1 IZMX circuit-breakers, INX switch-disconnectors 55

Terminal assignment of control circuit terminals


IZMX40

IZMX16-PXR20/25 control circuit terminal assignment

1, 2 - Shunt trip 29~32 - PT module


3, 4 - UVR/2nd shunt trip 33~35 - Onboard ModBus
5~7 - Overload trip switch 1 (OTS) 36 - ACCY4 (Reserved)
8~10 - Overload trip switch 2 (OTS)/ Remote reset 37~39 - Latch check switch, LCC-COM, LCM-N.O., LCB-N.C.
11,12 - External neutral sensor 40 - Message :Spring energy store tensioned
13~16 - Alarm 41,42 - Motor operator
17,18 - Ground fault source sensor 43,44 - Spring closing release
19, 20 - Control voltage supply 24VDC 45~56 - Auxiliary contact On/off, C-COM, A-N.O., B-N.C.
21,23,24 - Zone selectivity ZSI
20,22 - ARMs
25-28 - External CAM module

IZMX40-PXR20/25 control circuit terminal assignment

1, 2 - Shunt trip 25-28 - External CAM module


3, 4 - UVR/2nd shunt trip 29~32 - PT module
5~7 - Overload trip switch 1 (OTS) 33~35 - Onboard ModBus
8~10 - Overload trip switch 2 (OTS) 36~39 - External CAM module (future)
11,12 - External neutral sensor 40~42 - ARCON
13~16 - Alarm 43,44 - Remote reset
17,18 - Ground fault source sensor 45~48 - Reserved
19, 20 - Control voltage supply 24VDC
21,23,24 - Zone selectivity ZSI
20,22 - ARMs

49~51 Latch check switch, LCC-COM, LCM-N.O., LCB-N.C.


52 - Message :Spring energy store tensioned
53, 54 - Motor operator
55~56 - Spring closing release
57~92 - Auxiliary contact On/off, C-COM, A-N.O., B-N.C.

CA01305001Z-EN www.eaton.com