Feedback Systems in HVAC

ASHRAE Distinguished Lecture Series


Jim Coogan
Siemens Building Technologies

ASHRAE, Madison Chapter


October, 2014

Agenda

Definitions: feedback and closed-loop control


Types of feedback algorithms
Application: Supply Air Temperature Control
DX cooling – staged control
Chilled water valve – PI and PID control
Application: Mixed Air Control
Adaptive control
Application: Duct pressure reset
Specifying loop performance

Page 2 Copyright © 2014. All rights reserved.

Handout 1
What is a loop?

A closed loop controller responds to the results of it’s own actions

Controller Plant

Closed loop control Open loop control


temperature affects controller output temperature does not affect controller
valve curve is not crucial depends on known valve curve
uses a temperature sensor doesn’t need a sensor
delivers temperature data delivers no data

Page 3 Copyright © 2014. All rights reserved.

Examples of closed loop control

Many feedback technologies


Float valve
Bi-metal pneumatic stat
DDC with sensor,
controller, actuator

Page 4 Copyright © 2014. All rights reserved.

Handout 2
Characterizing response

Mathematical measures of:


Speed
Accuracy
Stability
Apply feedback theory to get
the behavior we want

Diagram from: Control Technology


Page 5 Siemens Switzerland, 2013 Copyright © 2014. All rights reserved.

Some things stay true,


1958 ASHRAE Handbook

Page 6 Copyright © 2014. All rights reserved.

Handout 3
AHU Supply Air Temperature Control

Consider the cooling loop in 2 similar air handlers


4-stage DX unit Chilled water coil and
modulating valve

Diagrams from:
Sequences of Operation for Common HVAC Systems
Page 7 ASHRAE, 2005 Copyright © 2014. All rights reserved.

Staged control of DX machine

Equipment cycles on and off


Temperature rises and falls
Can reduce the size of the swing
by cycling equipment faster

Page 8 Copyright © 2014. All rights reserved.

Handout 4
Staged control of DX machine

Fixed relationship between


cycle rate and size of
temperature swing
Slower cycle = Bigger swing
Depends on mechanical
and thermal sizing,
NOT on control calculations

Diagram adapted from: Control Technology


Page 9 Siemens Switzerland, 2013 Copyright © 2014. All rights reserved.

Modulating control of a Chw valve

Refinement of the on/off approach


Don’t just turn it on and off,
adjust for steady operation
Executed with many different
technologies
Today we use DDC
Today we (usually) use PID
Proportional
Integral
Derivative
Diagram from: Control Technology We need to tune it
Siemens Switzerland, 2013

Page 10 Copyright © 2014. All rights reserved.

Handout 5
What is tuning?

Adjust feedback parameters


for closed loop performance
Determines speed, stability
and accuracy
Tuning is matching controller
to the mechanical system
Match the size of response
Match the timing or response

Page 11 Copyright © 2014. All rights reserved.

What is tuning

Matching values of the feedback parameters to the


characteristics of the system under control
For PID
Proportional band
Integral time
Derivative time
Sample time
What are “characteristics”
Physical sensitivity
Response time

Page 12 Copyright © 2014. All rights reserved.

Handout 6
PID Operation and Tuning

Mathematical model simulates the


cooling control process
Easy to study effects of tuning and other conditions

Schematic diagram from:


Sequences of Operation for Common HVAC Systems
ASHRAE, 2005

Page 13 Copyright © 2014. All rights reserved.

PID Operation and Tuning


P: 50 deg

Page 14 Copyright © 2014. All rights reserved.

Handout 7
PID Operation and Tuning
P: 5 deg

Page 15 Copyright © 2014. All rights reserved.

PID Operation and Tuning


P: 0.5 deg

Page 16 Copyright © 2014. All rights reserved.

Handout 8
PID Operation and Tuning

Page 17 Copyright © 2014. All rights reserved.

PID Operation and Tuning


P: 5 deg
I: 100 sec

Page 18 Copyright © 2014. All rights reserved.

Handout 9
PID Operation and Tuning
P: 5 deg
I: 400 sec

Page 19 Copyright © 2014. All rights reserved.

PID Operation and Tuning


P: 5 deg
I: 20 sec

Page 20 Copyright © 2014. All rights reserved.

Handout 10
PID Operation and Tuning

Page 21 Copyright © 2014. All rights reserved.

PI vs PID?

Tuning presents range of acceptable performance


trade-off of speed vs. stability
PID (rather than PI) can extend the range
allowing a better trade-off
Occasionally valuable

Page 22 Copyright © 2014. All rights reserved.

Handout 11
PID Operation and Tuning

Page 23 Copyright © 2014. All rights reserved.

PID Operation and Tuning

total
I+ bias
P

Page 24 Copyright © 2014. All rights reserved.

Handout 12
Second Application: Mixed air loop

Q: What is the sensitivity


of the process?
A: Difference between
temperature inside and out
Weather changes, loop
behavior changes too
Options:
Tune for stability in cold,
accept slow response
in warm weather
Recalculate gains based on OAT `Diagram from:
Sequences of Operation for Common HVAC Systems
Apply adaptive control ASHRAE, 2005

Page 25 Copyright © 2014. All rights reserved.

Adaptive Control

Approaches to the varying


physical system
Calculate varying gain for PID
from known conditions
W1

W2

Apply generic PID gain W3

W4

adjusting algorithm
Apply alternate, non-linear
adaptive technology
Adaptive controllers are
available in the market today

Page 26 Copyright © 2014. All rights reserved.

Handout 13
Return Air Tracking Loop
with Adaptive Control

PID Control Adaptive Control

Pink – VFD
Blue – Supply Air
Green – Return Air
Page 27 Copyright © 2014. All rights reserved.

Duct Pressure Control

VSD

Fan
Controller
F F F F

Flow Flow Flow Flow


Controller Controller Controller Controller

Page 28 Copyright © 2014. All rights reserved.

Handout 14
Duct Pressure Control,
Duct Pressure Reset
Duct pressure loop is usually not very difficult
System can oscillate
De-coupling is the key
Duct pressure reset can be tricky
Pressure is “reset until one zone damper
is nearly wide open”

Page 29 Copyright © 2014. All rights reserved.

ASHRAE Energy Standard

Setpoint Reset. For systems


with direct digital control of
individual zone boxes
reporting to the central
control panel, static pressure
setpoint shall be reset
based on the zone requiring
the most pressure; i.e., the
setpoint is reset lower until
one zone damper is nearly
wide open.

Page 30 Copyright © 2014. All rights reserved.

Handout 15
Duct Pressure Reset

“reset until one zone damper is nearly wide open”

What control algorithm?


Some use open loop
Some use PID
What is the controlled variable?
What is the setpoint?
Some use ad hoc feedback (“trim and respond”)

Page 31 Copyright © 2014. All rights reserved.

Specifying loop performance

Already discussed loop behavior


Already characterized responses
Should be easy to define performance requirements
Difficult because it’s hard to nail down test condition
Behavior defined in math world
Test occurs in real world
Standard 195 defines flow control performance test
Intended as a product qualification test, not a
commissioning procedure

Page 32 Copyright © 2014. All rights reserved.

Handout 16
Summary

Closed-loop control concepts


2-state control
Modulating control and PID
Tuning and performance
Advanced approaches

Page 33 Copyright © 2014. All rights reserved.

Questions?

Jim Coogan, PE
Jim.Coogan@Siemens.com W1

W2

W3

W4

Page 34 Copyright © 2014. All rights reserved.