read our product code: Example PSC150B24
For higher ambient temperature see option T3. PSC150 = Family code
Other input and output combination on demand. Outputs up to 125 Vdc.
B = input voltage code B, 24 = Output voltage 24 V
The above voltage and currents are rated at -25 to +55°C, continuous operation. How to read our product code: Example PSC240 48/24
For higher ambient temperature see option T3. Other inputs like 36, 60, 72, 96 V or PSC240 = Family code
outputs up to 150 V on demand. 48 = input voltage code 48, 24 = Output voltage 24 V
FEATURES
Output under voltage alarm Inhibit – power down signal
A built in logic alarm changes to alarm state if the convert- To stop the converter, an external voltage (5 to 24 V) can be
er output voltage drops 10 % below nominal output. The put between pin 26 and input zero (pin 30), see figure 1.
DC OK LED is also controlled by the alarm circuit. The alarm Do not use the output voltage to supply the inhibit.
has an open collector configuration.
A voltage < 1 V is normal operating condition. In alarm Reverse input voltage protection
state the output can drive max 20 mA 60 V. The logic alarm Is provided by a parallel diode on the input. This diode is
works if a voltage is applied through a resistor on the only intended to blow an external input fuse. See option K
collector output max voltage 60 V. For relay output, see for more possibilities.
option B.
H15
Inrush current limit
PIN A NTC resistor is provided on models with input code D, E,
12, 14 0V, MASTER 0 220 and 440. See also option ICL
Conformal coating
30 -DCIN The PSC-series is conformally coated to withstand non-con-
densing tropical environment Rh 95 %.
Figure 1. Open collector alarm and inhibit input.
Page 2
OPTIONAL FEATURES
Overvoltage protection OVP -A Inrush current limit with NTC
A standard unit has an Overvoltage Limiting, OVL circuit Reduces the inrush current during start up. The input volt-
that limit the output voltage to about 15% above nominal age range might be affected. This feature or option is not
in case the regulator fails. recommended for stand-by operation (One supply the load
The OVP shuts down the output by activating the Inhibit. and the other is used as an idling back-up). The stand-by
This inhibit can only be released by switching off the input. unit might not be able to supply enough current until the
On 5 V output the OVP is standard and trigs at 6.2 V. NTC warms up.
12
U1- Power class
U1- 14
Page 3
GENERAL DATA / INPUT DATA OUTPUT DATA
LABEL VALUE LABEL VALUE
Design topology Full Bridge Source regulation 0.2 %
Switching frequency 50 kHz Load regulation (0 to 100 % load) 0.2 %
Emission / Immunity See page 8 Transient recovery time for load step 10 < 2 ms
Max. accepted input ripple to 100 % voltage deviation 3%
50-400 Hz 1 % of nominal voltage Output ripple (50 kHz)1 RMS 20 mV
Mechanical Design
The PSC has two basic mechanical stiles; the N-mechanics
PSC-series N-mechanics
for wall, chassis, DIN mount and the 3HE Euro format
L-mechanics 8 to 12TE.
Additional coolers (T3) can be added for higher operat-
ing ambient temperatures or accommodate built in series
diode and other options.
The PSC series case is based on a convection cooled ex-
truded aluminum tube with thick material for best heat
distribution.
This also assure the efficiency of the extra coolers T3.
Extruded aluminum is easy to recycle. PSC-series L-mechanics
Page 4
HOT PLUGIN SYSTEMS
Polyamp supplies customized power systems with AC/DC
and DC/DC converters in 19”-sub rack with 3U/3HE or
6U/6HE units. They are based on our 3HE Euro cassettes
with PSE and PSC-series up to 250 W per unit or PSC600
series with 6HE units, please see separate datasheet for
PSE and PSC600-series. The solutions can be convection
cooled or cooled from cabinet ventilation.
The photo and figure 3 above is an example of Safety Critical power supply system where 2
different input batteries are used (A and B) with 2 or 3 redundant units per group. All outputs
are parallel connected with alarm signalization. One side can also be supplied by AC.
Page 5
N-MECHANICS: WALL & CHASSIS MOUNTING WITH H15 CONNECTORS
200
106
42 52.2 64.2
(e)
Figure 5. Front and connector view of N-Mechanics, includes connector holder. Female H15 connector is optional.
200
190
CONNECTOR OPTIONS
49
Page 6
L-MECHANICS: 3HE FOR 8-12TE PLUGIN MODULES
167
106
37
Figure 11. L-Mechanics 8TE standard 10TE with T3 cooler 12TE with 2xT3 cooler Figure 12. PSC without L-panel
2TE
PSC mounted in Euro format 19”-subrack. PSC with standard L-mechanic mounted in a Euro format 19” -subrack.
The type code do not include the letter L (L-panel)
Page 7
CE MARK SAFETY STANDARD EN/IEC 60950
The PSC-series meets the requirements defined by CE mark ISOLATION TESTABLE LEVELS TEST VOLTAGE
as an apparatus.
Input / Output:
PSC-series meets requirements of EMC directive and low Input code: 24, A, B, CT 2 kVd.c.
Input code: 110, C, 220, D, E 2.5 kVa.c. / 4 kVd.c.
voltage directive (LVD) and RoHS II directive.
Input / Case:
The PSC-series family is in respect to EMC, a stand alone
Input code: 24, A, 48, B, CT 2 kVd.c.
unit that can also be installed in any other environment by Input code: 110, C, 220, D, E 2.5 kVa.c. / 4 kVd.c.
a professional installer.
Output / Case all outputs 2 kVd.c.
Please note that product standards can demand different Alarm / Input:
levels or other basic standard tests. We test according to Input code: 24, A, 48, B, CT 2 kVd.c.
levels below. For higher levels or other tests, contact Input code: 110, C, 220, D, E 2.5 kVa.c. / 4 kVd.c.
factory.
Installation Class I
EMC
EMC STANDARDS EMC PERFORMANCE REMARKS
Emission standards EN IEC 61000-6-3 Commercial and light-industrial environments
Input Output
EN 55016 CISPR 16 (0.15-30 MHz) OK OK opt.EN 55022 level B
EN 55016 CISPR 16 (30-1000 MHz) OK Enclosure test